Construction Of New Hospital Block At District Hospital , Mavelikkara ( Sh- Civil Works , Mep Works And Associated Utilities ) , District Hospital, Mavelikkara-Kerala

INKEL Limited has published Construction Of New Hospital Block At District Hospital , Mavelikkara ( Sh- Civil Works , Mep Works And Associated Utilities ) . Submission Date for this Tender is 17-06-2020. Building Work Tenders in District Hospital, Mavelikkara Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

23994563
Corrigendum : Construction Of New Hospital Block At District Hospital , Mavelikkara ( Sh- Civil Works , Mep Works And Associated Utilities )
Open Tender
Indian
Kerala
District Hospital, Mavelikkara
17-06-2020

Tender Details

Construction Of New Hospital Block At District Hospital , Mavelikkara ( Sh- Civil Works , Mep Works And Associated Utilities )

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 31-Mar-2020 Corrigendum8 Date 20-04-2020
2 17-Apr-2020 Corrigendum 9 Date 11-05-2020
3 05-May-2020 CORRIGENDUM No. 10 Date 23-05-2020
4 19-May-2020 CORRIGENDUM No. 11 Date 06-06-2020
5 03-Jun-2020 Corrigendum No. 13 Other 10-06-2020
6 10-Jun-2020 Corrigendum No.14 Date 17-06-2020

Key Value

Document Fees
INR 17850 /-
EMD
INR 9976190.0 /-
Tender Value
INR 89.76 Crore /-

BOQ Items

Work Name : Construction of New Hospital Block at District Hospital, Mavelikkara (SH: Civil Works, MEP Works and Associated Utilities)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Sub Head -Pile Foundation BI01010001010000000000000515BI0100001113
2 1.01 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-35 (Cement quantity -400kg/m3) of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap).Note:Truck mounted/Rotary/TMR/Tubewell boring machine shall not be used. (Min cement content is 400kg/cum and no payment shall be made for extra cement.) 600 mm dia piles BI01010001010000000000000515BI0100001114 714 metre
3 1.02 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-35 (Cement quantity -400kg/m3) of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap).Note:Truck mounted/Rotary/TMR/Tubewell boring machine shall not be used.(Min cement content is 400kg/cum and no payment shall be made for extra cement.) 750 mm dia piles BI01010001010000000000000515BI0100001115 18018 metre
4 1.03 Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile above 50 tonne and upto 100 tonne capacityInitial test BI01010001010000000000000515BI0100001116 1 per test
5 1.04 Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile above 50 tonne and upto 100 tonne capacityRoutine test BI01010001010000000000000515BI0100001117 1 per test
6 1.05 Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge.Note: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing.Note: 2. Testing agency shall submit the design of loading platform for the approval of Engineer-in-charge.Initial test up to 150 tonne capacity BI01010001010000000000000515BI0100001118 1 each
7 1.06 Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge.Note: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing.Note: 2. Testing agency shall submitt the design of loading platform for the approval of Engineer-in-charge.routine test up to 150 tonnes BI01010001010000000000000515BI0100001119 9 each
8 2 Sub Head- Earth Work BI01010001010000000000000515BI0100001120
9 2.01 Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil BI01010001010000000000000515BI0100001121 6130 cum
10 2.02 Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil BI01010001010000000000000515BI0100001122 2035 cum
11 2.03 Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil BI01010001010000000000000515BI0100001123 140 cum
12 2.04 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. BI01010001010000000000000515BI0100001124 5235 cum
13 2.05 Extra for every additional lead of 50 m or part there of for disposal of excavated earth and stacking BI01010001010000000000000515BI0100001125 1400 cum
14 2.06 Extra for every additional lead beyond 50m upto 1Km (within the hospital compound) for disposal of excavated earth & stacking. BI01010001010000000000000515BI0100001126 1200 cum
15 2.07 Filling with contractor's own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge BI01010001010000000000000515BI0100001127 75 cum
16 2.08 Supplying and packing 20mm stone aggregate between the retaining wall and earth fill along the building perimeter including watering, ramming, consolidating and dressing complete including lead, lift, stacking, transportation etc. as directed by the Engineer in charge - for retaining wall BI01010001010000000000000515BI0100001128 130 cum
17 2.09 Providing & applying two compound coal tar epoxy protection (brush application) after cleaning the surface -minimum 200 micron DFT-For retaining walls. BI01010001010000000000000515BI0100001129 850 sqm
18 2.1 Close timbering in trenches including strutting, shoring and packing cavities (wherever required) complete (Measurements to be taken of the face area timbered).Depth exceeding 3 m but not exceeding 4.5 m BI01010001010000000000000515BI0100001130 205 sqm
19 2.11 Close timbering in case of shafts, wells, cesspits, manholes and the like including strutting, shoring and packing cavities (wherever required) etc. complete (Measurements to be taken of the face area timbered).Depth exceeding 3 m but not exceeding 4.5 m BI01010001010000000000000515BI0100001131 307 sqm
20 2.12 Bailing out water using pump above 5 HP and Up to 10 HP-Bailing out water with engine and pump set above 5HP and up to 10HP, including conveyance to site and erection,cost of fuel, lubrication oil and other stores, pay of staff etc complete BI01010001010000000000000515BI0100001132 240 hour
21 3 Sub Head -plain cement concrete works BI01010001010000000000000515BI0100001133
22 3.01 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size) BI01010001010000000000000515BI0100001134 230 cum
23 3.02 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) BI01010001010000000000000515BI0100001135 323 cum
24 4 Sub Head - Reinforced cement concrete BI01010001010000000000000515BI0100001136
25 4.01 Providing and laying in position machine batched and machine mixed design mix M-35 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. (Note:- Min cement content is 350kg/cum and no payment shall be made for extra cement).All work upto plinth level. BI01010001010000000000000515BI0100001137 3119 cum
26 4.02 Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. (Note:- Min cement content is 340kg/cum and no payment shall be made for extra cement).All work above plinth level upto floor V level BI01010001010000000000000515BI0100001138 7428 cum
27 4.03 Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) : 3 graded stone aggregate 20 mm nominal size). BI01010001010000000000000515BI0100001139 184 cum
28 4.04 Extra for R.C.C. /B.M.C/R.M.C. work above floor V level for each four floors or part thereof. BI01010001010000000000000515BI0100001140 2984 cum
29 4.05 Providing and fixing at or near ground level precast cement concrete in kerbs, edgings etc. as per approved pattern and setting in position with cement mortar 1:3 (1 cement : 3 coarse sand), including the cost of required centering, shuttering complete.1:1.5:3 ( 1 cement : 1.5 coarse sand (Zone III): 3 graded stone aggregate 20 mm nominal size) BI01010001010000000000000515BI0100001141 11 cum
30 4.06 Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete BI01010001010000000000000515BI0100001142 3255 sqm
31 4.07 Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. BI01010001010000000000000515BI0100001143 5840 sqm
32 4.08 Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform BI01010001010000000000000515BI0100001144 24135 sqm
33 4.09 Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers BI01010001010000000000000515BI0100001145 17620 sqm
34 4.1 Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts BI01010001010000000000000515BI0100001146 8710 sqm
35 4.11 Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases) BI01010001010000000000000515BI0100001147 776 sqm
36 4.12 Centering and shuttering including strutting, etc. and removal of form for:Vertical and horizontal fins individually for forming box louvers band, facias and eaves boards BI01010001010000000000000515BI0100001148 100 sqm
37 4.13 Extra for shuttering in circular work (20% of respective centering and shuttering items) BI01010001010000000000000515BI0100001149 25 sqm
38 4.14 Centering and shuttering including strutting, etc. and removal of form for:Cornices and mouldings. BI01010001010000000000000515BI0100001150 150 sqm
39 4.15 Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges BI01010001010000000000000515BI0100001151 1596 sqm
40 4.16 Extra additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentering at all levels, over a height of 3.5m, for every additional height of 1 metre or part thereof (Plan area to be measured).Suspended floors, roofs, landing, beams and balconies (Plan area to be measured) BI01010001010000000000000515BI0100001152 18345 sqm
41 4.17 Providing and laying cement concrete in retaining walls, return walls, walls ( any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts,buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor, etc. up to floor five level, excluding the cost of centering, shuttering and finishing:1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) BI01010001010000000000000515BI0100001153 10 cum
42 4.18 Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete at all levels. Thermo - Mechanically Treated bars of grade Fe-500D or more BI01010001010000000000000515BI0100001154 1.92861e+06 kilogram
43 5 Sub Head- Block Work BI01010001010000000000000515BI0100001155
44 5.01 Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor two level upto floor five level with thickness 15cm in : CM 1:6 ( 1 cement : 6 coarse sand) etc complete BI01010001010000000000000515BI0100001156 80 cum
45 5.02 Extra for brick work/ AAC block masonry/Tile brick masonry in super structure above floor V level, for each four floors or part thereof by mechanical means. BI01010001010000000000000515BI0100001157 1690 cum
46 5.03 Brick work with common burnt clay F.P.S (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) BI01010001010000000000000515BI0100001158 75 cum
47 5.04 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in:Cement mortar 1:4 ( 1 cement : 4 coarse sand) BI01010001010000000000000515BI0100001159 85 cum
48 5.05 Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand ) etc complete BI01010001010000000000000515BI0100001160 43 cum
49 5.06 Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete BI01010001010000000000000515BI0100001161 2045 cum
50 5.07 Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor two level upto floor five level thickness 20cm and above in : CM 1:6 ( 1 cement : 6 coarse sand sand) etc complete BI01010001010000000000000515BI0100001162 2190 cum
51 6 Joinery Works BI01010001010000000000000515BI0100001163
52 6.01 Providing and supplying aluminium extruded tubular and other aluminium sectionsas per the architectural drawings and approved shop drawings , the aluminiumquality as per grade 6063 T5 or T6 as per BS 1474,including super durable powdercoating of 60-80 microns conforming to AAMA 2604 of required colour and shadeas approved by the Engineer-in-Charge. ( The item includes cost of material suchas cleats, sleeves, screws etc. necessary for fabrication of extruded aluminiumframe work. Nothing extra shall be paid on this account). BI01010001010000000000000515BI0100001164 8785 kg
53 6.02 Designing, fabricating, testing, protection, installing and fixing in position semi(grid) unitized system of structural glazing (with open joints) for linear as well ascurvilinear portions of the building for all heights and all levels, including:a) Structural analysis & design and preparation of shop drawings. (Refer Part C for more details) BI01010001010000000000000515BI0100001165 1225 sqm
54 6.03 Extra for openable side / top hung vision glass panels (IGUs) including providingand supplying at site all accessories and hardwares for the openable panels asspecified and of the approved make such as heavy duty stainless steel frictionhinges, min 4 -point cremone locking sets with stainless steel plates, handles,buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts,washers etc. all complete as per the Architectural drawings, as per the approvedshop drawings, as specified and as directed by the Engineer-in-Charge. BI01010001010000000000000515BI0100001166 7 sqm
55 6.04 Providing and supplying Spandrel Glass Panels comprising of 6 mm thick heat strengthened monolithic float glass of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade so as to match the colour and shade of the IGUs in the vision panels etc. ,all complete for the required performances as specified, as per the Architectural drawings, as per the approved shop drawings, as specified, and as directed by the Engineer- in- Charge."For payment, only the actual area of glass on face # 1 of the glass panels (but excluding the area of grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. (Payment for fixing of Spandrel Glass Panels in the curtain glazing is included in cost of relevent Item*). (i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. BI01010001010000000000000515BI0100001167 650 sqm
56 6.05 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately):For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) BI01010001010000000000000515BI0100001168 25924 kg
57 6.06 For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron) BI01010001010000000000000515BI0100001169 19011 kg
58 6.07 Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides BI01010001010000000000000515BI0100001170 616 sqm
59 6.08 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness BI01010001010000000000000515BI0100001171 751 sqm
60 6.09 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5.50 mm thickness BI01010001010000000000000515BI0100001172 363 sqm
61 6.1 Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS: 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors including cost of cutting floors, embeding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer -in- Charge.With stainless steel cover plate minimum 1.25 mm thickness BI01010001010000000000000515BI0100001173 305 each
62 6.11 Providing and fixing stainless steel (SS 304 grade) adjustable friction window stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineer - in-Charge complete.255 x 19 mm BI01010001010000000000000515BI0100001174 206 no
63 6.12 Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. BI01010001010000000000000515BI0100001175 305 no
64 6.13 Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame. BI01010001010000000000000515BI0100001176 1145 metre
65 6.14 Providing and fixing to existing door frames.30 mm thick Glas Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS : 14856, including fixing to frames. BI01010001010000000000000515BI0100001177 360 sqm
66 6.15 Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete:250x16mm BI01010001010000000000000515BI0100001178 352 no
67 6.16 Providing and fixing 100 mm brass locks ( best make of approved quality ) for aluminium doors including necessary cutting and making good etc. complete BI01010001010000000000000515BI0100001179 50 each
68 6.17 Providing and fixing aluminium casement windows fastener of required length for aluminium windows with necessary necessary screws etc. complete.Powder coated minimum thickness 50 micron aluminium BI01010001010000000000000515BI0100001180 400 no
69 6.18 Providing and fixing aluminium round shape handle of outer dia 100 mm with SS screws etc. complete as per direction of Engineer-in-Charge.Powder coated minimum thickness 50 micron aluminium BI01010001010000000000000515BI0100001181 274 no
70 6.19 Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:300x10 mm BI01010001010000000000000515BI0100001182 150 no
71 6.2 Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 150x10 mm BI01010001010000000000000515BI0100001183 250 no
72 6.21 Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and stopper etc to be paid separately) BI01010001010000000000000515BI0100001184 10 sqm
73 6.22 Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete.Upto 5 mm depth and 5 mm width BI01010001010000000000000515BI0100001185 3000 metre
74 6.23 Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Single rubber stopper BI01010001010000000000000515BI0100001186 230 no
75 6.24 Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper BI01010001010000000000000515BI0100001187 85 no
76 6.25 Providing and fixing in position frameless fixed glazing using 10mm toughened glass fitted with patch fittings of approved brand or manufacture as detailed in the draiwng of specified size including supplying and fixng necessary holdfats, screws for fixing cleats, toughened glass with all labour and materials complete as per drawings and as directed. BI01010001010000000000000515BI0100001188 125 sqm
77 7 Sub head -Steel Work BI01010001010000000000000515BI0100001189
78 7.01 Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc BI01010001010000000000000515BI0100001190 10095 kg
79 7.02 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.On steel work BI01010001010000000000000515BI0100001191 1276 sqm
80 7.03 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. BI01010001010000000000000515BI0100001192 71090 kg
81 7.04 Providing and fixing 1 mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.Using M.S. angels 40x40x6 mm for diagonal braces BI01010001010000000000000515BI0100001193 195 sqm
82 7.05 Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works BI01010001010000000000000515BI0100001194 6375 kg
83 7.06 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes BI01010001010000000000000515BI0100001195 50 kg
84 7.07 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.80x1.20 mm M.S. laths with 1.20 mm thick top cover BI01010001010000000000000515BI0100001196 15 sqm
85 7.08 Providing and fixing ball bearing for rolling shutters. BI01010001010000000000000515BI0100001197 4 no
86 7.09 Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) BI01010001010000000000000515BI0100001198 4570 kg
87 8 Sub head -Flooring and Waterproofing Work BI01010001010000000000000515BI0100001199
88 8.01 Providing and laying C.C pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator, vacuum dewatering process and finally finished by floating brooming with wire brush etc. complete as per specifications and directions of Engineer-in-charge ( The panel shuttering work shall be paid for separately) BI01010001010000000000000515BI0100001200 142 cum
89 8.02 Extra for providing and mixing hardening compound of approved quality as per manufacturers specification in cement concrete BI01010001010000000000000515BI0100001201 9140 kg
90 8.03 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.On concrete work BI01010001010000000000000515BI0100001202 1882 sqm
91 8.04 Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints of flooring tiles having joints of 3 mm width with spacer, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing with matching pigments etc., complete as per direction of Engineer-in-charge. Size of Tile 800x 800 mm.(Note - Basic Price of tile - Rs 765/sqm Any savings/reduction in basic price shall be accounted in the bill on pro rata basis ) BI01010001010000000000000515BI0100001203 1213 sqm
92 8.05 Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints of flooring tiles having joints of 3 mm width with spacer,jointing with grey cement slurry @ 3.3kg/sqm including grouting the joints with epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling /grouting and matching pigments finishing complete as per direction of Engineer-in-charge. Size of Tile 600 x 600 mm.(Note - Basic Price of tile - Rs 430/sqm Any savings/reduction in basic price shall be accounted in the bill on pro rata basis ) BI01010001010000000000000515BI0100001204 11923 sqm
93 8.06 Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joints of flooring tiles having joints of 3mm width with spacer, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling /grouting and finishing using matching pigments etc. complete as per direction of Engineer-in-charge.Size of Tile 600x600 mm. (Note - Basic Price of tile - Rs 430/sqm Any savings/reduction in basic price shall be accounted in the bill on pro rata basis ) BI01010001010000000000000515BI0100001205 2244 sqm
94 8.07 Providing and fixing Ist quality ceramic glazed wall tiles of size 600x600 conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer in- Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), keeping 3mm space between tiles with spacer and fixing glazed/ Ceramic/ Vitrified floor tiles with cement based high polymer modified quick-set tile adhesive @ 4kg per sqm conforming to IS: 15477, in average 3mm thickness and finishing complete as per direction of Engineer-in-charge.(Note - Basic Price of tile - Rs 380/sqm Any savings/reduction in basic price shall be accounted in the bill on pro rata basis) BI01010001010000000000000515BI0100001206 20206 sqm
95 8.08 Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg). including filling /grouting and finishing complete as per direction of Engineer-in-charge.Size of Tile 600x600 mm BI01010001010000000000000515BI0100001207 20206 sqm
96 8.09 Kota stone slab flooring over 20 mm ( average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1:4 (1 cement : 4 coarse sand)25 mm thick BI01010001010000000000000515BI0100001208 830 sqm
97 8.1 Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab. BI01010001010000000000000515BI0100001209 1330 metre
98 8.11 Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm BI01010001010000000000000515BI0100001210 115 sqm
99 8.12 Providing edge moulding to 18 mm thick marble stone counters, vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer -in-Charge.Granite work BI01010001010000000000000515BI0100001211 300 metre
100 8.13 Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye orequivalent. BI01010001010000000000000515BI0100001212 150 sqm
101 8.14 Grading roof for water proofing treatment with:Cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) BI01010001010000000000000515BI0100001213 226 cum
102 8.15 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer in-charge. The product performance shall carry guarantee for 10 years against any leakage.For vertical surface two coats @0.70 kg per sqm BI01010001010000000000000515BI0100001214 1860 sqm
103 8.16 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer in-charge. The product performance shall carry guarantee for 10 years against any leakage.For horizontal surface one coat @1.10 kg per sqm. BI01010001010000000000000515BI0100001215 5048 sqm
104 8.17 Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. BI01010001010000000000000515BI0100001216 1391 sqm
105 8.18 Vinyl flooring - Providing and installing PUR reinforced homogeneous Vinyl Flooring of approved make and colour / shade with skirting (done over coving cum capping pad of size 100x30mm) upto 100mm height, sheet 2 mtr wide and 15 - 23 mtr long, having a nominal total thickness of the wear layer of 2 mm and are produced with Phthalate-free Technology and total VOC emmissions < 10ug/m3 (after 28 days). The Slip Resistance should meet the R9 group and should be chemical resistance as per EN 423 & bacterial resistance as per EN ISO 846: Part C. The impact sound reduction should be as per EN ISO 717/2. The wear resistance should be tested as per EN 649 and and should come under the T Group criteria.The Light fastness should be tested in according to ISO-105 B02 and should be rated >6. The thermal resistance should be 0.01 m2 K/W. The static electrical discharge should be < 2kV (EN1815). Installation : It is important to ensure the sub floor on which the sheet is being laid is on smooth, flat & free from moisture, grease, etc.In case of uneven sub floor upto 3mm the same should be levelled by self levelling compound. The moisture level present in the sub floor should be less than 8% before installation of the floor.The installation shall be undertaken as per the manufacturers installation instructions and as directed by the Engineer-in-Charge. The joints should be minimum and heat welded with matching PVC rod so as to get a seamless perfect level surface. The rate shall be inclusive of cost and conveyance of all materials, labour etc complete as directed by the Engineer in charge. - for sterile areas BI01010001010000000000000515BI0100001217 2508 sqm
106 8.19 Anti static Vinyl flooring - Providing and installing PUR reinforced permanently static conductive pressed homogenous Vinyl flooring of approved make and colour / shade with skirting done over coving cum capping pad for OT`s/ICU's sheets 2 mtr wide and 15 - 23mtr long, having a nominal total thickness of the wear layer 2mm meeting EN 685 standards and are produced with Phthalate-free Technology and total VOC emmissions < 10ug/m3(after 28 days). The Slip Resistance should meet the R9 group and should be chemical resistance as per EN 423 & bacterial resistance as per EN ISO 846: Part C.The reaction to fire to meet EN 13501-1 standards.The wear resistance should be tested as per EN 649 and and should come under the P Group criteria.The light fastness should be tested in according to ISO 105- B02 and should be rated >7. The thermal resistance should be according to EN12667. The static electrical dischargeTest should meet EN 1815 standards(< 2kV). The electrical insulation to ground should meet VDE0100,part600. Installation : It is important to ensure the sub floor on which the sheet is being laid is smooth, flat & hard & free from moisture, grease, etc. In case of uneven sub floor upto 3mm the same should be levelled by self levelling compound and coved using pvc cove fillets . The moisture level present in the sub floor should be less than 8% before installation of the floor.The installation shall be undertaken as per the manufacturer's installation instructions and as directed by the Engineer-in-Charge. The joints should be minimum and heat welded with matching PVC rod so as to get a seamless perfect level surface. The rate shall be inclusive of cost and conveyance of all materials, labour etc complete as directed by the Engineer in charge. BI01010001010000000000000515BI0100001218 420 sqm
107 8.2 Vinyl wall dado - Supply and installation of HO Wallgard 014 1.3mm thick for wall covering works at all levels. The rate shall be inclusive of cost and conveyance of all materials, labour etc complete as directed by the Engineer in charge. - for sterile areas BI01010001010000000000000515BI0100001219 3633 sqm
108 9 Sub head -Specialized items BI01010001010000000000000515BI0100001220
109 9.01 Frosted film - Supply and installation of 3M make frosted film pattern throughout all the internal glass panels wherever required of approx. 1.5 m height as per the approved pattern. BI01010001010000000000000515BI0100001221 150 sqm
110 9.02 Coloured graphics pattern - Supply and installation of coloured graphics pattern / instructions / images etc over fixed glass panels / doors of approx. 1.5 m height as per the approved pattern. BI01010001010000000000000515BI0100001222 100 sqm
111 9.03 Anchoring of reinforcement bars in already casted concrete by drilling the required diameter holes at the required depth and as per the design diameter and applying anchoring chemical of Hilti or any approved make after cleaning the hole from all debriesand fixing the reinforcement bars in the chemical etc.complete. This is applicable only in case of extending the existing RCC work as per the direction of engineer in charge. BI01010001010000000000000515BI0100001223 250 no
112 9.04 Providing and fixing in position 25mm to 30 mm thick bitumen impregnated fibre board conforming to IS: 1838, including cost of primer, sealing compound in expansion joints between Beams, Slabs and Columns at all level. BI01010001010000000000000515BI0100001224 440 per cm depth per 100 m
113 9.05 Providing and fixing sheet covering over expansion joints with iron screws as per design.Aluminium fluted strips 3.15 mm thick150 mm wide BI01010001010000000000000515BI0100001225 348 metre
114 9.06 Labour material and supervision charges for filling 25 mm baker road and PU sealant, providing synthetic expansion tape-Mapei band Tape 170 or equivalent on floor using Adesilex PG 2 of Mapei(in 1:3 ratio) or equivalent and filling PU sealant upto floor finish level and provide Aluminium 3.15 mm thick strips- 200 mm wide All complete as per manufacture specification. BI01010001010000000000000515BI0100001226 807 RM
115 9.07 Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12 mm dia steeel bar conforming to IS:1786, having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufactures permanent identification mark to be visible even after fixing including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1cement: 3 coarse sand: 6 graded stone aggregate 20 mm nominal size)Complete as per design BI01010001010000000000000515BI0100001227 30 each
116 9.08 Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with Zinc coating of 120 gms/ (both side inclusive), consisting of floor and ceiling channel 50 mm wide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with joints staggered to avoid through cracks, M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corners (25 mm x 25 mm x0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture's specification and direction of engineer in charge all complete.66 mm overall thickness Partition with 8 mm thick double skin Calcium Silicate Board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process with Compressive Strength 225 kg/sq cm, Bending Strength 100 kg/sq cm BI01010001010000000000000515BI0100001228 350 sqm
117 9.09 Providing and fixing thermal insulation with Resin Bonded rock wool conforming to IS: 8183, having density 49 Kg/m3, 50mm thick, wrapped in 200 G Virgin Polythene Bags fixed to wall with screw, rowel plug & washers and held and in position by criss crossing GI wire etc. complete as per directions of Engineer-in-charge. BI01010001010000000000000515BI0100001229 350 sqm
118 10 Sub head -False Ceiling Work BI01010001010000000000000515BI0100001230
119 10.01 Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending BI01010001010000000000000515BI0100001231 9200 sqm
120 10.02 Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.GI Metal Ceiling Lay in perforated Tegular global white color tiles of size 595x595 mm and 0.5mm thick with 8 mm drop; made of GI sheet having glavanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient) of 0.5, electro statically polyster powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece. BI01010001010000000000000515BI0100001232 1625 sqm
121 10.03 Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.12.5 mm thick square edge PVC Laminated Gypsum Tile size 595x595 mm made of Gypsum plasterboard , manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16 mm thick fire retardant PVC film on the face side and 12 micron metalized polyster on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyster film so as to make the tile a completely sealed unit. BI01010001010000000000000515BI0100001233 50 sqm
122 10.04 Aluminium Non perforated false ceiling - Providing & Fixing true horizontal level swing down suspended ceiling comprising of approved make Aluminum Clip in Swing Down with double pip self-leveling feature and special tabs to allow swing down of tile to enable plenum access with plain visual consisting of 600X600 mm clip in plain tiles of 0.7mm uniform thickness Aluminum with bevel edge in approved color precoated with primer coat at the rear side with Light Reflectance > 60%.Tiles should have fire performance of Class A2-s1.d0 as per EN13501.The grade of aluminiumshall mandatorily be AA 3003. The AluminiumTile shall mandatorily be RoHS Compliant (Resistance of Hazardous Substance).Compliant certificate shall be provided on demand. The tile shall maintain uniform Thickness of 0.7mm across all areas of tiles with no deviation. The tile shall have paint thickness of 25 microns to enable better scratch resistance.The tile shall have the ability to combine the main light with extra illumination providing 77% light reflectance & enables to achieve light uniformity. The tile shall have g Ceiling Attenuation Class of 44db. It shall withstands upto 150 Scrub cycle using Scrubablity tester as per ASTM D 2486. The tile shall offer superior wash performance without compromising panel finish integrity using a washablity tester as per ASTM D 4828. Installation: To comprise 3000mm long "C" channels spaced at 1200mm centers securely fixed to the structural soffit by support clamp & approved hangers.The last hanger at the end of each C channel should not be greater than 600mm from the adjacent wall. Use a C-channel connector for splicing two pieces of C-channels. 4000mm spring tee bars shall be spaced at 600mm centers in a direction perpendicular to the C-channels and shall be secured at every intersection with C channel using a tee bar hanger. Use T bar connector to splice two pieces of spring tee bars. Tiles should be clipped in between two spring tee bars from below. This is a downward installation. All full panels can be removed and reinstalled without movement up into the plenum area. Perimeter trims of approved color secured to walls at 450mm maximum centers. Cut tiles to be secured to the wall angles using a spring clamp. The installation shall be undertaken as per the manufacturers installation instructions and as directed by the Engineer-in-Charge. BI01010001010000000000000515BI0100001234 2120 sqm
123 10.05 Stainless Steel false ceiling - Providing and fixing in position stainless steel false ceiling of approx size 600 x 600 x 20mm with ceiling made of 1 mm thick stainless steel sheets of AISI 304 grade, visible side having satin/matt finish and coated with protective PVC taping.The joints of the stainless steel wall panels shall be made seamless, and homogeneous.There shall not be any sharp edges and all corners should be curved to avoid bacteria/fungal contamination.The Ceiling panels shall be supported to the slab with stainless steels brackets, fixtures and using nonferrous hard ware. The ceiling panel design and construction shall be provided with openings required for later inclusion of additional equipments, repair of installed equipments, without affecting the rigidity and strength of the structure. The joints between walls and ceiling(skirting) panels shall be connected by curved panels at a radius of 450mm. All provisions shall be in the Operation theatre ceiling for mounting other equipment i.e. Ceiling-mounted Operation theatre light, Pendants, Brackets for monitors, Cameras etc. complete. The rate shall also be inclusive of all materials, labour, transportation etc. complete. BI01010001010000000000000515BI0100001235 545 sqm
124 10.06 Providing and fixing tiled false ceiling of approved materials of size 595x595 mm in true horizontal level, suspended on interlocking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long space between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening of services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanized butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge.8 mm thick fully perforated calcium silicate board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process to give stable crystalline structure with minimum compressive strength 225 Kg/ sq. cm, bending strength 100 Kg/sq. cm, of size 595x595 mm, having perforation of dia, 10 mm with minimum perforated area 18% with non woven tissue on the back side, having an NRC (Noise Reduction Coefficient) of 0.85, with 50 mm thick rockwool of 48 Kg/cum backing. BI01010001010000000000000515BI0100001236 1166 sqm
125 11 Sub head -Finishes BI01010001010000000000000515BI0100001237
126 11.01 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. BI01010001010000000000000515BI0100001238 11795 sqm
127 11.02 Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer BI01010001010000000000000515BI0100001239 42882 sqm
128 11.03 Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work BI01010001010000000000000515BI0100001240 21441 sqm
129 11.04 Smooth finishing of the exposed surface of RCC work with 6mm thick cement mortar 1:3 ( cement : 3 fine sand). BI01010001010000000000000515BI0100001241 13580 sqm
130 11.05 Add for plaster drip course / groove in plastered surface or moulding to R.C.C. projections. BI01010001010000000000000515BI0100001242 1995 metre
131 11.06 Providing and fixing PVC chicken mesh of approved quality in the junction of RCC beam and block masonry atleast 100 mm on either face.(total 200mm width ) all complete as directed by the Engineer in charge. BI01010001010000000000000515BI0100001243 370 sqm
132 11.07 12 mm cement plaster of mix:1:6 (1 cement : 6 fine sand). BI01010001010000000000000515BI0100001244 25475 sqm
133 11.08 15 mm cement plaster on rough side of single or half brick wall of mix:1:4 ( 1 Cement : 4 coarse sand) BI01010001010000000000000515BI0100001245 6009 sqm
134 11.09 15 mm cement plaster on rough side of single or half brick wall of mix:1:6 ( 1 cement : 6 coarse sand) BI01010001010000000000000515BI0100001246 8729 sqm
135 11.1 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 ( 1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 ( 1 cement : 6 fine sand). BI01010001010000000000000515BI0100001247 3704 sqm
136 11.11 Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof. BI01010001010000000000000515BI0100001248 9030 sqm
137 11.12 Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers. BI01010001010000000000000515BI0100001249 42200 kg
138 11.13 Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer's specification . BI01010001010000000000000515BI0100001250 1.02925e+06 kg
139 11.14 Finishing walls with textured exterior pint of required shade:New work (Two or more coats applied @ 3.28 ltr/ 10 sqm ) over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm BI01010001010000000000000515BI0100001251 9077 sqm
140 11.15 Finishing walls with Acrylic Smooth exterior paint of required shade:New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) BI01010001010000000000000515BI0100001252 3026 sqm
141 11.16 Providing and applying of swellable type water stop tape, 19mm x 25mm thick inlinear meter (expansive nature) for construction joints treatment of RCC structuresuch as raft slab, retaining walls, water storage tank and at the junctions of raftslab with the retaining walls etc.. After cleaning the surface, one coat of requiredprimer for swellable water stop tape shall be applied throughout the length of thejoint @3.78 litre per 240 running meter. Over the primed surface swellable typewater stop tape shall be placed. The work shall be carried out all complete as perspecification and the direction of the engineer-in-charge. The product performanceshall carry guarantee for 10 years against any leakage. BI01010001010000000000000515BI0100001253 175 metre
142 12 Sub head - Finishing and Roofing BI01010001010000000000000515BI0100001254
143 12.01 Polycarbonate sheet roofing for super speciality block - Providing, installing and fixing profiled sheeting using premium quality single skin polycarbonate sheet having minimum thickness of 3mm supported on steel members. The structural steel members shall include rafters and purlins made of steel hollow sections of approx. size 50mm x 50mm x 1.6mm thick, purlin support of approx. size 25mm x 25mm x 1.6mm thick, fabricated posts and lattice of approx. size 30mm x 30mm x 1.6mm thick. All steel members shall be preferably galvanized pipe standard hollow sections. The spacing of the rafters / purlins should be controlled in such a way that it is placed right under the joints of the roofing sheet. Roofing sheet shall be factory cut and required length to suite site conditions and design drawings. Roofing sheet shall be crest fixed to purlins with hot dip 'galvanized self drilling fasteners with integral EPDM washers (one fastener on each crest). Also, fasteners to be provided on side laps. Minimum sheet overlap at end laps shall be 150mm. Penetration and end laps in sheet shall be sealed by using proper sealant. Profiled HDPE fillers shall be provided wherever required to close voids between capings and troughs of the sheet to provide a weather tight exterior. Rate shall be inclusive of cost and conveyance of all materials, painting of steel members using two coats of approved make and colour synthetic enamel paint over two coats of approved make anti - corrosive approved zinc chromate primer, lead, lift, scaffolding, all labour charges, making the roof water tight with required sealant etc. complete at all level and as directed by Engineer-in-Charge.(Note: The contractor shall take prior approval for the materials to be used for the work from the concerned Authority) BI01010001010000000000000515BI0100001255 570 sqm
144 12.02 Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. BI01010001010000000000000515BI0100001256 2570 sqm
145 12.03 Providing and fixing 15cm wide, 45 cm overall semi circular plain G.S. sheet gutter with iron brackets 40x3 mm size, bolts, nuts and washers etc., including making necessary connections with rain water pipes complete.0.80 mm thick with zinc coating not less than 275 gm/m2 BI01010001010000000000000515BI0100001257 400 metre
146 13 Sub head - External Work BI01010001010000000000000515BI0100001258
147 13.01 Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge. BI01010001010000000000000515BI0100001259 75 cum
148 13.02 Extra for cutting reinforcement bars manually/ by mechanical means in R.C.C. or R.B. work ( Payment shall be made on the cross sectional area of R.C.C. or R.B work) as per direction of Engineer-in-charge. BI01010001010000000000000515BI0100001260 10 sqm
149 13.03 Disposal of building rubbish/ malba/ similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved BI01010001010000000000000515BI0100001261 100 cum
150 13.04 Demolishing stone rubble masonry manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer -in- Charges:In cement mortar BI01010001010000000000000515BI0100001262 50 cum
151 13.05 Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar BI01010001010000000000000515BI0100001263 25 cum
152 14 Sub head - Tree Cutting and Other External Work BI01010001010000000000000515BI0100001264
153 14.01 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 30 cm girth up to and including 60 cm girth BI01010001010000000000000515BI0100001265 5 each
154 14.02 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 60 cm girth up to and including 120 cm girth BI01010001010000000000000515BI0100001266 4 each
155 14.03 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyond 120 cm girth up to and including 240 cm girth BI01010001010000000000000515BI0100001267 8 each
156 14.04 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Above 240 cm girth BI01010001010000000000000515BI0100001268 2 each
157 14.05 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared BI01010001010000000000000515BI0100001269 2800 sqm
158 14.06 Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the excavated soil. and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m:Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm BI01010001010000000000000515BI0100001270 75 metre
159 14.07 Carriage of RCC pipe 300 mm dia above 50 m up to 100 m BI01010001010000000000000515BI0100001271 75 metre
160 14.08 Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete.450 mm dia RCC pipes. BI01010001010000000000000515BI0100001272 60 metre
161 14.09 Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete.600 mm dia RCC pipes. BI01010001010000000000000515BI0100001273 25 metre
162 14.1 Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand) BI01010001010000000000000515BI0100001274 165 cum
163 14.11 Random rubble masonry with hard stone in superstructure above plinth level and upto floor five level, including leveling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) at window sills, ceiling level and the like.Cement mortar 1:6 (1 cement : 6 coarse sand) BI01010001010000000000000515BI0100001275 25 cum
164 14.12 Pointing on stone work with cement mortar 1:3 ( 1 cement : 3 fine sand):Flush/ Ruled pointing BI01010001010000000000000515BI0100001276 651 sqm
165 14.13 Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres. BI01010001010000000000000515BI0100001277 4750 sqm
166 14.14 Construction of granular sub- base by Providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, Carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in- Charge.With Material conforming to Grade - I ( size range 75 mm to 0.075 mm) having CBR Value- 30 BI01010001010000000000000515BI0100001278 1425 cum
167 14.15 Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. 60mm thick cement concrete paver block of M-35 grade with approved colour, design & pattern. BI01010001010000000000000515BI0100001279 3420 sqm
168 14.16 Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness &amp; size/ shape, made by table vibratory method using PU mould, laid in required colour &amp; pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. 80 mm thick C.C. paver block of M-40 grade with approved color design and pattern. BI01010001010000000000000515BI0100001280 4075 sqm
169 14.17 Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS: 15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge. BI01010001010000000000000515BI0100001281 450 sqm
170 14.18 Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature jointed with cement mortar 1:3 ( 1 cement : 3 coarse sand) , including making joints with or without grooves ( thickness of joints except at sharp curve shall not to more than 5 mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge ( length of finished kerb edging shall be measured for payment ). ( Precast C.C. kerb stone shall be approved by Engineer-in-Charge) BI01010001010000000000000515BI0100001282 45 cum
171 14.19 Provision for removing the waste from STP disinfecting and treating with lime. BI01010001010000000000000515BI0100001283 1 L.S
172 15 Sub head - Site Clearence BI01010001010000000000000515BI0100001284
173 15.01 Uprooting and Removing Stumps & Roots: Uprooting and Removing Stumps & roots, compaction of backfilling and stacking of servicable material by manual means as per Technical Specification Clause 201.A.Lead upto 100 m(i)Girth above 300 mm to 600 mm BI01010001010000000000000515BI0100001285 5 each
174 15.02 Uprooting and Removing Stumps & Roots: Uprooting and Removing Stumps & roots, compaction of backfilling and stacking of servicable material by manual means as per Technical Specification Clause 201.A. Lead upto 100 m (ii)Girth above 600 mm to 900 mm BI01010001010000000000000515BI0100001286 2 each
175 15.03 Uprooting and Removing Stumps & Roots: Uprooting and Removing Stumps & roots, compaction of backfilling and stacking of servicable material by manual means as per Technical Specification Clause 201.A. Lead upto 100 m (iii)Girth above 900 mm to 1800 mm BI01010001010000000000000515BI0100001287 5 each
176 15.04 Uprooting and Removing Stumps & Roots: Uprooting and Removing Stumps & roots, compaction of backfilling and stacking of servicable material by manual means as per Technical Specification Clause 201.A. Lead upto 100 m (iv)Girth above 1800 mm to 2700 mm BI01010001010000000000000515BI0100001288 3 each
177 15.05 Uprooting and Removing Stumps & Roots: Uprooting and Removing Stumps & roots, compaction of backfilling and stacking of servicable material by manual means as per Technical Specification Clause 201.A. Lead upto 100 m (v)Girth above 2700 mm to 4500 mm BI01010001010000000000000515BI0100001289 2 each
178 16 Sub head - Wall guard and corner guard BI01010001010000000000000515BI0100001290
179 16.01 Supply and installation of Wall Guards cum hand rails with the following specification. The wall Guards shall be of height 140mm with an outer cover made out of PVC,PP/ABS with an interior core of high quality aluminium design with anti corrosive strips. The wall guards shall be fitted to the tile surface with adequate fasteners and anchor screws and braces. The thickness of vinyl and aluminium shall be 1.5mm.The surface texture shall be fire resistant . The units shall be of approved make and colour. As per Annexure II, Item No. 8 Wall Guard cum hand rails. BI01010001010000000000000515BI0100001291 600 metre
180 16.02 Supply and installation of Brace for wall guards with the following specification. The Brace shall be made out of PVC with a thickness of 1.5mm. The Brace shall be provided at an interval of 500mm. The Brace shall be of approved make and colour. This item shall be a part of Item No. 16.01 BI01010001010000000000000515BI0100001292 1500 each
181 16.03 Supply and installation of Elbow for wall guards with the following specification. The elbow shall be of height 140mm which shall be provided at the corners. The Outer Cover shall be made out of PVC,PP/ABS with an interior core of high quality aluminium design with anti corrosive strips. The thickness of vinyl and aluminium shall be 1.5mm. The surface texture shall be fire resistant . The units shall be of approved make and colour. This item shall be a part of Item No. 16.01 BI01010001010000000000000515BI0100001293 510 each
182 16.04 Supply and installation of Wall Guard with the following specification. The wall Guards shall be of height 100mm with an outer cover made out of PVC,PP/ABS with an interior core of high quality aluminium design with anti corrosive strips. The wall guards shall be fitted to the tile surface with adequate fasteners and anchor screws and braces. The thickness of vinyl and aluminium shall be 1.5mm.The surface texture shall be fire resistant. The units shall be of approved make and colour. As per Annexure II, Item No. 8. Wall Guard BI01010001010000000000000515BI0100001294 600 metre
183 16.05 Supply and installation of End cap for Wall Guards with the following specification. The end cap for wall Guards shall be of height 100mm with an outer cover made out of PVC,PP/ABS. The End cap shall be fitted to the at every termination of wall guards. The surface texture shall be fire resistant. The units shall be of approved make and colour. This item shall be a part of Item No. 16.04. End Cap BI01010001010000000000000515BI0100001295 510 each
184 16.06 Supply and installation of corner guards made ourt of Stainless Steel 304 Grade material of thickness 1mm with an inside rubber backup of thickness 1.5mm of approved make and shall be fitted to the corner of the wall to the finished wall tile using anchor screws.. Each corner guard shall be of dimension 35mmx35mmx1500mm(H) and of approved make. As per Annexure II, Item No. 13. BI01010001010000000000000515BI0100001296 455 metre
185 17 Sub head Signage BI01010001010000000000000515BI0100001297
186 17.01 Supply and installation of way finding signages as per following specifications. The signages shall be plotter cut 2 mil 3M or equivalent pigmented translucent vinyl pasted on3mm thick ACP/ 6mm thick hybrid board on both Sides of approved make and colour. The vinyl shall conform to class A rating for fire retardant as per ASTM E84 standard. The signage shall be ceiling suspended using Stainless Steel strings as per the directions of engineer in charge. Contractor shall get approval for the design before fabrication. As per Annexure II, Item No. 1. Way Finding Signage: 1200mmx600mm BI01010001010000000000000515BI0100001298 100 each
187 17.02 Supply and installation of door signage with the following specification. The signages shall be plotter cut 2 mil 3M or equivalent pigmented translucent vinyl of approved design pasted on 3mm thick sunboard and installed on doors using VHB tapes. The vinyl shall conform to class A rating for fire retardant as per ASTM E84 standard. Contractor shall get approval for the design before fabrication. As per Annexure II, Item No. 2. Door Signage: 300mmx100mm BI01010001010000000000000515BI0100001299 1000 each
188 17.03 Supply and installation of Aluminium profile sliding door signage with the following specifications. The signage shall have an aluminium profile modular frame of height 100mm. The letters shall be plotter cut 2 mil 3M or equivalent pigmented translucent vinyl of approved design pasted on 3mm thick sunboard/ ACP Board. The vinyl shall conform to class A rating for fire retardant as per ASTM E84 standard and shall be fixed with adequate fasteners. The signage shall be in such a way that the Sunboard/ACP Board is slid to the aluminium profile for easy replacement of names. Contractor shall get approval for the design before fabrication. As per Annexure II, Item No. 3. Aluminium profile sliding, door signage. 300mmx100mm BI01010001010000000000000515BI0100001300 45 each
189 17.04 Supply and installation of aluminium profile toilet signage with the following specification. The signage shall have an aluminium profine frame of thickness 2mm. The letters shall be plotter cut 2 mil 3M or equivalent pigmented translucent vinyl of approved design. The vinyl shall conform to class A rating for fire retardant as per ASTM E84 standard and shall be fixed with adequate fasteners. The signage shall be in such a way that the Sunboard/ACP Board is slid to the aluminium profile for easy replacement of names. The signage shall be of approved colour and design. Contractor shall get approval for the design before fabrication. As per Annexure II, Item No. 4.Toilet Signage- 150mmx100mm. BI01010001010000000000000515BI0100001301 60 each
190 17.05 Supply and installation of illuminted signage of dimension 600mmx200mm with a projection of 90mm made out of acrylic box of thickness 3mm in the front and 4mm thickness in the sides wall mounted with necessary accessories. Signages shall be plotter cut 2 mil 3M or equivalent pigmented translucent vinyl with a minimum height of 120mm of approved design and colour. The vinyl shall conform to class A rating for fire retardant as per ASTM E84 standard. Contractor shall get approval for the design before fabrication. As per Annexure II, Item No. 5. BI01010001010000000000000515BI0100001302 45 each
191 17.06 Supply and installation of illuminated Round signage of diameter 600mm with the following specifications. The signage shall me made out of 50mm projectd ACP base with letters made out of 60mm projected 3mm Acrylic box of approved height. The first phase shall be pasted with 3M or equivalent vinyl with LED for each letters of approved make and metal frame for letters including all necessary accessories. The signage shall be of approved design colour and make. Contractor shall get approval for the design before fabrication. As per Annexure II, Item No. 6. BI01010001010000000000000515BI0100001303 15 each
192 17.07 Supply and installation of illuminated signage with the following specifications. The letters shall be made out of 70mm projected 3mm Acrylic box of height 800mm. The first phase shall be pasted with 3M or equivalent vinyl with LED for each letters of approved make and metal frame for letters including all necessary accessories. Contractor shall get approval for the design before fabrication.As per Annexure II, Item No. 7. Illuminated Main Signage. BI01010001010000000000000515BI0100001304 18 sqm
193 18 Electrical Works
194 18.001 625KVA DIESEL GENERATOR\nSupply, Installation, Testing & commissioning of 'Silent Type' Diesel Generating Sets along with acoustic enclosure having Prime Power Rating of 500KW at 1500 RPM 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 Phase system & for 0.85 Load factor (Detailed Technical Specification Attached) 2 Set
195 18.002 EXHAUST PIPES\nSupplying and fixing exhaust gas piping of suitable dia specified by the OEM for 625KVA DG with black M.S 'B' class pipe welded confirming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral Wool/ Rockwool,50 mm thick wire mesh & aluminium cladding etc., as required as per specifications. suitable rain cap for top to avoid rain water entry. The distance between exhaust pipe at top and rain cap should be higher than diameter of pipe. Horizontal run of exhaust piping should slope downwards away from engine to the condensate trap. Silencer should be installed with drain plug at bottom. Fixing shall be done with proper clamps, expansion bolts, and all other accessories as instructed by the Engineer in charge and the rate inclusive of all minor civil works required, bolts, clamps etc. as required for installation. Necessary MS Support to exhaust piping should be done in such a manner that load of exhaust piping is not exerted to turbo charger and the vertical run of the pipes shall be provided with indirect supporting method so that when the pipes are hot and expanded they will be lifted into the supports. Exhaust pipe height shall be 3m more than the top of any adjacent building within 10m radius of the exhaust. 1 Set
196 18.003 SITC of Outdoor Type RMU with Metering Cubicle (Detailed Technical Specification Attached). 1 Set
197 18.004 SITC of HT Panel (Detailed Technical Specification Attached). 1 Set
198 18.005 750KVA - 11kV/433V Cast Resin (Dry type) Laser Scribed Transformer\nSupply, installation, testing & commissioning of 1No. of 750kVA 11kV/433V indoor cast resin dry type transformer with laser scribed core and copper winding, connected Delta on HT side and Star on LT side with "ON Load Tap Changer" having a continuous rating for 11kV / 433V 3 phase 50 Hz. Vector group Dyn 11 with tapping's from +5% to -10% in steps of 2.5 %, AVR & RTCC, include separate winding temperature indicator for each phase and core in the Transformer. Insulation Class 'F'.Transformer should be directly connected to cable on HV side and have suitable adaptor box on LV side for connecting 1250A AL BBT with all accessories, complete as required and losses as per ECBC, IE rules specifications. The transformer shall confirm to IS 2026, 11171/1985 with latest amendment etc. complete. \n(Detailed Technical Specification Attached). 2 Set
199 18.006 Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Indoor type Sandwich Type Bus Trunking for use on 3 phase 4 wire 415 volts, 50 Hz A.C.supply in convenient section complete with 4 No's aluminium bus bars, necessary joints, elbow joints & expansion joints and bends, adopter box and copper flexible for joints, continuous earthing with 2 No's CU strip of 25x3mm including G.I clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. \n1250 amps 36kA SC for 1 sec 54 metre
200 18.007 MAIN SWITCH BOARD\nFabrication, supply, erection, testing and commissioning of TTA type, Indoor Cubicle , dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all accessories as required for complete installation as instructed by engineer in charge and as shown in the schematic layout provided. \nThe panel shall be with PLC components for interlocking of incoming breakers & bus couplers, UPS for PLC and all connections and interconnections required for PLC Logic Operations for interlocking of breakers as indicated in schematic.\n(Detailed Technical Specification attached) 1 Nos
201 18.008 DG SYNCH PANEL\nFabrication, supply, erection, testing and commissioning of TTA, Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge and as shown in the schematic layout provided. \nThe panel shall be with PLC components for Synchronisation of 2Nos. of 625KVA DG Sets and 1No. 400KVA, Auto Load Sharing, AMF which includes synchronising relays, UPS for PLC and all connections and interconnections required for synchronising and load sharing for 3 nos. of DG sets and individual Generator selection and control facilities as well as mimic diagram. (Detailed Technical Specification attached) 1 Nos
202 18.009 FLOOR PANEL-1\nFabrication, supply, erection, testing and commissioning of TTA PANEL, Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge and as shown in the schematic layout provided.(Refer SLD) 1 Nos
203 18.01 FLOOR PANEL-2\nFabrication, supply, erection, testing and commissioning of TTA PANEL, Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge and as shown in the schematic layout provided. (Refer SLD) 1 Nos
204 18.011 LOWER GROUND -1 PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge and as shown in the schematic layout provided. (Refer SLD) 1 Nos
205 18.012 GROUND -FLOOR PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge and as shown in the schematic layout provided. (Refer SLD) 1 Nos
206 18.013 FIRST FLOOR PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge and as shown in the schematic layout provided. (Refer SLD) 1 Nos
207 18.014 SECOND FLOOR PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge and as shown in the schematic layout provided. (Refer SLD) 1 Nos
208 18.015 THIRD FLOOR PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
209 18.016 FOURTH FLOOR PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
210 18.017 FIFTH FLOOR PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
211 18.018 SIXTH & TERRACE FLOOR PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
212 18.019 GROUND FLOOR UPS PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided.(Refer SLD) 1 Nos
213 18.02 FOURTH FLOOR UPS PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
214 18.021 FIFTH FLOOR UPS PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
215 18.022 OT PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
216 18.023 EMERGENCY LIGHTING PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
217 18.024 UPS INPUT PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
218 18.025 MEDICAL EQUIPMENT PANEL\nFabrication, supply, erection, testing and commissioning of TTA PANEL, Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
219 18.026 APFC PANEL-300KVAR\nFabrication, supply, erection, testing and commissioning of PTTA Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided.\nAPFC PANEL - With inbuilt solid state automatic power factor correction arrangement having microprocessor based control circuit and contactor switching power circuit having a required capacity of 300KVAR having capacitor bank in steps of [(2x50KVAR)+(6x25KVAR)+(2x10KVAR)+(1x15KVAR)]+ fixed capacitor of (1 x 15 KVAR), including main MCCB, MCB's, APFC relay, contactors, Reactors, capacitors, indicating lamps, etc. Complete with all necessary hardware & accessories. (Refer SLD) 2 Nos
220 18.027 MAIN LIFT PANEL\nFabrication, supply, erection, testing and commissioning of TTA PANEL, Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
221 18.028 LIFT PANEL-1\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
222 18.029 LIFT PANEL-2\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
223 18.03 LIFT PANEL-3\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor/wall mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
224 18.031 PLUMBING PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
225 18.032 UPS O/P PANEL\nFabrication, supply, erection, testing and commissioning of Indoor Cubicle Type, dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet (7 tank treatment) fully compartmentalised as per Form 4B Construction complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel for cable end termination including all components as shown in the schematic drawing. All opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all assecories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. (Refer SLD) 1 Nos
226 18.033 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3.5cx400sq.mm Al Cable 830 Metre
227 18.034 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3.5cx300sq.mm Al Cable 160 Metre
228 18.035 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3.5cx240sq.mm Al Cable 935 Metre
229 18.036 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3.5cx185sq.mm Al Cable 500 Metre
230 18.037 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3.5cx150sq.mm Al Cable 15 Metre
231 18.038 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3.5cx120sq.mm Al Cable 80 Metre
232 18.039 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3.5cx95sq.mm Al Cable 1055 Metre
233 18.04 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3.5cx70sq.mm Al Cable 165 Metre
234 18.041 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3.5cx50sq.mm Al Cable 595 Metre
235 18.042 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 4cx35sq.mm Al Cable 540 Metre
236 18.043 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 4cx25sq.mm Al Cable 550 Metre
237 18.044 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 4cx16sq.mm Al Cable 851 Metre
238 18.045 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor, A2XFY power cable confirming to IS 7098 (part 1) amended up to date. 4cx10sq.mm Al Cable 8193 Metre
239 18.046 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3cx10sq.mm CU Cable 1056 Metre
240 18.047 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3cx04sq.mm CU Cable 150 Metre
241 18.048 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3cx2.5sq.mm CU Cable 180 Metre
242 18.049 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 4cx16sq.mm CU Cable 30 Metre
243 18.05 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 4cx10sq.mm CU Cable 430 Metre
244 18.051 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 6C x 1.5sq.mm Cu Control Cable 100 Metre
245 18.052 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 4C x 1.5sq.mm Cu Control Cable 300 Metre
246 18.053 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3C x 1.5sq.mm CU Shielded Arm Cable 150 Metre
247 18.054 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 3C x 1.5sq.mm Cu Control Cable 348 Metre
248 18.055 Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 2C x 1.5sq.mm Cu Control Cable 520 Metre
249 18.056 Supply drawings and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded FRLS conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:694:1990 of the following sizes in existing cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms and making good the damages etc. as required and instructed by engineer in charge.\n1C x 95sq.mm Copper Flexible Cable 780 Metre
250 18.057 Supply drawings and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded FRLS conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:694:1990 of the following sizes in existing cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms and making good the damages etc. as required and instructed by engineer in charge.\n1C x 35sq.mm Copper Flexible Cable 30 Metre
251 18.058 Supply drawings and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded FRLS conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:694:1990 of the following sizes in existing cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms and making good the damages etc. as required and instructed by engineer in charge.\n1C x 25sq.mm Copper Flexible Cable 300 Metre
252 18.059 Supply drawings and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded FRLS conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:694:1990 of the following sizes in existing cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms and making good the damages etc. as required and instructed by engineer in charge.\n1C x 16sq.mm Copper Flexible Cable 540 Metre
253 18.06 Supply drawings and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded FRLS conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:694:1990 of the following sizes in existing cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms and making good the damages etc. as required and instructed by engineer in charge.\n1C x 10sq.mm Copper Flexible Cable 240 Metre
254 18.061 Supply drawings and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded FRLS conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:694:1990 of the following sizes in existing cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms and making good the damages etc. as required and instructed by engineer in charge.\n1C x 06sq.mm Copper Flexible Cable 100 Metre
255 18.062 \nSupply drawings and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded FRLS conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:694:1990 of the following sizes in existing cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms and making good the damages etc. as required and instructed by engineer in charge.\n1C x 04sq.mm Copper Flexible Cable 180 Metre
256 18.063 Supply of following 11kV (E) grade XLPE insulated PVC sheathed armoured aluminium conductor HT power cable, insulation screened with extruded semi conducting compound in combination with copper tape suitable for 11kV earthed system confirming to relevant standard. \n3cx300sq.mm XLPE Cable 400 Metre
257 18.064 Supply & laying of DWC pipe in ground level excluding excavation 110/94 mm or nearest size. 400 Metre
258 18.065 Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: \n300 sq. mm 9 Each
259 18.066 Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : \n300 sq. mm 1 Each
260 18.067 Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : \n300 sq. mm 2 Each
261 18.068 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 1/2X 400 sq. mm (82mm) 32 Set
262 18.069 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 1/2X 300 sq. mm (70mm) 10 Set
263 18.07 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 1/2X 240 sq. mm (62mm) 14 Set
264 18.071 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 1/2X 185 sq. mm (57mm) 12 Set
265 18.072 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 1/2 X 150 sq. mm (50mm) 2 Set
266 18.073 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 1/2 X 120 sq. mm (45mm) 2 Set
267 18.074 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 1/2X 95 sq. mm (45mm) 18 Set
268 18.075 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 1/2X 70 sq. mm (38mm) 4 Set
269 18.076 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 1/2 X 50 sq. mm (35mm) 14 Set
270 18.077 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n4C X 35 sq. mm (32mm) 12 Set
271 18.078 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n4C X 25 sq. mm (28mm) 10 Set
272 18.079 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n4C X 16 sq. mm (28mm) 48 Set
273 18.08 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n4C X 10 sq. mm (25mm) 308 Set
274 18.081 Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 X 10 sq. mm (22mm) 72 Set
275 18.082 Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required. \n2C X 1.5 sq. mm 20 Set
276 18.083 Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required. \n3C X 1.5 sq. mm 42 Set
277 18.084 Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required. \n4C X 1.5 sq. mm 18 Set
278 18.085 Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required. \n6C X 1.5 sq. mm 240 Set
279 18.086 Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required. \n4C X 16 sq. mm (28mm) 2 Set
280 18.087 Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required. \n4C X 10 sq. mm (25mm) 20 Set
281 18.088 Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required. \n3C X 04 sq.mm 8 Set
282 18.089 Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required. \n3C X 2.5 sq.mm 6 Set
283 18.09 Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. \n95 sq. mm 44 Set
284 18.091 Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. \n35 sq. mm 6 Set
285 18.092 Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. \n25 sq. mm 8 Set
286 18.093 Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. \n16 sq. mm 6 Set
287 18.094 Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. \n10 sq. mm 24 Set
288 18.095 Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. \n6 Sq. mm 6 Set
289 18.096 Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. \n4 sq. mm 12 Set
290 18.097 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.\nUp to 35 sq. mm. 1452 Metre
291 18.098 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.\nAbove 35 sq. mm and up to 95 sq. mm 300 Metre
292 18.099 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.\nAbove 95 sq. mm and up to 185 sq. mm 15 Metre
293 18.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.\nAbove 185 sq. mm and up to 400 sq. mm 50 Metre
294 18.101 Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc. as required. \nAbove 185 sq. mm and up to 400 sq. mm 30 Metre
295 18.102 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. \nUp to 35 sq. mm 1500 Metre
296 18.103 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. \nAbove 35 sq. mm and up to 95 sq. mm 150 Metre
297 18.104 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. \nAbove 95 sq. mm and up to 185 sq. mm 70 Metre
298 18.105 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. \nAbove 185 sq. mm and up to 400 sq. mm 500 Metre
299 18.106 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. \nUp to 35 sq. mm (clamped with 1mm thick saddle) 9300 Metre
300 18.107 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. \nAbove 35 sq. mm and up to 95 sq. mm (clamped with 25x3mm MS flat clamp) 1365 Metre
301 18.108 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. \nAbove 95 sq. mm and up to 185 sq. mm (clamped with 25/40x3mm MS flat clamp) 450 Metre
302 18.109 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. \nAbove 185 sq. mm and up to 400 sq. mm (clamped with 40x3mm MS flat clamp) 1450 Metre
303 18.11 Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. 150 No
304 18.111 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. \nAbove 120 sq. mm and up to 400 sq. mm 270 Metre
305 18.112 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. \nAbove 120 sq. mm and up to 400 sq. mm 60 Metre
306 18.113 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required. \nAbove 120 sq. mm and up to 400 sq. mm 60 Metre
307 18.114 Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc. \nAbove 120 sq. mm and up to 400 sq. mm 30 Metre
308 18.115 Excavation for cable trenches in soft soil, depth up to 1.2 m including dressing of sides lift up to 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc. in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres. 256 Cum
309 18.116 Filling available excavated earth (excluding rock) in trenches, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 metres. 120 Cum
310 18.117 Deduct for not consolidation by ramming and watering while re-filling with sand and or good soil in cable/ pipe laying. 50 Cum
311 18.118 Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc. as required \n100 mm dia 18 Metre
312 18.119 Supplying and laying of following size DWC HDPE pipe lSI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. \n160 mm dia (OD-160 mm & ID-135 mm nominal) 45 Metre
313 18.12 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. \nPrimary Point (Switch to First Light Point) 2066 Point
314 18.121 Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required 15 Point
315 18.122 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required. \n3 X 1.5 sq.mm 28500 Metre
316 18.123 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required. \n3 x 2.5 sq. mm 47500 Metre
317 18.124 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required. \n3 x 4 sq. mm 6800 Metre
318 18.125 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required. \n3 x 6 sq. mm 240 Metre
319 18.126 Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. \n100 mm X 100 mm X 60 mm deep 30 Each
320 18.127 Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. \n250 mm X 300 mm X 60 mm deep 12 Each
321 18.128 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. \n5/6 amps switch 698 Each
322 18.129 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. \n15/16 amp switch 276 Each
323 18.13 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. \n3 pin 5/6 amp socket outlet 698 Each
324 18.131 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. \n6 pin 15/16 amp socket outlet 276 Each
325 18.132 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. 190 Each
326 18.133 Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. \n1 or 2 Module (75mmX75mm) 410 Each
327 18.134 Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. \n3 Module (100mmX75mm) 265 Each
328 18.135 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. \n6 Module 145 Each
329 18.136 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. \n3 Module 270 Each
330 18.137 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). 723 Each
331 18.138 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. 497 Each
332 18.139 Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc. as required. 750 Each
333 18.14 Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant ) \nStep Fan regulator - type 2 M 397 Each
334 18.141 Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant ) \n16A 3 pin plug top 15 Each
335 18.142 Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings). 155 Each
336 18.143 Supplying & fixing suitable size Gl box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required. 15 Each
337 18.144 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required \n8 way (8+24) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) 1 Each
338 18.145 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required \n6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) 2 Each
339 18.146 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required \n4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) 2 Each
340 18.147 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required \n12 way (8+36) - Three phase double cover Horizontal DB (IP 42/43) 9 Each
341 18.148 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required \n8 way (8+24) - Three phase double cover Horizontal DB (IP 42/43) 8 Each
342 18.149 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required \n6 way (8+18) - Three phase double cover Horizontal DB (IP 42/43) 13 Each
343 18.15 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required \n4 way (8+12) - Three phase double cover Horizontal DB (IP 42/43) 36 Each
344 18.151 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator \n8 way, Double door 1 Each
345 18.152 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator \n6 way, Double door 7 Each
346 18.153 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. \n63 amps 1 Each
347 18.154 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. \n40 amps 4 Each
348 18.155 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. \n32 amps 25 Each
349 18.156 Supplying and fixing following rating 25A, FP, 415 V, RCBO, having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 24 Each
350 18.157 Supplying and fixing following rating 32A, FP, 415 V, RCBO, having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 1 Each
351 18.158 Supplying and fixing following rating 25A, FP, 415 V, RCBO, having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 1 Each
352 18.159 Supplying and fixing following rating 32A, FP, 415 V, RCBO, having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 14 Each
353 18.16 Supplying and fixing following rating 40A, FP, 415 V, RCBO, having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 10 Each
354 18.161 Supplying and fixing following rating 63A, FP, 415 V, RCBO, having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 1 Each
355 18.162 Supplying and fixing following rating 25A, DP, 240 V, RCBO, having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 7 Each
356 18.163 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. \nSingle pole 951 Each
357 18.164 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "D" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. \nSingle pole 376 Each
358 18.165 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. \nDouble pole 2 Each
359 18.166 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. \nTriple pole 13 Each
360 18.167 Supplying and fixing 40 amps to 63 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. \nTriple pole 4 Each
361 18.168 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. 284 Each
362 18.169 Supplying, installation, testing and commissioning of Astronomical time switch capable of following output in feeder pillars/ Lighting DBs for automatic switching On &OFF of street lights at sun set & sun ruse or twilight override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete ad required \n3 output (1output per phase) and suitable for three phase supply 1 No
363 18.17 Supplying and fixing FP sheet steel enclosure on surface/ recess along with 25/32/40amps 415 volts "C" curve FP MCB complete with connections, testing and commissioning etc. as required. 40 No
364 18.171 SITC of Lockable off push button near pumps & Cooling Tower 15 No
365 18.172 Supplying and fixing following rating, four pole, 415 volts, isolator in MS Enclosure complete with connections, testing and commissioning etc. as required. \n100 amps FP Isolator 1 No
366 18.173 Supplying and fixing following rating, TPN, 415 volts, MCCB in MS Enclosure complete with connections, testing and commissioning etc. as required. \n125 amps TPN MCCB 2 No
367 18.174 Supplying and fixing following rating, TPN, 415 volts, MCCB in MS Enclosure complete with connections, testing and commissioning etc. as required. \n160 amps TPN MCCB 1 No
368 18.175 Supplying and fixing following rating, TPN, 415 volts, MCCB in MS Enclosure complete with connections, testing and commissioning etc. as required. \n200 amps TPN MCCB 1 No
369 18.176 Supplying and fixing following rating, TPN, 415 volts, MCCB in MS Enclosure complete with connections, testing and commissioning etc. as required. \n250 amps TPN MCCB 1 No
370 18.177 Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.\n20 mm 420 Metre
371 18.178 Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. \n25 mm 330 Metre
372 18.179 Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.\n32 mm 75 Metre
373 18.18 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.\n20 mm 27500 Metre
374 18.181 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.\n25 mm 34500 Metre
375 18.182 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.\n32 mm 1500 Metre
376 18.183 Supplying and installing perforated Hot Dipped Galvanised Perforated cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, Rate is inclusive of factory fabricated Tee's, Reducer, Bends etc. as required.\n300 mm width X 50 mm depth X 1.6 mm thickness 1820 Metre
377 18.184 Supplying and installing perforated Hot Dipped Galvanised Perforated cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, Rate is inclusive of factory fabricated Tee's, Reducer, Bends etc. as required.\n450 mm width X 50 mm depth X 2.0 mm thickness 55 Metre
378 18.185 Providing and fixing the following 14 SWG Hot Dip Galvanised Ladder tray (Bolted/Fabricated) along with necessary GI suspenders (not more than 1000 MM long) at equal intervals of 900 mm as directed. Including providing cost of GI supports, nuts, bolts, washers and dash fasteners as required. The installation shall be complete in all respects (All accessories like tees, bends vertical / horizontal shall be factory fabricated and cost of these to be included in the rate).\n450 mm width X 50 mm depth X 2.0 mm thickness 600 Metre
379 18.186 Providing and fixing the following 14 SWG Hot Dip Galvanised Ladder tray (Bolted/Fabricated) along with necessary GI suspenders (not more than 1000 MM long) at equal intervals of 900 mm as directed. Including providing cost of GI supports, nuts, bolts, washers and dash fasteners as required. The installation shall be complete in all respects (All accessories like tees, bends vertical / horizontal shall be factory fabricated and cost of these to be included in the rate.\n600 mm width X 50 mm depth X 2.0 mm thickness 140 Metre
380 18.187 Providing and fixing the following 14 SWG Hot Dip Galvanised Ladder tray (Bolted/Fabricated) along with necessary GI suspenders (not more than 1000 MM long) at equal intervals of 900 mm as directed. Including providing cost of GI supports, nuts, bolts, washers and dash fasteners as required. The installation shall be complete in all respects (All accessories like tees, bends vertical / horizontal shall be factory fabricated and cost of these to be included in the rate.\n900 mm width X 75 mm depth X 2.0 mm thickness 100 Metre
381 18.188 Supplying and installing Hot Dipped Galvanised Cable Tray Cover (galvanisation thickness not less than 50 microns), in convenient sections, joined with connectors, GI Nuts, Bolts etc….. as required.\nCover for 300 mm width X 50 mm depth X 2.0 mm thickness 300 Metre
382 18.189 Supplying and installing of Pre Galvanised Raceway with Cover, in convenient sections, joined with connectors, Rate inclusive of GI Suspenders & Supports, GI Nuts, Bolts etc….. as required.\n300mm width X 50 mm depth X 1.6 mm thickness for Raceways and 1.6mm for Cover 60 Metre
383 18.19 Supplying and installing of Pre Galvanised Raceway with Cover, in convenient sections, joined with connectors, Rate inclusive of GI Suspenders & Supports, GI Nuts, Bolts etc….. as required.\n450mm width X 50 mm depth X 2.0 mm thickness for Raceways and 1.6mm for Cover 45 Metre
384 18.191 Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories like cable divider, angles, couplers, cross, end caps etc.... conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required. 90 Metre
385 18.192 Fabrication and installing of Steel supports for Trays (Vertical/Horizontal) as required and as per prevailing standards with other steel works associated with electrical works completion as required as per site conditions using structural steel work (riveted, bolted or welded) in built up sections, including angle, channel, I sections, necessary nut and bolt and all required accessories including cutting, hoisting, fixing in position and applying 2 coats of zinc chromate primer and 2 coats of synthetic enamel paint of approved quality and colour as directed by engineer in charge. 7500 Kg
386 18.193 SITC of recess mounted 24W(+/- 10% Tolerance) LED luminaire of CRCA powder coated housing, driver with minimum 4KV Surge protection, power factor >0.9,THD<10%, rated life of 50,000 hours, system efficacy greater than or equal to 110 lm, with a CRI of 80 or above, ANSI rated LEDs from reputed makes such as Nichia, Japan / Cree, USA / Bridgelux, USA / Lumiled USA / Citizen Japan / Osram should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor). \nMakes: Philips- RC380B LED30S-5700 G5 L60W60 PSU OD, Wipro-CRCO10R024HP57HE, Bajaj:BZRSQL 24W XE WH\nNote: Light fixtures complete with all necessary accessories including suspenders, PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 1129 Nos
387 18.194 SITC of recess mounted 31W(+/- 10% Tolerance) LED luminaire of CRCA powder coated housing, driver with minimum 4KV Surge protection, power factor >0.9,THD<10%, rated life of 50,000 hours, system efficacy greater than or equal to 110 lm, with a CRI of 80 or above, ANSI rated LEDs from reputed makes such as Nichia, Japan / Cree, USA / Bridgelux, USA / Lumiled USA / Citizen Japan / Osram should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor). \nMakes: Philips: RC380B LED36S-5700 G5 L60W60 PSU OD, Wipro: CRCO10R030HP57HE, Bajaj: BZRSQL 30L XE WH OD SD\nNote: Light fixtures complete with all necessary accessories including suspenders, PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 275 Nos
388 18.195 SITC of recess mounted LED Cleanroom fitting 40W(+/- 10% Tolerance) of CRCA powder coated housing, driver with minimum 4KV Surge protection, power factor >0.9,THD<10%, rated life of 50,000 hours, system efficacy greater than or equal to 80 lm, with a CRI of 80 or above, ANSI rated LEDs from reputed makes such as Nichia, Japan / Cree, USA / Bridgelux, USA / Lumiled USA / Citizen Japan / Osram should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor). Makes: Philips-CR652B LED33S CR CW CA, Wipro LC20-551-XXX-57-XX Recess mounted Bajaj: BPRF 36W WH LED\nNote: Light fixtures complete with all necessary accessories including suspenders, PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 49 Nos
389 18.196 SITC of recess mounted Downlights of 6W(+/- 10% Tolerance) LED luminaire of Die Cast Aluminium Housing, driver with minimum 4KV Surge protection, power factor >0.9,THD<10%, rated life of 50,000 hours, system efficacy greater than or equal to 90 lm, with a CRI of 80 or above, ANSI rated LEDs from reputed makes such as Nichia, Japan / Cree, USA / Bridgelux, USA / Lumiled USA / Citizen Japan / Osram should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor). Makes: Philips- DN295B LED6S-5700 PSU WH, Wipro- CRDL11R008HP57, Bajaj: BGSLO SLEEK 6W WH RD.\nNote: Light fixtures complete with all necessary accessories including suspenders, PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 322 Nos
390 18.197 SITC of recess mounted Downlights of 18W(+/- 10% Tolerance) LED luminaire of Die Cast Aluminium Housing, driver with minimum 4KV Surge protection, power factor >0.9,THD<10%, rated life of 50,000 hours, system efficacy greater than or equal to 90 lm, with a CRI of 80 or above, ANSI rated LEDs from reputed makes such as Nichia, Japan / Cree, USA / Bridgelux, USA / Lumiled USA / Citizen Japan / Osram should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor). Makes: Philips- DN194B LED16S-5700 PSU WH S2, Wipro- CRDL11R023HP57, Bajaj: BZSLO 18W WH PRO.\nNote: Light fixtures complete with all necessary accessories including suspenders, PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 520 Nos
391 18.198 SITC of Surface mounted Downlights of 15W(+/- 10% Tolerance) LED luminaire of driver with minimum 4KV Surge protection, power factor >0.9,THD<10%, rated life of 50,000 hours, system efficacy greater than or equal to 90 lm, with a CRI of 80 or above, ANSI rated LEDs from reputed makes such as Nichia, Japan / Cree, USA / Bridgelux, USA / Lumiled USA / Citizen Japan / Osram should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor). Makes: Philips- SM250C LED16S- 6500 PSU WH, Wipro- LD81-131-XXX-60-SM, Bajaj: BGSLO SLEEK SURFACE 15W WH RD\nNote: Light fixtures complete with all necessary accessories including PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 39 Nos
392 18.199 SITC of LED Tube Lights of 20W(+/- 10% Tolerance) with Aluminium Profile linear batten and polycarbonate diffuser having driver of minimum 4KV Surge protection, power factor >0.9,THD<10%, rated life of 50,000 hours, system efficacy greater than or equal to 90 lm, with a CRI of 80 or above, ANSI rated LEDs from reputed makes such as Nichia-Japan/ Cree-USA / Bridgelux-USA / Lumiled-USA / Citizen-Japan / Osram should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor). Makes: Philips- BN308C LED20S-6500 L120 PSU WH, Wipro- LL24-251-XXX-57-XX, Bajaj: BCLAB 20W\nNote: Light fixtures complete with all necessary accessories including PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 380 Nos
393 18.2 SITC of LED Tube Lights of 40W(+/- 10% Tolerance) with Aluminium Profile linear batten and polycarbonate diffuser having driver of minimum 4KV Surge protection, power factor >0.9,THD<10%, rated life of 50,000 hours, system efficacy greater than or equal to 90 lm, with a CRI of 80 or above, ANSI rated LEDs from reputed makes such as Nichia, Japan / Cree, USA / Bridgelux, USA / Lumiled USA / Citizen Japan / Osram should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor). Makes: Philips- BN308C LED40S-6500 L120 PSU WH, Wipro- LL24-541-XXX-57-XX, Bajaj: BCLAB 40W\nNote: Light fixtures complete with all necessary accessories including PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 25 Nos
394 18.201 SITC of LED Mirror Lights of 10W(+/- 10% Tolerance) with polycarbonate diffuser having driver of minimum 4KV Surge protection, power factor >0.9,THD<10%, system efficacy greater than or equal to 80 lm, ANSI rated LEDs from reputed makes should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor).\nMakes: Philips, Wipro, Bajaj.\nNote: Light fixtures complete with all necessary accessories including PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 34 Nos
395 18.202 SITC of Bulkhead of 10W(+/- 10% Tolerance) with polycarbonate diffuser having driver of minimum 4KV Surge protection, power factor >0.9,THD<10%, system efficacy greater than or equal to 80 lm, ANSI rated LEDs from reputed makes should be provided and including all necessary accessories as required for the light fixture. (Test Reports for the above credentials shall be submitted and minimum 5 Year Warranty for the fixture should be provided by the contractor). \nMakes: Philips, Wipro, Bajaj.\nNote: Light fixtures complete with all necessary accessories including PVC Flexible pipes, adopters, connectors etc. as required (Sample shall be approved by the engineer in charge). The installation shall be complete in all respects. 70 Nos
396 18.203 Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required. \n1200mm sweep -5star rated ceiling fan complete with 300mm down rod , canopies, shackles and blades and resistance type regulator working on 230V/240V single phase A/C 397 Nos
397 18.204 SITC of Industrial Type 400mm Sweep Exhaust fan 5 Nos
398 18.205 SITC of LED Aviation Light 1 Nos
399 18.206 Supply installation testing and commissioning of Octagonal Pole made of hot dip galvanised GI sheet 70 mm top diameter, 130 mm bottom diameter thickness 3mm base plate dimensions of 200x200x16 mm suitable for wind speed as per IS 875 Part III double arm bracket 0.5mt including connector foundation bolt 4 no's fixed in existing RCC foundation and junction box etc. complete 8 Meters 6 Each
400 18.207 Supply installation testing and commissioning of Octagonal Pole made of hot dip galvanised GI sheet 70 mm top diameter, 130 mm bottom diameter thickness 3mm base plate dimensions of 200x200x16 mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 no's fixed in existing RCC foundation and junction box etc. complete 8 Meters 18 Each
401 18.208 Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV, and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be separately accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) 30 Each
402 18.209 Supply and installation of Plate Earthing with 1200mmx1200mmx12mm CI plate (conforming to IS:3043-1987) complete with RCC inspection chamber of size 1000x600x500mm with RCC cover, GI class B pipe of 50 mm dia extending up to middle of the plate and clamping to the plate with GI clamps and bolts, funnel having 20G GI wire mesh, identification of earth pit with yellow paint below the chamber cover, mixtures of charcoal around electrode including digging of pit up to permanent moisture level but not less than 3 metre depth and back filling. (value of earth resistance should be less than 1 ohm ). 8 Nos
403 18.21 Supply of UL Listed & CPRI tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating thickness of 250 micron tested as per IEC 62561-2 & is provided with universal clamp made of SS to connect rod with flat conductor. Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested. The above arrangements shall be provided with Heavy duty earth chamber with dimension of 300mmx 300mmx 450mm of 5000kg load bearing capacity to ensure the safety of earthing system including all accessories as required for complete installation as instructed by engineer in charge. 6 Nos
404 18.211 Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling ,including necessary clamps and bolts etc. and all accessories as required for complete installation as instructed by engineer in charge/consultant.\n50x06 Cu strips tinned at the point of contact. 30 Metre
405 18.212 Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling ,including necessary clamps and bolts etc. and all accessories as required for complete installation as instructed by engineer in charge/consultant.\n32x6 Cu strips tinned at the point of contact. 140 Metre
406 18.213 Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling ,including necessary clamps and bolts etc. and all accessories as required for complete installation as instructed by engineer in charge/consultant.\n25x6 Cu strips tinned at the point of contact. 90 Metre
407 18.214 Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling ,including necessary clamps and bolts etc. and all accessories as required for complete installation as instructed by engineer in charge/consultant.\n25x3 Cu strips tinned at the point of contact. 30 Metre
408 18.215 Supply and laying the following sizes of strips on cable tray or wall surface, including necessary clamps (each clamp not exceeding 60 cm) and bolts etc. as required for complete installation as instructed by engineer in charge/consultant.\n50x6 Cu strips tinned at the point of contact. 20 Metre
409 18.216 Supply and laying the following sizes of strips on cable tray or wall surface, including necessary clamps (each clamp not exceeding 60 cm) and bolts etc. as required for complete installation as instructed by engineer in charge/consultant.\n32x6 Cu strips tinned at the point of contact. 195 Metre
410 18.217 Supply and laying the following sizes of strips on cable tray or wall surface, including necessary clamps (each clamp not exceeding 60 cm) and bolts etc. as required for complete installation as instructed by engineer in charge/consultant.\n25x6 Cu strips tinned at the point of contact. 260 Metre
411 18.218 Supply and laying the following sizes of strips on cable tray or wall surface, including necessary clamps (each clamp not exceeding 60 cm) and bolts etc. as required for complete installation as instructed by engineer in charge/consultant.\n25x3 Cu strips tinned at the point of contact. 60 Metre
412 18.219 Supply and laying the following sizes of strips on cable tray or wall surface, including necessary clamps (each clamp not exceeding 60 cm) and bolts etc. as required for complete installation as instructed by engineer in charge/consultant.\n20x3 Cu strips tinned at the point of contact. 1516 Metre
413 18.22 Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. 18 Metre
414 18.221 Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required \n3.15 mm copper conductor ( 10 SWG) 2250 Metre
415 18.222 4 meter air terminal with accessories\nProviding and fixing Air terminals as per IEC -62305 part-3 and IS 2309 16mm rod tapered to 10 mm aluminium rod 3 meter rod:\nMeets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202). Meets the requirement of VDE0185/305(IEC 62305) 101 VL 3000: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. System consist of Fang Fix with base and clamp on the top air terminal is erected. Fang fix clamp made of cable bracket, lightning tested for 100 KA 10/350 micro sec waveform. 2 no's of 16 KG stone of 365 mm diameter, high level of stability. Quick and easy mounting of interception rod using anchors. Concrete, frost-resistant, can be stacked. 6 Set
416 18.223 8mm solid aluminium round conductor:\nsupply and providing 8mm solid aluminium round conductor, meets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202). Meets the requirement of VDE0185/305(IEC 62305) RD 8/ALU: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. \nPolyamide Conductor holder with holding base for parapet/Flat roof:\nWith M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.\nWeather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black @ 1 meter distance.\na) Vertical run- Down conductor 1050 Metre
417 18.224 8mm solid aluminium round conductor:\nsupply and providing 8mm solid aluminium round conductor, meets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202). Meets the requirement of VDE0185/305(IEC 62305) RD 8/ALU: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. \nPolyamide Conductor holder with holding base for parapet/Flat roof:\nWith M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.\nWeather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black @ 1 meter distance.\nb) Horizontal run-Parapet application 1450 Metre
418 18.225 Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) 270 Metre
419 18.226 Providing and fixing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 no's of hexagonal plate. 60 Nos
420 18.227 Providing and fixing of cross universal connector: For T and cross connection, to route vertical down conductor /mesh formation made of hot dipped galvanised iron with necessary screws etc. as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts . 48 Nos
421 18.228 Providing and fixing of expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU. Connectors: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece ). 30 Nos
422 18.229 Providing and fixing of Equipotential bonding rail for outdoor use. 24 Nos
423 18.23 SITC of Lightening counter - To count no of lightening strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6. 1 Nos
424 18.231 Providing and fixing of test joint suitable for 10mm dia copper coated solid steel round conductor with 100 microns of copper bonding (if pure copper conductor 25x3 mm solid tape also can be used) and 8mm dia solid round aluminium conductor made of stainless steel SS 304 grade. Conforms to the requirements according to (IS/IEC 62305).with an outdoor glass-fibre reinforced polycarbonate enclosure having minimum inner dimension of 75mm x 75 mm x 50 mm. 6 Nos
425 18.232 Providing of Plastic Corrosion Protection strip: Approx. 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric. 6 Nos
426 18.233 SITC of CPRI tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 20mm with copper coating thickness of 250micron tested as per IEC 62561-2 & is provided with universal clamp made of SS to connect rod with flat conductor. Earth conductivity enhancing mineral compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested. The above arrangements shall be provided with Heavy duty earth chamber of dimension 300mmx 300mmx 170mm with 5000kg load bearing capacity to ensure the safety of earthing system. 6 Nos
427 18.234 Supply and providing 6 mm thick and 1 m wide electrical grade chequered type rubber mat to withstand 3.3 kV dielectric strength conforming to IS 5429/1969. 90 Sqm
428 18.235 Supply and providing First Aid Box. 2 Nos
429 18.236 SITC of Photoluminesent LT & HT Danger Boards of required sizes (as directed by Engineer in charge) 8 Nos
430 18.237 Supply and providing laminated First Aid chart duly framed and placed in a conspicuous location for clear vision 2 Nos
431 18.238 Supply & fixing Approved Electrical Scheme/ Layouts printed in 6mm thick Transparent Acrylic sheet fixed with suitable SS Studs in walls as directed by Engineer in charge. 10 Nos
432 18.239 Supply and providing 6mm Thick MS chequered plate including cutting, welding, painting etc. as required for cable duct covering etc. 100 Sqm
433 18.24 Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters “FIRE” in black and gold. Cost shall be inclusive of providing MS stand for 2 no's of fire buckets, or , duly painted over a coat of primer. 2 Set
434 18.241 Supply of 1 pair 11 KV rubber hand gloves of approved make. 3 Pair
435 18.242 Supply and providing 12 mm thick and 1 m wide electrical grade chequered type rubber mat to withstand 11 kV dielectric strength conforming to IS 5429/1969 20 Sqm
436 19 FIRE FIGHTING WORKS
437 19.001 MAIN PUMP - ELECTRICAL\nSupply, installation, testing and commissioning of Horizontal End Suction Fire Hydrant Pump Set: Electrical Driven, Capacity: 2280 LPM at 90Mtr Head, conforming to IS 1520, with Bronze Impeller, S. S. Shaft, Mechanical Seal coupled to High Efficient, IE-3 Rated, Squirrel Gauge Induction Electric Motor, 100HP, 3Ph, 3000 RPM, TEFC, complete with all civil works, M.S. foundation, foundation bolts, compound gauge, water re-circulation arrangement, pressure relief valve, anti-vibration mounts, as per requirement, Proper Earthing etc. Works should be Completed as per Technical Specifications, Prevailing Rules, Standards, Requirement and Site Conditions. 1 Set
438 19.002 SPRINKLER PUMP - ELECTRICAL\nSupply, installation, testing and commissioning of Horizontal End Suction Fire Sprinkler Pump Set: Electrical Driven, Capacity: 2280 LPM at 100Mtr Head, conforming to IS 1520, with Bronze Impeller, S. S. Shaft, Mechanical Seal coupled to High Efficient, IE-3 Rated, Squirrel Gauge Induction Electric Motor, 100HP, 3Ph, 3000 RPM, TEFC, complete with all civil works, M.S. foundation, foundation bolts, compound gauge, water re-circulation arrangement, pressure relief valve, anti-vibration mounts, as per requirement, Proper Earthing etc. Works should be Completed as per Technical Specifications, Prevailing Rules, Standards, Requirement and Site Conditions. 1 Set
439 19.003 DIESEL PUMP\nSupply installation testing and commissioning of Stand By/Back Up Fire Pump, Horizontal, End Suction Pump, Engine Driven, suitable for Automatic operation and consisting of the following and complete in all respect as required; Capacity: 2280 LPM at 100Mtr Head conforming to IS 1520, with Bronze Impeller, S. S. Shaft, Mechanical Seal, coupled to High Efficient Radiator Cooled Diesel Engine, 110HP, 1800/2150 RPM, and with Control Panel with Auto Starting Facility, by activation of concerned Pressure Switch and thro. 12V/24 V Electric Starter, Battery with adequate rating and with Battery Charger, Battery Leads, Diesel Tank for 6 hrs operation, exhaust pipe extended up to 2 mtr outside pump house, duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per specification, complete with all civil works, M.S. foundation, foundation bolts, compound gauge, water re-circulation arrangement, pressure relief valve, and all other necessary fixing accessories,Proper Earthing all as per Technical Specifications. 1 Set
440 19.004 EXHAUST PIPES\nSupplying and fixing exhaust gas piping of suitable dia matching the Diesel Fire pump, welded black M.S 'B' class pipe confirming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral Wool/ Rockwool,50 mm thick wire mesh & aluminium cladding etc., as required as per specifications. suitable rain cap for top to avoid rain water entry. The distance between exhaust pipe at top and rain cap should be higher than diameter of pipe. Horizontal run of exhaust piping should slope downwards away from engine to the condensate trap. Silencer should be installed with drain plug at bottom. Fixing shall be done with proper clamps, expansion bolts, and all other acessories as instructed by the Engineer and the rate inclusive of all civil works required, bolts, clamps etc as required for installation. Support to exhaust piping should be done in such a manner that load of exhaust piping is not exerted to engine and the vertical run of the pipes shall be provided with indirect supporting method so that when the pipes are hot and expanded they will be lifted into the supports. Exhaust pipe height shall be 3m more than the top of any adjacent building withing 10m radius of the exhaust. 60 Mtr
441 19.005 JOCKEY PUMP\nSupply, installation, testing and commissioning of Jockey Pump: Electrical Driven, Capacity: 180 LPM at 105 Mtr Head, Vertical Multi Stage Inline Pump with S.S Impeller, Mechanical Seal, and with High Efficient Squirrel Gauge Induction Motor, 7.5HP, 3000 RPM, TEFC, complete with foundation, foundation bolts, anti vibration pad, and all other necessary fixing accessories. The Price for Pump Set shall be inclusive of connected Power and Control Cabling / Wiring work in / thro. heavy duty screwed steel Conduits / Powder Coated M.S. Tray and proper Earthing of Electric Motors, all as per Technical Specifications, Prevailing Rules, Standards, Requirement and Site Conditions. 2 Set
442 19.006 MOTOR CONTROL PANEL\nSupply, fixing, testing and commissioning of Fire Pump Panel for Main Fire Pumps, Sprinkler pump & Jockey Pump, complete as per Technical Specifications and as detailed below. Fabricate, supply, convey, install, testing and commissioning of cubicle type, dust and vermin proof, floor mounted, front operated Control Panel, as per IS: 8623 (with latest amendments) fabricated with 2 mm/14gauge thick CRCA sheet as per approved design and requirement, IP: 54 protection, complete with Main Isolator, Bus Bar Chamber, Volt Meter, Ammeter, Individual Star-Delta Starters for Main & Sprinkler Pumps, DOL Starter for Jockey Pump, Contactors, Auxiliary Contacts, Timers, Indicating Lamps, Fuses, Auto / Manual Selector Switches for all Fire Pumps, Manual On /Off Buttons for Jockey Pump & Manual On Buttons for Main Pumps, all internal wiring etc. The price for Control Panel shall be inclusive of Control Cabling in Steel Conduits for automatic starting of Main Pumps & Automatic start and stop for Jockey Pump and Earthing of the Panel, all as per Technical Specifications, Prevailing Rules, Standards, Requirement and Site Conditions. \n(Detailed Technical Specification Attached) 1 Set
443 19.007 Supply and Laying of below sized XLPE insulated PVC sheathed Aluminium conductor armored cabling to the incoming and outgoing of fire pump panel including necessary termination, glanding, necessary connections etc\n3C x 185 sq mm 60 Meter
444 19.008 Supply and Laying of below sized XLPE insulated PVC sheathed Aluminium conductor armored cabling to the incoming and outgoing of fire pump panel including necessary termination, glanding, necessary connections etc\n3C x 10 sq mm 60 Meter
445 19.009 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 X 185 sq. mm (57mm) 4 Nos
446 19.01 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. \n3 X 10 sq. mm (22mm) 4 Nos
447 19.011 AIR CUSHION VESSEL\nSupplying, Installation, Testing & Commissioning of air cushion tank (air vessel) of continuous welded construction, fabricated out of atleast 8mm thick steel with dished ends, and supporting legs, Capable of carrying 15Bar Pressure, 250mm dia & 1200mm high complete with necessary air release valve, safety valve, pressure gauge, flange connection to the wet riser piping with necessary piping to meet the functional requirement of the system. 1 No
448 19.012 AIR RELEASE VALVE\nSupply, installation, testing and commissioning of Air Release Valve Gunmetal, conforming to IS 903:1993, having rubber ball with sealing seat and with 25mm. BSP threaded male inlet, including necessary accessories and connections. 8 No
449 19.013 PRESSURE GAUGE\nSupply installation testing and commissioning of 4" dia. Pressure Gauge, with ISI Mark or of equivalent International Standards.Weather / Water Proof, Type with gunmetal /brass shut off cock. 5 No
450 19.014 PRESSURE SWITCH\nSupply, installation, testing and commissioning of industrial type pressure switch having 1/4" BSP(F) connection IP:32 enclosure protection, phosphor bronze bellows as sensing element, SDPT contact system, switch rating 6A Inductive/lOA resistive 380 V AC, 0.2A Inductive/10A resistive 250V DC etc. complete as required. 5 No
451 19.015 ALARM CHECK VALVE\nSupply, installation, testing and commissioning of Alarm check valve with CI Body and Clapper, torsion Spring & Nut of Stainless Steel for 6" (150mm Dia) featured with grooved seat alarm port, external by pass, and vertically installed Alarm Check Valve having Working pressure of 175psig, Flow Rate of 3000lit/min, UL Certified, should have the following accessories like Pressure gauages, Pressure Operated switches, Drain Valve, Alarm Test Units, water motor gong, retard chamber inclusive. 1 No
452 19.016 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n250 mm Dia 18 Mtrs
453 19.017 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n200 mm Dia 30 Mtrs
454 19.018 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n150 mm Dia 1330 Mtrs
455 19.019 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n100 mm Dia 252 Mtrs
456 19.02 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n80 mm Dia 177 Mtrs
457 19.021 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n65 mm Dia 431 Mtrs
458 19.022 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n50 mm Dia 702 Mtrs
459 19.023 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n40 mm Dia 1030 Mtrs
460 19.024 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n32 mm Dia 916 Mtrs
461 19.025 ABOVE GROUND PIPING \nSupply, laying, fixing and jointing in position Mild Steel 'C' class Heavy Duty pipes with Screwed Fittings for Pipes up to 50mm dia. and Heavy Duty butt Welded Fittings for pipes above 50mm dia. conforming to IS 1239 / 3589 Part-1 with malleable specials confirming to IS:1239 part-2 such as elbows, bends, couplings, tees, reducers etc. as required including testing hydraulically to 1.5 times the working pressure painting with Two coats of anticorrosive paint and two coats of red enamel paint etc complete with fabricating & fixing MS angle, flats, channels fabricated brackets / supports for supporting the pipes with 10mm 'U' bolts,hitech type brackets for pipes.The Price for 200mm. Suction Line for Fire Pumps shall be inclusive of Puddle Flanges, 600 x 600mm Vortex Plates inside the Water Tanks fabricated from 10mm. M.S. Plate, with approved Paint Protection, all as per Technical Specifications.\n25 mm Dia 3405 Mtrs
462 19.026 Supply, fixing, testing and commissioning of Butterfly Valve, Wafer Type, Maximum Working Pressure 16 Bar, Gear Operated type, confirming to BS:5155 /ASTM A-536, grade 65-45-12, with Supervisory / Tamper Switch, as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n250 mm Dia 2 Nos
463 19.027 Supply, fixing, testing and commissioning of Butterfly Valve, Wafer Type, Maximum Working Pressure 16 Bar, Gear Operated type, confirming to BS:5155 /ASTM A-536, grade 65-45-12, with Supervisory / Tamper Switch, as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n200 mm Dia 2 Nos
464 19.028 Supply, fixing, testing and commissioning of Butterfly Valve, Wafer Type, Maximum Working Pressure 16 Bar, standard lever operated type, confirming to BS:5155 / ASTM A-536, grade 65-45-12, with Supervisory / Micro Switch, as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n150 mm Dia 30 Nos
465 19.029 Supply, fixing, testing and commissioning of Butterfly Valve, Wafer Type, Maximum Working Pressure 16 Bar, standard lever operated type, confirming to BS:5155 / ASTM A-536, grade 65-45-12, with Supervisory / Micro Switch, as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n100 mm Dia 4 Nos
466 19.03 Supply, fixing, testing and commissioning of Butterfly Valve, Wafer Type, Maximum Working Pressure 16 Bar, standard lever operated type, confirming to BS:5155 / ASTM A-536, grade 65-45-12, with Supervisory / Micro Switch, as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n80 mm Dia 11 Nos
467 19.031 Supply, fixing, testing and commissioning of Butterfly Valve, Wafer Type, Maximum Working Pressure 16 Bar, standard lever operated type, confirming to BS:5155 / ASTM A-536, grade 65-45-12, with Supervisory / Micro Switch, as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n65 mm Dia 2 Nos
468 19.032 Supply, fixing, testing and commissioning of Butterfly Valve, Wafer Type, Maximum Working Pressure 16 Bar, standard lever operated type, confirming to BS:5155 / ASTM A-536, grade 65-45-12, with Supervisory / Micro Switch, as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n50 mm Dia 17 Nos
469 19.033 Supply, fixing, testing and commissioning of Non Return Valve, Wafer Swing Check type, PN-16, conforming to IS: 13095 with nuts, bolts etc. complete. \n250 mm Dia 2 Nos
470 19.034 Supply, fixing, testing and commissioning of Non Return Valve, Wafer Swing Check type, PN-16, conforming to IS: 13095 with nuts, bolts etc. complete. \n200 mm Dia 3 Nos
471 19.035 Supply, fixing, testing and commissioning of Non Return Valve, Wafer Swing Check type, PN-16, conforming to IS: 13095 with nuts, bolts etc. complete. \n150 mm Dia 2 Nos
472 19.036 Supply, fixing, testing and commissioning of Non Return Valve, Wafer Swing Check type, PN-16, conforming to IS: 13095 with nuts, bolts etc. complete. \n100 mm Dia 1 Nos
473 19.037 Supply, fixing, testing and commissioning of Non Return Valve, Wafer Swing Check type, PN-16, conforming to IS: 13095 with nuts, bolts etc. complete. \n80 mm Dia 1 No
474 19.038 Supply, fixing, testing and commissioning of Non Return Valve, Wafer Swing Check type, PN-16, conforming to IS: 13095 with nuts, bolts etc. complete. \n50 mm Dia 1 No
475 19.039 Supply, fixing, testing and commissioning of Forged Ball Valve, PN-20 gunmetal /cast alloy, including necessary accessories and connections.\na) 25 mm Dia 39 Nos
476 19.04 Supply, fixing, testing and commissioning of Forged Ball Valve, PN-20 gunmetal /cast alloy, including necessary accessories and connections.\nb) 50 mm Dia 3 Nos
477 19.041 Supply, Laying, fixing, pressure testing and commissioning of Underground Fire Hydrant Pipe Work with Heavy Duty (Class-C) Mild Steel Pipes, confirming to IS: 3589/1239 Part - I (wherever applicable) and with Heavy Duty Black Ductile Iron Screwed Fittings for Pipes up to 50mm. dia. and But Welded Fittings, for pipes above 50mm. dia. confirming to IS:1239 Part - II, such as tees, elbows, reducers, check nuts, unions, flanges, nipples and neoprene gasket, bolts, nuts, washers etc. including cutting, threading, welding, joining, laying in trenches, providing thrust blocks, providing higher sizes of Protective Sleeve / Pipes and RCC encasement, all as per requirement and to the approval of Engineer - in - Charge /Consultant. The total pipe work shall be protected with approved painting systems and bitumen based flexible wrapping, all as per Technical Specifications\na) 150 mm Dia 650 Mtrs
478 19.042 Supply, Laying, fixing, pressure testing and commissioning of Underground Fire Hydrant Pipe Work with Heavy Duty (Class-C) Mild Steel Pipes, confirming to IS: 3589/1239 Part - I (wherever applicable) and with Heavy Duty Black Ductile Iron Screwed Fittings for Pipes up to 50mm. dia. and But Welded Fittings, for pipes above 50mm. dia. confirming to IS:1239 Part - II, such as tees, elbows, reducers, check nuts, unions, flanges, nipples and neoprene gasket, bolts, nuts, washers etc. including cutting, threading, welding, joining, laying in trenches, providing thrust blocks, providing higher sizes of Protective Sleeve / Pipes and RCC encasement, all as per requirement and to the approval of Engineer - in - Charge /Consultant. The total pipe work shall be protected with approved painting systems and bitumen based flexible wrapping, all as per Technical Specifications\nb) 100 mm Dia 20 Mtrs
479 19.043 Supply, Laying, fixing, pressure testing and commissioning of Underground Fire Hydrant Pipe Work with Heavy Duty (Class-C) Mild Steel Pipes, confirming to IS: 3589/1239 Part - I (wherever applicable) and with Heavy Duty Black Ductile Iron Screwed Fittings for Pipes up to 50mm. dia. and But Welded Fittings, for pipes above 50mm. dia. confirming to IS:1239 Part - II, such as tees, elbows, reducers, check nuts, unions, flanges, nipples and neoprene gasket, bolts, nuts, washers etc. including cutting, threading, welding, joining, laying in trenches, providing thrust blocks, providing higher sizes of Protective Sleeve / Pipes and RCC encasement, all as per requirement and to the approval of Engineer - in - Charge /Consultant. The total pipe work shall be protected with approved painting systems and bitumen based flexible wrapping, all as per Technical Specifications\nc) 80 mm Dia 190 Mtrs
480 19.044 Supply, installation, testing and commissioning of Fire Hydrant Valve, bearing to ISI:5290 Type-A mark, Stainless Steel-304 body with 63mm. oblique instantaneous single outlet, 75mm. N.B. flanged inlet, Stainless Steel -304 spindle, complete with PVC blank cap, G.I. chain etc. 46 Nos
481 19.045 Supply, installation, testing and commissioning of Branch Pipe, Stainless Steel-304, short type, with 63mm. male instantaneous inlet, male threaded outlet, fitted with 16mm. bore nozzle, having IS: 903 mark. 46 Nos
482 19.046 Supply, installation, testing and commissioning of Fire Hose, RRL hose jacketed with circular woven synthetic fiber. conforming to IS: 636:88, with Working Pressure 14 Kg/Cm2, Proof Pressure 22 Kg/Cm2 and Burst Pressure 38 Kg/Cm2. The Fire Hose shall be with IS: 636 Type-A marking and 63mm. dia.x15Mtr.long with pair of 63mm. male and female instantaneous couplings, Stainless steel-304, having IS: 903 mark and duly S. S. wire wounded. 92 Nos
483 19.047 Supply, installation, testing and commissioning of Manual Swing Type Fire Hose Reel Complete Set with heavy duty drum / reel, 19mm. dia. x 30Mtr. long 2-ply polyester yarn braided /rubber braided pressure hose, Red Coloured, heavy duty nylon on/off jet/spray nozzle, 22mm. isolating valve and all other necessary fixing accessories including Fabrication and Erection of M.S. Support, as per requirement, for Fixing the Fire Hose Reel Set. 26 Nos
484 19.048 Supply, installation, testing and commissioning of M.S. CRCA sheet fabricated 16 SWG Fire Hydrant hose boxes suitable for storing 2 Nos.15M hoses and 1 No. Branch pipe of 63mm dia size. Boxes will be duly painted with two coats zinc primer and finish fire red colour enamel paint outside with locking arrangement for Double leaf front glass doors having 4mm thick glass, complete as per specifications. 24 Nos
485 19.049 Supply and fix at site in position Weather Proof Fire Hose Cabinet, wall / pole mounting type, 30” x 24” x 10” size, to accommodate Two 15m length of delivery hose and branch pipe, acrylic fronted double door with lock 2 keys and a break glass recess for keys, painted Fire Red. The price shall be inclusive of fixing accessories and pole for mounting, all as per requirement. 22 Nos
486 19.05 Supply, installation, testing and commissioning of Fire Brigade Inlet Breeching, C.I. body, having 4 Gunmetal, 63mm. male instantaneous inlet, conforming to IS: 903, with non return valves, 25mm. drain valve, flanged outlet, 4 nos. of rubber blank caps and G.I. chains. 2 No
487 19.051 Supply, installation, testing and commissioning of Fire Brigade Draw Off Outlet C.I. body, having 4 Gunmetal, 63mm. female instantaneous inlet, conforming to IS: 903, with non return valves, 25mm. drain valve, flanged outlet, 4 nos. of rubber blank caps and G.I. chains. 1 No
488 19.052 Providing, fixing, testing and commissioning of Standard Coverage , Quick Response Automatic Fire Sprinkler, K- Factor: 5.6 (80 Metric) or equal to the approval of system consultant / engineer - in - charge, with necessary accessories and fittings.\nPendant Type, 68 / 79 Degree C Rating 1352 Nos
489 19.053 Providing, fixing, testing and commissioning of Standard Coverage , Quick Response Automatic Fire Sprinkler, K- Factor: 5.6 (80 Metric) or equal to the approval of system consultant / engineer - in - charge, with necessary accessories and fittings.\nPendant Type, 93 Degree C Rating 40 Nos
490 19.054 Providing, fixing, testing and commissioning of Standard Coverage , Quick Response Automatic Fire Sprinkler, K- Factor: 5.6 (80 Metric) or equal to the approval of system consultant / engineer - in - charge, with necessary accessories and fittings.\nUpright Type, 68 Degree C Rating. 1327 Nos
491 19.055 ROSETTE PLATE - Providing & Fixing 2 Piece Chrome Plated Friction Fit recessed escutcheon for pendant sprinklers, as per requirement. 1227 Nos
492 19.056 Providing, Fixing, Testing and Commission Flexible Sprinkler Hose; UL Listed, FM Approved, 25mm. (1") BSP Male Inlet, 15mm. (1/2") NPT Female Outlet, Braided, Working Pressure 13.8 Bar, length: 1500 mm, and with all connecting systems and accessories. 1227 Nos
493 19.057 Providing, fixing, testing and commissioning of SLUICE VALVE with Body Ductile Iron, Disc:Ductile Iron+EPDM, PN-20, TYPE: RISING STEM SS304, Sealing Kits:Graphite, Handy Wheel: Round Plate Epoxy Coated, Ends: Flanged Ends to ANSI as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n250 mm 3 Nos
494 19.058 Providing, fixing, testing and commissioning of SLUICE VALVE with Body Ductile Iron, Disc:Ductile Iron+EPDM, PN-20, TYPE: RISING STEM SS304, Sealing Kits:Graphite, Handy Wheel: Round Plate Epoxy Coated, Ends: Flanged Ends to ANSI as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n200 mm 1 Nos
495 19.059 Providing, fixing, testing and commissioning of SLUICE VALVE with Body Ductile Iron, Disc:Ductile Iron+EPDM, PN-20, TYPE: RISING STEM SS304, Sealing Kits:Graphite, Handy Wheel: Round Plate Epoxy Coated, Ends: Flanged Ends to ANSI as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n150 mm 6 Nos
496 19.06 Providing, fixing, testing and commissioning of SLUICE VALVE with Body Ductile Iron, Disc:Ductile Iron+EPDM, PN-20, TYPE: RISING STEM SS304, Sealing Kits:Graphite, Handy Wheel: Round Plate Epoxy Coated, Ends: Flanged Ends to ANSI as per Technical Specifications and with required matching Flanges, nuts, bolts etc. complete. \n80 mm 5 Nos
497 19.061 Excavation for cable trenches in soft soil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres. 560 Cum
498 19.062 10 Loop Fire Alarm Control Panel - \nSupply, installation, testing and commissioning of 32 Bit Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 event plus 1000 alarm log history events, QWERTY keypad/Soft programming. The panel should be equipped with Loop Cards considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 200 analog addressable devices with minimum 125 detectors (as per design). The panel shall work in degrade mode to give a general alarm even in case of CPU failure .FACP shall have Four access levels, flash EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. The FACP shall be provided with Modbus/Bacnet for integrating to Building Management System. All the FACPs shall be networked over RS485 or propreitory protocol with minimum network speed of 256 kbps on Copper wire communication. The complete FACP and all accessories including peripheral devices shall be UL Listed and FM approved. Provision for FACP integrated with alarm handling, SMS/EMail facility etc.... 1 Nos
499 19.063 Supply, installation, testing and commissioning of active repeater panel. It shall be powered from the Main FACP & shall be supplied with necessary interface cards for connecting to FACP. The Panel shall have minimum 2 x 40 characters back lit LCD display with necessory battery backup for 48 hrs operation. The panel shall be UL listed and FM approved. 1 Nos
500 19.064 Addressable Manual Call Point (Pull down / Break Glass Type). Addressing shall be with user friendly Rotary and dip switch/electronically addressable. The MCP shall be UL Listed and FM Approved 41 Nos
501 19.065 SITC of Addressable Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 2% obs/ft.The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall adapt to its environment by utilizing a built-in microprocessor to determine its environment and choose the appropriate sensing settings for early detection and reduction in false alarm. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal/dip switch/Electronically Addressable. The detector shall be UL Listed and FM Approved.\n(a) Above ceiling 425 Nos
502 19.066 SITC of Addressable Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 2% obs/ft.The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall adapt to its environment by utilizing a built-in microprocessor to determine its environment and choose the appropriate sensing settings for early detection and reduction in false alarm. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal/dip switch/Electronically Addressable. The detector shall be UL Listed and FM Approved.\n(b) Below ceiling 613 Nos
503 19.067 SITC of Addressable Rate of Rise Heat Detector rated at 9.4 deg C/min. The detector shall have LED for 360 deg viewing. Addressing shall be with user friendly Rotary and dip switch/electronically addressables.The detector shall be UL Listed and FM Approved. 5 Nos
504 19.068 SITC of Addressable Sounder cum Strobe rated at 75 dBA @ 3m for Audible annunciation and 75cd flashintg at 1 Hz for visual indication. The sounder shall be UL Listed and FM approved. 32 Nos
505 19.069 SITC of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes. The control module shall provide DPDTcontact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal/Dip switches/Electronically Addressable. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The Module shall be UL Listed and FM Approved. 32 Nos
506 19.07 SITC of Addressable Relay Module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs. The relay module shall provide DPDT contact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal/DIP switches/Electronically Addressable. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The Module shall be UL Listed and FM Approved. 25 Nos
507 19.071 SITC of Addressable Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall provide DPDTcontact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal/DIP switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The Module shall be UL Listed and FM Approved. 32 Nos
508 19.072 SITC of Addressable Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The Module shall be UL Listed and FM Approved. 62 Nos
509 19.073 Providing, fixing, test and commission External Power Supply Unit, 24V, 5Amps. DC, with 7Ah. Battery Back up, for sounders, sounder bases, Strobes etc, as detailed in the technical specifications. 12 Nos
510 19.074 Providing, fixing / laying, test and commission 2Core x 1.5 mm2 FRLS Armored Cables with Red Colour, as per requirement and Technical Specifications. 14460 Mtrs
511 19.075 Providing, Fixing, testing and commissioning of Flow Switch, Vane type, IP 65 Protection with above 20 Bar Working Pressure Protection with all necessary accessories, for monitoring Fire Sprinkler System. The control cabling from flow switches to Fire Sprinkler Annunciating Panel shall be measured separately. 24 Nos
512 19.076 Providing, fixing, test and commissiong of 24 Zone Simplex type talk back master control Console having zone wise selection in powder coated 16 swg CRCA sheet housing, complete with 8 to 64 zone expandable system, AC and DC meter to measure supply, push to talk facility by call/call back facilities and Mike LED display unit for location display, in built batter charger and battery space along with Amplifier, 500 W RMS Output including necessary control wires, jack ets as per specification and required. 1 Set.
513 19.077 Providing, fixing, testing and commissioning of 6 Watt Wall Mounted type Talk Back System Speaker with Call Switch, in suitable and approved housing to approved colour /shade, all as per specification.\n 24 Nos.
514 19.078 Providing, fixing, laying, test and commissioning 2Core x 1.5 mm2 FRLS Armoured Cables, as per Technical Specifications. 1840 Mtr.
515 19.079 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(a) Fire Lift sign board (12" x 4") 18 Nos
516 19.08 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(b) Passenger/Fire Lift sign board (12" x 4") 36 Nos
517 19.081 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(c) Fire Duct sign board (12" x 4") 27 Nos
518 19.082 (d) SITC of Fire Exit Light, Laser type, with High Glow LED, size: 12” x 6” Size, Ceiling Mounting type with hanging clamps, on/off switch, Red/ Green Colour option, min power consumption & with 2 Hr. battery backup. 18 Nos
519 19.083 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(e) Electrical Duct sign board (12" x 4") 27 Nos
520 19.084 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(f) Main Staircase sign board (12" x 4") 9 Nos
521 19.085 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(g) Fire Staircase sign board (12" x 4") 18 Nos
522 19.086 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(h) Floor Display sign board (12" x 4") 27 Nos
523 19.087 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(i) Fire Assembly Point (16" x 16") 1 No
524 19.088 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(j) Pump Room sign board (12" x 4") 1 No
525 19.089 Supply and install in position Sign Boards made out of 3mm thick "Opaque" PVC foam board with computer cut, self adhesive vinyl painted foam board in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes and mounting height of the board shall be as per technical specification, complete with mirror fasteners.\n(k) Fire Control Room sign board (12" x 4") 1 Nos
526 19.09 Supply, installation, testing & commissioning of Portable Fire Extinguisher as per BIS 2190 and IS: 15683:2018 and with relevant ISI Stamping/Marking. ABC Dry Chemical Store Pressure Type - 4 Kg. 88 Nos
527 19.091 Supply, installation, testing & commissioning of Clean Agent Modular Type Fire Extinguisher 5Kgs Capacity made of Mild Steel Body of 1.6 mm thickness with pressure gauge, refillable device and safety release device CE Certified Brass valve suitable for A, B and C Classes of Fire complete with charge of HFC Blend A, It is a blend of Hydro Fluoro Carbon and organic detossificant essence P26. The sprikler body will comprise of temperature sencitive quartsoid bulb of temperature rating of 68 deg C. The cylinder will be supplied with a proper mounting arrangement to mount it on the ceiling. Fire Extinguisher manufatured as per BIS 2190 and IS: 15683:2018 and with relevant ISI Stamping/Marking. 20 Nos
528 19.092 Providing and fixing 48mm thick fire resistant door for 120 minutes fire rating conforming to BS476 Part-22 & IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-in-charge, made out of 1.2mm thick galanized steel sheets, double skin door shell with suitable mounting on door frame, The door frames are manufactured from 1.6mm thick galvanised steel sheet (zinc coating not less than 120 gsm/m2) sandwiching with FR insulation material in between, formed to double rebate profile of minimum size 143mmx60mm (+/-0.3mm). The frame shall have GI Anchor fastners of suitable size for fixing in the opening along with factory made template for SS Ball Bearing Hinges for fixing the fire rated shutters/doors. The door frames and doors shutter shall be powder coated with approved fire ressistant paint & Primers etc... all complete as per direction of Engineer-in-charge. 120 sqm.
529 19.093 Providing and fixing fire vision panel of requierd size with clear, toughened, interlayered, non-wired, 120minutes fire ressistant glass panes of 5mm thick on sides of the door shutters including GI U beading & Ceramic tape as required 1.5 sqm.
530 19.094 Providing and fixing SS Door Closure on the fire door shutters as required 32 Nos
531 19.095 Providing & fixing Dead Lock with 70mm cylinder on fire door shutters as required. 16 Nos
532 19.096 Providing & fixing of SS Pull Handle of 300mm in size. 32 Nos
533 19.097 Providing and fixing panic bar-Single Leaf, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete. 2 Nos.
534 19.098 Providing and fixing panic bar-Double Leaf, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete. 14 Nos.
535 19.099 Supply and Fixing of load bearing Fire stop mortar CP636 or equivalent system with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, for openings in floors or slabs after passing service lines. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. The product shall be age tested as per Dafstb and DIBT standards. The product shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96 and shall have a VOC content of approx. <1 g/l as per LEED 2009. Firestop installation should be done by trained applicators and in accordance with manufacturer's guidelines by providing 10mm dia rebars at 200mm c/c both ways with chemical anchoring along the length and breadh of the shaft and provide 2 layers of chicken mesh etc.,as the base for fire mortar at 65mm thickness having load bearing capacity of 200kg/sq.mtr, For shaft size more than 0.64 sqmtr proper engineering judgement needs to be submitted through the manufacturer. Applicator needs to submit complete installation report for inspection purpose. 65 Sqm
536 19.1 Providing a intumescent, flexible firestop wrap strip CP 648 E for plastic pipe, insulated pipe and various non-metalic penetrations from 2" to 6" diameter. Can be used with orthogonal pipes and pipes at 45°. It is mold and mildew resistant and the performance is Class 0 according ASTM G21-96 and EN ISO 846. Highly intumescent with an expansion temperature (intumescent activation) of 320 °F (160°C) and the expansion ratio up to 1:40. FBC System Compatible. The product shall meet LEED requirements for indoor environmental quality credit (4.1 and 4.2) with a VOC content of 3.1 g/l. Firestop installation should be done by trained applicators and in accordance with Manufacturer guidelines. Applicator needs to provide complete installation report for inspection purpose\nPlastic Pipe diameter of 2.5'' (CP 648-E Firestop Wrap), Min. recommended hole dia. in wall/floor: 92 mm. 54 Nos
537 19.101 Providing a intumescent, flexible firestop wrap strip CP 648 E for plastic pipe, insulated pipe and various non-metalic penetrations from 2" to 6" diameter. Can be used with orthogonal pipes and pipes at 45°. It is mold and mildew resistant and the performance is Class 0 according ASTM G21-96 and EN ISO 846. Highly intumescent with an expansion temperature (intumescent activation) of 320 °F (160°C) and the expansion ratio up to 1:40. FBC System Compatible. The product shall meet LEED requirements for indoor environmental quality credit (4.1 and 4.2) with a VOC content of 3.1 g/l. Firestop installation should be done by trained applicators and in accordance with Manufacturer guidelines. Applicator needs to provide complete installation report for inspection purpose\nPlastic Pipe diameter of 3'' (CP 648-E Firestop Wrap), Min. recommended hole dia. in wall/floor: 112 mm. 27 Nos
538 19.102 HVAC Ducts: Providing Acrylic Firestop Sealant Hilti CP 606 in gaps between periphery of the ducts to provide minimum 2 hours fire rating when subject to the test conditions of UL 2079 standards. The product shall be age tested as per DafStb guidelines. Sealant should provide sufficient MAF, water and gas tight seal. Sealant shall also provide airborne sound transmission reduction (STC of 50) and shall be tested as per DIN 52210 for sound insulation. Sealant shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96 and should have a VOC content of approx. 75 g/l as per LEED 2009. The sealant shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. The product shall be UL listed & classified and shall bear the UL and FM approval logo on the packing. Firestop installation should be done by trained applicator and in accordance with Manufacturer guidelines. Applicator needs to provide complete installation report for inspection purpose. 3 Sqm
539 19.103 Providing expanding firestop foam CP 620, with minimum 2 hours fire rating when tested in accordance with UL 1479, for horizontal openings in floors or slabs after passing service lines like cable trays or cables/cable bundles. The expanding foam expands seven times its volume to fill the cavity at the time of dispensing the material and shall fully cure within two minutes after dispensing. The product shall be age tested as per Dafstb and DIBT standards. The product shall provide water tightness when tested for W rating as per UL standards and shall carry test certificate for sound insualtion of 50 db when tested in accordance with ASTM E 90. The product shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96 and shall have a VOC content of approx. 1.3 g/l as per LEED 2009. The product shall be tested in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. The product shall be UL listed & classified and shall bear the UL and FM approval logo on the packing.Firestop installation should be done by trained applicators and in accordance with Manufacturer guidelines. Applicator needs to submit complete installation report for inspection purpose. 2.5 Sqm
540 19.104 SITC of 8 zone IP based, digital Voice Alarm controller expandable upto 128 zones. The voice alarm controller shall support multi channel audio and shall be able to connect directly over Ethernet (no other protocol accepted). It shall be having in-built memory of minimum 500 Mb and shall be able to broadcast the messages to any zone in the network as per the configuration. It should have functions like the audio playing, zone control, fault monitoring, log recording, volume control and amplifier switchover. It shall include PTT microphone for emergency manual announcements. The voice alarm controller shall be integrated with addressable fire alarm system for zone wise evacuation at the event of an emergency. The Voice alarm controller should also have the following functions:\n . 255 Priorities\n . Time schedule broadcasts\n . Capable of amplifier redundancy\n . 8 trigger inputs/outputs\n . Hospital codes (Code Blue/Red/Pink/White etc) broadcasting (customizable as per customer). PA System Management software with one server & client licence. It should connect with upto minimum 20 controllers. Administrator can decide No. of users and define user authorities freely. It Can display all equipment status and indicate fault alarm location. It Can record and read history operation and fault logs. It Support Text-to-Speech (TTS) function. It shall support uploading of floor maps for effective management with broadcast details etc. Audio files stored on the server can be played in any zone on the system network. 1 Each
541 19.105 SITC of TCP/IP based Networkable 7" touch screen paging station for selection of zones, supervision of system status, setting of scheduled broadcasts with the following functions:\n. Built-in monitoring loudspeaker\n. Detachable goose-neck microphone\n. LCD touchscreen display\n. Audio input 2 Each
542 19.106 SITC of 480 W Power Amplifier Speaker Output 4~16O Low-Z output, 480W,70V(10.7O), 100V (21.7O) Frequency response of 60 Hz~15 kHz ( ± 3 dB ), S/N >80dB, Protection like - AC Fuse × 15 A AC FUSE×1, Current limiter, short circuit and thermal protection circuits. It should have D/A converter and all accessories required. 4 Each
543 19.107 SITC of Metal Grille 6W Ceiling Speaker with max SPL 1M/1W 96dB . Frequency response of 80Hz-20KHz with a dispersion angle of 160 deg. The speaker should have tappings at 6W/3W/1.5W 194 Nos
544 19.108 SITC of 6W Wall mount Box Speaker with max SPL 1M/1W 96dB . Frequency response of 160Hz-20KHz. The speaker shoud have tappings at 6W/3W 39 Nos
545 19.109 Speaker Cable - Supplying and drawing of 2 Core x 1.5sq.mm flexible Unarmored Speaker cable for speakers through existing PVC conduit with all acessories as required for complete installation and as instructed by engineer in charge/ consultant and making good all damages made for installation. 6660 Metre
546 20 EXTRA LOW VOLTAGE WORKS
547 20.001 Supplying and drawn of UTP 4 pair CAT-6 LAN cable in the existing surface/recessed steel/PVC conduit as required - \n1 run of Cable 16435 Meter
548 20.002 Supplying and drawn of UTP 4 pair CAT-6A LAN cable in the existing surface/recessed steel/PVC conduit as required - \n1 run of Cable 780 Meter
549 20.003 Supplying, fixing testing & commissioning of CAT-6 information oultets and accessories on wall surface/recess etc complete as required. 234 Each
550 20.004 Supplying, fixing testing & commissioning of CAT-6A information oultets and accessories on wall surface/recess etc complete as required. 15 Each
551 20.005 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. \nTelephone socket outlet 80 Nos
552 20.006 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. \n1 or 2 Module (75mmX75mm) 329 Nos
553 20.007 Supplying and fixing of CAT-6 24 port Front Managable Straight Loaded Patch panels 22 Each
554 20.008 Supplying and fixing of CAT-6A 24 port Front Managable Straight Loaded Patch panels 3 Each
555 20.009 Providing and fixing 1 or 2 metre long CAT-6 UTP Patch Cords 234 Each
556 20.01 Providing and fixing 1 or 2 metre long CAT-6A UTP Patch Cords 15 Each
557 20.011 SITC of 42U Wall Mount Rack with power distribution unit, cable managers, fans and other accessories. 1 Each
558 20.012 SITC of 15U Wall Mount Rack with power distribution unit, cable managers, fans and other accessories. 6 Each
559 20.013 SITC of 09U Wall Mount Rack with power distribution unit, cable managers, fans and other accessories. 8 Each
560 20.014 Supply, installation and testing commissioning of Fully Managed 24 Port CAT 6 Network Switch with minimum of 2 SFP Uplink 15 Nos
561 20.015 Supply, installation and testing commissioning of Fully Managed 08 Port CAT 6 Network Switch with minimum of 2 SFP Uplink 2 Nos
562 20.016 Supply, installation and testing commissioning of Fully Managed 24 Port 10GBASE CAT 6A Network Switch with minimum of 2x10G SFP Uplink 2 Nos
563 20.017 Supply Installation Testing & Commissioning of Managed 24 Port Giga PoE intelligent Ethernet Switch with 370Watt PoE Power at 24 x 10/100/1000 Base-T PoE Fast Ethernet ports and with min 2SFP Giga Ports (provision for Fiber Giga connectivity) 4 Nos
564 20.018 Supply Installation Testing & Commissioning of Managed 08 Port Giga PoE Intelligent Ethernet Switch with minimum of 75Watt PoE Power at 8 x 10/100/1000 Base-T PoE Fast Ethernet ports and with min 1SFP Giga Ports (provision for Fiber Giga connectivity) 8 Nos
565 20.019 SITC of Fully Managable & Stackable, Layer-3 switching compactible 24 port Gigabit Ethernet Core Switch delivers 24 Hot Swappable SFP Gigabit interfaces for fibre connectivity with 10/100/1000 SFP Switch With 2 nos 10G base-T ports and 2*SFP 1 Nos
566 20.02 SITC 10G SFP Module for Access Switches 2 Nos
567 20.021 SITC 1G SFP Module for Access Switches 29 Nos
568 20.022 SITC of 1Mtr DAC Cables 20 Nos
569 20.023 SITC of POE Based Wireless-N Access Point 10 Nos
570 20.024 Supply & Laying of 06 core unarmoured Multimode Optical Fibre Cable. 1330 Metre
571 20.025 Supply fixing splicing Termination & commissioning of 06 Port Fully loaded LIU Rack mountable (with Pigtail) including all the accessories like, LC duplex for 6mm fibre cassette for pigtails, blanking plate for modular drawer etc... as required for the proper functioning of the system. 14 Nos
572 20.026 Supply fixing splicing Termination & commissioning of High Density 96 Core Fully loaded LIU Rack mountable (with Pigtail) including all the accessories like, LC duplex for 6mm fibre cassette for pigtails, blanking plate for modular drawer etc... as required for the proper functioning of the system. 1 Nos
573 20.027 SITC of LC-LC Patch Cord 60 Nos
574 20.028 Supply, installation, testing & commissioning of IPABX Equipped with below configuration. \n• 100 Analogue extension & 8 Digital extension, expandable up to 128 lines. \n• PRI interface & rack mountable\n• 4 port welcome message and Auto Attendant up 4 level, Linux Based & support XML Applications.\n• Minimum 8 Nos IP/SIP Extension number\n• Operator console (24 key KTS +DSS) \nIncludes all the accessories like Connectors, Wall/Floor Mounted Racks, Cables & Jumper Wires for connectivity etc.... for its proper functioning of the system and as directed by the Engineer in charge. 1 Nos
575 20.029 Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. \n2 Pair 5830 Meter
576 20.03 SITC of 10 Pair (0.5mm) Armoured Telephone cable 510 Metre
577 20.031 SITC of 20 Pair (0.5mm) Armoured Telephone cable 530 Metre
578 20.032 SITC of 100 Pair (0.5mm) Armoured Telephone cable 20 Metre
579 20.033 SITC of IP Telephone 2 Nos
580 20.034 SITC of Analogue Telephone 80 Nos
581 20.035 SITC of 20Pair Telephone Krone Module in MS Powder Coated Enclsoure with lockable arrangement 4 Nos
582 20.036 SITC of 10Pair Telephone Krone Module in MS Powder Coated Enclsoure with lockable arrangement 5 Nos
583 20.037 SITC of 120Pair Telephone Krone Module in MS Powder Coated Enclsoure with lockable arrangement 1 Nos
584 20.038 Supply, Installation, Testing Commissioning of 2MP IR Bullet camera (Detailed Technical Specification Attached) 12 Nos
585 20.039 Supply, Installation, Testing Commissioning of 2MP IR Dome camera (Detailed Technical Specification Attached) 46 Nos
586 20.04 Supply, Installation, Testing Commissioning of 32 Channel NVR (Detailed Technical Specification Attached) 2 Nos
587 20.041 Supply, Installation, Testing Commissioning of Workstation (Detailed Technical Specification Attached) 1 Nos
588 20.042 Supply, installation, Testing and Commissioing of 40'' Flat Screen HD Professional LED(24X7) with Interfaces include HDMI, DVI, D-sub, Component and Composite input as well as RS-232C and RJ45 for extensive connectivity, remote control and wall mount unit / floor stand complete with making connections etc complete as reqd. 2 Nos
589 20.043 SITC of 6TB Survillance Hard Disk Drive. 6 Nos
590 21 LIFT WORKS
591 21.001 LIFT-1,3,4,5\nDesign, manufacture, supply, installation at site, testing, commissioning and maintain (during guarantee period of 36 months from the date of commissioning) Passenger cum Bed Lift to carry 26 (Twenty Six) persons capacity of load 1768 Kgs with a minimum speed of 1.5 metre per second as per the detailed specification attached including all necessary safety features and in accordance with theparticulars of lift service requirement and technical specifications etc. complete.\n8 Stops and 8 openings. \n(Shaft Size available - 3500 mm x 2500 mm)\nNote :The rate shall include obtaining necessary initial and final approval from Kerala State electrical Inspectorate for lift installation and operation before handing over the entire lift installation. 4 Nos
592 21.002 LIFT-2 & 6\nDesign, manufacture, supply, installation at site, testing, Commissioning and maintain (during guarantee period of 36 months from the date of commissioning) Goods cum Bed Lift of 2Ton capacity with a minimum speed of 1.0 metre per second and as per the detailed specification attached including all necessary safety features and in accordance with the particulars of lift service requirement and technical specifications etc. complete. \n8 Stops and 8 openings. \n(Shaft Size available - 3500 mmx 2500 mm)\nNote :The rate shall include obtaining necessary initial and final approval from Kerala State electrical Inspectorate for lift installation and operation before handing over the entire lift installation 2 Nos
593 22 MEDICAL GAS PIPELINE SYSTEM
594 22.001 SITC of Oxygen Manifold - 2 banks x 10 cylinders 1 Set
595 22.002 SITC of Fully Automatic Oxygen Control Panel with minimum flow rate of 1500 LPM 1 Set
596 22.003 SITC of Emergency Oxygen Manifold - 2 banks x 5cylinders 1 Set
597 22.004 SITC of Oxygen Flowmeters with humidifier bottle 189 Nos
598 22.005 SITC of Nitrous Oxide Manifold - 2 banks x 1 cylinders 1 Set
599 22.006 SITC of Fully automatic Gas Control Panel for Nitrous Oxide with a minimum flow rate of 500 LPM 1 Set
600 22.007 SITC of Emergency Nitrous Oxide Manifold - 1 bank x 1 cylinders 1 Set
601 22.008 SITC of Carbon Dioxide Manifold - 2 banks x 1 cylinders 1 Set
602 22.009 SITC of Fully automatic Gas Control Panel for Carbon Di Oxide with minimum flow rate of 300 LPM 1 Set
603 22.01 SITC of Emergency Carbon Dioxide Manifold - 1 bank x 1cylinders 1 Set
604 22.011 SITC of Compressed air plant system having minimum free air delivery of 1500 LPM with complete accessories as mentioned in technical specifications. 1 Each
605 22.012 SITC of vacuum plant system having minimum free air aspirated of 2500 LPM at 450 mmHg with complete accessories as mentioned in technical specifications. 1 Each
606 22.013 SITC of Ward Vacuum Units 178 No.
607 22.014 SITC of Theatre Vacuum Units 11 No.
608 22.015 SITC of Electrical Panel for Air Compressor & Vacuum Pump 1 No.
609 22.016 SITC of ICU Terminal Units - Imported - O2 114 No
610 22.017 SITC of ICU Terminal Units - Imported - Air 57 No
611 22.018 SITC of ICU Terminal Units - Imported - VAC 112 No
612 22.019 SITC of Ward Terminal Units - Indigenous - O2 115 No
613 22.02 SITC of Ward Terminal Units - Indigenous - N2O 2 No
614 22.021 SITC of Ward Terminal Units - Indigenous - Air 2 No
615 22.022 SITC of Ward Terminal Units - Indigenous - Air 7 bar 2 No
616 22.023 SITC of Ward Terminal Units - Indigenous - Vac 115 No
617 22.024 SITC of Matching Probe - O2 229 No
618 22.025 SITC of Matching Probe - N2O 2 No
619 22.026 SITC of Matching Probe - Air 59 No
620 22.027 SITC of Matching Probe - Air 7 bar 2 No
621 22.028 SITC of Matching Probe - VAC 227 No
622 22.029 SITC of Master Plant Alarm Panel (post source), BMS compatible, 1 No
623 22.03 SITC of Area Valve Service Units with Alarm Systems - 6 Services 11 No.
624 22.031 SITC of Area Valve Service Units with Alarm Systems - 4 Services 9 No.
625 22.032 SITC of Area Valve Service Units with Alarm Systems - 3 Services 1 No.
626 22.033 SITC of Area Valve Service Units with Alarm Systems - 2 Services 7 No.
627 22.034 SITC of Copper pipe - per mtr. - 12mm 1090 Mtrs
628 22.035 SITC of Copper pipe - per mtr. - 15mm 2003 Mtrs
629 22.036 SITC of Copper pipe - per mtr. - 22mm 2420 Mtrs
630 22.037 SITC of Copper pipe - per mtr. - 28mm 857 Mtrs
631 22.038 SITC of Copper pipe - per mtr. - 35mm 275 Mtrs
632 22.039 SITC of Copper pipe - per mtr. - 42mm 68 Mtrs
633 22.04 SITC of Copper pipe - per mtr. - 54mm 160 Mtrs
634 22.041 SITC of Copper pipe - per mtr. - 76mm 83 Mtrs
635 22.042 SITC of Copper pipe - per mtr. - 108mm 1 Mtrs
636 22.043 SITC of Ball Valves - 15mm 16 No.
637 22.044 SITC of Ball Valves - 22mm 13 No.
638 22.045 SITC of Ball Valves - 28mm 7 No.
639 22.046 SITC of Ball Valves - 35mm 9 No.
640 22.047 SITC of Ball Valves - 42mm 2 No.
641 22.048 SITC of Ball Valves - 54mm 2 No.
642 22.049 SITC of Ball Valves - 76mm 1 No
643 22.05 SITC of Ball Valves - 108mm 1 No
644 22.051 SITC of Bed Head Units - 1000 mm for Wards 9 No.
645 22.052 SITC of Bed Head Units - 1500 mm for ICU Category. 57 No.
646 22.053 SITC of Bed Head Panel - Running Meter 190 Rm
647 22.054 SITC of Rigid Pendent 1 No.
648 23 HEATING VENTILATION AND AIR CONDITIONING WORKS
649 23.001 Supply at site including local transport with full cover insurance, fire or any other contigencies, unload, store, handle, erect, balance, test and commission the entire water chilling plant as per specifications including all accessories as specified for water chilling plant. WATER COOLED SCREW CHILLER - (R-134A/410) EACH WITH SEMI SEALED/SEALED, SINGLE/MULTIPLE COMPRESSOR OF MINIMUM CAPACITY 110 TR.\nMinimum Overall Chiller efficiency offered shall have COP = 4.9 AS PER ECBC / ASHRAE / ARI 550/590 (Detailed Technical Specification Attached) 3 Nos
650 23.002 Supply, installation, testing & commissioning the chilled water primary pumps as per specification including all accessories as specified and as required. Including Factory made base frame & fixing foundation with necessary fittings as required\nEndsuction Chilled water Pump sets complete with TEFC sq.cage induction motor (WITH MECHANICAL SEAL) stainless steel shaft, bronze impeller, base plate couplings, pressure gauges (2 Nos. with syphon and gauge cock, anti vibration springs. guards etc. including insulation as per specifications:\nCapacity : 264 USgpm, 1440rpm (1 Stand by)\nHead : 45 feet\nMotor : 5 H.P (suggested) - IE 3 4 Nos.
651 23.003 Supply, installation, testing & commissioning the chilled water secondary pumps as per specification including all accessories as specified and as required. Including Factory made base frame & fixing foundation with necessary fittings as required\nEndsuction Chilled water Pump sets complete with TEFC sq.cage induction motor (WITH MECHANICAL SEAL) stainless steel shaft, bronze impeller, base plate couplings, pressure gauges (2 Nos. with syphon and gauge cock, anti vibration springs. guards etc. including insulation as per specifications:\nCapacity : 264 USgpm, 1440rpm (1 Stand by)\nHead : 90 feet\nMotor : 10 H.P (suggested) - IE 3 4 Nos.
652 23.004 Supply, Installation, Testing & commissioning of Variable Frequency Drive complete with VSPS control panel (IP 55 if panel is to be installed under open air, IP 20 if VFD is to be installed with panel enclosure) consisting of adjustable frequency drive (AFD) for each pump, one dedicated microprocessor based pump logic controller per zone housed within this enclosure panel with parallel pumping software duly down loaded and single / multiple differential pressure sensor / transmitters as per the site requirement. The entire system along with secondary pumps as described above must be sourced from single manufacturer only, to ensure unit responsibility. The VFD should be incorporated with RFI (radio frequency interface) filters which can control THDi [Total Harmonic Distortion Current] below 5%, auto bypass starter compatible to the third party bms. 1 Set
653 23.005 Supply, Installation, testing & commsssioning the condenser water pumps as per specification including all accessories as specified and as required. Including Factory made base frame & fixing foundation with necessary fittings as required\nEndsuction Chilled water Pump sets complete with TEFC sq.cage induction motor (WITH MECHANICAL SEAL) stainless steel shaft, bronze impeller, base plate couplings, pressure gauges (2 Nos. with syphon and gauge cock, anti vibration springs. guards etc. including insulation as per specifications:\nCapacity : 440 USgpm, 1440rpm (1 Stand by)\nHead : 70 feet\nMotor : 15 H.P (suggested) - IE 3 4 Nos.
654 23.006 Supply, Installation, testing & commissioning the cooling towers as per specification including all accessories as specified and as required. COOLING TOWERS of actual capacity complete in all respects as per technical specifications and equipment schedule complete with FRP casing, FRP fan cylinder, PVC louvers, PVC drift eliminator polypropelene nozzles, drive assembly, HDG fan guard/bird screen, non-clogging nozzle type water distribution system. PVC fill, aluminium ladder with railings, make up water, quick fill and drain over flow connections with valves & fittings etc. as per specifications.\nIncluding R.C.C foundation along with PCC/RCC sub base, fixing with bolts and nuts and finishing the slabs or any opening etc.\n110 TR - CTI/JCI approved induced draft, cross flow cooling tower with vertical air discharge.\nEWT = 97.5 degree F\nLWT = 90 degree F\nWET bulb = 82 degree F\nFlow rate = 440 USgpm \nMotor suggested - 5 HP 3 Nos.
655 23.007 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n30 TR, 12000 cfm, 24 sqft./ 4 row.\nDouble Skin Floor mounted Horizontal AHU with mixing Box 1 No
656 23.008 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n16 TR, 7250 cfm, 14.4 sqft./ 4 row.\nDouble Skin Floor mounted Horizontal AHU with mixing Box, 2 x 3 KW Heater 2 No
657 23.009 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n10 TR 4000 CFM 8 sqft / 4 row.\nDouble Skin Floor mounted Horizontal AHU with mixing Box 1 No
658 23.01 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n9TR 3600 CFM 7.2 sqft / 6 row.\nDouble Skin Ceiling suspended AHU with mixing Box, including heater of 2 x 3kW 1 No
659 23.011 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n7TR 2800 CFM 5.6 sqft / 6 row.\nDouble Skin Ceiling suspended AHU with mixing Box, including heater of 2 x 3kW 1 No
660 23.012 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n5 TR 2000 CFM 4 sqft/ 4 row. \nDouble Skin Floor mounted Horizontal AHU with mixing Box 1 No
661 23.013 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n26 TR, 10400 cfm, 20.8 sqft./ 4row.\nDouble Skin Floor mounted Horizontal AHU with fine filter, mixing Box 1 No
662 23.014 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n10 TR 4000 CFM 8.8 sqft./ 4 row. \nDouble Skin Floor mounted Horizontal AHU with fine filter, mixing Box 2 No
663 23.015 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n9TR 3600 CFM 7.2 sqft./ 4 row. \nDouble Skin Floor mounted Horizontal AHU with fine filter, mixing Box 1 No
664 23.016 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n8TR 3200 CFM 6.4 sqft./ 4 row. \nDouble Skin Floor mounted Horizontal AHU with fine filter, mixing Box 2 No
665 23.017 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n4 TR 1600 CFM 3.2 sqft./ 4 row.\nDouble Skin Floor mounted Horizontal AHU with fine filter, mixing Box 2 No
666 23.018 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n15 TR 6000 CFM 12 sq.ft./ 4 row. \nDouble Skin ceiling suspended AHU 1 No
667 23.019 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n12 TR 4800 CFM 7.2sq.ft./ 4 row. \nDouble Skin ceiling suspended AHU 1 No
668 23.02 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \n\nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n4 TR 1800 CFM 3.6 sq.ft./ 4 row. \nDouble Skin ceiling suspended AHU 1 No
669 23.021 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n3 TR, 1005 cfm, 2.01 sqft./ 6 Row\nDouble skin ceiling suspended AHU with fine filter, mixing box. 1 No
670 23.022 Supply, Installation, testing & commissioning the Air Handling Units as per specification including all accessories as specified and as required. VFD driven AHU with plug fans and VFD starter panel with all necessary connections with pressure sensors (minimum 2 nos.) and cabling to be included. Only HVAC application VFD's shall be used. All AHU’s will be given only one power input cable. Any looping should be done by OEM in case of multiple motors in one AHU. \nThermostat, Thermowell at the inlet and outlet of cooling coils, gauge cocks at the the inlete and outlet of coiling coils for pressure gauges (only provision), duct damper, including Control wiring to make M/V in close position while AHU is OFF with relays etc. Limit switch in door and inspection lamps to be fixed. Lockable off push button to be provided near AHU if machine is 3mtrs and above far from respective pannel board to be included in the AHU cost. Fixing with bolts and nuts and finishing the slabs or any opening etc good as same\nNotes: Fine filter efficiency 99.9% down to 5 micron.\nExternal Static Pressure for: \nOperation theater AHU's 100 mm Static\nCathlab, CT/MRI- 65 mm Static\nAHU's with fine filters - 55 mm Static\nall other AHU's - 50 mm Static\n7 TR, 3200 cfm, 6.4 sqft./ 8 Row - OT\nDouble Skin Floor mounted Horizontal AHU with mixing box, 10 micron pre filters , 5 micron fine filters, heater capacity 2 x 3KW, Thermal break 11 No
671 23.023 Supply at site, including, local transport, unload, store, handle, erect, balance and commission of the entire HRW as per specifications including all accessories as specified and as required\nSummer Ambient conditions: DBT – 95 deg F, WBT- 82 Deg F\nReturn Air condition: DBT- 75 Deg F , RH– 55%\nSupply Fan Static - 60 to 70 mm WG\nReturn fan - 40 mm to 60 mm WG\nEfficiency 80- 85%\n\nTFA \nTFA - 37 TR AHU, 12.8 sq.ft./ 8 Row coil with 6400 CFM Supply fan, 5750 cfm Return fan with Heater 1 No
672 23.024 Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and suitable TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin & with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)\n0.75 TR Hideway FCU 8 No
673 23.025 Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and suitable TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin & with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)\n1 TR Hideway FCU 48 No
674 23.026 Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and suitable TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin & with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)\n1.25 TR Hideway FCU 12 No
675 23.027 Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and suitable TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin & with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)\n1.5 TR Hideway FCU 30 No
676 23.028 Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and suitable TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin & with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)\n2 TR Hideway FCU 8 No
677 23.029 Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and suitable TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin & with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)\n2.5 TR Hideway FCU 1 No
678 23.03 Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and suitable TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin & with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)\n3 TR Hideway FCU 3 No
679 23.031 SITC of 1.5 TR Chilled Water Hiwall Unit 6 No
680 23.032 SITC of 1 TR Chilled Water Hiwall Unit 4 No
681 23.033 Supply, installing, testing and commissioning of following cassette units with drain pump & fresh air provision as per specification including all accessories as specified and as required\n1 TR one way cassette unit 1 No
682 23.034 Supply, installing, testing and commissioning of following cassette units with drain pump & fresh air provision as per specification including all accessories as specified and as required\n1.5 TR one way cassette unit 1 No
683 23.035 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.200 mm dia. 160 Meter
684 23.036 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.150 mm dia. 5 Meter
685 23.037 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.125 mm dia. 40 Meter
686 23.038 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.100 mm dia. 230 Meter
687 23.039 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.80 mm dia. 85 Meter
688 23.04 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.65 mm dia. 200 Meter
689 23.041 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.50 mm dia. 200 Meter
690 23.042 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.40 mm dia. 510 Meter
691 23.043 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.32 mm dia. 450 Meter
692 23.044 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.25 mm dia. 635 Meter
693 23.045 Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.\nUndergorund piping shall have bitumen coating. Piping insulation shall be expanded polyurethane foam with 36 kg/cu m minimum density, 90% minimum closed cell content, minimum compressive strength of 40 psi and thermal conductivity of 0.14 Btu-in/hr/ft2/°F. The insulation shall completely fill the annular space between the service pipe and jacket and shall be bonded to both, the service pipe & jacket. All the fittings & bends shall be finished with the same finish as specified for preinsulated pipe, supplied by the same company. All supports pipes to be welded with V-cut grooves as per specifications. MS Class B, IS 3589, IS 1239 piping. RCC opening as good as same. Wall opening as good as same.20 mm dia. 1830 Meter
694 23.046 Site fabricated pipe (MS class B) with adequate structural support and with PUF injection insulation & GI cladding for part plant room & AHU room area & valve insulation with openable boxing for inspection.200 mm dia. 95 Meter
695 23.047 Site fabricated pipe (MS class B) with adequate structural support and with PUF injection insulation & GI cladding for part plant room & AHU room area & valve insulation with openable boxing for inspection.100 mm dia. 75 Meter
696 23.048 DRAIN WATER PIPING:\nSupply and fixing in position of condensate drain water & AHU room drain pipe to the floor trap/nearest drain piping with 25 mm nitrile rubber insulation and with necessary fittings like traps, clamps, elbows, tees and reducers etc. Openings as good as same.\n32 mm dia. PVC 150 Meter
697 23.049 DRAIN WATER PIPING:\nSupply and fixing in position of condensate drain water & AHU room drain pipe to the floor trap/nearest drain piping with 25 mm nitrile rubber insulation and with necessary fittings like traps, clamps, elbows, tees and reducers etc. Openings as good as same.\n20 mm dia. PVC 300 Meter
698 23.05 Supply, installation, testing & commissioning of the following Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating.200 mm dia. 7 Nos
699 23.051 Supply, installation, testing & commissioning of the following Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating.150 mm dia. 1 Nos
700 23.052 Supply, installation, testing & commissioning of the following Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating.125 mm dia. 4 Nos
701 23.053 Supply, installation, testing & commissioning of the following Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating.100 mm dia. 28 Nos
702 23.054 Supply, installation, testing & commissioning of the following Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating.80 mm dia. 2 Nos
703 23.055 Supply, installation, testing & commissioning of the following Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating.65 mm dia. 14 Nos
704 23.056 Supply, installation, testing & commissioning of the following Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating.50 mm dia. 6 Nos
705 23.057 Supply, installation, testing & commissioning of the following Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating.40 mm dia. 28 Nos
706 23.058 Supplying, fixing, testing and commissioning of following Ball valves and Drain valves for AHUs, plant room, shaft riser & chilled water piping adequately supported as per specifications. 32 mm dia 30 Nos
707 23.059 Supplying, fixing, testing and commissioning of following Ball valves and Drain valves for AHUs, plant room, shaft riser & chilled water piping adequately supported as per specifications. 25 mm dia 33 Nos
708 23.06 Supplying, fixing, testing and commissioning of following Ball valves and Drain valves for AHUs, plant room, shaft riser & chilled water piping adequately supported as per specifications. 20 mm dia 2 Nos
709 23.061 Supply, installation, testing & commissioning of the following non return valves as per the specifications and as required. Non Return valves up to 65mm size shall be of gun metal with screwed female ends. Valves of 65mm and above shall be of CI with flanged ends. PN 16 pressure rating, EPDM seal.\nNon- Return Valve of size:- 100 mm dia 8 Nos
710 23.062 BALANCING VALVE WITH PROVISION FOR FLOW MEASURMENT:\nSupply, installation, testing & commissioning of Balancing valve with built in measuring facility, C.I Body with EPDM seal, long pitch with protected out pipe insulation & PN 16 pressure rating for chilled water as specified. Balancing Valve with 90 Deg C maximum operating temperature; built-in locking device for Tamper-Proof positioning; flanged connections; Valves shall have connections with isolation device for portable differential pressure meter with integral seals, Flow accuracy shall be 5%+/-, necessary insulation as per specification\nBalancing valve with built in measuring facility 100 mm dia 3 Nos
711 23.063 SUCTION GUIDE with strainer:\nSupply, installation, testing & commissioning of the following suction guides as per the specifications and as required.\nSize: 100 mm dia. 8 Nos
712 23.064 Supplying, fixing, testing and commissioning of following Y- Strainer in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y- Strainer of 65 mm dia 3 Nos
713 23.065 Supplying, fixing, testing and commissioning of following Y- Strainer in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y- Strainer of 50 mm dia 4 Nos
714 23.066 Supplying, fixing, testing and commissioning of following Y- Strainer in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y- Strainer of 40 mm dia 8 Nos
715 23.067 Supplying, fixing, testing and commissioning of following Y- Strainer in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y- Strainer of 32 mm dia 12 Nos
716 23.068 Supplying, fixing, testing and commissioning of following Y- Strainer in the chilled water piping duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y- Strainer of 25 mm dia 4 Nos
717 23.069 PRESSURE GAUGE - For chiller, pumps, AHU:\nProviding and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required 84 Nos
718 23.07 THERMOMETERS - For chiller, pumps, AHU: \nSupply, installation, testing and commissioning of 4 inch Dial type thermometers with Stem with Copper-plated steel, aluminum, or brass for thermowell installation and of length to suit installation, Stainless Steel U-Siphon and 15mm Brass body ball valve as per specification 84 Nos
719 23.071 Supply, installation, testing & commissioning of differential pressure switch as per the specifications and as required. 3 Nos
720 23.072 Supply, installation, testing & commissioning of the following motorized cut off valves as per the specifications and as required. Cl Body, minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, capable of accepting upto 10V DC and upto 20mA electric signal and providing similar transduced feedback output to control system as required.\nSize: 100 mm dia. 3 Nos
721 23.073 500 L Pressurized Tank:\nDesign, supply, installation, testing and commissioning of Pressurised chilled water expansion tank with insulation, Make up connection for closed loop system along with necessary pneumatic devices and accessories and MS 'C' section supports in order to keep chilled water under pressure. The tank shall be precharged steel tank with replacable heavy duty butyl rubber bladder. The tank shall have 50mm system connection and 20mm drain and charging valve connection to facilitate on-site charging of tank. The tank shall be fitted with lifting rings and floor mounting skirt for vertical installation. The tank shall be constructed according to section 8 of ASME boiler and pressure vessel code and stamped 125psi working pressure.The contractor shall submit calculation regarding the above data. Pumps shall be of N+1 configuration. including with control wiring 1 Nos
722 23.074 Supply, installation, testing & commissioning of a common air separator on the chilled water return line located at the pump suction and suitable for Secondary pump water flow; the separator shall be complete with high capacity air vent, flanges, service valve, non return valve, isolation butterfly valve for makeup water inlet.\nCapacity suitable for 792 USGPM and 200mm NB CHW Header line 1 Nos
723 23.075 AUTO AIR VENTS including Ball Valves:\nSupply & install of airvents / purge valves including 15mm Ball Valves at the highest points in chilled water piping complete each floor with pipes nipple welded to pipe, hex nipple, socket, U-pipe connection at outlet of air vent etc. as required. 35 Nos
724 23.076 Supply and fix flexible connections with control rods for pumps and chiller.\nSize: 100 mm dia. 22 Nos
725 23.077 Supply, Installation, testing and commissioning of following size Pressure independent type 2 way modulating flow Control valves in a single Unit of Valves with PN16 Rating. DN 15 to DN 32 Brass Body Ext. Threaded, DN 40 & DN 50 Cast Iron Body Ext. Threaded, DN 65 to DN 100 Cast Iron body, Flanged Ends Connection Duly mounted with a BMS compatible Modulating actuator IP54 Type suitable for 24V AC for AHU/FCU as per specification65 mm dia. 3 Nos
726 23.078 Supply, Installation, testing and commissioning of following size Pressure independent type 2 way modulating flow Control valves in a single Unit of Valves with PN16 Rating. DN 15 to DN 32 Brass Body Ext. Threaded, DN 40 & DN 50 Cast Iron Body Ext. Threaded, DN 65 to DN 100 Cast Iron body, Flanged Ends Connection Duly mounted with a BMS compatible Modulating actuator IP54 Type suitable for 24V AC for AHU/FCU as per specification50 mm dia. 4 Nos
727 23.079 Supply, Installation, testing and commissioning of following size Pressure independent type 2 way modulating flow Control valves in a single Unit of Valves with PN16 Rating. DN 15 to DN 32 Brass Body Ext. Threaded, DN 40 & DN 50 Cast Iron Body Ext. Threaded, DN 65 to DN 100 Cast Iron body, Flanged Ends Connection Duly mounted with a BMS compatible Modulating actuator IP54 Type suitable for 24V AC for AHU/FCU as per specification40 mm dia. 8 Nos
728 23.08 Supply, Installation, testing and commissioning of following size Pressure independent type 2 way modulating flow Control valves in a single Unit of Valves with PN16 Rating. DN 15 to DN 32 Brass Body Ext. Threaded, DN 40 & DN 50 Cast Iron Body Ext. Threaded, DN 65 to DN 100 Cast Iron body, Flanged Ends Connection Duly mounted with a BMS compatible Modulating actuator IP54 Type suitable for 24V AC for AHU/FCU as per specification32 mm dia. 12 Nos
729 23.081 Supply, Installation, testing and commissioning of following size Pressure independent type 2 way modulating flow Control valves in a single Unit of Valves with PN16 Rating. DN 15 to DN 32 Brass Body Ext. Threaded, DN 40 & DN 50 Cast Iron Body Ext. Threaded, DN 65 to DN 100 Cast Iron body, Flanged Ends Connection Duly mounted with a BMS compatible Modulating actuator IP54 Type suitable for 24V AC for AHU/FCU as per specification25 mm dia. 4 Nos
730 23.082 Supply, receive, store handle, install, test and commission the condenser water line with GI class (B) IS 3589 pipes complete with all fittings such as bends, tees, elbows, reducers, flanges, special fittings, suspension hangers, structural supports, etc. as reqd. for installation as per site conditions and as per specfiications. Opening as good as same.200 mm dia. 75 Meter
731 23.083 Supply, receive, store handle, install, test and commission the condenser water line with GI class (B) IS 3589 pipes complete with all fittings such as bends, tees, elbows, reducers, flanges, special fittings, suspension hangers, structural supports, etc. as reqd. for installation as per site conditions and as per specfiications. Opening as good as same.125 mm dia. 45 Meter
732 23.084 Supply, receive, store handle, install, test and commission the condenser water line with GI class (B) IS 3589 pipes complete with all fittings such as bends, tees, elbows, reducers, flanges, special fittings, suspension hangers, structural supports, etc. as reqd. for installation as per site conditions and as per specfiications. Opening as good as same.100 mm dia. For equalizer line 15 Meter
733 23.085 Supply, installation, testing & commissioning of the following butterfly valves as per the specifications and as required.\nBUTTERFLY VALVE (MANUAL): Size- 125 mm 20 No.
734 23.086 Supply, installation, testing & commissioning of the following butterfly valves as per the specifications and as required.- For equalizer line\nBUTTERFLY VALVE (MANUAL): Size- 100 mm 3 No.
735 23.087 Supplying, fixing, testing and commissioning of following non return valves, in the condenser water piping and adequately supported as per specifications. \nNon- Return Valve of 125 mm dia 4 No.
736 23.088 Supply, installation, testing & commissioning of the following suction guides as per the specifications and as required\nSize: 125 mm dia 4 No.
737 23.089 Supply and fix flexible connections with control rods for pumps, cooling tower & condenser. \nSize: 125 mm NB 14 No.
738 23.09 Supply, installation, testing & commissioning of Balancing Valve, with built in measuring facility with C.I Body, 90 Deg C maximum operating temperature; built-in locking device for Tamper-Proof positioning; flanged connections;Valves shall have connections with isolation device for portable differential pressure meter with integral seals, Flow accuracy shall be 5%+/- \nSize: 125 mm NB 6 No.
739 23.091 Supply, installation, testing and commissioning of 4" Dial type thermometers with Stem with Copper-plated steel, aluminum, or brass for thermowell installation and of length to suit installation, Stainless Steel U-Siphon and 15mm Brass body ball valve as per specification 14 No.
740 23.092 Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required 14 No.
741 23.093 Supply, installation, testing & commissioning of differential pressure switch as per the specifications and as required. 3 No.
742 23.094 Supply, installation, testing & commissioning of the following motorized cut off valves as per the specifications and as required. Cl Body, Nylon coated DI disc, EPDM seal, minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, capable of accepting upto 10V DC and upto 20mA electric signal and providing similar transduced feedback output to control system as required.\nSize: 125 mm dia 6 No.
743 23.095 Supply, fabricate, handle, erect, balancing and commissioning factory fabricated GSS ducting as per drawing, complete with all fittings such as tee bends, special off-chutes, turning vanes, splitter dampers, ins.doors, transformation pieces, slip on flanges, rubber gaskets, elbows, hangers, supports etc. etc. as reqd. as per IS 655 including suspension and supporting arrangement for plenums, ducts, complete as reqd. and as per specs.Thickness 0.63 mm GSS sheet 1900 Sq.m
744 23.096 Supply, fabricate, handle, erect, balancing and commissioning factory fabricated GSS ducting as per drawing, complete with all fittings such as tee bends, special off-chutes, turning vanes, splitter dampers, ins.doors, transformation pieces, slip on flanges, rubber gaskets, elbows, hangers, supports etc. etc. as reqd. as per IS 655 including suspension and supporting arrangement for plenums, ducts, complete as reqd. and as per specs.Thickness 0.80 mm GSS sheet 1025 Sq.m
745 23.097 Supply, fabricate, handle, erect, balancing and commissioning factory fabricated GSS ducting as per drawing, complete with all fittings such as tee bends, special off-chutes, turning vanes, splitter dampers, ins.doors, transformation pieces, slip on flanges, rubber gaskets, elbows, hangers, supports etc. etc. as reqd. as per IS 655 including suspension and supporting arrangement for plenums, ducts, complete as reqd. and as per specs.Thickness 1.00 mm GSS sheet 225 Sq.m
746 23.098 SITC of below specified Factory Fabricated Aluminium ducting for clean rooms such as major & Minor OT's, CT/MRI, etc.Thickness 0.80 mm Al. Sheet ducting 1175 Sq.m
747 23.099 SITC of below specified Factory Fabricated Aluminium ducting for clean rooms such as major & Minor OT's, CT/MRI, etc.Thickness 1.00 mm Al. Sheet ducting 585 Sq.m
748 23.1 Supply installing, testing and commissioning of fine filters of efficiency 99.9% down to 5 microns in filter plenum in suitable frame work for MRI/CT:\nFine filters - as per dwg, 7250 cfm 1 Lot
749 23.101 TOTAL HEPA FILTRATION AREA – 5.4 Sq.mt:\nSupply installing, testing and commissioning of (Factory Fabricated) HEPA filters of efficiency 99.9% down to 0.3 microns in filter plenum of 18 Gauge with rubber Gaskets In SS suitable frame work with 70% perforated grille \nUltra Clean Ventilation arrangement of A/C inside the clean room comprising of SS supply plenum including the 1.5" flanges on all sides., material SS 304, 0.8mm, 2B finish. HEPA filters 0.3microns, efficiency 99.97% EU13 Sizes of: 1200 x 900 x 150mm - 4 Nos, 900 x 600 x 150mm- 2 Nos. The HEPA filters will be fixed to the plenum using M6 SS rode, 304 Q type SS bolts and nuts). SS perforated sheets Mat finish.\nHepa filters (550 cfm x 4 nos.+ 500 cfm x 2 Nos.) 11 Set
750 23.102 Supplying and Fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. 4.5 Sq.m
751 23.103 Supplying and Fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. 6 Sq.m
752 23.104 Supply and fixing of Square Supply air diffusers of powder coated Aluminium with opposed blade dampers with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600\nSD: 375×375 400 Nos
753 23.105 Supply and fixing of Square Supply air diffusers of powder coated Aluminium with opposed blade dampers with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600\nSD: 450×450 4 Nos
754 23.106 Supply and fixing of Square Return air diffusers of powder coated Aluminium with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600\nSD: 375×375 400 Nos
755 23.107 Supply and fixing of Square Return air diffusers of powder coated Aluminium with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600\nSD: 450×450 4 Nos
756 23.108 Supply installing, testing and commissioning of perforated aluminium grille for return with VCD and 10 Micron Filter in OT 32 Sq.m
757 23.109 Supply, Fabrication, installation and testing of following size insulated flexible duct, complete with connecting rings, duct supports etc. as per standards and specification.\n350 mm dia 650 Meter
758 23.11 SITC of following Insulated Plenum Box made of 22g G.I & Spigot & Butterfly Dampers with necessary threaded rods for supporting for the following sizes\n450 X 450 X 450H 400 Nos
759 23.111 SITC of following Insulated Plenum Box made of 22g G.I & Spigot & Butterfly Dampers with necessary threaded rods for supporting for the following sizes\n600 X 600 X 450H 4 Nos
760 23.112 SITC of Factory made fresh air dampers with louvers and control lever, filter etc as required. (as per drawing) 49 Nos
761 23.113 SITC of Factory made fresh air dampers having 20 micron filter with louvers and control lever. (for OT as per drawing) 1 Nos
762 23.114 Supply, fix, balance and commissioning of louvre type smooth supply air duct dampers made of extruded aluminium linkage, lever, brass bushings complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges, fixing arrangement etc, as per specifications.\nAl. volume control duct damper 16 sq.m
763 23.115 Supply and fix 1 1/2 hour fire rated fire dampers air ducts (main line) with fusible link & microswitch to shut of corresponding AHU (including control cable.) 12 sq.m
764 23.116 SITC of VAVs of following CFMs for supply air in rectangular ducts including thermostat and controls. Casing and damper blade made of galvinized sheet steel with proper seal and polyurethane plain bearings. Sensor tubes should be aluminium, maintenance free damper blade with minimum leakage rate. Actuator suitable for AC 24V 50 Hz and rated for dust pressure upto 50mm water gauge.\nVAV - 1350 cfm 1 Nos
765 23.117 SITC of VAVs of following CFMs for supply air in rectangular ducts including thermostat and controls. Casing and damper blade made of galvinized sheet steel with proper seal and polyurethane plain bearings. Sensor tubes should be aluminium, maintenance free damper blade with minimum leakage rate. Actuator suitable for AC 24V 50 Hz and rated for dust pressure upto 50mm water gauge.\nVAV - 1450 cfm 1 Nos
766 23.118 Thermal insulation:\nSupply & fixing of 8 mm thick Class O nitrile rubber insulation with antimicrobial property with adhesive as per the recommendation of the manufacturer with density 45-55kg/m3 2500 Sq.m
767 23.119 Acoustic insulation:\nSupply & fixing of 10 mm thick Class 1 acoustic nitrile rubber insulation with antimicrobial property with adhesive as per the recommendation of the manufacturer with density 140-180kg/m3 700 Sq.m
768 23.12 Non ac area duct insulation:\nSupply & fixing of 19 mm thick Class O nitrile rubber insulation with adhesive as per the recommendation of the manufacturer with density 45-55kg/m3 1600 Sq.m
769 23.121 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 80 cfm Exhaust blower 7 Nos
770 23.122 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 100 cfm Exhaust blower 7 Nos
771 23.123 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 150 cfm Exhaust blower 15 Nos
772 23.124 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 200 cfm Exhaust blower 8 Nos
773 23.125 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 250 cfm Exhaust blower 1 Nos
774 23.126 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 300 cfm Exhaust blower 4 Nos
775 23.127 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 350 cfm Exhaust blower 14 Nos
776 23.128 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 400 cfm Exhaust blower 2 Nos
777 23.129 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 450 cfm Exhaust blower 1 Nos
778 23.13 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 500 cfm Exhaust blower 1 Nos
779 23.131 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 650 cfm Exhaust blower 2 Nos
780 23.132 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 750 cfm Exhaust blower 3 Nos
781 23.133 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 800 cfm Exhaust blower 1 Nos
782 23.134 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 850 cfm Exhaust blower 2 Nos
783 23.135 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 900 cfm Fresh Air blower 1 Nos
784 23.136 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 1000 cfm Exhaust blower 5 Nos
785 23.137 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 1150 cfm Exhaust blower 1 Nos
786 23.138 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 1250 cfm Exhaust blower 1 Nos
787 23.139 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 1300 cfm Exhaust blower 1 Nos
788 23.14 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 1400 cfm Exhaust blower 1 Nos
789 23.141 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 1500 cfm Exhaust blower 2 Nos
790 23.142 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 1600 cfm Exhaust blower 1 Nos
791 23.143 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 1700 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; cfm Exhaust blower 2 Nos
792 23.144 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 2100 cfm Exhaust blower 1 Nos
793 23.145 Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen; 2700 cfm Exhaust blower 3 Nos
794 23.146 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006.\nThickness 0.63mm Sheet 700 Sq.m
795 23.147 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006.\nThickness 0.80mm Sheet 10 Sq.m
796 23.148 Supply, Fabrication, installation and testing of the flexible ducting, complete with connecting rings, duct supports, Plenum etc as per standards and specification.\nSize: 100mm dia. 520 Meter
797 23.149 Supply and fix the following grilles and diffusers as per specifications. Machine made, powder coated, supply and return air grilles and diffusers. Design to be approved (material : Aluminium)\nReturn air grille/diffuser with vcd 8 Sq.m
798 23.15 Acoustic Lining of AHU Rooms/boxing without Mixing Box /Boxing Insulation for Ceiling suspended AHU\nSupply & fixing of 15 mm thick acoustic nitrile rubber insulation with adhesive as per the recommendation of the manufacture with density 140-180kg/m3 100 Sq.m
799 23.151 UNDER DECK INSULATION - FOR ICU, OPERATION THEATRE, MRI, CT, ISOLATION ROOMS: \nSupply & fixing of 9 mm thick class O nitrile rubber insulation with adhesive as per the recommendation of the manufacture with density 45-55kg/m3 1700 Sq.m
800 23.152 Roof(inside) insulation for exposed slabs/walls: \nSupply & fixing of 12 mm thick class O nitrile rubber insulation with adhesive as per the recommendation of the manufacture with density 45-55kg/m3 1200 Sq.m
801 23.153 Fabrication, supply, erection, testing and commissioning of dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components including fully automatic Star/delta/DOL starters for pumps, Variable Speed drives suitable for cubicle panel mounting inside the main panel for secondary pumps Control wiring, interlocks, push buttons, indication lamps etc. All the panels shall be compactable for BMS & CPRI Approved. All mandatory and statuatory sanction orders and approvals from the electrical inspectorate and KSEB shall be obtained by the contractor before energizing the system. (Rate Quoted as per the attached Electrical Scheme)\na) INCOMER - 1 No. MCCB\nb) BUSBARS- 3 phase and neutral Aluminium bus bars with bus supports in suitable bus chamber.\nc) METERING- 0-250 Amp ammeter with CT's and selector switch, 0-500 volts voltmeter with selector switch and fuses.\nd) 1 set R.Y.B lmps with fuses.\ne) OUTGOING- TPN MCCB/ MPCB for pumps, cooling tower's, AHU's. & 1 No. earth bus(CU) throughout the panel with earthing bolts\nPump Panel with Energy meter in the Panel \n(Total HP- 105 HP) 1 Nos
802 23.154 Fabrication, supply, erection, testing and commissioning of dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components including fully automatic Star/delta/DOL starters for pumps, Variable Speed drives suitable for cubicle panel mounting inside the main panel for secondary pumps Control wiring, interlocks, push buttons, indication lamps etc. All the panels shall be compactable for BMS & CPRI Approved. All mandatory and statuatory sanction orders and approvals from the electrical inspectorate and KSEB shall be obtained by the contractor before energizing the system. (Rate Quoted as per the attached Electrical Scheme)\na) INCOMMER - 1 No. MCCB\nb) BUSBARS- 3 phase and neutral Aluminium bus bars with bus supports in suitable bus chamber.\nc) METERING- 0-250 Amp ammeter with CT's and selector switch, 0-500 volts voltmeter with selector switch and fuses.\nd) 1 set R.Y.B lmps with fuses.\ne) OUTGOING- TPN MCCB/ MPCB for pumps, cooling tower's, AHU's. & 1 No. earth bus(CU) throughout the panel with earthing bolts\nAHU Panel -1 with above specifications & as per drawings - Basement, Ground floor\n(Total HP- 53 HP) 1 Nos
803 23.155 Fabrication, supply, erection, testing and commissioning of dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components including fully automatic Star/delta/DOL starters for pumps, Variable Speed drives suitable for cubicle panel mounting inside the main panel for secondary pumps Control wiring, interlocks, push buttons, indication lamps etc. All the panels shall be compactable for BMS & CPRI Approved. All mandatory and statuatory sanction orders and approvals from the electrical inspectorate and KSEB shall be obtained by the contractor before energizing the system. (Rate Quoted as per the attached Electrical Scheme)\na) INCOMMER - 1 No. MCCB\nb) BUSBARS- 3 phase and neutral Aluminium bus bars with bus supports in suitable bus chamber.\nc) METERING- 0-250 Amp ammeter with CT's and selector switch, 0-500 volts voltmeter with selector switch and fuses.\nd) 1 set R.Y.B lmps with fuses.\ne) OUTGOING- TPN MCCB/ MPCB for pumps, cooling tower's, AHU's. & 1 No. earth bus(CU) throughout the panel with earthing bolts\nAHU Panel -2 with above specifications & as per drawings - Terrace floor, Left \n(Total HP- 49 HP) 1 Nos
804 23.156 Fabrication, supply, erection, testing and commissioning of dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components including fully automatic Star/delta/DOL starters for pumps, Variable Speed drives suitable for cubicle panel mounting inside the main panel for secondary pumps Control wiring, interlocks, push buttons, indication lamps etc. All the panels shall be compactable for BMS & CPRI Approved. All mandatory and statuatory sanction orders and approvals from the electrical inspectorate and KSEB shall be obtained by the contractor before energizing the system. (Rate Quoted as per the attached Electrical Scheme)\na) INCOMMER - 1 No. MCCB\nb) BUSBARS- 3 phase and neutral Aluminium bus bars with bus supports in suitable bus chamber.\nc) METERING- 0-250 Amp ammeter with CT's and selector switch, 0-500 volts voltmeter with selector switch and fuses.\nd) 1 set R.Y.B lmps with fuses.\ne) OUTGOING- TPN MCCB/ MPCB for pumps, cooling tower's, AHU's. & 1 No. earth bus(CU) throughout the panel with earthing bolts\nAHU Panel -3 with above specifications & as per drawings - Terrace Floor, Left \n(Total HP- 34 HP) 1 Nos
805 23.157 Fabrication, supply, erection, testing and commissioning of dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components including fully automatic Star/delta/DOL starters for pumps, Variable Speed drives suitable for cubicle panel mounting inside the main panel for secondary pumps Control wiring, interlocks, push buttons, indication lamps etc. All the panels shall be compactable for BMS & CPRI Approved. All mandatory and statuatory sanction orders and approvals from the electrical inspectorate and KSEB shall be obtained by the contractor before energizing the system. (Rate Quoted as per the attached Electrical Scheme)\na) INCOMMER - 1 No. MCCB\nb) BUSBARS- 3 phase and neutral Aluminium bus bars with bus supports in suitable bus chamber.\nc) METERING- 0-250 Amp ammeter with CT's and selector switch, 0-500 volts voltmeter with selector switch and fuses.\nd) 1 set R.Y.B lmps with fuses.\ne) OUTGOING- TPN MCCB/ MPCB for pumps, cooling tower's, AHU's. & 1 No. earth bus(CU) throughout the panel with earthing bolts\nAHU Panel -4 with above specifications & as per drawings - Terrace Floor, Right\n(Total HP- 57 HP) 1 Nos
806 23.158 Fabrication, supply, erection, testing and commissioning of dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components including fully automatic Star/delta/DOL starters for pumps, Variable Speed drives suitable for cubicle panel mounting inside the main panel for secondary pumps Control wiring, interlocks, push buttons, indication lamps etc. All the panels shall be compactable for BMS & CPRI Approved. All mandatory and statuatory sanction orders and approvals from the electrical inspectorate and KSEB shall be obtained by the contractor before energizing the system. (Rate Quoted as per the attached Electrical Scheme)\na) INCOMMER - 1 No. MCCB\nb) BUSBARS- 3 phase and neutral Aluminium bus bars with bus supports in suitable bus chamber.\nc) METERING- 0-250 Amp ammeter with CT's and selector switch, 0-500 volts voltmeter with selector switch and fuses.\nd) 1 set R.Y.B lmps with fuses.\ne) OUTGOING- TPN MCCB/ MPCB for pumps, cooling tower's, AHU's. & 1 No. earth bus(CU) throughout the panel with earthing bolts\nAHU Panel -5 with above specifications & as per drawings - Terrace Floor, Right\n(Total HP- 64 HP) 1 Nos
807 23.159 Fabrication, supply, erection, testing and commissioning of dust and vermin proof, floor mounted, front operated MV panel board made out of 14 SWG thick CRCA sheet fully compartmentalised complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components including fully automatic Star/delta/DOL starters for pumps, Variable Speed drives suitable for cubicle panel mounting inside the main panel for secondary pumps Control wiring, interlocks, push buttons, indication lamps etc. All the panels shall be compactable for BMS & CPRI Approved. All mandatory and statuatory sanction orders and approvals from the electrical inspectorate and KSEB shall be obtained by the contractor before energizing the system. (Rate Quoted as per the attached Electrical Scheme)\na) INCOMER - 1 No. MCCB\nb) BUSBARS- 3 phase and neutral Aluminium bus bars with bus supports in suitable bus chamber.\nc) METERING- 0-250 Amp ammeter with CT's and selector switch, 0-500 volts voltmeter with selector switch and fuses.\nd) 1 set R.Y.B lmps with fuses.\ne) OUTGOING- TPN MCCB/ MPCB for pumps, cooling tower's, AHU's. & 1 No. earth bus(CU) throughout the panel with earthing bolts\nAHU Panel -6 with above specifications & as per drawings - Terrace Floor, Top\n(Total HP- 13 HP) 1 Nos
808 23.16 SITC of Control box & DIGITAL DISPLAY PANEL inside the Operation theater with indication lamp, ON/OFF of AHU control, thermostat control of OT, cooling & heating mode, humidity control etc. Digital display of RH/TEMPERATURE, pressure (including pressure sensor & necessary control), wiring from AHU to unit etc. 11 Nos
809 23.161 SITC of Central core Computer - PC (Intel i7 Processor ) , 8 GB RAM, 2 GB Graphics card, DVD Writer, 22" LED monitor, 1 TB HDD, Microsoft mouse, Keyboards, 2 serial, 1 parallel port/KB, Windows 8 operating system , antivirus software 1 Set
810 23.162 SITC of A4 Colour Laser printer 1 Set
811 23.163 Supply, Installation, Testing and Commissioning of Building Management System Graphic User Interface software with 3 user client license, user groups, user profiles and scopes, alarm handling, scheduling, trending, reporting engine, database system, system activity log, historical data management, real time zoom enabled vector graphics, system backup and restore, HTML based documentation and help, SMS/EMail facility complete in all respects as per tender specification. Graphical Software complete to cater to hardware points as specified in the Data Point Summary as well as Third Party Software Integrated Systems. 1 Lot
812 23.164 SITC of Interface for integrating Third Party Systems. (All Systems to provide data on MODBUS RTU with values shown on MODSCAN or BacNET shown on BacNET explorer). Chiller System - 3 Chiller (50 points/chiller) 1 Lot
813 23.165 SITC of Interface for integrating Third Party Systems. (All Systems to provide data on MODBUS RTU with values shown on MODSCAN or BacNET shown on BacNET explorer). Secondary Pumps System (10 Points/Pump) 1 Lot
814 23.166 SITC of Interface for integrating Third Party Systems. (All Systems to provide data on MODBUS RTU with values shown on MODSCAN or BacNET shown on BacNET explorer). Variable Frequency Drives for AHU's (10 Points per VFD 1 Lot
815 23.167 SITC of Networkable DDC Controllers as per Data Point Summary (1- 5 ) with enclosure with all necessary wiring and accessories 1 Lot
816 23.168 SITC of Immersion Type Temperature Sensor 4 Nos.
817 23.169 SITC of Outside Air Temperature & RH Sensor 1 No.
818 23.17 SITC of Level Switch for expansion tank ( 2 point) (depth of tank - 1 mtr.) 1 No.
819 23.171 SITC of Differential Pressure Switch 8 Nos.
820 23.172 SITC of Level Switch for cooling tower 3 Nos.
821 23.173 SITC of Diffrential Pressure sensor 1 Nos.
822 23.174 Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 2 AHU / DDC for AHU's 2 Nos
823 23.175 Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 1 AHU / DDC for AHU's 2 Nos
824 23.176 SITC of Differential Pressure Switch across filter for AHU's 6 Nos.
825 23.177 SITC of Return air Temperature Sensor for AHU's 6 Nos.
826 23.178 Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 2 AHU / DDC for Air Handling Units with Fine filter 4 Nos.
827 23.179 Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 1 AHU / DDC for Air Handling Units with Fine filter 1 Nos.
828 23.18 SITC of Differential Pressure Switch across filter - pre filter and fine filter for Air Handling Units with Fine filter 18 Nos.
829 23.181 SITC of Return air Temperature Sensor for Air Handling Units with Fine filter 9 Nos.
830 23.182 Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 2 AHU / DDC for Air Handling Units with Heater 1 Nos.
831 23.183 SITC of Differential Pressure Switch across filter for Air Handling Units with Heater 2 Nos.
832 23.184 SITC of Return air Temperature Sensor for Air Handling Units with Heater 2 Nos.
833 23.185 SITC of RH Sensor Room type for Air Handling Units with Heater 2 Nos.
834 23.186 Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 1 AHU / DDC or 2 AHU / DDC for Air Handling Units with Fine filter, heater 2 Nos.
835 23.187 SITC of Differential Pressure Switch across filter - pre filter and fine filter for Air Handling Units with Fine filter, heater 4 Nos.
836 23.188 SITC of Return air Temperature Sensor for Air Handling Units with Fine filter, heater 2 Nos.
837 23.189 SITC of RH Sensor Room type for Air Handling Units with Fine filter, heater 2 Nos.
838 23.19 Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 1 AHU / DDC - for OT AHU's 11 Nos.
839 23.191 SITC of Differential Pressure Switch across filter -Pre filter,fine filter and Hepa filter - for OT AHU's 33 Nos.
840 23.192 SITC of Return air Temperature Sensor for OT AHU's 11 Nos.
841 23.193 SITC of RH Sensor Room type for OT AHU's 11 Nos.
842 23.194 SITC of Air Diffrential Pressure Sensor for OT AHU's 11 Nos.
843 23.195 Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories , consider 1 AHU / DDC for AHU WITH HEAT RECOVERY WHEEL 1 Nos.
844 23.196 SITC of Differential Pressure Switch across filter for AHU WITH HEAT RECOVERY WHEEL 1 Nos.
845 23.197 SITC of Return air Temperature Sensor for AHU WITH HEAT RECOVERY WHEEL 1 Nos.
846 23.198 SITC of RH Sensor Room type for AHU WITH HEAT RECOVERY WHEEL 1 Nos.
847 23.199 SITC of Signal Cabling - 2 Core 1.0 sq.mm. shielded FRLS armoured cable 2260 Meter
848 23.2 SITC of Signal Cabling - 4 Core 1.0 sq.mm. shielded FRLS armoured cable 775 Meter
849 23.201 SITC of Signal Cabling - 8 Core 1.0 sq.mm. shielded FRLS armoured cable 750 Meter
850 23.202 SITC of Communication Cabling - 2 Core 1.5 sq.mm. shielded FRLS armoured cable or CAT5E armoured cable 2400 Meter
851 23.203 SITC of Power Cable - 3 C X 2.5 SQMM -ATC Armoured Cable 50 Meter
852 24 Public Health Engineering (PHE) System & Sewage Treatment Plant
853 24.001 Providing and fixing White Vitreous China Extended Wall Mounted EWC, Complete Set with 3/6 LPF Dual Cistern, overall size 765 x 370 x 650mm. or as per approved model and shape, including Cistern Fittings, Soft Close Seat Cover, bolts, nuts, washers, expansion/ rawl sleeves, gasket etc. complete, and fixing to wall, as per manufacturer's instruction and to the approval of Engineer-in-charge. Model Jaquar- FLS WHT- 5351, FLS -WHT-5201 or equivalent 128 each
854 24.002 Providing, fixing, testing, and commissioning at site Disabled Toilet, Complete Set, including White Floor Mounted Water Closet, Suitable standard flushing cistern with internal fittings, Lid, Antimicrobial Soft close Seat Cover etc, Spatula Lever Basin Pillar tap and with 1 Set of Hinged Arm, 760mm. long, 4 Set of Grab Rail, each of 600mm. long, and with all necessary accessories and fixed with Brackets Expansion/ Rawl Sleeves, Stainless Steel/ Brass Bolts/Screws, Nuts, Washers etc, including cutting and making good the walls and floors wherever required including, all as per manufacturer's instruction and to the approval of Engineer-in-charge. Model - HINDWARE MATRIX set or Equivalent. 6 Set
855 24.003 Supplying, installing, testing & commissioning at site in position white / colour vitreous china wash basin (480x365x205mm) with C.I./MS brackets painted white, C.P brass waste coupling of standard pattern, 32mm dia C.P, basin Pillarcock with aerator, including cutting & making good the walls wherever required complete.\nWash basin below counter type with aerator PillarCock. Model - JAQUAR CNS-WHT-701, FLR-5011N-1250, ALD 709, Or Equivalent. 80 each
856 24.004 Supplying, installing, testing & commissioning at site in position white / colour vitreous china wash basin (550x400x195mm) with C.I./MS brackets painted white, C.P brass waste coupling of standard pattern, 32mm dia C.P, basin Pillarcock with aerator, including cutting & making good the walls wherever required complete.\nFlat back Pedestal wash basin PillarCock with aerator Model - JAQUAR CNS-WHT-801, FLR-5011N-1250, ALD 709 88 each
857 24.005 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Angle back wash basin size 600x480 mm with single 15 mm C.P. brass pillar tap 8 each
858 24.006 Providing and fixing White vitreous china Laboratory Sink with C.I brackets, C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required; all as per manufacturer's instruction and the direction of Engineer-in-charge. Size: 600 x450 x 20mm. Deep 64 each
859 24.007 Providing, Fixing & testing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350mm or 340x410x265 mm sizes with waste coupling respectively \nModel - Kerovit RASSO(ISI) - KS507 or Equivalent. 18 each
860 24.008 Supplying, installing, testing & commissioning at site in position Self Closing Urinal Angle Valve with attachment and Flange of approved quality\nModel - Kerovit KA860004 or Equivalent. 18 each
861 24.009 Providing and fixing CP 15 mm Urinal spreader size 95x69x100 mm with Steel screws and washers complete, including cutting and making good the walls wherever required.\nModel - Kerovit KA970001 or Equivalent. 18 each
862 24.01 Supplying, installing, testing & commissioning at site in position vitreous china urinal partition (Size 330x105x683) with expandable anchor fasteners with C.P brass bolts and washers complete, including cutting and making good the walls wherever required.\nModel - Kerovit Division Plate - KS506 or Equivalent. 10 each
863 24.011 Hot & cold CP aerator wall mixer unit - Providing, Fixing, testing and commissioning Of Hot & cold CP wall mixer unit with long bend pipe for overhead shower with all accessories. CP elbow and Overhead shower with revolving joint and shower arm with wall flanges etc complete. Model - JAQUAR Wall Mixer CON - 273 KNUPR,Shower arm SHA-477 190 mm long, Over head shower - OHS-CHR-1989 100mm dia or Equivalent 24 each
864 24.012 Supplying and fixing SS Towel rod 60cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge. Model - JAQUAR ACN-1111-SM or Equivalent 69 each
865 24.013 CP Towel Ring - Providing and Fixing CP Towel Ring trapezoidal shape 215mm long, 200mm wide with minimum distance of 37mm from wall face with concealed fittings arrangement of approved quality. Model - JAQUAR ACN-1121N or Equivalent 48 each
866 24.014 Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.Model - JAQUAR - ALD-CHR-585 or Equivalent Hand Shower (Health Faucet)(ABS Body) With 1 metre long PVC Tube & Wall Hook or Equivalent. 135 each
867 24.015 Supplying, installing, testing & commissioning at site in position soap tray by means of screws and rawl plug embedded in the walls complete including cutting and making good the walls wherever required. Model - Cera F5003106 or Equivalent 69 each
868 24.016 Supplying, installing, testing & commissioning at site in position Heavy Duty Flexible Braided Connectors, 15mm. nominal bore, 450mm. Long with higher thermal stability for cold and Hot water, for Wash Basin & Kitchen Sink Mixer and Geyser points, of approved quality. 350 each
869 24.017 Supplying, installing, testing & commissioning at site in position 15mm dia C.P Long Body brass aerator bib cocks with wall flange including cutting and making good the walls wherever required. Model - FLR-5047N- 1250 or Equivalent 98 each
870 24.018 Providing and fixing Stainless Steel A ISI 304 (18/8) Kitchen Sink as per IS: 13983 with C.I. brackets and stainless steel plug 40 mm, waste coupling including painting of fittings and brackets, cutting and making good the walls wherever required\nKitchen sink with drain board\n510x1015 mm bowl depth 200 mm Model - DIAMOND REK 4020 OR Equivalent 2 each
871 24.019 Providing and fixing Stainless Steel A ISI 304 (18/8) Kitchen Sink as per IS: 13983 with C.I. brackets and stainless steel plug 40 mm, waste coupling including painting of fittings and brackets, cutting and making good the walls wherever required\nKitchen sink without drain board\n610x510 mm bowl depth 200 mm Model - DIAMOND REK 2420 (BO) OR Equivalent 2 each
872 24.02 Providing, fixing, testing, and commissioning at site Kitchen Sink Cock with aerator, Wall Mounted Type 15mm. nominal bore, overall dimensions: 208x237mm, including all necessary accessories, all as per manufacturer's instruction and to the approval of the Engineer-in-charge. Model - JAQUAR CON-357KN or Equivalent. 10 each
873 24.021 Providing, fixing, testing, and commissioning at site Single Lever Surgical Purpose Elbow Action Sink Mixer (Wall Mounted)with aerator Extended Operating Lever, Connecting legs & wall flanges, 15mm. nominal bore, including all necessary accessories, all as per manufacturer's instruction and to the approval of the Engineer-in-charge.Model - JAQUAR FLR-5166 or Equivalent. 68 each
874 24.022 Providing and fixing C.P brass stop cock ( concealed) with exposed path of standard design and of approved make conforming to IS: 8931 15 mm nominal bore Model - JAQUAR ALD-069FT\nJAQUAR CON-069FTK or Equivalent. 38 each
875 24.023 Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet: 100 mm diametre Model - JAQUAR Shower arm SHA-477 190 mm long, Over head shower - OHS-CHR-1989 100mm dia or Equivalent 38 each
876 24.024 Supplying, installing, testing & commissioning at site in position 15 mm dia angle valve with CP wall flange etc complete Model - JAQUAR FLR 5053 N or Equivalent 510 each
877 24.025 Supplying, installing, testing & commissioning at site in position Toilet paper holder fixed to the wall by means of screws and rawl plug embedded in the walls complete including cutting and making good the walls wherever required. Model - JAQUAR ACN-1151N or Equivalent 5 each
878 24.026 Supplying, installing, testing & commissioning at site in position Grab Bar up to 600mm complete. Model - Cera. Cat.No.B2210106 or Equivalent 10 each
879 24.027 Mirror - Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P brass screws and washers complete.Saint Gobain or Equivalent 55 each
880 24.028 Soap Dispenser - Providing and Fixing Soap dispenser of standard shape with bracket of approved quality and colour.Model JAQUAR ACN-1135N 48 each
881 24.029 C. P. Robe Hook, 60mm. Dia. x 45mm. High.\nModel - JAQUAR ACN-1191N or Equivalent 160 each
882 24.03 Providing,fixing testing and commissioning Energy Efficient Storage Type Electric Water Heater, 2kw each, as per specification\nCapacity 15 Ltrs 18 each
883 24.031 Providing,fixing testing and commissioning Energy Efficient Storage Type Electric Water Heater, 2kw each, as per specification\nCapacity 25 Ltrs 3 each
884 24.032 Providing,fixing testing and commissioning Energy Efficient Storage Type Electric Water Heater, 2kw each, as per specification\nCapacity 40 Ltrs 5 each
885 24.033 Providing,fixing testing and commissioning Energy Efficient Storage Type Electric Water Heater, 2kw each, as per specification\nCapacity 60 Ltrs 4 each
886 24.034 Providing,fixing testing and commissioning 1¼"x 32x300 CP Brass Tube Trap (P Trap) for wash basin. Adjusting pipe 120mm, drain elbow 220mm. Model - Cat No: Viega 704872 or equivalent. 176 each
887 24.035 Providing,fixing testing and commissioning 1½"x 40x300 Plastic P Trap (P Trap) for Sink. Adjusting pipe 120mm, drain elbow 220mm. Model - Cat No: Viega 105952 or equivalent. 86 each
888 24.036 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type B (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Soil & Waste pipes -Internal).\n110mm OD 495 metre
889 24.037 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type B (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters, rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Soil & Waste pipes -Internal).\n75mm OD 465 metre
890 24.038 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe of 6Kg/sq.cm (IS:4985) including injection moulded fittings with bosses where required eg 90 Degree bend, 45 Degree bends, 'Y', couplings, adapters & clamping with Universal clamps/U bolt 1metre spacing, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Soil & Waste pipes -Internal).\n63 mm (IS 4985,6kgf/cm2) 270 metre
891 24.039 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe of 6Kg/sq.cm (IS:4985) including injection moulded fittings with bosses where required eg 90 Degree bend, 45 Degree bends, 'Y', couplings, adapters & clamping with Universal clamps/U bolt 1metre spacing, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Soil & Waste pipes -Internal).\n50 mm (IS 4985,6kgf/cm2) 246 metre
892 24.04 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe of 6Kg/sq.cm (IS:4985) including injection moulded fittings with bosses where required eg 90 Degree bend, 45 Degree bends, 'Y', couplings, adapters & clamping with Universal clamps 1metre spacing, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Soil & Waste pipes -Internal).\n40 mm (IS 4985,6kgf/cm2) 140 metre
893 24.041 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe of 10Kg/sq.cm (IS:4985) including injection moulded fittings with bosses where required eg 90 Degree bend, 45 Degree bends, 'Y', couplings, adapters & clamping with Universal clamps 1metre spacing, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n32 mm OD (10kg/cm2)- for sunken drain 120 metre
894 24.042 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type A (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Vent pipes -Internal).\n110mm OD 12 metre
895 24.043 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type A (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Vent pipes -Internal).\n90mm OD 12 metre
896 24.044 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type A (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Vent pipes -Internal).\n75mm OD 286 metre
897 24.045 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of 4kg/cm2 (IS:4985)including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Vent pipes -Internal).\n63mm OD 266 metre
898 24.046 Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of 4kg/cm2 (IS:4985)including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site \n(For Vent pipes -Internal).\n50mm OD 572 metre
899 24.047 Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type B(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, 'Y', bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping).\nCore Cutting in RCC Structure shall measured separately.\nClamping details - For Vertical Shafts\nG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated\nClamping details - For Suspended lines\nG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.\n160mm OD 15 metre
900 24.048 Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type B(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, 'Y', bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping).\nCore Cutting in RCC Structure shall measured separately.\nClamping details - For Vertical Shafts\nG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated\nClamping details - For Suspended lines\nG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.\n110mm OD 772 metre
901 24.049 Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type B(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, 'Y', bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping).\nCore Cutting in RCC Structure shall measured separately.\nClamping details - For Vertical Shafts\nG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated\nClamping details - For Suspended lines\nG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.\n75mm OD 672 metre
902 24.05 Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type A(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, 'Y', bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping for rainwater/Vent).\nClamping details - For Vertical Shafts\nG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated\nClamping details - For Suspended lines\nG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.\n160mm OD 40 metre
903 24.051 Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type A(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, 'Y', bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping for rainwater/Vent).\nClamping details - For Vertical Shafts\nG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated\nClamping details - For Suspended lines\nG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.\n110mm OD 820 metre
904 24.052 Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type A(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, 'Y', bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping for rainwater/Vent).\nClamping details - For Vertical Shafts\nG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated\nClamping details - For Suspended lines\nG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.\n75mm OD 296 metre
905 24.053 Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of 4kg/cm2 (IS:4985)) including jointing PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, 'Y', bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping for rainwater/Vent).\nClamping details - For Vertical Shafts\nG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated\nClamping details - For Suspended lines\nG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.\n63 mm OD(4kg/cm2) 760 metre
906 24.054 Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe of 6kg/cm2 (IS:4985)) including jointing with PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, 'Y', bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping for rainwater/Vent).\nClamping details - For Vertical Shafts\nG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated\nClamping details - For Suspended lines\nG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.\n50 mm OD(6kg/cm2) 30 metre
907 24.055 Deep Seal uPVC fabricated Multi floor trap - Providing, Fixing, testing and commissioning at site in position Deep Seal (7”) uPVC Fabricated Multi Floor Trap, with suitable supporting on GI slotted rails (1.6mmthick) full threaded rod, Anchor fasteners etc. complete in all respects - 50/75 mm dia inlet/outlet (In Ceiling) 220 each
908 24.056 uPVC fabricated Multi floor trap - Providing, Fixing, testing and commissioning at site in position uPVC Fabricated Multi Floor Trap, with thrust block support including complete cost o cutting chases and making good the walls in all respects - 50/75 mm dia inlet/outlet (In Sunken) 14 each
909 24.057 C.P. cast brass or stainless steel Square Flat cut lock anti cockroach grating cover - Providing and Fixing Heavy Duty Stainless Steel Square Flat cut lock anti Cockroach Trap Stainless Steel A ISI 304 with 153x153mm. Grating, for 110mm. Floor Traps. 401 each
910 24.058 Heavyduty stainless steel cover for Concealed Floor Trap for Urinal - Providing and Fixing 153x153mm dia Heavyduty stainless steel cover for Concealed Floor Trap ISI 304 Cover, for Urinal. 33 each
911 24.059 Heavyduty stainless steel cleanout cover - Providing and Fixing Heavy Duty Stainless Steel A ISI 304 Clean out Cover, sealed, threaded covers, including suitable insert keys for opening, if required. 25 each
912 24.06 Low noise level soil & waste system 110mm Dia - Providing, Fixing, testing Low noise level soil & waste system as per EN 12056, DIN 4109, as approved in proper line and level jointing With push fit rubber ring socket fittings complete with holder bats or dash fasteners fixed to walls or ceiling or run on floor or in trenches at require slopes and necessary special heavy Detachable Hot Dip Galvanized M.S. Brackets, Hangers, clamps and bricks / RCC pedestals as directed, including clamps, bracket, supports in MS making good walls etc. The rates for pipes shall be inclusive of all the specials, and fittings like elbow, rodding eye etc., The diametre of pipe shall be of the following nominal bore.(Pipes and fittings shall consist of polypropylene mineral reinforce with sound insulation density not less than 1.9gm/cm3). Astral Silencio shall have a B2 fire classification according to EN 4102 and shall be hot water resistant up to 95°C short term loading (90°C long term loading) with a chemical resistance of pH 2-12 and complete sound protection system according to DIN 4109. Galvanized clamps and brackets, legend boards shall be included in the price. 480 metre
913 24.061 Low noise level soil & waste system 75mm Dia - Providing, Fixing, testing Low noise level soil & waste system as per EN 12056, DIN 4109, as approved in proper line and level jointing With push fit rubber ring socket fittings complete with holder bats or dash fasteners fixed to walls or ceiling or run on floor or in trenches at require slopes and necessary special heavy Detachable Hot Dip Galvanized M.S. Brackets, hangers, clamps and bricks / RCC pedestals as directed, including clamps, bracket, supports in MS making good walls etc. The rates for pipes shall be inclusive of all the specials and fittings like elbow, rodding eye etc. The diametre of pipe shall be of the following nominal bore.(Pipes and fittings shall consist of polypropylene mineral reinforce with sound insulation density not less than 1.9gm/cm3). Astral Silencio shall have a B2 fire classification according to EN 4102 and shall be hot water resistant up to 95°C short term loading (90°C long term loading) with a chemical resistance of pH 2-12 and complete sound protection system according to DIN 4109. Galvanized clamps and brackets, legend boards shall be included in the price. 860 metre
914 24.062 Low noise level soil & waste system 50mm Dia - Providing, Fixing, testing Low noise level soil & waste system as per EN 12056, DIN 4109, as approved in proper line and level jointing With push fit rubber ring socket fittings complete with holder bats or dash fasteners fixed to walls or ceiling or run on floor or in trenches at require slopes and necessary special heavy Detachable Hot Dip Galvanized M.S. Brackets, hangers, clamps and bricks / RCC pedestals as directed, including clamps, bracket, supports in MS making good walls etc. The rates for pipes shall be inclusive of all the specials and fittings like elbow, rodding eye etc. The diametre of pipe shall be of the following nominal bore.(Pipes and fittings shall consist of polypropylene mineral reinforce with sound insulation density not less than 1.9gm/cm3). Astral Silencio shall have a B2 fire classification according to EN 4102 and shall be hot water resistant up to 95°C short term loading (90°C long term loading) with a chemical resistance of pH 2-12 and complete sound protection system according to DIN 4109. Galvanized clamps and brackets, legend boards shall be included in the price. 340 metre
915 24.063 Low noise level soil & waste system 110mm Dia - Providing, Fixing, testing Low noise level soil & waste system as per EN 12056, DIN 4109, as approved in proper line and level jointing With push fit rubber ring socket fittings complete including clamping with Position, including cutting and making good the walls and floors as required at site. The rates for pipes shall be inclusive of all the specials, and fittings like elbow, rodding eye etc., The diametre of pipe shall be of the following nominal bore.(Pipes and fittings shall consist of polypropylene mineral reinforce with sound insulation density not less than 1.9gm/cm3). Astral Silencio shall have a B2 fire classification according to EN 4102 and shall be hot water resistant up to 95°C short term loading (90°C long term loading) with a chemical resistance of pH 2-12 and complete sound protection system according to DIN 4109.\nClamping details - For Vertical Shafts\nG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ''STD Powder Coated\nClamping details - For Suspended lines\nG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete. 504 metre
916 24.064 Supplying, installing & testing at site in position Deep Seal Polypropylene floor trap (ht 7") - (sound level 13dB @4L/sec) supporting on GI slotted rails (1.6mmthick) full threaded rod, Anchor fasteners etc. with all necessary fittings of approved make. 165 each
917 24.065 Supplying, installing & testing at site in position Polypropylene P Trap - (sound level 13dB @4L/sec)of size 110mm dia of approved make for Drainage, complete with all necessary fittings of approved make as per drawings to the satisfaction of the project manager. 3 each
918 24.066 Supplying, installing, testing & commissioning at site in position 110mm dia deep seal PVC P Trap with boss tee and access cap including all necessary fittings and supports complete. 25 each
919 24.067 Providing, Fixing, Testing & Commissioning at site in position of Hubless Centrifugally Cast Iron Pipes and fittings (Epoxy coated Inside & Outside as per (IS:15905, ISO 6594) Standard and jointing with Stainless Steel Shielded (SS-304) Coupling with a double Stainless Steel bolt and screw Housing in corporating a EPDM Rubber Gasket as per IS-15905/ ASTM 1277 Standard inclusive of all necessary specials like Bends, Tees, Offset, Junctions, Cowls, End plug, Inspection Pipes, Rodding eye, etc. laid under floor / fixed on walls and in shafts. The rate shall be including suitable angle supports, Hanger, nuts, bolts, anchor fastner, fixing Clamps / Channels with U Bolt, etc. complete. Hubless Cast Iron Pipes & Fitting should have been tested for Noise level which should not more than 25dB (A) at L/s.\n(For CSSD and Laundry Drainage).100 mm dia 65 metre
920 24.068 Providing, Fixing, Testing & Commissioning at site in position of Hubless Centrifugally Cast Iron Pipes and fittings (Epoxy coated Inside & Outside as per (IS:15905, ISO 6594) Standard and jointing with Stainless Steel Shielded (SS-304) Coupling with a double Stainless Steel bolt and screw Housing in corporating a EPDM Rubber Gasket as per IS-15905/ ASTM 1277 Standard inclusive of all necessary specials like Bends, Tees, Offset, Junctions, Cowls, End plug, Inspection Pipes, Rodding eye, etc. laid under floor / fixed on walls and in shafts. The rate shall be including suitable angle supports, Hanger, nuts, bolts, anchor fastner, fixing Clamps / Channels with U Bolt, etc. complete. Hubless Cast Iron Pipes & Fitting should have been tested for Noise level which should not more than 25dB (A) at L/s.\n(For CSSD and Laundry Drainage).75 mm dia 20 metre
921 24.069 Providing, Fixing, Testing & Commissioning at site in position of Hubless Centrifugally Cast Iron Pipes and fittings (Epoxy coated Inside & Outside as per (IS:15905, ISO 6594) Standard and jointing with Stainless Steel Shielded (SS-304) Coupling with a double Stainless Steel bolt and screw Housing in corporating a EPDM Rubber Gasket as per IS-15905/ ASTM 1277 Standard inclusive of all necessary specials like Bends, Tees, Offset, Junctions, Cowls, End plug, Inspection Pipes, Rodding eye, etc. laid under floor / fixed on walls and in shafts. The rate shall be including suitable angle supports, Hanger, nuts, bolts, anchor fastner, fixing Clamps / Channels with U Bolt, etc. complete. Hubless Cast Iron Pipes & Fitting should have been tested for Noise level which should not more than 25dB (A) at L/s.\n(For CSSD and Laundry Drainage).50 mm dia 10 metre
922 24.07 Supplying & Fixing 110mm dia deep seal Cast Iron 'P' trap with access cap inside & outside as per IS:15905 Including all necessary fittings & supports complete (For CSSD and Laundry Drainage). 5 each
923 24.071 Supplying, Installing & Testing at site in position Hubless centrifugally cast (spun) iron epoxy coated Multi inlet trap inside & outside as per IS:15905 supporting on G.I. slotted rails (1.6 mm thick), Full threaded rod , Anchor Fasteners etc at site. (For CSSD and Laundry Drainage). 2 each
924 24.072 Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter\nand weighing not less than 440 grams. 26 EACH
925 24.073 Providing, fixing, pressure testing and commission Concealed Cold Water Services Pipe Work, with High Pressure uPVC Pipes, Sch. 40 (ASTM D 1785) and Sch. 40 (ASTM D 2466) Fittings, such as Elbows, Tees, Reducers, 15mm. Female Brass Threaded Elbows, Tess & Sockets, as per requirement, Sockets, Flanges, Unions, Adaptors, End Plugs etc, Pipe Supports, Fasteners, Clamps, Expansion Joints, Bolts, Washers, Nuts, Masonary Supports etc, as per requirement and site conditions, including cutting, chasing, drilling etc, in Block Walls, RCC Slabs etc, wherever required and making good walls, floors, duct etc. The Solvent Cement shall be one step for pressure pipes and fittings from the same Manufacturer. All as per Technical Specifications and to the approval of Engineer- in -Charge.\nConcealed work, including cutting chases and making good the walls etc.\n15 mm nominal outer dia. Pipes. 48 metre
926 24.074 Providing, fixing, pressure testing and commission Concealed Cold Water Services Pipe Work, with High Pressure uPVC Pipes, Sch. 40 (ASTM D 1785) and Sch. 40 (ASTM D 2466) Fittings, such as Elbows, Tees, Reducers, 15mm. Female Brass Threaded Elbows, Tess & Sockets, as per requirement, Sockets, Flanges, Unions, Adaptors, End Plugs etc, Pipe Supports, Fasteners, Clamps, Expansion Joints, Bolts, Washers, Nuts, Masonary Supports etc, as per requirement and site conditions, including cutting, chasing, drilling etc, in Block Walls, RCC Slabs etc, wherever required and making good walls, floors, duct etc. The Solvent Cement shall be one step for pressure pipes and fittings from the same Manufacturer. All as per Technical Specifications and to the approval of Engineer- in -Charge.\nConcealed work, including cutting chases and making good the walls etc.\n20 mm nominal outer dia. Pipes. 1842 metre
927 24.075 Providing, fixing, pressure testing and commission Concealed Cold Water Services Pipe Work, with High Pressure uPVC Pipes, Sch. 40 (ASTM D 1785) and Sch. 40 (ASTM D 2466) Fittings, such as Elbows, Tees, Reducers, 15mm. Female Brass Threaded Elbows, Tess & Sockets, as per requirement, Sockets, Flanges, Unions, Adaptors, End Plugs etc, Pipe Supports, Fasteners, Clamps, Expansion Joints, Bolts, Washers, Nuts, Masonary Supports etc, as per requirement and site conditions, including cutting, chasing, drilling etc, in Block Walls, RCC Slabs etc, wherever required and making good walls, floors, duct etc. The Solvent Cement shall be one step for pressure pipes and fittings from the same Manufacturer. All as per Technical Specifications and to the approval of Engineer- in -Charge.\nConcealed work, including cutting chases and making good the walls etc.\n25 mm nominal outer dia. Pipes. 30 metre
928 24.076 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge.\nConcealed work, including cutting chases and making good the walls etc.\n15 mm nominal outer dia. Pipes. 60 metre
929 24.077 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge.\nConcealed work, including cutting chases and making good the walls etc.\n20 mm nominal outer dia. Pipes. 504 metre
930 24.078 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge.\nConcealed work, including cutting chases and making good the walls etc.\n25 mm nominal outer dia. Pipes. 30 metre
931 24.079 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n15 mm nominal outer dia. Pipes. 546 metre
932 24.08 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n20 mm nominal outer dia. Pipes. 294 metre
933 24.081 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n25 mm nominal outer dia. Pipes. 96 metre
934 24.082 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n32 mm nominal outer dia. Pipes. 8 metre
935 24.083 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n15 mm nominal outer dia. Pipes. 40 metre
936 24.084 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n20 mm nominal outer dia. Pipes. 1878 metre
937 24.085 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n25 mm nominal outer dia. Pipes. 630 metre
938 24.086 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n32 mm nominal outer dia. Pipes. 324 metre
939 24.087 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n40 mm nominal outer dia. Pipes. 180 metre
940 24.088 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n50 mm nominal outer dia. Pipes. 95 metre
941 24.089 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n65 mm nominal outer dia. Pipes. 80 metre
942 24.09 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n80 mm nominal outer dia. Pipes. 20 metre
943 24.091 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n100 mm nominal outer dia. Pipes. 36 metre
944 24.092 Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n65 mm nominal outer dia. Pipes. 108 metre
945 24.093 Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n80 mm nominal outer dia. Pipes. 36 metre
946 24.094 Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n100 mm nominal outer dia. Pipes. 12 metre
947 24.095 Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall - Ceiling and Shaft\n150 mm nominal outer dia. Pipes. 6 metre
948 24.096 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(9mm thick) for the hot water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n15 mm 10 metre
949 24.097 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(9mm thick) for the hot water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n20 mm 126 metre
950 24.098 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(9mm thick) for the hot water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n25mm 24 metre
951 24.099 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(19mm thick) for the Terrace cold water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n20 mm 42 metre
952 24.1 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(19mm thick) for the Terrace cold water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n25 mm 42 metre
953 24.101 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(19mm thick) for the Terrace cold water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n32 mm 32 metre
954 24.102 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(19mm thick) for the Terrace cold water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n40 mm 58 metre
955 24.103 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(19mm thick) for the Terrace cold water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n50 mm 312 metre
956 24.104 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(19mm thick) for the Terrace cold water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n65 mm 60 metre
957 24.105 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(19mm thick) for the Terrace cold water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n80 mm 402 metre
958 24.106 Supplying, Installing & Testing at site in position micro cellular closed cell Nitrile rubber elastomeric insulation (UL-94 Approved) tubes/ sheets(19mm thick) for the Terrace cold water supply pipes with protective glass fabric & co-extruded polymeric covering for UV & mechanical protection. \n100 mm 86 metre
959 24.107 Brass ball valve 15mm dia - Providing, Fixing at site in position full way lever operated forged Brass ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawing - ½” (15mm) dia 10 each
960 24.108 Brass ball valve 20mm dia - Providing, Fixing at site in position full way lever operated forged Brass ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawing - ¾” (20mm) dia 383 each
961 24.109 Brass ball valve 25mm dia - Providing, Fixing at site in position full way lever operated forged Brass ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawing - 1” (25mm) dia 42 each
962 24.11 Brass ball valve 32mm dia - Providing, Fixing at site in position full way lever operated forged Brass ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawing - 1¼”(32mm) dia 31 each
963 24.111 Brass ball valve 40mm dia - Providing, Fixing at site in position full way lever operated forged Brass ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawing - 1 ½”(40mm) dia 11 each
964 24.112 Brass ball valve 50mm dia - Providing, Fixing at site in position full way lever operated forged Brass ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawing - 2” (50mm) dia 13 each
965 24.113 Non Return Valves 1¼”(32mm) dia - Supplying, Installing & Testing at site in position spring loaded Brass Non Return Valve (PN-16) screw type with necessary fittings complete in all respect. 1 each
966 24.114 Non Return Valves 1 ½” (40mm) dia - Supplying, Installing & Testing at site in position spring loaded Brass Non Return Valve (PN-16) screw type with necessary fittings complete in all respect. 2 each
967 24.115 Non Return Valves 2” (50mm) dia - Supplying, Installing & Testing at site in position spring loaded Brass Non Return Valve (PN-16) screw type with necessary fittings complete in all respect. 2 each
968 24.116 Non Return Valves 2 ½” (65mm) dia - Supplying, Installing & Testing at site in position spring loaded Brass Non Return Valve (PN-16) screw type with necessary fittings complete in all respect. 8 each
969 24.117 Brass Automatic Air Release Valves - Providing, Fixing, testing and commissioning at site in positions Brass Automatic Air Release Valves, of approved quality and make on the top of the vertical water supply pipes as per specification and drawing - 3/4"(20mm) dia 62 each
970 24.118 Brass Y Strainer 1 ½” (40mm) dia - Supply,Installation,Testing and Commisioning of CI Y-type stainer with drain plug, SS screen 304 complete in all respects - 1 each
971 24.119 Brass Y Strainer 3” (80mm) dia - Supply,Installation,Testing and Commisioning of CI Y-type stainer with drain plug, SS screen 304 complete in all respects - 2 each
972 24.12 Brass Y Strainer 4” (100mm) dia - Supply,Installation,Testing and Commisioning of CI Y-type stainer with drain plug, SS screen 304 complete in all respects - 1 each
973 24.121 Supplying, Installing & Testing at site in position Brass Float valve (PN 16) of approved make with PP float & nipple with brass threaded insert, brass back nuts, piston and bolts etc complete in all respect to the satisfaction of Project Manager. 40mm dia (1 ½”) 2 Each
974 24.122 SS ball valve 15mm dia - Providing, Fixing at site in position full way lever operated forged SS ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings. - ½” (15mm) dia 5 each
975 24.123 SS ball valve 20mm dia - Providing, Fixing at site in position full way lever operated forged SS ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings. - ¾” (20mm) dia 46 each
976 24.124 SS ball valve 25mm dia - Providing, Fixing at site in position full way lever operated forged SS ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings. - 1” (25mm) dia 8 each
977 24.125 SS ball valve 32mm dia - Providing, Fixing at site in position full way lever operated forged SS ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings. - 1 1/4” (32mm) dia 5 each
978 24.126 SS ball valve 40mm dia - Providing, Fixing at site in position full way lever operated forged SS ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings. - 1 1/2” (40mm) dia 2 each
979 24.127 SS ball valve 50mm dia - Providing, Fixing at site in position full way lever operated forged SS ball valve (screwed end)of brass body with forged brass hard chrome plate (PN 10) of approved make with necessary MTA fittings in position as per drawings. - 2” (50mm) dia 3 each
980 24.128 Providing and fixing C.I. Sluice Valve, PN-16, with IS: 14846 Mark, with required flanges, rubber insertions, bolts, nuts, Washers etc. complete. 100mm. PN-16 1 each
981 24.129 CI Butterfly valve 250mm dia (PN 10) - Providing, Fixing at site in position CI Butterfly valve (PN 10) wafer type of approved make with necessary PVC flanges, gaskets, nuts and bolts etc complete within position as per drawing - 10”(250mm) dia 2 each
982 24.13 Providing and Fixing Ball Type Foot Valve. PN 10, with Cast Iron Body Nitrile Reinforced Ball, Screwed End, required in the Suction Lines of for Water Transfer and Distribution Pumps.65mm. 1 each
983 24.131 Providing and Fixing Ball Type Foot Valve. PN 10, with Cast Iron Body Nitrile Reinforced Ball, Screwed End, required in the Suction Lines of for Water Transfer and Distribution Pumps.50mm. 3 each
984 24.132 Supplying, installing,Testing & commissioning at site in position Multi Jet Water meter with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser,retrofitable for pulse output and conforming to ISO-4064 Class B complete. Water meter 40mm 3 each
985 24.133 CI Butterfly valve 65mm dia (PN 10) - Providing, Fixing at site in position CI Butterfly valve (PN 10) wafer type of approved make with necessary PVC flanges, gaskets, nuts and bolts etc complete within position as per drawing - 2 ½”(65mm) dia 23 each
986 24.134 CI Butterfly valve 80mm dia (PN 10) - Providing, Fixing at site in position CI Butterfly valve (PN 10) wafer type of approved make with necessary PVC flanges, gaskets, nuts and bolts etc complete within position as per drawing - 3”(80mm) dia 11 each
987 24.135 CI Butterfly valve 100mm dia (PN 10) - Providing, Fixing at site in position CI Butterfly valve (PN 10) wafer type of approved make with necessary PVC flanges, gaskets, nuts and bolts etc complete within position as per drawing - 4”(100mm) dia 6 each
988 24.136 CI Butterfly valve 150mm dia (PN 10) - Providing, Fixing at site in position CI Butterfly valve (PN 10) wafer type of approved make with necessary PVC flanges, gaskets, nuts and bolts etc complete within position as per drawing - 6”(150mm) dia 2 each
989 24.137 SS Butterfly valve 65mm dia (PN 16) - Providing, Fixing at site in position SS Butterfly valve (PN 16) wafer type of approved make with necessary PVC flanges, gaskets, nuts and bolts etc complete within position as per drawing - 2 ½”(65mm) dia 2 each
990 24.138 Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation to the specified hydrostatic test pressure including Supplying Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for building drainage) complete\n200mm OD 36 metre
991 24.139 Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation to the specified hydrostatic test pressure including Supplying Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for building drainage) complete\n160mm OD 1356 metre
992 24.14 Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation to the specified hydrostatic test pressure including Supplying Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for building drainage) complete\n110mm OD 366 metre
993 24.141 Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation to the specified hydrostatic test pressure including Supplying Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for building drainage) complete\n75mm OD 180 metre
994 24.142 Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(4kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation to the specified hydrostatic test pressure including Supplying Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for rain water pipes) complete\n250mm OD 132 metre
995 24.143 Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(4kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation to the specified hydrostatic test pressure including Supplying Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for rain water pipes) complete\n200mm OD 72 metre
996 24.144 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.\nExternal work (Including excavation)\n20 mm nominal outer dia Pipes 75 metre
997 24.145 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.\nExternal work (Including excavation)\n25 mm nominal outer dia Pipes 50 metre
998 24.146 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.\nExternal work (Including excavation)\n32 mm nominal outer dia Pipes 100 metre
999 24.147 Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.\nExternal work (Including excavation)\n40 mm nominal outer dia Pipes 50 metre
1000 24.148 Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.\nExternal work (Including excavation)\n50 mm nominal outer dia Pipes 372 metre
1001 24.149 Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.\nExternal work (Including excavation)\n65 mm nominal outer dia Pipes 390 metre
1002 24.15 Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.\nExternal work (Including excavation)\n80 mm nominal outer dia Pipes 204 metre
1003 24.151 Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.\nExternal work (Including excavation)\n100 mm nominal outer dia Pipes 6 metre
1004 24.152 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : \nInside size 60x60 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :\nWith Sewer bricks conforming to IS : 4885 5 each
1005 24.153 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement: 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand)finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :\nWith Sewer bricks conforming to IS : 4885 39 each
1006 24.154 Extra for depth for manholes : \nSize 90x80 cm\nWith Sewer bricks conforming to IS : 4885 17 metre
1007 24.155 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand) with R.C.C. top with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size,) inside plastering 12 mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) finished with a floating coat of neat cement complete as per standard design:\nInside size 120x 90 cm and 90 cm deep including C.I. cover with frame ( heavy duty ) 560 mm internal diameter, total weight of cover and frame to be not less than 208 kg ( weight of cover 108 kg and weight of frame 100 kg)\nWith Sewer bricks conforming to IS: 4885 34 each
1008 24.156 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand) with R.C.C. top with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size,) inside plastering 12 mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) finished with a floating coat of neat cement complete as per standard design:\nInside size 120x90 cm and 90 cm deep including C.I. cover with frame ( medium duty ) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg ( weight of cover 58 kg and weight of frame 58 kg):\nWith Sewer bricks conforming to IS : 4885 2 each
1009 24.157 Supply,installation, testing and commissioning of stainless steel coarse Screen (opening 10mm) suitable for screen chamber of size 1.00mx1.50m including all material charges,labour transportation,loading unloading etc. Complete as per the direction of Engineer in charge. 2 No
1010 24.158 Extra for depth for manholes\nSize 120x90 cm\nWith Sewer bricks conforming to IS : 4885 13 metre
1011 24.159 Constructing brick masonry circular type manhole 0.91 m internal dia at bottam and 0.56 m dia at to[ in cement mortar 1:4 (1 cement : 4 coarse sand), in side cement plaster 12 mm thick with cement mortar 1:3 ( 1 cement: 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix ( 1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size ), and making necessary channel in cement concrete 1:2:4 ( 1 cement:2 coarse sand: 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design:\nWith Sewer bricks conforming to IS:4885 10 each
1012 24.16 Extra depth circular type manhole 0.91 m internal dia ( at bottom) beyound 0.91 m to 1.67 m\nWith Sewer bricks conforming IS: 4885 7.6 metre
1013 24.161 Constructing brick masonry circular manhole 1.22 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 ( 1 cement: 4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 ( 1 cement: 3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 ( 1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design:\n1.68 m deep with SFRC cover and frame (heavy duty Hd- 20 grade designation)\n560 mm internal diameter conforming to IS: 12592, total weight of cover and frame to be not less than 182 kg fixed in cement concrete 1:2:4 ( 1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. ( Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately)\nWith sewer bricks conforming IS:4885 15 each
1014 24.162 Extra depth for circular type manhole 1.22 m internal dia (at bottom) beyond 1.68 m to 2.29 m:\nWith sewer bricks conforming IS:4885 9 metre
1015 24.163 Constructing brick masonry circular manhole 1.52 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement:4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 (1 cement:3 coarse sand: 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement:2 coarse sand: 4 graded stone aggregate 20 mm nominal size)finished with a floating coat of neat cement, all complete as per standard design:\n2.30 m deep with SFRC cover and frame (heavy duty HD - 20 grade designation)\n560 mm internal diameter conforming to IS:12592, total weight of cover and frame to be not less than 182 kg fixed in cement concrete 1:2:4 ( 1 cement:2 coarse sand: 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately):\nWith sewer bricks conforming IS:4885 3 each
1016 24.164 Extra depth for circular type manhole 1.52 m internal dia (at bottom) beyond 2.30 m:\nWith Sewer bricks conforming IS: 4885 2 metre
1017 24.165 Supplying, Installing & Testing at site in position best quality PVC gully trap of size 160 X110mm outlet  embedded in plain cement concrete 1:4:8 (20mm metal),  all the above encased in a chamber of 300 X 300mm built with 115mm thick brick masonry using first class country bricks in CM 1:3 over  a bed  of CC 1:4:8 using  40mm size metal 100mm thick ,plastering  with CM1:3,13mm thick inside, outside, exposed top surfaces and internal and top exposed surface finished smooth with a floating coat of neat cement, providing and fixing Ductile Iron(Hinged type) frame and cover of size 300 X 300mm weighing  not less than 8 kgs   load tested as per IS:1726  fixing the frame in PCC 1:2:4 using 20mm stone metal including painting the frame and cover with 2 coats of anticorrosive black bitumastic painting etc. complete all as specified and directed. 42 EACH
1018 24.166 Constructing masonry chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for stop cock, with C.I. surface box 100x100x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 \n(1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:\nWith common burnt clay F.P.S (non modular) bricks of class designation 7.5 17 EACH
1019 24.167 Constructing masonry chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement:4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 ( 1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:\nWith common burnt clay F.P.S (non modular) bricks of class designation 7.5 5 EACH
1020 24.168 Constructing masonry chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 \n(1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 1 EACH
1021 24.169 Constructing masonry chamber 120x120x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix ( 1 cement : 2 coarse sand : 4 grades stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 ( 1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:\nWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5 1 EACH
1022 24.17 Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12 mm dia steeel bar conforming to IS:1786, having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufactures permanent identification mark to be visible even after fixing including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1cement: 3 coarse sand: 6 graded stone aggregate 20 mm nominal size)\nComplete as per design 100 no
1023 24.171 Excavating trenches of required width for pipes, including excavation for sockets, depth up to 1.5 m, including getting out the excavated materials, returning the soil as required in layers not exceeding 20 cm in depth, including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, within a lead of 50 m :\nIn all kinds of Soil\nPipes and cables not exceeding 80 mm dia. 180 metre
1024 24.172 Excavating trenches of required width for pipes, including excavation for sockets, depth up to 1.5 m, including getting out the excavated materials, returning the soil as required in layers not exceeding 20 cm in depth, including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, within a lead of 50 m :\nIn all kinds of Soil\nPipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia 1962 Metre
1025 24.173 Extra for excavating trenches for pipes above 80mm. But not exceeding 300mm.. in all kinds of soil for depth exceeding 1.5 m, but not exceeding 3 m. (Rate is over corresponding basic item for depth up to 1.5 metre). 120 Metre
1026 24.174 Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work : \nSub analysis item for sand filling component 90 cum
1027 24.175 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:5:10 (1 cement : 5 coarse sand (zone-III): 10 graded stone aggregate 40 mm nominal size).Around under ground UPVC pipes. 150 cum
1028 24.176 Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick - 160mm dia. 4 each
1029 24.177 Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick - 110mm dia. 636 each
1030 24.178 Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick - 75mm dia. 30 each
1031 24.179 Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick - 50mm dia. 250 each
1032 24.18 Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick - 40mm dia. 100 each
1033 24.181 Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick - 32mm dia. 151 each
1034 24.182 600 X 600 mm (24" X 24") inside using self pigmented type double seal (Air & Water tight) FRP manhole cover and frame Light Duty (5 MT) with closed bottom (not thru & thru) lifting key holes & load tested as per IS:1726 & BS EN:124.\nFor OH Water tank 4 each
1035 24.183 600 X 900 mm (24" X 36") inside using self pigmented type double seal (Air & Water tight) FRP manhole cover and frame Heavy Duty (20 MT) with closed bottom (not thru & thru) lifting key holes & load tested as per IS:1726 & BS EN:124.\nFor UG Sump 7 each
1036 24.184 600 X 600 mm (24" X 24") inside using self pigmented type double seal (Air & Water tight) FRP manhole cover and frame Heavy Duty (20 MT) with closed bottom (not thru & thru) lifting key holes & load tested as per IS:1726 & BS EN:124.\nFor UG Sump 6 each
1037 24.185 Supplying, Installing & Testing at site in position Fabricated 150mm (6")uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. - 150mm(6") uPVC Astm Sch 80 Puddle flange 4 each
1038 24.186 Supplying, Installing & Testing at site in position Fabricated 100mm (4")uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. - 100mm(4") uPVC Astm Sch 80 Puddle flange 10 each
1039 24.187 Supplying, Installing & Testing at site in position Fabricated 80mm (3")uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. - 80mm(3") uPVC Astm Sch 80 Puddle flange 6 each
1040 24.188 Supplying, Installing & Testing at site in position Fabricated 65mm (2½") uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. - 65mm (2½") uPVC Astm Sch 80 Puddle flange 10 each
1041 24.189 Supplying, Installing & Testing at site in position Fabricated 50mm (2")uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. - 50mm(2") uPVC Astm Sch 80 Puddle flange 3 each
1042 24.19 Supplying, Installing & Testing at site in position Fabricated 40mm (1½")uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. -40mm (1½")uPVC Astm Sch 80 Puddle flange 2 each
1043 24.191 Supplying, Installing & Testing at site in position Fabricated 32mm (1¼")uPVC Astm Sch 80 Puddle flange in the overhead water tanks as per the drawings and the requirement of the Project Manager. - 32mm 1¼"uPVC Astm Sch 80 Puddle flange 1 each
1044 24.192 Vertical multi stage centrifugal pumps (surface pump) for Domestic Water Supply - Providing, Fixing, Testing and Commissioning 2 nos, Vertical multi stage centrifugal pumps (surface pump) set, having SS/Bronze Impeller, Shafts and CI casing, Mechanical Seal Each pumps should be capable to deliver 12 lps @ 60mtr head, Head range 40 to 75mtrs (14.5 lps to 7.08 lps), with 9.3kW/12.5 HP'' F'' class motor, with motor efficiency more than 85% with Wall mounting Microprocessor based common control Panel to operate the pumpset as ( 1W + 1S ) having features of automatic pump change over in every Start/Stop, Dry run , Overload, Phase Reversal Protections etc. level controller for Auto Start/ Stop Function , Digital display , Float Switches, Auto/Manuel Operation . The total system shall be assembled and tested at factory as per the duty conditions. (For Domestic Water from sump to OHT)\nBrand Grundfos OR Equivalent 1 Set
1045 24.193 Providing, Fixing, Testing and Commission Pressure Booster Flushing Water Distribution System with Factory Assembled Packaged Pump Set, Suitable for Negative Suction for Pumping Raw Water from a Depth of 4 Mtr, complete with 3 Vertical Multistage Inline Pumps, with S. S Impeller and S. S Shafts, One Working, One Assist and 1 Stand by Pumps, each of Capacity: 14.5M3 / Hr @ 50 Mtr. Head, each, with 3.7 / 4.0kW, 3Ph, IE3 Rated Electric Motors, complete with VFD Drive, Automatic Microprocessor Based Control Panel, Pressure Transducer Sensors, Pressure Gauges, 200Ltr. Diaphragm Pressure Vessel, Individual Suction Lines, Common Delivery Manifolds, Isolating Valves, Non Return Valves, Fittings, Accessories etc, all a on common frame. . etc, all a on common frame. The Quoted Price for the Pump Set shall be inclusive of connected Electrical Work, all as per Technical Specifications.\nEach Pump Shall be capable of working with Negative Suction for Pumping Raw Water from a Depth of 4 Mtr, The Manufacturer can decide the Pumps accordingly.Brand Grundfos OR Equivalent 1 Set
1046 24.194 Sewage Solid handling pumps - Supply, installing, testing and commissioning of Submersible non clog Sewage Solid handling pumps. Control Panel for Controlling 2 Pumps, having SS: Shaft and CI Casing, impeller, Each pumps should be capable to deliver 5 lps @ 8mtr head for each pump, solid handling 50mm with 1.11kW/1.5HP with Wall mounting Microprocessor based common control Panel to operate the pumpset as ( 1W + 1S ) having features of Cyclic Timer for Cascading Operation and Float Switch/Probe Suitable for Automatic Operation. The Panel should have the following Protection for Single Phase Prevention, Over Load Protection, Over /Under Voltage Protection, Dry Running Protection, Transient Surge Protection, with Auto/Manual Operation & Auto coupling . The Enclosure should be of IP 55 standards. The Panel should have BMS compatible thro RS 485 Communication( Modbus). (For Medical Waste Tranfer Pump)\nBrand Grundfos OR Equivalent 2 Set
1047 24.195 Sewage Solid handling pumps - Supply, installing, testing and commissioning of Submersible non clog Sewage Solid handling pumps. Control Panel for Controlling 2 Pumps, having SS: Shaft and CI Casing, impeller, Each pumps should be capable to deliver 4 lps @ 8mtr head for each pump, solid handling 50mm with 1.11kW/1.5HP with Wall mounting Microprocessor based common control Panel to operate the pumpset as ( 1W + 1S ) having features of Cyclic Timer for Cascading Operation and Float Switch/Probe Suitable for Automatic Operation. The Panel should have the following Protection for Single Phase Prevention, Over Load Protection, Over /Under Voltage Protection, Dry Running Protection, Transient Surge Protection, with Auto/Manual Operation & Auto coupling . The Enclosure should be of IP 55 standards. The Panel should have BMS compatible thro RS 485 Communication( Modbus). (For Medical Waste Tranfer Pump)\nBrand Grundfos OR Equivalent 1 Set
1048 24.196 FILTER FEED PUMP SET.\nProviding, Fixing, Testing and Commission Filter Feed Pump Set, Submersible Type for Pumping Raw Water to Water Treatment Plant, 2 Pump System with One Working + 1 One Cyclically Stand by Pumps, each Pump of Capacity: 20M3 / Hr. @ 45Mtr. Head, each, with 5.5kW, 3Ph, IE3 Rated Electric Motors, complete with Microprocessor Based Control Panel, for Auto and Cyclic Operation, with all Protection (Digital display, Low &high voltage protection, dry run, phase reversal, pump over load, etc.), Level Sensors / Float Switches in Treated Water & Raw Water Tanks and Control Cabling / Wiring between Level Sensors / Float Switches and Control Panel, Delivery Manifold, Isolating Valves, Non Return valves, Pressure Gauge, Fittings, Stainless Steel (Grade:304) Lifting Chains, Accessories etc. all as per Technical Specifications.\nThe Control Panel shall be capable operating the pumps (starts and stops) by sensing the level difference in water in the Treated Water Tank. Also; capable of ‘not starting or stopping the running pumps', when the water in the underground Raw Water Tank goes below the pre-set minimum level. \nThe Pumps to be installed in the Underground Raw Water Tank and Common Control Panel in the Pump Room, in Basement Floor, approx. 100 Mtr. away from Raw Water Tank. The Underground Power Cabling between Pumps and Control Panel and Control Cabling between Control Panel & Level Sensor / Float Switch, in the Underground Raw Water Tank, shall be measured as a part of Electrical Work. The Quoted Price for the Pump Set shall be inclusive of all above requirement, necessary Level Sensors / Float Switches, Power Cabling, Control Cabling etc, except what measured as a part of Electrical Work, as detailed above. 1 Set
1049 24.197 Providing, Fixing, Testing and Commission Submersible Type Storm Water Transfer Dewatering Pump Set, complete set with 1 working + 1 Standby Submersible non- clog pump , Solids handling: 40mm , and with Common Control Panel for auto and cyclic operation. Capacity 12 M3/Hr. at 10 Mtrs. head, each, with 1.0 / 1.1KW, Single / Three Phase (all as per selection of pump without change in minimum duty conditions), with float switches/level sensors etc. necessary control valves, fittings and accessories, for discharging rain water from collection pits in basement floor, to lower strata. The price shall inclusive of all connected electrical work as detailed in the technical specification. For Pump Room 1 Set
1050 24.198 Supply, Installation, testing and commission Water Pre-Treatment Plant Capacity: 20M3 /Hr, for continuous operation of 10 Hr, complete with High Pressure Sand Filter, Activated Carbon Filter,with Multiport valves, Chemical Dosing etc as per final requirement, connected Pipe Work etc, all as per Technical Specifications.Filter Feed Pumps shall be measured seperately. 1 Set
1051 24.199 Supply installation, testing and commissioning of Sewage Treatment Plant of 300 KLD capacity \n(Detailed Technical Specification Attached)\n 1 Set
Disclaimer :