Repair And Maintenance Of Lightning Arrester And Connected Accessories At Airforce Station Thanjavur, THANJAVUR-Tamil Nadu

Military Engineer Services-MES has published Repair And Maintenance Of Lightning Arrester And Connected Accessories At Airforce Station Thanjavur. Submission Date for this Tender is 11-02-2021. Bolts Tenders in THANJAVUR Tamil Nadu. Bidders can get complete Tender details and download the document.




Tender Notice

26762616
Corrigendum : Repair And Maintenance Of Lightning Arrester And Connected Accessories At Airforce Station Thanjavur
Open Tender
Indian
Tamil Nadu
THANJAVUR
11-02-2021

Tender Details

Repair And Maintenance Of Lightning Arrester And Connected Accessories At Airforce Station Thanjavur , Material And Labour For Tripod ( Delta ) Type Maintenance Free Chemical Earthing ( Comprising Of Three Nos Chemical Earthing ) As Per Drawing Attached ( Sketch No - 01 ) The Chemical Earthing Including Taking Down Will Have Specification As Follows:- ( A ) Copper Electrode Of Wall Thickness Minimum 2Mm Not Less Than 3 Mtr Length With Not Less Than 76Mm Outer Dia Total 03 Nos Including Copper Strip Of Size 50 X 6Mm Minimum 2 Mtr Long Connected / Brazing With 75Mm Dia Copper Electrode And 25Mm X 3Mm Copper Strip Not Less Than 3 Mtr Long For Inter Connecting Three 75Mm Copper Earth Electrode Complete As Per Drawing . ( B ) Fixing Of Copper Earth Electrode By Drilling / Boring 175Mm Dia Hole 5 . 00 Mtr Deep In Any Type Of Strata , Placing Electrode Along With Extention Earth Strip 50 X 6Mm 2 Mts Long And Mixing Earthing Soil Resitivity Improvement Compound Gel Min 10 Kg Per Bore Total 30 Kg For 3 Bores And 75 Kg Per Bore Total 225 Kg For 3 Bores Soil Resistivity Improvement Compound Homogeneously As Per Manufacturer Instruction . ( C ) Frp Earthing Display Board 254Mm X 380Mm Made Out Of Plastic Material Showing Information Related To Type Of Earthing , Earthing Result , Due Date Of Testing Along With Fixing Size 610Mm Height Made Of Plastic Hollow Pipe Of 20Mm Dia . ( D ) Pcc Earthing Pit In Pcc 1:2:4 Type B-1 Of Internal Size 300Mm X 300Mm X 300Mm With 120Mm Thick Wall And 700Mm X 70Mm X 150Mm Thick Bed Concrete And 50Mm Thick Precast Chamber Cover Of Rcc 1:2:4 Type B1 For Reinforced With Welded Steel Wire Fabric Or Xpm Jali ( Weight Not Less Than 4 . 00 Kg / Sqm ) , Complete All As Shown In Electrical Plate No -3 Of Ssr Part - I Complete . ( E ) Contractor Must Visit The Site Before Quoting The Tender To Understand The Difficulty And Cost For Carrying Out The Job In The Station . It Is Important That Contractor Ascertain The Quontum Of Work . ( F ) Contractor Must Produce The Certificate From The Manufacturer That Chemical Earthing Has Been Carried Out By Manufacturer . The Manufacturer Must Also Issue The Warranty For Chemical Earthing That Ohmic Value Of Earth Shall Not Increse More Than 1 Ohm For Five Year . ( G ) Extension Strip From Electrode Upto 0 . 15Mtr Height From Gl To Be Deemed Included In Quted Rate Including Brazing Of All Joints . Make:- Powertrac / Pragati / Mcmls Earthing Solution / Ashlock . , Material And Labour For Maintenance Free Chemical Earthing Comprising Of One No Chemical Earthing Including Taking Down The Chemical Earthing Will Have Specification As Follows:- ( A ) Copper Electrode Of Wall Thickness Minimum 2Mm Not Less Than 3 Mtr Length With Not Less Than 76Mm Outer Dia Including Copper Strip Of Size 50 X 6Mm Minimum 2 Mtr Long Connected / Brazing With 76Mm Dia Copper Electrode . ( B ) Fixing Of Copper Earth Electrode By Drilling / Boring 175Mm Dia Hole 5 . 00 Mtr Deep In Any Type Of Strata , Placing Electrode Along With Extention Earth Strip 50 X 6Mm 2 Mts Long And Mixing Earthing Soil Resistivity Improvement Compound Gel Min 10 Kg Per Bore And 75 Kg Soil Resistivity Improvement Compound Mixing Homogeneously As Per Manufacturer Instruction . ( C ) Frp Earthing Display Board 254 X 380Mm Made Out Of Plastic Material Showing Information Related To Type Of Earthing , Earthing Result , Due Date Of Testing Along With Fixing Size 610Mm Height Made Of Plastic Hollow Pipe Of 20Mm Dia . ( D ) Pcc Earthing Pit In Pcc 1:2:4 Type B-1 Of Internal Size 300Mm X 300Mm X 300Mm With 120Mm Thick Wall And 700Mm X 70Mm X 150Mm Thick Bed Concrete And 50Mm Thick Precast Chamber Cover Of Rcc 1:2:4 Type B1 For Reinforced With Welded Steel Wire Fabric Or Xpm Jali ( Weight Not Less Than 4 . 00 Kg / Sqm ) , Complete All As Shown In Electrical Plate No -3 Of Ssr Part - I Complete . ( E ) Contractor Must Visit The Site Before Quoting The Tender To Understand The Difficulty And Cost For Carrying Out The Job In The Station . It Is Important That Contractor Ascertain The Quontum Of Work . ( F ) Contractor Must Produce The Certificate From The Manufacturer That Chemical Earthing Has Been Carried Out By Manufacturer . The Manufacturer Must Also Issue The Warranty For Chemical Earthing That Ohmic Value Of Earth Shall Not Increse More Than 3 Ohm For Five Year . ( G ) Extension Strip From Electrode Upto 0 . 15Mtr Height From Gl To Be Deemed Included In Quted Rate Including Brazing Of All Joints . Make:- Powertrac / Pragati / Mcmls Earthing Solution / Ashlock . , Material And Labour For Maintenance Free Chemical Earthing Comprising Of One No Chemical Earthing Including Taking Down The Chemical Earthing Will Have Specification As Follows:- ( A ) Gi Electrode Duel Technology Filled With Hcc Compound Not Less Than 3 Mtr Length With Not Less Than 88Mm Outer Dia Including Gi Strip Of Size 50 X 6Mm Minimum 2 Mtr Long Connected / Welding With 88Mm Dia Gi Electrode . ( B ) Fixing Of Gi Earth Electrode By Drilling / Boring 175Mm Dia Hole 5 . 00 Mtr Deep In Any Type Of Strata , Placing Electrode Along With Extention Earth Strip 50 X 6Mm 2 Mts Long And Mixing Earthing Soil Resistivity Improvement Compound Gel Min 10 Kg Per Bore And 75 Kg Soil Resistivity Improvement Compound Mixing Homogeneously As Per Manufacturer Instruction . ( C ) Frp Earthing Display Board 254 X 380Mm Made Out Of Plastic Material Showing Information Related To Type Of Earthing , Earthing Result , Due Date Of Testing Along With Fixing Size 610Mm Height Made Of Plastic Hollow Pipe Of 20Mm Dia . ( D ) Pcc Earthing Pit In Pcc 1:2:4 Type B-1 Of Internal Size 300Mm X 300Mm X 300Mm With 120Mm Thick Wall And 700Mm X 70Mm X 150Mm Thick Bed Concrete And 50Mm Thick Precast Chamber Cover Of Rcc 1:2:4 Type B1 For Reinfoced With Welded Steel Wire Fabric Or Xpm Jali ( Weight Not Less Than 4 . 00 Kg / Sqm ) , Complete All As Shown In Electrical Plate No -3 Of Ssr Part - I Complete . ( E ) Contractor Must Visit The Site Before Quoting The Tender To Understand The Difficulty And Cost For Carrying Out The Job In The Station . It Is Important That Contractor Ascertain The Quontum Of Work . ( F ) Contractor Must Produce The Certificate From The Manufacturer That Chemical Earthing Has Been Carried Out By Manufacturer . The Manufacturer Must Also Issue The Warranty For Chemical Earthing That Ohmic Value Of Earth Shall Not Increse More Than 5 Ohm For Five Year . ( G ) Extension Strip From Electrode Upto 0 . 15Mtr Height From Gl To Be Deemed Included In Quted Rate Including Brazing Of All Joints . Make:- Powertrac / Pragati / Mcmls Earthing Solution / Ashlock . , Supply And Pouring Earthing Soil Resistivity Improvement Compound Gel ( Power Plus Gel ) Enhancement Compound Transparent Liquid Gel In 5 Kg Packing All As Specified And Directed By Engr In Charge . Make:- Powertrac / Jj Engineering / Sm Infotech . , M & L For Providing Earthing In Repairs With Gi Earth Plate Electrode 600 X 600 X 6Mm Buried Directly In Ground ( Earth Pit Not Less Than 2 . 25M Deep Below Ground Level ) With Top Edge Of The Earth Plate Not Less Than 1 . 5M Below Ground Level Connected To Gi Strip 25 X 4Mm Thick For Earthing Lead Fixed By Means Of Nuts , Bolt , Washers Etc Connected To Earth Test Point Complete All As Specified In Electrical Plate No 3 Of Ssr1996 Part 1 , Including Earthing Soil Resitivity Improvement Compound Gel Min 10 Kg Per Earth Pit And Soil Resistivity Improvement Compound 150 Kg Per Earth Pit And Necessary Excavation And Earth Work In Any Strata Of Soil , Gi Water Pipe With 20Mm Dia Funnel &Wire Mesh Pcc Pit With Ci Cover And Frame Etc All As Specified And All As Directed . Note:- All The Joints Shall Be Made With Welding To Get Proper Conductivity . , M&L For Earth Continuity Conductor In Repairs Or Main Earthing Lead Fixed To Wall On Batten Or Recess Or Chases Or Buried In Ground Or Drawn In Conduit / Pipe Or Fixed To P

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 04-Feb-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 11-02-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 44000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: REPAIR AND MAINTENANCE OF LIGHTNING ARRESTER AND CONNECTED ACCESSORIES AT AIRFORCE STATION THANJAVUR.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Material and labour for Tripod (Delta) type maintenance free chemical earthing (comprising of three Nos chemical earthing) as per drawing attached (Sketch No - 01) the chemical earthing including taking down will have specification as follows:-\n(a) Copper electrode of wall thickness minimum 2mm not less than 3 mtr length with not less than 76mm outer dia total 03 Nos including copper strip of size 50 x 6mm minimum 2 mtr long connected /brazing with 75mm dia copper electrode and 25mm x 3mm copper strip not less than 3 mtr long for inter connecting three 75mm copper earth electrode complete as per drawing.\n(b) Fixing of copper earth electrode by drilling/ boring 175mm dia hole 5.00 mtr deep in any type of strata, placing electrode along with extention earth strip 50 x 6mm 2 mts long and mixing earthing soil resitivity improvement compound Gel min 10 KG per bore total 30 KG for 3 bores and 75 KG per bore total 225 KG for 3 bores soil resistivity improvement compound homogeneously as per manufacturer instruction.\n(c) FRP earthing display board 254mm x 380mm made out of plastic material showing information related to type of earthing, earthing result, due date of testing along with fixing size 610mm height made of plastic hollow pipe of 20mm dia.\n(d) PCC earthing pit in PCC 1:2:4 type B-1 of internal size 300mm x 300mm x 300mm with 120mm thick wall and 700mm x 70mm x 150mm thick bed concrete and 50mm thick precast chamber cover of RCC 1:2:4 type B1 for reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 kg/Sqm), complete all as shown in electrical plate No -3 of SSR part - I complete.\n(e) Contractor must visit the site before quoting the tender to understand the difficulty and cost for carrying out the job in the station. It is important that contractor ascertain the quontum of work.\n(f) Contractor must produce the certificate from the manufacturer that chemical earthing has been carried out by manufacturer. The manufacturer must also issue the warranty for chemical earthing that Ohmic value of earth shall not increse more than 1 Ohm for five year.\n(g) Extension strip from electrode upto 0.15mtr height from GL to be deemed included in quted rate including brazing of all joints.\nMake:- Powertrac / Pragati / McML's Earthing Solution / Ashlock. 2 Each Job
2 2 Material and labour for maintenance free chemical earthing comprising of one No chemical earthing including taking down the chemical earthing will have specification as follows:-\n(a) Copper electrode of wall thickness minimum 2mm not less than 3 mtr length with not less than 76mm outer dia including copper strip of size 50 x 6mm minimum 2 mtr long connected /brazing with 76mm dia copper electrode.\n(b) Fixing of copper earth electrode by drilling/ boring 175mm dia hole 5.00 mtr deep in any type of strata, placing electrode along with extention earth strip 50 x 6mm 2 mts long and mixing earthing soil resistivity improvement compound Gel min 10 KG per bore and 75 KG soil resistivity improvement compound mixing homogeneously as per manufacturer instruction.\n(c) FRP earthing display board 254 x 380mm made out of plastic material showing information related to type of earthing, earthing result, due date of testing along with fixing size 610mm height made of plastic hollow pipe of 20mm dia.\n(d) PCC earthing pit in PCC 1:2:4 type B-1 of internal size 300mm x 300mm x 300mm with 120mm thick wall and 700mm x 70mm x 150mm thick bed concrete and 50mm thick precast chamber cover of RCC 1:2:4 type B1 for reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 kg/Sqm), complete all as shown in electrical plate No -3 of SSR part - I complete.\n(e) Contractor must visit the site before quoting the tender to understand the difficulty and cost for carrying out the job in the station. It is important that contractor ascertain the quontum of work.\n(f) Contractor must produce the certificate from the manufacturer that chemical earthing has been carried out by manufacturer. The manufacturer must also issue the warranty for chemical earthing that Ohmic value of earth shall not increse more than 3 Ohm for five year.\n(g) Extension strip from electrode upto 0.15mtr height from GL to be deemed included in quted rate including brazing of all joints.\nMake:- Powertrac / Pragati / McML's Earthing Solution / Ashlock. \n 10 Each Job
3 3 Material and labour for maintenance free chemical earthing comprising of one No chemical earthing including taking down the chemical earthing will have specification as follows:-\n(a) GI electrode duel Technology filled with HCC compound not less than 3 mtr length with not less than 88mm outer dia including GI strip of size 50 x 6mm minimum 2 mtr long connected / welding with 88mm dia GI electrode.\n(b) Fixing of GI earth electrode by drilling/ boring 175mm dia hole 5.00 mtr deep in any type of strata, placing electrode along with extention earth strip 50 x 6mm 2 mts long and mixing earthing soil resistivity improvement compound Gel min 10 KG per bore and 75 KG soil resistivity improvement compound mixing homogeneously as per manufacturer instruction.\n(c) FRP earthing display board 254 x 380mm made out of plastic material showing information related to type of earthing, earthing result, due date of testing along with fixing size 610mm height made of plastic hollow pipe of 20mm dia.\n(d) PCC earthing pit in PCC 1:2:4 type B-1 of internal size 300mm x 300mm x 300mm with 120mm thick wall and 700mm x 70mm x 150mm thick bed concrete and 50mm thick precast chamber cover of RCC 1:2:4 type B1 for reinfoced with welded steel wire fabric or XPM Jali (weight not less than 4.00 kg/Sqm), complete all as shown in electrical plate No -3 of SSR part - I complete.\n(e) Contractor must visit the site before quoting the tender to understand the difficulty and cost for carrying out the job in the station. It is important that contractor ascertain the quontum of work.\n(f) Contractor must produce the certificate from the manufacturer that chemical earthing has been carried out by manufacturer. The manufacturer must also issue the warranty for chemical earthing that Ohmic value of earth shall not increse more than 5 Ohm for five year.\n(g) Extension strip from electrode upto 0.15mtr height from GL to be deemed included in quted rate including brazing of all joints.\nMake:- Powertrac / Pragati / McML's Earthing Solution / Ashlock. 10 Each Job
4 4 Supply and pouring Earthing soil resistivity improvement compound Gel (Power plus Gel) Enhancement compound transparent liquid Gel in 5 kg packing all as specified and directed by Engr In Charge. Make:- Powertrac / JJ Engineering / SM Infotech. 25 Each
5 5 M & L for providing earthing in repairs with GI earth plate electrode 600 X 600 X 6mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to GI strip 25 x 4mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR1996 part 1 ,including earthing soil resitivity improvement compound Gel min 10 KG per earth pit and soil resistivity improvement compound 150 KG per earth pit and necessary excavation and earth work in any strata of soil,GI water pipe with 20mm dia funnel &wire mesh PCC pit with CI cover and frame etc all as specified and all as directed. Note:- All the joints shall be made with welding to get proper conductivity. 10 Each
6 6 M&L for earth continuity conductor in repairs or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 25 x 4mm GI strip including fixing arrengment like epoxy insulatos on wall/pole etc. Note:- All the joints shall be made with welding to get proper conductivity. 80 Running Metre
7 7 M & L for providing earthing in repairs with GI earth plate electrode 600 X 600 X 6mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to GI wire 4mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR-2012 part 1 ,including earthing soil resitivity improvement compound Gel min 10 KG per earth pit and soil resistivity improvement compound 150 KG per earth pit and necessary excavation and earth work in any strata of soil,GI water pipe with 20mm dia.funnel &wire mesh PCC pit with CI cover and frame etc all as specified and all as directed . Note:- All the joints shall be made with welding to get proper conductivity. 2 Each set
8 8 M&L for earth continuity conductor in repairs or main earthing lead fixed to wall on battern or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 4mm GI wire including fixing arrengment like epoxy insulators on wall/pole etc.. 20 Running Metre
9 9 M & L for providing earthing in repairs with copper earth plate electrode 600 X 600 X 6mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to copper strip 25 x 3mm thick for earthing lead fixed by means of nuts,bolt,washers etc.of copper / brass connected to earth test point complete all as specified in electrical plate NO 3 of SSR-2012 part 1 ,including earthing soil resistivity improvement compound Gel min 10 KG per earth pit and soil resistivity improvement compound 150 KG per earth pit and necessary excavation and earth work in any strata of soil,GI water pipe with 20mm dia.funnel &wire mesh PCC pit with CI cover and frame etc all as specified and directed . Note:- All the joints shall be made with brazing to get proper conductivity. 63 Each
10 10 M&L earth continuity conductor in repairs or main earthing lead fixed to wall on battern or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 25 x 3mm copper strip including fixing arrengment like epoxy insulators on wall/pole etc.. Note:- All the joints shall be made with brazing to get proper conductivity. 400 Running Metre
11 11 M&L earth continuity conductor in repairs or main earthing lead fixed to wall on battern or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 25 x 3mm alluminium strip including fixing arrengment like epoxy insulators on wall/pole etc. Note:- All the joints shall be made with welding to get proper conductivity. 40 Running Metre
12 12 Supply and fixing in repair air termination single pointed aluminium rod 12mm dia and 300mm long complete all as specified and directed . 5 Each
13 13 Supply and fixing in repair air termination single pointed copper rod 12mm dia and 300mm long complete all as specified and directed . 5 Each
14 14 M&L in repair for test point termininal block made of gun metal or phosphorus bronze size 75 x 75 x 25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexoganal head screw. 10 Each
15 15 Supply and pouring common salt commercial best quality complete all as specified and directed . 5 Qtl
16 16 Supply and pouring charcoal dust/breeze best quality complete all as specified and directed . 5 Qtl
17 17 Excavation in trenches in soft/loose soil not exc. 1.5 metre wide and not exc. 1.5 metre in depth and getting out for taking up / laying under ground electric cable or for pole etc complete all as specified and as directed. 60 Cum
18 18 Returning, filling in, including spreading levelling watering and well ramming in layers not exceeding 25 cms in depth in soft/loose soils complete all as specified and as directed. 54 Cum
19 19 Removing surplus soils to a distance not exceeding 50 mtr and depositing where directed at a level not exc. 1.5 mtr above the starting point all complete as specified and as directed. 6 Cum
20 20 Demolition of old unserviceable earth pit chamber and providing PCC earthing pit in PCC 1:2:4 type B-1 of internal size 300mm x 300mm x 300mm with 120mm thick wall and 700mm x 70mm x 150mm thick bed concrete and 50mm thick precast chamber cover of RCC 1:2:4 type B1 for reinfoced with welded steel wire fabric or XPM Jali (weight not less than 4.00 kg/Sqm), complete all as shown in electrical plate No -3 of SSR part - I complete. 10 Each Job
21 21 M&L for brazing of existing copper strip any size of old earthings installed at Tech / Domastic area at Af Stn complete all as specified and directed . . 50 Each Joint
22 22 M&L for welding of existing GI strip any size of old earthings installed at Tech / Domastic area at Af Stn complete all as specified and directed . 50 Each Joint
23 23 Supply and fix epoxy insulators suitable for fixing of copper / GI strip 25 x 3mm including fixing accessories like screws plastic plugs etc complete all as directed . 50 Each
24 24 Supply and fix in repair tube medium grade, galvanised with all fittings and fixed complete to wall and ceiling or laid in floors of size 15mm dia laid in trenches. 100 Running Metre
25 25 Supply and fix in repair tube medium grade, galvanised with all fittings and fixed complete to wall and ceiling or laid in floors of size 40mm dia laid in trenches. 50 Running Metre
26 26 Supply and fix in repair tube medium grade, galvanised with all fittings and fixed complete to wall and ceiling or laid in floors of size 80mm dia laid in trenches. 12 Running Metre
27 27 M&L for cutting of existing GI tube 40mm bore for making new connection inserting unequal Tee 40x40x25mm bore complete all as specified. 3 Each
28 28 S&f in repair Gun metal globe or gate valve with iron wheel head, screwed both ends for iron pipe and fixed of size 25mm dia. 3 Each
29 29 S&F in repair bib taps cast copper alloy with crutch or butterfly handle screwed down screwed for iron pipe or for brass ferrule and fixed of size 15mm bore. 20 Each
Disclaimer :