Sales : +91-777 804 8217
| Name of Work: Construction of Expansion of OPD Block “Centre of Excellence” at - IHBAS, Delhi | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1.01 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30cm in depth. 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed. | |||
| 2 | 1.02 | All kinds of soil | 2600 | Cum | |
| 3 | 2 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. | |||
| 4 | 2.01 | All kinds of soil. | 160 | Cum | |
| 5 | 3 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m: | |||
| 6 | 3.01 | All kinds of soil | |||
| 7 | 3.02 | Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia | 250 | Metre | |
| 8 | 4 | Filling available (at site premises) excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, with all leads and lifts. | 3450 | Cum | |
| 9 | 5 | Extra for every additional lift of 1.5 m or part there of in excavation/banking excavated or stacked materials. | |||
| 10 | 5.01 | All kinds of soil. | 172 | Cum | |
| 11 | 6 | Supplying and filling in plinth with Zone-V sand under floors including, watering. ramming consolidating and dressing complete. | 262 | Cum | |
| 12 | 7 | Supplying and stacking of good earth at site including royalty and carriage complete (earth measured in stacks will be reduced by 20% for payment).\n | 696 | Cum | |
| 13 | 7.01 | CONCRETE WORK | |||
| 14 | 8 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : | |||
| 15 | 8.01 | 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) | 3 | Cum | |
| 16 | 8.02 | 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size). | 124 | Cum | |
| 17 | 8.03 | 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) | 633 | Cum | |
| 18 | 9 | Providing and laying damp-proof course 40 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size). | 188 | Sqm | |
| 19 | 10 | Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer's specification | 49 | per 50 kg cement | |
| 20 | 11 | Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. | 188 | Sqm | |
| 21 | 11.01 | REINFORCED CEMENT CONCRETE | |||
| 22 | 12 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. | |||
| 23 | 12.01 | (Note :- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/recoverable separately). | |||
| 24 | 12.02 | All works upto plinth level. | 792 | Cum | |
| 25 | 12.03 | All works above plinth level upto floor V level. | 1406 | Cum | |
| 26 | 13 | Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using fly ash and cement content as per approved design mix, and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering, finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate / retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge. | |||
| 27 | 13.01 | NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately. | |||
| 28 | 13.02 | (2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement to be ensured in accordance with clauses 5.2 and 5.2.1 of IS:456 -2000 in the items of BMC and RMC. | |||
| 29 | 13.03 | All works up to Plinth level. | 88 | Cum | |
| 30 | 13.04 | All works above plinth & up to floor V level. | 157 | Cum | |
| 31 | 13.05 | Note :- The above item shall be used judiciously where specified quality of Fly Ash is available for mixing in concrete. Also, the guidelines issued by CDO, CPWD, vide circular no. CDO/SE(RR)/Fly Ash (Main)/102 dated 9th April 2009 shall be followed in such cases. | |||
| 32 | 14 | Centering and shuttering including strutting, propping etc. and removal of form for : | |||
| 33 | 14.01 | Foundations, footings, bases of columns, etc. for mass concrete\n | 882 | Sqm | |
| 34 | 14.02 | Suspended floors, roofs, landings, balconies and access platform\n | 4321 | Sqm | |
| 35 | 14.03 | Shelves (Cast in situ) | 25 | Sqm | |
| 36 | 14.04 | Lintels, beams, plinth beams, girders, bressumers and cantilevers\n | 4775 | Sqm | |
| 37 | 14.05 | Columns, Pillars, Piers, Abutments, Posts and Struts | 2777 | Sqm | |
| 38 | 14.06 | Stairs, (excluding landings) except spiral-staircases | 131 | Sqm | |
| 39 | 14.07 | Small lintels not exceeding 1.5 m clear span, moulding as in cornices, window sills, string courses, bands, copings, bed plates, anchor blocks and the like | 109 | Sqm | |
| 40 | 14.08 | Weather shade, Chajjas, corbels etc., including edges | 156 | Sqm | |
| 41 | 15 | Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured). | |||
| 42 | 15.01 | Suspended floors, roofs, landing, beams and balconies (Plan area to be measured) | 50 | Sqm | |
| 43 | 16 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete at all levels. | |||
| 44 | 16.01 | Thermo-Mechanically Treated bars. | 383067 | kg | |
| 45 | 17 | Add/deduct for using extra/less cement in the items of design mix over and above the specified cement content therein. | 489 | Quintal | |
| 46 | 18 | Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical locations in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge. (Material shall conform to ASTM 6063). | |||
| 47 | 18.01 | Floor Joint of 100 mm gap | 88 | mtr | |
| 48 | 19 | Providing and fixing of expansion joint system related with wall joint (internal/external) location as per drawings and direction of Engineer-In- Charge.The joints shall be of extruded aluminum base members, self aligning /centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall conform to ASTM 6063.) | |||
| 49 | 19.01 | Wall Joint of 100 mm gap | 60 | mtr | |
| 50 | 20 | Providing and fixing of expansion joint system of approved make and manufacture for various roof locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members with, self aligning and self centering arragement support plates as per ASTM B221-02. The system shall be such that it provides water tight roof to roof /roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminum base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of fallingice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement.(Material shall confirm to ASTM 6063.) | |||
| 51 | 20.01 | Roof Joint of 100 mm gap | 46 | mtr | |
| 52 | 20.02 | Walls and Partitions | |||
| 53 | 21 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: | |||
| 54 | 21.01 | Cement mortar 1:6 (1 cement : 6 coarse sand) | 250 | Cum | |
| 55 | 22 | Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength in super structure above plinth level up to floor V level in :\n\n | |||
| 56 | 22.01 | Cement mortar 1:6 (1 cement : 6 Coarse sand) | 750 | Cum | |
| 57 | 23 | Half brick masonry with non modular fly ash bricks of class designation 10, conforming to IS :12894, in super structure above plinth and upto floor V level. | |||
| 58 | 23.01 | Cement mortar 1 : 4 (1 cement : 4 coarse sand) | 1833 | Sqm | |
| 59 | 24 | Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry. | 1833 | Sqm | |
| 60 | 24.01 | DOORS & WINDOWS | |||
| 61 | 25 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazings, paneling to be paid for separately) : | |||
| 62 | 25.01 | For fixed portion | |||
| 63 | 25.02 | Polyester Powder coated aluminium (minimum thickness of polyester powder coating 50 micron) | 3200 | Kg | |
| 64 | 26 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) | |||
| 65 | 26.01 | Polyester Powder coated aluminium (minimum thickness of polyester powder coating 50 micron) | 1225 | Kg | |
| 66 | 27 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): | |||
| 67 | 27.01 | With float glass panes of 5.50 mm thickness | 200 | Sqm | |
| 68 | 28 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: | |||
| 69 | 28.01 | 30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws. | 239 | Sqm | |
| 70 | 29 | Extra for providing lipping with 2nd class teak wood battens 6 mm depth on all edges of flush door shutters (over all area of door shutter to be measured).including polishing etc complete. | 239 | Sqm | |
| 71 | 30 | Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured) : | |||
| 72 | 30.01 | Rectangular or square. | 120 | Sqm | |
| 73 | 31 | Extra for providing frosted glass panes 5.5 mm thick instead of ordinary float glass panes 5.5 mm thick in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured).\n | 20 | Sqm | |
| 74 | 32 | Providing and fixing glass panes, with wooden fillets wherever necessary. | |||
| 75 | 32.01 | Float glass panes of thickness 4 mm | 6 | Sqm | |
| 76 | 33 | Extra if louvers (not exceeding 0.2 sqm) are provided in flush door shutters (overall area of door shutters to be measured). | |||
| 77 | 33.01 | Decorative type door | 5 | Sqm | |
| 78 | 34 | Extra for cutting rebate in flush door shutters (Total area of the shutter to be measured). | 39 | Sqm | |
| 79 | 35 | Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt / suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality. | |||
| 80 | 35.01 | 1.0 mm thick. | 477 | Sqm | |
| 81 | 36 | Providing and installation of fully insulated wooden fire rated shutter of 120min. fire rating conforming to BS: 476 part 22 and IS:3614 Part II as per the prototype tested and certified by CBRI Roorkee, of minimum 50 mm thickness, comprising of 75mm x 44mm hardwood internal timber frame work, with infill of 96 kg/m3, ceramic fiber blankets, coated with intumuscent coating on both sides for insulation. The coated insulation shall be sandwiched between 12mm thick, Non combustible Boards (Calcium Silicate of approved quality and manufacture) on both sides (edge to edge on internal Hardwood frame) and cladded with 3mm thick commercial ply of approved quality & 1mm thick laminate of approved brand and manufacture on both sides, with 50mm x 14mm 2nd class teak wood lipping all round the shutter. | |||
| 82 | 36.01 | The shutter is suitable for mounted on the door frame, as per the item given below. Both frame and shutter shall be fitted with fire & smoke intumescent seal of Viper or equivalent make of size 20 x 4mm on all the three sides except bottom. The pasting of the ply/veneer/laminate should be done using automatic machine and should be free from any nails or perforations. The board shall be Resistant to vermin, mould growth, minor impact, abrasion and short term water attack. The shutter shall be fixed with the frame with the help of SS 304 grade ball bearing hinges of size 100x75x3mm of approved quality with necessary screws and making cut out for vision panel. Provisions/reinforcement for fixing all fixtures shall be built in on the door prior to the supply. The rate shall include all the materials, labour and T&P for the works described in the item above. | |||
| 83 | 36.02 | Single/Double Shutter | 51 | Sqm | |
| 84 | 37 | Providing and fixing door frames as per BS: 476 part 22, IS:3614 Part II as per the prototype certified by CBRI Roorkee made out of 2nd class Teak Wood (Ivory Coast)frame of section 120 X 70 mm for fire resistant doors of 120 minutes fire rating, with heat activated intumescent fire seal strips of size 20 x 4 mm( for smoke sealing) provided in grooves on all three sides of the frame with one coat of approved brand of fire retardant primer including two coats of fire retardant paint FR 881or equivalent un thinned on cleared hard wood surface of door frames (@3.5 sq.m. per litre per coat) including preperation of base surface as per recommendations of manufacturer to make the surface fire retardant, including fixing the frame with 8 nos. 100 mm long, 10 mm dia metal dash fastners complete as per directions of the Engineer in charge NOTE:- cost of fire seal strips, dash fastners are included in the item. Nothing extra shall be paid if size of any component of material exceeds the limit mentioned in the item to achieve desired fire rating. | 76 | Metre | |
| 85 | 38 | Providing and fixing UL listed door Co-ordinator of approved Make for coordination of double leaf 120 min fire rated doors, of approved brand and manufacture. | 13 | Each | |
| 86 | 39 | Supply & fixing of Fire-stop Fire sealing System Board Type(barriers) of approved make for sealing of floors, wall openings under control panels for the purpose of compartmentation.The FPSS consists of 100mm thick mineral wool insulation pad of approved make having density of 48 kg/m3 coated with FR in tumescent compound encased with 10 mm thick calcium silicate board of approved make, sealed with intumescent Fire Seal Putty of approved Make. The system is coated and fixed with openings with the help of slotted angles of size 40x40mm of 16 SWG thickness, nutbolts of size 1.5\"x8mm Dia. The FPSS system all provide 2 hours fire rating as per IS 12458-1989.After insulation of this system it will be painted with Fire Retardant Paint of approved Make. | 6 | sqm | |
| 87 | 40 | Providing & fixing 11.0 mm thick sandwich clear glass of approved make tested upto 2 hours fire rating and complied with BS 476: Part 22 as vision panel including cost of fire rated ceramic tape and moulding/beading all complete. | 3 | Sqm | |
| 88 | 41 | Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. | 116 | Each | |
| 89 | 42 | Providing and fixing SS 304 Aldrop 300 x 16mm of approved quality with necessary provision of anti theft screws. Complete set including the fixing accessories. | 41 | Each | |
| 90 | 43 | Providing and fixing SS304 tower bolts, with necessary screws etc. complete : | |||
| 91 | 43.01 | 250x10 mm | 385 | Each | |
| 92 | 43.02 | 150x10 mm | 381 | Each | |
| 93 | 44 | Providing and fixing SS304 H-Type Pull Handle of Length 457mm, 32mm Diameter and CD 305mm in Satin Steel Finish. Complete set including the fixing accessories. | 82 | Each | |
| 94 | 45 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. | |||
| 95 | 45.01 | Twin rubber stopper | 75 | Each | |
| 96 | 46 | Providing and fixing 240mm Europfrofile Narrow Stile Mortise Lock of approved quality with necessary , SS tube Lever Handle D Type with Oval rose ring , 70mm Pin Cylinder 1CK. Complete set including the fixing accessories. | 75 | Each | |
| 97 | 47 | Providing and fixing stainless steel (SS 304 grade) adjustable friction windows stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineer-in-charge complete. | |||
| 98 | 47.01 | 255 X 19 mm | 498 | Each | |
| 99 | 48 | Providing and fixing aluminium casement windows fastener of required length for aluminium windows with necessary screws etc. complete. | |||
| 100 | 48.01 | Polyester powder coated minimum thickness 50 micron aluminium | 249 | Each | |
| 101 | 49 | Providing and fixing of UL listed fire rated single/double leaf panic exit devices for two hours fire rated door with min one year warrantee. | |||
| 102 | 49.01 | Double Leaf Panic Bar Set | 13 | Nos. | |
| 103 | 50 | Providing and fixing of heavy duty door closer of approved quality for 120 min fire door with minimum one year warranty. | 13 | Each | |
| 104 | 51 | Providing and fixing fire rated mortice lock with lever handle with 80 mm long cylinder of approved manufacturer for 120 min fire reated door. | 4 | Each | |
| 105 | 52 | Providing and fixing 300 mm long stainless steel grade 304 D type back to back pull handle of approved make with necessary bolts with alen key arrangement etc complete for 120 min fire rated door. | 4 | Each | |
| 106 | 53 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. | |||
| 107 | 53.01 | With brass cover plate minimum 1.25 mm thickness | 9 | Each | |
| 108 | 54 | Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0 mm thick & 2100 mm long with SS screws etc .complete as per direction of Engineer-in-Charge. | |||
| 109 | 54.01 | Polyester powder coated minimum thickness 50 micron aluminium tubular handle bar | 18 | Each | |
| 110 | 55 | Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineer-in-charge. | 5 | Each | |
| 111 | 56 | Providing and fixing PVC rigid foam sheet 1 mm thick on door shutters (bathroom and W.C. doors) using synthetic rubber based adhesive | 33 | Sqm | |
| 112 | 56.01 | STEEL WORK | |||
| 113 | 57 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. | |||
| 114 | 57.01 | In gratings, frames, guard bar, ladder, railings, brackets, gates, signage and similar works. | 18038 | Kg | |
| 115 | 58 | Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer. | |||
| 116 | 58.01 | M.S. tube | 307 | Kg | |
| 117 | 59 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, ( for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). | 6050 | Kg | |
| 118 | 59.01 | FLOORING | |||
| 119 | 60 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc. complete. | |||
| 120 | 60.01 | 40mm thick with 20mm nominal size stone aggregate. | 20 | Sqm | |
| 121 | 61 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. | |||
| 122 | 61.01 | 18 mm thick | 5 | sqm | |
| 123 | 62 | Marble stone flooring with 18 mm thick marble stone, as per sample of marble approved by Engineer-in-charge, over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with grey cement slurry, including rubbing and polishing complete with : | |||
| 124 | 62.01 | Raj Nagar plain | 100 | Sqm | |
| 125 | 62.02 | Udaipur green/Jaiselmer marble | 620 | Sqm | |
| 126 | 63 | Providing and fixing machine cut, mirror / eggshell polished , Marble stone work for wall lining (veneer work) including dado, skirting, risers of steps etc., in required design and pattern wherever required, stones of different finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 oarse sand) laid and jointed with white cement slurry @ 3.3 kg/sqm including pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing, polishing etc. all complete as per Architectural drawings, and as directed by the Engineer-in-Charge. | |||
| 127 | 63.01 | 18 mm thick Flamed/polished granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent | 370 | Sqm | |
| 128 | 64 | Providing and laying Polished / flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building, all complete as per the architectural drawings, with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand), laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. | |||
| 129 | 64.01 | Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. | 2127 | Sqm | |
| 130 | 65 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : | |||
| 131 | 65.01 | 25 mm thick. | 747 | Sqm | |
| 132 | 66 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. | 40 | Sqm | |
| 133 | 67 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete. | 20 | Sqm | |
| 134 | 68 | Providing and laying rectified/ antiskid Glazed Ceramic floor tiles 300x300 mm or more (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigments etc., complete. | 20 | Sqm | |
| 135 | 69 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption's less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) including grouting the joints with white cement and matching pigments etc., complete. | |||
| 136 | 69.01 | Size of Tile 600x600 mm | 532 | Sqm | |
| 137 | 70 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer) with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make in all colours & shade in skirting, riser of steps and dado over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. | |||
| 138 | 70.01 | Size of Tile 600x600 mm | 1730 | Sqm | |
| 139 | 71 | Providing and fixing machine cut, mirror/ eggshell polished , Marble stone work for wall lining (veneer work) including dado, skirting, risers of steps etc., in required design and pattern wherever required, stones of different finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand) laid and jointed with white cement slurry @ 3.3 kg/sqm including pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing, polishing etc. all complete as per Architectural drawings, and as directed by the Engineer-in-Charge. | |||
| 140 | 71.01 | 18 mm thick Italian Marble stone slab, Perlato, Rosso verona, Fire Red or Dark Emperadore etc. | 12 | Sqm | |
| 141 | 72 | Providing and laying machine cut, mirror polished Marble stone flooring,in required design (Simple geometrical, abstract etc.) and in patterns in combination with Italian marble stones of different colours, shades and finished surface texture etc., in linear portions of the building, all complete as per the architectural drawings, with 18 mm thick stone slab laid over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with white cement slurry @ 4.4 kg/sqm including pointing with white cement slurry admixed with pigment to match the marble shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. | |||
| 142 | 72.01 | 18 mm thick Italian Marble stone slab, Perlato, Rosso verona,Fire Red or Dark Emperadore etc. | 341 | Sqm | |
| 143 | 73 | Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 (1 cement :4 coarse sand) : | |||
| 144 | 73.01 | Medium shade pigment using 50% white cement, 50% ordinary cement | 33 | Sqm | |
| 145 | 74 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels | |||
| 146 | 74.01 | Granite of any colour and shade | |||
| 147 | 74.02 | Area of slab upto 0.50 sqm | 5 | Sqm | |
| 148 | 74.03 | Area of slab over 0.50 sqm. | 20 | Sqm | |
| 149 | 75 | Extra for fixing marble /granite stone, over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive, including cleaning etc. complete. | 33 | Metre | |
| 150 | 76 | Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/Granite/stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.\n | 31 | Each | |
| 151 | 77 | 40 mm thick rubbed stone flooring over 20 mm (average) thick base of cement mortar 1:5 (1 cement : 5 coarse sand) with joints 3 mm thick, side buttered with cement mortar 1:2 (1 cement : 2 stone dust) admixed with pigment to match the shade of stone and pointing with same mortar. | |||
| 152 | 77.01 | Red sand stone | 372 | Sqm | |
| 153 | 77.02 | ROOFING | |||
| 154 | 78 | Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 | |||
| 155 | 78.01 | mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening“for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all Tsections shall be pre-painted with polyster baked paint,for all heights, as per specifications, drawings and as directed byEngineer-in-Charge. | |||
| 156 | 78.02 | Note :- Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall be made for exposed frames/ opening (cut outs) having area less than 0.30 sqm.The calcium silicate ceiling tile shall have NRC value of 0.50 (Minimum), light reflection > 85%, non- combustible as per B.S. 476 part IV, 100% humidity resistance and also having thermal conductivity <0.043 w/mK. | 279 | Sqm | |
| 157 | 79 | Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm ) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised @80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod upto 1000mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be prepainted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge. | |||
| 158 | 79.01 | With 16 mm thick beveled tegular mineral fibre Antimicrobial false ceiling tile | 1555 | Sqm | |
| 159 | 80 | Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1 200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle length with nuts & bolts of required size and other end of angle at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges section 0.5 mm thick bottom wedge of 80 mm with tapered flanges shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. | |||
| 160 | 80.01 | wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : | |||
| 161 | 80.02 | 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- Part I | 839 | Sqm | |
| 162 | 81 | Providing and fixing 10mm thick clear multi wall solar control polycarbonate sheets of approved quality and shade in desired shape in roofing including the cost of EPDM gaskets , sealing tape , aluminium profile and all necessary accessories complete as per architectural drawings and as directed by Engineer incharge. The item includes designing the complete system and supplying & getting approved from client and / or reputed engineering institue like IIT etc. The detailed shop drawings including supplying structural design calculations based on relevent codal provisions and carrying out water penetration test as per standards followed in India. | |||
| 163 | 81.01 | The whole work is to be done through reputed and approved vendor having experience in polycarbonate work in Commercial/ Govt/ Corporate buildings as per architectural elevation drawings including filling of joints with silicon sealent and also with masonary/ RCC work, at all heights including double heights, straight or curved etc. complete in all respect. ( Surface Area shall be measured for the payment) ( M.S. Framing to be paid for seprately ) | |||
| 164 | 81.02 | For Dome Structure | 851 | Sqm | |
| 165 | 82 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : | |||
| 166 | 82.01 | First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours. | |||
| 167 | 82.02 | Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. | 97 | Sqm | |
| 168 | 83 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm. of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs c) After two days of proper curing applying a second coat of cement slurry using 2.75kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. | |||
| 169 | 83.01 | d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : | |||
| 170 | 83.02 | With average thickness of 120 mm and minimum thickness at khurra as 65 mm. | 3078 | Sqm | |
| 171 | 83.03 | FINISHING | |||
| 172 | 84 | 12 mm cement plaster of mix : | |||
| 173 | 84.01 | 1:6 (1 cement: 6 fine sand) | 3438 | Sqm | |
| 174 | 85 | 15 mm cement plaster on the rough side of single or half brick wall of mix: | |||
| 175 | 85.01 | 1:4 (1 cement: 4 fine sand) | 406 | Sqm | |
| 176 | 85.02 | 1:6 (1 cement : 6 fine sand) | 5157 | Sqm | |
| 177 | 86 | 20 mm cement plaster of mix : | |||
| 178 | 86.01 | 1:4 (1 cement: 4 fine sand) | 1720 | Sqm | |
| 179 | 87 | 6 mm cement plaster of mix : | |||
| 180 | 87.01 | 1:3 (1 cement : 3 fine sand) | 2462 | Sqm | |
| 181 | 88 | Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof. | 323 | Sqm | |
| 182 | 89 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. | 12774 | Sqm | |
| 183 | 90 | White washing with lime to give an even shade : | |||
| 184 | 90.01 | New work (three or more coats) | 110 | Sqm | |
| 185 | 91 | Distempering with 1st quality acrylic distemper, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour. | |||
| 186 | 91.01 | Two Coats | 1106 | Sqm | |
| 187 | 92 | Finishing walls with Acrylic Smooth exterior paint of required shade : | |||
| 188 | 92.01 | New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) | 406 | Sqm | |
| 189 | 93 | Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content. | |||
| 190 | 93.01 | With ready mixed red oxide zinc chromatic on steel / iron works having VOC content less than 250 grams/ litre | 872 | Sqm | |
| 191 | 93.02 | With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre | 11055 | Sqm | |
| 192 | 94 | Finishing walls with textured exterior paint of required shade: | |||
| 193 | 94.01 | New work (Two or more coats applied @ 3.28 Itr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. | 2125 | Sqm | |
| 194 | 95 | Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. | |||
| 195 | 95.01 | Two Coats | 9950 | Sqm | |
| 196 | 96 | Painting with synthetic enamel paint, having VOC (Volatile Organic Compound) content less than 150 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. | |||
| 197 | 96.01 | Two Coats | 872 | Sqm | |
| 198 | 97 | Providing and fixing 150 mm wide, 22 gauge and 18mm square chicken wiremesh at junctions of concrete and brick work and other locations at all heights placed symmetrically on the joint, including cutting to required size, fixing in position with cement and nails etc complete in all respects as per specifications/drawings and to the entire satisfaction of the Engineer in Charge. | 664 | Sqm | |
| 199 | 97.01 | MISCELLANEOUS | |||
| 200 | 98 | Stone work (machine cut edges) for wall lining etc. (veneer work) upto 10 metre height, backing filled with a grout of average 12 mm thick cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment matching the stone shade : (To be secured to the backing and the sides by means of cramps and pins which shall be paid for separately) : | |||
| 201 | 98.01 | Gang saw cut stone | |||
| 202 | 98.02 | 30mm thick White sand stone | 1720 | Sqm | |
| 203 | 99 | Providing and fixing stainless steel cramps of required size and shape for anchoring stone wall lining to the backing or securing adjacent stones in stone wall lining in cement mortar 1:2 (1 cement : 2 coarse sand),including making the necessary chases in stone and holes in walls wherever required. | 6017 | Kg | |
| 204 | 100 | Providing and fixing copper pins 7.5 cm long 6 mm diameter for securing adjacent stones in stone wall lining in cement mortar 1:2 (1 cement : 2 coarse sand), including making the necessary chases. | 220 | each | |
| 205 | 101 | Providing and fixing Glass mossaic tiles on finished plain wall surface of size 20 mm x 20 mm x 4 mm in all colour, design , fixing in approved design. The glass mosaic tiles shall be fixed on the wall surface with the help of approved adhesive applied at the rate of 2.5 kg per sqm and grouting of the same. All completed as per direction of Engineer-incharge. | 26 | sqm | |
| 206 | 102 | Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. (The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account). | 1214 | Kg | |
| 207 | 103 | Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including: | |||
| 208 | 103.01 | Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: | |||
| 209 | 103.02 | Fabricating and supplying serrated M.S. hot dip galvanised /Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. | |||
| 210 | 103.03 | Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. | |||
| 211 | 103.04 | Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. | |||
| 212 | 103.05 | Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. | |||
| 213 | 103.06 | Note:- 1. The cost of providing extruded aluminium frames,shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub- head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places. | |||
| 214 | 103.07 | Note:- 2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NBL Certified laboratories | |||
| 215 | 103.08 | 1. Performance Laboratory Test for Air Leakage Test (-50pa to –300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr” | |||
| 216 | 103.09 | 2. Static Water Penetration Test. (50pa to 1500pa) as per ASTME-331-09 testing method for a range up to 2000 ml.” | |||
| 217 | 103.1 | 3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01-05 testing method for a range upto 2000 ml” | |||
| 218 | 103.11 | 4. Structural Performance Deflection and deformation by static air pressure test (1.5 times desing wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm” | |||
| 219 | 103.12 | 5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing method for Qualitative test” Tests to be conducted on site | |||
| 220 | 103.13 | 6. Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000ml” | 162 | Sqm | |
| 221 | 104 | Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified,comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor.“(Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.26.2)“For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm.“ | |||
| 222 | 104.01 | Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. | 17 | Sqm | |
| 223 | 105 | Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all accessories and hardwares for the openable panels as specified and of the approved make such as heavy duty stainless steel friction hinges, min 4 -point cremone locking sets with stainless steel plates, handles, buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all complete as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer- in-Charge. | 17 | Sqm | |
| 224 | 106 | Proving and fixing glass Reinforced Concrete (G.R.C) Screens in approved size, pattern design, thickness and color of approved make .The Screen should be made from White Portland cement ,Quartz, Fine Silica Sand, Alkali Resistant Glass Fibre Super Plasticizer Polymer and U.V resistant Synthetic inorganic pigment for pigmentation. The material casting should take place in Synthetic Rubber /FRP moulds of approved make & shape. The fixing of screens to be done with Stainless Steel (SS-304) ‘L’ shaped Clamps, dash fasteners and pins, as required at site. | |||
| 225 | 106.01 | Technical specification of GRC Screens. | |||
| 226 | 106.02 | Internal member thickness 30 mm and border thickness 50 mm Dry Density: 1800 kg/m3 (min)\nWater absorption: Less than 6% of dry weight by immersion over a period of 24 hours.\nCompressive strength: (M-40 Grade)\nWet Transverse Strength: 7 N/mm (min)\nAbrasion Resistance: Less than 2.0 for E.H.D\nThermal Conductivity: 1.63 W/MK at 3% moisture content\n : 1.80W/MK at 5% moisture content\n | 347 | Sqm | |
| 227 | 107 | Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement: 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth. | 372 | Sqm | |
| 228 | 108 | Manufacturing, supplying and fixing retro reflective overhead signage boards made up of 2 mm thick aluminium sheet, face to be fully covered with high intensity and encapsulated lens type heat activated retro reflective sheeting conforming to type - III of ASTM-D-4956-01 as approved by Engineer-in-charge, letters, borders etc. as per IRC : 67-2001 in silver white with blue colour back ground and with high intensity grade, pasted on substrate by pressure sensitive adhesive backing which shall be activated by applying pressure conforming to class II ofASTM-D-4956-01 and fixing the same to the plate of structural frame work by means of suitable sized aluminium alloys, rivets or bolts & nuts @ 300 mm centre to centre all along the periphery as well as in two vertical rows along with theft resistant measures, including the cost of painting with two or more coats of epoxy paint in grey colour on the back side of aluminium sheet including appropriate priming coat. | |||
| 229 | 108.01 | The rate includes the cost of rounding off the corners, lowering down the structural frame work from the gantry, fixing and erecting the same in position all complete as per drawings, specification and direction of the engineer-in-charge.(Structural frame work including M.S. plate to be provided separately. Rectangular area of the sheet only shall be measured for seperately. | |||
| 230 | 108.02 | Overhead informatory road signage | 20 | Sqm | |
| 231 | 108.03 | Providing and applying 2.5 mm thick road marking strips (retro- reflective) of specified shade/ colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface including cost of material, labour ,T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc. complete as per direction of Engineer-in-charge and accordance with applicable specifications. | 50 | Sqm | |
| 232 | 109 | Providing fabricating and fixing of signages of varying sizes and shapes using three mm thick PVC sheet at base with self addhesive coloured vinyl with graphicson top of glow tape complete including fixing on wall with screws and washers or hanging on ceiling with GI chain/GI Bar complete as per technical specifications and directions of Engineer. | 10000 | Sqcm | |
| 233 | 110 | Providing and fixing of sinages of varying sizes and shapes using stainless steel sheet of minimum 16G thickness brush finish including engraving/etching of letters of required size filled with colour as desired by engineer,fixing with ss screws on walls. | 20000 | Sqcm | |
| 234 | 111 | Providing & fixing of EDGELIT signage with battery back up made from acrylic sheet of 8 mm thickness laser engraved, transformer to be inbuilt Maintenance-free sealed nickel cadmium battery including • 120V/277V AC Operation • Crystal clear acrylic • Engraved letters increase visibility • Anodized aluminum faceplate • Field applied chevron directional indicators simplify installation • Energy-saving LED lamps • UL listed | 10000 | Sqcm | |
| 235 | 112 | Providing, fabricating installation and fixing of LED LIT glass finish SS & acrylic letters sides made of 20 gauge SS 304 sheet of required size and shape with neatly fabricated joints properly welded and grinded with all corners rubbed and polished and top made of white imported acrylic sheet with bright white LEDs inside with arrangement of screws in the letters itself for mounting on the walls including cost of screws and fixing complete as per directions of engineer. (max length and max height of each letter to be used for finding area) | 10000 | Sqcm | |
| 236 | 113 | Providing, fabricating and fixing of LED signages made from acrylic 2 sheets + LED strips & power supply with the message print out and stainless steel studs on the walls including cost of screws and fixing complete as per directions of engineer. | 5 | Sqm | |
| 237 | 114 | Providing. Fabricating and fixing of Aluminium Composite Panel Signages with 3mm thick ACP Sheet, using 25X25 mm MS pipe Frame of approved qualiy with anti rust coating, back with G.I. and 5 Sides with ACP Sheet (alucobond or equivalent approved make), lettering to be done with 5mm Acrylic Sheet and Vinyl's( if Needed), backlit with (Philips or approved equivalent) Slim Lite Tube light Fittings, Acrylic Letters to Protrude out and be lit, together with a timer for switching on and off automatically at night and day including transportation and fixing at site as per the direction of the site engineer. | 5 | Sqm | |
| 238 | 115 | Providing & Fixing Wall Mounted Nonlit Fire Exit 61 cm x 23 cm Internal sign of approved make & made of 10mm Acrylic with the required text matters stuck on it with plotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panel bracketed at suitable locations including necessary fittings & fastening etc. complete & as directed by The Engineer in charge. | 30 | Each | |
| 239 | 116 | Providing & Fixing Suspended Nonlit sign 122x23 cm of approved make & made of 1\" Aluminium framing duly PU painted and 10mm Acrylic element mounted to it from either side with the required text matters stuck on it with plotted Self Adhesive Vinyl bracketed at suitable locations, including necessary fittings & fastening etc. complete & as directed by The Engineer in charge. | 50 | Each | |
| 240 | 117 | Providing & Fixing Wall Mounted Nonlit Utility 15x15 cm Internal sign of approved make & made of 10mm Acrylic with the required text matters stuck on it with plotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panel bracketed at suitable locations including necessary fittings & fastening etc. complete & as directed by The Engineer in charge. | 50 | Each | |
| 241 | 118 | Providing & Fixing Wall Mounted Nonlit Identification sign 46x12.5 cm of approved make & made of 10mm Acrylic with the required text matters stuck on it with plotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panel bracketed at suitable locations including necessary fittings & fastening etc. complete & as directed by The Engineer in charge. | 50 | Each | |
| 242 | 119 | Providing & Fixing Wall Mounted Nonlit Utility 61x23 cm Internal sign of approved make & made of 10mm Acrylic with the required text matters stuck on it with plotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panel bracketed at suitable locations including necessary fittings & fastening etc. complete & as directed by The Engineer in charge. | 50 | Each | |
| 243 | 120 | Providing & Fixing Wall Mounted Nonlit directory sign 91x61 cm of approved make & made of 10mm Acrylic with the required text matters stuck on it with plotted self adhesive vinyl & Mounted on 3mm Aluminium Composit Panel bracketed at suitable locations including necessary fittings & fastening etc. complete & as directed by The Engineer in charge. | 5 | Each | |
| 244 | 121 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. | |||
| 245 | 121.01 | Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) | 3 | cum | |
| 246 | 121.02 | Nominal concrete 1:4:8 or leaner mix (i/c equivalent design mix) | 9 | cum | |
| 247 | 122 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge. | 28 | cum | |
| 248 | 123 | Extra for cutting reinforcement bars manually/ by mechanical means in R.C.C. or R.B. work (Payment shall be made on the cross sectional area of R.C.C. or R.B. work) as per direction of Engineerin-charge. | 3 | sqm | |
| 249 | 124 | Demolishing brick work manually by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. | |||
| 250 | 124.01 | In cement mortar | 107 | cum | |
| 251 | 125 | Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : | |||
| 252 | 125.01 | Of area 3 sq. metres and below | 11 | each | |
| 253 | 126 | Dismantling steel work in single sections including dismemberin \nand stacking within 50 metres lead in: | |||
| 254 | 126.01 | Channels, angles, tees and flats | 110 | kg | |
| 255 | 127 | Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead. | |||
| 256 | 127.01 | For thickness of tiles 10 mm to 25 mm | 55 | sqm | |
| 257 | 128 | Dismantling stone slab flooring laid in cement mortar including stacking of serviceable material and disposal of unserviceable material within 50 metres lead. | 55 | sqm | |
| 258 | 129 | Demolishing brick tile covering in terracing including stacking of serviceable material and disposal of unserviceable material within 50 metres lead. | 110 | sqm | |
| 259 | 130 | Demolishing mud phaska in terracing and disposal of material within 50 metres lead. | 17 | cum | |
| 260 | 131 | Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable surplus material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge. | 22 | sqm | |
| 261 | 132 | Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as ap approved by Engineer-in-charge, beyond 50 m initial lead, for all leadsincluding all lifts involved. | 145 | cum | |
| 262 | 132.01 | ROAD WORK & HORTICULTURE | |||
| 263 | 133 | Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm. depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earth lead upto 50 metres. | 2200 | Sqm | |
| 264 | 134 | Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. | |||
| 265 | 134.01 | With material conforming to Grade-I (size range 75 mm\nto 0.075 mm) having CBR Value-30 | 440 | Cum | |
| 266 | 135 | Construction of dry lean cement concrete sub base over a prepared sub-grade with coarse and fine aggregate conforming to IS:383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per specifications, cement content not to be less than 150 Kg/cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, for all leads & lifts, laid with a mechanical paver, compacting with 8-10 tonne vibratory roller, finishing and curing etc. complete as per direction of Engineer-in- charge. | 120 | Cum | |
| 267 | 136 | Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 40 mm nomina size in appropriate proportions as per approved & specified design criteria, providing dowel bars with sleeve/ tie bars wherever required,laying at site, spreading and compacting mechanically by using needle and surface vibrators, levelling to required slope/ camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints ( 10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in-charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars to be paid separately). | |||
| 268 | 136.01 | Note:- Cement content considered in M-30 is @ 340 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately. | |||
| 269 | 136.02 | Cement concrete prepared with batch mixing machine | 180 | Cum | |
| 270 | 137 | Extra for providing and mixing hardening compound of approved quality as per manufacturer's specification in cement concrete. | 2400 | litre | |
| 271 | 138 | Providing and fixing in position pre-moulded joint filler in expansion joints. | 7000 | Per cm depth per cm width per m length | |
| 272 | 139 | Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction and of approved size and design/ shape laid in required colour and pattern over and including 50mm thick compacted bed of fine sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. | 1000 | sqm | |
| 273 | 140 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement in position to the required line, level and curvature jointed with cement mortar 1:3 (1 cement: 3 coarse sand) including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm) including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). | 67 | Cum | |
| 274 | 141 | Trenching in ordinary soil upto a depth of 60cm including removal and stacking of serviceable materials and then disposing surplus soil, by spreading and neatly levelling with in a lead of 50m and making up the trenched area to proper levels by filling with earth or earth mixed with sludge or/and manure before and after flooding trench with water (excluding cost of imported earth, sludge or manure). | 600 | Cum | |
| 275 | 142 | Supplying and stacking sludge at site including royalty and carriage complete (sludge measured in stacks will be reduced by 8% for payment). | 100 | Cum | |
| 276 | 143 | Supplying and stacking at site dump manure from approved source, including carriage complete (manure measured in stacks will be reduced by 8% for payment). | 100 | Cum | |
| 277 | 143.01 | Screened through sieve of I.S. designation 16 mm | |||
| 278 | 144 | Rough dressing the trenched ground including breaking clods & Uprooting weeds from the trenched area after 10 to 15 days of its flooding with water including disposal of uprooted vegetation. | 2000 | Sqm | |
| 279 | 145 | Fine dressing the ground | 2000 | Sqm | |
| 280 | 146 | Spreading of sludge, dump manure or/and good earth in required thickness including mixing earth and sludge or manure in the required proportion specified or directed by the Officer in Charge (Cost of sludge, dump manure or/ and good earth to be paid separately). | 200 | Cum | |
| 281 | 147 | Proving & fixing Selection no.1 grass turf with earth 50 mm to 60 mm thickness of existing ground prepared with proper level and ramming with required tools wooden (Dhurmos) and than rolling the surface with light roller make the surface smoothening and watering. | 2000 | Sqm. | |
| 282 | 148 | Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure or sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20% : 1part of stacked volume of manure after reduction by 8%) flooding with water, dressing including removal of rubbish and surplus earth, if any with all leads and lifts (cost of manure, sludge or extra good earth if needed to be paid for separately): | |||
| 283 | 148.01 | Holes 1.2 m dia and 1.2 m deep. | 25 | Each | |
| 284 | 148.02 | Holes 60 cm dia, and 60 cm deep. | 25 | Each | |
| 285 | 148.03 | SANITARY FIXTURES | |||
| 286 | 149 | Providing&fixing water closet squatting pan( Indian W.C.Pan)with 100 mm sand cast iron P or S strap,10 Litre low level white P.V.C flushing cistern with manually controled device(handle lever) conforming to IS:7231 with all fittings & fixture complete including cutting and making good the walls & floors whereever required.(Parryware model no. C0117 or other equivalent model as per approved make) | |||
| 287 | 149.01 | White vitreous china orissa pattern W.C. pan of size 580 x 440 mm with integral type foot rests. | 2 | Each | |
| 288 | 150 | Providing and fixing white vitreous china Pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous flushing cistern and C.P. flush bend with fittings & C.I. brackets, 40mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete including painting of fittings and brackets, cutting and making good the walls and floors wherever required:(Parryware model no. C0271 or other equivalent as per approved make | |||
| 289 | 150.01 | W.C. pan with ISI black solid plastic seat & lid. | 30 | Each | |
| 290 | 151 | Providing and fixing wash basin with C.I. brackets, 15mm C.P. brass pillar taps, 32mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required:(Jaquar or other equivalent approved make. | |||
| 291 | 151.01 | White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap | 28 | Each | |
| 292 | 152 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- (a) White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer. (Roca model no RT5A3127CA1 &RS325463 OR other equivalent model as per approved make | |||
| 293 | 152.01 | White Vitreous China Wash basin size 550x400 mm with a\n15 mm CP Brass single hole basin mixer | 10 | Each | |
| 294 | 153 | Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings. | 2 | Each | |
| 295 | 154 | Providing and fixing Stainless Steel A ISi 304 (18/8) kitchen sink as\nper IS: 13983 with C.I. brackets and stainless steel plug 40 mm,\nincluding painting of fittings and brackets, cutting and making good\nthe walls wherever required : | |||
| 296 | 154.01 | Kitchen sink with drain board | |||
| 297 | 154.02 | 510x1040 mm bowl depth 225 mm | 1 | Each | |
| 298 | 154.03 | Kitchen sink without drain board | |||
| 299 | 154.04 | 610x460 mm bowl depth 200 mm | 2 | Each | |
| 300 | 155 | Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean type W.C. of quality and make as approved by Engineer - in -charge.code RF9061A1 From Roca or other equivalent make. | 10 | Each | |
| 301 | 156 | Providing and fixing CP Brass 32mm size Bottle Trap of approved quality & make and as per the direction of Engineerin- charge.RF 9066A1 From Roca or other equivalent make. | 40 | Each | |
| 302 | 157 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. | |||
| 303 | 157.01 | Semi rigid pipe | |||
| 304 | 157.02 | 32 mm dia | 40 | Each | |
| 305 | 157.03 | 40 mm dia | 10 | Each | |
| 306 | 158 | Providing and fixing superior glass mirror (of approved quality) and of required shape and size with plastic moulded frame of approved make and shape with 6 mm thick hard board backing. | |||
| 307 | 158.01 | Rectangular shape 453x357 mm | 30 | Each | |
| 308 | 158.02 | Rectangular shape 1500x450 mm | 3 | Each | |
| 309 | 159 | Providing and fixing 600x120x5 mm glass shelf with edges round of supported and anodised alominium angle frame with C.P. brass brackets and guard rail complete fixed with 40 mm long screws, rawl plugs etc., complete. Code no RA816708001 from Roca or othe equivalent make) | 3 | Each | |
| 310 | 160 | Providing and fixing toilet paper holder. (Roca model no. or other equivalent model as per approved make) code RA816713001 from roca or other equivalent make | |||
| 311 | 160.01 | C.P. brass | 35 | Each | |
| 312 | 161 | Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/ 6 litre (adjustable to 4 litre/ 8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete.(Roca model no.RS342617460 & RA80N612001 or other equivalent model as per approved make | 3 | Each | |
| 313 | 162 | Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 mlconsumption), havingwater inlet from back side, including fixing to wall with suitablebrackets all as per manufacturers specification and direction of Engineer-in-charge ROCA model no. RS35945E000 or other equalvalent model as per approved make. | 17 | Each | |
| 314 | 163 | Providing and fixing floor mounted, white vitreous china single piece, double traps syphonic water closet of approved brand/ make, shape, size and pattern including integrated white vitreous china cistern of capacity 10 litres with dual flushing system, including all fittings and fixtures with seat cover, cistern fittings, nuts, bolts and gasket etc including making connection with the existing P/S trap, complete in all respect as per directions of Engineer-in-Charge.(ROCA model no. RS349467000 & RE80P467001 or other equivalent model as per approved make) | 3 | Each | |
| 315 | 164 | Exta for Providing and fixing wall hung water closet with seat cover of approved model and slim concealed flushing cistern of 9 litre capacity, body with floor mounted frame and installation kit with SS actuating panel with dual flush with fittings in place of pedestal type water closet 10 lits. & vitreous china cistern ,complete of Roca make & model RS 34630346S,RA80P396461 & RA890031410 respectively or equivalent model of other approved make as approved by Engineer-in-charge. | 30 | Each | |
| 316 | 165 | Poviding and fixing health faucet with pipe and hook complete ( Roca model no. RF9060A1 or other equivalent model as per approved make) | 30 | Each | |
| 317 | 166 | Extra for providing and fixing white vitreous china oval shape wash basin in place of normal wash basin of size 580x440 | |||
| 318 | 166.01 | under Counter oval shape wash basin size 600x390mm approx. (centre tap hole) along with , single 15 mm CP brass pressmatic type pillar tap.(Roca mopdel no. RS327893000 and RT5A4277C00 or other equivalent model as per approved make) | 30 | Each | |
| 319 | 167 | Providing and fixing white vitreous china urinal of approx. size 797x 425 mm having top inlet urinal with CP brass pressmatic urinal valve auto closing system with built in control cock & wall flanged complete icluding fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge.(roca model no. RS35945H000 & Jaquar model no.PRS-077 or other equivalent model as per approved make) | 2 | Each | |
| 320 | 168 | Extrafor providing and fixing Sentronic Concealed Urinal Sensor Powered by 220 volts-AC. Concealed box diamension: 110x110x92 mm Front plate dimention :120 x120 mm in place of pressmatic urinal valve. code RT5X9215E00 from roca or other equivalent make. | 17 | Each | |
| 321 | 169 | P&F wall Soap Holder with brackets' , complete fittings of roca or other equivalent approved make ( Jaquar or other equivalent model as per approved make) | 10 | Each | |
| 322 | 170 | Providing and fixing Liquid Soap Dispenser all cmplete (Roca model No. RA 816070105 or equivalent model approved make) | 38 | Each | |
| 323 | 171 | Providing and fixing CP brass towel rail complete of approve quality and colour .(Jaquar or other equivalent make.) | |||
| 324 | 171.01 | 600 mm long towel rail | 38 | Each | |
| 325 | 172 | providing and fixing CP Brass bottle trap for sink and urinal basin including CP waste fittings complete 40 mm dia complete in all respect of approved quality. | 6 | Each | |
| 326 | 173 | providing & fixing double robe hook with all complete fittings(Jaquar or other equivalent model as per approved make) | 38 | Each | |
| 327 | 174 | Providing and fixing beveled edge mirror 6 mm thick of superior glass(of approved quality) complete with 6 mm thick hard board ground fixed to wooen cleats with ss studds complete | 5 | Sqm | |
| 328 | 175 | Supply and instaling of Grab Bar S type-304,18-gauge(1mm) stainless steel tubing with satin-finish.1-/2''(25.4 mm) outside dia.Concealed mounting flanges- 18-8 S,type-304, stainless steel palte: end flanges with two holes for attachments to wall. stainless steel with satin-finish. Each cover snaps over mounting flange to conceal mounting screws.make Euronics or equivalent-600 mm(L) | 2 | Each | |
| 329 | 176 | Providing & fixing SS body solid state fully hygienic no touch Hand Drier of approved make rated for continuous repeat usage with solid state time delay LSF protection, with independent ambient light level & seasonal control temperatures including providing necessary C.I./M.S. brackets painted with two or three coats of enamel paint of approved shade over a coat of primer, wiring cables from drier to plug, plug tops etc. complete including cutting and making good the walls wherever required. | 5 | Each | |
| 330 | 176.01 | SOIL, WASTE AND VENT PIPES | |||
| 331 | 177 | Providing and fixing soil, waste and vent pipes-Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 (make: NECO, HEPCO & SANT GOVIND/SKF) | |||
| 332 | 177.01 | 100 mm dia-Hubless centrifugally cast (spun) iron pipes epoxy\ncoated inside & outside IS:15905 | 319 | Metre | |
| 333 | 177.02 | 150 mm dia-Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905 | 10 | Metre | |
| 334 | 178 | Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. | |||
| 335 | 178.01 | 100 mm dia-Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905 | 19 | Each | |
| 336 | 178.02 | 150 mm dia-Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905 | 10 | Each | |
| 337 | 179 | Providing and fixing plain bend of required degree. | |||
| 338 | 179.01 | 100 mm -Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905 | 51 | Each | |
| 339 | 179.02 | 150 mm dia-Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside | 10 | Each | |
| 340 | 180 | Providing and fixing double equal plain junction of required degree. | |||
| 341 | 180.01 | 100x100x100x100 mm Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside | 9 | Each | |
| 342 | 181 | Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3mm thick, bolts and nuts complete. | |||
| 343 | 181.01 | 100x100x100mm - H.L.C.C.I | 11 | Each | |
| 344 | 181.02 | 150x 150x 150 mm-H.L.C.C.I | 10 | Each | |
| 345 | 182 | Providing and fixing single equal plain junction of required degree | |||
| 346 | 182.01 | 100x100x100mm -Hubless centrifugally cast (spun) iron epoxy coated inside & outside | 11 | Each | |
| 347 | 182.02 | 150x150x150-Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside | 5 | Each | |
| 348 | 182.03 | 200 X200X200 mm dia-Hubless centrifugally cast (spun) iron epoxy coated inside & outside | 5 | Each | |
| 349 | 183 | Providing and fixing single unequal plain junction of required degree | |||
| 350 | 183.01 | 150x150x100 mm-H.L.C.C.I | 11 | Each | |
| 351 | 184 | Providing and fixing door piece, insertion rubber washer 3mm thick, bolts and nuts complete | |||
| 352 | 184.01 | 100 mm CI | 19 | Each | |
| 353 | 185 | Providing and fixing terminal guard. | |||
| 354 | 185.01 | 100 mm-Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905 | 11 | Each | |
| 355 | 186 | Providing and fixing shielded coupling for Hubless centrifugally cast iron pipe of same manufactureing. | |||
| 356 | 186.01 | 100 mm dia-SS 304 grade coupling with EPDM rubber gasket | 319 | Each | |
| 357 | 186.02 | 150 mm dia | 10 | Each | |
| 358 | 187 | Providing and fixing M.S. stays and clamps for sand cast iron / centrifugally cast (spun) iron pipes of diameter : | |||
| 359 | 187.01 | 100 mm | 7 | Each | |
| 360 | 187.02 | 150 mm dia | 3 | Each | |
| 361 | 188 | Providing and fixing Trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors: | |||
| 362 | 188.01 | 100 mm inlet and 100 mm outlet-Hubless centrifugally cast (spun) iron epoxy coated inside & outside | 55 | Each | |
| 363 | 189 | Cutting chases in brick masonary walls for following diameter sand cast iron/centrifugally cast (spun) iron pipes and making good the same with cement concrete 1:3:6 (1 cement:3 coarse sand:6 graded stone aggregate 12.5 mm nominal size) including necessary plaster and pointing in cement mortar 1:4 (1 cement: 4 coarse sand): | |||
| 364 | 189.01 | 100 mm diameter pipe | 11 | Metre | |
| 365 | 190 | Painting sand cast iron / centrifugally cast (spun) iron soil, waste vent pipes and fittings with paint of any colour such as chocolate, grey, or buff etc. over a coat of primer (of approved quality) for new work: | |||
| 366 | 190.01 | 100 mm diameter pipe | 319 | Metre | |
| 367 | 191 | Providing and fixing M.S. holder bat clamp of approved design to sand cast iron/ cast iron (spun) pipes comprising of M.S. flat brackets made of 50x5 mm flat of specified shape, projecting 75 mm outside the wall surface and fixed on wall with 4nos, 6mm dia expansion hold fasteners, including drilling necessary holes in brick wall/ CC/ RCC surface and the cost of bolts etc. The pipes shall be fixed to the already fixed brackets with the help of 30 mm x1.6 mm galvanised M.S. flats of specified shape and of total length 420 mm and shall be fixed with M.S. nuts, bolts, & washers of size 25x6 mm, one bolts on each side of the pipe. | |||
| 368 | 191.01 | Total bracket length 580 mm of approved shape and design (for single 100/150 mm dia pipe) | 55 | Each | |
| 369 | 191.02 | Total bracket length 810 mm of approved shape and design (for two 100/150 mm dia pipes or 150mmm) | 6 | Each | |
| 370 | 191.03 | Total bracket length 1040 mm of approved shape and design (for three 100/150 mm dia pipes) | 6 | Each | |
| 371 | 191.04 | Total bracket length 1540 mm of approved shape and design (for three 200/150 mm dia pipes) | 6 | Each | |
| 372 | 192 | Providing and fixing GI pipes complete with GI fittings and clamps, i/c cutting and making good the walls etc and making good the same for waste water disposal complete as per direction of engineer incharge. | |||
| 373 | 192.01 | 32 mm dia nominal bore (Wash basin to floor trap/floor drain) | 42 | Metre | |
| 374 | 192.02 | 40 mm dia nominal bore (Sink,Urinal to floor trap) | 22 | Metre | |
| 375 | 192.03 | 50 mm dia nominal bore (Floor Drain to Floor Trap) | 33 | Metre | |
| 376 | 193 | Providing and fixing floor drain & balcony drain made of 100 x 50 mm dia elbow / tee as applicable connected with 50 mm dia GI pipe painted with primer, two coats of black bituminastic paint,wrapping 1 mm thick PVC tape and final coat of black bituminastic paint B109 complete in all complete including cutting and making good the walls and floor wherever required | 28 | Each | |
| 377 | 194 | Providing and laying cement concrete 1:2:4 (1 cement:2 coarse sand:4 graded stone aggregate 20 mm nominal size) 80 mm thick all-round the SCI/centrifugally S&S pipe diameter. | |||
| 378 | 194.01 | 100/150 mm dia | 110 | Metre | |
| 379 | 195 | Providing and fixing dash fastner made of rust proof plated steel for holding the soil/waste supply pipes complete in all respect | |||
| 380 | 195.01 | Dash fastner for pipe more than 25 mm dia to 150 mm dia pipe of size 25 mm dia and 75 mm long minimum & shall be capable of taking 6 tonnes load and also include the supporting angles 35x35x5 mm/ of required size or MS bars steel structures as per drawing. | 319 | Each | |
| 381 | 196 | Providing and fixing SS floor trap (FD+FT) grating 143x143x5 mm thick screwable with SS fixed framed of 150x150 mm size as per approved make and model | 33 | Each | |
| 382 | 197 | Providing and laying Laboratory/hospital effluent waste pipe and fitting of high density polyethelene (HDPE),CLASS -PE 80 ,pressure rating PN-6,conforming to IS :4427, electric fusion joints/flanged joints , fittings which includes bends,,junctions,cowls,offsets,access pieces.etc. complete including jointing. | |||
| 383 | 197.01 | 50 mm dia | 50 | meter | |
| 384 | 197.02 | 90 mm dia | 30 | meter | |
| 385 | 197.03 | 110 mm dia | 25 | meter | |
| 386 | 198 | Providing and fixing floor clean out plug consist of CI bend & GI socket heavy class with Brass cap & key for opening male threaded cap etc. including lead caulked to CI pipescomplete in all respects as per drawing/ sample approved by Engineer -in -ChargeFCO (floor clean out plug shall be flushed with floor finish | |||
| 387 | 198.01 | 100 mm dia/150/200 mm dia | 51 | Each | |
| 388 | 199 | Providing and fixing G.I EXTENSION PIECE for 100 mm dia floor trap formed out of main pipe( Type A) with multiple side inlets, suitable for various dia pipes, side connections, including all fixtures and fittings as per site conditions and as per standard details and water tight sealing of joints and area surrounding the grating and as directed. | 68 | Each | |
| 389 | 200 | Providing and fixing WC connector socket(for vitreous china & CI pipe) of EDPM good quality with polypropelene body 100x150/100x250 of approved quality and make complete in all respect. | 33 | Each | |
| 390 | 200.01 | WATER SUPPLY | |||
| 391 | 201 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. INTERNAL WORK - EXPOSED ON WALL | |||
| 392 | 201.01 | Internal work – Exposed on wall | |||
| 393 | 201.02 | 15 mm nominal outer dia Pipes(SDR-11) | 20 | Metre | |
| 394 | 201.03 | 20 mm nominal outer dia Pipes(SDR-11) | 40 | Metre | |
| 395 | 201.04 | 25 mm nominal outer dia Pipes(SDR-11) | 175 | Metre | |
| 396 | 201.05 | 32 mm nominal outer dia Pipes(SDR-11) | 200 | Metre | |
| 397 | 201.06 | 40 mm nominal outer dia Pipes(SDR-11) | 150 | Metre | |
| 398 | 201.07 | 50 mm nominal outer dia Pipes(SDR-11) | 125 | Metre | |
| 399 | 201.08 | 62.5 mm nominal inner dia Pipes(SCH-80) | 20 | Metre | |
| 400 | 202 | Providing and fixing Chlorinated Polyvenyl Chloride(CPVC)pipes having thermal stability for hot & cold water supply including all CPVC plain &brass threaded fittings i/c fixing the pipe with clamps at 1.0 m spacing.This includes jointing of pipes &fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints ciomplete as per direction of Engineer in charge. | |||
| 401 | 202.01 | Concealed work including cutting chases and making good the walls etc. | |||
| 402 | 202.02 | 15 mm nominal outer dia pipes (SDR-11) | 100 | Metre | |
| 403 | 202.03 | 20 mm nominal outer dia pipes (SDR-11) | 325 | Metre | |
| 404 | 202.04 | 25 mm nominal outer dia pipes (SDR-11) | 165 | Metre | |
| 405 | 202.05 | 32 mm nominal outer dia pipes (SDR-11) | 50 | Metre | |
| 406 | 202.06 | 40mm nominal outer dia pipes (SDR-11) | 20 | Metre | |
| 407 | 203 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. | |||
| 408 | 203.01 | External Work | |||
| 409 | 203.02 | 32 mm nominal outer dia pipes (SDR-11) | 10 | Metre | |
| 410 | 203.03 | 40 mm nominal outer dia pipes (SDR-11) | 40 | Metre | |
| 411 | 203.04 | 50 mm nominal outer dia Pipes (SDR-11) | 100 | Metre | |
| 412 | 203.05 | 62.5 mm nominal inner dia Pipes (SCH-80) | 45 | Metre | |
| 413 | 203.06 | 75 mm nominal inner dia Pipes (SCH-80) | 15 | Metre | |
| 414 | 203.07 | 100 mm nominal inner dia Pipes (SCH-80) | 10 | Metre | |
| 415 | 203.08 | 150 mm nominal inner dia Pipes (SCH-80) | 10 | Metre | |
| 416 | 204 | Making connection of G.I./CPVC distribution branch with G.I./D.I main of following sizes by providing and fixing tee, including, cutting and threading the pipe etc. commplete including obtaining approval for connection from Municipal corporation , if required | |||
| 417 | 204.01 | 25 to 150 mm nominal bore | 1 | Each | |
| 418 | 205 | providing and fixing Gun metal gate valve with C.I. wheel of approved quality (screwed end) | |||
| 419 | 205.01 | 25 mm nominal bore | 10 | Each | |
| 420 | 205.02 | 20 mm nominal bore | 10 | Each | |
| 421 | 205.03 | 32 mm nominal bore | 10 | Each | |
| 422 | 205.04 | 40 mm nominal bore | 10 | Each | |
| 423 | 205.05 | 50 mm nominal bore | 5 | Each | |
| 424 | 205.06 | 65 mm nominal bore | 5 | Each | |
| 425 | 205.07 | 80 mm nominal bore | 5 | Each | |
| 426 | 206 | Providing and fixing Ball valve (brass) of approved quality, High or low pressure with plastic floats complete | |||
| 427 | 206.01 | 15 mm | 2 | Each | |
| 428 | 206.02 | 20mm. | 4 | Each | |
| 429 | 207 | Providing and fixing Gun metal non-return valve of approved quality (screwed end) | |||
| 430 | 207.01 | 25 mm nominal bore | |||
| 431 | 207.02 | Horizontal | 3 | Each | |
| 432 | 207.03 | 40 mm nominal bore | |||
| 433 | 207.04 | Horizontal | 3 | Each | |
| 434 | 207.05 | 50 mm nominal bore | |||
| 435 | 207.06 | Horizontal | 3 | Each | |
| 436 | 207.07 | 80 mm nominal bore | |||
| 437 | 207.08 | Horizontal | 1 | Each | |
| 438 | 208 | Providing and fixing brass Ferrule with C.I. mouth cover including boring and tapping the main | |||
| 439 | 208.01 | 25 mm nominal bore or as per required size | 1 | Each | |
| 440 | 208.02 | 40mm to 65 mm dia bore | 2 | Each | |
| 441 | 209 | Providing and fixing unplasticised PVC connection pipe with brass unions: | |||
| 442 | 209.01 | 45 cm length | |||
| 443 | 209.02 | 15 mm nominal bore | 100 | Each | |
| 444 | 210 | Constructing masonary chamber 30x30x50 cm, inside with 75 class designation brick work in cement mortar 1:4 (1 cement: 4 coarse sand) for stop cock, with C.I. surface box 100x100x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement: 2 coarse sand:4 graded stone aggregate 20 mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cenment:5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement :3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design | |||
| 445 | 210.01 | With F.P.s bricks | 4 | Each | |
| 446 | 211 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI:12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank | |||
| 447 | 211.01 | Treated water Tank and Untreated water tank | 13000 | per litre | |
| 448 | 212 | Providing and fixing C.P brass Bib Cock of approved quality.(Jaquar or other equivalent model as per approved make) | |||
| 449 | 212.01 | 15 mm nominal bore | 55 | Each | |
| 450 | 213 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. Code FLR-CHR-5021N From Jaquar or other equivalent make. | |||
| 451 | 213.01 | 15 mm nominal bore | 40 | Each | |
| 452 | 214 | Providing and fixing C.P. brass Angle Valve for basin mixer and geyser/cisterns points of approved quality conforming to IS:8931.(jaquar or other equivalent model as per approved make) | |||
| 453 | 214.01 | 15 mm nominal bore | 38 | Each | |
| 454 | 215 | Providing and fixing C.P. Brass extension nipple (size 15mmx50mm) of approved make and quality as per direction of Engineer-in-charge. | 150 | Each | |
| 455 | 216 | Providing and fixing C.I. double acting air valve of approved quality with bolts, nuts, rubber insertions etc. complete (The tail pieces, tapers etc. if required will be paid separately): | |||
| 456 | 216.01 | 50 mm dia | 2 | Each | |
| 457 | 216.02 | 80 mm dia | 2 | Each | |
| 458 | 217 | Providing and fixing enclosed type water meter ( bulk type) conforming to IS : 2373 and tested by muncipal board complete with bolts,nuts rubber, insersions etc. ( the tail plases if required will be paid seperatly ) | |||
| 459 | 217.01 | 80mm dia nominal bore (25 to 80 mm) | 1 | Each | |
| 460 | 218 | Providing and fixing PTMT ball cock of approved quality, colour and make complete with Epoxy coated aluminium rod with L.P./H.P.H.D. plastic ball. | |||
| 461 | 218.01 | 40 mm nominal bore, 206 mm long weighin not less than 690 gms | 2 | Each | |
| 462 | 218.02 | 50 mm nominal bore, 242 mm long weighin not less than 1240 gms | 2 | Each | |
| 463 | 219 | Cutting holes upto 30x30 cm in walls including making good the same | |||
| 464 | 219.01 | with F.P.S bricks | 20 | Each | |
| 465 | 220 | Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement:2 coarse sand: 4 graded stone aggregate 20 mm nominal size) including finishing complete so as to make it leak proof | 60 | Each | |
| 466 | 221 | Providing and fixing Ball valve (SS) as per specifications of PN 10 rating. | |||
| 467 | 221.01 | 25 mm | 10 | Each | |
| 468 | 221.02 | 32 mm | 6 | Each | |
| 469 | 221.03 | 40 mm | 3 | Each | |
| 470 | 221.04 | 50 mm | 3 | Each | |
| 471 | 222 | Supply, installation, Testing & Commissioning of PN10 rated Solenoid valves including High / Low switches, and all necessary electric wiring, cabling complete | |||
| 472 | 222.01 | Size of valve 25 mm dia | 2 | Each | |
| 473 | 222.02 | Size of valve 32 mm dia | 4 | Each | |
| 474 | 222.03 | Size of valve 40 mm dia | 4 | Each | |
| 475 | 222.04 | Size of valve 50 mm dia | 4 | Each | |
| 476 | 223 | Providing and fixing Indian make CP brass air valves with gunmetal isolation valve fixed on pipe lines. | |||
| 477 | 223.01 | 15mm n.b air vent with 15mm isolation valve. | 8 | Each | |
| 478 | 223.02 | 20mm n.b air vent with 20mm isolation valve. | 12 | Each | |
| 479 | 223.03 | 40mm n.b air vent with 20mm isolation valve. | 2 | Each | |
| 480 | 224 | Providing and Fixing concealed Bath & Shower Mixer and diverter cutting and making good the wall complete as per instructions of the engineer-in-charge. | 2 | Each | |
| 481 | 225 | Providing and Fixing Over head shower 100 mm dia having aerators/flow restrictor to achieve the desired flowrate with Shower Arm complete as per instructions of the engineer-in-charge (Flowrate : 8.4 LPM at 45 Psi pressure) | 2 | Each | |
| 482 | 226 | Providing and Fixing CP Bath spout with wall flange having aerators/flow restrictor to achieve the desired flowrate complete as per instructions of the engineer-in-charge or as per equivalent make. (Flowrate : 8.4 LPM at 45 Psi pressure) | 1 | Each | |
| 483 | 227 | Providing fixing testing and commissioning of CP brass wall/counter mounted sink mixer with C.P. wall flange, overhead swinging spout/goose neck complete as required having aerator/flow restrictor to achieve the desired flow rate and making good including necessary wall cutting/chasing and making as required as per direction of engineer in_charge( flowrate:6.4 LPM at Psi Pressure) | 1 | Each | |
| 484 | 228 | Providing and fixing CP Brass single lever basin mixer with Swinging spout (Table Mounted) with 450 mm long braided hoses of approved quality confirming to IS :8931. Code no. FLR-CHR-5173B from Jaquar or equivalent make. | 1 | Each | |
| 485 | 229 | Providing and fixing closed cell polyolefin tube type thermal insulation over hot water pipes with thermal conductivity not exceeding 0.034 w/mk. At an average temp of 0 degree c , having density of material as 30 kg/m3 , with operating range of -80 degree C to +95 degree C, hcfc- free including all required accessories complete as per manufactur\"s specifications for the following pipe sizes and finishing it as per site requirement.(Hot water supply/return pipes) | |||
| 486 | 229.01 | 15 mm dia | 4 | Metre | |
| 487 | 229.02 | 20 mm dia | 8 | Metre | |
| 488 | 229.03 | 25 mm dia | 45.5 | Metre | |
| 489 | 229.04 | 32 mm dia | 30.5 | Metre | |
| 490 | 229.05 | 40 mm dia | 25.5 | Metre | |
| 491 | 229.06 | 50 mm dia | 25.5 | Metre | |
| 492 | 230 | Providing and fixing double seal type D.I. Manhole cover of 560 mm clear internal diameter of over all heavy duty with locking arrangement complete in all respects. | 18 | Each | |
| 493 | 231 | Supplying, fixing, testing and commissioning of storage type water heater (Geyser) etc. with outer body of ABS, 2 MM Thick Mild Steel inner Tank with glass line coating,option of 1/2/3 KW electrically operated single phase 230V, including Glass Lined Double Heating Element,Digital Display, Multifunction Safety Device, ELCB, Anode Rod System, and Brackets for fixing on wall with connecting Wire & plug etc. conforming to IS: 2082 and energy efficient star rated model. | |||
| 494 | 231.01 | 15 Litre Capacity | 1 | Each | |
| 495 | 231.02 | 25 Litre Capacity | 2 | Each | |
| 496 | 231.03 | 35 litre capacity | 2 | Each | |
| 497 | 232 | Providing & fixing water storage cooler of approved make and brand with SS body Complete in respects-230V Single Phase. (Voltas/Shriram/BLUE-STAR) | |||
| 498 | 232.01 | minimum flow rate of 40 ltrs. Per hour and storage capacity 80 ltrs. | 1 | Each | |
| 499 | 233 | Providing and fixing approved make & suitable model of R.O. plant 100 ltrs. Per hour flow rate having capacity to treat the raw water having TDS 1200 ppm and not less than 40%. The treated water should have TDS less than 100 ppm and hardness less than 50 ppm. The operating voltage to 230 volt AC +/- 10% alongwith required capacity pump and solenoid valves, dry run protection of pump, automatic tank level control, inbuilt auto flush timer for periodic flushing of membranes, hydro pneumatic tank, over voltage and over current protection with switch mode power supply system antiscaling dosing system complete in all respects including installation and fittings with the following provisions: (IONIEXCHANGE/ KENT/AQUAPROCESS/Pantair ) | |||
| 500 | 233.01 | 10 micron polypropylene sediment pre filter | |||
| 501 | 233.02 | 10 micron bacteriostatic activated carbon block on line micron filter with 5 micron rating | |||
| 502 | 233.03 | 3 Nos. of reverse osmosis memberane with 0.0001 micron pore size energy saving poly amide type | |||
| 503 | 233.04 | UV lamp of minimum capacity 100 LPM and minimum lamp wattage 9W | 1 | Each | |
| 504 | 234 | Providing and fixing approved make & suitable model of R.O. plant (fully automatic operation) 600ltrs. Per hour flow rate having capacity to treat the raw water and average recovery not less than 35% . The operating voltage to 230 volt AC +/- 10% alongwith required capacity on line SS pump of approved make (3HP minimum) and solenoid valves, dry run protection of pump, automatic tank level control, inbuilt auto flush timer for periodic flushing of membranes, storage tank (3.0 mm (minimum) thick S.S. 304 sheet) 1500 lts of suitable size and ita supporting structure, over voltage and over current protection with switch mode power supply system complete in all respects including installation and fittings with the following provisions: (IONIEXCHANGE/ KENT/AQUAPROCESS,Pantair ) | |||
| 505 | 234.01 | 10 micron polypropylene sediment pre filter | |||
| 506 | 234.02 | 10 micron bacteriostatic activated carbon block on line micron filter with 5 micron rating | |||
| 507 | 234.03 | Required Nos. and size of reverse osmosis memberane with 0.0001 micron pore size energy saving poly amide type | |||
| 508 | 234.04 | UV lamp of minimum capacity 600LPH and minimum lamp wattage 15W | |||
| 509 | 234.05 | MS powder coated frame efficient of TDS removal more than 90%. Antiscalant dosing and acid dosing system for self flushing/cleaning.Pressure switches and gauges, pH correction dosing system, Digital TDS meter, Digital pH meter, electric panel and necessary instrumentation included Rotameter.MS structure and fibre glass sheet weather protection cover as per site condition. | 1 | Each | |
| 510 | 235 | Supplying, installing, testing and commissioning vertical on line multi stage centrifugal pumping set(including electrical panel) with mechanical seal, C.I. volute and SS impeller & SS shaft connected to a TEFC induction motor of suitable HP for 415 volts, 3 phase, 50 cycles A.C. supply with 150 mm dia pressure gauge with SS/gunmetal isolation cock, vibration eliminating pads, base plate wiring upto panel and equipment for water level controller to start and stop the pump automatically at predecided levels of the water in the tank with provision of protection for dry run etc. complete in all respect. The efficiency of the pump shall be more than 60% (The shop drawing or the pumps along with its characteristics curves, model and technical data etc. are to be submitted for approval before purchase of pump). | |||
| 511 | 235.01 | Treated Water Pump | |||
| 512 | 235.02 | Capacity : 50 lpm (Each) | |||
| 513 | 235.03 | Head 35 m | |||
| 514 | 235.04 | Power :1 HP(minimum) | |||
| 515 | 235.05 | with 100% standby pumps | |||
| 516 | 235.06 | complete pump set as above | 2 | SET | |
| 517 | 235.07 | Raw Water Pump | |||
| 518 | 235.08 | Capacity : 40 lpm (Each) | |||
| 519 | 235.09 | Head 35 m | |||
| 520 | 235.1 | Power :1 HP(minimum) | |||
| 521 | 235.11 | with 100% standby pumps | |||
| 522 | 235.12 | complete pump set as above | 2 | SET | |
| 523 | 236 | Supply, installing, testing and commissioning vertical fully floodable type Submersible drainage pump of non-corrosive material (including electrical panel) in close coupled design single stage, suitable for handling minimum 10 mm dia solids for transferring waste water from sump to outside the building with float switch for automatic start and stop arrangement with panel and wiring, chain and pulley, mechanical seal complete in all respect as per instruction of the Engineer in charge. (The shop drawing or the pumps along with its characteristics curves, model and technical data etc. are to be submitted for approval before purchase of pump).Star delta suitable starter complete in all respect for automatic/manual operation of pump, start and stop push button contactor with required overload production and single phase preventer. | |||
| 524 | 236.01 | Material of Construction (M.O.C): \nCorrosion Resistant in general\n : Casing — Cast Iron | |||
| 525 | 236.02 | : Impeller — SS | |||
| 526 | 236.03 | : Bearings — Anti friction, \n prelubricated ball bearings,\n packed with grease for life. | |||
| 527 | 236.04 | Motor: — Dry Motor with built in over\n load protection | |||
| 528 | 236.05 | Protection - IP68. | |||
| 529 | 236.06 | Insulation Class - F | |||
| 530 | 236.07 | Duty of each pump | |||
| 531 | 236.08 | 100 LPM against 15 M head - For Pump Room Drainage | 1 | Each | |
| 532 | 236.09 | SEWARAGE & DRAINAGE | |||
| 533 | 237 | Providing laying and jointing glazed stoneware pipes grade 'A' with stiff mixture of cement mortar in the pro-portion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete. | |||
| 534 | 237.01 | 100 mm diameter | 20 | Metre | |
| 535 | 238 | Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design: | |||
| 536 | 238.01 | 100 mm diameter S.W. pipe/RCC NP2 | 20 | Metre | |
| 537 | 238.02 | 150 mm diameter S.W. pipe/RCC NP2 | 100 | Metre | |
| 538 | 238.03 | 250 mm diameter S.W. pipe/RCC NP2 | 100 | Metre | |
| 539 | 239 | Providing and fixing square-mouth S.W. gully trap grade ‘A’' complete with C.I. grating, brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design:. | |||
| 540 | 239.01 | 150x100mm size P type | |||
| 541 | 239.02 | F.P.S. Bricks class designation 75 | 8 | Each | |
| 542 | 240 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement:2 fine sand) including testing of joints etc. complete | |||
| 543 | 240.01 | 150 mm dia R.C.c. pipe | 200 | Metre | |
| 544 | 240.02 | 250 mm dia R.C.c. pipe | 200 | Metre | |
| 545 | 241 | Constructing brick masonry circular type manhole 0.91m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand), in side cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement: 3 coarse sand: 6 graded stone aggregate 40mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement all complete as per standard design: | |||
| 546 | 241.01 | 0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182kg., fixed in cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) including centering shuttering all complete. (Excavation, foot rests and 12mm thick cement plaster at the external surface shall be paid for separately) : | |||
| 547 | 241.02 | With F.P.S. bricks class designation 75 | 20 | Each | |
| 548 | 242 | Extra depth for circular type manhole 0.91m dia (at bottom) with beyond 0.91m to 1.67 m | |||
| 549 | 242.01 | With F.P.S. bricks class designation 75 | 20 | Metre | |
| 550 | 243 | Constructing brick masonry manhole in cement mortar 1:4 (1 cement : 4 coarse sand), R.C.C. top slab with 1:2:4 mix ( 1cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size ), foundation concrete 1:4:8 ( 1cement : 4 coarse sand : 8graded stone aggregate 40 mm nominal size ), inside plastering 12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, and making necessary channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement all complete as per standard design. | |||
| 551 | 243.01 | Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg): | |||
| 552 | 243.02 | With F.P.S. bricks with class designation 75 | 4 | Each | |
| 553 | 244 | Extra depth for manholes | |||
| 554 | 244.01 | Size 90 x 80 cm | |||
| 555 | 244.02 | With F.P.S. bricks class designation 75 | 1 | Metre | |
| 556 | 245 | Providing and fixing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12 mm dia steel bar conforming to IS: 1786 having minimum cross section as 23 mm x 25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design. | 20 | Each | |
| 557 | 246 | Making connection of drain or sewer line with existing manhole including breking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement:2 coarse sand:4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cemnet mortar 1:3 (1 cement:3 coarse sand) finished with a floating coat of neat cement and making necessary channels for the drain etc. complete (including obtaining approval from DJB/Municipal corporation | |||
| 558 | 246.01 | For pipes 100 to 250 mm dia | 1 | Each | |
| 559 | 246.02 | SOLAR WATER HEATING SYSTEM | |||
| 560 | 247 | Providing and fixing G.I.fittings and clamps,i/c cutting and making good the walls etc. | |||
| 561 | 247.01 | Internal work - Exposed on wall | |||
| 562 | 247.02 | 25 mm nominal bore | 30 | Meter | |
| 563 | 247.03 | 32 mm nominal bore | 20 | Meter | |
| 564 | 247.04 | 40 mm nominal bore | 10 | Meter | |
| 565 | 247.05 | 50mm nominal bore | 10 | Meter | |
| 566 | 248 | Insulation of G.I.piping with aluminium cladded mineral fibre glass insulation suitable for outdoor applications suitable for following pipe sizes | |||
| 567 | 248.01 | 25 dia | 30 | Meter | |
| 568 | 248.02 | 32 dia | 20 | Meter | |
| 569 | 248.03 | 40 dia | 10 | Meter | |
| 570 | 248.04 | 50 dia | 10 | Meter | |
| 571 | 249 | Providing & fixing 9 mm thick thermal insulation tubing of elastomeric flexible material having hermetic blistered closed cell structure of expanded synthetic rubber over pipes/ fitting as per manufacturer's specifications etc.complete with aluminium cladding over insulated tubing. | |||
| 572 | 249.01 | 15 mm dia to 25 mm dia | 30 | Each | |
| 573 | 249.02 | 32 mm dia to 50 mm dia | 100 | Each | |
| 574 | 249.03 | 65 mm dia to 80 mm dia | 20 | Each | |
| 575 | 250 | Supply, installation, testing and commissioning of solar water heating system, Thermosyphon type, all complete based on Flat plat collector system (Cu-Cu Type only) comprising of but not limited to the following: | |||
| 576 | 250.01 | Requisite number of Flat plate collectors of 2.30 sq. mtr. collector area. Collector absorber plate to be made of copper tubes & copper fins only | |||
| 577 | 250.02 | Hot water storage tank made of stainless steel 304- food grade quality minimum 3mm thick with 2 coats of 3M epoxy anti corrosive paint inside the tank with 100 mm Glass wool insulation and cladding with 24 SWG Aluminum sheet. One temperature measuring device and suitable inlet, outlet and drain connections on the storage tank to be provided. Suitable Electrical Heater backup to be provided inside the tank along with thermostat | |||
| 578 | 250.03 | Heat Exchanger - plate type external heat exchanger of SS316 plates (make Gea echo flex/Alfalavel/transter ) with MS Flanges for transfer of heat minimum 1000 K Calories/collector/hr with necessary pressure guage and temperature guage and isolation valve etc. complete . Suitable make up tank for the Heat Exchanger circuit shall also be provided | |||
| 579 | 250.04 | Primary Pumps between Collector and Heat Exchanger---Provdiing of Recirculation Pumps (between Collectors and Heat Exchanger) with SS Impellars and Shaft for Temperature Application upto 90 Deg.C of Required Flow 100 Ltrs./Collector for Minimum Pressure drop of 2 Kg./Cm2 with Isolation Valves, NRVs and Stainer(1W+1S) Pumps. | |||
| 580 | 250.05 | Secondary Pump between Hot Water Tank and Heat Exchanger--Provdiing of Recirculation Pumps (between Hot Water Tank and Heat Exchanger) with SS Impellars and Shaft for Temperature Application upto 90 Deg.C of Required Flow 100 Ltrs./Collector for Minimum Pressure drop of 2 Kg./Cm2 with Isolation Valves, NRVs and Stainer(1W+1S) Pumps. | |||
| 581 | 250.06 | Interconnecting system piping shall consist of B Class insulated GI/CPVC pipes covered with 50mm thick glasswool & clad with 26 SWG Aluminium Sheet. All Gate/Ball valves shall be of ISI make. | |||
| 582 | 250.07 | Electrical control panel, cabling from panel to pumps shall also be provided, Electrical panel:16 SWG sheet powder coated electrical panel for outdoor application IP-65, with Digital differential temperature controller for automatic ON/OFF at primary and secendary pumps (3ph) with necessary contractors, relays, control fuse, isolation switches. The cable beyond 100 m if required will be paid seperately in electrical head. | |||
| 583 | 250.08 | The solar collector shall be arranged on roof of building in such a way that shadow can be avoided and requisite number of MS support for collector/tanks of minimum 40x40x5 MS angle adequate for 150 Km/Hr wind speed. | |||
| 584 | 250.09 | Solar water heating system based on Flat plat collector systmem technology with output capacity of as mentioned below with hot water at 60 degree centigrade having reqired Nos. solar collectors as per complete item as per technical specification of make BHEL/TATA/EMMVEE/INTER-SOLAR. The system has to be installed by Manufacturers authorised distributors/approved specialised firms of Solar water heating of approved makeThe shop drawing of the systems shall be provided by the agency as per site condition obtain the proper efficiency The system shall be procured after obtaining the approval of shop drawings from HSCC / Engineer-in-charge.(Electric heating element shall not be provided in the system as the solar hot water system will supply the hot water to the individual geyser). | |||
| 585 | 250.1 | Supply, Installation, Testing and commissioning of the system complete with necessary Temperature gauge, Temperature sensor, Thermostat with rubber gaskets, Electrical & Control wiring | |||
| 586 | 250.11 | Complet Solar System as above of Capcity 5000 Litre/day (With minimum 38 nos of Collect) of 2.30 Sqm area | 1 | Each | |
| 587 | 250.12 | RAIN WATER PIPING | |||
| 588 | 251 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15/25 cm diameter and weighing not less than 440 grams | 19 | Each | |
| 589 | 252 | Providing and fixing rain water ,soil, waste and vent pipes. | |||
| 590 | 252.01 | 100 mm dia. | |||
| 591 | 252.02 | Centrifugally cast (spun) iron socketed pipe as per IS:3989 | 88 | Metre | |
| 592 | 252.03 | 150 mm dia pipe as per IS:3989 | 64 | Metre | |
| 593 | 253 | Providing and fixing M.S holder-bat clamps of approved design to Sand Cast iron/ cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) including cost of cutting holes and making good the walls etc. | |||
| 594 | 253.01 | for 100 mm dia. pipe | 44 | Each | |
| 595 | 253.02 | for 150 mm dia pipe | 32 | Each | |
| 596 | 254 | Providing and fixing plain bend of required degree. | |||
| 597 | 254.01 | 100 mm | 11 | Each | |
| 598 | 254.02 | Sand cast iron S&S as per IS:3989 | |||
| 599 | 254.03 | 150 mm | 8 | Each | |
| 600 | 255 | Providing and fixing heel rest sanitary bend. | |||
| 601 | 255.01 | 100 mm dia | |||
| 602 | 255.02 | sand cast iron S&S as per IS-3989 | 11 | Each | |
| 603 | 255.03 | 150 mm dia | 8 | Each | |
| 604 | 256 | Providing and fixing collar | |||
| 605 | 256.01 | 100 mm | 22 | Each | |
| 606 | 256.02 | Sand cast iron S&S as per IS-3989 | |||
| 607 | 256.03 | 150 mm | 16 | Each | |
| 608 | 257 | Providing lead caulked joints to sand cast iron /centrifugally cast (spun) iron pipes and fittings of diameter: | |||
| 609 | 257.01 | 100 mm | 44 | Each | |
| 610 | 257.02 | 150 mm | 32 | Each | |
| 611 | 258 | Painting sand cast iron / centrifugally cast (spun) iron soil, waste vent pipes and fittings with paint of any colour such as chocolate, grey, or buff etc. over a coat of primer (of approved quality) for new work: | |||
| 612 | 258.01 | 100 mm diameter pipe | 88 | Metre | |
| 613 | 258.02 | 150 mm diameter pipe | 64 | Metre | |
| 614 | 258.03 | EXTERNAL WATER SUPPLY | |||
| 615 | 259 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps,\ni/c cutting and making good the walls etc(Class-C)\n(For Pump Room) | |||
| 616 | 259.01 | Internal work - Exposed on wall | |||
| 617 | 259.02 | 25 mm dia nominal bore | 10 | Metre | |
| 618 | 259.03 | 40 mm dia nominal bore | 50 | Metre | |
| 619 | 259.04 | 50 mm dia nominal bore | 50 | Metre | |
| 620 | 259.05 | 80 mm dia nominal bore | 50 | Metre | |
| 621 | 259.06 | 150 mm dia nominal bore | 10 | Metre | |
| 622 | 260 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. | |||
| 623 | 260.01 | 25 mm dia nominal bore | 15 | Metre | |
| 624 | 260.02 | 32 mm dia nominal bore | 10 | Metre | |
| 625 | 260.03 | 40 mm dia nominal bore | 50 | Metre | |
| 626 | 260.04 | 50 mm dia nominal bore | 50 | Metre | |
| 627 | 260.05 | 65 mm dia nominal bore | 50 | Metre | |
| 628 | 261 | Providing and fixing gunmetal gate valve with CI wheel of approved quality (Screwed end) (For Garden Hydrant) | |||
| 629 | 261.01 | 25 mm NB | 8 | Each | |
| 630 | 261.02 | Providing and fixing gun metal non-return valve of approved quality (screwed end) | |||
| 631 | 261.03 | 25 mm nominal bore | |||
| 632 | 261.04 | Horizontal | 10 | Each | |
| 633 | 261.05 | 40 mm nominal bore | |||
| 634 | 261.06 | Horizontal | 4 | Each | |
| 635 | 261.07 | 50 mm nominal bore | |||
| 636 | 261.08 | Horizontal | 4 | Each | |
| 637 | 261.09 | 80 mm nominal bore | |||
| 638 | 261.1 | Horizontal | 4 | Each | |
| 639 | 261.11 | 100 mm nominal bore | |||
| 640 | 261.12 | Horizontal | 2 | Each | |
| 641 | 261.13 | 150 mm nominal bore | |||
| 642 | 261.14 | Horizontal | 1 | Each | |
| 643 | 262 | Constructing masonary chamber 60x60x75 cm, inside with 75 class designation brick work in cement mortar 1:4 (1 cement: 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement: 2 coarse sand:4 graded stone aggregate 20 mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cenment:5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement :3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design | |||
| 644 | 262.01 | With F.P.S. bricks | 2 | Each | |
| 645 | 263 | Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :\n | |||
| 646 | 263.01 | With F.P.S. bricks | 10 | Each | |
| 647 | 264 | Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : | |||
| 648 | 264.01 | 32 mm dia nominal bore | 10 | Metre | |
| 649 | 264.02 | 40 mm dia nominal bore | 50 | Metre | |
| 650 | 264.03 | 50 mm dia nominal bore | 50 | Metre | |
| 651 | 264.04 | 65 mm dia nominal bore | 50 | Metre | |
| 652 | 265 | Providing and filling sand of grading zone V or coarser grade, allround the G.I. pipes in external work : | |||
| 653 | 265.01 | 32 mm dia nominal bore | 10 | Metre | |
| 654 | 265.02 | 40 mm diameter pipe | 50 | Metre | |
| 655 | 265.03 | 50 mm diameter pipe | 50 | Metre | |
| 656 | 265.04 | 65 mm diameter pipe | 50 | Metre | |
| 657 | 265.05 | 80 mm dia nominal bore | 10 | Metre | |
| 658 | 266 | Providing and fixing G.I. Union in existing G.I. pipe line, cutting and threading the pipe and making long screws including excavation, refilling the earth or cutting of wall and making good the same complete wherever required: | |||
| 659 | 266.01 | 20 mm nominal bore | 2 | Each | |
| 660 | 266.02 | 25 mm nominal bore | 2 | Each | |
| 661 | 266.03 | 32 mm nominal bore | 2 | Each | |
| 662 | 266.04 | 50 mm diameter pipe | 2 | Each | |
| 663 | 266.05 | 80 mm diameter pipe | 1 | Each | |
| 664 | 267 | Providing and fixing C.I. double acting air valve of approved quality with bolts, nuts, rubber insertions etc. complete (The tail pieces, tapers etc. if required will be paid separately): | |||
| 665 | 267.01 | 50 mm dia | 1 | Each | |
| 666 | 267.02 | 80 mm dia | 1 | Each | |
| 667 | 268 | Providing and fixing enclosed type water meter ( bulk type) conforming to IS : 2373 and tested by muncipal board complete with bolts,nuts rubber, insersions etc. ( the tail plases if required will be paid seperatly ) | |||
| 668 | 268.01 | 80mm dia nominal bore (25 to 80 mm) | 1 | Each | |
| 669 | 269 | Providing and Fixing CI dirt box strainer for bulk type water meter with nuts, bolts, rubber insertions etc. complete conforming to IS : 2373 | |||
| 670 | 269.01 | 80 mm nominal bore | 2 | Each | |
| 671 | 270 | Supply installation, testing & commissioning of cast iron (CI) Butterfly Valves of PN 16 rating | |||
| 672 | 270.01 | 65 mm nominal bore | 2 | Each | |
| 673 | 270.02 | 80 mm nominal bore | 1 | Each | |
| 674 | 270.03 | 100 mm nominal bore | 1 | Each | |
| 675 | 271 | Providing and fixing Ball valve (SS) as per specifications of PN 10 rating. | |||
| 676 | 271.01 | 25 mm | 2 | Each | |
| 677 | 271.02 | 32 mm | 2 | Each | |
| 678 | 271.03 | 40 mm | 2 | Each | |
| 679 | 271.04 | 50 mm | 3 | Each | |
| 680 | 272 | Providing and fixing gun metal foot valve with stainer of approved quality/model complete in all respect | |||
| 681 | 272.01 | 50 mm dia | 1 | Each | |
| 682 | 272.02 | 80 mm dia | 2 | Each | |
| 683 | 272.03 | 100 mm dia | 2 | Each | |
| 684 | 273 | Supply, installation, testing and commissioning of heavy duty Pop-up type irrigation sprinkler with working pressure range of 2-6 Bar | 3 | Each | |
| 685 | 274 | Providing and fixing of C.I. 'Y' type strainer flanged with SS 304 perforated screen including nuts, bolts and rubber insertions etc | |||
| 686 | 274.01 | 80 mm dia | 2 | Each | |
| 687 | 274.02 | 100 mm dia | 1 | Each | |
| 688 | 275 | Supplying and installing Bourden type pressure gauges range 0 to 20 bar 10mm brass gauge cock brass pipe snubber etc complete. | 3 | Each | |
| 689 | 276 | Providing fixing and testing water flow meters in CI/brass body flanged at both ends with companion flanges,gaskets, bolts nuts and washers, with electronic digital type display for real time & totalized flow rate of water with panel and cabinet ,memory facility, flow switches and sensors and required accessories complete including cutting and making good the pipeline, and making all electrical connections, water meters should be BMS compatible testing to be carried out at 200 lbs/psi with cold water for consistent quality.( with bypass arrangements with 3 valves) | |||
| 690 | 276.01 | Sizes of valve 65 mm dia | 1 | Each | |
| 691 | 276.02 | Sizes of valve 80 mm dia | 1 | Each | |
| 692 | 276.03 | Sizes of valve 100 mm dia | 1 | Each | |
| 693 | 277 | Providing and fixing puddle flanged including 40 cm long GI pipe piece welded/threaded with MS plates 450x450x6 mm thick with both end screwed/flanged. | |||
| 694 | 277.01 | For 80 mm dia pipe | 2 | Each | |
| 695 | 277.02 | For 100 mm dia pipe | 2 | Each | |
| 696 | 277.03 | For 150 mm dia pipe | 2 | Each | |
| 697 | 278 | Providing and fixing double seal type D.I. Manhole cover of 560 mm clear internal diameter of over all heavy duty with locking arrangement complete in all respects. | 5 | Each | |
| 698 | 279 | Providing and fixing motorized butterfly valve/rotary actuator (CI body, SS316 disc, EPDM boot seat, SS416 shaft, RPTEF bushing @PN16 rating) for filling of water tank complete with electrical water level control panel, including by-pass connection for the same dia with manually operated butterfly valve and all piping and accessories complete in all respects - For Cluster Level UG Domestic and Flushing Tanks Clusterwise | |||
| 699 | 279.01 | 50 mm dia | 2 | Each | |
| 700 | 279.02 | 65 mm dia | 3 | Each | |
| 701 | 279.03 | 80 mm dia | 3 | Each | |
| 702 | 279.04 | 100 mm dia | 3 | Each | |
| 703 | 279.05 | 150 mm dia | 3 | Each | |
| 704 | 279.06 | BOREWELL | |||
| 705 | 280 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) | |||
| 706 | 280.01 | 80 mm dia(horizontal) | 1 | Each | |
| 707 | 281 | Providing and fixing gunmetal non return valve of approved make tested to a pressure of 21kg/sqcm. | |||
| 708 | 281.01 | 80 mm dia(horizontal) | 1 | Each | |
| 709 | 281.02 | Submersible pumps | |||
| 710 | 282 | Providing and installing submersible pump and electrical panel suitable for 100 mm dia casing of bore with SS impeller, high tensile SS shaft, copper wound squirrel cage wet type induction motor 2880 rpm, 415 V, 50 Hz,3 phase A.C. supply, conforming to ISS: 8034-1976, capacity 100 LPM at 50-80 m head along with a directly coupled submersible type squirrel cage electric induction 2 H.P(minimum). motor suitable for operation on 400 V, 3 phase, 50 c.p.s. A.C. supply, water lubricated bearings and provided with pivoted segment type thrust bearings to withstand non-vertical lead with minimum wear and tear and duly fitted with device to take up the expansion of water with heating of motor, including supply, testing and commissioning of elctrical panel from the same manufacturer, complete with all accessories in all respects. The contractor to obtain approval for model and make of pumpset & suitable Electrical panel after having yield report of fully developed tube well and submite actual bore strata chart. | |||
| 711 | 282.01 | including supplying laying and fixing water proof PVC insulated flat submersible cable 3x10 sqmm with end termination with its accessories. complete in all respect as required. 1 No. 3 Phase, fully automatic star-delta starter, type - II of 15 HP with thermal overload relay, contactor, Timer, Push Buttons and Auto-manual selector switch etc complete as required. | 1 | set | |
| 712 | 283 | Carrying out Electrical logging of Borewell before lowering of pipe for analysiing of water quality including Electrical logging report, calculation etc. including carry out hydrological survey report before boring & getting the approval based on Hydrogeological survey before start of the work.Also getting approval from local authority if any required | 1 | Job | |
| 713 | 284 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level | |||
| 714 | 284.01 | All types of soil | |||
| 715 | 284.02 | 300mm | 70 | metre | |
| 716 | 284.03 | Rocky strata including Boulders | |||
| 717 | 284.04 | 300 mm dia | 10 | metre | |
| 718 | 285 | Boring/drilling bore well of required dia for casing/ strainer pipe, bysuitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools,plants & machineries required for the job, all complete as per direction of Engineer -in-charge, beyond 90 metre & upto 150 metre depthbelow ground level. | |||
| 719 | 285.01 | All types of soil | |||
| 720 | 285.02 | 300 mm dia | 10 | metre | |
| 721 | 285.03 | Rocky strata including Boulders | |||
| 722 | 285.04 | 300 mm dia | 2 | metre | |
| 723 | 286 | Gravel packing in tubewell construction in accordance with IS: 4097,including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction ofEngineer-in-charge. | 5 | cum | |
| 724 | 287 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 mild steel screwed and socketed/ plain ended casing pipes of required dia, conforming to IS: 4270, of reputed & approved make, including painted with outside surface with two coats of anticorrosive paint of approved brand and manufacture, including required hire & labour charges,fittings & accessories, all complete, for all depths, as per direction\nof Engineer-in-charge. | |||
| 725 | 287.01 | 100 mm nominal size dia having minimum wall thickness\n5.00 mm | 60 | metre | |
| 726 | 288 | Supplying, assembling, lowering and fixing in vertical position in borewell, ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of size 1.6/3.2 mm) mild steel threaded and socketed/ plainbevel ended pipe (type A) of required dia, conforming to IS: 8110, of reputed and approved make, having wall thickness not less than 5.40 mm, including painted with outside surface with two coats of anticorrosive bitumestic paint of approved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer -in-charge | |||
| 727 | 288.01 | 100 mm nominal size dia | 40 | metre | |
| 728 | 289 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \"V\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested inapproved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc.,all as per requirement and direction of Engineer-in-charge.. | 50 | hour | |
| 729 | 290 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removableas per requirement, all complete for borewell of: | |||
| 730 | 290.01 | 100 mm dia | 1 | each | |
| 731 | 291 | Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. | |||
| 732 | 291.01 | 100 mm clamp | 1 | each | |
| 733 | 292 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :Providing and laying cement concrete 1:2:4 mix (for sanitary sealing of well at top.) | |||
| 734 | 292.01 | \"1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone\naggregate 20 mm nominal size). | 1 | cum | |
| 735 | 293 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I). | |||
| 736 | 293.01 | 100 MM DIA | 1 | Each | |
| 737 | 294 | Providing and fixing G.I. pipes complete with G.I. fittings including\ntrenching and refilling etc | |||
| 738 | 294.01 | 65 mm dia nominal bore | 30 | metre | |
| 739 | 294.02 | 80 mm dia nominal bore | 50 | metre | |
| 740 | 294.03 | RAIN WATER HARVESTING | |||
| 741 | 295 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, reparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level | |||
| 742 | 295.01 | All types of soil | |||
| 743 | 295.02 | 400mm | 20 | Metre | |
| 744 | 295.03 | Rocky strata including Boulders | |||
| 745 | 295.04 | 400 mm dia | 20 | Metre | |
| 746 | 296 | Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge. | |||
| 747 | 296.01 | 150 mm dia | 20 | Metre | |
| 748 | 297 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of\nEngineer-in-charge. | |||
| 749 | 297.01 | 150 mm nominal size dia | 20 | Metre | |
| 750 | 298 | Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge | 4 | Cum | |
| 751 | 299 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per directionof Engineer-in-charge. | 4 | Cum | |
| 752 | 300 | Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer,for all leads & lifts, all complete as per direction of Engineer -incharge. | 4 | Cum | |
| 753 | 301 | Gravel packing in tubewell construction in accordance with IS: 4097,including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction ofEngineer-in-charge | 2 | Cum | |
| 754 | 302 | Providing and fixing factory made precast RCC perforated drain covers, having concrete of strength not less than M-25, of size 1000 x 450x50 mm, reinforced with 8 mm dia four nos longitudinal & 9 nos cross sectional T.M.T. hoop bars, including providing 50 mm dia perforations @ 100 to 125 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm complete, all as per direction of Engineerin-charge | 1 | Each | |
| 755 | 303 | Constructing bar screen / settling tank, of sizes 4500x2500 with suitable depth up to 2.0 m in 1: 4 Cement Mortar (one cement : 4 coarse sand) height as per site requirement, in brick masonry 350mm thick walls upto water level and 230mm thick walls above water level & upto ground level, including all excavation, 20 cm thick bed concrete in 1:4:8 (one cement 4 fine sand 8 stone aggregate 40 mm), cement plaster 1:3 (one cement :3 coarse sand) with a floating coat of neat cement as inside finish , top slab in RCC 1:2:4, including centring, shuttering and steel work, also providing and fixing D.I. manhole cover & frame of size 605mm x 450mm of weight not less than 38 kg (frame + cover) and cost of 100mm dia C.I. vent pipe with C.I. Ventilating Cowl and suitable wire mesh provision for inlet, 115mm baffle walls extending 2/3 the width spaced@500mm c/c including finishing with 1:3 cement plaster 15mm thick with floating coat of neat cement slurry , all complete in every respect as per drawing and as directed to suit site condition. | 1 | Each | |
| 756 | 303.01 | EXTERNAL SEWERAGE AND DRAINAGE( except Around Building ) | |||
| 757 | 304 | Constructing brick masonry circular manhole 1.22 m intenral dia at bottom and 0.56 m dia at top in cement mortar 1:4 ( 1 cement: 4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 mix (1 cement :3 coarse sand : 6 graded stone aggregate 40mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement :2 coarse sand : 4 graded stone aggregate 20mm nominalsize) fineished with a floating coat of neat cement complete as per standard design. | |||
| 758 | 304.01 | 1.68 m deep with SFRC cover and frame(heavy duty HD-20 grade designation) 560 mm internal diameter conforming to IS: 12592, total weight of cover and frame to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement :2 coarse sand : 4 graded stone aggregate 20mm nominalsize) including centering shuttering all complete. (Excavation, foot rests and 12 mm tick cement plaster at the external surface shall be paid for separately) | |||
| 759 | 304.02 | With F.P.S. bricks with class designation 75 | 1 | Each | |
| 760 | 305 | Extra depth for circular type manhole 1.22 m internal dia (at bottom) with beyond 1.68 m to 2.29 m | |||
| 761 | 305.01 | With F.P.S. bricks with class designation 75 | 1 | Metre | |
| 762 | 306 | Constructing brick masonry road gully chamber 50x45x60 cm with bricks of class designation 75 in cement mortar 1:4 (1 cement:4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design: | |||
| 763 | 306.01 | With F.P.S. bricks | 40 | Each | |
| 764 | 307 | Constructing brick masonry road gully chamber 110x50x77.5 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm precast R.C.C. horizontal grating with frame and vertical grating complete as per standard design : | |||
| 765 | 307.01 | With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 | 20 | Each | |
| 766 | 308 | Providing and fixing factory made precast RCC perforated drain covers,\nhaving concrete of strength not less than M-25, of size 1000 x 450x50 mm, reinforced with 8 mm dia four nos longitudinal & 9 nos cross sectional T.M.T. hoop bars, including providing 50 mm dia perforations@ 100 to 125 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm complete, all as per direction of Engineerin-charge | 60 | Each | |
| 767 | 309 | Constructing brick masonry open surface drain including with edge protected with MS plate of 3 mm thick with bricks of class designation 75 in cement mortar 1:4 (1 cement : 4 fine sand) including earth excavation, 10cm thick bed concrete 1:5:10 (1 cement: 5 fine sand :10 graded stone aggregate 40mm nominal size) and 25mm thick cement concrete 1:2:4 (1 cement:2 coarse sand:4 graded stone aggregate 12.5 mm nominal size) for filling hunches including 12mm cement plaster 1:4 (1 cement:4 coarse sand) with a floating coat of neat cement inside the drain, its top and exposed side including disposal of surplus earth complete as per standard design. | |||
| 768 | 309.01 | 300mm drain 450 mm average depth | |||
| 769 | 309.02 | With F.P.S bricks | 60 | Metre | |
| 770 | 310 | Supply, installing, testing and commissioning vertical fully floodable type submersible sewage pump of non-corrosive material with shredder/cutter in close coupled design single stage, suitable for handling minimum 10 mm dia solids for transferring raw sewer from sump to outside the building with float switch for automatic start and stop arrangement with panel and wiring, chain and pulley, mechanical seal complete in all respect as per instruction of the Engineer in charge. (The shop drawing or the pumps along with its characteristics curves, model and technical data etc. are to be submitted for approval before purchase of pump).Star delta suitable starter complete in all respect for automatic/manual operation of pump,start and stop push button contactor with required overload production and single phase preventor.Electicl panal complet as per instruction of the Engineer in charge | |||
| 771 | 310.01 | Material of Construction (M.O.C): \nCorrosion Resistant in general\n : Casing — Cast Iron | |||
| 772 | 310.02 | : Impeller — SS | |||
| 773 | 310.03 | : Bearings — Anti friction, \n prelubricated ball bearings,\n packed with grease for life. | |||
| 774 | 310.04 | Motor: — Dry Motor with built in over\n load protection | |||
| 775 | 310.05 | Protection - IP68. | |||
| 776 | 310.06 | Insulation Class - F | |||
| 777 | 310.07 | Duty of each pump | |||
| 778 | 310.08 | 100LPM against 10 M head ( Sewage pump) | 1 | Each | |
| 779 | 310.1 | ELECTRICAL ITEMS | |||
| 780 | 310.11 | SUB HEAD 1 : MV PANELS | |||
| 781 | 310.12 | MV PANELS | |||
| 782 | 310.13 | Supply, installation, testing and commissioning of following M.V. cubicle type totally enclosed, wall mounted/Free standing type, powder coated, dust, damp and vermin proof, indoor type Distribution Board/Panel complete with busbars, M.V. danger notice plate, interconnections with suitable capacity aluminium leads/solid aluminium strips/rods, connection of incoming and outgoing cables with thimbles, and having following incoming and outgoing switchgears complete as per techinical specification and as required. | |||
| 783 | 310.14 | NOTE | |||
| 784 | 310.15 | All MCCBs shall have Ics=Icu. | |||
| 785 | 310.16 | MCB Should be connected through terminal Strip of suitable rating | |||
| 786 | 310.17 | MV PANEL (Ground Floor ) (Section-1) | |||
| 787 | 310.18 | INCOMER: | |||
| 788 | 310.19 | 1 No. MCCB Panels each having following | |||
| 789 | 310.2 | 630 Amp 415 volts, 35 KA FP MCCB with microprocessor based release having variable current settings of O/L, S/C & inbuilt E/F protection release. | |||
| 790 | 310.21 | R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP Indication (LED type). | |||
| 791 | 310.22 | Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB should have spreader links & phase barriers. | |||
| 792 | 310.23 | 1 No. 0 to 500 V Digital voltmeter with selector switch. | |||
| 793 | 310.24 | Digital ammeter with selector switch with one set Suitable C.Ts. | |||
| 794 | 310.25 | BUSBARS: | |||
| 795 | 310.26 | 500 Amp TPN Aluminium busbars | |||
| 796 | 310.27 | OUTGOING: | |||
| 797 | 310.28 | 1 Nos. MCCB as per following details/ specifications: | |||
| 798 | 310.29 | 320 Amp 35 KA TP+NL 35 KA FP MCCB with microprocessor based release having variable current settings of O/L, S/C & inbuilt E/F protection release. | |||
| 799 | 310.3 | Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should be with spreader link and phase barriers. | |||
| 800 | 310.31 | ON, OFF, TRIP indication (LED Type). | |||
| 801 | 310.32 | Digital Ampere Metre of suitable range with suitable set of CT's and ASS. | |||
| 802 | 310.33 | 2 Nos. MCCB as per following details/ specifications: | |||
| 803 | 310.34 | 200 Amp 35 KA TP+NL MCCB with thermal magnetic release having variable current settings of O/L, S/C protection release. | |||
| 804 | 310.35 | Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should be with spreader link and phase barriers. | |||
| 805 | 310.36 | ON, OFF, TRIP indication (LED Type). | |||
| 806 | 310.37 | Digital Ampere Metre of suitable range with suitable set of CT's and ASS. | |||
| 807 | 310.38 | 4 Nos. MCCB as per following details/ specifications: | |||
| 808 | 310.39 | 63 Amp 35 KA TP+NL MCCB with thermal magnetic release having variable current settings of O/L, S/C protection release. | |||
| 809 | 310.4 | Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should be with spreader link and phase barriers. | |||
| 810 | 310.41 | ON, OFF, TRIP indication (LED Type). | |||
| 811 | 310.42 | Digital Ampere Metre of suitable range with suitable set of CT's and ASS. | |||
| 812 | 310.43 | 7 no. 63 Amps, 415 volts, 9 KA, Four Pole Miniature Circuit Breaker. | |||
| 813 | 310.44 | 7 no. 40 Amps, 415 volts, 9 KA, Four Pole Miniature Circuit Breaker. | |||
| 814 | 310.45 | MV Panel as mentioned above | 1 | Set | |
| 815 | 311 | MV PANEL NORMAL ( SECTION -2) | |||
| 816 | 311.01 | INCOMER: | |||
| 817 | 311.02 | 1 No. MCCB Panels each having following | |||
| 818 | 311.03 | 200 Amp 415 volts, ,25 KA FP MCCB with thermal magnetic release having variable current settings of O/L, S/C protection and E/ F Module. | |||
| 819 | 311.04 | R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP Indication (LED type). | |||
| 820 | 311.05 | Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB should have spreader links & phase barriers. | |||
| 821 | 311.06 | 1 No. 0 to 500 V Digital voltmeter with selector switch. | |||
| 822 | 311.07 | Digital ammeter with selector switch with one set Suitable C.Ts. | |||
| 823 | 311.08 | BUSBARS: | |||
| 824 | 311.09 | 300 Amp TPN Aluminium busbars | |||
| 825 | 311.1 | OUTGOING: | |||
| 826 | 311.11 | 6 no. 63 Amps, 415 volts, 9 KA, Four Pole Miniature Circuit Breaker. | |||
| 827 | 311.12 | 6 no. 40 Amps, 415 volts, 9 KA, Four Pole Miniature Circuit Breaker. | |||
| 828 | 311.13 | MV Panel as mentioned above | 1 | Set | |
| 829 | 312 | Computer Panel | |||
| 830 | 312.01 | INCOMER: | |||
| 831 | 312.02 | 1 Nos. MCCB as per following details/ specifications: | |||
| 832 | 312.03 | 63 Amp 415 volts, 35 KA FP MCCB with thermal magnetic release having variable current settings of O/L, S/C protection and E/ F Module. | |||
| 833 | 312.04 | R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP Indication (LED type). | |||
| 834 | 312.05 | Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB should have spreader links & phase barriers. | |||
| 835 | 312.06 | 1 No. 0 to 500 V Digital voltmeter with selector switch. | |||
| 836 | 312.07 | Digital ammeter with selector switch with one set Suitable C.Ts. | |||
| 837 | 312.08 | BUSBARS: | |||
| 838 | 312.09 | 300 Amp TPN Aluminium busbars | |||
| 839 | 312.1 | OUTGOING: | |||
| 840 | 312.11 | 10 no. 32 Amps, 250 volts, 9 KA, Double Pole Miniature Circuit Breaker. | |||
| 841 | 312.12 | Computer Panel as mentioned above | 1 | Set | |
| 842 | 312.13 | SUB HEAD 2: MCB DISTRIBUTION BOARDS. | |||
| 843 | 312.14 | MCB DISTRIBUTION BOARD | |||
| 844 | 313 | Supplying & fixing following way, three pole and neutral sheet steel, MCB distribution board, 415 volts,on recess/surface complete with loose wire box, terminal blocks, tinned copper busbar, neutral link, earth bar,din bar, detachable gland plate, interconnections, phosphatized and powder coated including earthing connection bolt etc. as per technical specifications and as required.(but without MCB & RCCB). | |||
| 845 | 313.01 | 4 way (8+12), Double door | 10 | Each | |
| 846 | 313.02 | 6 way (8+18) Double door | 2 | Each | |
| 847 | 313.03 | 8 way (8+24), Double door | 10 | Each | |
| 848 | 314 | Supplying & fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 volts,on recess/surface complete with loose wire box, terminal blocks, tinned copper busbar, neutral link, earth bar,din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc.Before procurement of DB the contractor has to take approval of DB schedule/ drawing of each DB from the Electrical Engineer, HSCC, as per technical specifications and as required.(but without MCB & RCCB), | |||
| 849 | 314.01 | 8 way Double door | 8 | Each | |
| 850 | 315 | Supplying & fixing 6 Amps to 32 Amps rating, 240 volts,'B' series, miniature circuit breaker suitable for lighting & other loads of following poles in the existing MCB DB complete with connections, testing & commissioning etc. as per technical specifications & as required. | |||
| 851 | 315.01 | Single pole | 460 | Each | |
| 852 | 316 | Supplying & fixing following rating, four pole, 415 volts, Miniature Circuit Breaker (MCB),in the existing MCB DB complete with connections, testing & commissioning etc. as per technical specifications and as required. | |||
| 853 | 316.01 | 25 Amps | 10 | Each | |
| 854 | 316.02 | 40 Amps | 2 | Each | |
| 855 | 316.03 | 63 Amps | 10 | Each | |
| 856 | 317 | Supplying & fixing following rating, four pole, 415 volts, Residual Current Circuit Breaker (RCCB) having a sensitivity current upto 300 mA in the existing MCB DB complete with connections, testing & commissioning etc. as per technical specifications and as required. | |||
| 857 | 317.01 | 25 Amps | 10 | Each | |
| 858 | 317.02 | 40 Amps | 2 | Each | |
| 859 | 317.03 | 63 Amps | 10 | Each | |
| 860 | 318 | Supplying and fixing following rating, double pole, 240 volts, MCB (B/C/D/ Curve) in the existing MCB DB complete with connections, testing and commissioning etc. as required. | |||
| 861 | 318.01 | 40 amp | 8 | Each | |
| 862 | 319 | Supplying & fixing following rating, Double pole, 240 volts, Residual Current Circuit Breaker (RCCB) having a sensitivity current upto 300 mA in the existing MCB DB complete with connections, testing & commissioning etc. as per technical specifications and as required. | |||
| 863 | 319.01 | 40 amp | 8 | Each | |
| 864 | 320 | Supplying and fixing Single pole Blanking plate in the existing MCB DB complete as required. | 50 | Each | |
| 865 | 320.01 | SUB HEAD 3: WIRING | |||
| 866 | 320.02 | WIRING | |||
| 867 | 321 | Wiring for light point/fanpoint/ exhaust fan point/call bell point with 1.5 sq.mm. PVC insulated, fire retardant low smoke (FRLS) copper conductor cable, single core/ multi strand, in steel conduit (Including supplying & recess laying of MS conduit and accessories) including the following and complete as required. | |||
| 868 | 321.01 | Supplying and Fixing Modular type switches (modular Bell push in case of call bell points) in suitable size modular metal boxes, base plate & modular cover plates, space for fixing electronic fan regulator in case of fan point wiring & space for fixing 5A socket on the board etc. | |||
| 869 | 321.02 | Supplying and fixing Hexagonal fan Boxes with 3 mm thick hylem sheet covers in case of Fan Points | |||
| 870 | 321.03 | Supplying & Fixing Ceiling Rose in case of Exhaust Fan Points etc. | |||
| 871 | 321.04 | Note : | |||
| 872 | 321.05 | i) Unless otherwise specified all the conduiting work to be done in recess | |||
| 873 | 321.06 | Point wiring as mentioned above | 800 | Point | |
| 874 | 322 | Wiring for twin control light points with 1.5 sq.mm. PVC insulated, FRLS copper conductor cable in MS conduit (including supplying and recess laying of MS conduit) including the following and complete as required. | |||
| 875 | 322.01 | Supplying and Fixing Modular type two numbers 2 Way switches in suitable size modular metal boxes, base plate & modular cover plates etc. | |||
| 876 | 322.02 | Note : | |||
| 877 | 322.03 | i) Unless otherwise specified all the conduiting work to be done in recess | |||
| 878 | 322.04 | Wiring for twin control light points as mentioned above | 10 | Point | |
| 879 | 323 | Wiring for Submain/ circuit wiring with following size of PVC insulated FRLS copper conductor single core/multi strand cable in recessed steel conduit (including supply & laying of recessed conduit) as required. | |||
| 880 | 323.01 | 2X1.5 Sqmm with 1 No. 1.5 sqmm PVC FRLS insulated, copper conductor for earthing. | 1020 | Metre | |
| 881 | 323.02 | 2X2.5 Sqmm with 1 No. 2.5 sqmm PVC FRLS insulated, copper conductor for earthing. | 495 | Metre | |
| 882 | 323.03 | 2X4 Sqmm with 1 No. 4 sqmm PVC insulated FRLS copper conductor for earthing | 1700 | Metre | |
| 883 | 323.04 | 2X6 Sqmm with 1 No. 6 sqmm PVC insulated FRLS copper conductor for earthing | 30 | Metre | |
| 884 | 323.05 | 2X10 Sqmm with 1 No. 6 sqmm PVC insulated FRLS copper conductor for earthing | 200 | Metre | |
| 885 | 323.06 | 4X4 Sqmm with 2 No. 4 sqmm PVC insulated FRLS copper conductor for earthing | 200 | Metre | |
| 886 | 323.07 | 4X6 Sqmm with 2 No. 6 sqmm PVC insulated FRLS copper conductor for earthing | 250 | Metre | |
| 887 | 323.08 | 4X10 Sqmm with 2 No. 6 sqmm PVC insulated FRLS copper conductor for earthing | 50 | Metre | |
| 888 | 323.09 | 4X16 Sqmm with 2 nos 6 sq mm PVC insulated FRLS copper conductor for earthing. | 250 | Metre | |
| 889 | 324 | Supplying and fixing suitable Modular GI box on surface or in recess including providing and fixing 3 pin 5/6 amps. modular socket outlet with shutters and 5/6 amps. modular type switch with indicator type, base plate, modular cover plate, connections etc. and all civil works 'complete as required. | 75 | Each | |
| 890 | 325 | Supplying and fixing suitable modular GI box on surface or in recess including providing and fixing 6 pin 15/16 A modular socket outlet with shutters and 15/16 A modular switch with indicator, base plate, modular cover plate, connections, etc. and all civil works complete as required. | 150 | Each | |
| 891 | 326 | Supplying and fixing suitable Modular metal box on surface or in recess including providing and fixing three nos 3 pin 5/6 amps. modular socket outlet with shutters and one no. 10 amps. modular type switch, base plate, modular cover plate, connections etc. and all civil works 'complete as required. ( For computer Points) | 80 | Each | |
| 892 | 327 | Supplying and fixing suitable Module metal box on surface or in recess including providing and fixing two nos 3 pin 5/6 amps. & one 6 pin 15/16 amp modular socket outlet with shutters and one no. 20 amps. modular switch, base plate, modular cover plate, connections etc. and all civil works 'complete as required. (For Comb-2/Consultant point) | 20 | Each | |
| 893 | 328 | Supplying and fixing suitable Modular metal box surface or in recess including providing and fixing two nos 3 pin 5/6 amps. modular socket outlet with shutters and one no. 5 amps. modular type switch, base plate, modular cover plate, connections etc. and all civil works 'complete as required. ( COMBO POINT-3/ TV Point ) | 10 | Each | |
| 894 | 329 | Supply and fixing following 20/32 Amps, 240 volts, 2P+E, Industrial Socket Outlet (with plugs) in a metal box with 20/32 SP MCB in a sheet steel cover on surface or recess complete with all accessories including connections, testing and commissioning etc. as required. | 2 | Each | |
| 895 | 330 | Supplying, providing & fixing cordless musical bell with batteries etc of approved make complete as required. | 2 | Each | |
| 896 | 331 | Supply and fixing following FP MCCB, 415 volts, 35 KA (Isc), Four Pole with thermal magnetic release having variable current setting (0.8 to 1.0 In) with Extended rotary operating mechanism including door interlocking with defeat feature and padlock facility in a sheet steel enclosure on surface complete with all accessories including , connections, testing and commissioning etc. as required. | |||
| 897 | 331.01 | 63 Amp | 1 | Each | |
| 898 | 332 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. | 40 | Each | |
| 899 | 333 | Supply, Installation, Testing & Commissioning of 360 degree Ceiling recess mountable 360 degree multifunction sensor that combines motion detection (PIR), Infrared remote control reception (IR) and ambient light level detection (PE) into one device. | 5 | Nos. | |
| 900 | 334 | Supply, Installation, Testing & Commissioning of Standalone Ceiling Mounted Motion PIR sensor 360 degree. | 40 | Nos. | |
| 901 | 335 | Supply, Installation, Testing & Commissioning of Standalone Wall Mounted Motion PIR sensor 90 degree. | 20 | Nos. | |
| 902 | 335.01 | SUB HEAD 4: LIGHT FIXTURE AND FANS | |||
| 903 | 335.02 | LIGHT FIXTURES AND FANS | |||
| 904 | 336 | Supply of following LED light fixture with high efficiency with Driver , tubes/lamps, reflector, diffuser, body/housing holder etc. complete with all fixing accessories as required. | |||
| 905 | 336.01 | 1 x 20 W LED box type fluorescent light fixture (Philips BN108C LED 20S PSU CDL WH including Mounting Accessories, with minimum system lumen 2100 or approved equivalent from list of Makes )(120b/ 120bw) | 95 | Each | |
| 906 | 337 | LED Recessed flush mounted light fixture (Full Glow (1200mm), Philips RC380B G2 LED-34S-6500 L120W30 PSU OD or Cromptom LCTLR-40-CDL as per requirment with minimum system lumen 3000 or approved equivalent from list of Makes)(RMSQ3,) | 50 | Each | |
| 907 | 338 | LED recessed flush mounted light fixture (Full Glow (600mm), Philips RC380B G2 LED34S-6500 PSU OD WH or Cromptom LCTLRN-36-FO-CDL per requirment with minimum system lumen 3000 or approved equivalent from list of Makes)(RMSQ3, ) | 50 | Each | |
| 908 | 339 | LED Surface mounted light fixture (Philips SP824P LED 29S-5000 GR OD or Cromptom LCTLS-40-CDL as per requirment with minimum system lumen 3000 or approved equivalent from list of Makes)(236SM01) | 185 | Each | |
| 909 | 340 | 1 x 10 W Bulk Head light fixture (Philips WT202 W LED 6S CW PSU S1 PC or approved equivalent from list of Makes)(BH) | 5 | Each | |
| 910 | 341 | 1 x 14 W Mirror top with diffuser in 2ft variant (Crompton Greaves LINNET # LCL-14-CDL or approved equivalent from list of Makes)(wtoilet) | 35 | Each | |
| 911 | 342 | Surface mounted Batten holder (Plastic) with 9 watt LED | 10 | Each | |
| 912 | 343 | 1 x 15 W LED Surface mounted down light fixture (Philips DN170C LED 10S-6500 PSU WH or approved equivalent from list of Makes)(DL0-S) | 26 | Each | |
| 913 | 344 | LED Recessed flush mounted down light fixture (Philips DN194B LED 15S -6500 PSU WH or Crompton LCDD-18-CDL/TL/WW or approved equivalent from list of Makes)(DL1) | 10 | Each | |
| 914 | 345 | 1 x 18 W LED Surface mounted down light fixture (Crompton Greaves Pearl Round LCD SPL-R-18-CDL or approved equivalent from list of Makes ) | 64 | Each | |
| 915 | 346 | 1X70 LED Surface mounted down light fixture (Crompton Greaves LHB 11 -70-CDL/60 or approved equivalent ) (DL2) | 22 | Each | |
| 916 | 347 | Supply of following ceiling fans (BEE -5 Star Rated) complete with double ball bearing, motor, blades, downrod, canopies, capacitor, modular type electronic fan regulator, suitable for operation on 230 volts, 50 Hz., 1 phase, AC supply complete as required. | |||
| 917 | 347.01 | 1400 mm Sweep | 10 | Each | |
| 918 | 347.02 | 1200 mm Sweep | 180 | Each | |
| 919 | 347.03 | 900mm Sweep | 5 | Each | |
| 920 | 348 | Supply of 1380 RPM, 300 mm (Crompton Greaves Trans Air or approved equivalent) exhaust fan suitable for single phase 230 volts, 50 Hz., AC supply complete with motor, louvers/shutters etc. complete as required.\n | 10 | Each | |
| 921 | 349 | Supply of 1250 RPM, 250 mm (Crompton Greaves Brisk Air or approved equivalent) exhaust fan suitable for single phase 230 volts, 50 Hz., AC supply complete with motor, louvers/shutters etc. complete as required.\n | 2 | Each | |
| 922 | 350 | Supply of 400 mm sweep, Crompton greaves model high flow 16'' wall mounted fan complete with double ball bearing, motor, blades, capacitor etc suitable for single phase 230 volts, 50 Hz., AC supply, complete as required. | 11 | Each | |
| 923 | 351 | Installation, testing and commissioning of wall bracket /ceiling fittings of all sizes and shapes containing LED lamps per fitting, complete with all accessories including connections etc. as required. | 552 | Each | |
| 924 | 352 | Installation, testing and commissioning of ceiling fan and modular type electronic fan regulator (Electronic regulator to be fixed in switch board) including wiring the down rod and connection with 1.5 sqmm FR PVC insulated, copper conductor single core/multi strand cable including providing & fixing phenolic laminated sheet cover on the fan box, etc. as required. | 195 | Each | |
| 925 | 353 | Installation, testing and commissioning of exhaust fan up to 400 mm sweep in the opening, including making the hole to suit the size of the above fan including , fixing of louvers/ shutters with frame making good the damages etc. as required. | 12 | Each | |
| 926 | 354 | Installation, testing and commissioning of wall mounted fan up to 400 mm sweep including supply and fixing wall bracket arrangement complete as required. | 11 | Each | |
| 927 | 354.01 | SUB HEAD 5: TELEPHONE SYSTEM | |||
| 928 | 354.02 | TELEPHONE SYSTEM | |||
| 929 | 355 | Supplying drawing, connecting and testing of 0.5mm dia annealed copper conductor PVC insulated PVC sheathed telephone Wire/cables in Existing M.S/ PVC conduit or a racks as required. | |||
| 930 | 355.01 | 2 pair Telephone cable. (0.5 mm) | 1650 | Meter | |
| 931 | 356 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. | |||
| 932 | 356.01 | 20 mm | 1125 | Metre | |
| 933 | 356.02 | 25 mm | 375 | Metre | |
| 934 | 357 | Supply, fixing, connecting and testing of telephone modular sockets modular plate anodised MS box and blanking plate in surface / recessed including connectionetc as required. | |||
| 935 | 357.01 | Telephone socket outlet (RJ-11 telephone Jack Single with Shutter) | 75 | Each | |
| 936 | 358 | Supplying, Installation, testing and commissioning of following sizes of telephone distribution board in M.S. hinged type lockable box duly painted complete with Krone type tag block etc. including terminations of cable as required. | |||
| 937 | 358.01 | 10 Pair | 8 | Each | |
| 938 | 359 | Supplying and drawing of following pairs 0.5mm dia annealed bare copper conductor Polythene insulated, core twisted into pairs armoured telephone cable on surface/tray with saddels including termination of cables at both sides in Krone Tag Block etc. complete as required. | |||
| 939 | 359.01 | 10 Pair | 100 | Metre | |
| 940 | 360 | Supplying and drawing of following pairs 0.5 mm dia annealed bare copper conductor Polythene insulated, core twisted into pairs armoured jelly filled telephone cable in the existing trench/ hume pipe/ GI pipe etc with saddels etc. including terniation of cables in both sides at krone tag block complete as required. | |||
| 941 | 360.01 | 100 Pair | 50 | Metre | |
| 942 | 360.02 | SUBHEAD 6: CONDUITING FOR COMPUTER SYSTEM . | |||
| 943 | 360.03 | CONDUITING FOR COMPUTER SYSTEM . | |||
| 944 | 361 | Supply and fixing of following sizes of MS conduit along with the accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required | |||
| 945 | 361.01 | 20 mm dia | 1200 | Metre | |
| 946 | 361.02 | 25 mm dia | 400 | Metre | |
| 947 | 362 | Supplying and fixing two module modular plate in recess flush mounted with clear acrylic cover RJ-45 computer socket with GI box complete as required. | 80 | Each | |
| 948 | 362.01 | SUB HEAD 7: CONDUTING FOR TV OUTLETS | |||
| 949 | 362.02 | CONDUITING FOR TV OUTLETS | |||
| 950 | 363 | Supply and fixing of following sizes of MS conduit along with the accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required | |||
| 951 | 363.01 | 20 mm dia | 300 | Metre | |
| 952 | 363.02 | 25 mm dia | 50 | Metre | |
| 953 | 364 | Supplying and fixing 2 module modular metal box in recess flush mounted with clear acrylic cover with modular cover plate including fixing 1 no. coaxial TV outlet connection and all accessories complete as required | 10 | Each | |
| 954 | 365 | Supply and drawing Coaxial TV Cable RG - 6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. | 400 | Metre | |
| 955 | 365.01 | SUBHEAD 8: ADDRESSABLE FIRE ALARM SYSTEM | |||
| 956 | 365.02 | ADDRESSABLE FIRE ALARM SYSTEM | |||
| 957 | 366 | Supply, Installation, testing and commissioning of microprocessor based addressable type networkable Fire Detection & Alarm Panel complete with inbuilt power supply, battery charger with SMF batteries for minimum 24 hours back-up. The panel shall have a communication module and HI 485 network card. The panel should have rectifier, loop card, minimum 80 character LCD unit to indicate fire/ fault signals with address including external/ internal printer port etc complete as per technical specifications and as per the requirement of Local Fire Authority and as required. | |||
| 958 | 366.01 | 2 Loop | 1 | Nos. | |
| 959 | 367 | Supply, installation, testing and commissioning of Automatic Analog addressable Photo - Thermal multicriteria detector with mounting Base, alarm LED. The Detector shall have automatic Electronic/ dip switch addressing feature , complete with the GI Mounting Box and the hardware etc. as required. (UL Approved) | 90 | Nos. | |
| 960 | 368 | Supply, installation, testing and commissioning of Automatic Analog addressable Photoelectric smoke detector with mounting Base, alarm LED .The Detector shall have automatic Electronic/ dip switch addressing feature , complete with the GI Mounting Box and the hardware etc. as required. (UL Approved). | 65 | Nos. | |
| 961 | 369 | Supply, installation, testing and commissioning of Automatic Analog addressable Fixed Temperature cum rate of Rise type Heat detector with mounting Base, alarm LED shall be viewable from 360 degrees. The Detector shall have automatic Electronic/ dip switch addressing feature, complete with the GI Mounting Box and the hardware etc. as required. (UL Approved). | 2 | Nos. | |
| 962 | 370 | Supply, installation, testing and commissioning of Automatic Addressable control module for AHU & Stair Pressurization fan, The Module shall have automatic Electronic addressing feature & each of these shall be equipped with fault Isolator complete with the GI Mounting Box and the hardware etc. as required. (UL Approved). | 1 | Nos. | |
| 963 | 371 | Supply, installation, testing and commissioning of Automatic Addressable Monitor module for Flow Switch Monitoring etc. The Module shall have automatic Electronic/ dip switch addressing feature, complete with the GI Mounting Box and the hardware etc. as required. (UL Approved). | 1 | Nos. | |
| 964 | 372 | Supply, installation, testing and commissioning of Dual LED Response indicator for indicating the activation of the Remotely located Detector. | 45 | Nos. | |
| 965 | 373 | Supply, installation, testing and commissioning of Addressable Manual call Station. The Call Point shall have automatic Electronic/ dip Swich addressing feature, complete with the Mounting Box and the hardware etc. as required. (UL Approved). | 6 | Nos. | |
| 966 | 374 | Supply, installation, testing and commissioning of Addressable electronic Sounder. The Sounder shall have automatic Electronic/ dip switch addressing feature ,complete with the Mounting Box and the hardware etc. as required. The Sounders shall be Loop powered i.e. should not require additional cable to feed the Power & shall be programmable from the Fire Panel for Multiple type of tones selection. (UL Approved). | 6 | Nos. | |
| 967 | 375 | Supply, installation, testing and commissioning of Addressable electronic Sounder with Optical Beacon. The unit shall have automatic Electronic addressing/ dip switch feature,complete with the Mounting Box and the hardware etc. as required. The unit shall be Loop powered i.e. should not require additional cable to feed the Power & shall be programmable from the Fire Panel for Multiple type of tones selection. (UL Approved). | 2 | Nos. | |
| 968 | 376 | Supply and laying of following size of MS Conduit pipe in recess including all accessories MS pull/ junction boxes, GI fish wire of 6 SWG, fixing hardware etc., including cutting, chasing the walls/ floor and plastering the chased portion and making good the damages etc., complete as required. | |||
| 969 | 376.01 | 20 mm dia | 700 | Meter | |
| 970 | 376.02 | 25 mm dia | 100 | Meter | |
| 971 | 377 | Supply and drawing of 2C x 1.5 Sq.mm. Sheathed anneled flexible copper Conductor FRLS cable in existing M. S. Conduit, Complete with termination and testing as per requirement. | 200 | Meter | |
| 972 | 378 | Supply and drawing of 4C x 1.5 Sq.mm. anneled flexible copper Conductor, Copper breaded shielding and overall Sheathed FRLS cable in existing MS Conduit, Complete with termination and testing as per requirement. | 40 | Meter | |
| 973 | 378.01 | SUB HEAD 9: CONDUITING CCTV SURVEILLANCE SYSTEM | |||
| 974 | 379 | Supply and fixing of following sizes of steel conduit along with the accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of conduit as recessed required | |||
| 975 | 379.01 | 20 mm dia | 400 | Metre | |
| 976 | 379.02 | SUB HEAD 10: LT CABLES | |||
| 977 | 379.03 | LT CABLES | |||
| 978 | 380 | Supply of following sizes of 1.1 kV grade multicore aluminium conductor PVC sheathed armoured XLPE cable as per IS 7098. | |||
| 979 | 380.01 | 3.5 Core 25 Sqmm. | 100 | Metre | |
| 980 | 380.02 | 3.5 Core 70 Sqmm. | 250 | Metre | |
| 981 | 380.03 | 3.5 Core 150 Sqmm. | 200 | Metre | |
| 982 | 380.04 | 3.5 Core 185Sqmm. | 100 | Metre | |
| 983 | 380.05 | 3.5 Core 300 Sqmm. | 500 | Metre | |
| 984 | 380.06 | 4 Core 16 Sq mm | 100 | Metre | |
| 985 | 380.07 | 4 Core 10Sq mm | 100 | Metre | |
| 986 | 380.08 | 3 Core 6 Sqmm. | 100 | Metre | |
| 987 | 380.09 | 3 Core 4 Sqmm. | 100 | Metre | |
| 988 | 380.1 | 2 Core 10 Sq mm | 600 | Metre | |
| 989 | 380.11 | 2 Core 16 Sq mm | 400 | Metre | |
| 990 | 381 | Laying of one number PVC insulated and PVC sheathed power cable 1.1kV grade direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required | |||
| 991 | 381.01 | Up to 35 sq.mm | 1050 | Metre | |
| 992 | 381.02 | Above 35 Sq mm and upto 95 Sq mm | 175 | Metre | |
| 993 | 381.03 | Above 95 Sq mm and up to 185 Sq mm | 140 | Metre | |
| 994 | 381.04 | Above 185 Sq mm and up to 400 Sq mm | 420 | Metre | |
| 995 | 382 | Laying of one number PVC insulated and PVC sheathed power cable 1.1kV grade direct in the existing RCC/ Hume/Stoneware/Metal pipe as required | |||
| 996 | 382.01 | Up to 35 sq.mm | 225 | Metre | |
| 997 | 382.02 | Above 35 Sq mm and upto 95 Sq mm | 83 | Metre | |
| 998 | 382.03 | Above 95 Sq mm and up to 185 Sq mm | 30 | Metre | |
| 999 | 382.04 | Above 185 Sq mm and up to 400 Sq mm | 90.5 | Metre | |
| 1000 | 383 | Laying of one number PVC insulated and PVC sheathed power cable 1.1kV grade on surface or on existing cable tray complete as required. | |||
| 1001 | 383.01 | Up to 35 sq.mm | 225 | Metre | |
| 1002 | 383.02 | Above 35 Sq mm and upto 95 Sq mm | 83 | Metre | |
| 1003 | 383.03 | Above 95 Sq mm and up to 185 Sq mm | 30.5 | Metre | |
| 1004 | 383.04 | Above 185 Sq mm and up to 400 Sq mm | 90.5 | Metre | |
| 1005 | 384 | Supplying and making end termination with suitable size Aluminium lugs including double compression glands of following sizes of 1.1 kV grade multicore aluminium conductor PVC insulated and PVC sheathed | |||
| 1006 | 384.01 | 3.5 Core 25 Sqmm. | 6 | Each | |
| 1007 | 384.02 | 3.5 Core 70 Sqmm. | 4 | Each | |
| 1008 | 384.03 | 3.5 Core 150 Sqmm. | 8 | Each | |
| 1009 | 384.04 | 3.5 Core 185Sqmm. | 4 | Each | |
| 1010 | 384.05 | 3.5 Core 300 Sqmm. | 10 | Each | |
| 1011 | 384.06 | 4 Core 16 Sq mm | 10 | Each | |
| 1012 | 384.07 | 4 Core 10Sq mm | 10 | Each | |
| 1013 | 384.08 | 3 Core 6 Sqmm. | 10 | Each | |
| 1014 | 384.09 | 3 Core 4 Sqmm. | 10 | Each | |
| 1015 | 384.1 | 2 Core 10 Sq mm | 30 | Each | |
| 1016 | 384.11 | 2 Core 16 Sq mm | 30 | Each | |
| 1017 | 384.12 | SUBHEAD 11: EARTHING | |||
| 1018 | 384.13 | EARTHING | |||
| 1019 | 385 | Supply and installation of one number earth pit with advance maintinance free Earthing System consisting of one Number, CPRI tested copper bonded steel electrode of minimum 19 mm dia (as per IE C62561-2 ) With a minimum. coating thickness of 250 microns and length of 3 meters. 25 kg/Electrode of earth enhancing compound (tested as per IEC-62561-7) fill the 100mm augered hole surrounding to the electrode , SS Universal Clamp of Size 175X50X3 mm for terminal Connection including Poly Propylene Heavy duty Pit cover including all accessories , excavation of earth, filling with back fill compound, and earth pit marking. The Complete installation shall be as per the drawing, technical specifications and as required | 2 | Set | |
| 1020 | 386 | Supply and installation of one number earth pit with of advance maintinance free Earthing System consisting of one Number UL Listed CPRI tested copper bonded steel electrode of minimum 13 mm dia. (as per IE C62561-2 ) With a minimum. coating thickness of 250 microns and length of 3 meters. 25 kg/Electrode of earth enhancing compound (tested as per IEC-62561-7) fill the 100mm augered hole surrounding to the electrode , SS Universal Clamp of Size 175X50X3 mm for terminal Connection including Poly Propylene Heavy duty Pit cover including all accessories , excavation of earth, filling with back fill compound, and earth pit marking. The Complete installation shall be as per the drawing, technical specifications and as required | 2 | Set | |
| 1021 | 387 | Supplying and laying 25mmX5mm GI strip at 0.5m below ground level as strip earth electrode, including soldering etc. as required. | 100 | Metre | |
| 1022 | 388 | Providing and fixing 25mmX5mm GI strip on surface/on existing cable trench/RCC pipe/GI pipe or in recess for earth electrode as required. | 100 | Metre | |
| 1023 | 389 | Supplying and laying 50mmX6mm GI strip at 0.5m below ground level as strip earth electrode, including soldering etc. as required. | 100 | Metre | |
| 1024 | 390 | Providing and fixing 50mmX6mm GI strip on surface/on existing cable trench/RCC pipe/GI pipe or in recess for earth electrode as required. | 50 | Metre | |
| 1025 | 391 | Providing and fixing25mmX5mm Copper strip on surface/on existing cable trench/RCC pipe/GI pipe or in recess for earth electrode as required. | 50 | Metre | |
| 1026 | 392 | Supplying and laying 25mmX5mm Copper strip at 0.5m below ground level as strip earth electrode, including soldering etc. as required. | 50 | Metre | |
| 1027 | 393 | Supplying and laying 50mmX6mm Copper strip at 0.5m below ground level as strip earth electrode, including soldering etc. as required. | 20 | Metre | |
| 1028 | 394 | Providing and fixing 50mmX6mm Copper strip on surface/on existing cable trench/RCC pipe/GI pipe or in recess for earth electrode as required. | 30 | Metre | |
| 1029 | 395 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I.pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required | 50 | Metre | |
| 1030 | 396 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. | 50 | Metre | |
| 1031 | 397 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. | 100 | Metre | |
| 1032 | 397.01 | 300 mm dia | 100 | Metre | |
| 1033 | 397.02 | 150 mm dia | 50 | Metre | |
| 1034 | 397.03 | CABLE ROUTE MARKER | |||
| 1035 | 398 | Supplying and fixing cable route marker with 10 cm x 10 cm x 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm x 35 mm x 6 mm angle iron, 60 cm long and fixing the same in ground as required. | 20 | each | |
| 1036 | 398.01 | SAFETY EQUIPMENT | |||
| 1037 | 399 | Providing and fixing MV danger notice plate of 200 x 150 mm made of mild steel, atleast 2 mm thick and vitreous enammelled white on both sides and with inscription in signal red colour on front side as required. | 3 | Each | |
| 1038 | 400 | Supply & erection of the following Safety and testing Equipment including miscellanoes items like Clamps, nuts & Bolts, rawl plugs etc. at suitable places in the Substation building as required. | |||
| 1039 | 400.01 | GI buckets, 4 nos of 5 Litres Capacity duly painted white inside and red oxide paint out side and with 'FIRE' witten in white paint & Filled with Dry sand and mounted on MS angel iron bracket of Size 50 x 50 x 6 mm thick and 1200 mm long including grounting in walll / floor etc as required . | 1 | Each | |
| 1040 | 402 | Supplying, storing, handling and fixing in position First Aid Medical Box complete as per technical specifications as required. | 2 | Each | |
| 1041 | 403 | Shock Treatment Chart duly glazed mounted on Aluminum Frame with Sheet Glass as required. | 1 | Each | |
| 1042 | 404 | Supplying and laying of 1.1 kV grade 1 metre wide anti skid chequered type rubber mat. | 10 | Metre | |
| 1043 | 405 | Supply rubber hand gloves 11 kV grade as per I.S. Code. | 1 | Set | |
| 1044 | 406 | Supplying of digital Earth Tester complete with probes etc as required | 1 | Set | |
| 1045 | 407 | Supplying of Telesscopic folding Aluminium ladder folding double with sitting stand 6 M etc as required. | 1 | Each | |
| 1046 | 408 | Providing and fixing of M.S Slotted angle iron with fixing materials and painting for cable racks in trenches/ on wall etc. as required. | 5 | KG | |
| 1047 | 409 | Providing and fixing of M.S Slotted angle 'C' channel/ Ladder type rack/ tray including fixing material grouted in wall or haning with M.S rod hanger from ceiling including 2 coat synthetic enamel painting over 1 coat of red oxide primer etc. as required. | 5 | KG | |
| 1048 | 410 | Fabrication and Installing following size of preforted M.S Cable tray including Horizontal and vertical bends, reducers, tee, crossmember and other accessories as required and duly Suspended from the ceiling with M.S 12 mm rod suspenders and including painting etc. as required. | |||
| 1049 | 410.01 | 150 mm width x 50 mm depth x 1.6 mm thickness | 100 | Metre | |
| 1050 | 410.02 | 300 mm width x 50 mm depth x 1.6 mm thickness | 200 | Metre | |
| 1051 | 410.03 | 450 mm width x 62.5 mm depth x 2.0 mm thickness | 100 | Metre | |
| 1052 | 411 | Fabrication and Installing following size of Ladder type M.S Cable tray including Horizontal and vertical bends, reducers, tee, crossmember and other accessories as required and duly Suspended from the ceiling with M.S 12 mm rod suspenders and including painting etc. as required. | |||
| 1053 | 411.01 | 450 mm width x 62.5 mm depth x 2.0 mm thickness | 50 | Metre | |
| 1054 | 411.02 | 600 mm width x 62.5 mm depth x 2.0 mm thickness | 50 | Metre | |
| 1055 | 411.03 | SUBHEAD 12: OUT DOOR LIGHTING | |||
| 1056 | 411.04 | OUT DOOR LIGHTING | |||
| 1057 | 412 | Supply, erection, testing and commissioning of external swaged steel tubular pole with following specifications & items : | |||
| 1058 | 412.01 | 9.0 Mtrs. high swaged steel tubular pole with arm length around 1.5 Metre, the construction of the pole shall be as per IS:2713 - 1980 410 SP-30 with base plate 450 x 450 x 6 mm complete as per requirement with two coats of spray paints of approved shade. | |||
| 1059 | 412.02 | 90 watts LED street light fixture in die cast aliuminum body with 90 watts LED lamp complete with control gear, cover etc. similar to Compton Greeves s LSTN-90-CDL-A or approved equivalent including its wiring with 2X2.5 sq.mm. PVC insulated, FRLS copper conductor and 1.5 sqmm PVC insulated, FRLS copper earth wire from control box complete as required. | |||
| 1060 | 412.03 | Suitable size 32 A DP MS Control box with 2 no. incoming and outgoing terminals and 2 nos. tap-out terminal with 6A DP MCB complete as required - 1 Set | |||
| 1061 | 412.04 | Suitable number(s) 40mm dia Class-B GI Pipe(s) from above control box to upto 0.5 metre below ground level for power cable entry | |||
| 1062 | 412.05 | Providing foundation including excavation, shuttering, alingment of poles, casting etc. including lean concrete at the bottom as per CPWD/ BIS specifications. | |||
| 1063 | 412.06 | The above installations shall be completed as CPWD specifications and as required | |||
| 1064 | 412.07 | Steel Tubular Poles (9M) Single Arm as mentioned above | 12 | Set | |
| 1065 | 412.08 | Steel Tubular Poles (9M) same as above but for Double Arm as mentioned above | 4 | Set | |
| 1066 | 413 | Supply, installation, testing and commissioning of external post top lantern with following accessories and complete as required : | |||
| 1067 | 413.01 | 4m high (3.3m above ground) 80mm dia GI pole as approved, adopting socket at top for fixture mentioned below, base plate 300 x 300 x 6 mm and provision for mounting junction box etc. - 1 set. | |||
| 1068 | 413.02 | 1 x 40 LED Post top lantern with 40W LED lamp (Crompton Greeves LPTO-40-CDL or equivalent) and its wiring with 2 x 2.5 sq.mm PVC insulated copper wire and 1.5 sqmm PVC insulated copper earth wire from control box . | |||
| 1069 | 413.03 | Suitable size 20A DP MS Control box with 2 no. incoming and outgoings terminals and 2 nos. tap-out terminal with 1 nos. 5A HRC fuses complete 1 set. | |||
| 1070 | 413.04 | Suitable number(s) 40mm dia Class-B GI Pipe(s) from above control box to upto 0.5 metre below ground level for power cable entry | |||
| 1071 | 413.05 | Providing 400 x 400 x 1000 mm deep 1:3:6 ratio cement concrete including excavation shuttering alignment of poles casting etc. including 100mm thick lean concrete shall be provided at the bottom | |||
| 1072 | 413.06 | Supply, installation, testing and commissioning of external post top lantern as mentioned above | 10 | Set | |
| 1073 | 414 | Supply, Installation, testing and commissioning of Post top lantern 1 x 40 Watts LED Post top lantern with 40 Watt LED lamp (Crompton Greeves LPTO-40-CDL or equivalent) and its wiring with 2 x 2.5 sq.mm PVC insulated copper wire and 1.5 sqmm PVC insulated copper earth wire from control box. | 2 | set | |
| 1074 | 415 | Supply, installation, testing and commissioning of bollard lamps 1 x 10 Watts LED Light Fixture (Crompton Greeves LBLS1-10-CDl (LIARA) or equivalent) with control box - 1 set. | 8 | Each | |
| 1075 | 415.01 | ROAD LIGHTING PANEL | |||
| 1076 | 416 | Supply, installation, testing and commissioning of following outdoor type with canopy, IP-54 protected MV cubicle type totally enclosed, free standing type, dust, damp and vermin proof, MV Panel, busbars, MV danger notice plate, interconnections with suitable capacity aluminium leads/solid aluminium strips/rods, connection of incoming and outgoing cables with thimbles, stove enamelled painted and having following incoming and outgoing switchgears complete as required. | |||
| 1077 | 416.01 | INCOMER: | |||
| 1078 | 416.02 | 100 Amps,415 volts, TP+NL, 35 KA Moulded Case Circuit Breaker with thermal magnetic release having variable current settings . | |||
| 1079 | 416.03 | R, Y & B phase indicating lamp (LED type) with 2A control SP MCB. | |||
| 1080 | 416.04 | ON, OFF, TRIP indication (LED Type) | |||
| 1081 | 416.05 | Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB should have spreader links & phase barriers. | |||
| 1082 | 416.06 | 1 Set of timer switch & 100A TP contactor with nuetral link (for street lights control) . | |||
| 1083 | 416.07 | BUSBARS: | |||
| 1084 | 416.08 | 300 Amp TPN Aluminium busbars | |||
| 1085 | 416.09 | OUTGOING: | |||
| 1086 | 416.1 | 20 Nos. 16 Amp 415 volts, DP MCB | |||
| 1087 | 416.11 | ROAD LIGHTING PANEL AS MENTIONED ABOVE | 1 | Set | |
| 1088 | 416.12 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. | 200 | Metre | |
| 1089 | 416.13 | FIRE FIGHTING SYSTEM | |||
| 1090 | 417 | Providing, fixing joiting and testing of Heavy (class -C) G.I. pipes as per relevant IS :1239/4736 with special accessories like tees, elbow, gesket, flanges, flanged joints, rubber insertion nuts and bolts including earth work excavation and trenching, wrapping pipekot 4mm thick 500mm width tar based plymaric corrosion protection tape or equivalent suitable to GI/ MS pipe line including applying uniform coat of cold pipekot primer complete 1 m below the ground level, refillling in layers not exeeding 20 cm in depth consolidated each deposited layer by ramming & watering complete in all respect as pe IS : 1022 (Under ground ) | |||
| 1091 | 417.01 | 150 mm dia G.I. Pipe with flange joints (5.4 mm wall thickness) | 10 | Metre | |
| 1092 | 417.02 | 100 mm dia G.I. Pipe with flange joints | 30 | Metre | |
| 1093 | 417.03 | 80 mm dia G.I. Pipe with flange joints | 10 | Metre | |
| 1094 | 418 | Heavy class G.I. pipes conforming to IS with accessories like tees, elbows, flanged joints, rubber insertion, nuts, bolts or welded joints including fixing the pipe with suitable flat iron strip clamps/brackets, structural members, dash fastener , cutting hole and chases in walls, floor, R.C.C. slab etc. and making good the same, including painting pipes and fittings with a primer coat of steel primer and two coats of postal red enamel paint etc. complete as required. (All the fitting i.e. tee /elbow, Valve shall be joint the pumps will flanged joints) | |||
| 1095 | 418.01 | 200 mm dia (with Flanged joints) IS: 3589 thick 6 mm | 10 | Metre | |
| 1096 | 418.02 | 150 mm dia (with Flanged joints) IS: 1239 thick 5.4 mm | 40 | Metre | |
| 1097 | 418.03 | 100 mm dia (with Flanged joints) | 20 | Metre | |
| 1098 | 418.04 | 80 mm dia | 10 | Metre | |
| 1099 | 419 | Providing & fixing fire authority approved Alluminium shutter (size 1200 (L) x 2100 (H) mm ), The shutter size shall be as per approved drawing capable of accommodating fire hose reel, fire hydrant, hose pipe, fittings & accessories. The box shall have a single or double glazed front glass door (with 4 mm thick glass) with lock & key arrangement & shall be painted with Fire red as per IS:5, shade no. 536 complete in all respects. (For Internal Hydrant) (Excluding the cost of alluminium work which will be paid as per civil work items) | 3 | Each | |
| 1100 | 420 | Supplying and Fixing First Aid Hose Reel, wall mounting swinging type complete with drum & bracket of MS construction, spray painted in Post office Red, confirming to IS 884/1995 with upto date amendments, complete with the following as required. | |||
| 1101 | 420.01 | 36 Meter long 20 mm dia water hose Thermoplastic (Textile reinforced) Type - 2 as per IS : 12585 | |||
| 1102 | 420.02 | 20 mm dia gun metal ball valve & nozzle. | |||
| 1103 | 420.03 | Drum and brackets for fixing the equimpments on wall. | |||
| 1104 | 420.04 | Connection from riser with stop valve (gun metal) & M.S. Pipe | 3 | Each | |
| 1105 | 421 | Supplying and Fixing of Fire Man's axe with heavy insulated rubber as per standard conforming to IS 926 | 3 | Each | |
| 1106 | 422 | Fabricating, Supplying, Installation, Testing and Commissioning Air Vessel of continuous welded construction with flanged discharge header on the top of each riser fabricated out of 10 mm thick dished ends and 8 mm thick MS sheet, Air Release Valve complete with suitable drain arrangement with 25 mm dia gun metal wheel valve complete with all accessories etc. as required of the following sizes | |||
| 1107 | 422.01 | 1.2 Metre high and 250 mm dia | 1 | Each | |
| 1108 | 423 | Providing and fixing 25mm dia. Gunmetal Air Release valve, single acting including the cost of 25mm gate valve, Pressure gauge, all pipes and fittings as per standard design complete in all respects. | 1 | Each | |
| 1109 | 424 | Providing and fixing Hose Cabinet for External Hydrant Stand post type of size (750 x 600 mm x 300 mm) fabricated from 2 mm thick SS sheet having openable glazed door shutter with 4mm thick glass suitable to accommodate hydrants, 2 Nos. canvas hose pipe bearing ISI mark Under IS:639-992 type B ( not less then 30 Meter length) and branch pipe including necessary locking arrangements, painting inside and external part shall be natural polished in matt finish including SS 304 angle stand and PCC foundation 1:2:4 complete with locking arrangement and inbuilt key box. | 6 | Each | |
| 1110 | 425 | Supply, Installation, Testing and Commissioning External Yard Hydrant Stand Post comprising of GI pipe 80 mm dia (heavy duty C class) from existing ringmain to about 1 meter above ground level and Single Headed Yard Hydrant Valve with 80 mm dia flanged inlet, intantanneous gunmetal coupling of 63 mm dia with cast iron wheel ISI marked, conforming to IS : 5290 (Type A), with ABS cap and chain etc.complete with all accessroies as required. | 6 | Each | |
| 1111 | 426 | Providing and fixing Single headed hydrants flanged inlet with 63 mm female instantaneous outlet of gunmetal/SS complete with male blank caps, chains conforming to IS:5290 type A with stainless steel orifice plate (if required) to keep the pressure not more than 3.5 kg/sq.cm at any point. | 9 | Each | |
| 1112 | 427 | Providing and fixing Gunmetal/SS branch pipe with 20mm dia nozzle conforming to IS:903. suitable for installation connections to hose coupling etc. as required. | 12 | Each | |
| 1113 | 428 | Providing 63mm dia 15 m long reinforced Rubber lined hose pipe conforming to IS: 636-1992 Part-II with gunmetal/SS male & female coupling wire wound with pipe as required. | 18 | Each | |
| 1114 | 429 | Supply, erection, testing & commissioning of Exit Glow Sign Board of size 200mm x 350 mm wall mounting signage consisting of photo luminescent coating, non radioactive on acrylic cover | |||
| 1115 | 429.01 | Single sided luminescent exit glow sign board | 3 | Each | |
| 1116 | 429.02 | Double sided luminescent exit glow sign board | 3 | Each | |
| 1117 | 430 | Supply, Installation, Testing and Commissioning of 100 mm dia Bourden type, Stainless Steel dial type Pressure Gauge including brass isolation valve and siphon pipe having caliberation of 0 - 16 Kg / cm2 . | 3 | Each | |
| 1118 | 431 | Constructing Masonry chamber 90x90x100 cm, inside with 75 class designation brick work in cement mortar 1:4 (1 cement: 4 fine sand) for sluice valve, with C.I. surface box 100mm top diameter, 160mm bottom diameter and 180mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design. | |||
| 1119 | 431.01 | with F.P.S. bricks | 1 | Each | |
| 1120 | 432 | Providing and fixing C.I. sluice valves (With cap) of approved quality complete with bolts, nuts, rubber insertions etc. ( the tail pieces if required will be paid separately ) Class II | |||
| 1121 | 432.01 | 150 mm dia | 2 | Each | |
| 1122 | 432.02 | 100mm dia | 2 | Each | |
| 1123 | 433 | Providing and fixing cast iron body IS: 210 FG 200 and double flange gear simple operation type Butterfly valve conforming to IS: 13095 with SS304 disc and shaft NITNLE rubber replaceable seat of the following size complete with bolts, nuts, washers and rubber insertions as per specification. | |||
| 1124 | 433.01 | 200 mm dia | 1 | Each | |
| 1125 | 433.02 | 150 mm dia | 3 | Each | |
| 1126 | 433.03 | 100 mm dia | 1 | Each | |
| 1127 | 433.04 | 80 mm dia | 1 | Each | |
| 1128 | 434 | Providing and fixing C.I. double flanged horizontal/vertical type check valve NRV including nuts, bolts, rubber insertions as required conforming to IS:5312 | |||
| 1129 | 434.01 | 150 mm dia | 2 | Each | |
| 1130 | 434.02 | 100 mm dia | 1 | Each | |
| 1131 | 435 | Providing and fixing of C.I. 'Y' type strainer flanged with SS 304 perforated screen including nuts, bolts and rubber insertions etc | |||
| 1132 | 435.01 | 150 mm dia | 1 | Each | |
| 1133 | 435.02 | 100 mm dia | 1 | Each | |
| 1134 | 436 | Providing and fixing of Foot valve complete with including M.S. flange nuts, bolts, washers, gaskets insertions etc. | |||
| 1135 | 436.01 | 150 mm dia | 1 | Each | |
| 1136 | 437 | Supplying, testing, installation & commissioning of Pressure switches for pumps including necessary wiring upto the control panel. | 2 | Each | |
| 1137 | 438 | Supplying and Fixing vane type Waterflow switch with contacts suitable for installation on 50 mm to 150 mm dia pipeline for a service pressure upto 20 Kg/sq.cm. | 2 | Each | |
| 1138 | 439 | Providing & Fixing of gun metal Two way fire brigade inlet to riser with 63 mm dia instantaneous type inlet and 150 mm dia flanges outlet conforming to IS:904 with blank cap and chain complete with nuts, bolts, flanges and complete in all respect along with 150 mm dia butterfly valve and 150 mm dia dual plate type NRV. Cost shall include a wall mounted box of M.S. construction (16 SWG) with glass door (4.0 mm thick) to house the above mentioned component. (Location : For Hydrant Riser, outside every block) | 1 | Each | |
| 1139 | 440 | Providing and fixing stainless steel Four way fire brigade inlet connection to UG fire tank with 4 Nos. 63 mm dia instantaneous type inlet and 150 mm dia flanges outlet conforming to IS:904 with blank cap and chain including 150 mm dia butterfly valve (PN 16 rating) complete with nuts, bolts, flanges and complete in all respect. Cost shall include a wall mounted box of SS construction 2mm thick with glass door (4.0 mm thick) of adequate size (approx 0.6 m x 0.6 m x 0.45 m) to house the above mentioned component. | 1 | Each | |
| 1140 | 441 | Providing and fixing stainless steel four way fire brigade inlet connection to main discharge header in fire pump room with 4 Nos. 63 mm dia instantaneous type inlet and 150 mm dia flanges outlet conforming to IS:904 with blank cap and chain including 150 mm dia butterfly valve (PN 16 rating) and 150 mm dia wafer type non-return valve complete with nuts, bolts, flanges and complete in all respect. Cost shall include a wall mounted box of M.S. construction 2mm thick with glass door (4.0 mm thick) of adequate size (approx 0.6 m x 0.6 m x 0.45 m) to house the above mentioned component. | 1 | Each | |
| 1141 | 442 | Providing and fixing 150 mm dia gun metal fire brigade suction hose coupling of (SS draw off connection) with 150 mm dia M.S. 'C’ Class suction pipe with 150 mm dia C.I. foot valve.Cost shall include a wall mounted box of SS. construction 2mm of adequate size with glass door (4.0 mm thick) to house the above mentioned component to be connected to static water tank. | 1 | Each | |
| 1142 | 443 | Providing and fixing Set of \"Siamese\" quadraplet instantaneous fire brigade connections comprising of two gunmetal instantaneous male inlet coupling 63mm dia with plug and cap, chain bends, tees etc for inlet to the static tank. | 1 | Each | |
| 1143 | 444 | Providing and placing on Terrace Polyethylene Water Storage Tank ISI : 12701 MARKED indicating the BIS license No with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. | 10000 | Ltrs. | |
| 1144 | 445 | Providing and fixing Sand Bucket with Stand (6 Bucket) as per site conditions | 1 | Each | |
| 1145 | 446 | Providing & fixing of IS marked (IS:15683) portable fire extinguisher, carbondioxide type flat base including valve, discharge hose of not less than 10 mm dia. 1 M long & complete in all respects including initial fill with CO2 gas confirming to IS:15222 filled to a filling ratio of not more than 0.667 and wall suspension bracket- | |||
| 1146 | 446.01 | Capacity 4.5 Kg | 3 | Each | |
| 1147 | 447 | Providing and fixing Modular type ceiling mounted clean UL listed & FM Approved agent (FE-36) Hexaflouropropane type fire extinguisher, ISI Marked IS 15683:2006, Gas listed under EPA SNAP, having sprinkler with glass bulb rated at 68 deg.C, CE MArked Valve, suitable for Class A,B and C type of fires, conforming to ISO 14520, FM approved and UL listed.- For Electrical, UPS, Server, Battery Rooms etc. | |||
| 1148 | 447.01 | Capacity 10 Kg - One in each Electrical Room | 1 | Each | |
| 1149 | 448 | Providing & Fixing 6 Kg. ABC MAP-90% Powder type fire extinguishers are manufactured and marked to Indian standard IS: 15683 with test cirtificates of Helium leak detection Hose shall made of EPDM Rubber, UGTS Pressure Gauge, CE Marked Valve, Suitable first aid appliance for fighting fires in Class A, B & C fire that is wood, textile, flammable liquids & gases. | 3 | Each | |
| 1150 | 449 | K (Kitchen) type 6 Ltr. Stored Pressure type Fire Extinguisher, with UGTS Pressure Gauge, Deep Drawn, Stainless Steel Body, EPDM Rubber Hose with SS Nozzle, CE Mark Valve with Safety Release Provision, Helium Leak Detection Tested, Controllable discharge mechanism applicable on Class K (Kitchen) Fire, maintenance, care and refilling as per IS 2190:2010 | 1 | Each | |
| 1151 | 450 | Providing & fixing of IS marked (IS: 13386-1992) Mechanical foam type fire extinguishers 50 lts consisting of welded M.S. trolley mounted cylindrical body, squeeze lever discharge valve fitted with pressure discharge hose, discharge nozzle, trolley etc. finished externally with red enamel paint and fixed to wall with brackets complete with internal charges - For DG Set, Substation area | 1 | Each | |
| 1152 | 451 | Providing and fixing 9 liters capacity fire extinguisher Water type Gas pressure, fixed to wall. With EPDM Rubber Hose pipe with test cirtificate of helium leak detection complete to IS 15683-2006 & ISI marked | 3 | Each | |
| 1153 | 452 | Providing and fixing complete CO2 flooding system of approved make and model for main LT panel including two nos. 22 kg seamless cylinder required quantity of MS seamless pipe, manifold, NRV, high pressure flexible hose, weighing arrangement, pneumatic valve, CO2 nozzles including painting and MS support.The size of main LT panel will be as per Electrical scope of work. The shop drawing/datasheet of CO2 flooding system shall be provided by Agency for approval of HSCC before start of the work. The CO2 flooding panel shall also meet out the local Fire Officers latest requirement and anything extra or any modification required by Fire officer shall be carried uot by Agency without any extra cost. | 1 | Each | |
| 1154 | 452.01 | Supression System | |||
| 1155 | 453 | S/F 10 LB capacity NOVEC 1230 DLP Assembly with Automatic valve, push in connector for tube, 5 LB NOVEC 1230 gas, mounting bracket, end of line adopter and low pressure switch for monitoring system activation of automatic linear pneumatic tube detection system complete etc. as reqd as one job make: Fire Trex /Seimens / UTC | 1 | JOB | |
| 1156 | 454 | S/F 2.5 LB capacity NOVEC 1230 DLP Assembly with Automatic valve, push in connector for tube, 2.5 LB NOVEC 1230 gas, mounting bracket, end of line adopter and low pressure switch for monitoring system activation of automatic linear pneumatic tube detection system, complete etc. as reqd as one job make: Fire Trex /Seimens / UTC | 2 | JOB | |
| 1157 | 455 | S/F linear pneumatic heat detection tube UL marked and suppression system operated on 92-100 deg, Cent temp. With all necessary fittings and supports, fixing in the existing electrical panel board, complete etc as required at site . Make: FireTraco/Srevo System/Fire System/Fire TEC | 20 | MTR | |
| 1158 | 456 | S/F audio visual alarm system for automatic linear fire trace tube detection system, complete etc as required at site | 2 | Each | |
| 1159 | 457 | Supplying, Installation, Testing & Commissioning modular construction master control annciation panel for sprinkler with provision for requider No. of Zone (30% additional spares),eachsprinkler hydrant will have atleast 4 zone on each floor as approved by engineer.The panel shall have but not limited to the following arrangment. | |||
| 1160 | 457.01 | Indication of Zone sprinkler | |||
| 1161 | 457.02 | Indication of zone fault | |||
| 1162 | 457.03 | Fire/fault hooter | |||
| 1163 | 457.04 | Alarm cancel for fire/fault | |||
| 1164 | 457.05 | Battery for emergency back up of 4 Hrs. | 1 | Set | |
| 1165 | 458 | Providing and fixing heavy duty floating flange EPDM rubber expansion joint with unit control(tie rod & gusset plate) as per manufactures specifications of standard length complete with all acessories and a working pressure not less than 16 kg/sqcm including rubber gaskets, flanges, nuts, bolts & washers complete as required. | |||
| 1166 | 458.01 | 100 mm dia | 1 | No. | |
| 1167 | 458.02 | 150 mm dia | 1 | No. | |
| 1168 | 458.03 | 200mm dia | 1 | No. | |
| 1169 | 459 | Providing & fixing Puddle Flanged including 40 cm long GI pipe piece welded / threaded with MS plates 450x450x6mm thick with both end screwed / flanged | |||
| 1170 | 459.01 | For 50 mm dia pipe | 1 | Each | |
| 1171 | 459.02 | For 100 mm dia pipe | 1 | Each | |
| 1172 | 459.03 | for 150 mm dia pipe | 1 | Each | |
| 1173 | 460 | Supplying, installing, testing and commissioning of electric motor driven type automatic pressurisation, pump set suitable for automatic operation of terrace down comer and consisting of the following (as per CPWD specifications Part V-1985) for fire fighting and its amendmendts). | |||
| 1174 | 460.01 | Fire pump with stainless steel impeller CI casing, SS shaft shall be horizontal end suction centrifugally type having a capacity of 450 LPM against a total head of 25m so as to ensure a minimum pressure of 3.0 kg/sqm at the highest and farthest out at the specified flow complete with necessary strainer with foot valve in suction side and pressure gauge on the delivery side including bypass arrangement for periodic testing of the working of the pumping set as required. The pump shall be provided with mechamical seals.(Including taking necessary approval of complete fire fighting scheme from local fire authority before and after start of work) {Agency also has to submit characterstic curve of the pumps, model & other technical data for approval before placing the order} | |||
| 1175 | 460.02 | Squirrel cage AC induction motor suitable fot operation of 415 V ,+/-10%, 3 phase 50 HZ, AC supply and of minimum 7.5 HP,1500 RPM for the above pump with flexible coupling as per spwcification and conforming to IS 325-1978 and shall be TEFC type only | |||
| 1176 | 460.03 | Common base plate fabricated from mild steel channel ot castiron type | |||
| 1177 | 460.04 | 1 No. 3 Phase, fully automatic DOL starter, type - II of 10 HP with thermal overload relay, contactor, Timer, Push Buttons and Auto-manual selector switch etc complete as required. | |||
| 1178 | 460.05 | Suitable cement concrete pump foundation with vibration damping arrangememnt with cushy foot mounting as required and having provision of suitable weather protection cover. | 1 | Each | |
| 1179 | 461 | HVAC ITEMS | |||
| 1180 | 461.01 | EQUIPMENTS | |||
| 1181 | 461.02 | VRV SYSTEMS (Variable Refrigerant volume) | |||
| 1182 | 461.03 | Outdoor Units-Heat Pump (R410A) (Heating & Cooling both) | |||
| 1183 | 461.04 | Supply Installation Testing and Commissioning of AIR COOLED and ALL INVERTER BASED VARIABLE REFRIGERANT VOLUME MODULAR TYPE AIR CONDITIONING SYSTEM with R410A suitable for 415 ± 10% , 50 ± 3% Hz. The unit shall consist of indoor units and external condensing units and other accessories as listed below complete in all respects as under: | |||
| 1184 | 461.05 | Outdoor Units-Heat Pump (R410A) (Heating & Cooling both) - EER as per ASHRAE 90.1-2010 | |||
| 1185 | 461.06 | 16 HP Heat Pump type | 2 | No. | |
| 1186 | 461.07 | 10 HP Heat Pump type | 6 | No. | |
| 1187 | 462 | Indoor Units-(Hi wall type) | |||
| 1188 | 462.01 | 1.0 TR | 28 | Nos. | |
| 1189 | 462.02 | 1.3 TR | 8 | Nos. | |
| 1190 | 462.03 | 1.5 TR | 8 | Nos. | |
| 1191 | 462.04 | 2.0 TR | 4 | Nos. | |
| 1192 | 463 | Indoor Units- (Cassette type) | |||
| 1193 | 463.01 | 4.0 TR | 4 | Nos. | |
| 1194 | 464 | Remote Controller | |||
| 1195 | 464.01 | Corded Remotes | 4 | Nos. | |
| 1196 | 464.02 | Cordless Remotes | 48 | Nos. | |
| 1197 | 465 | Central Remote Controller | 1 | No. | |
| 1198 | 465.01 | Important Note for VRV system: | |||
| 1199 | 465.02 | All compressors shall be with inverter technology. VRF system shall be with heating / cooling mode. | |||
| 1200 | 465.03 | The indoor unit shall be with drain pump kit. | |||
| 1201 | 465.04 | Ductable Indoor Units shall be complete with its electrical control panel having switches & starters.(BMS Compatible) | |||
| 1202 | 465.05 | The VRV controller should communicate all the parameters to BMS an Modbus (Bacnet). | |||
| 1203 | 465.06 | The cost must include transportation to site & lifting upto terrace floor in knocked down condition. | |||
| 1204 | 465.07 | Installation including necessary resisto-flex anti-vibrations pads etc. | |||
| 1205 | 466 | Refrigerant Piping | |||
| 1206 | 466.01 | Supply, Installation, commisioning of Interconnecting refrigerant pipe work (including refrigerant joints) with (19mm/13 mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps. Exposed refrigerant copper piping shall be with uv coating. | |||
| 1207 | 466.02 | 34.9 mm O.D. (insulation : 19 / 13 mm) | 100 | RM | |
| 1208 | 466.03 | 28.6 mm O.D. (insulation : 19 / 13 mm) | 100 | RM | |
| 1209 | 466.04 | 22.2 mm O.D. (insulation : 19 / 13 mm) | 80 | RM | |
| 1210 | 466.05 | 19.1 mm O.D. (insulation : 19 / 13 mm) | 80 | RM | |
| 1211 | 466.06 | 15.9 mm O.D. (insulation : 19 / 13 mm) | 200 | RM | |
| 1212 | 466.07 | 12.7 mm O.D. (insulation : 19 / 13 mm) | 150 | RM | |
| 1213 | 466.08 | 9.5 mm O.D. (insulation : 19 / 13 mm) | 200 | RM | |
| 1214 | 466.09 | 6.4 mm O.D. (insulation : 19 / 13 mm) | 120 | RM | |
| 1215 | 467 | Drain Piping | |||
| 1216 | 467.01 | Supply,installation,testing and commissioning of rigid uPVC piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber. Density of uPVC pipe shall not be less than 10 kg / m3. | |||
| 1217 | 467.02 | 40 mm dia | 100 | RM | |
| 1218 | 467.03 | 32 mm dia | 80 | RM | |
| 1219 | 467.04 | 25 mm dia | 150 | RM | |
| 1220 | 468 | Supply, installation, testing and commissioning of G.I. tray for exposed refrigerant copper piping at terrace to be covered with self threaded screw. | 250 | RM | |
| 1221 | 469 | Control & Transmission Wiring | |||
| 1222 | 469.01 | Supply,installation,testing and commissioning of control cum transmission wiring of 2 core x 1.5 sqmm copper in suitable PVC conduits between indoor and out door unit. | 750 | RM | |
| 1223 | 470 | Weather Proof Isolators For outdoor Units | |||
| 1224 | 470.01 | Weather proof Isolator box with 100 mA 4P RCBO of suitable ratings near the outdoor units for isolations. | 8 | Nos. | |
| 1225 | 470.02 | Ventilation Fans | |||
| 1226 | 470.03 | Inline Fans | |||
| 1227 | 470.04 | Supply, installation, testing and commissioning of Inline Fans as shown in drawings and as per equipment schedule .Each fan shall be complete with centrifugal blowers, totally enclosed fan cooled motor. Fan motor shall be suitable for single phase, 220 +/- 6% V, 50 Hz AC supply. Item shall be complete with starter & cabling. | |||
| 1228 | 470.05 | Duty: Toilet Exhaust | |||
| 1229 | 470.06 | Air Quantity : 500 CFM | 4 | Nos. | |
| 1230 | 470.07 | Static Pressure :20 mm wg | |||
| 1231 | 470.08 | Duty: Toilet Exhaust | |||
| 1232 | 470.09 | Air Quantity : 1000 CFM | 2 | Nos. | |
| 1233 | 470.1 | Static Pressure :20 mm wg | |||
| 1234 | 470.11 | Duty: Dirty Corridor Exhaust | |||
| 1235 | 470.12 | Air Quantity : 1500 CFM | 2 | Nos. | |
| 1236 | 470.13 | Static Pressure :20 mm wg | |||
| 1237 | 470.14 | AIR DISTRIBUTION | |||
| 1238 | 470.15 | DUCTING | |||
| 1239 | 471 | GSS DUCTING | |||
| 1240 | 471.01 | Supply, installation, balancing and commissioning of factory/ site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. | |||
| 1241 | 471.02 | Thickness 0.63 mm sheet | 100 | Sqm. | |
| 1242 | 471.03 | Thickness 0.80 mm sheet | 10 | Sqm. | |
| 1243 | 471.04 | Thickness 1.00 mm sheet | 10 | Sqm. | |
| 1244 | 472 | VOLUME CONTROL DAMPERS | |||
| 1245 | 472.01 | Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. | 4 | Sqm. | |
| 1246 | 473 | GRILLES, DIFFUSERS AND DAMPERS | |||
| 1247 | 473.01 | ALUMINIUM GRILLES | |||
| 1248 | 473.02 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills in adjustable double louvered with aluminium volume control dampers as per specifications. | 6 | Sqm. | |
| 1249 | 473.03 | Supplying & fixing of powder coated extruded aluminium Return Air Grills in adjustable double louvered but without volume control dampers complete as required. | 5 | Sqm. | |
| 1250 | 474 | LINEAR GRILLES | |||
| 1251 | 474.01 | Supply, installation,testing and balancing of air linear grilles of powder coated aluminium construction suitable for installation in walls/false ceiling, boxing etc as per specifications and drawings. | 20 | Sqm. | |
| 1252 | 475 | FRESH AIR GRILLES with bird screen | |||
| 1253 | 475.01 | Supply, installation,testing and balancing of extruded aluminium fresh air/ Exhaust air grilles with louvers and bird screen as per specification and drawings. | 2 | Sqm. | |
| 1254 | 476 | GRILLE DAMPERS | |||
| 1255 | 476.01 | Supply, installation and balancing of aluminium construction volume control dampers for linear grills. | 10 | Sqm. | |
| 1256 | 476.02 | ELECTRICAL | |||
| 1257 | 476.03 | AIR- CONDITIONING PANELS | |||
| 1258 | 477 | Distribution Panels | |||
| 1259 | 477.01 | Supply, installation, testing and commissioning of following M.V. cubicle type totally enclosed, wall mounted/Free standing type, powder coated, dust, damp and vermin proof, indoor type Distribution Board/Panel complete with busbars, M.V. danger notice plate, interconnections with suitable capacity aluminium leads/solid aluminium strips/rods, connection of incoming and outgoing cables with thimbles, and having following incoming and outgoing switchgears complete as per techinical specification and as required. | |||
| 1260 | 477.02 | NOTE | |||
| 1261 | 477.03 | i. All MCCBs shall have Ics=Icu=100% | |||
| 1262 | 477.04 | ii. 100 VA transformer 220v/24v AC for control wiring with 10 no.s 6A SP MCB 10 KA in all AHU panel is also in the scope of supply | |||
| 1263 | 477.05 | iii. All starters shall be provided with digital ampere meter with suitable CTs, thermal overload relay, inbuilt/separate single phase preventer, contactors, Timers, spare NO-NC contacts, Push Buttons ON, OFF, TRIP indication (LED Type) and potential free Contact & relays for interlocking to FDA etc. complete as required. | |||
| 1264 | 477.06 | iv. All indication Lamps will be LED Type. | |||
| 1265 | 477.07 | v. All incomer and outgoing shall have extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB should have spreader links & phase barriers. | |||
| 1266 | 477.08 | AHP - I | |||
| 1267 | 477.09 | INCOMER : | |||
| 1268 | 477.1 | 1 nos. 160 Amp 415 volts, 35 KA FP MCCB with thermal magnetic release having variable current settings of O/L, S/C ,E/F protection. | |||
| 1269 | 477.11 | R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP Indication. | |||
| 1270 | 477.12 | 1 No. 0 to 500 V Digital voltmeter with selector switch. | |||
| 1271 | 477.13 | Digital ammeter with selector switch with one set Suitable C.Ts. | |||
| 1272 | 477.14 | Bus Bar | |||
| 1273 | 477.15 | 300 A TPN Aluminium bus bar 415V , 50 Hz. | |||
| 1274 | 477.16 | OUTGOINGS : | |||
| 1275 | 477.17 | 6 Set- 63 Amp 415 volts, 35 KA FP MCCB with thermal magnetic release having variable current settings of O/L, S/C protection. | |||
| 1276 | 477.18 | 2 set - 32 A, 415 volts, 35 KA FP MCCB with thermal magnetic release having variable current settings of O/L, S/C protection. | |||
| 1277 | 477.19 | 4 set - 16 A, 415 volts, 35 KA C- Curve, Four Pole, Miniature Circuit Breaker. | |||
| 1278 | 477.2 | Complete panel as above | 1 | Panel | |
| 1279 | 478 | CABLING | |||
| 1280 | 478.01 | Supplying, laying, effecting proper connections, testing & commissioning of following size of 1.1 kv XLPE insulated aluminium conducting armoured cables as per IS 7096 laid underground/cable tray/on surface of wall/hume pipe etc. & termination with brass compression glands as required. | |||
| 1281 | 478.02 | 3.5C x 120 sq.mm cable | 80 | Mtr | |
| 1282 | 478.03 | 4 C X 10 sq. mm. Cable | 50 | Mtr | |
| 1283 | 478.04 | 3C X 6 sq. mm. Cable | 50 | Mtr | |
| 1284 | 478.05 | 3C X 4 sq. mm. Cable | 150 | Mtr | |
| 1285 | 479 | CABLE TRAYS | |||
| 1286 | 479.01 | Supply & installation of following sizes of perforated MS cable trays including horizontal & vertical bends, reducers, tees, cross members and other accessories as required and duly supported from the ceiling/wall/floor with MS suspenders/supports and including painting etc. as required | |||
| 1287 | 479.02 | 150 mm widthx50 mm deep x1.6 mmthickness | 50 | Mtr | |
| 1288 | 480 | EARTHING | |||
| 1289 | 480.01 | Providing & fixing GI earth strip 40mm x 6mm on surface or in recess for earth connections etc. as required | 50 | Mtr | |
| 1290 | 480.02 | Providing and fixing GI earth strip on walls/ trenches complete as per specifications and as required. | |||
| 1291 | 480.03 | 25mm x 5mm | 50 | Mtr | |
| 1292 | 481 | Add cost index @12.75% for civil work on DSR items amounting to Rs. 106345437.25 | 1.06345e+08 | each | |
| 1293 | 482 | Less @9.5% for civil work on DSR items amounting to Rs. 106345437.25 | 1.06345e+08 | each | |
| 1294 | 483 | Add cost index @12.75% for Fire Fighting work on DSR items amounting to Rs. 102496.65 | 102497 | each | |
| 1295 | 484 | Less @9.5% forFire Fighting work on DSR items amounting to Rs. 102496.65 | 102497 | each | |
| 1296 | 485 | Add cost index @12.75% for HVAC work on DSR items amounting to Rs. 210200 | 210200 | each | |
| 1297 | 486 | Less @9.5% for HVAC work on DSR items amounting to Rs. 210200 | 210200 | each |