Public Works Department-PWD has published Tender For Repair Maintenance Of Of Central Air Conditioner Plant Package Units At Ddu Hospital Hari Nagar New Delhi Sh Replacement Of Duct , Diffuser In Labour Room And Gayne Emergency Ot Area. Submission Date for this Tender is 18-03-2020. HVAC Tenders in dduh Delhi. Bidders can get complete Tender details and download the document.
Name of Work: RMO of Central AC Plant /package units at DDU Hospital Hari Nagar NEW Delhi SH:Replacement of Duct, diffuser in Labour Room and Gayne Emergency OT Area | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. | |||
2 | 1.1 | Thickness 0.80 mm sheet | 100 | sq.mtrs | |
3 | 1.2 | Thickness 0.63 mm sheet | 70 | sq.mtrs | |
4 | 2 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. | 10 | sq.mtrs | |
5 | 3 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. | 8 | sq.mtrs | |
6 | 4 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & emovable core | 8 | sq.mtrs | |
7 | 5 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core. | 5 | sq.mtrs | |
8 | 6 | Supplying and fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.\n(a) 19mm\n | 170 | sq.mtrs | |
9 | 7 | Dismantling of GSS sheet metal rectangular/round ducting, grill and Difuser complete etc as required and submitted to JE Store. | 150 | sq.mtrs | |
10 | 8 | Supplying/Replacement of following Defective accessories in the existing chiller/condenser pump starter i/c modification of the existing bus bar i/c connection wiring & dismantling credit/buy back of old etc as reqd. | |||
11 | 8.1 | MNX70. (Make: L&T Model MNX70) | 3 | nos | |
12 | 8.2 | MNX18. (Make: L&T Model MNX70) | 2 | nos | |
13 | 8.3 | ML 1.5 Contactor (2 NO + 2 NC) 3 Pole Power Contactor | 3 | nos | |
14 | 8.4 | Over load relay 6-10 Amp | 2 | nos | |
15 | 9 | Providing and fixing following rating and breaking capacity and pole MCCB with thermo magnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, i/c dismantling and credit buy back of old etc. as required.\n(a) 100 A,16KA,TPMCCB\n | 3 | nos | |
16 | 10 | Supply and Replacement of following parts in the existing starter i/c dismantling, re-fixing installation testing and commissioning etc. as required including control wiring for the starter complete etc. as required.\n\n(a) Single Phase Preventer (Make minilac, Model No. VSP-2)\n | 12 | nos | |
17 | 11 | Rewinding of following size three phase induction motor running on 1440 RPM of the existing AHU with the copper wire of appropriate size and approved quality including cutting the existing winding wire, reassembling of motor after winding ,replacement of bearings all screws, nuts and bolts etc. as required including buy back of burnt copper wire.\n(a)20 HP\n | 1 | job |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail