A ) Construction Of33/11Kv , 2X5mva S/Sand ( B ) Erection Of 0. 155Km S/C33kv Line With Acsr Panthercondctortoff Frmtagore Nagar F/Dands/C33kvline Toff Frm Bangr F/D To33/11Kvgss Bangurclge ( C ) Erection Of 11Kv I/C2 . 35Km Bangrcolleges/S , S/D Csd-Ii , Pali-Rajasthan

Jodhpur Vidyut Vitaran Nigam Limited has published A ) Construction Of33/11Kv , 2X5mva S/Sand ( B ) Erection Of 0. 155Km S/C33kv Line With Acsr Panthercondctortoff Frmtagore Nagar F/Dands/C33kvline Toff Frm Bangr F/D To33/11Kvgss Bangurclge ( C ) Erection Of 11Kv I/C2 . 35Km Bangrcolleges/S , S/D Csd-Ii . Submission Date for this Tender is 08-02-2021. Conductor Tenders in Pali Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

26725775
Corrigendum : A ) Construction Of33/11Kv , 2X5mva S/Sand ( B ) Erection Of 0. 155Km S/C33kv Line With Acsr Panthercondctortoff Frmtagore Nagar F/Dands/C33kvline Toff Frm Bangr F/D To33/11Kvgss Bangurclge ( C ) Erection Of 11Kv I/C2 . 35Km Bangrcolleges/S , S/D Csd-Ii
Open Tender
Indian
Rajasthan
Pali
08-02-2021

Tender Details

A ) Construction Of33 / 11Kv , 2X5mva S / Sand ( B ) Erection Of 0. 155Km S / C33kv Line With Acsr Panthercondctortoff Frmtagore Nagar F / Dands / C33kvline Toff Frm Bangr F / D To33 / 11Kvgss Bangurclge ( C ) Erection Of 11Kv I / C2 . 35Km Bangrcolleges / S , S / D Csd-Ii , Pali , Palicircleonlrc 2020

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 27-Jan-2021 Corrigendum_I Technical Bid 08-02-2021

Key Value

Document Fees
INR 2950 /-
EMD
Refer document
Tender Value
Refer document

BOQ Items

Name of Work:(a) Construction of 33/11 KV, 2x 5 MVA sub-station at Bangur College (b) Erection of 0.155 Km S/C 33 KV line with ACSR Panther Conductor T-off from Tagore Nagar feeder to 33/11 KV GSS Bangur College and S/C 33 KV line with ACSR Panther Conductor T-off from Bangur feeder to 33/11 KV GSS Bangur College (c) Erection of 11 KV Interconnection line 2.35 KM from proposed Bangur College sub-station under Pali Circle on Labour Rate basis
Sl. No. Item Description Item Code / Make Quantity Units
1 1 PART - (A):Construction of 01 No. of 33/11 KV 2x5 MVA Sub-Station at Bangur College BI01010001010000000000000515BI0100001112
2 2 ( 1.3 ) Levelling of ground BI01010001010000000000000515BI0100001113
3 3 Levelling of ground up to 30 cm.depth. with tractor and T&P required as per condition of ground including removal of rubbish plants from ground & marking of boundary with lime powder.(Including all lead & lifting) BI01010001010000000000000515BI0100001114 900 Sq. mtr.
4 4 Levelling of ground above 30 cm.to 90 CM.depth. with tractor and T&P required as per condition of ground including removal of rubbish plants from ground & marking of boundary with lime powder.(Including all lead & lifting) BI01010001010000000000000515BI0100001115 700 Sq. mtr.
5 5 (2.2) Excavation of pit in Hard Soil BI01010001010000000000000515BI0100001116
6 6 (B) Lattice Tower /Size of pit BI01010001010000000000000515BI0100001117
7 7 11.4/10.8 Mtr/ 1.5mx1.5m x1.80 m deep BI01010001010000000000000515BI0100001118 48 Pit
8 8 (2.5) Earth work excavation and foundation of platfrom of transformers and brakers including dressing of sides and ramming of bottoms .Liftup to 1.5 Meter including taking out the excavated soil and depositing and refilling of jhiri, watering and ramming and disposal of surplus excavated soil as directed with in a lead of 50 Meter. 01(PT) 05 (Brekr) BI01010001010000000000000515BI0100001119
9 9 Hard /dense soil BI01010001010000000000000515BI0100001120 74 CUM
10 10 Providing and laying cement concrete including compaction etc, complete using stone aggregate 40 mm nominal size (hand broken ) in foundation plinth excluding the cost of shuttering using 1 cement:5 sand:10 aggregate mix. Note: 1. The rates are all lead of cement,lime,ballast, sand,surkhi and grit etc.at site of work 2. For all concrete work coarse sand shall be used no extra will be paid 3. Concrete mix prepared by power driven mechanical mixer shall be used 4. Under exceptional coditions, where mechanical mixer and vibrator are not used(with the approval of Engineer Incharge reduced by 3% for mechanical mixer and 2% for Vibrator 5. Thickness of the cement concrete should not exceeed 100 mm BI01010001010000000000000515BI0100001121 42.768 CUM
11 11 Plaster on new surface on walls in cement ,sand mortar 1:6 including racking of joint etc. complete fine finsh 25 mm thick. Note: 1. The rates for complete work including racking of joints,curing,grinding,mixing and finishing T&P and scaffolding material and cost of material with all lead and lift 2. The rates cover protection of all place and things,requiring protection and cleaing such places and thing of all droppings and splashes of mortar etc 3. Cement concrete flooring grade 1:2:4 (1-cement :2- coarse sand :4-graded stone aggregate ) rounding off edges etc.but excluding cost of nosing of steps etc. complete BI01010001010000000000000515BI0100001122 132 Sq. M
12 12 (2.8) Cement concrete flooring grade 1:2:4 (1-cement :2- coarse sand :4-graded stone aggregate ) rounding off edges etc.but excluding cost of nosing of steps etc. complete BI01010001010000000000000515BI0100001123
13 13 25 mm thick with 12.5 mm thick nominal size aggregate. BI01010001010000000000000515BI0100001124 47.52 Sq M
14 14 (2.11) Masonry for foundation and plinth BI01010001010000000000000515BI0100001125
15 15 Randon Rubble stone masonry for foundation and plinth in cement sand mortar 1:6(1 Cement : 6 Sand) including labour charges. Note: (1) Rates provided are for the complete finished items insl of cost of water & material with all leads labour , All type of taxes royalty ,scaffolding ,curing , laying ,fixing ,finsihing Etc.,higher charges (2) In case of non avalibility of stone hedder of proper size cement ocncret headder of mix 1:3:6 (M-10) with 25 mm graded stone agregate with smooth finish may be provided by the contractor at no extra cost. BI01010001010000000000000515BI0100001126 34.27 CUM
16 16 (3.2) Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site BI01010001010000000000000515BI0100001127
17 17 Within 10 Kms. BI01010001010000000000000515BI0100001128 2.41 M.T.
18 18 (3.3) Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. BI01010001010000000000000515BI0100001129
19 19 Within 10 Kms. BI01010001010000000000000515BI0100001130 1.18 M.T.
20 20 (3.4) Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. including loading/unloading and stacking in the Nigam. Stores / at work site. BI01010001010000000000000515BI0100001131
21 21 Within 10 Kms. BI01010001010000000000000515BI0100001132 32.16 M.T.
22 22 (3.5) Safe carriage of 11/.4 KV 3 Phase distribution transformer including loading/unloading.from store to site BI01010001010000000000000515BI0100001133
23 23 C) Above 40 KVA & upto 100 KVA BI01010001010000000000000515BI0100001134
24 24 Within 10 Kms. BI01010001010000000000000515BI0100001135 1 Nos.
25 25 (3.12) Safe carriage of breakers/kiosks etc. including loading/ unloading and stacking in Nigam stores BI01010001010000000000000515BI0100001136
26 26 Within 10 Kms. BI01010001010000000000000515BI0100001137 8 Nos.
27 27 (3.13) Safe carriage of panels including loading/ unloading and stacking in Nigam stores BI01010001010000000000000515BI0100001138
28 28 Within 10 Kms. BI01010001010000000000000515BI0100001139 2 Nos.
29 29 (4.2) Safe loading of power/ distribution transformer. BI01010001010000000000000515BI0100001140
30 30 (A) 33/11 KV power transformer. BI01010001010000000000000515BI0100001141
31 31 5 MVA BI01010001010000000000000515BI0100001142 2 Nos.
32 32 (4.3.1) Safe unloading of power/distribution transformers BI01010001010000000000000515BI0100001143
33 33 (a) 33/11 KV power transformer. BI01010001010000000000000515BI0100001144
34 34 Above 3.15 MVA BI01010001010000000000000515BI0100001145 2 Nos.
35 35 Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base. BI01010001010000000000000515BI0100001146 48 CUM
36 36 Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 nos .disc.& 1set of H/W) on terminal point including fixing of hardware and strips. BI01010001010000000000000515BI0100001147 36 Nos.
37 37 Fixing of 33kv pin insulator with pins. BI01010001010000000000000515BI0100001148 18 Nos.
38 38 (6.16) Assembly. Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories completein all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001149
39 39 (B) G.O. switch . without earthing blade. BI01010001010000000000000515BI0100001150
40 40 33kv G.O.switch BI01010001010000000000000515BI0100001151 5 Set
41 41 11kv G.O.switch BI01010001010000000000000515BI0100001152 12 Set
42 42 (6.19) Installation of lightening arrestors on erected structure /support (set of 3 nos) including connection with earth by wire /strip as required and jumpering etc. The nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates, BI01010001010000000000000515BI0100001153
43 43 (A) Sub-station type BI01010001010000000000000515BI0100001154
44 44 33 KV L.A. each BI01010001010000000000000515BI0100001155 3 Set
45 45 11 KV L.A. each BI01010001010000000000000515BI0100001156 12 Set
46 46 (6.20) Installation testing as per Nigams norm & commissioning of 11/.4 KV distribution transformer on erected supports including fixing of base channels as per requirment jumpering on HV&LV side, crimping of lugs/ clamping earth connections of body and neutral of transformer with wire /strip (as already provided with earthing ) complete in all respect. The PG clamps nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates, BI01010001010000000000000515BI0100001157
47 47 Above 40 KVA & up to 100 KVA BI01010001010000000000000515BI0100001158 1 Nos.
48 48 Three nos. Earthing of each 11/0.4 KV distribution transformer /sub-station with M.S.Rod 20mm dia 3 meter long and driving them into earth by mechanical means at a distance as per approved design & drawing & specification.The work includes flattening of top ends of M.S.rod drilling a hole of 9/16" dia.at flattened top and tightening of M.S.flat 50x6mm/25x3mm/(having 3 hole 2ends and 1mm middle) with nuts and bolts with M.S.rods top end hole.The flat will also be welded with M.S.rod.The end will be connected to equipments as under in sequence. BI01010001010000000000000515BI0100001159 3 Per-Trans
49 49 (8.3) Mesh earthing for 33/11 kv sub-station as per approved map &design usingMS flat 50X6mm/MS road 20mm dia includinglaying of flat/rod at the depth of 0.65 Mtrs.,welding & jointing at joints , structures & equipments etc.asunder: BI01010001010000000000000515BI0100001160
50 50 (8.3.1) Excavation of trench of 0.65Mtrs.depth and 0.5Mtr.width BI01010001010000000000000515BI0100001161
51 51 (b) Hard Soil BI01010001010000000000000515BI0100001162 130 Cum
52 52 Laying of MS flat /MS rod in 0.65Mtr.deep excavated trench and welding of MS flat/rod continuosly with 100 mm overlaping for straight joint including coating of MS flat joints with molten bitumen and covering joint with bitumen impregnated tape to protect from rust. BI01010001010000000000000515BI0100001163 400 Mtr.
53 53 Shaping of MS flat for connecting the equipments with earthmesh .The work includes the welding of MS flat with equipments/structure and also with earth mesh.The work also includes coating of MS flat joint with molten bitumen and covering jointwith bitumen impregnated tape to protect from rust. BI01010001010000000000000515BI0100001164 220 Mtr.
54 54 (8.3.4) Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr.length as per design and requirment to be driven in earth by mechanical means and Providing & .fastening of suitable clampswith the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil: BI01010001010000000000000515BI0100001165
55 55 (a) Where drilling is not required BI01010001010000000000000515BI0100001166 21 Per-Nos.
56 56 Filling of trench with available excavated muck in layers of 20cm (Max.)consolidating each deposited layer by ramming & watering with lead up to 50 Mtr, and lift up to 1.5 Mtr. BI01010001010000000000000515BI0100001167 150 R.Mtr.
57 57 Painting of exposed portion of MS flat/rod with two coats of red-oxide primer and two coats of green enamel paint.including material. BI01010001010000000000000515BI0100001168 220 Mtr.
58 58 Pipe Earthing for Power Transformer at 33 / 11 KV S/S:- Supply & erection of earthing electrode shall consist of G.I. Pipe 100 mm,of 3 Mtr Length. The electrode shall be buried as far as practicable 3 meters below ground level. Wherever possible, earth electrodes shall be located as near the water tap, water drain or near down take pipe. Earth electrodes shall not be installed in proximity to a metal fence. It shall be kept clear of the buildings foundations and in no case it shall be nearer than 2 meters from the outer face of the wall. The electrode shall be surrounded with layer of charcoal dust and salt mixture through out the length. The 100 mm GI pipe shall be provided with holes of 12 mm dia. drilled at 75 mm interval upto 2.5 meters length from bottom. The top of the pipe shall be provided with a G.I. threaded cap for watering the earth through a pipe. A Clamp with Pati of 12" of M.S. Flat of size 50X6 mm shall be fixed (Bolted) on the top edge of the pipe which in turn shall be connected to Neutral / Body of the Power Transformer through M.S. Flat size 50X6 mm. The G.I. cap over the GI pipe shall be housed in a masonry chamber, approximately 300 mm x 300 mm x 300 mm deep. The masonry chamber shall be provided with a RCC inspection cover resting over a RCC frame, embedded in masonry. BI01010001010000000000000515BI0100001169 2 Per Earthing
59 59 (10.1) Erection of steel supports in the excavated pit in alignment after checking then same with plumb line as per approved design and drawing of 33/11KV Sub- station.The support should be grouted and muffed in cement concrete ratio 1:3:6 as per chapter -5 No.5.7.The remaining portion of the pit will be back filled with soil.The charges for grouting & muffing will be paid by extra as per chapter no 5.7 The nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Store issue rates. BI01010001010000000000000515BI0100001170
60 60 Fabricated structure AB type BI01010001010000000000000515BI0100001171 20.03 M.T.
61 61 Isolator / C.T.structure BI01010001010000000000000515BI0100001172 10.752 M.T.
62 62 (10.3) Laying / stringing of bus bar with ACSR Dog & jumper connection using tie rod ,33KV /11KV insulator strings,required hardware,P.G.clamps/T clamps etc.as per requirement including Y-connections at bus bar jumpering point as per the direction of engineer in-charge. BI01010001010000000000000515BI0100001173
63 63 ACSR PANTHER BI01010001010000000000000515BI0100001174 600 Mtrs.
64 64 (11.1) Erection of OCB/Kiosk/VCB complete with accessories including use of special tools & conducting all pre-commissioning test before energization,filling oil etc. complete in all respect with erection & grouting of structure (excluding civil works). The relays will be tested by Discom. BI01010001010000000000000515BI0100001175
65 65 33 KV VCB/SF-6 Breaker BI01010001010000000000000515BI0100001176 2 Nos.
66 66 11 KV VCB (Outdoor ) BI01010001010000000000000515BI0100001177 6 Nos.
67 67 (11.2) Installation of control panel including checking of wiring and conducting all pre-commissioning tests before energization, satisfactory operation of all equipment existing thereof. ( The relay will be tested by Discom ). BI01010001010000000000000515BI0100001178
68 68 33 KV Control Panel BI01010001010000000000000515BI0100001179 2 Nos.
69 69 (11.3) Installation of current/potential transformers on supporting structure including checking of wiring & conducting all pre-commissioning tests before energization & satisfactory operation in all respect (The CT/PT set will be tested by Discom). BI01010001010000000000000515BI0100001180
70 70 33 KV CT(1 set of 3 Nos. ) OR PT Set BI01010001010000000000000515BI0100001181 3 Set
71 71 (11.4) Erection & commissioning of battery set and battery charger including all required connection/wiring from battery set to battery charger and A.C.mains complete in all respect. BI01010001010000000000000515BI0100001182
72 72 110 Volts D.C. BI01010001010000000000000515BI0100001183 1 Set
73 73 (11.5) Laying, testing termination of control cable 1100 volts PVC insulated including supply and installation of ferrules to designate various cores of control cables by terminal Nos. of identification including utilization of cable gland. The control cable should be clearly arranged in trenches avoiding crossings including clamping of control cable at regular interval and providing identify tags. BI01010001010000000000000515BI0100001184
74 74 4x2.5 Sq.mm. BI01010001010000000000000515BI0100001185 100 Mtr.
75 75 12x2.5 Sq.mm. BI01010001010000000000000515BI0100001186 150 Mtr.
76 76 (12.1) Painting with priming coats or ready mixed red-oxide paint 2 coats of approved make on steel works after cleaning with wire brush / sand paper.(including cost of red oxide) BI01010001010000000000000515BI0100001187
77 77 On new surface BI01010001010000000000000515BI0100001188 1000 Sq. mtr.
78 78 (12.2) Painting with aluminium paint of approved brand and manufacturer to give an even surface.(including cost aluminium paint) BI01010001010000000000000515BI0100001189
79 79 On new works with two coats. BI01010001010000000000000515BI0100001190 1000 Sq. mtr.
80 80 (14.2) Fabrication of steel structures of M.S angle ,M.S.channel & M.S.Flat including cutting ,drilling and continunous welding joint as per design and drawing.\n BI01010001010000000000000515BI0100001191
81 81 Other steel items BI01010001010000000000000515BI0100001192 0.0283 M.T.
82 82 PART - (B): Erection of 0.155 Km S/C 33 KV line with ACSR Panther Conductor T-off from Tagore Nagar feeder to 33/11 KV GSS Bangur College and S/C 33 KV line with ACSR Panther Conductor T-off from Bangur feeder to 33/11 KV GSS Bangur College BI01010001010000000000000515BI0100001193
83 83 Conducting route survey as per approved route map and pegging of route with tee off point section point & double pole locations. BI01010001010000000000000515BI0100001194 0.155 Km
84 84 Trimming of tree branches/plants manually/ by machine and preparing route approchases for proposed line/line maintenance work of existing HT/LT lines. BI01010001010000000000000515BI0100001195 10 Per tree/ plant
85 85 (2.2) Excavation of pit in Hard Soil BI01010001010000000000000515BI0100001196
86 86 (B) Lattice Tower /Size of pit BI01010001010000000000000515BI0100001197
87 87 11.4/10.8 Mtr/ 1.5mx1.5m x1.80 m deep BI01010001010000000000000515BI0100001198 1 Pit
88 88 12.8/12.6 Mtr/ 1.5mx1.5m x2.10 m deep BI01010001010000000000000515BI0100001199 2 Pit
89 89 (C)Stay set/Depth of pit BI01010001010000000000000515BI0100001200
90 90 8'x 3/4" -0.75x0.5x1.6 m BI01010001010000000000000515BI0100001201 6 Pit
91 91 (3.2) Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site BI01010001010000000000000515BI0100001202
92 92 Within 10 Kms. BI01010001010000000000000515BI0100001203 0.66 M.T.
93 93 (3.3) Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. BI01010001010000000000000515BI0100001204
94 94 Within 10 Kms. BI01010001010000000000000515BI0100001205 0.58 M.T.
95 95 (3.4) Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. including loading/unloading and stacking in the Nigam. Stores / at work site. BI01010001010000000000000515BI0100001206
96 96 Within 10 Kms. BI01010001010000000000000515BI0100001207 1.61 M.T.
97 97 (5.1) Erection of all type of steel supports in the excavated pit in alignment after checking the same with plumb line including fixing of cross arms and top hamper before erecting the supports. The support should be grouted and muffed in cement concrete of ratio 1:3:6 as per item No. 5.7 the remaining portion of the pit will be back filled with soil. The nuts & bolts will be provided by the contractor as per Nigam's specification for which payment will be made at the prevailing store issue rates. BI01010001010000000000000515BI0100001208
98 98 Lattice Structure BI01010001010000000000000515BI0100001209 1.61 M.T.
99 99 (5.4) Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire BI01010001010000000000000515BI0100001210
100 100 8"x3/4" with 7/8 SWG stay wire BI01010001010000000000000515BI0100001211 6 Nos.
101 101 (5.6) Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base. BI01010001010000000000000515BI0100001212 9.504 CUM
102 102 Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 nos .disc.& 1set of H/W) on terminal point including fixing of hardware and strips. BI01010001010000000000000515BI0100001213 24 Nos.
103 103 Fixing of 33kv pin insulator with pins. BI01010001010000000000000515BI0100001214 18 Nos.
104 104 (7.1) Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate. BI01010001010000000000000515BI0100001215
105 105 (A) IN URBAN AREA BI01010001010000000000000515BI0100001216
106 106 ACSR PANTHAR BI01010001010000000000000515BI0100001217 0.465 Km/cond
107 107 (7.3) Laying , jointing,stringing,tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc.including proper binding at each end.The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001218
108 108 (A) IN URBAN AREA BI01010001010000000000000515BI0100001219
109 109 G.I.Earth wire 6 SWG BI01010001010000000000000515BI0100001220 0.155 km/wire
110 110 (12.1) Painting with priming coats or ready mixed red-oxide paint 2 coats of approved make on steel works after cleaning with wire brush / sand paper.(including cost of red oxide) BI01010001010000000000000515BI0100001221
111 111 On new surface BI01010001010000000000000515BI0100001222 88.15 Sq. mtr.
112 112 (12.2) Painting with aluminium paint of approved brand and manufacturer to give an even surface.(including cost aluminium paint) BI01010001010000000000000515BI0100001223
113 113 On new works with two coats. BI01010001010000000000000515BI0100001224 88.15 Sq. mtr.
114 114 PART - (C): Erection of 11KV inter connection of 11KV feeder for 33/11KV S/S Bangur College (2.35 Km) BI01010001010000000000000515BI0100001225
115 115 Conducting route survey as per approved route map and pegging of route with tee off point section point & double pole locations. BI01010001010000000000000515BI0100001226 2.35 Km
116 116 Trimming of tree branches/plants manually/ by machine and preparing route approchases for proposed line/line maintenance work of existing HT/LT lines. BI01010001010000000000000515BI0100001227 70 Per tree/ plant
117 117 (2.2) Excavation of pit in Hard Soil BI01010001010000000000000515BI0100001228
118 118 (A) Height of poles/R.S.Joist/M.S. Rail /Size of pit BI01010001010000000000000515BI0100001229
119 119 9 Mtr/ 1.2mx0.6mx1.50 m deep BI01010001010000000000000515BI0100001230 44 Pit
120 120 (C) Stay set/Depth of pit BI01010001010000000000000515BI0100001231
121 121 6'x 5/8" -0.75x0.5x1.35 m BI01010001010000000000000515BI0100001232 10 Pit
122 122 (3.1) Safe carriage of PCC poles including loading / un-loading BI01010001010000000000000515BI0100001233
123 123 a) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole BI01010001010000000000000515BI0100001234
124 124 Within 10 Kms. BI01010001010000000000000515BI0100001235 44 Pole
125 125 (3.2) Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site BI01010001010000000000000515BI0100001236
126 126 Within 10 Kms. BI01010001010000000000000515BI0100001237 3.43 M.T.
127 127 (3.3) Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. BI01010001010000000000000515BI0100001238
128 128 Within 10 Kms. BI01010001010000000000000515BI0100001239 3.6 M.T.
129 129 (3.4) Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. including loading/unloading and stacking in the Nigam. Stores / at work site. BI01010001010000000000000515BI0100001240
130 130 Within 10 Kms. BI01010001010000000000000515BI0100001241 0.14 M.T.
131 131 (5.2) Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the payment will be made at the prevailing Discom store issue rates. BI01010001010000000000000515BI0100001242
132 132 (B) Urban Area BI01010001010000000000000515BI0100001243
133 133 PCC Poles 9 Mtr. Long(400Kg.) BI01010001010000000000000515BI0100001244 38 Nos.
134 134 (5.3) Erection &assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line.Including fixing of complete steel structure for line D.P.The support is to be back filled with soil with proper ramming.The nuts &bolts are to be provided by the contractor as per Nigams specfication for which the payment will be made at the prevailing Discom store issue rates. BI01010001010000000000000515BI0100001245
135 135 PCC Poles 9 Mtr. Long(400 Kg.)/11Mtr.long BI01010001010000000000000515BI0100001246 3 Nos.
136 136 (5.4) Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire BI01010001010000000000000515BI0100001247
137 137 6"x5/8" with 7/10 SWG stay wire BI01010001010000000000000515BI0100001248 10 Nos.
138 138 (6.1) Fixing of cross arms with clamp on erected support as per design. The nuts &bolts will be supplied by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001249
139 139 11 KV cross arms BI01010001010000000000000515BI0100001250 32 Nos.
140 140 (6.2) Fixing of top hampers with clamp on erected support as per design. The nuts &bolts will be supplied by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001251
141 141 11 KV Top Hampers BI01010001010000000000000515BI0100001252 32 Nos.
142 142 (6.8) Fixing and assembly of disc.point channel pair with pilot plates top hampers & clamps on erected single pole structure as per design. The nuts &bolts are to be provided by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates, BI01010001010000000000000515BI0100001253
143 143 11 KV line BI01010001010000000000000515BI0100001254 2 Nos.
144 144 Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 2 nos.disc.& 1set of H/ W ) on terminal point including fixing of hardware and strips. BI01010001010000000000000515BI0100001255 36 Nos.
145 145 Fixing of 11 KV pin insulator with pins. BI01010001010000000000000515BI0100001256 112 Nos.
146 146 (6.16) Assembly. Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories completein all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001257
147 147 (B) G.O. switch . without earthing blade. BI01010001010000000000000515BI0100001258
148 148 11kv G.O.switch BI01010001010000000000000515BI0100001259 3 Set
149 149 (7.1) Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate. BI01010001010000000000000515BI0100001260
150 150 (A) IN URBAN AREA BI01010001010000000000000515BI0100001261
151 151 ACSR DOG BI01010001010000000000000515BI0100001262 6.6 Km/cond
152 152 Earthing of line for all type of supports as per REC construction standards using Stay wire/GI wire with one pcs.of M.S.rod 20mm dia each 3 meter long and driving into earth by mechanical means as per approved design.Drawing &specification.All material except MS rod,MS flat & stay wirewill be supplied by the contractor.If material is supplied by the contractor ,the payment will be made as per prevailing Discom store issue rates.(In case of PCC poles earthing must be connected with earthwire already available on PCC pole at bottom) BI01010001010000000000000515BI0100001263 6 Nos.
153 153 (11.11) Providing and fixing of G.I. Pipe B-Class (IS:1239 marks) at the starting and finishing point of 33 & 11 KV under ground cables and to lay & clamp vertically with the existing support including labour charges. BI01010001010000000000000515BI0100001264
154 154 Providing and fixing of G.I. Pipe of 125 mm diameter. B-Class (IS:1239 mark),at the starting and finishing point of 11 KV under ground cables and to lay & clamp vertically with the existing support including labour charges. BI01010001010000000000000515BI0100001265 48 Mtr.
155 155 (20.2) Laying of two (D/C) 11 KV, XLPE, Cable (Al. conductor) underground cable w/o overlapping as per relevant IS/JdVVNL standards including excavation of 50 cm width x120 cm deep trench in Kaccha land, 25 cm thick under layer of sand. 'A' class bricks or concrete block covering refilling soil in the remaining portion and providing/fixing cable route indicators at every 30Mtr.of cable and at every turn. BI01010001010000000000000515BI0100001266
156 156 a) 3x35 Sq mm to 3x185 Sq mm BI01010001010000000000000515BI0100001267 236 Mtr.
157 157 (20.3) Installation of cable termination / straight through joints on 11KV Aluminium conductor XLPE Cable with outdoor/ indoor termination end and /or straight through joint including required excavation / remoral/ fixing / refixing/ testing etc. as required BI01010001010000000000000515BI0100001268
158 158 Outdoor end terminal 3x35 Sq mm to 3x185 Sq mm BI01010001010000000000000515BI0100001269 16 Nos.
159 159 (20.14) For Extra Loop (Ghera) to be provided near the pole on termination point and the length of cable along the pole for mounting of cable jointing kit. BI01010001010000000000000515BI0100001270
160 160 A) For 11 KV:- BI01010001010000000000000515BI0100001271
161 161 3X35 Sq.mm to 3X185 Sq.mm BI01010001010000000000000515BI0100001272 80 Mtr.
162 162 Note-1.Dismentaling, if any: Dismentaling charges for all the items will be 60% of item rates of erection charges. However, charges for transportation of the material from works site in the Nigam/sub division store shall be paid as item rate of that material(Chapter-III, Transportation of material). The payment will be made after issuance of certificate by Engineer In Charge that all the dismentaled material has been safely received in the Nigam/sub division store Note-2. The nut & bolts will be provided/supplied by the contractor which will confirm to relevant ISS & payment will be made as per prevailing Discom store issue rate. Note-3. The quality of material supplied by the contractor be got checked & approved by the circle SE. Note-4. In case of pole upper end of the GI wire provided for earthing shall be bolted with cross arm. Note-5. The qty mentioned for normal soil/ordinary rock. Hard soil which does not required drilling and Hard Rock/ CC road which required drilling are tentative & shall be payble as per actual site condition and due verification by Engineer In Charge. Note-6. Safe Carriage of PCC poles/other material including Loading/un-loading as per actual distance of work-site from place of lifting & shall be payble as per actual distance and due verification by Engineer In Charge. Note-7. Unit rates are exclusive of GST and shall be paid extra if applicable. Note-8. The work should be carried out as per specification and standard measurement of Jodhpur Discom BI01010001010000000000000515BI0100001273