University Of Hyderabad-UOHYD has published 1St Recall Maintenance Of Buildings Providing Grading Water Proofing Treatment Over Main Admin Building In Uoh Campus. Submission Date for this Tender is 15-04-2021. Building Repair Tenders in University of Hyderabad, Hyderabad Telangana. Bidders can get complete Tender details and download the document.
Name of Work: 1st Recall: Maintenance of buildings: Providing grading water proofing treatment over main Admin building in UoH campus | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | 1. The Bidder should quote rates inclusive of GST 2. All the above item rates are all inclusive of GST | |||
2 | 2 | Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead. For thickness of tiles above 25 mm and up to 40 mm. Without distrubing the existing solar panels on first floor. | 1364.76 | Sqm | |
3 | 3 | Demolishing dry brick pitching in floors, drains etc. including stacking of serviceable material and disposal of unserviceable material within 50 metres lead : Without distrubing the existing solar panels on first floor. | 99.13 | Cum | |
4 | 4 | Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 metres lead. Without distrubing the existing solar panels on first floor. | 180 | Sqm | |
5 | 5 | 20 mm cement plaster of mix : 1:4 (1 cement: 4 coarse sand) | 180 | Sqm | |
6 | 6 | 6 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand) | 180 | Sqm | |
7 | 7 | Finishing walls with Acrylic Smooth exterior paint of required shade : New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) Without distrubing the existing solar panels on first floor. \n | 120 | Sqm | |
8 | 8 | Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) | 85 | Cum | |
9 | 9 | Neat cement punning. Without distrubing the existing solar panels on first floor. | 1416.06 | Sqm | |
10 | 10 | Providing and laying four courses water proofing treatment with bitumen felt over roofs consisting of first and third courses of blown bitumen 85/25 or 90/15 conforming to IS : 702 applied hot @ 1.45 Kg per square metre of area for each course, second course of roofing felt type 3 grade-I (hessian based self finished bitumen felt) and fourth and final course of stone grit 6 mm and down size or pea sized gravel spread at 6 cubic decimeter per square metre, including preparation of surface but excluding grading complete with : Bitumen felt (hessian base) type 3 grade I conforming to IS : 1322 Without distrubing the existing solar panels on first floor. | 60 | Sqm | |
11 | 11 | Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer's specification.\n | 544 | Kgs | |
12 | 12 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter | 120 | Rmt | |
13 | 13 | Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. Bend 87.5° 110 mm bend | 20 | Each | |
14 | 14 | Shoe (Plain), 110 mm Shoe | 20 | Each | |
15 | 15 | Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm | 80 | Each | |
16 | 16 | Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved. | 100 | Cum | |
17 | 17 | Providing and fixing double scaffolding (cup lock type) on the exterior side up to 10 meter height, above ground level, including additional rows of scaffolding in stepped manner as per required of site. Made with wooden bellies, placed 0.90 m centre to centre, horizontal & vertical tied with rope formed staircase system in the scaffolding for working platform etc. and maintenance it in a serviceable condition for the required duration as approved and removing it thereafter. The scaffolding system shall be stiffened with bracings, runners, connections with the building etc. wherever required for inspection of work at required locations with essential safety feature for the workmen. | 120 | Sqm |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy