Public Works Department-PWD has published Construction Of A ( G Plus 5 ) Storied Academic Building With The Provision Of Ten-Storied Foundation For The Integrated Open Campus-Cum-Regional Centre Of Netaji Subhas Open University At New Town , Kolkata - Fire Fighting ( Prevention ) System . . Submission Date for this Tender is 23-10-2020. Building Work Tenders in New Town, Rajarhat West Bengal. Bidders can get complete Tender details and download the document.
Name of Work: Construction of a (G+5) Storied Academic Building with the provision of Ten-storied Foundation for the Integrated Open Campus-cum-Regional Centre of Netaji Subhas Open University at New Town, Kolkata - Fire Fighting (Prevention) System. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Part A: Pump House | |||
2 | 2 | Supply Installation, Testing & Commissioning of Motor Driven fire pumps shall be of 80 mts and discharge capacity of 171 cum/hr. The flow requirement of pump shall be 150% of rated capacity, at a total rated head not less than 65% of total rated head.The total shut off head shall not exceed 120% of total rated head on the pump. TEFC motor (2900 rpm) shall capable of driving pumps at 150% of its rated discharge and shall be designed for continous full load duty.\n | 1 | Set | |
3 | 3 | Supply Installation, Testing & Commissioning of Engine Driven fire pumps shall be of 80 mts and discharge capacity of 171 cum/hr. The flow requirement of pump shall be 150% of rated capacity, at a total rated head not less than 65% of total rated head.The total shut off head shall not exceed 120% of total rated head on the pump. Radiator cooled Engine (2100 rpm) shall capable of driving pumps at 150% of its rated discharge and shall be designed for continous full load duty.\n | 1 | Set | |
4 | 4 | Supply Installation, Testing & Commissioning of Electric Motor Driven Jockey pump capacity 10.8 Cum and 80 mtr head with CI casing, bronze impeller, SS shaft, RPM- 2900 (approx), with adequate motor and accessories | 1 | Set | |
5 | 5 | Supply Installation, Testing & Commissioning of MCC panel for 1 no. EMD pump , 1 no Engine Pump and 1 No. Jockey pump for Auto start stop and other safety features, fabricated from 16 SWG MS sheet as per IS: 2062 with accessories. | 1 | Each | |
6 | 6 | Supply Installation, Testing & Commissioning of CI Gate Valve as per IS: 14846 with fittings | |||
7 | 6.01 | 200 NB | 4 | Each | |
8 | 6.02 | 150 NB | 3 | Each | |
9 | 6.03 | 80 NB | 1 | Each | |
10 | 6.04 | 65 NB | 1 | Each | |
11 | 6.05 | 50 NB | 1 | Each | |
12 | 7 | Supply Installation, Testing & Commissioning of CI swing check type Non-Return Valve as per IS: 5312 with fittings | |||
13 | 7.01 | 150 NB | 2 | Each | |
14 | 7.02 | 65 NB | 1 | Each | |
15 | 8 | Supply Installation, Testing & Commissioning of MS Pipe up to 150 NB as per IS: 1239, part-I (Heavy Grade) and 200 NB and above as per IS: 3589, thk 6 mm with fittings with structural support and paint as per IS: 5 (shade: 536) . For under ground piping 4mm thk wrapping and coating shall be applicable. | |||
16 | 8.01 | 200 NB | 18 | m | |
17 | 8.02 | 150 NB | 18 | m | |
18 | 8.03 | 80 NB | 6 | m | |
19 | 8.04 | 65 NB | 6 | m | |
20 | 8.05 | 50 NB | 6 | m | |
21 | 9 | Supply Installation, Testing & Commissioning of Pressure Gauge 150mm dial with half coupling, nipple, root valve adaptor, 3 waygauge cock, vibration damper as per standard guideline. | 4 | Each | |
22 | 10 | Supply Installation, Testing & Commissioning of Pressure Switch with CI isolation valve with fittings | 5 | Each | |
23 | 11 | Supply Installation, Testing & Commissioning of 3-way Fire brigade inlet with 150 NB Gate valve (fabricated from MS pipe & SS coupling)for reservoir with fittings. | 1 | Each | |
24 | 12 | Supply Installation, Testing & Commissioning of Power & Control cable with fittings | |||
25 | 12.01 | 3C X 150 Sq mm (Al) | 30 | m | |
26 | 12.02 | 3C X 10 Sq mm (Cu) | 30 | m | |
27 | 12.03 | 2C X 1.5 Sqmm (Cu) | 80 | m | |
28 | 12.04 | 12C X 1.5 Sqmm | 30 | m | |
29 | 13 | Supply Installation, Testing & Commissioning of Level Switch with fittings for reservoir | 1 | Each | |
30 | 14 | Supply Installation, Testing & Commissioning of Level gauge with fittings for reservoir | 1 | Each | |
31 | 15 | Supply Installation, Testing & Commissioning of MS Fabricated Suction type strainer and with necessary fittings.\n\n200 NB | 2 | Each | |
32 | 16 | Part B: Hydrant System | |||
33 | 17 | Supply Installation, Testing & Commissioning of MS Pipe up to 150 NB as per IS: 1239, part-I (Heavy Grade) and 200 NB and above as per IS: 3589, thk 6 mm with fittings with structural support and paint as per IS: 5 (shade: 536) . For under ground piping 4mm thk wrapping and coating shall be applicable. | |||
34 | 17.01 | 200 NB | 390 | m | |
35 | 17.02 | 150 NB | 48 | m | |
36 | 17.03 | 80 NB | 24 | m | |
37 | 17.04 | 25 NB | 18 | m | |
38 | 18 | Supply Installation, Testing & Commissioning of CI Gate Valve as per IS: 14846 with fittings | |||
39 | 18.01 | 200 NB | 3 | Each | |
40 | 18.02 | 150 NB | 2 | Each | |
41 | 19 | Supply Installation, Testing & Commissioning of CI swing check type Non-Return Valve as per IS: 5312 with fittings.\n\n150 NB | 2 | Each | |
42 | 20 | Supply Installation, Testing & Commissioning of SS single headed Hydrant Valve as per IS : 5290, type-A with fittings | 18 | Each | |
43 | 21 | Supply Installation, Testing & Commissioning of SS Branch pipe with nozzle(19mm) as per IS: 903 with fittings | 18 | Each | |
44 | 22 | Supply Installation, Testing & Commissioning of 15 mtr long RRL Hose as per IS: 636 with fittings | 36 | Each | |
45 | 23 | Supply Installation, Testing & Commissioning of Hose Reel made of 18 SWG M.S. Sheet along with 30 mtr long and 20 mm dia ISI marked rubber hose with shut-off nozzle as per IS 884. | 12 | Each | |
46 | 24 | Supply Installation, Testing & Commissioning of Hose box fabricated from 16 SWG MS sheet (IS: 513) size: 750 X 600 X 250 mm with 3mm thk glass and fittings | 18 | Each | |
47 | 25 | Supply Installation, Testing & Commissioning of Pressure Gauge 150mm dial with half coupling, nipple, root valve adaptor, 3 waygauge cock, vibration damper as per standard guideline. | 2 | Each | |
48 | 26 | Supply Installation, Testing & Commissioning of CI Air release valve (25NB) with CI isolation valve with fittings | 2 | Each | |
49 | 27 | Supply Installation, Testing & Commissioning of CI Ball valve(25NB) with fittings | 12 | Each | |
50 | 28 | Supply Installation, Testing & Commissioning of 3-way Fire brigade made of CI with 3 nos SS non return valve to be fitted with fir brigade inlet body with 150 NB Gate Valve and nessary fittings. | 1 | Each | |
51 | 29 | Supply Installation, Testing & Commissioning of 2-way Fire brigade made of CI with 3 nos SS non return valve to be fitted with fir brigade inlet body with 100 NB Gate Valve and nessary fittings. | 2 | Each | |
52 | 30 | Part C: Sprinkler System | |||
53 | 31 | Supply Installation, Testing & Commissioning of MS Pipe up to 150 NB as per IS: 1239, part-I (Heavy Grade) and 200 NB and above as per IS: 3589, thk 6 mm with fittings with structural support and paint as per IS: 5 (shade: 536) . For under ground piping 4mm thk wrapping and coating shall be applicable. | |||
54 | 31.01 | 150 NB | 60 | m | |
55 | 31.02 | 100 NB | 708 | m | |
56 | 31.03 | 80 NB | 282 | m | |
57 | 31.04 | 50 NB | 210 | m | |
58 | 31.05 | 40 NB | 324 | m | |
59 | 31.06 | 25 NB | 1890 | m | |
60 | 32 | Supply Installation, Testing & Commissioning of 68 deg C Sprinkler with fittings (Pendent / Upright/Sidewall) | |||
61 | 32.01 | Pendent type | 890 | Each | |
62 | 32.02 | Upright type | 73 | Each | |
63 | 32.03 | Side Wall type | 6 | Each | |
64 | 33 | Supply Installation, Testing & Commissioning of Alarm valve with fittings.\n\n150 NB | 1 | Each | |
65 | 34 | Supply Installation, Testing & Commissioning of CI Butterfly Valve as per IS: 13095 with fittings | |||
66 | 34.01 | 150 NB | 1 | Each | |
67 | 34.02 | 100 NB | 6 | Each | |
68 | 34.03 | 50 NB | 6 | Each | |
69 | 35 | Supply Installation, Testing & Commissioning of Cast Iron wafer type Check Valve as per API : 594 with fittings.\n\n100 NB | 6 | Each | |
70 | 36 | Supply Installation, Testing & Commissioning of 150 NB Cast Iron Double Flange “ Y ? Type Strainer with fittings | 1 | Each | |
71 | 37 | Supply Installation, Testing & Commissioning of Pressure Gauge 150mm dial with half coupling, nipple, root valve adaptor, 3 waygauge cock, vibration damper as per standard guideline. | 1 | Each | |
72 | 38 | Supply Installation, Testing & Commissioning of CI Air release valve (25NB) with CI isolation valve with fittings | 1 | Each | |
73 | 39 | Part D: Portable Type Extinguisher | |||
74 | 40 | Supply Installation, Testing & Commissioning of ISI marked & ISO certified CO2 type fire extinguisher 4.5 Kg capacity conforming to IS 15683 | 12 | Each | |
75 | 41 | Supply Installation, Testing & Commissioning of 9 Ltr Foam type Fire extinguisher. | 2 | Each | |
76 | 42 | Supply Installation, Testing & Commissioning of ISI marked & ISO certified dry Chemical powder type fire extinguisher 6 Kg capacity with GM wheel type cap conforming to IS 15683 | 30 | Each | |
77 | 43 | Supply Installation, Testing & Commissioning of ISI marked water (CO2 gas Expelled) type extinguishers 9 litres capacity with discharge tube, metal cap, 60 grams carbon dioxide cartridge complete in all respects conforming to IS 15683 | 30 | Each | |
78 | 44 | Part E: Signage | |||
79 | 45 | Providing and installing in position the following type AUTOGLO Photoluminescent Signages complete with fastners | |||
80 | 45.01 | Signage with printed "EXIT" (Size: 150mm x 200mm) | 60 | Each | |
81 | 45.02 | Floor identification signage (i.e., 1/2/3....etc) Size 225mm x 225mm at each stair enclosure on every floor | 60 | Each | |
82 | 46 | Providing and fixing in position the signage "FIRE ORDER" it should contain the following matter on 3mm thick "Opaque" PVC foam board of computerized cut ,PVC non-reflective self adhesive vinyl painted foam board of 3' x 4'\n\nA) ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL CALL POINT LOCATED AT STRATEGIC LOCATIONS.\n\nB) EVACUATE THE OCCUPANTS BY USING FIRE EXITS AND EMERGENCY EXITS ONLY AND ASSEMBLE AT VARIOUS ASSEMBLY POINTS.\n\nC) IF POSSIBLE ONE TRY TO EXTINGUISH THE FIRE BY USING NEAREST /SUITABLE PORTABLE EXTINGUISHER OR WATER FROM NEAREST WET RISER.\n\nD) BE CALM AND DO NOT GIVE ANY ROOM FROM PANIC, WALK, DO NOT RUN.\n\nE) IF YOU ENCOUNTER SERIOUS DIFFICULTY IN EVACUATION, FLAT AND TRY TO ATTRACT ATTENTION OF RESCUE TEAM.\n\n\n\n\n | 1 | Each | |
83 | 47 | Part F: Fire Door | |||
84 | 48 | FCD : Fire rated Steel Doors with Steel Frames with ironmongery items comprising of Steel frame having double rebaed frame profile 139 x 57 mm made from 1.5 mm galvanised steel sheets and 45 mm thick shutter made from 0.8 mm thick galvanized steel sheets filled with fire retardant materials suitable for stability and integrity with 120 minutes fire rating conforming to IS : 3614 and finished with Powder Coating of Fire Door with smoke seal, hinges, door closer. Handle and lock. | 54 | m2 |