Defence Statutory Bodies & Commissions/Committees Closing in 0 days TDR #23183745

Comprehensive Maintenance Of Fire Fighting System And Repair/Maintenance Of Fire Detection , Alarm Systems At Af Stn Maharajpur

Issued by Statutory Bodies & Commissions/Committees · GE(AF) TECH AREA MAHARAJPUR, Madhya Pradesh
Tender Value
24.50 Lakhs
Estimated cost
Bid Submission
07 Feb 2020
0 days left
EMD
49000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
GE(AF) TECH AREA MAHARAJPUR → Madhya Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Comprehensive Maintenance Of Fire Fighting System And Repair/Maintenance Of Fire Detection , Alarm Systems At Af Stn Maharajpur

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 01-Feb-2020 Critical dates Date 07-Feb-2020

BOQ

NAME OF WORK : COMPREHENSIVE MAINT OF FIRE FIGHTING SYSTEM AND REPAIR/ MAINT OF FIRE DETECTION, ALARM SYSTEMS AT AF STN MAHARAJPUR
Sl.No.Item DescriptionItem Code / MakeQuantityUnits
11Carrying out comprehensive maintenance of fire fighting system CO2 flood type of existing model & of make Fire-bell (fire fighting system, installed at ETB and fire alarm system with connected control wiring & panel at AF Station Maharajpur Gwalior) all as directed in order to maintain the fire fighting plants in functional and serviceable conditions complete all as specified and directed.\n(Note:- The following scope of work includes for item above:-\n(i) The entire system shall be inspected & checked by the qualified technician at a interval of approx 5 to 6 months or as and when for cheking of serviceability and comprehensive maint of parts by repairing or replacement to mainteain system serviceable directed by Engr-in-Charge. The replaced parts, control wiring, gas charging, distilled water & acid shall be measured and paid for separately as ‘Supply/filling only’ except pipe under respective item of this Schedule but fixing & testing etc is deemed to be included in the rate quoted against this item.\n(ii) All MS pipe line shall be inspected with respect to sefety purpose etc.\n(iii) Checking of the high pressure flexible hose pipes complete with connectors/adopters for CO2 connection to manifold as well as for pneumatic line between cylinders etc. \n(iv) Cleaning, oiling/greasing, servicing /overhauling of complete valves & fittings/assemblies. \n(v) Checking of the high pressure seamless cylinders of CO2 / N2 for their weight etc. and refilling of gas if found 10% less than the gross weight.\n(vi) Cleaning, oiling/greasing, servicing /overhauling of complete valves pneumatic actuator / valve of CO2 cylinders & fittings/assemblies. \n(vii) Checking of Non return valve of manifold and discharge hose and Cleaning, oiling/greasing, servicing /overhauling of valves.\n(viii) Cleaning, oiling/greasing, servicing /overhauling of all the nozzles of CO2 cylinders. \n2Each job
21.01(ix) All the manual call points and electronic hooters to be checked for normal functioning.\n(x) Checking of pressure release valve and Cleaning, oiling/greasing, servicing /overhauling of valves.\n(xi) All main fire control panel including battery & filling of distilled water/acid, smoke detectors, temperature heat detectors, connected control wiring etc. to be checked for normal functioning.\n(xii) During six month period any parts replaced earlier or other part be come deffective, labour for replacement of parts shall be deemed to be included in quoted rates but items shall be paid separately except item replaced earlier which shall be replaced free of cost.
32Carrying out Periodical servicing at interval of 5 to 6 months,Testing of fire alarm system complete Conventional / Addressable at New ATC building single or multi stories having many No of detectors and accessories controled through one or more control panels of any loop for functiong of the purpose installed with all accessories, such as MCP, Hooter, Detectors/ pipe line etc for finding out defects if any or its serviceability complete all as specified and directed. (i) Functionally test will be Carried Out before and after repair of the System .2Each Job
43All as per item no.2.00 above but at CEO complex all as directed by Eng-in-Charge.2Each Job
54All as per item no.2 .00above but at WSMT all as directed by Eng-in-Charge.2Each Job
65All as per item no.2.00 above but at Old & New 10 tetra sc hool all as directed by Eng-in-Charge.2Each Job
76All as per item no.2.00 above but at 26 MMPU all as directed by Eng-in-Charge.2Each Job
87Carring out Comprehensive Maint of fire fighting system at DWR/NEW ATC/24 MMPU including necessary testing as per fire fighting noms having one electric pumping set 60 HP , one No. of Diesel engine driven pumping set 2200 LPM and one no jokey pump of 15 HP 3 Phase having one control panel , interlock with each other in opration as per fire fighting System connected to sprinklar System , External fire hydrant system and controlled with fire detuction system . The scope of work is as under :- (i) Checking the functionally System of fire pumping set (02 Nos ) if any fault rectly fault either of mechanically , electrically including material of any type to Make functional in all respect as per fire fighting norms . (ii) Genral servicing of pumping sets including oiling , greasing etc. (iii) Genral servicing of sluice valves , nonreturn valves etc. (iv) Genral servicing of fire hydrant system . (v) Servicing of Diesel engine with replacement of oil filter , Diesel filter , engine oil , electrolyte etc . \n(vi) Cleaning & servicing of radiator. (vii) Reparing of foot valves etc including nut bolt and washers , automatically / mannually and making panel automatic functionally of all three pumping sets including necesssary repaired materials / controls . (viii) Repair of Electric panel for its functioning. Note :- The work shall be carried out at various locations at AF Station .2Each Job
98Material and labour for flushing out the complete pipe system from Co2 bank to gas nozzles with the adequate pressure of Nitrogen gas including taking out, opening and cleaning of nozzle complete all as specified and directed.4Each Job
109M&L including filling of CO2 gas 22.5 Kg in existing empty high pressure seamless cylinders having 22.5 Kgs capacity after carrying to authorized filling station of CO2 gas and fixing back to the plant complete all as specified and directed.\nNote: Cylinder shall be affixed with lamintated sticker of size not less than 100mmX75mm compresing details of cylinder i.e. Tare wt of cylinder, Nett wt. or filled gas & date.110Kg
1110Supply CO2 gas cylinder seam less of capacity 22.5 kg or nearest higher size conferming to relevent of IS with control , valves etc duly filled with CO2 gas all as specified and directed .5Each
1211M&L including filling of Nitrogen (N2) gas 2 Kg in high pressure seamless cylinders having 2 Kgs capacity after carrying to authorized filling station of N2 gas and fixing back to the plant complete all as specified and directed..20Kg
1312Supply N2 gas cylinder seam less of capacity 2 kg or nearest higher size conferming to relevent of IS with control , valves etc with N2 gas all as specified and directed .3Each
1413M & L for preparation of old painted steel surfaces of any description over 10 cm width or girth and applying two coats of synthetic enamel paint of approved colour complete all as specified and directed.20.9Sqm
1514M & L for preparation of the old existing steel surfaces of CO2 Gas cylinder and applying two coats of synthetic enamel paint of approved colour complete all as specified and directed.20Each
1615Supply and fixing 80mm bore MS pipe class 'C' heavy duty with Seemless welding induding required MS fittings & testing complete all as specified and directed.15RM
1716Supply only brass discharge nozzles cone type for CO2 cylinders of approved make complete all as specified nd directed.10Each
1817Supply only high pressure flexible hose pipe10 Kg /cm2 with flexible hose pipe flexible connector for pneumatic line & cylinder of approved make complete all as specified and directed .20Each
1918Supply only high pressure flexible hose pipe 10 kg/cm2 with flexible hose pipe flexible connector for cylinder to cylinder of approved make complete all as specified and directed.20Each
2019Supply only high pressure brass ISI mark non return valve 20mm bore for manifold and discharge hose connection of approved make complete all as specified and directed.10Each
2120Supply only solenoid valve 60Kg/cm2 pressure two way 15 mm dia (ISI mark) including all fitting complete all as specified and directed.2Each
2221Supply only high pressure brass safety valve 25mm bore (ISI mark) with outlet pipe of approved make complete all as specified and directed.2Each
2322Supply, fixing, testing and commissioning of Detector complying with and type certified to EN 45 addressable type, multisensor detector with heat and smoke combination with base complete ofexisting make to match with make of control panel all as specified and directed.75Each
2423Supply & fixing, in repair including testing and commissioning of Intelligent Wall Mounted Sounder of existing make and colour of control panel complete all as specified and directed .20Each
2524Supply, fixing in repair including testing and commissioning of Fire alrm system wiring using three single core PVC insulated, sheathed stranded copper conductor cable of size 1.5 Sqmm 1100 Volts drawn in and including PVC conduit (Medium grade ISI marked) of dia not less than 20mm on wall/roof with standard accessories complete all as specified and directed .250RM
2625Disconnecting of unserviceable battery of any description and supply and fixing maintenance free battery of 12 volts 7 AH capacity and connecting and testing at site complete all as specified and directed.10Each
2726Supply & fixing, in repair including testing and commissioning of Fire alrm Control panel complying with BSEN54 addressable two loop panel of capacity from 99 detector and 99 modules upto 200 detector and modules complete with battery 12 volts 7 AH capacity (02 Nos ) all as specified and directed Make :- GST/System Sensor/Agni devices5Each set
2827Supply & fixing, in repair including testing and commissioning of addressable / conventional manual call point (MCP) surface mounting with glass cover complete all as specified and directed.\n8Each
2928Supply & fixing, in repair including testing and commissioning of Auto Dialer system complete all as specified and directed.1Each
3029Programming/re-loading of software for existing unserviceable fire alarm control panel to make it functional with the help of software to suit existing panel/model including testing of all connected circuits/detectors complete all as specified and directed. \n2Each\nJob
3130Supply only Pneumatic actuator suitable for cylinder valve (ISI mark) operating at 15 to 30 Kg/cm2 complete all as specifiec and of approved make.8Each
3231Supply only Butter Fly Valve 150 mm CI Lever operated pressure /Class /Rating PN-1.6, Water type Nitrile Rubber Lining SG Iron (Make: Sant ,Castral, Kartar) ISI Marked .2Each
3332All as per item no.31.00 but butter fly valve 100 mm dia all as directed by Eng-in-Charge.2Each
3433All as per item no. 31.00 but butter fly valve 80 mm dia all as directed by Eng-in-Charge.2Each
3534Supply Hose Reel Drum with 30mtr Flexible pipe 25mm Dia and Shut off Nozzle (Make :New Age ,Min Max Mtech )ISI Marked.2Each
3635Supply Singal Hydrant Gun Matal 63mm Dia with Water Tigghtness test :-14kgf/cm2 and Hydrostatic Test :- 21kgf/cm2 and Flow test :90 LPM min at :7kgf/cm2 .LPMm(Make :New Age ,Min Max Mtech )ISI Marked.2Each
3736Supply RRL Hose pipe 63mm Dia 15mtr Gun Metal Male/Female Coupling with working pressure : 200 PSI Test Pressure: 300 PSI and Burst Pressure :500 PSI . (Make :New Age ,Min Max ,M Tech ) ISI Marked.4Each
3837Supply RRL MS Hose Box size 900/750/250 Double Door . (Make :New Age ,Min Max ,M Tech ) ISI Marked.2Each
3938Supply Pendent Sprinklers Standard and quick responce with standard coverage , Temprature rating :57 ,68 79 & 93 C, K factor 5.6 and 4.2 Brass , Chrome or White/custom colour finish , UL Listed and FM Approved .(Make :HD Tyco )15Each
4039Carbon -Di-Oxide (CO2 ) Portable Fire Extinguisher capacity 4.5 Kg MS Seamless body ISI With Gun mattle Valve . High Pressure Horn type Hose pipe ,with Syphan ,95% Min Efficitive Discharge ,Operation valve Upright Wheel / Squeeze Grip type (Make : Like Gurd , Safex )15Each
4140Suppy ABC type Power Filled Fire Extinguisher capacity 4 kg IS 15683 ,85% Mon effective Discharge , 13 Sec Discharge Time ,35 kgf /cm2 Hydraulic tested Pressure . (Make : Like Gurd , Safex )15Each
4241M&L for rewinding of electric motor of capacity 50 to 60 HP with super enamelled copper winding wire of same gauge and quantity to maint RPM including insulating meterial varnessing etc complete all as specified and directed.1Each
4342Taking down of old unserviceable AMF panel and connected accessories carefully with trend and qualified technician.1Each
4443AMF CONTROL PANEL(KIRLOSKER/AUTOMATION ELECTRONICS/ELECTRO INDIA/HAVELLS) : Supply, fabrication, fixing commissioning and testing, factory made, floor mounted, cubiocal automatic mains failure panel suitable for 125 KVA DG set, fabricated using 14 guage thick CRCA sheet, powder coated painting, suitable rated bus bar, internal wiring with control MCB, provn of connecting incoming & outgoing leads/bus bas as approved with and including the following accessories as under:-\n(i) Master switch for auto/manual/reset/off- 01 No\n(ii) Ammeter digital type 96x96 mm to read 0 - 400 amps with CT's 1 set of 3, aux supply 230 volts, AC, accuracy class 1.0\n(iii) Voltmeter digital type,96 x 96 mm to read 0 - 500 volts aux supply 230 volts, AC, accuracy class 1.0\n(vi) Set of lamp for indicating load on , low pressure, high cylinder temperature, load on mains, set fails to start, low oil pressure \n(v) Push button start, stop/ reset - 01 No\n(vi) Set of lamp for indicating load on , low pressure, high cylinder temperature, load on mains, set fails to start, low oil pressure \n(vii) Battery charger, connected to load side to charge battery from mains comprising of :-\n(a) Transformer of adequate rating.\n(b) Rectifiers\n(c) DC Ampere and volt meter\n(d) Charger rate selector for trickle or high charging\n(e) Indicating lamp for battery charging\n(viii) Fault accept/reset push button\n\n\n\n1Each
4543.01(ix) Set of relays and contactor with MCCB, 4 ploe, 250 Amps,415 volt, 25 KA for automatic start & automatically shut down of DG set of suitable rating & capacity and adjustable 75 to 100% - 02 Nos\n(x) By pass arrangement by prooving change over switch of 250 Amps 4 Pole in separate panel box to be installed with AMF -02 Nos\n(xi) ERS AND U/V Relay 12/24 Volts as required.\nNote:- 1. AMF Panel shall be installed out side the coustic enclosure.\n 2. Old existing AMF panel shall be dismantled and disposed where \n directed.
4644Supply and fix in repair PLC controller for air drier heat less type Air Drier operating pressure at 145 PSI . Make-Ingersoll Rand Model No -HL 120 . at 26 MMPU complete all as Specified and directed by Engineer In Charge .1EACH

AI Tender Summary

OUR REF NO 23183745
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 24.50 Lakhs
LAST DATE 07-02-2020
Authority
Authority Name Military Engineer Services
Work Description Comprehensive Maintenance Of Fire Fighting System And Repair/Maintenance Of Fire Detection , Alarm Systems At Af Stn Maharajpur
Basic Detail
Tender No 8900/1218/MJR/E8
Bidding Type Tender
Location
City GE(AF) TECH AREA MAHARAJPUR
State Madhya Pradesh
Key Dates
Publish Date 01 Feb 2020
Submission Date 07 Feb 2020
Open Date 10 Feb 2020
Finance
Tender Value 24.50 Lakhs
Tender Fee 500
EMD 49000
Exemption Not Available
Document List
BOQ_350550.xls
Tendernotice_1.pdf
5F2E4FE5-4BE4-456F-80DC-D03E496E1541.html
TENDER.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Feb 01, 2020
11:30 IST

Tender Published

Tender notice published.

Completed
Feb 07, 2020
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Feb 07, 2020
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Feb 10, 2020

Bid Opening Date