752731A Provision Of Central Air Conditioning And Fire Fighting For Additional Infrastructure For Ctw In Mcte Mhow Provision Of Central Air Conditioning And Fire Fighting For Additional Infrastructure For Ctw In Mcte Mhow

Tender Notice

27161463
Corrigendum : 752731A Provision Of Central Air Conditioning And Fire Fighting For Additional Infrastructure For Ctw In Mcte Mhow Provision Of Central Air Conditioning And Fire Fighting For Additional Infrastructure For Ctw In Mcte Mhow
Indian
Madhya Pradesh
10-07-2021
17-07-2021
19-07-2021

Tender Details

752731A Provision Of Central Air Conditioning And Fire Fighting For Additional Infrastructure For Ctw In Mcte Mhow Provision Of Central Air Conditioning And Fire Fighting For Additional Infrastructure For Ctw In Mcte Mhow

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 16-Mar-2021 Corrigendum No 01 Date 12-04-2021
2 31-Mar-2021 Corrigendum No 02 Date 26-04-2021
3 13-Apr-2021 Corrigendum No 03 Date 04-05-2021
4 23-Apr-2021 Corrigendum No 04 Date 19-05-2021
5 11-May-2021 CORRIGENDUM NO 05 Date 01-06-2021
6 21-May-2021 Corrigendum No 06 Date 15-06-2021
7 03-Jun-2021 Corrigendum No 07 Date 29-06-2021
8 08-Jun-2021 Corrigendum No 08 BOQ 29-06-2021
9 16-Jun-2021 Corrigendum No 09 Date 10-07-2021
10 10-Jul-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-07-2021

Key Value

Document Fees
INR 1000 /-
EMD
INR 259000.00 /-
Tender Value
INR 1.83 Crore /-

BOQ Items

Name of Work: PROVISION OF CENTRAL AIR CONDITIONING AND FIRE FIGHTING FOR ADDITIONAL INFRASTRUCTURE FOR CADET TRG WING AT MCTE MHOW.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 SCHEDULE "A" Part-I :
2 2 M & L for design, supply, installation, commissioning and testing of Chilled water type Air Conditioning plant complete with all accessories all as specified for Auditorium, the Areas hatched in the drawing for Auditorium and marked as AC to meet design parameters given in Annexure A having min capacity 2 X 70 TR (min) (Two are working) comprising of the following :-
3 3 Item No 01:- CHILLER :- Supply, Installation, testing and Commissioning of water-cooled scroll chiller with multi compressors, comprising of Hermetic compressors, DX Evaporator, shell & tube condenser, suitable expansion device, suitable for operation on R-407C refrigerant and complete in all respects as required of 70 TR actual Cooling Capacity :\nWater Temperature IN - 54.0 deg F\nWater Temperature OUT - 44.0 deg F\nFouling Factor - 0.0005 FPS\nCondenser :\nWater Temperature IN - 90.0 deg F\nWater Temperature OUT - 97.5 deg F\nFouling Factor - 0.001 FPS\nWater flow rate through Chiller - 168 USGPM\nWater flow rate through Condenser - 280 USGPM\n\n 2 EACH
4 4 Item No 2 :- \nSupply, Installation, testing and Commissioning of end-suction centrifugal Chiller water pump set capable of delivering 168 USGPM of water against 20 mtr WG head comprising of the following and complete as required : \n(a) 1 no. - Pump with bronze impeller, S.S Shaft, CED Coated CI body and mechanical seal\n(b) 1 no. suitable HP, TEFC squirrel cage induction motor (IE-2) with class 'F' insulation, 2900/1450 RPM synchronous speed, operating at 415 ± 10 % Volts, 3 phase, 50 Hz A.C. supply; Minimum Efficiency 75% duly insulated with 19 mm thick closed cell nitrile rubber insulation cladded with aluminium sheets of 24G thickness and properly clamped to pump in two semi-circular sections as required.\n(c) Lot-Mounting frame work with anti-vibration pads\n\n 2 EACH
5 5 Item No 03 : Supply, Installation, testing and Commissioning of end suction centrifugal Condenser water pump set capable of delivering 280 USGPM of water against 18 mtr WG head each comprising of the following and complete as required : \n(a) 1 No. Pump with bronze impeller, S.S Shaft, CI body and mechanical seal\n(b) 1 No. suitable HP, TEFC squirrel cage induction motor (IE-2) with class 'F' insulation, 2900/1450 RPM synchronous speed, operating on 415 ± 10 % Volts, 3 phase, 50 Hz A.C. supply; Minimum Efficiency 75% duly insulated with 19 mm thick closed cell nitrile rubber insulation cladded with aluminium sheets of 24G thickness and properly clamped to pump in two semi-circular sections as required.\n(c) Lot-Mounting frame work with anti vibration pads.\n 2 EACH
6 6 Item No 04 :.Supply, Installation, Testing and Commissioning of Monoblock-type Hot water pump set for hot water recirculation, capable of delivering 34 USGPM of water against 16 mtr head each comprising of the following and complete as required :\n(a) 1 No. - Pump with bronze impeller, S.S Shaft, CI body and mechanical seal\n(b) 1 No. suitable HP, TEFC squirrel cage induction motor (IE-2) with class 'F' insulation, 2900/1450 RPM synchronous speed, operating on 415 ± 10 % Volts, 3 phase, 50 Hz A.C. supply; Minimum Efficiency 75% duly insulated with 19 mm thick closed cell nitrile rubber insulation cladded with aluminium sheets of 24G thickness and properly clamped to pump in two semi-circular sections as required.\n(c) Lot-Mounting frame work with anti vibration pads\n 2 EACH
7 7 Item No 05 : Supply, Installation, Testing and Commissioning of electrically operated Hot Water Generator of following actual capacity; made of 8 mm M.S. sheet and dish end made of 10mm M.S. having 16 gauge stainless steel lining with heaters arranged in banks and Controller and Thermostat so that required qty of hot water is generated at 50°C with nominal variation, including 100mm thick resin-bonded fiber glass insulation of 24 kg / cum density finished with 1.25mm thick aluminium sheet cladding including necessary Electrical panel with automatic controls including inlet and outlet connections for water complete with pressure release valve, low level cut-out, Autovent sight-glass as per specifications complete as required. (Degree of protection IP-52 with IS 2147)\nHeating capacity : 45 KW\nWater in temp. : 45 deg C\nWater out temp : 50 deg C\nFlow Rate : 34 USGPM \n\n 1 EACH
8 8 Item No 6 - Supply, Installation, testing and Commissioning of Steam-type Humidifier package of following capacities with suitable humidistat as required; the humidifier shall be interlocked with thermostat or RH sensor, suitable for outdoor installation:-
9 9 (a) 2.0 KW 1 EACH
10 10 (b) 2.5 KW 2 EACH
11 11 Item No 7 : Supply, Installation, testing and Commissioning of induced draft counter flow, vertical discharge-type FRP Cooling tower of 2.65 lacs kCal/hr heat rejection capacity with ultra-violet treated durable & highly efficient PVC fillings with integral louvers and drift eliminators, open pan suitable for water distribution complete with hot FRP water basin. The hot water shall be distributed to fills in each cell via open-type gravity basin or with spray nozzles or having self-rotating sprinklers. Cooling tower shall be provided with statically and dynamically balanced one no. anti-corrosion treated axial flow type fan - direct-driven or driven through special bevelled reduction gear box with TEFC induction flame-proof motor with IP-65 protection, IE-2, suction screen, make up and quick fill arrangement, overflow and drain connections and suitably inspected hot-dipped galvanized ladder, access arrangement for cooling tower interior, anti-vibration mountings etc., complete as required: -\n 2 EACH
12 12 Notes - 1.The unit shall be installed at proper foundation as per requirements. \n 2. Civil foundation works is not included in the item, shall be in the scope of civil work contract.\nWater Leaving Temperature : 90.0 deg F\nWater Entering Temperature : 97.5 deg F\nWater Flow Rate : 280 USGPM\nAmbient Wet Bulb Temperature : 83 deg F \n
13 13 Item No. 8 - Supply, Installation, Testing and Commissioning of factory built Floor-standing double-skin type air handling units with thermal break profile made of 43 mm thick panels, consisting of pre-plasticized G.I. casing of thickness 0.6 mm at outside layer and plain Al. sheet of thickness 0.6 mm at inside layer with polyurethane foam (PUF) insulation of density 40(+2) kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower Direct Driven plug / DIDW backward curved centrifugal fan of 65mm WG static pressure, 4/6 row deep cooling coil and 2 rows deep heating coil section with aluminium finned copper tubes, filter sections with 50 mm thick washable synthetic type Pre-filters having efficiency 90% down to 10 micron, direct/belt-driven package with TEFC drive motor (IE-2) suitable at 415 + 10% Volts, 50 Hz, 3-phase, A.C. supply, complete with mixing box of same material as AHU, drain connections with drain valve, stainless steel drain pan, necessary vibration isolation arrangement (spring-loaded), silicon-coated flexible duct connector etc., complete as required in all respects:-\n \n
14 14 Notes:- (i) AHU to be provided with canopy for outdoor installation.\n (ii)The AHU should have space for humidifier.\n (iii) VFD panel with VFD (quantified separately), necessary control arrangement to switch off the fan in case of fire, indicating lamp & all safety precautions in a flame-proof powder-coated GI enclosure with necessary power and control cable as required.\n
15 15 (a) 8000 CFM / 47.0 TR 2 EACH
16 16 (b) 12600 CFM / 44.45 TR 1 EACH
17 17 Item No. 09 Supply, Installation, Testing & Commissioning of HVAC dedicated VFDs suitable for the following fan motor capacities (The integration of the VFD with fan motor is included in this item) with IP-55 enclosures with Mains disconnect suitable to fit-out in electrical panel (flame-proof), having:\nBuilt-in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the VFD. \nBuilt-in EMC Filters (electromagnetic compatibility filters) for VFDs for restriction of conducted emissions to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 1 for 50 meters of cable length between motor & VFD.\nThree-feedback PID (proportional-integrated-derivative) controller having capability to simultaneously accept 3 feedback signals from temperature sensor, pressure sensors or RH sensor for process optimization and accordingly regulate the speed of the fans.\n
18 18 (a) 7.5 KW 1 EACH\nSET
19 19 (b) 5.5 KW 2 EACH\nSET
20 20 Item No. 10 - Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled/hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with closed cell Class 'O' Nitrile Rubber Elastomeric Insulation of Density 40 - 60 kg/m3, Thermal Conductivity of 0.035 W/mK at 0 deg. C mean temp. and µ=7000 (without any additional vapour barrier) and factory laminated 7 mil Glass Cloth (GC) covering; to be applied on pipes using manufacturer's recommended rubber-based adhesive in a blend of solvents, complete as per specifications and as required complete in all respects :-
21 21 Note : Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS:1239 and pipes of sizes above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. sheet for pipes upto 350 mm dia and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
22 22 (a) 125 mm dia. (32 mm thick insulation) 26 RM
23 23 (b) 100 mm dia. (32 mm thick insulation) 44 RM
24 24 (c) 80 mm dia. (25 mm thick insulation) 20 RM
25 25 (d) 65 mm dia. (25 mm thick insulation) 30 RM
26 26 (e) 50 mm dia. (25 mm thick insulation) 46 RM
27 27 (f) 40 mm dia. (25 mm thick insulation) 50 RM
28 28 (g) 32 mm dia. (25 mm thick insulation) 20 RM
29 29 (h) 25 mm dia. (25 mm thick insulation) 10 RM
30 30 Item-11 Supplying, Fixing, Testing and Commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as required.
31 31 (A) BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water circulation as required:
32 32 (a) 100 mm dia. 12 EACH
33 33 (b) 80 mm dia. 12 EACH
34 34 (c) 50 mm dia. 6 EACH
35 35 (B) BALL VALVE set with and without Y-strainer with bronze body, flanged end type for chilled water circulation as specified:-
36 36 (a) 32 mm dia. 2 EACH\nSET
37 37 (b) 25 mm dia. 1 EACH\nSET
38 38 (C) BALANCING VALVE with BUILT-IN MEASURING FACILITY of C I body flanged construction with EPDM coated disc with long pitch with protruded out pipe insulation & PN 1.6 pressure rating for chilled water circulation as required:-
39 39 (a) 100 mm dia. 2 EACH
40 40 (b) 80 mm dia. 3 EACH
41 41 (c) 50 mm dia. 1 EACH
42 42 (d) 32 mm dia. 2 EACH
43 43 (e) 20 mm dia. 1 EACH
44 44 (D) NON - RETURN VALVE with dual plates of C I body SS plates vulcanized NBR seal flanged end & PN 1.6 pressure rating for chilled water circulation including insulation as required.
45 45 (a) 100 mm dia. 3 EACH
46 46 (b) 50 mm dia. 2 EACH
47 47 (E) Y - STRAINER of ductile CI Body flanged ends with stainless steel strainer for chilled water circulation including insulation as required.
48 48 (a)100 mm dia. 2 EACH
49 49 (b) 80 mm dia. 3 EACH
50 50 (c) 50 mm dia. 2 EACH
51 51 (F) Three-way Motorized Valves with modulating motor in cooling/heating coil of air handling units as required of following sizes :-
52 52 (a) 5-25 USGPM 3 EACH
53 53 (b) 81-120 USGPM 3 EACH
54 54 (G) FLOW SWITCH of brass/polymer construction as per requirement.
55 55 (a) 100 mm dia. 3 EACH
56 56 (b) 50 mm dia. 2 EACH
57 57 (H) Industrial type pressure gauges with gunmetal / brass construction isolating valve complete with all accessories as required. 24 EACH
58 58 (I) Industrial type mercury in glass industrial type thermometers with gunmetal/ brass construction isolating valve complete with all accessories as required. 16 EACH
59 59 (J) Digital thermometers with probe suitable for binder test point application with Brass construction, nitrile sealing bushes, max. operating pressure of 16 bar & max. working temperature of 110 deg celsius as required. 1 SET
60 60 (K) Dial type pressure gauge with probe suitable for binder test point application with brass construction, nitrile sealing bushes, max. operating pressure of 16 bar & max. working temperature of 110 deg celsius as required. 1 SET
61 61 (L) Auto Air - purge valve of brass construction of 15 mm dia (Air Vent will be fitted with an isolating ball valve - gunmetal/brass construction) 8 EACH
62 62 Item-12 Supply, Installation, Testing and Commissioning of Flexible Connector for following dia. pipe having PN 16 working pressure with anti-vacuum rings complete with flanges, nuts, bolts, seal etc. to be installed at chiller suction and discharge.
63 63 (a) 100 mm dia. 12 EACH
64 64 (b) 80 mm dia. 6 EACH
65 65 Item-13 Supplying, Fixing, Testing and Commissioning of G.I. medium class water pipes as per IS 1239/1979 of following sizes along with necessary clamps, fittings such as bends, tees etc. adequately supported and duly insulated with 13 mm thick closed cell elastomeric nitrile rubber of class 'O' insulation applied by adhesive conforming to standard specifications complete with type 3, grade 1 roofing feltstrip (as per IS:1322 as amended up to date) at joints and repairing of damage to building etc. as required complete in all respects:-
66 66 (a) 40 mm dia. 25 RM
67 67 Item-14 Supply, Installation, Testing of open-type expansion tank of MS Construction made of 6 mm thick mild steel sheet duly insulated with XLPE insulation applied by adhesive conforming to standard specifications and finally applying 0.63 mm thick aluminium sheet cladding complete with type 3, grade 1 roofing feltstrip (as per IS:1322 as amended up to date) at joints and repairing of damage to building etc., as required, complete in all respects with connection over flow and drain 40 mm dia.
68 68 (a) 500 mm x 500 mm x 500 mm (high) 2 SET
69 69 Item-15 Supply & Installation of make up water tank of HDPE Construction as required complete in all respect with connection, over flow and drain. Make up connection with float valve, drain valve, incoming line valves and fittings as required.
70 70 (a) 500 ltr. 2 EACH
71 71 Item-16 Supplying, Fixing, Testing and Commissioning of condenser water pipes of following sizes and materials along with necessary clamps, vibration-isolators and fittings such as bends, tees etc. but excluding strainer and gauges etc. adequately supported on rigid supports / including painting valves including minor holes & works making good the damage done welded black steel pipe as per IS:3589 walls etc as required :-
72 72 Note: The pipes of sizes 150mm & below shall be M.S. heavy class as per IS : 1239 and pipes of sizes above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. & from minimum 7mm thick M.S. sheet for pipes of 400 mm dia. & above.
73 73 (a) 200 mm dia. 45 RM
74 74 (b) 125 mm dia. 70 RM
75 75 Item-17 Supplying, Fixing, Testing and Commissioning of following valves, gauges and strainers for condenser water circulation as required.
76 76 (A) BUTTERFLY VALVE (MANUAL) with Cast steel body SS Disc, Buna-N integrally moulded Seal & O-Ring; the valve shall be suitable for PN-16 working pressure for condenser water circulation as required.
77 77 (a) 200 mm dia. 3 EACH
78 78 (b) 125 mm dia. 14 EACH
79 79 (B) BALANCING VALVE with BUILT-IN MEASURING FACILITY of Gun-metal construction upto 50 mm dia & cast steel/ ductile iron body upto 300 mm. dia as required having flanged construction with SS disc having long pitch with protruded out pipe insulation & suitable for PN 16 working pressure for condenser water circulation as required. The Ductile iron body shall be painted with one coat of Inorganic ethyl self-curing zinc silicate premier at 75 microns & single coat of Super High build epoxy MIO Coating cured with polyamide hardener at 150 microns & finally two coats of High Build Gloss Aliphatic Acrylic Polyurethane at 50 micron dry film thickness :-
80 80 (a) 125 mm dia. 2 EACH
81 81 (C) NON - RETURN VALVE with dual plates of cast steel construction, SS plates, Body lining-BUNA -N, flanged end construction, suitable for PN-16 working pressure for condenser water circulation as required.
82 82 (a) 125 mm dia. 3 EACH
83 83 (D) Y - STRAINER of cast steel Body, flanged ends with stainless steel strainer, suitable for PN-16 working pressure for condenser water circulation as required.
84 84 (a) 125 mm dia. 2 EACH
85 85 (E) BALL VALVE of brass construction, flanged end type for drain connection & make up water connection as required.
86 86 (a) 32 mm dia. 2 EACH
87 87 (b) 25 mm dia. 2 EACH
88 88 Item-18 Supply, Installation, Testing and Commissioning of Flexible Connector for following dia. pipe having PN-16 working pressure with anti-vacuum rings complete with flanges, nuts, bolts, seal etc. to be installed at condenser suction and discharge.
89 89 (a) 125 mm dia. 14 EACH
90 90 Item-19 FLOW SWITCH of brass/polymer construction suitable for 80 mm dia pipe 3 EACH
91 91 Item-20 Industrial type pressure gauges with gun metal/brass construction isolating valve complete with all accessories as required. 10 EACH
92 92 Item-21 Industrial type mercury in glass industrial-type thermometers with gun metal/ brass construction isolating valve complete with all accessories as required. 4 EACH
93 93 Item-22 Auto Air - purge valve of brass construction of 15 mm dia (Air Vent will be fitted with an isolating ball valve - gunmetal/brass construction ) 4 EACH
94 94 Item-23 Supply, Installation, Testing and commissioning of On-line, non-chemical water treatment scale preventer system (suitable for 200 mm dia. pipe) having flow rate 560 USGPM. 1 SET
95 95 Item-24 Supply & Installation of make-up water tank of HDPE Construction as required complete in all respects with connection, over flow and drain. Make up connection with float valve, drain valve, incoming line valves and fittings as required.
96 96 (a) 10000 ltr. 1 EACH
97 97 Item-25 Supply, Installation, Balancing and Commissioning of factory-fabricated GSS sheet metal rectangular ducting with supports as per IS 655-2010 complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and as required of following sheet thickness complete as required:-
98 98 (a) 24 gauge (thickness 0.63 mm) 430 SQM
99 99 (b) 22 gauge (thickness 0.8 mm) 570 SQM
100 100 Item-26 Supply, Fabrication, Installation, Balancing and Commissioning of site- fabricated GSS sheet metal rectangular ducting with supports as per IS 655-2010 complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and as required of following gauges:
101 101 (a) 24 gauge (thickness 0.63 mm) 100 SQM
102 102 (b) 22 gauge (thickness 0.8 mm) 140 SQM
103 103 Item-27 Supply, Installation, Testing and Commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as required. 3 SQM
104 104 Item-28 Supply & Fixing of powder coated extruded aluminum 4-way Supply air grills complete with nuts, bolts, screws etc. as per approved drawings and as required. 8 SQM
105 105 Item-29 Supply & Fixing of powder coated extruded aluminum 4-way Return air grills complete with nuts, bolts, screws etc. as per approved drawings and as required. 6 SQM
106 106 Item-30 Supply, Installation, Testing and Commissioning of powder coated extruded aluminium louvers with synthetic removable type filter, bird screen & damper for fresh air intake. 4 SQM
107 107 Item-31 BLANK
108 108 Item-32 Supply, Installation, Testing and Commissioning of powder coated extruded aluminum door transfer grill complete with nuts, bolts, screws etc. to make the system complete. 1.5 SQM
109 109 Item No. 33 Supplying, Installation, Testing and Commissioning of fire-cum-smoke motorized dampers as required, the blades and frame shall be min. 1.6 mm thick GI sheet and factory fitted in a sleeve made out of 1.6 mm thick GS Sheet of min. 400 mm long, as & where required, of required sizes including control wiring. The damper shall be motorized and have spring-return mechanism so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall have in-built mechanism and not externally mounted. For smoke extraction, necessary control arrangement shall be provided for passive smoke control system in the event of fire signal. The dampers shall be CBRI tested and certified for 90 minute fire rating against flame penetration as per UL standard 555-1995. The assembly shall be complete in all respects, as required.
110 110 (a) Motorized fire cum smoke damper 4 SQM
111 111 (b) Spring-return motorized assembly 13 EACH
112 112 (c) Actuator with control panel 13 EACH
113 113 Item No. 34 - ACOUSTIC INSULATION :- Supply and Application of Acoustic Insulation inside the supply air duct with engineered nitrile rubber open cell foam with density 140 - 180 kg/m3 passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test for 10,000 fpm air velocity as per ASTM C 1071-05 and with built-in antimicrobial protection. The material should pass Fungi Resistance Test as per DIN EN ISO 846 Method A and Bacterial Resistance Test as per DIN EN ISO 846 Method C; to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents.
114 114 (a) 15 mm thick 320 SQM
115 115 Item No. 35 - Supply & Installation of Thermal Insulation on Ducts not exposed to sunlight using closed cell Class 'O' nitrile rubber elastomeric insulation of density 40 - 55 kg/m3, Thermal Conductivity of 0.037 W/mK at 200 deg. C mean temp. and µ=7000 (without any additional vapour barrier) and with factory laminated aluminium foil of minimum 60 Microns thickness having weight of 193 gsm as per EN ISO 2286-2, tensile strength shall be 90N/15mm as per EN ISO 527-3 with elongation > 10% as per EN ISO 527-3; to be applied on Ducts using manufacturer's recommended Rubber based Adhesive in a blend of Solvents.
116 116 (a) 19 mm thick 800 SQM
117 117 Item No. 36 Supply & Installation of Thermal Insulation on ducts running outside the building using closed cell Class 'O' nitrile rubber elastomeric insulation of density 40 - 55 kg/m3, Thermal Conductivity of 0.037 W/mK at 200 deg. C mean temp. and µ=7000 (without any additional vapour barrier) and with factory-laminated cladding made from 3- layered composite film of metallic appearance with aluminium intermediate layer and UV protection of 230µm in thickness; to be applied on Ducts using manufacturer's recommended rubber-based adhesive in a blend of solvents.
118 118 (a) 19 mm thick 100 SQM
119 119 Item No. 37 Supply, Installation, Testing and Commissioning of ceiling-hung Supply Air Axial flow fans of 15 mm WG static pressure complete with GSS casing , aluminium alloy impellers, directly driven by TEFC induction motor suitable to operate at 415 ± 10% volts, 50Hz, 3 Phase AC supply, 1450/970 RPM, supporting frame, backdraft damper, louvers, weld mesh inlet guard, flexible duct connector as required etc. \n
120 120 Axial fans should be AMCA rated for air performance and sound. It should have motor & fan of Class- F and be third-party certified.
121 121 The fans are to be interlocked with fire detection system with necessary fire module, to be operated in case of fire which shall be in the scope of other agency.
122 122 (a) 15000 CFM 2 EACH
123 123 Item No. 38 Supply, Installation, Testing and Commissioning of ceiling-hung Exhaust Air Axial flow fans of 15 mm WG static pressure complete with GSS casing , aluminium alloy impellers, directly driven by TEFC induction motor suitable to operate at 415 ± 10% volts, 50Hz, 3 Phase AC supply, 1450/970 RPM, supporting frame, backdraft damper, louvers, weld mesh inlet guard, flexible duct connector, as required etc. \n
124 124 Axial fans should be AMCA and UL rated for air performance and sound. It should be motorized & have a fire-rated fan of Class- H and be third-party certified, suitable for working at high temperature (250 deg. C for minimum 2 hrs.)
125 125 The fans are to be interlocked with fire detection system with necessary fire module, to be operated in case of fire which shall be in the scope of other agency.
126 126 (a) 10000 CFM 2 EACH
127 127 (b) 4000 CFM 2 EACH
128 128 Pre-requisites (requirement of items) :
129 129 The outgoing feeders as indicated in BOQ shall have suitable range of followings (except capacitor feeders): \n
130 130 All Digital electronic MFM cum KWH meter where provided shall be equipped with communication port & three-phase indicating lamps protected by 2 amps SP MCBs.
131 131 415/110V suitable rating control transformer shall be provided for aux. control supply.
132 132 Wiring with space heater, thermostat and control MCBs shall be provided for all vertical sections of main LT panel.
133 133 All incoming as well as outgoing feeders shall have pad locking facility.
134 134 Suitable danger board shall be provided.
135 135 All MCCBs shall be provided with front rotary handle and operating mechanism for door interlock with pad locking of MCCBs handles in “OFF” position.
136 136 All hinged door shall be earthed through 2.5 sq.mm tinned braided copper wire.
137 137 Panels shall be powder-coated with grey paint shade no. RAL-7032 of IS-5.
138 138 Minimum Degree of protection for following type of distribution panel enclosure shall be as per IS:60439
139 139 All motor feeders MCCBs shall be of motor duty.
140 140 Supporting/Base rigid steel framework.
141 141 TPN MCCB’s shall mean 3 pole MCCB’s with adequate sizes of neutral link.
142 142 Final rating & various parameters, in addition to those specified below, shall be selected on the bases of ambient conditions at site, client specific requirements, requirement for the NOC from various statutory authorities, as per detailed design stage calculations.
143 143 Each Panel incomers/outgoings shall be provided with suitable contacts/terminals to receive the Al. conductor cables given in the latter section.
144 144 Each Panel shall be minimum IP-54 for Indoor environment except for outdoor conditions, which are mentioned separately.
145 145 Item No. 39 Supply, installation, testing & commissioning of wall-mounted front operated LT PANEL for 415V, 3 Phase, 4Wire 50 Hz AC supply system fabricated in compartmentalized design with CRCA sheet steel of 2mm thickness for frame work and covers, 3mm thickness for gland plates i/c cleaning & surface treatment with 9 tank process before powder coating in approved shade, having specified below Amp. capacity extensible type TPN Aluminium Alloy bus bars with suitable rating: Neutral to high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 35kA for 1 sec, bottom base channel of MS section not less than 100mm x 75mm x 5mm thick, fabrication shall be done in transportable
146 146 sections, entire panel shall have a common copper earth bar of size 32mm x 5mm at the rear with 2 nos. earth stud, solid connections from main bus bar to switch gears with required size of earth bus, Al. bus bars, numbering & sign writing, interconnection & control wiring including the cost of connection through bus bar / copper conductor flexible connection with necessary interlocking as per requirement with PVC insulated FRLS copper conductor single core cable, cable alleys, cable gland plates in two halves, i/c providing following switch gears:
147 147 (a) HVAC PANEL - PLANT ROOM 1 EACH\n SET
148 148 INCOMER
149 149 1 no. 400A 4P MCCB (35 kA) Icu=Ics micro-processor based having earth fault protection with 600A 4P ASTS(T) with bridging bars and as per IS/IEC-60947 complete as required.
150 150 METERING & INDICATION
151 151 1 set of R, Y, B phase, ON indicating lamps
152 152 1 no. (0-500V) Voltmeter with built-in VSS with 3 nos. 2A SP MCB
153 153 1 no. (0-500A) Ammeter with ASS with 3 nos. 500/5A CTs
154 154 BUS-BAR
155 155 1 set of 500A TPN Aluminium Bus-Bar with colour-coded PVC sleeves
156 156 OUTGOINGS
157 157 Following Outgoings with thermal magnetic-based releases (except specified anywhere) with Volt Meter & required CTs, indications, operating handle with door interlock, spreader links and phase barrier, solid neutral link and accessories as required. (Ics=Icu=35kA) for each.
158 158 Note: Chiller is assumed to be provided with its starting arrangement with chiller supply.
159 159 3 nos. 150A TP MCCB 25 kA (2 Chiller, 1 spare) microprocessor-based having earth fault
160 160 4 nos. 16A TP MCB 25 kA (3 CHWP, 1 spare)
161 161 4 nos. 25A TP MCB 25 kA (3 CDWP, 1 spare)
162 162 3 nos. 25A TP MCB 25 kA (2 CT fan, 1 spare)
163 163 2 nos. 16A TP MCB 25 kA (1 HW pump, 1 spare)
164 164 10 nos. 25A TPN/SPN MCB c curve 10 kA
165 165 Automatic DOL starter for 2 kW motors with over load relay, SET indications, Push Buttons, auto manual selector switch, C.T. operated Ammeter with selector switch etc. complete with single phase preventer as required - 2 sets
166 166 Automatic DOL starter for 2.08 kW motors with over load relay, SET indications, Push Buttons, auto manual selector switch, C.T. operated Ammeter with selector switch etc. complete with single phase preventer as required - 3 sets
167 167 Automatic DOL starter for 1.25 kW motors with over load relay, SET indications, Push Buttons, auto manual selector switch, C.T. operated Ammeter with selector switch etc. complete with single phase preventer as required - 3 sets
168 168 Automatic DOL starter for 0.38 kW motors with over load relay, SET indications, Push Buttons, auto manual selector switch, C.T. operated Ammeter with selector switch etc. complete with single phase preventer as required - 2 sets
169 169 (b) AHU PANEL 1 EACH \nSET
170 170 INCOMER
171 171 1 no. 40A 4P MCB (25 kA) Icu=Ics; thermal magnetic-based having earth fault protection with front operating rotary handle and as per IS/IEC-60947 complete as required.
172 172 METERING & INDICATION
173 173 1 set of R, Y, B phase, ON indicating lamps
174 174 1 no. (0-500V) Voltmeter with built-in VSS with 3 nos. 2A SP MCB
175 175 1 no. (0-100A) Ammeter with ASS with 3 nos. 100/5A CTs
176 176 BUS-BAR
177 177 1 set of 63A TPN Aluminium bus-bar with colour-coded PVC sleeves
178 178 OUTGOINGS
179 179 Following Outgoings with thermal magnetic-based releases with Volt Meter & required CTs, indications, operating handle with door interlock, Spreader links and phase barrier, solid neutral link and accessories as required. \n(Ics=Icu=16kA) for each
180 180 4 nos. 25A TP MCCB (3 AHU, 1 spare)
181 181 5 nos. 16A SPN MCB c curve 10 kA
182 182 Note- Panel should have space to fix VFD in AHU, indicating lamp & all safety precautions in a GI enclosure with necessary power and control cable as required.
183 183 STARTER PANEL located near each Axial Flow Fan
184 184 ITEM No. 40 (A) Supply, installation, testing & commissioning of wall-mounted front operated LT PANEL for 415V, 3 Phase, 4Wire 50 Hz AC supply system fabricated in compartmentalized design with CRCA sheet steel of 2mm thickness for frame work and covers, 3mm thickness for gland plates i/c cleaning & surface treatment with 9 tank process before powder coating in approved shade, having specified below Amp. capacity extensible type TPN Aluminium Alloy bus bars with suitable rating: Neutral to high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 35kA for 1 sec, with suitable bottom base channel of MS section complete cable gland plates in two halves incl providing following switch gears: 2 EACH \nSET
185 185 Automatic DOL starter with suitable MCB isolator for 3.7 KW motors with over load relay, SET indications, Push Buttons, auto manual selector switch, C.T. operated Ammeter with selector switch etc. complete with single phase preventer as required.
186 186 ITEM No. 40 (B) Panel described above but ; \nAutomatic DOL starter with suitable MCB isolator for 2.2 KW motors with over load relay, SET indications, Push Buttons, auto manual selector switch, C.T. operated Ammeter with selector switch etc. complete with single phase preventer as required. 2 EACH \nSET
187 187 ITEM No. 40 (C) Panel described above but ; \nAutomatic DOL starter with suitable MCB isolator for 0.75 KW motors with over load relay, SET indications, Push Buttons, auto manual selector switch, C.T. operated Ammeter with selector switch etc. complete with single phase preventer as required. 2 EACH \nSET
188 188 Item No. 41 Supply, laying testing and commissioning of following sizes of XLPE insulated, PVC sheathed, round wire armoured aluminium conductor cable of 1.1 KV grade on cable tray / surface including clamps, ties etc. as required.
189 189 (a) 3.5 core x 50 sq.mm. 50 RM
190 190 (b) 3.5 core x 25 sq.mm. 20 RM
191 191 (c) 3 core x 6 sq.mm. 50 RM
192 192 (d) 3 core x 4 sq.mm. 100 RM
193 193 Item No. 42 Supplying and making end terminations with brass compression gland and aluminium lugs for following sizes of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
194 194 (a) 3.5 core x 50 sq.mm. 3 EACH\n SET
195 195 (b) 3.5 core x 25 sq.mm. 1 EACH \nSET
196 196 (c) 3 core x 6 sq.mm. 8 EACH \nSET
197 197 (d) 3 core x 4 sq.mm. 3 EACH \nSET
198 198 Item No. 43 Supply & fix control wiring/power cabling with following sizes of copper conductor armoured cable, making connections etc., as required:-
199 199 (a) 2 Core x 1.5 sq.mm 200 RM
200 200 Item No. 44 M & L for earthing complete with galvanized steel earth plate 600 x 600 x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI strip of size 32 x 6 mm by means of bolts, check nut, nuts and washers including charcoal dust and common salt, necessary excavation in soil, returning filling in and removal of surplus soil to a distance upto 50 mtrs, PCC pit in cement concrete 1:3:6 type C1 using (20mm grade stone aggregate), precast pit cover 40 mm thick in RCC 1:2:4 type B-1 (using 20mm grade stone aggregate) reinforced with 8 mm dia TMT bars 75 mm c/c both ways, MS handle 12 mm dia, PGI funnel wire mesh and GI watering pipe of 20 mm bore (light grade) and earth lead protection pipe 40 mm bore (light grade) GI pipe for earth lead protection,as specified incl testing of earthing all as specified and directed by Engineer-in- charge.\nNote: GI strip and protection pipe of 40 mm dia upto 7.5 meter length is deemed to be included in the rate quoted. 2 SET OF\n TWO
201 201 Item No. 45 Supply & fix 25 x 5 mm GI strip for earthing all as specified and directed. 30 RM
202 202 Item No. 46 Supply, fabrication and installing of following sizes of hot dip galvanized ladder-type cable trays including horizontal vertical bends, reducers, tees, cross members and other accessories as required and duly installed from the ceiling/ side walls with suitable sizes of channels/ angles with anti-corrosion painting, full threaded GI rods etc. complete as required & approved by the Engineer-in-charge:-
203 203 (a) 150 mm (50 mm x 1.6 mm thick ) 90 RM
204 204 (b) 200 mm (50 mm x 2.0 mm thick ) 140 RM
205 205 (c) 300 mm (50 mm x 2.0 mm thick ) 180 RM
206 206 FIRE FIGHTING
207 207 Item No 47. Supply, installation, testing and commissioning of analogue addrassable Single loop "Main Fire Alarm Control Panel", expandable up to 10 loops with 99 detectors & modules & up to 200 detectors and modules per each loop, LCD display & QWERTY numeric keypad, power supply & 24 hrs battery back-up suitable for loop length 1.5 km per loop complete all as specified and directed.\nMake: Notifier NFS2-3030 or Equivalent 1 EACH \n
208 208 Item No 48. Supply, installation, testing and commissioning of networkable active repeater panel with 40 character LCD display connected peer to peer with "Main Fire Alarm Panel" with accept, reset functions complete all as specified and directed.\nMake: Notifier NCA-2 or Equivalent 1 EACH \n
209 209 Item No.49 Supply, installation, testing and commissioning of detectors complying with and type certified to EN - 45 addressable type smoke & heat detector photoelectric /optical with base (above false-ceiling) with self built intelligence as per IS 11360: 1985 complete all as specified and directed.\nMake: Notifier FAPT-851 or Equivalent 14 EACH \n
210 210 Item No 50. Supply, installation, testing and commissioning of detectors complying with and type certified to EN - 45 addressable type smoke & heat detector photoelectric /optical with base (below false-ceiling) with self built intelligence as per IS 11360: 1985 complete all as specified and directed.\nMake: Notifier FST-851 or Equivalent 33 EACH \n
211 211 Item No 51. S&F remote response indicator flush mounted on false-ceiling / wall complete all as specified and directed.\nMake: Agni or equivalent 33 EACH \n
212 212 Item No 52. Supply, installation, testing and commissioning of addressable type Manual Call Point (break glass type) complete with push button, enclosed in box with provision for cable or conduit coupling, painted fire red outside, white inside and written 'In case of fire break glass' complete as specified and directed. \nMake: Notifier NBG-12LX or equivalent 4 EACH \n
213 213 Item No 53. Supply, installation, testing and commissioning of addrassable type indoor Sounder cum Flasher with addressable control module and box consisting 8 different tone varients complete all as specified and directed.\nMake: Notifier SYS/HS/FCM or equivalent 4 EACH \n
214 214 Item No 54. S & F 5 A, 24 V DC power supply for sounder cum flasher with enclosure complete all as specified and directed. 4 EACH \n
215 215 Item No 55. Supply, installation, testing and commissioning of fault isolator module with required junction box complete all as specified and directed.\nMake: Notifier ISO/X or equivalent 3 EACH \n
216 216 Item No 56. Supply, installation, testing and commissioning of control relay module with enclosure / junction box complete for third party integration complete all as specified and directed.\nMake: Notifier FRM/1 or equivalent 4 EACH \n
217 217 Item No 57. Supply, installation, testing and commissioning of open area smoke imaging detection- OSID- with dual wavelength LED based smoke detection, 90° FOV, dust & intrusive solid object rejection connected through monitor module on FAS loop including imager (02 Nos), battery powered emitter(04 Nos), diagnostic tool (01 No.) and external power source (02 Nos) complete all as specified and directed. 1 EACH SET\n
218 218 (a) imager\nMake: XTRALIS OSI-90 or equivalent\n
219 219 (b) battery powered emitter\nMake: XTRALIS OSE-SP-01 or equivalent
220 220 (c) diagnostic tool\nMake: XTRALIS OSID-INSTor equivalent\n
221 221 (d) external power supply source (24 V DC, 5 A)\nMake: Notifier PF-24V-FCM-1 or equivalent
222 222 Item No.58 M & L for copper conductor, XLPE insulated armoured cables, conforming to IS: BS EN 60228, having annealed copper conductor, PVC inner sheath, single armouring of galvanized round steel wire, one layer of PETP tape wrapping, collective screen of PETP/Aluminum tape over tinned copper drain wire, RED in colour, including clamping, termination and ferruling complete all as specified and directed of following size:-\nMake: RR Kabel, Havells or Polycab
223 223 (a) 2 core, 1.5 Sq mm 750 RM
224 224 (b) 2 core, 2.5 Sq mm 400 RM
225 225 Item No 59. Supply and Fix LED Fire exist signage Single/Double side Display Outer frame made of ABS material of Size 300 mm X 175 mm , Lit by 9 Watt LED with 12 Volt Battery Back up for one hour duration as required 20 EACH \n
226 226 Item No 60. Supply, installation, testing and commissioning of electric motor driven horizontal end-suction & top discharge, back pull-out type centrifugal pump, confirming to IS: 12469- 2011, with CI casing, bronze impeller and stainless steel shaft, mechanical seal, etc. to deliver 2280 LPM at 70 m head coupled with a spacer coupling to a 2 pole TEFC type squirrel cage induction motor of suitable HP with IP 55 protection of enclosure at 2900 RPM speed, efficiency not less than 55%, suitable for operation on 415 V ±10%, 3-Phase, 50 Hz AC supply, horizontal foot-mounted type with class F insulation, confirming to S: 12615- 2018, with coupling guard, foundation as per manufacturer's recommandation, etc. complete all as specified and directed. \nMake: Kirloskar, Mather & Platt, Crompton Greves 1 EACH \n
227 227 Item No 61. Supply, installation, testing and commissioning of diesel engine driven horizontal end-suction & top discharge, backpull out type centrifugal pump, conforming to IS: 12469- 2011, with CI casing, bronze impeller and stainless steel shaft, mechanical seal, etc. mounted on heavy duty bearings, couplings, zero access type coupling guard, etc. capable to deliver 2280 LPM at 70 m head. The pump shall be coupled to a water-cooled radiator, diesel engine of suitable BHP & speed, two sets of batteries of adequate rating with suitable for battery leads & stand, battery charger, residential silencer, diesel tank of capacity adequate for 6 hours of operation and fitted with level and exhaust silencer. The complete set shall be mounted on common base frame including foundation as per manufacturer's recommendation complete all as specified and directed. \nMake: Kirloskar, Mather & Platt, Crompton Greves, Cummins 1 EACH \n
228 228 Item No 62. Supply, installation, testing and commissioning of electric motor driven horizontal end-suction & top discharge, back pull-out type centrifugal booster pump, confirming to IS: 12469- 2011, with CI casing, bronze impeller and stainless steel shaft, mechanical seal, etc. to deliver 450 LPM at 36 m head coupled with a spacer coupling to a 2 pole TEFC type squirrel cage induction motor of suitable HP with IP 55 protection of enclosure at 2900 RPM speed, efficiency not less than 55%, suitable for operation on 415 V ±10%, 3-Phase, 50 Hz AC supply, horizontal foot-mounted type with class F insulation, confirming to IS: 12615- 2018, with coupling guard, foundation as per manufacturer, complete all as specified and directed.\nMake: Kirloskar, Mather & Platt, Crompton Greves 1 EACH \n
229 229 Item No 63. Supply, installation, testing and commissioning of electric motor driven horizontal end-suction & top discharge, back pull-out type centrifugal jockey pump, confirming to IS: 12469- 2011, with CI casing, bronze impeller and stainless steel shaft, mechanical seal, etc. to deliver 180 LPM at 70 m head coupled with a spacer coupling to a 2 pole TEFC type squirrel cage induction motor of suitable HP with IP 55 protection of enclosure at 2900 RPM speed, efficiency not less than 55%, suitable for operation on 415 V ±10%, 3-Phase, 50 Hz AC supply, horizontal foot-mounted type with class F insulation, confirming to S: 12615- 2018, with coupling guard, foundation as per manufacturer, complete all as specified and directed.\nMake: Kirloskar, Mather & Platt, Crompton Greves 1 EACH \n
230 230 Item No. 64. M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe on floor/wall/ceiling with clamps, hangers, angles, channels (using anchor fastners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete all as specified and directed.\nMake: Tata, Jindal, BST
231 231 NOTE:\n[i] Standard MS fittings with welded joint shall be used on the pipes.\n[ii] All hangers, clamps, brackets etc. shall be of galvenized iron.\n[iii] Welding of any kind on the galvanised support/hanger shall not be permitted.\n[iv] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded.
232 232 (a) 150 mm NB 25 RM
233 233 (b) 100 mm NB 200 RM
234 234 (c) 80 mm NB 30 RM
235 235 (d) 65 mm NB 10 RM
236 236 (e) 25 mm NB 40 RM
237 237 Item No.65 M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe in excavated trenches with painting of one coat primer and 2 or more coats of synthetic enamel paint of and wrapping of 4 mm thick protection coating by thermo fusion process complete all as specified and directed.\nMake: Tata, Jindal, BST
238 238 NOTE: \n[i] Standard MS fittings with welded joint shall be used on the pipes.\n[ii] All hangers, clamps, brackets etc. shall be of galvenized iron.\n[iii] Welding of any kind on the galvanised support/hanger shall not be permitted.\n[iv] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded.
239 239 (a) 150 mm NB 140 RM
240 240 (b) 100 mm NB 20 RM
241 241 Item No. 66 Supply, installation, testing and commissioning of PN 1.6 rated CI 'Y' -type strainer for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps all complete as specified and directed.\nMake: Kirloskar, Leader, Venus
242 242 (a) 150 mm NB 1 Each
243 243 (b)100 mm NB 4 Each
244 244 Item No. 67 Supply, installation, testing and commissioning of PN 1.6 rated CI sluice valve, conforming to IS: 14846- 2000, with SS spindle conforming to IS: 6603- 2001 and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories all complete as specified and directed.\nMake: Kirloskar, Leader, Venus
245 245 (a) 150 mm NB 9 Each
246 246 (b) 100 mm NB 6 Each
247 247 (c) 80 mm NB 1 Each
248 248 (d) 65 mm NB 1 Each
249 249 Item No. 68 Supply, installation, testing and commissioning of PN 1.6 rated CI swing check type reflux (non return) valve, conforming to IS: 5312 (Part 1)- 2004 with flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories all complete as specified and directed.\nMake: Kirloskar, Leader, Venus
250 250 (a) 150 mm NB 4 Each
251 251 (b) 100 mm NB 3 Each
252 252 (c) 80 mm NB 3 Each
253 253 Item No 69. Supply, installation, testing and commissioning of pressure switch suitable for pressure range 0- 14 bar having die cast aluminium construction and SS sensing element with ball valve, fittings viz. unions, collars, reducers etc. for fire pumpsets complete all as specified and directed.\nMake: Schneider, Danfoss, Honeywell, Siemens 4 Each
254 254 Item No 70. Supply, installation, testing and commissioning of bourdon pressure gauge suitable for 0-14 kg pressure range with 4" dial, die cast aluminium body, ball valve, nipple, socket, etc. for delivery lines of fire pumpsets near the flow switches all complete as specified and directed.\nMake: L & T, Danfoss, Fiebig, Baker Mercer 4 Each
255 255 Item No 71. S & F gunmetal fire hydrant single landing valve with 80 mm NB flanged inlet, brass spindle controlled 63 mm NB female instantaneous outlet type gunmetal coupling, blank cap, chain, twist release type lug & all accessories conforming to IS:5290- 1993 including fixing with anchor fastner and flanged tapping from wet riser and pressure gauge with gunmetal ball valve complete all as specified and directed.\nMake: Minimax, Vijoy, Safex, Ceasefire 8 Each
256 256 Item No 72. S & F indoor type wall-mounted lockable hose cabinet made of 18 gauge MS sheet with double door and 3 mm thick glazed glass with water proof rubber beading. it shall be in red out side and white inside with two coats of enamel paint over a coat of primer. "HOSE CABINET NO." shall be painted on the inner face of the glass in 50 mm size block letter. Cost shall include the cost of break glass box containing the key of the cabinet. Size of Cabinet shall be suitable to house 2 Nos. of 15 m RRL hose and 2 Nos. branch nozzles. Cabinet size 600 mm (H) x 800 mm (L) x 250 mm (D). 8 Each
257 257 Item No 73. S & F non-percolating rubber reinforced lined RRL hose type- A 15 m long fire hose of 63 mm NB size, conforming to IS: 636- 1988, rated for bursting pressure of 35.7 kg/cm² complete with gunmetal male & female coupling conforming to IS: 903- 1993, bound and rivetted to the hose pipe with copper rivets and 1.5 mm² copper wire complete as specified and directed. \nMake: Minimax, Vijoy, Safex, Ceasefire 16 Each
258 258 Item No 74. S & F 63 mm NB instantaneous inlet, 15 mm NB made threaded outlet nozzle branch short gunmetal pipe, conforming to IS 903- 1993, suitable for inter connection to hose pipe coupling complete all as specified and directed.\nMake: Minimax, Vijoy, Safex, Ceasefire 8 Each
259 259 Item No 75. S & F swinging type 36 m long First Aid Hose Reel, conforming to IS:884-1969, having 19 mm NB thermoplastic reinforced hose reel tubing, conforming to IS: 12585- 1988, 25 mm NB ball valve, stop cock, terminating with gunmetal coupling & nozzle of 6 mm NB outlet with shut-off valve, conforming to IS: 8090- 1976 complete with MS socket for tap-off, red colour drum, brackets (including painting) for fixing on wall with anchor fastner, bolts, nuts, etc. complete all as specified and directed.\nMake: Minimax, Vijoy, Safex, Ceasefire 8 Each
260 260 Item No 76. Supply, installation, testing and commissioning of 4- way fire brigade inlet connection, conforming to IS: 5290- 1993, with four 63 mm NB inbuilt gunmetal non-return valves, four 63 mm NB instanteneous couplings arranged on 150 mm NB pipe manifold and connected to fire hydrant ring main and fire hydrant wet riser pipe all complete as specified and directed. \nMake: Minimax, Vijoy, Safex, Ceasefire 1 Each
261 261 Item No 77. Supply, installation, testing and commissioning of 2- way fire brigade inlet connection, conforming to IS: 5290- 1993, with two 63 mm NB inbuilt gunmetal non-return valves, four 63 mm NB instanteneous couplings arranged on 150 mm NB pipe manifold and connected to fire hydrant ring main and fire hydrant wet riser pipe all complete as specified and directed. \nMake: Minimax, Vijoy, Safex, Ceasefire 4 Each
262 262 Item No 78. Supply, installation, testing and commissioning of 2-way fire brigade draw- off connection with two 63 mm NB inbuilt gunmetal non-return valves instanteneous coupling type arranged on 100 mm NB pipe manifold and connected to wet riser main as well as to fire water tank including CI butterfly valve, CI non-return valve and MS cabinet with mounting supports, etc. all complete as specified and directed.\nMake: Minimax, Vijoy, Safex, Ceasefire 1 Each
263 263 Item No 79. Supplying, installing, testing and commissioning of MS air cushion tank, conforming to IS: 4736-1968 on top of each riser fabricated from 6 mm thick MS plate, 200 mm in diameter and 1.2 m in height with dished ends fabricated from 8 mm thick MS plate with Air release valve with stop cock, flanged inlet connection and drain arrangement with 25 mm NB valve, pressure gauge with gun metal stop cock complete all as specified and directed. 5 Each
264 264 Item No 80. M & L for Construction of fly-ash brick masonary valve chamber of size 1000 mm X 800 mm X 1000 mm (internal dimenssions) with PCC foundation 1:4:8 type D2 using 40 mm graded stone aggregate, 150 mm thick & 150 mm wide offsets around over 100 mm thick hardcore , 200 mm thick fly-ash brick masonry walls built in CM 1:6, 100 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including excavation earth work in hard/Dense soil 6 mm thick MS sheet cover fixed on 25 mm X 25 mm X 6 mm thick angle iron frame with hold fasts embedded in PCC coaping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil to a distance not exceeding 50 m etc complete all as specified and directed. 3 Job
265 265 Item No 81. Excavation in trenches/foundation not exceeding 1.5 m wide and n exc 1.5 m deep for poles, laying of cables, etc. and getting out in soft/loose soil all complete as specified and directed. 10 Cum
266 266 Item No 82. Returning filling including spreading leveling watering and well ramming in layers not exceeding 25 cm in soft/loose soil all complete as specified and directed. 2 Cum
267 267 Item No 83. Removing excavated material to a distance exc. 250 m but not exceeding 500m and depositing where directed in soil all complete as specified and directed. 8 Cum
268 268 Item No 84. Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type "Motor Control Center" (MCC) of suitable size, conforming to IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 54 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed. \nMake: Schneider Blokset, Siemens - Sivacon, ABB-MNS 1 Each
269 269 The MCC shall comprise of the following:\n[a] Busbar Chamber:\n[i] Copper busbar of rated capacity 400 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (3P + N)
270 270 [b] Incoming:\n[i] 250 A, 36 kA, 415 V, 50 Hz, FP MCCB with thermal magnetic trip unit (TMD), compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 1.5- 10 X Ir), inbuilt encapsulated double break roto active type instanteneous protection, earth fault leakage protection, etc. having Ics = 100% Icu as per IEC 60947-2- 01 Nos\n[ii] LED phase indicators (Red, Yellow, Blue)- 04 Set\n[iii] Power Measurement Device with Class 1 accuracy, complying to IEC 62053- 22, 64 samples/cycle, 31st harmonic analysis, RS485, calibration LED, third party accuracy test certificate - 03 Nos.
271 271 [c] Outgoing:\n[i] Fully automatic variable frequency drive, suitable for main fire pump, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc- 01 Nos.\n[ii] Fully automatic DOL starter, suitable for the booster pump, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc.- 01 Nos
272 272 [iii] Fully automatic DOL starter, suitable for the jockey pump, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc.- 01 Nos.\n[iv] 32 A, 10 kA, 230 V SPN MCB along with battery charger and indication lamps for phase indication, battery charging, overload relay, low oil pressure etc., auto/manual selector switch, push buttons for engine start, engine stop, engine hooter acknowledgement, engine fault reset, selector switches, auxiliary relays, contactors, timers for sequence operating for starting & stopping the engine and sufficient NO/NC contacts for annunciation of fire pumps to the Fire Alarm Panel- 01 Nos.
273 273 [v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 03 Nos.\n[vi] LED phase indicators (Red, Yellow, Blue)- 03 Set\nNOTE: \n[i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System & shall be Web based application in-built.\n[ii] 03 Nos. of ON/OFF/trip status and operations counters as well as multi-function meters shall be wired to Ethernet Gateway part of the Panel.
274 274 Item No.85 : M & L for ISI marked 1.1 kV grade aluminium conductor, XLPE insulated armoured cables, conforming to IS: 7098 (Part 1)- 1988 having stranded aluminium compact shaped conductor as per Cl. 2, IS: 8130- 1984, PVC inner sheath, single armouring of galvanized steel strip/wire and PVC Type ST- 2 outer sheath conforming to IS: 5831- 1984, including clamping and termination complete as specified and directed.\nMake: RR Kabel, Polycab, Havells
275 275 (a) 3.5 core 70 Sq mm 70 RM
276 276 (b) 4 core 16 Sq mm 50 RM
277 277 Item No 86. M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised strip of size 32 mm x 6 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed. 10 EACH \n
278 278 Item No 87. M & L for GI strip of size 32 mm x 6 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed. 100 RM
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.

Copyright © 2021 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail