Military Engineer Services-MES has published Manning & Operation Of Ac Plants, Dg Set, Pump Sets, Swimming Pool, Maintenance Of Ac Plants & Cooling Appliance And Repair/ Replacement Of Fire Fighting & Fire Alarm System At Mo (Mb) Ghatkopar And Nchc Powai Under Ge (Nw) Bhandup. Submission Date for this Tender is 26-11-2020. Fire Alarm Systems Tenders in GHATKOPAR AND POWAI Maharashtra. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 23-Nov-2020 | DATE CORRIGENDUM 2 | Date | 26-11-2020 |
2 | 26-Nov-2020 | OTHER AMDT | Other | 26-11-2020 |
Name of Work: MANNING & OPERATION OF AC PLANTS, DG SET, PUMP SETS, SWIMMING POOL, MAINTENANCE OF AC PLANTS & COOLING APPLIANCE AND REPAIR/ REPLACEMENT OF FIRE FIGHTING & FIRE ALARM SYSTEM AT MO (MB) GHATKOPAR AND NCHC POWAI UNDER GE (NW) BHANDUP | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | SECTION-I MAINTENANCE AND OPERATION OF E/M INSTALLATIONS | |||
2 | 2 | Manning and Operation of the following items in three shifts per day (each shift 08 hrs continuous duration) operated by one operator in each shift including periodical maintenance/repairs (daily check and cleaning, monthly, quarterly, half yearly maintenance) with all consumables parts (except for major assembly/items/jobs as mentioned) of Central AC plant\n (a) Central AC plant of capacity 3 x 40 ton (DX system) comprising of compressors, motor, condensers, Chillers, AHU, refrigerant, piping, controls, pumps, water supply pipes and controls cooling towers, eletrical panels, instruments starters, strip heaters and repairs/replacement of control cabling/wiring including for the smooth and effiecient of AC plant to achieve desired inside conditions through out the given period. (Location SSK 47 MO MB Ghatkopar)\n (i) First Shift - 0600 hrs to 1400hrs\n (ii) Second Shift - 1400 hrs to 2200 hrs\n (iii) Third Shift - 2200 hrs to 0600 hrs | |||
3 | 2.01 | Basic Rate (Wage) payable to the operators | 1005 | Per Shift | |
4 | 2.02 | Contribution towards EPF | 1005 | Per Shift | |
5 | 2.03 | Contribution towards ESIC | 1005 | Per Shift | |
6 | 2.04 | Contribution towards Bonus | 1005 | Per Shift | |
7 | 2.05 | Over Head and Profit on Srl item No. 2.01 to 2.04 | 1005 | Per Shift | |
8 | 2.06 | Labour Welfare Cess payable on Srl item No 2.01 to 2.05 | 1005 | Per Shift | |
9 | 3 | Notes for Srl No. 2.01 to 2.06 :-\n(a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment.\n(b) The rates quoted shall be inclusive of all taxes, cess, levies as applicable including GST.\n(c) At the time of financial evaluation if quoted rate against Srl No. 2.01, 2.02, 2.03, 2.04, 2.05 and 2.06 which corresponds to/works out to lower than the corresponding prevailing minimum rates of wages/subscription/contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/wage/contribution shall be as applicable on bid submission end date. | |||
10 | 4 | Manning and operating of central AC plant of capacity 3 x 50 ton (2 x 50 TR in running and 1 x 50 TR in standby) in three shifts/day (including Sundays and holidays) per day each shift of 8 hrs operated by one operator in each shift of central AC plant comprising of compressors, motors, condensors, chillers, AHU, refrigerant, piping, controls, pumps, water supply pipes and controls cooling towers, eletrical panels, instruments starters, strip heaters complete all as specified and directed. Make: Voltas, Location Heavy Lift Shed (Vikramaditya) at MO (MB) Ghatkopar)\n(i) First Shift - 0600 hrs to 1400hrs\n(ii) Second Shift - 1400 hrs to 2200 hrs\n(iii) Third Shift - 2200 hrs to 0600 hrs | |||
11 | 4.01 | Basic Rate (Wage) payable to the operators | 1005 | Per Shift | |
12 | 4.02 | Contribution towards EPF | 1005 | Per Shift | |
13 | 4.03 | Contribution towards ESIC | 1005 | Per Shift | |
14 | 4.04 | Contribution towards Bonus | 1005 | Per Shift | |
15 | 4.05 | Over Head and Profit on Srl item No. 4.01 to 4.04 | 1005 | Per Shift | |
16 | 4.06 | Labour Welfare Cess payable on Srl item No 4.01 to 4.05 | 1005 | Per Shift | |
17 | 5 | Notes for Srl No. 4.01 to 4.06 :-\n(a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment.\n(b) The rates quoted shall be inclusive of all taxes, cess, levies as applicable including GST.\n(c) At the time of financial evaluation if quoted rate against Srl No. 4.01, 4.02, 4.03, 4.04, 4.05 and 4.06 which corresponds to/works out to lower than the corresponding prevailing minimum rates of wages/subscription/contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/wage/contribution shall be as applicable on bid submission end date. | |||
18 | 6 | Manning and operating of central type water cooled chiller type/DX AC plant of capacity 3 x 26 ton (2 x 26 TR in running and 1 x 26 TR in standby) in One shifts/day (including sundays/Holidays) each shift of 8 hrs operated by one operator from 0900 hrs to 0500 hrs each shift of central AC plant comprising of compressors, motors, condensors, chillers, AHU, refrigerant, piping, controls, pumps, water supply pipes and controls cooling towers, eletrical panels, instruments starters, strip heaters complete all as specified and directed. Make: Blue star, NS-26 at MO (MB) Ghatkopar)\n(i) Shift - 0900 hrs to 1700hrs\n | |||
19 | 6.01 | Basic Rate (Wage) payable to the operators | 335 | Per Shift | |
20 | 6.02 | Contribution towards EPF | 335 | Per Shift | |
21 | 6.03 | Contribution towards ESIC | 335 | Per Shift | |
22 | 6.04 | Contribution towards Bonus | 335 | Per Shift | |
23 | 6.05 | Over Head and Profit on Srl item No. 6.01 to 6.04 | 335 | Per Shift | |
24 | 6.06 | Labour Welfare Cess payable on Srl item No 6.01 to 6.05 | 335 | Per Shift | |
25 | 7 | Notes for Srl No. 6.01 to 6.06 :-\n(a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment.\n(b) The rates quoted shall be inclusive of all taxes, cess, levies as applicable including GST.\n(c) At the time of financial evaluation if quoted rate against Srl No. 6.01, 6.02, 6.03, 6.04, 6.05 and 6.06 which corresponds to/works out to lower than the corresponding prevailing minimum rates of wages/subscription/contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/wage/contribution shall be as applicable on bid submission end date. | |||
26 | 8 | Manning and operating of package type AC plant of capacity 3 x 11 ton (2 x 11TR in running and 1 x 11 TR in standby) in One shifts/day (including sundays/Holidays) each shift of 8 hrs operated by one operator from 0900 hrs to 0500 hrs each shift of central AC plant comprising of compressors, motors, condensors, chillers, AHU, refrigerant, piping, controls, pumps, water supply pipes and controls cooling towers, eletrical panels, instruments starters, strip heaters complete all as specified and directed. Make: Voltas, Location :SPDC-08\n(i) Shift - 0900 hrs to 1700hrs\n | |||
27 | 8.01 | Basic Rate (Wage) payable to the operators | 335 | Per Shift | |
28 | 8.02 | Contribution towards EPF | 335 | Per Shift | |
29 | 8.03 | Contribution towards ESIC | 335 | Per Shift | |
30 | 8.04 | Contribution towards Bonus | 335 | Per Shift | |
31 | 8.05 | Over Head and Profit on Srl item No. 8.01 to 8.04 | 335 | Per Shift | |
32 | 8.06 | Labour Welfare Cess payable on Srl item No 8.01 to 8.05 | 335 | Per Shift | |
33 | 9 | Notes for Srl No. 8.01 to 8.06 :-\n(a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment.\n(b) The rates quoted shall be inclusive of all taxes, cess, levies as applicable including GST.\n(c) At the time of financial evaluation if quoted rate against Srl No. 8.01, 8.02, 8.03, 8.04, 8.05 and 8.06 which corresponds to/works out to lower than the corresponding prevailing minimum rates of wages/subscription/contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/wage/contribution shall be as applicable on bid submission end date. | |||
34 | 10 | Manning, operation and routine maintenance of swimming pool and its pump sets alongwith electrical panel board and chloronomes plant including their periodical maintenance and repairs (excluding major assy/items/jobs as mentioned) all as specified in one shifts of 8 hours consisting of the following:-\n(a) Vertical type pressure filteration plant capacity 3500 Ltrs / hour with 1/2"thick nozzle, inlet, out let complete with filter media, GI Pipe sluice valve etc complete.\n(b) Pumping set monoblock centrifugal 5HP induction motor electric driven for pressure filter -2 Nos.\n(c ) Suction sweepr trolley mounted 2ft wide complete with centrifugal pump driven by electric motor 2HP 415V 50 cycles supply with DOL starter etc complete-2 Nos. \n(d) Water Softener - 01 No.\n(e) Alum dosing tank FRP material 8 gallons capacity with manual mixing arrangement inlet and outlet connection etc complete - 1 No\n(f) Air compressor 125 Cubic ft air per minute driven by 5HP induction electric motor 3 ph, 415 Volts 50Hz incl DOL starter etc complete - 1 No.\n(g) LT panel board suitable for 3 phase 415 Volts AC supply wall mounted and 100 Amps MCCB incoming LOCATION :MO (MB) GHATKOPAR. | |||
35 | 10.01 | Basic Rate (Wage) payable to the operators | 335 | Per Shift | |
36 | 10.02 | Contribution towards EPF | 335 | Per Shift | |
37 | 10.03 | Contribution towards ESIC | 335 | Per Shift | |
38 | 10.04 | Contribution towards Bonus | 335 | Per Shift | |
39 | 10.05 | Over Head and Profit on Srl item No. 10.01 to 10.04 | 335 | Per Shift | |
40 | 10.06 | Labour Welfare Cess payable on Srl item No 10.01 to 10.05 | 335 | Per Shift | |
41 | 11 | Notes for Srl No. 10.01 to 10.06 :-\n(a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment.\n(b) The rates quoted shall be inclusive of all taxes, cess, levies as applicable including GST.\n(c) At the time of financial evaluation if quoted rate against Srl No. 10.01, 10.02, 10.03, 10.04, 10.05 and 10.06 which corresponds to/works out to lower than the corresponding prevailing minimum rates of wages/subscription/contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/wage/contribution shall be as applicable on bid submission end date. | |||
42 | 12 | Manning and Operation of DG Set in two shifts per day (each shift 08 hrs continuous duration) operated by one operator in each shift including periodical maintenance/repairs (daily check and cleaning, monthly, quarterly, half yearly maintenance) with all consumables parts (except for major assembly/items/jobs as mentioned) of DG Set - Engine Make :- Kirloskar Cummins Make Greaves \nMake of alternator : Stamford, Capacity : 400KW/500KVA \nStaff employed : FGM - 01 No \nLocation :NS 09 MO MB Ghatkopar \n(i) Frist Shift - 0600 hrs to 1400hrs \n(ii) Second Shift - 1400 hrs to 2200 hrs\n | |||
43 | 12.01 | Basic Rate (Wage) payable to the operators | 870 | Per Shift | |
44 | 12.02 | Contribution towards EPF | 870 | Per Shift | |
45 | 12.03 | Contribution towards ESIC | 870 | Per Shift | |
46 | 12.04 | Contribution towards Bonus | 870 | Per Shift | |
47 | 12.05 | Over Head and Profit on Srl item No. 12.01 to 12.04 | 870 | Per Shift | |
48 | 12.06 | Labour Welfare Cess payable on Srl item No 12.01 to 12.05 | 870 | Per Shift | |
49 | 13 | Notes for Srl No. 12.01 to 12.06 :-\n(a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment.\n(b) The rates quoted shall be inclusive of all taxes, cess, levies as applicable including GST.\n(c) At the time of financial evaluation if quoted rate against Srl No. 12.01, 12.02, 12.03, 12.04, 12.05 and 12.06 which corresponds to/works out to lower than the corresponding prevailing minimum rates of wages/subscription/contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/wage/contribution shall be as applicable on bid submission end date. | |||
50 | 14 | Manning and Operation of the following items in three shifts per day (each shift 08 hrs continuous duration) operated by one operator and helper in each shift including periodical maintenance/repairs (daily check and cleaning, monthly, quarterly, half yearly maintenance) with all consumables parts (except for major assembly/items/jobs as mentioned) of Pump sets.\n(a) (i) Pumping set mono block 5 HP - 02 Nos. (ii) Sewage Pump 10 HP - 01 Nos. (iii) Electric LT panel \nLocation - New Management Complex at NSD Ghatkopar.\n(b) Fire Pump House Vikramaditya store House :\n(i) Fire Main Pump Set 75 HP three phase 415 V, Make :- Kirloskar -01 No\n(ii) Fire pump set 72 HP Diesel engine operated, Make :- Kirloskar -01 No\n(iii) Fire jockey pump set 7.5 HP , Make :- Kirloskar -01 No\n(iv) Fire priming/booster pump set 7.5 HP , Make :- Kirloskar -02 Nos\n(v) LT controll pannel and water pressure switch \nStaff employed : FGM - 01 No, Helper -01 No.\n(i) First Shift - 0600 hrs to 1400hrs\n(ii) Second Shift - 1400 hrs to 2200 hrs\n(iii) Third Shift - 2200 hrs to 0600 hrs | |||
51 | 14.01 | Basic Rate (Wage) payable to the operators | 1005 | Per Shift | |
52 | 14.02 | Contribution towards EPF | 1005 | Per Shift | |
53 | 14.03 | Contribution towards ESIC | 1005 | Per Shift | |
54 | 14.04 | Contribution towards Bonus | 1005 | Per Shift | |
55 | 14.05 | Over Head and Profit on Srl item No. 14.01 to 14.04 | 1005 | Per Shift | |
56 | 14.06 | Labour Welfare Cess payable on Srl item No 14.01 to 14.05 | 1005 | Per Shift | |
57 | 15 | Notes for Srl No. 14.01 to 14.06 :-\n(a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment.\n(b) The rates quoted shall be inclusive of all taxes, cess, levies as applicable including GST.\n(c) At the time of financial evaluation if quoted rate against Srl No. 14.01, 14.02, 14.03, 14.04, 14.05 and 14.06 which corresponds to/works out to lower than the corresponding prevailing minimum rates of wages/subscription/contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/wage/contribution shall be as applicable on bid submission end date. | |||
58 | 16 | Manning and Operation of the following items in three shifts per day (each shift 08 hrs continuous duration) operated by one operator and helper in each shift including periodical maintenance/repairs (daily check and cleaning, monthly, quarterly, half yearly maintenance) with all consumables parts (except for major assembly/items/jobs as mentioned) of Pump sets.\n(a) (i) Pumping set mono block 25 HP - 02 Nos. (ii) Electric LT panel \nLocation - Main pump House at NSD Ghatkopar.\n(i) First Shift - 0600 hrs to 1400hrs\n(ii) Second Shift - 1400 hrs to 2200 hrs\n(iii) Third Shift - 2200 hrs to 0600 hrs | |||
59 | 16.01 | Basic Rate (Wage) payable to the operators | 1005 | Per Shift | |
60 | 16.02 | Contribution towards EPF | 1005 | Per Shift | |
61 | 16.03 | Contribution towards ESIC | 1005 | Per Shift | |
62 | 16.04 | Contribution towards Bonus | 1005 | Per Shift | |
63 | 16.05 | Over Head and Profit on Srl item No. 16.01 to 16.04 | 1005 | Per Shift | |
64 | 16.06 | Labour Welfare Cess payable on Srl item No 16.01 to 16.05 | 1005 | Per Shift | |
65 | 17 | Notes for Srl No. 16.01 to 16.06 :-\n(a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment.\n(b) The rates quoted shall be inclusive of all taxes, cess, levies as applicable including GST.\n(c) At the time of financial evaluation if quoted rate against Srl No. 16.01, 16.02, 16.03, 16.04, 16.05 and 16.06 which corresponds to/works out to lower than the corresponding prevailing minimum rates of wages/subscription/contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/wage/contribution shall be as applicable on bid submission end date. | |||
66 | 18 | SECTION-II COMPREHENSIVE REPAIR / MAINTENANCE | |||
67 | 19 | M&L for three pole contractor with 2 NO + 2NC Auxilary contacts for AC circuits type ML-2 standard coil voltage 415/440 volts complete all as specified and directed. Make: L&T/Siemens/ABB | 1 | Each | |
68 | 20 | All as per srl item No 19 here in before but ML 1.5 complete all as specified and directed. Make: L&T/Siemens/ABB | 1 | Each | |
69 | 21 | Supply only bimetal overload relay type ML range 20-32A, 415Volts directly operated complete all as specified and directed. Make: L&T/Siemens/ABB | 1 | Each | |
70 | 22 | Supply and fixing shaft seal assembly with complete accessories for SMC 4-65 to SMC-8-65 complete all as specified and directed. Make ACCEL or equivalent as approved by GE | 1 | Each | |
71 | 23 | Taking down existing supply and return air diffusers of any sizes cleaning with blowers and water painting with two coats of synthetic enamel paint and refixing in positions complete all as specified and directed. | 4 | Each | |
72 | 24 | M&L for replacement of old safety valves of 1/2" 300 PSI operating pressure complete all as specified and directed. Make Brasomatic or equivalent as approved by GE | 1 | Each | |
73 | 25 | Supply only pressure gauge 0 to 300 LBS/SQ inch complete all as specified and directed. Make Feibig/Adarsh | 1 | Each | |
74 | 26 | Supply only bimetal overload relay type ML 1.5 range 10-15A, 415Volts directly operated complete all as specified and directed. Make: L&T/Siemens/ABB | 1 | Each | |
75 | 27 | Supply and fixing of gun metal,globe or gate valves,with iron wheel head,screwed both ends for iron pipes of 25 mm dia as specified and directed.Make.Leader ISI marked | 1 | Each | |
76 | 28 | Supply and fixing of gun metal,globe or gate valves,with iron wheel head,screwed both ends for iron pipes of 50 mm dia as specified and directed.Make.Leader ISI marked | 1 | Each | |
77 | 29 | Taking down existing unserviceable cooling tower and supply install testing & commissioning of FRP induced draft cooling Tower of capacity 100TR inducing all accessories like FRP basin PVC fills, Nozzles, PVC water inlet header fan motor fan blade, fan bulb, fan shaft, GI nuts,/ bolts, MS Frame, FRP casing ladder etc. complete all as specified & directed. \nLocation- N.Make : Mihir\nLocation : S.S.K 47 AC PLANT MO Ghatkopar, Make : Mihir & Advance | 1 | Each Job | |
78 | 30 | Taking down AC Plant compressor reciprocating open type Model No. 5H.40/60 Voltas Make by dismantling complete assembly for overhauling including replacement of unserviceable minor spares (rate included) including machining of crank shaft bearing polishing, replacing of gaskets packing reassembly and recharging of pumped down including replacement of major spares parts, refrigerant & topping up if required to maintain the required standing charged pressure of compressor oil complete testing for smooth functioning etc. complete all as specified and directed.\nLocation at S.S K47 -Vikramaditya / Ghatkopar \nNote: Compressor major spare parts, compressor oil and refrigerant for topping up will be paid separately under relevant items supply only. However labour element for replacing these major spares shall be deemed to be included in quoted rates. | 2 | Each Job | |
79 | 31 | Supply only following spares parts for compressor Model-5H-40,Location:SSK-47 Make :-Voltas | |||
80 | 31.01 | Crankshaft 5H60 | 1 | Each | |
81 | 31.02 | Main bearing | 4 | Each | |
82 | 31.03 | Connecting rod bearing half section | 16 | Each | |
83 | 31.04 | Connecting rod | 4 | Each | |
84 | 31.05 | Liner assembly | 6 | Each | |
85 | 31.06 | Piston | 6 | Each | |
86 | 31.07 | Piston Ring | 15 | Each | |
87 | 31.08 | Oil ring | 15 | Each | |
88 | 31.09 | Gudgeon Pin | 10 | Each | |
89 | 31.1 | Oil pump assembly | 2 | Each | |
90 | 31.11 | Suction Reeds | 10 | Each | |
91 | 31.12 | Discharge reeds | 10 | Each | |
92 | 31.13 | Suction valve plate | 4 | Each | |
93 | 31.14 | Discharge valve plate | 4 | Each | |
94 | 31.15 | Oil filter inner | 2 | Each | |
95 | 31.16 | Suction strainer | 2 | Each | |
96 | 31.17 | Loader rocker arm | 8 | Each | |
97 | 31.18 | Loader power elements | 6 | Each | |
98 | 31.19 | Shaft seal assembly | 3 | Each | |
99 | 31.2 | Loader solenoid assembly | 4 | Each | |
100 | 31.21 | Suction service valve | 1 | Each | |
101 | 31.22 | Compressor safety valve | 1 | Each | |
102 | 32 | M & L for disconnecting condensor for descalling & plugging them & providing of 15mm bore tee out let for local circulation of mild acid solution in the condenser (separate container & small pump set to circulate diluted acid solution to be used)PH value of solution shall be 4 and it should be checked frequently i.e every 1hour during the operation Scalgun WS solution to be used for descalling purpose after 2 to 3hours of cleaning if PH value remains less than 7 flush with fresh water added with sodium carbonateTube to be cleaned with nylone brush after closing the end covers circulate diluted acid solution as specified above & PH value toe be maintained as above by flushing the same with fresh water including recharging of stored refrigerant up to required pressure complete as specified & directed for the AC plants following capacity:- | |||
103 | 32.01 | 3 x 30TR Capacity (Location -SSK A7 NSD Ghatkopar ) | 3 | Each Job | |
104 | 32.02 | 3 x 22.5TR Capacity (Location - NS -26 Ghatkopar) | 3 | Each Job | |
105 | 32.03 | 3 x 50 TR Capacity (Location - Vikramaditya Ghatkopar ) | 3 | Each Job | |
106 | 32.04 | 3 x 11 TR capacity ( Location ILMS) | 3 | Each Job | |
107 | 32.05 | 1 x 7.5 TR Capacity (Location - Technical cell Ghatkopar) | 1 | Each Job | |
108 | 33 | Preparation of old painted steel surface of AC Plant including scraping, cleaning and applying two coats of synthetic enamel paint of approved shed & colour over a coat of primer including marking and writing SM & MES No/ letters other details etc. complete all as specified and directed for AC plants of following capacities:- | |||
109 | 33.01 | 3 x 30TR Capacity (Location -SSK A7 NSD Ghatkopar ) | 1 | Each Job | |
110 | 33.02 | 3 x 50TR Capacity (Location - Vikramaditya Ghatkopar ) | 1 | Each Job | |
111 | 34 | Pumping down the existing refrigerant from the condensor and carrying out the leak test of plant with the pressure of Nitrogen gas and monoitoring for 24hrs asses leakages by brazing & replacement of necessary gasket wherever required including copper tubes of suitable size vacumizing of the plant by vaccum pump finally reharging of existing refrigerant gas to the plant and topping up of refrigerant if required to maintain the standard pressure etc complete including testing of the plant for smooth functioning complete all as specified & directed ( Note: Refrigerant required for topping up will be measured and paid separately under relevant items)\nLocation : MO Ghatkopar | 2 | Each | |
112 | 35 | M & L for dismantling cooling tower by removing CT Fans, sprinklers, PVC filler and clean cooling tower body by removing scale , dust, dirt and refix PVC filler by cleaning with diluted HCL solution reassembling, connecting , cleaning external surface and applying two coats of approved synthetic enamel paint including writing SM number/ marking and testing etc. complete all as specified and directed for the following capacity cooling towers. | |||
113 | 35.01 | Cooling tower of 100TR Capacity (Location- Vikramaditya Ghatkopar | 1 | Each Job | |
114 | 35.02 | Cooling tower of 56TR Capacity(Location - NS-26 and NSD Ghatkopar | 1 | Each Job | |
115 | 35.03 | Cooling tower of 80TR Capacity (Location- NS SSK47 NSD Ghatkopar) | 1 | Each Job | |
116 | 36 | S & F in repairs thermostat of central AC plant of range 5 Degree centigrade to 25 Degree centigrade etc. complete with all acessories all as specified and directed | 2 | Each | |
117 | 37 | All as per item No.36 but Sensor type . Make : Voltas | 2 | Each | |
118 | 38 | S & F in repairs pilot solenoid valve from the liquid line suitable for AC Plant of various capacities etc. complete with all accessories all as specified and directed. | 2 | Each | |
119 | 39 | S & F in repairs pressure gauges HP/LP/OP from existing position of following capacities etc. complete with all accessories all as specified and directed. | |||
120 | 39.01 | 0-30 Kg/ cm2 | 2 | Each | |
121 | 39.02 | 0-12.5Kg/ cm2 | 2 | Each | |
122 | 39.03 | 0 to 16kg. | 1 | Each | |
123 | 40 | Removing the unserviceable water pressure gauges from water line & supply and fix new pressure gauge capable to measure pressure upto 7kg/ Sqcm etc. complete with all accessories all as specified and directed. | 5 | Each | |
124 | 41 | All as per item No. 40 above but for pressure upto 10Kg/ Sqcm | 2 | Each | |
125 | 42 | S & F in repairs ball valve of cast steel flange type of size 40mm bore from the liquid line after pumping down the refrigerent and test for leakages etc. complete all as specified and directed. | 2 | Each | |
126 | 43 | M & L for expansion valve of AC plant of capacity 25TR to 50TR including taking down unserviceable valve etc. complete all as specified and directed. | 1 | Each | |
127 | 44 | M & L for replacement of Power contactor type ML-1.5etc. Complete all as specified and directed Make : L & T, Siemens | 2 | Each | |
128 | 45 | M & L for replacement of Power contactor type 3TF46- 2etc. Complete all as specified and directed Make : L & T, Siemens Location :- SSK47 , Vikramaditya MO Ghatkopar | 4 | Each | |
129 | 46 | M & L for replacement of Thermal Timer range GT-100, 9 to 30Sec adjustable type voltage 215/ 450V etc. complete all as specified & directed.( L & T/ Siemens or equivalent) | 2 | Each | |
130 | 47 | All as per item No. 46 above but of range GT-200, 5 to 18Sec etc. complete all as specified & directed (Make: L & T/ Siemens or equivalent) | 1 | Each | |
131 | 48 | Supply and fix in replacement single phase preventor type ES-100etc. Complete all as specified & directed.(Make : L & T/ Minilac or equivalent) | 2 | Each | |
132 | 49 | S & F in replacement of following unserviceable / worn-out 'V' compressor AHU etc. of fenner or equivalent of Dunlop/ Nerlon | |||
133 | 49.01 | "V" Belt (B-76) | 4 | Each | |
134 | 49.02 | "V" Belt (B-68) | 2 | Each | |
135 | 49.03 | "V" Belt (B-108) | 4 | Each | |
136 | 49.04 | "V" Belt (B-85) | 4 | Each | |
137 | 50 | Material & Labour for replacement of unserviceable HP cut out MP 5 etc. complete all as specified & directed. | 2 | Each | |
138 | 51 | All as item No. 50 but Sensor type MO Ghatkopar | 3 | Each | |
139 | 52 | Material & Labour for replacement of unserviceable LP cut out MP 1 etc. complete all as specified & directed. | 3 | Each | |
140 | 53 | All as item No. 52 but Sensor type | 3 | Each | |
141 | 54 | Material & Labour for replacement of unserviceable oil pressure cut out controls for compressor etc. complete all as specified & directed. | 2 | Each | |
142 | 55 | All as per Sr. No. 54 but Sensor type | 2 | Each | |
143 | 56 | Material & Labour for replacement of the defective indicator lamp LED type etc. complete all as specified & directed | 12 | Each | |
144 | 57 | M & L for replacement of following unserviceable / defective existing ampere meter digital type with CT of size 96 x 96mm etc. complete all as specified & directed. | |||
145 | 57.01 | 0 to 50A | 1 | Each | |
146 | 57.02 | 0 to 30A | 1 | Each | |
147 | 57.03 | 0 to 20A | 1 | Each | |
148 | 58 | Pumping down compressor model SMC -4- 65 to make : ACCEL to replace the shaft seal assembly and replace the same with new assembly and recharge the compressor all as specified and directed by Engineer- in -charge | 2 | Each | |
149 | 59 | Removing defective unserviceable coil of loader solenoid valve from the system of compressor of make : ACCEL model SMC -4-65/6-65 Including supplying and fixing new coil of loader suitable to the existing system all as specified and as directed. | 1 | Each | |
150 | 60 | Supply only lubricating oil Freezol-36 or equivalent for top up of compressors of AC plants all as specified and directed | 100 | Ltrs | |
151 | 61 | Supply only refrigerent (R-22) gas for top up etc. complete all as specified and directed | 65 | Kg | |
152 | 62 | All as Item No. 61 but R407C complete all as specified and directed | 25 | Kg | |
153 | 63 | M & L for disconnecting cooling coil section of AHU for descaling & Plugging them & providing 15mm bore tee out let for local circulation of mild acid solution in the condenser (separate container & small pump set to circulate diluted acid solution to be used) PH value of solution shall be 4 and it should be checked frequently i.every 1hour during the operation Scalgun WS solutionto be used for descaling purpose after 2 to 3hours of cleaning if ph value remains less than 7flush with nylon brush after closing the end covers circulate diluted acid solution as specified above & PH value to be maintained as above by flushing the same with fresh water incl recharging of stored refrigerant up to required pressure etc. complete all as specified & directed for the cooling coil section of AHU plants of following capacity:- \nNotes: i) The solution should be warmed up to 35oC by immersion of heater\nii) It should be ensured during the entire process of cleaning the PH value of insulating water shall be 7\niii)Rate quoted against the items deemed to be included solution for decaling, rubber gasket washer, nuts, bolts, etc. as applicable) | |||
154 | 63.01 | AHU of 1 x 22.5TR Capacity (Location- NS-26 Ghatkopar) | 1 | Each Job | |
155 | 63.02 | AHU of 1 x 60TR Capacity (Location- SSK47 Ghatkopar) | 1 | Each Job | |
156 | 63.03 | AHU of 1 x 100TR Capacity (Location- Vikramaditya Ghatkopar) | 1 | Each Job | |
157 | 64 | S & F in repairs unserviceable hermetically sealed compressor reciprocating type 5.5TR working on R-22, 3Phase , 407V including brazing and electric/ piping connection etc. complete all as specified & directed(Location :- Ghatkopar | 1 | Each Job | |
158 | 65 | S & F in repair AHU pre air filter 10 micron 80% efficiency as per exising model size | |||
159 | 65.01 | 600X 608 X 50 mm SSK 47AC PLANT GHATKOPAR | 4 | Each Job | |
160 | 65.02 | 610X 610 X 45 mm Vikramaditiya GHATKOPAR | 4 | Each Job | |
161 | 66 | S & F in unserviceable micro-Processors with display-L-5.5K47-Ghatkopar | 1 | Each Job | |
162 | 67 | S & F in unserviceable MVPP Location: NSD Ghatkopar | 1 | Each Job | |
163 | 68 | S & F in unserviceable liquid line, Drier filter 1/2" size, Make Danfoss Location, Ghatkopar | 2 | Each Job | |
164 | 69 | Material & Labour for replacement of the defective cable, 3core, 2.5Sqmm Location -SSK 47 Ghatkopar | 30 | RM | |
165 | 70 | M & L for replacement of the defective AHU duct canvas2.5feet square Location: NSD Ghatkopar | 3 | Each Job | |
166 | 71 | Pumping down compressor model 5H-40/60 Make :Voltas for replacing the shaft seal assembly and replacing the shaft seal assembly and replacing the same with new assembly and recharging the compressor all as specified and directed . | 2 | Each Job | |
167 | 72 | Annual maintenance of water coolers of bluestar make Model No. SWCSDLX6080UVE installed at Naval Depot Area ghatkopar to check water quality, opreventive and breakdown maintenance, lubrication, , power supply, repair and replacement of filter candles time to time and the water cooler under contract will be serviced for times during the contract time as per standard checklist ,compressor will be checked for its proper functioningAll breakdown calls will be attended to during the contract period,The Blower motor will be checked,the driver set of the blower section wll be inspected but tension adjusted and belts changed,Any defects in the electrical item and control wiring will be attended during contract period.cost of spare parts/consumables required shall be borne as per type of contract and shall be applicable to all activities specified under contract etc complete all as specified and directed. | 26 | Each | |
168 | 73 | Dismantling of existing defective unserviceable compressor of any capacity from window or split AC, Refrigerators, water coolers etc complete all as specified and directed. | 5 | Each | |
169 | 74 | Supply & Fix new hermetically sealed compresor in existing window type AC, 1.5 Ton capacity including initial filling of refrigerant gas to the required pressure, brazing, electric/piping connection etc complete all as specified and directed, Make : Voltas / Shriram/Tecumseh/Kirloskar / Hitachi/LG / Blue Star. | 1 | Each | |
170 | 75 | All as per item No. 74 above but for split type AC 1.5 Ton capacity. | 2 | Each | |
171 | 76 | All as per item No. 74 above but for Refrigerator exceeding165 Ltr and upto 310 Ltr Capacity. | 1 | Each | |
172 | 77 | All as per item No. 74 above but for Water Cooler Blue star make 80 Litres capacity. | 2 | Each | |
173 | 78 | all as per item No. 74 above but for Water Cooler Blue Star Make 80/120 Litres capacity and 60/120 Litres capacity.\nNote : (i) The Contractor shall submit original purchase voucher alongwith manufacturer's test certificate and Guarantee Card etc. (ii) The quoted rates shall also be deeed to include to undertake Guarantee of one year from certified dated of completion by the contractor for free replacement of compressor and/or rectification of the same (including charging of gas) all as directed by the GE in case any defects are noticed (during Guarantee Period of 01 year) due to any reasons whatsoever may be. | 1 | Each | |
174 | 79 | Taking out split type air conditioner (both indoor and outdoor units) of capacity upto 2 TR of any make/type after disconnecting refrigerant pipes, drain pipe and electric connection and removing dust by using blower and cleaning the condenser coils and components by using water and caustic soda, checking and replacing the spares like relay, capacitors, thermostat, fan motor, blades & blower and including servicing, overhauling and connecting of refrigerant pipe,drain pipe and charging of refrigerant and testing including fixing back in its original location complete all as specified and directed. \nNOTE : (i) Spares will be measured and paid separately as supply only. (ii) Refrigerant gas will be measured and paid separately as supply only. | 50 | Each Job | |
175 | 80 | Replacement of fan blades of motor for water cooler upto 80 Ltr capacity including testing etc complete all as specified and directed | 3 | Each Job | |
176 | 81 | Replacement of fan motor of water cooler up to 80 Ltr capacity including testing etc complete all as specified and directed. | 2 | Each Job | |
177 | 82 | Supply only running capacitor of 36 MFD complete all as specified and directed.\n | 15 | Each | |
178 | 83 | Supply only refrigerent (R-22) gas for top up etc. complete all as specified and directed | 15 | Kg | |
179 | 84 | Supply only refrigerent R-407C gas for top up etc complete all as specified and directed | 5 | Kg | |
180 | 85 | Replacement of relay for Water Cooler of Bluestar Make 80 Litre storage capacity, complete all as specified and directed. | 2 | Each | |
181 | 86 | Replacement of relay for Refrigerator 165 to 310 Litre Capacity, complete all as specified and directed. | 1 | Each | |
182 | 87 | Taking out existing unserviceable thermostat switch of water cooler and Supply & fix new thermostat switch for water cooler of any capacity including testing etc complete all as specified and directed. \n(Make:INDOFOSS/RANUTRAL)\n | 2 | Each | |
183 | 88 | Taking out existing unserviceable thermostat switch of refrigerator and supply & fix new thermostat switch for refrigerator of any capacity including testing etc complete all as specified and directed. \n(Make : INDOFOSS/RANUTRAL)\n | 1 | Each | |
184 | 89 | Supply and fix in repairs blower motor capacitor 4 MFD etc complete all as specified and directed. (Make : ASIAN/KEIL/EPCOS)\n | 2 | Each | |
185 | 90 | All as per item No. 89 above but 6 MFD capacitor. (Make: ASIAN/KEIL/ EPCOS) | 3 | Each | |
186 | 91 | Supply only over load protector No 1022 in window type AC upto 2 ton capacity complete all as specified and directed.(Make : USHA/ RANUTRAL)\n | 1 | Each | |
187 | 92 | Taking out existing unserviceable over load relay and supply & fix new over load relay in water cooler upto 80 ltrs capacity etc complete all as specified and directed. | 5 | Each | |
188 | 93 | Taking down carefully split type AC upto 2 Ton capacity & refixing inner & outer unit at new location alongwith existing frame work, bracket, refrigerant tubing, cable, stablizer etc and making good existing surface to match with the adjoining surfaces etc complete all as specified and directed. | 5 | Each | |
189 | 94 | Supply, fixing, clamping and jointing copper tubing in replacement of 3/8" dia for suction line and for liquid discharge line duly insulated with suitable insulation material for split AC including necessary soldering, flaring work, jointing, testing etc, making hole in wall for passing though pipe and making good to the disturbed surface to match with the adjoining surfaces etc complete all as specified and directed. | 20 | RM | |
190 | 95 | Supply & Lay PVC Nylon braided pipe 20 mm bore heavy duty including fittings to drain out condensed water of split AC including cutting of floor / wall & making good after laying of pipe to match the existing surface etc complete all as specified and directed. | 10 | RM | |
191 | 96 | Supply & fix in repair, push cock / lift cock 15mm bore of brass, chromium plated, ISI marked for water cooler of any capacity etc complete all as specified and directed. | 24 | Each | |
192 | 97 | Supply and fix water tray made out of GI sheet 2 mm thick for water cooler any capacity with out let system connection provided with and including PVC nylon braided pipe of 20 mm dia upto 3 mtr length and also connecting to drain pipe etc complete all as specified and directed. | 3 | Each | |
193 | 98 | Removing existing unserviceable electronic circuit control board of split AC unit upto 2 ton capacity and supply and fixing new electronic PCB & display board kit in the indoor unit including testing etc complete all as specified and directed. | 2 | Each Job | |
194 | 99 | Supply and fixing filter media sediment for water cooler complete all as specified and directed. | 25 | Nos | |
195 | 100 | Supply and fixing Carbon filter for water cooler complete all as specified and directed. | 25 | Nos | |
196 | 101 | Supply only remote sensor handset suitable for split AC upto 2.0 ton capacity etc complete all as specified and directed. | 2 | Each | |
197 | 102 | Supply and fix in repair remote sensor plate suitable for split AC upto 2.0 ton capacity etc complete all as specified and directed. | 2 | Each | |
198 | 103 | Supply and fix in repairs multipurpose door lock with duplicate key of water cooler of any make & capacity etc complete all as specified and directed. | 2 | Each | |
199 | 104 | Dismantling of Monoblock pump of under mentioned capacities from connected suction/ delivery pipes and electric connections etc, taking to workshop. overhauling of the same and replacing unserviceable spares/parts/components, cleaning of impeller, greasing, reassembling, bringing back from workshop to the site, refixing in original position including providing packing, necessary nuts & bolts etc, and reconnecting, recommissioning and testing for smooth functioning.\nLocation : NCHC Hospital\n(Note: Cost of all the elements (material cost as well as labour cost) for making the pumps completely functional except supply only of the spares/components/parts included in this item shall be deemed to be included in the quoted rates).\n | |||
200 | 104.01 | 3 HP Capacity | 2 | Each Job | |
201 | 104.02 | 7.5 HP Capacity | 1 | Each Job | |
202 | 105 | Supply only following spares /components/parts for monoblock pump set all as specified and directed :- | |||
203 | 105.01 | Gun metal bushes for 3 HP capacity | 2 | Each | |
204 | 105.02 | Gun metal bushes for 7.5HP capacity | 1 | Each | |
205 | 105.03 | Bearing for 3 HP capacity | 2 | Each | |
206 | 105.04 | Bearing for 7.5HP capacity | 1 | Each | |
207 | 105.05 | Water seal packing for 3 HP Capacity | 2 | Each | |
208 | 106 | Rewinding of unserviceable electric motor 3 phase, 50 Hz, 415 Volt of following capacity pump set complete comprises as under :- \n(a) Disconnecting & removing the electric motor from installed position including loading, unloading and transporting to approved workshop.\n(b) Taking out the existing burnt winding from the motor including rewinding complete with super enameled copper winding wire of existing gauge including provision of all insulating material such as insulation paper, sleeves, tape, varnish etc. complete for class 'F' insulation. \n(c) Transporting the motor back to the location, reinstalling in original position including making alignment, electrical & water connection, commissioning and testing for 8hours continuously to check the RPM etc. to the satisfactory performance etc. \nLocation : NCHC Hospital | |||
209 | 106.01 | Motor of capacity 3 HP | 2 | Each Job | |
210 | 106.02 | Motor of capacity 7.5HP (AHU Blower ) | 1 | Each Job | |
211 | 107 | M & L for disconnecting condenser for descalling, plugging them & providing 15mm bore tee outlet for local circulation of mild acid solution in the condenser (separate container & small pump set to circulate diluted acid solution shall be used)PH value of solution shall be 4 and it shall be checked frequently i.e every 1hour during the operation, Scalgun WS solution shall be used for descalling purpose after 2 to 3hours of cleaning if PH value remains less than 7, flush with fresh water added with sodium carbonateTube, to clean with nylon brush, after closing the end covers circulate diluted acid solution as specified above & PH value to maintained as above by flushing the same with fresh water including recharging of stored refrigerant upto required pressure complete all as specified & directed for 2 x 11 TR capacity of AC plants :- (Location-NCHC Hospital) | 2 | Each | |
212 | 108 | Pumping down the existing refrigerant from the condenser, carrying out the leak test of plant with the pressure of Nitrogen gas and monitoring for 24hrs, assess leakages by brazing & replacement of necessary gaskets wherever required including copper tubes of suitable sizes, vacumizing of the plant by vaccum pump, finally recharging of existing refrigerant gas to the plant and topping up of refrigerant if required to maintain the standard pressure etc complete including testing of the plant for smooth functioning complete all as specified & directed.\nNote: Refrigerant required for topping up will be measured and paid as supply only separately under relevant item. However, cost of all the other elements as specified above including replacement of gaskets, copper tubes etc for making the condensor functional shall be deemed to be included in the quoted rate of above item.\nLocation : NCHC Hospital\n | 2 | Each Job | |
213 | 109 | M & L for dismantling cooling tower of undermentioned capacity by removing CT Fans, sprinklers, PVC filler, cleaning cooling tower body by removing scale, dust, dirt, refixing PVC filler after cleaning with diluted HCL solution, reassembling, connecting,cleaning external surfaces and applying two coats of approved synthetic enamel paint including writing SM number/ marking and testing etc. complete all as specified and directed :-\nCooling tower 2 x 11TR Capacity (Location- NCHC Hospital) | 1 | Each Job | |
214 | 110 | S & F in repairs Sensor type thermostat of central AC plant of range 5 Degree centigrade to 25Degree centigrade complete with all accessories, as specified and directed, Make : ANERGY / SIEMENS / HONEYWELL / JOHNSON | 2 | Each Job | |
215 | 111 | Removing the unserviceable water pressure gauges from water line & supply and fix new pressure gauge capable to measure pressure upto 7kg/ Sqcm etc. complete with all accessories, as specified and directed, Make : FIEBIGH / H.GURU / BAKER MERCER. | 2 | Each Job | |
216 | 112 | All as per item No. 111 above but for pressure upto 10Kg/ Sqcm | 1 | Each Job | |
217 | 113 | S & F in repairs for expansion valve of AC plant of capacity 15 TR to 25 TR, complete all as specified and directed, (Location-NCHC Hospital | 1 | Each Job | |
218 | 114 | M & L for replacement of Power contactor type ML-1.5, complete all as specified and directed, Make : L & T, Siemens | 1 | Each Job | |
219 | 115 | M & L for replacement of Power contactor type ML- 2, complete all as specified and directed, Make : L & T, Siemens | 1 | Each Job | |
220 | 116 | M & L for replacement of Thermal Timer range GT-100, 9 to 30Sec adjustable type voltage 215/ 450V, complete all as specified & directed, (Make : L & T/ Siemens) | 1 | Each Job | |
221 | 117 | Supply and fix in replacement single phase preventer type ES-100, complete all as specified & directed, (Make : L & T/ Minilac) | 1 | Each Job | |
222 | 118 | S & F in replacement of unserviceable / worn-out "V" Belt (B-85) of compressor, AHU etc. of Make : Dunlop/ Nerlon :- | 4 | Each | |
223 | 119 | Material & Labour for replacement of unserviceable Sensor type HP cut out, complete all as specified & directed, Make : PENN / INDOFOSS / RANCO / DANFOSS / JOHNSON. | 1 | Each | |
224 | 120 | M&L replacement of unserviceable LP cut out, Sensor type, complete all as specified & directed, Make : PENN / INDOFOSS / RANCO / DANFOSS / JOHNSON. | 2 | Each | |
225 | 121 | Material & Labour for replacement of the defective indicator lamp LED type, complete all as specified & directed, Make : SIEMENS / CONCORED / C&S / L&T. | 4 | Each | |
226 | 122 | M&L for replacemetn of existing unserviceable/defective multifunctional meter, digital type of size 96 x 96mm with and including CT, complete all as specified and directed, Make : L&T (RISHAB) / TRINITY / C&S / L&T. | 1 | Each | |
227 | 123 | M & L for replacement existing unserviceable / defective ampere meter with new digital type, 0-30 Ampers of size 96 x 96mm with and including CT, complete all as specified & directed, Make : AE / ENERCON / SECURE / L&T | 1 | Each | |
228 | 124 | Supply only refrigerant (R-407C) gas for topping-up complete all as specified and directed, Make: MAFRON / FREON. | 35 | Kg | |
229 | 125 | Removing old unserviceable globe valve and S & F new CI globe valve with nuts, bolts, washer, new gaskets etc. of 50 mm bore sizes complete all as specified & directed, Make: ADVANCE / AUDCO / SANT / BIR. | 2 | Each | |
230 | 126 | S & F in repairs MVPD, complete all as specifed and directed, Location - NCHC Hospital | 1 | Each | |
231 | 127 | S & F in repairs liquid line, Drier filter 1/2" size, Make DANFOSS / EMERSON / CASTLE, Location: NCHC Hospital | 2 | Each | |
232 | 128 | M & L for Cleaning complete DX type cooling coil of AHU with chemical solution caustic soda to remove impurities completely, dust and foreign materials with nylon brush and cleaning cooling coil with fresh water, complete all as specified & directed for the cooling coil section of AHU of 2 x11TR Capacity (Location :- NCHC Hospital | 1 | Each Job | |
233 | 129 | S & F in repairs unserviceable hermetically sealed compressor reciprocating type 5.5 TR working on R-22, 3Phase , 415V including brazing and electric/ piping connection etc. complete all as specified & directed, Make : COPLAN / EMERSON / BLUE STAR. Location :-NCHC Hospital | 1 | Each Job | |
234 | 130 | Supply and fix in repairs, MCCB, TP, 25 to 100 Amps, 415 Volt, 50 Hz, breaking capacity 16 KA, fixed type, Complete all as specified and directed. | 1 | Each | |
235 | 131 | Supply and fix in repairs MCCB, TP, 125 Amps, 415 Volt, 50 Hz, breaking capacity 16 KA, fixed type, Complete all as specified and directed. | 1 | Each | |
236 | 132 | M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected with and including 32 x 6mm galvanised iron strip by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No. 3 and earthing strip connected to earthing test point all as specified and directed, including provision of mild steel frame, CI cover, PCC chamber, funnel with watering pipe, wire mesh and lugs etc, GI protection pipe of size 40mm bore light grade laid in trench, fixed on wall, floor etc, including testing on completion and dismantling of existing earthing set.\nNote: Cost for provision of GI strip and 40mm bore potection pipe upto 7.50 metre shall also be deemed to be included in the quoted rate. | 1 | Each Set | |
237 | 133 | Dismantling of existing defective unserviceable compressor of any capacity from window or split AC, Refrigerators, water coolers etc complete all as specified and directed. | 21 | Each | |
238 | 134 | Supply & Fix new hermetically sealed compressor in existing window type AC, 1.5 Ton capacity including initial filling of refrigerant gas to the required pressure, brazing, electric/piping connection etc complete all as specified and directed. | 2 | Each | |
239 | 135 | All as per item No. 134 above but for split type AC 1.5 Ton capacity | 4 | Each | |
240 | 136 | All as per item No. 134 above but for split type AC 2 Ton capacity. | 3 | Each | |
241 | 137 | All as per item No 134 above but for refrigerator 165 ltrs to 310 ltr Capacity. | 2 | Each | |
242 | 138 | All as per item No. 134 above but Water Coolers 40 / 80 Ltrs Capacity. | 2 | Each | |
243 | 139 | Taking out window type air conditioner of capacity upto 2 TR of any make/type after disconnecting of electric supply and removing dust by using blower and cleaning the condenser coils and components by using water and caustic soda, checking and replacing the spares like relay, capacitors, thermostat, fan motor, blades & blower and including servicing,overhauling and charging of refrigerant and testing including fixing back in its original location complete all as specified and directed. | 2 | Each Job | |
244 | 140 | Taking out split type air conditioner (both indoor and outdoor units) of capacity upto 2 TR of any make/type after disconnecting refrigerant pipes, drain pipe and electric connection and removing dust by using blower and cleaning the condenser coils and components by using water and caustic soda, checking and replacing the spares like relay, capacitors, thermostat, fan motor, blades & blower and including servicing, overhauling and connecting of refrigerant pipe,drain pipe and charging of refrigerant and testing including fixing back in its original location complete all as specified and directed. \nNOTE FOR ITEM NOS. 139 & 140 : (i) Spares will be measured and paid separately as supply only. (ii) Refrigerant gas will be measured and paid separately as supply only." | 10 | Each Job | |
245 | 141 | Replacement of corroded body base tray & connected portion of window type AC upto 2 Ton capacity (base tray made out of M S Sheet 18 BG and other portion with MS sheet 20 BG) including motor mounting frame, nuts/bolts of suitable size and spray painting with two coats of synthetic enamel paint over one coat of primer including replacement of damaged insulation etc complete all as specified and directed. Note : For replacement of the body, cost of dismantling of compressor etc including reassembling and gas charging etc as required at site shall also be deemed to be included in the quoted rates. | 2 | Each Job | |
246 | 142 | Supply only blower fan motor for 1.5 TR capacity window type air conditioner complete all as specified and directed. | 2 | Each | |
247 | 143 | Supply only blower fan blade for 1.5 TR window type air conditioner complete all as specified and directed. | 2 | Each Job | |
248 | 144 | Supply only blower drum of window type AC upto 1.5 ton capacity complete all as specified and directed. \n | 1 | Each Job | |
249 | 145 | S&F in repairs of blower fan motor for 1.5 TR capacity window type air conditioner complete all as specified and directed. | 2 | Each | |
250 | 146 | S&F in repairs of blower fan blade for 1.5 TR window type air conditioner complete all as specified and directed. | 2 | Each Job | |
251 | 147 | S&F in repairs of blower drum of window type AC upto 1.5 ton capacity complete all as specified and directed. \n | 1 | Each Job | |
252 | 148 | Supply only relay for window type AC upto 1.5 Ton capacity complete all as specified and directed. | 4 | Each | |
253 | 149 | Supply only over load protector in window type AC upto 1.5 ton capacity complete all as specified and directed. | 1 | Each | |
254 | 150 | Supply only selector switch push button type for window type AC upto 1.5 Ton capacity complete all as specified and directed. | 1 | Each | |
255 | 151 | All as per item No. 150 above but selector switch rotary type complete all as specified and directed. | 1 | Each | |
256 | 152 | Supply only blower fan motor upto 2.0 TR capacity spilt type air conditioner complete all as specified and directed. | 6 | Each | |
257 | 153 | Supply only blower drum of split type AC upto 2.0 ton capacity complete all as specified and directed. \n | 5 | Each Job | |
258 | 154 | Supply only outdoor motor upto 2.0 TR split type air conditioner complete all as specified and directed. | 6 | Each Job | |
259 | 155 | Supply only outdoor fan blade upto 2.0 TR split type air conditioner complete all as specified and directed. | 5 | Each Job | |
260 | 156 | S&F in repairs of blower fan motor upto 2.0 TR capacity spilt type air conditioner complete all as specified and directed. | 5 | Each | |
261 | 157 | S&F in repairs of blower drum of split type AC upto 2.0 ton capacity complete all as specified and directed. \n | 5 | Each Job | |
262 | 158 | S&F in repairs of outdoor motor upto 2.0 TR split type air conditioner complete all as specified and directed. | 6 | Each Job | |
263 | 159 | S&F in repairs of outdoor fan blade upto 2.0 TR split type air conditioner complete all as specified and directed. | 5 | Each Job | |
264 | 160 | Supply only thermostat switch for window type/split type AC upto 2 Ton capacity complete all as specified and directed. | 5 | Each | |
265 | 161 | S&F in repairs of thermostat switch for window type/split type AC upto 2 Ton capacity complete all as specified and directed. | 5 | Each | |
266 | 162 | S&F in replacement air filter pad suitable for any type AC 1.5/2.0 ton capacity complete all as specified and directed. | 10 | Each | |
267 | 163 | S&F in replacement condensing coil assembly suitable upto 2.0 Ton capacity window/split AC complete all as specified and directed. | 2 | Each | |
268 | 164 | S&F in replacement cooling coil assembly suitable upto 2.0 Ton capacity window/split AC complete all as specified and directed. | 2 | Each | |
269 | 165 | Replacement of PVC cover grill of window type AC upto 1.5 ton capacity complete all as specified and directed. | 1 | Each Job | |
270 | 166 | Replacement of existing damaged outer cover of window type AC with 20 SWG aluminium anodised sheet including moulding, screwing etc complete all as specified and directed. | 1 | Each | |
271 | 167 | Taking out corroded body & frame of water cooler of 80 Litres storage capacity and replacement with new angle iron frame of size 40 x 40 x 6mm and cooler body with MS/CRCA sheet of 20 gauge, painting with two coats of synthetic enamel paint over a coat or red oxide primer by spray painting, including reassembleing & refixing of all parts etc complete all as specified and directed . | 2 | Each Job | |
272 | 168 | Taking out corroded body & frame of Refrigerator of 165 Litres Capacity & replacing refrigerator body with MS/CRCA sheet 20 gauge duly painted with 2 coats of synthetic enamel paint over a cot of red oxide primer by spray painting including reassembling and refixing all the parts etc complete all as specified and directed. | 2 | Each Job | |
273 | 169 | All as per item No. 168 above but for Refrigerator more than 165 Litres but upto 310 Ltr Capacity complete all as specified and directed. | 2 | Each Job | |
274 | 170 | Replacement of fan motor of water cooler up to 150 Ltr capacity including testing etc complete all as specified and directed. | 2 | Each Job | |
275 | 171 | Replacement of fan blades of motor for water cooler upto 150 Ltr capacity including testing etc complete all as specified and directed | 2 | Each Job | |
276 | 172 | Supply only starting capacitor 60 to 80 MFD complete all as specified and directed. | 3 | Each | |
277 | 173 | Supply only starting capacitor 80 to 100 MFD complete all as specified and directed. | 2 | Each | |
278 | 174 | Supply only starting capacitor 100 to 120 MFD complete all as specified and directed. | 4 | Each | |
279 | 175 | Supply only running capacitor of 55 MFD complete all as specified and directed. | 4 | Each | |
280 | 176 | S&F in repairs of starting capacitor 60 to 80 MFD complete all as specified and directed. | 6 | Each | |
281 | 177 | S&F in repairs of starting capacitor 80 to 100 MFD complete all as specified and directed. | 8 | Each | |
282 | 178 | S&F in repairs of starting capacitor 100 to 120 MFD complete all as specified and directed. | 6 | Each | |
283 | 179 | S&F in repairs of running capacitor of 55 MFD complete all as specified and directed. | 8 | Each | |
284 | 180 | Replacement of relay for Water Cooler of 60 to 150 Litre storage capacitycomplete all as specified and directed. | 4 | Each | |
285 | 181 | Replacement of relay for Refrigerator 165 to 310 Litre Capacitycomplete all as specified and directed. | 2 | Each | |
286 | 182 | Taking out existing unserviceable thermostat switch of water cooler and Supply & fix new thermostat switch for water cooler of any capacity including testing etc complete all as specified and directed. (Make:INDOFOSS/RANUTRAL) | 2 | Each | |
287 | 183 | Taking out existing unserviceable thermostat switch of refrigerator and supply & fix new thermostat switch for refrigerator of any capacity including testing etc complete all as specified and directed. (Make : INDOFOSS/RANUTRAL) | 1 | Each | |
288 | 184 | Supply and fix in repairs blower motor capacitor 4 MFD etc complete all as specified and directed. (Make : ASIAN/KEIL/EPCOS) | 5 | Each | |
289 | 185 | All as per item No. 184 above but 6 MFD capacitor complete all as specified and directed. (Make: ASIAN/KEIL/ EPCOS) | 3 | Each | |
290 | 186 | Taking out existing unserviceable over load relay and supply & fix new over load relay in water cooler upto 150 ltrs capacity etc complete all as specified and directed. | 5 | Each | |
291 | 187 | Taking out existing unserviceable door gasket and supply & fix new door gasket for refrigerator upto 310 ltrs capacity etc complete all as specified and directed. | 2 | Each | |
292 | 188 | S & F in repairs sheet metal enclosure in repair with 3 pin 20 Amp earth plug & socket, also with and including single pole MCB of 20 Amps etc complete all as specified and directed. | 10 | Each | |
293 | 189 | Taking down existing unserviceable cable on wall/ceiling and supply and lay 1100 Volt grade PVC insulated 3 core 4 Sqmm stranded copper conductor cable suitable for indoor unit to outdoor unit complete all as specified and directed. | 40 | RM | |
294 | 190 | Supply, fixing, clamping and jointing copper tubing in replacement of 3/8" dia for suction line and for liquid discharge line duly insulated with suitable insulation material for split AC including necessary soldering, flaring work, jointing, testing etc, making hole in wall for passing though pipe and making good to the disturbed surface to match with the adjoining surfaces etc complete all as specified and directed. | 30 | RM | |
295 | 191 | Supply & lay PVC pipe 20 mm dia heavy duty including fittings to drain out condensed water of split AC including cutting of floor / wall & making good after laying of pipe to match the existing surface etc complete all as specified and directed. | 30 | RM | |
296 | 192 | Supply & fix push cock / lift cock 15mm bore of brass, chromium plated, ISI marked in repair for water cooler of any capacity etc complete all as specified and directed. | 2 | Each | |
297 | 193 | Supply and fix water tray made out of GI sheet 2 mm thick for water cooler any capacity with out let system connection provided with and including PVC pipe connecting to drain pipe etc complete all as specified and directed. | 2 | Each | |
298 | 194 | Removing existing unserviceable electronic circuit control board of split AC unit upto 2 ton capacity and supply and fixing new electronic PCB & display board kit in the indoor unit including testing etc complete all as specified and directed. | 2 | Job | |
299 | 195 | Supply only remote sensor handset suitable for split AC upto 2.0 ton capacity etc complete all as specified and directed. | 4 | Each | |
300 | 196 | Supply and fix in repair remote sensor plate suitable for split AC upto 2.0 ton capacity etc complete all as specified and directed. | 2 | Each | |
301 | 197 | S & F in repairs 15mm bore gun metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipes etc complete all as specified and directed. | 3 | Each | |
302 | 198 | S & F in repairs 15mm bore ball brass valve high pressure with polythene float & fly nut screwed for iron pipes etc complete all as specified and directed. | 5 | Each | |
303 | 199 | Supply only refrigerant (R-22) gas as per requirement complete all as specified and directed. | 20 | Kg | |
304 | 200 | Testing of entire Fire alarm system at each store for functionality test and carrying out preventive maintenance of the Panel. Checking of Voltage supply to all cards, battery health checking,\nlamp test of Panel, checking of History log of Alarm and trouble. Clearing of temp files from Graphics panel, checking of network communication and cable checking for proper signal\ntransmission. Checking of detector, hooter, MCP, Weather proof hooter, Weather proof MCP Isolator, network repeater and it communication. Graphics system checking for proper\nfunctionality and maintaining the log book for the test carried out. Test shall consist of Visual inspection and functionality test complete all as specified and directed. | 15 | Each Set | |
305 | 201 | Monthly corrective and remedy maintenance service to set rights the malfunctions of the system. This may include replacement of unserviceable parts. Parts replaced will either be New parts or parts equivalent in performance to new parts. Visit will consist of one engineer and 2 technicians. Spare parts/Component will be paid separately complete all as specified and directed | 11 | Months | |
306 | 202 | Supply installation testing & commissioning of AMPS-24E for Fire alarm panel, It shall be fully compatible with the existing Fire panel of Notifier make with following specification - 240\nVAC 50/60 Hz input, 2.25 A maximum • One 5 VDC @ 1.0 A - nonpower-limited output - TB6 One 24VDC @ 1.0 A - nonpower- limited output - TB6 Power-limited if 5V output is not used.\nMaximum Ripple Voltage (24 VDC & 5VDC): 250 mVrms • One 24 VDC @ 4.5 A - filtered, nonpower-limited source - TB2 Maximum output:4.2 A when 5V output (TB6) is used. 3.5 A when 24V output (TB6) is used. 3.2 A when both outputs on TB6 are used.Maximum Ripple Voltage: 250 mVrms complete all as specified and directed Make Notifier | 1 | Each Job | |
307 | 203 | Supply, Installation, Testing and commissioning of CPU Card for Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 event plus 1000 alarm log history events. It should be compatible to panel\nequipped with sufficient numbers of. Card shall have loop capacity of minimum 150 analog addressable devices. It should support the panel to work in degrade mode. Four access levels,\ninbuilt flash EPROM complete all as specified and directed Make Notifier. | 1 | Each Job | |
308 | 204 | Supply, installation, testing and commissioning of loop card of 150 point for NFS 3030 Fire alarm panel. It should be programmable by laptop at site. The card should be compatible to the existing system and device in the network. Its functionality should not adversely affect the installed system\nand shall be complete as specified and directed. Make : Notifier | 1 | Each | |
309 | 205 | Supply, installation, testing and commissioning Addressable Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 4.0% obs/ft.The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-color LED for 360 deg viewing. Addressing\nshall be with user friendly rotary decimal switches. Designed to meet UL268, 7th Edition complete all as specified and directed Make Notifier | 38 | Each | |
310 | 206 | Supply, installation, testing and commissioning of Intrinsically safe Photoelectric Smoke Detector with Zener barrier and all necessary accessories sensitivity range of 0.5 to 3.7% obs/ft. The\ndetector shall have multi co-operative sensing technology for faster response & avoid false alarms. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches complete all as specified and directed Location: Paint Storage shop | 1 | Each Job | |
311 | 207 | Supply, installation, testing and commissioning Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the health status of the device complete all as specified and directed Make: Notifier | 1 | Each | |
312 | 208 | Supply installation testing and commissioning Addressable Sounder cum Strobe rated at 75 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication all as directed and specified | 1 | Each | |
313 | 209 | Supply and fixing in repairs Fire Exit Signage’s, complete all as specified and directed, Make :Prolite Autoglow | 6 | Each | |
314 | 210 | Supply and fix in repairs Fire and emergency signage Boards( Fire escape directions, First aid charts, First aid box indications, safe material handling procedures, Fire assembly area indications etc,) \n | 5 | Each Set | |
315 | 211 | Supply and fix in repairs Isolators complete all as specified and directed | 4 | Each Job | |
316 | 212 | Supply and fix in repairs Cast iron wafer end type Butterfly valves (standard lever operated type for 150 mm dia. and below and gear operated type for 200 mm and above dia.) butterfly valves as per BS 5155/ IS 13095 (PN 10) having nylon coated CI disc, nitrile rubber seat complete with matching flanges, gaskets, galvanised fasteners. | |||
317 | 213 | 150 mm nominal dia | 1 | Each | |
318 | 214 | 100 mm nominal dia | 2 | Each | |
319 | 215 | 80 mm nominal dia | 1 | Each | |
320 | 216 | Supply and fix in repairs Forged brass screwed ends full bore ball valves (min PN 10 rating) with suitable fittings of screwed end type complete 25NB complete all as specified and directed | 1 | Each | |
321 | 217 | Supply and fix in repairs Reinforced rubber lined fire hose as per IS: 636 (Type A) with stainless steel couplings as per IS: 903, 7.5m long for internal hydrants complete all as specified and directed. | 5 | Each | |
322 | 218 | supply and fix in repairs Swinging type first aid fire hose reel drum comprising of reinforced rubber tubing of 20 mm dia and following lengths conforming to IS :444 Type II, MS drum with fixing bracket conforming to IS:884 & with 5 mm dia gun metal shut off nozzle conforming to IS:8090 and 25NB forged brass valve. (30 meters Hose length) | 6 | Each | |
323 | 219 | Supply and fix in repairs 63 mm x 20 mm stainless steel branch pipe and nozzle as per IS:903 to be connected to hose coupling | 3 | Each | |
324 | 220 | Supply and fix in repairs Weather proof outdoor lockable hose cabinet made of 14 SWG CRCA MS Sheet with 2 doors and 4 mm thick glazed glass with water proof rubber beading. it shall be in red outside and white inside with two coats of enamel paint over a coat of primer. "HOSE CABINET NO.." shall be painted on the inner face of the glass in 50 mm size block letter. Cost shall include the cost of break glass box containing the key of the cabinet. Size 600(H) x 750(L) x 250(D) mm complete all as specified and directed. | 6 | Each Job | |
325 | 221 | Supply and fix in repairs Fire brigade inlet connection of 4 way with 4 nos 63 mm dia stainless steel outlet, built in check valve complete as per specification. Rate shall include cost of 1 no 150NB butterfly valve and one no cabinet to house the inlet connection only. | 1 | Each | |
326 | 222 | Supply & fixing in repairs gun metal Fire internal Hydrant single landing valve with 80 mm N.B. flanged inlet, brass spindle controlled 63 mm dia female instantaneous outlet type. G.M. coupling, blank cap, chain, twist release type lug & all accessories conforming to IS:5290. Including fixing with anchor fastener and flanged tapping from wet riser and providing pressure gauge with gun metal ball valve complete as required. | 2 | Each | |
327 | 223 | Supply only copper sulphate of super quality ISI Marked complete all as specified and directed. | 100 | Kg | |
328 | 224 | Supply only aluminium potash of super quality ISI Marked complete all as specified and directed. | 500 | Kg | |
329 | 225 | Supply only Soda Ash of super quality ISI Marked complete all as specisified and directed. | 400 | Kgs | |
330 | 226 | Supply only Calcium hyppchloritein Garnual Calcium Based Chlorine usefull for Disinfection Of Drinking Water treatment. These highly concentrated solid calcium hypochlorite products deliver upto 70% available chlorine. conforms to BS EN 900:2007 (Chemicals used for treatment of water intended for human consumption - calcium hypochlorite make:Altoch GP | 850 | Kgs | |
331 | 227 | Supply only stable bleaching powder (calcium hypochloride with chlorine content not less than 30%) as per IS: 15738 : 2007 and 1065 : 1989 Marke : M/s Sree Rayalaseema Hi-Strength Hypo Ltd or Grasim industries Ltd or Bengal Chemichal & Pharmaceuticals. | 850 | Kg | |
332 | 228 | Testing of water Supply and obtain the following the research and tested through NABL accredited Lab including submitting of test certificate to Engineer – in Charge complete all as specified. Details of tests to be carried out (i) Turbidity (NTU), (ii) PH, (iii) Total Hardness CaCO3 (mg/l), (iv) Sulphate (SO4) (mg/l), (v) Iron (Fe) (mg/l), (vi) Magnesium (Mg) (mg/l), (vii) E-coli or thermo tolerant coliform bacteria Note: The rate quoted deemed to include the cost of collecting sample of water in four different locations from MO (MB) Ghatkopar and the test to be carried out in the first and seventh month of the contract. | 16 | Each | |
333 | 229 | Taking down unserviceable suction sweeper motor pump set 5Hp capacity, dismantling the pump side and replacing the worn out shaft, bearings, bush and coupling rubber bush and dismantling 3 phase 5Hp AC induction motor and rewinding with super enameled copper wire of suitable gauge including varnishing, reassembling and re-coupling with pump set, testing and painting with synthetic enameled paint after preparing the existing surface complete | 1 | Each Job | |
334 | 230 | Supply and fixing CI pipe with spigot and socket ends, titan joints type, centrifugal cast class'LA; of size 150 mm laid in trenches ,earth work and joints shall be measeured and paid separately | 65 | RM | |
335 | 231 | Takig down unserviceable moo block motor pump set of capacity 3 phase 5 HP disconnecting the all necessary electrical connections and dismantlng the pump side and replacing the worn out winding and connected items like bearings, bush and coupling and rubber coupling etc; and rewinding with super enameled copper wire of suitable guage including varnishing, reassembling and re-coupling with pump set, testing and painting with synthetic enameled paint after preparing the existing surface complete all as specified. | 1 | Each job | |
336 | 232 | Supply and operate swimming pool cleaning leaf rake mess frame net skimmer complete all as specified and directed. | 2 | Nos | |
337 | 233 | Removing old unserviceable sluice valve 150 mm dia and S & F new sluice valve 150 mm dia bore PN 1.6 with nuts, bolts washer new gaskets etc all as per IS specifications complete all as specified & directed. | 2 | Each | |
338 | 234 | M&L for carrying out 'B' check for 250KVA DG set trolley mounted all as per manufacturers instructions.\nNote : Rate quote shall be deemed to be inclusive of spares and filters but excluding engine oil. | 1 | Each Job | |
339 | 235 | Supply and filling Engine Oil 15W 40 for 500/250 KVA DG set complete all as specified and directed. | 150 | Ltrs | |
340 | 236 | Supply and replacement of diesel filter of 500 KVA DG Set complete all as specified and directed | 2 | Nos | |
341 | 237 | Supply and replacement of diesel filter of 250 KVA DG Set complete all as specified and directed | 2 | Nos | |
342 | 238 | Supply and replacement of Oil filter of 500 KVA DG Set complete all as specified and directed | 2 | Nos | |
343 | 239 | Supply and replacement of Oil filter of 250 KVA DG Set complete all as specified and directed | 2 | Nos | |
344 | 240 | Supply and filling coolent for 500/250 KVA DG Set complete all as specified and directed | 250 | Ltrs | |
345 | 241 | Overhauling of monoblock pump set by removing and dismantling of pump from connected suction/ delivery pipes and electric connections etc. and taking to workshop and replacing (labour element only) unserviceable spares such as gland packing set, gun metal bushes, bearing, water seal packing set, gun metal bushes , bearing, water seal packing etc. cleaning of impeller, greasing etc. reassembling and refixing in original position including packing, and necessary nut & bolt etc. including minor parts and reconnection, recommissioning and testing for smooth functioning of following capacity pumps:-\nLocation : MO(MB) Ghatkopar\n(Note:- Major spares such as gunmetal bushes, gland packing, bearing and water seal to be replaced will be measured & paid as supply only under respective items)\n | |||
346 | 241.01 | 3.01 5HP Capacity | 1 | Each | |
347 | 241.02 | 3.02 7.5HP Capacity | 1 | Each | |
348 | 241.03 | 3.03 10 HP capacity | 1 | Each | |
349 | 242 | Supply only following spares for monoblock pump set all as specified and directed | |||
350 | 242.01 | Gun metal bushes for 5HP capacity | 1 | Each | |
351 | 242.02 | Gun metal bushes for 7.5HP capacity | 1 | Each | |
352 | 242.03 | Gun metal bushes for 10 HP capacity | 1 | Each | |
353 | 242.04 | Gland packing set for 5HP capacity | 1 | Each | |
354 | 242.05 | Gland packing set for 7.5HP capacity | 1 | Each | |
355 | 242.06 | Bearing for 5HP capacity | 1 | Each | |
356 | 242.07 | Bearing for 7.5HP capacity | 1 | Each | |
357 | 243 | Testing of water Supply and obtain the following the research and tested through NABL accredited Lab including submitting of test certificate to Engineer – in Charge complete all as specified. Details of tests to be carried out (i) Turbidity (NTU), (ii) PH, (iii) Total Hardness CaCO3 (mg/l), (iv) Sulphate (SO4) (mg/l), (v) Iron (Fe) (mg/l), (vi) Magnesium (Mg) (mg/l), (vii) E-coli or thermo tolerant coliform bacteria \n | 11 | Each | |
358 | 244 | Repair/Routine maintenance including carrying out daily check of fire alarm/fire fighting system complete with electronic control panel consisting of 02 zones in P/267 and P/268 buildings (G+16 floors) ie 17 stories including attendance of alarm personnel to attend the fire alarm system faults, testing, checking including replacement of unserviceable components other than mentioned in schedule “A” The fire alarm system consisting the following:-\n(a) Indicator \n(b) Electronic hooter\n(c) Manual call point\n(d) Smoke detector\n(e) Heat detector\n(f) Electronic fire control panel\n(g) Main/Zone cards\n(h) Battery of Fire panel DC supply \n(J) All wiring and cable connections \n(k) Fire diesel pump\n(l) Fire pump \n(m) Booster pump\nNote : Contractor shall be arrange monthly demonstration of fire fighting system of his own cost. b)contractor shall be liable to give warrently all fire fighting system shall serviceable/working condition. if the system found unserviceable/ not working at any time the contractor liable to penality. | 11 | Per Month | |
359 | 245 | Supplying, installing, testing and commissioning cast iron body, ISI marked,BUTTERFLY VALVE as per IS 13095, ISI Marked with necessary fittings as per specification. Details : The Butterfly valve shall suitable for waterworks and tested to minimum of 20 kg/cm2 pressure. The body shall of cast iron conforming to IS:210 in circular shape and of high strength to take the minimum water pressure of 10kg/cm2 . The disk shall be heavy duty cast iron with anticorrosive epoxy or nickel coating Make- Audco/Kirloskar/Honeywell Note : i) The valve seat shall be of high grade elastomer or nitrile rubber. The valve in closed position shall have complete contact between the seat and the disc thoughout the perimeter. the elastomer rubber shall have a long life & shall not give away on continuous water pressue. The shaft shall be on EN 8 grade carbon steel. ii) the valve shall be fitted between two flanges on upper side of pipe flanges. The valve edge rubber shall be projected outside such that they are wedged within the pipe flanges to prevent leakages.iii) The valves shall be suppied with manual gear operated openin/closing system by lever. | |||
360 | 245.01 | 150mm dia | 2 | Each | |
361 | 245.02 | 100 mm dia | 1 | Each | |
362 | 245.03 | 80 mm dia | 2 | Each | |
363 | 245.04 | 65 mm dia | 2 | Each | |
364 | 246 | Supply and fixing in repair of Y stainer with necessary fittings, flanges, nut bolts etc as per specification. The "Y" type strainer shall have cast iron body confirming to IS 210 FG 200 Perforaed sheet shall be of brass or strain less steel 304. The Screen open area shall be minimum Four times cross sectional area at inlet. The Strainer shall be suitable for MIN. flow of 300 LPM at 10kg/cm2 sq pressure. The flanges shall be to IS 1538. The nut bolt sand washers shall be galvanised confirming too IS 1367. The pressure loss shall not be more than 0.5 kg/cm2 sq. The Hydraulic Testing shall done at 21kg/cm sq for the duration of Two hours of the following sizes :- | |||
365 | 246.01 | 150 mm dia | 2 | Each | |
366 | 246.02 | 100 mm dia | 2 | Each | |
367 | 247 | Supply & fixing in repair presure gauge glycerine filled with 15mm inlet connection dial size 100 mm of pressure range 0.21Kg/cm sq. with 15mm isolation valve with G.I. nipple all as specified | 2 | Each | |
368 | 248 | Supply and fixing in repair pressure switches with adjustable pressure range from 1 to 10 bar with 15mm isolation valve with GI Nipple all as specified. | 2 | Each | |
369 | 249 | Supply and fixing in repair approved quartezoid bulb 15mm dia sprinkler pendent type , IS 15106 chrome plated crossette plate, with temperature rating 68 degree with universal deflector as approved by T.A.C complete with all necessary connections complete all as specified and directed. | 6 | Each | |
370 | 250 | All as per item No 249 but with temperature rating 79 degree | 6 | Each | |
371 | 251 | Supply and fixing Bronze Orifice with 12mm thick disc with tag on plate mentioning dia of orifice for sprinkler system to control the pressure including rubber gasket packing, bolts, nuts washers all complete as per specified and directed | 2 | Each | |
372 | 252 | S&F ball valve with brass speindle of 25mm dia complete all as specified | 2 | Each | |
373 | 253 | S&F ball valve with brass speindle of 50 mm dia complete all as specified | 2 | Each | |
374 | 254 | Supply and Fix in repairs outside hose box cabinet made out of 18 gauge MH sheet of size as per site reqirement but not less than 800mm X 600nun X 250mm with double leafed glazed shutters (glazed with 4mm thick transperent fiber sheet) and door frame made out of 16 guage MS sheet painted fire red outside and brilliant white inside and concealed in wall complete all as specied and directed for housing two number RRL hose each 15m long, one number branch pipe with nozzle , first aid hose and single outlet hydrant valve etc and must have the legend " FIRE HOSE" painted prominently in graphic style and all as specified and directed | 6 | Each | |
375 | 255 | Supply and Fix in repairs internal hose box cabinet made out of 18 gauge MH sheet of size as per site reqirement but not less than 800 mm x 600mm x 250mm with double leafed glazed shutters (glazed with 4mm thick transperent fiber sheet) and door frame made out of 16 guage MS sheet painted fire red outside and brilliant white inside fixed on wall complete all as specied and directed for housing two number RRL hose each 15m long, one number branch pipe with nozzle , first aid hose and single outlet hydrant valve etc and must have the legend " FIRE HOSE" painted prominently in graphic style and all as specified and directedall as specied and directed. | 4 | Each | |
376 | 256 | Supply and Fix in repairs fire fighting RRL hose pipe of 63mm, ISI marked, IS 636(type A), 15m long fitted with male and female gun metal coupling ISI marked, IS 903 complete all as specied and directed. | 5 | Each | |
377 | 257 | Supply and Fix in repairs gunmetal branch pipe with nozzle suitable for 63 mm dia RRL hose pipe, ISI marked, complete all as specied and directed. | 11 | Each | |
378 | 258 | Supply and Fix in repairs fire hydrant landing valve GM single outlet hydrant morris pattern oblique type 63 mm size confirming to IS 5290 with PVC blank cap and MS or GI chain in an approved manner. | 12 | Each | |
379 | 259 | Supply and Fix in repairs two way fire brigade inlet, ISI marked, IS 5290, with non return valve, of gun metal size 63mm dia and including all fixing accessories complete all as specified and directed. Location: NS-130 (Cauvery), NS-175 (Samagri Bhavan) | 1 | Each | |
380 | 260 | Supply and Fix in repairs four way brigade inlet, ISI marked, IS 5290,with non return valve of gun metal size 63mm dia and including all fixing accesorries complete all as specified and directed. Location: Vikramaditya | 1 | Each | |
381 | 261 | Repair and maintenance of 100 HP fire service main pump multi stage having 2280 LPM at 90 mtrs head multi stage pump of horizontal split casing running at 1450 RPM coupled with 100HP diesel engine including servicing by replacing unserviceable items of gland packing, bearings and charging lubricants for smooth running including servicing of 100 hp diesel engine by replacing filters, lubricant oil including defective parts like coupling, oil air filters, servicing of radiator, replacement exhaust gasket, replacement of diesel supply and return pipes from tank to engine, battery leads and checking of chaging circuit complete including base frame and pipe lines upto inside pump room of approved colour after preparation of existing surface complete all as specified and directed . | 1 | Each Job | |
382 | 262 | Repair and maintenance of 100HP fire service main pump multi stage having 2280 LPM at 90 mtrs head multi stage pump of horizontal split casing running at 1450 RPM coupled with 100HP AC induction motor including servicing by replacing unserviceable items of gland packing, bearings, gaskets, nuts, bolts and charging lubricants for smooth running including painting of pumpset, base frame and pipe lines upto inside pump room of approved colour after preparation of existing surface complete all as specified and directed . \n | 1 | Each Job | |
383 | 263 | Repair and maintenance of 5.5 HP fire service jockey pump multi stage having 180 LPM at 90 mtrs head multi stage pump of horizontal split casing running at 2900 RPM coupled with 5.5 HP AC induction motor including servicing by replacing unserviceable items of gland packing, bearings, gaskets, nuts, bolts and charging lubricants for smooth running including painting of pumpset, base frame and pipe lines upto inside pumproom of approved colour after preparation of existing surface complete all as specified and directed. | 2 | Each Job | |
384 | 264 | Repair and maintenance of fire service booster pump multi stage having 900 LPM at 36 mtrs head ,horizontal split casing running at 2900 RPM coupled with AC induction motor including servicing by replacing unserviceable items of gland packing, bearings, gaskets, nuts, bolts and charging lubricants for smooth running including painting of pumpset, base frame and pipe lines upto inside pumproom of approved colour after preparation of existing surface complete all as specified and directed. | 2 | Each Job | |
385 | 265 | Material and labour for replacement of un serviceable timer of starter, range 9 to 30 sec adjustable type voltage 415 V all as specified and directed by Engr-in- Charge. | 2 | Each | |
386 | 266 | Material and labour for repalcement of un serviceable single phase preventer , 415 V 50Hz including electric connection all as specified and directed by Engineer-in-Charge. Make Minilec. | 2 | Each | |
387 | 267 | S&F in repair MPCB (motor protection circuit breaker), 3 Phase, 415 Volts, 50 Hz, contractor type - MO 50 suitable of 75 HP pumps complete all as specifed and directed Make- L&T/Schneider/Siemens | 2 | Each | |
388 | 268 | S&F in repair soft starter Model No CSXi-030-41, 3 Phase 60 Amp with auxiliary 30 VDC for withstanding current 5000A RMS 575 V AC Maximum in panels with proper wiring complete all as specified and directed. Make L&T Model No CSXi-030-41 or ABB/Schneider | 2 | Each | |
389 | 269 | Supply and fix in repair barrel type HRC Fuse 2 to 32 Amps complete all as specifed | 12 | Each | |
390 | 270 | Supply and fix in repair barrel type HRC Fuse 40 to 63 Amps complete all as specifed | 11 | Each | |
391 | 271 | Supply and fix in repair maintenance free SMF type lead acid battery duly charged 12 Volts, 24 Ah complete all as specifed. Make- Exide/Amron | 4 | Each | |
392 | 272 | Supply and fix in repairs Foot valve cast iron body both ends flanged suitable for 150mm bore CI pipe connection all as specified and directed Make -Kirloskar/Kartar/SIR/AUDICO | 1 | Each Job | |
393 | 273 | Supply and fix in repair analogue addressable multisensor detector (Photo + Thermal) with base with galvanised steel, back box and all mounting accessories complete as specifed and directed Make- GE Edwards Model : SIGA-PHS+SB or equivalent siemens/ system sensor/Safex | 10 | Each | |
394 | 274 | Supply and fix in repair analogue addressable heat detector, with galvanised steel back box all mounting accessories complete as specifed and directed Make- GE Edwards Model : SIGA-PHS+SB or equivalent siemens/ system sensor/Safex | 12 | Each | |
395 | 275 | Supply and fix in repair addressable Dual Action Manual Pull staions inside for providing MS box of suitable size for concealing the manual call point in the wall and with mounting accessories all as specified Make- GE Edwards Model : SIGA-270 or equivalent siemens/ system sensor/Safex | 5 | Each | |
396 | 276 | Supply and fix in repair addressable Monitor Modules in a suitable gavanised steel junction box with mounting accessories all as specified Make- GE Edwards Model : SIGA-CT1 or equivalent siemens/ system sensor/Safex | 4 | Each | |
397 | 277 | Supply and fix in repair addressable control Module for Hooter in a suitable gavanised steel junction box with mounting accessories all as specified Make- GE Edwards Model : SIGA-CR or equivalent siemens/ system sensor/Safex | 10 | Each | |
398 | 278 | Supply and fix in repair Electronic Hooter include provide MS box suitable size for concealing the hooter in the wall mounting accessories all as specified Make- GE Edwards Model : R HD or equivalent siemens/ system sensor/Safex | 9 | Each |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy