| 1 | 1 | Supplying & Installation, Testing and commissioning of 17 TR R-410 with twin scroll compressor capacity outdoor unit with matching capacity indoor unit suitable for atleast 6800 cfm air capacity ductable split air conditioners fitting complete with including MS painted stand for outdoor units suitable size foundation and allied minor civil works as per drawings, spicifacations and instructions of engineer in charge of following rating including electric control panel & fitting as per specifications. (Make Carrier / Hitachi / Daikin) | item 1 | 1 | NO |
|---|
| 2 | 2 | Supplying & Installation,Testing and commissioning of 11 TR R-410 with twin scroll compressor capacity outdoor unit with matching capacity indoor unit suitable for atleast 4400 cfm air capacity ductable split air conditioners fitting complete with including MS painted stand for outdoor units suitable size foundation and allied minor civil works as per drawings, spicifacations and instructions of engineer in charge of following rating including electric control panel & fitting as per specifications (Make Carrier / Hitachi / Daikin) | item 2 | 1 | NO |
|---|
| 3 | 3 | Supplying & Installation, Testing and commissioning of 8.5 TR R-410 with twin scroll compressor capacity outdoor unit with matching capacity indoor unit suitable for atleast 3400 cfm air capacity ductable split air conditioners fitting complete with including MS painted stand for outdoor units suitable size foundation and allied minor civil works as per drawings, spicifacations and instructions of engineer in charge of following rating including electric control panel & fitting as per specifications (Make Carrier / Hitachi / Daikin) | item 3 | 1 | NO |
|---|
| 4 | 4 | Supplying & Installation, Testing and commissioning of 5.5 TR R-410 with twin scroll compressor capacity outdoor unit with matching capacity indoor unit suitable for atleast 2200 cfm air capacity ductable split air conditioners fitting complete with including MS painted stand for outdoor units suitable size foundation and allied minor civil works as per drawings, spicifacations and instructions of engineer in charge of following rating including electric control panel & fitting as per specifications (Make Carrier / Hitachi / Daikin) | item 4 | 3 | NO |
|---|
| 5 | 5 | Supplying & Installation, Testing and commissioning of refrigerant copper piping 17, 11, 8.5, 5.5 TR units size as per OEM design manual (per circuit) complete with all fitting such as bends, tees, elbow ets. Including insulation as per sepecifications and cabling between indoor and outdoor units. the quoted rates shall include rates for chiseling, making good of wall and clamps etc. Make :- Tataline/ Rajco/Mandev | item 5 | 230 | RMT |
|---|
| 6 | 6 | Providing and fixing in position the 40mm dia . Pvc pipes cut to required lengths and installed with all joints with the necessary elbows , tees and redcers ets with 9mm thick nitrile rubber insulation on condensate drain piping as per the approved shop drawing and specifications. Make:- Prince/ Supreme | item 6 | 70 | RMT |
|---|
| 7 | 7 | Supply ,installation, testing and commissioning of GS sheetmetal ducting complete with supports, dompers ets. As per is 655 and approved drawing and as per specification of 24 gauge. Make:- Sail/ Tata | item 7 | 315 | sqm |
|---|
| 8 | 8 | Supply ,installation, testing and commissioning of GS sheetmetal ducting complete with supports, dompers ets. As per is 655 and approved drawing and as per specification of 22 gauge. Make:- Sail/ Tata | item 8 | 65 | sqm |
|---|
| 9 | 9 | Supply, installation testing and commissioning os closed cell nitrile rubber insulation of following thickness applied with proper adhesive and sealed with 75 mm wide aluminium tape onall longitudinal / transverse joints complete as per sepcifications. 9mm thick on ducts in conditioned space. Make:- Armacell / K flex / vido flex | item 9 | 315 | sqm |
|---|
| 10 | 10 | Supply ,installation, testing and commissioning of 32 kg /m3 density fiberglass insulation in the from of 12 mm thich acoustic lining fiber glass boards , 2 layers of tissue paper finished with 28 gauhe perforated aluminum sheet with nuts, bolts complete as per specifications. Make :- UP twiga / Owen corning | item 10 | 65 | sqm |
|---|
| 11 | 11 | providing and fixing canves fire retardant non porous dounle layer fiexible connection between each inder unit and duct as per approved drawings and sepecifications . | item 11 | 6 | NOS |
|---|
| 12 | 12 | Supply, intallation and testing of GI construction louver dampers within ducts to be provided with suitable ducts lever quadrants for manual control of volume of air flow and for proper balanicing of the air distribution system complete as per approved drawings and specifications. Make:- Caryaire / Ravistar / airflow | item 12 | 10 | Sqm |
|---|
| 13 | 13 | Supply, intallation and testing and balancing of powder coated extruded aluminum construction linear grilles as per approved drawing and sepecations. Quoted price shall be without volume control domper at the location of air callar .Make:- Caryaire / Ravistar / Airflow | item 13 | 14 | Sqm |
|---|
| 14 | 14 | Supply, intallation and testing and balancing of powder coated extruded aluminum spuare shape ceiling diffusers with removable core and anti smudge as per approved drawing and specifications. Make:- Caryaire / Ravistar / Airflow | item 14 | 12 | Sqm |
|---|
| 15 | 15 | Supplying & fixing of fresh air grill with bird screen as per approved drawing and as per approved drawing and specifications. Make:- Caryaire / Ravistar / Airflow | item 15 | 5 | Sqm |
|---|
| 16 | 16 | Supply, intallation and testing and commissioning of refrigeration conttrol cable with all fitting and including insulation as per specifacation between indoor and outdoor unti for 17Tr unit. Make:- Havells/Polycab | item 16 | 240 | Rmt |
|---|
| 17 | 17 | Supplying and laying of following 1100 volt grade PVC insulated sheathed conductor armoured cables / copper cables on tays, in trenches on walls clamped to wall with suitable clamps , saddles ,and fixing bolts , or laying in ground including cost of digging brick and sand protection and including commissioning of 4x16 sqmm (copper unarmoured) Make:- Havells/Polycab | item 17 | 190 | Rmt |
|---|
| 18 | 18 | Supply & Erection of Step type Heater 3 KW X 6 No. in ducting including MCB TPN , SCR fuse ,Thermostat for high temp, Airflow suitch complete in all respect as and desired by the Engineer in charge at site for 17 Tr. Make :- rapid cool/ Dass pass | item 18 | 1 | Nos |
|---|
| 19 | 19 | Supply & Erection of Step type Heater 3 KW X 3 No. in ducting including MCB TPN , SCR fuse ,Thermostat for high temp, Airflow suitch complete in all respect as and desired by the Engineer in charge at site for 11 TR. Make :- rapid cool/ Dass pass | item 19 | 1 | Nos |
|---|
| 20 | 20 | Supply & Erection of Step type Heater 3 KW X 2 No. in ducting including MCB TPN , SCR fuse ,Thermostat for high temp, Airflow suitch complete in all respect as and desired by the Engineer in charge at site for 8.5 TR. Make :- rapid cool/ Dass pass | item 20 | 1 | Nos |
|---|
| 21 | 21 | Supply & Erection of Step type Heater 3 KW X 2 No. in ducting including MCB TPN , SCR fuse ,Thermostat for high temp, Airflow suitch complete in all respect as and desired by the Engineer in charge at site for 5.5 TR Make :- rapid cool/ Dass pass | item 21 | 2 | Nos |
|---|