Public Works Department-PWD has published Repair Maintenance Of Electrical And Mechanical Services At D . C Office Nand Nagri , And Iti Nand Nagri , Delhi . ( Sh-Operation Of Fire Alarm And Vrf/Vrv System At Dc ( Ne ) Office And Replacement Of Defective Fire Alarm System And Improvem. Submission Date for this Tender is 30-09-2020. Fire Alarm Systems Tenders in DC (NE) office complex, Nand Nagari Delhi. Bidders can get complete Tender details and download the document.
Name of Work: R.M.O E & M services at D.C office Nand Nagri, and ITI Nand Nagri, Delhi. (SH:-Operation of Fire Alarm and VRF/VRV System at DC (NE) office and Replacement of defective fire alarm system & improvement of Electrical Installation) | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Providing services of following staff for day to day operation of addressable Fire Alarm System, Detector, all accessories, VRV,VRF etc by providing experienced and qualified staff on all working days excluding Sunday and Holidays in general shift i/c cleaning/ minor repair at DC office Nand Nagari, Delhi\na) Fire Alarm Operator – 1 No \nb) AC Mechanic cum Operator- 1 No. \nc) Khallasi – 1 No. | 12 | Per Month | |
2 | 2 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. "Group C" | 80 | Pts | |
3 | 3 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. | |||
4 | 3.1 | Single pole | 200 | Each | |
5 | 3.2 | Double pole | 15 | Each | |
6 | 4 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) | |||
7 | 4.1 | 6 way, Double door | 6 | Each | |
8 | 4.2 | 12 way, Double door | 2 | Each | |
9 | 5 | Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. | |||
10 | 5.1 | 250 A, 25 kA,TPMCCB | 4 | Each | |
11 | 5.2 | 400 A, 35 kA,TPMCCB | 2 | Each | |
12 | 5.3 | 630 A, 50 kA,TPMCCB | 1 | Each | |
13 | 6 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. | 50 | Each | |
14 | 7 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connection but excluding modular plate etc as reqd. | 50 | Each | |
15 | 8 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.)\n12 way (4 + 36), Double door | 4 | Each | |
16 | 9 | Supplying and fixing of 18 to 20 watt 1200 mm long high efficiency LED linear batten Luminaries having aluminium extruded housing and polycarbonate diffuser within built APFC driver having efficiency of driver 85% power factor > 0.90, THD <20% with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency 100 luman per watt. and colour temperature of 6500 K, CRI >80 including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable with the help of two nos. fastener Hook, etc. as required. | 50 | Each | |
17 | 10 | S.I.T.C 18-20 Watt down light recess mounting LED luminaire fittings professional grade downlight with efficacy of 100im/W. Best suitable for high lux level requirement and replacing existing CFL Downlight suitable for operation on 220 Volt 50 Hz AC supply i/c Pdg. & Fixing suitable for recess, earthing the body complete etc as reqd. | 80 | Each | |
18 | 11 | Supplying Installation Testing and Commissioning of 36 to 40 Watt SMD LED Panel surface mounted type LED Luminaries of size 600 mm (Length) x 600 mm (Width) housing made with white powder coated CRCA sheet metal and polycarbonate diffuser suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency not less than 120 luman per watt. and colour temperature of 6000-6500 K, CRI >80 with driver having power factor > 0.90, THD < 20% and efficiency > 85% driver should be IC Complete, with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable with the help with suitable arrangement of hanging etc. i/c making connections, testing, commissioning etc. complete as required. | 80 | Each | |
19 | 12 | Supplying Installation Testing and Commissioning of 36 to 40 watt surfaced mounted LED Luminaries of size 300 mm (Length) x 1200 mm (Width) housing made with white powder coated CRCA sheet metal and polycarbonate diffuser suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency not less than 100 luman per watt. and colour temperature of 6000-6500 K, CRI >80 with driver having power factor > 0.90, THD < 20% and efficiency > 85% driver should be IC Complete, with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable with the help with suitable arrangement of hanging etc. i/c making connections, testing, commissioning etc. complete as required. | 25 | Each | |
20 | 13 | Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. | 10 | Each | |
21 | 14 | Supplying & Replacement of existing of old worn out of stainless steel storage type water coller 150/150 Ltr. capacity, fully stainless steel suitable for operation on 230 V+10% 50 Hz single phase AC supply i/c making water line and electrical connection etc as required. | 3 | Each | |
22 | 15 | Supplying, installation, testing and commissioning of Following Capacity Split AC type suitable for operation on 230 Volt, 50 Hz Single Phase AC supply with capable to perform cooling, dehumidification, filtering i/c Supplying & fixing of copper tubing and stand etc. complete as required.\n2.0 T R, 5 Star rating | 2 | Each | |
23 | 16 | Fabrication, supplying & errection of wiremesh of netting enclosure made out of 40 x40 x6 mm. Thick (M.S) angle iron & T-section covered with wiremesh of size 75mmx 25mmx6 SWC thick duly welded on angle iron frame work i/c having lockable type openable door with heavy duty godown type lock/padlock type locking arrangement 0.55 mtr. long at the corner & grouting thr legs with C.C of 1:3:6 i/c painting with one coat of red oxide & two coat of enameled painting, welding etc. as required. | 10 | Sqm | |
24 | 17 | Replacement of defective A.C by Supplying, installation, testing and commissioning of following capacity (4500 Kcal) 5 star Split Type Air Conditioner suitable for operation on 230 volt, 50 Hz single phase AC supply with energy efficient rotary compressor with cordless remote, capable of performing, Cooling, Dehumidifying, Air-Circulating, Filtering along with minimum 5 Mtr long copper pipe, insulation and connecting wires with outdoor stand i/c dismantling the existing as required. etc. complete as required.\n1.5 TR | 2 | Each | |
25 | 18 | Replacement of defective exhaust fan by Supplying and Installation of exhaust fan upto 380mm sweep 900 RPM in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning etc. as required. | 6 | Each | |
26 | 19 | Supplying Installation, testing & commissioning of wall fan 400 mm sweep in the existing surface and making good the damage, making connections, interconnections, earthing etc, as required. | 10 | Each | |
27 | 20 | Supply, Installation of 5 KVA Automatic Line voltage correctors and wall mounted type for domestic use, copper wound complete with the voltmeter etc. complete as required. | 2 | Each | |
28 | 21 | Replacement of wornout by Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.\n3 x 4 sq. Mm | 100 | Mtr | |
29 | 22 | Supplying, installation, testing & commissioning of smoke detector with built in LED and mounting base complete with all connections etc. as required. | 40 | Each | |
30 | 23 | Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess assembly complete with glass and push button etc. as required. | 5 | Each | |
31 | 24 | Supplying, installation, testing & commissioning response indicator on surface/recess ABS/MS box having two LEDs metallic cover complete with all connections etc. as required. | 5 | Each | |
32 | 25 | AMC of 165 KVA DG Set installed at G-BLOCK D.C(N.E) Office Nand Nagri including preventive maintenance and break down maintenance of engine/Alternator and other electrical works with AMF Panel and batteries etc. replacement of lube oil filter elements, fuel filter elements pre & micro, air filter elements, Inhibitor Corrosion (Part No. 3167217)-02 Nos., gasket, rocker liver cover, valve cover, valvoline Cummins oil/Oil premium blue-40 Ltr., coolant & lube oil complete as required & Replacement of Following parts\n(a)"B"Check Kit, 6CTA (Part No. KIT 3238543)-02Nos.\n(b ) Element Air Cleaner (Part No. 3815928) - 01Nos.\n(c) Element Air Cleaner (Part No. 3815929) - 01Nos.\n(d) Seal, Rocker Lever Cover (Part No. 3905449) - 01 Nos.\n(e) Belt V-Ribbed\n( Job for 12 Month) | 12 | Per job per month | |
33 | 26 | Supplying & fixing 3 x 10 sq.mm. P.V.C insulated XLPE Al. conducter armoured cable on surface of wall i/c connection testing etc. as required. | 100 | Mtr | |
34 | 27 | Supplying & fixing 3.5 X120 sq.mm. P.V.C insulated XLPE Al. conducter armoured cable on surface of wall i/c connection testing etc. as required. | 100 | Mtr | |
35 | 28 | Refilling of ABC type Automatic Modular fire extinguishers following capacity i/c carrying out to work shop and after refilling, reinstallation at same site i/c pasting sticker. | |||
36 | 28.1 | 5 KG | 3 | Each | |
37 | 28.2 | 10 KG | 5 | Each | |
38 | 28.3 | 15 Kg | 14 | Each | |
39 | 29 | Refilling of the fire Extinguishers of following capacity Co2 type fire extinguishers i/c carrying out to work shop & Back to site etc. as reqd. i/c pasting sticker. | |||
40 | 29.1 | 4.5 Kg | 44 | Each | |
41 | 29.2 | 9 KG | 5 | Each | |
42 | 30 | Refilling of ABC type fire extinguishers following capacity carrying to work shop and after refilling reinstallation at same site i/c pasting sticker. | |||
43 | 30.1 | 5 KG | 24 | Each | |
44 | 30.2 | 6 Kg | 122 | Each | |
45 | 30.3 | 10 Kg | 7 | Each | |
46 | 31 | Supplying & Fixing horn pipe bush rubber hose for the discharge the gas for fire extinguishers complete all accessories etc. as reqd. | 50 | Each | |
47 | 32 | Supplying & fixing M.S stand for the installation of fire extinguishers etc. as reqd. | 50 | Each | |
48 | 33 | Supplying & Fixing Pressure Indicator valve for ABC type fire extinguishers capacity 5KG etc. as reqd. | 50 | Each | |
49 | 34 | Supplying & Fixing valve for Co2 type fire extinguishers capacity 4.5 Kg Complete with all accessories etc. as reqd. | 10 | Each | |
50 | 35 | Less on account of buy back of following dismantled material received from this site. | |||
51 | 35.1 | Wire, Conduit, Switch Socket, MCCB, MCB, DB,TPMCCB, MCB (SP/DP) | 1 | Lot | |
52 | 35.2 | Box type fittings/Mirror optic/Down Lighter | 150 | Each | |
53 | 35.3 | Water Cooler | 3 | Each | |
54 | 35.4 | Assorted A.C | 2 | Each | |
55 | 35.5 | Ceiling Fan | 50 | Each | |
56 | 35.6 | Exhaust Fan | 6 | Each | |
57 | 35.7 | Wall Fan | 10 | Each | |
58 | 35.8 | Horn pir | 50 | Each | |
59 | 35.9 | Pressure Indicator valve | 50 | Each | |
60 | 36 | Valve for Co2 Extinguisher | 10 | Each | |
61 | 36.1 | M.S. Stand for Fire Extinguisher | 50 | Each |