Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 09-02-2021 | Revised Annexure-I | Technical Bid | 10-02-2021 |
| 2 | 07-02-2021 | Corrigendum Cum Extension | Technical Bid | 10-02-2021 |
| 3 | 04-02-2021 | Corrigendum | Technical Bid | 08-02-2021 |
| 4 | 22-01-2021 | Notice | BOQ | 08-02-2021 |
| 5 | 18-01-2021 | Drawing-07 | Other | 08-02-2021 |
| Name of Work: Construction of New Medical College Centering MMCH and Kalapahar Campus along with 800 Bedded General Hospital at MMCH Campus in Guwahati. | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | CIVIL WORK\nSurface dressing of ground including removing vegetation and/ or undulation of ground not exceeding 150mm deep and disposal of rubbish outside the periphery and lift up to 1800mm in all kinds of soil. | item1 | 64742 | SQM. |
| 2 | 2 | Earthwork in excavation for foundation trenches of walls, retaining walls, footings of column, steps, septic tank etc. including refilling (return filling) the quantity as necessary after completion of work, breaking clods in return filling, dressing, watering and ramming etc. and removal of surplus earth with all lead and lifts as directed and specified in the following classification of soils including bailing out water where necessary as directed and specified.\nUp to a depth of 2.00 M below the existing ground level.\nIn ordinary soil | item2 | 198717 | CUM. |
| 3 | 3 | Extra over item above for each subsequent 1 m depth or part thereof beyond the initial depth of 2m | item3 | 1.17904e+06 | CUM. |
| 4 | 4 | Shuttering and shoring the earth at different levels in foundations where necessary with required prop, struts, planks, timbers, nails etc. including dewatering if necessary, complete as directed and specified (measurement to be taken in the face area timbered)\n(a) Upto a depth of 1.5m | item4 | 32235 | CUM. |
| 5 | 5 | Extra over item above for each subsequent 1.5 m depth beyond the initial depth of 1.5m | item5 | 193410 | CUM. |
| 6 | 6 | Earth/ sand filling in plinth in layers not more than 150mm thick including necessary carriage, watering, ramming etc. complete as directed and specified including payment of land compensation, forest royalty, sales tax and other duties and taxes as may be necessary.\n(c) With river sand or silt (predominantly non plastic) by truck carriage including loading and unloading. | item6 | 10313 | CUM. |
| 7 | 7 | Extra cost for lifting of sand for filling of sunk floor for each subsequent floors above the ground floor as directed and specified. | item7 | 247 | CUM. |
| 8 | 8 | Pre construction anti - termite treatment in the back fill in immediate contact with the foundation structure after completion, column, wall etc. to a depth of 450mm and width 300mm (when required refill in 200mm thick layers) applying the emulsion @ 5 (five) litres per square meter towards the concrete and masonry walls so as to ensure earth in contact with the structure well treated - with chemical (supplying of necessary tools and accessories by the contractor) as per the direction of the Department complete.\na) with aqueous emulsion having concentration 1:19 with chloropirophose solution (tricel or euivalent) and water, i.e. 1% solution. | item8 | 25390 | SQM. |
| 9 | 9 | Pre construction anti - termite treatment by applying in the entire levelled area after plinth filling and before laying floor by applying the emulsion @ 5 (five) litres per square meter of the surface to be spread with light rodding so as to ensure proper absorption by the filled up earth (supplying of necessary tools and accessories by the contractor) as per the direction of the Department complete. a) with aqueous emulsion having concentration 1:19 with chloropirophose solution (tricel or euivalent) and water, i.e. 1% solution.\na) with aqueous emulsion having concentration 1:19 with chloropirophose solution (tricel or euivalent) and water, i.e. 1% solution. | item9 | 24256 | SQM. |
| 10 | 10 | Pre construction anti - termite treatment by applying in the junction of walls, column with the floor before laying floor and after operation of item no. 26.1.3 above making a channel 30mmx30mm all over the walls and making rod holes @ 150mm apart up to ground level below and applying emulsion @ 11 litres per square meter of vertical plinth wall surface inside the building so as to soak the soil with the emulsion up to the ground level and refill the holes and channel with the original materials obtained in making channels (supplying of necessary tools and accessories by the contractor) as per the direction of the Department complete.\na) with aqueous emulsion having concentration 1:19 with chloropirophose solution (tricel or euivalent) and water, i.e. 1% solution. | item10 | 4668 | SQM. |
| 11 | 11 | Pre construction anti - termite treatment by applying the soil along the external perimeter of the building (after construction completed) to a distance close to the plinth wall as specified and as directed by the deptt. up to a depth of 300mm making rod holes along the line @ 150mm apart to a depth of 300mm and applying emulsion @ 4.5 litres per running meter ensure moistening of the soil with emulsion (supplying of necessary tools and accessories by the contractor) as per the direction of the Department complete.\na) with aqueous emulsion having concentration 1:19 with chloropirophose solution (tricel or euivalent) and water, i.e. 1% solution. | item11 | 4417 | SQM. |
| 12 | 12 | Raising low site around the building with approved soil obtained from outside by truck carriage including breaking clods, dressing etc. complete including paying necessary forest royelty, sales tax, land compensation, municipal gate fees, if any monopoly duty etc. (profile measurement to be taken and 12.5% deduction for shrinkage to be made from total quantity) etc. complete as directed and specified.\n(a) Within Guwahati city only | item12 | 129694 | CUM. |
| 13 | 13 | Extra lead per km truck carriage for sand gravel beyond the initial lead of 8 km. | item13 | 129694 | CUM. |
| 14 | 14 | Plain cement concrete works with coarse aggregate of sizes 13 mm to 32 mm in foundation bed for footing steps, walls, brick works etc. as directed and specified including dewatering if necessary, curing complete (Shuttering where necessary shall be measured and paid saperately).\nIn prop 1 cement :4 Sand :8 coarse aggreget by volume | item14 | 6770 | CUM. |
| 15 | 15 | Plain cement concrete works with coarse aggregate of sizes 13 mm to 32 mm in foundation bed for footing steps, walls, brick works etc. as directed and specified including dewatering if necessary, curing complete (Shuttering where necessary shall be measured and paid saperately).\nIn prop 1 cement :3 Sand :6 coarse aggregete by volume | item15 | 4050 | CUM. |
| 16 | 16 | Plain cement concrete works with coarse aggregate of sizes 13 mm to 32 mm in foundation bed for footing steps, walls, brick works etc. as directed and specified including dewatering if necessary, curing complete (Shuttering where necessary shall be measured and paid saperately).\nIn prop 1 cement :5 Sand :10 coarse aggregete by volume | item16 | 1560 | CUM. |
| 17 | 17 | Plain cement concrete floor base in prop 1:3:6 laid in alternate bays as specified with coarse agg. of size 13 mm to 32 mm including dewatering if necessary, and curing etc. complete.\n100 mm thick | item17 | 9058 | SQM. |
| 18 | 18 | Providing plinth protection 50mm thick to cement concrete 1 : 3 : 6 with coarse agg.of 20mm nominal size including finishing the surface with 10mm thick cement plaster in proportion 1:3 with a floating coat of neat cement finished. | item18 | 3658 | SQM. |
| 19 | 19 | Supplying, fitting and fixing in position reinforcement bars conforming to relevent IS code, for reinforced cement concrete works in piles including straightening, cleaning, cutting and bending to proper shapes and length as per specifications and drawings. The rings should be welded with vertical reinforcements as per specified IS codes of practice. (Inclusive of lap length, hook, chair, bend, anchor...etc)\nTMT bar made of Primary producer (From Primary producer) | item19 | 17300 | Qtl |
| 20 | 20 | Providing cast in-situ machine driven reinforced cement concrete piles of required bore-diameter, bulb diameter, lengths and with reinforcement as per specifications and drawings including using of Admixture/ Bentonite solution. (Reinforcement to be measured and paid seperately)\nUNIFORM PILE,\nConcrete Grade M25\nPile dia 500 mm | item20 | 31353 | R.m |
| 21 | 21 | Providing cast in-situ machine driven reinforced cement concrete piles of required bore-diameter, bulb diameter, lengths and with reinforcement as per specifications and drawings including using of Admixture/ Bentonite solution. (Reinforcement to be measured and paid seperately)\nUNIFORM PILE,\nConcrete Grade M25\nPile dia 600 mm | item21 | 83975 | R.m |
| 22 | 22 | Empty boring for specified diameter piles from ground level to cut-off level. f) Pile Dia. 500 mm | item22 | 1308 | R.m |
| 23 | 23 | Empty boring for specified diameter piles from ground level to cut-off level. h) Pile Dia. 600 mm | item23 | 9527 | R.m |
| 24 | 24 | Routine test for test loading to 1.5 times the specified safe working load including construction of any test pile cap and dismantling the same after completion of test safe load capacity from 21 tonnes to 25 tonnes | item24 | 213 | Ton |
| 25 | 25 | Initial test for test loading to 2.5 times the specified safe working load including construction of any test pile cap and dismantling the same after completion of test.Safe load capacity from 21 tonnes to 25 tonnes | item25 | 502 | Ton |
| 26 | 26 | Demolishing RCC / PCC pile head of different diameters carefully without disturbing the remaining portion of the pile including opening out of the pile head to be demolished by excavating the earth upto required depth and clearing the debris as directed. | item26 | 1334 | CUM. |
| 27 | 27 | Providing form work of ordinary timber planking so as to give rough finish including centering , shuttering, strutting and propping etc. height of propping and centering below supporting floor to ceiling not exceeding 4.0m & removal of the same for in-situ reinforced concrete and plain concrete work in:\nFoundations, footings, bases of columns, pile cap, raft and mass concrete work etc.\nUsing 25 mm thick plank | item27 | 22371 | SQM. |
| 28 | 28 | Vertical surfaces such as walls (any thickness), parapet walls, partition, walls of septic tank, inspection pit and the like including attached pilasters, butresses, plinth and string courses.\nUsing 25 mm thick plank | item28 | 56935 | SQM. |
| 29 | 29 | Extra for each subsequent floor or part thereof above the first floor level as mentioned in item above | item29 | 102159 | SQM. |
| 30 | 30 | Staircase with sloping or stepped or stepped soffits including riser and stringers but excluding landing. Using 38 mm thick plank.\n | item30 | 15543 | SQM. |
| 31 | 31 | Extra for each subsequent floor or part thereof above the first floor level as mentioned in item above | item31 | 70058 | SQM. |
| 32 | 32 | Extra for each subsequent 1.0 M height or part there of beyond the initial height of 4.0 M as mentioned in above item | item32 | 22284 | SQM. |
| 33 | 33 | Providing form work of ordinary timber planking and removal of the same in edge of slab and breaks in floors and walls etc. of in situ reinforced concrete work upto first floor level.\nThickness not exceeding 200 mm - Gr. Floor to Terrace | item33 | 29000 | RM. |
| 34 | 34 | Extra for each subsequent floor or part thereof above the first floor level as mentioned in item above | item34 | 125132 | RM. |
| 35 | 35 | Providing form work of 12mm thick plywood board so as to give a rough finish including centering, shuttering, strutting and propping etc., height of propping and centering below supporting floor to ceiling not exceeding 4.0 M and removal of the same of in situ reinforced concrete and plain concrete work in:\nColumns. Pillars, posts and strut of square / rectangular / polygonal in plan or any shape like Tee / L etc., having plane vertical face | item35 | 75830 | SQM. |
| 36 | 36 | Extra for each subsequent floor or part thereof above the first floor level as mentioned in item above | item36 | 269223 | SQM. |
| 37 | 37 | Providing form work of 12mm thick plywood board so as to give a rough finish including centering, shuttering, strutting and propping etc., height of propping and centering below supporting floor to ceiling not exceeding 4.0 M and removal of the same of in situ reinforced concrete and plain concrete work in:\nSides and soffits of beams, beam haunchings, cantilever girders, bressumers, lintels and horizontal tiles. For depth not exceeding 1.0M | item37 | 85139 | SQM. |
| 38 | 38 | Extra for each subsequent floor or part thereof above the First Floor level as mentioned in above item\n | item38 | 277572 | SQM. |
| 39 | 39 | Providing formwork using 2mm pressed bend shuttering plate of mild sheet and tubular telescopic steel props including centering, shuttering, strutting and propping etc. complete and removal of the same for in situ reinforced concrete and plain concrete work in:\nFlat Surfaces such as soffits of suspended floors, roofs, landings and the like. | item39 | 187284 | SQM. |
| 40 | 40 | Extra for each subsequent floor or part there of as mentioned in above item above the First Floor level\n | item40 | 546917 | SQM. |
| 41 | 41 | Supplying, fitting and fixing in position reinforcement bars confirming to relevant I.S. Code for R.C.C. work/ R.B. walling including straigtening, cleaning, cutting and bending to proper shapes and length as per details, supplying and binding with 20G annealed black, supports, chairs, spacers etc. complete. (No extra measurement for lap, hook, chair, anchor etc. will be entertained in the measurement as they are included in the rate) (Upto 1st floor level.)\nFrom primary Producer: TATA/ SAIL/ Jindal Steel/ Shyam Steel/ RINL\nTMT bars (Fe 500 D) | item41 | 157604 | QTL. |
| 42 | 42 | Extra over item for each subsequent floor or part thereof above first floor level. | item42 | 482575 | QTL. |
| 43 | 43 | Providing and laying plain/reinforced cement croncrete works cement, coarse sand & 20mm down graded stone aggregate including dewatering if necessary, and curing complete but excluding cost of form work and reinforcement for reinforced cement concrete work (form work and reinforcement will be measured and paid separately).\nUsing Batching Plant/ RMC/ Truck mounted batching plant including Transit Mixer and Concerete Pump.\n(A) In substructure up to plinth level Foundation, footing, columns with base tie and plinth beam, pile cap, base slab, retaining walls, walls of septic tank, inspection pit and the like and other works not less than 100mm thick up to plinth level.\nUsing admixture, plasticiser etc for air entraining, water reducing purposes including addition of agent for changing normal setting time of concrete as required.\nC) M25 grade concrete | item43 | 16224 | CUM. |
| 44 | 44 | C) M40 grade concrete | item44 | 15585 | CUM. |
| 45 | 45 | B) M20grade concrete | item45 | 9271 | CUM. |
| 46 | 46 | A) M15 grade concrete | item46 | 6953 | CUM. |
| 47 | 47 | Providing and laying plain/reinforced cement croncrete works cement, coarse sand & 20mm down graded stone aggregate including dewatering if necessary, and curing complete but excluding cost of form work and reinforcement for reinforced cement concrete work (form work and reinforcement will be measured and paid separately).\nUsing Batching Plant/ RMC/ Truck mounted batching plant including Transit Mixer and Concerete Pump.\n(B) In super structure from plinth level up to 1st floor level.\nii) Columns, pillars, posts, struts, suspended floor, roof, landing, shelf and support, balcony, lintel, sill band, beam, girder, bressumer, cantilever, staircase (except spiral staircase and landing ) including preparing the top surface and finishing of nosing.\nUsing admixture, plasticiser etc for air entraining, water reducing purposes including addition of agent for changing normal setting time of concrete as required.\nc) M25 grade concrete | item47 | 17590 | CUM. |
| 48 | 48 | C) M40 grade concrete | item48 | 15393 | CUM. |
| 49 | 49 | B) M20grade concrete | item49 | 16493 | CUM. |
| 50 | 50 | A) M15 grade concrete | item50 | 5498 | CUM. |
| 51 | 51 | Extra over item above for each subsquent floor or part thereof above 1st floor level. | item51 | 204543 | CUM. |
| 52 | 52 | Brick work in cement morter with 1st class brick including racking out joints and curing complete as directed.\nIn Sub-structure upto plinth level including dewatering if necessary\nIn proportion 1:6 | item52 | 2900 | CUM. |
| 53 | 53 | Brick work in cement morter with 1st class brick including racking out joints and curing complete as directed.\nIn super structure above plinth level upto 1st floor level\nIn proportion 1:6 (Gr. Floor To Terace Floor) | item53 | 15289 | CUM. |
| 54 | 54 | Extra over item above for brick work in each subsquent floor or part thereof above 1st floor level. | item54 | 88971 | CUM. |
| 55 | 55 | 112 mm thick reiforced brick wall in prop 1:5 reinforced with two lines of M.S. rod/ Tor Steel as specified embeded in 38 mm thick concrete course in prop 1:2:4 with coarse agg. 12 mm down at every fourth courses embeded with protruding rod in column including curing etc. complete as directed (M.S. rod/ Tor steel shall be measured and paid separately) in super structure up to 1st floor level. | item55 | 55210 | SQM. |
| 56 | 56 | Extra for brick walling for each subsquent floor or part thereof above 1st floor level. 112 mm thick brick/ R.B. wall | item56 | 244041 | SQM. |
| 57 | 57 | Light Weight Autoclaved Aerated concrete Block work using Grade-I AAC block of required Size and thickness of compressive strength 40Kg/cm2 having dry density 550 to 650 Kg /Cum conforming to IS-2185 Pt-3 or pt-4 in cement mortar of prop 1:4 / adhesive of approved manufacturer including racking out joints and curing complete as specified & directed. (protruding rod is to be provided at every 3 course interval and will be measured and paid separately)\n(II) In superstructure above plinth level up to 1st floor level.\n(a) For 225mm thick wall | item57 | 109736 | SQM. |
| 58 | 58 | Extra for AAC block walling for each subsequent floor or part thereof above the 1st floor level to Roof\n(i) 225mm thick wall | item58 | 185142 | SQM. |
| 59 | 59 | Light Weight Autoclaved Aerated concrete Block work using Grade-I AAC block of required Size and thickness of compressive strength 40Kg/cm2 having dry density 550 to 650 Kg /Cum conforming to IS-2185 Pt-3 or pt-4 in cement mortar of prop 1:4 / adhesive of approved manufacturer including racking out joints and curing complete as specified & directed. (protruding rod is to be provided at every 3 course interval and will be measured and paid separately)\nFor 125mm thick wall\nIn superstructure above plinth level up to 1st floor level. | item59 | 14444 | SQM. |
| 60 | 60 | Extra for AAC block walling for each subsequent floor or part thereof above the 1st floor level to Roof\n(i) 125mm thick wall | item60 | 14706 | SQM. |
| 61 | 61 | Stone masonary work in retaining wall, wing wall, abutment, foundation, steps, plinth etc. in cement mortar in prop 1:6 with levelling course of 1:6:12 with both faces hammer dressed including bonding, providing face stone, through stone and centering including racking of joints, curing and supplying and all carriage of stone as directed including payment of forest royalty and sales tax and carriage.\n(a) Random Rubble Masonry | item61 | 121 | CUM. |
| 62 | 62 | Providing and fixing flush door shutters solid core construction with frame of 1st class hard wood with cross band and face veneered ply wood face panels conforming to relevent I.S code including oxidised iron butt hinges (100mm x 75mm x 3.5mm) 6 nos with necessary wood screws.\nNon decorative type and block board core.\n(ii) 35 mm thick . | item62 | 4117 | SQM |
| 63 | 63 | Providing, fitting and fixing factory made Flush door shutters having core & cross bands fabricated from seasoned 1st class timber, 25mm core battens, 2.5mm to 3.5mm uniformly thick cross bands, styles & rails made from hardwood timber of width not less than 50mm, fixed to the door frames (chowkath) with necessary hinges, screws, bolts etc. as specified and directed at all levels (Door fixtures and fittings to be measured and paid seperately.)\n(b) 35mm thick | item63 | 9239 | SQM |
| 64 | 64 | Extra for providing lapping with 1st class Teak wood battens of 25mm minimum depth on all edges of the shutters. | item64 | 13106 | SQM |
| 65 | 65 | Providing, fitting and fixing Wire gauge shutters using galvd. M.S. wire of I.S designation 85G with wire of dia 0.56mm for doors, windows and clerestory windows including oxidised M.S butt hinges (100mm x 58mm x1.90mm)\n(ii) 35 mm thick . | item65 | 1736 | SQM |
| 66 | 66 | Supplying, fitting, fixing Stainless Steel fittings of approved make, resonably smooth, free from sharp edges and corners, flaws and other defects and with counter sunk holes for screws including necessary c.p. brass screws etc. complete.( bright natural matt & satin finished )\nb) Tower Bolt\nii) 250mm x 10mm | item66 | 4608 | EACH |
| 67 | 67 | Supplying, fitting, fixing Stainless Steel fittings of approved make, resonably smooth, free from sharp edges and corners, flaws and other defects and with counter sunk holes for screws including necessary c.p. brass screws etc. complete.( bright natural matt & satin finished )\nb) Tower Bolt\nii) 150mm x 10mm | item67 | 2249 | EACH |
| 68 | 68 | Supplying, fitting, fixing anodised aluminium fittings of approved make, resonably smooth, free from sharp edges and corners, flaws and other defects and with counter sunk holes for screws including necessary aluminium screws etc. complete.( anodised to bright natural matt & satin finished )\nr) Curtain rod\ni) 20mm x 2mm | item68 | 5516 | RM |
| 69 | 69 | Providing and fixing 12 mm thick and 150mm wide pelmet with 25 mm dia wooden curtain rod and bracket including fixing with 15mmx3mm M.S flat 100mm long plugs complete.\n(a) First class Indian Teak wood/ Sisu wood | item69 | 844 | R.M. |
| 70 | 70 | Supplying, fitting, fixing anodised aluminium fittings of approved make, resonably smooth, free from sharp edges and corners, flaws and other defects and with counter sunk holes for screws including necessary aluminium screws etc. complete.( anodised to bright natural matt & satin finished )\nc) Door handles\niii) 150mm | item70 | 10317 | EACH |
| 71 | 71 | Supplying, fitting, fixing anodised aluminium fittings of approved make, resonably smooth, free from sharp edges and corners, flaws and other defects and with counter sunk holes for screws including necessary aluminium screws etc. complete.( anodised to bright natural matt & satin finished )\nm) Mortice lock vertical type\nii) 75mm(Godrej with handle(4 lever) | item71 | 4530 | EACH |
| 72 | 72 | Supplying, fitting, fixing anodised aluminium fittings of approved make, resonably smooth, free from sharp edges and corners, flaws and other defects and with counter sunk holes for screws including necessary aluminium screws etc. complete.( anodised to bright natural matt & satin finished )\nt) Door stopper with rubber stopper) | item72 | 4532 | EACH |
| 73 | 73 | Supplying, fitting, fixing anodised aluminium fittings of approved make, resonably smooth, free from sharp edges and corners, flaws and other defects and with counter sunk holes for screws including necessary aluminium screws etc. complete.( anodised to bright natural matt & satin finished )\nl) Hydraulic door closure | item73 | 2112 | EACH |
| 74 | 74 | Supplying, fitting, fixing anodised aluminium fittings of approved make, resonably smooth, free from sharp edges and corners, flaws and other defects and with counter sunk holes for screws including necessary aluminium screws etc. complete.( anodised to bright natural matt & satin finished ) -\nq) Kicking plate | item74 | 9648 | EACH |
| 75 | 75 | Supplying and installing uPVC- Sliding Windows made out of Lead free green profile having \"GREENLINE\" mark of BIS standard uPVC multichambered sections of wall thickness 2.4mm with corners fusion welded, fully reinforced with Galvanized steel 1.5/2mm including interlock profile, glazing bead, grooving bead, brush seal, aluminum sliding track, stainless steel rollers, sealing wedge block, Espag, int handle, pop up handle, keeper, drain cap, fisher screws, packing pieces with all necessary stainlessness screws etc. complete as directed. The windows must be installed complete with all kinds of ironmongery including EPDM gaskets, bridging wedges and glass packers and with suitable water draining system. Application of silicon sealant from inside / outside of Dowcorning / GE or equivalent.\nWith 5mm clear glass\n(a) 2 Track Sliding Window with Flyscreen using uPVC section of sizes 88mm x 50 mm x 2.4mm thick wall for frame with inbuilt flyscreen track, 37mm x 61mm x 2.4mm thick wall for glass sash, 25mm x 49mm x 2.4mm thick wall for flyscreen sash having 1.5mm thick reinforcement, Interlock: 43mm x 23mm (Glass Panel)\n(WINSTA KOMMERLING/ FINESTA/ ENCRAFT)\n(i) 2-Panel with 5mm clear float glass | item75 | 1284 | SQM. |
| 76 | 76 | Providing and fixing stainless steel (Grade 304) railing made of hallow tubes, chanells, plates etc. including welding grinding buffing, polising and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i.e. fixing railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts etc. of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer in charge.(for payment purpose only weight of stainless steel members shall be considered excluding fixing assessories such as nuts, bolts, fasteners etc.) | item76 | 87858 | KG |
| 77 | 77 | Providing, fitting and fixing M.S. grill of required pattern for windows/ clerestory windows/ openingwith M.S. flats at required spacing in frame all round, squre or round M.S. bars with round headed bolts and nuts or screws.\nI . Plain grill ( Fixed to wooden frames) | item77 | 140166 | KG |
| 78 | 78 | Providing and fixing in position collapsible M.S. shutters with vertical channels 20mmx10mmx2mm braced with flat iron diagonals 20mmx5mm size with top and bottom rails of T-iron 40mmx40mmx6mm with 38mm dia steel pulleys complete with bolts and nuts, locking arrangements, stoppers, handles including applying a priming coat of red lead paint. | item78 | 38 | SQM |
| 79 | 79 | Providing, fitting and fixing powder coated pressed steel door frame made of 1.25mm/ 1.6mm thick sheet of various sizes with necessary hinge jamb, lock jamb, head and steel base ties at the bottom of the frame. The whole frame shall be welded or rigidly fixed together by mechanical means with base ties of pressed mild steel angle of size 20x20x1.25mm thick. Frame to be filled up with 1:4:8 P.C.C. after fitting the frame with brick/ concrete works etc.complete as directed by the department for all levels. (P.C.C. to be measured and paid for seperately).\n(a) 1.25mm thick sheet\n(i) Size 90mm x 60mm (Single rebate) | item79 | 12483 | RM |
| 80 | 80 | Providing, fitting and fixing powder coated pressed steel door frame made of 1.25mm/ 1.6mm thick sheet of various sizes with necessary hinge jamb, lock jamb, head and steel base ties at the bottom of the frame. The whole frame shall be welded or rigidly fixed together by mechanical means with base ties of pressed mild steel angle of size 20x20x1.25mm thick. Frame to be filled up with 1:4:8 P.C.C. after fitting the frame with brick/ concrete works etc.complete as directed by the department for all levels. (P.C.C. to be measured and paid for seperately).\n(a) 1.25mm thick sheet\n(iv) Size 125mm x 60mm (Double rebate | item80 | 3839 | RM |
| 81 | 81 | 40 mm thick cement concrete floor consisting of 25 mm under layer of cement concrete in prop 1:3:6 (1cement : 3coarse sand : 6 coarse aggregate of 12.5 mm and down) and 15 mm thick wearing layer in cement concrete in prop. 1:1:2 (1cement : 1coarse sand : 2 coarse aggregate of 10 mm and down) finished with a floating coast of neat cement finish using cement slurry for bond @ 2.75 kg. per sqm. of floor area, wearing layer is to be laid in panels including curing complete as directed. | item81 | 6012 | SQM |
| 82 | 82 | Cement plaster skirting with cement mortar in prop. 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement including rounding of junctions with floor.\n(b) 20 mm thick | item82 | 602 | SQM |
| 83 | 83 | Providing Ceramic Floor Tiles of approved quality, size, shape and thickness not less than 8 mm on floors, skirtings, treads and risers of steps over cement mortar bed 15 mm thick in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with fix-A Tile Choksey/ Sika/ Pedelite/ Rouf/ White cement slurry mixed with approved pigment to match the shade of granite slab, complete at all levels as specified and directed (coloured pigment should be in conformity with colour of slab and as approved and directed by the Department).\nDelux range\nSomany/ Orient/Nitco/Qutone Make\nOf size 300mmx300mm and above | item83 | 4350 | SQM |
| 84 | 84 | Providing Ceramic Floor Tiles of approved quality, size, shape and thickness not less than 8 mm on floors, skirtings, treads and risers of steps over cement mortar bed 15 mm thick in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with fix-A Tile Choksey/ Sika/ Pedelite/ Rouf/ White cement slurry mixed with approved pigment to match the shade of granite slab, complete at all levels as specified and directed (coloured pigment should be in conformity with colour of slab and as approved and directed by the Department).\nExecutive range\nSomany/ Orient/Nitco/Asian Make\nOf size 600mmx600mm and above | item84 | 4700 | SQM |
| 85 | 85 | Providing Ceramic Floor Tiles of approved quality, size, shape and thickness not less than 8 mm on floors, skirtings, treads and risers of steps over cement mortar bed 15 mm thick in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with fix-A Tile Choksey/ Sika/ Pedelite/ Rouf/ White cement slurry mixed with approved pigment to match the shade of granite slab, complete at all levels as specified and directed (coloured pigment should be in conformity with colour of slab and as approved and directed by the Department).\nDelux range\nSomany/ Orient/Nitco/Qutone Make\nOf size 600mmx600mm and above | item85 | 1427 | SQM |
| 86 | 86 | Providing polished Ceramic wall Tiles of approved quality, size, shape and thickness not less than 8 mm on walls and skirtings over cement mortar bed 10 mm thick in prop. 1:3 (1 Cement: 3 Coarse sand), including cutting where necessary finished with flush pointing with fix-A Tile (Choksey/ Sika/ Pedelite/ Rouf/ White cement slurry) mixed with approved pigment to match the shade of tiles complete at all levels as specified and directed (coloured pigment should be in conformity with colour of tiles and as approved and directed by the Department). (Wall means both interior and exterior walls).\nDelux Range (Somany/ Orient/ Nitco/ Varmora Make)\nof size 300mm x 450mm and above | item86 | 17513 | SQM. |
| 87 | 87 | Providing VITRIFIED floor tiles of approved quality of specified size, shape and thickness not less than 8mm on floors, skirtings, risers and treads of steps over 15 mm thick base of cement mortar in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with Fix-A-Tile (Choksey/Sika/Pedelite/Rouf) / white cement slurry mixed with approved pigment to match shade of tiles, mixed with approved pigment to match the shade of the tiles, complete at all levels as specified and directed. (Coloured pigment should be in conformity with colour of tiles and as approved and directed by the Department)\nNormal range\nSomany/ Orient/Nitco /Varmora/VITA/ Marbito/ Make\nOf size 600mmx600mm and above | item87 | 62370 | SQM |
| 88 | 88 | Providing VITRIFIED floor tiles of approved quality of specified size, shape and thickness not less than 8mm on floors, skirtings, risers and treads of steps over 15 mm thick base of cement mortar in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with Fix-A-Tile (Choksey/Sika/Pedelite/Rouf) / white cement slurry mixed with approved pigment to match shade of tiles, mixed with approved pigment to match the shade of the tiles, complete at all levels as specified and directed. (Coloured pigment should be in conformity with colour of tiles and as approved and directed by the Department)\nNormal range\nExecutive range (800mmx800mm)\nSomany/Varmora/Nitco/Orient made\nOf size 800mmx800mm and above | item88 | 35297 | SQM |
| 89 | 89 | Providing VITRIFIED floor tiles of approved quality of specified size, shape and thickness not less than 8mm on floors, skirtings, risers and treads of steps over 15 mm thick base of cement mortar in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with Fix-A-Tile (Choksey/Sika/Pedelite/Rouf) / white cement slurry mixed with approved pigment to match shade of tiles, mixed with approved pigment to match the shade of the tiles, complete at all levels as specified and directed. (Coloured pigment should be in conformity with colour of tiles and as approved and directed by the Department)\nc) Delux range\nSomany/ Orient/Nitco /Varmora/VITA/ Marbito/ Make\nOf size 1000mmx1000mm and above | item89 | 10211 | SQM |
| 90 | 90 | Providing Polished vitrified wall tiles of approved quality of specified size, shape and thickness not less than 8mm on walls and skirtings over cement mortar bed 10 mm thick in prop. 1:3 (1 cement : 3 coarse sand) including cutting where necessary finished with flush pointing with Fix-A-Tile (Choksey/ Sika/ Pedelite/ Rouf)/ White cement slurry mixed with approved pigment to match the shade of tiles complete at all levels as specified and directed (coloured pigment should be in conformity with colour of tiles and as approved and directed by the Department).\nOf size 300mm x 600mm and above | item90 | 143010 | SQM. |
| 91 | 91 | Kota stone slab flooring of 18 mm thick over 20 mm thick base of cement mortar 1 : 6 (1 cement : 6 coarse sand) laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete.\n550mm x 550mm | item91 | 15618 | SQM. |
| 92 | 92 | Kota stone slab of 18 mm thick in riser of steps, skirting, dado and pillars laid with 10 mm thick cement plaster 1 : 3 (1 cement : 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete.\n550mm x 550mm | item92 | 1700 | SQM. |
| 93 | 93 | Extra for nosing in steps of red or white, fine dressed and rubbed with sand stone. | item93 | 23575 | R.m |
| 94 | 94 | Providing Polished Granite Slab of approved quality, size, shape and thickness not less than 18 mm on floors, skirtings, treads and risers of steps over cement mortar bed 15 mm thick in prop. 1:3 (1 cement : 3 coarse sand) including cutting where necessary finished with flush pointing with Fix-A-Tile (Choksey/ Sika/ Pedelite/ Rouf)/ White cement slurry mixed with approved pigment to match the shade of granite slab, complete at all levels as specified and directed (Cement plastering to be measured and paid separatly) (coloured pigment should be in conformity with colour of slab and as approved and directed by the Department).\nDelux Quality\nWith Fix-A-Tile (Choksey/ Sika/ Pedelite/ Rouf) | item94 | 11946 | SQM |
| 95 | 95 | Providing polished granite tiles of approved quality, size, shape and thickness not less than 8mm on walls and skirtings over cement mortar bed 15 mm thick in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished with flush pointing with Fix-A-Tile (Choksey / Sika / Pedelite / Rouf) /white cement slurry mixed with approved pigment to match shade of tiles complete at all levels as specified and directed. (Cement plastering to be measured and paid separately). (Coloured pigment should be in conformity with colour of tiles and as approved and directed by the Department). (Walls means both interior and exterior walls).\n(ii) With White cement | item95 | 9580 | SQM |
| 96 | 96 | Providing, fitting and fixing Laminated abrasion resisitant wooden flooring from Uniproducts (India) Ltd. of thickness not less than 8.2 mm laid on existing concrete floor with under layer of approved transparent polythene and foam sheet to make the floor surface even and sound free complete as Per Design and approved by Department.\nUnitex AC4 Brand | item96 | 3575 | SQM |
| 97 | 97 | Providing Antiskid tile of approved quality size, shape and thickness not less than 8mm on floor, skirting over a cement mortor bed of 15 mm thick in prop. 1:3 ( 1 Cement : 3 Coarse Sand) approved make fix with Fix-A-Tile (Choksey/sika/Pedelite/Rouf)/white Cement Complete at all level as specified and directed.\nCeremic - (Somany/ Orient/Nitco /Varmora/VITA/ Marbito/ Make)\nNormal Range (Size 300mm X 300mm and above) | item97 | 1629 | SQM |
| 98 | 98 | Providing Antiskid tile of approved quality size, shape and thickness not less than 8mm on floor, skirting over a cement mortor bed of 15 mm thick in prop. 1:3 ( 1 Cement : 3 Coarse Sand) approved make fix with Fix-A-Tile (Choksey/sika/Pedelite/Rouf)/white Cement Complete at all level as specified and directed.\nVitrified- (Somany/ Orient/Nitco /Varmora/VITA/ Marbito/ Make)\nExecutive Range-2, Imperial Series -Gres Tiles (Size 600mm X 600mm and above) | item98 | 6339 | SQM |
| 99 | 99 | 10 mm cement plaster in single coat on fair side of brick/concrete walls for interior plastering upto 1st floor level including aries or rounded angles not exceeding 80mm grith and finished even and smooth including curing complete as directed.\nIn cement mortar 1:5 (Gr. Floor to Terrace Floor) | item99 | 270813 | SQM. |
| 100 | 100 | Extra over item above for interior plastering above 1st floor level for every additional floor or part there of including curing complete as directed. | item100 | 1.14689e+06 | SQM. |
| 101 | 101 | 15 mm cement plaster in single coat on rough side of single or half brick walls for interior plastering upto 1st floor level including aries or rounded angles not exceeding 80mm grith and finished even and smooth including curing complete as directed.\nIn cement mortar 1:5 (Gr. Floor to Terrace Floor) | item101 | 261534 | SQM. |
| 102 | 102 | Extra over item above for interior plastering above 1st floor level for every additional floor or part there of including curing complete as directed. | item102 | 1.10535e+06 | SQM. |
| 103 | 103 | 20 mm thick Cement plaster in two coats on single or half brick walls for interior plastering up to 1st floor level including arises, internal rounded angles,chamfers and / or rounded angles not exceeding 80mm in girth and finished even and smooth including curing complete as directed.\nOn rough side (backing coat 15 mm and finishing coat 5mm thick)\nd) In cement mortar 1:5 (Gr. Floor to Terrace Floor) | item103 | 98115 | SQM. |
| 104 | 104 | Extra over item above for exterior plastering over wall for every additional floor or part there of beyond 1st floor level including curing complete as directed. | item104 | 384622 | SQM. |
| 105 | 105 | 15 mm thick plain cement mortar bands in cement mortar 1:4 in width including curing complete as directed.\nA) Up to 300 mm width\nFlush band | item105 | 11635 | SQM. |
| 106 | 106 | 15 mm thick plain cement mortar bands in cement mortar 1:4 in width including curing complete as directed.\nA) Up to 300 mm width\nRaised band | item106 | 11635 | SQM. |
| 107 | 107 | Applying one coat of cement primer of approved brand and manufacture on new wall surface after throughly brooming the surfaces free from mortar droppings and other foreign matter and including preparing the surface even and sand papered smooth. | item107 | 98113 | SQM. |
| 108 | 108 | Providing two coats of Birla White Wall Care Putty (Water Resistance White Cement based putty for concrete/ mortar walls and ceiling both internal and external) after removing all loosely adhering material from the wall surface with the help of emery stone, putty blade or wire brush and moistening the wall with sufficient quantity of clean water as specified and directed by the department. (Total thickness of two coats is maximum 1.5mm).\nThickness = 1.5 mm thick | item108 | 631457 | SQM |
| 109 | 109 | Wall painting (two coats) with acrylic emulsion paint of approved brand and manufacture (Asian paint/ Berger paint/ ICI paint/ J&N paint/ Narolac) on new surface to give an even shade after throughly brushing the surfaces free from mortar droppings and other foreign matter and sand papered smooth.\nAcrylic Emulsion Paint approved brand and manufacture (Asian paint/ Berger paint/ ICI paint/ J&N paint/ Narolac). | item109 | 533447 | SQM. |
| 110 | 110 | Painting two coats (Including priming coat) on new wood and wood based surface surface with enamel paint of approved brand and manufactures (Asian paint/ Berger paint/ ICI paint/ J&N paint/ Narolac) to give an even shade including cleaning the surfaces of all dirt, dust and other foreign matter sand papering and stopping.\nSurfaces over 100 mm in width or girth.\nHigh gloss (Asian paint/ Berger paint/ ICI paint/ J&N paint / Nerolec). | item110 | 269 | SQM. |
| 111 | 111 | Painting two coats (Including priming coat) on new steel and metal surface surface with enamel paint of approved brand and manufactures (Asian paint/ Berger paint/ ICI paint/ J&N paint/ Narolac) to give an even shade including cleaning the surfaces of all dirt, dust and other foreign matter.\nSurfaces over 100 mm in width or girth.\nHigh gloss (Asian paint/ Berger paint/ ICI paint/ J&N paint / Nerolec). | item111 | 173111 | SQM. |
| 112 | 112 | Finishing old/ new wall with water proofing weather coat smooth anti-fungal premium textured exterior finish of Sandex Matt brand of Snowcem India Ltd. of required shade after clearing and clearing the surfaces etc.including scaffolding complete as directed at all levels (two coats). | item112 | 115182 | SQM. |
| 113 | 113 | Providng and laying of plaster (1:4) with GI chicken/PVC Wire Mesh/Glass Fibre Mesh Or Providing or laying of wall putty of 1mm(Max) thick over the insuboard's bottom surface and painting\ni) Providng and laying of plaster (1:4) with GI chicken/PVC Wire Mesh/Glass Fibre Mesh | item113 | 63735 | SQM. |
| 114 | 114 | Extra for fibre reinforcing concrete/ mortars by providing and mixing Recron3S of Reliance Industries Ltd. @ 125gms per bag of cement as specified and directed by the Department complete at all levels.\nB In Plasters/ mortars of proportion:\n(ii) 1 : 4 (1cement : 4coarse sand) | item114 | 9769 | CUM. |
| 115 | 115 | Providing, fitting and fixing anodised aluminium framed glazed doors with partition walls partly glass and partly prelaminated board with anodised aluminium frame made of 100mm x 43mm x 2mm sections of approved brand with doors style of size 81mm x 43mm x 2mm, top rails 46mm x 43mm x 2mm, lock rails 81mm x 43mm x 2mm, fitting with glazing clip, special rubber type gusket complete including hydraulic floor spring pivot aluminium door handle lock angles cleat etc. complete as directed by the department at all levels.\n6mm thick glass panes and 12mm prelaminated board | item115 | 6774 | SQM. |
| 116 | 116 | Providing, fitting and fixing coloured anodised aluminium sliding glazed doors with anodised aluminium frames made of 100mm x 45mm x 2mm section of approved brand with door style of size 81mm x 45mm x 2mm, top rails 55mm x 45mm x 2mm, lock rails 81mm x 45mm x 2mm, fitted with glazing clip, special type rubber gasket complete including roller, tower bolt, aluminium door handle, lock, angles, cleat etc. complete as specified and directed by the department at all levels.\n6mm clear glass | item116 | 847 | SQM. |
| 117 | 117 | Supplying and installing uPVC- Casement Windows made out of Lead free green profile having \"GREENLINE\" mark of BIS standard uPVC sections of wall thickness 2.4mm, multichambered with corners fusion welded, fully reinforced with Galvanized steel 1.5/2mm including glazing bead, folding gasket, glazing gasket, friction stay, Espag handle, Espag, keeper, drain cap, run up block, fisher screws, packing pieces with all stainless steel screws complete as directed. The windows must be installed complete with all kinds of ironmongery including EPDM gaskets,bridging wedges and glass packers and with suitable water draining system. Fittings ROTO / GQ or Equivalent. Application of Silicon sealant from Inside / Outside of Dowcorning / GE or equivalent.\n(d) Single leaf Top hung Window using uPVC section of size 58mm x 57mm x 2.4mm thick wall for frame, 58mm x 68mm x 2.4mm thick wall for glass sash\nWith 5mm clear float glass\n(WINSTA KOMMERLING/ FINESTA/ ENCRAFT) | item117 | 1914 | SQM. |
| 118 | 118 | FOR TOILET WATERPROOFING\nApplying 2 coats of 1mm thick elastomeric cementitious waterproofing coating Brushbond RFX of Fosroc Chemicals for water proofing structures like roof slabs, basement, sunken slabs, water tank etc., after proper surface preparation and soaking the surface with water prior to application complete as specified and directed by the Department at all levels. | item118 | 7563 | SQM. |
| 119 | 119 | FOR ROOF\n(A) Supplying, mixing, laying and applying the following waterproofing systems over Raft slabs, Roof slabs, Terraces etc. including curing complete as specified and directed by the Department at all levels.:\n(i) 1mm thick single coat of Master Crete M-81 of Choksey Chemicals /Dr. Sealkit Sealcrete (Asian Chemicals)/ mixed with cement in the ratio 1:2 as a prime coat.\n(ii) 3mm thick Polymer modified mortar - Cement sand mortar (in prop 1:3) mixed with Master Crete M-81/Dr. Sealkit Sealcrete (Asian Chemicals) @ 15% by weight of cement.\n(iii) 1mm thick coat of Master Crete M-81 /Dr. Sealkit Sealcrete (Asian Chemicals) mixed with cement in the ratio 1:2 as final coat. | item119 | 10356 | SQM. |
| 120 | 120 | FOR ROOF\n(A)Providing & applying over roof slab/raft slab, polymer modified bituminous /PU waterproofing membrane Proofex SM / Nitoproof 600 PF, Fosroc Chemical or equivalent on an unprimed substrate using specially designed spray application applicaation to be applied in a single coat, using wet on wet passes to give a nominal dry film thickness of 2 mm followed by applying ProofexGeo Textile having weight of 200gm per Sqm immediately after the application of Proofex SM Membrane when the surface is still wet but not tacky and as specified and directed by the department. | item120 | 20447 | SQM. |
| 121 | 121 | FOR TOILET & ROOF\nSupplying, providing, mixing and laying over waterproofing layers/coatings ( brick bat or water proofing) with cement mortar screed of average 25mm thick or as per drawings / requirements in proportion 1:4 (1 cement : r sand) admixed with integral waterproofing admixture Conplast x 421IC of Fosroc Chemicals @ 125ml per bag of cement complete as specified and directed by the Department at all levels. | item121 | 37700 | SQM. |
| 122 | 122 | FOR TOILET & ROOF\nFilling sunken floor with broken jhama brick bats and sand including compacting and supplying of materials complete as specified and directed upto first floor level. | item122 | 4716 | CUM. |
| 123 | 123 | Extra cost for lifting of brickbats and sand for filling of sunk floor for each subsequent floors above the 1st floor as directed and specified. | item123 | 23285 | CUM. |
| 124 | 124 | Providing and fixing of leak proof,fire retardant and Uv resistant skylighting galzing with Lexan polycarbonate sheet fixed with specially designed Domal management system confirming to IS:737 alloy & temper 6063 - T6 with a UTS of 180 to 200 mpa and weight of 1.03 kg/mtr. approx with EPDM rubber gasket of specific gravity as per ISO 2781,age resistant as per ASTM - D573 hardness as per 2240 & tensile strength as per ASTM 412 including the silicon sealent GE Bayer Weathersil NY as per drawing and directed by the Engineer in charge.\n10 mm thick Polycarbonate Sheet (Multiwall) | item124 | 1354 | SQM. |
| 125 | 125 | Demolishing brickwork including stacking of serviceable materials and disposal of unserviceable materials as directed for all levels.\nIn cement mortar | item125 | 4559 | CUM. |
| 126 | 126 | Dismantling and removing the existing door and window frame (chowkath) both wooden and steel of different sizes without damaging the walls and removing the frame and necessary repairs to the edges of the walls as directed for all levels.\nArea of door/window up to 3.00 m2 | item126 | 2314 | EACH |
| 127 | 127 | Dismantling and removing the existing door and window frame (chowkath) both wooden and steel of different sizes without damaging the walls and removing the frame and necessary repairs to the edges of the walls as directed for all levels.\n(iArea of door/window above 3.00 m2 | item127 | 5422 | EACH |
| 128 | 128 | Demolishing RCC work including stacking of steel bars and disposal of unserviceable material as directed for all levels | item128 | 5177 | CUM. |
| 129 | 129 | Demolishing CC floors of various thickness including top layer and base course and disposal of debris as directed for all levels. | item129 | 14606 | SQM. |
| 130 | 130 | Dismantling all types of corrugated/ trapezoidal sheet roofing including ridges, hips, valleys and gutters etc. and stacking the materials as directed by the department for all levels | item130 | 9500 | SQM. |
| 131 | 131 | Demolishing the plastering from walls/ R.C.C. and P.C.C. members without causing any damage to the wall/ member upto any height including disposal of debris as directed for all levels. | item131 | 576 | CUM. |
| 132 | 132 | Dismantling all types of ceiling, partition and wall lining and stacking the materials as directed by the department for all levels | item132 | 14964 | SQM. |
| 133 | 133 | Dismantling steel work in single sections (R.S.Joists, channels, angles, tees and flats etc.) including dismembering and stacking the materials as directed by the Department for all levels. | item133 | 150000 | Kg |
| 134 | 134 | Dismantling steel work in built up sections in joists, angles, channels, tees, flats etc. including all gusset plates, bolts, nuts, cutting rivets, welding etc. including dismembering and stacking the materials as directed by the Department for all levels | item134 | 105000 | Kg |
| 135 | 135 | Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical locations in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions.The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge. (Material shall conform to ASTM 6063).\nFloor Joint upto 200 mm gap | item135 | 523 | metre |
| 136 | 136 | Providing and fixing of expansion joint system related with wall joint (internal/external) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning /centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall conform to ASTM 6063.)\nWall Joint of 200 mm gap | item136 | 218 | metre |
| 137 | 137 | Providing and fixing of expansion joint system of approved make and manufacture for various roof locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members with, self aligning and self centering arragement support plates as per ASTM B221-02. The system shall be such that it provides water tight roof to roof /roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminum base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions.\nThe Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063.)\nRoof Joint upto 200 mm gap | item137 | 185 | metre |
| 138 | 138 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size,approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1cement : 4coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups,including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.\nGranite of any colour and shade (Area of slab upto 0.50 sqm) | item138 | 97 | SQM. |
| 139 | 139 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size,approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1cement : 4coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups,including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.\nGranite of any colour and shade (Area of Slab over 0.50sqm) | item139 | 2529 | SQM. |
| 140 | 140 | Providing edge moulding to 18 mm thick marble stone counters, vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.\nGranite work. | item140 | 916 | RMT. |
| 141 | 141 | Extra for fixing marble/granite stone over and above coresponding basic item, in facia and drops of width upto 150 mm with expoxy resin based (Araldite or equivalent) adhesive including cleaning etc. complete. | item141 | 3728 | RMT. |
| 142 | 142 | Extra for providing opening of required size & shape for wash basins/kitchen sink in kitchen platform. Vanity counters and similar location in marble/granite/stone work including necessary holes for pillar taps etc. including rubbing,moulding and polishing of cut edges etc. complete. | item142 | 1007 | RMT. |
| 143 | 143 | Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality.\n1.0 mm thick | item143 | 26212 | SQM |
| 144 | 144 | Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured):\nRectangular or square. | item144 | 3835 | SQM |
| 145 | 145 | Extra for providing frosted glass panes 4 mm thick instead of ordinary float glass panes 4 mm thick in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured). | item145 | 1396 | SQM |
| 146 | 146 | Providing and fixing fire resistant door frame of section 50 x 60mm on horizontal side & 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mm thick GI sheet ( Zinc coating not less than 120gm/m²) suitable for mounting 120 min Fire Rated Glazed Door Shutters. The frame shall be filled with Mineral wool Insulation having density min 96Kg/m³ . The frame will have a provision of G.I. Anchor fastners 14 nos ( 5 each on vertical style & 4 on horizontal style of size M10 x 80 ) suitable for fixing in the opening along with Factory made Template for SS Ball Bearing Hinges of Size 100x89x3mm for fixing of fire rated glazed shutter. The frame shall be finished with a approved fire resistant primer or Powder coating of not less than 30 micron in desired shade as per the directions of Engineer - in- charge . (Cost of SS ball bearing hinges is excluded). | item146 | 2856 | RMT. |
| 147 | 147 | Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 min Fire Rating confirming to IS:3614 (Part II) or EN1634-1:1999, tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, top rail & side rail 60 mm x 60 mm wide and bottom rail of 110 mm x 60 mm made out of 1.6mm thick G.I. sheet (zinc coating not less than 120gm/m²) duly filled mineral wool insulation having density min 96 kg/m³ and fixing with necessary stainless steel ball bearing hinges of size 100x89x3mm of approved make, including applying a coat of approved fire resistant primer or powder coating not less than 30 micron etc all complete as per direction of Engineer-in-charge (panelling to be paid for seperately). | item147 | 1848 | SQM |
| 148 | 148 | Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per direction of Engineer-in-charge. The glass shall be clear, toughened, interlayered, non-wired fire resistant having 11 mm thickness of approved brand with 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 15 min of insulation (EI15) and having a sound reduction of 37dB and LT of 86%. Glass shall be compliant to class 2(B)2 category of Impact Resistance as per EN 12600. The glass should be manufactured in UL & TUV audited Facility and including UL-EU Certification.The maximum glazing size cannot be more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The test report for the complete system (Glazed Door or Partition) will be considered valid only if it contains the stamp and signature of the authorized signatory from the glass manufacturer. (Actual glass size is to be measured at site for payments). | item148 | 1848 | SQM |
| 149 | 149 | Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete. | item149 | 676 | EACH |
| 150 | 150 | Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with zinc coating of 120 gms/ sqm(both side inclusive), consisting of floor and ceiling channel 50 mm wide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with joints staggered to avoid through cracks, M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corners (25 mm x 25 mm x 0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture’s specification and direction of engineer in charge all complete.\n75 mm overall thickness partition with 12.5 mm thick double skin fire rated board conforming to IS:2095: part I | item150 | 4280 | SQM |
| 151 | 151 | Providing and fixing approved brand and manufacture SS 304 grade wall mounted door buffer fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. | item151 | 5843 | EACH |
| 152 | 152 | Extra for providing ISI marked Stainless Steel butt hinges instead of M.S. pressed butt hinges bright finished of required size with necessary screws. (Shutter area to be measured). | item152 | 13966 | SQM |
| 153 | 153 | Providing and fixing approved brand and manufacture SS 304 grade D type 1200mm Pull Handle with 32mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. | item153 | 35 | PAIR |
| 154 | 154 | Providing and fixing approved brand and manufacture SS 304 grade D type 300mm Pull Handle with 32mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. | item154 | 328 | PAIR |
| 155 | 155 | Providing and fixing approved brand and manufacture SS 304 grade Glass to Glass Lock Round type with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. | item155 | 195 | EACH |
| 156 | 156 | Providing and fixing special quality bright finished brass cupboard or ward robe locks with four levers of approved quality including necessary screws etc. complete. 50 mm | item156 | 1149 | EACH |
| 157 | 157 | Providing and fixing magnetic catcher of approved quality in cupboard / ward robe shutters, including fixing with necessary screws etc. complete.\nDouble strip (horizontal type) | item158 | 2297 | EACH |
| 158 | 158 | FOR EXTERNAL BAMBOO CLADDING\nProviding & fixing in position Phenol bonded Bamboowood external wall cladding at all height with planks of sizes 10mm thick, 1800mm length (minimum) and 130 mm wide (minimum), in approved colour, texture and finish, having Performance Appraisal Certificate (PAC) issued by Building Materials & Technology Promotion Council (BMTPC), with necesasary profiled edges fixed with 40mm SS screws 5 nos in each tile to frame work made of second class teak wood of size 20x15 mm in centre of each tile and bottom and top of work height, 40x15mm placed at ends of each tile. The cladding shall be laid over backlayment of 1.00 mm thick expanded polyethylene foam of density 40kg/cum in two layers, first layer on wall surface before fixing wooden frame and second layer on frame under cladding. The bamboowood planks shall have minimum density of 1000 Kg/cum & minimum Hardness 1000 Kgf. with Eco friendly UV coating, all complete as per direction of the Engineer in-charge. | item159 | 1750 | SQM |
| 159 | 159 | Providing and fixing of Hollow metal lead lined door from ISO 9001-2000 certified manufacturer. Pressed Galvanized steel Single/Double leaf to required sizes of approved make shakthi met-door or approved equivalent which consists of frame, shutter, infill and finish as detailed below Door frame shall be double rebate profile of size 143x57 mm made out of 1.60mm (16 gauge) thick galvanized steel sheet. Frames shall be metered and field assembled with self tabs. The inside face of the frame face trim to rebate height should be protected with 2mm thick lead line. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Rubber door silencers should be provided on the striking jamb. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Once frame installed should be grouted with cement & sand slurry necessary for fire doors on the clear masonry opening.\nDoor leaf shall be 48mm thick fully flush double skin door with or without vision lite. Door leaf shall be manufactured from 1.2 mm (18 gauge) thick galvanised steel sheet. The internal construction of the door should be rigid with lead line of 2mm thick all across the inside of the exposed surface. In addition the door should have a basic infill Honey comb core with necessary reinforcement both on top and bottom. All doors should be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers as per ANSI Standard. The edges should be interlocked with a bending radius of 1.4 mm.\nAll doors and frames shall be finished with etched primer coating, stove zinc phosphate primer and thermosetting polyurethane aliphatic grade paint of approved RAL colour. The door leaf and frame shall have passed minimum 250 hours of salt spray test.\nRate should include supply and installation of door and hardware set.\nLead line door Single / double leaf of size\nDoor - 1500 mm x 2100 mm | item160 | 15 | EACH |
| 160 | 160 | Structural steel work riveted or bolted in built up sections, trusess and framed work, including cutting,hoisting,fixing in position and applying a priming coat of approved ateef primer all complete. | item161 | 19337 | KG |
| 161 | 161 | Steel work in built up tubular trusses including cutting, hoisting, fixing in position and applying a priming coar of approved steel primer, welded and bolted including special shaped washers etc. complete: Hot finished welded type tubes | item162 | 761464 | KG |
| 162 | 162 | Steel work welded in built up sections/framed work including cutting hoisting, rixing in position and applying a priming coat of approved steel primer using structural steel, etc. as required.\nIn gratings, frames, guard bar, ladder, railings, brackets, gates and similar works | item163 | 55613 | KG |
| 163 | 163 | Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.\nUsing M.S. angels 40x40x6 mm for diagonal braces | item164 | 150 | SQM |
| 164 | 164 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover | item165 | 197 | SQM. |
| 165 | 165 | Providing and fixing ball bearing for rolling shutters. | item166 | 36 | EACH |
| 166 | 166 | Extra for providing mechanical device chain and crank operation for operating rolling shutters.\nExceeding 10.00 sqm and upto 16.80 sqm in the area. | item167 | 197 | SQM. |
| 167 | 167 | Extra for providing grilled rolling shutters manufactured out of 8 mm dia.M.S. bar instead of laths as per design approved by Engineer-in-charge.(area of grill to be measured). | item168 | 99 | SQM. |
| 168 | 168 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape\nwherever required. | item169 | 8321 | SQM. |
| 169 | 169 | Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete :\nRidges plain (500 - 600mm) | item170 | 698 | metre |
| 170 | 170 | Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete :\nGutter (600 mm over all girth) | item171 | 283 | metre |
| 171 | 171 | Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. | item172 | 3911 | SQM |
| 172 | 172 | Providing and fixing 18mm thick pre-polished granite stone strip of any colour and shade 60mm wide with one edge round moulded and polished, fixing the strip in wall above the top of dado, by cutting chase in wall and fixing the same with cement mortar 1:3 (1cement : 3 coarse sand), neatly finished and fixed such that the outer rounded edge projected 20mm beyond the surface of dado , all complete as per direction of engineer-in-charge. | item173 | 25209 | RMT. |
| 173 | 173 | Providing and laying C.C. pavement (TRIMIX) of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work shall be paid for separately). | item174 | 3740 | CUM. |
| 174 | 174 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / aneling,C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :\nFor fixed portion\nPowder coated aluminium (minimum thickness of powder coating 50 micron) | item175 | 159374 | KG. |
| 175 | 175 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately)\nPowder coated aluminium (minimum thickness of powder coating 50 micron) | item176 | 82661 | KG. |
| 176 | 176 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge .(Cost of aluminium snap beading shall be paid in basic item):\nWith float glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm) | item177 | 5396 | SQM. |
| 177 | 177 | Filling the gap in between aluminium frame & adjacent RCC/ Brick/Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-incharge complete.\nUpto 5mm depth and 5 mm width | item178 | 81123 | RMT. |
| 178 | 178 | Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per specifications, drawings and direction of Engineer-in-charge complete. | item179 | 4785 | SQM. |
| 179 | 179 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock and stopper etc.to be paid separately). | item180 | 968 | SQM. |
| 180 | 180 | Providing and fixing Single Glazing 6mm thick toughened glass complete in all respects as per direction of the Engineer-in-charge. (Required properties Solar factor = 0.45, U-Value = (W/sq.m-K) 5.7W /M2K, Visible light transmittance = 0.30) | item181 | 25550 | SQM. |
| 181 | 181 | Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes, wire mesh and silicon sealent shall be paid separately)\nNote: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable. Variation in profile dimension in higher side shall be accepted but no extra payment on this account shall be made.\nThree track three panels sliding window with fly proof S.S wire mesh (Two nos. glazed & one no. wire mesh panels) made of (big series) frame 116 x 45 mm & sash 46 x 62 mm both having wall thickness of 2.3 ± 0.2 mm and single glazing bead / double glazing bead of appropriate dimension. (Area of window above 1.75 sqm). | item182 | 5751 | SQM. |
| 182 | 182 | Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. ( The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account). The weight of aluminium extruded section shall be taken for purpose of payment. | item183 | 14533 | Kg |
| 183 | 183 | Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including:\na) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including:\nb) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers.\nc) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass.\nd) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight.\ne) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge.\nNote:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub- head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places..\nNote:- 2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NBL Certified laboratories\n6) Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml | item184 | 1262 | SQM. |
| 184 | 184 | Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor.“(Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.26.2)“For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm.“\nColoured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. | item185 | 1262 | SQM. |
| 185 | 185 | Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all accessories and hardwares for the openable panels as specified and of the approved make such as heavy duty stainless steel friction hinges, min 4 -point cremone locking sets with stainless steel plates, handles, buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all complete as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer- in-Charge. | item186 | 318 | SQM. |
| 186 | 186 | Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminium Composite Panel Cladding, with open grooves for linear as well as curvilinear portions of the building , for all heights and all levels etc. including:\na) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design.\nb) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium item.s The Contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places.\" | item187 | 453 | SQM. |
| 187 | 187 | Design supply & installation of suspended Spider Glazing system designed to withstand the wind pressure as per IS 875 (Part-III). The Suspended System held with Spider Fittings of SS-316 Grade Steel of approved manufacturer with glass panel having 12 mm thick clear toughened glass held together with SS- 316 Grade Stainless steel Spider & bolt assembly with laminated glass fins 21 mm thick. The Glass fins and glass panel assembly shall be connected to Slab/beams by means of SS- 316 Grade stainless steel brackets & Anchor bolts and at the bottom using SS channel of 50x25x2mm using fastener & anchor bolts, non staining weather sealants of approved make, Teflon/ nylon bushes and separators to prevent bi-metallic contacts, all complete to perform as per specification and approved drawings. The complete system to be designed to accommodate thermal expansion & seismic movements etc. The joints between glass panels (6 to 8 mm) and gaps at the perimeter & in U channel of the assembly to be filled with non staining weather sealant, so as to make the entire system fully water proof & dust proof.\nThe rate shall include all design, Engineering and shop drawing including approval from structural designer, labour, T&P, scaffolding, other incidental charges including wastage, enabling temporary services all fitting fixers nut bolts, washer, Buffer plates, fastener, anchors, SS channel laminated glass etc. all complete. For the purpose of payment, actual elevation area of Glazing including thickness of joints and the portion of Glass panel inside the SS channel shall be measured. | item188 | 1262 | SQM. |
| 188 | 188 | Providing and fixing fly proof stainless steel grade 304 wire gauge, to windows and clerestory windows using wire gauge with average width of aperture 1.4 mm in both directions with wire of dia. 0.50 mm all complete.\nWith 12 mm mild steel U beading | item189 | 24266 | SQM. |
| 189 | 189 | Providing and mixing integral crystalline admixture for water proofing treatment to RCC structures like basement raft, retaining walls, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc. at the time of transporting of concrete into the drum of the ready-mix truck, using integral crystalline admixture @ 0.80% (minimum) to the weight of cement content per cubic meter of concrete) or higher as recommended by the manufacturer’s specification in reinforced cement concrete at site of work. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90%, compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure. The crystalline admixture shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the Engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage. | item190 | 50345 | kg |
| 190 | 190 | Basement Waterproofing for Vertical Surfaces and Retailing Wall\nSupplying and Installing Proofex3000 manufractured by Fosroc / Chocksey Cehmicals / Dr.Fixit, a selfadhesive, coldapplied, flexible 1.5 mm thick waterproofing membrane by manufacturer approved applicator which comprises of a self adhesive polymer modified bitumen compound with crosslaminated HDPE film. The membrane shall have a premarked minimum 50mm overlap aid available & applied on the uniform surface of the Vertical RCC Wall after application of single component solvent/water based bituminous primer approved & Installed as permanufacturer's recommendation. The rate inclusive of minimum 20mm expanded polystyrene protection board Tierod cutting and grout filling, pipe sleeve joint filling and sealing. The self adhesive membrane Suitable for waterproofing basements grades 2 and 3 as define din BS8102:2009, ‘Protection Of Structures Against Water From The Ground’ basement as per BS8102:2009 and shall be BBA certified andhaving elongation. | item191 | 9063 | Sqm |
| 191 | 191 | Basement Waterproofing for Horizontal Surfaces\nProviding and installing waterproofing treatment for \"Raft 'Slab\" by using fully bonded HDPE sheet membrane 1.2mm thick HDPE P manufactured by Fosroc / Chocksey Cehmicals / Dr.Fixit or equivalent before casting of the base RCC slab. The Membrane should be a unique composite sheet comprised of a thick HDPE film, pressure sensitive adhesive and weather resistant protective coating. The membrane shall conforms to basement waterproofing protection to grade 3 as defined in BS 8102:2009.The membrane shall have thickness- : 1.2mm,Tensile strength :27 MPa as per ASTM D412, Elongation (Peak) : 500%, puncture resistance :1000N as per ASTM E154, Peel Adhesion to concrete 880N/m as per ASTM D903, Hydrostatic pressure resistance up to 70 M Head of water as per ASTM D751-06(2011). The cost inclusive of material, application, machinaries required including treatment of Pile Heads using micro-concrete. | item192 | 41282 | Sqm |
| 192 | 192 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage.\nFor vertical surface two coats @ 0.70 kg per sqm | item193 | 9016 | SQM. |
| 193 | 193 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage.\nFor horizontal surface one coat @1.10 kg per sqm. | item194 | 25913 | SQM. |
| 194 | 194 | Providing and Placing in position suitable PVC water stops for construction/expansion joints between two RCC memberrs and fixed to the reinforfement with binding wire before pouring concrete etc. complete.\nSerrated with central buld (225 mm wide, 8-11 mm thick) | item195 | 450 | RMT. |
| 195 | 195 | Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross section as 23 mmx25mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture’s permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. | item196 | 64 | EACH |
| 196 | 196 | Providing and fixing at all height false ceiling including providing and fixing of frame work made of special sections power pressed from M.S. sheet and galvanised in accordance with zinc coating of grade 350 as per IS : 277 and consisting of angle cleats of size 25mm wide x 1.6mm thick with flanges of 22mm and 37mm at 1200mm centre to centre one flange fixed to the ceiling with dash fastener 12.5mm diax40mm long with 6mm dia bolts to the angle hangers of 25x25x0.55mm of required length, and other end of angle hanger being fixed with nut and bolts to G.I. channels 45x15x0.9mm running at the rate of 1200mm centre to centre to which the ceiling section 0.5mm thick button wedge of 80mm with tapered flanges of 26mm each having clips of 10.5mm at 450mm centre to centre shall be fixed in a direction perpendicular to G.I. channel with connecting clips made out of 2.64mm diax230mm long G.I. wire at every junction including fixing the gypsum board with ceiling section and perimeter channels 0.5mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450mm centre to centre with 25mm long drive-all screws @ 230mm interval including jointing and fixing to a flush finish of tapered and square edges of the board with recommended filler, jointing tapes, finisher and two coats of primer suitable for board as per manufactures specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed all complete as per drawing and specification and direction of the Engineer in Charge but excluding the cost of painting with :\n12.5 mm thick tapered edge gypsum fire resistant board conforming to IS: 2095- Part I | item197 | 14227 | SQM. |
| 197 | 197 | Providing and fixing tiled false ceiling of approved materials of size 595x595 mm in true horizontal level suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 gsm/sqm, both side inclusive) consisting of main \"T\" runner with suitably spaced joints to get required length and of size 24x38mm made from 0.30mm thick (minimum) sheet, spaced at 1200mm center to center and cross \"T\" of size 24x25mm made of 0.30mm thick (minimum) sheet, 1200mm long spaced between main \"T\" at 600mm center to center to form a grid of 1200x600 mm and secondary cross \"T\" of length 600mm and size 24x25mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600mm panel to form grids of 600x600mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, wherever, required, cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \"T\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 x mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete at all heights as per specifications drawings and as directed by Engineer-in-charge.\nGI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum),including factory painted after bending and perforation,and backed with a black Glass fiber acoustical fleece. | item198 | 16153 | SQM. |
| 198 | 198 | Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm ) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised @80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod upto 1000mm length and L-hape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be prepainted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge.\nWith 16 mm thick beveled tegular mineral fibre Antimicrobial false ceiling tile confirming to ISO 5 (class 100 ) specifications | item199 | 16153 | SQM. |
| 199 | 199 | Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres. | item200 | 34418 | SQM. |
| 200 | 200 | Extra for compaction of earth work in embankment under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density). | item201 | 32698 | CUM. |
| 201 | 201 | Supplying and stacking at site :\n90 mm to 45 mm size stone aggregate | item202 | 5163 | CUM. |
| 202 | 202 | Supplying and stacking at site :\n363 mm to 45 mm size stone aggregate | item203 | 5163 | CUM. |
| 203 | 203 | Supplying and stacking at site :\nStone screening 13.2 mm nominal size (type A) | item204 | 258 | CUM. |
| 204 | 204 | Supplying and stacking at site :\nStone screening 11.2 mm nominal size (type A) | item205 | 258 | CUM. |
| 205 | 205 | Supplying and stacking at site : Moorum | item206 | 1721 | CUM. |
| 206 | 206 | Laying spreading and compacting stone aggregate of specified sizes to WBM specifications including spreading in uni form thickness, hand picking, rolling with 3 wheeled road/vibratory roller 8-10 tonne in stages to proper grade and camber, applying and brooming requisite type of screening/binding material to fill up interstics of coarse aggregate watering and compacting to the required density. | item207 | 12563 | CUM. |
| 207 | 207 | Surface dressing one coat on new surface with bitumen of specified grade at a rate of 1.95 kg/sqm of surface area with 1.5 cum of stone chippings 13.2 mm nominal size per 100 sqm of road surface, including consolidation with road roller of 6 to 8 tonne capacity , etc. complete :\nUsing bitumen emulsion (minimum 50% bitumen content-RS grade conforming to IS : 8887) | item208 | 17881 | SQM. |
| 208 | 208 | Providing and applying tack coat using bitumen emulsion conforming to IS:8887, using emulsion pressure distributer including preparing the surface & cleaning with mechanical broom.\nWith rapid setting bitumen emulsion\nOn bituminous surface @ 0.25kg/sqm | item209 | 17881 | SQM. |
| 209 | 209 | Providing and laying Bitumen Penetration Macadam with hard stone aggregate of quality, size and grading as specified, with bitumen of suitable penetration grade, including required key aggregate as specified, spreading coarse aggregate with the help of self propelled/tipper tail mounted aggregate spreader and applying bitumen by a pressure distributor and then spreading key aggregate with the help of aggregate spreader complete, including consolidation with road roller of minimum 8 to 10 tonne capacity to achieve specified values of compaction and surface accuracy :\nFor 50mm compacted thickness using coarse aggregate of size 50-20 mm graded @ 0.60 cum per 10 sqm key aggregate of size 12.5 mm graded @ 0.15 cum per 10 sqm. With paving asphalt grade VG - 10 @ 50 kg/ 10 sqm. | item210 | 17881 | SQM. |
| 210 | 210 | Providing and laying seal coat over prepared surface of road with bitumen heated in bitumen boiler fitted with the spray set spraying using 98 kg of bitumen of grade VG - 10 and blinding surface with 0.90 cum of stone aggregate of 6.7 mm size (Passing 11.2 mm sieve and retained on 2.36 mm sieve) per 100 sqm of road surface, including rolling and finishing with power road roller all complete.\nNote: Seal coat items to be operated only with the prior approval of chief Engineer concerned. | item211 | 17881 | SQM. |
| 211 | 211 | Painting runway/taxi track/apron marking with adequate no. of coats to give uniform finish with road marking paint of superior make as approved by the Engineer-in-charge i/c cleaning the surface of all dirt, scales, oil, grease and other foreign material etc. and lining out complete.\nNew work (Two or more coats) | item212 | 985 | SQM. |
| 212 | 212 | Providing and laying 60mm thick factory made cement concrete interlocking paver block of M-30 grade made by block making machine with strong vibratory compaction and of approved size and design/shape laid in required colour and pattern over and including 50 mm thick compacted of coarse sand, filling the joints with coarse sand etc. all complete as per direction of engineer-in-charge. | item213 | 9333 | SQM. |
| 213 | 213 | Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).\nMedium shade pigment using 50% white cement 50% Grey cement | item214 | 8889 | SQM. |
| 214 | 214 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement in position to the required line ,level and curvature jointed with cement mortar 1:3 (1 cement : 3 coarse sand) including making joints with or without grooves (thickness of joints except sharp curve shall not be more than 5mm) including making drainage opening wherever required complete etc. as per direction of engineer-in-charge(length of finished kerb edging shall be measured for payment).(Precast C.C. kerb stone shall be approved by engineer-in-charge). | item215 | 482 | CUM. |
| 215 | 215 | Trenching in ordinary soil up to a depth of 60 cm including removal and stacking of serviceable materials and then disposing of surplus soil, by spreading and neatly leveling within a lead of 50 m and making up the trenched area to proper levels by filling with earth or earth mixed with sludge or/and manure before and after flooding trench with water (excluding cost of imported earth, sludge or manure). | item217 | 2866 | CUM. |
| 216 | 216 | For Horticulture and Landscaping Supplying and stacking of good earth at site including royalty and carriage up to 1 km (earth measured in stacks will be reduced by 20% for payment). | item218 | 2130 | CUM. |
| 217 | 217 | For Horticulture and Landscaping Supplying and stacking at site dump manure from approved source, including carriage up to 1 km (manure measured in stacks will be reduced by 8% for payment) : Screened through sieve of I.S. designation 20 mm | item219 | 533 | CUM. |
| 218 | 218 | For Horticulture and Landscaping Supplying and stacking at site dump manure from approved source, including carriage up to 1 km (manure measured in stacks will be reduced by 8% for payment) : Screened through sieve of I.S. designation 16 mm | item220 | 533 | CUM. |
| 219 | 219 | For Horticulture and Landscaping Supplying and stacking at site dump manure from approved source, including carriage up to 1 km (manure measured in stacks will be reduced by 8% for payment) : Screened through sieve of I.S. designation 4.75 mm | item221 | 533 | CUM. |
| 220 | 220 | For Horticulture and Landscaping Fine dressing of the ground | item222 | 10647 | sqm |
| 221 | 221 | For Horticulture and Landscaping Spreading of sludge, dump manure and / or good earth in required thickness as per direction of Officer-in-charge (Cost of sludge, dump manure and / or good earth to be paid separately). | item223 | 1597 | CUM. |
| 222 | 222 | For Horticulture and Landscaping Mixing earth and sludge or manure in the required proportion specified or directed by the Officer-in-charge.. | item224 | 1597 | CUM. |
| 223 | 223 | For Horticulture and Landscaping Supplying & Stacking of Selection No.1 Grass at site fresh & free from weeds having proper roots in green including loading, unloading, carriage and all taxes paid etc.and as per direction of officer in charge. | item225 | 10647 | SQM. |
| 224 | 224 | Grassing with selection No.1 grass including watering and maintenance of the lawn for 30 days or more till the grass forms a thick lawn, free from weeds and fit for mowing including supplying good earth, if needed (the good earth if needed shall be paid for separately).\nIn rows 5 cm apart in both directions | item226 | 10647 | SQM. |
| 225 | 225 | Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure or sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20% : 1 part of stacked volume of manure after reduction by 8%) flooding with water, dressing including removal of rubbish and surplus earth, if any, with all leads and lifts (cost of manure, sludge or extra good earth if needed to be paid for separately) :\nHoles 60 cm dia, and 60 cm deep. | item227 | 1447 | EACH |
| 226 | 226 | Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure or sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20% : 1 part of stacked volume of manure after reduction by 8%) flooding with water, dressing including removal of rubbish and surplus earth, if any, with all leads and lifts (cost of manure, sludge or extra good earth if needed to be paid for separately) :\nHoles 45 cm dia, and 45 cm deep. | item228 | 1166 | EACH |
| 227 | 227 | Providing and Displaying of Wadelia trilobata plant,full of leaves in 15 cm size of Poly bags & as per direction of the officer-in-charge. | item229 | 254 | EACH |
| 228 | 228 | Providing and Displaying of Duranta Golden plant, having ht.15 to 20 cm bushty shape plant with fresh and healthy leaves in 20 cm size of Earthen Pot / Plastic Pot & as per direction of the officer-in-charge.. | item230 | 338 | EACH |
| 229 | 229 | Providing and Displaying of Iresine herbstii plant, of height 20-30 cm. full of branches well developed in 15 cm size of Earthen Pot / Plastic Pot & as per direction of the officer-in-charge. | item231 | 169 | EACH |
| 230 | 230 | Supply and stacking of Alstonia scholaris plant of height 150-165 cm. in bag of size 25 cm as per direction of the officer-in-charge. | item232 | 85 | EACH |
| 231 | 231 | Supply and stacking of Bauhinia blakeana (Kachnar) plant of height 120-150 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge. | item233 | 135 | EACH |
| 232 | 232 | Supply and stacking of Bombax ceiba plant of height 150-165 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge. | item234 | 126 | EACH |
| 233 | 233 | Supply and stacking of Grevillea robusta (Silver Oak) plant of height 150-165 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge. | item235 | 254 | EACH |
| 234 | 234 | Supply and stacking of Kigelia pinnata plant of height 150-165 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge. | item236 | 506 | EACH |
| 235 | 235 | Supply and stacking of Melia azedarach plant of height 120-135 cm. in big poly bag of size 25cm as per direction of the officer-in-charge. | item237 | 675 | EACH |
| 236 | 236 | Supply and stacking of Michelia champa (Golden Champa)plant of height 90-105 cm. in earthen pots of size 25 cm as per direction of the officer-in-charge. | item238 | 338 | EACH |
| 237 | 237 | Supply and stacking of Putranjiva roxburghii plant of height 90-105 cm. in big polybag of size 25 cm as per direction of the officer-in-charge. | item239 | 254 | EACH |
| 238 | 238 | Supply and stacking of plant Jatropha multifida (red colour) of height 60-75 cm. multibranched in p.bag of size 25 cm as per direction of the officer-in-charge. | item240 | 169 | EACH |
| 239 | 239 | Supply and stacking of plant Calliandra hybrida of height 105-120 cm., well branched, bushy in big size HDPE bag as per direction of the officer-in-charge. | item241 | 246 | EACH |
| 240 | 240 | Supply and stacking of plant Gardenia jasminoides of height 45-60 cm. with 3-4 branches in earthen pots of size 20 cm as per direction of the officer-in-charge. | item242 | 492 | EACH |
| 241 | 241 | Supply and stacking of plant Nerium oleander (kaner) of height 45-60 cm. with 3-4 branches in poly bags of size 20 cm as per direction of the officer-in-charge. | item243 | 338 | EACH |
| 242 | 242 | Supply and stacking of Clerodendrum splendens plant of height 30 cm to 45 cm. in 20 cm size of Earthen pots / Plastic pots & as per direction of the officer-in-charge. | item244 | 254 | EACH |
| 243 | 243 | Supply and stacking of Jasminum grandiflorum (chameli) plant of height 30 cm to 45 cm. in 20 cm size of Earthen pots / Plastic pots & as per direction of the officer-in-charge. . | item245 | 506 | EACH |
| 244 | 244 | Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.\nFor thickness of tiles 10 mm to 25 mm | item246 | 11680 | SQM. |
| 245 | 245 | Dismantling stone slab flooring laid in cement mortar including stacking of serviceable material and disposal of unserviceable material within 50 metres lead. | item247 | 2920 | CUM. |
| 246 | 246 | Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials including excess earth by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved. | item248 | 11577 | CUM. |
| 247 | 247 | PLUMBING WORKS\nSanitary Fixtures & CP Brass Fittings\nProviding fitting and fixing vitreous water closet squatting pan (Indian type W.C Orissa pattern) with all fittings and fixtures complete including cutting and making good to the walls and floors whereever required. (Flushing Cistern to be paid separately)\nIndian type W.C Orissa pattern of size 580 x 440 mm\na) White\niii) Jaquar make | item249 | 263 | Each |
| 248 | 248 | Provinding fitting and fixing Vitreous china wall hang water closet (European type W.C PAN 400 mm high) with seat and lead, CP Brass hinges and rubber buffers , CI/MS brackets,40 mm dia flush band with fittings including painting of fittings and brackets, required.(flushing Cistern to be paid separately)\na) White\niii) Jaquar make\n(i) Florentine Cat. No. FLS-WHT-0111 (inclusive of seat cover and fittings) | item250 | 729 | Each |
| 249 | 249 | (Provinding fitting and fixing Vitreous china wall hang water closet (European type W.C PAN 400 mm high) with seat and lead, CP Brass hinges and rubber buffers , CI/MS brackets,40 mm dia flush band with fittings including painting of fittings and brackets, required.(flushing Cistern to be paid separately)\na) White\niii) Jaquar make\nii) Solo Cat. No. SLS-WHT-0117 (inclusive of seat cover and fittings) | item251 | 511 | Each |
| 250 | 250 | Supplying, fiting and fixing PVC flushing cistern with all internal fittings with CI brackets including fitting and fixing standard size CP flush pipe, union clamps etc. compete as directed and specified (pipes will be measured separately)\ni) Parryware make\na) White\n(i) Economy Single Flush (Cat No.C8090/C8055) | item252 | 183 | Each |
| 251 | 251 | Supplying ,fitting and fixing concealed cistern with all internal fittings with CI brackets including fitting and fixing standard size CP flush pipe, union clamps etc. compete as directed and specified (pipes will be measured separately)\nC) Jaquar make\na) White\nConcealed Cistern ( Cat. No. CIB-WHT-31801011X) with Control Plate (CP) (Cat.No. CIS-CHR-31191510X) | item253 | 1251 | Each |
| 252 | 252 | Providing fitting and fixing vitreous china flat back type lipped front urinal; basin of with automatic flushing cistern with standard flush pipe and CP brass spreader andbrass unions,etc. complete including painting of fittings and complete, cutting and making good the walls & brackets, cutting and making good the walls & floors wherever required.\nC) Jaquar make\na) White\n(i) Urinal (Cat.No. URS-WHT-0704) with Sensor (Cat. No. SNR-CHR-51097) | item254 | 249 | Each |
| 253 | 253 | Suppling fiting and fixing glass division plate of jaquar make including fitting and fixing compate as directed and specified. | item255 | 139 | Each |
| 254 | 254 | Provinding vitreous china wash basin with CI/MS brackets, C.P brass chain with plug,PVC waste pipe including painting of fittings and brackets, cutting and making good the walls wherever required.(Pillar cock, stop cocks, waste coupling are to be paid separately )\nTable Top Basin\n(C) Jaquar Make\n(ii) Solo ( Cat. No. SLS- WHT-0558) | item256 | 749 | Each |
| 255 | 255 | Provinding vitreous china wash basin with CI/MS brackets, C.P brass chain with plug,PVC waste pipe including painting of fittings and brackets, cutting and making good the walls wherever required.(Pillar cock, stop cocks, waste coupling are to be paid separately )\nTable Top Basin\n(C) Jaquar Make\n(iii) Lyric ( Cat. No. LYL-WHT-0555) | item257 | 678 | Each |
| 256 | 256 | Providing fitting & fixing stainless steel kitchen sink of parry make with CI/MS brackets, C.P. brass chain with rubber plug, PVC waste pipe etc. complete including painting the fittings, cutting & making good the walls wherever required.( Sink cock, stop cocks, waste coupling are to be paid separately .\n(A) Parryware Make\n(ii) Single Bowl with Drain board (400x200) flat Edge - Glossy ( Cat. No. C8537) | item258 | 221 | Each |
| 257 | 257 | Providing fitting & fixing laboratory sink of Parryware make with CI/MS brackets, C.P. brass chain with rubber plug, PVC waste pipe etc. complete including painting the fittings ,cutting &making good the walls wherever required. (Sink cock, stop cocks, waste coupling are to be paid separately.\n(A) Parryware Make\na) White\n(i) Lab Sink 450mm (Cat.No.C0602) | item259 | 375 | Each |
| 258 | 258 | Providing fitting and fixing Decorative Mirror complete as directed and specified.\n(A) Parryware Make\n(a) Size 800mmx600mm | item260 | 678 | Each |
| 259 | 259 | Providing fitting and fixing Decorative Mirror complete as directed and specified.\n(A) Parryware Make\n(b) Size 600mmx 450mm | item261 | 749 | Each |
| 260 | 260 | Providing,fitting and fixing CP soap tray / soap dish complete as directed and specified.\n(i) Jaquar make\n(e) Hotelier (Cat.No. AHS - 1531) | item262 | 548 | Each |
| 261 | 261 | Providing fitting and fixing liquid soap dispenser and liquid soap container complete as directed ad specified.\n(i) Jaquar make\n(c) Kubix with glass bottle (Cat.No. AKB-35735) | item263 | 1055 | Each |
| 262 | 262 | Providing fitting and fixing CP towel rail complete as direted and specified\n(a) Jaquar make\n(vii) Kubix(600mm long) (Cat.No. AKB-35711) | item264 | 561 | Each |
| 263 | 263 | Providing, fitting and fixing Chrome Plated towel ring complete as directed and specified.\n(a) Jaquar make\n(ii) Continental towel ring round (Cat.No. ACN-1121BN) | item265 | 1055 | Each |
| 264 | 264 | Providing ,fitting and fixing chrome plated robe hook complete as direted and specified.\n(a) Jaquar make\n(iii) Kubix (Cat.No.AKB-35791) | item266 | 1414 | Each |
| 265 | 265 | Providing, fitting and fixing chrome plated tumbler holder complete as directed and specified.\n(a) Jaquar make\n(iii) Kubix (Cat.No.AKB-35741) | item267 | 548 | Each |
| 266 | 266 | Providing fitting and fixing chrome plated TOILET PAPER holder of complete as directed and specified\n(a) Jaquar make\n(ii) Continetal toilet paper holder with flap(cat.No. ACN1153N) | item268 | 797 | Each |
| 267 | 267 | Providing fitting and fixing chrome plated TOILET PAPER holder of complete as directed and specified\n(a) Jaquar make\n(vii) Kubix toilet roll holder with cover (Cat.No. AKB-35753) | item269 | 511 | Each |
| 268 | 268 | Providing ,fitting andd Fixing chrome plated waste coupling complete as directed and specified.\n(a) Jaquar make\n(i) 32mm (HT/FT) (Cat.No. ALD-705/709 | item270 | 1978 | Each |
| 269 | 269 | Providing ,fitting andd Fixing chrome plated Bottle Trap complete as directed and specified.\n(a) Jaquar make\n(i) Bottle trap (with internal partition) 32mm size with 250mm long wall connection pipe(Cat.No.ALD-769) | item271 | 1427 | Each |
| 270 | 270 | Supplying fitting and fixing C.P bib cock 15 mm dia of approved brand as directed and specified (G.I & C.P pipes will be measured separately)\nJaquar make\n(a) Continental / clarion\n(ii) Bibcock long thread | item272 | 183 | Each |
| 271 | 271 | Supplying fitting and fixing C.P bib cock 15 mm dia of approved brand as directed and specified (G.I & C.P pipes will be measured separately)\nJaquar make\n(a) Continental / clarion\n(iii) 2-Way bib cock | item273 | 1231 | Each |
| 272 | 272 | Supplying fitting and fixing chorom plated (C.P) stop- cock of approved brand and size as mentioned below as directed and specified.(G.I) & C.P Pipes will be measured and paid separately)\nJaquar\n(a) Continental / Clarion\n(iii) 15mm (Angular stop cock with long thread ) | item274 | 3390 | Each |
| 273 | 273 | Supplying and fiiting fixing C.P pillar cock of 15 mm dia of approved brand as specified and directed.\nJaquar make\n(a) Continental | item275 | 749 | Each |
| 274 | 274 | Supplying,fitting and fixing chorme plated (C.P) shower 15 mm dia. Of approved nrand as directed and specified.( pipes will be measured and paid separately)\n(III) Jaquar Make\n(a) Continental\n(ii) Shower arm 190mm long heavy casted body with wall flange | item276 | 548 | Each |
| 275 | 275 | Supplying,fitting and fixing chorme plated (C.P) shower 15 mm dia. Of approved nrand as directed and specified.( pipes will be measured and paid separately)\n(III) Jaquar Make\n(a) Continental\n(iii) Pressure adjustable shower with revolving joint | item277 | 548 | Each |
| 276 | 276 | Supplying, fitting and fixing Chorme plated (C.P) basin mixer complete as directed\nJaquar make (For VIP use. Prior approval of chief Enginner PWD (Bidg) must be taken before use)\n(a) Continental/ Clarion\n(iii) Central hole basin mixer without popup waste system with 450mm long coper pipe and brass nuts Cat.No. 169 | item278 | 678 | Each |
| 277 | 277 | Supplying, fitting and fixing Chrome Plated (C.P) sink mixer complete as directed.\nJaquar make\n(a) Continental / Clarion\n(i) Sink mixer with swinging casted spout ( wall mounted model) Cat No. 309 | item279 | 551 | Each |
| 278 | 278 | Supplying fitting and fixing Chrome plated (C.P) bath tub spout of approved brand complete as directed.\nJaquar make\n(a) Continental\n(ii) Bath tub spout 235 mm long with wall falnge Cat No. 433 | item280 | 548 | Each |
| 279 | 279 | Supplying , fitting and fixing Chorme Plated (C.P) divertor of approved brand complete as directed .\nJaquar make\n(a) Continental/ Clarion - 4 way divertor for concealed fitting with build in non return valves with divertor handle Cat. No.421 | item281 | 548 | Each |
| 280 | 280 | Providing and fixing hand shower (Health faucet) with 1.2mtr long with 8mm dia Easy Flex Tube with wall hook and flow restrictor with flow rate 6 litre per minute at 3 bar in chrome finish and wall hook. | item282 | 1231 | Each |
| 281 | 281 | Providing & fixing wall mounted 300mm Long SS Grab Bar including cutting & making good the walls. | item283 | 131 | Each |
| 282 | 282 | Providing and fixing Stainless Steel Swing Handicap Grab Bar ,Including cutting and making good the walls wherever required. | item284 | 131 | Each |
| 283 | 283 | Providing and fixing of fully automatic \"NO TOUCH\" durable & shock proof hand drier of approved make & manufacture suitable to operate on 220 volts, single phase 50 hz, A.C. power supply, 1500 Watt and directly plugged to power point complete in ABS plastic body having drying time 20-30 seconds complete as per direction of Engineer in Charge. The rate include cost of all material & labour involved in the item complete and all as per direction of engineer incharge. | item285 | 206 | Each |
| 284 | 284 | Providing and fixing 150 litre/ hr. cooling and storage capacity,fully stainless steel electric storage type water cooler ( Blue Star model No. SDLX 15150 or equvalant) with inlet hose connection inbuilt float valve. 2 Nos. outlet foucet, drain tray with waste and pipe up to fllor trap heavy compressor and wire up to socket, 3 pin plug etc complete in all respect. | item286 | 110 | Each |
| 285 | 285 | Soil, Waste, Vent & Rain Water Pipes\nSupplying, fitting and fixing PVC pipes of 6 kg/cm2 (supreme/Price) or other ISI approved including joining, fitting and fixing with clamps etc.as necessary complete at all levels including below G.L as directed and specified.\n(a) In Exposed Surface or in Trenches.\ni. 160mm dia. | item287 | 3935 | Each |
| 286 | 286 | Supplying, fitting and fixing PVC pipes of 6 kg/cm2 (supreme/Price) or other ISI approved including joining, fitting and fixing with clamps etc.as necessary complete at all levels including below G.L as directed and specified.\n(a) In Exposed Surface or in Trenches.\nii. 110mm dia | item288 | 23116 | Each |
| 287 | 287 | Supplying, fitting and fixing PVC pipes of 6 kg/cm2 (supreme/Price) or other ISI approved including joining, fitting and fixing with clamps etc.as necessary complete at all levels including below G.L as directed and specified.\n(a) In Exposed Surface or in Trenches.\niv. 75mm dia | item289 | 5140 | Each |
| 288 | 288 | Supplying, fitting and fixing PVC pipes of 6 kg/cm2 (supreme/Price) or other ISI approved including joining, fitting and fixing with clamps etc.as necessary complete at all levels including below G.L as directed and specified.\n(a) In Exposed Surface or in Trenches.\nv. 63mm dia | item290 | 1496 | Each |
| 289 | 289 | Supplying, fitting and fixing PVC pipes of 6 kg/cm2 (supreme/Price) or other ISI approved including joining, fitting and fixing with clamps etc.as necessary complete at all levels including below G.L as directed and specified.\n(a) In Exposed Surface or in Trenches.\nvi. 50mm dia | item291 | 2654 | Each |
| 290 | 290 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\ni. 160mm dia. | item292 | 320 | Each |
| 291 | 291 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\nii. 110mm dia | item293 | 1038 | Each |
| 292 | 292 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\niv. 75mm dia | item294 | 479 | Each |
| 293 | 293 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\nv. 63mm dia | item295 | 670 | Each |
| 294 | 294 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\nvi. 50mm dia | item296 | 503 | Each |
| 295 | 295 | Supplying fitting and fixing 87.5 degree PVC bend of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\ni. 160mm dia. | item297 | 670 | Each |
| 296 | 296 | Supplying fitting and fixing 87.5 degree PVC bend of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\nii. 110mm dia | item298 | 1323 | Each |
| 297 | 297 | Supplying fitting and fixing 87.5 degree PVC bend of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\niv. 75mm dia | item299 | 479 | Each |
| 298 | 298 | Supplying fitting and fixing 87.5 degree PVC bend of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\nv.50mm dia | item300 | 492 | Each |
| 299 | 299 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\ni. 160mm dia. | item301 | 194 | Each |
| 300 | 300 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\nIi. 110mm dia | item302 | 255 | Each |
| 301 | 301 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\niv. 75mm dia | item303 | 222 | Each |
| 302 | 302 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\nv. 50mm dia | item304 | 374 | Each |
| 303 | 303 | Supplying fitting and fixing 87.5 degree PVC bend with door of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\nii. 110mm dia | item305 | 738 | Each |
| 304 | 304 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\nii. 110mm dia | item306 | 187 | Each |
| 305 | 305 | Supplying fitting and fixing 45 degree PVC bend of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\ni. 160mm dia. | item307 | 300 | Each |
| 306 | 306 | Supplying fitting and fixing 45 degree PVC bend of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\nii. 110mm dia | item308 | 632 | Each |
| 307 | 307 | Supplying fitting and fixing 45 degree PVC bend of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\niv. 75mm dia | item309 | 372 | Each |
| 308 | 308 | Supplying fitting and fixing 45 degree PVC bend of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\nv. 50mm dia | item310 | 374 | Each |
| 309 | 309 | Supplying fitting and fixing PVC plain single tee of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\ni. 160mm dia. | item311 | 469 | Each |
| 310 | 310 | Supplying fitting and fixing PVC plain single tee of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\n(a) In Exposed Surface or in Trenches.\nii. 110mm dia | item312 | 2809 | Each |
| 311 | 311 | Supplying fitting and fixing PVC plain single tee of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.Las directed and specified .\nIn Exposed Surface or in Trenches.\niv. 75 mm dia. | item313 | 741 | Each |
| 312 | 312 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\ni. 160mm dia. | item314 | 60 | Each |
| 313 | 313 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\nii. 110mm dia | item315 | 219 | Each |
| 314 | 314 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\niv. 75 mm dia. | item316 | 55 | Each |
| 315 | 315 | Supplying fitting and fixing PVC plain single tee with door of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified .\n(a)In Exposed Surface or in Trenches.\ni. 160mm dia | item317 | 104 | Each |
| 316 | 316 | Supplying fitting and fixing PVC plain single tee with door of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified .\n(a) In Exposed Surface or in Trenches.\nii. 110mm dia | item318 | 3070 | Each |
| 317 | 317 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\ni. 160mm dia | item319 | 90 | Each |
| 318 | 318 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\nIi. 110mm dia | item320 | 64 | Each |
| 319 | 319 | Supplying fitting and fixing PVC plain single Y of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified.\n(a) In Exposed Surface or in Trenches.\ni. 160mm dia. | item321 | 134 | Each |
| 320 | 320 | Supplying fitting and fixing PVC plain single Y of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified.\n(a) In Exposed Surface or in Trenches.\nii. 110mm dia | item322 | 2524 | Each |
| 321 | 321 | Supplying fitting and fixing PVC plain single Y of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified.\n(a) In Exposed Surface or in Trenches.\niv. 75 mm dia. | item323 | 289 | Each |
| 322 | 322 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\ni. 160mm dia. | item324 | 40 | Each |
| 323 | 323 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\nIi. 110mm dia | item325 | 208 | Each |
| 324 | 324 | (b) Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\niv. 75 mm dia. | item326 | 33 | Each |
| 325 | 325 | Supplying fitting and fixing PVC plain single Y with door of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified .\n(a) In Exposed Surface or in Trenches.\ni. 110mm dia | item327 | 832 | Each |
| 326 | 326 | (b)Concealed by chiselling or breaking brick wall/C.C./R.C.C and making good to the damages.\ni. 110mm dia | item328 | 398 | Each |
| 327 | 327 | Supplying fitting and fixing PVC coupler of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified .\n(a) In Exposed Surface or in Trenches.\ni. 110mm dia | item329 | 9914 | Each |
| 328 | 328 | Supplying fitting and fixing PVC coupler of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified .\n(a) In Exposed Surface or in Trenches.\nii. 75mm dia | item330 | 2304 | Each |
| 329 | 329 | Supplying fitting and fixing PVC reducing Tee of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified .\n(a) In Exposed Surface or in Trenches.\ni. 160mmx110mm | item331 | 137 | Each |
| 330 | 330 | Supplying fitting and fixing PVC reducing Tee of (Supreme/Prince) or other ISI approved including joining, fitting and fixing etc.as necessary complete at all levels including below G.L as directed and specified .\n(a) In Exposed Surface or in Trenches.\nii. 110mmx75mm | item332 | 1244 | Each |
| 331 | 331 | Supplying fiting and fixing PVC reducing Tee with door of (Supreme/Prince) or other ISI approved including joinning, fitting and fixing etc. in exposed surface or trenches as necessry complete at all levels including below G.L as directed and specified.\ni. 160mmx110mm | item333 | 37 | Each |
| 332 | 332 | Supplying fiting and fixing PVC socket plug of (Supreme/Prince) or other ISI approved including joinning, fitting and fixing etc. in exposed surface or trenches as necessry complete at all levels including below G.L as directed and specified.\n(a) 110mm | item334 | 929 | Each |
| 333 | 333 | Supplying fiting and fixing PVC socket plug of (Supreme/Prince) or other ISI approved including joinning, fitting and fixing etc. in exposed surface or trenches as necessry complete at all levels including below G.L as directed and specified.\n(b) 75mm | item335 | 174 | Each |
| 334 | 334 | Supplying fiting and fixing PVC cleaning pipe of (Supreme/Prince) or other ISI approved including joinning, fitting and fixing etc. in exposed surface or trenches as necessry complete at all levels including below G.L as directed and specified.\n(a) 160mm | item336 | 80 | Each |
| 335 | 335 | Supplying fiting and fixing PVC cleaning pipe of (Supreme/Prince) or other ISI approved including joinning, fitting and fixing etc. in exposed surface or trenches as necessry complete at all levels including below G.L as directed and specified.\n(b) 110mm | item337 | 429 | Each |
| 336 | 336 | Providing fitting and fixing PVC of cowel of ISI make complete as directed and specified .\ni. 110mm dia . PVC cowel of ISI make | item338 | 405 | Each |
| 337 | 337 | Providing fitting and fixing PVC of cowel of ISI make complete as directed and specified .\nIi. 75mm dia . PVC cowel of ISI make | item339 | 149 | Each |
| 338 | 338 | C.P. Grating.\ni. 160mm | item340 | 128 | Each |
| 339 | 339 | C.P. Grating.\nii. 110mm | item341 | 3181 | Each |
| 340 | 340 | Providing and fixing uPVC P-Trap including setting with cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 hand stone ballast 20 MM nominal size) the inlet from floor level to trap rim to be grouted and cemented neat manner including cutting and making good the floor & wall wherever requiredcomplete in all respects.\n110 mm inlet and 110 mm outlet. | item342 | 2435 | Each |
| 341 | 341 | Providing and fixing cast brass clean out plug with suitable insert keys for opening, male threaded joint with PP/ uPVC female threaded socket caulked to PP/ uPVC pipe including cost of Solvent cement or Other Joint.\n100 mm dia | item343 | 1450 | Each |
| 342 | 342 | Providing and fixing cast brass clean out plug with suitable insert keys for opening, male threaded joint with PP/ uPVC female threaded socket caulked to PP/ uPVC pipe including cost of Solvent cement or Other Joint.\n150 mm dia | item344 | 80 | Each |
| 343 | 343 | Providing and fixing in position 110x63 mm OD uPVC reducing elbow including fix to floor with cement mortar. | item345 | 746 | Each |
| 344 | 344 | Providing and fixing 110 mm OD uPVC inlet fitting/ Extension Piece with 2 or 3 inlets of 40 to 63 mm OD, fixed to uPVC trap with solvent cement joint and set in cement concrete as per drawing complete. | item346 | 2435 | Each |
| 345 | 345 | Water Supply System\nSupplying fitting and fixing CPVC (Chlorinated Polyvinyl Chloride) pipes having thermal stability for hot and cold water supply including all CPVC Plain and bruss threaded fitting including clamps at 1.00 m spacing including joining of pipes and fitting with one step CPVC solvent cement and testing of joints complete at all levels as directed and spcified.\n(Note: Ball Valve and union will be charged extra and does not comes under Accessories).\n(i) In internal Wall - Exposed on Wall\n(b) 20 mm OD | item347 | 6225 | Metre |
| 346 | 346 | Supplying fitting and fixing CPVC (Chlorinated Polyvinyl Chloride) pipes having thermal stability for hot and cold water supply including all CPVC Plain and bruss threaded fitting including clamps at 1.00 m spacing including joining of pipes and fitting with one step CPVC solvent cement and testing of joints complete at all levels as directed and spcified.\n(Note: Ball Valve and union will be charged extra and does not comes under Accessories).\ni. In internal Wall - Exposed on Wall\n(c) 25 mm OD | item348 | 1865 | Metre |
| 347 | 347 | Supplying fitting and fixing CPVC (Chlorinated Polyvinyl Chloride) pipes having thermal stability for hot and cold water supply including all CPVC Plain and bruss threaded fitting including clamps at 1.00 m spacing including joining of pipes and fitting with one step CPVC solvent cement and testing of joints complete at all levels as directed and spcified.\n(Note: Ball Valve and union will be charged extra and does not comes under Accessories).\ni. In internal Wall - Exposed on Wall\n(d) 32mm OD | item349 | 1366 | Metre |
| 348 | 348 | Supplying fitting and fixing CPVC (Chlorinated Polyvinyl Chloride) pipes having thermal stability for hot and cold water supply including all CPVC Plain and bruss threaded fitting including clamps at 1.00 m spacing including joining of pipes and fitting with one step CPVC solvent cement and testing of joints complete at all levels as directed and spcified.\n(Note: Ball Valve and union will be charged extra and does not comes under Accessories).\ni. In internal Wall - Exposed on Wall\n(e) 40 mm OD | item350 | 700 | Metre |
| 349 | 349 | Supplying fitting and fixing CPVC (Chlorinated Polyvinyl Chloride) pipes having thermal stability for hot and cold water supply including all CPVC Plain and bruss threaded fitting including clamps at 1.00 m spacing including joining of pipes and fitting with one step CPVC solvent cement and testing of joints complete at all levels as directed and spcified.\n(Note: Ball Valve and union will be charged extra and does not comes under Accessories).\ni. In internal Wall - Exposed on Wall\n(f) 50 mm OD | item351 | 489 | Metre |
| 350 | 350 | Suppling fitting and fixing G.I pipes of following sizes, with all necessary 'R' brand or similar approved G.I. fittings such as bend,tee,elbow, reducer,nipple,plug,long screw fitting,H.W. clamps etc. complete at all levels including below G.L as directed and specified.\n(A) Exposed on Walls\n(a) 50 mm dia (medium)\ni. Using Tata make | item352 | 3614 | RM |
| 351 | 351 | Suppling fitting and fixing G.I pipes of following sizes, with all necessary 'R' brand or similar approved G.I. fittings such as bend,tee,elbow, reducer,nipple,plug,long screw fitting,H.W. clamps etc. complete at all levels including below G.L as directed and specified.\n(A) Exposed on Walls\n(b) 40 mm dia (medium)\ni. Using Tata make | item353 | 2310 | RM |
| 352 | 352 | Suppling fitting and fixing G.I pipes of following sizes, with all necessary 'R' brand or similar approved G.I. fittings such as bend,tee,elbow, reducer,nipple,plug,long screw fitting,H.W. clamps etc. complete at all levels including below G.L as directed and specified.\n(A) Exposed on Walls\n(c) 32 mm dia (medium)\ni. Using Tata make | item354 | 1874 | RM |
| 353 | 353 | Suppling fitting and fixing G.I pipes of following sizes, with all necessary 'R' brand or similar approved G.I. fittings such as bend,tee,elbow, reducer,nipple,plug,long screw fitting,H.W. clamps etc. complete at all levels including below G.L as directed and specified.\n(A) Exposed on Walls\n(d) 25 mm dia (medium)\ni. Using Tata make | item355 | 1696 | RM |
| 354 | 354 | Suppling fitting and fixing G.I pipes of following sizes, with all necessary 'R' brand or similar approved G.I. fittings such as bend,tee,elbow, reducer,nipple,plug,long screw fitting,H.W. clamps etc. complete at all levels including below G.L as directed and specified.\n(A) Exposed on Walls\n(e) 20 mm dia (medium)\ni. Using Tata make | item356 | 1153 | RM |
| 355 | 355 | Providing and fixing Chlorinated polyvinyle Chlorinated polyvinyle chloride (CPVC)Pipes, having thermal stability for hot and cold water supply including all CPVC plain with brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing .This includes jointig of pipes.\n(B) Concealed pipe with cutting chase & making good the walls\n(a) 15 mm OD | item357 | 10989 | RM |
| 356 | 356 | Providing and fixing Chlorinated polyvinyle Chlorinated polyvinyle chloride (CPVC)Pipes, having thermal stability for hot and cold water supply including all CPVC plain with brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing .This includes jointig of pipes.\n(B) Concealed pipe with cutting chase & making good the walls\n(b) 20 mm OD | item358 | 10834 | RM |
| 357 | 357 | Providing and fixing Chlorinated polyvinyle Chlorinated polyvinyle chloride (CPVC)Pipes, having thermal stability for hot and cold water supply including all CPVC plain with brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing .This includes jointig of pipes.\n(B) Concealed pipe with cutting chase & making good the walls\n(c) 25 mm OD | item359 | 4339 | RM |
| 358 | 358 | Providing and fixing Chlorinated polyvinyle Chlorinated polyvinyle chloride (CPVC)Pipes, having thermal stability for hot and cold water supply including all CPVC plain with brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing .This includes jointig of pipes.\n(B) Concealed pipe with cutting chase & making good the walls\n(d) 32mm OD | item360 | 648 | RM |
| 359 | 359 | Providing and fixing Chlorinated polyvinyle Chlorinated polyvinyle chloride (CPVC)Pipes, having thermal stability for hot and cold water supply including all CPVC plain with brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing .This includes jointig of pipes.\n(B) Concealed pipe with cutting chase & making good the walls\n(e) 40 mm OD | item361 | 578 | RM |
| 360 | 360 | Providing and fixing Chlorinated polyvinyle Chlorinated polyvinyle chloride (CPVC)Pipes, having thermal stability for hot and cold water supply including all CPVC plain with brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing .This includes jointig of pipes.\n(B) Concealed pipe with cutting chase & making good the walls\n(f) 50 mm OD | item362 | 543 | RM |
| 361 | 361 | Supplying fitting and fixing pipes with all necessary fitings in exposed or in treches including trenching and refilling the same etc complete as directed.\n(A) G.I pipe with GI fitting\n(a) TATA / SAIL (Medium)\niii. 25mm diameter | item363 | 11 | Rm |
| 362 | 362 | Supplying fitting and fixing pipes with all necessary fitings in exposed or in treches including trenching and refilling the same etc complete as directed.\n(A) G.I pipe with GI fitting\n(a) TATA / SAIL (Medium)\niv. 32 mm diameter | item364 | 280 | Rm |
| 363 | 363 | Supplying fitting and fixing pipes with all necessary fitings in exposed or in treches including trenching and refilling the same etc complete as directed.\n(A) G.I pipe with GI fitting\n(a) TATA / SAIL (Medium)\nv. 40 mm diameter | item365 | 305 | Rm |
| 364 | 364 | Supplying fitting and fixing pipes with all necessary fitings in exposed or in treches including trenching and refilling the same etc complete as directed.\n(A) G.I pipe with GI fitting\n(a) TATA / SAIL (Medium)\nvi. 50mm diameter | item366 | 630 | Rm |
| 365 | 365 | Supplying fitting and fixing pipes with all necessary fitings in exposed or in treches including trenching and refilling the same etc complete as directed.\n(A) G.I pipe with GI fitting\n(a) TATA / SAIL (Medium)\nvii. 65mm diameter | item367 | 4643 | Rm |
| 366 | 366 | Supplying fitting and fixing pipes with all necessary fitings in exposed or in treches including trenching and refilling the same etc complete as directed.\n(A) G.I pipe with GI fitting\n(a) TATA / SAIL (Medium)\nviii. 80mm diameter | item368 | 3886 | Rm |
| 367 | 367 | Supplying fitting and fixing pipes with all necessary fitings in exposed or in treches including trenching and refilling the same etc complete as directed.\n(A) G.I pipe with GI fitting\n(a) TATA / SAIL (Medium)\nix. 100 mm diameter | item369 | 3360 | Rm |
| 368 | 368 | Supplying fitting and fixing pipes with all necessary fitings in exposed or in treches including trenching and refilling the same etc complete as directed.\nG.I pipe with GI fitting\nTATA / SAIL (Medium)\n150 mm diameter | item370 | 470 | Rm |
| 369 | 369 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :\nWith common burnt clay F.P.S.(non modular) bricks of class designation 7.5 | item371 | 13 | Each |
| 370 | 370 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :\nWith common burnt clay F.P.S.(non modular) bricks of class designation 7.5 | item372 | 3 | Each |
| 371 | 371 | Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :\n20 mm dia nominal bore | item373 | 1153 | Metre |
| 372 | 372 | Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :\n25 mm dia nominal bore | item374 | 1696 | Metre |
| 373 | 373 | Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :\n32 mm dia nominal bore | item375 | 1874 | Metre |
| 374 | 374 | Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :\n40 mm dia nominal bore | item376 | 2310 | Metre |
| 375 | 375 | Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :\n50 mm dia nominal bore | item377 | 3259 | Metre |
| 376 | 376 | Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :\n65 mm dia. nominal bore | item378 | 4393 | Metre |
| 377 | 377 | Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :\n80 mm dia. nominal bore | item379 | 3028 | Metre |
| 378 | 378 | Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :\n100 mm dia. nominal bore | item380 | 2225 | Metre |
| 379 | 379 | Painting G.I. pipes and fittings with two coats of anticorrosive bitumastic paint of approved quality.\n25mm diameter | item381 | 10 | Metre |
| 380 | 380 | Painting G.I. pipes and fittings with two coats of anticorrosive bitumastic paint of approved quality.\n32 mm diameter | item382 | 280 | Metre |
| 381 | 381 | Painting G.I. pipes and fittings with two coats of anticorrosive bitumastic paint of approved quality.\n40 mm diameter | item383 | 305 | Metre |
| 382 | 382 | Painting G.I. pipes and fittings with two coats of anticorrosive bitumastic paint of approved quality.\n50mm diameter | item384 | 330 | Metre |
| 383 | 383 | Painting G.I. pipes and fittings with two coats of anticorrosive bitumastic paint of approved quality.\n65mm diameter | item385 | 4643 | Metre |
| 384 | 384 | Painting G.I. pipes and fittings with two coats of anticorrosive bitumastic paint of approved quality.\n80 mm dia. nominal bore | item386 | 3828 | Metre |
| 385 | 385 | Painting G.I. pipes and fittings with two coats of anticorrosive bitumastic paint of approved quality.\n100 mm dia. nominal bore | item387 | 3275 | Metre |
| 386 | 386 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work :\n25 mm dia nominal bore | item388 | 20 | Metre |
| 387 | 387 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work :\n32 mm dia nominal bore | item389 | 175 | Metre |
| 388 | 388 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work :\n40 mm dia nominal bore | item390 | 195 | Metre |
| 389 | 389 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work :\n50 mm dia nominal bore | item391 | 260 | Metre |
| 390 | 390 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work :\n65 mm dia nominal bore | item392 | 310 | Metre |
| 391 | 391 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work :\n80 mm dia. nominal bore | item393 | 840 | Metre |
| 392 | 392 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work :\n100 mm dia. nominal bore | item394 | 1090 | Metre |
| 393 | 393 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :\n20mm nominal bore | item395 | 972 | Each |
| 394 | 394 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :\n25mm nominal bore | item396 | 217 | Each |
| 395 | 395 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :\n32mm nominal bore | item397 | 277 | Each |
| 396 | 396 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :\n40mm nominal bore | item398 | 146 | Each |
| 397 | 397 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :\n50mm nominal bore | item399 | 142 | Each |
| 398 | 398 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :\n65mm nominal bore | item400 | 57 | Each |
| 399 | 399 | Butterfly valve (manual) with C.I body SS disc nitrile sheet & O ring & PN 16 Pressure rating as specified .\n65 mm dia | item401 | 68 | Each |
| 400 | 400 | Butterfly valve (manual) with C.I body SS disc nitrile sheet & O ring & PN 16 Pressure rating as specified .\n80 mm dia | item402 | 47 | Each |
| 401 | 401 | Butterfly valve (manual) with C.I body SS disc nitrile sheet & O ring & PN 16 Pressure rating as specified .\n100 mm dia | item403 | 20 | Each |
| 402 | 402 | Supplying and fixing in position of approved quality Solenoid Valve with by-pass arrangement, isolation cock etc. complete with all required accessories such as level sensor, level indicator, level controller and required cabling for the same.\n25 mm dia | item404 | 10 | Each |
| 403 | 403 | Supplying and fixing in position of approved quality Solenoid Valve with by-pass arrangement, isolation cock etc. complete with all required accessories such as level sensor, level indicator, level controller and required cabling for the same.\n32 mm dia | item405 | 19 | Each |
| 404 | 404 | Supplying and fixing in position of approved quality Solenoid Valve with by-pass arrangement, isolation cock etc. complete with all required accessories such as level sensor, level indicator, level controller and required cabling for the same.\n40 mm dia | item406 | 21 | Each |
| 405 | 405 | Supplying and fixing in position of approved quality Solenoid Valve with by-pass arrangement, isolation cock etc. complete with all required accessories such as level sensor, level indicator, level controller and required cabling for the same.\n50 mm dia | item407 | 12 | Each |
| 406 | 406 | Supplying and fixing in position of approved quality Solenoid Valve with by-pass arrangement, isolation cock etc. complete with all required accessories such as level sensor, level indicator, level controller and required cabling for the same.\n65 mm dia | item408 | 6 | Each |
| 407 | 407 | Supplying and fixing in position of approved quality Solenoid Valve with by-pass arrangement, isolation cock etc. complete with all required accessories such as level sensor, level indicator, level controller and required cabling for the same.\n80 mm dia | item409 | 6 | Each |
| 408 | 408 | Supplying and fixing in position of approved quality Solenoid Valve with by-pass arrangement, isolation cock etc. complete with all required accessories such as level sensor, level indicator, level controller and required cabling for the same.\n100 mm dia | item410 | 6 | Each |
| 409 | 409 | Providing and fixing Thermoflex or Kaiflex thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber over pipes of following nominal bores and thickness including protection by wrapping with 24 gauge alumminium sheet with riveted screw joints all required accessories complete as per specification.\n13 mm thick (Exposed Pipes)\nFor 20 mm dia Pipe | item411 | 1657 | Metre |
| 410 | 410 | Providing and fixing Thermoflex or Kaiflex thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber over pipes of following nominal bores and thickness including protection by wrapping with 24 gauge alumminium sheet with riveted screw joints all required accessories complete as per specification.\n13 mm thick (Exposed Pipes)\nFor 25 mm dia Pipe | item412 | 1019 | Metre |
| 411 | 411 | Providing and fixing Thermoflex or Kaiflex thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber over pipes of following nominal bores and thickness including protection by wrapping with 24 gauge alumminium sheet with riveted screw joints all required accessories complete as per specification.\n13 mm thick (Exposed Pipes)\nFor 32 mm dia Pipe | item413 | 634 | Metre |
| 412 | 412 | Providing and fixing Thermoflex or Kaiflex thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber over pipes of following nominal bores and thickness including protection by wrapping with 24 gauge alumminium sheet with riveted screw joints all required accessories complete as per specification.\n13 mm thick (Exposed Pipes)\nFor 40 mm dia Pipe | item414 | 604 | Metre |
| 413 | 413 | Providing and fixing Thermoflex or Kaiflex thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber over pipes of following nominal bores and thickness including protection by wrapping with 24 gauge alumminium sheet with riveted screw joints all required accessories complete as per specification.\n13 mm thick (Exposed Pipes)\nFor 50 mm dia Pipe | item415 | 655 | Metre |
| 414 | 414 | Providing and fixing Thermoflex or Kaiflex thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber over pipes of following nominal bores and thickness including protection by wrapping with 24 gauge alumminium sheet with riveted screw joints all required accessories complete as per specification.\n13 mm thick (Exposed Pipes)\nFor 65 mm dia Pipe | item416 | 1165 | Metre |
| 415 | 415 | Providing and fixing Thermoflex or Kaiflex thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber over pipes of following nominal bores and thickness including protection by wrapping with 24 gauge alumminium sheet with riveted screw joints all required accessories complete as per specification.\n13 mm thick (Exposed Pipes)\nFor 80 mm dia Pipe | item417 | 1350 | Metre |
| 416 | 416 | Providing and fixing Thermoflex or Kaiflex thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber over pipes of following nominal bores and thickness including protection by wrapping with 24 gauge alumminium sheet with riveted screw joints all required accessories complete as per specification.\n13 mm thick (Exposed Pipes)\nFor 100 mm dia Pipe | item418 | 60 | Metre |
| 417 | 417 | Providing and fixing forged brass single acting air release valve with screwed inlet 25 mm dia. | item419 | 6 | Each |
| 418 | 418 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.)\n25mm dia pipe, 600mm long with size of 250x250x6 mm MS plate | item420 | 8 | Each |
| 419 | 419 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.)\n32mm dia pipe, 600mm long with size of 250x250x6 mm MS plate | item421 | 22 | Each |
| 420 | 420 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.)\n40mm dia pipe, 600mm long with size of 300x300x6 mm MS plate | item422 | 22 | Each |
| 421 | 421 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.)\n50mm dia pipe, 600mm long with size of 350x350x6 mm MS plate | item423 | 70 | Each |
| 422 | 422 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.)\n65mm dia pipe, 600mm long with size of 350x350x6 mm MS plate | item424 | 24 | Each |
| 423 | 423 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.)\n80mm dia pipe, 600mm long with size of 400x400x6 mm MS plate | item425 | 56 | Each |
| 424 | 424 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.)\n100mm dia pipe, 600mm long with size of 400x400x6 mm MS plate | item426 | 106 | Each |
| 425 | 425 | Providing and fixing M.S fabricated hot dipped galvanized coating puddle flange comprising of 600 mm dia long M.S class 'B' pipe (screwed end up to 50 mm & flange for more than 50 mm dia) with 6 mm thick M.S plates of required size including cutting holes in centre of plate, inserting pipe & making welded (Arc) joint complete. Same shall be installed with TEC welded joint in position with reinforcement bars of RCC tank wall/slab including making cutout in shuttering during concrete casting of tank of following diameter. (Location: Underground / Overhead Tanks.)\n150mm dia pipe, 600mm long with size of 450x450x6 mm MS plate | item427 | 12 | Each |
| 426 | 426 | Solar Water Heating System (FOR TB HOSPITAL) :\nSupply, installion, testing and commissioning of Hot Water Generation Plant with Packaged type Air to Water Heat Pump. These units shall be completely factory assembled including 2 Nos. Scroll Hermatically Sealed Scroll Compressor(s), evaporator, Condenser and Microprocessor Control Panel etc with R410 Referigerant and COP between 3-4. The Heat Pump shall have inbuilt hot water heat exchanger, pumps, valves. expansion valve, integrated CIP system and other accessories.The Heat Pump should be capable of producing hot water at minimum 60°C temperaure at outlet (condenser circuit) temperatures at 10°C ?T. The Machine should have an operating ambient temperature range of 5°C to 40°C. Location: Terrace Level.\na. Built in electric panel as per safety norms as manufacturer standard.\nb. All other mountings, fittings & controls with all accessories and safeties\nc. All other mounting, fittings and controls.\nd. Suitable for electric supply of 415 + 10% volts & 50 Hz.\ne. All interconnecting wiring / cabling between heat pump and electrical panel.\nf. The Heat pump shall have an in-built facility to start / stop depending on variation in demand at different periods.\ng. System shall be complete with SS 304 Tank of 2 Hrs Storage Capacity, Primary and Seconary Circualtion pumps, Heat Exchangers, Return Recirculation Pump, interconnecting piping, valves and all accessories as required.\nh. System shall have 20% of total capacity in electrical heating as standby.\ni. System shall have an integrated Solar Heating system with 20% of total capacity for energy saving including Flat Plate Solar Panels, Mixing Tanks, Recirculation Pumps, etc\nFor Hospital\nHeating capacity : Approx. 150 KW (4 working + 1 standby) For Hospital\nHot Water Storage Tank : 11000 Ltrs\nSystem as Described Above | item428 | 2 | Set |
| 427 | 427 | For Solar Water Heating System-500 LPD\nProviding and fixing Solar Hot Water indirect Heating System using heating liquid medium comprising of flat plate solar panels, including all interconnecting insulated G.I. piping, pressure type insulated hot water tank, , outlet, Y stainer and a water meter on the inlet, air release valve all mounted on galvanized MS sections complete with connection with the existing piping. Comparising of following:-\nFive Nos of. flat plate solar collector panels of 10 Sqm size approx. the panels enclosed in insulated collector boxes with single piece toughned glass 4 mm thick and fixed with heat resistant gasket.\nOne Lot of Inter-connected insulated G.I. piping insulated with 9 mm thick nitrile rubber heat resitant insulation sections ( Vidoflex or equiv.) and valves with outer mechanical protection of aluminium sheet cladding.\nSolar Water Heating System as Describe Above | item429 | 19 | Set |
| 428 | 428 | Solar Water Heating System (FOR MMCH HOSPITAL) :\nSupply, installion, testing and commissioning of Hot Water Generation Plant with Packaged type Air to Water Heat Pump. These units shall be completely factory assembled including 2 Nos. Scroll Hermatically Sealed Scroll Compressor(s), evaporator, Condenser and Microprocessor Control Panel etc with R410 Referigerant and COP between 3-4. The Heat Pump shall have inbuilt hot water heat exchanger, pumps, valves. expansion valve, integrated CIP system and other accessories.The Heat Pump should be capable of producing hot water at minimum 60°C temperaure at outlet (condenser circuit) temperatures at 10°C ?T. The Machine should have an operating ambient temperature range of 5°C to 40°C. Location: Terrace Level.\na. Built in electric panel as per safety norms as manufacturer standard.\nb. All other mountings, fittings & controls with all accessories and safeties\nc. All other mounting, fittings and controls.\nd. Suitable for electric supply of 415 + 10% volts & 50 Hz.\ne. All interconnecting wiring / cabling between heat pump and electrical panel.\nf. The Heat pump shall have an in-built facility to start / stop depending on variation in demand at different periods.\ng. System shall be complete with SS 304 Tank of 2 Hrs Storage Capacity, Primary and Seconary Circualtion pumps, Heat Exchangers, Return Recirculation Pump, interconnecting piping, valves and all accessories as required.\nh. System shall have 20% of total capacity in electrical heating as standby.\ni. System shall have an integrated Solar Heating system with 20% of total capacity for energy saving including Flat Plate Solar Panels, Mixing Tanks, Recirculation Pumps, etc\nFor Hospital\nHeating capacity : Approx. 200 KW (4 working + 1 standby) For Hospital\nHot Water Storage Tank : 15000 Ltrs\nSystem as Described Above | item430 | 1 | Set |
| 429 | 429 | Providing, laying and jointing glazed stoneware pipes grade 'A' with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete.\n150 mm diameter | item431 | 2525 | Metre |
| 430 | 430 | Providing, laying and jointing glazed stoneware pipes grade 'A' with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete.\n200 mm diameter | item432 | 1010 | Metre |
| 431 | 431 | Providing, laying and jointing glazed stoneware pipes grade 'A' with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete.\n250 mm diameter | item433 | 540 | Metre |
| 432 | 432 | Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design :\n180 x 150mm size P-type\nWith Sewer bricks conforming to IS : 4885 | item434 | 254 | Each |
| 433 | 433 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :\nInside size 90 x 80 cm and 45 cm deep including CI cover with frame (light duty) 455 x 610mm internal dimensiions total weight of cover and frame to be not less than 38 Kg. ( weight of cover 23 Kg. and weight of frame 15 Kg.), with FPS bricks with class designation 7.5.\nWith Sewer bricks conforming to IS : 4885 | item435 | 255 | Each |
| 434 | 434 | Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg) :\nWith Sewer bricks conforming to IS : 4885 | item436 | 53 | Each |
| 435 | 435 | Extra for depth for manholes:\nSize 90 x 80 cm\nWith Sewer bricks conforming to IS : 4885 | item437 | 24 | Metre |
| 436 | 436 | Size 120x90 cm\nWith Sewer bricks conforming to IS : 4885 | item438 | 5 | Metre |
| 437 | 437 | Constructing brick masonary circular type manhole 0.91m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand) in side cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1 :3:6 mix (1 cement : 3 coarse sand : 6 graded 40mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement all complete as per standard design:\n0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560mm internal diameter confirming to I.S. 12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) :\nWith Sewer bricks conforming IS : 4885 | item439 | 50 | Each |
| 438 | 438 | Extra depth for circular type manhole 0.91m internal dia (at bottom) with beyond 0.91m to 1.67m.\nWith Sewer bricks conforming IS : 4885 | item440 | 13 | Metre |
| 439 | 439 | Constructing brick masonry circular manhole 1.22m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement plaster 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :\n1.68 m deep with SFRC Cover and frame (heavy duty HD-20 grade designation) 560mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) :\nWith Sewer bricks conforming IS : 4885 | item441 | 18 | Each |
| 440 | 440 | Extra depth for circular type manhole 1.22m internal dia (at bottom) beyond 1.68 m to 2.29 m :\nWith Sewer bricks conforming IS : 4885 | item442 | 6 | Metre |
| 441 | 441 | Constructing brick masonry circular manhole 1.52 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :\n2.30 m deep with SFRC Cover and frame (heavy duty HD-20 grade designation) 560mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) :\nWith Sewer bricks conforming IS : 4885 | item443 | 8 | Each |
| 442 | 442 | Extra depth for circular type manhole 1.52 m internal dia (at bottom) beyond 2.30 m :\nWith Sewer bricks conforming IS : 4885 | item444 | 2 | Metre |
| 443 | 443 | Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS : 1786 having minimum cross section as 23 mmx25mm and over all minimum length 263 mm and width as 165mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. | item445 | 1502 | Each |
| 444 | 444 | Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement and making necessary channels for the drain etc. complete :\nFor pipes 250 to 300 mm diameter | item446 | 2 | Each |
| 445 | 445 | Providing and Installing Grease Separator EasyClean ground Standard NS 2\nBased on Euro-Norm EN 1825-1 Manufactured from Polyethylene. For underground installation, installation depth 550 - 950 mm, with integrated sludge trap, polymer upper section, vertically adjustable, rotatable and tiltable up to 5°, cast iron cover in load class B based on EN 124, odor tight.\nØ 110 in- and outlet according to DIN 19534\nSludge trap capacity: 200 l\nTotal separator capacity: 370 l\nFat storage: 120 l\nCertification: Z-54.1-440\nWeight: 120 kg\nDimension: 1470 x 1300 mm\nInspection chambers may be installed in a maximum of 500 mm groundwater. | item447 | 3 | Each |
| 446 | 446 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :\n150 mm dia. R.C.C. pipe | item448 | 1335 | Metre |
| 447 | 447 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :\n250 mm dia. R.C.C. pipe | item449 | 945 | Metre |
| 448 | 448 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :\n300 mm dia. R.C.C. pipe | item450 | 450 | Metre |
| 449 | 449 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :\n450 mm dia. R.C.C. pipe | item451 | 400 | Metre |
| 450 | 450 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :\n600 mm dia. R.C.C. pipe | item452 | 280 | Metre |
| 451 | 451 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :\n700 mm dia. R.C.C. pipe | item453 | 170 | Metre |
| 452 | 452 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :\n800 mm dia. R.C.C. pipe | item454 | 50 | Metre |
| 453 | 453 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :\n900 mm dia. R.C.C. pipe | item455 | 25 | Metre |
| 454 | 454 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :\n1000 mm dia. R.C.C. pipe | item456 | 15 | Metre |
| 455 | 455 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :\nInside size 90 x 80 cm and 45 cm deep including CI cover with frame (light duty) 455 x 610mm internal dimensiions total weight of cover and frame to be not less than 38 Kg. ( weight of cover 23 Kg. and weight of frame 15 Kg.), with FPS bricks with class designation 7.5.\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item457 | 84 | Each |
| 456 | 456 | Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg) :\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item458 | 15 | Each |
| 457 | 457 | Extra for depth for manholes:\nSize 90 x 80 cm\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item459 | 9 | Metre |
| 458 | 458 | Size 120x90 cm\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item460 | 5 | Metre |
| 459 | 459 | Constructing brick masonary circular type manhole 0.91m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand) in side cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1 :3:6 mix (1 cement : 3 coarse sand : 6 graded 40mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement all complete as per standard design:\n0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560mm internal diameter confirming to I.S. 12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) :\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item461 | 18 | Each |
| 460 | 460 | Extra depth for circular type manhole 0.91m internal dia (at bottom) with beyond 0.91m to 1.67m.\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item462 | 1 | Metre |
| 461 | 461 | Constructing brick masonry circular manhole 1.22m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement plaster 12mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :\n1.68 m deep with SFRC Cover and frame (heavy duty HD-20 grade designation) 560mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) :\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item463 | 9 | Each |
| 462 | 462 | Extra depth for circular type manhole 1.22m internal dia (at bottom) beyond 1.68 m to 2.29 m :\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item464 | 1 | Metre |
| 463 | 463 | Constructing bricks masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design :\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item465 | 173 | Each |
| 464 | 464 | Extra for depth beyond 45 cm of brick masonry chamber\nFor 455x610 mm size\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | item466 | 38 | Metre |
| 465 | 465 | Providing and fixing in position precast RCC manhole cover and frame of required shape and approved quality.\nHD-20 circular shape 560 mm internal diameter. | item467 | 28 | Each |
| 466 | 466 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer –in-charge, upto 90 metre depth below ground level.\nAll types of soil\n400 mm dia. | item468 | 880 | Metre |
| 467 | 467 | Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer –in-charge.\n200 mm nominal size dia. | item469 | 660 | Metre |
| 468 | 468 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. | item470 | 220 | Metre |
| 469 | 469 | Supplying, filling, spreading & levelling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. | item471 | 140 | Cum |
| 470 | 470 | Supplying, filling, spreading & levelling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. | item472 | 210 | Cum |
| 471 | 471 | Supplying, filling, spreading & levelling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer –in-charge. | item473 | 140 | Cum |
| 472 | 472 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. | item474 | 248 | Cum |
| 473 | 473 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \"V\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. | item475 | 432 | Hours |
| 474 | 474 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of:\n200 mm dia | item476 | 60 | Each |
| 475 | 475 | Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete.\n200 mm Clamp. | item477 | 32 | Each |
| 476 | 476 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer –in-charge, beyond 90 metre & upto 150 metre depth below ground level.\nAll types of soil\n400 mm dia | item478 | 80 | Metre |
| 477 | 477 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I).\n200 mm dia | item479 | 4 | Each |
| 478 | 478 | Providing and fixing 80 mm dia. GI pipes complete (IS:1239 Heavy Class) with GI fittings and clamps including MS pipe supports, enamel paint as per specifications cutting and making good the walls etc. complete. | item480 | 370 | Metre |
| 479 | 479 | Supply, Lowering, installation & testing of KSB make submersible pumping set with 7.5 HP motor 4 stage pump suitable for 20/26/30/38/40/45/50 m3 hr. at 42/38/36/32/29/25/20 mtr. Head respectively. With Three Phase. (Model: 273/4) | item481 | 4 | Each |
| 480 | 480 | Providing & fixing cable 6 sq.mm. From submersible pump to panel board. | item482 | 400 | Metre |
| 481 | 481 | Providing & fixing Panel Board for submersible pump fitted with DOL starter ammeter, voltmeter single phase preventer standard/indo/cop make MCB of off switch push bottom duly wired and made out of 16/18 SWG sheet. | item483 | 4 | Each |
| 482 | 482 | Non - return valve with dual plate of CI Body SS plates vulcanized NBR seal flanged end & PN 16 rating as specified.\n80 mm dia. | item484 | 8 | Each |
| 483 | 483 | Sewage Treatment Plant 450 KLD ( SBR Technology ) for TB Hospital\nNote : All Civil Works with Structural Walk Ways/ Railings, General Lighting and Ventilation to be Done by Client/Owner.\nDesign, Supplying, of Sewage Treatment Plant capacity 450 KLD .(excluding excavation, back filling & disposal of surplus earth /Civil construction work) for the following duty:\nNature of effluent - Office Building Sewage from Toilet use , kitchen waste and other areas of office buildings.\nIncoming parameters:\npH - 6 - 8.5\nBOD5 - upto 250-350 Mg/L\nS. Solids - 250 - 400 Mg/L\nCOD - upto 450-600 Mg/L\nOil & Grease - 50-100 Mg / L\nFinal effluent discharge standard after treatment\npH - 6.0 - 8 After UF 6-8\nBOD5 - Less than 10 Mg/L After UF <4\nS. Solids - Less than 30 Mg/L After UF <2\nCOD - Less than 60 Mg/L After UF <30\nOil & Grease - Less than 5 Mg/L After UF <Nil\n\nSupply of 2 Nos Manual Stainless Steel Bar Screen with suitable lifting arrangement for required sizes (size 1000 mm wide x 1000 mm high) approx. (Item for Both the STP) | item485 | 4 | Nos |
| 484 | 484 | Supply, installation, testing & commissioning of Mechanical roto brush Fine Screen having 3 mm opening. (Item for Both the STP) | item486 | 2 | Set |
| 485 | 485 | Supply, installation, testing & commissioning of electronic type level indicator and controller for automatic operation of the system with high/low level alarm complete with auxiliary NO/NC contacts.\n(Item for Both the STP) | item487 | 2 | Each |
| 486 | 486 | Supply, installation, testing & commissioning of non clog open impeller type pumps, having CI casing & CI impeller complete with all accessories, motor of required capacity. Delivery header with isolation valve and NRV, lifting arrangement, pressure gauge on delivery line with isolation cock level controller with wiring to control the level of sump automatically. Pump shall have following duty for reference and vendor to confirm on design base.\nSubmersible Sewage Transfer Pumps 2 Nos. (1 Working + 1 Standby )\n(Solid Handling Cap. 35 mm)\nFlow rate (each) = 25 M3 / Hr\nHead = 10 Mtr\n | item488 | 1 | Set |
| 487 | 487 | Supply, installation, testing & commissioning of non clogging submersible type Return Activated Sludge Pumps and Secondary Activated pumps(RAS and SAS Pumps) having CI casing & CI impeller complete with and foundation bolt and lifting arrangement with all accessories, motor of required capacity. pressure gauge on delivery line with isolation cock, level controller to control the level of sump automatically. Pumps shall have following duty: Pumps 2 Nos. (1 Working + 1 Standby )\n(Solid handling cap. 8.5 mm)\nFlow rate (each) = 15m3 / hr\nHead = 12 Mtr\nCost shall be inclusive of PVC flexible Hose pipe ( for piping submerged in effluent) with M S epoxy piping (for piping non-submerged in effluent) | item489 | 1 | Set |
| 488 | 488 | Provision of guide ropes to guide submersible pump from upper level to operational level in sump basin with channels / angle section of MSEP shall be made by the STP contractor.\nAir diffusion system shall include the following: | item490 | 1 | Lot |
| 489 | 489 | Twin type rotary air blowers 2 Nos. (1 W + 1 S) Capable of delivering 450 cum/hr (each) of free air at 0.6 kg/cm2 driven through “V” belt or directly coupled through flexible coupling to a TEFCmotor of suitable HP Suitable for 415 ± 10% volts, 3 phase, 50 cycles a/c supply | item491 | 2 | Each |
| 490 | 490 | Air piping shall comprise of pipes droppers/ laterals with M S (epoxy coated) Header complete with all fittings such as tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc cutting chases & making good in Plant Room. All submerged piping will be SS-304 | item492 | 1 | Lot |
| 491 | 491 | Non clog type air dispersion system capable of handling 3-5 cfm of air with oxygen transfer efficiency of 3-4% per/meter water depth. Air dispersion grid shall be assembled in modular form so that they can be replaced / repaired Fine /coarse aeration bubble diffusers as required.\nFor equalization tank -1 Nos. (Item for Both the STP) | item493 | 2 | Lot |
| 492 | 492 | Non clog type air dispersion system capable of handling 3-5 cfm of air with oxygen transfer efficiency of 3-4% per/meter water depth. Air dispersion grid shall be assembled in modular form so that they can be replaced / repaired Fine /coarse aeration bubble diffusers as required.\nFor sludge holding tank - 1 No. (Item for Both the STP) | item494 | 2 | Lot |
| 493 | 493 | Non clog type air dispersion system capable of handling 3-5 cfm of air with oxygen transfer efficiency of 3-4% per/meter water depth. Air dispersion grid shall be assembled in modular form so that they can be replaced / repaired Fine /coarse aeration bubble diffusers as required.\nSBR reactor tank- 1 No. (Item for Both the STP) | item495 | 2 | Lot |
| 494 | 494 | Air dispersion system shall be provided for Equalisation Tank, Sludge holding Tank and SBR reactor Tanks.\nSupply of all piping (as described below) and isolation control valves for making the system complete.\nSS 304 : Submerged air piping Make Jindal Steel Ltd.\nMS Epoxy : Air piping, Filters & other Eqp. Make: Jindal Hissar/Prakash Surya\nPVC piping ASTM SCH 40 :Pumped effluent & tank overflow pipe line.\n(Item for Both the STP) | item496 | 2 | Job |
| 495 | 495 | Supplying of Submersible Mixer in Equalization Tank 1 Nos .\nCapacity :suitable for 450 M3/day plant\nMOC :CI\n | item497 | 3 | Each |
| 496 | 496 | Supplyof motorized Moving Decanter to suit SBR tank with MOC SS-304 with scum guard and connected with ultrasonic level transmitter & ultrasonic level element for automatic control etc. complete as required. | item498 | 2 | Each |
| 497 | 497 | Supply of multitube type disinfection system comprising of U.V and U.F Reactor in a close circuit chamber with required no of lamps as per detail design on flow conditions with auto dosing controller, display monitor as per manufacturers requirement complete in all respects\nFlow Rate = 25 M3 / Hr. | item499 | 1 | Set |
| 498 | 498 | Supply of vertical inline multistage pumping set (Imported) with Stainless steel-304 body, Stainless steel-304 impeller, Stainless steel-304 casing, shaft of Stainless steel-316 and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+/- 10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.\nCapacity : 25 M3 / Hr\nHead : 25-30 M\nNo. of Pumps (1 working + 1 standby) | item500 | 1 | Set |
| 499 | 499 | Note: Operation of pump shall be based on level controller proposed to be installed in tank as per site location. The contractor to ascertain the Head required for pumps as per site conditions and provide accordingly.\nSupply of MSEP vessel filter with all necessary accessories. Filter shall be suitable for minimum working pressure of 5 kg / cm2 and shall include media, standard fittings like pressure gauges, sampling cock, rinse drain, vacuum breaker etc. The MS sheet thickness for shell shall be min. 8 mm and for dishes shall 10 mm. The internal surfaces of tank shall be treated with epoxy coaing and external surface with primer and anticorrosive enamel paint (Min. 2 coats). with frontal piping shall be 100 mm dia MSEP along with valves PN 1.0, test cock, air inlet for back washing and pressure gauges at inlet and outlet.\nMultigrade Pressure Sand Filter\nFlow Rate = 25 M3 / Hr\nFiltration velocity : 15 Cum/Hr/Sqm\nFilter HOS : 1800 MM\nFilter Diameter : 1500 MM. | item501 | 1 | Each |
| 500 | 500 | Supply of MSEP vessel filter with all necessary accessories. Filter shall be suitable for minimum working pressure of 5 kg / cm2 and shall include media, standard fittings like pressure gauges, sampling cock, rinse drain, vacuum breaker etc. The MS sheet thickness for shell shall be min. 8 mm and for dishes shall 10 mm. The internal surfaces of tank shall be treated with epoxy coaing and external surface with primer and anticorrosive enamel paint (Min. 2 coats). with frontal piping shall be 100 mm dia MSEP along with valves PN 1.0, test cock, air inlet for back washing and pressure gauges at inlet and outlet.\nActivated Carbon Filter\nFlow Rate = 25 M3 / Hr\nFiltration velocity : 15 Cum/Hr/Sqm\nFilter HOS : 1800 MM\nFilter Diameter : 1500 MM. | item502 | 1 | Each |
| 501 | 501 | Supply of Filter Press of plate as required (size24\"x 24\" x 24 nos plate for reference) with screw feed pumps of 6 m3/hr with adequate head (1Working+1Standby) with interconnecting piping and poly dosing system all complete.\n(Item for Both the STP) | item503 | 2 | Set |
| 502 | 502 | Supply of Magnetic flow meter suitable for 450 KLD Plant with preamplifier and microprocessor including necessary cabling, conduit, etc complete suitable for raw sewage application. | item504 | 1 | Each |
| 503 | 503 | Electrical panel With PLC Control\nSupply of the PLC based control panel with interlocking arrangement with supply pumps, suction pumps, modulating or shut-off valves including necessary wiring, magnetic switches & sensors complete to make the system functional with following interlocking.\nConstruction: Compartmentalized Type Skid Mounted, MCC Cum PLC Control panel will be free standing; vertical, fabricated from CRCA steel sheet 14/16 G conforming to degree of protection IP-52 or better. Cable entry will be from bottom. Colour shade - RAL 7032.\nSystem Voltage: 380 to 410 Volts & 50HZ ( 415 V ±10% , AC, 50 HZ ±5% for India ). Surge protection to be provided at every applicable point.PLC: The Programmable Logic Controller [PLC] shall consist of a PLC hardware, with 16k (min) program memory shall be protected by a backup battery with further memory protection from an EEPROM.\nHMI: 5.5 Inch Colour Touch screen HMI, will be mounted on A Man-Machine Interface Terminal (MMI) shall be mounted on the front of the main control panel for control of the activated sludge plant. It will provide a display of the process parameters and equipment status. The display will have an associated keypad. The system will allow operator changes to set points and control of equipment. The terminal shall include an alarm annunciation with a dedicated alarm page and allow acknowledgment of alarms. | item505 | 1 | Each |
| 504 | 504 | Motor Control Centre\nDesign, fabrication, assembling, wiring, supply, installation, testing and commissioning of motor control centre shall be fabricated with reinforcement of suitable size angle iron, channel ‘T’ sections irons and/or flats wherever necessary. Cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of red oxide primer and final approved shade of powder coated paint. 2 Nos. earthing terminals shall be provided for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided in case of large panels.\nIncoming\n400 amps TPN MCCB with the following accessories:\na. 0-500 volts 96 x 96 mm square electronic voltmeter with selector switch shall be protected by 2 amps TP MCB. 1 Set.\nc. Phase indicating lamps shall be protected by 2 amp SP MCB 3 Sets.\nBus Bar\n300 amps TPN (15 KA) copper bus bar with heat shrinkable insulation sleeves.\nRequired Nos of required capacity TPN MCB for direct on line starter/star delta starters and out going feeders to all the pumps/blowers etc. (including standbys). Each compartment shall contain auto / manual selector switch and indicating lamp with MCB’s for ‘ON/OFF/TRIP’ status of motor.\nSpare MCB’s of following capacities: 32 amps TPN MCB’s 3 Nos.\nAll MCCBs / MCBs shall be of 15 KA breaking capacity and suitable for motor duty application.\nAll motor starters shall be provided with Automatic level controller.\nDOL starters shall be used for mototrs below 10HP and Star-Delta Starters for other motors .\nProvision shall be made for providing potential free contacts to all pumps starters. | item506 | 1 | Each |
| 505 | 505 | Supplying & Fixing of Cables , Conector, Cable Trays, to make Electrical Installation Complete. Necessary cable alleys, internal / cabling, wiring, cabling from MCC to various pumps / equipment and interlocking, earthing and earthing pits for all equipment | item507 | 1 | Lot |
| 506 | 506 | Ultrafiltration System - 15 KL/Hr - For Generating 150 KL Water for Flushing\nUF Module (Hollow Fibre -outside in type porocity 0.1 to 0.01 micron) including micron cartridge filter in PP housing, Pneumatic Valve, PLC Electrical Panel, flow meter, compressor and all other accessories making the system complete.\nFlow rate : 15 cum/hr Output.\nInlet TSS :- 10-30 mg/lt.\nFiltration Flux :- 90 lt/m2/hr.\nMembrane Area - 128 M2 as per approved makes.\nMembrane MOC - PVDF / PES.\nMembrane Type :- Pressure Feed Mambrane 0.01-0.04 Micron rating type, Out to in process.\nNo. of UF Membrane - As Per Manufacturer . | item508 | 1 | Set |
| 507 | 507 | UF Feed Pump\nCapacity 15 M3/hr each (1 W + 1 SB)\nHead 20-25 Mts\nRPM 2900 | item509 | 1 | Set |
| 508 | 508 | Supply, installation, testing & commissioning of UF pre fine filtration. It can be micron filter or Bag filter as per vendor design. The MOC of housing of filter shall be PP | item510 | 1 | Set |
| 509 | 509 | Supplying, installing, testing, commissioning of centrifugal Vertical UF Backwash pumps with Complete SS - 304 with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, strainer at suction. The pump shall be suitable for 415±10% volts 3 phase AC supply .\nCapacity : - 15 M³/h\nHead : - 18- 20 m\nNo. of Pumps: 1 No\nNote-CIP pumps can be common with item no.c | item511 | 1 | Set |
| 510 | 510 | Supplying, Installation, testing and commissioning of chlorine dosing system compromising of Sintex Tank with inlet/ outlet connection, piping and valves alongwith metering pump of 6 LPH for dosing.\n(Item for Both the STP) | item512 | 2 | Set |
| 511 | 511 | Supply, Installation, testing and commissioning of CEB / CIP dosing station including dosing tank, pumps complete in all respect as per UF memrbane specification requirement.\n(Item for Both the STP) | item513 | 2 | Set |
| 512 | 512 | Supply installation commissioning of PLC control panel with all automation required like Pneumatic valves, piping in uPVC PLC and other required accessories.\n(Item for Both the STP) | item514 | 2 | Set |
| 513 | 513 | MS epoxy coated skid for the complete plant.\n(Item for Both the STP) | item515 | 2 | Set |
| 514 | 514 | Supply, installation & commissioning of HDPE backwash tank of 500 Litre capacity including required level controller inlet, outlet, overflow and drain connection.\n(Item for Both the STP) | item516 | 2 | Set |
| 515 | 515 | Effluent Treatment Plant 50 KLD for TB Hospital\nDesign, Supplying, installing, testing & commissioning of Effluent Treatment Plant of 50 KLD (excluding excavation, back filling & disposal of surplus earth and Civil construction work) for the following duty:\nEffluent from OT Scrubs, blood bank, labs etc. Some solvent/ chemical waste originating typically from hospital complex shall also be discharged into the ETP. Design to take consideration of same.\nINLET EFFLUENT CHARACTERSTICS (ASSUMED)\nPH : 5.5 - 9.0\nBOD : 250 - 600 mg/l\nS. Solids : 200 - 650 Mg/l\nCOD : 600 - 1200 mg/l\nOil & Grease : 50 - 140 mg/L\nDesired Effluent Quality After Treatment\npH - 6.5 – 8.5\nBOD - Less than 150 Mg/L\nS. Solids - Less than or equal to 100 Mg/L\nCOD - Less than or equal to 300 Mg/L\nOil & Grease - Less than 5 Mg/L\nEffluent treatment plant shall include the following items:\nScreen Chamber\nEqualization tank/sump\nPrimary Tube Settler\nDosing System\nSludge Holding Tank\nUV System\nAir Blowers, Pumps & equipment\nPiping, valves etc\nClarified Water tank\nElectrical Panel & Cabling\nNote:\nContractor shall ensure submission of detailed GA drawings (Plan & Section), P&I diagram, schematic diagram for the above said component and additional component if so required for the complete working of the ETP for the full capacity. | item517 | 1 | Set |
| 516 | 516 | Sewage Treatment Plant 650 KLD ( SBR Technology ) for MMCH Hospital\nNote : All Civil Works with Structural Walk Ways/ Railings, General Lighting and Ventilation to be Done by Client/Owner.\nDesign, Supplying, of Sewage Treatment Plant capacity 650 KLD .(excluding excavation, back filling & disposal of surplus earth /Civil construction work) for the following duty:\nNature of effluent - Office Building Sewage from Toilet use , kitchen waste and other areas of office buildings.\nIncoming parameters:\npH - 6 - 8.5\nBOD5 - upto 250-350 Mg/L\nS. Solids - 250 - 400 Mg/L\nCOD - upto 450-600 Mg/L\nOil & Grease - 50-100 Mg / L\nFinal effluent discharge standard after treatment\npH - 6.0 - 8 After UF 6-8\nBOD5 - Less than 10 Mg/L After UF <4\nS. Solids - Less than 30 Mg/L After UF <2\nCOD - Less than 60 Mg/L After UF <30\nOil & Grease - Less than 5 Mg/L After UF <Nil\n\nSupply, installation, testing & commissioning of non clog open impeller type pumps, having CI casing & CI impeller complete with all accessories, motor of required capacity. Delivery header with isolation valve and NRV, lifting arrangement, pressure gauge on delivery line with isolation cock level controller with wiring to control the level of sump automatically. Pump shall have following duty for reference and vendor to confirm on design base.\nSubmersible Sewage Transfer Pumps 2 Nos. (1 Working + 1 Standby )\n(Solid Handling Cap. 35 mm)\nFlow rate (each) = 35 M3 / Hr\nHead = 10 Mtr | item518 | 1 | Set |
| 517 | 517 | Supply, installation, testing & commissioning of non clogging submersible type Return Activated Sludge Pumps and Secondary Activated pumps(RAS and SAS Pumps) having CI casing & CI impeller complete with and foundation bolt and lifting arrangement with all accessories, motor of required capacity. pressure gauge on delivery line with isolation cock, level controller to control the level of sump automatically. Pumps shall have following duty: Pumps 2 Nos. (1 Working + 1 Standby ).\n(Solid handling cap. 8.5 mm)\nFlow rate (each) = 25m3 / hr\nHead = 12 Mtr\nCost shall be inclusive of PVC flexible Hose pipe ( for piping submerged in effluent) with M S epoxy piping (for piping non-submerged in effluent) | item519 | 1 | Set |
| 518 | 518 | Provision of guide ropes to guide submersible pump from upper level to operational level in sump basin with channels / angle section of MSEP shall be made by the STP contractor.\nAir diffusion system shall include the following: | item520 | 1 | Lot |
| 519 | 519 | Twin type rotary air blowers 2 Nos. (1 W + 1 S) Capable of delivering 650 cum/hr (each) of free air at 0.6 kg/cm2 driven through “V” belt or directly coupled through flexible coupling to a TEFCmotor of suitable HP Suitable for 415 ± 10% volts, 3 phase, 50 cycles a/c supply . | item521 | 2 | Each |
| 520 | 520 | Air piping shall comprise of pipes droppers/ laterals with M S (epoxy coated) Header complete with all fittings such as tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc cutting chases & making good in Plant Room. All submerged piping will be SS-304 | item522 | 1 | Lot |
| 521 | 521 | Supplying of Submersible Mixer in Equalization Tank 1 Nos .\nCapacity :suitable for 650 M3/day plant\nMOC :CI\n | item523 | 3 | Each |
| 522 | 522 | Supplyof motorized Moving Decanter to suit SBR tank with MOC SS-304 with scum guard and connected with ultrasonic level transmitter & ultrasonic level element for automatic control etc. complete as required. | item524 | 2 | Each |
| 523 | 523 | Supply of multitube type disinfection system comprising of U.V and U.F Reactor in a close circuit chamber with required no of lamps as per detail design on flow conditions with auto dosing controller, display monitor as per manufacturers requirement complete in all respects.\nFlow Rate = 35 M3 / Hr | item525 | 1 | Set |
| 524 | 524 | Supply of vertical inline multistage pumping set (Imported) with Stainless steel-304 body, Stainless steel-304 impeller, Stainless steel-304 casing, shaft of Stainless steel-316 and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+/- 10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.\nCapacity : 35 M3 / Hr\nHead : 25-30 M\nNo. of Pumps (1 working + 1 standby) | item526 | 1 | Set |
| 525 | 525 | Note: Operation of pump shall be based on level controller proposed to be installed in tank as per site location. The contractor to ascertain the Head required for pumps as per site conditions and provide accordingly.\nSupply of MSEP vessel filter with all necessary accessories. Filter shall be suitable for minimum working pressure of 5 kg / cm2 and shall include media, standard fittings like pressure gauges, sampling cock, rinse drain, vacuum breaker etc. The MS sheet thickness for shell shall be min. 8 mm and for dishes shall 10 mm. The internal surfaces of tank shall be treated with epoxy coaing and external surface with primer and anticorrosive enamel paint (Min. 2 coats). with frontal piping shall be 100 mm dia MSEP along with valves PN 1.0, test cock, air inlet for back washing and pressure gauges at inlet and outlet.\nMultigrade Pressure Sand Filter\nFlow Rate = 35 M3 / Hr\nFiltration velocity : 15 Cum/Hr/Sqm\nFilter HOS : 1800 MM\nFilter Diameter : 1700 MM. | item527 | 1 | Each |
| 526 | 526 | Supply of MSEP vessel filter with all necessary accessories. Filter shall be suitable for minimum working pressure of 5 kg / cm2 and shall include media, standard fittings like pressure gauges, sampling cock, rinse drain, vacuum breaker etc. The MS sheet thickness for shell shall be min. 8 mm and for dishes shall 10 mm. The internal surfaces of tank shall be treated with epoxy coaing and external surface with primer and anticorrosive enamel paint (Min. 2 coats). with frontal piping shall be 100 mm dia MSEP along with valves PN 1.0, test cock, air inlet for back washing and pressure gauges at inlet and outlet.\nActivated Carbon Filter\nFlow Rate = 35 M3 / Hr\nFiltration velocity : 15 Cum/Hr/Sqm\nFilter HOS : 1800 MM\nFilter Diameter : 1700 MM. | item528 | 1 | Each |
| 527 | 527 | Supply of Magnetic flow meter suitable for 650 KLD Plant with preamplifier and microprocessor including necessary cabling, conduit, etc complete suitable for raw sewage application. | item529 | 1 | Each |
| 528 | 528 | Electrical panel With PLC Control\nSupply of the PLC based control panel with interlocking arrangement with supply pumps, suction pumps, modulating or shut-off valves including necessary wiring, magnetic switches & sensors complete to make the system functional with following interlocking.\nConstruction: Compartmentalized Type Skid Mounted, MCC Cum PLC Control panel will be free standing; vertical, fabricated from CRCA steel sheet 14/16 G conforming to degree of protection IP-52 or better. Cable entry will be from bottom. Colour shade - RAL 7032.\nSystem Voltage: 380 to 410 Volts & 50HZ ( 415 V ±10% , AC, 50 HZ ±5% for India ). Surge protection to be provided at every applicable point.\nPLC: The Programmable Logic Controller [PLC] shall consist of a PLC hardware, with 16k (min) program memory shall be protected by a backup battery with further memory protection from an EEPROM.\nHMI: 5.5 Inch Colour Touch screen HMI, will be mounted on A Man-Machine Interface Terminal (MMI) shall be mounted on the front of the main control panel for control of the activated sludge plant. It will provide a display of the process parameters and equipment status. The display will have an associated keypad. The system will allow operator changes to set points and control of equipment. The terminal shall include an alarm annunciation with a dedicated alarm page and allow acknowledgment of alarms. | item530 | 1 | Each |
| 529 | 529 | Motor Control Centre\nDesign, fabrication, assembling, wiring, supply, installation, testing and commissioning of motor control centre shall be fabricated with reinforcement of suitable size angle iron, channel ‘T’ sections irons and/or flats wherever necessary. Cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of red oxide primer and final approved shade of powder coated paint. 2 Nos. earthing terminals shall be provided for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided in case of large panels.\nIncoming\n400 amps TPN MCCB with the following accessories:\na. 0-500 volts 96 x 96 mm square electronic voltmeter with selector switch shall be protected by 2 amps TP MCB. 1 Set\nb. 0-100 amps 96 x 96 mm square electronic ammeter with selector switch and 100./5 amps 10 VA CL:1 CTs. 1 Set.\nc. Phase indicating lamps shall be protected by 2 amp SP MCB 3 Sets.\nBus Bar\n300 amps TPN (15 KA) copper bus bar with heat shrinkable insulation sleeves.\nRequired Nos of required capacity TPN MCB for direct on line starter/star delta starters and out going feeders to all the pumps/blowers etc. (including standbys). Each compartment shall contain auto / manual selector switch and indicating lamp with MCB’s for ‘ON/OFF/TRIP’ status of motor.\nSpare MCB’s of following capacities: 32 amps TPN MCB’s 3 Nos.\nAll MCCBs / MCBs shall be of 15 KA breaking capacity and suitable for motor duty application.\nAll motor starters shall be provided with Automatic level controller.\nDOL starters shall be used for mototrs below 10HP and Star-Delta Starters for other motors .\nProvision shall be made for providing potential free contacts to all pumps starters. | item531 | 1 | Each |
| 530 | 530 | Supplying & Fixing of Cables , Conector, Cable Trays, to make Electrical Installation Complete. Necessary cable alleys, internal / cabling, wiring, cabling from MCC to various pumps / equipment and interlocking, earthing and earthing pits for all equipment | item532 | 1 | Lot |
| 531 | 531 | Ultrafiltration System - 22 KL/Hr - For Generating 220 KL Water for Flushing\nUF Module (Hollow Fibre -outside in type porocity 0.1 to 0.01 micron) including micron cartridge filter in PP housing, Pneumatic Valve, PLC Electrical Panel, flow meter, compressor and all other accessories making the system complete.\nFlow rate : 22 cum/hr Output.\nInlet TSS :- 10-30 mg/lt.\nFiltration Flux :- 90 lt/m2/hr.\nMembrane Area - 128 M2 as per approved makes.\nMembrane MOC - PVDF / PES.\nMembrane Type :- Pressure Feed Mambrane 0.01-0.04 Micron rating type, Out to in process.\nNo. of UF Membrane - As Per Manufacturer. | item533 | 1 | Set |
| 532 | 532 | UF Feed Pump\nCapacity 22 M3/hr each (1 W + 1 SB)\nHead 20-25 Mts\nRPM 2900 | item534 | 1 | Set |
| 533 | 533 | Supply, installation, testing & commissioning of UF pre fine filtration. It can be micron filter or Bag filter as per vendor design. The MOC of housing of filter shall be PP | item535 | 1 | Set |
| 534 | 534 | Supplying, installing, testing, commissioning of centrifugal Vertical UF Backwash pumps with Complete SS - 304 with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, strainer at suction. The pump shall be suitable for 415±10% volts 3 phase AC supply .\nCapacity : - 35 M³/h\nHead : - 18- 20 m\nNo. of Pumps: 1 No\nNote-CIP pumps can be common with item no.c | item536 | 1 | Set |
| 535 | 535 | Effluent Treatment Plant 75 KLD for MMCH Hospital\nDesign, Supplying, installing, testing & commissioning of Effluent Treatment Plant of 75 KLD (excluding excavation, back filling & disposal of surplus earth and Civil construction work) for the following duty:\nEffluent from OT Scrubs, blood bank, labs etc. Some solvent/ chemical waste originating typically from hospital complex shall also be discharged into the ETP. Design to take consideration of same.\nINLET EFFLUENT CHARACTERSTICS (ASSUMED)\nPH : 5.5 - 9.0\nBOD : 250 - 600 mg/l\nS. Solids : 200 - 650 Mg/l\nCOD : 600 - 1200 mg/l\nOil & Grease : 50 - 140 mg/L\nDesired Effluent Quality After Treatment\npH - 6.5 – 8.5\nBOD - Less than 150 Mg/L\nS. Solids - Less than or equal to 100 Mg/L\nCOD - Less than or equal to 300 Mg/L\nOil & Grease - Less than 5 Mg/L\nEffluent treatment plant shall include the following items:\nScreen Chamber\nEqualization tank/sump\nPrimary Tube Settler\nDosing System\nSludge Holding Tank\nUV System\nAir Blowers, Pumps & equipment\nPiping, valves etc\nClarified Water tank\nElectrical Panel & Cabling\nNote:\nContractor shall ensure submission of detailed GA drawings (Plan & Section), P&I diagram, schematic diagram for the above said component and additional component if so required for the complete working of the ETP for the full capacity. | item537 | 1 | Set |
| 536 | 536 | Water Supply, Drainage Pumps & Water Treatment Equipments\nSupply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with Stainless steel body, impeller, casing, shaft and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+/- 10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.\nFilter Feed Pump ( Dom. Water) at Water Supply Pump Room (TB)\nSet of Two Pumps ( 2 Working+ 1 Standby)\nCapacity 300 LPM\nHead 35 M.\nHP 5.0 HP Approxi. | item538 | 1 | Set |
| 537 | 537 | Supply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with Stainless steel body, impeller, casing, shaft and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+/- 10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.\nFilter Feed Pump ( Dom. Water) at Water Supply Pump Room (MMCH)\nSet of Two Pumps ( 2 Working+ 1 Standby)\nCapacity 450 LPM\nHead 35 M.\nHP 5.0 HP Approxi. | item539 | 1 | Set |
| 538 | 538 | Supply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with Stainless steel body, impeller, casing, shaft and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+/- 10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.\nSoftener Feed Pump ( Cooling Tower) at STP Pump Room\nSet of Two Pumps ( 1 Working+ 1 Standby)\nCapacity 250 LPM\nHead 35 M.\nHP 5.0 HP Approxi. | item540 | 2 | Set |
| 539 | 539 | Supply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with Stainless steel body, impeller, casing, shaft and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+/- 10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.\nSoft Water Transfer Pump at STP Pump Room\nSet of Two Pumps ( 1 Working+ 1 Standby)\nCapacity 250 LPM\nHead 65 M.\nHP 6.0 HP Approxi. | item541 | 2 | Set |
| 540 | 540 | Supply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with Stainless steel body, impeller, casing, shaft and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+/- 10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.\nWater makeup pump in UGT Pump room (TB)\nSet of Two Pumps ( 1 Working+ 1 Standby)\nCapacity 350 LPM\nHead 35 M.\nHP 5.0 HP Approxi. | item542 | 1 | Set |
| 541 | 541 | Supply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with Stainless steel body, impeller, casing, shaft and C.I. base & head with mechanical seal, connected to a TEFC induction motor suitable for 415+/- 10% volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.\nWater makeup pump in UGT Pump room (MMCH)\nSet of Two Pumps ( 1 Working+ 1 Standby)\nCapacity 450 LPM\nHead 35 M.\nHP 5.0 HP Approxi. | item543 | 1 | Set |
| 542 | 542 | Providing, installing, testing and commissining of variable speed (VSPS) hydropneumatic system mounted on a common base plate comprising of vertical centrifugal pumping set with S.S body, stainless steel impeller and mechanical seal, shaft directly coupled to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles AC supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, one No. microprocessor based controller, dedicated variable frequency drive for each pump, one No.remote sensors, pressure transducers, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, one No. 60 litre capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including stainless steel grade 316 pipe suction and delivery headers and isolation/ control valves( ball valves/butterfly valves/ Nan return valves/ vibration eliminators etc as required) , power box, equipped with fuses/ isolators/circuit breakers as required.\nThe entire Hydropneumatic system shall be factory fitted.\nDomestic Water Transfer at Pump Room (TB)\nSet of Two Pumps ( 2 Working+ 1 Standby)\nCapacity 350 LPM\nHead 75 M.\nHP 7.5 HP Approxi. | item544 | 1 | Set |
| 543 | 543 | Providing, installing, testing and commissining of variable speed (VSPS) hydropneumatic system mounted on a common base plate comprising of vertical centrifugal pumping set with S.S body, stainless steel impeller and mechanical seal, shaft directly coupled to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles AC supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, one No. microprocessor based controller, dedicated variable frequency drive for each pump, one No.remote sensors, pressure transducers, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, one No. 60 litre capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including stainless steel grade 316 pipe suction and delivery headers and isolation/ control valves( ball valves/butterfly valves/ Nan return valves/ vibration eliminators etc as required) , power box, equipped with fuses/ isolators/circuit breakers as required.\nThe entire Hydropneumatic system shall be factory fitted.\nDomestic Water Transfer at Pump Room (MMCH)\nSet of Two Pumps ( 2 Working+ 1 Standby)\nCapacity 550 LPM\nHead 75 M.\nHP 10 HP Approxi. | item545 | 1 | Set |
| 544 | 544 | Providing, installing, testing and commissining of variable speed (VSPS) hydropneumatic system mounted on a common base plate comprising of vertical centrifugal pumping set with S.S body, stainless steel impeller and mechanical seal, shaft directly coupled to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles AC supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, one No. microprocessor based controller, dedicated variable frequency drive for each pump, one No.remote sensors, pressure transducers, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, one No. 60 litre capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including stainless steel grade 316 pipe suction and delivery headers and isolation/ control valves( ball valves/butterfly valves/ Nan return valves/ vibration eliminators etc as required) , power box, equipped with fuses/ isolators/circuit breakers as required.\nThe entire Hydropneumatic system shall be factory fitted.\nFlushing Water Transfer STP Pump Room (TB)\nSet of Two Pumps ( 1 Working+ 1 Standby)\nCapacity 350 LPM\nHead 75 M.\nHP 7.5 HP Approxi. | item546 | 1 | Set |
| 545 | 545 | Providing, installing, testing and commissining of variable speed (VSPS) hydropneumatic system mounted on a common base plate comprising of vertical centrifugal pumping set with S.S body, stainless steel impeller and mechanical seal, shaft directly coupled to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles AC supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, one No. microprocessor based controller, dedicated variable frequency drive for each pump, one No.remote sensors, pressure transducers, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, one No. 60 litre capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including stainless steel grade 316 pipe suction and delivery headers and isolation/ control valves( ball valves/butterfly valves/ Nan return valves/ vibration eliminators etc as required) , power box, equipped with fuses/ isolators/circuit breakers as required.\nThe entire Hydropneumatic system shall be factory fitted.\nFlushing Water Transfer STP Pump Room (MMCH)\nSet of Two Pumps ( 1 Working+ 1 Standby)\nCapacity 450 LPM\nHead 75 M.\nHP 7.5 HP Approxi. | item547 | 1 | Set |
| 546 | 546 | Providing, installing, testing and commissining of variable speed (VSPS) hydropneumatic system mounted on a common base plate comprising of vertical centrifugal pumping set with S.S body, stainless steel impeller and mechanical seal, shaft directly coupled to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles AC supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, one No. microprocessor based controller, dedicated variable frequency drive for each pump, one No.remote sensors, pressure transducers, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, one No. 60 litre capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including stainless steel grade 316 pipe suction and delivery headers and isolation/ control valves( ball valves/butterfly valves/ Nan return valves/ vibration eliminators etc as required) , power box, equipped with fuses/ isolators/circuit breakers as required.\nThe entire Hydropneumatic system shall be factory fitted.\nIrrigation Pumps at STP Pump Room\nSet of Two Pumps ( 1 Working+ 1 Standby)\nCapacity 200 LPM\nHead 50 M.\nHP 5 HP Approxi. | item548 | 2 | Set |
| 547 | 547 | Providing, installing, testing and commissining of variable speed (VSPS) hydropneumatic system mounted on a common base plate comprising of vertical centrifugal pumping set with S.S body, stainless steel impeller and mechanical seal, shaft directly coupled to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles AC supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, one No. microprocessor based controller, dedicated variable frequency drive for each pump, one No.remote sensors, pressure transducers, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, one No. 60 litre capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including stainless steel grade 316 pipe suction and delivery headers and isolation/ control valves( ball valves/butterfly valves/ Nan return valves/ vibration eliminators etc as required) , power box, equipped with fuses/ isolators/circuit breakers as required.\nThe entire Hydropneumatic system shall be factory fitted.\nHyd. System for Domestic Water Supply at Hospital Terrace\nSet of Two Pumps ( 1 Working+ 1 Standby)\nCapacity 300 LPM\nHead 20 M.\nHP 3 HP Approxi. | item549 | 4 | Set |
| 548 | 548 | Providing, installing, testing and commissining of variable speed (VSPS) hydropneumatic system mounted on a common base plate comprising of vertical centrifugal pumping set with S.S body, stainless steel impeller and mechanical seal, shaft directly coupled to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles AC supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation, one No. microprocessor based controller, dedicated variable frequency drive for each pump, one No.remote sensors, pressure transducers, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, one No. 60 litre capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including stainless steel grade 316 pipe suction and delivery headers and isolation/ control valves( ball valves/butterfly valves/ Nan return valves/ vibration eliminators etc as required) , power box, equipped with fuses/ isolators/circuit breakers as required.\nThe entire Hydropneumatic system shall be factory fitted.\nHyd. System for Domestic Water Supply at housing Terrace\nSet of Two Pumps ( 1 Working+ 1 Standby)\nCapacity 200 LPM\nHead 20 M.\nHP 2.5 HP Approxi. | item550 | 2 | Set |
| 549 | 549 | Supply, installing, testing and commissioning of submersible open impeller non-clog pumps with C.I.body and to TEFC submersible motor for 415 + 10% volts, 3 phase, 50 cycles A.C. power supply with mechanical seal, pump connector unit with rubber diaphragm and bend, vertical discharge pipe, guide pipe and chain in built level controller, sequence running controller, arrangement for both pumps together inacase of emenegency, audible hooter for failure or flooding, dry running Protection complete in all respects., painting, testing and commissioning complete with approved quality and make as required as per instruction of site incharge.\n(Pumps shall be installed in a set of two pumps One working and One standby)\nBasement & Pump Room Drainage Pumps\n(Pumps to be suitable to handle solids upto 12 mm size)\nCapacity - 4.0 LPS (Each)\nHead - 20 M\nH.P. - 2.0 HP Approx. | item551 | 11 | Set |
| 550 | 550 | Supply, installing, testing and commissioning of submersible open impeller non-clog pumps with C.I.body and to TEFC submersible motor for 415 + 10% volts, 3 phase, 50 cycles A.C. power supply with mechanical seal, pump connector unit with rubber diaphragm and bend, vertical discharge pipe, guide pipe and chain in built level controller, sequence running controller, arrangement for both pumps together inacase of emenegency, audible hooter for failure or flooding, dry running Protection complete in all respects., painting, testing and commissioning complete with approved quality and make as required as per instruction of site incharge.\n(Pumps shall be installed in a set of two pumps One working and One standby)\nSewage Sump Pumps\n(Pumps to be suitable to handle solids upto 40 mm size)\nCapacity - 4.0 LPS (Each)\nHead - 20 M\nH.P. - 3.0 HP Approx. | item552 | 4 | Set |
| 551 | 551 | Supply Installation,Testing & Commissioning of vertical self supporting Filter fabricated from MS sheet as per IS: 2825, ((minimum thickness of shall 6 mm and dished end 8 mm)) pressure gauges, sample cock, GI class 'C' face piping, CI butterfly valves and all accessories , with initial charge of filter media including anthracite, painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testing and commissioning complete.\nDual Media Filter For Domestic Water Supply (TB)\nCapacity- 35000 LPH\nFiltration rate- 16000 LPH/Sqm.\nFilter dia approx. - 1700 MM\nWorking pressure: 3.0 Kg/sq cm.\nTest pressure : 4. 5 Kg/sq cm | item553 | 1 | Each |
| 552 | 552 | Supply Installation,Testing & Commissioning of vertical self supporting Filter fabricated from MS sheet as per IS: 2825, ((minimum thickness of shall 6 mm and dished end 8 mm)) pressure gauges, sample cock, GI class 'C' face piping, CI butterfly valves and all accessories , with initial charge of filter media including anthracite, painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testing and commissioning complete.\nDual Media Filter For Domestic Water Supply (MMCH)\nCapacity- 52500 LPH\nFiltration rate- 16000 LPH/Sqm.\nFilter dia approx. - 2100 MM\nWorking pressure: 3.0 Kg/sq cm.\nTest pressure : 4. 5 Kg/sq cm | item554 | 1 | Each |
| 553 | 553 | Supply Installation,Testing & Commissioning of vertical self supporting Filter fabricated from MS sheet as per IS: 2825, ((minimum thickness of shall 6 mm and dished end 8 mm)) pressure gauges, sample cock, GI class 'C' face piping, CI butterfly valves and all accessories , with initial charge of filter media including anthracite, painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testing and commissioning complete.\nActivated Carbon Filter For Domestic Water Supply (TB)\nCapacity- 35000 LPH\nFiltration rate- 16000 LPH/Sqm.\nFilter dia approx. - 1700 MM\nWorking pressure: 3.0 Kg/sq cm.\nTest pressure : 4. 5 Kg/sq cm | item555 | 1 | Each |
| 554 | 554 | Supply Installation,Testing & Commissioning of vertical self supporting Filter fabricated from MS sheet as per IS: 2825, ((minimum thickness of shall 6 mm and dished end 8 mm)) pressure gauges, sample cock, GI class 'C' face piping, CI butterfly valves and all accessories , with initial charge of filter media including anthracite, painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testing and commissioning complete.\nActivated Carbon Filter For Domestic Water Supply (MMCH)\nCapacity- 52000 LPH\nFiltration rate- 16000 LPH/Sqm.\nFilter dia approx. - 2100 MM\nWorking pressure: 3.0 Kg/sq cm.\nTest pressure : 4. 5 Kg/sq cm | item556 | 1 | Each |
| 555 | 555 | Supply Installation,Testing & Commissioning of \"Cation\" ion exchange Water Softener fabricated from MS plate as per IS: 2825 (minimum thickness of shall 6 mm and dished end 8 mm) complete with initial charge of resins , GI class 'C' face piping, CI butterfly valves, pressure gauge, hydraulic brine injector, accessories, painting inside with epoxy paint, including 500 liters capacity PVC / HDPE brine tank suitable for 2 regeneration capacity, testing and commissioning complete with resins of approved quality and make.\nSoftener For Cooling Tower Water Supply\nHardness-\nInlet- 500-600 PPM\nOutlet- Less than 5 PPM\nCapacity- 8000 LPH\nRegeneration period 12 hrs.\nQuantity of soft water\nbetween two regenerations = 180000 lit\nWorking pressure: 3.0 Kg/sq cm.\nTest pressure : 4. 5 Kg/sq cm | item557 | 2 | Each |
| 556 | 556 | Supply Installation,Testing & Commissioning of metering pump type chemical doser with 100 lits. HDPE chemical grade solution tank,injection fitting assembly,suction and delivery hose upto the point of injection, capacity 0-6 lph, complete in all respects.\nChlorination of Domestic Water | item558 | 2 | Each |
| 557 | 557 | Design, manufacture, supplying, fixing in position, testing and commissioning of the following front operated cubicle type, front access 2mm thick mild steel sheet, free standing, dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors complete with interconnections, tinned copper crimping lugs, bonding to earth and painting, suitable for use at 415 volts, 3 phase 4 wire 50 Hz system and suitable for a fault level of 25 MVA symmetrical at 415 volts.\nAll switchboards shall have provision for entry of cables from the top or bottom as required.\nAll live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders doors and switch handles shall be lockable in OFF position.\nElectric Panel For Water Supply Pumps at Water Supply Pump Room\nINCOMING\n1 No. 200 amps TPN MCCB with the following accessories:\n1 No. square flush mounting 0-500 volts scaled voltmeter with three way and OFF switch.\nThree phase indicating lights.\nElectrolytic high conductivity three phase and neutral tinned copper bus bar rated at 300 amps having a current density of 1 amp per Sqmm suitable to with stand symmetrical fault level of 25 MVA at 415 volts. The neutral bus bar is to be of 100% capacity.\nOUTGOING UNITS\nTwo 25 Amp. TP + NL M.C.C.B. with rotary handle of breaking capacity 25KA\nSix 63 Amp. TP + NL M.C.C.B. with rotary handle of breaking capacity 25KA\n8 Nos. fully automatic DOL starters with push buttons and ON/OFF indicating lights and overload relays for 1.5 to 7.5 HP pump .\n8 Nos. rotary selector switch for selecting mode of operation i.e. auto/manual/off.\n8 Nos.cyclic relay for automatic duty changeover of pumps.\n8 No. single phase preventors.\n8 Nos. square flush mounting 0-30 amps scaled ammeters with three way and OFF selector switch.\nSpace for 3 Nos. Level Controllers.\nSwitchgear shall be suitable for the HPS of various motors.\n4 Nos. 32 Amp. TPN MCB Spare.\nThe motor control panel shall be prewired with colour coded wires with identification labels complete in all respects as required. | item559 | 2 | Set |
| 558 | 558 | Electric Panel For Water Supply Pumps at STP Pump Room\nINCOMING\n1 No. 200 amps TPN MCCB with the following accessories:\n1 No. square flush mounting 0-500 volts scaled voltmeter with three way and OFF switch.\nThree phase indicating lights.\nElectrolytic high conductivity three phase and neutral tinned copper bus bar rated at 200 amps having a current density of 1 amp per Sqmm suitable to with stand symmetrical fault level of 25 MVA at 415 volts. The neutral bus bar is to be of 100% capacity.\nOUTGOING UNITS\nTwo 25 Amp. TP + NL M.C.C.B. with rotary handle of breaking capacity 25KA\nTen 63 Amp. TP + NL M.C.C.B. with rotary handle of breaking capacity 25KA\n12 Nos. fully automatic DOL starters with push buttons and ON/OFF indicating lights and overload relays for 1.5 to 7.5 HP pump .\n12 Nos. rotary selector switch for selecting mode of operation i.e. auto/manual/off.\n12 Nos.cyclic relay for automatic duty changeover of pumps.\n12 No. single phase preventors.\n12 Nos. square flush mounting 0-30 amps scaled ammeters with three way and OFF selector switch.\nSpace for 5 Nos. Level Controllers.\nSwitchgear shall be suitable for the HPS of various motors.\n4 Nos. 32 Amp. TPN MCB Spare.\nThe motor control panel shall be prewired with colour coded wires with identification labels complete in all respects as required. | item560 | 2 | Set |
| 559 | 559 | Electric Panel For Drainage Sump Pump\nOne incoming main MCCB unit of 63 amps rating.\nCopper bus bar is separate chamber fully taped of 100 amps capacity.\nTwo MCB units of 25 amps\nTwo fully automatic DOL starters with push buttons and on/off indicating lights.\nOne rotary duty selector switch\nTwo manual/auto/off switches.\nTwo single phasing presenters.\nOne panel type voltmeter with rotary selector switch for reading voltage between phases.\nTwo ampere meters one for each motor.\nThree neon phase indicating lights on the incoming mains.\nSpace for one liquid level controllers.\nAll internal wiring colour coded from incoming mains to various switchgear, starters, meters, indicating lamps and bus bar with a changeover facility to run each pump alternatively with an alarm bell in case of both pump’s running at one time. Switchegear offered must be compatible with the HP of the motors offered.\nMotor control centre as described above. | item561 | 15 | Set |
| 560 | 560 | Supplying, installing, testing and commissioning controllers with low voltage relays, stainless steel probes and PVC shroud wiring from tank top to probes of required.\nLevel Controller For Water Supply Pump:\nTo start pump when water level is low in Domestic Water U.G. tank and shut off pump when Domestic Water U.G. tank is full. Also to stop when water level is low in raw water underground tank. | item562 | 4 | Each |
| 561 | 561 | Supplying, installing, testing and commissioning controllers with low voltage relays, stainless steel probes and PVC shroud wiring from tank top to probes of required.\nLevel Controller For Sump Pumps:\nTo start pump when water level is high in sump and shut off pump when sump is empty. Both pumps are start when sump is over flowing. | item563 | 15 | Each |
| 562 | 562 | Providing and fixing GI pipes complete (IS:1239 Heavy Class) with GI fittings and clamps including MS pipe supports, enamel paint as per specifications cutting and making good the walls etc. complete.\n50 mm dia | item564 | 40 | Metre |
| 563 | 563 | Providing and fixing GI pipes complete (IS:1239 Heavy Class) with GI fittings and clamps including MS pipe supports, enamel paint as per specifications cutting and making good the walls etc. complete.\n65 mm dia | item565 | 40 | Metre |
| 564 | 564 | Providing and fixing GI pipes complete (IS:1239 Heavy Class) with GI fittings and clamps including MS pipe supports, enamel paint as per specifications cutting and making good the walls etc. complete.\n100 mm dia | item566 | 50 | Metre |
| 565 | 565 | Providing and fixing GI pipes complete (IS:1239 Heavy Class) with GI fittings and clamps including MS pipe supports, enamel paint as per specifications cutting and making good the walls etc. complete.\n150 mm dia | item567 | 20 | Metre |
| 566 | 566 | Butterfly valve (manual) with C.I body SS disc nitrile sheet & O ring & PN 16 Pressure rating as specified .\n50 mm dia | item568 | 42 | Each |
| 567 | 567 | Butterfly valve (manual) with C.I body SS disc nitrile sheet & O ring & PN 16 Pressure rating as specified .\n150 mm dia | item569 | 2 | Each |
| 568 | 568 | Non - return valve with dual plate of CI Body SS plates vulcanized NBR seal flanged end & PN 16 rating as specified.\n50 mm dia | item570 | 24 | Each |
| 569 | 569 | Non - return valve with dual plate of CI Body SS plates vulcanized NBR seal flanged end & PN 16 rating as specified.\n65mm dia. | item571 | 24 | Each |
| 570 | 570 | Providing and fixing resilient rubber neoprene lined style arch vibration eliminators suitable for raw water upto 45 deg.C. Temperature working pressure upto 16 Kg/Sqcm.\n50 mm dia | item572 | 24 | Each |
| 571 | 571 | Providing and fixing resilient rubber neoprene lined style arch vibration eliminators suitable for raw water upto 45 deg.C. Temperature working pressure upto 16 Kg/Sqcm.\n65 mm dia | item573 | 24 | Each |
| 572 | 572 | Providing and fixing resilient rubber neoprene lined style arch vibration eliminators suitable for raw water upto 45 deg.C. Temperature working pressure upto 16 Kg/Sqcm.\n80 mm dia | item574 | 4 | Each |
| 573 | 573 | Providing and fixing heavy duty armoured cables 1.1 KVA grade including necessary support clamps at ceiling level and connection lugs complete in all respects.\nPower cable Copper 3 core 10 sq.mm | item575 | 100 | Metre |
| 574 | 574 | Providing and fixing heavy duty armoured cables 1.1 KVA grade including necessary support clamps at ceiling level and connection lugs complete in all respects.\nPower cable Copper 3 core 6 sq.mm | item576 | 150 | Metre |
| 575 | 575 | Providing and fixing heavy duty armoured cables 1.1 KVA grade including necessary support clamps at ceiling level and connection lugs complete in all respects.\nPower cable Copper 3 core 4 sq.mm | item577 | 100 | Metre |
| 576 | 576 | Providing and fixing heavy duty armoured cables 1.1 KVA grade including necessary support clamps at ceiling level and connection lugs complete in all respects.\nControl cable copper 2 core 1.5 sq.mm | item578 | 300 | Metre |
| 577 | 577 | Reverse Osmosis (RO) for best Quality Drinking Water.\nvi. Taurus-250 LPH do 100 Litres Storage | item579 | 10 | Each |
| 578 | 578 | Supply, installation, testing and commissioning of double wall insulated stainless steel water storage tank (inner sheet is SS 316 & outer sheet of SS-304), thickness of sheet as per manufacturer specification, placed at terrace level with inlet, outlet, overflow connection complete with 25 mm dia bend for vent, ball valve for scour, mosquito proof brass overflow grating and 600 mm dia manhole cover with locable arrangment completeas per direction of Engineer-in-charge.\n1500 Litres Capacity for RO Water | item580 | 4 | Each |
| 579 | 579 | Providing and fixing F.R.P. Grating drain cover M.S. Angle ( 35 x35 x 5 mm). ( Load Bearing cap. 2.5 T, suitable for car parking, basement, Pump room, Parking Area ).\n377mm wide and 30mm thick | item581 | 910 | Metre |
| 580 | 580 | FIRE FIGHTING WORKS\nFIRE PUMPS\nSupplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :\n(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.\n(b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.\n(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.\n(d)Suitable cement concrete foundation duly plastered with anti vibration pads.\n2280 lpm at 88 m Head (For Hydrant & Sprinkler System).\nNote: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. | item582 | 4 | Set |
| 581 | 581 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :\n(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.\n(b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.\n(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.\n(d)Suitable cement concrete foundation duly plastered with anti vibration pads.\n1620 lpm at 56 m Head (For Water Curtain System).\nNote: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. | item583 | 2 | Set |
| 582 | 582 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)\n(a) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.\n(b) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.\n(c) M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required.\n(d) Suitable cement concrete foundation duly plastered with anti vibration pads.\n2280 lpm at 88 m Head (For Hydrant & Sprinkler System).\nNote: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. | item584 | 4 | Set |
| 583 | 583 | Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump).\n(a) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520.\n(b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325.\n(c) M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.\n(d) Suitable cement concrete foundation duly plastered and with anti vibration pads.\n180 lpm at 88 m Head (For Hydrant & Sprinkler System). | item585 | 4 | Set |
| 584 | 584 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump).\n(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520.\n(b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.\n(c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.\n(d) Suitable cement concrete foundation duly plastered and with anti vibration pads.\n900 lpm at 35 m Head | item586 | 4 | Set |
| 585 | 585 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump).\n(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520.\n(b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.\n(c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.\n(d) Suitable cement concrete foundation duly plastered and with anti vibration pads.\n450 lpm at 35 m Head | item587 | 5 | Set |
| 586 | 586 | CONTROL PANELS\nFabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :\nIncomings\n400A, 50kA 4 Pole MCCB, Ics=100% Icu rating\nDigital Voltmeter 0-500V with selector switch\nAmmeter (0-400 A) with selector swtich & CTs etc.\nLED type RYB phase indicating lamps, ON, OFF, trip indicating lamps\nSet of Copper Bus Bar 500A\nOutgoings\n( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)\nMain Fire Pump\n200 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. 2 Set\nJockey Pump\n100 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. 2 Set\nDiesel Engine Control\nControl for diesel engine comprising -\nAutomatic/Manual selctor switch & 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode\nIndicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication\nBattery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter\nAll standard relays and accessories for automatic operation of diesel engine\nSystem Controller\nDesigning, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specifications. | item588 | 2 | Set |
| 587 | 587 | Pressurisation Pump and Terrace Pump Control\n(a) 63 Amps. TP & N SFC with HRC fuses\n(b) Voltmeter (0-500 Volt) with selector switch.\n© Ammeter (0-60 Amps.) with selector switch & CTs.\n(d) Set of 3 phase indication lamp\n(e) Suitable HP fully automatic Star/Delta Starter with over load protection, current sensing type single phase preventor complete with all accessories and internal wiring required for automatic operation.\n(f) Selector switch for local/remote, auto/manual/off operation ON/OFF indication etc. | item589 | 9 | Set |
| 588 | 588 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. It should be complete as per specifications & directions of Engineer-in-charge.\n4 x 25 sqmm ( 28 mm ) | item590 | 8 | Each |
| 589 | 589 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. It should be complete as per specifications & directions of Engineer-in-charge.\n3.5 x 50 sqmm ( 35 mm ) | item591 | 12 | Each |
| 590 | 590 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. It should be complete as per specifications & directions of Engineer-in-charge.\n3 X 10 sq. mm (22mm) | item592 | 18 | Each |
| 591 | 591 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.\n150 mm width x 50mm depth x 1.6 mm thickness. | item593 | 125 | Meter |
| 592 | 592 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | item594 | 8 | Set |
| 593 | 593 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. | item595 | 60 | Meter |
| 594 | 594 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. | item596 | 120 | Meter |
| 595 | 595 | Supplying & laying one number XLPE insulated PVC sheathed Aluminium Conductor armoured UG cable of 1.1 KV grade Conforming to IS 7098/1988 with upto date ammendment of following size in the existing RCC/HUME/ METAL /GI /CI /Stoneware/DWC pipe/ masonary Open Duct/ cable tray/ open in air etc. as requred.\n4 core, 25 sq.mm. Aluminium Armoured | item597 | 400 | Meter |
| 596 | 596 | Supplying & laying one number XLPE insulated PVC sheathed Aluminium Conductor armoured UG cable of 1.1 KV grade Conforming to IS 7098/1988 with upto date ammendment of following size in the existing RCC/HUME/ METAL /GI /CI /Stoneware/DWC pipe/ masonary Open Duct/ cable tray/ open in air etc. as requred.\n3.5 core, 50 sq.mm. Aluminium Armoured | item598 | 400 | Meter |
| 597 | 597 | Supplying & laying one number XLPE insulated PVC sheathed Aluminium Conductor armoured UG cable of 1.1 KV grade Conforming to IS 7098/1988 with upto date ammendment of following size in the existing RCC/HUME/ METAL /GI /CI /Stoneware/DWC pipe/ masonary Open Duct/ cable tray/ open in air etc. as requred.\n3 core, 10 sq.mm. Aluminium Armoured | item599 | 180 | Meter |
| 598 | 598 | Supply and fixing in position 1 m wide Insulation mat made of elastomeric polymers Material (Class -A) of 415V grade as per IS 15642-2006 . Thickness of insulation mat shall be not less than 2 mm to withstand 1.1 KV dielectric strength AS PER IS 15652 : 2006. It should be complete as per specifications & directions of Engineer-in-charge. | item600 | 20 | Meter |
| 599 | 599 | PIPES & ACCESSORIES\nProviding laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. ( For Underground )\n200 mm. dia (wall thickness = 6.3 mm) | item601 | 850 | Meter |
| 600 | 600 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. ( For Underground )\n150 mm. Dia | item602 | 2105 | Meter |
| 601 | 601 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. ( For Underground )\n100 mm. Dia | item603 | 220 | Meter |
| 602 | 602 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. ( For Underground )\n80 mm. Dia | item604 | 510 | Meter |
| 603 | 603 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n25 mm dia | item605 | 21664 | Meter |
| 604 | 604 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n32 mm dia | item606 | 3966 | Meter |
| 605 | 605 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n40 mm dia | item607 | 6461 | Meter |
| 606 | 606 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n50 mm dia | item608 | 6167 | Meter |
| 607 | 607 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n65 mm dia | item609 | 4382 | Meter |
| 608 | 608 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n80 mm dia | item610 | 4309 | Meter |
| 609 | 609 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n100 mm dia | item611 | 3786 | Meter |
| 610 | 610 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n150 mm dia | item612 | 6066 | Meter |
| 611 | 611 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n200 mm dia (wall thickness 6.3 mm) | item613 | 34 | Meter |
| 612 | 612 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n250 mm dia (wall thickness 6.3 mm) | item614 | 32 | Meter |
| 613 | 613 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. (Plant Room piping/Vertical Riser/Downcomer/Floor).\n300 mm dia (wall thickness 7.1 mm) | item615 | 12 | Meter |
| 614 | 614 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :\nSingle headed Stainless steel | item616 | 249 | Set |
| 615 | 615 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :\nSingle headed Stainless steel | item617 | 65 | Set |
| 616 | 616 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :\n50mm dia | item618 | 50 | Set |
| 617 | 617 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :\n80 mm dia | item619 | 54 | Set |
| 618 | 618 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :\n100 mm dia | item620 | 10 | Set |
| 619 | 619 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :\n150 mm dia | item621 | 194 | Set |
| 620 | 620 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :\n200 mm dia | item622 | 4 | Set |
| 621 | 621 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :\n250 mm dia | item623 | 2 | Set |
| 622 | 622 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. | item624 | 384 | Each |
| 623 | 623 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :\n80 mm dia | item625 | 18 | Set |
| 624 | 624 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :\n100 mm dia | item626 | 10 | Set |
| 625 | 625 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :\n150 mm dia | item627 | 27 | Set |
| 626 | 626 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :\n200 mm dia | item628 | 2 | Set |
| 627 | 627 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :\n250 mm dia | item629 | 2 | Set |
| 628 | 628 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.\n80 mm dia | item630 | 5 | Each |
| 629 | 629 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.\n100 mm dia | item631 | 5 | Each |
| 630 | 630 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.\n150 mm dia | item632 | 4 | Each |
| 631 | 631 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.\n200 mm dia | item633 | 4 | Each |
| 632 | 632 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :\nStainless Steel (Grade 304) | item634 | 628 | Set |
| 633 | 633 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.\n20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585\n20 mm nominal internal dia gun metal globe valve & nozzle.\nDrum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.\n40 m | item635 | 266 | Set |
| 634 | 634 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :\nStainless Steel (Grade 304) | item636 | 314 | Set |
| 635 | 635 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :\n2 way-100 mm dia M.S. Pipe. (FOR UG TANK ) | item637 | 23 | Set |
| 636 | 636 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :\n4 way - 150 mm dia M.S. Pipe. (FOR UG TANK & RISER) | item638 | 9 | Set |
| 637 | 637 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. | item639 | 49 | Set |
| 638 | 638 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :\nPendent Sprinkler | item640 | 10667 | Each |
| 639 | 639 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :\nUpright Sprinkler | item641 | 12909 | Each |
| 640 | 640 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :\nHorizontal side wall sprinkler | item642 | 506 | Each |
| 641 | 641 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. | item643 | 159 | Each |
| 642 | 642 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.\n100mm dia | item644 | 18 | Each |
| 643 | 643 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.\n150mm dia | item645 | 116 | Each |
| 644 | 644 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required :\n150mm dia | item646 | 16 | Set |
| 645 | 645 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.\n700 mm | item647 | 4267 | Each |
| 646 | 646 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.\n1000 mm | item648 | 4267 | Each |
| 647 | 647 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.\n1200 mm | item649 | 1067 | Each |
| 648 | 648 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.\n1500 mm | item650 | 1067 | Each |
| 649 | 649 | Supplying, installation, testing & commissioning of deluge valve (to be used for water curtains) UL listed with wet pilot basic trim assembly for DVA with test and alarm, drip and drain valve with water motor gong complete as required.\n100 mm dia | item651 | 2 | Set |
| 650 | 650 | Supplying, installation, testing & commissioning of deluge valve (to be used for water curtains) UL listed with wet pilot basic trim assembly for DVA with test and alarm, drip and drain valve with water motor gong complete as required.\n150 mm dia | item652 | 5 | Set |
| 651 | 651 | Providing, installation, testing & commissioning of water curtain nozzle 15mm dia nickel chrome plated brass, BSPT, K-factor as per design consideration complete as required. | item653 | 240 | Each |
| 652 | 652 | Providing, installation, testing & commissioning of electric release trim assembly for deluge wall with two way solelnoid valve, weather proof operation on 24 volts DC supply complete as required. | item654 | 7 | Set |
| 653 | 653 | Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. | item655 | 10667 | Each |
| 654 | 654 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required | item656 | 761 | Each |
| 655 | 655 | Providing and fixing standard fireman's axe with heavy insulated rubber handle conforming to IS: 926 complete. | item657 | 249 | Each |
| 656 | 656 | Providing & Fixing of MS door made up of 16 gauge MS Sheet capable of accommodating fire hose reel, landing valve, hose pipes, fittings, 1 No. CO2 & 1 No. Dry podwer type portable fire extinguishers & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with one coat of primer & two coat of finished stove enamelled post office red colour paint & \"FIRE HOSE\" written on front.\n(Approx. size of door: 2100 mm HEIGHT, WIDTH OF DOOR AS PER SHAFT SIZE ) | item658 | 266 | Each |
| 657 | 657 | Providing and fixing hose cabinet of size 700mmX600mm made of 16 gause thick MS sheet with 4 mm thick float glass doors in front painted \"FIRE\" in red paint i/c recessary locking arrangement suitable to accommodate external hydrant with butterfly valve 2 nos. 15 mtr. long hose pipe. 1 no. brach pipe mounted on wall or raised brick platform & duly painted with post office red externally and white internally with synthetic enamel paint complete in all respects for external hydrant. as directed by Engineer-in-Charge. | item659 | 65 | Each |
| 658 | 658 | Pressure Vessel\nSupplying, installing, testing and commissioning of pressure vessel for pressurization of fire system complete with valves at outlet / drain to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, outside with one coat of primer & two coats of synthetic enamel paint of approved shade complete as required to operate commonly main fire pump, sprinkler pump & jockey pump at drop of pressure, automatically at required pressure setting. Complete as per manufacturer's specifications & as directed by Engineer- in-charge.\nworking pressure:- 11 kg/sqcm\ntest pressure: 20 kg/sqcm\n(450 mm dia & 2000 mm height) | item660 | 6 | Nos. |
| 659 | 659 | Providing, Fixing, testing and commissioning of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 11 Kg/cm2 and test pressure 16 Kg/cm2 to provide relief from stresses at pipe flanges.\n150 mm dia | item661 | 20 | Nos. |
| 660 | 660 | Providing, Fixing, testing and commissioning of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 11 Kg/cm2 and test pressure 16 Kg/cm2 to provide relief from stresses at pipe flanges.\n80 mm dia | item662 | 26 | Nos. |
| 661 | 661 | Supply, fixing, testing and commissioning of screwed type brass/bronze lever operated ball valve of full flow with stainless steel ball (AISI 304 & spindle AISI 410) with setting & gland of superior quality having minimum working pressure of 16 kg/sqcm.\n25 mm Dia | item663 | 28 | Nos. |
| 662 | 662 | Providing and fixing 25 mm dia inspection & testing assembly with gun metal ball valve, gun metal sight glass connection to drain pipe/riser. | item664 | 134 | Set |
| 663 | 663 | Providing & fixing cast iron 100 mm dia. Foot valve with nuts, bolts, 1.5 mm thick CAF gasket complete with all accessories (To be provided into UG Fire Water Tanks). | item665 | 3 | Each |
| 664 | 664 | Providing, fixing water flow meter on test line complete with all accessories for flow indication , monitoring & testing of fire pumps with bypass arrangment including piping & bypass valves.\n150 mm dia | item666 | 2 | Each |
| 665 | 665 | FIRE EXTINGUISHERS\nProviding, storing, handling, shifting, installation, testing and commissioning of halon free portable fire Extinguishers as described below:\nProviding and fixing of 4.5 Kg. carbon-di-oxide type fire extinguishers consisting of welded M.S. cylinderical body, squeeze lever discharge valve fitted with pressure indicating guase ingernal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming ro IS:15683 finished externally with re enamel paint and fixed to wall with brackets complete with internal charge. | item667 | 258 | Nos. |
| 666 | 666 | Providing, storing, handling, shifting, installation, testing and commissioning of halon free portable fire Extinguishers as described below:\nProviding and fixing 6.0 Kg. ABC Powder type fire extinguishers consisting of welded M.S. cylinderical body, squeeze lever discharge valve fitted with pressure indicating guase internal discharge tube 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket conforming to IS:15683 finished externally with re enamel paint and fixed to wall with brackets complete with inernal charge. | item668 | 258 | Nos. |
| 667 | 667 | Providing, storing, handling, shifting, installation, testing and commissioning of halon free portable fire Extinguishers as described below:\nProviding and fixing mechanical foam type fire extingushers consisting of welded M.S. trolley mounted cylindrical body, squeeze lever discharge valve fitted with pressure discharge hose, discharge nozzle, trolley etc., ISI marked as per IS:IS:13386 finished externally with red enamel paint.\nCapacity 50 lit (D.G.Room) | item669 | 2 | Nos. |
| 668 | 668 | Providing, storing, handling, shifting, installation, testing and commissioning of halon free portable fire Extinguishers as described below:\nProviding and fixing carbon-di-oxide fire extingushers trolley mounted with all accessories internal discharge tube,high pressure discharge hose,discharge nozzle, ISI marked as per IS:2878 finished externally with red enamel paint.\nCapacity 22.5 kg | item670 | 4 | Nos. |
| 669 | 669 | LT & HT PANEL, ELECTRICAL ROOM & SERVER ROOM GAS FLOODING SYSTEM:-\n5 LB capacity Novec 1230 , DLP Assembly with automatic valve, push in connector for tube, 5 LB Novec 1230 gas , mounting bracket, End of Line adopter and low pressure switch for monitoring system activation. | item671 | 4 | No. |
| 670 | 670 | 10 LB capacity Novec 1230 , DLP Assembly with automatic valve, push in connector for tube, 10 LB Novec 1230 gas , mounting bracket, End of Line adopter and low pressure switch for monitoring system activation. | item672 | 10 | No. |
| 671 | 671 | Linear Pneumatic Heat detection tube with all necessary & supperts | item673 | 625 | Meter |
| 672 | 672 | Master Control Unit with Audio Visual Alarm with wiring to make complete system operational . The control Panel should have provision for integration with fire Alarm /SCAD/BMS System. | item674 | 14 | No. |
| 673 | 673 | Supply, fixing, testing and commissioning of 1x40 Itr completele system with CCOE approved high pressure, seamless Cylinders having sutable 40 ltr water capacity & suitable to store Novec 1230 (FK5-1-12) gas at 34.5 bar pressure with valve assembly, low pressure supervisory switch for monitoring cylinder pressure gauge with safety burst disc safety cap, elbow and other accessories, mounting bracket, container straps, NRV. Electrically operated control head capable of being electrically operated from the fire detection & control, Pressure operated control head which shall allow for pressure actuation of gas mounted directly on top of cylinder valve, manually operated actuator to actuate the gas flooding process with the help of a lever, flexible rubber hose with wire bralded enforcment to route the gas from the storage cyinder to the discharge piping, to be connected to the discharge outlet of gas cylinder valve & to be terminated at the system piping or discharge manifold, Flexible actuation hose complete as required. Discharge nozzle, 180/360 degree. Designated to provide proper flow rate & distrbution Novec 1230 (FK5-1-12) gas to flood the hazard area as per requrement. Electrical non conductive,Novec 1230 (FK5-1-12) required as per NFPA 2001 latest eddition 4.5% Design Concentration. Piping ASTM grade A 106 schedule 40 with fittings & supports and Gas Release Panel compatible to Fire Alarm System. | item675 | 5 | Set |
| 674 | 674 | Supply, fixing, testing and commissioning of 1x150 Itr completele system with CCOE approved high pressure, seamless Cylinders having sutable 150 ltr water capacity & suitable to store Novec 1230 (FK5-1-12) gas at 34.5 bar pressure with valve assembly, low pressure supervisory switch for monitoring cylinder pressure gauge with safety burst disc safety cap, elbow and other accessories, mounting bracket, container straps, NRV. Electrically operated control head capable of being electrically operated from the fire detection & control, Pressure operated control head which shall allow for pressure actuation of gas mounted directly on top of cylinder valve, manually operated actuator to actuate the gas flooding process with the help of a lever, flexible rubber hose with wire bralded enforcment to route the gas from the storage cyinder to the discharge piping, to be connected to the discharge outlet of gas cylinder valve & to be terminated at the system piping or discharge manifold, Flexible actuation hose complete as required. Discharge nozzle, 180/360 degree. Designated to provide proper flow rate & distrbution Novec 1230 (FK5-1-12) gas to flood the hazard area as per requrement. Electrical non conductive,Novec 1230 (FK5-1-12) required as per NFPA 2001 latest addition 4.7% Design Concentration. Piping ASTM grade A 106 schedule 40 with fittings & supports and Gas Release Panel compatible to Fire Alarm System. | item676 | 3 | Set |
| 675 | 675 | Internal Electrical\nWiring for light/fan/call bell point with 3x1.5 sq. mm. P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed conduit wiring system with 20mm dia 2mm thick / heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including 6 Amp flush type switch/ bell push (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) GI/ MS switch board (ISI marked) with phenolic laminated sheet cover ,ceiling rose etc. complete. Short point upto 3.00 metre length. | item677 | 5478 | Each |
| 676 | 676 | Wiring for light/fan/call bell point with 3x1.5 sq. mm. P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed conduit wiring system with 20mm dia 2mm thick / heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including 6 Amp flush type switch/ bell push (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) GI/ MS switch board (ISI marked) with phenolic laminated sheet cover ,ceiling rose etc. complete. Medium point upto 6.00 metre length. | item678 | 11671 | Each |
| 677 | 677 | Wiring for light/fan/call bell point with 3x1.5 sq. mm. P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed conduit wiring system with 20mm dia 2mm thick / heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including 6 Amp flush type switch/ bell push (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) GI/ MS switch board (ISI marked) with phenolic laminated sheet cover ,ceiling rose etc. complete. Long point upto 10.00 metre length. | item679 | 10889 | Each |
| 678 | 678 | Wiring for circuit wiring with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) wiring system. With 3 x 1.5 sq. mm. cable in 20 mm dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit. | item680 | 81985 | Metre |
| 679 | 679 | Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including earth continuity in surface/ recessed 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit wiring system. With 2 x 2.5 sq. mm. + earth continuity with 1x1.5 sq. mm. in 20 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit. | item681 | 106314 | Metre |
| 680 | 680 | Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including earth continuity in surface/ recessed 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit wiring system. With 2 x 4 sq. mm. + earth continuity with 1x2.5 sq. mm. cable in 20 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit. | item682 | 122052 | Metre |
| 681 | 681 | Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including earth continuity in surface/ recessed 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit wiring system. With 2 x 6 sq. mm. + earth continuity with 1x 4 sq. mm. cable in 25 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit. | item683 | 19148 | Metre |
| 682 | 682 | Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including earth continuity in surface/ recessed 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit wiring system. With 2 x 10 sq. mm. + earth continuity with 1x 6 sq. mm. cable in 25 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit. | item684 | 2613 | Metre |
| 683 | 683 | Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed PVC 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) wiring system. With 4 x 4 sq. mm. + earth continuity with 2x2.5 sq. mm. cable in 25 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit. | item685 | 31648 | Metre |
| 684 | 684 | Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed PVC 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) wiring system. With 4x 6 sq. mm. + earth continuity with 2x4 sq. mm. cable in 32 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit. | item686 | 10059 | Metre |
| 685 | 685 | Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed PVC 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) wiring system. With 4 x 10 sq. mm. + earth continuity with 2x6 sq. mm. cable in 40 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit. | item687 | 1115 | Metre |
| 686 | 686 | Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed PVC 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) wiring system. With 4 x 16 sq. mm. + earth continuity with 2x10 sq. mm. cable in 40 mm. dia. 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit. | item688 | 13137 | Metre |
| 687 | 687 | Wiring to 5 a pin 6 Amps plug point with 1.5 sq. mm P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed 2 mm thick/ heavy rigid ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) wiring system including earth continuity with 1.5 sq. mm. cable to third pin of the plug socket etc. as required complete. Short point upto 3.00 metre length. | item689 | 1381 | Each |
| 688 | 688 | Wiring to 5 a pin 6 Amps plug point with 1.5 sq. mm P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed 2 mm thick/ heavy rigid ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) wiring system including earth continuity with 1.5 sq. mm. cable to third pin of the plug socket etc. as required complete. Medium point upto 6.00 metre length. | item690 | 7071 | Each |
| 689 | 689 | Wiring to 5 a pin 6 Amps plug point with 1.5 sq. mm P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed 2 mm thick/ heavy rigid ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) wiring system including earth continuity with 1.5 sq. mm. cable to third pin of the plug socket etc. as required complete. Long point upto 10.00 metre length. | item691 | 5642 | Each |
| 690 | 690 | Wiring for 5/6 pin 16 Amps power plug point with 4 sq. mm. P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed conduit wiring system including earth continuity with 2.5 sq. mm cable to the 3rd pin of the socket as required complete with 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) Short point upto 3.00 metre length. | item692 | 375 | Each |
| 691 | 691 | Wiring for 5/6 pin 16 Amps power plug point with 4 sq. mm. P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed conduit wiring system including earth continuity with 2.5 sq. mm cable to the 3rd pin of the socket as required complete with 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) Medium point upto 6.00 metre length. | item693 | 6160 | Each |
| 692 | 692 | Wiring for 5/6 pin 16 Amps power plug point with 4 sq. mm. P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed conduit wiring system including earth continuity with 2.5 sq. mm cable to the 3rd pin of the socket as required complete with 20 mm. dia. 2mm thick/ heavy ISI marked IS: 9537 PART - III rigid PVC conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) Long point upto 10.00 metre length. | item694 | 5471 | Each |
| 693 | 693 | Wiring for twin control light point with 1.5 sq mm P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed conduit wiring system with 20mm dia 2mm thick / heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including 6 amp flush type 2 way switch (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) GI/ MS switch board (ISI marked) with phenolic laminated sheet cover ,ceiling rose (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) etc. complete. Medium point upto 6.00 metre length. | item695 | 381 | Each |
| 694 | 694 | Wiring for twin control light point with 1.5 sq mm P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed conduit wiring system with 20mm dia 2mm thick / heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including 6 amp flush type 2 way switch (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) GI/ MS switch board (ISI marked) with phenolic laminated sheet cover ,ceiling rose (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) etc. complete. Long point upto 10.00 metre length. | item696 | 389 | Each |
| 695 | 695 | Supplying and fixing 19 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by the Dept.) in surface/recessed including cutting the wall and making good the same ti its original architectural finish. | item697 | 11775 | Metre |
| 696 | 696 | Supplying and fixing 25 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by the Dept.) in recessed including cutting the wall and making good the same ti its original architectural finish. | item698 | 9303 | Metre |
| 697 | 697 | Supplying and fixing 32 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by the Dept.) in recessed including cutting the wall and making good the same ti its original architectural finish. | item699 | 145 | Metre |
| 698 | 698 | Supplying and fixing 38 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by the Dept.) in recessed including cutting the wall and making good the same ti its original architectural finish. | item702 | 145 | Metre |
| 699 | 699 | Supplying and fixing 50 mm dia ISI marked steel conduit pipe (AKG or equivalent as approved by the Dept.) in recessed including cutting the wall and making good the same ti its original architectural finish. | item703 | 145 | Metre |
| 700 | 700 | Supply and fixing 19 mm dia 2.00mm average wall thickness heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) in recessed system including cutting the wall and making good the same as required: | item704 | 44290 | Metre |
| 701 | 701 | Supply and fixing 25 mm dia 2.00mm average wall thickness heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) in recessed system including cutting the wall and making good the same as required: | item705 | 119135 | Metre |
| 702 | 702 | Supply and fixing 32 mm dia 2.00mm average wall thickness heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) in recessed system including cutting the wall and making good the same as required: | item706 | 28465 | Metre |
| 703 | 703 | Supply and fixing 38 mmdia 2.00mm average wall thickness heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) in recessed system including cutting the wall and making good the same as required: | item707 | 145 | Metre |
| 704 | 704 | Supply and fixing 50 mmdia 2mm thick 2.00mm average wall thickness heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) in recessed system including cutting the wall and making good the same as required: | item708 | 145 | Metre |
| 705 | 705 | Supplying and fixing of following Metal Boxes for Model Range Legrand (Arteor), Anchor (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) in surface / recessed system complete as per direction of department. 1-2 Module Type Metal | item709 | 8388 | Each |
| 706 | 706 | Supplying and fixing of following Metal Boxes for Model Range Legrand (Arteor), Anchor (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) in surface / recessed system complete as per direction of department. 3 Module Type Metal | item710 | 10903 | Each |
| 707 | 707 | Supplying and fixing of following Metal Boxes for Model Range Legrand (Arteor), Anchor (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) in surface / recessed system complete as per direction of department. 6 Module Type Metal | item711 | 7357 | Each |
| 708 | 708 | Supplying and fixing of following Metal Boxes for Model Range Legrand (Arteor), Anchor (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) in surface / recessed system complete as per direction of department. 8 Module Type Metal | item712 | 17 | Each |
| 709 | 709 | Supplying and fixing of following Metal Boxes for Model Range Legrand (Arteor), Anchor (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) in surface / recessed system complete as per direction of department. 12 Module Type Metal | item713 | 110 | Each |
| 710 | 710 | Supplying including fitting fixing of following MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE(MURANO) front plate of suitable colour as per direction of department. 1 module | item714 | 1380 | Each |
| 711 | 711 | Supplying including fitting fixing of following MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE(MURANO) front plate of suitable colour as per direction of department. 2 module | item715 | 7008 | Each |
| 712 | 712 | Supplying including fitting fixing of following MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE(MURANO) front plate of suitable colour as per direction of department. 3 module | item716 | 10903 | Each |
| 713 | 713 | Supplying including fitting fixing of following MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE(MURANO) front plate of suitable colour as per direction of department. 6 module | item717 | 7357 | Each |
| 714 | 714 | Supplying including fitting fixing of following MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE(MURANO) front plate of suitable colour as per direction of department. 8 module | item718 | 17 | Each |
| 715 | 715 | Supplying including fitting fixing of following MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE(MURANO) front plate of suitable colour as per direction of department. 12 module | item719 | 110 | Each |
| 716 | 716 | Supplying including installation of socket outlet 6/10/13 Amps INTERNATIONAL SOCKET, MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) including making necessary connections as per direction of department. | item720 | 14078 | Each |
| 717 | 717 | Supplying with fitting fixing of 6/10 amp one way modular clip in switch, MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE(MURANO) including making necessary connection as per direction of department. | item721 | 9121 | Each |
| 718 | 718 | Supplying including installation of socket outlet 10/16 Amps 3/5 pin combine shuttered complete , MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE(MURANO) including making necessary connection as per direction of department. | item722 | 12785 | Each |
| 719 | 719 | Supplying with fitting and fixing of 16 amp one way modular clip in switch, MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) including making necessary connections as per direction of department. | item723 | 12040 | Each |
| 720 | 720 | Supplying with fitting and fixing of 6 amp one way modular clip in bell push MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) including making necessary connections as per direction of department. | item724 | 136 | Each |
| 721 | 721 | Supplying with fitting and fixing of 6/10 amp two way modular clip in switch, MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) including making necessary connections as per direction of department. | item725 | 17 | Each |
| 722 | 722 | 20A Capacity. (ABB, Schneider MG, legrand, Hager make) | item727 | 218 | Each |
| 723 | 723 | Supplying and fixing 32 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 32 A \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. | item728 | 254 | Each |
| 724 | 724 | Supplying fitting and fixing industrial plug & socket in surface mounted TPN sheet steel powder painted MCB DB incorporated with MCB DIN rail, neutral link Earth bar of the following rating of 4P MCB complete with making necessary connection etc. as specified and directed by the Dept. (ABB, Schneider MG, legrand, Hager make). 30/32A Capacity | item729 | 542 | Each |
| 725 | 725 | Supplying with fitting and fixing sheet steel, phosphatised, powder painted dust & vermin proof Double door(IP-43) surface mounting SPN MCB DB incorporated with bus-bar, Neutral link, Earth Bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved , specified & directed by the dept. (ABB, Schneider MG, legrand, Hager, Crabtree xpro make). 8 way SPN double door | item730 | 71 | Each |
| 726 | 726 | Supplying with fitting and fixing sheet steel, phosphatised, powder painted dust & vermin proof Double door(IP-43) surface mounting SPN MCB DB incorporated with bus-bar, Neutral link, Earth Bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved , specified & directed by the dept. (ABB, Schneider MG, legrand, Hager, Crabtree xpro make). 12 way SPN double door | item731 | 104 | Each |
| 727 | 727 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door | item732 | 75 | Each |
| 728 | 728 | Supplying with fitting and fixing sheet steel, phosphatised, powder painted dust & vermin proof Double door(IP-43) surface mounting vertical per phase isolation (PP) DB incorporated with bus-bar 125A, Neutral link, Earth Bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved , specified & directed by the dept. (ABB, Schneider MG, legrand, Hager, Crabtree xpro make) 6 way TPN (8+6+18) double door | item733 | 70 | Each |
| 729 | 729 | Supplying with fitting and fixing sheet steel, phosphatised, powder painted dust & vermin proof Double door(IP-43) surface mounting vertical per phase isolation (PP) DB incorporated with bus-bar 125A, Neutral link, Earth Bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved , specified & directed by the dept. (ABB, Schneider MG, legrand, Hager, Crabtree xpro make) 8 way TPN (8+6+24) double door | item734 | 228 | Each |
| 730 | 730 | Supplying with fitting and fixing sheet steel, phosphatised, powder painted dust & vermin proof Double door(IP-43) surface mounting vertical per phase isolation (PP) DB incorporated with bus-bar 125A, Neutral link, Earth Bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved , specified & directed by the dept. (ABB, Schneider MG, legrand, Hager, Crabtree xpro make) 12 way TPN (8+6+36) double door | item735 | 555 | Each |
| 731 | 731 | Supplying with fitting and fixing MCCB income and MCB outgoing sheet steel, phosphatised, powder painted double door IP-43 surface mounting vertical TPN MCB DB incorporated with bas-bar up to 250A, Neutral link, Earth bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved, specified and directed by the deptt. 4 way TPN (4+12) double door | item736 | 88 | Each |
| 732 | 732 | Supplying with fitting and fixing MCCB income and MCB outgoing sheet steel, phosphatised, powder painted double door IP-43 surface mounting vertical TPN MCB DB incorporated with bas-bar up to 250A, Neutral link, Earth bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved, specified and directed by the deptt. 8way TPN (4+18) double door | item737 | 91 | Each |
| 733 | 733 | Supplying with fitting and fixing MCCB income and MCB outgoing sheet steel, phosphatised, powder painted double door IP-43 surface mounting vertical TPN MCB DB incorporated with bas-bar up to 250A, Neutral link, Earth bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved, specified and directed by the deptt. 12 way TPN (4+36) double door | item738 | 11 | Each |
| 734 | 734 | Supplying with fitting and fixing single pole 10KA 240/415V 50Hz MCB of the following capacity complete with making necessay connection as approved, specified and directed by the Dept. (Schneider MG, legrand, Hager, Crabtree xpro make) 6 to 32A | item739 | 23556 | Each |
| 735 | 735 | Supplying with fitting and fixing 30/100/300mA sensitivity 240/415V 50Hz DP RCCB of the following capacity complete with making necessary connection as approved, spcified and directed by the dept. ( ABB, Schneider MG, legrand, Hager, Crabtree xpro make) 25A | item740 | 361 | Each |
| 736 | 736 | Supplying with fitting and fixing 30/100/300mA sensitivity 240/415V 50Hz DP RCCB of the following capacity complete with making necessary connection as approved, spcified and directed by the dept. ( ABB, Schneider MG, legrand, Hager, Crabtree xpro make) 40A | item741 | 396 | Each |
| 737 | 737 | Supplying with fitting and fixing 30/100/300mA sensitivity 240/415V 50Hz DP RCCB of the following capacity complete with making necessary connection as approved, spcified and directed by the dept. ( ABB, Schneider MG, legrand, Hager, Crabtree xpro make) 63A | item742 | 2019 | Each |
| 738 | 738 | 100/300mA sensitivity DP RCCB 25A | item743 | 7 | Each |
| 739 | 739 | 100/300mA sensitivity DP RCCB 40A | item744 | 14 | Each |
| 740 | 740 | 100/300mA sensitivity DP RCCB 63A | item745 | 14 | Each |
| 741 | 741 | Supplying with fitting and fixing TP 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 6 to 32A | item746 | 197 | Each |
| 742 | 742 | Supplying with fitting and fixing TP 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 40A | item747 | 80 | Each |
| 743 | 743 | Supplying with fitting and fixing TP 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 63A | item748 | 932 | Each |
| 744 | 744 | Supplying with fitting and fixing Surge protector of max operation voltage 350V at 400 V network for maximum discharge current 40KA with operator indicator and draw out cartridge of (Schneider or equivalent make), of the following ways complete with making necessary connection as approved, specified and directed by the dept. 1P+N | item749 | 74 | Each |
| 745 | 745 | Supplying with fitting and fixing Surge protector of max operation voltage 350V at 400 V network for maximum discharge current 40KA with operator indicator and draw out cartridge of (Schneider or equivalent make), of the following ways complete with making necessary connection as approved, specified and directed by the dept. 3P+N | item750 | 795 | Each |
| 746 | 746 | Supplying, installation of pre galvanised sheet steel std thickness 1.6mm under floor / ceiling trunking including necessary nuts & bolts, washer etc. as required, as directed and specified by the department. ( MK/ LEGRAND make) Size 100X38X1.6/1 compartment | item751 | 3360 | Metre |
| 747 | 747 | Supplying, installation of pre galvanised sheet steel std thickness 1.6mm under floor / ceiling trunking including necessary nuts & bolts, washer etc. as required, as directed and specified by the department. ( MK/ LEGRAND make) Size 150X38X1.6/2 compartment | item752 | 2117 | Metre |
| 748 | 748 | Supplying, installation of pre galvanised sheet steel std thickness 1.6mm under floor / ceiling trunking including necessary nuts & bolts, washer etc. as required, as directed and specified by the department. ( MK/ LEGRAND make) Size 225X38X1.6/3 compartment | item753 | 1130 | Metre |
| 749 | 749 | Supplying, installation of pre galvanised sheet steel std thickness 1.6mm under floor / ceiling trunking including necessary nuts & bolts, washer etc. as required, as directed and specified by the department. ( MK/ LEGRAND make) Size 250X38X1.6/3 compartment | item754 | 1765 | Metre |
| 750 | 750 | Supplying, installation of pre galvanised sheet steel std thickness 1.6mm under floor / ceiling trunking including necessary nuts & bolts, washer etc. as required, as directed and specified by the department. ( MK/ LEGRAND make) Size 300X38X1.6/3 compartment | item755 | 181 | Metre |
| 751 | 751 | JUNCTION BOX 150X150X60 - 75 mm Depth | item756 | 468 | Each |
| 752 | 752 | JUNCTION BOX 250X250X60 - 75 mm Depth | item757 | 316 | Each |
| 753 | 753 | JUNCTION BOX 300X300X60 - 75 mm Depth | item758 | 237 | Each |
| 754 | 754 | JUNCTION BOX 350X350X60 - 75 mm Depth | item759 | 14 | Each |
| 755 | 755 | JOINT SLEEVE 100/1/6 FOR 38mm | item760 | 206 | Each |
| 756 | 756 | JOINT SLEEVE 150/2/6 FOR 38mm | item761 | 109 | Each |
| 757 | 757 | JOINT SLEEVE 225/3/6 FOR 38mm | item762 | 80 | Each |
| 758 | 758 | JOINT SLEEVE 250/3/6 FOR 38mm | item763 | 63 | Each |
| 759 | 759 | JOINT SLEEVE 300/3/6 FOR 38mm | item764 | 12 | Each |
| 760 | 760 | Cross over/ Junction box Cross over 250X250X60 - 75mm 3 compartments | item765 | 29 | Each |
| 761 | 761 | Cross over/ Junction box Cross over 300X300X60 - 75mm 3 compartments | item766 | 14 | Each |
| 762 | 762 | Cross over/ Junction box Cross over 350X350X60 - 75mm 3 compartments | item767 | 7 | Each |
| 763 | 763 | Supplying including fitting and fixing of TV SOCKET, MODEL RANGE LEGRAND (ARTEOR), ANCHOR (AVE), MK (BLENZE), SCHNEIDER (ZENSELO), CRABTREE (MURANO) including making necessary connections as per direction of department. | item768 | 873 | Each |
| 764 | 764 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. | item769 | 25338 | Meter |
| 765 | 765 | Supply, erection, testing and commissioning of following sizes of splitter of aluminium die cast body in suitable size of G.I. Box. 6 way | item770 | 71 | Each |
| 766 | 766 | Supply, erection, testing and commissioning of following sizes of splitter of aluminium die cast body in suitable size of G.I. Box. 8 way | item771 | 99 | Each |
| 767 | 767 | ELECTRICAL PANEL GROUND FLOOR (JUNIOR RESIDENT) - Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. INCOMING 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. OUTGOING METERING 2 Nos Single Phase KWHr Meter Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item772 | 1 | Set |
| 768 | 768 | METER BOARD - 1 FIRST FLOOR (JUNIOR RESIDENT) - Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. INCOMING 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. OUTGOING METERING 4 Nos Single Phase KWHr Meter Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item773 | 1 | Set |
| 769 | 769 | METER BOARD - 2 TYPICAL FOR 2ND TO 6TH FLOOR (JUNIOR RESIDENT) - Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. INCOMING 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. OUTGOING METERING 10 Nos Single Phase KWHr Meter Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item774 | 5 | Set |
| 770 | 770 | ELECTRICAL PANEL GROUND FLOOR (DG SUPPLY) (JUNIOR RESIDENT) (TYPICAL FOR SENIOR RESIDENT) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. INCOMING 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item775 | 2 | Set |
| 771 | 771 | LIFT PANEL (JUNIOR RESIDENT) (TYPICAL FOR SENIOR RESIDENT) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. INCOMING 1 No Fixed type Automatic transfer switch 100 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item776 | 2 | Set |
| 772 | 772 | ELECTRICAL PANEL GROUND FLOOR (NON DG SUPPLY) (SENIOR RESIDENT) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. INCOMMING 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 200 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item777 | 1 | Set |
| 773 | 773 | METER BOARD - 1 TYPICAL FOR GROUND TO 3RD FLOOR (SENIOR RESIDENT) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 6 Nos Single Phase KWHr Meter Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item778 | 4 | Set |
| 774 | 774 | ELECTRICAL PANEL GROUND FLOOR (NON DG SUPPLY) (FEMALE INTERN HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 6 Nos Single Phase KWHr Meter Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item779 | 1 | Set |
| 775 | 775 | ELECTRICAL PANEL GROUND FLOOR (DG SUPPLY) (FEMALE INTERN HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item780 | 1 | Set |
| 776 | 776 | METER BOARD - 1 FIRST FLOOR (FEMALE INTERN HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 9 Nos Single Phase KWHr Meter Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item781 | 1 | Set |
| 777 | 777 | METER BOARD - 2 TYPICAL FOR 2ND & 3RD FLOOR (FEMALE INTERN HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 9 Nos Single Phase KWHr Meter Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item782 | 2 | Set |
| 778 | 778 | LIFT PANEL (FEMALE INTERN HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 100 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. BUS BARS 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item783 | 1 | Set |
| 779 | 779 | ELECTRICAL PANEL GROUND FLOOR (NON DG SUPPLY) (MALE INTERN HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item784 | 1 | Set |
| 780 | 780 | ELECTRICAL PANEL GROUND FLOOR (DG SUPPLY) (MALE INTERN HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item785 | 1 | Set |
| 781 | 781 | METER BOARD - 1 TYPICAL FOR 1ST & 2ND FLOOR (MALE INTERN HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 13 Nos Single Phase KWHr Meter. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item786 | 2 | Set |
| 782 | 782 | LIFT PANEL (MALE INTERN HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 100 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item787 | 1 | Set |
| 783 | 783 | ELECTRICAL PANEL GROUND FLOOR (NON DG SUPPLY) (NURSE HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item788 | 1 | Set |
| 784 | 784 | ELECTRICAL PANEL GROUND FLOOR (DG SUPPLY) (NURSE HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item789 | 1 | Set |
| 785 | 785 | METER BOARD - 1 TYPICAL FOR GROUND & FIRST FLOOR (NURSE HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 4 Nos Single Phase KWHr Meter. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item790 | 2 | Set |
| 786 | 786 | METER BOARD - 2 TYPICAL FOR 2ND TO 7TH FLOOR (NURSE HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 8 Nos Single Phase KWHr Meter. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item791 | 6 | Set |
| 787 | 787 | LIFT PANEL (NURSE HOSTEL)Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 100 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item792 | 1 | Set |
| 788 | 788 | ELECTRICAL PANEL GROUND FLOOR (NON DG SUPPLY) (BOY'S HOSTEL) (TYPICAL FOR GIRLS HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 500 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item793 | 2 | Set |
| 789 | 789 | ELECTRICAL PANEL GROUND FLOOR (DG SUPPLY) (BOY'S HOSTEL) (TYPICAL FOR GIRLS HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item794 | 2 | Set |
| 790 | 790 | ELECTRICAL PANEL-1 FOR GROUND & FIRST FLOOR (TYPICAL FOR 2ND & 3RD FLOOR) (BOY'S HOSTEL) (TYPICAL FOR GIRL'S HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 200 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item795 | 4 | Set |
| 791 | 791 | KITCHEN PANEL (BOY'S HOSTEL) (TYPICAL FOR GIRL'S HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item796 | 2 | Set |
| 792 | 792 | LIFT PANEL (BOY'S HOSTEL) (TYPICAL FOR GIRL'S HOSTEL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 100 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item797 | 2 | Set |
| 793 | 793 | ELECTRICAL PANEL GROUND FLOOR (DG SUPPLY) (TYPE-II & III RESIDENCE) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 200 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item798 | 1 | Set |
| 794 | 794 | ELECTRICAL PANEL GROUND FLOOR (DG SUPPLY) (TYPICAL FOR TYPE-IV&V) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 200 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 2 Nos Single Phase KWHr Meter. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item799 | 1 | Set |
| 795 | 795 | METER BOARD - 1 TYPICAL FOR GROUND TO 17TH FLOOR (TYPE-II & III) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 4 Nos Single Phase KWHr Meter. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item800 | 18 | Set |
| 796 | 796 | LIFT PANEL (TYPE-II RESIDENCE) (TYPICAL FOR TYPE-II & III, TYPE-IV&V) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 100 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item801 | 2 | Set |
| 797 | 797 | METER BOARD - 1 TYPICAL FOR GROUND TO 1ST FLOOR (TYPE-IV&V) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 3 Nos Single Phase KWHr Meter. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item802 | 2 | Set |
| 798 | 798 | METER BOARD -2 TYPICAL FOR SECOND TO 7TH FLOOR (TYPE-IV&V) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 3 Nos Single Phase KWHr Meter. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item803 | 6 | Set |
| 799 | 799 | METER BOARD -3, 8TH FLOOR (TYPE-IV&V) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. 4 Nos Single Phase KWHr Meter. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item804 | 1 | Set |
| 800 | 800 | METER BOARD -4 (NINENTH FLOOR) (DIRECTOR'S RESIDENCE) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item805 | 2 | Set |
| 801 | 801 | ELECTRICAL PANEL (NON DG BACK UP) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 2 No. Digital Multifunction Meter with inbuilt selector switch. 2 Set of phase indicating lamps with Single Pole MCB. 2 Set of ON / OFF indicating lamps with Single Pole MCB. 2000 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. The Bus Coupler shall be Electrically / Mechanically interlocked with both the incomers. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item806 | 1 | Set |
| 802 | 802 | ELECTRICAL PANEL (DG BACK UP) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 2 No. Digital Multifunction Meter with inbuilt selector switch. 2 Set of phase indicating lamps with Single Pole MCB. 2 Set of ON / OFF indicating lamps with Single Pole MCB. 1600 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. The Bus Coupler shall be Electrically / Mechanically interlocked with both the incomers. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item807 | 1 | Set |
| 803 | 803 | MEDICAL EQUIPMENT PANEL (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 2 No. Digital Multifunction Meter with inbuilt selector switch. 2 Set of phase indicating lamps with Single Pole MCB. 2 Set of ON / OFF indicating lamps with Single Pole MCB. 1600 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item808 | 2 | Set |
| 804 | 804 | POWER+AHU PANEL-1 DG BACK UP (LEFT SIDE) (GROUND FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 400 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item809 | 2 | Set |
| 805 | 805 | LIFT & STAIRCASE VENTILATION PANEL-1 (LEFT SIDE) (TERRACE FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item810 | 2 | Set |
| 806 | 806 | LAB PANEL-1 (MID SIDE) (FIRST FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 400 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item811 | 2 | Set |
| 807 | 807 | UPS PANEL-1 (GROUND FLOOR, UPPER SIDE), TYPICAL FOR UPS PANEL-3 (THIRD FLOOR, LEFT SIDE), UPS PANEL-5 (7TH FLOOR, LEFT SIDE), UPS PANEL-2 (FIRST FLOOR, MID SIDE), UPS PANEL-3 (SECOND FLOOR, MID SIDE), (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 63 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item812 | 5 | Set |
| 808 | 808 | UPS PANEL-1 (GROUND FLOOR, LEFT SIDE), TYPICAL FOR UPS PANEL-2 (2ND FLOOR, LEFT SIDE), UPS PANEL-4 (4TH FLOOR, LEFT SIDE), UPS PANEL-1 (GROUND FLOOR, MID SIDE), UPS PANEL-8 (7TH FLOOR MID SIDE), UPS PANEL-1 (GROUND FLOOR RIGHT SIDE), UPS PANEL-2 (2ND FLOOR RIGHT SIDE), UPS PANEL-3 (3RD FLOOR RIGHT SIDE), UPS PANEL-4 (6TH FLOOR RIGHT SIDE), UPS PANEL-5 (7TH FLOOR RIGHT SIDE) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 63 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item813 | 10 | Set |
| 809 | 809 | EMERGENCY LIGHT PANEL-1 (GROUND FLOOR, MID SIDE), TYPICAL FOR EMERGENCY LIGHT PANEL-2 (BASEMENT FLOOR, LEFT SIDE), (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item814 | 4 | Set |
| 810 | 810 | EMERGENCY LIGHT PANEL-3 (GROUND FLOOR, RIGHT SIDE) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item815 | 1 | Set |
| 811 | 811 | LIFT & STAIRCASE VENTILATION PANEL-1 (RIGHT SIDE) (TERRACE FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch . 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve.Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item816 | 2 | Set |
| 812 | 812 | UPS PANEL-5 (4TH FLOOR MID SIDE), TYPICAL FOR UPS PANEL-6 (5TH FLOOR MID SIDE), (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 100 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item817 | 18 | Set |
| 813 | 813 | UPS PANEL-4 (3RD FLOOR MID SIDE), (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 63 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item818 | 1 | Set |
| 814 | 814 | UPS PANEL-7 (6TH FLOOR MID SIDE), (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 63 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item819 | 1 | Set |
| 815 | 815 | MAIN UPS PANEL GROUND FLOOR (3 X 160 KVA) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 3 No. Digital Multifunction Meter with inbuilt selector switch. 3 Set of phase indicating lamps with Single Pole MCB. 3 Set of ON / OFF indicating lamps with Single Pole MCB. 630 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item820 | 2 | Set |
| 816 | 816 | INCOMING OT PANEL-1 (2X25 KVA UPS) (THIRD FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 63 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item821 | 2 | Set |
| 817 | 817 | INCOMING OT PANEL-2 (3X40 KVA UPS) (SIXTH FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 160 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 200 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item822 | 2 | Set |
| 818 | 818 | 3X40 KVA UPS OUTGOING PANEL-1 FOR OT (SIXTH FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 3 No. Digital Multifunction Meter with inbuilt selector switch. 3 Set of phase indicating lamps with Single Pole MCB. 3 Set of ON / OFF indicating lamps with Single Pole MCB. 250 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item823 | 2 | Set |
| 819 | 819 | 2X25 KVA UPS OUTGOING PANEL-1 (THIRD FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 2 No. Digital Multifunction Meter with inbuilt selector switch. 2 Set of phase indicating lamps with Single Pole MCB. 2 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item824 | 2 | Set |
| 820 | 820 | 2X15KVA UPS PANEL (GROUND FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 2 Nos. 63A DP MCCB, 25KA breaking capacity. 2 No. Digital Multifunction Meter with inbuilt selector switch. 2 Set of phase indicating lamps with Single Pole MCB. 2 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp DP aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item825 | 2 | Set |
| 821 | 821 | LIFT PANEL-1 (TERRANCE M/C ROOM) (LEFT SIDE) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 160 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 250 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item826 | 2 | Set |
| 822 | 822 | LIFT PANEL-2 (TERRANCE M/C ROOM) (LEFT SIDE), TYPICAL FOR LIFT PANEL-1 (TERRANCE M/C ROOM), LIFT PANEL-1 (TERRANCE M/C ROOM) (RIGHT SIDE) (MID SIDE)(TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 63 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 100 Amp/ 200 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item827 | 5 | Set |
| 823 | 823 | LIFT PANEL-1 (TERRANCE M/C ROOM) (RIGHT SIDE) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 250 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 400 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item828 | 2 | Set |
| 824 | 824 | MAIN ELECTRICAL PANEL-1 DG BACK UP (GROUND FLOOR) (ACADEMIC BLOCK) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 800 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item829 | 1 | Set |
| 825 | 825 | MAIN ELECTRICAL PANEL-2 NON DG BACK UP (GROUND FLOOR) (ACADEMIC BLOCK) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. The Bus Coupler shall be Electrically / Mechanically interlocked with both the incomers. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item830 | 1 | Set |
| 826 | 826 | MAIN UPS PANEL (3 X 40 KVA) (GROUND FLOOR) (ACADEMIC BLOCK) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 3 No. Digital Multifunction Meter with inbuilt selector switch. 3 Set of phase indicating lamps with Single Pole MCB. 3 Set of ON / OFF indicating lamps with Single Pole MCB. 300 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item831 | 1 | Set |
| 827 | 827 | KITCHEN PANEL (ACADEMIC BLOCK) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 200 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item833 | 1 | Set |
| 828 | 828 | LIFT PANEL-1 (TERRACE M/C ROOM) (ACADEMIC BLOCK) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No Fixed type Automatic transfer switch 100 Amp rating in open frame with live to live transfer time <150ms. The ATS should have complete switching neutral with zero position having positive isolation and on load manual operation complying to IEC 60947-3 and IEC 60947-6-1. The control unit shall be integral part of the ATS. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item834 | 1 | Set |
| 829 | 829 | LIFT PANEL-2 (TERRACE M/C ROOM) (ACADEMIC BLOCK) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 300 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item835 | 1 | Set |
| 830 | 830 | VENTILATION PANEL (ACADEMIC BLOCK) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item836 | 1 | Set |
| 831 | 831 | ELECTRICAL PANEL (BMW BLOCK) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 1 No. Digital Multifunction Meter with inbuilt selector switch. 1 Set of phase indicating lamps with Single Pole MCB. 1 Set of ON / OFF indicating lamps with Single Pole MCB. 150 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item837 | 2 | Set |
| 832 | 832 | MAIN UPS PANEL GROUND FLOOR (4 X 160 KVA) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 3 No. Digital Multifunction Meter with inbuilt selector switch. 3 Set of phase indicating lamps with Single Pole MCB. 3 Set of ON / OFF indicating lamps with Single Pole MCB. 1000 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item838 | 1 | Set |
| 833 | 833 | 3X15KVA UPS PANEL (GROUND FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 3 Nos. 63A DP MCCB, 25KA breaking capacity. 3 Nos. Digital Multifunction Meter with inbuilt selector switch. 3 Set of phase indicating lamps with Single Pole MCB. 3 Set of ON / OFF indicating lamps with Single Pole MCB. 200 Amp DP aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item839 | 1 | Set |
| 834 | 834 | 3X15KVA UPS PANEL (GROUND FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 3 Nos. 63A DP MCCB, 25KA breaking capacity. 3 Nos. Digital Multifunction Meter with inbuilt selector switch. 3 Set of phase indicating lamps with Single Pole MCB. 3 Set of ON / OFF indicating lamps with Single Pole MCB. 200 Amp DP aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item840 | 1 | Set |
| 835 | 835 | 3X20 KVA UPS OUTGOING PANEL-1 (THIRD FLOOR) (TEACHING HOSPITAL) Design, Manufacturing, Supply, Receiving, Unloading, Shifting, installation, testing & commissioning of cubicle type totally enclosed free standing type moisture, dust and vermin proof compartmentlized Floor Distribution Panel made out of 2.0 mm thick & front cover 1.6 mm thick CRCA sheet complete with following equipments, including digital AVF meter with inbuilt selector switch, indicating lamps, CT's, internal wiring with suitable size wires / cable, interconnection, painting complete as per specification & drawing. All the dual source energy meter shall be with RS 485 port for BMS Connectivity. 3 No. Digital Multifunction Meter with inbuilt selector switch. 3 Set of phase indicating lamps with Single Pole MCB. 3 Set of ON / OFF indicating lamps with Single Pole MCB. 300 Amp TPN aluminium busbar with coloured heat shrinkable sleeve. Panel described as above (Incomming / Outgoing MCCB / MCB shall be paid seperately. However the fabrication cost for Incomming / Outgoing shall be included in above.) | item841 | 1 | Set |
| 836 | 836 | Supplying with fitting and fixing DP 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series\n(ABB, Schneider MG, legrand, Hager make) 6 to 32A | item842 | 145 | Each |
| 837 | 837 | Supplying with fitting and fixing DP 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series\n(ABB, Schneider MG, legrand, Hager make) 40A | item843 | 430 | Each |
| 838 | 838 | Supplying with fitting and fixing DP 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series\n(ABB, Schneider MG, legrand, Hager make) 63A | item844 | 56 | Each |
| 839 | 839 | Supplying with fitting and fixing 4P 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series (ABB, Schneider MG, legrand, Hager make) 6 to 32A | item847 | 462 | Each |
| 840 | 840 | Supplying with fitting and fixing 4P 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series (ABB, Schneider MG, legrand, Hager make) 40A | item849 | 171 | Each |
| 841 | 841 | Supplying with fitting and fixing 4P 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series (ABB, Schneider MG, legrand, Hager make) 63A | item850 | 763 | Each |
| 842 | 842 | Supplying with fitting and fixing panel mounting open execution 25KA 415V 50Hz 4P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure) of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 25 KA 415V 50 Hz 4P MCCB (Schneider, legrand, Siemens, Indo Asian make) 40A | item851 | 2 | Each |
| 843 | 843 | Supplying with fitting and fixing panel mounting open execution 415V 50Hz 4P MCCB with Microprocessor Release (Ics=Icu, adjustable Over Load and Short Circuit setting, Without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 36KA (ABB, Schneider, legrand, L&T, Siemens, C&S make) 40A | item852 | 8 | Each |
| 844 | 844 | Supplying with fitting and fixing panel mounting open execution 25KA 415V 50Hz 4P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure) of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 25 KA 415V 50 Hz 4P MCCB (Schneider, legrand, Siemens, Indo Asian make) 63A | item854 | 294 | Each |
| 845 | 845 | Supplying with fitting and fixing panel mounting open execution 25KA 415V 50Hz 4P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure) of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 25 KA 415V 50 Hz 4P MCCB (Schneider, legrand, Siemens, Indo Asian make) 100A | item855 | 78 | Each |
| 846 | 846 | Supplying with fitting and fixing panel mounting open execution 415V 50Hz 4P MCCB with Microprocessor Release (Ics=Icu, adjustable Over Load and Short Circuit setting, Without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 36KA (ABB, Schneider, legrand, L&T, Siemens, C&S make) 100A | item858 | 172 | Each |
| 847 | 847 | Supplying with fitting and fixing panel mounting open execution 35/36KA 415V 50Hz 4P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure) of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 160A | item859 | 55 | Each |
| 848 | 848 | Supplying with fitting and fixing panel mounting open execution 415V 50Hz 4P MCCB with Microprocessor Release (Ics=Icu, adjustable Over Load and Short Circuit setting, Without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 36KA (ABB, Schneider, legrand, L&T, Siemens, C&S make) 160A | item860 | 39 | Each |
| 849 | 849 | Supplying with fitting and fixing panel mounting open execution 35/36KA 415V 50Hz 4P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure) of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 250A | item861 | 7 | Each |
| 850 | 850 | Supplying with fitting and fixing panel mounting open execution 415V 50Hz 4P MCCB with Microprocessor Release (Ics=Icu, adjustable Over Load and Short Circuit setting, Without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 36KA (ABB, Schneider, legrand, L&T, Siemens, C&S make) 250A | item863 | 55 | Each |
| 851 | 851 | Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, neutral adjustable with earth fault protection without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the dept. 50KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make) 250A | item864 | 23 | Each |
| 852 | 852 | Supplying with fitting and fixing panel mounting open execution 415V 50Hz 4P MCCB with Microprocessor Release (Ics=Icu, adjustable Over Load and Short Circuit setting, Without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 36KA (ABB, Schneider, legrand, L&T, Siemens, C&S make) 400A | item866 | 26 | Each |
| 853 | 853 | Supplying with fitting and fixing panel mounting open execution 415V 50Hz 4P MCCB with Microprocessor Release (Ics=Icu, adjustable Over Load and Short Circuit setting, Without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 36KA (ABB, Schneider, legrand, L&T, Siemens, C&S make) 630A | item868 | 20 | Each |
| 854 | 854 | Supplying with fitting and fixing panel mounting open execution 415V 50Hz 4P MCCB with Microprocessor Release (Ics=Icu, adjustable Over Load and Short Circuit setting, Without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 50KA (ABB, Schneider, legrand, L&T, Siemens, C&S make) 800A | item869 | 6 | Each |
| 855 | 855 | Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, neutral adjustable with earth fault protection without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the dept. 65KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make) 800A | item870 | 4 | Each |
| 856 | 856 | Supplying with fitting & fixing panel mounting open execution 415V 50Hz 4P MCCB with microprocessor Release (Ics=Icu, adjustable over Load and Short Circuit setting, neutral adjustable with earth fault protection without enclosure of the following capacity complete with making necessary connection as approved, specified and directed by the dept. 50KA ( ABB, Schneider MG, legrand, Hager C&S, L&T, Siemens make) 1000A | item872 | 4 | Each |
| 857 | 857 | Supplying with fitting and fixing panel mounting open execution 4 pole Air Circuit Breaker type (MDO/EDO) with guide frame and 4 standard auxiliary contacts in the existing cubical panel board of the following capacity complete with making necessary connection as specified and directed by the deptt. (ABB Emax/L & T U Power/ Siemens 3 WL/ Schneider Master pact NW) 1000A Breaking capacity @ Ics = 50 KA (MDO) | item873 | 3 | Each |
| 858 | 858 | Supplying with fitting and fixing panel mounting open execution 4 pole Air Circuit Breaker type (MDO/EDO) with guide frame and 4 standard auxiliary contacts in the existing cubical panel board of the following capacity complete with making necessary connection as specified and directed by the deptt. (ABB Emax/L & T U Power/ Siemens 3 WL/ Schneider Master pact NW) 1250A Breaking capacity @ Ics = 50 KA (EDO) 1250A Breaking capacity @ Ics = 50 KA (EDO) | item875 | 9 | Each |
| 859 | 859 | Supplying with fitting and fixing 30/100/300mA sensitivity 240/415V 50Hz 4P RCBO of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 300mA sensitivity 4P RCBO (Schneider neo break, C&S, Havells, Indo Asian, HPL, V-Guard or equivalent make as approved by the Deptt.) 63A | item877 | 75 | Each |
| 860 | 860 | Design and Supply of IP-55 Sandwich Rising mains with plug-outlets in every 850mm on both side of trunking of following capacity with Aluminium conductor , TPN with 100% neutral , 1000V, IP-55, 50 Hz , housing made from 1.5mm hot-galvanized sheet steel treated according to UNI 10327 and painted with RAL7035 resins with high resistance to chemical agents including End cover, supports and with two runs of GI earth Bar and complying with IEC-60439 I & . (Legrand/ C&S or equivalent as approved by the Deptt.) 630 amps Rising Mains ( SC rating for 1 sec- 36K | item878 | 164 | Metre |
| 861 | 861 | Design and Supply of IP-55 Sandwich Rising mains with plug-outlets in every 850mm on both side of trunking of following capacity with Aluminium conductor , TPN with 100% neutral , 1000V, IP-55, 50 Hz , housing made from 1.5mm hot-galvanized sheet steel treated according to UNI 10327 and painted with RAL7035 resins with high resistance to chemical agents including End cover, supports and with two runs of GI earth Bar and complying with IEC-60439 I & . (Legrand/ C&S or equivalent as approved by the Deptt.) 800 amps Rising Mains ( SC rating for 1 sec- 42K | item879 | 154 | Metre |
| 862 | 862 | Design and Supply of IP-55 Sandwich Rising mains with plug-outlets in every 850mm on both side of trunking of following capacity with Aluminium conductor , TPN with 100% neutral , 1000V, IP-55, 50 Hz , housing made from 1.5mm hot-galvanized sheet steel treated according to UNI 10327 and painted with RAL7035 resins with high resistance to chemical agents including End cover, supports and with two runs of GI earth Bar and complying with IEC-60439 I & . (Legrand/ C&S or equivalent as approved by the Deptt.) 1000 amps Rising Mains ( SC rating for 1 sec- 50K | item880 | 136 | Metre |
| 863 | 863 | Supply of following capacity End Feed Unit Made of 1.6 mm thick sheet steel enclosure dully painted with powder coating to existing rising mains complete with provision of fixing MCCB. (Legrand/C&S or equivalent as approved by the deptt.) 630A End Feed Unit (W/0 MCCB) | item881 | 5 | Each |
| 864 | 864 | Supply of following capacity End Feed Unit Made of 1.6 mm thick sheet steel enclosure dully painted with powder coating to existing rising mains complete with provision of fixing MCCB. (Legrand/C&S or equivalent as approved by the deptt.) 800A End Feed Unit (W/0 MCCB) | item882 | 4 | Each |
| 865 | 865 | Supply of following capacity End Feed Unit Made of 1.6 mm thick sheet steel enclosure dully painted with powder coating to existing rising mains complete with provision of fixing MCCB. (Legrand/C&S or equivalent as approved by the deptt.) 1000A End Feed Unit (W/0 MCCB) | item883 | 4 | Each |
| 866 | 866 | Supply of following capacity TPN Tap off box Made of 1.6 mm thick sheet steel enclosure dully painted with powder coating to existing rising mains complete with provision of fixing MCCB. (Legrand/C&S or equivalent as approved by the deptt.) 63A Tap-off Box with inbuilt Disconnection (Legrand/ C&S or equivalent as approved by the Deptt.) on Cover ( W/0 MCCB/HRC fuse) | item884 | 49 | Each |
| 867 | 867 | Supply of following capacity TPN Tap off box Made of 1.6 mm thick sheet steel enclosure dully painted with powder coating to existing rising mains complete with provision of fixing MCCB. (Legrand/C&S or equivalent as approved by the deptt.) 125A Tap-off Box with inbuilt Disconnection (Legrand/ C&S or equivalent as approved by the Deptt.) on Cover ( W/0 MCCB/HRC fuse) | item885 | 37 | Each |
| 868 | 868 | Supply of following capacity TPN Tap off box Made of 1.6 mm thick sheet steel enclosure dully painted with powder coating to existing rising mains complete with provision of fixing MCCB. (Legrand/C&S or equivalent as approved by the deptt.) 160A Tap-off Box with inbuilt Disconnection (Legrand/ C&S or equivalent as approved by the Deptt.) on Cover ( W/0 MCCB/HRC fuse) | item886 | 50 | Each |
| 869 | 869 | Supply of following capacity TPN Tap off box Made of 1.6 mm thick sheet steel enclosure dully painted with powder coating to existing rising mains complete with provision of fixing MCCB. (Legrand/C&S or equivalent as approved by the deptt.) 250A Tap-off Box with inbuilt Disconnection (Legrand/ C&S or equivalent as approved by the Deptt.) on Cover ( W/0 MCCB/HRC fuse) | item887 | 8 | Each |
| 870 | 870 | Supply of following capacity TPN Tap off box Made of 1.6 mm thick sheet steel enclosure dully painted with powder coating to existing rising mains complete with provision of fixing MCCB. (Legrand/C&S or equivalent as approved by the deptt.) 400/ 630A Tap-off Box with inbuilt Disconnection (Legrand/ C&S or equivalent as approved by the Deptt.) on Cover ( W/0 MCCB/HRC fuse) | item888 | 2 | Each |
| 871 | 871 | Supply of following capacity TPN with 100% neutral ,1000V, 50 Hz , IP-55 Compact Air-Insulated Bus Bar Trunking compliance with IEC 60439 with Busbar made from Aluminium alloy with Copper + Tin coating over whole length of Busbar insulated and supported by Insulating materials in regular interval with ''omega shaped'' ribbed sealed section housing of size mentioned below made from Hot-galvanized steel of 0.8mm thick with having Plug-in -outlets in every 500mm, IK-10 category of mechanical strength including junction monobloc, joint cover, end cover, supports with GI earth bar and design is compliance with IEC 60439 I & II. (Legrand/ C&S or equivalent as approved by the Deptt.) 250 amps Rising Mains ( SC rating for 1 sec- 8KA, | item889 | 506 | Metre |
| 872 | 872 | Supply of following capacity TPN with 100% neutral ,1000V, 50 Hz , IP-55 Compact Air-Insulated Bus Bar Trunking compliance with IEC 60439 with Busbar made from Aluminium alloy with Copper + Tin coating over whole length of Busbar insulated and supported by Insulating materials in regular interval with ''omega shaped'' ribbed sealed section housing of size mentioned below made from Hot-galvanized steel of 0.8mm thick with having Plug-in -outlets in every 500mm, IK-10 category of mechanical strength including junction monobloc, joint cover, end cover, supports with GI earth bar and design is compliance with IEC 60439 I & II. (Legrand/ C&S or equivalent as approved by the Deptt.) 400 amps Rising Mains ( SC rating for 1 sec- 25K | item891 | 254 | Metre |
| 873 | 873 | Supply of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains with provision of fixing MCCB/HRC fuse . (Legrand/ C&S or equivalent as approved by the Deptt.) 63A Tap-off Box with inbuilt Disconnection (Legrand/ C&S or equivalent as approved by the Deptt.) on Cover ( W/0 MCCB/HRC fuse) | item892 | 135 | Each |
| 874 | 874 | Supply of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains with provision of fixing MCCB/HRC fuse . (Legrand/ C&S or equivalent as approved by the Deptt.) 125A Tap-off Box with inbuilt Disconnection (Legrand/ C&S or equivalent as approved by the Deptt.) on Cover ( W/0 MCCB/HRC fuse) | item893 | 25 | Each |
| 875 | 875 | Supply of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains with provision of fixing MCCB/HRC fuse . (Legrand/ C&S or equivalent as approved by the Deptt.) 160A Tap-off Box with inbuilt Disconnection (Legrand/ C&S or equivalent as approved by the Deptt.) on Cover ( W/0 MCCB/HRC fuse) | item894 | 6 | Each |
| 876 | 876 | Supply of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains with provision of fixing MCCB/HRC fuse . (Legrand/ C&S or equivalent as approved by the Deptt.) 250A Tap-off Box with inbuilt Disconnection (Legrand/ C&S or equivalent as approved by the Deptt.) on Cover( W/0 MCCB/HRC fuse) | item895 | 1 | Each |
| 877 | 877 | Supplying with fitting and fixing sheet steel, phosphatised, powder painted Single door surface mounting MCCB enclosure of the following rating MCCB fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved, specified and directed by the deptt. ABB, Schneider MG, legrand, Hager make) for 100A 3P/4P MCCB (including 63A) | item896 | 21 | Each |
| 878 | 878 | Supplying with fitting and fixing sheet steel, phosphatised, powder painted Single door surface mounting MCCB enclosure of the following rating MCCB fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved, specified and directed by the deptt. ABB, Schneider MG, legrand, Hager make) for 160A 3P/4P MCCB | item897 | 6 | Each |
| 879 | 879 | Supplying with fitting and fixing sheet steel, phosphatised, powder painted Single door surface mounting MCCB enclosure of the following rating MCCB fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved, specified and directed by the deptt. ABB, Schneider MG, legrand, Hager make) for 400/630A 3P/4P MCCB | item898 | 6 | Each |
| 880 | 880 | Supplying with fitting and fixing sheet steel, phosphatised, powder painted Single door surface mounting MCB enclosure incorporated with bas-bar, Neutral link, Earth bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved, specified and directed by the deptt. ABB, Schneider MG, legrand, Hager make) 4 way single door | item899 | 20 | Each |
| 881 | 881 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-2 (A2XWay, A2XFaY) 6 sq.mm two core armoured cable | item900 | 1500 | Meter |
| 882 | 882 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-2 (A2XWay, A2XFaY) 10 sq.mm two core armoured cable | item901 | 750 | Meter |
| 883 | 883 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 35 sq.mm 3 and 1/2 core armoured cable | item902 | 1103 | Meter |
| 884 | 884 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 50 sq.mm 3 and 1/2 core armoured cable | item903 | 429 | Meter |
| 885 | 885 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 70 sq.mm 3 and 1/2 core armoured cable | item904 | 2674 | Meter |
| 886 | 886 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 95 sq.mm 3 and 1/2 core armoured cable | item905 | 3148 | Meter |
| 887 | 887 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 120 sq.mm 3 and 1/2 core armoured cable | item906 | 2120 | Meter |
| 888 | 888 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 150 Sq.mm 3 and 1/2 core armoured cable | item907 | 1326 | Meter |
| 889 | 889 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 185 sq.mm 3 and 1/2 core armoured cable | item908 | 108 | Meter |
| 890 | 890 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 240 sq.mm 3 and 1/2 core armoured cable | item909 | 3244 | Meter |
| 891 | 891 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 300 sq.mm 3 and 1/2 core armoured cable | item910 | 8226 | Meter |
| 892 | 892 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-3.5 (A2XFY) 400.00 Sq.mm 3 and 1/2 core armoured cable | item911 | 8620 | Meter |
| 893 | 893 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) Core-4 (A2XWY, A2XFY) 25 sq.mm four core armoured cable | item912 | 601 | Meter |
| 894 | 894 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) 4 Core-4, 2XWY, 2XFY 4 sq.mm four core armoured cable | item913 | 2450 | Meter |
| 895 | 895 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) 4 Core-4, 2XWY, 2XFY 6 sq.mm four core armoured cable | item914 | 4690 | Meter |
| 896 | 896 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) 4 Core-4, 2XWY, 2XFY 10 sq.mm four core armoured cable | item915 | 2118 | Meter |
| 897 | 897 | Supply and laying of following size solid aluminium conductor up to 10 sq.mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured /armour (Aluminium for single core up to 70 sq.mm balance Aluminium strip, Galvanized for cables up to 2x10 sq.mm, 3x10 sq.mm, 4x6 sq.mm balance all galvanized steel strip), extruded PVC ST2 sheathed, 650/1100 V grade as per IS 7098 (Part1) 1988, laid in air or through existing cable trench / duct / cable tray / HDPE pipe including fitting required size of lugs at the both end of the cable by using crimping tool and making good damaged done as specified and directed by the department. (Nicco / Havells / RPG / CCI / Polycab / Gloster / Finolex make or equivalent.) 4 Core-4, 2XWY, 2XFY 16 sq.mm four core armoured cable | item916 | 2934 | Meter |
| 898 | 898 | Supply & Laying of following sizes of 1.1KV grade multistranded copper conductor FRLS insulated cable including termination complete as required in existing cable tray. 1C x 120 sq.mm PVC Insulated cu wire including end termination. | item917 | 648 | Meter |
| 899 | 899 | Supply & Laying of following sizes of 1.1KV grade multistranded copper conductor FRLS insulated cable including termination complete as required in existing cable tray. 1C x 6 sq.mm PVC Insulated cu wire including end termination. | item918 | 576 | Meter |
| 900 | 900 | Supply & Laying of following sizes of 1.1KV grade multistranded copper conductor FRLS insulated cable including termination complete as required in existing cable tray. 1C x 35 sq.mm PVC Insulated cu wire including end termination. | item919 | 918 | Meter |
| 901 | 901 | Supply & Laying of following sizes of 1.1KV grade multistranded copper conductor FRLS insulated cable including termination complete as required in existing cable tray. 1C x 16 sq.mm PVC Insulated cu wire including end termination. | item920 | 864 | Meter |
| 902 | 902 | Supply, Installation, Testing & Commissioning of Earthing Junction Box size - 400mm x 300mm x 80mm made out of 16 SWG CRCA sheet with seven tank process & powder coating, earthing link (32mmx6mm copper strip), front door with glass as complete as required. | item921 | 12 | Set |
| 903 | 903 | Supplying Fitting and Fixing of (Dowells / Commet make) Single compression brass gland heavy duty. Single Compression Brass Gland Heavy Duty. Size:1'' | item922 | 1266 | Each |
| 904 | 904 | Supplying Fitting and Fixing of (Dowells / Commet make) Single compression brass gland heavy duty. Single Compression Brass Gland Heavy Duty. Size:1-1/8'' | item923 | 308 | Each |
| 905 | 905 | Supplying Fitting and Fixing of (Dowells / Commet make) Single compression brass gland heavy duty. Single Compression Brass Gland Heavy Duty. Size:1-1/4'' | item924 | 64 | Each |
| 906 | 906 | Supplying Fitting and Fixing of (Dowells / Commet make) Single compression brass gland heavy duty. Single Compression Brass Gland Heavy Duty. Size:1-3/8'' | item925 | 126 | Each |
| 907 | 907 | Supplying Fitting and Fixing of (Dowells / Commet make) Single compression brass gland heavy duty. Single Compression Brass Gland Heavy Duty. Size:1-1/2'' | item926 | 56 | Each |
| 908 | 908 | Supplying Fitting and Fixing of (Dowells / Commet make) Single compression brass gland heavy duty. Single Compression Brass Gland Heavy Duty. Size:1-3/4'' | item927 | 150 | Each |
| 909 | 909 | Supplying Fitting and Fixing of (Dowells / Commet make) Single compression brass gland heavy duty. Single Compression Brass Gland Heavy Duty. Size:2-1/4'' | item928 | 52 | Each |
| 910 | 910 | Supplying Fitting and Fixing of (Dowells / Commet make) Single compression brass gland heavy duty. Single Compression Brass Gland Heavy Duty. Size:2-3/4'' | item929 | 286 | Each |
| 911 | 911 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. | item930 | 3150 | Metre |
| 912 | 912 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm wide x 50 mm depth x 1.6 mm thickness. | item931 | 1865 | Metre |
| 913 | 913 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 300 mm wide x 50 mm depth x 1.6 mm thickness. | item932 | 754 | Metre |
| 914 | 914 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 450 mm wide x 50 mm depth x 2.0 mm thickness. | item933 | 375 | Metre |
| 915 | 915 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 600 mm width X 50 mm depth X 2.0 mm thickness | item934 | 930 | Metre |
| 916 | 916 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 750 mm width X 62.5 mm depth X 2.0 mm thickness | item935 | 145 | Metre |
| 917 | 917 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 900 mm width X 62.5 mm depth X 2.0 mm thickness | item936 | 51 | Metre |
| 918 | 918 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"bends\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. | item937 | 185 | Each |
| 919 | 919 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"bends\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm wide x 50 mm depth x 1.6 mm thickness. | item938 | 132 | Each |
| 920 | 920 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"bends\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 300 mm wide x 50 mm depth x 1.6 mm thickness. | item939 | 77 | Each |
| 921 | 921 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"bends\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 450 mm wide x 50 mm depth x 2.0 mm thickness. | item940 | 50 | Each |
| 922 | 922 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"bends\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 600 mm width X 50 mm depth X 2.0 mm thickness | item941 | 84 | Each |
| 923 | 923 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"bends\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 750 mm width X 62.5 mm depth X 2.0 mm thickness | item942 | 12 | Each |
| 924 | 924 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"bends\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 900 mm width X 62.5 mm depth X 2.0 mm thickness | item943 | 7 | Each |
| 925 | 925 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Tee\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. | item944 | 88 | Each |
| 926 | 926 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Tee\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm wide x 50 mm depth x 1.6 mm thickness. | item945 | 74 | Each |
| 927 | 927 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Tee\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 300 mm wide x 50 mm depth x 1.6 mm thickness. | item946 | 29 | Each |
| 928 | 928 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Tee\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 450 mm wide x 50 mm depth x 2.0 mm thickness. | item947 | 12 | Each |
| 929 | 929 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Tee\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 600 mm width X 50 mm depth X 2.0 mm thickness | item948 | 8 | Each |
| 930 | 930 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Tee\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 750 mm width X 62.5 mm depth X 2.0 mm thickness | item949 | 6 | Each |
| 931 | 931 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Tee\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 900 mm width X 62.5 mm depth X 2.0 mm thickness | item950 | 7 | Each |
| 932 | 932 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Cross member\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 100 mm wide x 50 mm depth x 1.6 mm thickness. | item951 | 29 | Each |
| 933 | 933 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Cross member\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 150 mm wide x 50 mm depth x 1.6 mm thickness. | item952 | 16 | Each |
| 934 | 934 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Cross member\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 300 mm wide x 50 mm depth x 1.6 mm thickness. | item953 | 11 | Each |
| 935 | 935 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Cross member\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 450 mm wide x 50 mm depth x 2.0 mm thickness. | item954 | 6 | Each |
| 936 | 936 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Cross member\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness | item955 | 6 | Each |
| 937 | 937 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Cross member\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 750 mm width X 62.5 mm depth X 2.0 mm thickness | item956 | 5 | Each |
| 938 | 938 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \"Cross member\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 900 mm width X 62.5 mm depth X 2.0 mm thickness | item957 | 6 | Each |
| 939 | 939 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm wide x 50 mm depth x 1.6 mm thickness. | item958 | 22 | Each |
| 940 | 940 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 300 mm wide x 50 mm depth x 1.6 mm thickness. | item959 | 26 | Each |
| 941 | 941 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 450 mm wide x 50 mm depth x 2.0 mm thickness. | item960 | 14 | Each |
| 942 | 942 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 600 mm width X 50 mm depth X 2.0 mm thickness | item961 | 26 | Each |
| 943 | 943 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 750 mm width X 62.5 mm depth X 2.0 mm thickness | item962 | 7 | Each |
| 944 | 944 | Cable Tray Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 900 mm width X 62.5 mm depth X 2.0 mm thickness | item963 | 7 | Each |
| 945 | 945 | Supply and laying of following sizes of 1.1KV grade Aluminium conductor XLPE insulated and FRLS PVC sheathed Fire Survival armoured cable conforming to relevant BS-7846. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 3.5 core, 120 sq.mm. Aluminium Cond Fire Survival Cable | item964 | 228 | Meter |
| 946 | 946 | Supply and laying of following sizes of 1.1KV grade Aluminium conductor XLPE insulated and FRLS PVC sheathed Fire Survival armoured cable conforming to relevant BS-7846. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 3.5 core, 95 sq.mm. Aluminium Cond Fire Survival Cable | item965 | 406 | Meter |
| 947 | 947 | Supply and laying of following sizes of 1.1KV grade Aluminium conductor XLPE insulated and FRLS PVC sheathed Fire Survival armoured cable conforming to relevant BS-7846. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 3.5 core, 50 sq.mm. Aluminium Cond Fire Survival Cable | item966 | 144 | Meter |
| 948 | 948 | Supply and laying of following sizes of 1.1KV grade Aluminium conductor XLPE insulated and FRLS PVC sheathed Fire Survival armoured cable conforming to relevant BS-7846. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 3.5 core, 35 sq.mm. Aluminium Cond Fire Survival Cable | item967 | 474 | Meter |
| 949 | 949 | Supply and laying of following sizes of 1.1KV grade Aluminium conductor XLPE insulated and FRLS PVC sheathed Fire Survival armoured cable conforming to relevant BS-7846. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 4 core, 25 sq.mm. Aluminium Cond Fire Survival Cable | item968 | 310 | Meter |
| 950 | 950 | Supply and laying of following sizes of 1.1KV grade Aluminium conductor XLPE insulated and FRLS PVC sheathed Fire Survival armoured cable conforming to relevant BS-7846. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 4 core, 16 sq.mm. Aluminium Cond Fire Survival Cable | item969 | 1574 | Meter |
| 951 | 951 | Supply and laying of following sizes of 1.1KV grade Aluminium conductor XLPE insulated and FRLS PVC sheathed Fire Survival armoured cable conforming to relevant BS-7846. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 4 core, 10 sq.mm. Aluminium Cond Fire Survival Cable | item970 | 4746 | Meter |
| 952 | 952 | Supply and laying of following sizes of 1.1KV grade Aluminium conductor XLPE insulated and FRLS PVC sheathed Fire Survival armoured cable conforming to relevant BS-7846. (Cable shall be purchased only after approval of cable schedule by architect / consultant). 4 core, 6 sq.mm. Aluminium Cond Fire Survival Cable | item971 | 2700 | Meter |
| 953 | 953 | Supply, Installation, Testing & Commissioning of Recess LED Downlighter made of pressure die cast aluminum housing with high efficiency reflector, LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, 1000 - 1200 lumen, Life of fixture (Including Driver) : 30K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500 (SDCM<5), CRI >80, PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection 2.0KV The fixture design should comply with IS10322, EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598,Minimum system Lumens 1000-1200. | item972 | 52 | Each |
| 954 | 954 | Supply, Installation, Testing & commissioning of Recess LED Downlighter made of pressure die cast aluminum housing with high efficiency reflector, LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, 1600 - 1800 Lumen, Life of fixture (Including Driver) : 30K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500 (SDCM<5), CRI >80, PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection 2.0KV The fixture design should comply with IS10322, EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598,Minimum system Lumens 1000. | item973 | 170 | Each |
| 955 | 955 | Supply, Installation, Testing & commissioning of Recess LED Downlighter made of pressure die cast aluminum housing with high efficiency reflector, LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, 2000 Lumen, Life of fixture (Including Driver) : 30K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500 (SDCM<5), CRI >80, PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection 2.0KV The fixture design should comply with IS10322, EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598,Minimum system Lumens 1000. | item974 | 1191 | Each |
| 956 | 956 | Supply, Installation, Testing & Commissioning of 1x9 watt LED Mirror light fixture wall mounted (600mm) with electronic high efficiency electronic driver, more than 100 lumens/watt, complete as required. | item975 | 1559 | Nos |
| 957 | 957 | Supply, Installation, Testing & Commissioning of Surface Mounted Linear LED IP65 fitting made of Virgin Polycarbonate housing & Non Yellowing PC Diffuser ,LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, Life of fixture (Including Driver) : 50K Hrs. @ L70B50 Lumen maintenance, CCT 6500 (SDCM<5), CRI >80 , PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection 3KV The fixture design should comply with IS10322, EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598,Minimum system Lumens 4000. | item976 | 78 | Nos |
| 958 | 958 | Supply, Installation, Testing & Commissioning of Recess LED 600x600mm fitting made of white CRCA powder quoted finish with fully covered by PMMA Acrylic Lumio Diffuser, LED Used shall be SMD type and fixture should have minimum efficacy at System level >=100lumens/watt, Life of fixture : 50K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500 (SDCM<5), CRI >80 , PF >0.95 & THD<10%, Fixture must be office compliant & have to comply to UGR<19 value for optimim glare.an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection 2.5KV The fixture design should comply with IS:10322 & Must be EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598, Minimum system Lumens 3000. | item977 | 7355 | Nos |
| 959 | 959 | Supply, Installation, Testing & Commissioning of Recess LED 600x600mm fitting made of white CRCA powder quoted finish with fully covered by PMMA Acrylic Lumio Diffuser, LED Used shall be SMD type and fixture should have minimum efficacy at System level >=100lumens/watt, Life of fixture : 50K Hrs. @ L70B50 Lumen maintenance, CCT up to 6500 (SDCM<5), CRI >80 , PF >0.95 & THD<10%, Fixture must be office compliant & have to comply to UGR<19 value for optimim glare.an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection 2.5KV The fixture design should comply with IS:10322 & Must be EMC / EMI compliance maintaining driver leakage current as per as per IEC 60598, Minimum system Lumens 3600. | item978 | 4448 | Nos |
| 960 | 960 | Supply, Installation, Testing & Commissioning of LED Bulkhead Fixture made of pressure die cast aluminum housing with high efficiency reflector, LED Used shall be SMD type and fixture should have minimum efficacy at System level (Not Chip Level) >=100lumens/watt, Life of fixture (Including Driver) : 30K Hrs. @ L70B50 Lumen maintenance, CCT - 6500 (SDCM<5), CRI >70, PF >0.95 , an operating Voltage Range of 140 - 270 V.Minimum Internal Surge Protection 2.0KV The fixture design should comply with IS10322, Minimum system Lumens 700. | item979 | 790 | Nos |
| 961 | 961 | Supply, Installation, Testing & Commissioning of Self contained emergency light units 1x9 watt double sided for wall / ceiling mounting with suspension / mounting kit, lamps, inbuilt standby battery (for 2 hours backup) and battery charger etc. in suitable enclosure. | item980 | 23 | Each |
| 962 | 962 | Supply, installation, Testing & Commissioning of 18-22W Watt, surface Type, 6500K, LED batten light fixture, having minimum system lumen output of 100 Lumen / watt complete as requried. | item981 | 7415 | Nos |
| 963 | 963 | Supply, installation, Testing & Commissioning of 36W Watt, surface Type, 6500K, LED batten light fixture, having minimum system lumen output of 100 Lumen / watt complete as requried. | item982 | 440 | Nos |
| 964 | 964 | Supply, Installation, Testing & Commissioning of 20 watt LED Light surface mounted downlight with high efficiency electronic driver, more than 100 lumens/watt, complete as required. | item983 | 1244 | Nos |
| 965 | 965 | Supply, Installation, Testing & Commissioning of 10-12W Surface mouted LED Downlight as complete as required. | item984 | 320 | Meter |
| 966 | 966 | Supply, Installation, Testing & Commissioning of 1x6 watt LED Light surface mounted downlight with high efficiency electronic driver, more than 100 lumens/watt, complete as required. | item985 | 2400 | Each |
| 967 | 967 | Supply, Installation, Testing & Commissioning of 1x6 watt LED Light recessed mounted downlight with high efficiency electronic driver, more than 100 lumens/watt, complete as required. | item986 | 2801 | Each |
| 968 | 968 | Supply, Installation, Testing & Commissioning of 10-12 watt LED wall bracket Light fitting with more than 100 lumens/watt, complete as required. | item987 | 819 | Each |
| 969 | 969 | Supply, Installation, Testing & Commissioning of LED strip light, Strip should have minimum efficacy at System level >=70lumens/watt with nominal system lumens 300/mtr, Life of strip : 15000 burning Hrs. @ (ta 25 C) @L70B50 Lumen maintenance , CCT of WW, CRI Ra >=80, an operating Voltage Range of 140 - 270 VAC. Minimum Internal Surge Protection 2.0KV & Supply Voltage of 24VDC.The fixture design should comply with CB report, LM79, IP test, thermal test. | item988 | 434 | Each |
| 970 | 970 | Supplying and fixing of 250 mm sweep decorative Fresh air fan with all accessories suitable for operation single phase 230 volt 50 cycle per second per sec. AC supply etc. as required. in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning earthing etc. as required. | item989 | 443 | Nos |
| 971 | 971 | Supply, Installation, Testing & Commissioning of Recessed Mounted LED Downlighter with 2X 26W LED Module individually adjustable (Tilt 30° (2 sides); Pan 360°). Fixture to be made of Metal housing with powder coating, matt finishing, white color RAL9010, . LED Used shall be COB type with Minimum system Lumens 3600, Life of : 50000 burning Hrs. @ L70B50 Lumen maintenance, CCT of 4000K (SDCM<=4), CRI >90 for high quality light output with light Beam angle of 34/40 Deg. power factor >0.9 an operating Voltage Range of 140 - 277 VAC. Minimum Internal Surge Protection 2.0KV & Fixed output (remote SELV driver with 0.3m length cable), Fixture dimensions similar to L: 324~328mm W:114~118mm. The fixture design should comply with EMC / EMI compliance with CB, EMC, CE, AS/NZS, CCC Certifications along with BIS certification for LED Driver & Luminaire, Luminaire manufacture shall provide LM79report from NABL accredited lab & LM80 report issued by LED manufacturer. | item990 | 45 | Nos |
| 972 | 972 | Supply, Installation, Testing & Commissioning of 1x3 watt LED Light recess mounted downlight with high efficiency electronic driver, more than 100 lumens/watt, complete as required. | item991 | 32 | Nos |
| 973 | 973 | Supply, Installation, Testing & Commissioning of 1x26 watt LED Light recess mounted downlight with high efficiency electronic driver, more than 100 lumens/watt, complete as required. | item992 | 4 | Nos |
| 974 | 974 | Supply, Installation, Testing & Commissioning of 70 watt LED Midbay Light with high efficiency electronic driver, more than 100 lumens/watt, complete as required. | item993 | 390 | Nos |
| 975 | 975 | Supplying including fitting and fixing of following star rated A.C. ceiling fan complete with all accessories like down rod, canopy etc of following sweeps with making necessary connection cable as approved by Deptt.s etc as required complete and as directed by the department as required complete etc. (Without regulator). (Orient / PSPO / Usha / Crompton / Havells/ ATC / V Gaurd.) Energy efficient 5-star 1200 mm sweep. (Orient / PSPO / Usha / Crompton / Havells/ ATC / V Gaurd.) | item994 | 5647 | Each |
| 976 | 976 | Supplying including fitting fixing of following A.C. Wall fan in the wall of following sweeps with making necessary connection as approved by the Deptt.)as required complete and as directed by the Department. (CROMPTON /ORIENT/Havells/USHA or equivalent make) Air Circulator wall fan 600 mm sweep Turbo force | item995 | 109 | Each |
| 977 | 977 | Supplying including fitting fixing of following A.C. Wall fan in the wall of following sweeps with making necessary connection as approved by the Deptt.)as required complete and as directed by the Department. (CROMPTON /ORIENT/Havells/USHA or equivalent make) SDX 120 with metal body metal blade 400 mm sweep | item996 | 31 | Each |
| 978 | 978 | Supply, installation, testing and commissioning of following LAN networks equipments. Solid Copper Cable 6, 4 pair, UTP 305m SCHNEIDER/LEGRAND or equivalent make as approved by the Deptt. | item997 | 422403 | Meter |
| 979 | 979 | Supply, installation, testing and commissioning of following LAN networks equipments. Patch Panel Cat 6 UTP Keystone-24 Port- Loaded SCHNEIDER/LEGRAND or equivalent make as approved by the Deptt. | item998 | 387 | Nos. |
| 980 | 980 | APW Cyber Rack Networking Equipment Rack APW President Enclosure, 600mmW CYBERACK 42U/800mmD (CRCA Steel Frame with Aluminium Profiles & 2 Nos. of Removable Side Panels with followwing items:- Top cover with cable entry-1no.-Bottom cover with cable entry-1no.-19\" Mounting Angles-2 pairs., Finish: Powder coated to 80 microns; Matt Finish. Colour: BLACK with, Load rating capacity -500 Kgs., Front side vented glass door and rear full perforated steel door with locks. \" PDU 10*5/15A-01 Nos., Fan Housing Unit with 4 Fans-01 Set, Mounting Hardware (Set of 20)-1 Set, Castor with Brake- 2Nos., Castor without Brake - 2 Nos., Earthing Kit - 01 Set, Cable Manager 19\" 1U - 2 Nos. | item999 | 14 | Each |
| 981 | 981 | Supply 8 mm round aluminium conductor for horizontal lightning protection - run in roof. | item1000 | 7490 | Mtr. |
| 982 | 982 | Supply of roof conductor holder for 8 mm round aluminium conductor made of Gun Metal for horizontal installation. The distance between each holder should be min of 1.5 mtr. | item1001 | 1150 | Nos. |
| 983 | 983 | Supply of Cross connector for connecting of 8 mm Al round conductor . The connector should be of Gun Metal with SS nuts and bolt. | item1002 | 376 | Nos. |
| 984 | 984 | Supply of T connector for connecting of 8 mm Al round conductor . The connector should be of Gun Metal with SS nuts and bolt. | item1003 | 182 | Nos. |
| 985 | 985 | Supply of L connector for connecting of 8 mm Al round conductor . The connector should be of Gun Metal with SS nuts and bolt. | item1004 | 171 | Nos. |
| 986 | 986 | Supply of straight connector for connecting of 8 mm Al round conductor . The connector should be of Gun Metal with SS nuts and bolt. | item1005 | 175 | Nos. |
| 987 | 987 | Supply of Expansion piece to compensate the expansion of round 8 mm Al conductor when temperature variation . Connection should be in every 20 mtr. | item1006 | 151 | Nos. |
| 988 | 988 | Supply of fixing glue for fixing of roof conductor holder . | item1007 | 141 | Pc |
| 989 | 989 | Supply of Expansion piece connector for connecting of 8 mm Al round conductor . The connector should be of Gun Metal with SS nuts and bolt. | item1008 | 288 | Nos. |
| 990 | 990 | Supply of 8 mm round aluminium conductor as a down conductor mounted in the surface of wall which will carry the lightning current to earth pit. | item1009 | 2883 | Mtr. |
| 991 | 991 | Supply of Down conductor holder for 8 mm round aluminium conductor of min distance between the wall to the conductor will be of 50 mm. The distance between each holder should be min of 1.5 mtr. | item1010 | 348 | Nos. |
| 992 | 992 | Supply of Test Joint Point for 8 mm round aluminium conductor , the size should be of 25 x 3 x 150 mm copper in ABS boxes. | item1011 | 90 | Nos. |
| 993 | 993 | Supply of UL approved low carbon high tensile steel rod with copper coating of min 254 micron JK Chemrode - 317 CBR the dia should be 17.2 mm with length of 10 feet ( 3000 mm) . The rod shall be as per IEC 62561-2 and approved by UL 467. The rod shall be tested from NABL lab for current discharge not less then 46kA peak. The Chemrode shall be surrounded with 50 kg ( 2 bag) of Earth enhance materiel JK Activer+ according to IEC 62561-7 and the Chemical resistance value shall not increase more then 0.064 Om and same will be tested from NABL lab. | item1012 | 90 | Nos. |
| 994 | 994 | Supplying, erection, testing and commissioning of Aviation lights with LED lamp with flasher 170mm suitable for 230V AC complete with fitting including photochromatic switch for automatic ON/OFF of Aviation lights complete. | item1013 | 7 | Nos. |
| 995 | 995 | Supply with installation & commissioning of readymade maintenance free CPRI approved chemical earthing system with 50mm dia. 3.00 Meters length corrosion free dual pipe technology G.I. Chemrode Electrode complete with Reslow grounding Minerals 25 k and Advance Earth pit cover including excavation of earth pit and construction of brick earth chamber including plastering both inner & outer surface of brick wall as specified and directed by the deptt. | item1014 | 97 | Each |
| 996 | 996 | Supply with installation & commissioning of readymade maintenance free CPRI approved chemical earthingsystem with 50mm dia. 3.00 Meters length corrosion free Single pipe technology -Copper Chemrode Electrode complete with Reslow grounding Minerals 25 k and Advance Earth pit cover including excavation of earth pit and construction of brick earth chamber including plastering both inner &outer surface of brick wall as specified and directed by the deptt. | item1015 | 216 | Each |
| 997 | 997 | Supplying &laying of 6 SWG G.I. Earth from earth electrode (below G.L.)to electrical swicth gears or electrical machineries including making necessary connection as approved, specified and directed by the deptt. | item1016 | 505 | Meter |
| 998 | 998 | Supplying & laying of 25x6 mm size G.I. strips drawn on surface from earth electrode to electrical switch gears , machineries etc.complete with supply of G.I. nuts & bolts screws etc including reverting, soldering & making necessary connection as approved,specified and directed by the deptt. | item1017 | 10322 | Meter |
| 999 | 999 | Supplying & laying of 50x6 mm size G.I. strips drawn on surface from earth electrode to electrical switch gears , machineries etc.complete with supply of G.I. nuts & bolts screws etc including reverting, soldering & making necessary connection as approved,specified and directed by the deptt. | item1018 | 1880 | Meter |
| 1000 | 1000 | Supply, fitting & fixing 20 mmx3 mm Copper strips drawn on vertically or horizontally on building wall/parapet wall in surface system complete with supply of Brass Nuts & Bolts, Screws etc including riveting, soldering and making connection as approved by the Deptt.)with earth electrode copper strips and Lightning Arrestor etc. as specified and directed by the deptt. | item1019 | 10760 | Meter |
| 1001 | 1001 | Supplying &laying of 8 SWG G.I. wire with existing cable on cable tray. | item1021 | 5463 | Meter |
| 1002 | 1002 | Supply, installation, testing & commissioning of 1 Loop Intelligent / Analogue Addressable Fire Alarm Panel Microprocessor based character display Network option built in Alarm, Trouble & supervisory relays LPCB listed. make : Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) | item1022 | 4 | Each |
| 1003 | 1003 | Supply, installation, testing & commissioning of 2 Loop Intelligent / Analogue Addressable Fire Alarm Panel Microprocessor based character display Network option built in Alarm, Trouble & supervisory relays LPCB listed. make : Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) | item1023 | 4 | Each |
| 1004 | 1004 | Supply, installation, testing & commissioning of 5 Loop Intelligent / Analogue Addressable Fire Alarm Panel Microprocessor based character display Network option built in Alarm, Trouble & supervisory relays LPCB listed. make : Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) | item1024 | 18 | Each |
| 1005 | 1005 | Supply, installation, testing & commissioning of intelligent plug in photo electric Smoke Detectors having features like integral communication, dual LED for 360° viewing angle, walk test with address display etc. UL / LPCB approved, make : Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) | item1025 | 7794 | Each |
| 1006 | 1006 | Supply, Installation, Testing & Commissioning of rate of rise & fixed temperature resettable heat detector with mounting base. make : Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) | item1026 | 114 | Each |
| 1007 | 1007 | Supply, installation, testing & commissioning of Monitor Module.UL / LPCB approved, make - Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) with housing box | item1027 | 303 | Each |
| 1008 | 1008 | Supply, installation, testing & commissioning of Control Module.UL / LPCB approved, make - Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) with housing box Model:200e-SMD. | item1028 | 129 | Each |
| 1009 | 1009 | Supply, installation, testing & commissioning of Addressable Hooter / SOUNDER; UL / LPCB approved, make - Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) | item1029 | 463 | Each |
| 1010 | 1010 | Supply, installation, testing & commissioning of Manual pull station with addressable interface, built in LED with key reset facility. UL / LPCB listed. make : Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) | item1030 | 463 | Each |
| 1011 | 1011 | Supply, installation, testing & commissioning of Response Indicator to give visual indication of detection of smoke - RED colour LED for indication. make - Agni Suraksha, or equivalent as approved by the Deptt.)System Sensor. | item1031 | 4944 | Each |
| 1012 | 1012 | Supply, installation, testing & commissioning of Addressable Loop Powered Beam Detectors. 10-100M range. Automatic Drift Compensation. UL / LPCB approved, make : Honeywell, Siemens, Bosch, Schrack, Notofier, Notifier, Apollo or equivalent as approved by the Deptt.) | item1032 | 4 | Each |
| 1013 | 1013 | Supply Installation, Testing & Commissioning of fire fighter main console at control room including power supply and accessories. | item1033 | 6 | Nos. |
| 1014 | 1014 | Supply Installation, Testing & Commissioning of Fire fighters telephone handset. | item1034 | 26 | Nos. |
| 1015 | 1015 | Supply Installation, Testing & Commissioning of Fire fighters telephone jack. | item1035 | 338 | Nos. |
| 1016 | 1016 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. | item1036 | 478 | Nos. |
| 1017 | 1017 | SITC of EN54-16 compliant IP Based Digital Public Address & Voice Alarm system. The selected system devices like controllers and Paging Microphones, should use the TCP/IP technologies and build on the standard network platform to ensure expandability. The individual systems should be able to play 4 simutaneous audio messages and also be able to be networked over IP. SITC of 8 zone IP based, digital Voice Alarm controller expandable upto 128 zones. The voice alarm controller should be able to connect directly over Ethernet. It should have functions like the audio playing, zone control, fault monitoring, log recording, volume control and amplifier switchover. The Voice alarm controller should also have the following functions:\n. 255 Priorities\n. Time schedule broadcasts\n. Its own PTT microphone\n. Capable of amplifier redundancy\n. 8 trigger inputs/outputs | item1037 | 32 | Set |
| 1018 | 1018 | SITC of IP based Networkable touch screen paging station for selection of zones, supervision of system status, setting of scheduled broadcasts with the following functions:\n. Built-in monitoring loudspeaker\n. Detachable goose-neck microphone\n. LCD touchscreen display\n. Audio input\n | item1038 | 5 | Set |
| 1019 | 1019 | SITC of 2x250W Amplifier with 4 independent channels and can provide automatic re-settable overcurrent, overload, overheating, overvoltage, under-voltage and DC protection. | item1039 | 53 | Set |
| 1020 | 1020 | Supplying installation, testing, programming and commissioning of Audio equipment, 4-Channel Power Amplifier, 75 W per channel @ 8 ohms | item1040 | 4 | Set |
| 1021 | 1021 | SITC of 6W Ceiling mount with max SPL1M/1W 96dB . Frequency response of 160Hz-20KHz. The speaker shoud have tappings at 6W/3W\n\n | item1041 | 3668 | Set |
| 1022 | 1022 | SITC of Surface Mount 6W Ceiling / Wall mount with max SPL1M/1W 96dB . Frequency response of 160Hz-20KHz. The speaker shoud have tappings at 6W/3W. | item1042 | 700 | Set |
| 1023 | 1023 | Supply, Installation, Testing & Commissioning of 2C x 1.5 sq.mm Fire Survival armoured cable (300/500V) with Class-2 Copper conductor having Mineral ceramic glass fire barrier tape covered by an extruded layer of Cross-linkable Low Smoke Zero Halogen (LSZH) insulation as per EI-5 Of BS EN 50363 along with ATC drain wire, aluminium tape screening and LSZH outer sheath as per BS 7629-1 & BS-5839-1 (latest edition). Outer sheath should be Anti Rodent/Anti Termite. Should retain circuit integrity as per BS 8434-2 (930 deg C for 120 mins on single sample) including end termination etc as complete as required. (For Fire & PA System) | item1043 | 360 | Meter |
| 1024 | 1024 | Wiring for circuit wiring with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed ISI marked Steel conduit pipe wiring system. With 2 x 1.5 sq. mm. cable in 20 mm dia. rigid Steel conduit. | item1044 | 116646 | Meter |
| 1025 | 1025 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. speaker cable Single pair, 2-core, 1.5 sqmm | item1045 | 65496 | Meter |
| 1026 | 1026 | Supply, installation, testing and commissioning of following LAN networks equipments. Solid Copper Cable 6, 4 pair, UTP SCHNEIDER/LEGRAND or equivalent make as approved by the Deptt. | item1046 | 33478 | Meter |
| 1027 | 1027 | Supply, Installation, Testing & Commissioing of 160 KVA Modular UPS in paralleling mode at 0.99 input power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, Isolation transformer as per specification given in the document with following broad features. (Make- Auto Meter Allience / Socomec / Delta / Reillo Power / APC Schneider / Emerson) U PS shall carry design output at 40 deg. Shall have soft start and hold of for incoming supply.Invertor capability to supply 150% load for 5 sec. Three Phase Input and Three Phase Output. (Input - 340V - 470V, Three Phase, 4 wire. / Output - 400-415 Volt, Three Phase, 4 Wire.) Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt cells. Battery shall be external type with rack and suitable for 30 minute backup on 100% load. UPS shall be compatible for 4 nos unit in parallel operation. (Synchronize). Parallel operation kit shall be supplied with UPS. Suitable size & length of Copper Cable between battery to battery and battery to UPS shall be provided without any extra cost. UPS described as above | item1047 | 8 | Each |
| 1028 | 1028 | Supply, installation, testing & commissioing of 40 KVA Modular UPS at 0.99 input power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, inbuilt isolation transformer as per specification given in the document with following broad features. (Make- Auto Meter Allience / Socomec / Delta / Reillo Power / APC Schneider / Emerson) UPS shall carry design output at 40 deg. Shall have soft start and hold of for incoming supply. Invertor capability to supply 150% load for 5 sec. Three Phase Input and Three Phase Output. (Input - 340V - 470V, Three Phase, 4 wire. / Output - 400-415 Volt, Three Phase, 4 Wire.) Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt cells. Battery shall be external type with rack and suitable for 30 minute backup on 100% load. Suitable size & length of Copper Cable between battery to battery and battery to UPS shall be provided without any extra cost. UPS shall be compatible for 3 nos unit in parallel operation. (Synchronize). Parallel operation kit shall be supplied with UPS. UPS described as above | item1048 | 4 | Each |
| 1029 | 1029 | Supply, installation, testing & commissioing of 25 KVA Modular UPS at 0.99 input power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, inbuilt isolation transformer as per specification given in the document with following broad features. (Make- Auto Meter Allience / Socomec / Delta / Reillo Power / APC Schneider / Emerson) UPS shall carry design output at 40 deg. Shall have soft start and hold of for incoming supply. Invertor capability to supply 150% load for 5 sec. Three Phase Input and Three Phase Output. (Input - 340V - 470V, Three Phase, 4 wire. / Output - 400-415 Volt, Three Phase, 4 Wire.) Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt cells. Battery shall be external type with rack and suitable for 30 minute backup on 100% load. Suitable size & length of Copper Cable between battery to battery and battery to UPS shall be provided without any extra cost. UPS shall be compatible for 2 nos unit in parallel operation. (Synchronize). Parallel operation kit shall be supplied with UPS. UPS described as above | item1049 | 1 | Each |
| 1030 | 1030 | Supply, installation, testing & commissioing of 20 KVA Modular UPS at 0.99 input power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, inbuilt isolation transformer as per specification given in the document with following broad features. (Make- Auto Meter Allience / Socomec / Delta / Reillo Power / APC Schneider / Emerson) UPS shall carry design output at 40 deg. Shall have soft start and hold of for incoming supply. Invertor capability to supply 150% load for 5 sec. Three Phase Input and Three Phase Output. (Input - 340V - 470V, Three Phase, 4 wire. / Output - 400-415 Volt, Three Phase, 4 Wire.) Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt cells. Battery shall be external type with rack and suitable for 90 minute backup on 100% load. Suitable size & length of Copper Cable between battery to battery and battery to UPS shall be provided without any extra cost. UPS shall be compatible for 3 nos unit in parallel operation. (Synchronize). Parallel operation kit shall be supplied with UPS. UPS described as above | item1050 | 6 | Each |
| 1031 | 1031 | Supply, installation, testing & commissioing of 15 KVA Modular UPS at 0.99 input power factor with SNMP card, compatible for BMS connectivity on backnet/MODBUS, inbuilt isolation transformer as per specification given in the document with following broad features. (Make- Auto Meter Allience / Socomec / Delta / Reillo Power / APC Schneider / Emerson) UPS shall carry design output at 40 deg. Shall have soft start and hold of for incoming supply. Invertor capability to supply 150% load for 5 sec. Three Phase Input and Three Phase Output. (Input - 340V - 470V, Three Phase, 4 wire. / Output - 200-230 Volt, Single Phase, 2 Wire.) Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt cells. Battery shall be external type with rack and suitable for 90 minute backup on 100% load. Suitable size & length of Copper Cable between battery to battery and battery to UPS shall be provided without any extra cost. UPS shall be compatible for 2 nos/3 nos / 4 nos unit in parallel operation. (Synchronize). Parallel operation kit shall be supplied with UPS. UPS described as above | item1051 | 9 | Each |
| 1032 | 1032 | Supply, installation, testing & commissioing of 3 KVA UPS as per specification given in the document with following broad features. (Make- Auto Meter Allience / Socomec / Delta / Reillo Power / APC Schneider / Emerson) Input power factor shall be more than 0.95. from 25% to 100% load. UPS shall carry design output at 40 deg. Shall have soft start and hold of for incoming supply. Invertor capability to supply 150% load for 5 sec. Single Phase Input and Single Phase Output. (Input - 220V - 260V, Single Phase, 2 wire. / Output - 220 Volt, Single Phase, 2 Wire.) Shall not allow deep discharge of the battery and shall not go to 10.5 volts in case of 12 volt cells. Battery shall be external type with rack and suitable for 90 minute backup on 100% load. UPS described as above | item1052 | 5 | Each |
| 1033 | 1033 | Supply installation , testing & Commissioning of following rating of invertor with battery and trolley as complete as required. Invertor shall be suitable for 90 minute backup on full load as per spercification. 1500 VA, 220 Volt | item1053 | 3 | Each |
| 1034 | 1034 | Supply installation , testing & Commissioning of following rating of invertor with battery and trolley as complete as required. Invertor shall be suitable for 90 minute backup on full load as per spercification. 2000 VA, 220 Volt | item1054 | 2 | Each |
| 1035 | 1035 | Supply installation , testing & Commissioning of following rating of invertor with battery and trolley as complete as required. Invertor shall be suitable for 90 minute backup on full load as per spercification. 3000 VA, 220 Volt | item1055 | 1 | Each |
| 1036 | 1036 | ISOLATION PANEL FOR OT'S (10 KVA) Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of (Pieco make ) isolation panels fabricated out of 14 gauge CRCA sheet steel incubicle compartmentalized wall mounted, dust and vermin proof with reinformcement of suitable size angle iron, channels T sections and / or flats wherever necessary including stainless steel door fitted with stainless screws (Degree of protection IP42). Knockouts shall be provided at the top of the panel. Panels shall be treated with all anticrossive process before painting. (Make- PICO / Schneider / Socomec) Approval shall be taken in form of shop drawings before fabrication. Cadmimum plated hardware and conform to NFPA / UL / IS / IEC code of pratice shall be used with followings : 1 No. 63 amps DP ELCB 30 mA leakage current (primary side of transformer). 1 No. 63 amps DP MCB (Primary side of transformer). Isolation Transformer , Rating : 10 KVA, Ratio : 1:1, Primary voltage : 230 V AC + 10%, Secondary Voltage : 230 V AC + 1%, Cooling : Air Cooled, Winding & Type : Copper winding double wound with shield grounded to isolated ground bus secondary ungrounded, Spike suppression level : Not more than 3 dB, Insulation Class : H, Overloading Capacity : 50% for one hour, Sound level complete Unit with cabinet : Not more than 28 dB., Line Isolation Monitor : Hazard Index 5 mA Conist of leakage current detector control transformer mother board with relay etc. LIM monitor card.(Pieco Make), Indication & Metering Meter with selection indicator including selector switch : 0-10 mA. Following indication for Hazard Index. Leakage Lamp Zone, Current mA Colour , 3-4 Green Safe Zone, 5-10 Red Hazard Zone Alarm, 1 No. orange colour lamp shall be provided for mains ON., Suitable rating MCB’s shall be provided for all indicating lamps. Audio / Visual alarm, test / reset PB’s including all accessories as required. Outgoing MCB : 14 Nos. 20 amps DP MCBs. Note: All ELCB shall be of SI/HI-type. All MCB’s shall be minimum of 10 KA breaking capacity & ‘D’ curve only. Ventilation fans for cooling of isolation transformers shall be provided. Isolation for OT’s described as above. | item1056 | 17 | Each |
| 1037 | 1037 | Supply, Installation, Testing & Commissioning of Controllers- Networkable 2 reader/ 2 door Intelligent controller with enclosure and power supply (Enclosure + Power Supply) . | item1057 | 33 | No. |
| 1038 | 1038 | Supply, installation, testing and commissioning Short Range (up to 9 cm ) Smart Card Reader For Exit of Lift Access Doors , tripod/Flap barrier- Entry & Exit (doors) as per the specification. | item1058 | 66 | No. |
| 1039 | 1039 | Supply, installation, testing and commissioning of contactless Clamshell 2K /2Application Area Smart Card suitable for Access Door as per the specification. | item1059 | 900 | No. |
| 1040 | 1040 | Supply, installation, testing and commissioning Access Control System Server Software consisting of Access Control system , Alarm Document , Alarm management , All these along with high end security features consist in single package as per specification. | item1060 | 3 | No. |
| 1041 | 1041 | Supply, Installation, testing & commissioning of Single Leaf Electro Magnetic Lock of Suitable Capacity(Min 600 lbs) as per specification Double Leaf Door | item1061 | 57 | No. |
| 1042 | 1042 | Supply, Installation, testing & commissioning of Single Leaf Electro Magnetic Lock of Suitable Capacity(Min 600 lbs) as per specification . Single Door Leaf | item1062 | 9 | No. |
| 1043 | 1043 | Supply and Laying of of 8 Core x 0.2 sq mm multi strand, copper, unarmored shielded Cable as per specification (between the every card readers & the access controllers) | item1063 | 3300 | Meter |
| 1044 | 1044 | Power Supply- Supply, Installation , testing and commissioning of 12 V SMPS DC Power Supply Unit, highly regulated and spikes free terminal voltage and heavy sourcing current for regulated terminal voltage. | item1064 | 17 | No. |
| 1045 | 1045 | Magnetic Contact- Supply, Installation, Testing and commissioning of Magnetic Contact. | item1065 | 66 | No. |
| 1046 | 1046 | Supply , Installation , Testing and commissioning of Single Front Facia Plate consisting of Soft Touch Push Buttons Emergency Exit Door Release and indicator LED to show the door status | item1066 | 66 | No. |
| 1047 | 1047 | Supply, Installation, Testing & Commissioning of Switch Layer 2/3 managed switch with 24 ports (RJ-45) port. The switch shall have 2 RSTP enabled ports to communicate with other switches to built a ring topology network on CAT6 cable. The switch shall have 1 Giga-byte port to communicate with other switches including Passive components inbuilt 2 SFP ports including SFP modules, rack mountable, SMPS power supply & other termination accessories (Like Pigtails/LIUs/ Convertors/Splicing equipment, Patch panel, Patch Cord, Etc) | item1067 | 99 | No. |
| 1048 | 1048 | Supply, Installation, Testing & Commissioning of IP based Nurse Station Terminal: 'Nurse Station shall comprises of minimum 7“ large touch screen colour graphic display for displaying all details, Electronic circuit board with controller and FlashProm, 100BaseTX interface to the system switch, 3m connection cable. The ward terminal shall display date and time, indication of all presence, indication of all calls including the exact location. | item1068 | 78 | No. |
| 1049 | 1049 | Supply, Installation, Testing & Commissioning of IP based Patient Bedhead Terminal - Without Speech consisting of a plastic case in antimicrobial finish having\n- having Call button with nurse symbol with integrated led light on the top of button.\n- 3 lighting keys for other functions like code blue, emergency and house-keeping. | item1069 | 424 | No. |
| 1050 | 1050 | Supply, Installation, Testing & Commissioning of Lamp Module For optical indication of calls, presences and reminders in the 3 relevant colours consisting of:\n- Single light chamber with light reflectors for homogeneous illumination. | item1070 | 276 | No. |
| 1051 | 1051 | Central Monitoring & Even Database Software with Server & LAN switches, Even Database Software, Supply, Installation, Testing & Commissioning of Software- Event Database Software Software pack installed on the system server for automatically logging all events in the entire communications system, such as, e.g., calls, presence markings, call acknowledgements, reminders. | item1071 | 2 | No. |
| 1052 | 1052 | Server for Nurse Call System, Supply, Installation, Testing & Commissioning of Management center - Nurse Call Server Management Centre Server for Nurse Call System for uploading the firmware and the system configuration, for operating interfaces to foreign systems, for logging of all system events and as a central location for system configuration and remote maintenance\n- Intel i5 3GHz or higher\n- 8 GB RAM, 1TB HDD\n- 2 x Gbit LAN Ethernet RJ45\n- 1 x serial connection RS232 and 2 x USB | item1072 | 2 | No. |
| 1053 | 1053 | Supply, Installation, Testing & Commissioning of Pull Cord with cancel Button / call cancell button shall consist of:\n- 1 call button (pull cord) including integrated LED,\n- 1 presence button (green) incl. control LED,\n- micro switch with a 2 metre pull cord and a luminous grip with a nurse call symbol,\n- Moisture Protected. | item1073 | 1560 | No. |
| 1054 | 1054 | BED LIFT - TEACHING HOSPITAL BLOCK, Supplying, Installation, Testing & Commissioning of 26 Passenger (1768 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> B+G+7, Travel --> 39.0 Mtrs Approx., Stops & door opening - --> 9/1200 mm WideX 2100mm High, Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1074 | 10 | Set |
| 1055 | 1055 | BED LIFT - TEACHING HOSPITAL BLOCK, Supplying, Installation, Testing & Commissioning of 20 Passenger (1360 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:-Speed --> 1.0 MPS, Floors , Travel , Stops & door opening - --> 6/1200 mm WideX 2100mm High --> 26.0 Mtrs Approx. --> B+G+4, Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1075 | 2 | Set |
| 1056 | 1056 | SERVICE LIFT - TEACHING HOSPITAL BLOCK, Supplying, Installation, Testing & Commissioning of 16 Passenger (1088 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors , Travel --> 26.0 Mtrs Approx. --> B+G+4, Stops & door opening - --> 6/1200 mm WideX 2100mm High, Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1076 | 2 | Set |
| 1057 | 1057 | FIRE LIFT - TEACHING HOSPITAL BLOCK, Supplying, Installation, Testing & Commissioning of 20 Passenger (1360 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors , Travel --> 39.0 Mtrs Approx. --> B+G+7, Stops & door opening - --> 9/1200 mm WideX 2100mm High, Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1077 | 3 | Set |
| 1058 | 1058 | BMW LIFT - TEACHING HOSPITAL BLOCK, Supplying, Installation, Testing & Commissioning of 2500 KG Freight lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> B+G+7 , Travel --> 39.0 Mtrs Approx. Stops & door opening - --> 9/1200 mm WideX 2100mm High, Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1078 | 1 | Set |
| 1059 | 1059 | DUM WEIGHTER - TEACHING HOSPITAL BLOCK, Design, manufacturing, testing at works, supply and delivery, receiving, unloading, storing, inspection, handling, assembling, installing in correct assigned position, effecting proper connections, testing and commissioning of following capacity Dum weighter, having speed of 0.5 MPS 4 stops and 4 openings and total travel of 17.2 meters approx. with VVVF drive, full collective Simplex / Duplex control on 415 V, 50 cycles, 3 phase power complete in accordance with specifications and drawings as required with Car, Car Door & Hoistway Door in SS Hairline, inclusive of built in ARD and as per specification., 250 Kg | item1079 | 4 | Set |
| 1060 | 1060 | FIRE LIFT - ACADEMIC BLOCK, Supplying, Installation, Testing & Commissioning of 16 Passenger (1088 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> G+6, Travel --> 30.0 Mtrs Approx. Stops & door opening - --> 7/1000 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1080 | 1 | Set |
| 1061 | 1061 | 13 PASSENGER LIFT - ACADEMIC BLOCK, Supplying, Installation, Testing & Commissioning of 13 Passenger (884 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> G+6, Travel --> 30.0 Mtrs Approx. Stops & door opening - --> 7/900 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1081 | 5 | Set |
| 1062 | 1062 | 20 PASSENGER LIFT - ACADEMIC BLOCK , Supplying, Installation, Testing & Commissioning of 20 Passenger (1360 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> G+6, Travel --> 30.0 Mtrs Approx., Stops & door opening - --> 7/1200 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1082 | 1 | Set |
| 1063 | 1063 | 16 PASSENGER LIFT - JUNIOR RESIDENCE, Supplying, Installation, Testing & Commissioning of 16 Passenger (1088 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> G+6, Travel --> 23.0 Mtrs Approx. Stops & door opening - --> 7/1000 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1083 | 2 | Set |
| 1064 | 1064 | 16 PASSENGER LIFT - SENIOR RESIDENCE, Supplying, Installation, Testing & Commissioning of 16 Passenger (1088 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> G+3, Travel --> 13.20 Mtrs Approx. Stops & door opening - --> 4/1000 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1084 | 2 | Set |
| 1065 | 1065 | 16 PASSENGER LIFT - MALE INTERN, Supplying, Installation, Testing & Commissioning of 16 Passenger (1088 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> G+6, Travel --> 21.0 Mtrs Approx. Stops & door opening - --> 7/900 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1085 | 1 | Set |
| 1066 | 1066 | 16 PASSENGER LIFT - FEMALE INTERN, Supplying, Installation, Testing & Commissioning of 16 Passenger (1088 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> G+6, Travel --> 21.0 Mtrs Approx. Stops & door opening - --> 7/900 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1086 | 2 | Set |
| 1067 | 1067 | 15 PASSENGER STREATCHER LIFT - UG GIRLS HOSTEL , Supplying, Installation, Testing & Commissioning of 15 Passenger (1020 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> G+3, Travel --> 13.20 Mtrs Approx. Stops & door opening - --> 4/800 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1087 | 2 | Set |
| 1068 | 1068 | 16 PASSENGER LIFT - TYPE-II & TYPE-III RESIDENCE, Supplying, Installation, Testing & Commissioning of 16 Passenger (1088 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.5 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.5 MPS, Floors --> G+17, Travel --> 55.80 Mtrs Approx. Stops & door opening - --> 18/1000 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1088 | 1 | Set |
| 1069 | 1069 | 26 PASSENGER LIFT - TYPE-II & TYPE-III RESIDENCE, Supplying, Installation, Testing & Commissioning of 26 Passenger (1768 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.5 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.5 MPS, Floors --> G+17. Travel --> 55.80 Mtrs Approx. Stops & door opening - --> 18/1200 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1089 | 1 | Set |
| 1070 | 1070 | 16 PASSENGER LIFT - TYPE-IV & V RESIDENCE, Supplying, Installation, Testing & Commissioning of 16 Passenger (1088 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.5 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.5 MPS, Floors --> G+10, Travel --> 34.0 Mtrs Approx. Stops & door opening - --> 11/1000 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1090 | 1 | Set |
| 1071 | 1071 | STREATCHER LIFT - TYPE-IV & V RESIDENCE, Supplying, Installation, Testing & Commissioning of 20 Passenger (1360 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.5 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.5 MPS, Floors --> G+10, Travel --> 34.0 Mtrs Approx. Stops & door opening - --> 11/1000 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1091 | 1 | Set |
| 1072 | 1072 | BED LIFT - TEACHING HOSPITAL BLOCK, Supplying, Installation, Testing & Commissioning of 26 Passenger (1768 Kg) Lifts (Gearless), MR/MRL having contract speed of 1.0 MPS serving different floors in the lift shaft as per detailed specifications enclosed and as under:- Speed --> 1.0 MPS, Floors --> 2B+G+7, Travel --> 43.0 Mtrs Approx. Stops & door opening --> 10/1200 mm WideX 2100mm High. Controller: A.C. variable voltage & variable frequency drive. Automatic rescue device complete with dry maintenance free batteries as required. Operation: Microprocessor based single automatic push button / Quadrant / Triplex / Duplex / Simplex selective collective with / without attendant. The group of Lift shall be as per Arch Drwg. Power-415 V, 3 phase, 50 Hz, 4 wires system, Type of doors, (i) Car Power operated, Two Speed Stainless Steel in Scratch resistant finish. (SS 304 Grade), (ii) Landing doors : Stainless Steel in Scratch resistant finish. (SS 304 Grade), Hand rail not less than 600mm long at 900mm above floor level to be fixed on all the three sides adjacent to control panel in the lift car. The Lift shall be provided with Brail System. Ceiling as per manufacturer's standards with Fan & LED Lights. On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE. Fire man switch at ground floor to be provided. Interlocking provision with Fire detection system shall be provided. Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. IP based CCTV interfaced to be provided. BMS interface for lift position & 3 way Intercom system. 2 Hour Fire rated door. Manufacturer shall be submit the certificate alongwith supply of material from NABL approved Lab. Lift described as above. | item1092 | 18 | Set |
| 1073 | 1073 | HVAC WORK\nAHRI Certified Rotary Screw Water Cooled Chilling Machine With Air Cooled VFD & Microprocessor Based Control Panel (Capacity - 300 TR)\nSupply, installation, testing and commissioning of Rotary Screw Water cooled water Chilling M/C of 300 TR actual capacity at below mentioned operating conditions with R - 134 A refrigerant, open / semihermatic / hermatically sealed compressor, driven by suitable KW Sq. Cage induction motor complete with variable speed drive complete with watercooled shell & tube condenser, insulated shell and tube flooded chiller, flow switches at condenser & chiller outlet, refrigerant piping, Refrigerant and Oil (First Charge), Microprocessor based control panel, chiller / floor mounted aircooled VSD with IP 54 enclosure, active harmonic filters & accessories etc. all mounted on M.S. frame. Motor shall be suitable for 415 volts ± 10%, 50Hz ± 5 %, three phase A.C. supply. The chilling m/c as described above shall be in line with specifications & shall have interface card compatible with BMS system. Actual capacity of chillers shall be based the parameters given below & power consumption / TR at 100%, 75%, 50% & 25% load shall be based on ARI Condition.\nCondenser CDW IN - 29.44º C.\nCDW OUT - 33.61º C.\nFLOW - 4536 LPM\nFouling Factor (MKS) - 0.0002\nPressure Drop Max - 6.5 Meter\nChiller CHW IN - 12.22º C.\nCHW OUT - 6.67º C.\nFLOW - 2721 LPM\nFouling Factor (MKS) - 0.0001\nPressure Drop Max - 6.5 Meter\nCOP At AHRI Condition - 5.8 (Min)\nCapacity of Chiller at above\nOperating condition - 300 TR\nPower Consumption Of Chiller\n/ TR At Tender Condition\nMentioned Above (Max) - 0.68\nThe price quoted for supply, installation, testing & commissioning of Screw Water Chilling Unit shall be inclusive of all duties & taxes, insurance, transportation / shipment cost from works to site, loading / unloading, port clearance charges etc. as required in Indian Rupees. (2W+1Future) in TB Hospital Campus & (2W+1S) in MMCH Hospital Campus | item1093 | 5 | NO |
| 1074 | 1074 | Condenser Water Pumps Set\nSupply, installation, testing and commissioning of Vertical Inline split coupled condenser water centrifugal pump sets with bronze impeller for condenser water recirculation complete with TEFC (IE3) Sq. Cage induction motor with class \"F\" insulation, coupling guard, SS Shaft Grade 416, bronze impeller, factory fitted mechanical seal, flexible pipe connector at inlet and outlet etc. conforming to technical specification & as per following parameters.\nCondenser Water Pumps Set (2W+1S)\nCapacity of Each Pump LPM 4536\nPump Head (Mt) 27.5\nMotor HP (Indicative Only) 40.0\nPump Efficiency (Min) 80% | item1094 | 6 | NO |
| 1075 | 1075 | Primary Chilled Water Pumps Set\nSupply, installation, testing and commissioning of Vertical Inline split coupled chilled water centrifugal pump sets with bronze impeller for chilled water recirculation complete with TEFC (IE3) Sq. Cage induction motor with class \"F\" insulation, coupling guard, SS Shaft Grade 416, bronze impeller, factory fitted mechanical seal, flexible pipe connector at inlet and outlet etc. conforming to technical specification & as per following parameters. The chilled water pumps shall also include the cost of thermal insulation.\nPrimary Chilled Water Pumps Set (2W+1S)\nCapacity of Each Pump LPM 2721\nPump Head (Mt) 14.00\nMotor HP (Indicative Only) 12.5\nPump Efficiency (Min) 75% | item1095 | 6 | NO |
| 1076 | 1076 | Secondary Chilled Water Pumps Set\nSupply, installation, testing and commissioning of Vertical Inline split coupled chilled water centrifugal pump sets with bronze impeller for chilled water recirculation complete with TEFC (IE3) Sq. Cage induction motor with class \"F\" insulation, couplingguard, SS Shaft Grade 416, bronze impeller, factory fitted mechanical seal, flexible pipe connector at inlet and outlet etc. conforming to technical specification & as per following parameters. The chilled water pumps shall also include the cost of thermal insulation. Secondary chilled water pumps shall be suitable for operation on variable frequency drives & conforming to the specifications of variable speed pumping system.\nFor TB Hospital Building (2 x 200 TR @ 2.4 GPM/TR)\nSecondary Chilled Water Pumps Set (2W+1S)\nCapacity of Each Pump LPM 1814\nPump Head (Mt) 22\nPump Motor HP (Indicative Only) 15\nPump Efficiency (Min) 80% | item1096 | 3 | NO |
| 1077 | 1077 | Secondary Chilled Water Pumps Set\nSupply, installation, testing and commissioning of Vertical Inline split coupled chilled water centrifugal pump sets with bronze impeller for chilled water recirculation complete with TEFC (IE3) Sq. Cage induction motor with class \"F\" insulation, couplingguard, SS Shaft Grade 416, bronze impeller, factory fitted mechanical seal, flexible pipe connector at inlet and outlet etc. conforming to technical specification & as per following parameters. The chilled water pumps shall also include the cost of thermal insulation. Secondary chilled water pumps shall be suitable for operation on variable frequency drives & conforming to the specifications of variable speed pumping system.\nFor MMCH Hospital Building (2 x 300 TR @ 2.4 GPM/TR)\nSecondary Chilled Water Pumps Set (2W+1S)\nCapacity of Each Pump LPM 2721\nPump Head (Mt) 22\nPump Motor HP (Indicative Only) 20\nPump Efficiency (Min) 80% | item1097 | 3 | NO |
| 1078 | 1078 | Secondary Chilled Water Pumps Set\nSupply, installation, testing and commissioning of Vertical Inline split coupled chilled water centrifugal pump sets with bronze impeller for chilled water recirculation complete with TEFC (IE3) Sq. Cage induction motor with class \"F\" insulation, couplingguard, SS Shaft Grade 416, bronze impeller, factory fitted mechanical seal, flexible pipe connector at inlet and outlet etc. conforming to technical specification & as per following parameters. The chilled water pumps shall also include the cost of thermal insulation. Secondary chilled water pumps shall be suitable for operation on variable frequency drives & conforming to the specifications of variable speed pumping system.\nFor Medical College Building (1 x 200 TR @ 2.4 GPM/TR)\nSecondary Chilled Water Pumps Set (2W+1S)\nCapacity of Each Pump LPM 1814\nPump Head (Mt) 22\nPump Motor HP (Indicative Only) 15\nPump Efficiency (Min) 80%\n | item1098 | 4 | NO |
| 1079 | 1079 | Variable Speed Pumping System for Secondary Chilled Water Pumps\nFor TB Hospital Building\nSupply, installation, testing and commissioning of Variable Speed Pumping system consisting of three numbers 15 HP variable frequency drive (VFD) having IP-54/55 enclosure with heat sink suitably interfaced with other system components, hand / auto macro designed for pumping application, 01 no. dedicated microprocessor based pump logic controller, parallel pumping software duly downloaded, 02 No. Differential Pressure Sensor / Transmitters, interfacing amongst all components and compatibility of I/O signals etc complete with other accessories as required. | item1099 | 1 | NO |
| 1080 | 1080 | Variable Speed Pumping System for Secondary Chilled Water Pumps\nFor MMCH Hospital Building\nSupply, installation, testing and commissioning of Variable Speed Pumping system consisting of three numbers 20 HP variable frequency drive (VFD) having IP-54/55 enclosure with heat sink suitably interfaced with other system components, hand / auto macro designed for pumping application, 01 no. dedicated microprocessor based pump logic controller, parallel pumping software duly downloaded, 02 No. Differential Pressure Sensor / Transmitters, interfacing amongst all components and compatibility of I/O signals etc complete with other accessories as required. | item1100 | 1 | NO |
| 1081 | 1081 | Variable Speed Pumping System for Secondary Chilled Water Pumps\nFor Medical College Building\nSupply, installation, testing and commissioning of Variable Speed Pumping system consisting of two numbers 15 HP variable frequency drive (VFD) having IP-54/55 enclosure with heat sink suitably interfaced with other system components, hand / auto macro designed for pumping application, 01 no. dedicated microprocessor based pump logic controller, parallel pumping software duly downloaded, 02 No. Differential Pressure Sensor / Transmitters, interfacing amongst all components and compatibility of I/O signals etc complete with other accessories as required. | item1101 | 2 | NO |
| 1082 | 1082 | CTI Certified FRP Induced Draft Cooling Tower (300 TR)\nSupply, installation, testing and commissioning of CTI Certified FRP Induced draft, cross / counter flow, twin fan, direct driven, site erected cooling tower of capacity as mentioned below based on the parameters given below and complete with PVC Fill, Louvers, Drift Eliminator, Weather Proof IP 55 TEFC Motor (IE3), Propeller Fan, FRP Basin with additional sump in the bottom of the basin on every outlet point to avoid vortex formation in the condenser water pipe line, Hot dip galvanised Steel Ladder, Stainless Steel hardware including nut, bolt, washer etc. The cooling tower shall conform to technical specifications given in the tender. The maximum allowable sound power at a distance of 1 M from the cooling Tower shall be less than 75 dB. Tower fan motor shall be suitable for VFD operation and operation of VFD system shall be based approach of cooling tower.\nWater Flow - (4 GPM / TR)\nDesigned Wet Bulb Temperature - 27.8 °C\nWater Inlet / Outlet Temperature - 33.61 °C / 29.44 °C\nCooling Tower Basin Height - 300.0 MM\nFan Motor HP (Indicative) - 1 x 15 / 20 HP\nFan Motor RPM (Indicative) - Below 720 RPM\nCooling Tower Capacity: (2W+1S) | item1102 | 6 | NO |
| 1083 | 1083 | VFD System For Cooling Tower\nSupply, installation, testing and commissioning of VFD having IP-54/55 enclosure from factory with heat sink for each cooling tower fan (15 / 20 HP Each, 3 Nos.) with VFD control panel & other accessories as required. VFD control panel shall be installed in the AC Plant Room. The system shall be complete with variable frequency drive (VFD) suitably interfaced with other system components, hand / auto macro designed, 01 no. dedicated microprocessor based logic controller, software duly downloaded, tempearture Sensor / Transmitters, interfacing amongst all components and compatibility of I/O signals etc complete with other accessories as required. Operation of VFD system shall be based approach of cooling tower. | item1103 | 2 | NO |
| 1084 | 1084 | Pressurised Expansion Tank (Suitable for 1440 GPM Chilled Water, 600 TR)\nSupply, installation, testing and commissioning of pressurised insulated chilled water Expansion Tank of capacity as given below made of MS Sheet & finished with epoxy enamel, having interchangeable butile - EPDM membrane, operating pressure 10 Kg/cm² or as actually required, suitable HP 2 numbers pump (1W+1S), pressure switch, valves, make up water connection & the tank shall be complete with necessary controls etc. as required to make it fully functional. The capacity of each tank shall be 1000 Liters approx. Capacity of tank is for the guidance only & AC Contractor to quote as per actual requirement. | item1104 | 2 | NO |
| 1085 | 1085 | Pressurised Expansion Tank (Suitable for 167 GPM Hot Water, 240 KW)\nSupply, installation, testing and commissioning of pressurised insulated hot water Expansion Tank of capacity as given below made of MS Sheet & finished with epoxy enamel, having interchangeable butile - EPDM membrane, operating pressure 10 Kg/cm² or as actually required, suitable HP 2 numbers pump (1W+1S), pressure switch, valves, make up water connection & the tank shall be complete with necessary controls etc. as required to make it fully functional. The capacity of each tank shall be 800 Liters approx. Capacity of tank is for the guidance only & AC Contractor to quote as per actual requirement. | item1105 | 2 | NO |
| 1086 | 1086 | Hot Water Generator For Winter Heating / Monsoon Reheat (Hospital Building)\nSupply, installation, testing and commissioning of electrically operated Hot Water Generator of capacity 120 KW in multiple bank complete with PLC based microprocessor controls, electrical panels etc. confirming to technical specifications section. (2W+1S)\nInlet Water Temperature 50 °C\nOutlet Water Temperature 55 °C | item1106 | 6 | NO |
| 1087 | 1087 | Hot Water Pump Sets\nSupply, installation, testing and commissioning of Vertical Inline split coupled hot water centrifugal pump sets with bronze impeller for hot water recirculation complete with TEFC (IE3) Sq. Cage induction motor with class \"F\" insulation, coupling guard, SS Shaft Grade 416, bronze impeller, factory fitted mechanical seal, flexible pipe connector at inlet and outlet etc. conforming to technical specification & as per following parameters. The hot water pumps shall also include the cost of thermal insulation. Hot water pumps shall be suitable for operation on variable frequency drives & conforming to the specifications of variable speed pumping system.\nHot Water Pump Sets (2W+1S)\nCapacity of Each Pump LPM 278\nPump Head (Mt) 27.5\nMotor HP 5.0 | item1107 | 6 | NO |
| 1088 | 1088 | Variable Speed Pumping System for Hot Water Pumps\nSupply, installation, testing and commissioning of Variable Speed Pumping system consisting of three number 5 / 7.5 HP variable frequency drive (VFD) having IP-55 enclosure with heat sink suitably interfaced with other system components, hand / auto macro designed for pumping application, interfacing amongst all components and compatibility of I/O signals etc complete with other accessories as required. | item1108 | 2 | NO |
| 1089 | 1089 | Double Skin Floor Mounted AHU (CC + MERV 8 Filter)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted / ceiling suspended as per HVAC Drawing, horizontal type , fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,\n6 Row cooling coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n1,500 CFM, 40 mm St. Pr., 6 Row CC (Floor Mounted / Ceiling Suspended) | item1109 | 4 | NO |
| 1090 | 1090 | Double Skin Floor Mounted AHU (CC + MERV 8 Filter)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted / ceiling suspended as per HVAC Drawing, horizontal type , fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,\n6 Row cooling coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n2,000 CFM, 40 mm St. Pr., 6 Row CC (Floor Mounted / Ceiling Suspended) | item1110 | 3 | NO |
| 1091 | 1091 | Double Skin Floor Mounted AHU (CC + MERV 8 Filter)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted / ceiling suspended as per HVAC Drawing, horizontal type , fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,\n6 Row cooling coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n3,000 CFM, 45 mm St. Pr., 6 Row CC (Floor Mounted / Ceiling Suspended) | item1111 | 1 | NO |
| 1092 | 1092 | Double Skin Floor Mounted AHU (CC + MERV 8 Filter)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted / ceiling suspended as per HVAC Drawing, horizontal type , fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,\n6 Row cooling coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n5,000 CFM, 45 mm St. Pr., 6 Row CC | item1112 | 1 | NO |
| 1093 | 1093 | Double Skin Floor Mounted AHU (CC + MERV 8 Filter)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted / ceiling suspended as per HVAC Drawing, horizontal type , fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,\n6 Row cooling coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n7,000 CFM, 50 mm St. Pr., 6 Row CC | item1113 | 1 | NO |
| 1094 | 1094 | Double Skin Floor Mounted AHU (CC + MERV 8 Filter)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted / ceiling suspended as per HVAC Drawing, horizontal type , fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,\n6 Row cooling coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n9,000 CFM, 50 mm St. Pr., 6 Row CC | item1114 | 5 | NO |
| 1095 | 1095 | Double Skin Floor Mounted AHU (CC + MERV 8 Filter)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted / ceiling suspended as per HVAC Drawing, horizontal type , fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,\n6 Row cooling coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n10,000 CFM, 50 mm St. Pr., 6 Row CC | item1115 | 1 | NO |
| 1096 | 1096 | Double Skin Floor Mounted AHU (CC + MERV 8 Filter)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted / ceiling suspended as per HVAC Drawing, horizontal type , fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,\n6 Row cooling coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n14,000 CFM, 55 mm St. Pr., 6 Row CC | item1116 | 1 | NO |
| 1097 | 1097 | Double Skin Floor Mounted AHU (CC + MERV 8 Filter)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted / ceiling suspended as per HVAC Drawing, horizontal type , fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,\n6 Row cooling coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n12,000 CFM, 55 mm St. Pr., 6 Row CC | item1117 | 3 | NO |
| 1098 | 1098 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n2,000 CFM, 60 mm St. Pr., 6 Row CC, 2 Row HC | item1118 | 8 | NO |
| 1099 | 1099 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n2,500 CFM, 60 mm St. Pr., 6 Row CC, 2 Row HC | item1119 | 1 | NO |
| 1100 | 1100 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n3,000 CFM, 60 mm St. Pr., 6 Row CC, 2 Row HC | item1120 | 1 | NO |
| 1101 | 1101 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n3,500 CFM, 60 mm St. Pr., 6 Row CC, 2 Row HC | item1121 | 1 | NO |
| 1102 | 1102 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n4,000 CFM, 65 mm St. Pr., 6 Row CC, 2 Row HC | item1122 | 1 | NO |
| 1103 | 1103 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n5,000 CFM, 65 mm St. Pr., 6 Row CC, 2 Row HC | item1123 | 1 | NO |
| 1104 | 1104 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n6,000 CFM, 65 mm St. Pr., 6 Row CC, 2 Row HC | item1124 | 5 | NO |
| 1105 | 1105 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n7,000 CFM, 70 mm St. Pr., 6 Row CC, 2 Row HC | item1125 | 3 | NO |
| 1106 | 1106 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n8,000 CFM, 70 mm St. Pr., 6 Row CC, 2 Row HC | item1126 | 2 | NO |
| 1107 | 1107 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n8,500 CFM, 70 mm St. Pr., 6 Row CC, 2 Row HC | item1127 | 1 | NO |
| 1108 | 1108 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n10,000 CFM, 70 mm St. Pr., 6 Row CC, 2 Row HC | item1128 | 6 | NO |
| 1109 | 1109 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n12,000 CFM, 75 mm St. Pr., 6 Row CC, 2 Row HC | item1129 | 3 | NO |
| 1110 | 1110 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n13,000 CFM, 75 mm St. Pr., 6 Row CC, 2 Row HC | item1130 | 1 | NO |
| 1111 | 1111 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n14,000 CFM, 75 mm St. Pr., 6 Row CC, 2 Row HC | item1131 | 5 | NO |
| 1112 | 1112 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n15,000 CFM, 75 mm St. Pr., 6 Row CC, 2 Row HC | item1132 | 5 | NO |
| 1113 | 1113 | Double Skin Floor Mounted AHU (CC + HC + MERV 8 & 13)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted horizontal type, fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 6 Row cooling coil and 2 row heating coil made of Aluminium finned Copper tube with coil section, Copper Header, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame, fine filter section with MERV 13 filters in extruded aluminium frame, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.\nThe AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n16,000 CFM, 75 mm St. Pr., 6 Row CC, 2 Row HC | item1133 | 5 | NO |
| 1114 | 1114 | Double Skin Floor Mounted AHU (For OT With 10 ACH/Hr)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm polished SS sheet inside complete with supply & exhaust blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters for both supply & exhaust fan motor, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling & 2 row heating coil made of Aluminium finned Copper tube, Copper header with coil section, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame in both the supply & exhaust side of AHU, fine filter section with MERV 13 filters in extruded aluminium frame in supply after fan, (Hepa filters shall be at terminals along with laminar flow plenum & not to be included in the cost), mixing chamber, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers.The AHU panels shall be insulated with 48mm thick & 36 Kg/m³ density PU foam & shall have thermal break. These AHUs shall have air inlet / outlet connection made of aluminium 20 G & all fixing arrangement / blank off shall be of SS. The static pressure given below is for guidance only actual to be calculated by vendor.\n3500 CFM Supply Air, 8 Row CC, 2 Row HC, 125 mm St. Pr., Supply Fan, 850 CFM Ex. Air Fan, 40 mm St. Pr.for Exhaust fan with other accessories as specified) | item1134 | 13 | NO |
| 1115 | 1115 | Double Skin Floor Mounted AHU (For OT With 10 ACH/Hr)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit floor mounted fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm polished SS sheet inside complete with supply & exhaust blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters for both supply & exhaust fan motor, power control panel with necessary switchgears incoming & outgoing for VFD & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling & 2 row heating coil made of Aluminium finned Copper tube, Copper header with coil section, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame in both the supply & exhaust side of AHU, fine filter section with MERV 13 filters in extruded aluminium frame in supply after fan, (Hepa filters shall be at terminals along with laminar flow plenum & not to be included in the cost), mixing chamber, polished stainless steel drain pan made out of 22 G sheet duly insulated, AHU panels insulation with 48mm thick & 36 Kg/m³ density PU foam, thermal break, motor & blower assembly mounted on Aluminium extruded section only, air inlet / outlet connection made of aluminium 20 G & all fixing arrangement / blank off made of SS. The static pressure given below is for guidance only actual to be calculated by vendor.\n5000 CFM Supply Air, 8 Row CC, 2 Row HC, 125 mm St. Pr., Supply Fan, 1200 CFM Ex. Air Fan, 40 mm St. Pr.for Exhaust fan with other accessories as specified) | item1135 | 1 | NO |
| 1116 | 1116 | Double Skin Floor Mounted AHU (For 100% Fresh Air OT)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm polished SS sheet inside complete with supply & exhaust blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters for both supply & exhaust fan motor, power control panel with necessary switchgears incoming & outgoing for VFD, HRW & humidifier, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling & 2 row heating coil made of Aluminium finned Copper tube, Copper header with coil section, Coilotron UV section only of 600 mm in length in floor mounted AHU, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame in both the supply & exhaust side of AHU, fine filter section with MERV 13 filters in extruded aluminium frame in supply after fan, (Hepa filters shall be at terminals along with laminar flow plenum & not to be included in the cost), Heat Recovery Wheel with HRW Section, mixing chamber, polished stainless steel drain pan made out of 22 G sheet duly insulated, AHU panels insulation with 48mm thick & 36 Kg/m³ density PU foam, thermal break, air inlet / outlet connection made of aluminium 20 G & all fixing arrangement / blank off shall be of SS The static pressure given below is for guidance only actual shall be as per shop drawings.\n(3500 CFM Supply Air Blower, 8 Row CC, 2 Row HC, 140 mm St. Pr., 3000 CFM Ex. Air Blower, 60 mm St. Pr. with other accessories as specified above) | item1136 | 9 | NO |
| 1117 | 1117 | Double Skin Floor Mounted AHU (100% Fresh Air For Post Mortem Autopsy Room, Dissection Hall)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with supply & exhaust blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters for both supply & exhaust fan motor, power control panel with necessary switchgears incoming & outgoing for VFD & HRW, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling coil made of Aluminium finned Copper tube, Copper header with coil section, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame in both the supply & exhaust side of AHU, Coilotron UV section only of 600 mm in length in floor mounted AHU, fine filter section with MERV 13 filters in extruded aluminium frame in supply after fan, Heat Recovery Wheel with HRW Section, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers. The AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n(2000 CFM Supply Air Blower, 8 Row CC, 85 mm St. Pr., 2300 CFM Ex. Air Blower, HRW, 50 mm St. Pr. with other accessories as specified above) | item1137 | 1 | NO |
| 1118 | 1118 | Double Skin Floor Mounted AHU (100% Fresh Air For Post Mortem Autopsy Room, Dissection Hall)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with supply & exhaust blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters for both supply & exhaust fan motor, power control panel with necessary switchgears incoming & outgoing for VFD & HRW, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling coil made of Aluminium finned Copper tube, Copper header with coil section, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame in both the supply & exhaust side of AHU, Coilotron UV section only of 600 mm in length in floor mounted AHU, fine filter section with MERV 13 filters in extruded aluminium frame in supply after fan, Heat Recovery Wheel with HRW Section, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers. The AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n(3500 CFM Supply Air Blower, 8 Row CC, 100 mm St. Pr., 4000 CFM Ex. Air Blower, HRW, 60 mm St. Pr. with other accessories as specified above) | item1138 | 1 | NO |
| 1119 | 1119 | Double Skin Floor Mounted AHU (100% Fresh Air For Post Mortem Autopsy Room, Dissection Hall)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling unit fabricated out of extruded aluminium section with 0.8mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside complete with supply & exhaust blower section with single / multiple AMCA certified backward curved plug fan with aerofoil design blades, VFD with built in harmonic filters for both supply & exhaust fan motor, power control panel with necessary switchgears incoming & outgoing for VFD & HRW, control transformer 220 / 24 V & auxiliary relay etc as required, blower suitable for static pressure as required (Fan Static given below is for guideline), blower motor TEFC (IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling coil made of Aluminium finned Copper tube, Copper header with coil section, pre-filter section with non woven synthetic media MERV 8 filters in extruded aluminium frame in both the supply & exhaust side of AHU, Coilotron UV section only of 600 mm in length in floor mounted AHU, fine filter section with MERV 13 filters in extruded aluminium frame in supply after fan, Heat Recovery Wheel with HRW Section, polished stainless steel drain pan made out of 22 G sheet duly insulated etc. without face and bypass dampers. The AHU panels shall be insulated with 25 mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard specication. The face velocity across coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be as follows. The static pressure given below is for guidance only actual to be calculated by vendor.\n(10,000 CFM Supply Air Blower, 8 Row CC, 100 mm St. Pr., 10,500 CFM Ex. Air Blower, HRW, 60 mm St. Pr. with other accessories as specified above) | item1139 | 1 | NO |
| 1120 | 1120 | Fan Coil Unit\nSupply, installation, testing and commissioning of GI powder coated fan coil units complete with fan, 3 speed motor, 4 row deep cooling coil, aluminium filters MERV 8, filter box, double sandwitched insulated extended tray to accomodate all FCU valves within extended tray duly insulated with nitrile rubber as specified for pipe insulation, supporting arrangement, electrical wiring etc. The fan shall be selected for 5 - 8 mm external static pressure as given below & as per approved drawing.\nThe complete fan coil unit shall have acoustically lined casing & shall be in line with the standard specification. The capacity of fan coil units shall be as follows. The FCU shall be with one set of commissioning filter which shall be replaced with actual filter.\n1.0 TR, 4 mm external static | item1140 | 27 | NO |
| 1121 | 1121 | Fan Coil Unit\nSupply, installation, testing and commissioning of GI powder coated fan coil units complete with fan, 3 speed motor, 4 row deep cooling coil, aluminium filters MERV 8, filter box, double sandwitched insulated extended tray to accomodate all FCU valves within extended tray duly insulated with nitrile rubber as specified for pipe insulation, supporting arrangement, electrical wiring etc. The fan shall be selected for 5 - 8 mm external static pressure as given below & as per approved drawing.\nThe complete fan coil unit shall have acoustically lined casing & shall be in line with the standard specification. The capacity of fan coil units shall be as follows. The FCU shall be with one set of commissioning filter which shall be replaced with actual filter.\n1.5 TR, 4 mm external static | item1141 | 63 | NO |
| 1122 | 1122 | Fan Coil Unit\nSupply, installation, testing and commissioning of GI powder coated fan coil units complete with fan, 3 speed motor, 4 row deep cooling coil, aluminium filters MERV 8, filter box, double sandwitched insulated extended tray to accomodate all FCU valves within extended tray duly insulated with nitrile rubber as specified for pipe insulation, supporting arrangement, electrical wiring etc. The fan shall be selected for 5 - 8 mm external static pressure as given below & as per approved drawing.\nThe complete fan coil unit shall have acoustically lined casing & shall be in line with the standard specification. The capacity of fan coil units shall be as follows. The FCU shall be with one set of commissioning filter which shall be replaced with actual filter.\n2.0 TR, 5 mm external static | item1142 | 1 | NO |
| 1123 | 1123 | Fan Coil Unit\nSupply, installation, testing and commissioning of GI powder coated fan coil units complete with fan, 3 speed motor, 4 row deep cooling coil, aluminium filters MERV 8, filter box, double sandwitched insulated extended tray to accomodate all FCU valves within extended tray duly insulated with nitrile rubber as specified for pipe insulation, supporting arrangement, electrical wiring etc. The fan shall be selected for 5 - 8 mm external static pressure as given below & as per approved drawing.\nThe complete fan coil unit shall have acoustically lined casing & shall be in line with the standard specification. The capacity of fan coil units shall be as follows. The FCU shall be with one set of commissioning filter which shall be replaced with actual filter.\n2.5 TR, 5 mm external static | item1143 | 4 | NO |
| 1124 | 1124 | Fan Coil Unit\nSupply, installation, testing and commissioning of GI powder coated fan coil units complete with fan, 3 speed motor, 4 row deep cooling coil, aluminium filters MERV 8, filter box, double sandwitched insulated extended tray to accomodate all FCU valves within extended tray duly insulated with nitrile rubber as specified for pipe insulation, supporting arrangement, electrical wiring etc. The fan shall be selected for 5 - 8 mm external static pressure as given below & as per approved drawing.\nThe complete fan coil unit shall have acoustically lined casing & shall be in line with the standard specification. The capacity of fan coil units shall be as follows. The FCU shall be with one set of commissioning filter which shall be replaced with actual filter.\n3.0 TR, 8 mm external static | item1144 | 5 | NO |
| 1125 | 1125 | FCU Valves With Three Way Bypass Flushing Unit Set For Cooling Coil\nSupply, installation, testing and commissioning of factory insulated jacket copper / brass connection set for chilled water line consisting of Pressure Independant Balancing Cum Two Way Control Valve in a single body equipped with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal, ball valve with strainer at inlet, ball valve at outlet, three way bypass flushing unit, copper / brass connection set with braided pipe flexible connector at in and out at one end etc. Ball valves & strainer sizes in cooling coil shall be 25 mm up to 2 TR & 32 mm for 2.5 TR & above. PIBCV valves sizes in cooling coil shall be 20 mm up to 2 TR & 25 mm for 2.5 TR & above. | item1145 | 94 | NO |
| 1126 | 1126 | Thermostat for FCU\nSupply, installation, testing and commissioning of automatic control for Fan Coil Units for cooling / heating consisting of pressure independant balancing cum two way control valve (already quantified herein) & digital thermostat, which will have provision of setting of room temperature, setting of fan speed (High, Medium, Low). The quoted price of thermostat shall include the cost of 20mm MS conduits, control cabling, MS Box etc as required. Thermostats shall be interlocked to prevent simultaneous heating and cooling. | item1146 | 94 | Set |
| 1127 | 1127 | Digital Display Type Thermostat For AHU\nSupply, installation, testing and commissioning of Proportional cooling / heating, digital display, communicating type thermostat at air-handler. Temperature Sensor for AHUs are also specified in BMS Part. Thermostat shall be installed in case BMS commissioning is significantly delayed. | item1147 | 10 | NO |
| 1128 | 1128 | For All OT AHU (T + RH Control)\nSupply, installation, testing and commissioning of digital display, communicating type thermostat with humidistat for various air handling Units. The thermostat with built in / individual humidistat shall have provision of setting of space temperature & RH and shall display the both. The quoted price of thermostat / humidistat shall include the cost of 20mm MS conduits, control cabling, MS Box etc as required. Temperature + RH Sensor for AHUs are also specified in BMS Part. Thermostat with built in humidistat shall be installed in case BMS commissioning is significantly delayed. | item1148 | 8 | NO |
| 1129 | 1129 | Pressure Independant Balancing Cum Two Way Control Valve (Cooling Coil For AHU)\nSupply, installation, testing and commissioning of Pressure Independant Balancing Cum Two Way Control Valve in a single body equipped with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications of following sizes:\n20 mm Dia, Maximum 2.4 GPM | item1149 | 8 | NO |
| 1130 | 1130 | Pressure Independant Balancing Cum Two Way Control Valve (Cooling Coil For AHU)\nSupply, installation, testing and commissioning of Pressure Independant Balancing Cum Two Way Control Valve in a single body equipped with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications of following sizes:\n25 mm Dia, Maximum 5 GPM | item1150 | 5 | NO |
| 1131 | 1131 | Pressure Independant Balancing Cum Two Way Control Valve (Cooling Coil For AHU)\nSupply, installation, testing and commissioning of Pressure Independant Balancing Cum Two Way Control Valve in a single body equipped with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications of following sizes:\n32 mm Dia, Maximum 15 GPM | item1151 | 49 | NO |
| 1132 | 1132 | Pressure Independant Balancing Cum Two Way Control Valve (Cooling Coil For AHU)\nSupply, installation, testing and commissioning of Pressure Independant Balancing Cum Two Way Control Valve in a single body equipped with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications of following sizes:\n40 mm Dia, Maximum 26 GPM | item1152 | 19 | NO |
| 1133 | 1133 | Pressure Independant Balancing Cum Two Way Control Valve (Cooling Coil For AHU)\nSupply, installation, testing and commissioning of Pressure Independant Balancing Cum Two Way Control Valve in a single body equipped with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications of following sizes:\n50 mm Dia, Maximum 54 GPM | item1153 | 47 | NO |
| 1134 | 1134 | Pressure Independant Balancing Cum Two Way Control Valve (Cooling Coil For AHU)\nSupply, installation, testing and commissioning of Pressure Independant Balancing Cum Two Way Control Valve in a single body equipped with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications of following sizes:\n65 mm Dia, Maximum 80 GPM | item1154 | 13 | NO |
| 1135 | 1135 | Pressure Independant Balancing Cum Two Way Control Valve (Cooling Coil For AHU)\nSupply, installation, testing and commissioning of Pressure Independant Balancing Cum Two Way Control Valve in a single body equipped with electronic modulating actuator working on 2-10 V DC, 4- 20 mA electric signal. The minimum close off Pressure of actuator must be 1.5 times shut off head of pump as per specifications of following sizes:\n80 mm Dia, Maximum 125 GPM | item1155 | 11 | NO |
| 1136 | 1136 | Inline Fans\nSupply, installation, testing and commissioning of Inline fans with motor complete in all respect & of following capacities. The casing of inline fans shall be acoustically lined & shall be selected for lower noise level. Fan motor shall have inbuilt speed controller.\n100 - 200 CFM (10mm static pressure, single phase) | item1156 | 61 | NO |
| 1137 | 1137 | Inline Fans\nSupply, installation, testing and commissioning of Inline fans with motor complete in all respect & of following capacities. The casing of inline fans shall be acoustically lined & shall be selected for lower noise level. Fan motor shall have inbuilt speed controller.\n300 - 500 CFM (12mm static pressure, single phase) | item1157 | 99 | NO |
| 1138 | 1138 | Inline Fans\nSupply, installation, testing and commissioning of Inline fans with motor complete in all respect & of following capacities. The casing of inline fans shall be acoustically lined & shall be selected for lower noise level. Fan motor shall have inbuilt speed controller.\n600 - 900 CFM (15mm static pressure, single phase) | item1158 | 4 | NO |
| 1139 | 1139 | Inline Fans\nSupply, installation, testing and commissioning of Inline fans with motor complete in all respect & of following capacities. The casing of inline fans shall be acoustically lined & shall be selected for lower noise level. Fan motor shall have inbuilt speed controller.\n1000 - 1500 CFM (15mm static pressure, single phase) | item1159 | 94 | NO |
| 1140 | 1140 | Plastic Propeller Fans\nSupply, installation, testing and commissioning of propeller exhaust fans of various capacities as given below suitable for 240 volts, 50 Hz, single phase AC supply complete with gravity louvers & speed regulator etc.\n100 - 200 CFM | item1160 | 184 | NO |
| 1141 | 1141 | Plastic Propeller Fans\nSupply, installation, testing and commissioning of propeller exhaust fans of various capacities as given below suitable for 240 volts, 50 Hz, single phase AC supply complete with gravity louvers & speed regulator etc.\n300 - 500 CFM | item1161 | 41 | NO |
| 1142 | 1142 | Plastic Propeller Fans\nSupply, installation, testing and commissioning of propeller exhaust fans of various capacities as given below suitable for 240 volts, 50 Hz, single phase AC supply complete with gravity louvers & speed regulator etc.\n600 - 1000 CFM | item1162 | 24 | NO |
| 1143 | 1143 | Axial Flow Fan For Basement Ventilation, Lift Well, Lobby & Staircase Pressurisation, Fresh Air & Exhaust Air Ventilation etc.\nSupply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with TEFC (Motor Efficiency IE3) Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along with motor shall be suitable for 250 °C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan Dia, Fan motor KW & static pressure given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Cost of fan & motor shall be inclusive of the actual fan static pressure required.\nAxial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted. Complete Fan shall be tested and approved by UL in accordance with \"Power Ventilators for Smoke Control Systems\" for 250 °C for 2 hours.\nManufacturer shall furnish AMCA Test Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan sourced from that particular factory.\n50,000 CFM (32mm st. pr, 1400 mm Dia Axial Fan, 15 KW, 1450 RPM Fan Motor, Direct Driven) | item1163 | 6 | NO |
| 1144 | 1144 | Axial Flow Fan For Basement Ventilation, Lift Well, Lobby & Staircase Pressurisation, Fresh Air & Exhaust Air Ventilation etc.\nSupply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with TEFC (Motor Efficiency IE3) Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along with motor shall be suitable for 250 °C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan Dia, Fan motor KW & static pressure given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Cost of fan & motor shall be inclusive of the actual fan static pressure required.\nAxial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted. Complete Fan shall be tested and approved by UL in accordance with \"Power Ventilators for Smoke Control Systems\" for 250 °C for 2 hours.\nManufacturer shall furnish AMCA Test Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan sourced from that particular factory.\n40,000 CFM (25mm st. pr, 1250 mm Dia Axial Fan, 11 KW, 1450 RPM Fan Motor, Direct Driven) | item1164 | 40 | NO |
| 1145 | 1145 | Axial Flow Fan For Basement Ventilation, Lift Well, Lobby & Staircase Pressurisation, Fresh Air & Exhaust Air Ventilation etc.\nSupply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with TEFC (Motor Efficiency IE3) Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along with motor shall be suitable for 250 °C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan Dia, Fan motor KW & static pressure given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Cost of fan & motor shall be inclusive of the actual fan static pressure required.\nAxial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted. Complete Fan shall be tested and approved by UL in accordance with \"Power Ventilators for Smoke Control Systems\" for 250 °C for 2 hours.\nManufacturer shall furnish AMCA Test Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan sourced from that particular factory.\n33,000 CFM (25mm st. pr, 1100 mm Dia Axial Fan, 9.3 KW, 1450 RPM Fan Motor, Direct Driven) | item1165 | 2 | NO |
| 1146 | 1146 | Axial Flow Fan For Basement Ventilation, Lift Well, Lobby & Staircase Pressurisation, Fresh Air & Exhaust Air Ventilation etc.\nSupply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with TEFC (Motor Efficiency IE3) Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along with motor shall be suitable for 250 °C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan Dia, Fan motor KW & static pressure given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Cost of fan & motor shall be inclusive of the actual fan static pressure required.\nAxial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted. Complete Fan shall be tested and approved by UL in accordance with \"Power Ventilators for Smoke Control Systems\" for 250 °C for 2 hours.\nManufacturer shall furnish AMCA Test Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan sourced from that particular factory.\n20,000 CFM (25mm st. pr, 1000 mm Dia Axial Fan, 7.5 KW, 1450 RPM Fan Motor, Direct Driven) | item1166 | 9 | NO |
| 1147 | 1147 | Axial Flow Fan For Basement Ventilation, Lift Well, Lobby & Staircase Pressurisation, Fresh Air & Exhaust Air Ventilation etc.\nSupply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with TEFC (Motor Efficiency IE3) Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along with motor shall be suitable for 250 °C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan Dia, Fan motor KW & static pressure given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Cost of fan & motor shall be inclusive of the actual fan static pressure required.\nAxial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted. Complete Fan shall be tested and approved by UL in accordance with \"Power Ventilators for Smoke Control Systems\" for 250 °C for 2 hours.\nManufacturer shall furnish AMCA Test Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan sourced from that particular factory.\n15,000 CFM (25mm st. pr, 900 mm Dia Axial Fan, 3.7 KW, 1450 RPM Fan Motor, Direct Driven) | item1167 | 9 | NO |
| 1148 | 1148 | Axial Flow Fan For Basement Ventilation, Lift Well, Lobby & Staircase Pressurisation, Fresh Air & Exhaust Air Ventilation etc.\nSupply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with TEFC (Motor Efficiency IE3) Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along with motor shall be suitable for 250 °C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan Dia, Fan motor KW & static pressure given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Cost of fan & motor shall be inclusive of the actual fan static pressure required.\nAxial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted. Complete Fan shall be tested and approved by UL in accordance with \"Power Ventilators for Smoke Control Systems\" for 250 °C for 2 hours.\nManufacturer shall furnish AMCA Test Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan sourced from that particular factory.\n12,000 CFM (25mm st. pr, 800 mm Dia Axial Fan, 3.7 KW, 1450 RPM Fan Motor, Direct Driven) | item1168 | 3 | NO |
| 1149 | 1149 | Axial Flow Fan For Basement Ventilation, Lift Well, Lobby & Staircase Pressurisation, Fresh Air & Exhaust Air Ventilation etc.\nSupply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with TEFC (Motor Efficiency IE3) Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along with motor shall be suitable for 250 °C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan Dia, Fan motor KW & static pressure given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Cost of fan & motor shall be inclusive of the actual fan static pressure required.\nAxial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted. Complete Fan shall be tested and approved by UL in accordance with \"Power Ventilators for Smoke Control Systems\" for 250 °C for 2 hours.\nManufacturer shall furnish AMCA Test Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan sourced from that particular factory.\n10,000 CFM (20mm st. pr, 800 mm Dia Axial Fan, 2.2 KW, 1450 RPM Fan Motor, Direct Driven) | item1169 | 72 | NO |
| 1150 | 1150 | Axial Flow Fan For Basement Ventilation, Lift Well, Lobby & Staircase Pressurisation, Fresh Air & Exhaust Air Ventilation etc.\nSupply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with TEFC (Motor Efficiency IE3) Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along with motor shall be suitable for 250 °C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan Dia, Fan motor KW & static pressure given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Cost of fan & motor shall be inclusive of the actual fan static pressure required.\nAxial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted. Complete Fan shall be tested and approved by UL in accordance with \"Power Ventilators for Smoke Control Systems\" for 250 °C for 2 hours.\nManufacturer shall furnish AMCA Test Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan sourced from that particular factory.\n8,000 CFM (20mm st. pr, 600 mm Dia Axial Fan, 2.2 KW, 1450 RPM Fan Motor, Direct Driven) | item1170 | 10 | NO |
| 1151 | 1151 | Axial Flow Fan For Basement Ventilation, Lift Well, Lobby & Staircase Pressurisation, Fresh Air & Exhaust Air Ventilation etc.\nSupply, installation, testing and commissioning of ceiling mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with TEFC (Motor Efficiency IE3) Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The complete fan along with motor shall be suitable for 250 °C temperature rated for 2 hours. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan Dia, Fan motor KW & static pressure given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on maximum 16 m/sec outlet velocity. Cost of fan & motor shall be inclusive of the actual fan static pressure required.\nAxial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete certified model appearing on AMCA web site shall be accepted. Complete Fan shall be tested and approved by UL in accordance with \"Power Ventilators for Smoke Control Systems\" for 250 °C for 2 hours.\nManufacturer shall furnish AMCA Test Certificate for air & sound performance along with UL fire test certificate (Latest) for each fan sourced from that particular factory.\n6,000 CFM (20mm st. pr, 500 mm Dia Axial Fan, 1.1 KW, 1450 RPM Fan Motor, Direct Driven) | item1171 | 6 | NO |
| 1152 | 1152 | Factory Fabricated Double Skin Airwasher\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Air-washer unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Motor Efficiency IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, belt drive package, wet section & tank shall be made of 18 G stainless steel.\nThe Air-washer shall be complete with fill of depth 200 mm & face velocity across the fill shall be limited to 152 MPM. The Air-washer shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves Aluminum viscous filters. The Air-washer shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves Aluminum viscous filters. The airwasher panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The static pressure given below is for guidance only actual to be calculated by vendor. The Airwasher shall conform to specication given in the tender & shall be of following capacity.\n25,000 CFM, 1 x 800 mm Dia. Fan, 1 x 15 Kw Fan Motor, 50 mm St. Pressure, Monoblock Pump | item1172 | 2 | NO |
| 1153 | 1153 | Factory Fabricated Double Skin Airwasher\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Air-washer unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Motor Efficiency IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, belt drive package, wet section & tank shall be made of 18 G stainless steel.\nThe Air-washer shall be complete with fill of depth 200 mm & face velocity across the fill shall be limited to 152 MPM. The Air-washer shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves Aluminum viscous filters. The Air-washer shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves Aluminum viscous filters. The airwasher panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The static pressure given below is for guidance only actual to be calculated by vendor. The Airwasher shall conform to specication given in the tender & shall be of following capacity.\n20,000 CFM, 1 x 800 mm Dia. Fan, 1 x 11 Kw Fan Motor, 50 mm St. Pressure, Monoblock Pump | item1173 | 2 | NO |
| 1154 | 1154 | Factory Fabricated Double Skin Airwasher\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Air-washer unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Motor Efficiency IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, belt drive package, wet section & tank shall be made of 18 G stainless steel.\nThe Air-washer shall be complete with fill of depth 200 mm & face velocity across the fill shall be limited to 152 MPM. The Air-washer shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves Aluminum viscous filters. The Air-washer shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves Aluminum viscous filters. The airwasher panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The static pressure given below is for guidance only actual to be calculated by vendor. The Airwasher shall conform to specication given in the tender & shall be of following capacity.\n6,000 CFM, 1 x 450 mm Dia. Fan, 1 x 3.7 Kw Fan Motor, 50 mm St. Pressure, Monoblock Pump | item1174 | 1 | NO |
| 1155 | 1155 | Mechanical Ventilation Unit (MVU)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Mechanical Ventilation Unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Efficiency Class 1) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, polished stainless steel drain pan made out of 22 G sheet duly insulated complete with belt drive package etc. The AHU panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete MVU shall conform to tender specication. The static pressure given below is for guidance only actual to be calculated by vendor. The capacity of MVU shall be as follows:\n15,000 CFM, 30mm st. pr, 710 mm Dia Fan, 10.0 HP, 1440 RPM Fan Motor, Belt Driven | item1175 | 4 | NO |
| 1156 | 1156 | Mechanical Ventilation Unit (MVU)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Mechanical Ventilation Unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Efficiency Class 1) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, polished stainless steel drain pan made out of 22 G sheet duly insulated complete with belt drive package etc. The AHU panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete MVU shall conform to tender specication. The static pressure given below is for guidance only actual to be calculated by vendor. The capacity of MVU shall be as follows:\n9,000 CFM, 30mm st. pr, 610 mm Dia Fan, 5 / 7.5 HP, 1440 RPM Fan Motor, Belt Driven | item1176 | 3 | NO |
| 1157 | 1157 | Mechanical Ventilation Unit (MVU)\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Mechanical Ventilation Unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Efficiency Class 1) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, polished stainless steel drain pan made out of 22 G sheet duly insulated complete with belt drive package etc. The AHU panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete MVU shall conform to tender specication. The static pressure given below is for guidance only actual to be calculated by vendor. The capacity of MVU shall be as follows:\n6,500 CFM, 25mm st. pr, 500 mm Dia Fan, 5.0 HP, 1440 RPM Fan Motor, Belt Driven | item1177 | 1 | NO |
| 1158 | 1158 | Factory Fabricated Double Skin Scrubber\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Scrubber unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized /pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Motor Efficiency IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, belt drive package, wet section & tank shall be made of 18 G tainless steel. The Scrubber shall be complete with spray arrangement with metallic viscous filter & face velocity across the section shall be limited to 152 MPM. The scrubber shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves, viscous filters. The scrubber panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The scrubber shall conform to specication given in the tender & shall be of following capacity.\n27,000 CFM, 1 x 800 mm Dia. Fan, 1 x 18.5 Kw Fan Motor, 80 mm St. Pressure, Monoblock Pump For Kitchen | item1178 | 1 | NO |
| 1159 | 1159 | Factory Fabricated Double Skin Scrubber\nSupply, installation, testing and commissioning of factory fabricated Double Skinned Scrubber unit floor mounted type fabricated out of extruded aluminium section with 0.6mm pre-plasticized /pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC (Motor Efficiency IE3) type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, belt drive package, wet section & tank shall be made of 18 G tainless steel. The Scrubber shall be complete with spray arrangement with metallic viscous filter & face velocity across the section shall be limited to 152 MPM. The scrubber shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves, viscous filters. The scrubber panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The scrubber shall conform to specication given in the tender & shall be of following capacity.\n8,000 CFM, 1 x 500 mm Dia. Fan, 1 x 5.6 Kw Fan Motor, 70 mm St. Pressure, Monoblock Pump For Kitchen | item1179 | 1 | NO |
| 1160 | 1160 | VFD For 50% of Basment Parking Ventilation Fan (Only Normal Mode)\nSupply, installation, testing and commissioning of BMS compitable VFD for Axial Fan Motor having IP-54 OEM enclosure with heat sink, Built-in Harmonic Filters (ThDi less than 5%), EMC Filters (Electromagnetic Compatibility Filters Category C2 as per EN 61800-3), 2 PID Controlers, Automatic Energy Optimization / Load dependent flux optimization functionality for maximum energy savings & complying with the tender specifications.\n9.3 / 11 KW Motor | item1180 | 14 | NO |
| 1161 | 1161 | CO Based Sensing System For Automated Working Of Parking Ventilation Fans (Normal & Fire Mode)\nSupply, installation, testing and commissioning of CO based sensing system for automatic running & modulating the VFD motor for parking ventilation supply and exahust fans for normal mode operation. Each set of system for each zone shall have six number of infrared CO senser,\nSensor shall have following measuring range & accuracy:-\nCO ( Electrochemical Type ) - Minimum measuring range : 0 ~ 500 ppm.\nCoverage of each sensor shall be approximately 5500 Sq Ft\nThe fan control mechanism shall be based on variable frequency drive . Each zone shall have controlled ventilation rate of 25% of the specified fan capacity at a given frequency, when CO measurement is below 25 ppm & Ventilation rate shall increase proportionally when CO level increase beyond 25 ppm and reach the maximum fan capacity when CO level is above 50 ppm. IF CO level reaches 150 ppm then fans in fire mode shall be switched on automatically. User should be able to vary these setpoints through web based software interface / supervisory controller. Logic Controller shall also have the logic to switch ON the fan when CO is above 20 ppm & switched OFF again when CO drops below 15 ppm. Logic Controller shall also have the facility of Timer & Manual Override for fan operation. | item1181 | 9 | NO |
| 1162 | 1162 | Standalone, Networkable, Intelligent Microprocessor based Programmable DDC\nSupply, installation, testing and commissioning of one no. Standalone Intelligent Microprocessor based Programmable DDC (For Each Zone) with inbuilt HMI , Onboard Modbus port & network functionalities based upon KNX protocol along with suitable Enclosures with all accessories including necessary switchgear, step down transformer, internal power and control cabling (excluding power & control cable to Fan), complete in all respect & as required to suit the site conditions etc. Each Set of DDC Controller should have 1 AI, 8 DI, 2 AO, 4 DO as per IO Summary given in specification per Zone. (UPS Power Supply By Client to each DDC) | item1182 | 9 | NO |
| 1163 | 1163 | AHU Mounted Coilotron UV System For Floor Mounted AHU\nSupply, installation, testing and commissioning of AHU mountable self contained and factory assembled Coilotron UV System with UL 1995 ABQK listed and UL 2043 certified, UV lamp life shall not be less than 11000 hours. Coilotron shall be installed in all floor mounted AHUs as specified herein. All the component / parts shall comply with the specification given in the tender. AHU supplier and coilotron supplier shall co-ordinate with each other regarding the fixing of the same in the AHU.\nFor 2,000 to 8,000 CFM AHU | item1183 | 59 | NO |
| 1164 | 1164 | AHU Mounted Coilotron UV System For Floor Mounted AHU\nSupply, installation, testing and commissioning of AHU mountable self contained and factory assembled Coilotron UV System with UL 1995 ABQK listed and UL 2043 certified, UV lamp life shall not be less than 11000 hours. Coilotron shall be installed in all floor mounted AHUs as specified herein. All the component / parts shall comply with the specification given in the tender. AHU supplier and coilotron supplier shall co-ordinate with each other regarding the fixing of the same in the AHU.\nFor 9,000 to 20,000 CFM AHU | item1184 | 23 | NO |
| 1165 | 1165 | UVGI (Ultra Voilet Germicidal Irradiation) System in Supply Duct (OT & ICU)\nSupply, installation, testing & commissioning of Duct mounted, factory assembled, UVGI system of minimum 90% kill rate with intensity of 3,000 mW-Sec/cm² per pass of air borne viruses, Covid - 19 virus, mold, spores, bacteria & odour etc. complete with all electrical components such as Ballasts, Disconnect Switch, Fuse, Hour Meter etc. in Electrical Box, UL Listed cable between Electrical Box and UVGI frame, Guide Rails and Installation Rails, Cover Plates & all necessary hardware required for installation. The complete package shall be sourced from UVGI manufacturer. The selection of UVGI shall be based on above parameters, tender specification & suitable for duct air quantity as given below:-\nFor 2,000 to 8,000 CFM Duct | item1185 | 33 | NO |
| 1166 | 1166 | UVGI (Ultra Voilet Germicidal Irradiation) System in Supply Duct (OT & ICU)\nSupply, installation, testing & commissioning of Duct mounted, factory assembled, UVGI system of minimum 90% kill rate with intensity of 3,000 mW-Sec/cm² per pass of air borne viruses, Covid - 19 virus, mold, spores, bacteria & odour etc. complete with all electrical components such as Ballasts, Disconnect Switch, Fuse, Hour Meter etc. in Electrical Box, UL Listed cable between Electrical Box and UVGI frame, Guide Rails and Installation Rails, Cover Plates & all necessary hardware required for installation. The complete package shall be sourced from UVGI manufacturer. The selection of UVGI shall be based on above parameters, tender specification & suitable for duct air quantity as given below:-\nFor 9,000 to 15,000 CFM Duct | item1186 | 13 | NO |
| 1167 | 1167 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n250 mm dia. (32 mm thick insulation) | item1187 | 160 | RMT |
| 1168 | 1168 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n200 mm dia. (32 mm thick insulation) | item1188 | 270 | RMT |
| 1169 | 1169 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n150 mm dia. (32 mm thick insulation) | item1189 | 500 | RMT |
| 1170 | 1170 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n125 mm dia. (32 mm thick insulation) | item1190 | 580 | RMT |
| 1171 | 1171 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n100 mm dia. (32 mm thick insulation) | item1191 | 1060 | RMT |
| 1172 | 1172 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n80 mm dia. (32 mm thick insulation) | item1192 | 670 | RMT |
| 1173 | 1173 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n65 mm dia. (32 mm thick insulation) | item1193 | 660 | RMT |
| 1174 | 1174 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n50 mm dia. (32 mm thick insulation) | item1194 | 960 | RMT |
| 1175 | 1175 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n40 mm dia. (32 mm thick insulation) | item1195 | 360 | RMT |
| 1176 | 1176 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n32 mm dia. (19 mm thick insulation) | item1196 | 820 | RMT |
| 1177 | 1177 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n25 mm dia. (19 mm thick insulation) | item1197 | 880 | RMT |
| 1178 | 1178 | Chilled / Hot / Condensate Drain Water Piping With Nitrile Rubber Insulation & Aluminium Cladding\nSupplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive covered with a layer of 120 gm/sq.m polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints complete including repairing of damage to building etc. as per specifications and as required complete in all respect.\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n20 mm dia. (19 mm thick insulation) | item1198 | 60 | RMT |
| 1179 | 1179 | Motorised Butterfly Valves\nSupply, installation, testing and commissioning of motorised on / off butterfly valves with modulating motor in return chilled & hot water line of each chiller & Hot Water Generator operated through BMS & of following sizes. Valves shall be insulated as per pipe insulation material & thickness given above.\n200 mm dia (For Chiller) | item1199 | 6 | NO |
| 1180 | 1180 | Motorised Butterfly Valves\nSupply, installation, testing and commissioning of motorised on / off butterfly valves with modulating motor in return chilled & hot water line of each chiller & Hot Water Generator operated through BMS & of following sizes. Valves shall be insulated as per pipe insulation material & thickness given above.\n80 mm dia (For Hot Water Generator) | item1200 | 6 | NO |
| 1181 | 1181 | Manual Balancing Valves\nBALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.\n200 mm dia (For Chiller) | item1201 | 6 | NO |
| 1182 | 1182 | Manual Balancing Valves\nBALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.\n80 mm dia (For Hot Water Generator) | item1202 | 6 | NO |
| 1183 | 1183 | Valves & Strainer\nSupply, installation, testing and commissioning of following valves in chilled / hot water line as per specification given in the tender. Valves shall be insulated as per pipe insulation material & thickness given above.\nGlobe / Ball Valves\n19 mm dia | item1203 | 30 | NO |
| 1184 | 1184 | Valves & Strainer\nSupply, installation, testing and commissioning of following valves in chilled / hot water line as per specification given in the tender. Valves shall be insulated as per pipe insulation material & thickness given above.\nGlobe / Ball Valves\n25 mm dia | item1204 | 117 | NO |
| 1185 | 1185 | Valves & Strainer\nSupply, installation, testing and commissioning of following valves in chilled / hot water line as per specification given in the tender. Valves shall be insulated as per pipe insulation material & thickness given above.\nGlobe / Ball Valves\n32 mm dia | item1205 | 150 | NO |
| 1186 | 1186 | Valves & Strainer\nSupply, installation, testing and commissioning of following valves in chilled / hot water line as per specification given in the tender. Valves shall be insulated as per pipe insulation material & thickness given above.\nGlobe / Ball Valves\n40 mm dia | item1206 | 24 | NO |
| 1187 | 1187 | BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified\n200 mm dia | item1207 | 28 | NO |
| 1188 | 1188 | BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified\n150 mm dia | item1208 | 24 | NO |
| 1189 | 1189 | BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified\n125 mm dia | item1209 | 4 | NO |
| 1190 | 1190 | BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified\n100 mm dia | item1210 | 34 | NO |
| 1191 | 1191 | BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified\n80 mm dia | item1211 | 54 | NO |
| 1192 | 1192 | BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified\n65 mm dia | item1212 | 44 | NO |
| 1193 | 1193 | BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified\n50 mm dia | item1213 | 102 | NO |
| 1194 | 1194 | NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.\n200 mm dia\n | item1214 | 9 | NO |
| 1195 | 1195 | NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.\n150 mm dia\n | item1215 | 5 | NO |
| 1196 | 1196 | NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.\n80 mm dia\n | item1216 | 6 | NO |
| 1197 | 1197 | Y-strainer ( With Insulation )-200 mm dia | item1217 | 6 | NO |
| 1198 | 1198 | Y-strainer ( With Insulation )-150 mm dia | item1218 | 5 | NO |
| 1199 | 1199 | Y-strainer ( With Insulation )-100 mm dia | item1219 | 2 | NO |
| 1200 | 1200 | Y-strainer ( With Insulation )-80 mm dia | item1220 | 18 | NO |
| 1201 | 1201 | Y-strainer ( With Insulation )-65 mm dia | item1221 | 13 | NO |
| 1202 | 1202 | Y-strainer ( With Insulation )-50 mm dia | item1222 | 57 | NO |
| 1203 | 1203 | Y-strainer ( With Insulation )-40 mm dia | item1223 | 37 | NO |
| 1204 | 1204 | Y-strainer ( With Insulation )-32 mm dia | item1224 | 34 | NO |
| 1205 | 1205 | Y-strainer ( With Insulation )-25 mm dia | item1225 | 9 | NO |
| 1206 | 1206 | Thermometer\nProviding & fixing in position the mercury in glass industrial type thermometers. | item1226 | 186 | NO |
| 1207 | 1207 | Auto Air Vent\nSupply, installation, testing and commissioning of auto air vent valve of following sizes and complying with tender specification.\na) 10 mm dia auto air vent valve | item1227 | 120 | NO |
| 1208 | 1208 | Burried Chilled / Hot Water Piping With TF Quality Expanded Polysterene Insulation & Sand Cement Plaster\nSupplying, laying / fixing, testing and commissioning of following nominal sizes of chilled / hot water piping outside the building laid in the ground including earth excavation & filling as required (with necessary clamps and fittings but excluding valves, strainers, gauges etc.) duly insulated with following thickness TF Quality Expanded Polysterene of minimum 20 Kg / m3 density, thermal conductivity 0.035 (K.cal/ hr. degree C/m or better at 10 deg mean temperature covered with 500 gauge polythene faced hessian with 50 mm overlap, All joints sealed with bitumen, A layer of 0.50 mm x 20 mm G.I. wire mesh netting provided over it butting all joints and laced down with GI wire, sand cement plaster (1:4) 20 mm. thick provided in 2 layers of each 10mm and water proofed by applying hot bitumen & fixing tar felt over the plaster as per specifications and as required complete in all respect.\n\nNote:-The Pipes of sizes 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n150 mm dia. (75 mm thick insulation) | item1228 | 230 | RMT |
| 1209 | 1209 | Condenser Water Piping\nSupplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends, tees etc..but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect.\n\nNote:-The Pipes size 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n50 mm dia pipe | item1229 | 100 | RMT |
| 1210 | 1210 | Condenser Water Piping\nSupplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends, tees etc..but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect.\n\nNote:-The Pipes size 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n250 mm dia pipe | item1230 | 150 | RMT |
| 1211 | 1211 | Condenser Water Piping\nSupplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends, tees etc..but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect.\n\nNote:-The Pipes size 150 mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.\n300 mm dia pipe | item1231 | 380 | RMT |
| 1212 | 1212 | Motorised Butterfly Valves\nSupplying, fixing, testing and commissioning of following sizes Motorized Butterfly Valve with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20 mA electric signal and providing similar transduced feedback output to control system as required.\n250 mm dia (For Condenser Out, Cooling Tower In & Out) | item1232 | 18 | NO |
| 1213 | 1213 | Manual Balancing Valves\nSupply, installation, testing and commissioning of manual balancing valves in return chilled and condenser water line of each chiller, condenser and cooling tower as per tender specification & of following sizes:\n250 mm dia (For Condenser Out, Cooling Tower In) | item1233 | 12 | NO |
| 1214 | 1214 | Valves & Strainer\nSupply, installation, testing and commissioning of following valves in chilled / condenser water line as per specification given in the tender.\nBUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.\n250 mm dia | item1234 | 36 | NO |
| 1215 | 1215 | Valves & Strainer\nSupply, installation, testing and commissioning of following valves in chilled / condenser water line as per specification given in the tender.\nBUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.\n300 mm dia | item1235 | 6 | NO |
| 1216 | 1216 | NON - RETURN VALVE with dual plate of CI body SS plates\nvulcanized NBR seal flanged end & PN 16 pressure rating as specified.\n250 mm dia\n | item1236 | 6 | NO |
| 1217 | 1217 | Pot Strainer\nSupply, installation, testing and commissioning of PN 16 rating Pot - Strainer of the following sizes confirming to tender specification.\na) 300 mm dia | item1237 | 2 | NO |
| 1218 | 1218 | Thermometer\nProviding & fixing in position the mercury in glass industrial type thermometers. | item1238 | 12 | NO |
| 1219 | 1219 | Rectangular GI Ducting (Factory Made - L Shape)\nSupply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.\n24 G (Up To 750 mm) | item1239 | 6860 | SMT |
| 1220 | 1220 | Rectangular GI Ducting (Factory Made - L Shape)\nSupply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.\n22 G (751 to 1500 mm) | item1240 | 8720 | SMT |
| 1221 | 1221 | Rectangular GI Ducting (Factory Made - L Shape)\nSupply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.\n20 G (1501 to 2250 mm) | item1241 | 2455 | SMT |
| 1222 | 1222 | Rectangular GI Ducting (Factory Made - L Shape)\nSupply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.\n18 G (Above 2250 mm) | item1242 | 520 | SMT |
| 1223 | 1223 | Site Fabricated GI Ducting\nSupply, installation, balancing and commissioning of site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required\n24 G (Up To 750 mm) | item1243 | 1050 | SMT |
| 1224 | 1224 | Site Fabricated GI Ducting\nSupply, installation, balancing and commissioning of site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required\n22 G (Up To 750 mm) | item1244 | 1240 | SMT |
| 1225 | 1225 | Site Fabricated GI Ducting\nSupply, installation, balancing and commissioning of site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required\n20 G (Up To 750 mm) | item1245 | 360 | SMT |
| 1226 | 1226 | Site Fabricated GI Ducting\nSupply, installation, balancing and commissioning of site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required\n18 G (Up To 750 mm) | item1246 | 260 | SMT |
| 1227 | 1227 | Site Fabricated Aluminium Ducting\nSupply, fabrication, installation & testing of Aluminium sheet metal ducting duly polysulphide sealed complete with Spliter Damper, vanes etc. as required for OT and as per ISI specifications and as per approved shop drawings.\n22 G | item1247 | 2000 | SMT |
| 1228 | 1228 | Site Fabricated Aluminium Ducting\nSupply, fabrication, installation & testing of Aluminium sheet metal ducting duly polysulphide sealed complete with Spliter Damper, vanes etc. as required for OT and as per ISI specifications and as per approved shop drawings.\n20 G | item1248 | 2200 | SMT |
| 1229 | 1229 | Duct Accoustic Lining\nSupply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications. | item1249 | 1170 | SMT |
| 1230 | 1230 | Duct Insulation\nSupplying and fixing of external thermal insulation on ducts with EPDM Rubber foam with completely closed cell structure as per specifications - Density 40-60 kg /cum , Class A as per ASTM E 84 , Class V-0 as per UL 94 and Mu value > 7000, tape & adhesive (pidilite SR -998) as required of following thickness.\n13mm | item1250 | 9165 | SMT |
| 1231 | 1231 | Fire Dampers & Actuator\nSupplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.\nFire Damper | item1251 | 79 | SMT |
| 1232 | 1232 | Fire Dampers & Actuator\nSupplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.\nActuator | item1252 | 155 | SMT |
| 1233 | 1233 | Grilles, Diffusers, VCD\nSupply, installtion and testing of Powder coated Aluminium extruded grills / diffusers as per specifications given in tender and of following sizes.\nSupplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. | item1253 | 155 | SMT |
| 1234 | 1234 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. | item1254 | 155 | SMT |
| 1235 | 1235 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core. | item1255 | 140 | SMT |
| 1236 | 1236 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core. | item1256 | 140 | SMT |
| 1237 | 1237 | Fresh / Exhaust air louvers with bird screen & damper | item1257 | 38 | SMT |
| 1238 | 1238 | Volume control GI Dampers to be provided in supply & Exhaust air registers / terminals. | item1258 | 100 | SMT |
| 1239 | 1239 | Fixed bar linear air register of following sizes\n100 mm | item1259 | 270 | RMT |
| 1240 | 1240 | Fixed bar linear air register of following sizes\n150 mm | item1260 | 960 | RMT |
| 1241 | 1241 | Fixed bar linear air register of following sizes\n200 mm | item1261 | 160 | RMT |
| 1242 | 1242 | Slot linear air diffusers of following sizes:\n2 Slot | item1262 | 55 | RMT |
| 1243 | 1243 | Slot linear air diffusers of following sizes:\n3 Slot | item1263 | 120 | RMT |
| 1244 | 1244 | GSS Duct Damper\nSupply, installation and testing of multiblade box type Galvanized Sheet Steel construction damper for ducts to be provided with suitable links and quadrants for control of volume of air. | item1264 | 170 | SMT |
| 1245 | 1245 | Acoustic Insulation of AC Plant Room & AHU\nSupplying, fixing acoustic lining on wall and ceiling of AC Plant Room & AHU Room with 50 mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed in 610 mm x 610 mm frame work made of 25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.80 mm perforated aluminium sheet etc. complete as required and as per specifications. | item1265 | 2480 | SMT |
| 1246 | 1246 | Main AC Panel Supply, installation, testing and commissioning of Cubical type sectinalised floor standing switch board by CPRI apprved firms of 31 MVA fault capacity at 415 V complete with 4 strip, 1000 A capacity Aluminium Bus - Bar Electrolytic grade E-91, cable alley, switchgears suitable for AC-23 duty & of following capacity & as per specification given in the tenderA).a) Incomer 800 A 4 Pole ACB with overload, short ckt., earth fault, protection release, with 144 mm (0 -800 A) ammeter with 3 CT and selector switch, 144 mm (0 - 500 V) Voltmeter with selector switch, phase indication light with protection fuse, on / off / trip indicating light with protection fuse.SET 02 b) Bus Coupler Bus Coupler for section A, B & standby chiller of 800 A capacity, four pole ACB.SET 02 c) Incomer and bus coupler shall be mechanically & electrically interlocked to avoid paralleling of the two supplies. LOT B Outgoings a) For 3 Nos. Water-cooled Chiller (2W+1S) 630 A 4 Pole MCCB with overload, short circuit & earth fault protection with (0 - 630A) ammeter with three CT & selector switch, on / off indication light with protection fuses. SET - 03 b) For 3 Nos. HW Generator (2W+1S) 250 A 4 Pole MCCB. SET - 03 c) For 3 Nos. 12.5 / 15 HP Pr. CHW Pumps for Chiller (2W+1S) 63 A TPN MCB with 25 A star delta starter, overload relay, start/stop push buttons, ammeter (0-60A) with three CT & selector switch, on/off/trip indication lights with SP MCB, single phase preventer & auto / manual mode selector switch. SET - 05 d) For 3 Nos. 40 HP CDW Pumps for Chiller (2W+1S) 125 A 4 Pole MCCB with 45 A star delta starter, overload relay, start / stop push buttons, ammeter (0-125A) with three CT & selector switch, on/off/trip indication lights with SP MCB, single phase preventer & auto / manual mode selector switch. SET-03 e) For Hospital & MC - 8 Nos. 15 HP Sr. CHW Pumps, Cooling Tower Fans, 3 Nos. HW Pumps 40 A TPN MCB SET- 11 | item1266 | 2 | Set |
| 1247 | 1247 | Electrical Sub Panel for AHU / FAN / AWS / Scrubber\nSupply, installation, testing and commissioning of Cubical wall mounted type switch board as detailed below & switch gears suitable for AC - 23 duty including making interconnection etc as required. BMS compitable electronic KWH meter shall have been taken in main electrical work therefore same shall not be part of followings sub panel. Note: AHU for Hospital has VFD starter.\nFor Vent Fan Motor Up to 3.73 Kw\n40 A TPN MCB with 9 / 12 / 16 A DOL starter, overload relay, start / stop push buttons, phase indication lights with protection fuse, on / off / trip indication lights with protection fuse, single phase preventer & auto / manual mode selector switch. Set - 01\nControls & interlocking accessories as required. Lot | item1267 | 59 | NO |
| 1248 | 1248 | For Vent Fan Motor of 5.6 Kw\n40 A TPN MCB with 25 A DOL starter, overload relay, start / stop push buttons, phase indication lights with protection fuse, on / off / trip indication lights with protection fuse, single phase preventer & auto / manual mode selector switch. SET-01\nControls & interlocking accessories as required. Lot | item1268 | 27 | NO |
| 1249 | 1249 | For Vent Fan Motor of 7.5 Kw\n40 A TPN MCB with 16 A Star Delta starter, overload relay, start / stop push buttons, phase indication lights with protection fuse, on / off / trip indication lights with protection fuse, single phase preventer & auto / manual mode selector switch. SET-01\nControls & interlocking accessories as required. Lot | item1269 | 17 | NO |
| 1250 | 1250 | For Vent Fan Motor of 9.3 / 11 Kw\n63 A TPN MCB with 25 A Star Delta starter, overload relay, start / stop push buttons, phase indication lights with protection fuse, on / off / trip indication lights with protection fuse, single phase preventer & auto / manual mode selector switch. SET-01\nControls & interlocking accessories as required. Lot | item1270 | 10 | NO |
| 1251 | 1251 | For Vent Fan Motor of 15 / 18.5 Kw\n63 A TPN MCB with 32 A Star Delta starter, overload relay, start / stop push buttons, phase indication lights with protection fuse, on / off / trip indication lights with protection fuse, single phase preventer & auto / manual mode selector switch. SET-01\nControls & interlocking accessories as required. Lot | item1271 | 8 | NO |
| 1252 | 1252 | For Fan Motor, 1 x 5.5 Kw Air Washer + 1 x 3.7 Kw Fan For Laundry Ventilation\nSupply, installation, testing and commissioning of Cubical type sectinalised floor standing switch board by CPRI apprved firms of 18 MVA fault capacity at 415 V complete with 4 strip, 100 A capacity Aluminium Bus - Bar Electrolytic grade E-91, cable alley, switchgears suitable for AC-23 duty & of following capacity & as per specification given in the tender.\nIncomer :\n63 A TPN MCB with (0-63A) ammeter with three CT and selector switch, (0 - 500 V) voltmeter with selector switch, phase indication light with protection fuse. SET-01\nOutgoing\na) For Air-washer Fan Motor of 5.5 Kw 32 A TPN MCB with 25 A DOL starter, overload relay, start/stop push buttons, ammeter (0-32A) with single CT, on/off/trip indication lights with SP MCB, single phase preventer & auto / manual mode selector switch. SET-01\nb) For Fan Motor of 3.7 Kw\n32 A TPN MCB with 16 A DOL starter, overload relay, start/stop push buttons, ammeter (0-32A) with single CT, on/off/trip indication lights with SP MCB, single phase preventer & auto / manual mode selector switch. SET-01\nc) For Air Washer Pump 16 A SP MCB, SET-1\nControls & interlocking accessories as required. Lot | item1272 | 2 | NO |
| 1253 | 1253 | For Fan Motor, 1 x 9.3/11 Kw Air Washer + 1 x 15 Kw Scrubber Fan For Kitchen Ventilation\nSupply, installation, testing and commissioning of Cubical type sectinalised floor standing switch board by CPRI apprved firms of 18 MVA fault capacity at 415 V complete with 4 strip, 160 A capacity Aluminium Bus - Bar Electrolytic grade E-91, cable alley, switchgears suitable for AC-23 duty & of following capacity & as per specification given in the tender.\nIncomer\n125 A 4 Pole MCCB with (0-125A) ammeter with three CT and selector switch, (0 - 500 V) voltmeter with selector switch, phase indication light with protection with protection fuse, on / off indicating light with protection fuse. SET 01\nOutgoing\na) For Air-washer Fan Motor of 9.3 / 11 Kw\n63 A TPN MCB with 25 A star delta starter, overload relay, start/stop push buttons, ammeter (0-60A) with three CT & selector switch, on/off/trip indication lights with SP MCB, single phase preventer & auto / manual mode selector switch. SET-01\nb) For Scrubber Fan Motor of 15 Kw\n100 A 4 Pole MCCB with 32 A star delta starter, overload relay, start/stop push buttons, ammeter (0-100A) with three CT & selector switch, on/off/trip indication lights with SP MCB, single phase preventer & auto / manual mode selector switch. SET-01\nc) For Air Washer Pump\n16 A SP MCB, SET-2\nControls & interlocking accessories as required. Lot | item1273 | 2 | NO |
| 1254 | 1254 | For Fan Motor, 2 x 1.5 / 2.2 / 3.7 Kw For Panel Room, STP etc\nSupply, installation, testing and commissioning of Cubical type sectinalised floor standing switch board by CPRI apprved firms of 18 MVA fault capacity at 415 V complete with 4 strip, 100 A capacity Aluminium Bus - Bar Electrolytic grade E-91, cable alley, switchgears suitable for AC-23 duty & of following capacity & as per specification given in the tender.\nIncomer\n40 A TPN MCB with (0-40A) ammeter with three CT and selector switch, (0 - 500 V) voltmeter with selector switch, phase indication light with protection fuse. SET-01\nOutgoing\na) For Fan Motor of 2 x 1.5 / 2.2 / 3.7 Kw\n32 A TPN MCB with 9 / 12 / 16 A DOL starter, overload relay, start/stop push buttons, ammeter (0-32A) with single CT, on/off/trip indication lights with SP MCB, single phase preventer & auto / manual mode selector switch. SET-02\nb) For Kitchen Air Washer Pump Only 16 A SP MCB, SET-1\nControls & interlocking accessories as required. Lot | item1274 | 5 | NO |
| 1255 | 1255 | For Basement Car Parking Ventilation Fan Motor, 2 x 9.3 / 11 Kw on VFD + 2 x 9.3 / 11 Kw without VFD\nSupply, installation, testing and commissioning of Cubical type sectinalised floor standing switch board by CPRI apprved firms of 18 MVA fault capacity at 415 V complete with 4 strip, 200 A capacity Aluminium Bus - Bar Electrolytic grade E-91, cable alley, switchgears suitable for AC-23 duty & of following capacity & as per specification given in the tender.\nIncomer\n125 A TPN MCCB with (0-125A) ammeter with three CT and selector switch, (0 - 500 V) voltmeter with selector switch, phase indication light with protection fuse. SET-01\nOutgoing\na) For Fan Motor of 2 x 11 Kw on VFD SET-02\n40 A TPN MCB\nb) For Fan Motor of 2 x 11 Kw without VFD\n40 A TPN MCB with 25 A Star Delta starter, overload relay, start/stop push buttons, ammeter (0-40A) with single CT, on/off/trip indication lights with SP MCB, single phase preventer & auto / manual mode selector switch. SET-02 Controls & interlocking accessories as required. Lot | item1275 | 5 | NO |
| 1256 | 1256 | For Basement Car Parking Ventilation Fan Motor, 1 x 9.3 / 11 Kw on VFD + 1 x 9.3 / 11 Kw without VFD\nSupply, installation, testing and commissioning of Cubical type sectinalised floor standing switch board by CPRI apprved firms of 18 MVA fault capacity at 415 V complete with 4 strip, 125 A capacity Aluminium Bus - Bar Electrolytic grade E-91, cable alley, switchgears suitable for AC-23 duty & of following capacity & as per specification given in the tender.\nIncomer\n100 A TPN MCCB with (0-100A) ammeter with three CT and selector switch, (0 - 500 V) voltmeter with selector switch, phase indication light with protection fuse. SET-01\nOutgoing\na) For Fan Motor of 1 x 11 Kw on VFD SET-01\n40 A TPN MCB\nb) For Fan Motor of 1 x 11 Kw without VFD\n40 A TPN MCB with 25 A Star Delta starter, overload relay, start/stop push buttons, ammeter (0-40A) with single CT, on/off/trip indication lights with SP MCB, single phase preventer & auto / manual mode selector switch. SET-01\nControls & interlocking accessories as required. Lot | item1276 | 4 | NO |
| 1257 | 1257 | Single Phase MCB for FCU / Inline Fan\nSupply, Installation, testing & Commissioning of single phase MCB of following capacity:\n16 A SP MCB, SET-01 | item1277 | 195 | NO |
| 1258 | 1258 | Isolators\n63 A 6 pole isolator switch with sheet metal enclosure, rain protection etc. as required to suit the site condition. | item1278 | 23 | NO |
| 1259 | 1259 | Isolators\n40 / 63 A 3 pole isolator switch with sheet metal enclosure, rain protection etc. as required to suit the site condition. | item1279 | 25 | NO |
| 1260 | 1260 | Power Cabling\nSupply, laying, testing and commissioning of power cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor Chiller (315 Kw Each)\n2 x 3.5C x 240 Sq. mm (Rate For Single Run) | item1280 | 280 | RMT |
| 1261 | 1261 | Power Cabling\nSupply, laying, testing and commissioning of power cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor CHW Pump, Cooling Tower Fan (20 HP Each)\n2 x 3C x 16 Sq. mm (Rate For Single Run) | item1281 | 1020 | RMT |
| 1262 | 1262 | Power Cabling\nSupply, laying, testing and commissioning of power cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor CDW Pump (40 HP Each)\n2 x 3C x 35 Sq. mm (Rate For Single Run) | item1282 | 240 | RMT |
| 1263 | 1263 | Power Cabling\nSupply, laying, testing and commissioning of power and control cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor HW Pump (5 HP Each)\n1 x 3C x 6 Sq. mm (Rate For Single Run) | item1283 | 70 | RMT |
| 1264 | 1264 | Power Cabling\nSupply, laying, testing and commissioning of power cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor Hot Water Generator (120 Kw Each)\n1 x 4C x 240 Sq. mm (Rate For Single Run) | item1284 | 120 | RMT |
| 1265 | 1265 | Power Cabling\nSupply, laying, testing and commissioning of power cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor Motor Up to 3.73 Kw\n1 x 3C x 4 Sq. mm | item1285 | 1120 | RMT |
| 1266 | 1266 | Power Cabling\nSupply, laying, testing and commissioning of power cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor Motor of 5.5 Kw\n1 x 3C x 6 Sq. mm | item1286 | 970 | RMT |
| 1267 | 1267 | Power Cabling\nSupply, laying, testing and commissioning of power cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor Motor of 7.5 to 11 Kw\n2 x 3C x 6 Sq. mm | item1287 | 730 | RMT |
| 1268 | 1268 | Power & Control Cabling\nSupply, laying, testing and commissioning of power and control cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor Motor of 15.0 Kw\n2 x 3C x1 6 Sq. mm | item1288 | 360 | RMT |
| 1269 | 1269 | Power Cabling\nSupply, laying, testing and commissioning of power cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor Motor of 18.65 Kw\n2 x 3C x 16 Sq. mm | item1289 | 90 | RMT |
| 1270 | 1270 | Power Cabling\nSupply, laying, testing and commissioning of power cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor Motor of 22.5 Kw\n2 x 3C x 25 Sq. mm | item1290 | 110 | RMT |
| 1271 | 1271 | Power Cabling\nSupply, laying, testing and commissioning of power and control cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nPower Cabling.\nFor Inline Fan / FCU\n1 x 3C x 2.5 Sq. mm Copper | item1291 | 1070 | RMT |
| 1272 | 1272 | Control Cabling\nSupply, laying, testing and commissioning of control cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nControl cabling (PVC insulated Copper conductor of 1.1 KV Grade armoured cable)\n3C x 1.5 Sq. mm | item1292 | 370 | RMT |
| 1273 | 1273 | Control Cabling\nSupply, laying, testing and commissioning of control cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nControl cabling (PVC insulated Copper conductor of 1.1 KV Grade armoured cable)\n4C x 1.5 Sq. mm | item1293 | 870 | RMT |
| 1274 | 1274 | Control Cabling\nSupply, laying, testing and commissioning of control cabling as per specification given in the tender. Power cabling of XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade including cable end termination with brass compression glands & aluminium lugs etc as per specification\nControl cabling (PVC insulated Copper conductor of 1.1 KV Grade armoured cable)\n5C x 1.5 Sq. mm | item1294 | 550 | RMT |
| 1275 | 1275 | Earthing Strip / Wires as per specs.\nSupply & laying of 32 x 6 mm GI strip recess / surface as strip earth lead including soldering etc. as required. | item1295 | 180 | RMT |
| 1276 | 1276 | Earthing Strip / Wires as per specs.\nSupply & laying of 25 x 6 mm GI strip recess / surface as strip earth lead including soldering etc. as required. | item1296 | 420 | RMT |
| 1277 | 1277 | Earthing Strip / Wires as per specs.\nSupply & laying of 4 SWG GI wire or in recess for loop earthing as required. | item1297 | 6050 | RMT |
| 1278 | 1278 | Earthing Strip / Wires as per specs.\nSupply & laying of 6 SWG GI wire or in recess for loop earthing as required. | item1298 | 3360 | RMT |
| 1279 | 1279 | Earthing Strip / Wires as per specs.\nSupply and fixing rubber matting conforming to IS-15652-2006 complete etc. as required. | item1299 | 41 | RMT |
| 1280 | 1280 | Cable Tray\nFabricating and installing following size of perforated M.S. Cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders and including painting with powder coating etc as required.\n100 mm wide x 50 mm x 1.6 mm | item1300 | 770 | RMT |
| 1281 | 1281 | Cable Tray\nFabricating and installing following size of perforated M.S. Cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders and including painting with powder coating etc as required.\n150 mm wide x 50 mm x 1.6 mm | item1301 | 340 | RMT |
| 1282 | 1282 | Cable Tray\nFabricating and installing following size of perforated M.S. Cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders and including painting with powder coating etc as required.\n300 mm wide x 50 mm x 1.6 mm | item1302 | 340 | RMT |
| 1283 | 1283 | Cable Tray\nFabricating and installing following size of perforated M.S. Cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders and including painting with powder coating etc as required.\n450 mm wide x 50 mm x 2 mm | item1303 | 180 | RMT |
| 1284 | 1284 | Cable Tray\nFabricating and installing following size of perforated M.S. Cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders and including painting with powder coating etc as required.\n600 mm wide x 50 mm x 2 mm | item1304 | 220 | RMT |
| 1285 | 1285 | Junction Box For FCU / Propeller / Inline Fan etc (Single Phase)\nSupply, Installation, Testing & Commissioning of 4\" x 3\" x 3\" G.I. Box with modular type 6A socket & switch, modular cover plate etc as required at site. | item1305 | 280 | Set |
| 1286 | 1286 | Starter for Propeller / Inline fan (Single Phase)\nSupply, Installation, Testing & Commissioning of modular type single phase motor starter up to 6A (Rating shall be as per motor) including 3\" x 3\" x 2.5\" G.I. Box with modular, modular cover plate, conduiting and wiring from starter to fan etc as required at site\nNOTE:\nThe AC contractor shall provide fire shunt relay contact in his panel wherever necessary along with auto / manual mode selector switch in the outgoing feeder for AHU Fan, Ventilation & Pressurization fan etc. to take fire input signal (Potential Free Contact). Cost shall be included in the panel price quoted by him. | item1306 | 170 | Set |
| 1287 | 1287 | All the items listed below shall include supply, installation, testing & commissioning.\nSoftware and Operator Workstation\nHost PC comprising core i7 processor or later, 3 GHz, 8.0 GB RAM, 1 TB HDD, DVD drive, 6 nos. USB Port, 18.5\" SVGA color flat TFT monitor, keyboard, mouse and pre-loaded windows 8 operating system and anti virus software, Laserjet printer (A4 size, B/W) | item1307 | 2 | Job |
| 1288 | 1288 | Supply, installation, testing & commissioning of the following Web Based graphical Software. Providing facilities to create static & animate the graphics, navigation between the pages, display of logs, changing the time zones, popup alarms with single user license & point capacity as per I-O Summary with 20% spare points configurable password protection for the system and should be able to communicate with BACnet/M-BUS/LONWORK & MODBUS devices simultaneously. This software will act as web server & no additional license should require at client side.\nApplication Software for Building Automation System having facility to to exchange information using SQL database. Software shall have the features to calculate the total power consumption, total refrigeration load consumed on every day etc. Critical alarms generated in a day and its status should also be mailed along with daily report. | item1308 | 2 | Job |
| 1289 | 1289 | Supervisory Controllers\nNetwork Area / Supervisory Controller for Building Management System (BMS). Network Area Controller Shall support Communication with AC Plant Controllers (DDC controllers) & Other Application Controllers on BACnet, Shall support Communication with Integrator Units as defined below on BACnet / MODBUS / LONWORKS. Router must be compliant with ANSI / ASHRAE 135-2012 (Rev. 1.10) | item1309 | 2 | Job |
| 1290 | 1290 | Direct Digital Controllers (BACNET / LON Type)\nStand alone, intelligent, UL Listed, BTL listed & BTL tested, ANSI / ASHRAE approved Interoperable DDC as per the specifications. All the Controllers shall be UL / BTL tested & CE certified. Each controllers shall be equipped with Universal Inputs with a maximum polling speed of 100 ms. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level.The controller shall be housed in a vandal proof, lockable and secure MS cabinets to be supplied along with controllers. DDC must match BACnet profile B-BC (Building Controller) / B-AAC Profile as per BTL listing. The controller shall have 15% Extra IO capacity.\nEach of the following systems shall have seperate multiple controllers, as required. The DDC selection shall be based on I-O Summary as given in the tender.\nFor Chilled water system - Chillers, CHW & CDW Pumps, Cooling Towers, HWG, HW Pumps & Headers etc. as required. | item1310 | 2 | Job |
| 1291 | 1291 | Direct Digital Controllers (BACNET / LON Type)\nStand alone, intelligent, UL Listed, BTL listed & BTL tested, ANSI / ASHRAE approved Interoperable DDC as per the specifications. All the Controllers shall be UL / BTL tested & CE certified. Each controllers shall be equipped with Universal Inputs with a maximum polling speed of 100 ms. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level.The controller shall be housed in a vandal proof, lockable and secure MS cabinets to be supplied along with controllers. DDC must match BACnet profile B-BC (Building Controller) / B-AAC Profile as per BTL listing. The controller shall have 15% Extra IO capacity.\nEach of the following systems shall have seperate multiple controllers, as required. The DDC selection shall be based on I-O Summary as given in the tender.\nFor Air Handling Units (Category A) as per IO Summary as required. (2 Nos. AHU with 1 No. DDC) . | item1311 | 59 | NO |
| 1292 | 1292 | Direct Digital Controllers (BACNET / LON Type)\nStand alone, intelligent, UL Listed, BTL listed & BTL tested, ANSI / ASHRAE approved Interoperable DDC as per the specifications. All the Controllers shall be UL / BTL tested & CE certified. Each controllers shall be equipped with Universal Inputs with a maximum polling speed of 100 ms. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level.The controller shall be housed in a vandal proof, lockable and secure MS cabinets to be supplied along with controllers. DDC must match BACnet profile B-BC (Building Controller) / B-AAC Profile as per BTL listing. The controller shall have 15% Extra IO capacity.\nEach of the following systems shall have seperate multiple controllers, as required. The DDC selection shall be based on I-O Summary as given in the tender.\nFor All 3 Phase Fans - Fresh Air / Exhaust Air Fan, Airwasher, Scrubber, Pressurisation Fan etc. as required. (4 No. Fans with 1 No. DDC) | item1312 | 31 | NO |
| 1293 | 1293 | Direct Digital Controllers (BACNET / LON Type)\nStand alone, intelligent, UL Listed, BTL listed & BTL tested, ANSI / ASHRAE approved Interoperable DDC as per the specifications. All the Controllers shall be UL / BTL tested & CE certified. Each controllers shall be equipped with Universal Inputs with a maximum polling speed of 100 ms. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level.The controller shall be housed in a vandal proof, lockable and secure MS cabinets to be supplied along with controllers. DDC must match BACnet profile B-BC (Building Controller) / B-AAC Profile as per BTL listing. The controller shall have 15% Extra IO capacity.\nEach of the following systems shall have seperate multiple controllers, as required. The DDC selection shall be based on I-O Summary as given in the tender.\nFor Lift Well, Lift Lobby & Staicase Pressurisation Fans (4 Nos. Fans with 1 No. DDC) | item1313 | 7 | NO |
| 1294 | 1294 | Field instruments As Per I-O Summary\nImmersion Temperature sensor with thermowell for Chilled water system (3 Nos. Chiller Outlet, 2 Nos. Chilled Water Header, 1 No. Condenser Water Return Header, 2 Nos. Hot Water Generator Outlet, 2 Nos. Hot Water Header)\n | item1314 | 20 | NO |
| 1295 | 1295 | Field instruments As Per I-O Summary\nAmbient air temperature and humidity sensor\n | item1315 | 2 | NO |
| 1296 | 1296 | Field instruments As Per I-O Summary\nCurrent relay for pumps (3 Nos. Primary CHW Pumps, 3 Nos. CDW Pumps, Excluding Pumps on VFD)\n | item1316 | 12 | NO |
| 1297 | 1297 | Field instruments As Per I-O Summary\nDifferential pressure switch for various vent. fans excluding Inline & Propeller Fans | item1317 | 102 | NO |
| 1298 | 1298 | Field instruments As Per I-O Summary\nDifferential pressure switch for AHU blower status | item1318 | 98 | NO |
| 1299 | 1299 | Field instruments As Per I-O Summary\nDifferential pressure switch AHU Pre, Fine & Hepa Filter status | item1319 | 150 | NO |
| 1300 | 1300 | Field instruments As Per I-O Summary\nTemperature sensor for return temperature monitoring (Common for cooling / heating) | item1320 | 150 | NO |
| 1301 | 1301 | Integrators for third party systems on BACnet/MODBUS/LONWORKS/OPC/M-BUS and other industry standard Open protocols for the following Third Party Systems. Integrator should have dedicated one Lon, RS-485 & RS-232 Port with minimum of 96 MB storage.Integrator should be able to store trending to ensure gap free storage.The Third Party Integrator should be from the same manufacturer as that of DDC. Chillers on BACnet/MODbus/LONworks Variable Frequency Drives on BACnet/MSTP, MODBUS-RTU Over RS-485 | item1321 | 2 | NO |
| 1302 | 1302 | Cabling and Conduiting\nCommunication & Signal Cabling 2C x 1.5 Sq. mm Shielded Tinned Copper Cable. | item1322 | 24200 | RMT |
| 1303 | 1303 | Cabling and Conduiting\nMS Conduit 25 mm for Signal & Communication Cable | item1323 | 18100 | RMT |
| 1304 | 1304 | Hi-wall Split Unit\nSupplying with installation testing and commissioning of Hi -- wall 3 STAR rating non ducted split type air conditioner of the following capacity with cordless remote complete with indoor and outdoor unit, copper pipe and electrical connection up to 5 m between the room unit and out door unit as approved by the Deptt.) and as directed by the department.\n1.5 TR | item1324 | 43 | NO |
| 1305 | 1305 | Hi-wall Split Unit\nSupplying with installation testing and commissioning of Hi -- wall 3 STAR rating non ducted split type air conditioner of the following capacity with cordless remote complete with indoor and outdoor unit, copper pipe and electrical connection up to 5 m between the room unit and out door unit as approved by the Deptt.) and as directed by the department.\n2.0 TR | item1325 | 17 | NO |
| 1306 | 1306 | Ceiling Suspended Ductable Split Unit\nSupply, installation, testing & commissioning of Air cooled Ceiling Suspended Ductable Split type Air conditioners of following capacities suitable for refrigerant R22/R407C with outdoor unit consisting of hermetically sealed imported power efficient Scroll compressors, condenser coil and condenser fan and indoor unit consisting of evaporating coil, blower fan, motor & filter. Both cooling coil & condenser coil will be made up of copper-internally grooved with slit fins, anti corrosion blue fins along. The control system shall be microprocessor bases with following safety inbuilt: HP/LP cut-out, SPPR (protection against single phasing & reverse polarity) In-built thermal/temperature protection. Microprocessor controller is provided with following features: Auto switch on or off of compressors\nmemory back up of settings\nAuto restart after power failure\nRuntime equalisation of the compressors\nBuilt-in time delay to protect compressors\nFault diagnostics to facilities speedy correction\nThe cost of the machines will also include 20G hard drawn copper refrigerant piping properly saddles using wall spacers CPVC condensate drain piping including U Trap properly saddled, ( Fire Retardant Canvas Cloth duct connection as approved by the Deptt., ( Electrical interconnection as approved by the Deptt.)between IDU & ODU using ISI marked cables in 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit properly saddled, ( Nitrogen pressure testing of refrigerant circuit, ( Refrigerant Gas Charging ensuring optimum performance, etc complete in all respects \"make)s Approved Bluestar, Voltas, Carrier, Hitachi, Daikin, Mitsubishi.\n5.8 TR | item1326 | 8 | NO |
| 1307 | 1307 | Ceiling Suspended Ductable Split Unit\nSupply, installation, testing & commissioning of Air cooled Ceiling Suspended Ductable Split type Air conditioners of following capacities suitable for refrigerant R22/R407C with outdoor unit consisting of hermetically sealed imported power efficient Scroll compressors, condenser coil and condenser fan and indoor unit consisting of evaporating coil, blower fan, motor & filter. Both cooling coil & condenser coil will be made up of copper-internally grooved with slit fins, anti corrosion blue fins along. The control system shall be microprocessor bases with following safety inbuilt: HP/LP cut-out, SPPR (protection against single phasing & reverse polarity) In-built thermal/temperature protection. Microprocessor controller is provided with following features: Auto switch on or off of compressors\nmemory back up of settings\nAuto restart after power failure\nRuntime equalisation of the compressors\nBuilt-in time delay to protect compressors\nFault diagnostics to facilities speedy correction\nThe cost of the machines will also include 20G hard drawn copper refrigerant piping properly saddles using wall spacers CPVC condensate drain piping including U Trap properly saddled, ( Fire Retardant Canvas Cloth duct connection as approved by the Deptt., ( Electrical interconnection as approved by the Deptt.)between IDU & ODU using ISI marked cables in 2mm thick/ heavy rigid PVC IS: 9537 Part - III conduit properly saddled, ( Nitrogen pressure testing of refrigerant circuit, ( Refrigerant Gas Charging ensuring optimum performance, etc complete in all respects \"make)s Approved Bluestar, Voltas, Carrier, Hitachi, Daikin, Mitsubishi.\n16.6 TR | item1327 | 4 | NO |
| 1308 | 1308 | Refrigerant Piping, Cabling, Insulation\nSupplying fitting fixing and connection as approved by the Deptt.)1/2 inch & 3/4 inch copper piping with insulation along with connection as approved by the Deptt.)cable including testing and commissioning as directed by the department. | item1328 | 965 | NO |
| 1309 | 1309 | NON- MEDICAL EQUIPMENT\nMOT comprising of walls & ceiling system for operating area, steel framework, static dissipative flooring, laminar flow, double dome OT light, touch screen surgeon’s control panel, scrub station, X ray viewing screen, hatch box, automatic sliding doors, anesthesia pendent, surgeon pendent etc.\nWith stainless steel technology | item1329 | 24 | per OT |
| 1310 | 1310 | Medical Gas pipeline system (as per international standards) comprising of oxygen, carbon dioxide, nitrous oxide, AGSS, Air-4, Air-7, Vacuum outlets, manifolds, pressure alarms, fully automatic gas control system, Bed head panels, copper piping, cylinder banks, plant equipment such as compressors, Vacuum pumps etc. | item1330 | 1296 | per bed |
| 1311 | 1311 | Sterilizer for CSSD Double Door with Generator 550 liters Vertical Sliding door | item1331 | 2 | Each |
| 1312 | 1312 | Sterilizer for CSSD Double Door with Generator 1000 liters Horizontal sliding door | item1332 | 2 | Each |
| 1313 | 1313 | Washer Disinfector\nModel Tiva10-2M 265 liters12 DIN Basket 2door TUTTNAUER | item1333 | 4 | Each |
| 1314 | 1314 | Sterilizer 1 door with Steam Generator 160 Liters\nModel 5075 HSG-1A TUTTNAUER | item1334 | 2 | Each |
| 1315 | 1315 | Plasma Sterilizer PM 100 Chamber volume:100 Liters | item1335 | 2 | Each |
| 1316 | 1316 | Drying Cabinet 360Liters DRY | item1336 | 2 | Each |
| 1317 | 1317 | Automatic Ultra sonic Cleaner | item1337 | 2 | Each |
| 1318 | 1318 | SPRAY GUN RINSER | item1338 | 2 | Each |
| 1319 | 1319 | HEAT SEALING MACHINE | item1339 | 4 | Each |
| 1320 | 1320 | STAINLESS STEEL PASS BOX | item1340 | 6 | Each |
| 1321 | 1321 | Control & Packaging Table with two shelves | item1341 | 4 | Each |
| 1322 | 1322 | Stainless Steel Work Table With Double Sink | item1342 | 2 | Each |
| 1323 | 1323 | Stainless Steel work table with under shelf | item1343 | 8 | Each |
| 1324 | 1324 | SS BASKET RACKS | item1344 | 4 | Each |
| 1325 | 1325 | Closed transport trolley | item1345 | 8 | Each |
| 1326 | 1326 | SS Storage Rack With Five Shelves | item1346 | 8 | Each |
| 1327 | 1327 | SS Full size Wire Basket Modular | item1347 | 80 | Each |
| 1328 | 1328 | SS Half size Wire Basket Modular | item1348 | 80 | Each |
| 1329 | 1329 | Sterilizer 1 door with Steam Generator 160 Liters | item1349 | 4 | Each |
| 1330 | 1330 | Washer Disinfector | item1350 | 2 | Each |
| 1331 | 1331 | Automatic Ultra sonic\nCleaner -45L | item1351 | 2 | Each |
| 1332 | 1332 | HEAT SEALING MACHINE | item1352 | 2 | Each |
| 1333 | 1333 | LAUNDRY (500 Bedded Hospital)\nAs per Technical Specification\nBarrier Washer Extractor, Steam Heated, 50 Kg. Capacity - 2 No's\nDrying Tumbler, Steam Heated, 30 Kg. Capacity - 2 No's\nBarrier Washer Extractor, Steam Heated 18 Kg. Capacity - 1 No\nDrying Tumbler, Steam Heated, 15 Kg. Capacity - 1 No\n\"Flat Work Ironer (Roller Heated) (Single Roller) Size : Dia 800 x Depth 3000 MM\" - 1 No\n\"Vacuum Ironing Table Size : 1250 x 750 MM\" - 4 No's\n\"General Utility Press, Steam Heated Size of Bed : 350 x 1190 MM\"- 1 No.\nMobile Table, Size : 10'x2.5' - 2 No's\nMobile Table, Size : 4'x2.5' - 1 No's\nDry Linen Trolley-Cage Type, 50 Kg. Capacity - 4 No's\nWet Linen Trolley- Box Type, 50 Kg. Capacity - 4 No's\nScrubbing Station (Double Sink) - 1 No\nShelf Trolley-Transportation , 100 Kg. Capacity - 4 No's\nDiesel Fired Steam Boiler, 1000 Kg. Capacity - 1 No.\nAir Compressor 5 HP Capacity - 1 No.\n | item1353 | 1 | Job |
| 1334 | 1334 | LAUNDRY (800 Bedded Hospital)\nAs per Technical Specification\nBarrier Washer Extractor, Steam Heated, 50 Kg. Capacity - 3 No's\nBarrier Washer Extractor, Steam Heated, 28 Kg. Capacity - 1 No.\nDrying Tumbler, Steam Heated, 60 Kg. Capacity - 1 No.\nDrying Tumbler, Steam Heated, 30 Kg. Capacity - 2 No's\nBarrier Washer Extractor, Steam Heated 18 Kg. Capacity - 1 No\nDrying Tumbler, Steam Heated, 15 Kg. Capacity - 1 No\n\"Flat Work Ironer (Roller Heated) (Double Roller) Size : Dia 800 x Depth 3000 MM\" - 1 No\n\"Vacuum Ironing Table Size : 1250 x 750 MM\" - 6 No's\n\"Flat Bed Press, Steam Heated Size of Bed : 750 x 1500 MM\"- 1 No.\n\"General Utility Press, Steam Heated Size of Bed : 350 x 1190 MM\"- 1 No.\nMobile Table, Size : 10'x2.5' - 2 No's\nMobile Table, Size : 4'x2.5' - 2 No's\nDry Linen Trolley-Cage Type, 50 Kg. Capacity - 6 No's\nWet Linen Trolley- Box Type, 50 Kg. Capacity - 6 No's\nScrubbing Station (Double Sink) - 1 No\nShelf Trolley-Transportation , 100 Kg. Capacity - 5 No's\nDiesel Fired Steam Boiler, 1000 Kg. Capacity - 1 No.\nAir Compressor 5 HP Capacity - 1 No.\n | item1354 | 1 | Job |
| 1335 | 1335 | MILK BOILER -Cap.100Ltrs.\nS.S.Sheet insulated body with triple jacket. The water jacket will be fitted with 2 Kw heating element. Milk outlet, water level indicator & draw off valve at the bottom & water tank. element, Elcon thermostat, GVC rotary switch, LED indicator for Power, 4mm thickness 3 core wire\nS.S.Sheet insulated body with triple jacket. The water jacket will be fitted with 2 Kw heating element. Milk outlet, water level indicator & draw off valve at the bottom & water tank. element, Elcon thermostat, GVC rotary switch, LED indicator for Power, 4mm thickness 3 core wire | item1355 | 2 | No. |
| 1336 | 1336 | TEA BOILER - Cap.100Ltrs.\nS.S.Sheet insulated body with triple jacket. The water jacket will be fitted with 2 Kw heating element. Milk outlet, water level indicator & draw off valve at the bottom & water tank. element, Elcon thermostat, GVC rotary switch, LED indicator for Power, 4mm thickness 3 core wire | item1356 | 2 | No. |
| 1337 | 1337 | MICROWAVE OVEN - Cap.20-30Ltrs.\n | item1357 | 2 | No. |
| 1338 | 1338 | PICK UP COUNTER WITH OVERSHELF - Size 1800X600X850+300\nTop 3 sides, under & over shelf of s.s.sheet, on m.s.angle & s.s.tubular legs frame work. The counter will have 3 sides fully covered, operator side open. With one under shelf. One over shelf 300mm wide & running along the full length of counter u type heating element of 1 Kw is placed under the one head shelf to keep the dishes warm provided with toggle switch also connected with 4 mm 3 core wire. | item1358 | 4 | Nos. |
| 1339 | 1339 | WORK TABLE FOR SUPPORT OF TWO BURNER RANGE - Size 1350x600x850mm\nTop & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs, with adjustable feet. Top to have sound deadning material lining as required. | item1359 | 2 | No. |
| 1340 | 1340 | TWO BURNER COOKING RANGE - App. Size 1200X600X850mm\nFrame work of m.s.anlge duly painted, mounted on s.steel tubular legs with adjustable feet. Top & sides & under shelf of s.s.sheet. The range will be complete with 2nos. Hy-pressure gas burners with individual control valves. Cast iron pan support | item1360 | 2 | No. |
| 1341 | 1341 | For Comunity Kitchen\nTWO BURNER COOKING RANGE - App. Size 1200X600X850mm\nFrame work of m.s.anlge duly painted, mounted on s.steel tubular legs with adjustable feet. Top & sides & under shelf of s.s.sheet. The range will be complete with 2nos. Hy-pressure gas burners with individual control valves. Cast iron pan support | item1361 | 6 | No. |
| 1342 | 1342 | EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) FOR TWO BURNER RANGE - Size 1950x750x600mm\nMade of s.steel sheet, 20G thick duly welded & pop rivetted as required. The hood will be complete with s.s.sheet removable type baffle filters. Complete with greese collection channel & greese collection cup/s. | item1362 | 2 | No. |
| 1343 | 1343 | JUICER (table top model)\nCast Aluminum/CI body, duly polished / painted, with worm & perforated insert. Top feeding tray. Worm easily cleanable fitted with 1/2HP elect. motor. | item1363 | 2 | No. |
| 1344 | 1344 | CONVEYOR TOASTER - App. Cap. 100-125 Toasts/hr.\nS.S.Sheet body, having s.s.sheet conveyor belt. App.225mm wide. The unit will have heating elements on top & lower portion of conveyor belt with variable heat & speed control switch. (MADE IN ITALY) | item1364 | 2 | No. |
| 1345 | 1345 | WORK TABLE WITH SINK FOR JUICER STATION - Size 1800x750x850+150\nTop & Sink bowl of s.s.sheet, on s.s.anlge & s.s.tubular frame work with cross bracing at lower portion. Sink bowl will be integrally welded with top & grinded smooth. Sink bowl size 450x450x250mm. | item1365 | 2 | No. |
| 1346 | 1346 | WORK TABLE WITH SINK FOR IDLY STEAMER - Size 1950x600x850+150\nTop & Sink bowl of s.s.sheet, on s.s.anlge & s.s.tubular frame work with cross bracing at lower portion. Sink bowl will be integrally welded with top & grinded smooth. Sink bowl size 450x450x250mm. | item1366 | 2 | No. |
| 1347 | 1347 | UNDER COUNTER REFRIGERATOR WITH PICK UP SHELF - Size 1200x600x850+450+300\nDouble walled 'PUF' insulated s.s.sheet outer & inner body of s.s.sheet 0.8mm thick having hinged doors with rubber gascuts. Inside s.s.wire shelves on adjustable channel frame complete with 'Kirloskar/Tecumesh' make compressor. Having condensor, | item1367 | 2 | No. |
| 1348 | 1348 | FOUR DOOR REFRIGERATOR - App. Size 1200x675x2000mm\nDouble walled, insulated 'PUF' body made of 0.8mm thick s.s.sheet. Inside chamber to have 4nos. S.s.wire shelves on adjustable channel. The unit will have 4 doors with magnatic rubber gascuts & locking provision. | item1368 | 4 | Nos. |
| 1349 | 1349 | WORK TABLE - Size 1500X600X850mm\nTop & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs, with adjustable feet. Top to have sound deadning material lining as required. | item1369 | 6 | Nos. |
| 1350 | 1350 | EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) - Size 1950x750x600mm\nMade of s.steel sheet, 20G thick duly welded & pop rivetted as required. The hood will be complete with s.s.sheet removable type baffle filters. Complete with greese collection channel & greese collection cup/s. | item1370 | 2 | No. |
| 1351 | 1351 | DOSA PLATE - O/S 1500X600X850\nFramework made of m.s. angle of size 38x38x5mm and 25x25x5 mm. Top made of 16 mm thick m.s. plate with stainless steel channel for draining the excess oil from fry top. The verticals of the equipment are made of stainless steel of size 38 mm dia and cross | item1371 | 2 | No. |
| 1352 | 1352 | IDLY STEAMER (CAP. - 104 IDLY per batch) - STD MODEL\nMade of stainless steel sheet, fitted with Elect. Controls. | item1372 | 2 | No. |
| 1353 | 1353 | EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) for low height burner - Size 1650x750x600mm\nMade of s.steel sheet, 20G thick duly welded & pop rivetted as required. The hood will be complete with s.s.sheet removable type baffle filters. Complete with greese collection channel & greese collection cup/s. | item1373 | 4 | Nos. |
| 1354 | 1354 | LOW HT. TABLE for supporting low height burner - Size 750x750x600mm\nSpecification same as that of work table but the table will be without undershelf & will have cross bracing support at lower portion. | item1374 | 8 | Nos. |
| 1355 | 1355 | LOW HT. BURNER - Size 750x750x600mm\nSpecification same as that of cooking range but the unit will be without undershelf, but will only have cross bracing support at lower portion. | item1375 | 8 | Nos. |
| 1356 | 1356 | EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) for 03 burner cooking range - Size 1650x750x600mm\nMade of s.steel sheet, 20G thick duly welded & pop rivetted as required. The hood will be complete with s.s.sheet removable type baffle filters. Complete with greese collection channel & greese collection cup/s. | item1376 | 4 | Nos. |
| 1357 | 1357 | THREE BURNER COOKING RANGE - O/S 1800X600X850\nStructure made of m.s. angle of size 38x38x5mm, duly rust proof painted. Top of 16Swg thick s.s.sheet. All four side covered up to height of app. 10” by 20Swg stainless steel sheet. Bottom stainless steel stripes sheets complete with gas burners. | item1377 | 4 | Nos. |
| 1358 | 1358 | WORK TABLE for support of 03 burner cooking range - Size 1500X600X850mm\nTop & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs, with adjustable feet. Top to have sound deadning material lining as required. | item1378 | 2 | No. |
| 1359 | 1359 | EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) for bulk cooker/boiler & fryer - Size 1950x750x600mm\nMade of s.steel sheet, 20G thick duly welded & pop rivetted as required. The hood will be complete with s.s.sheet removable type baffle filters. Complete with greese collection channel & greese collection cup/s. | item1379 | 8 | Nos. |
| 1360 | 1360 | BULK COOKER/boiler TILTING TYPE - Cap.160Ltrs.\nSpecification same as Sno.13 but the frying pan will be Of rectangular shaped with 12”depth & a pouring lip & the unit will be fitted with v type high pressure gas burner with control valve & pilot lamp. | item1380 | 4 | Nos. |
| 1361 | 1361 | BULK FRYER TILTING TYPE - Cap.100Ltrs.\nTriple jacketed body of stainless steel sheet, Inner most jacketed of 16g thick with 12g thick dish ended bottom, second wall for air gap of 18g stainless steel sheet & outer insulation jacket also of 18g stainless steel sheet. The unit will have counter | item1381 | 4 | Nos. |
| 1362 | 1362 | WET GRINDER - Cap.15ltrs (1.0HP)\nStainless steel sheet constd. Body with s.s.sheet constd. Revolving drum, cromium plated pillar support on m.s.angle frame work fitted with electric motor gear box & grinding stones & coconut scraper. | item1382 | 2 | No. |
| 1363 | 1363 | DOUGH KNEADING MACHINE - (CROMPTON MOTOR 2.0 HP) - App. Cap of Bowl 25Ltrs.\nS.S.Mixing bowl, with s.s.rod/strip mixing arm, mounted on steel tubular & sheet frame work duly painted. Complete with 1.0HP Elect. Motor with control switch. | item1383 | 2 | No. |
| 1364 | 1364 | POTATO PEELER - Cap.15Kg./chrgs.(CROMPTON MOTOR 1.0 HP)\n16 gauge Stainless steel sheet peeling drum, lined inside with Abrasive material, stainless steel /cast iron rotating peeling disc. Top of the drum will have a potato inlet door, waste Inlet provision peeled potato discharge door & waste water Outlet pipe | item1384 | 2 | No. |
| 1365 | 1365 | PULVeRISER (Std.) - (CROMPTON MOTOR 1.0 HP)\nStainless steel sheet body,20g thick. the unit will have A top feeding tray & a housing of stainless steel casting With grinding plates & 3 type of meshes for variable type Of grinding requirements. The unit will be fitted with 1.0 hp single Phase electric | item1385 | 2 | No. |
| 1366 | 1366 | WORK TABLE support of pulverisor - Size 1500X600X850mm\nTop & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs, with adjustable feet. Top to have sound deadning material lining as required. | item1386 | 2 | No. |
| 1367 | 1367 | WORK TABLE WITH SINK for vegetable washing -Size 1950x600x850+150\nTop & Sink bowl of s.s.sheet, on s.s.anlge & s.s.tubular frame work with cross bracing at lower portion. Sink bowl will be integrally welded with top & grinded smooth. Sink bowl size 450x450x250mm. | item1387 | 2 | No. |
| 1368 | 1368 | CHOPPING BOARD for manual vegetable cutting - size:- 1200X600X850mm\nFrame work made of s.s.anlge top will have P.P./Nylon Board for chopping 700x700x100mm chopping board. | item1388 | 2 | No. |
| 1369 | 1369 | VEGETABLE CUTTING MACHINE\nAluminium casted body with ½ hp electric motor safety switch & double feed pusher for round flat & vertical shaped food items etc., the unit will be Table top model with easy to clean provision. Provided with 4 no cutting discs for slicing grating Dicing | item1389 | 2 | No. |
| 1370 | 1370 | CHAPPATI COLLECTION TABLE - Size 1500X600X800\nTop tray of 16G s.s.sheet, tray will have App.100mm ht. collor all around, mounted on s.s.tubular legs with adjustable feet & one s.s.sheet undershelf. | item1390 | 2 | No. |
| 1371 | 1371 | CHAPPATI ROLLING TABLE - Size 2100x750x850mm\nTop & undershelf of s.s.sheet on m.s.anlge frame work & s.s.tubular legs, with adjustable feet. Top to have sound deadning material lining as required. THREE SIDE CROSS BRACING MADE OF S.S. PIPE 1\" DIA FOR UNDERNEATH STORAGE. | item1391 | 4 | Nos. |
| 1372 | 1372 | CHAPPATI PLATE CUM PUFFER - Size 1800x750x850mm\nFrame work of m.s.anlge, mounted on s.s.tubular legs frame work. All sides pannels & undershelf of s.s.sheet, top plate 10mm thick mild steel with cast iron puffing grills for puffing of chappaties. Complete with 'V' shape LPG burners with individual cont | item1392 | 4 | Nos. |
| 1373 | 1373 | EXHAUST HOOD (Without Ducting, Fixing & Extraction fan) for chapatti plate - Size 1950x750x600mm\nMade of s.steel sheet, 20G thick duly welded & pop rivetted as required. The hood will be complete with s.s.sheet removable type baffle filters. Complete with greese collection channel & greese collection cup/s. | item1393 | 4 | Nos. |
| 1374 | 1374 | FOOD TROLLEY WITH 4 ROUND PANS, 1 RICE TRAY & STORAGE beneath - O/S 1350X750X900mm\nS.S.Sheet insulated body, Frame work of m.s.anlge of size 38x38x5mm, mounted on 4 castors (2 with brakes) of size 150mm top to have cutout for 4nos. Round pans for Dal, Subzi etc. with 1 rice tray & storage below. Three side covered with s.s.sheet with s. | item1394 | 16 | Nos. |
| 1375 | 1375 | TRAY CARRIER TROLLEY - Size 1200X600X1200mm\nS.S.Bottom base shelf mount at 150mm with all four sides turned down 50mm in 12mm and secured to welded s.s.anlge frame work & PROVIDED WITH THREE NOS. OF DETACHABLE TRAYS CUM SHELFS UNIT WILL BE MOUNTED ON 4\" PILLAR TYPE CASTORS WHEELS (2 NOS. WITH BRAKE & 2 NOS. WITHOUT BRAKE) | item1395 | 4 | Nos. |
| 1376 | 1376 | TRAY SET UP COUNTER WITH BAIN MARIE & DOUBLE OVERSHELVES - Size 1800x600x850+375+225\nTop of 16G s.s.sheet, Bain Marie water tank of 18G s.s.sheet, fitted with 3.0kw heating element with automatic temperature controller. Water outlet provision with drain valve, 3 sides covered with 20G s.s.sheet, Top to accommodate s.s.sheet Food Pans with GN pan 1x2x4\" depth with lid 5 sets. | item1396 | 8 | Nos. |
| 1377 | 1377 | STORAGE CABINET - Size 1200X600X850mm\nTop of 16Swg S.S.Sheet one over shelf, three sides of 20SWG s.s. sheet. Dish storage cabinet with 2 shelves and sliding door will be provided on service side. | item1397 | 4 | Nos. |
| 1378 | 1378 | STORAGE RACK - Size 900X450X1800\nVertical of 32 mm dia stainless steel pipe with adjustable feet 4 no of 18 S.S Sheet at equaly distance. | item1398 | 20 | Nos. |
| 1379 | 1379 | INGREDIENT BINS - Size 600X600X600mm\nMade of S.S. 18 SWG WITH TOP HINGE OPENABLE DOORS SUPPORT WITH FOUR NOS. OF CASTORS, anti crack body, top half hinged lid. Provided with a scoop. | item1399 | 12 | Nos. |
| 1380 | 1380 | DUNNAGE RACK - Size 1200X600X500mm\nMade of s.s.square pipes of size 32x32mm, with support of 25mm square s.s.pipe. | item1400 | 4 | Nos. |
| 1381 | 1381 | DIGITAL WEIGHING SCALE\nCAP. 300KG | item1401 | 2 | No. |
| 1382 | 1382 | POT RACK-3 TIER - Size 1200X600X1500mm\nVerticals of 32mmX32mm square s.s.pipe, 3 shelves welded with vertical frame of 19mm dia s.s.pipe shelves with equal space between two tubes mounted on adjustable feet. | item1402 | 12 | Nos. |
| 1383 | 1383 | SOILED DISH LANDING TABLE WITH GARBAGE CHUTE - Size 2400x600x850mm\nTop of 16G s.s.sheet with 'Sunkun' top. A garbage chute provided on top with a space below to keep dust bin (Not part of equipment). The top will be mounted on m.s.anlge, rust proof painted & s.s.vertical tubular legs with cross bracing support on 3 sides | item1403 | 2 | No. |
| 1384 | 1384 | THREE SINK UNIT - Size 1800x600x850+150mm\nTop & 3 sink bowls of 16G s.s.sheet. Duly welded, grinded & polished smooth mounted on m.s.anlge & s.s.tubular frame work with 150mm back splash. Each Sink Bowl Size 500x500x300mm (without sanitory fittings) | item1404 | 2 | No. |
| 1385 | 1385 | CLEAN DISH TABLE - Size 2100x600x850mm\nSpecification same as that of work table but with 2 undershelves. | item1405 | 2 | No. |
| 1386 | 1386 | CLEAN DISH RACK - Size 900x450x1800mm\nVertical of 32 mm dia stainless steel pipe with adjustable feet 5 no vertical at equal distance 1st shelf fixed at 150mm from floor level. | item1406 | 10 | Nos. |
| 1387 | 1387 | pot stacking platform for heavy pot storage - Size 1500x750x150mm\nS.S Palate frame will be made of 1.5” S.S Square pipe with adjustable bullet feet. And shelf will be made of 2”x3mm S.S Flat Patti. | item1407 | 2 | No. |
| 1388 | 1388 | Masala trolley - Size 600x600x750mm | item1408 | 4 | Nos. |
| 1389 | 1389 | Plateform trolley - Size 900X600X900mm\nStructure will be made of 40x40x5mm duly painted with rust proof paint. Top will be made of 10 SWG. M.S Sheet. 6” high moving wheel (02 Break + 02 Moving) | item1409 | 2 | No. |
| 1390 | 1390 | PRE WASH SINK UNIT - Size 1800x750x850+150\nTop & Sink bowl of s.s.sheet, on s.s.anlge & s.s.tubular frame work with cross bracing at lower portion. Sink bowl will be integrally welded with top & grinded smooth. Sink bowl size 450x450x250mm. | item1410 | 2 | No. |
| 1391 | 1391 | HOOD TYPE COMMERCIAL DISHWASHER\nCap. 40-50 Racks per Hr.\nCYCLE TIME TOTAL/RINSE (SEC) 60-120-180/20\nBASKET SIZE 500X500 MM\nWATER CONSUMPTION 3L/CYCLE\nTANK CAPACITY 20L\nRINSE CAPACITY 12L\nWASH PUMP 1.1KW\nWASH TANK 3KW\nRINSE TANK 8KW\nMAXIMUM USED POWER 9.1\nWATER HARDNESS 70-140 PPM\nWATER PRESSURE 2-4 BAR\nPOWER SUPPLY 400/3+N-/50 | item1411 | 2 | No. |
| 1392 | 1392 | DIRTY DISH UNLOADING TABLE - Size 1500x600x850mm\nTop of stainless steel sheet, mounted on m.s.angle & stainless steel tubular frame work. One 18g thick stainless steel sheet bottom Shelf will be fitted on table at a ht dia 150mm from floor. | item1412 | 2 | No. |
| 1393 | 1393 | CLEAN DISH TABLE - Size 2100x750x850mm\nSpecification same as that of work table but with 2 undershelves. | item1413 | 2 | No. |
| 1394 | 1394 | COLD ROOM SECTION\nWALK IN CHILLER CUM FREEZER\nExternal Room Dimensions : 3600X3000mm\nCHILLER Room Temperature - (+ 2°C to 8 °C)\nProduct Entering Temp - + 30°C\nPull Down Time - 15hrs.\nProduct Loading - App.550kg./24hrs.\nWall & Ceiling Panels Insulation - 80mm thick Prefabricated RPUF Panels\nFloor Panel Insulation - 80mm thick RPUF Panels with layer of Tarfelt sheet on both sides.\nPanel Finish - Internal :PCGI , External: PCGI\nRefrigerant -R-22\nNo. of Units - 1 (MAKE:- KIRLOSKAR/TECUMSEH/CARRIER\nConnected Load - 2.5 KW | item1414 | 2 | No. |
| 1395 | 1395 | ALUMINIUM RACK FOR COLD ROOM - Size 1100X500X1500\nVertical of 50x50x5mm aluminium angle with adjustable feet 4 no of 18 swg. Sheet perforated aluminium shelves.. | item1415 | 10 | Nos. |
| 1396 | 1396 | ALUMINIUM PALLET FOR COLD ROOM STORAGE - Size 1500X450X150MM\nTop made of 16 swg aluminum sheet placed with s.s. angle 35x35x4 frame work with adjustable bullet feet. | item1416 | 2 | No. |
| 1397 | 1397 | L.P.G GAS PIPE LINE (200 RUNNING FEET APPROX)\nACTUAL MEASUREMENT WILL BE ACCORDING TO As per site conditions | item1417 | 400 | Rn/ Ft |
| 1398 | 1398 | CENTRIFUGAL EXHAUST BLOWER - 20000 CFM | item1418 | 2 | No. |
| 1399 | 1399 | S.S GRATING for kitchen drainage trough\n(APPROX 40 RUNNING FEET)\nACTUAL MEASUREMENT WILL BE ACCORDING TO As per site conditions | item1419 | 80 | Rn/ Ft |
| 1400 | 1400 | EXHAUST HOOD DUCTING (APPROX 2000 SQUARE FEET)\nACTUAL MEASUREMENT WILL BE ACCORDING TO As per site conditions | item1420 | 2 | No. |
| 1401 | 1401 | M.S CYLINDER BANK - 120\"X36”X42”\n(ACCESSORIES ARE NOT INCLUDED)\nTotally constructed in MS angle base of 40x40x5 mm supported with 12mm square wrought iron bars. Front doors are provided along with the locking arrangements made up of 18 SWG CR sheet is duly premiered and painted to prevent from rust etc. | item1421 | 2 | Set |
| 1402 | 1402 | SITC of Liquid Oxygen Tank 10 KL as per technical specifications & List of approved make | item1422 | 4 | Each |
| 1403 | 1403 | SITC of Vaporizer for Liquid Oxygen Tank 10 KL as per technical specifications & List of approved make | item1423 | 4 | Each |
| 1404 | 1404 | SIGNAGE\nFOR BUILDINGS\nSupplying & fixing of retro reflective sign plates of required size. The plate made of High intensity prismatic grade type IV retro reflective sheeting of 3M / Avery Denison or equivalent make approved by I.R.C. / M.O.S.T. with message and graphics to be overlay film/High intensity prismatic grade type IV retro reflective sheeting of 3M / Avery Denison or equivalent make approved by I.R.C. / M.O.S.T Reflective tape of same make duly plotter cut, of approved color, letters (single side) in white colour, to be pasted on 3mm thick ACP sheet of make Alstone / Alstrong / Eurobond / Alucobond or equivalent etc. as per drawings. The sign boards shall fixeed on wall/ roof duly fixed with rawls plugs stainless steel srew/ double side tape 3M make/ SS chain of required size of required nos of holes, wherever required complete as per direction of Unit Incharge | item1424 | 21 | SQM |
| 1405 | 1405 | Supply and fixing of 18 gauge Stainless Steel plates with water jet cutting of grade 304 etching (engraved)signage plate of required size and letters duly bordred . Engraved portion painted of as per required colour/ approved colour (DUCO) of approved brand and filling with required matt/ mirror finish polish on base and border with shining polish of required shade and colour and duly fixed with required nos of rawls plugs stainless steel srew/ double side tape of 3M make/ nut bolt/ spacer required nos of holes, wherever required complete as per direction of Unit Incharge. (make Jindal or Equivalent) | item1425 | 2040 | Sq Inch |
| 1406 | 1406 | Supply and fixing of Powder coated Aluminum Panel for directory of size 900mm x 750mm with partition of required Nos supported on aluminum channel 2 nos backiside with ACP sheet .Matter will Be digital print, matter covered with transprent polycarbonate sheet 0.5 mm wherever required completeand duly fixed with required nos of rawls plugs stainless steel srew/ spacer required nos of holes, wherever required complete as per direction of Unit Incharge | item1426 | 21 | Nos. |
| 1407 | 1407 | Supply and fixing of Amuminium Silver powder coated signage of reqired size complete with message. Matter will be digital print written single sides, matter covered with transparent polycarbonate sheet 0.5mm. and duly fixed with required nos of rawls plugs stainless steel srew/ double side tape of 3M make/ screw required nos of holes, wherever required complete as per direction of Unit Incharge | item1428 | 55250 | SQ INCH |
| 1408 | 1408 | Supply and fixing of Amuminium Silver powder coated signage two plates ( vertical type) of reqired size complete with message. Matter will be digital print written both sides, matter covered with transparent polycarbonate sheet 0.5mm. and duly fixed with required nos of rawls plugs stainless steel srew/ double side tape of 3M make/ screw required nos of holes, wherever required complete as per direction of Unit Incharge | item1429 | 21250 | SQ INCH |
| 1409 | 1409 | Providing & fixing of emergency sign boards single side of required size made of Photo luminescent film having glow power of 4 hours with message and graphics to be screen printing / vinyl cut film of 3M / Avery Denison / LG / Oracle or equivalent make to be pasted on 3mm thick Sun Board sheet all complete and duly fixed with required numbers of rawls plugs stainless steel srew/ double side tape of 3M make required nos of holes, wherever required complete as per direction of Unit Incharge | item1430 | 55250 | Sq Inch |
| 1410 | 1410 | Providing & fixing of Glow-in-the-dark tape to mark safe lanes for pedestrians on the floors/ corridors to lead people to exit location. • Clearly visible in a dark room for 4 + hours • UV and chemical resistant • Strong adhesive Clearly designate aisle ways and emergency pathways in the dark condition. The surface should be cleaned thoroughly before sticking the tape with cleaning agents. Size: 4” Arrow size – green color. | item1431 | 3400 | MTR |
| 1411 | 1411 | Supply & Fixing Display notice pinup board of required size, aluminum beeding of 12 mm and fixed with required numbers of rawls plugs stainless steel srew as per direction of Unit Incharge. | item1432 | 1530 | Sq Ft |
| 1412 | 1412 | Supply & Fixing Key ring holder stand of size 900mm x 600mm. Front door covered with transparent acyrlic shhet and locking arrangment. Fixed with required numbers of rawls plugs stainless steel srew as per direction of Unit Incharge. | item1433 | 15 | Each |
| 1413 | 1413 | Supplying and fixing of 18 gauge Stainless Steel Key Rings 1.245 mm thick (18 gauge) Stainless Steel plates of grade 304 etching (engraved)signage plate of Size 50mm x 38mm of and letters duly bordred as per sample approved and all as per sample. Engraved portion painted of as per required colour/ approved colour (DUCO) of approved brand written bth sides and filling with required matt/ mirror finish polish on base and border with shining polish of required shade and colour as per direction of Unit Incharge | item1434 | 850 | Nos. |
| 1414 | 1414 | Supply & placing of Stainless Steel 304 series Dustbin of size 300 x 175 as per direction of Unit Incharge. | item1435 | 153 | Nos. |
| 1415 | 1415 | Supply & placing of Stainless Steel 304 series Dustbin with foot operated of size 356 mm x 584 mm with plastic bucket as per direction of Unit Incharge. | item1436 | 153 | Nos. |
| 1416 | 1416 | Supplying of Q Manager made of hollow stainless steel pipe of 18 gauge and 900 mm high including 1.30 mtr and 50mm width long ribbon etc. all complete as per direction of Unit Incharge. | item1437 | 15 | Nos. |
| 1417 | 1417 | Provinding and fixing transparent logos/ Letters made out of etching tape 3M sparkle type on the lean glass surface with plain water, scraping glass before fixing film with blade, spray soap solution on glass squeeze excess water and air bubbles. All as directed of approved shape and sizes etc fixed with of required size as required as per direction of Unit Incharge. Make 3M/ Avery Denson | item1438 | 323 | Sqm |
| 1418 | 1418 | Supply & Fixing signages for exit of size 375mm x 200mm x 8mm in acrylic sheet LED light with battary backup | item1439 | 153 | Each |
| 1419 | 1419 | Supply & fixing of signboard made out of 3mm thick sun board with face fully covered with digital print of approved shade and make. The sign board should be fixing on wall,fixed with four rawls plugs stainless steel srew/ double side tape of 3M make required nos of holes, wherever required complete as per direction of Unit Incharge. | item1440 | 850 | Sq Ft |
| 1420 | 1420 | FOR EXTERNAL\nSupplying & fixing of retro reflective sign plates of required size. The plate made of High intensity prismatic grade type IV retro reflective sheeting of 3M / Avery Denison or equivalent make approved by I.R.C. / M.O.S.T. with message and graphics to be overlay film/High intensity prismatic grade type IV retro reflective sheeting of 3M / Avery Denison or equivalent make approved by I.R.C. / M.O.S.T Reflective tape of same make duly plotter cut, of approved color, letters (single side) in white colour, to be pasted on 3mm thick ACP sheet of make Alstone / Alstrong / Eurobond / Alucobond or equivalent etc. as per drawings. The sign boards shall fixeed on wall/ roof duly fixed with rawls plugs stainless steel srew/ double side tape 3M make/ SS chain of required size of required nos of holes, wherever required complete as per direction of Unit Incharge | item1441 | 85 | SQM |
| 1421 | 1421 | Supply and fixing of 18 gauge Stainless Steel plates with water jet cutting of grade 304 etching (engraved)signage plate of required size and letters duly bordred . Engraved portion painted of as per required colour/ approved colour (DUCO) of approved brand and filling with required matt/ mirror finish polish on base and border with shining polish of required shade and colour and duly fixed with required nos of rawls plugs stainless steel srew/ double side tape of 3M make/ nut bolt/ spacer required nos of holes, wherever required complete as per direction of Unit Incharge. (make Jindal or Equivalent) | item1442 | 34000 | Sq Inch |
| 1422 | 1422 | Supply and fixing of Powder coated Aluminum Panel for directory of size 900mm x 750mm with partition of required Nos supported on aluminum channel 2 nos backiside with ACP sheet .Matter will Be digital print, matter covered with transprent polycarbonate sheet 0.5 mm wherever required completeand duly fixed with required nos of rawls plugs stainless steel srew/ spacer required nos of holes, wherever required complete as per direction of Unit Incharge | item1443 | 68 | Nos. |
| 1423 | 1423 | Supply and fixing of Amuminium Silver powder coated signage of reqired size complete with message. Matter will be digital print written single sides, matter covered with transparent polycarbonate sheet 0.5mm. and duly fixed with required nos of rawls plugs stainless steel srew/ double side tape of 3M make/ screw required nos of holes, wherever required complete as per direction of Unit Incharge | item1444 | 102000 | SQ INCH |
| 1424 | 1424 | Supply and fixing of Amuminium Silver powder coated signage two plates ( vertical type) of reqired size complete with message. Matter will be digital print written both sides, matter covered with transparent polycarbonate sheet 0.5mm. and duly fixed with required nos of rawls plugs stainless steel srew/ double side tape of 3M make/ screw required nos of holes, wherever required complete as per direction of Unit Incharge | item1445 | 34000 | SQ INCH |
| 1425 | 1425 | Providing & fixing of emergency sign boards single side of required size made of Photo luminescent film having glow power of 4 hours with message and graphics to be screen printing / vinyl cut film of 3M / Avery Denison / LG / Oracle or equivalent make to be pasted on 3mm thick Sun Board sheet all complete and duly fixed with required numbers of rawls plugs stainless steel srew/ double side tape of 3M make required nos of holes, wherever required complete as per direction of Unit Incharge | item1446 | 102000 | Sq Inch |
| 1426 | 1426 | Providing & fixing of Glow-in-the-dark tape to mark safe lanes for pedestrians on the floors/ corridors to lead people to exit location. • Clearly visible in a dark room for 4 + hours • UV and chemical resistant • Strong adhesive Clearly designate aisle ways and emergency pathways in the dark condition. The surface should be cleaned thoroughly before sticking the tape with cleaning agents. Size: 4” Arrow size – green color. | item1447 | 2975 | MTR |
| 1427 | 1427 | Supply & Fixing Display notice pinup board of required size, aluminum beeding of 12 mm and fixed with required numbers of rawls plugs stainless steel srew as per direction of Unit Incharge. | item1448 | 850 | Sq Ft |
| 1428 | 1428 | Supply & Fixing Key ring holder stand of size 900mm x 600mm. Front door covered with transparent acyrlic shhet and locking arrangment. Fixed with required numbers of rawls plugs stainless steel srew as per direction of Unit Incharge. | item1449 | 15 | Each |
| 1429 | 1429 | Supplying and fixing of 18 gauge Stainless Steel Key Rings 1.245 mm thick (18 gauge) Stainless Steel plates of grade 304 etching (engraved)signage plate of Size 50mm x 38mm of and letters duly bordred as per sample approved and all as per sample. Engraved portion painted of as per required colour/ approved colour (DUCO) of approved brand written bth sides and filling with required matt/ mirror finish polish on base and border with shining polish of required shade and colour as per direction of Unit Incharge | item1450 | 680 | Nos. |
| 1430 | 1430 | Supply & placing of Stainless Steel 304 series Dustbin of size 300 x 175 as per direction of Unit Incharge. | item1451 | 213 | Nos. |
| 1431 | 1431 | Supply & placing of Stainless Steel 304 series Dustbin with foot operated of size 356 mm x 584 mm with plastic bucket as per direction of Unit Incharge. | item1452 | 51 | Nos. |
| 1432 | 1432 | Supplying of Q Manager made of hollow stainless steel pipe of 18 gauge and 900 mm high including 1.30 mtr and 50mm width long ribbon etc. all complete as per direction of Unit Incharge. | item1453 | 21 | Nos. |
| 1433 | 1433 | Provinding and fixing transparent logos/ Letters made out of etching tape 3M sparkle type on the lean glass surface with plain water, scraping glass before fixing film with blade, spray soap solution on glass squeeze excess water and air bubbles. All as directed of approved shape and sizes etc fixed with of required size as required as per direction of Unit Incharge. Make 3M/ Avery Denson | item1454 | 298 | Sqm |
| 1434 | 1434 | Supply & Fixing signages for exit of size 375mm x 200mm x 8mm in acrylic sheet LED light with battary backup | item1455 | 102 | Each |
| 1435 | 1435 | Supply & fixing of signboard made out of 3mm thick sun board with face fully covered with digital print of approved shade and make. The sign board should be fixing on wall,fixed with four rawls plugs stainless steel srew/ double side tape of 3M make required nos of holes, wherever required complete as per direction of Unit Incharge. | item1456 | 1020 | Sq Ft |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy