| 1 | 1 | Checking &removing oil leakage in 1250 KVA oil type transformer at site i/c disconnection of HT and LT side cable / bus bar, remove complete oil and store in drum, and lift transformer with the help of chain pully ,heavy Labour, i/c Dehydration/filtration of oil, replacement of cork gaskets megraing ,testing ,VDV value, reconnection HT and LT side ,refilling of oil into transformer complete as required. | Item 1 | 2 | Job |
|---|
| 2 | 2 | Supplying & filling the transformer oil, sealed pack drum including transportation charges etc. ( Make : M/S Power oil / Savita with ISI marked ) | Item 2 | 200 | Ltr |
|---|
| 3 | 3 | Servicing of one no. HT panel i/c megraing ,check protection relay , repair springing charging mechanism, CT,PT ,indication lamp, amp. meter , voltmeter ,tight every nut bolt of end termination ,complete as per equipment codition complete as required. | Item 3 | 4 | Job |
|---|
| 4 | 4 | SITC of following accessories in the existing LT/MV panel: | | | |
|---|
| 5 | 4.01 | a) Indicator Lamps of coloured multiple LED Type | Item 4.01 | 20 | NO |
|---|
| 6 | 4.02 | b)Digital ammeter of suitable range & size to match the existing meter size | Item 4.02 | 10 | NO |
|---|
| 7 | 4.03 | c) Voltmeter Digital Type 96 x 96 mm size | Item 4.03 | 3 | NO |
|---|
| 8 | 5 | S/F selector switch in the existing panel including wiring etc complete as per site requirement. | Item 5 | 6 | NO |
|---|
| 9 | 6 | Servicing of 1250 KVA Dry type transformer i/c calibration, meggraing, cleaning, checking protection relay, CT testing, complete is required. | Item 6 | 1 | Job |
|---|
| 10 | 7 | Servicing of LT/MV panel with MCCB of any rating as incomer i/c cleaning, removing carbon from bus- bars, tightning of all connections & nut-bolts, calibration of all meters, replacement of faulty/burnt out control wiring, testing for proper earthing and submitting test report etc. complete as required. | Item 7 | 2 | Job |
|---|
| 11 | 8 | Servicing & lubrication of ACB of all ratings i/c all components etc complete as required. | Item 8 | 7 | Job |
|---|
| 12 | 9 | Replacement of 1000 AMP. MDO TYPE ACB THREE POLE IN THE EXISTING PANEL I/C DISMENTALING THE EXISTING ACB ,MODIFICATION IN THE EXISTING BUS BAR I/C PROVIDING ADDITIONAL BUS BAR as per site requirement ALUMIUM bus bar,MODIFICATION IN MOUNTAING ARRANGMENT ,NUT BOLT ,REQUIRED HARDWARE, COMPLETE AS REQUIRED. | Item 9 | 1 | Job |
|---|