| 1 | 1 | Supplying, installing, balancing and commissioning of fabricated at site GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, support as per approved drawing and specifications of following sheet thickness complete as required. | | | |
|---|
| 2 | 1.1 | (ii) Thickness 0.80 mm sheet | item1 | 12 | sqmtr |
|---|
| 3 | 2 | SITC of fire dampers in supply air paths complete as required | item2 | 2 | sqmtr |
|---|
| 4 | 3 | SITC of duct dampers in supply air main ducts / branch ducts complete as required | item3 | 2 | sqmtr |
|---|
| 5 | 4 | Providing, Making & Fixing of flaxibal Double Layer canvas connection complete as required. | item4 | 3 | Job |
|---|
| 6 | 5 | SITC of indoor extensible type sheet steel metal clad, totally enclosed rigid floor mounted, air insulated cubical type M.V. panel made out of minimum 1.66 mm thick sheet steel metal with name plate, labels and shall be folded and braced as necessary to provide rigid support , separate housing for each switch, MCCB, Bus bar fixing arrangement i/c painting with powder coating paint, mounted with complete accessories suitable for operation on 415 volt, 3 phase, 4 wire 50 Hz, A.C. supply system, MCCB shall be provided with handle interlock & Door interlock having electrical and mechanical interlocking arrangement including interconnection with 2.5 sqmm FRLS PVC insulated copper conductor crimping the lugs, ferrules and sign wrighting, interconnection between busbar to outgoing switchgear and outgoing switch gear to connector in cable alley by adequate rating copper conductors pvc insulated wire and supply & fixing of Announciator control alarm (audio/visual) system window /panel in this panel. Including S/F of MS base channel of size 100mm X 50mm & the panel shall fixing on MS base channel of size 100mm X 50mm i/c minor civil works, panel made out as per CPRI guidelines and relevant IS/IEC codes etc. as required, consisting of following items. (For details see attached specification). Note:- 1. The panel shall be type tested design at CPRI / Independent test house for the rating required. 2. Panel drawing should be got approved from Engineer in charge before fabrication. | | | |
|---|
| 7 | 5.1 | (a) 125 Amp, 36 KA, 4 pole MCCB with Microprocessor release range of 100-250A (L&T D Shine MTX1.0 Model DN2-250D/ similar superior make) along with rotary handle ----- 2 Nos. (b) 200 Amp. Aluminium BUS BARS (c) MCB 6 AMP (FOR indication lamp and multifunction meter supply)-07 Nos (d) 125/5 Amp. CTs----15 Nos (e) LED type indication lamp -06 Nos (f) 63 Amp TPN switch L&T FN 63 TPN SDF with bolted fuse - 3 Nos (g) 96mm x96mm square flush Digital Voltmeter-01 No (h) Voltmeter selector switch-01 Nos (i) 96mm x96mm square flush Digital Ameter -05 Nos (j) Ameter selector switch --05 Nos (f) Announciator control alarm (Audio/visual) system (i) LED type indication lamp -05 Nos (ii) PLA Relays with base-05 Nos (iii) potential free contactor relay-02 Nos (iv) limit switch-03 Nos (v) Industrial hooter-01 No (vi) Thermostat-01 No (vii) Humidistats-01 No (viii) Humidistats box-01 No (ix) 16 Ampere fuse base & carrier with 2/4 Ampere cartridge-01 set (x) Push Buttons for acceptance & reset | item5 | 1 | Job |
|---|
| 8 | 6 | Supply and fixing of PVC insulated PVC sheathed aluminum conductor armoured cable of following sizes on the existing MS tray /walls with saddles/PVC of cables with glands etc. as required | | | |
|---|
| 9 | 6.1 | i) 4 x 10Sqmm (for Pkg.) | item6 | 30 | Mtrs. |
|---|
| 10 | 7 | Supply and fixing of following PVC insulated PVC sheathed copper conductor armoured cable for control wiring on the existing MS tray / walls with saddles/PVC thread/cable tie, screws etc. I/c end termination of cables with glands etc as required. | | | |
|---|
| 11 | 7.1 | i) 4 x1.5sqmm | item7 | 60 | mtr |
|---|
| 12 | 8 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. | | | |
|---|
| 13 | 8.1 | i) 100mm width x 50mm x 1.6mm thickness | item8 | 10 | mtr |
|---|
| 14 | 9 | SITC 25mmx5mm thick G.I. strip for loop earthing on cable tray wall etc as required | item9 | 30 | mtr |
|---|
| 15 | 10 | Supply of one number PVC insulated and PVC sheathed XLPE power cable of 1.1 KV grade of 3.5x35 sqmm aluminium conductor armoured cable etc. as required. | item10 | 60 | Mtr |
|---|
| 16 | 11 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. | | | |
|---|
| 17 | 11.1 | Up to 35 sq. mm | item11 | 10 | Mtr |
|---|
| 18 | 12 | Laying and fixing of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size on wall surface / recess as required. | | | |
|---|
| 19 | 12.1 | Up to 35 sq. mm (clamped with 1mm thick saddle) | item12 | 50 | Mtr |
|---|
| 20 | 13 | Supplying and making end termination with brass compression gland and aluminium for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. | | | |
|---|
| 21 | 13.1 | 3½ X 35 sq. mm (32mm) | item13 | 4 | Nos |
|---|
| 22 | 14 | Supplying and fixing of AC plant information board made out of 12 mm thick both side white colour prelaminated partical board of 3 feet x 2 feet i/c sign writing on board as per instruction by Engg in charge etc complete as reqd | item14 | 1 | Job |
|---|
| 23 | 15 | Conducting initial and final Acceptance testing as per department norms complete with all required necessary tools, controls and equipments etc. as directed. ( For items covered in this agreement) | item15 | 1 | Job |
|---|