Military Engineer Services-MES has published Repairs Renewals Periodical Maintenance To Lt Equipments At Various Sub Stations At Afa Hyderabad. Submission Date for this Tender is 23-12-2019. Bolts Tenders in GE (AFA) Hyderabad Telangana. Bidders can get complete Tender details and download the document.
Name of Work : - REPAIRS/ RENEWALS / PERIODICAL MAINT TO LT EQUIPMENTS AT VARIOUS SUB STATIONS AT AFA HYDERABAD. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Disconnecting and taking out existing ACBs from housing and cleaning, rubbing and overhauling the mechanical parts and making serviceable of Local/Remote electrical operation of the panel incl Greasing Oiling , replacement of unserviceable Trip coil, Breaker System ,Gear Pinion, roller Switch and re-assembling the same, Servicing of 440V in door ACB 630A to1600A capacity, fixed type/ MDO/ EDO checking of quality of Air interrupter, insulation resistances, static contact resistance, Testing (IR value, ratio test, polarity test) , connection testing and calibration of relay including all other functional tests of the ACB panel complete all as specified and as directed.\nLocation:- Sub Stn No 7, Sub Stn No 11, Sub Stn No 02, Sub Stn No 08, Sub Stn No 24 and Sub Stn No 05. | 10 | Each Job | |
2 | 2 | Taking down worn out old / unserviceable Cubical Panel Box only and Supply ,Install Testing & Commissioning of self supporting indoor / outdoor type totally enclosed Cubical Panel Box of size 1.2 x 1.2 x 0.50 mtr as per comfortable for repair work in future, compartmentalised design, dust and vermin proof of suitable size for 440 Volt 3 phase 4 wire system made out of 3.0mm (minimum) thick CRCA sheet and built upon rigid frame work having front and rear hinged doors with neoprene rubber gasket including danger plate, earthing strip point and, ventilation louvers at the rear side extended canopy, bottom detachable gland plate complete with suitable size of Zinc/Cromium plated and nuts, bolts ;and washers etc. The panel shall be painted / fabricated in as per CPRI approved / certified factory and including incomming / outgoing cable holes at the bottom. The Panel shall be emmbeded with 50 x 50 x 5 mm MS Angle Iron frame and 30 cm above the normal ground level complete with PCC foundation (1:2:4) type B 2 complete all as specified and as directed. | 1 | Each Job | |
3 | 3 | All as per Ser item No 2 above, but of size 1.2 x 1.0 x 0.50 mtr. | 2 | Each Job | |
4 | 4 | All as per Ser item No 2 above, but of size 1.0 x 0.80 x 0.50 mtr. | 2 | Each Job | |
5 | 5 | All as per Ser item No 2 above, but of size 0.90 x 0.60 x 0.30 mtr. | 2 | Each Job | |
6 | 6 | All as per item No 2 above, but of size 0.60 x 0.60 x 0.30 mtr. Note :- Location (for Item Sl No 02 to 06) Sub stn No 04 & FCM sports complex area, Sub Stn No 06 & area, Sub Stn No 11 & Senior office Qtrs area | 2 | Each Job | |
7 | 7 | Taking down worn out old / unserviceable Aluminium bus bar 400 Amps rating and Supply & Fixing 4 Nos Aluminium bus bars of rating not less than 400 amps ,supported with suitable size heavy duty DMC/SMC/FRP insulator complete as per direction, with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral, complete all as specified and as directed. (For any type of LT panel) | 3 | set of 04 | |
8 | 8 | All as per item No 07 above, but 200 Amps rating, with suitable size as per direction. | 4 | set of 04 | |
9 | 9 | All as per item No 07 above, but 100 Amps rating, with suitable size as per direction. | 2 | set of 04 | |
10 | 10 | Supply and fixed in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 50 kA, 400 Amps connecting up complete all as specified and as directed.\n | 2 | Each | |
11 | 11 | Supply and fixed in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 35 kA 250 Amps connecting up complete all as specified and as directed.\n | 3 | Each | |
12 | 12 | Supply and fixed in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 35 kA 200 Amps including connecting up complete all as specified and as directed.\n | 3 | Each | |
13 | 13 | Supply and fixed in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 16 kA 160 Amps connecting up complete all as specified and as directed.\n | 4 | Each | |
14 | 14 | Supply and fixed in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 16 kA 100 Amps connecting up complete all as specified and as directed.\n | 3 | Each | |
15 | 15 | Supply and fixed in repairs MCCB adjustable thermal & fixed magnetic release TP 16 kA 63 Amps connecting up complete all as specified and as directed.\n | 4 | Each | |
16 | 16 | Supply and fixed in repairs MCCB adjustable thermal & fixed magnetic release TP 16 kA 32 A to 40 Amps connecting up complete all as specified and as directed.\n | 4 | Each | |
17 | 17 | Supply and fixed in repairs Change Over Switch 400 Amps, front operated, open execution type complete all as specified and as directed.\n | 1 | Each | |
18 | 18 | Supply and fixed in repairs Change Over Switch 250 Amps, front operated, open execution type complete all as specified and as directed.\n | 1 | Each | |
19 | 19 | Supply and fixed in repairs Change Over Switch 160 Amps, front operated, open execution type complete all as specified and as directed.\nNote :- Location (for Item Sl No 10 to 19) Sub stn No 04 & FCM sports complex area, Sub Stn No 06 & Sub Stn No 11 & Senior officers Qtrs area | 1 | Each | |
20 | 20 | Supply and fixed in repairs Digital voltmeter 96 mm x 96 mm having accuracy class 1.0, 4.5 digit with selector switch - 01 No complete all as specified and as directed. | 20 | Each | |
21 | 21 | Supply and fixed in repairs Digital Ammeter 96mm x 96mm having accuracy class 1.0, 4.5 digit with 3 Nos CT (400/5) with selector switch- 01 No complete all as specified and as directed. | 20 | Each | |
22 | 22 | Supply and fixed in repairs Astronomical time switch daily 1 channel having in built mechanism for calculating sun rise /sun set timing of a particular place suitable for 240 V AC supply - 01 No complete all as specified and as directed. | 4 | Each | |
23 | 23 | Supply and fixed in repairs 3 Pole power contactor of AC 3 duty rating of 40 amps having 240 volts rated no volt coil and having 2 NO (Normally open) + 2 NC (Normally closed) configuration- 01 No complete all as specified and as directed. | 4 | Each | |
24 | 24 | Supply and fixed in repairs LED indicating lamps with holder for main supply - (R-Y-B) complete all as specified and as directed. | 20 | Set of 03 | |
25 | 25 | Excavation in trenches in hard / dense soil not exc 1.5 mtr wide and not exc 1.5 mtr depth and getting out, including trimming the sides and forming bottom surface to required levels for laying cables complete all as specified and as directed. | 260 | Cum | |
26 | 26 | M&L for River dry sand cushioning to UG cables (8 cm deep before laying of cable and 15 cm deep over the cable) in trenches including consolidation punned thickness up to 18 cm , complete all as specified and as directed.\nNote :- Punned thickness only will be considered for payment. | 78 | Cum | |
27 | 27 | Returning, filling in trenches excavated soil in layers not .exc. 25 cm after laying of cables including spreading, levelling, and well ramming complete all as specified and as directed. | 150 | Cum | |
28 | 28 | Re laying of old retreived bricks vide excavation in trenches of exisitng laid cables complete all as specified and as directed. | 3 | Per 1000 Nos | |
29 | 29 | Supply & lay common burnt, clay building bricks, sub class 'B' designation over the sand cushioning in cable trenched for protection of cables (LT) complete all as specified and as directed. | 4.68 | Per 1000 Nos | |
30 | 30 | Removing surplus excavated material (soil) to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed. | 110 | Cum | |
31 | 31 | Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 240 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.\n | 150 | RM | |
32 | 32 | Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 185 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.\n | 150 | RM | |
33 | 33 | Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 120 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.\n | 200 | RM | |
34 | 34 | Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 95 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.\n | 300 | RM | |
35 | 35 | Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 70 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.\n | 200 | RM | |
36 | 36 | Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 50 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.\n | 200 | RM | |
37 | 37 | M&L for light grade galvanized pipe ISI marked with all fitting laid in trenches, under road or fixing on wall / pole / crossing nallah etc of bore 100 mm complete all as specified and as directed . | 18 | RM | |
38 | 38 | M&L for light grade galvanized pipe ISI marked with all fitting ISI marked, laid in trenches, under road or fixing on wall/pole/ crossing nallah etc of bore 80 mm complete all as specified and as directed . | 18 | RM | |
39 | 39 | M&L for Boring of holes under road, pavement hard standing by using trenchless technology using ultrasound technique and necessary machine to insert pipe of 50 to 100mm light grade GI pipes as per site requirement with all fittings such as bends, elbows, Tees, etc, for protection of cable complete including all plant & machinaries, alongwih Butt fusion welding machine with all accessories, T&P etc required complete all as specified and as directed.\nNote :- Protection pipe will be measured and paid separately | 30 | RM | |
40 | 40 | Dismantling ACSR or AAC conductors from the disturbed span including removing the binding with insulator, removing line spacer, of any size for LT / HT OH Line, etc complete all specefied and as directed | 2 | Qtl | |
41 | 41 | Re Stringing and Fixing only in position of existing sagged ACSR conductor of required size in over head line including biniding with aluminium binding wire complete after removing and refixing of UG cables/service wires to the ACSR conductor complete all as specified and as directed. | 6 | Qtl | |
42 | 42 | M&L for Stringing and Fixing in position of new ACSR conductor in over Head lines conductor (squirrel/wessel/rabbit) including binding with aluminium binding wire complete all as specified and as directed | 2 | Qtl | |
43 | 43 | S&F pin type porcelain vitreous white brown or green insulators including one galvanized steel spindle two galvanized iron washers and one galvanized iron nut 100 mm height, 65mm dia for 1100 volts grade complete including dismantling of old unserviceable insulator complete all as specified and as directed | 50 | Each | |
44 | 44 | S&F Shackle Type Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts 75 x 90mm for 1100 volts grade complete including dismantling of old unserviceable insulator complete all as specified and as directed | 50 | Each | |
45 | 45 | Dismantling / taking down old unserviceable cross arms, bracings, support, clamp including nuts, bolts and washers complete all as specified and as directed. | 3 | Qtl | |
46 | 46 | M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, drilling holes for bolts in any shapes or size all as specified and directed complete incl painting of one primer coat one under coat and one finishing coat paint one complete all as specified and as directed. | 3.5 | Qtl | |
47 | 47 | Supply & Fix PVC LT line separators 4 way with nut, bolt arrangement, in the existing O/H line on pole on height 7.0 to 7.50 mtrs above ground level complete all as specified and as directed. | 100 | Each | |
48 | 48 | All as per item no. 47 above, but 2 way. | 50 | Each | |
49 | 49 | M&L for stay assembly complete with accessories as shown in electrical plate No- 1 of SSR 2009 Part -I for dia of stay rod 20 mm including GI stay strand of size 7/3.15 mm (maximum length 11.00 mtr) to keep the pole in vertical position incl loop insulator stay all as specified and directed including dismantling and taking out old unsv stay assembly set complete (PCC will be measured and paid separately) including dismantling and taking out the exisiting unserviceable stay assembly complete all as specified and as directed. | 4 | Each | |
50 | 50 | M&L for Trimming of trunk and branches of trees not exceeding 30 cm grith and disposal of the same to a distance not exc 50 mtr and clearing site complete all as directed to clear the OH line (HT/LT) for a span of length 100 mtr. | 100 | Each Span | |
51 | 51 | M&L for Cutting of Vegetations, creapers, grasses, earth heaps etc, cleaning and levelling of cutting areas in various electrical installation areas, sorrounding of HT/LT poles / structures complete all as specified and as directed. | 500 | Sq mtr | |
52 | 52 | Demolition of Cement concrete plate form on floor of any description and in any position not otherwise described complete all as specified and as directed. | 5 | Cum | |
53 | 53 | M&L for Preparation of steel surfaces of any description over 10 cm width or girth and painting two coats of synthetic enamel paint over one coat of red oxide primer for metal surface of panels, cable duct cover, and any surface area etc complete all as specified and as directed. | 200 | Sqm | |
54 | 54 | M&L for PCC 1:2:4 type B1 using 20 mm graded stone aggregate as in platform, filling and mass concrete, coping to pole for embedding stay road all as specified, including necessary form work and applying two coats of white wash to exposed surface of coping/platform complete all as specified and as directed. | 6 | Cum | |
55 | 55 | M&L for PCC 1:4:8 type D-2 mix using 40 mm graded stone aggregate for pole foundation filling and mass concrete complete all as specified and as directed. | 8 | Cum | |
56 | 56 | Material and labour for providing PCC 1:3:6 type C-2 mix using 40 mm graded stone aggregate for embedding stay wire complete all as specified and as directed. | 4 | CUM | |
57 | 57 | M&L for Pre-cast cement concrete block masonry type C-1 (PCC 1:3:6) using 20 mm graded stone aggregate with solid blocks, exc. 10 cm in width and setting in cement mortar 1:6 complete, for foundation / platform / pedestal etc, complete all as specified and as directed. | 10 | Cum | |
58 | 58 | M&L for rendering 10 mm thick on brick /concrete / block masonry surface in cm (1:6) finished fair complete all as specified and as directed. | 40 | SQM | |
59 | 59 | M&L for laying for stone course boulders exceeding 7 cm and upto 15 cm to avoid growth of grass / weeds and protection against soil erosion at outdoor electrical sub station complete all as specified and as directed. | 20 | Cum | |
60 | 60 | Taking down unserviceable mat sheet and S&F Fire retardant / extinguishing electric insulated synthetic mat suitable for electric system of 2.5mm thick, confirming to relevant IS/IEC codes, tested for breakdown strength, tensile elongation properties, insulation resistance, effect of acid, alkaline, diesel and transformer oil leakage, current test, fire test etc., having a minimum width of 100mm including all pasting materials such as PU resin, chemi bond (hardener), special PVC adhesive and fixed in electrical installation complete as per sample complete all as specified and as directed. | 40 | Sqm | |
61 | 61 | S&F Dry type Fire Extinguisher (For A-B-C type of fire) Packed in 4.5 Kg Cylinder (ISI marked) with necessary fixing arrangement on wall complete all as specified and as directed.\nMake:- GE TECH/UNIMAX/ CEASEFIRE | 10 | Each | |
62 | 62 | S&F Electric Shock Treatment chart (as per sample) in language English & Local (Telugu) on PVC sheet with white colour letter on red colour base complete all as specified and as directed.\n\n | 10 | Each Job |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy