Construction Of A ( G Plus 5 ) Storied Academic Building With The Provision Of Ten-Storied Foundation For The Integrated Open Campus-Cum-Regional Centre Of Netaji Subhas Open University At New Town , Kolkata - Fire Fighting ( Prevention ) System . , New Town, Rajarhat-West Bengal

Public Works Department-PWD has published Construction Of A ( G Plus 5 ) Storied Academic Building With The Provision Of Ten-Storied Foundation For The Integrated Open Campus-Cum-Regional Centre Of Netaji Subhas Open University At New Town , Kolkata - Fire Fighting ( Prevention ) System . . Submission Date for this Tender is 23-10-2020. Building Work Tenders in New Town, Rajarhat West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

25596269
Construction Of A ( G Plus 5 ) Storied Academic Building With The Provision Of Ten-Storied Foundation For The Integrated Open Campus-Cum-Regional Centre Of Netaji Subhas Open University At New Town , Kolkata - Fire Fighting ( Prevention ) System .
Open Tender
Indian
West Bengal
New Town, Rajarhat
23-10-2020

Tender Details

Construction Of A ( G Plus 5 ) Storied Academic Building With The Provision Of Ten-Storied Foundation For The Integrated Open Campus-Cum-Regional Centre Of Netaji Subhas Open University At New Town , Kolkata - Fire Fighting ( Prevention ) System .

Key Value

Document Fees
Refer document
EMD
INR 80000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Construction of a (G+5) Storied Academic Building with the provision of Ten-storied Foundation for the Integrated Open Campus-cum-Regional Centre of Netaji Subhas Open University at New Town, Kolkata - Fire Fighting (Prevention) System.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Part A: Pump House
2 2 Supply Installation, Testing & Commissioning of Motor Driven fire pumps shall be of 80 mts and discharge capacity of 171 cum/hr. The flow requirement of pump shall be 150% of rated capacity, at a total rated head not less than 65% of total rated head.The total shut off head shall not exceed 120% of total rated head on the pump. TEFC motor (2900 rpm) shall capable of driving pumps at 150% of its rated discharge and shall be designed for continous full load duty.\n 1 Set
3 3 Supply Installation, Testing & Commissioning of Engine Driven fire pumps shall be of 80 mts and discharge capacity of 171 cum/hr. The flow requirement of pump shall be 150% of rated capacity, at a total rated head not less than 65% of total rated head.The total shut off head shall not exceed 120% of total rated head on the pump. Radiator cooled Engine (2100 rpm) shall capable of driving pumps at 150% of its rated discharge and shall be designed for continous full load duty.\n 1 Set
4 4 Supply Installation, Testing & Commissioning of Electric Motor Driven Jockey pump capacity 10.8 Cum and 80 mtr head with CI casing, bronze impeller, SS shaft, RPM- 2900 (approx), with adequate motor and accessories 1 Set
5 5 Supply Installation, Testing & Commissioning of MCC panel for 1 no. EMD pump , 1 no Engine Pump and 1 No. Jockey pump for Auto start stop and other safety features, fabricated from 16 SWG MS sheet as per IS: 2062 with accessories. 1 Each
6 6 Supply Installation, Testing & Commissioning of CI Gate Valve as per IS: 14846 with fittings
7 6.01 200 NB 4 Each
8 6.02 150 NB 3 Each
9 6.03 80 NB 1 Each
10 6.04 65 NB 1 Each
11 6.05 50 NB 1 Each
12 7 Supply Installation, Testing & Commissioning of CI swing check type Non-Return Valve as per IS: 5312 with fittings
13 7.01 150 NB 2 Each
14 7.02 65 NB 1 Each
15 8 Supply Installation, Testing & Commissioning of MS Pipe up to 150 NB as per IS: 1239, part-I (Heavy Grade) and 200 NB and above as per IS: 3589, thk 6 mm with fittings with structural support and paint as per IS: 5 (shade: 536) . For under ground piping 4mm thk wrapping and coating shall be applicable.
16 8.01 200 NB 18 m
17 8.02 150 NB 18 m
18 8.03 80 NB 6 m
19 8.04 65 NB 6 m
20 8.05 50 NB 6 m
21 9 Supply Installation, Testing & Commissioning of Pressure Gauge 150mm dial with half coupling, nipple, root valve adaptor, 3 waygauge cock, vibration damper as per standard guideline. 4 Each
22 10 Supply Installation, Testing & Commissioning of Pressure Switch with CI isolation valve with fittings 5 Each
23 11 Supply Installation, Testing & Commissioning of 3-way Fire brigade inlet with 150 NB Gate valve (fabricated from MS pipe & SS coupling)for reservoir with fittings. 1 Each
24 12 Supply Installation, Testing & Commissioning of Power & Control cable with fittings
25 12.01 3C X 150 Sq mm (Al) 30 m
26 12.02 3C X 10 Sq mm (Cu) 30 m
27 12.03 2C X 1.5 Sqmm (Cu) 80 m
28 12.04 12C X 1.5 Sqmm 30 m
29 13 Supply Installation, Testing & Commissioning of Level Switch with fittings for reservoir 1 Each
30 14 Supply Installation, Testing & Commissioning of Level gauge with fittings for reservoir 1 Each
31 15 Supply Installation, Testing & Commissioning of MS Fabricated Suction type strainer and with necessary fittings.\n\n200 NB 2 Each
32 16 Part B: Hydrant System
33 17 Supply Installation, Testing & Commissioning of MS Pipe up to 150 NB as per IS: 1239, part-I (Heavy Grade) and 200 NB and above as per IS: 3589, thk 6 mm with fittings with structural support and paint as per IS: 5 (shade: 536) . For under ground piping 4mm thk wrapping and coating shall be applicable.
34 17.01 200 NB 390 m
35 17.02 150 NB 48 m
36 17.03 80 NB 24 m
37 17.04 25 NB 18 m
38 18 Supply Installation, Testing & Commissioning of CI Gate Valve as per IS: 14846 with fittings
39 18.01 200 NB 3 Each
40 18.02 150 NB 2 Each
41 19 Supply Installation, Testing & Commissioning of CI swing check type Non-Return Valve as per IS: 5312 with fittings.\n\n150 NB 2 Each
42 20 Supply Installation, Testing & Commissioning of SS single headed Hydrant Valve as per IS : 5290, type-A with fittings 18 Each
43 21 Supply Installation, Testing & Commissioning of SS Branch pipe with nozzle(19mm) as per IS: 903 with fittings 18 Each
44 22 Supply Installation, Testing & Commissioning of 15 mtr long RRL Hose as per IS: 636 with fittings 36 Each
45 23 Supply Installation, Testing & Commissioning of Hose Reel made of 18 SWG M.S. Sheet along with 30 mtr long and 20 mm dia ISI marked rubber hose with shut-off nozzle as per IS 884. 12 Each
46 24 Supply Installation, Testing & Commissioning of Hose box fabricated from 16 SWG MS sheet (IS: 513) size: 750 X 600 X 250 mm with 3mm thk glass and fittings 18 Each
47 25 Supply Installation, Testing & Commissioning of Pressure Gauge 150mm dial with half coupling, nipple, root valve adaptor, 3 waygauge cock, vibration damper as per standard guideline. 2 Each
48 26 Supply Installation, Testing & Commissioning of CI Air release valve (25NB) with CI isolation valve with fittings 2 Each
49 27 Supply Installation, Testing & Commissioning of CI Ball valve(25NB) with fittings 12 Each
50 28 Supply Installation, Testing & Commissioning of 3-way Fire brigade made of CI with 3 nos SS non return valve to be fitted with fir brigade inlet body with 150 NB Gate Valve and nessary fittings. 1 Each
51 29 Supply Installation, Testing & Commissioning of 2-way Fire brigade made of CI with 3 nos SS non return valve to be fitted with fir brigade inlet body with 100 NB Gate Valve and nessary fittings. 2 Each
52 30 Part C: Sprinkler System
53 31 Supply Installation, Testing & Commissioning of MS Pipe up to 150 NB as per IS: 1239, part-I (Heavy Grade) and 200 NB and above as per IS: 3589, thk 6 mm with fittings with structural support and paint as per IS: 5 (shade: 536) . For under ground piping 4mm thk wrapping and coating shall be applicable.
54 31.01 150 NB 60 m
55 31.02 100 NB 708 m
56 31.03 80 NB 282 m
57 31.04 50 NB 210 m
58 31.05 40 NB 324 m
59 31.06 25 NB 1890 m
60 32 Supply Installation, Testing & Commissioning of 68 deg C Sprinkler with fittings (Pendent / Upright/Sidewall)
61 32.01 Pendent type 890 Each
62 32.02 Upright type 73 Each
63 32.03 Side Wall type 6 Each
64 33 Supply Installation, Testing & Commissioning of Alarm valve with fittings.\n\n150 NB 1 Each
65 34 Supply Installation, Testing & Commissioning of CI Butterfly Valve as per IS: 13095 with fittings
66 34.01 150 NB 1 Each
67 34.02 100 NB 6 Each
68 34.03 50 NB 6 Each
69 35 Supply Installation, Testing & Commissioning of Cast Iron wafer type Check Valve as per API : 594 with fittings.\n\n100 NB 6 Each
70 36 Supply Installation, Testing & Commissioning of 150 NB Cast Iron Double Flange “ Y ? Type Strainer with fittings 1 Each
71 37 Supply Installation, Testing & Commissioning of Pressure Gauge 150mm dial with half coupling, nipple, root valve adaptor, 3 waygauge cock, vibration damper as per standard guideline. 1 Each
72 38 Supply Installation, Testing & Commissioning of CI Air release valve (25NB) with CI isolation valve with fittings 1 Each
73 39 Part D: Portable Type Extinguisher
74 40 Supply Installation, Testing & Commissioning of ISI marked & ISO certified CO2 type fire extinguisher 4.5 Kg capacity conforming to IS 15683 12 Each
75 41 Supply Installation, Testing & Commissioning of 9 Ltr Foam type Fire extinguisher. 2 Each
76 42 Supply Installation, Testing & Commissioning of ISI marked & ISO certified dry Chemical powder type fire extinguisher 6 Kg capacity with GM wheel type cap conforming to IS 15683 30 Each
77 43 Supply Installation, Testing & Commissioning of ISI marked water (CO2 gas Expelled) type extinguishers 9 litres capacity with discharge tube, metal cap, 60 grams carbon dioxide cartridge complete in all respects conforming to IS 15683 30 Each
78 44 Part E: Signage
79 45 Providing and installing in position the following type AUTOGLO Photoluminescent Signages complete with fastners
80 45.01 Signage with printed "EXIT" (Size: 150mm x 200mm) 60 Each
81 45.02 Floor identification signage (i.e., 1/2/3....etc) Size 225mm x 225mm at each stair enclosure on every floor 60 Each
82 46 Providing and fixing in position the signage "FIRE ORDER" it should contain the following matter on 3mm thick "Opaque" PVC foam board of computerized cut ,PVC non-reflective self adhesive vinyl painted foam board of 3' x 4'\n\nA) ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL CALL POINT LOCATED AT STRATEGIC LOCATIONS.\n\nB) EVACUATE THE OCCUPANTS BY USING FIRE EXITS AND EMERGENCY EXITS ONLY AND ASSEMBLE AT VARIOUS ASSEMBLY POINTS.\n\nC) IF POSSIBLE ONE TRY TO EXTINGUISH THE FIRE BY USING NEAREST /SUITABLE PORTABLE EXTINGUISHER OR WATER FROM NEAREST WET RISER.\n\nD) BE CALM AND DO NOT GIVE ANY ROOM FROM PANIC, WALK, DO NOT RUN.\n\nE) IF YOU ENCOUNTER SERIOUS DIFFICULTY IN EVACUATION, FLAT AND TRY TO ATTRACT ATTENTION OF RESCUE TEAM.\n\n\n\n\n 1 Each
83 47 Part F: Fire Door
84 48 FCD : Fire rated Steel Doors with Steel Frames with ironmongery items comprising of Steel frame having double rebaed frame profile 139 x 57 mm made from 1.5 mm galvanised steel sheets and 45 mm thick shutter made from 0.8 mm thick galvanized steel sheets filled with fire retardant materials suitable for stability and integrity with 120 minutes fire rating conforming to IS : 3614 and finished with Powder Coating of Fire Door with smoke seal, hinges, door closer. Handle and lock. 54 m2
Disclaimer :