Repair Maintenance Of Air Conditioner Plant And Refrigeration Equipment Installed At Cnbc Geeta Colony Delhi Sh Repairing Work At Different Location At Cnbc, CNBC Geeta Colony Delhi-Delhi

Public Works Department-PWD has published Repair Maintenance Of Air Conditioner Plant And Refrigeration Equipment Installed At Cnbc Geeta Colony Delhi Sh Repairing Work At Different Location At Cnbc. Submission Date for this Tender is 04-08-2020. HVAC Tenders in CNBC Geeta Colony Delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

24999558
Repair Maintenance Of Air Conditioner Plant And Refrigeration Equipment Installed At Cnbc Geeta Colony Delhi Sh Repairing Work At Different Location At Cnbc
Open Tender
Indian
Delhi
CNBC Geeta Colony Delhi
04-08-2020

Tender Details

Repair Maintenance Of Air Conditioner Plant And Refrigeration Equipment Installed At Cnbc Geeta Colony Delhi Sh Repairing Work At Different Location At Cnbc

Key Value

Document Fees
Refer document
EMD
INR 10409.0 /-
Tender Value
INR 5.20 Lakhs /-

BOQ Items

Name of Work: RMO AC Plant & refrigeration equipment installed at CNBC, Geeta Colony, Delhi (SH: Repairing work at different location at CNBC)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supplying, fixing, testing and commissioning of following valves,strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified
2 1.01 a) 150 mm 6 Nos.
3 1.02 b) 125 mm 6 No.
4 1.03 c) 100 mm 4 Nos.
5 2 Supply, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modulating control valve in a single body. The actuator shall be capable of\naccepting upto 10V DC and upto 20 mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum.
6 2.01 a) 150 mm 1 No.
7 2.02 b) 125mm 1 No.
8 3 Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required 14 Set
9 4 Providing & fixing in position the mercury in glass industrial type thermometres. 4 Nos.
10 5 Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS ‘C’ class along with necessary clamps, vibration isolators and fittings such as bends,tees etc..but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:-The Pipes size 150 mm & below shall be M.S. ‘C’ class\nas per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
11 5.01 a) 150mm 30 Mtrs
12 5.02 b) 125mm 30 Mtrs