Provision Of Fire Alarm System For Joc ( Koc ) Naval Base Kochi, Kochi-Kerala

Military Engineer Services-MES has published Provision Of Fire Alarm System For Joc ( Koc ) Naval Base Kochi. Submission Date for this Tender is 17-06-2020. Fire Alarm Systems Tenders in Kochi Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

24011763
Corrigendum : Provision Of Fire Alarm System For Joc ( Koc ) Naval Base Kochi
Open Tender
Indian
Kerala
Kochi
17-06-2020

Tender Details

Provision Of Fire Alarm System For Joc ( Koc ) Naval Base Kochi

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 24-Mar-2020 Corrigendum No1 Date 15-04-2020
2 13-Apr-2020 Corrigendum No 3 Date 21-04-2020
3 20-Apr-2020 Corrigendum No3a Date 05-05-2020
4 04-May-2020 Corrigendum No4 Date 12-05-2020
5 11-May-2020 Corrigendum No5 Date 19-05-2020
6 18-May-2020 Corrigendum No6 Date 03-06-2020
7 03-Jun-2020 Corrigendum No7 Date 10-06-2020
8 10-Jun-2020 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-06-2020

Key Value

Document Fees
INR 2000 /-
EMD
INR 315000.0 /-
Tender Value
INR 2.40 Crore /-

BOQ Items

Name of Work: PROVISION OF FIRE ALARM SYSTEM FOR JOC(KOC) NAVAL BASE (KOCHI)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 LIST OF WORKS
2 2 Schedule A Part I to Part VII
3 3 Total amount of Sch 'A' part-I (Buildings & Structures) 1 Lumpsum
4 4 Total amount of Sch 'A' part-II (Excavation and Earth work) 1 Lumpsum
5 5 Total amount of Sch 'A' part-III ( Addn/Altn & Special repairs of building) 1 Lumpsum
6 6 Total amount of Sch 'A' part-IV (Internal Electrification) 1 Lumpsum
7 7 Total amount of Sch 'A' part-V (Internal Water Supply) 1 Lumpsum
8 8 Total amount of Sch 'A' part-VI (External Electric Supply) 1 Lumpsum
9 9 Total amount of Sch 'A' part-VII (External Water Supply) 1 Lumpsum
10 10 Sch 'A' Part- VIII (MISCELLANEOUS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
11 11 Internal Electrification:- Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 1.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) including PVC insulated multi-stranded copper conductor 1.5 Sqmm nominal cross sectional area single core F.R.L.S. cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed at site for the following:- (NOTE: Switch and socket to be measured and paid for separately):-
12 12 (a) One light/Ceiling Fan/exhaust fan point controlled by one 5/6 amps one way switch. 11 Point
13 13 (b) One Socket outlet, three/five pin, 5 Amp, independent controlled by one 5/6 amps one way switch or switch/socket combination 5 amps, 5 pin. 2 Point
14 14 Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 2.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty, PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) , including PVC insulated multi-stranded copper conductor 2.5 Sq mm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed at site for the one 3/5 pin 15/16 amps socket outlet independent:- (Incl Geyser 160 pts) (NOTE: Switch and socket to be measured and paid for separately) 3 Point
15 15 Modular switch 1 way 6 A,1 module 230 Volts,50Hz, ISI marked complete all specified and directed. 13 Each
16 16 Modular switch 1 way 16 A, 1 module 230 Volts,50Hz, ISI marked complete all specified and directed. 3 Each
17 17 Socket, 6A-2/3 pin combined 2 module 230 Volts,50Hz, ISI marked complete all specified and directed. 2 Each
18 18 Socket, 16A-2/3 pin combined 2 module 230 Volts,50Hz, ISI marked complete all specified and directed. 3 Each
19 19 Ceiling fan 1400 mm sweep copper wound, including fixing of down rod and connecting up complete with and including three core flexible PVC insulated multi stranded copper conductor cable of size 0.5 Sq mm from ceiling rose/ connector to fan.(Make :CG/USHA/HAVELLS) 1 Each
20 20 Exhaust fan 250 mm sweep 230 Volts AC 50 Hz PVC body with copper wound and including complete all as specified and directed at site. 3 Each
21 21 LED Tube light 1X18/20 Watt 6000K Havells Cat Part No LHEWEBP7IN1W/020 or equivalent in other makes in list of manufacturer 7 Each
22 22 MCB DB SPN 8 way double door 240 Volts without bus bar 1 Each
23 23 MCB SP 06 to 32 Amps "C" Curve 6 Each
24 24 MCB SPN 06 to 32 Amps "C" Curve 1 Each
25 25 Internal Water Supply:-CPVC pipe, 20 mm OD SDR-11 with SDR 11 fittings fixed on wall/ceiling including suitable saddles clamps screws etc or conceiled in wall whereever required and making good the disturbed surface all as specified and directed. 3 Running Meter
26 26 CPVC pipe, 16 mm OD SDR-11 with SDR 11 fittings fixed on wall/ceiling including suitable saddles clamps screws etc or conceiled in wall whereever required and making good the disturbed surface all as specified and directed. 1 Running Meter
27 27 Gun metal gate valve with iron wheel head screwed both ends 20 mm dia complete all as specified and directed. 1 Each
28 28 Angular stop cock, chromium plated, cast copper alloy, screwed down, screwed for CPVC pipe 15 mm dia bore complete all as specified and directed. 2 Each
29 29 External Electric Supply:- Cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric cable (heavy duty) with stranded aluminium conductors, 1100 volts grade of size 400 sqmm 3.5 core including suitable double compression stainless steel gland all as specified and directed by Engr-in-Charge 160 Running Meter
30 30 Cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric cable (heavy duty) with stranded aluminium conductors, 1100 volts grade of size 240 sqmm 3.5 core including suitable double compression stainless steel gland all as specified and directed by Engr-in-Charge 40 Running Meter
31 31 Onload chage over switch with sheet steel enclosure 400 Amp 4 Pole 415 V as per Indoasian Cat part No ICASO 400 or equivalent with all fixing accessories all as specified. 1 Each
32 32 Indoor type floor mounted LT panel suitable for 415 volts, 3 phase 4 wire , 50 Hz AC supply system conforming to IS:8623/93, floor mounted, factory made, weather and vermin proof, fully ventilated and fabricated out of angle iron 40mm X 40mm X 6mm thick frame work and MS CRCA sheet 2mm thick having aluminium bus bar of rating 1000 Amps, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. The panel shall be front and back openable and having inner & outer shells. The inner shell duly compartmented for each control gear, including powder coating internally and externally the entire steel surfaces. All the cover shall be provided with suitable locking arrangements. The size of the outer shell should not be less than 1500mm x 1000mm x 500mm, mounted on angle iron stand made out of size 40mm x 40mm x 6mm grouted in PCC 1:3:6, type C-2, including two coats of synthetic enamel paint over a coat of red oxide primer including following gears and suitable size of Digital volt meter & apms meter with CTs including taking down of old existing panel complete all as specified and directed:- 1 Each
33 33 (a) Bus bar chamber of 3 phase and 1 neutral 4 strip 415 volts with 1000 Amps aluminium strip - 1 set (b) ACB 630 Amp 4 pole -01 No (Incoming) (c) MCCB 400 Amp 35 KA 4 pole -01 No (Outgoing) (d) MCCB 125 Amp 35 KA 4 pole -01 No (Outgoing) (e) Volt meter digital 0-500 volt = 01 (f) Amp meter digital 0 -200 Amp = 01 (g) Indicator lamp yellow , Red , blue - 01 Set
34 34 Horizondal drilling for laying of HT/LT cable to avoid road cutting at required depth by trenchless technology using ultra sound techniqueand necessasry machine including inserting of 110mm OD HDPE pipe of pressure rating 0.8 Mpa. The work also includes connecting underground scanning for cable, pipe line etc to avoid damages on drilling length complete all as specified and as directed. 150 Running Metre
35 35 External Water Supply:- Stop valves 15mm size, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed all as specified and as directed of size 50 mm .” 1 Each
36 36 Fire Alaram System:- Supply installation testing and commissioning of 32 Bit Microprocessor based Intelligent Addressable 2 Loop Main Fire Alarm Panel expandable to 10 Loops having loop capacity of minimum 250 devices per loop with 4000 event plus 1000 alarm log history events, QWERTY keypad for programming with inbuilt panel display.The panel shall be networkable over copper wire for 900m with a network speed of minimum 312 kbps. The Intelligent panel shall be able to give pin point location of all fire/fault conditions. The panel shall be complete with Integrated 8 channel Digital Voice Evacuation System Controller capable of broadcasting Evacuation Messages on same peer-to-peer Network capable of supervising all the speaker circuits with adequate zone control and accessories. The Voice evacuation amplifier shall be of 70W and shall have automatic battery charger available with it. The fire alarm panel and all accessories shall be UL Listed and FM approved. The Fire alarm control panel shall be provided with 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during an emergency conditions as required. Approval standards UL/ VdS / FM MAKE: NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 1 Each
37 37 Supply installation testing and commissioning of Active Repeater Panel with inbuilt annuciation repeaters with 640Charator LCD Display 320 Alpha numeric Characters on LCD display/ or Touch Screen LCD. Networkable with all functionality of Main Panel having Reset / Alarm Silence and Acknowledgement Buttons . On the Active Repeater over Serial Interface or Network there shall be Annuciation Panels as well for all Control stations. Individual Active Repeater shall be able to take care of upto minimum 16 nos Annunciation LCD Indicator Panels . Approval Standards : UL/ VdS / EN54/ FM MAKE : NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 1 Each
38 38 Supply installation testing and commissioning of Addressable Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 2.5% obs/ft.The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall adapt to its environment by utilizing a built-in microprocessor to determine its environment and choose the appropriate sensing settings for early detection and reduction in false alarm. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. The detector and base shall be UL lsited and FM approved. MAKE : NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 92 Each
39 39 Supply installation testing and commissioning of Addressable Photoelectric Smoke Detector. The detector shall have multi co-operative sensing technology, the detectors in cooperative mode shall communicate with each other to ascertain the level of smoke received to reduce false alarm and providing faster detection by going into alarm without waiting for detectors to go into 100% alarm threshold levels. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. The detector and base shall be UL lsited and FM approved. MAKE : NOTIFIER - MODEL - FSP/951 + B501 or EQUIVALENT 7 Each
40 40 Supply installation testing and commissioning of Addressable Rate of Rise Heat Detector rated at 9.4 deg C/min. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. The detector and base shall be UL lsited and FM approved. MAKE : NOTIFIER - MODEL - FST/951R + B501 or EQUIVALENT 8 Each
41 41 Supply installation testing and commissioning of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. The module shall be UL lsited and FM approved. MAKE : NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 6 Each
42 42 Supply installation testing and commissioning of Addressable Sounder cum Strobe rated at 75 dBA @ 3m for Audible annunciation and 75cd flashintg at 1 Hz for visual indication. The sounder shall be UL lsited. MAKE : NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 8 Each
43 43 Supply installation testing and commissioning of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes. The control module shall provide DPDTcontact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The module shall be UL lsited and FM approved. MAKE : NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 8 Each
44 44 Supply installation testing and commissioning of Addressable Relay Module for AHU / Dampers etc. The Relay module shall provide DPDTcontact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The module shall be UL lsited and FM approved. MAKE : NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 8 Each
45 45 Supply installation testing and commissioning of Addressable Input Module for interconnecting Flow switches in hydrant line and various input from pump room etc to the Main fire alarm panel. The Monitor module shall provide DPDTcontact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The module shall be UL lsited and FM approved. MAKE : NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 20 Each
46 46 Supply installation testing and commissioning of Addressable Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. The Isolator module shall not occupy any address on loop. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The module shall be UL lsited and FM approved. MAKE : NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 7 Each
47 47 Supply installation testing and commissioning of Response Indicator for addressable detectors which are placed in above celling area. MAKE : AGNI / RAVEL/HONEY WELL/SIEMENS 31 Each
48 48 Supply installation testing and commissioning of 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling Mount Speakers. The speakers shall be of same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms. The speaker shall be UL lsited. MAKE: NOTIFIER/HONEYWELL/EDWARDS/SIEMENS 18 Each
49 49 Supplying, laying Installation, testing and commissioning of 2 Core x 1.5 Sqmm FRLS armoured copper multi strand Red colour cable. MAKE : POLYCAB/ VARSHA/ FINOLEX/HAVELLS 4000 Running Metre
50 50 Supply installation testing and commissioning of Wall / Ceiling mounted LED emergency Exit Signage luminaire Lit up using regular mains supply / UPS, wiring shall be same as item no.14. MAKE : Make: CROMPTON GREAVES/WIPRO/ HAVELLS / PHILIPS 12 Each
51 51 Fire fighting system:-Supplying, Installation, testing and commissioning of Main electric motor driven fire pump sets suitable for automatic operation and consisting of the following complete in all respect as required. Horizontal type, End suction pump of cast iron body and bronze impellor with stain less steel shaft, mechanical seal to ensure a minimum pressure of 3.5kg /sqcm at highest and farthest outlet at specified flow of 2280lpm at 70 M head, conforming to IS standards, coupled to 60 HP Squirrel cage induction motor, TEFC, sychoronous speed of 2900rpm, suitable for operation on 415V, 3phase 50Hz, AC with IP 55 protection for enclosure, horizontal foot mounted type with claas F insulation conforming to IS standards. M.S. fabricated common base plate, coupling, coupling guard , foundation bolts etc. as required. Suitable cement concrete foundation duly plastered with anti vibration pads. Make: KIRLOSKAR/MATHER & PLATT/CROMPTON / GREAVES 1 Each
52 52 Supplying, Installation, testing and commissioning of Standby Diesel Engine driven fire pump sets suitable for automatic operation and consisting of the following complete in all respect as required. Horizontal type, End suction pump of cast iron body and bronze impellor with stain less steel shaft, mechanical seal to ensure a minimum pressure of 3.5kg /sqcm at highest and farthest outlet at specified flow of 2280lpm at 70 M head, conforming to IS standards, coupled to 60 HP water cooled with radiator Diesel engine of suitable RPM conforming to relevant BS and IS standard complete with auto starting mechanism, 12V /24V electric starting equipment, diesel tank ,exhaust pipe extended upto 1meter outside pump house duly insulated with 50mm thick glass wool with 1.0mm thick aluminium sheet cladding, residential silencer, instruments and protection as per specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red color etc. as required. M.S. fabricated common base plate, coupling, coupling guard , foundation bolts etc. as required. Suitable cement concrete foundation duly plastered with anti vibration pads. Make: KIRLOSKAR/MATHER & PLATT/CROMPTON GREAVES 1 Each
53 53 Supplying, Installation, testing and commissioning of electric motor driven Jockey pump sets suitable for automatic operation and consisting of the following complete in all respect as required. Horizontal type, End suction pump of cast iron body and bronze impellor with stain less steel shaft, mechanical seal to ensure a minimum pressure of 3.5kg /sqcm at highest and farthest outlet at specified flow of 180lpm at 70 M head, conforming to IS standards, coupled to 12.5HP Squirrel cage induction motor, TEFC, sychoronous speed of 2900rpm, suitable for operation on 415V, 3phase 50Hz, AC with IP 55 protection for enclosure, horizontal foot mounted type with claas F insulation conforming to IS standards. M.S. fabricated common base plate, coupling, coupling guard , foundation bolts etc. as required. Suitable cement concrete foundation duly plastered with anti vibration pads. Make: KIRLOSKAR/MATHER & PLATT/CROMPTON GREAVES 2 Each
54 54 Electrical Control Panel of cubical construction, fabricated out of 2mm. thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter connection, having switchgears and accessories mounting and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for operation on 415 V, 3 phase, 50 Hz. AC supply with enclosure protection class IP 42 required. Make : Panel Fabricated & its Components make : INCOMER (a) 250A MCCB ( L&T/SIEMENS/C&S/LEGRANT) - 1 No.\n(b) Voltmeter (0-500 Volts) with selector switch.\n(c) Ameter (0-100 Amps) with selector switch & CT's etc.\n(d) Set of 3 Phase indicating lamp. \n(e) Aluminium bus bar 400A rated for three phases and neutral. OUT GOING :- (a) 200A MCCB with suitable for 1 Nos of 40 HP fully automatic Star - Delta starter with Variable Fequency control, Sensor-less Vector Control, with Slip Compensation, Starting Torque at 200% at 0.5Hz for Sensor-less Control, Component Life Monitor, Peer to Peer Communication to share I/Os, Built-in PLC Logic, Built-in Brake Control, Multi Keypad, Stores last 5 faults, Conformal Coating complying to IEC 60721-3-3 class 3C2 n Built-in RS485 Modbus RTU Communication complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/ OFF operation. \n 1 Each
55 55 (b) 100 A MCCB TPN fuses with suitable for 10 HP fully automatic Star - Delta starter with over load protection, current sensing type single phase preventor complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, auto / manual / OFF operation.\nControl for Diesel Engine comprising :- \n(a) 16 Amps. - 02 Nos DP MCB with Auto / Manual selector switch & 3 attempt starting device, timers and relays as required, push buttons, start / stop in manual mode ( For Jockey Pump)\n(b) Indication lamp for High/Low Lub. Oil pressure, High Water Temp. and Engine ON indication. \n(c) SMPS Battery charger suitable for 12 V/ 24 V DC with boost and tickle selector switch, 0-30V DC digital volt meter, 0-20A DC digital Ammeter (d) All standard relays and accessories for automatic operation of\ndiesel engine.Designing, Supply, Installation, Testing and commissioning of System controller to control operation of Main Electric Fire Pump, Diesel Pump, Pressurisation Pump, Terrace Pump in sequence as per specification consisting of relays, timers, sensors, annunciation window for fault indication, complete as per specification.
56 56 Supplying, Installation, testing and commissioning of Interphase communication panel of cubical construction, fabricated out of 2mm. thick CRCA sheet with hinged lockable doors, dust and vermin proof, powder coated suitable to provide input signals for the audio and visual indication of Pump on / off status, Pump trip, Water level, AC fails with provision to add other 5 inputs and communicate these signals to Main Fire alarm panel. with enclosure protection class IP 42 required. Make:- (L&T/SIEMENS/C&S/LEGRANT) 1 Each
57 57 Supplying, Installation, testing and commissioning of Air Cushioning Tank (Air vessel) 250mm dia x 1000mm high with dished top, made of minimum 6mm thick MS pipe /plate complete with 20mm dia. Brass air valve (ball type), 20mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accessories complete Make : Fabricated 1 Each
58 58 Supplying, Installation, testing and commissioning of Priming Tank of 1000ltr capacity of PVC tank confoming to IS stanards provided with suitable MS angle support of 80mm size and necessary drain arrangment and Water level indicator with out put contact complete as required . Make : SINTEX/AQUATECH/INFRA/SUPREME 1 Each
59 59 Providing, laying, testing and commissioning of 'C' class heavy duty GI pipe conforming to IS:1239 I/c fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc fixing the pipe on the wall/ ceiling with suitable clamps and painting with two or more coats of synthetic enamel paint of required shade complete as required. (for pump room & internal piping) Make : JINDAL/TATA/ZENITH/SURYA/PRAKASH
60 60 (a) 100 mm dia 240 Running metre
61 61 (b) 80 mm dia 10 Running metre
62 62 (c) 40 mm dia 48 Running metre
63 63 (d) 25 mm dia 24 Running metre
64 64 Supplying, fixing, testing and commissioning of Cast Iron Butterfly valve class PN 1.6 with rubber insertion nuts, SG iron or DI Disc hand lever operated type with flanges, bolts, nuts, washers, etc, conforming to IS 13095,of follwing sizes:- Make : INTERVALVE/ZOLOTO/AUDCO/L&T/NORMEX
65 65 (a) 100 mm dia 4 Each
66 66 (b) 80 mm dia 1 Each
67 67 (c) 50 mm dia 1 Each
68 68 Supplying, fixing, testing and commissioning of horizontal type Cast Iron Dual plate Non-return valve of approved quality conforming to API-594 standards with nuts, Bolts, Washers etc complete as required. Make: LEADER/L&T/INTERVALVE/VENUS/KIRLOSKAR
69 69 (a) 100 mm dia 2 Each
70 70 (b) 80 mm dia 1 Each
71 71 (c) 50 mm dia 1 Each
72 72 Supplying, fixing, testing and commissioning of Gunmetal Ball valve PN 1.6 with rubber insertion nuts, Steel Ball with hand lever operated screwed end conforming to IS 554 of follwing sizes:- Make : LEADER/GEM/SEIKO/SANT
73 73 (a) 40 mm dia 6 Each
74 74 (b) 25 mm dia 4 Each
75 75 Supplying, fixing, testing and commissioning of horizontal type screwed end Gunmetal NRV of approved quality conforming to IS318 standards complete as required. Make: LEADER/L&T/INTERVALVE/VENUS/KIRLOSKAR/ZOLOTO
76 76 (a) 40 mm dia 4 Each
77 77 (b) 25 mm dia 2 Each
78 78 Supplying, fixing, testing and commissioning Fire Hydrant Landing Valve type A (Single Head Outlet) type with gun metal female coupling valve conformiong to IS:5290-1993 having 80mm dia inlet with PVC Cap and locking mechanism. Make : NEWAGE / ESSEL / SRI/EVER SAFE/MAHAVEER 9 Each
79 79 Supplying and fixing of weather proof Double door Hose cabinet fabricated from 2mm thick MS sheet with 6mm thick glazed front glass doors and looking arrangements suitable for accommodate internal hydrant with 2 Nos 15 Mtrs long hose pipe, 2 No. branch pipe, fittings etc.The cabinet shall be painted with one coat of primer and 2 coatts ofsynthetic enamel paint of post office red externally and white internally and shall be suitably mounted on concrete bases. Make : FABRICATED/FRIENDS/EVER SAFE/FIRE COOL \n 9 Each
80 80 Supply & erection of Fire Station having size 1800 x 250 x 600 made of 16Swg MS Sheet with front Glass door and lock fixed on angle frame suitable for accommodating 1 No. Hydrant Valve, Hose Reel, Fire Hose, Branch Pipe and Extinguishers provided at Duct. Make : FABRICATED/ FRIENDS/ EVER SAFE/FIRE COOL 6 Each
81 81 Supplying, fixing, testing and commissioning First Aid Hose Reel wall mounting swinging type complete with drum, bracket, gate valve/ stop cock and 19mm dia 30mtr long high pressure hose reel tubing of Thermoplast Type II hose conforming to IS12585 with ISI mark with gunmetal shutt off nozzle with 5mm orifice. : Make : NEWAGE / AAG / ARIHANT / EVER SAFE/MAHAVEER 6 Each
82 82 Supplying, fixing, testing and commissioningof 15 mtr long rubber lined woven jacketed hose pipe, type-A ( Reinforced rubber lined) of IS;636-1988 complete with necessary instantaneous spring lock type gumetal coupling conforming to IS903 at the ends to match with landing valve/ hose pipe/ branch pipe etc. Make : NEWAGE / AAG / ARIHANT / EVER SAFE/MAHAVEER 18 Each
83 83 Supply, installation, testing and commissioning gun metal 63mm dia short Branch Pipe with 20 mm dia nozzle of gunmetal having screw threaded and hexagonal head conforming to IS903 with ISI mark Make : NEWAGE / AAG / ARIHANT / EVER SAFE/MAHAVEER 9 Each
84 84 Supplying, fixing, testing and commissioning of 0-15 Kg/sq cm100mm dia Dial type Pressure Gauge bourbon type with 3/8" inlet connection with isolation cock and pipe at hydrant station as per specification. Make : H GURU / FEBIB /MIEPL/ MARSH 3 Each
85 85 Supplying, fixing, testing and commissioning of Industrial type Pressure Switch having 1/4" BSP(F) connection IP:32 enclosure protection, phosphor bronze bellows as sensing element, SDPT contact system, switch rating 6A Inductive/lOA resistive 380 V AC, 0.2A Inductive/10A resistive 250V DC suit with ball valve etc. complete as required. Make : DANFOSS/INDFOSS/SWITZER/HONEYWELL 4 Each
86 86 Supplying, fixing, testing and commissioning of Gun metal Air Release valve 20mm dia Make : NEWAGE / ESSEL / ARIHANT / LEADER / BIR / KIRLOSKAR 2 Each
87 87 Supplying, fixing, testing and commissioning of Gun metal Fire Brigade Inlet 4 way connection for connecting to external fire hydrant ring main consisting of two nos 63mm dia instantaneous type male coupling with built in check valves and 150mm dia, flanged outlet complete with all accessories. Make : NEWAGE / ESSEL / ARIHANT / AAG 1 Each
88 88 Material & Labour for Construction of Valve Chamber with 230 mm Brick masonry wall with best quality TM bricks & CM 1:4,on a PAC 1:4;8 bed of 100 mm thcik.The wall shall be plastered internally smooth in CM 1:3, water proofing as required and externally rough plastered with sponge finish, including curing. The chamber shall be provided with M.S. 6 / 8 mm thick plate fabricated top cover in leaves with necessary hinges and locking arrangement. The size of the chamber shall be 1200mm x 1200mm x1500mm in depth. 2 Each
89 89 GAS SUPPRESSION SYSTEM:- Supply, installation, testing & commissioning of 140 Ltr Seamless PESO approved 300 bar Cylinder conforming to IS7285 with BIS Certification and having mechanical Tested properties like Tensile strength, Yield stress, Elongation etc with record of hydrostatic stretch & Air leakage test certificate for the cylinders &Inert gas Peso certified valve conforming standard of IS3224 & EN120944 compliance filled with IG541 having suitable for automatic fire suppression system for Rooms as specified in the tender. Cylinder are subjected to hydrostatic stretch test at pressure of 500.kg/cm2 and working pressure of 300 kg/cm2 under the Gas cylinder regulation 2016. Design as per NFPA 2001 & UL 2127 guidelines (41% concentration. Contractor shall provide all the test certificate of the cylinder, Approval taken for exact volume of gas required with number of nozzles etc after condudcting Room integrity test and Vds analysis before commencement of work). Make:- ROTAREX / TYCO/SIEMENS 12 Each
90 90 Supply, installation, testing & commissioning of Stand-By Cylinder of 140 Ltr Seamless PESO approved 300 bar Cylinder conforming to IS7285 with BIS Certification and having mechanical Tested properties like Tensile strength, Yield stress, Elongation etc with record of hydrostatic stretch & Air leakage test certificate for the cylinders &Inert gas Peso certified valve conforming standard of IS3224 & EN120944 compliance filled with IG541 having suitable for automatic fire suppression system for Rooms as specified in the tender. Cylinder are subjected to hydrostatic stretch test at pressure of 500.kg/cm2 and working pressure of 300 kg/cm2 under the Gas cylinder regulation 2016. Design as per NFPA 2001 & UL 2127 guidelines ((41% concentration. Contractor shall provide all the test certificate of the cylinder, Approval taken for exact volume of gas required with number of nozzles etc after condudcting Room integrity test and Vds analysis before commencement of work). Make :- ROTAREX / TYCO/SIEMENS 12 Each
91 91 Supply installation, testing & commissioning of Pneumatic Directional Valve and acutaor assembly to isolate seperate protection zones from the same cylinder rack with suitable size as per VDS calculations for IG 541 suitable to work with pheneumatic actuator made out of Carbon Steel with nominal pressure of 140bar and actuation pressure of 8bar operational in temperature of -20 to 50deg celsius, provided with stainless steel ball vavles with steel housing conforming to VSD/UL/FM approval (four rooms as specified in the tender) Make : ROTAREX / TYCO/SIEMENS 4 Each
92 92 Supply, installation, testing & commissioning of constant Discharge Pressure Regulator to create constant flow druing discharge to prevent line freezing having dynamic pressure of 60 bar to 40bar from 300 bar - with VDS/LPCB approval. Flooding of line for inert gas agent is 120 Sec (duration of discharge)Make : ROTAREX / TYCO/SIEMENS 24 Each
93 93 Supply, installation, testing & commissioning of Manual / Pneumatic Release Devise to actuate the release of extinguishing agent for Cylinder banks as per the design/ rooms volume, made of brass material with 50mm dia (for manual lever cum pneumatic operation) VDS/LPCB approval Make : ROTAREX / TYCO/SIEMENS 8 Each
94 94 Supply, installation, testing & commissioning of Pneumatic Release Devise to actuate the release of extinguishing agent for Cylinder banks as per the design/ rooms volume, made of brass material with 50mm dia (for manual lever cum pneumatic operation) VDS/LPCB approval Make: ROTAREX / TYCO/SIEMENS 16 Each
95 95 Supply, installation, testing & commissioning of Electro Magnetic Device (Actuator) for electrically actuating the release of extinguishing agent by automatic opertaion from Gas Release Panel for the Main cylinder. It should be suitable mounted on valve head with 24V DC 0.5A diode protection with protection class of IP65 conforming to VDS/LPCB approval Make: ROTAREX / TYCO/SIEMENS 8 Each
96 96 Supply, installation, testing & commissioning of Pressure Gague for each cylinder suitable for measuring and display the cylinder pressure with IG 541 having M10 x 1 Size radial scale 0 to 400 bar with output signal of cyliner pressure for communicating with Gas leak panel. Conforming CE-Vds approval. (for cylinder pressure status updated in the Gas leak and Fire Alarm panel) Make : ROTAREX / TYCO/SIEMENS 24 Each
97 97 Supply installation, testing & commissioning of 24 zone Gas leak indication panel with LED display for monitoring Cylinder gas pressure and give common alarm to Main fire alarm panel. Make : RAVEL / AGNI / ASWIN / NOTIFIER 1 Each
98 98 Supply of Authorised manufacturers Reset Tool for electro magnetic actuator when putting system back in the active service after system discharge having size of M42 made of Brass material. Make :ROTAREX / TYCO/SIEMENS 2 Each
99 99 Supply installation, testing & commissioning of High Pressure Dicharge Hose W/21.8 x 1/14" din, 400 - 450mm long with working pressure of 350 bar and burst pressure of 1400bar with operation tempreture range of -40 to 100deg celsius made of synthetic rubber oil resistant material conforming to VDS/UL approval Make : ROTAREX / TYCO/SIEMENS 24 Each
100 100 Supply installation, testing & commissioning of Pilot Hose 700mm length for interconnecting valves for automatic operation, with 400 bar working pressure and 1600bar brust pressure with temperature range of -40 to 100deg.celsius, made of synthetic rubber oil resitant material having inner diameter of 1/8" with VDS/UL approval having size M12/11.5 with suitable adaptor and oring Make : ROTAREX / TYCO/SIEMENS 23 Each
101 101 Supply installation, testing & commissioning of Bleed Valve for to vent over pressure and prevent false system discharge during small pressure leak from cylinders into pheneumatic actuators. Conforming to VDS/UL approval Make : ROTAREX / TYCO/SIEMENS 4 Each
102 102 Supply installation, testing & commissioning of Check Valve to prevent back flow into the cylinder provided with each hose attached to the manifoed having IG 541 working pressure of 360 bar and test pressure of 150bar made of Brass material with hose connection of 3/4" conforming to VDS/UL approval Make : ROTAREX / TYCO/SIEMENS 24 Each
103 103 Supply installation, testing & commissioning of 4 zone Control panel for Directional Valves UL/FM approved suitable for IG 541 operation 24V DC with necessary attachments for integrating with phenumatically operated of directional valves Make : ROTAREX / TYCO/SIEMENS 1 Each
104 104 Supply, installation, testing & commissioning of Pressure Relief Device to work as a safety device to prevent over pressure during discharge connected to manifold relief pressure set for 66 bar having 1/2" inlet connection. Make : ROTAREX / TYCO/SIEMENS 2 Each
105 105 Supply, installation, testing & commissioning of Pressure and Flow Detector to sent the signal to the Gas release panel when the sytem is discharing. Having actuation pressure of 2 bar having connection of 1/2" with power supply of 24VDC / 10A and IP65 protection conforming CE standards. Make : ROTAREX / TYCO/SIEMENS 2 Each
106 106 Supply, installation, testing & commissioning of Nozzle for inert gas discharge, made of Brass material with working pressure of 300bar with special orifice diameters suitable for IG 541 Gas according to the VDS engineering. Nozzle size is depnd upon the VDS calucation and pipe sizing Make : ROTAREX / TYCO/SIEMENS 18 Each
107 107 Supply, installation, testing & commissioning of Pressure Gague for measuring Manifold pressure having radial scale 0 to 400 bar with output signal Conforming CE-Vds approval. Make : ROTAREX / TYCO/SIEMENS 2 Each
108 108 Supply, installation of Cylinder Manifold for connectiong more than two cylinders in single/ multiple row configurtion, made out of MS Angles/ channels suitable for 24 Cylinders with max working pressure of 100bar and test pressure of 150bar conformong to CE standards Make : ROTAREX / TYCO/SIEMENS 1 Each
109 109 Conducting comprehensive test calculation procedures predicts how long the agent will stay in the room while discharge.Room integrity test for rooms as per the drawing and test shall be as per NFPA 2001 NFPA12A and IS14520 4 Job
110 110 Supply, installation of Eight channel weather proof control panel with LED Display with hooter with flash, CE Approved. alrm Model no. TC800WP or equivalent. wiring shall be same as item no.32. Make : AMBETRONIC / AGNI/SIEMENS 1 Job
111 111 Supply, installation of Oxygent / Toxic level detector, weather proof with LED Display with 3 relay outout 4-20mA output etc. Miedel GT2500 or Equivalent. Make : AMBETRONIC / AGNI/SIEMENS 5 Job
112 112 Submission of Design/development of drawing with NFPA 2001/VDS engineering support through OEM - entire piping design for IG 541 Suppression System along with Gas volume and number of cylinders etc to be submitted to Engineer in charge before commencement of work. 1 Job
113 113 Supply, installation, testing & commissioning of Sch 40 Pipe suitable dia mention class of pipes for IG 541 Suppression System as per VDS design. Make : JINDAL/TATA/ZENITH/ SURYA/PRAKASH 1 Job
114 114 Supply installation, testing & commissioning of 2 / 4 zone Gas Release panel micorprocessor based with zone alarm indication, input signal for manual, abort and gas release, LED indicaiton for Open/Short, with NO/NC contact, Fire and fault relay opearated and Gas Release module with necessary accessories and battery Make : RAVEL/AGNI/ASWIN/ NOTIFIER/SIEMENS 4 Each
115 115 Supply, installation, testing & commissioning of conventional type Multi criterea Detectors with LED having combination of optical and thermal sensors for quick and accurate fire detection operational on 24VDC with 2/4 wire connection having 0-95% RH non- condensing operating humidiy range provided with standard mounting base conforming to EN/ UL / LPCB standards Make : NOTIFIER / HONEYWELL / EDWARDS / SIEMENS 12 Each
116 116 Supply, installation, testing & commissioning of conventional type Heat Detectors rate of rise or fixed temperature type with LED indication having thermal sensors for quick and accurate fire detection operational on 24VDC 24VDC with 2/4 wire connection having 0-95% RH non- condensing operating humidiy range provided with standard mounting base conforming to EN/ UL / LPCB standards Make :NOTIFIER / HONEYWELL / EDWARDS / SIEMENS 8 Each
117 117 Supply, installation, testing & commissioning of Abort switch break glass type for deactivating gas release, made of plastic body having LED indication operates on 24VDC and IP55 rating Make : RAVEL / AGNI/ASWIN/ NOTIFIER 5 Each
118 118 Supply, installation, testing & commissioning of Manual Release Switch break glass type for activating Gas release, having LED alarm indication, operates on 24V DC, and IP55 rating Make : RAVEL/AGNI/ASWIN/ NOTIFIER 5 Each
119 119 Supply, installation, testing & commissioning of multi candela 110cd multi tone 75Db Hooter Cum strobe for Audio visual indication made of ABS plastic wall mouting type operation on 24VDC with standard operating temperaterure between 0-49deg celsius, conforming to UL standards. Make : Apollo / Ravel / Agni or Equivalent 4 Each
120 120 Supply & laying 2C x 1.5 sqmm FRLS Copper armoured multistrand cable of red colour conforming to IS7098 or BS standards laid though wall with suitable size saddles and providing junction box as per the requirment. Make : Polycab / Havells/Finolex / Varsha 500 Running metre
121 121 Supply, installation, testing & commissioning of 10mm chrome plated Single compression Brass gland with nut and lock arrangement suitable to use with armoured cable and juction box. Make : ISI Marked 100 Each
122 122 Supply & installation of necessary Signages photolumincent type made of 3mm thick Aluminium acp sheet for various size for Gas suppression system Make : Autolite / Prolite / Aswin 1 Job
123 123 Annual Maintenance Contract for Fire Hydrants, Fire Alarm & Gas Suppression System installed at JOC Building for the first year after the defect liability period. Minimum one visit in every three months period shall be carried out and the scope include following works : 4 Job
124 124 (a) AMC FOR FIRE ALARM SYSTEM :- (i) Testing of entire Fire Alarm system during site visit such as General servicing of Manual Call Points including cleaning, checking etc. once in three months. (ii) General Servicing of Hooter including cleaning. (iii) General Servicing of Fire Alarm Panel including cleaning & checking. \n \n
125 125 (b) AMC FOR FIRE HYDRANT SYSTEM:-(i) Testing of Entire Fire fighting System , once in three month. (ii) General checking and servicing of Pumps and engine set etc which includescleaning, painting, greasing, battery checking etc. (iii) General servicing of hydrants valves, butterfly valves, NRV's, Pressure gauges, Pressure switches etc including cleaning , polishing, replacement of washers (if required) etc. (iv) General servicing of Hose box including cleaning, painting replacement of beading (if required) etc. (v) Servicing of Fire Hose Set, including cleaning, drying and etc. (vi) Servicing of Hose reel including cleaning, cheaking of hose , shutt off nozzle
126 126 (c) AMC FOR GAS SUPPRESSION SYSTEM:- (i) Includes checking of Gas Suppression System during site visit, once in every three months. (ii) General checking and simulation of suppresion system using spare cylinders. (iii) Checking of discharge lines, working of electromagnetic devices / solenoid valves, directional valves, nozzels, gauges etc, and cleaning of components etc. (iv) General servicing of Manual release switches, abort switches tec include cleaning, checking etc. (v) General servicing of Gas release Panel and device including cleaning, checking.Note:- (a) Every break down complaints/ calls shall be attended within 48 hrs. (b) Major spare parts and components of quipments, inert gas. overhauling of pumps & engine, coil changing, rewinding of motors, battery etc will be provided additionally.
127 127 All as per item No 123 to 126 here-in-above , but for Second year after defect liability period 4 Job
128 128 All as per item No 123 to 126 here-in-above , but for third year after defect liability period 4 Job
129 129 Supply only Loop card for Fire Alarm Panel 3 Each
130 130 Supply only Network card for the panel 3 Each
131 131 Supply only Battery for the LED light 3 Each
132 132 Supply only Mechanical Seal for Wet riser system 3 Each
133 133 Supply only Impeller Bronze 3 Each
134 134 Supply only spider Coupling 3 Each
135 135 Supply only Battery 12V 150Ah 3 Each
136 136 Supply only Engine oil 3 Litre
137 137 Supply only Coolant 3 Bottle
138 138 Supply only oil filter 3 Each
139 139 Supply only Fule filter 3 Each
140 140 Supply only Air filter 3 Each
141 141 Supply only LED Indicator 3 Each
142 142 Supply only cylinder valve for Gas Suppression Valve 3 Each
143 143 Supply only Inert Gas IG- 541 Note:- The quantity for item 129 to 143 is 1 per year. 3 Kilograme