Design , Supply Installation Testing And Commissioning Of Automation Of Tank Truck Loading System , Tank Farm Management System , Ip Based Cctv Surv . Sys . , Acs , Fire Alarm System , Hydrocarbon Vapour Detection System , Fire Fighting Automatio, Vijayawada, Andhra Pradesh-Andhra Pradesh

Indian Oil Corporation Limited-IOCL has published Design , Supply Installation Testing And Commissioning Of Automation Of Tank Truck Loading System , Tank Farm Management System , Ip Based Cctv Surv . Sys . , Acs , Fire Alarm System , Hydrocarbon Vapour Detection System , Fire Fighting Automatio. Submission Date for this Tender is 18-06-2020. CCTV System Tenders in Vijayawada, Andhra Pradesh Andhra Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

24277891
Corrigendum : Design , Supply Installation Testing And Commissioning Of Automation Of Tank Truck Loading System , Tank Farm Management System , Ip Based Cctv Surv . Sys . , Acs , Fire Alarm System , Hydrocarbon Vapour Detection System , Fire Fighting Automatio
Open Tender
Indian
Andhra Pradesh
Vijayawada, Andhra Pradesh
18-06-2020

Tender Details

Design , Supply Installation Testing And Commissioning Of Automation Of Tank Truck Loading System , Tank Farm Management System , Ip Based Cctv Surv . Sys . , Acs , Fire Alarm System , Hydrocarbon Vapour Detection System , Fire Fighting Automation System Etc Along With Associated Works At Vijayawada

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-May-2020 DATE CORRIGENDUM Date 18-06-2020
2 29-May-2020 PRE BID MEETING REPLY Other 18-06-2020

Key Value

Document Fees
Refer document
EMD
INR 2335722.0 /-
Tender Value
INR 58.42 Crore /-

BOQ Items

Name of Work: Design, supply, installation, testing and commissioning of automation of Tank Truck Loading System, Tank Farm Management System, IP Based CCTV Surveillance System, Access Control System, Fire Alarm System, Hydrocarbon Vapour Detection System, Fire Fighting Automation System etc along with associated works at Vijayawada Terminal, Andhra Pradesh
Sl. No. Item Description Item Code / Make Quantity Units
1 10 SUPPLY PHASE-I 10
2 20 TANK LORRY FILLING 20
3 30 Supply of Microprocessor based Coriolis mass flow meter for white oil application along with display unit and mounting accessories with adjustable screw support,bellow for vibrations etc complete as per specifications and tender document for loading of following main products \nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no additional cost to IOCL. 30
4 40 MS (for line size of 100 mm ) 40 8 EA
5 50 HSD (for line size of 100 mm ) 50 8 EA
6 60 Water (Master MFM for TT calibration) for line size 50 mm along with structural support and required accessories for mounting 60 2 EA
7 70 Supply of Strainer cum Air eliminator with differential pressure transmitter with display unit & keyboard across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 70
8 80 For product line size 100 mm - TLF 80 16 EA
9 90 For Water Line size 50 mm - TT calibration (along with structural support and required accessories) 90 2 EA
10 100 Supply of Multistage Piston type Digital Control Valve (DCV) along with TRV with two nos. isolation valves at inlet and outlet of TRV with associated piping , secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 100
11 110 For product line size 100 mm - TLF 110 16 EA
12 120 For Water Line size 50 mm - TT calibration along with vacuum breaker & isolation ball valve mounted on a spool piece & mounting accessories so that the entire water after DCV is drained into the TT after completion of each batch during TT calibration. 120 2 EA
13 130 Supply of piston type, hydraulically operated ON-OFF Valve along with accessories, secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning ,tubing arrangement as per installation drawing etc for line size 100 mm complete as per specifications and tender document. 130 1 EA
14 140 Supply of Triple Offset Butterfly valve with electrical/electro-hydraulic fail safe actuator ON-OFF along with accessories as per installation drawing etc for line size 100 mm complete as per specifications and tender document. 140 16 EA
15 150 Supply of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF metering skid complete as per specifications and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 150 22 EA
16 160 Supply of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermo well, mounting accessories etc complete as per specifications and tender document. \nNote:Mounting at each TLF loading point on main product for line size 100 mm 160 16 EA
17 170 Supply of online proving valves manifold comprising of 1 no. manual operated DBBV without actuator and 2 nos. of 100 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 170 16 SET
18 180 Supply of bottom loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm), API Coupler, break away coupler, parking stand with compatible API adaptor, Ex-proof/intrinsic safe position sensor for parking stand, associated piping for connecting loading arm with the metering skid , mounting structure etc complete as per specifications and tender document. Application: MS, HSD 180 16 EA
19 190 Supply of vapour recovery arm of size 80 mm NB having 3” (80 NB) with poppeted vapour coupler, break away coupler, NRV, flame arrestor, reducers, mounting structures, parking stand with compatible API adaptor, associated accessories, mounting structure etc complete as per specifications and tender document.\nApplication : MS 190 8 EA
20 200 Supply of Ex-proof Rack Monitors for TT overfill protection system along with accessories like 10 pin gantry plug, ATC copper coiled cable of minimum 8m as per API RP1004 including required support for mounting of the Rack Monitor and gantry plug, etc complete as per specifications and tender document.\nNote: In addition to above, minimum 2 nos. portable Rack Monitor along with accessories and 2 nos. lockable bypass switch are to be provided against total supply of Rack Monitor. 200 8 EA
21 210 Supply of Resistance - Capacitance type Tank Truck grounding unit along with accessories like 3 nos. of heavy duty flexible coiled cables with high quality rugged, heavy duty SS/ brass grounding socket, FLP double compression glands, Ex-Plug, mounting structure etc, complete as per specification and tender documents.\nNote: (2 nos. of coiled cable with socket for TT earthing relay interlocks and 1 no. for separate earthing of TT) 210 8 EA
22 220 Supply of heavy duty SS/brass earthing bolt compatible with offered earthing socket of the grounding unit for mounting on the Tank truck along with accessories like SS nut, lock washer etc complete as per specification and tender document. 220 2000 EA
23 230 Supply of Ex-proof field mounted Remote Interaction Terminal (RIT) along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents. 230 16 EA
24 240 Supply of Ex-proof field mounted Driver Ack Push Button station along with FLP double compression glands and Ex-Proof-plug, structural supports etc complete as per specifications and tender documents. 240 16 EA
25 250 Supply of Microprocessor based Field mounted dual arm Batch Controller with interface to minimum 2 nos. of main product + 2 nos. of blend product + 2 nos. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document.\n\nAlternatively vendor can supply 2 sets of Microprocessor based Field mounted single arm Batch Controller with interface to minimum 1 no. of main product + 1 no. of blend product + 1 no. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc in place of Dual Arm Batch Controller complete as per specification and tender document. 250
26 260 For TLF product loading 260 8 EA
27 270 For TT calibration with water 270 1 EA
28 280 Supply of intrinsically safe / flameproof type proximity card reader along with mounting accessories etc complete as per specifications and tender document for authorisation of TT at 280
29 290 TLF bays (1 no. Per bay) 290 8 EA
30 300 License area Entry barrier gates ( 2 nos. X 2) 300 4 EA
31 310 License area Exit barrier gates ( 1 no. X 3) 310 3 EA
32 320 Security Exit barrier gates ( 1 no.) 320 1 EA
33 330 Security Entry barrier gates ( 1 no.) 330 1 EA
34 340 Near Security Gate/TT parking ( for TT registration ) 340 2 EA
35 350 Supply, configuration and testing of Scratch proof, waterproof Smart cards along with messages printed compatible with proximity card reader complete as per specifications and tender document. 350 1500 EA
36 360 Supply of pre-fabricated Metering Skid (MS structure) for mounting of complete metering equipments as per BOQ and schematic drawing for one main product, one blend product and one additive dosing system. The metering assembly comprises of : \n\nMain product line: Strainer cum Air eliminator, Spool piece with tapping for additive dosing, Online Master Meter proving manifold, MFM,Spool piece with tapping for Temprature Transmitter installation, Pressure transmitter, spool piece with tapping for connecting outlet of TRV, ON-Off valve, DCV, Spool Piece with tapping for Ethanol blending & TRV installation. \n\nBlend Product line: Strainer cum air eliminator, Online Master Meter proving manifold, MFM, Spool piece with tapping for Temperature Transmitter installation, ON-Off valve, DCV, NRV, isolation valve and finally connected to Main stream line tap off point after DCV. \n\nAdditive Dosing System comprises of isolation valve, Additive injection mono block, connecting piping, NRV, isolation valve and finally connecting to Main stream tap off point before MFM. \n\nProvision to be made in the skid for mounting of Batch Controller, Rack Monitor, Grounding unit, RIT, Driver's Ack Push button stations, card reader, FLP sockets, FLP junctions boxes (Power, Signal and Control), FLP power isolator switch, interconnecting cables from respective equipment to JBs, cable trays with covers, glands, support, MS structure,Electroforged galvanized grating, nuts, bolts, gaskets, Tees, bends, elbows, WNRF flanges, nozzles, plugs, isolators, any other equipment if required as per design Engineering etc complete as per specification and tender document. \n\nKindly note, irrespective of facility available or not, each metering skid shall have provision for installation of metering assembly of one main product, one blend product and one additive product as detailed in tender document. \n\nItems including the provision for skid for calibration meters as well. 360 16 TO
37 370 Note: \n1. All the equipments, JBs, cable trays, interconnecting cables etc as stated above to be installed and loop tested at factory. Complete assembly to be dispatched at site. The skid to be designed and fabricated by the party taking into consideration of all the equipment sizing, space available for mounting of the skid at the bottom of the gantry etc. The design Engineering along with weight calculation of individual skid excluding equipments to be submitted to IOCL prior to taking up fabrication job for review purpose. Payment shall be made based on theoretical weight calculation of the skid excluding weight of equipments, JBs, cable trays. The rate is also inclusive of surface preparation, painting, transportation of the skid to site etc complete in all respect. \n2. All unuse nozzle/ tapping/ opening to be blind flanged.\n3. For SKO metering SKID, tapping to be provided in the skid for both bottom and top loading as per design Engineering.\n 370
38 380 Supply of barrier gate of minimum boom length of 3 m along with accessories, controllers etc complete as per specification and tender document for installation at following location. 380
39 390 License area Entry gate 390 2 SET
40 400 License area Exit gate 400 3 SET
41 410 Security Exit gate 410 1 SET
42 420 Security Entry gate 420 1 SET
43 430 DISPLAY BOARDS 430
44 440 Supply of weather proof LED bay queuing display board (Minimum 15 lines x 100 mm Character height x 25 characters per line) for outdoor installation at TT parking area / Customer service building along with accessories like public address system, speakers, amplifier, mike, structural steel for mounting of the same, Aluminium canopy/sunshade etc complete as per specifications and tender document. 440 1 EA
45 450 Supply of LED monitor of minimum 55" along with required hardware and software for interfacing with TAS, lockable enclosure (wall / ceiling mounted) for mounting the monitor along with accessories at Driver's Rest Room for repeat display of 15 lines Bay Queue Display board complete as per specification and tender document. Kindly note, no additional payment shall be made for any additional hardware/ software/ cable etc required for integration of the monitor with TAS. 450 1 EA
46 460 Supply of LED monitor of minimum 55" along with required hardware and software for interfacing with TAS, lockable enclosure (wall / ceiling mounted) for mounting the monitor along with accessories, Aluminium canopy/ sunshade etc at invoice room for displaying the list of TTs whose invoice has been generated and TT is still inside license area complete in all respect as per tender requirement. Kindly note, no additional payment shall be made for any additional hardware/ software/ cable etc required for integration of the monitor with TAS. 460 1 EA
47 470 Supply of weather proof three line coloured LED display board with scroll and flash effects (Each line of min. 50 mm Character height x 11 characters per line) for outdoor application near Security Gate/ TT parking Area and license area Entry barrier Gate along with mounting structure, Aluminium canopy/ sunshade, accessories etc complete as per specifications and tender document for displaying the TT Registration no. in bilingual (English + local language) of reported TT whose proximity card has been shown on the PCR adjacent to the display board for TT reporting at security gate/TT parking area, TT status at TT parking area exit gate and the bay no. (Bilingual) etc of the authorised TT reported at license area Entry Gate as per FDR.\n2 nos. for TT reporting + 1 no. at Security Entry gate + 2 nos. per License Area Entry Barrier Gate (2X2) + 1 No. at Security Exit gate; Total - 2+1+4+1=8\nNote : 1 line for display in English & 2 lines for displaying in local language 470 8 EA
48 480 Supply of 3 KL Stainless Steel Mobile Prover tank along with accessories like flanges, ball valves, calibrated sight glass, plunger, hoses, blind flanges, etc mounted on Trailer chassis along with wheels with solid rubber tyres complete as per specifications and tender document.\nNote: Vendor to arrange for prime mover for calibration of MFM at site during entire commissioning and CAMC period at no additional cost to IOCL. 480 1 SET
49 490 Supply of Mobile Master meter (Master MFM) proving system for line size 100mm consisting of Master Mass flow meter with display unit, Master Temperature Transmitter with RTD with Thermo-well, Mounting accessories suitable for installation on 4" line size, 2 nos. isolation ball valve of 100mm, hose pipe, trolley mounted Master Meter Skid with suitable wheels, FLP JB, FLP double compression glands, power adapter along with accessories (if required) for powering of Master Meter, FRLS Copper Armoured Power & Signal Cable of minimum 15m each with compatible FLP power plugs for powering the MFM, integration of Mobile Master MFM with TAS and integration of temperature transmitter with Master MFM, supports for mounting the equipments, pipes, flanges, reducers, gaskets, nuts, bolts, studs etc complete as per specification and tender document. 490 1 SET
50 500 Ethanol Dosing System 500
51 510 Supply of Microprocessor based Coriolis mass flow meter for white oil (Ethanol) application alongwith display unit and mounting accessories with adjustable screw support, reducer (if required) etc for line size 2" suitable for maximum flowrate of 500 LPM complete as per specifications and tender document for ethanol blending.\nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no adddtional cost to IOCL . 510 8 EA
52 520 Supply of Strainer cum Air eliminator for line size 50 mm with differential pressure transmitter across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 520 8 EA
53 530 Supply of Multistage Piston type Digital Control Valve (DCV), NRV, isolation valve for line size 50 mm alongwith accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 530 8 EA
54 540 Supply of Piston type, hydraulically operated, solenoid operated ON-OFF Valve along with accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves , tubing arrangement as per installation drawing etc for line size 50 mm complete as per specifications and tender document. \n 540 8 EA
55 550 Supply of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermowell for line size 50mm, mounting accessories etc complete as per specifications and tender document. \nNote : One no. of additional thermo well along with accessories to be provided and installed on ethanol point for installation of Master Temperature transmitter with RTD. 550 8 EA
56 560 Supply of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 50 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 560 8 SET
57 570 Supply of 1 KL Stainless Steel Mobile Prover tank alongwith accesories like flanges, ball valves, calibrated sight glass, plunger, hoses, blinds flanges, etc mounted on Trailer chassis along with wheels with solid rubber tyres complete as per specifications and tender document.\nNote: Vendor to arrange for prime mover for calibration of MFM at site during entire commissioning and CAMC period at no additional cost to IOCL. 570 1 SET
58 580 Supply of Mobile Master meter (Master MFM) proving system for line size 50mm consisting of Master Mass flow meter with display unit, Master Temperature Transmitter with RTD with Thermo-well, Mounting accessories suitable for installation on 2" line size, 2 nos. isolation ball valve of 50 mm, hose pipe, trolley mounted Master Meter Skid with suitable wheels, FLP JB, FLP double compression glands, power adapter along with accessories (if required) for powering of Master MFM, FRLS Copper Armoured Power & Signal Cable of minimum 15 m each with compatible FLP power plugs for powering the MFM, integration of Mobile Master MFM with TAS and integration of temperature transmitter with Master MFM, supports for mounting the equipments, pipes, flanges, reducers, gaskets, nuts, bolts, studs etc complete as per specification and tender document. 580 1 SET
59 590 Additive dosing System 590
60 600 Supply of additive injection mono block along with accessories for XTRAPREMIUM and XTRAMILE complete as per specification and tender document. \nNote - All the wetted parts within Additive injection panel/ block shall be of SS 316 or better. 600 6 SET
61 610 Supply of Additive tanks (500 Litres each) and pump module for XTRAPREMIUM /XTRAMILE comprising of Additive Tank, Additive Pumps (Two per tank) , Mild Steel SKID, Flameproof Motor, NRV 25 mm, Flanged ball valve 25 mm, Pressure Relief Valve, Pressure Gauge with pulse dampener, Strainer 25 mm, interconnecting pipings (25 mm SS), flanges etc. auxiliary potential free contact/serial communication complete as per specification and tender document. 610
62 620 For Xtramile 620 1 SET
63 630 For XtraPremium 630 1 SET
64 640 Supply of ASTM A106 Gr B Schedule 80 pipe of 25 NB from additive header pipe to additive injection panel at TLF bay complete as per tender document.. 640 100 M
65 650 Supply of Necessary hardware Like SS Tubing, reducer, Elbows, equal Tee ,unequal tee, Flanges, Coupling, Ball Valve for Isolation, NRV, 15 mm back pressure regulator on return line etc as required for piping and commissioning of the system complete in all respect. 650 1 LS
66 660 Note: Piping from Additive tank skid upto TLF header line up to meter skid along with isolation valve & return line shall be supplied and installed by IOCL. Integration of additive pumps for remote operation, level measurement shall be in the successful bidder's scope. 660
67 670 TLF Header line instruments 670
68 680 Supply of Bulk Air Eliminator as per product line size and flow requirement as per following sizes including mounting structure, foundation etc complete as per specification and tender document. 680
69 690 MS - 2.6 KL 690 1 EA
70 700 HSD - 2.6 KL 700 2 EA
71 710 ETHANOL-0.6 KL 710 1 EA
72 720 Supply of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF main header line complete as per specifications and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 720
73 730 TLF Header 730 4 EA
74 740 Tank Farm Management System 740
75 750 Supply of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 750
76 760 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 760
77 770 HSD 770 4 EA
78 780 BIO-DIESEL 780 4 EA
79 790 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 790
80 800 MS 800 6 EA
81 810 ETHANOL 810 4 EA
82 820 For U/G horizontal product tanks 820
83 830 MS 830 1 EA
84 840 HSD 840 1 EA
85 850 HSD (OWN) 850 1 EA
86 860 ETHANOL 860 1 EA
87 870 BIO-DIESEL 870 1 EA
88 880 Supply of Non-contact type Radar level gauges with instrument accuracy of +/-3 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 880
89 890 FIRE WATER 890 4 EA
90 900 SLUDGE 900 1 EA
91 910 Supply of Guided wave RADAR type level gauge with transmitter , instrument accuracy of +/- 3 mm or better, in built digital display, along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) as per specification. 910
92 920 For Additive Tanks 920 2 EA
93 930 Supply of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. 930
94 940 With minimum 8 elements temperature sensor (for A/G vertical tanks) 940
95 950 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 950
96 960 HSD 960 2 EA
97 970 BIO-DIESEL 970 2 EA
98 980 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 980
99 990 MS 990 3 EA
100 1000 ETHANOL 1000 2 EA
101 1010 For U/G horizontal product tanks 1010
102 1020 MS 1020 1 EA
103 1030 HSD 1030 1 EA
104 1040 HSD (OWN) 1040 1 EA
105 1050 ETHANOL 1050 1 EA
106 1060 BIO-DIESEL 1060 1 EA
107 1070 Supply of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 1070
108 1080 For A/G vertical tanks - Three elements 1080
109 1090 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 1090
110 1100 HSD 1100 2 EA
111 1110 BIO-DIESEL 1110 2 EA
112 1120 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 1120
113 1130 MS 1130 3 EA
114 1140 ETHANOL 1140 2 EA
115 1150 For U/G horizontal product tanks-One element 1150
116 1160 MS 1160 1 EA
117 1170 HSD 1170 1 EA
118 1180 HSD (OWN) 1180 1 EA
119 1190 ETHANOL 1190 1 EA
120 1200 BIO-DIESEL 1200 1 EA
121 1210 Supply of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 1210
122 1220 For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) 1220 18 EA
123 1230 For U/G Product tanks 1230 5 EA
124 1240 For water tanks 1240 4 EA
125 1250 For Sludge tank 1250 1 EA
126 1260 Supply of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document 1260
127 1270 For A/G Vertical Product tanks 1270 9 EA
128 1280 For U/G horizontal product tanks 1280 5 EA
129 1290 Supply of Auto Tank Gauging (ATG) probe combo with density measurement (Wireless or Wired) including necessary accessories as per Tender specifications. 1290 1 EA
130 1300 Supply of parallel redundant Communication Interface Units (CIU) including all accessories etc for tank farm management system complete as per specification and tender document. 1300
131 1310 For Primary Radar gauges installed on A/G vertical , under ground product tank, water tank ,slope ,additive & Sludge tank etc. 1310 1 SET
132 1320 For Secondary Radar Gauges installed on A/G product tanks 1320 1 SET
133 1330 Supply of 1 no. of Redundant TFMS Server (Form Factor:Rack ,Mountable in 19" rack ) along with 1 no. rack type (1U) ,one no. Min. 19" LED monitor with keyboard & mouse ,suitable for 19" mounting & 24x7 operation, Licensed OS (latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed software from Radar Gauge OEM etc complete as per specification and tender document. 1330 1 SET
134 1340 Supply of TFMS Workstation with minimum 27" LED colour monitor, keyboard, mouse, KVM Switch, Licensed OS(latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed client software from same Radar Gauge OEM etc complete as per specification and tender document. \nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 1340
135 1350 19" Rack type at Control Room, form factor - Rack, CPU height - 2U (Maximum) 1350 1 EA
136 1360 Push Buttons Outside Dyke Walls 1360
137 1370 Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. 1370
138 1380 For ROSOVs (A/G product tank's inlet, outlet and recirculation line) 1380 15 EA
139 1390 ESD PUSH BUTTON STATION 1390
140 1400 Supply of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. 1400
141 1410 Local ESD Push Button Station ( Each Battery of TLF -1X1 no., TLF pump house - 1 no.) 1410 2 EA
142 1420 Plant ESD Push Button Station ( Each battery of TLF - 1X1 No.) 1420 1 EA
143 1430 Supply of ESD push button stations (for indoor application), mushroom head type with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. (control room - 1 no., security room - 1 no., TM's cabin - 1 no.) 1430 3 EA
144 1440 Control Room equipments 1440
145 1450 Supply of redundant fault tolerant Integrated Distributed Control System (DCS) along with DCS Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Input Output modules, Power supply units, Relays with base, barriers, TBs, Redundant host communication ports, Serial Interface Modules, HART modules, other communication modules, HMI , wirings, glands, plugs, other modules/ hardware required for interfacing with all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: Any other hardware, software, OPC server, Historian Server, storage, firewall, functional control key board etc required as per tender specification and design requirements, the same to be provided by the vendor at no additional cost to IOCL. 1450 1 SET
146 1460 Supply of Complete Terminal Automation Software along with required licences, dongle/keys, GUI, SCADA etc meeting the complete functional and technical requirements of the tender document. \nVendor to provide required software, licences, dongle/keys, GUI, SCADA etc for TAS Management Server, Distributed Control System, Operator work stations, fire fighting OIC, Alarm display and annunciation OIC, Engineering Work Stations(for safety PLC & DCS), Web Server, OPC Server, Historian Server / work station, any other devices connected to Control & Management LAN of the integrated Distributed Control System complete as per specification and tender document.\nTAS software shall be interfaced with following but not limited to major sub-systems / equipments alongwith GUI development for monitoring, logging, reporting, controls & interlocks etc as per specification and tender document.\n- Safety PLC\n- TAS - Management Server\n- TLF Automation System (TT reporting, registration & entry system, TT Queuing, FAN generation, TT registration number reading system, Photo pass management system,TT crew authorization system, Bay allocation, Additive Dosing system, Ethanol blending System, Interface with TLF equipments like BCU, MFM, Barrier Gates, Bay Queue Display, Bay allocation Display, Invoice generated display, rack monitors, Proximity card readers etc)\n-Tank Lorry Decantation System\n-TT calibration System\n-Bio Diesel Blending system \n- ANPR and Face recognisation 1460 1 LS
147 1470 -- Valve Automation System (ROSOVs, MOVs, DBBV, MCS Interface, SOVs, etc)\n-Tank Farm Management System ( TFMS Server, Primary & Secondary Radar Gauging, AOPS, Level transmitters, Level Switch, Density probes, MSTW, CIU etc)\n- Pipeline/ Refinery PLC Interface, OMC PLC interface\n - MCC, Pump, Borewell, DG Sets, Air compressors, VFDs\n- PA paging Interface \n- HC Detection System Interface\n-FAS Interface, Fire Fighting System, HVLR, Fire Alarm System Interface, Fire Engines, DG Set, Jockey pumps, Foam pumps, CFFS, Sprinkler & Fixed foam pourer system etc\n- VRU Package Units\n- Effluent Treatment plant\n- CCTV systems\n- Access Control System\n- SKO Blue Dye Dosing System\n- ESD System, Emergency panel, Power ESD, Local ESD, Wailing sirens\n- Pressure Transmitters\n- UPS & Power distribution boards etc\n- Interface with IOCL SAP through firewall\n- Visitor Management Software for setup, configuration, operation, events, history and archiving, recording, printing etc. complete as per specification and tender document - Any other Third Party Interface/ devices as per scope of the work order etc\nNote: The offered software shall also includes fault detection module and Web Server software for remote over IOCL Intranet across India as detatiled in the tender document.\n\n\n\n 1470
148 1480 Supply of Redundant SIL 3 TUV/ EXIDA certified Safety PLC along with PLC Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Dual redundant Input Output modules, Power supply units, Relays with base, barriers, TBs, Dual Ethernet ports per processor, Serial Interface Modules, HMI , wirings, glands, plugs, other modules/ hardware required for interfacing all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: The offered safety PLC shall be of the same make family of the integrated Distributed Control System. 1480 1 SET
149 1490 Supply of redundant TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LCD/LED monitor of minimum size of 19" suitable for 24x7 operation along with High availability redundancy software working on redundant (Primary and Secondary) hot standby mode , keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document.\n OR\nSupply of Dual Mode Redundant Grade with built in redundancy TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 19" suitable for 24x7 operation, keyboard drawer, optical mouse and combo 4 port KVM switch (if required), OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document. \n\nTAS Management Servers (TAS-MS) shall have either of the above mentioned configuration meeting the complete specification and tender requirements. \n\nIn addition, the TAS-MS shall be configured to have Zero Downtime to repair, Full data redundancy shall be provided using proven technology , it shall also provide port level redundancy.The system solution shall be capable of self fault detection and isolation, all necessary hardware/software configuration etc to achieve the same shall be included. 1490 1 LOT
150 1500 Supply of 42 U Rack Enclosure cabinet/System cabinet with 19" rack size, along with accessories like Biometric fingerprint cum contactless smart card reader for front & back door seperately with accessories, limit switches, earthing arrangements, breaker, fuses, terminal blocks and wiring etc complete as per specification and tender document for mounting of below mentioned equipments. 1500
151 1510 For mounting of TAS Management Servers along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, Ethernet switch, GSM modems, MCBs etc as per specification and tender document. 1510 1 EA
152 1520 For mounting of Redundant ACS cum photopass management Server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking components, MCBs etc as per specification and tender document. 1520 1 EA
153 1530 For mounting of Redundant TFMS Server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, CIUs, MCBs etc as per specification and tender document. 1530 1 EA
154 1540 For mounting of Rack mounted Master Control Stations for MOVs & DBBVs along with power adaptors, MCBs, required accessories etc as per specification and tender document. 1540 2 EA
155 1550 For mounting of Rack mounted CPUs of Control room console workstation (Rack type) , one number 19" rack mounted monitor, rack mounted keyboard, mouse, KVM switches for connection of all CPUs along with power adaptors, MCBs, required accessories etc as per specification and tender document. 1550 2 EA
156 1560 For mounting of Network equipments along with power adaptors, MCBs, required accessories etc as per specification and tender document. 1560 1 EA
157 1570 Supply of Operator Interface Console Computer (OIC) with minimum 27" colour LED monitor,keyboard, mouse,KVM Switch, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. CPU shall be kept in Panel room in 42 U Rack. \nNote: CPU of control room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 1570
158 1580 19" Rack mounted at Control Room, form factor - Rack , Max. 2U height ( 3 OICs, 1 for alarm Display, 1 for fire fighting System) 1580 5 EA
159 1590 Supply of Operator Interface Console Computer (OIC) minimum 27" colour LED monitor,keyboard, mouse, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. 1590
160 1600 Tower type in TM's Cabin 1600 1 EA
161 1610 Supply of Engineering Workstation (EWS) with minimum 27" colour LED monitor, keyboard, mouse, KVM Switch, Safety PLC & DCS software, HMI software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. (Locations: 1 no. in CR for both DCS and Safety PLC) \nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 1610
162 1620 19" Rack mounted at Control Room, Form factor - Rack , Max. 2U height 1620 1 EA
163 1630 Supply of Tank Truck Entry System (TTES) Workstation with minimum 27" colour LED monitor, keyboard, mouse,KVM switch, software, SCADA, GUI, OS, Antivirus etc. complete as per specifications and tender document. (Locations: 2 nos. in Customer service Block +1 no. in Control room+1 no. in Lock shed room) \nNote: CPU of control room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 1630
164 1640 19" Rack mounted at Control Room, Form factor - Rack , Max. 2U height 1640 1 EA
165 1650 Tower type in Customer service block (2 nos.) and Lock shed room (1 no.) 1650 3 EA
166 1660 Supply of minimum 19" colored LED monitor (19" Rack type at panel Room, form factor - Rack, height - 1U) with , KVM switch, Rack type keyboard, mouse etc located in Control Room complete as per specifications and Tender Document. (For CPUs of Console kept in panel room) 1660 2 EA
167 1670 Supply of Web Server (Rack type mountable in 19" rack ) , Rack type CPU - 2U Max. , LED monitor of minimum size of 27" suitable for 24x7 operation, keyboard, mouse, KVM Switch, web application software, SCADA, GUI, OS, Antivirus etc located in panel Room complete as per specifications and Tender Document. \nNote: CPU of control room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 1670 1 EA
168 1680 Supply of the NMS System covering Network Devices operational in Terminal Automation System. The Offered Network Management Solution (NMS) solution should support at least the following:\n• All the proposed NMS Components should be from single vendor. \n• NMS Software should support Graphical view up to port level for the all the devices.\nDiscovery of Network Elements.\n• Real time Traffic monitoring of Network Links and Devices with Historical reports for various periods.\n• Management of SNMPv1, SNMPv2, SNMPv3 & MIB etc.\n• Configuration of thresholds for Generating alarms.\n• Configuration of alarm actions (visual, audible, email, sms etc.) for each \nNetwork element.\n• Should be able to provide secured windows based consoles / secured web based consoles for accessibility to NMS.\n• Should have web browser interface with user name and Password Authentication.\n• Administrator/ Manager should have privilege to create/modify/delete user.\n• NMS should have support for SNMPv3 & IPv6, including dual-stack IPv4 & IPv6 to provide flexibility in protocol strategy and implementation.\n 1680 1 LS
169 1690 Supply of Terminal servers (rack mounted) with inbuilt/externally mounted lightening and Surge Protection Device Type (1+2) at all Serial ports, for interfacing and integration of field devices (Indoor & outdoor), LED Display unit for TT reporting,at Main Entry gate & Exit gate and TLF Entry gate for Bay allocation with TAS.In case the above listed equipments do not come with open communication protocol compatible to be directly interfaced with DCS Serial / MODBUS TCP IP module complete as per specification and tender document.\nNote: Terminal Servers to be configured in Dual Redundant mode. 1690
170 1700 16 ports at Control Room/Customer service Room 1700 2 EA
171 1710 Supply of 24 ports Layer 3 Managed Ethernet Switches (10/100/1000 MBPS) with SFP, copper, fibre modules/ports along with accessories for connecting Plant management LAN equipments like CCTV System, TAS - MS Server/ Redundant OPC server, TFMS Server, TFMS work station, OICs, IOCL intranet for SAP connectivity through fire wall, Network printers, Access Control Server, Web Server Access over IOCL Intranet, connecting to OIC/ work stations etc which needs to be connected to both Plant Management LAN and Plant Control LAN for getting the entire GUIs of Complete Terminal Automation System and any other third party devices for interfacing with DCS etc.\nNote: \n1. Ethernet Switches to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs and any other equipment which are to be connected to above switch and the communication is through OFC cable. 1710 2 EA
172 1720 Supply of minimum 24 ports Layer 2 Managed Ethernet Switches (10/100/1000 MBPS) along with SFP, copper, fibre modules, accessories for connecting equipments installed in Plant Control LAN like TAS- MS Servers, OICs, TTES cum TWES , EWS, OPC Servers, Fire fighting OICs, Alarm Display OIC, DCS, Safety PLC, inter connecting building work stations etc as per system architecture and design requirement complete as per specification and tender document.\nNote:\n1. The switches are to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs, and any other equipment which are to be connected to above switch and the communication is through OFC cable. 1720 2 EA
173 1730 Supply of Layer 2 Managed Ethernet Switches along with accessories for connecting BCU with TAS, equipments installed in Customer service room, Lock room, Security room, Terminal Manager room and other TAS equipments as per system architecture and design requirement complete as per specification and tender document.\nNote: \n1. Ethernet switches for BCU communication shall have suitable mounting arrangement to mount inside FLP JBs. \n2. The switches are to be configured in Dual Redundant mode.\n3. All OICs, Workstations, Servers other than that of CCTV, ACS & TFMS are to be connected to both plant management and control LAN so that all the GUIs can be seen in all the PCs irrespective of its nomenclature like TTES, OIC, EWS, TM PC etc.\n4. Printers to be connected to Plant Management LAN and to be configured to all PCs, Workstation, TTES etc so that printout command can be issued from any of the Machine. 1730
174 1740 For BCU integration at TLF (copper ports of 10/100/1000 MBPS)-( Minimum 8 nos. copper ports and 2 nos. optical ports) 1740 6 EA
175 1750 For BCU integration at TT Calibration shed-2 Nos (copper ports of 10/100/1000 MBPS)-(Minimum 4 nos. copper ports and 2 nos. optical ports) 1750 2 EA
176 1760 For connecting all MODBUS TCP IP devices ( any other devices) to DCS Ethernet port directly for integration (copper ports of 10/100/1000 MBPS)- to be located in Control Room ( Minimum 8 nos. copper ports and 2 nos. optical ports) 1760 2 EA
177 1770 At Lock Shed - copper ports of 10/100/1000 MBPS [control LAN - 2 nos. & Management LAN - 2 nos.] ( Minimum 8 nos. copper ports and 2 nos. optical ports) 1770 4 EA
178 1780 At Admin Building for TM cabin - copper ports of 10/100/1000 MBPS [control LAN - 2 nos., Management LAN - 2 nos., CCTV - 2 no.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 1780 6 EA
179 1790 At Security Room - copper ports of 10/100/1000 MBPS [Management LAN - 2 nos.,CCTV - 2 no.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 1790 4 EA
180 1800 At Driver rest room - copper ports of 10/100/1000 MBPS [Managent LAN - 2 nos.] (Minimum 4 nos. copper ports and 2 nos. optical ports) 1800 2 EA
181 1810 Supply of industrial grade redundant Serial to Ethernet converter of 8 port with mounting acessories etc complete in all respect as per specification and tender document. (Ports:- 6 Main + 2 Spare) 1810
182 1820 For MFM and other serial devices integration to DCS -TLF 1820 3 EA
183 1830 Supply of Wall mounted/wheel mounted Network Rack-minimum 19U 19" Rack for mounting of Terminal Server/Ethernet switches/LIU/ OFC components along with accessories like power sockets, MCBs, fan, mounting accessories etc complete in all respective at Security Room, TM room, Invoice Room for TAS equipments 1830 4 EA
184 1840 Supply of Monochrome Laser Printer along with accessories for TAS and TFMS report printing in control room (2 nos.) and 2 nos. at security room complete as per specifications and tender document. 1840 4 EA
185 1850 Supply of heavy duty high speed laser printer and accessories for invoice printing in lock shed room, complete as per specifications and tender document. 1850 2 EA
186 1860 Supply of parallel redundant UPS of minimum capacity of 60 KVA or as per load calculation (whichever is higher) for entire TAS equipments and third party devices integrated with TAS and powered through TAS UPS with 30% spare capacity for future load connection. The scope also includes supply of parallel battery bank (2x50%) for minimum back up time of ½ hour at full load (rated capacity) along with stand, supports for mounting of the UPS and batteries etc complete as per specification and tender document. The batteries shall be Sealed Maintenance free type. 1860 1 SET
187 1870 Supply of UPS Power Distribution Panel along with Biometric fingerprint cum contactless smart card reader for front and rear gate sepearately with accessories for powering DCS Panel, Safety PLC Panel, TAS-MS, OIC, EWS, TFMS System, TTES, printers, Bay Instruments other control room equipments, Tank Farm Instruments, CCTV system, Fire Detection System, Access control system, Bay Queue Display boards, other display boards, ROSOV ESD port, header line instruments and any other TAS equipments where UPS power are required for smooth un-interrupted operation. Miscellaneous Instrumentation comprising of suitable MCCBs for Isolation, MCB etc are to be provided. The panel shall be complete in all respects with necessary indication lamps for powering, necessary control wiring with digital voltmeter & digital ammeter separately for UPS and Auxilliary supply for front and rear seperately etc as per specifications and tender document.\nNote: Minimum 20% spare power points to be made available for future use. 1870 1 LS
188 1880 Supply of Open desk operator consoles, chairs, printer tables etc complete as per specification and tender document. 1880
189 1890 Open desk operator consoles for mounting of monitor in two tiers , 2 nos. of key boards, 2 nos. of mouse, accesscories e.g. Telephone,VHF sets, Master control station for PA paging,storage etc complete as per specification and tender document.\n(For mounting of 3 nos. OICs monitor, 1 no. Alarm Display OIC monitor, 1 no. Fire fighting OIC monitor, 1 no. TTES monitor , 1 TFMS workstation monitor, 1 no. CCTV client monitor,1 no. EWS monitor,1 Web server, storage etc.) 1890 7 EA
190 1900 Chairs (Godrej interio Ace Mid back high performance chair) 1900 7 EA
191 1910 Standard Printer Tables of Godrej or equivalent make (2 nos. at security gate, 1 no. in Lock shed room, 1 no. in security room for visitor management) 1910 4 EA
192 1920 Standard Computer Table of Godrej or equivalent make for installation of CCTV client , ACS client in security room (2 nos.),Photo pass management PC (1 No.), TTES in Customer service room (2 nos.) and TTES in lock shed room (1 no.) 1920 6 EA
193 1930 Supply of IP based Redundant GSM modem suitable for 24x7 operation along with accessories for auto SMS as per specification and tender document. 1930 1 SET
194 1940 Hydrocarbon Detection system 1940
195 1950 Supply of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document. 1950
196 1960 Point type Infrared detector\n(Indicative location: Each tank dyke sump pit inside dyke wall - 5 nos., Near ROSOVs of MS tanks:-3 Nos., Ethanol tanks- 2 nos., TLF pump seal (MS+Ethanol) - 8 Nos,Sludge pump seal-2 No., Pump house drain pit - 2 no.; Vapour recovery system drain pit - 1 no.,ETP-1 No.) 1960 24 EA
197 1970 Open path type Infrared detector (10-90 m) along with alignment telescope, configuration & Testing kit etc (Tentative location: MS tanks - 8 Nos. & Ethanol tanks covering ROSOVs - 4 nos.) 1970 12 EA
198 1980 Open path type Infrared detector (10-120m) along with alignment telescope, configuration & testing kit etc (Tentative location: TLF PH-3 Nos) 1980 3 EA
199 1990 Supply of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessories and structural supports as per specification.( Tentative location : Each product tank dyke (MS)-1 No.,(Ethanol)-1 No., Pump House (TLF) - 1 No.,ETP-1 No.,VRU-1 No.) 1990 5 EA
200 2000 Supply of one no. of Portable Hydrocarbon vapour detector along with accessories complete as per specification and tender document. 2000 1 EA
201 2010 Automatic Fire Detection and Alarm System 2010
202 2020 Supply of microprocessor based automatic Fire Alarm Panel along with required Software, and hardware like Control module, monitor module, fault isolation module (in built/ External), mounting structure support etc complete as per standard design engineering, specification and tender document.\nLocation : Control Room 2020 1 EA
203 2030 Supply of Repeater Panel along with software, hardware, mounting accessories etc required as per standard design Engineer, specifications and tender document complete in all respect. \n(Tentative location : Security Gate - 1 no., Fire Pump House - 1 no.) 2030 2 EA
204 2040 Supply of addressable type detectors along with accessories, fault isolation module (Inbuilt/ External), structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 2040
205 2050 Combination/Multi-sensor Detector 2050 106 EA
206 2060 Rate of Rise Heat Detector 2060 3 EA
207 2070 IS detector 2070 4 EA
208 2080 Hydrogen Detector 2080 2 EA
209 2090 Supply of Manual Call Point along with accessories, fault isolation module (Inbuilt/ External) and structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 2090
210 2100 Ex-proof and weather proof MCP 2100 17 EA
211 2110 Weather proof MCP 2110 11 EA
212 2120 Supply of Hooter along with accessories, fault isolation module (inbuilt/ External), structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 2120
213 2130 Weather proof Hooter (Admn bldg-2, CR-1, MCC room-2, Fire pump house - 1, security room-1, TT rest room - 1, aminity room-1 no., Lab -1 NO., sample room-1 no.) 2130 11 EA
214 2140 Supply of Response Indicator along with accessories, mounting structure etc required as per standard design engineering, specification and tender document complete in all respect. 2140 40 EA
215 2150 Access Control System 2150
216 2160 Supply of half man height bi-directional turnstile (tripod) with controller along with accessories, mounting structure, pressure sensor etc required as per standard design engineering, specification and tender document complete in all respect. (Location : License area entry & exit gate - 2 nos. ; Entry/Exit to tank farm area - 2 nos.) 2160 4 EA
217 2170 Supply of half man height dual lane Uni-directional turnstile (tripod) with controller along with accessories, mounting structure, pressure sensor etc required as per standard design engineering, specification and tender document complete in all respect. (Location : At security entry gate -1 SET., security exit gate - 1 SET) 2170 2 SET
218 2180 Supply of Retractable Dual Lane Flap barrier with controller along with accessories, mounting structure, pressure sensor etc required as per standard design, engineering, specification and tender document complete in all respect. (Location: Admin building entry/exit ) 2180 1 SET
219 2190 Supply of face detection cum fingerprint cum contactless type smart card reader with controller along with electromagnetic door lock of 600 lb for single door/double door, 2 nos. of door position magnetic contact with buzzer etc as per specifications and tender document. (Location : control room entry/exit door - 2 nos., Panel room entry/exit door - 4 nos. ). \nNote: EM locks to be provided at no additional cost to IOCL. 2190 6 EA
220 2200 Supply of Biometric fingerprint cum contactless type smart card reader along with accessories, software , programming kit etc required as per standard design engineering, specification and tender document complete in all respect. (Turnstile:- security entry/exit gate -Dual Lane-Uni directional : 2x2 nos. license area entry/exit gates (bi-directional) - 2x2 nos., entry/exit to tank farm area (bi-directional)-2x2 nos.,Flap barrier - 2x2nos.) 2200 16 EA
221 2210 Supply of 2 No. Door Frame Metal Detector, 4 nos. hand held metal detector along with accessories, mounting structure etc complete as per specification and tender document. 2210 1 SET
222 2220 Supply of 2" size SS 304 guiding rail along with mounting accessories complete as per specification and tender document near turnstile/ tripod/flap barrier etc to prevent un-authorised movement. 2220 100 M
223 2230 Supply and configuration of Proximity smart access cards as per the specification and tender document. 2230 500 EA
224 2240 Supply of Redudnant ACS Server for photo pass management & visitor management (19" Rack type at panel Room, form factor - Rack, CPU height - 2U) with minimum 19" colored LED monitor, KVM switch, keyboard, mouse, OS, Antivirus etc located in Control Room complete as per specifications and Tender Document. 2240 1 SET
225 2250 Supply of Access Control cum photopass management System Software for setup, configuration, operation, events, history and archiving, alarm monitoring, recording, printing, time and attendance etc. complete as per specification and tender document including hardwired interface with TAS for ESD input. 2250 1 LS
226 2260 Supply of Client workstation of ACS cum Photopass management with minimum 27" coloured monitor,keyboard, mouse,KVM switch (extender/reciver) for Rack CPU, OS, Antivirus, HD coloured video camera (for taking visitors photograph) etc for ID badging & issuing of Visitor pass/Photo pass at security Room & other etc. complete as per specifications. 2260
227 2270 Rack Type - CPU in panel room with KVM sitch; Keyboard, mouse along with monitor etc. to be installed in security room for visitor pass 2270 1 EA
228 2280 Tower Type in Photopass room for TT crew/Contractor etc. 2280 1 EA
229 2290 Supply of Laser printer (Monochrome) for Visitor pass printing having flexibility to print on A4, A5, A6 paper complete as per specification and tender document. 2290 1 EA
230 2300 Supply of Colour photo pass printer along with integrated/seperate scanner for photo pass printing as per specification and tender document. 2300 2 EA
231 2310 Supply of PVC cards for printing of photo pass as per specification and tender document. 2310 1000 EA
232 2320 IP BASED CCTV SURVEILLANCE SYSTEM 2320
233 2330 Supply of 4 port Industrial grade layer 2 Managed POE based Ethernet Switch for connecting Cameras with 4 Nos. RJ copper port and 2 Nos. optical fibre ports with inbuilt/external surge protector (Type 1+2) at the input power supply as per specifications and Tender Document. 2330 3 EA
234 2340 Supply of outdoor Explosion proof cum weatherproof housing (IP 65 or better) suitable for installing Layer 2 switch, PSU, LIU and adaptor for Ethernet switch/media convertor, surge protectors and other accessories of CCTV cameras. Supply of required OFC components & accessories like LIU, splice trays, loaded adaptor, blank plates, UTP cables, Fibre patch cords, pigtails, tags, ties, Ethernet cable with RJ45 connector etc complete in all respect for functioning of CCTV camera.The scope also includes supply of Exd. blinding plugs, Exd. double compression cable glands etc as per specifications and Tender Document. 2340 3 EA
235 2350 Design, fabrication and supply of Heavy Duty self supported Hot Dip Galvanized Poles for mounting of CCTV cameras along with civil foundation along with GI foundation bolt, mounting brackets, ladder arrangement (taking into account of safety during climbing) on the pole for installation and maintenance of cameras, SS nut & bolts for fixing camera and other accessories required for complete installation and commissioning of the pole, submission of structural stability certificate based on existing soil bearing capacity and wind speed from Govt. Engineering colleges etc complete as per specifications and Tender Document of below mentioned height of the pole. (Foundation drawing and other details to be submitted prior to installation as per tender document)\nNote: In case pole do not have ladder arrangment for maintenance purpose, then vendor to arrange for ladder for installation & maintenance purpose throughout the contract period including CAMC period at no additional cost to IOCL. 2350
236 2360 4/6 M pole with Accessories as per specification of Tender 2360 6 EA
237 2370 Design & Supply of video wall along with required controller & complete accecories , cables etc , mounting arrangement from wall/ceiling for fire fighting cum critical Alarm display & annuniciation cum CCTV application complete as per specifications and tender document. \nIn control room:-Windows for all cameras should be available on single screen of 300-400 cm2 for min. 150 no. CCTV camera.\n\nNote: Two Number (min. 55” each or meeting size of video wall) for Alarm LED display and Fire fighting display along with one no. of hooter with provision of dual tone sound,ack push button & accessories. 2370 6 EA
238 2380 Design & Supply of video wall along with controller & complete accecories , cables etc. for CCTV complete as per specifications and tender document. In location in charge room:-viewing window size should be preferably be between 250-300 cm2 (in two pages) for CCTV camera. 2380 2 EA
239 2390 Design & Supply of video wall along with controller & complete accecories , cables etc. for CCTV complete as per specifications and tender document. \nIn security cabin:-viewing window size should be preferably be between min. 150-200 cm2 ( in two pages) for CCTV camera. 2390 2 EA
240 2400 Supply of 350 W LED flood ONLY light luminaries on Light poles up to 10M height including supply & fixing of clamps, scafolding , temporary fire screen ifrequired, supports, nuts,bolts, earthing , required modification infixing arrangement , Supply and welding of mounting structure as persite condition , painting etc. all complete with labour and materials asper drawings, specifications and directions of the Engineer-in-Charge. 2400 6 EA
241 2410 Supply of IP Fixed Bullet cameras with IR MFZ lens (8MP) – 4K resolution along with power supply unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document.(TT Reporting :-2+TTEntry/Exit:-2+Driver Entry/Exit-2,Helper Entry/Exit-2, Photo Pass issuance:- 2) 2410 10 EA
242 2420 Miscellaneous 2420
243 2430 Supply of flameproof cum weather proof to IP 65 or better SIL 2 smart pressure transmitter with in built display, SS manifold, isolation valve, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender)\nNote:1. Pressure transmitter at suction shall have range from -1 Kg/cm2.\n2. Underground tank shall have PT in Pump discharge end only. 2430
244 2440 TLF pump Suction end 2440 18 EA
245 2450 TLF pumps Discharge end 2450 18 EA
246 2460 MS, HSD, Transmix, Ethanol Tanks Sprinkler & Foam Line 2460 40 EA
247 2470 Fire Engine & Jockey Pump 2470 12 EA
248 2480 Sludge/Stripping Pumps suction end---Remote Seal Type 2480 4 EA
249 2490 Sludge/Stripping Pumps discharge end---Remote Seal Type 2490 4 EA
250 2500 Underground tank's pump discharge end 2500 7 EA
251 2510 Supply of flameproof cum weather proof to IP 65 or better SIL 2 Smart Differential pressure transmitter with in built display, SS 3 way manifold, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender) 2510
252 2520 Across TLF pump Strainers 2520 18 EA
253 2530 Across Sludge/Stripping Pumps Strainers---Remote Seal Type 2530 4 EA
254 2540 Supply of flameproof cum weather proof to IP 65 or better bi-colour magnetic flap type level gauge (side mounted) along with level transmitter with installed accuracy +/- 6 mm or better along with mounting accessories, complete as per specification and tender document. 2540
255 2550 Foam (Daughter+Mother) Tanks for HVLR 2550 12 EA
256 2560 Fire Engine Service tanks 2560 8 EA
257 2570 DG Set Service Tanks 2570 3 EA
258 2580 Supply of Level switch ( Magnetic Float / displacer type ) for low and high level alarm along with mounting accessories etc as per specifications 2580
259 2590 Fire water Sump 2590 1 EA
260 2600 TT calibration sump 2600 1 EA
261 2610 Treater water Tank + Service water 2610 2 EA
262 2620 Raw water sump 2620 1 EA
263 2630 Supply of Wailing siren along with controller with a provision to operate locally as well as from control room, mounting accessories etc complete as per specification and tender document. 2630 1 EA
264 2640 Supply of Digital Rodent Repellent System along with mounting accessories for main controller(s) & transducers etc complete as per specification and tender document (Minimum nos of transducers: Control Room - 12 nos., S&D room-4 Nos., Invoice room - 4 nos. & Security Room - 4 nos.) 2640 1 LS
265 2650 Supply of Ex-proof and weather proof Hooter cum Beacons along with accessories, mounting structure etc complete as per specification and tender document for audio visual alarm at field in case the MOVs installed at tank dyke drain and tank water draw off line is not fully closed. \nLocation : Near each tank dyke and to be installed outside dyke. 2650 6 EA
266 2660 Supply of solenoid valves (SOV) of 25/32/50/65 NB (as per line size) along with one no. of isolation by pass valve to bypass the SOV with associated piping, mounting accessories etc complete as per specification and tender document. \nNote: SOV need to be supplied factory fitted along with baypass valve and both side flanged option.For Ethanol tank HVLRs SOV is not required. 2660
267 2670 At the inlet of DG set Service tanks 2670 3 EA
268 2680 At the inlet of Fire Engine Service tanks 2680 8 EA
269 2690 At the inlet of HVLR tanks 2690 8 EA
270 2700 Supply of MCT block for entire Automation cable entry to Control Room, Admin Building, Invoice Room, Security Room, Customer service room, Driver's Rest Room with minimum 30% spare MCT blocks for future cable entry along with frame and mounting accessories complete as per specification and tender document. 2700 1 LS
271 2710 Supply of external surge & Lightening protection devices of suitable connector and type along with accessories complete as per specification and tender document at following places. 2710
272 2720 SPD (Type 2 / IC category C1,C2,C3,D1) - Serial port of MCS (RJ45 type) & Terminal Server 2720 42 EA
273 2730 Type 1 SPD - Earth pit 2730 10 EA
274 2740 Supply of Magentic Flow Meter in water line in outlet of borewell along with two number of SS ball valve and associated piping as tender specification and mounting accessories complete as per specification and tender document. 2740 1 EA
275 2750 Cabling, JB, Earthing: 2750
276 2760 Note: Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc 2760
277 2770 Supply of FRLS Armoured Copper Power cable as per tender specifications. 2770
278 2780 3C x 2.5 sqmm 2780 10875 M
279 2790 4C x 2.5 sqmm 2790 1650 M
280 2800 8C x 2.5 sqmm 2800 3600 M
281 2810 10C x 2.5 sqmm 2810 2850 M
282 2820 12C x 2.5 sqmm 2820 1650 M
283 2830 24C x 2.5 sqmm 2830 2700 M
284 2840 3C x 4 sqmm 2840 4500 M
285 2850 4C x 4 sqmm 2850 1800 M
286 2860 4C x 6 sqmm 2860 75 M
287 2870 4C x 10 sqmm 2870 75 M
288 2880 Supply of FRLS Armoured Aluminium Power cable as per tender specifications. 2880
289 2890 3.5C x 120 sqmm 2890 600 M
290 2900 Supply of FRLS Armoured Copper Control cable as per tender specifications. 2900
291 2910 2C x 1.5 sqmm 2910 9000 M
292 2920 3C x 1.5 sqmm 2920 750 M
293 2930 4C x 1.5 sqmm 2930 6000 M
294 2940 6C x 1.5 sqmm 2940 2250 M
295 2950 8C x 1.5 sqmm 2950 2250 M
296 2960 10C x 1.5 sqmm 2960 1500 M
297 2970 12C x 1.5 sqmm 2970 3750 M
298 2980 16C x 1.5 sqmm 2980 750 M
299 2990 18C x 1.5 sqmm 2990 3000 M
300 3000 20C x 1.5 sqmm 3000 750 M
301 3010 24C x 1.5 sqmm 3010 2625 M
302 3020 32C x 1.5 sqmm 3020 750 M
303 3030 36C x 1.5 sqmm 3030 900 M
304 3040 48C x 1.5 sqmm 3040 4125 M
305 3050 Supply of FRLS Armoured Copper Signal cable as per tender specifications. 3050
306 3060 1P x 1.5 sqmm 3060 9000 M
307 3070 2P x 1.5 sqmm 3070 6375 M
308 3080 3P x 1.5 sqmm 3080 1800 M
309 3090 4P x 1.5 sqmm 3090 675 M
310 3100 6P x 1.5 sqmm 3100 1875 M
311 3110 8P x 1.5 sqmm 3110 1125 M
312 3120 10P x 1.5 sqmm 3120 750 M
313 3130 12P x 1.5 sqmm 3130 4125 M
314 3140 16P x 1.5 sqmm 3140 900 M
315 3150 18P x 1.5 sqmm 3150 1125 M
316 3160 1T x 1.5 sqmm 3160 900 M
317 3170 8T x 1.5 sqmm 3170 1875 M
318 3180 Supply of FS Armoured Copper Power cable as per tender specifications. 3180
319 3190 3C x 2.5 sqmm 3190 6000 M
320 3200 3C x 4 sqmm 3200 1350 M
321 3210 4C x 2.5 sqmm 3210 900 M
322 3220 4C x 4 sqmm 3220 1050 M
323 3230 Supply of FS Armoured Copper Control cable as per tender specifications. 3230
324 3240 2C x 1.5 sqmm 3240 4350 M
325 3250 3C x 1.5 sqmm 3250 75 M
326 3260 4C x 1.5 sqmm 3260 1500 M
327 3270 6C x 1.5 sqmm 3270 3150 M
328 3280 8C x 1.5 sqmm 3280 3450 M
329 3290 10C x 1.5 sqmm 3290 750 M
330 3300 12C x 1.5 sqmm 3300 1800 M
331 3310 18C x 1.5 sqmm 3310 750 M
332 3320 24C x 1.5 sqmm 3320 2250 M
333 3330 32C x 1.5 sqmm 3330 1125 M
334 3340 36C x 1.5 sqmm 3340 750 M
335 3350 48C x 1.5 sqmm 3350 1875 M
336 3360 Supply of FS Armoured Copper Signal cable as per tender specifications. 3360
337 3370 1P x 1.5 sqmm 3370 5250 M
338 3380 2P x 1.5 sqmm 3380 4350 M
339 3390 3P x 1.5 sqmm 3390 2400 M
340 3400 4P x 1.5 sqmm 3400 3750 M
341 3410 1T x 1.5 sqmm 3410 3200 M
342 3420 Supply of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. 3420 5250 M
343 3430 Supply of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. 3430 3000 M
344 3440 Supply of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. 3440
345 3450 5/10 m 3450 140 EA
346 3460 15 m 3460 40 EA
347 3470 20 m 3470 30 EA
348 3480 25 m 3480 15 EA
349 3490 30 m 3490 20 EA
350 3500 Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document 3500 18750 M
351 3510 Supply of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 3510 3000 M
352 3520 Supply of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 3520 1500 M
353 3530 Supply of anodized Aluminium perforated cable trays (2.5mm Thick), tray covers (1.5mm Thick ) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. 3530
354 3540 50 mm 3540 6000 M
355 3550 100 mm 3550 6750 M
356 3560 150 mm 3560 3000 M
357 3570 300 mm 3570 4500 M
358 3580 600 mm 3580 1500 M
359 3590 Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. 3590
360 3600 24 ways JB 3600 25 EA
361 3610 18 ways JB 3610 25 EA
362 3620 12 ways JB 3620 30 EA
363 3630 8 ways JB 3630 45 EA
364 3640 6 ways JB 3640 45 EA
365 3650 4 ways JB 3650 45 EA
366 3660 Supply of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. 3660 500 M
367 3670 Supply of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc 3670 20 TO
368 3680 Earth Pit 3680
369 3690 Supply of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) 3690
370 3700 TLF gantry 3700 2 EA
371 3710 TT earthing 3710 6 EA
372 3720 Control room 3720 6 EA
373 3730 Tank farm 3730 10 EA
374 3740 Pump house 3740 4 EA
375 3750 SERVICE COMPONENTS PHASE-I 3750
376 3760 TANK LORRY FILLING 3760
377 3770 Installation, integration, testing and commissioning of Microprocessor based Coriolis mass flow meter for white oil application along with display unit and mounting accessories with adjustable screw support,bellow for vibrations etc complete as per specifications and tender document for loading of following main products \nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no additional cost to IOCL. 3770
378 3780 MS (for line size of 100 mm ) 3780 8 EA
379 3790 HSD (for line size of 100 mm ) 3790 8 EA
380 3800 Water (Master MFM for TT calibration) for line size 50 mm along with structural support and required accessories for mounting 3800 2 EA
381 3810 Installation, integration, testing and commissioning of Strainer cum Air eliminator with differential pressure transmitter with display unit & keyboard across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 3810
382 3820 For product line size 100 mm - TLF 3820 16 EA
383 3830 For Water Line size 50 mm - TT calibration (along with structural support and required accessories) 3830 2 EA
384 3840 Installation, integration, testing and commissioning of Multistage Piston type Digital Control Valve (DCV) along with TRV with two nos. isolation valves at inlet and outlet of TRV with associated piping , secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 3840
385 3850 For product line size 100 mm - TLF 3850 16 EA
386 3860 For Water Line size 50 mm - TT calibration along with vacuum breaker & isolation ball valve mounted on a spool piece & mounting accessories so that the entire water after DCV is drained into the TT after completion of each batch during TT calibration. 3860 2 EA
387 3870 Installation, integration, testing and commissioning of piston type, hydraulically operated ON-OFF Valve along with accessories, secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning ,tubing arrangement as per installation drawing etc for line size 100 mm complete as per specifications and tender document. 3870 1 EA
388 3880 Installation, integration, testing and commissioning of Triple Offset Butterfly valve with electrical/electro-hydraulic fail safe actuator ON-OFF along with accessories as per installation drawing etc for line size 100 mm complete as per specifications and tender document. 3880 16 EA
389 3890 Installation, integration, testing and commissioning of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF metering skid complete as per specifications and tender document. \n(Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 3890 22 EA
390 3900 Installation, integration, testing and commissioning of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermo well, mounting accessories etc complete as per specifications and tender document. \n(Mounting at each TLF loading point on main product for line size 100 mm) 3900 16 EA
391 3910 Installation, integration, testing and commissioning of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 100 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 3910 16 SET
392 3920 Installation, testing and commissioning of bottom loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm), API Coupler, break away coupler, parking stand with compatible API adaptor, Ex-proof/intrinsic safe position sensor for parking stand, associated piping for connecting loading arm with the metering skid , mounting structure etc complete as per specifications and tender document. \nApplication: MS, HSD, MS+ETHANOL 3920 16 EA
393 3930 Installation, testing and commissioning of vapour recovery arm of size 80 mm NB having 3” (80 NB) with poppeted vapour coupler, break away coupler, NRV, flame arrestor, reducers, mounting structures, parking stand with compatible API adaptor, associated accessories, mounting structure etc complete as per specifications and tender document.\nApplication : MS 3930 8 EA
394 3940 Installation, testing and commissioning of Ex-proof Rack Monitors for TT overfill protection system along with accessories like 10 pin gantry plug, ATC copper coiled cable of minimum 8m as per API RP1004 including required support for mounting of the Rack Monitor and gantry plug, etc complete as per specifications and tender document.\nNote: In addition to above, minimum 2 nos. portable Rack Monitor along with accessories and 2 nos. lockable bypass switch are to be provided against total supply of Rack Monitor. 3940 8 EA
395 3950 Installation, integration, testing and commissioning of Resistance - Capacitance type Tank Truck grounding unit along with accessories like 3 nos. of heavy duty flexible coiled cables with high quality rugged, heavy duty SS/ brass grounding socket, FLP double compression glands, Ex-Plug, mounting structure etc, complete as per specification and tender documents.\n(2 nos. of coiled cable with socket for TT earthing relay interlocks and 1 no. for separate earthing of TT) 3950 8 EA
396 3960 Installation, integration, testing and commissioning of Ex-proof field mounted Remote Interaction Terminal (RIT) along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents. 3960 16 EA
397 3970 Installation, integration, testing and commissioning of Ex-proof field mounted Driver Ack Push Button station along with FLP double compression glands and Ex-Proof-plug, structural supports etc complete as per specifications and tender documents. 3970 16 EA
398 3980 Installation, integration, testing and commissioning of Microprocessor based Field mounted dual arm Batch Controller with interface to minimum 2 nos. of main product + 2 nos. of blend product + 2 nos. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document.\nOr\nInstallation, integration, testing and commissioning can supply 2 sets of Microprocessor based Field mounted single arm Batch Controller with interface to minimum 1 no. of main product + 1 no. of blend product + 1 no. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc in place of Dual Arm Batch Controller complete as per specification and tender document. 3980
399 3990 For TLF product loading 3990 8 EA
400 4000 For TT calibration with water 4000 1 EA
401 4010 Installation, testing and commissioning of intrinsically safe / flameproof type proximity card reader along with mounting accessories etc complete as per specifications and tender document for authorisation of TT at 4010
402 4020 TLF bays (1 no. Per bay) 4020 8 EA
403 4030 License area Entry barrier gates ( 2 nos. X 2) 4030 4 EA
404 4040 License area Exit barrier gates ( 1 no. X 3) 4040 3 EA
405 4050 Security Exit barrier gates ( 1 no.) 4050 1 EA
406 4060 Security Entry barrier gates ( 1 no.) 4060 1 EA
407 4070 Near Security Gate/TT parking ( for TT registration ) 4070 2 EA
408 4080 Installation of pre-fabricated Metering Skid (MS structure) for mounting of complete metering equipments as per BOQ and schematic drawing for one main product, one blend product and one additive dosing system. The metering assembly comprises of : \n\nMain product line: Strainer cum Air eliminator, Spool piece with tapping for additive dosing, Online Master Meter proving manifold, MFM,Spool piece with tapping for Temprature Transmitter installation, Pressure transmitter, spool piece with tapping for connecting outlet of TRV, ON-Off valve, DCV, Spool Piece with tapping for Ethanol blending & TRV installation. \n\nBlend Product line: Strainer cum air eliminator, Online Master Meter proving manifold, MFM, Spool piece with tapping for Temperature Transmitter installation, ON-Off valve, DCV, NRV, isolation valve and finally connected to Main stream line tap off point after DCV. \n\nAdditive Dosing System comprises of isolation valve, Additive injection mono block, connecting piping, NRV, isolation valve and finally connecting to Main stream tap off point before MFM. \n\nProvision to be made in the skid for mounting of Batch Controller, Rack Monitor, Grounding unit, RIT, Driver's Ack Push button stations, card reader, FLP sockets, FLP junctions boxes (Power, Signal and Control), FLP power isolator switch, interconnecting cables from respective equipment to JBs, cable trays with covers, glands, support, MS structure,Electroforged galvanized grating, nuts, bolts, gaskets, Tees, bends, elbows, WNRF flanges, nozzles, plugs, isolators, any other equipment if required as per design Engineering etc complete as per specification and tender document. \n\nKindly note, irrespective of facility available or not, each metering skid shall have provision for installation of metering assembly of one main product, one blend product and one additive product as detailed in tender document. 4080 16 TO
409 4090 Note: \n1. All the equipments, JBs, cable trays, interconnecting cables etc as stated above to be installed and loop tested at factory. Complete assembly to be dispatched at site. The skid to be designed and fabricated by the party taking into consideration of all the equipment sizing, space available for mounting of the skid at the bottom of the gantry etc. The design Engineering along with weight calculation of individual skid excluding equipments to be submitted to IOCL prior to taking up fabrication job for review purpose. Payment shall be made based on theoretical weight calculation of the skid excluding weight of equipments, JBs, cable trays. The rate is also inclusive of surface preparation, powder coating, painting, transportation of the skid to site etc complete in all respect. \n2. All unuse nozzle/ tapping/ opening to be blind flanged.\n3. For SKO metering SKID, tapping to be provided in the skid for both bottom and top loading as per design Engineering.\n 4090
410 4100 Installation, integration, testing and commissioning of barrier gate of minimum boom length of 3 m along with accessories, controllers etc complete as per specification and tender document for installation at following location. 4100
411 4110 License area Entry gate 4110 2 SET
412 4120 License area Exit gate 4120 3 SET
413 4130 Security Exit gate 4130 1 SET
414 4140 Security Entry gate 4140 1 SET
415 4150 DISPLAY BOARDS 4150
416 4160 Installation, integration, testing and commissioning of weather proof LED bay queuing display board (Minimum 15 lines x 100 mm Character height x 25 characters per line) for outdoor installation at TT parking area / Customer service building along with accessories like public address system, speakers, amplifier, mike, structural steel for mounting of the same, Aluminium canopy/sunshade etc complete as per specifications and tender document. 4160 1 EA
417 4170 Installation, integration, testing and commissioning of LED monitor of minimum 55" along with required hardware and software for interfacing with TAS, lockable enclosure (wall / ceiling mounted) for mounting the monitor along with accessories at Driver's Rest Room for repeat display of 15 lines Bay Queue Display board complete as per specification and tender document. Kindly note, no additional payment shall be made for any additional hardware/ software/ cable etc required for integration of the monitor with TAS. 4170 1 EA
418 4180 Installation, integration, testing and commissioning of LED monitor of minimum 55" along with required hardware and software for interfacing with TAS, lockable enclosure (wall / ceiling mounted) for mounting the monitor along with accessories, Aluminium canopy/ sunshade etc at invoice room for displaying the list of TTs whose invoice has been generated and TT is still inside license area complete in all respect as per tender requirement. Kindly note, no additional payment shall be made for any additional hardware/ software/ cable etc required for integration of the monitor with TAS. 4180 1 EA
419 4190 Installation, integration, testing and commissioning of weather proof three line coloured LED display board with scroll and flash effects (Each line of min. 50 mm Character height x 11 characters per line) for outdoor application near Security Gate/ TT parking Area and license area Entry barrier Gate along with mounting structure, Aluminium canopy/ sunshade, accessories etc complete as per specifications and tender document for displaying the TT Registration no. in bilingual (English + local language) of reported TT whose proximity card has been shown on the PCR adjacent to the display board for TT reporting at security gate/TT parking area, TT status at TT parking area exit gate and the bay no. (Bilingual) etc of the authorised TT reported at license area Entry Gate as per FDR.\n2 nos. for TT reporting + 1 no. at Security Entry gate + 2 nos. per License Area Entry Barrier Gate (2X2) + 1 No. at Security Exit gate; Total - 2+1+4+1=8\nNote : 1 line for display in English & 2 lines for displaying in local language 4190 8 EA
420 4200 Ethanol Dosing System 4200
421 4210 Installation, integration, testing and commissioning of Microprocessor based Coriolis mass flow meter for white oil (Ethanol) application alongwith display unit and mounting accessories with adjustable screw support, reducer (if required) etc for line size 2" suitable for maximum flowrate of 500 LPM complete as per specifications and tender document for ethanol blending.\nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no adddtional cost to IOCL . 4210 8 EA
422 4220 Installation, integration, testing and commissioning of Strainer cum Air eliminator for line size 50 mm with differential pressure transmitter across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 4220 8 EA
423 4230 Installation, integration, testing and commissioning of Multistage Piston type Digital Control Valve (DCV), NRV, isolation valve for line size 50 mm alongwith accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 4230 8 EA
424 4240 Installation, integration, testing and commissioning of Piston type, hydraulically operated, solenoid operated ON-OFF Valve along with accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves , tubing arrangement as per installation drawing etc for line size 50 mm complete as per specifications and tender document. 4240 8 EA
425 4250 Installation, integration, testing and commissioning of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermowell for line size 50mm, mounting accessories etc complete as per specifications and tender document. \nNote : One no. of additional thermo well along with accessories to be provided and installed on ethanol point for installation of Master Temperature transmitter with RTD. 4250 8 EA
426 4260 Installation, testing and commissioning of online proving valves manifold comprising of 1 no. manual operated DBBV without actuator and 2 nos. of 50 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 4260 8 SET
427 4270 Additive dosing System 4270
428 4280 Installation, integration, testing and commissioning of additive injection mono block along with accessories for XTRAPREMIUM and XTRAMILE complete as per specification and tender document.\nNote - All the wetted parts within Additive injection panel/ block shall be of SS 316 or better. 4280 6 SET
429 4290 Installation, testing and commissioning of Additive tanks (500 Litres each) and pump module for XTRAPREMIUM /XTRAMILE comprising of Additive Tank, Additive Pumps (Two per tank) , Mild Steel SKID, Flameproof Motor, NRV 25 mm, Flanged ball valve 25 mm, Pressure Relief Valve, Pressure Gauge with pulse dampener, Strainer 25 mm, interconnecting pipings (25 mm SS), flanges etc. auxiliary potential free contact/serial communication complete as per specification and tender document. 4290
430 4300 For Xtramile 4300 1 SET
431 4310 For XtraPremium 4310 1 SET
432 4320 laying ,welding & commissioning of ASTM A106 Gr B Schedule 80 pipe of 25 NB from additive header pipe to additive injection panel at TLF bay complete as per tender document.. 4320 100 M
433 4330 Laying ,welding and commissioning of Necessary hardware Like SS Tubing, reducer, Elbows, equal Tee ,unequal tee, Flanges, Coupling, Ball Valve for Isolation, NRV, 15 mm back pressure regulator on return line etc as required for piping and commissioning of the system complete in all respect. 4330 1 LS
434 4340 Note: Piping from Additive tank skid upto TLF header line along with isolation valve & return line shall be supplied and installed by IOCL. Integration of additive pumps for remote operation, level measurement shall be in the successful bidder's scope. 4340
435 4350 TLF Header line instruments 4350
436 4360 Installation,testing and commissioning of Bulk Air Eliminator as per product line size and flow requirement as per following sizes including mounting structure, foundation etc complete as per specification and tender document. 4360
437 4370 MS - 2.6 KL 4370 1 EA
438 4380 HSD - 2.6 KL 4380 1 EA
439 4390 ETHANOL-0.6 KL 4390 1 EA
440 4400 Installation,testing and commissioning of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF main header line complete as per specifications and tender document. \n(Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 4400
441 4410 TLF Header 4410 4 EA
442 4420 Tank Farm Management System 4420
443 4430 Installation, integration, testing and commissioning of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 4430
444 4440 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 4440
445 4450 HSD 4450 4 EA
446 4460 BIO-DIESEL 4460 4 EA
447 4470 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 4470
448 4480 MS 4480 6 EA
449 4490 ETHANOL 4490 4 EA
450 4500 For U/G horizontal product tanks 4500
451 4510 MS 4510 1 EA
452 4520 HSD 4520 1 EA
453 4530 HSD (OWN) 4530 1 EA
454 4540 ETHANOL 4540 1 EA
455 4550 BIO-DIESEL 4550 1 EA
456 4560 Installation,integration,testing and commissioning of Non-contact type Radar level gauges with instrument accuracy of +/-3 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 4560
457 4570 FIRE WATER 4570 4 EA
458 4580 SLUDGE 4580 1 EA
459 4590 Installation,integration,testing and commissioning of Guided wave RADAR type level gauge with transmitter , instrument accuracy of +/- 3 mm or better,in built digital display, along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) as per specification. 4590
460 4600 For Additive Tanks 4600 2 EA
461 4610 Installation,integration,testing and commissioning of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. 4610
462 4620 With minimum 8 elements temperature sensor (for A/G vertical tanks) 4620
463 4630 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 4630
464 4640 HSD 4640 2 EA
465 4650 BIO-DIESEL 4650 2 EA
466 4660 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 4660
467 4670 MS 4670 3 EA
468 4680 ETHANOL 4680 2 EA
469 4690 For U/G horizontal product tanks 4690
470 4700 MS 4700 1 EA
471 4710 HSD 4710 1 EA
472 4720 HSD (OWN) 4720 1 EA
473 4730 ETHANOL 4730 1 EA
474 4740 BIO-DIESEL 4740 1 EA
475 4750 Installation,integration,testing and commissioning of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 4750
476 4760 For A/G vertical tanks - Three elements 4760
477 4770 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 4770
478 4780 HSD 4780 2 EA
479 4790 BIO-DIESEL 4790 2 EA
480 4800 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 4800
481 4810 MS 4810 3 EA
482 4820 ETHANOL 4820 2 EA
483 4830 For U/G horizontal product tanks-One element 4830
484 4840 MS 4840 1 EA
485 4850 HSD 4850 1 EA
486 4860 HSD (OWN) 4860 1 EA
487 4870 ETHANOL 4870 1 EA
488 4880 BIO-DIESEL 4880 1 EA
489 4890 Installation,integration,testing and commissioning of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 4890
490 4900 For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) 4900 18 EA
491 4910 For U/G Product tanks 4910 5 EA
492 4920 For water tanks 4920 4 EA
493 4930 For Sludge tank 4930 1 EA
494 4940 Installation,integration,testing and commissioning of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document 4940
495 4950 For A/G Vertical Product tanks 4950 9 EA
496 4960 For U/G horizontal product tanks 4960 5 EA
497 4970 Installation, testing, integration and commissioning of Auto Tank Gauging (ATG) probe combo with density measurement (Wireless or Wired) including necessary accessories as per Tender specifications. 4970 1 EA
498 4980 Installation,integration,testing and commissioning of parallel redundant Communication Interface Units (CIU) including all accessories etc for tank farm management system complete as per specification and tender document. 4980
499 4990 For Primary Radar gauges installed on A/G vertical , under ground product tank, water tank ,slope ,additive & Sludge tank etc. 4990 1 SET
500 5000 For Secondary Radar Gauges installed on A/G product tanks 5000 1 SET
501 5010 Installation,integration, testing and commissioning of 1 no. of Redundant TFMS Server (Form Factor:Rack ,Mountable in 19" rack ) along with 1 no. rack type (1U) ,one no. Min. 19" LED monitor with keyboard & mouse ,suitable for 19" mounting & 24x7 operation, Licensed OS (latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed software from Radar Gauge OEM etc complete as per specification and tender document. 5010 1 SET
502 5020 Installation,integration,testing and commissioning of TFMS Workstation with minimum 27" LED colour monitor, keyboard, mouse, KVM Switch, Licensed OS(latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed client software from same Radar Gauge OEM etc complete as per specification and tender document. \nNote:CPU of control room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 5020
503 5030 19" Rack type at Control Room, form factor - Rack, CPU height - 2U (Maximum) 5030 1 EA
504 5040 Push Buttons Outside Dyke Walls 5040
505 5050 Installation,integration,testing and commissioning of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS, along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. 5050
506 5060 For ROSOVs (A/G product tank's inlet, outlet and recirculation line) 5060 15 EA
507 5070 ESD PUSH BUTTON STATION 5070
508 5080 Installation,testing and commissioning of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. 5080
509 5090 Local ESD Push Button Station ( Each Battery of TLF -1X1 no., TLF pump house - 1 no.) 5090 2 EA
510 5100 Plant ESD Push Button Station ( Each battery of TLF - 1X1 No.) 5100 1 EA
511 5110 Installation,integration,testing and commissioning of ESD push button stations (for indoor application), mushroom head type with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. (control room - 1 no., security room - 1 no., TM's cabin - 1 no.) 5110 3 EA
512 5120 Control Room equipments 5120
513 5130 Design, engineering, installation, configuration, integration, testing and commissioning of redundant fault tolerant Integrated Distributed Control System (DCS) along with DCS Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Input Output modules, Power supply units, Relays with base, barriers, TBs, Redundant host communication ports, Serial Interface Modules, HART modules, other communication modules, HMI , wirings, glands, plugs, other modules/ hardware required for interfacing with all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: Any other hardware, software, OPC server, Historian Server, storage, firewall, functional control key board etc required as per tender specification and design requirements, the same to be provided by the vendor at no additional cost to IOCL. 5130 1 SET
514 5140 Design, installation, configuration, integration, testing and commissioning of Complete Terminal Automation Software along with required licences, dongle/keys, GUI, SCADA etc meeting the complete functional and technical requirements of the tender document. \nVendor to provide required software, licences, dongle/keys, GUI, SCADA etc for TAS Management Server, Distributed Control System, Operator work stations, fire fighting OIC, Alarm display and annunciation OIC, Engineering Work Stations(for safety PLC & DCS), Web Server, OPC Server, Historian Server / work station, any other devices connected to Control & Management LAN of the integrated Distributed Control System complete as per specification and tender document.\nTAS software shall be interfaced with following but not limited to major sub-systems / equipments alongwith GUI development for monitoring, logging, reporting, controls & interlocks etc as per specification and tender document.\n- Safety PLC\n- TAS-Management Server\n- TLF Automation System (TT reporting, registration & entry system, TT Queuing, FAN generation, TT registration number reading system, Photo pass management system,TT crew authorization system,Bay allocation, Additive Dosing system, Ethanol blending System, Interface with TLF equipments like BCU, MFM, Barrier Gates, Bay Queue Display, Bay allocation Display, Invoice generated display, rack monitors, Proximity card readers etc)\n-Tank Wagon loading Automation system (Rake inventory System,Rake registration system, FAN generation, Tank wagon allocation, Interface with TWG equipments like BCU, MFM etc,SAP-TWG integation)\n-Tank Wagon unloading Automation system\n-Tank Lorry Decantation System\n-TT calibration System\n-Bio Diesel Blending system \n- ANPR and Face recognisation 5140 1 LS
515 5150 -- Valve Automation System (ROSOVs, MOVs, DBBV, MCS Interface, SOVs, etc)\n-Tank Farm Management System ( TFMS Server, Primary & Secondary Radar Gauging, AOPS, Level transmitters, Level Switch, Density probes, MSTW, CIU etc)\n- Pipeline/ Refinery PLC Interface, OMC PLC interface\n - MCC, Pump, Borewell, DG Sets, Air compressors, VFDs\n- PA paging Interface \n- HC Detection System Interface\n-FAS Interface, Fire Fighting System, HVLR, Fire Alarm System Interface, Fire Engines, DG Set, Jockey pumps, Foam pumps, CFFS, Sprinkler & Fixed foam pourer system etc\n- VRU Package Units\n- Effluent Treatment plant\n- CCTV systems\n- Access Control System\n- SKO Blue Dye Dosing System\n- ESD System, Emergency panel, Power ESD, Local ESD, Wailing sirens\n- Pressure Transmitters\n- UPS & Power distribution boards etc\n- Interface with IOCL SAP through firewall\n- Visitor Management Software for setup, configuration, operation, events, history and archiving, recording, printing etc. complete as per specification and tender document - Any other Third Party Interface/ devices as per scope of the work order etc\nNote: The offered software shall also includes fault detection module and Web Server software for remote over IOCL Intranet across India as detatiled in the tender document.\n\n\n\n 5150
516 5160 Design, engineering, installation, configuration, integration, testing and commissioning of Redundant SIL 3 TUV/ EXIDA certified Safety PLC along with PLC Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Dual redundant Input Output modules, Power supply units, Relays with base, barriers, TBs, Dual Ethernet ports per processor, Serial Interface Modules, HMI , wirings, glands, plugs, other modules/ hardware required for interfacing all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: The offered safety PLC shall be of the same make family of the integrated Distributed Control System. 5160 1 SET
517 5170 Design, engineering, installation, configuration, integration, testing and commissioning of redundant TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LCD/LED monitor of minimum size of 19" suitable for 24x7 operation along with High availability redundancy software working on redundant (Primary and Secondary) hot standby mode , keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document.\n OR\nDesign, engineering, installation, configuration, integration, testing and commissioning of Dual Mode Redundant Grade with built in redundancy TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 19" suitable for 24x7 operation, keyboard drawer, optical mouse and combo 4 port KVM switch (if required) , OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document. \n\nTAS Management Servers (TAS-MS) shall have either of the above mentioned configuration meeting the complete specification and tender requirements. \n\nIn addition, the TAS-MS shall be configured to have Zero Downtime to repair, Full data redundancy shall be provided using proven technology , it shall also provide port level redundancy.The system solution shall be capable of self fault detection and isolation, all necessary hardware/software configuration etc to achieve the same shall be included. 5170 1 LOT
518 5180 Installation & commissioning of 42 U Rack Enclosure cabinet/System cabinet with 19" rack size, along with accessories like Biometric fingerprint cum contactless smart card reader for front & back door seperately with accessories, limit switches, earthing arrangements, breaker, fuses, terminal blocks and wiring etc complete as per specification and tender document for mounting of below mentioned equipments. 5180
519 5190 For mounting of TAS Management Servers along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, Ethernet switch, GSM modems, MCBs etc as per specification and tender document. 5190 1 EA
520 5200 For mounting of Redundant ACS cum photopass management Server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking components, MCBs etc as per specification and tender document. 5200 1 EA
521 5210 For mounting of Redundant TFMS Server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, CIUs, MCBs etc as per specification and tender document. 5210 1 EA
522 5220 For mounting of Rack mounted Master Control Stations for MOVs & DBBVs along with power adaptors, MCBs, required accessories etc as per specification and tender document. 5220 2 EA
523 5230 For mounting of Rack mounted CPUs of Control room console workstation (Rack type) , one number 19" rack mounted monitor, rack mounted keyboard, mouse, KVM switches for connection of all CPUs along with power adaptors, MCBs, required accessories etc as per specification and tender document. 5230 2 EA
524 5240 For mounting of Network equipments along with power adaptors, MCBs, required accessories etc as per specification and tender document. 5240 1 EA
525 5250 Installation, configuration, integration, testing and commissioning of Operator Interface Console Computer (OIC) with minimum 27" colour LED monitor,keyboard, mouse,KVM Switch, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. \nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 5250
526 5260 19" Rack mounted at Control Room, form factor - Rack , Max. 2U height ( 3 OICs, 1 for alarm Display, 1 for fire fighting System) 5260 5 EA
527 5270 Installation, configuration, integration, testing and commissioning of Operator Interface Console Computer (OIC) minimum 27" colour LED monitor, keyboard, mouse, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. 5270
528 5280 Tower type in TM's Cabin 5280 1 EA
529 5290 Installation, configuration, integration, testing and commissioning of Engineering Workstation (EWS) with minimum 27" colour LED monitor, keyboard, mouse, KVM Switch, Safety PLC & DCS software, HMI software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. (Locations: 1 no. in CR for both DCS and Safety PLC) \nNote: In case of Tower type workstation is supplied in place of Rack type.Rack mount Kit to be provided for installation in the 19" Rack.\nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 5290
530 5300 19" Rack mounted at Control Room, Form factor - Rack , Max. 2U height 5300 1 EA
531 5310 Installation, configuration, integration, testing and commissioning of Tank Truck Entry System (TTES) Workstation with minimum 27" colour LED monitor, keyboard, mouse,KVM switch, software, SCADA, GUI, OS, Antivirus etc. complete as per specifications and tender document. (Locations: 2 nos. in Customer service Block +1 no. in Control room+1 no. in Lock shed room) \nNote: CPU of contol room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 5310
532 5320 19" Rack mounted at Control Room, Form factor - Rack , Max. 2U height 5320 1 EA
533 5330 Tower type in Customer service block (2 nos.) and Lock shed room (1 no.) 5330 3 EA
534 5340 Installation, configuration, integration, testing and commissioning of minimum 19" colored LED monitor (19" Rack type at panel Room, form factor - Rack, height - 1U) with , KVM switch, Rack type keyboard, mouse etc located in Control Room complete as per specifications and Tender Document. (For CPUs of Console kept in panel room) 5340 2 EA
535 5350 Installation, configuration, integration, testing and commissioning of Web Server (Rack type mountable in 19" rack ) ,Rack type CPU -2U Max. , LED monitor of minimum size of 27" suitable for 24x7 operation, keyboard, mouse, KVM Switch, web application software, SCADA, GUI, OS, Antivirus etc located in panel Room complete as per specifications and Tender Document. \nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 5350 1 EA
536 5360 Installation, integration, maintenance and operation of the NMS System covering Network Devices operational in Terminal Automation System. The Offered Network Management Solution (NMS) solution should support at least the following:\n• All the proposed NMS Components should be from single vendor. \n• NMS Software should support Graphical view up to port level for the all the devices.\nDiscovery of Network Elements.\n• Real time Traffic monitoring of Network Links and Devices with Historical reports for various periods.\n• Management of SNMPv1, SNMPv2, SNMPv3 & MIB etc.\n• Configuration of thresholds for Generating alarms.\n• Configuration of alarm actions (visual, audible, email, sms etc.) for each \nNetwork element.\n• Should be able to provide secured windows based consoles / secured web based consoles for accessibility to NMS.\n• Should have web browser interface with user name and Password Authentication.\n• Administrator/ Manager should have privilege to create/modify/delete user.\n• NMS should have support for SNMPv3 & IPv6, including dual-stack IPv4 & IPv6 to provide flexibility in protocol strategy and implementation.\n 5360 1 LS
537 5370 Installation, configuration, integration, testing and commissioning of Terminal servers (rack mounted) with inbuilt/externally mounted lightening and Surge Protection Device Type (1+2) at all Serial ports, for interfacing and integration of card readers, Bay Queue display units (Indoor & outdoor), LED Display unit for TT reporting,at Main Entry gate & Exit gate and TLF Entry gate for Bay allocation with TAS.In case the above listed equipments do not come with open communication protocol compatible to be directly interfaced with DCS Serial / MODBUS TCP IP module complete as per specification and tender document.\n\nNote: Terminal Servers to be configured in Dual Redundant mode. 5370
538 5380 16 ports at Control Room 5380 2 EA
539 5390 Installation, configuration, integration, testing and commissioning of 24 ports Layer 3 Managed Ethernet Switches (10/100/1000 MBPS) with SFP, copper, fibre modules/ports along with accessories for connecting Plant management LAN equipments like CCTV System, TAS - MS Server/ Redundant OPC server, TFMS Server, TFMS work station, OICs, IOCL intranet for SAP connectivity through fire wall, Network printers, Access Control Server, Web Server Access over IOCL Intranet, connecting to OIC/ work stations etc which needs to be connected to both Plant Management LAN and Plant Control LAN for getting the entire GUIs of Complete Terminal Automation System and any other third party devices for interfacing with DCS etc.\nNote: \n1. Ethernet Switches to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs and any other equipment which are to be connected to above switch and the communication is through OFC cable. 5390 2 EA
540 5400 Installation, configuration, integration, testing and commissioning of minimum 24 ports Layer 2 Managed Ethernet Switches (10/100/1000 MBPS) along with SFP, copper, fibre modules, accessories for connecting equipments installed in Plant Control LAN like TAS- MS Servers, OICs, TTES cum TWES , EWS, OPC Servers, Fire fighting OICs, Alarm Display OIC, DCS, Safety PLC, inter connecting building work stations etc as per system architecture and design requirement complete as per specification and tender document.\nNote:\n1. The switches are to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs, and any other equipment which are to be connected to above switch and the communication is through OFC cable. 5400 2 EA
541 5410 Installation, configuration, integration, testing and commissioning of Layer 2 Managed Ethernet Switches along with accessories for connecting BCU with TAS, equipments installed in Customer service room, Lock room, Security room, Terminal Manager room and other TAS equipments as per system architecture and design requirement complete as per specification and tender document.\nNote: \n1. Ethernet switches for BCU communication shall have suitable mounting arrangement to mount inside FLP JBs. \n2. The switches are to be configured in Dual Redundant mode.\n3. All OICs, Workstations, Servers other than that of CCTV, ACS & TFMS are to be connected to both plant management and control LAN so that all the GUIs can be seen in all the PCs irrespective of its nomenclature like TTES, OIC, EWS, TM PC etc.\n4. Printers to be connected to Plant Management LAN and to be configured to all PCs, Workstation, TTES etc so that printout command can be issued from any of the Machine. 5410
542 5420 For BCU integration at TLF (copper ports of 10/100/1000 MBPS)-( Minimum 8 nos. copper ports and 2 nos. optical ports) 5420 6 EA
543 5430 For BCU integration at TT Calibration shed-2 Nos (copper ports of 10/100/1000 MBPS)-(Minimum 4 nos. copper ports and 2 nos. optical ports) 5430 2 EA
544 5440 For connecting all MODBUS TCP IP devices ( any other devices) to DCS Ethernet port directly for integration (copper ports of 10/100/1000 MBPS)- to be located in Control Room ( Minimum 8 nos. copper ports and 2 nos. optical ports) 5440 2 EA
545 5450 At Lock Shed - copper ports of 10/100/1000 MBPS [control LAN - 2 nos. & Management LAN - 2 nos.] ( Minimum 8 nos. copper ports and 2 nos. optical ports) 5450 4 EA
546 5460 At Admin Building for TM cabin - copper ports of 10/100/1000 MBPS [control LAN - 2 nos., Management LAN - 2 nos., CCTV - 2 no.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 5460 6 EA
547 5470 At Security Room - copper ports of 10/100/1000 MBPS [Management LAN - 2 nos.,CCTV - 2 no.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 5470 4 EA
548 5480 At Driver rest room - copper ports of 10/100/1000 MBPS [Managent LAN - 2 nos.] (Minimum 4 nos. copper ports and 2 nos. optical ports) 5480 2 EA
549 5490 Installation, testing and commissioning of industrial grade redundant Serial to Ethernet converter of 8 port with mounting acessories etc complete in all respect as per specification and tender document. (Ports:- 6 Main + 2 Spare) 5490
550 5500 For MFM and other serial devices integration to DCS -TLF 5500 3 EA
551 5510 Installation, testing and commissioning of Wall mounted/wheel mounted Network Rack-minimum 19U 19" Rack for mounting of Terminal Server/Ethernet switches/LIU/ OFC components along with accessories like power sockets, MCBs, fan, mounting accessories etc complete in all respective at Security Room, TM room, Invoice Room for TAS equipments 5510 4 EA
552 5520 Installation, configuration, integration, testing and commissioning of Monochrome Laser Printer along with accessories for TAS and TFMS report printing in control room (2 nos.) and 2 nos. at security room complete as per specifications and tender document. 5520 4 EA
553 5530 Installation, configuration, integration, testing and commissioning of heavy duty high speed laser printer and accessories for invoice printing in lock shed room, complete as per specifications and tender document. 5530 2 EA
554 5540 Installation, integration, testing and commissioning of parallel redundant UPS of minimum capacity of 60 KVA or as per load calculation (whichever is higher) for entire TAS equipments and third party devices integrated with TAS and powered through TAS UPS with 30% spare capacity for future load connection. The scope also includes supply of parallel battery bank (2x50%) for minimum back up time of ½ hour at full load (rated capacity) along with stand, supports for mounting of the UPS and batteries etc complete as per specification and tender document. The batteries shall be Sealed Maintenance free type. 5540 1 SET
555 5550 Installation, integration, testing and commissioning of UPS Power Distribution Panel along with Biometric fingerprint cum contactless smart card reader for front and rear gate sepearately with accessories for powering DCS Panel, Safety PLC Panel, TAS-MS, OIC, EWS, TFMS System, TTES, printers, Bay Instruments other control room equipments, Tank Farm Instruments, CCTV system, Fire Detection System, Access control system, Bay Queue Display boards, other display boards, ROSOV ESD port, header line instruments and any other TAS equipments where UPS power are required for smooth un-interrupted operation. Miscellaneous Instrumentation comprising of suitable MCCBs for Isolation, MCB etc are to be provided. The panel shall be complete in all respects with necessary indication lamps for powering, necessary control wiring with digital voltmeter & digital ammeter separately for UPS and Auxilliary supply for front and rear seperately etc as per specifications and tender document.\nNote: Minimum 20% spare power points to be made available for future use. 5550 1 LS
556 5560 Installation & fixing of Open desk operator consoles, chairs, printer tables etc complete as per specification and tender document. 5560
557 5570 Open desk operator consoles for mounting of monitor in two tiers , 2 nos. of key boards, 2 nos. of mouse, accesscories e.g. Telephone,VHF sets, Master control station for PA paging, storage etc complete as per specification and tender document.\n(For mounting of 3 nos. OICs monitor, 1 no. Alarm Display OIC monitor, 1 no. Fire fighting OIC monitor, 1 no. TTES monitor , 1 TFMS workstation monitor, 1 no. CCTV client monitor,1 no. EWS monitor,1 Web server, storage etc.) 5570 7 EA
558 5580 Standard Printer Tables of Godrej or equivalent make (2 nos. at security gate, 1 no. in Lock shed room, 1 no. in security room for visitor management) 5580 7 EA
559 5590 Standard Computer Table of Godrej or equivalent make for installation of CCTV client , ACS client in security room (2 nos.),Photo pass management PC(1 No.), TTES in Customer service room (2 nos.) and TTES in lock shed room (1 no.) 5590 6 EA
560 5600 Installation, integration, configuration, testing and commissioning of IP based Redundant GSM modem suitable for 24x7 operation along with accessories for auto SMS as per specification and tender document. 5600 1 EA
561 5610 Hydrocarbon Detection system 5610
562 5620 Conducting fire and hydrocarbon vapour mapping study through reputed agencies having proven track record of conducting similar studies for oil installation across globe,using standard licensed software along with submission of study reports as per specification and tender document. 5620 1 EA
563 5630 Installation, integration, calibration, testing and commissioning of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document. 5630
564 5640 Point type Infrared detector\n(Indicative location: Each tank dyke sump pit inside dyke wall - 5 nos., Near ROSOVs of MS tanks:-3 Nos., Ethanol tanks- 2 nos., TLF pump seal (MS+Ethanol) - 8 Nos,Sludge pump seal-2 No., Pump house drain pit - 2 no.; Vapour recovery system drain pit - 1 no.,ETP-1 No.) 5640 24 EA
565 5650 Open path type Infrared detector (10-90 m) along with alignment telescope, configuration & Testing kit etc (Tentative location: MS tanks - 8 Nos. & Ethanol tanks covering ROSOVs - 4 nos.) 5650 12 EA
566 5660 Open path type Infrared detector (10-120m) along with alignment telescope, configuration & testing kit etc (Tentative location: TLF PH-3 Nos) 5660 3 EA
567 5670 Installation, integration, testing and commissioning of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessories and structural supports as per specification.( Tentative location : Each product tank dyke (MS)-1 No.,(Ethanol)-1 No., Pump House (TLF) - 1 No.,ETP-1 No.,VRU-1 No.) 5670 5 EA
568 5680 Automatic Fire Detection and Alarm System 5680
569 5690 Installation, integration, testing and commissioning of microprocessor based automatic Fire Alarm Panel along with required Software, and hardware like Control module, monitor module, fault isolation module (in built/ External), mounting structure support etc complete as per standard design engineering, specification and tender document.\nLocation : Control Room 5690 1 EA
570 5700 Installation, integration, testing and commissioning of Repeater Panel along with software, hardware, mounting accessories etc required as per standard design Engineer, specifications and tender document complete in all respect. \n(Tentative location : Security Gate - 1 no., Fire Pump House - 1 no.) 5700 2 EA
571 5710 Installation, integration, testing and commissioning of addressable type detectors along with accessories, fault isolation module (Inbuilt/ External), structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 5710
572 5720 Combination/Multi-sensor Detector 5720 106 EA
573 5730 Rate of Rise Heat Detector 5730 3 EA
574 5740 IS detector 5740 4 EA
575 5750 Hydrogen Detector 5750 2 EA
576 5760 Installation, integration, testing and commissioning of Manual Call Point along with accessories, fault isolation module (Inbuilt/ External) and structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 5760
577 5770 Ex-proof and weather proof MCP 5770 17 EA
578 5780 Weather proof MCP 5780 11 EA
579 5790 Installation, integration, testing and commissioning of Hooter along with accessories, fault isolation module (inbuilt/ External), structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 5790
580 5800 Weather proof Hooter (Admn bldg-2, CR-1, MCC room-2, Fire pump house - 1, security room-1, TT rest room - 1, aminity room-1 no., Lab -1 NO., sample room-1 no.) 5800 11 EA
581 5810 Installation, integration, testing and commissioning of Response Indicator along with accessories, mounting structure etc required as per standard design engineering, specification and tender document complete in all respect. 5810 40 EA
582 5820 Access Control System 5820
583 5830 Installation, integration, testing and commissioning of half man height bi-directional turnstile (tripod) with controller along with accessories, mounting structure, pressure sensor etc required as per standard design engineering, specification and tender document complete in all respect. (Location : License area entry & exit gate - 2 nos. ; Entry/Exit to tank farm area - 2 nos.) 5830 4 EA
584 5840 Installation, integration, testing and commissioning of half man height dual lane Uni-directional turnstile (tripod) with controller along with accessories, mounting structure, pressure sensor etc required as per standard design engineering, specification and tender document complete in all respect. (Location : At security entry gate -1 SET., security exit gate - 1 SET) 5840 2 SET
585 5850 Installation, integration, testing and commissioning of Retractable Dual Lane Flap barrier with controller along with accessories, mounting structure, pressure sensor etc required as per standard design, engineering, specification and tender document complete in all respect. (Location: Admin building entry/exit ) 5850 1 SET
586 5860 Installation, integration, testing and commissioning of face detection cum fingerprint cum contactless type smart card reader with controller along with electromagnetic door lock of 600 lb for single door/double door, 2 nos. of door position magnetic contact with buzzer etc as per specifications and tender document. (Location : control room entry/exit door - 2 nos., Panel room entry/exit door - 4 nos. ) \nNote: EM locks to be provided at no additional cost to IOCL. 5860 6 EA
587 5870 Installation, integration, testing and commissioning of Biometric fingerprint cum contactless type smart card reader along with accessories, software , programming kit etc required as per standard design engineering, specification and tender document complete in all respect. (Turnstile:- security entry/exit gate -Dual Lane-Uni directional : 2x2 nos. license area entry/exit gates (bi-directional) - 2x2 nos., entry/exit to tank farm area (bi-directional)-2x2 nos., Flap barrier - 2x2nos.) 5870 16 EA
588 5880 Installation, integration, testing and commissioning of Door Frame Metal Detector, 4 nos. hand held metal detector along with accessories, mounting structure etc complete as per specification and tender document. 5880 1 SET
589 5890 Installation of 2"size SS 304 guiding rail along with mounting accessories complete as per specification and tender document near turnstile/ tripod/flap barrier etc to prevent un-authorised movement. 5890 100 M
590 5900 Installation, configuration, integration, testing and commissioning of Redudnant ACS Server for photo pass management & visitor management (19" Rack type at panel Room, form factor - Rack, CPU height - 2U) with minimum 19" colored LED monitor, KVM switch, keyboard, mouse, OS, Antivirus etc located in Control Room complete as per specifications and Tender Document. 5900 1 EA
591 5910 Installation, configuration, integration, testing and commissioning of Access Control cum photopass management System Software for setup, configuration, operation, events, history and archiving, alarm monitoring, recording, printing, time and attendance etc. complete as per specification and tender document including hardwired interface with TAS for ESD input. 5910 1 SET
592 5920 Installation, configuration,integration, testing and commissioning of Client workstation of ACS cum Photopass management with minimum 27" coloured monitor,keyboard, mouse,KVM switch for Rack CPU, OS, Antivirus, HD coloured video camera (for taking visitors photograph) etc for ID badging & issuing of Visitor pass/Photo pass at security Room & other etc. complete as per specifications. 5920
593 5930 Rack Type - CPU in panel room with KVM sitch; Keyboard, mouse along with monitor etc. to be installed in security room for visitor pass 5930 1 EA
594 5940 Tower Type in Photopass room for TT crew/Contractor etc. 5940 1 EA
595 5950 Installation, configuration, integration, testing and commissioning of Laser printer (Monochrome) for Visitor pass printing having flexibility to print on A4, A5, A6 paper complete as per specification and tender document. 5950 1 EA
596 5960 Installation, configuration, integration, testing and commissioning of Colour photo pass printer along with integrated/seperate scanner for photo pass printing as per specification and tender document. 5960 2 EA
597 5970 IP BASED CCTV SURVEILLANCE SYSTEM 5970
598 5980 Installation, configuration, integration, testing and commissioning of 4 port Industrial grade layer 2 Managed POE based Ethernet Switch for connecting Cameras with 4 Nos. RJ copper port and 2 Nos. optical fibre ports with inbuilt/external surge protector (Type 1+2) at the input power supply as per specifications and Tender Document. 5980 3 EA
599 5990 Installation, configuration, integration, testing and commissioning of outdoor Explosion proof cum weatherproof housing (IP 65 or better) suitable for installing Layer 2 switch, PSU, LIU and adaptor for Ethernet switch/media convertor, surge protectors and other accessories of CCTV cameras. Supply of required OFC components & accessories like LIU, splice trays, loaded adaptor, blank plates, UTP cables, Fibre patch cords, pigtails, tags, ties, Ethernet cable with RJ45 connector etc complete in all respect for functioning of CCTV camera.The scope also includes supply of Exd. blinding plugs, Exd. double compression cable glands etc as per specifications and Tender Document. 5990 3 EA
600 6000 Installation,errection & foundation of Heavy Duty self supported Hot Dip Galvanized Poles for mounting of CCTV cameras along with civil foundation along with GI foundation bolt, mounting brackets, ladder arrangement (taking into account of safety during climbing) on the pole for installation and maintenance of cameras, SS nut & bolts for fixing camera and other accessories required for complete installation and commissioning of the pole, submission of structural stability certificate based on existing soil bearing capacity and wind speed from Govt. Engineering colleges etc complete as per specifications and Tender Document of below mentioned height of the pole. (Foundation drawing and other details to be submitted prior to installation as per tender document)\nNote: In case pole do not have ladder arrangment for maintenance purpose, then vendor to arrange for ladder for installation & maintenance purpose throughout the contract period including CAMC period at no additional cost to IOCL. 6000
601 6010 4/6 M pole with Accessories as per specification of Tender 6010 6 EA
602 6020 Installation,commissioning & integration of video wall along with required controller & complete accecories , cables etc , mounting arrangement from wall/ceiling for fire fighting cum critical Alarm display & annuniciation cum CCTV application complete as per specifications and tender document. \nIn control room:-Windows for all cameras should be available on single screen of 300-400 cm2 for min. 150 no. CCTV camera.\n\nNote: Two Number (min. 55” each or meeting size of video wall) for Alarm LED display and Fire fighting display along with one no. of hooter with provision of dual tone sound,ack push button & accessories. 6020 6 EA
603 6030 Installation, commissioning & integration of video wall along with controller & complete accecories , cables etc. for CCTV complete as per specifications and tender document. \nIn location in charge room:-viewing window size should be preferably be between 250-300 cm2 ( in two pages) for CCTV camera. 6030 2 EA
604 6040 Installation, commissioning & integration of video wall along with controller & complete accecories , cables etc. for CCTV complete as per specifications and tender document. \nIn security cabin:-viewing window size should be preferably be between min. 150-200 cm2 ( in two pages) for CCTV camera. 6040 2 EA
605 6050 Installation, testing and commissioning of 350 W LED flood ONLY light luminaries on Light poles up to 10M height including supply & fixing of clamps, scafolding , temporary fire screen ifrequired, supports, nuts,bolts, earthing , required modification infixing arrangement , Supply and welding of mounting structure as persite condition , painting etc. all complete with labour and materials asper drawings, specifications and directions of the Engineer-in-Charge. 6050 6 EA
606 6060 Installation, integration, configuration, testing and commissioning of IP Fixed Bullet cameras with IR MFZ lens (8MP) – 4K resolution along with power supply unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document.(TT Reporting :-2+TTEntry/Exit:-2+Driver Entry/Exit-2,Helper Entry/Exit-2, Photo Pass issuance:- 2) 6060 10 EA
607 6070 Miscellaneous 6070
608 6080 Installation, integration, configuration, testing and commissioning of flameproof cum weather proof to IP 65 or better SIL 2 smart pressure transmitter with in built display, SS manifold, isolation valve, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender).\nNote:1. Pressure transmitter at suction shall have range from -1 Kg/cm2.\n2. Underground tank shall have PT in Pump discharge end only. 6080
609 6090 TLF pump Suction end 6090 18 EA
610 6100 TLF pumps Discharge end 6100 18 EA
611 6110 MS, HSD, Transmix, Ethanol Tanks Sprinkler & Foam Line 6110 40 EA
612 6120 Fire Engine & Jockey Pump 6120 12 EA
613 6130 Sludge/Stripping Pumps suction end---Remote Seal Type 6130 4 EA
614 6140 Sludge/Stripping Pumps discharge end---Remote Seal Type 6140 4 EA
615 6150 Underground tank's pump discharge end 6150 7 EA
616 6160 Installation, integration, configuration, testing and commissioning of flameproof cum weather proof to IP 65 or better SIL 2 Smart Differential pressure transmitter with in built display, SS 3 way manifold, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender) 6160
617 6170 Across TLF pump Strainers 6170 18 EA
618 6180 Across Sludge/Stripping Pumps Strainers---Remote Seal Type 6180 4 EA
619 6190 Installation, integration, configuration, testing and commissioning of flameproof cum weather proof to IP 65 or better bi-colour magnetic flap type level gauge (side mounted) along with level transmitter with installed accuracy +/- 6 mm or better along with mounting accessories, complete as per specification and tender document. 6190
620 6200 Foam (Daughter+Mother) Tanks for HVLR 6200 12 EA
621 6210 Fire Engine Service tanks 6210 8 EA
622 6220 DG Set Service Tanks 6220 3 EA
623 6230 Installation, integration, configuration, testing and commissioning of Level switch ( Magnetic Float / displacer type ) for low and high level alarm along with mounting accessories etc as per specifications 6230
624 6240 Fire water Sump 6240 1 EA
625 6250 TT calibration sump 6250 1 EA
626 6260 Treater water Tank + Service water 6260 2 EA
627 6270 Raw water sump 6270 1 EA
628 6280 Installation, integration, configuration, testing and commissioning of Wailing siren along with controller with a provision to operate locally as well as from control room, mounting accessories etc complete as per specification and tender document. 6280 1 EA
629 6290 Installation, integration, configuration, testing and commissioning of Digital Rodent Repellent System along with mounting accessories for main controller(s) & transducers etc complete as per specification and tender document (Minimum nos of transducers: Control Room - 16 nos., S & D Room - 4 Nos., Invoice room - 4 nos. & Security Room - 4 nos.) 6290 1 LS
630 6300 Installation, integration, configuration, testing and commissioning of Ex-proof and weather proof Hooter cum Beacons along with accessories, mounting structure etc complete as per specification and tender document for audio visual alarm at field in case the MOVs installed at tank dyke drain and tank water draw off line is not fully closed.\nLocation : Near each tank dyke and to be installed outside dyke. 6300 6 EA
631 6310 Installation, integration, configuration, testing and commissioning of Solenoid valves (SOV) of 25 /32/50/65 NB (as per line size) along with one no. of isolation by pass valve to bypass the SOV with associated piping, mounting accessories etc complete as per specification and tender document. \nNote: SOV need to be supplied factory fitted along with baypass valve and both side flanged option.For Ethanol tank's HVLRs SOV is not required. 6310
632 6320 At the inlet of DG set Service tanks 6320 3 EA
633 6330 At the inlet of Fire Engine Service tanks 6330 8 EA
634 6340 At the inlet of HVLR tanks 6340 8 EA
635 6350 Installation, testing and commissioning of MCT block for entire Automation cable entry to Control Room, Admin Building, Invoice Room, Security Room, Customer service room, Driver's Rest Room with minimum 30% spare MCT blocks for future cable entry along with frame and mounting accessories complete as per specification and tender document. 6350 1 LS
636 6360 Installation,testing and commissioning of external surge & Lightening protection devices of suitable connector and type along with accessories complete as per specification and tender document at following places. 6360
637 6370 SPD (Type 2 / IC category C1,C2,C3,D1) - Serial port of MCS (RJ45 type) & Terminal Server 6370 42 EA
638 6380 Type 1 SPD - Earth pit 6380 10 EA
639 6390 Installation, integration, configuration, testing and commissioning of Magnetic flow meter of 65 NB along with two no. SS ball valve with associated piping and mounting accessories etc complete as per specification and tender document. 6390 1 EA
640 6400 Cabling, JB, Earthing: 6400
641 6410 Note: laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc 6410
642 6420 Laying, glanding, ferruling, termination of FRLS Armoured Copper Power cable as per tender specifications. 6420
643 6430 3C x 2.5 sqmm 6430 10875 M
644 6440 4C x 2.5 sqmm 6440 1650 M
645 6450 8C x 2.5 sqmm 6450 3600 M
646 6460 10C x 2.5 sqmm 6460 2850 M
647 6470 12C x 2.5 sqmm 6470 1650 M
648 6480 24C x 2.5 sqmm 6480 2700 M
649 6490 3C x 4 sqmm 6490 4500 M
650 6500 4C x 4 sqmm 6500 1800 M
651 6510 4C x 6 sqmm 6510 75 M
652 6520 4C x 10 sqmm 6520 75 M
653 6530 Laying, glanding, ferruling, termination of FRLS Armoured Aluminium Power cable as per tender specifications. 6530
654 6540 3.5C x 120 sqmm 6540 600 M
655 6550 Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. 6550
656 6560 2C x 1.5 sqmm 6560 9000 M
657 6570 3C x 1.5 sqmm 6570 750 M
658 6580 4C x 1.5 sqmm 6580 6000 M
659 6590 6C x 1.5 sqmm 6590 2250 M
660 6600 8C x 1.5 sqmm 6600 2250 M
661 6610 10C x 1.5 sqmm 6610 1500 M
662 6620 12C x 1.5 sqmm 6620 3750 M
663 6630 16C x 1.5 sqmm 6630 750 M
664 6640 18C x 1.5 sqmm 6640 3000 M
665 6650 20C x 1.5 sqmm 6650 750 M
666 6660 24C x 1.5 sqmm 6660 2625 M
667 6670 32C x 1.5 sqmm 6670 750 M
668 6680 36C x 1.5 sqmm 6680 900 M
669 6690 48C x 1.5 sqmm 6690 4125 M
670 6700 Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. 6700
671 6710 1P x 1.5 sqmm 6710 9000 M
672 6720 2P x 1.5 sqmm 6720 6375 M
673 6730 3P x 1.5 sqmm 6730 1800 M
674 6740 4P x 1.5 sqmm 6740 675 M
675 6750 6P x 1.5 sqmm 6750 1875 M
676 6760 8P x 1.5 sqmm 6760 1125 M
677 6770 10P x 1.5 sqmm 6770 750 M
678 6780 12P x 1.5 sqmm 6780 4125 M
679 6790 16P x 1.5 sqmm 6790 900 M
680 6800 18P x 1.5 sqmm 6800 1125 M
681 6810 1T x 1.5 sqmm 6810 900 M
682 6820 8T x 1.5 sqmm 6820 1875 M
683 6830 Laying, glanding, ferruling, termination of FS Armoured Copper Power cable as per tender specifications. 6830
684 6840 3C x 2.5 sqmm 6840 6000 M
685 6850 3C x 4 sqmm 6850 1350 M
686 6860 4C x 2.5 sqmm 6860 900 M
687 6870 4C x 4 sqmm 6870 1050 M
688 6880 Laying, glanding, ferruling, termination of FS Armoured Copper Control cable as per tender specifications. 6880
689 6890 2C x 1.5 sqmm 6890 4350 M
690 6900 3C x 1.5 sqmm 6900 75 M
691 6910 4C x 1.5 sqmm 6910 1500 M
692 6920 6C x 1.5 sqmm 6920 3150 M
693 6930 8C x 1.5 sqmm 6930 3450 M
694 6940 10C x 1.5 sqmm 6940 750 M
695 6950 12C x 1.5 sqmm 6950 1800 M
696 6960 18C x 1.5 sqmm 6960 750 M
697 6970 24C x 1.5 sqmm 6970 2250 M
698 6980 32C x 1.5 sqmm 6980 1125 M
699 6990 36C x 1.5 sqmm 6990 750 M
700 7000 48C x 1.5 sqmm 7000 1875 M
701 7010 Laying, glanding, ferruling, termination of FS Armoured Copper Signal cable as per tender specifications. 7010
702 7020 1P x 1.5 sqmm 7020 5250 M
703 7030 2P x 1.5 sqmm 7030 4350 M
704 7040 3P x 1.5 sqmm 7040 2400 M
705 7050 4P x 1.5 sqmm 7050 3750 M
706 7060 1T x 1.5 sqmm 7060 3200 M
707 7070 laying, glanding, ferruling, termination of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. 7070 5250 M
708 7080 laying, glanding, ferruling, termination of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. 7080 3000 M
709 7090 laying, glanding, ferruling, termination of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. 7090
710 7100 5/10 m 7100 140 EA
711 7110 15 m 7110 40 EA
712 7120 20 m 7120 30 EA
713 7130 25 m 7130 15 EA
714 7140 30 m 7140 20 EA
715 7150 laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document 7150 18750 M
716 7160 Fabrication , cutting , laying & connection of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 7160 3000 M
717 7170 Fabrication , cutting , laying & connection of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 7170 1500 M
718 7180 Laying of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. 7180
719 7190 50 mm 7190 6000 M
720 7200 100 mm 7200 6750 M
721 7210 150 mm 7210 3000 M
722 7220 300 mm 7220 4500 M
723 7230 600 mm 7230 1500 M
724 7240 Installation of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. 7240
725 7250 24 ways JB 7250 25 EA
726 7260 18 ways JB 7260 25 EA
727 7270 12 ways JB 7270 30 EA
728 7280 8 ways JB 7280 45 EA
729 7290 6 ways JB 7290 45 EA
730 7300 4 ways JB 7300 45 EA
731 7310 Laying of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. 7310 500 M
732 7320 Design, fabrication, painting & errection of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc 7320 20 TO
733 7330 Earth Pit 7330
734 7340 Installation, testing and commisioning of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) 7340
735 7350 TLF gantry 7350 2 EA
736 7360 TT earthing 7360 6 EA
737 7370 Control room 7370 6 EA
738 7380 Tank farm 7380 10 EA
739 7390 Pump house 7390 4 EA
740 7400 SIL VERIFICATION / VALIDATION 7400
741 7410 SIL verification from approved third party agencies. (For SIFs as per SIL Assessment study report/detail engg). All required documentation as per specs and other documentation mentioned elsewhere in tender scope has to be submitted. Complete as per specification / tender documents. 7410 1 LS
742 7420 Validation of entire Safety System (SIS) for SIFs (for e.g. AOPS -SIF) shall be carried out from approved third party agency prior to trial period. Automation contractor shall bear the responsibility of its co-ordination and logistics. The third party has to submit a detailed report along with certification for SIS which is to be approved by IOCL along with all other required documentation as per specification and tender documents. 7420 1 LS
743 7430 Services for Safety Instrumented System testing after installation in presence of safety, operation and engg. Team from user. Demonstration of safety system during pre OISD / OISD & statutory audits & there after periodic testing. Complete as per specifications / tender documents. 7430 1 EA
744 7440 OTHER SERVICES 7440
745 7450 Providing training to IOCL employee as per schedule/Module for 2 days as per tender document 7450 1 Module
746 7460 Submission of detailed system design, Engineering, Documentations etc as per tender document 7460 1 LS
747 7470 Submission of Final Detailed system design, Engineering, Documentations, as built drawings etc complete as per tender 7470 1 LS
748 7480 Resident Engineer support on quarterly basis in case of shift addition during CAMC period 7480 1 EA
749 7490 Design, development, modification, configuration, testing and commissioning of existing TAS software, DCS/PLC logic, GUI etc for implementation of following features after FAT (if required) or during CAMC period as stated in tender document. The job includes necessary tro-& fro travel, lodging, boarding, food etc required for implementation at site complete in all respect and as per direction of EIC. 7490
750 7500 Loading point addition 7500 1 per LP
751 7510 Product pump addition 7510 1 per pump
752 7520 Product tank addition 7520 1 per tank
753 7530 Product code change 7530 1 per product code
754 7540 Comphrehensive AMC - PART -III 7540
755 7550 Comprehensive Annual Maintenance Contract for a period of Seven years for entire Terminal Automation System after successful completion of SAT as described in Technical Bid. \nCost of all the required spares, hardwares, software modification, tools and tackles, ladders, labours, Preventive & Breakdown maintenance Service, calibration of instruments, proving & stampings of metering equipments, rectification/ replacement of faulty TAS equipment etc required for running and maintenance of the entire Terminal Automation System to the desired performance level throughout the contract period of CAMC is included in the item rates and the same has to be borne by the Vendor. \nThe scope also includes posting of Resident Engineer (s) to take care of running and maintenance of the entire Automation System complete as per the tender document. 7550
756 7560 First Year @4% of the basic CAPEX cost 7560 1 LS
757 7570 Second Year @4% of the basic CAPEX cost 7570 1 LS
758 7580 Third Year @7% of the basic CAPEX cost 7580 1 LS
759 7590 Fourth Year @7% of the basic CAPEX cost 7590 1 LS
760 7600 Fifth Year @10% of the basic CAPEX cost 7600 1 LS
761 7610 Sixth Year @6% of the basic CAPEX cost 7610 1 LS
762 7620 Seventh Year @12% of the basic CAPEX cost 7620 1 LS
763 7630 SUPPLY PHASE-II 7630
764 7640 TANK LORRY FILLING 7640
765 7650 Supply of Microprocessor based Coriolis mass flow meter for white oil application along with display unit and mounting accessories with adjustable screw support,bellow for vibrations etc complete as per specifications and tender document for loading of following main products \nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no additional cost to IOCL. 7650
766 7660 MS (for line size of 100 mm ) 7660 8 EA
767 7670 HSD (for line size of 100 mm ) 7670 16 EA
768 7680 Supply of Strainer cum Air eliminator with differential pressure transmitter with display unit & keyboard across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 7680
769 7690 For product line size 100 mm - TLF 7690 24 EA
770 7700 Supply of Multistage Piston type Digital Control Valve (DCV) along with TRV with two nos. isolation valves at inlet and outlet of TRV with associated piping , secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 7700
771 7710 For product line size 100 mm - TLF 7710 24 EA
772 7720 Supply of Triple Offset Butterfly valve with electrical/electro-hydraulic fail safe actuator ON-OFF along with accessories as per installation drawing etc for line size 100 mm complete as per specifications and tender document. 7720 24 EA
773 7730 Supply of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF metering skid complete as per specifications and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 7730 24 EA
774 7740 Supply of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermo well, mounting accessories etc complete as per specifications and tender document. \nNote:Mounting at each TLF loading point on main product for line size 100 mm 7740 24 EA
775 7750 Supply of online proving valves manifold comprising of 1 no. manual operated DBBV without actuator and 2 nos. of 100 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 7750 24 SET
776 7760 Supply of bottom loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm), API Coupler, break away coupler, parking stand with compatible API adaptor, Ex-proof/intrinsic safe position sensor for parking stand, associated piping for connecting loading arm with the metering skid , mounting structure etc complete as per specifications and tender document. Application: MS, HSD 7760 24 EA
777 7770 Supply of vapour recovery arm of size 80 mm NB having 3” (80 NB) with poppeted vapour coupler, break away coupler, NRV, flame arrestor, reducers, mounting structures, parking stand with compatible API adaptor, associated accessories, mounting structure etc complete as per specifications and tender document.\nApplication : MS 7770 8 EA
778 7780 Supply of Ex-proof Rack Monitors for TT overfill protection system along with accessories like 10 pin gantry plug, ATC copper coiled cable of minimum 8m as per API RP1004 including required support for mounting of the Rack Monitor and gantry plug, etc complete as per specifications and tender document.\nNote: In addition to above, minimum 2 nos. portable Rack Monitor along with accessories and 2 nos. lockable bypass switch are to be provided against total supply of Rack Monitor. 7780 16 EA
779 7790 Supply of Resistance - Capacitance type Tank Truck grounding unit along with accessories like 3 nos. of heavy duty flexible coiled cables with high quality rugged, heavy duty SS/ brass grounding socket, FLP double compression glands, Ex-Plug, mounting structure etc, complete as per specification and tender documents.\nNote: (2 nos. of coiled cable with socket for TT earthing relay interlocks and 1 no. for separate earthing of TT) 7790 16 EA
780 7800 Supply of Ex-proof field mounted Remote Interaction Terminal (RIT) along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents. 7800 24 EA
781 7810 Supply of Ex-proof field mounted Driver Ack Push Button station along with FLP double compression glands and Ex-Proof-plug, structural supports etc complete as per specifications and tender documents. 7810 24 EA
782 7820 Supply of Microprocessor based Field mounted dual arm Batch Controller with interface to minimum 2 nos. of main product + 2 nos. of blend product + 2 nos. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document.\n\nAlternatively vendor can supply 2 sets of Microprocessor based Field mounted single arm Batch Controller with interface to minimum 1 no. of main product + 1 no. of blend product + 1 no. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc in place of Dual Arm Batch Controller complete as per specification and tender document. 7820
783 7830 For TLF product loading 7830 16 EA
784 7840 For TT calibration with water 7840
785 7850 Supply of intrinsically safe / flameproof type proximity card reader along with mounting accessories etc complete as per specifications and tender document for authorisation of TT at 7850
786 7860 TLF bays (1 no. Per bay) 7860 16 EA
787 7870 Supply of pre-fabricated Metering Skid (MS structure) for mounting of complete metering equipments as per BOQ and schematic drawing for one main product, one blend product and one additive dosing system. The metering assembly comprises of : \n\nMain product line: Strainer cum Air eliminator, Spool piece with tapping for additive dosing, Online Master Meter proving manifold, MFM,Spool piece with tapping for Temprature Transmitter installation, Pressure transmitter, spool piece with tapping for connecting outlet of TRV, ON-Off valve, DCV, Spool Piece with tapping for Ethanol blending & TRV installation. \n\nBlend Product line: Strainer cum air eliminator, Online Master Meter proving manifold, MFM, Spool piece with tapping for Temperature Transmitter installation, ON-Off valve, DCV, NRV, isolation valve and finally connected to Main stream line tap off point after DCV. \n\nAdditive Dosing System comprises of isolation valve, Additive injection mono block, connecting piping, NRV, isolation valve and finally connecting to Main stream tap off point before MFM. \n\nProvision to be made in the skid for mounting of Batch Controller, Rack Monitor, Grounding unit, RIT, Driver's Ack Push button stations, card reader, FLP sockets, FLP junctions boxes (Power, Signal and Control), FLP power isolator switch, interconnecting cables from respective equipment to JBs, cable trays with covers, glands, support, MS structure,Electroforged galvanized grating, nuts, bolts, gaskets, Tees, bends, elbows, WNRF flanges, nozzles, plugs, isolators, any other equipment if required as per design Engineering etc complete as per specification and tender document. \n\nKindly note, irrespective of facility available or not, each metering skid shall have provision for installation of metering assembly of one main product, one blend product and one additive product as detailed in tender document. \n\nItems including the provision for skid for calibration meters as well. 7870 24 TO
788 7880 Note: \n1. All the equipments, JBs, cable trays, interconnecting cables etc as stated above to be installed and loop tested at factory. Complete assembly to be dispatched at site. The skid to be designed and fabricated by the party taking into consideration of all the equipment sizing, space available for mounting of the skid at the bottom of the gantry etc. The design Engineering along with weight calculation of individual skid excluding equipments to be submitted to IOCL prior to taking up fabrication job for review purpose. Payment shall be made based on theoretical weight calculation of the skid excluding weight of equipments, JBs, cable trays. The rate is also inclusive of surface preparation, painting, transportation of the skid to site etc complete in all respect. \n2. All unuse nozzle/ tapping/ opening to be blind flanged.\n3. For SKO metering SKID, tapping to be provided in the skid for both bottom and top loading as per design Engineering.\n 7880
789 7890 Ethanol Dosing System 7890
790 7900 Supply of Microprocessor based Coriolis mass flow meter for white oil (Ethanol) application alongwith display unit and mounting accessories with adjustable screw support, reducer (if required) etc for line size 2" suitable for maximum flowrate of 500 LPM complete as per specifications and tender document for ethanol blending.\nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no adddtional cost to IOCL . 7900 8 EA
791 7910 Supply of Strainer cum Air eliminator for line size 50 mm with differential pressure transmitter across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 7910 8 EA
792 7920 Supply of Multistage Piston type Digital Control Valve (DCV), NRV, isolation valve for line size 50 mm alongwith accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 7920 8 EA
793 7930 Supply of Piston type, hydraulically operated, solenoid operated ON-OFF Valve along with accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves , tubing arrangement as per installation drawing etc for line size 50 mm complete as per specifications and tender document. \n 7930 8 EA
794 7940 Supply of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermowell for line size 50mm, mounting accessories etc complete as per specifications and tender document. \nNote : One no. of additional thermo well along with accessories to be provided and installed on ethanol point for installation of Master Temperature transmitter with RTD. 7940 8 EA
795 7950 Supply of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 50 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 7950 8 SET
796 7960 Additive dosing System 7960
797 7970 Supply of additive injection mono block along with accessories for XTRAPREMIUM and XTRAMILE complete as per specification and tender document. \nNote - All the wetted parts within Additive injection panel/ block shall be of SS 316 or better. 7970 6 SET
798 7980 Supply of ASTM A106 Gr B Schedule 80 pipe of 25 NB from additive header pipe to additive injection panel at TLF bay complete as per tender document.. 7980 100 M
799 7990 Tank Farm Management System 7990
800 8000 Supply of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 8000
801 8010 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 8010
802 8020 HSD 8020 6 EA
803 8030 For U/G horizontal product tanks 8030
804 8040 BIO-DIESEL 8040 1 EA
805 8050 Supply of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. 8050
806 8060 With minimum 8 elements temperature sensor (for A/G vertical tanks) 8060
807 8070 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 8070
808 8080 HSD 8080 3 EA
809 8090 For U/G horizontal product tanks 8090
810 8100 BIO-DIESEL 8100 1 EA
811 8110 Supply of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 8110
812 8120 For A/G vertical tanks - Three elements 8120
813 8130 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 8130
814 8140 HSD 8140 3 EA
815 8150 For U/G horizontal product tanks-One element 8150
816 8160 BIO-DIESEL 8160 1 EA
817 8170 Supply of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 8170
818 8180 For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) 8180 6 EA
819 8190 For U/G Product tanks 8190 1 EA
820 8200 Supply of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document 8200
821 8210 For A/G Vertical Product tanks 8210 3 EA
822 8220 For U/G horizontal product tanks 8220 1 EA
823 8230 Push Buttons Outside Dyke Walls 8230
824 8240 Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. 8240
825 8250 For ROSOVs (A/G product tank's inlet, outlet and recirculation line) 8250 15 EA
826 8260 ESD PUSH BUTTON STATION 8260
827 8270 Supply of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. 8270
828 8280 Local ESD Push Button Station ( Each Battery of TLF -1X2 no., TLF pump house - 0 no.) 8280 2 EA
829 8290 Plant ESD Push Button Station ( Each battery of TLF - 1X2 No.) 8290 2 EA
830 8300 Control Room equipments 8300
831 8310 Supply of Layer 2 Managed Ethernet Switches along with accessories for connecting BCU with TAS, equipments installed in Customer service room, Lock room, Security room, Terminal Manager room and other TAS equipments as per system architecture and design requirement complete as per specification and tender document.\nNote: \n1. Ethernet switches for BCU communication shall have suitable mounting arrangement to mount inside FLP JBs. \n2. The switches are to be configured in Dual Redundant mode.\n3. All OICs, Workstations, Servers other than that of CCTV, ACS & TFMS are to be connected to both plant management and control LAN so that all the GUIs can be seen in all the PCs irrespective of its nomenclature like TTES, OIC, EWS, TM PC etc.\n4. Printers to be connected to Plant Management LAN and to be configured to all PCs, Workstation, TTES etc so that printout command can be issued from any of the Machine. 8310
832 8320 For BCU integration at TLF (copper ports of 10/100/1000 MBPS)-( Minimum 8 nos. copper ports and 2 nos. optical ports) 8320 8 EA
833 8330 Supply of industrial grade redundant Serial to Ethernet converter of 8 port with mounting acessories etc complete in all respect as per specification and tender document. (Ports:- 6 Main + 2 Spare) 8330
834 8340 For MFM and other serial devices integration to DCS -TLF 8340 2 EA
835 8350 Cabling, JB, Earthing: 8350
836 8360 Note: Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc 8360
837 8370 Supply of FRLS Armoured Copper Power cable as per tender specifications. 8370
838 8380 3C x 2.5 sqmm 8380 3625 M
839 8390 4C x 2.5 sqmm 8390 550 M
840 8400 8C x 2.5 sqmm 8400 1200 M
841 8410 10C x 2.5 sqmm 8410 950 M
842 8420 12C x 2.5 sqmm 8420 550 M
843 8430 24C x 2.5 sqmm 8430 900 M
844 8440 3C x 4 sqmm 8440 1500 M
845 8450 4C x 4 sqmm 8450 600 M
846 8460 4C x 6 sqmm 8460 25 M
847 8470 4C x 10 sqmm 8470 25 M
848 8480 Supply of FRLS Armoured Copper Control cable as per tender specifications. 8480
849 8490 2C x 1.5 sqmm 8490 3000 M
850 8500 3C x 1.5 sqmm 8500 250 M
851 8510 4C x 1.5 sqmm 8510 2000 M
852 8520 6C x 1.5 sqmm 8520 750 M
853 8530 8C x 1.5 sqmm 8530 750 M
854 8540 10C x 1.5 sqmm 8540 500 M
855 8550 12C x 1.5 sqmm 8550 1250 M
856 8560 16C x 1.5 sqmm 8560 250 M
857 8570 18C x 1.5 sqmm 8570 1000 M
858 8580 20C x 1.5 sqmm 8580 250 M
859 8590 24C x 1.5 sqmm 8590 875 M
860 8600 32C x 1.5 sqmm 8600 250 M
861 8610 36C x 1.5 sqmm 8610 300 M
862 8620 48C x 1.5 sqmm 8620 1375 M
863 8630 Supply of FRLS Armoured Copper Signal cable as per tender specifications. 8630
864 8640 1P x 1.5 sqmm 8640 3000 M
865 8650 2P x 1.5 sqmm 8650 2125 M
866 8660 3P x 1.5 sqmm 8660 600 M
867 8670 4P x 1.5 sqmm 8670 225 M
868 8680 6P x 1.5 sqmm 8680 625 M
869 8690 8P x 1.5 sqmm 8690 375 M
870 8700 10P x 1.5 sqmm 8700 250 M
871 8710 12P x 1.5 sqmm 8710 1375 M
872 8720 16P x 1.5 sqmm 8720 300 M
873 8730 18P x 1.5 sqmm 8730 375 M
874 8740 1T x 1.5 sqmm 8740 300 M
875 8750 8T x 1.5 sqmm 8750 625 M
876 8760 Supply of FS Armoured Copper Power cable as per tender specifications. 8760
877 8770 3C x 2.5 sqmm 8770 2000 M
878 8780 3C x 4 sqmm 8780 450 M
879 8790 4C x 2.5 sqmm 8790 300 M
880 8800 4C x 4 sqmm 8800 350 M
881 8810 Supply of FS Armoured Copper Control cable as per tender specifications. 8810
882 8820 2C x 1.5 sqmm 8820 1450 M
883 8830 3C x 1.5 sqmm 8830 25 M
884 8840 4C x 1.5 sqmm 8840 500 M
885 8850 6C x 1.5 sqmm 8850 1050 M
886 8860 8C x 1.5 sqmm 8860 1150 M
887 8870 10C x 1.5 sqmm 8870 250 M
888 8880 12C x 1.5 sqmm 8880 600 M
889 8890 18C x 1.5 sqmm 8890 250 M
890 8900 24C x 1.5 sqmm 8900 750 M
891 8910 32C x 1.5 sqmm 8910 375 M
892 8920 36C x 1.5 sqmm 8920 250 M
893 8930 48C x 1.5 sqmm 8930 625 M
894 8940 Supply of FS Armoured Copper Signal cable as per tender specifications. 8940
895 8950 1P x 1.5 sqmm 8950 1750 M
896 8960 2P x 1.5 sqmm 8960 1450 M
897 8970 3P x 1.5 sqmm 8970 800 M
898 8980 4P x 1.5 sqmm 8980 1250 M
899 8990 Supply of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. 8990 1750 M
900 9000 Supply of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. 9000 1000 M
901 9010 Supply of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. 9010
902 9020 5/10 m 9020 10 EA
903 9030 15 m 9030 10 EA
904 9040 20 m 9040 10 EA
905 9050 25 m 9050 10 EA
906 9060 30 m 9060 5 EA
907 9070 Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document 9070 6250 M
908 9080 Supply of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 9080 1000 M
909 9090 Supply of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 9090 500 M
910 9100 Supply of anodized Aluminium perforated cable trays (2.5mm Thick), tray covers (1.5mm Thick ) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. 9100
911 9110 50 mm 9110 2000 M
912 9120 100 mm 9120 2250 M
913 9130 150 mm 9130 1000 M
914 9140 300 mm 9140 1500 M
915 9150 600 mm 9150 500 M
916 9160 Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. 9160
917 9170 24 ways JB 9170 5 EA
918 9180 18 ways JB 9180 10 EA
919 9190 12 ways JB 9190 10 EA
920 9200 8 ways JB 9200 15 EA
921 9210 6 ways JB 9210 15 EA
922 9220 4 ways JB 9220 15 EA
923 9230 Supply of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. 9230 1000 M
924 9240 Supply of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc 9240 10 TO
925 9250 Earth Pit 9250
926 9260 Supply of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) 9260
927 9270 Tank farm 9270 4 EA
928 9280 SERVICE COMPONENTS PHASE-II 9280
929 9290 TANK LORRY FILLING 9290
930 9300 Installation, integration, testing and commissioning of Microprocessor based Coriolis mass flow meter for white oil application along with display unit and mounting accessories with adjustable screw support,bellow for vibrations etc complete as per specifications and tender document for loading of following main products \nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no additional cost to IOCL. 9300
931 9310 MS (for line size of 100 mm ) 9310 8 EA
932 9320 HSD (for line size of 100 mm ) 9320 16 EA
933 9330 Installation, integration, testing and commissioning of Strainer cum Air eliminator with differential pressure transmitter with display unit & keyboard across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 9330
934 9340 For product line size 100 mm - TLF 9340 24 EA
935 9350 Installation, integration, testing and commissioning of Multistage Piston type Digital Control Valve (DCV) along with TRV with two nos. isolation valves at inlet and outlet of TRV with associated piping , secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 9350
936 9360 For product line size 100 mm - TLF 9360 24 EA
937 9370 Installation, integration, testing and commissioning of Triple Offset Butterfly valve with electrical/electro-hydraulic fail safe actuator ON-OFF along with accessories as per installation drawing etc for line size 100 mm complete as per specifications and tender document. 9370 24 EA
938 9380 Installation, integration, testing and commissioning of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF metering skid complete as per specifications and tender document. \n(Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 9380 24 EA
939 9390 Installation, integration, testing and commissioning of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermo well, mounting accessories etc complete as per specifications and tender document. \n(Mounting at each TLF loading point on main product for line size 100 mm) 9390 24 EA
940 9400 Installation, integration, testing and commissioning of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 100 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 9400 24 SET
941 9410 Installation, testing and commissioning of bottom loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm), API Coupler, break away coupler, parking stand with compatible API adaptor, Ex-proof/intrinsic safe position sensor for parking stand, associated piping for connecting loading arm with the metering skid , mounting structure etc complete as per specifications and tender document. \nApplication: MS, HSD, MS+ETHANOL 9410 24 EA
942 9420 Installation, testing and commissioning of vapour recovery arm of size 80 mm NB having 3” (80 NB) with poppeted vapour coupler, break away coupler, NRV, flame arrestor, reducers, mounting structures, parking stand with compatible API adaptor, associated accessories, mounting structure etc complete as per specifications and tender document.\nApplication : MS 9420 8 EA
943 9430 Installation, testing and commissioning of Ex-proof Rack Monitors for TT overfill protection system along with accessories like 10 pin gantry plug, ATC copper coiled cable of minimum 8m as per API RP1004 including required support for mounting of the Rack Monitor and gantry plug, etc complete as per specifications and tender document.\nNote: In addition to above, minimum 2 nos. portable Rack Monitor along with accessories and 2 nos. lockable bypass switch are to be provided against total supply of Rack Monitor. 9430 16 EA
944 9440 Installation, integration, testing and commissioning of Resistance - Capacitance type Tank Truck grounding unit along with accessories like 3 nos. of heavy duty flexible coiled cables with high quality rugged, heavy duty SS/ brass grounding socket, FLP double compression glands, Ex-Plug, mounting structure etc, complete as per specification and tender documents.\n(2 nos. of coiled cable with socket for TT earthing relay interlocks and 1 no. for separate earthing of TT) 9440 16 EA
945 9450 Installation, integration, testing and commissioning of Ex-proof field mounted Remote Interaction Terminal (RIT) along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents. 9450 24 EA
946 9460 Installation, integration, testing and commissioning of Ex-proof field mounted Driver Ack Push Button station along with FLP double compression glands and Ex-Proof-plug, structural supports etc complete as per specifications and tender documents. 9460 24 EA
947 9470 Installation, integration, testing and commissioning of Microprocessor based Field mounted dual arm Batch Controller with interface to minimum 2 nos. of main product + 2 nos. of blend product + 2 nos. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document.\nOr\nInstallation, integration, testing and commissioning can supply 2 sets of Microprocessor based Field mounted single arm Batch Controller with interface to minimum 1 no. of main product + 1 no. of blend product + 1 no. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc in place of Dual Arm Batch Controller complete as per specification and tender document. 9470
948 9480 For TLF product loading 9480 16 EA
949 9490 For TT calibration with water 9490
950 9500 Installation, testing and commissioning of intrinsically safe / flameproof type proximity card reader along with mounting accessories etc complete as per specifications and tender document for authorisation of TT at 9500
951 9510 TLF bays (1 no. Per bay) 9510 16 EA
952 9520 Installation of pre-fabricated Metering Skid (MS structure) for mounting of complete metering equipments as per BOQ and schematic drawing for one main product, one blend product and one additive dosing system. The metering assembly comprises of : \n\nMain product line: Strainer cum Air eliminator, Spool piece with tapping for additive dosing, Online Master Meter proving manifold, MFM,Spool piece with tapping for Temprature Transmitter installation, Pressure transmitter, spool piece with tapping for connecting outlet of TRV, ON-Off valve, DCV, Spool Piece with tapping for Ethanol blending & TRV installation. \n\nBlend Product line: Strainer cum air eliminator, Online Master Meter proving manifold, MFM, Spool piece with tapping for Temperature Transmitter installation, ON-Off valve, DCV, NRV, isolation valve and finally connected to Main stream line tap off point after DCV. \n\nAdditive Dosing System comprises of isolation valve, Additive injection mono block, connecting piping, NRV, isolation valve and finally connecting to Main stream tap off point before MFM. \n\nProvision to be made in the skid for mounting of Batch Controller, Rack Monitor, Grounding unit, RIT, Driver's Ack Push button stations, card reader, FLP sockets, FLP junctions boxes (Power, Signal and Control), FLP power isolator switch, interconnecting cables from respective equipment to JBs, cable trays with covers, glands, support, MS structure,Electroforged galvanized grating, nuts, bolts, gaskets, Tees, bends, elbows, WNRF flanges, nozzles, plugs, isolators, any other equipment if required as per design Engineering etc complete as per specification and tender document. \n\nKindly note, irrespective of facility available or not, each metering skid shall have provision for installation of metering assembly of one main product, one blend product and one additive product as detailed in tender document. 9520 24 TO
953 9530 Note: \n1. All the equipments, JBs, cable trays, interconnecting cables etc as stated above to be installed and loop tested at factory. Complete assembly to be dispatched at site. The skid to be designed and fabricated by the party taking into consideration of all the equipment sizing, space available for mounting of the skid at the bottom of the gantry etc. The design Engineering along with weight calculation of individual skid excluding equipments to be submitted to IOCL prior to taking up fabrication job for review purpose. Payment shall be made based on theoretical weight calculation of the skid excluding weight of equipments, JBs, cable trays. The rate is also inclusive of surface preparation, powder coating, painting, transportation of the skid to site etc complete in all respect. \n2. All unuse nozzle/ tapping/ opening to be blind flanged.\n3. For SKO metering SKID, tapping to be provided in the skid for both bottom and top loading as per design Engineering.\n 9530
954 9540 Ethanol Dosing System 9540
955 9550 Installation, integration, testing and commissioning of Microprocessor based Coriolis mass flow meter for white oil (Ethanol) application alongwith display unit and mounting accessories with adjustable screw support, reducer (if required) etc for line size 2" suitable for maximum flowrate of 500 LPM complete as per specifications and tender document for ethanol blending.\nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no adddtional cost to IOCL . 9550 8 EA
956 9560 Installation, integration, testing and commissioning of Strainer cum Air eliminator for line size 50 mm with differential pressure transmitter across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 9560 8 EA
957 9570 Installation, integration, testing and commissioning of Multistage Piston type Digital Control Valve (DCV), NRV, isolation valve for line size 50 mm alongwith accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 9570 8 EA
958 9580 Installation, integration, testing and commissioning of Piston type, hydraulically operated, solenoid operated ON-OFF Valve along with accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves , tubing arrangement as per installation drawing etc for line size 50 mm complete as per specifications and tender document. 9580 8 EA
959 9590 Installation, integration, testing and commissioning of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermowell for line size 50mm, mounting accessories etc complete as per specifications and tender document. \nNote : One no. of additional thermo well along with accessories to be provided and installed on ethanol point for installation of Master Temperature transmitter with RTD. 9590 8 EA
960 9600 Installation, testing and commissioning of online proving valves manifold comprising of 1 no. manual operated DBBV without actuator and 2 nos. of 50 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 9600 8 SET
961 9610 Additive dosing System 9610
962 9620 Installation, integration, testing and commissioning of additive injection mono block along with accessories for XTRAPREMIUM and XTRAMILE complete as per specification and tender document.\nNote - All the wetted parts within Additive injection panel/ block shall be of SS 316 or better. 9620 6 SET
963 9630 laying ,welding & commissioning of ASTM A106 Gr B Schedule 80 pipe of 25 NB from additive header pipe to additive injection panel at TLF bay complete as per tender document.. 9630 100 M
964 9640 Tank Farm Management System 9640
965 9650 Installation, integration, testing and commissioning of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 9650
966 9660 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 9660
967 9670 HSD 9670 6 EA
968 9680 For U/G horizontal product tanks 9680
969 9690 BIO-DIESEL 9690 1 EA
970 9700 Installation,integration,testing and commissioning of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. 9700
971 9710 With minimum 8 elements temperature sensor (for A/G vertical tanks) 9710
972 9720 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 9720
973 9730 HSD 9730 3 EA
974 9740 For U/G horizontal product tanks 9740
975 9750 BIO-DIESEL 9750 1 EA
976 9760 Installation,integration,testing and commissioning of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 9760
977 9770 For A/G vertical tanks - Three elements 9770
978 9780 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 9780
979 9790 HSD 9790 3 EA
980 9800 For U/G horizontal product tanks-One element 9800
981 9810 BIO-DIESEL 9810 1 EA
982 9820 Installation,integration,testing and commissioning of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 9820
983 9830 For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) 9830 6 EA
984 9840 For U/G Product tanks 9840 1 EA
985 9850 Installation,integration,testing and commissioning of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document 9850
986 9860 For A/G Vertical Product tanks 9860 3 EA
987 9870 For U/G horizontal product tanks 9870 1 EA
988 9880 Push Buttons Outside Dyke Walls 9880
989 9890 Installation,integration,testing and commissioning of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS, along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. 9890
990 9900 For ROSOVs (A/G product tank's inlet, outlet and recirculation line) 9900 15 EA
991 9910 ESD PUSH BUTTON STATION 9910
992 9920 Installation,testing and commissioning of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. 9920
993 9930 Local ESD Push Button Station ( Each Battery of TLF -1X2 no., TLF pump house - 0 no.) 9930 2 EA
994 9940 Plant ESD Push Button Station ( Each battery of TLF - 1X2 No.) 9940 2 EA
995 9950 Control Room equipments 9950
996 9960 Installation, configuration, integration, testing and commissioning of Layer 2 Managed Ethernet Switches along with accessories for connecting BCU with TAS, equipments installed in Customer service room, Lock room, Security room, Terminal Manager room and other TAS equipments as per system architecture and design requirement complete as per specification and tender document.\nNote: \n1. Ethernet switches for BCU communication shall have suitable mounting arrangement to mount inside FLP JBs. \n2. The switches are to be configured in Dual Redundant mode.\n3. All OICs, Workstations, Servers other than that of CCTV, ACS & TFMS are to be connected to both plant management and control LAN so that all the GUIs can be seen in all the PCs irrespective of its nomenclature like TTES, OIC, EWS, TM PC etc.\n4. Printers to be connected to Plant Management LAN and to be configured to all PCs, Workstation, TTES etc so that printout command can be issued from any of the Machine. 9960
997 9970 For BCU integration at TLF (copper ports of 10/100/1000 MBPS)-( Minimum 8 nos. copper ports and 2 nos. optical ports) 9970 8 EA
998 9980 Installation, testing and commissioning of industrial grade redundant Serial to Ethernet converter of 8 port with mounting acessories etc complete in all respect as per specification and tender document. (Ports:- 6 Main + 2 Spare) 9980
999 9990 For MFM and other serial devices integration to DCS -TLF 9990 2 EA
1000 10000 Cabling, JB, Earthing: 10000
1001 10010 Note: laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc 10010
1002 10020 Laying, glanding, ferruling, termination of FRLS Armoured Copper Power cable as per tender specifications. 10020
1003 10030 3C x 2.5 sqmm 10030 3625 M
1004 10040 4C x 2.5 sqmm 10040 550 M
1005 10050 8C x 2.5 sqmm 10050 1200 M
1006 10060 10C x 2.5 sqmm 10060 950 M
1007 10070 12C x 2.5 sqmm 10070 550 M
1008 10080 24C x 2.5 sqmm 10080 900 M
1009 10090 3C x 4 sqmm 10090 1500 M
1010 10100 4C x 4 sqmm 10100 600 M
1011 10110 4C x 6 sqmm 10110 25 M
1012 10120 4C x 10 sqmm 10120 25 M
1013 10130 Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. 10130
1014 10140 2C x 1.5 sqmm 10140 3000 M
1015 10150 3C x 1.5 sqmm 10150 250 M
1016 10160 4C x 1.5 sqmm 10160 2000 M
1017 10170 6C x 1.5 sqmm 10170 750 M
1018 10180 8C x 1.5 sqmm 10180 750 M
1019 10190 10C x 1.5 sqmm 10190 500 M
1020 10200 12C x 1.5 sqmm 10200 1250 M
1021 10210 16C x 1.5 sqmm 10210 250 M
1022 10220 18C x 1.5 sqmm 10220 1000 M
1023 10230 20C x 1.5 sqmm 10230 250 M
1024 10240 24C x 1.5 sqmm 10240 875 M
1025 10250 32C x 1.5 sqmm 10250 250 M
1026 10260 36C x 1.5 sqmm 10260 300 M
1027 10270 48C x 1.5 sqmm 10270 1375 M
1028 10280 Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. 10280
1029 10290 1P x 1.5 sqmm 10290 3000 M
1030 10300 2P x 1.5 sqmm 10300 2125 M
1031 10310 3P x 1.5 sqmm 10310 600 M
1032 10320 4P x 1.5 sqmm 10320 225 M
1033 10330 6P x 1.5 sqmm 10330 625 M
1034 10340 8P x 1.5 sqmm 10340 375 M
1035 10350 10P x 1.5 sqmm 10350 250 M
1036 10360 12P x 1.5 sqmm 10360 1375 M
1037 10370 16P x 1.5 sqmm 10370 300 M
1038 10380 18P x 1.5 sqmm 10380 375 M
1039 10390 1T x 1.5 sqmm 10390 300 M
1040 10400 8T x 1.5 sqmm 10400 625 M
1041 10410 Laying, glanding, ferruling, termination of FS Armoured Copper Power cable as per tender specifications. 10410
1042 10420 3C x 2.5 sqmm 10420 2000 M
1043 10430 3C x 4 sqmm 10430 450 M
1044 10440 4C x 2.5 sqmm 10440 300 M
1045 10450 4C x 4 sqmm 10450 350 M
1046 10460 Laying, glanding, ferruling, termination of FS Armoured Copper Control cable as per tender specifications. 10460
1047 10470 2C x 1.5 sqmm 10470 1450 M
1048 10480 3C x 1.5 sqmm 10480 25 M
1049 10490 4C x 1.5 sqmm 10490 500 M
1050 10500 6C x 1.5 sqmm 10500 1050 M
1051 10510 8C x 1.5 sqmm 10510 1150 M
1052 10520 10C x 1.5 sqmm 10520 250 M
1053 10530 12C x 1.5 sqmm 10530 600 M
1054 10540 18C x 1.5 sqmm 10540 250 M
1055 10550 24C x 1.5 sqmm 10550 750 M
1056 10560 32C x 1.5 sqmm 10560 375 M
1057 10570 36C x 1.5 sqmm 10570 250 M
1058 10580 48C x 1.5 sqmm 10580 625 M
1059 10590 Laying, glanding, ferruling, termination of FS Armoured Copper Signal cable as per tender specifications. 10590
1060 10600 1P x 1.5 sqmm 10600 1750 M
1061 10610 2P x 1.5 sqmm 10610 1450 M
1062 10620 3P x 1.5 sqmm 10620 800 M
1063 10630 4P x 1.5 sqmm 10630 1250 M
1064 10640 laying, glanding, ferruling, termination of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. 10640 1750 M
1065 10650 laying, glanding, ferruling, termination of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. 10650 1000 M
1066 10660 laying, glanding, ferruling, termination of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. 10660
1067 10670 5/10 m 10670 10 EA
1068 10680 15 m 10680 10 EA
1069 10690 20 m 10690 10 EA
1070 10700 25 m 10700 10 EA
1071 10710 30 m 10710 5 EA
1072 10720 laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document 10720 6250 M
1073 10730 Fabrication , cutting , laying & connection of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 10730 1000 M
1074 10740 Fabrication , cutting , laying & connection of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 10740 500 M
1075 10750 Laying of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. 10750
1076 10760 50 mm 10760 2000 M
1077 10770 100 mm 10770 2250 M
1078 10780 150 mm 10780 1000 M
1079 10790 300 mm 10790 1500 M
1080 10800 600 mm 10800 500 M
1081 10810 Installation of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. 10810
1082 10820 24 ways JB 10820 5 EA
1083 10830 18 ways JB 10830 10 EA
1084 10840 12 ways JB 10840 10 EA
1085 10850 8 ways JB 10850 15 EA
1086 10860 6 ways JB 10860 15 EA
1087 10870 4 ways JB 10870 15 EA
1088 10880 Laying of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. 10880 1000 M
1089 10890 Design, fabrication, painting & errection of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc 10890 10 TO
1090 10900 Earth Pit 10900
1091 10910 Installation, testing and commisioning of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) 10910
1092 10920 Tank farm 10920 4 EA
1093 10930 Comphrehensive AMC - PART -III 10930
1094 10940 Comprehensive Annual Maintenance Contract for a period of Seven years for entire Terminal Automation System after successful completion of SAT as described in Technical Bid. \nCost of all the required spares, hardwares, software modification, tools and tackles, ladders, labours, Preventive & Breakdown maintenance Service, calibration of instruments, proving & stampings of metering equipments, rectification/ replacement of faulty TAS equipment etc required for running and maintenance of the entire Terminal Automation System to the desired performance level throughout the contract period of CAMC is included in the item rates and the same has to be borne by the Vendor. \nThe scope also includes posting of Resident Engineer (s) to take care of running and maintenance of the entire Automation System complete as per the tender document. 10940
1095 10950 First Year @4% of the basic CAPEX cost 10950 1 LS
1096 10960 Second Year @4% of the basic CAPEX cost 10960 1 LS
1097 10970 Third Year @7% of the basic CAPEX cost 10970 1 LS
1098 10980 Fourth Year @7% of the basic CAPEX cost 10980 1 LS
1099 10990 Fifth Year @10% of the basic CAPEX cost 10990 1 LS
1100 11000 Sixth Year @6% of the basic CAPEX cost 11000 1 LS
1101 11010 Seventh Year @12% of the basic CAPEX cost 11010 1 LS
Disclaimer :