Description:- Supply,\rTransportation,Installation,Testing&Commissioningofaddressable,resettable Fire\rAlarm Control Panel with character display (LED/LCD) and alphanumeric keyboard. It shall have suitable audio\rvisual alarms for drawing attention/indicating various events. Audio Visual Indication shall be provided on the\rcontrol panel and get activated in case of fire/smoke, trouble/fault and for supervisory functions. It shall be\rpossibletodownloaddataandextendalarmsfromControlPanelthroughsuitableportslike\rRS485/RS232/USB/TCP/IPintoaPC/LaptopattheinstallationandremotelocationoperatingonWindows\rplatform. The panel shall capable to work on: 230VAC power supply, in-built charging facility, battery backup.\rPanel Should Be UL or FM or Vds or LPCB approved. All the above and other features should be as per RDSO\rSpec. no. RDSO/SPN/217/2018 Ver.2.0 or latest. Inspection by RDSO.
4
02
1
380.00
Numbers
2743.50
1042530.00
AT Par
1042530.00
5
Description:- Supply,Transportation,Installation, Testing & Commissioning of Analogue Addressable Multisensor\rDetector with multiple sensitivity( adjustable at site) levels e.g. smoke, heat, rate of rise heat etc, programmable\rfor timed automatic sensitivity selection with base, and other accessories as required. The Detectors/devices must\rhave inbuilt fault isolator or alternate arrangement at detector level which shall isolate the detector in case of short\rcircuit or open circuit in the loop as per the specification No. RDSO/SPN/217/2018 Ver.2.0 or latest. Inspection by\rRDSO.
6
03
1
19.00
Numbers
4222.10
80219.90
AT Par
80219.90
7
Description:- Supply, Transportation,Installation,Testing & Commissioning of Manual call points, addressable &\rresettable,withIn-builtisolatororalternatearrangement.ShallcomplytothespecificationNo.\rRDSO/SPN/217/2018 Ver.2.0 or latest. Inspection by RDSO.
8
04
1
19.00
Numbers
6614.60
125677.40
AT Par
125677.40
9
Description:- Supply,Trasportation,Installation, Testing & Commissioning of Output Module which will provide\rpotential free (NO/NC) contact to existing Data Logger. Complying to the specification No. RDSO/SPN/217/2018\rVer.2.0 or latest. Inspection by RDSO.
10
05
1
38.00
Numbers
5770.20
219267.60
AT Par
219267.60
11
Description:- Supply Transportation,Installation,, Testing & Commissioning of Hooter cum Strobe complying to\rthe specification No. RDSO/SPN/217/2018 Ver.2.0 or latest. Inspection by RDSO.