Public Works Department-PWD has published Tender For H And Fwd Centrally Sponsored Scheme Capacity Building For Developing Trauma Care Facilities On National Highways Construction Providing Additional Facilities In The Emergency Department And Trauma Care Department Attached To Mch Tvm H And Fwd . Submission Date for this Tender is 25-11-2019. Building Work Tenders in Thiruvananthapuram Kerala. Bidders can get complete Tender details and download the document.
Work Name : H& FWD-Centrally sponsored Scheme-Capacity Building for Developing trauma Care Facilities on National Highways Construction-Providing additional facilities in the Emergency Department and trauma care Department attached to Medical College Hospital,Thiruvananthapuram | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | PART-1 Electrification | BI01010001010000000000000515BI0100001113 | ||
2 | 1.01 | 90.2.1.1 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point | BI01010001010000000000000515BI0100001114 | 90 | point |
3 | 1.02 | 90.2.1.3 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control light point without ceiling rose - Short point | BI01010001010000000000000515BI0100001115 | 30 | point |
4 | 1.03 | 90.2.1.4 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point | BI01010001010000000000000515BI0100001116 | 30 | point |
5 | 1.04 | 90.2.1.6 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points | BI01010001010000000000000515BI0100001117 | 32 | each |
6 | 1.05 | 90.3.10 : Supplying and providing extra H.G conduit down rod of 19 mm dia 2 x 1.00 m long with 16/0.20 mm 3 core copper conductor flex wire conforming to relevant ISS or with the extended original wiring and giving connection etc. as required. | BI01010001010000000000000515BI0100001118 | 25 | each |
7 | 1.06 | 90.3.20.3 : Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture | BI01010001010000000000000515BI0100001119 | 30 | each |
8 | 1.07 | 90.3.24.3 : Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 1X20W LED Lamp with box type fixture | BI01010001010000000000000515BI0100001120 | 20 | each |
9 | 1.08 | 90.3.17.1 : Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.32 mm dia GI pipe | BI01010001010000000000000515BI0100001121 | 12 | metre |
10 | 1.09 | 90.6.6.1 : Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm | BI01010001010000000000000515BI0100001122 | 50 | metre |
11 | 1.1 | 90.15.4.2 : Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) | BI01010001010000000000000515BI0100001123 | 6 | each |
12 | 1.11 | od142553/2019_2020 : Supply, conveyance installation testing and commissioning of pre-wired 36W square type LED Clean Room fitting complete with all accessories and drives etc. Lumen out put not less than 3600 efficiency not less than 100lumen/watt suspended from ceiling using 4 nos steel chain (16 SWG or nearest) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. | BI01010001010000000000000515BI0100001124 | 8 | each |
13 | 1.12 | od142626/2019_2020 : Supply, conveyance installation testing and commissioning of pre-wired 600 x 600 mm square type LED fitting complete with all accessories and drives etc. Lumen out put not less than 3600 efficiency not less than 100lumen/watt UGR< 19 comfortable light suspended from ceiling using 4 nos steel chain (16 SWG or nearest) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. (for fitting in false ceiling) | BI01010001010000000000000515BI0100001125 | 30 | each |
14 | 1.13 | od142632/2019_2020 : Supply, conveyance installation testing and commissioning of pre-wired 300 x 300 mm square type LED fitting complete with all accessories and drives etc. Lumen out put not less than 1800 efficiency not less than 100lumen/watt suspended from ceiling using 4 nos steel chain (16 SWG or nearest) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. (for fitting in false ceiling) | BI01010001010000000000000515BI0100001126 | 40 | each |
15 | 1.14 | od142634/2019_2020 : Supply, conveyance installation testing and commissioning of pre-wired 600 x 600 mm square type LED fitting complete with all accessories and drives etc. Lumen out put not less than 3600 efficiency not less than 100lumen/watt suspended from ceiling using 4 nos steel chain (16 SWG or nearest) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. (for fitting in false ceiling) | BI01010001010000000000000515BI0100001127 | 50 | each |
16 | 1.15 | od142640/2019_2020 : Supply, conveyance installation testing and commissioning of pre-wired 300 x 300 mm square type LED fitting complete with all accessories and drives etc. Lumen out put not less than 1800 efficiency not less than 100lumen/watt on surface anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. | BI01010001010000000000000515BI0100001128 | 8 | each |
17 | 1.16 | od142648/2019_2020 : Supply, conveyance installation testing and commissioning of pre-wired 600 x 600 mm square type LED fitting complete with all accessories and drives etc. Lumen out put not less than 3600 efficiency not less than 100lumen/watt on surface anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. | BI01010001010000000000000515BI0100001129 | 8 | each |
18 | 1.17 | od142592/2019_2020 : Supply Conveyance, installation, testing and commissioning of pre-wired light fitting of all types complete with all accessories and fluorescent lamps etc. directly to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.for Round LED down light fitting out put not less than 1200lumen efficiency not less than 105lu/watt steel/aluminum enclosure complete | BI01010001010000000000000515BI0100001130 | 25 | each |
19 | 1.18 | od142594/2019_2020 : Supply, conveyance installation testing and commissioning of pre-wired 300x 1200 mm or nearest square type LED fitting complete with all accessories and drives etc. Lumen out put not less than 3600 efficiency not less than 100lumen/watt suspended from ceiling using 4 nos steel chain (16 SWG or nearest) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. (for fitting in false ceiling) | BI01010001010000000000000515BI0100001131 | 4 | each |
20 | 1.19 | od134470/2019_2020 : Supplying and fixing PVC batten/ angle holder including 3 W LED Bulb and plastic shade and giving connection etc. as required. | BI01010001010000000000000515BI0100001132 | 18 | each |
21 | 1.2 | od142598/2019_2020 : Supplying and fixing cast aluminium bulk head fitting with mesh guard with 7W LED bulb and giving connection etc. as required. | BI01010001010000000000000515BI0100001133 | 12 | each |
22 | 1.21 | 90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. | BI01010001010000000000000515BI0100001134 | 40 | each |
23 | 1.22 | 1.48 : Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) | BI01010001010000000000000515BI0100001135 | 60 | each |
24 | 1.23 | 90.4.5.2 : Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.1200mm sweep -5star rated ceiling fan complete with 300mm down rod , canopies, shackeles and blades and resistance type regulator working on 230V/240V single phase A/C | BI01010001010000000000000515BI0100001136 | 40 | each |
25 | 1.24 | 90.4.8 : Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required. | BI01010001010000000000000515BI0100001137 | 6 | each |
26 | 1.25 | od151563/2018_2019 : Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. 305 mm sweep, 1400 rpm Heavy Duty Exhaust fan working on 230 V A/C | BI01010001010000000000000515BI0100001138 | 6 | each |
27 | 1.26 | 90.6.10.1 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm | BI01010001010000000000000515BI0100001139 | 250 | metre |
28 | 1.27 | 90.6.10.2 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm | BI01010001010000000000000515BI0100001140 | 150 | metre |
29 | 1.28 | 90.6.10.3 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required32 mm | BI01010001010000000000000515BI0100001141 | 50 | metre |
30 | 1.29 | 1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm | BI01010001010000000000000515BI0100001142 | 150 | metre |
31 | 1.3 | 1.17.6 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm | BI01010001010000000000000515BI0100001143 | 100 | metre |
32 | 1.31 | 1.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm | BI01010001010000000000000515BI0100001144 | 150 | metre |
33 | 1.32 | 1.17.15 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm | BI01010001010000000000000515BI0100001145 | 150 | metre |
34 | 1.33 | 1.17.22 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm | BI01010001010000000000000515BI0100001146 | 150 | metre |
35 | 1.34 | 1.17.31 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm | BI01010001010000000000000515BI0100001147 | 50 | metre |
36 | 1.35 | 90.9.2.1 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid | BI01010001010000000000000515BI0100001148 | 75 | metre |
37 | 1.36 | 90.9.2.2 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable devider | BI01010001010000000000000515BI0100001149 | 40 | metre |
38 | 1.37 | 90.9.2.3 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree | BI01010001010000000000000515BI0100001150 | 10 | each |
39 | 1.38 | 90.9.2.4 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat angle 90 degree | BI01010001010000000000000515BI0100001151 | 10 | each |
40 | 1.39 | 90.9.2.8 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap | BI01010001010000000000000515BI0100001152 | 20 | each |
41 | 1.4 | 90.9.2.10 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Joint cover | BI01010001010000000000000515BI0100001153 | 20 | each |
42 | 1.41 | 90.9.2.12 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.1 to 3 module mounting box | BI01010001010000000000000515BI0100001154 | 10 | each |
43 | 1.42 | 90.9.2.14 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.8 module mounting box | BI01010001010000000000000515BI0100001155 | 30 | each |
44 | 1.43 | 90.9.2.24 : Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat Tee | BI01010001010000000000000515BI0100001156 | 10 | each |
45 | 1.44 | 1.28.2 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module | BI01010001010000000000000515BI0100001157 | 10 | each |
46 | 1.45 | 1.28.5 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module | BI01010001010000000000000515BI0100001158 | 30 | each |
47 | 1.46 | 1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) | BI01010001010000000000000515BI0100001159 | 50 | each |
48 | 1.47 | 1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm) | BI01010001010000000000000515BI0100001160 | 50 | each |
49 | 1.48 | 1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch | BI01010001010000000000000515BI0100001161 | 100 | each |
50 | 1.49 | 1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet | BI01010001010000000000000515BI0100001162 | 150 | each |
51 | 1.5 | 1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch | BI01010001010000000000000515BI0100001163 | 50 | each |
52 | 1.51 | 1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet | BI01010001010000000000000515BI0100001164 | 50 | each |
53 | 1.52 | 90.10.3.14 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator | BI01010001010000000000000515BI0100001165 | 13 | each |
54 | 1.53 | 90.10.3.32 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator | BI01010001010000000000000515BI0100001166 | 13 | each |
55 | 1.54 | 90.10.3.33 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket | BI01010001010000000000000515BI0100001167 | 13 | each |
56 | 1.55 | 90.11.1.11 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43) | BI01010001010000000000000515BI0100001168 | 4 | each |
57 | 1.56 | 90.11.1.14 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) | BI01010001010000000000000515BI0100001169 | 2 | each |
58 | 1.57 | 90.11.1.18 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) | BI01010001010000000000000515BI0100001170 | 2 | each |
59 | 1.58 | 90.11.1.19 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) | BI01010001010000000000000515BI0100001171 | 1 | each |
60 | 1.59 | 2.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door | BI01010001010000000000000515BI0100001172 | 6 | each |
61 | 1.6 | 2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole | BI01010001010000000000000515BI0100001173 | 96 | each |
62 | 1.61 | 2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole | BI01010001010000000000000515BI0100001174 | 12 | each |
63 | 1.62 | 2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | BI01010001010000000000000515BI0100001175 | 6 | each |
64 | 1.63 | 2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | BI01010001010000000000000515BI0100001176 | 6 | each |
65 | 1.64 | 2.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps | BI01010001010000000000000515BI0100001177 | 6 | each |
66 | 1.65 | 2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | BI01010001010000000000000515BI0100001178 | 2 | each |
67 | 1.66 | 2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps | BI01010001010000000000000515BI0100001179 | 2 | each |
68 | 1.67 | 90.12.7.27 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 25 sq mm with factory made clamp | BI01010001010000000000000515BI0100001180 | 100 | metre |
69 | 1.68 | 90.12.7.28 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp | BI01010001010000000000000515BI0100001181 | 250 | metre |
70 | 1.69 | 90.12.7.29 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp | BI01010001010000000000000515BI0100001182 | 200 | metre |
71 | 1.7 | 90.12.7.41 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp | BI01010001010000000000000515BI0100001183 | 50 | metre |
72 | 1.71 | 9.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) | BI01010001010000000000000515BI0100001184 | 10 | set |
73 | 1.72 | 9.1.20 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm) | BI01010001010000000000000515BI0100001185 | 6 | set |
74 | 1.73 | 9.1.21 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) | BI01010001010000000000000515BI0100001186 | 6 | set |
75 | 1.74 | 9.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) | BI01010001010000000000000515BI0100001187 | 6 | set |
76 | 1.75 | 5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | BI01010001010000000000000515BI0100001188 | 2 | set |
77 | 1.76 | 5.10 : Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. | BI01010001010000000000000515BI0100001189 | 25 | metre |
78 | 1.77 | 5.14 : Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. | BI01010001010000000000000515BI0100001190 | 50 | metre |
79 | 1.78 | od155913/2018_2019 : Supply of superior quality copper reducer (banana) cable socket and making core termination of cables of the following sizes including crimping etc. as required6 sq mm | BI01010001010000000000000515BI0100001191 | 32 | each |
80 | 1.79 | od155915/2018_2019 : Supply of superior quality copper reducer (banana) cable socket and making core termination of cables of the following sizes including crimping etc. as required.4 sq mm | BI01010001010000000000000515BI0100001192 | 42 | each |
81 | 1.8 | od155917/2018_2019 : Supply of superior quality copper reducer (banana) cable socket and making core termination of cables of the following sizes including crimping etc. as required.2.5 sq mm | BI01010001010000000000000515BI0100001193 | 40 | each |
82 | 1.81 | od134340/2019_2020 : Supply and providing brass bolt and nut 25x3mm | BI01010001010000000000000515BI0100001194 | 25 | each |
83 | 1.82 | od134313/2019_2020 : Supply and providing brass bolt and nut 25x6mm | BI01010001010000000000000515BI0100001195 | 25 | each |
84 | 1.83 | 90.16.1.1 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG) | BI01010001010000000000000515BI0100001196 | 330 | metre |
85 | 1.84 | 90.16.1.2 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) | BI01010001010000000000000515BI0100001197 | 380 | metre |
86 | 1.85 | 90.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) | BI01010001010000000000000515BI0100001198 | 200 | metre |
87 | 1.86 | 90.16.5.1 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG) | BI01010001010000000000000515BI0100001199 | 20 | each |
88 | 1.87 | 90.16.5.2 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG) | BI01010001010000000000000515BI0100001200 | 25 | each |
89 | 1.88 | 90.16.5.3 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) | BI01010001010000000000000515BI0100001201 | 30 | each |
90 | 1.89 | 90.14.10.1 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL | BI01010001010000000000000515BI0100001202 | 18 | no |
91 | 1.9 | 90.14.10.3 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL | BI01010001010000000000000515BI0100001203 | 2 | no |
92 | 1.91 | od143151/2019_2020 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.200A, 25 kA (Ics=100%Icu), 4pole, current limiting type MCCB withthermal magnetic release with overload setting of 80 - 100% having adjustable OL & SC | BI01010001010000000000000515BI0100001204 | 1 | no |
93 | 1.92 | od143153/2019_2020 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 25 kA (Ics=100%Icu), 4pole, current limiting type MCCB withthermal magnetic release with overload setting of 80 - 100% having adjustable OL & SC | BI01010001010000000000000515BI0100001205 | 1 | no |
94 | 1.93 | od143155/2019_2020 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 25 kA (Ics=100%Icu), 4pole, current limiting type MCCB withthermal magnetic release with overload setting of 80 - 100% having adjustable OL & SC | BI01010001010000000000000515BI0100001206 | 1 | no |
95 | 1.94 | od155975/2018_2019 : Painting letters or figures of the size2.50 cm, 4 cm or 5 cm with enamel paint as identification mark to SB, DB, panel board etc | BI01010001010000000000000515BI0100001207 | 350 | each |
96 | 1.95 | od117165/2019_2020 : Supply and Installation Three Phase Ammeter accuracy class 1 | BI01010001010000000000000515BI0100001208 | 6 | each |
97 | 1.96 | od117167/2019_2020 : Supply and Installation Three Phase Voltmeter accuracy class 1 | BI01010001010000000000000515BI0100001209 | 2 | each |
98 | 1.97 | od134500/2019_2020 : Providing and fixing Red, Green, Black, Yellow, Orange colours LED indicator, AC/DC, 22.5 mm cut out dia in existing panel and giving connection complete | BI01010001010000000000000515BI0100001210 | 4 | each |
99 | 1.98 | od134502/2019_2020 : Providing and fixing Blue colour LED indicator, AC/DC, 22.5 mm cut out dia in existing panel and giving connection complete | BI01010001010000000000000515BI0100001211 | 2 | each |
100 | 1.99 | od134504/2019_2020 : Providing and fixing following metering ct 100/5A 5VA /1A accuracy class 0.5 existing panel and giving connection complete | BI01010001010000000000000515BI0100001212 | 6 | each |
101 | 2 | od134506/2019_2020 : Providing and fixing 6A selector switch in existing panel and giving connection complete | BI01010001010000000000000515BI0100001213 | 2 | each |
102 | 2.01 | od142602/2019_2020 : Supply and providing sub main Distribution Board with IP42 protection complying to IEC 61439-2 with copper bus bar neutral link earth bus etc suitable for providing 3 pole MCCB as incoming and outgoing fixed on wall using necessary anchor bolts including cutting hole on the wall ,making good the damages,colour washing etc as required MCCB load Bank L&T Energys or equivalent 250A 8 way | BI01010001010000000000000515BI0100001214 | 2 | each |
103 | 2.02 | od143143/2019_2020 : Supply and providing side cabling boxes for 8 way sub main distribution boards as required | BI01010001010000000000000515BI0100001215 | 4 | each |
104 | 2.03 | od143145/2019_2020 : Supply and providing top/ bottom cabling boxes for sub main distribution boards as required | BI01010001010000000000000515BI0100001216 | 3 | each |
105 | 2.04 | od143147/2019_2020 : Supply and providing metering extension boxes for sub main distribution boards as required | BI01010001010000000000000515BI0100001217 | 1 | each |
106 | 2.05 | od143149/2019_2020 : Supply and providing corner boxes for sub main distribution boards as required | BI01010001010000000000000515BI0100001218 | 8 | each |