Providing Of Tech And Otm Accn ( Ph-Iii ) For Bh At Tezpur Under Ge ( S ) Tezpur

Tender Notice

21859155
Providing Of Tech And Otm Accn ( Ph-Iii ) For Bh At Tezpur Under Ge ( S ) Tezpur
Indian
Assam
30-06-2020
27-07-2020
28-07-2020

Tender Details

Providing Of Tech And Otm Accn ( Ph-Iii ) For Bh At Tezpur Under Ge ( S ) Tezpur

Corrigendum Details

Sr No CorrigendumDate Description Submission Date
1 05-02-2020 Date Corrigendum 4 05-03-2020
2 24-02-2020 Date Corrigendum 5 06-04-2020
3 17-03-2020 Date Corrigendum - 6 04-05-2020
4 13-04-2020 Date Corrigendem7 02-06-2020
5 02-06-2020 TD Drg - 1 22-06-2020
6 30-06-2020 Struc drg mortuary 27-07-2020

Key Value

Document Fees
INR 3000 /-
EMD
INR 1500000.00 /-
Tender Value
INR 79 Crore /-

Attachment

FileName File Description File Size
98706_TEZ_PDF_SEP_2019.rar Tender Document-Tender 98706-TEZ(S)-SZ-E8 4300.12
Tendernotice_1.pdf Tender Document-NIT 125.51
BOQ_317683.xls Tender Document-BOQ 98706-TEZ(S)-SZ-E8 674.50
Sch_of_Finishes.rar Tender Document-Sch of Finishes 4354.17
Struc.rar Tender Document-Structural Drawings 21890.40
Arch_pdf.rar Tender Document-Archtectural Drawings 27750.89
74F7C56E-A7AB-4DB5-9D97-33462926F8ED.html Tender Notice-Tender Notice 0
Services.rar Tender Document-Services Drawings 15743.88

Other Information

Attachments
Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

BOQ Items

NAME OF WORK : PROVN OF TECH & OTM ACCN (PH-III) FOR BH AT TEZPUR UNDER GE (S) TEZPUR
Sl. No. Item Description Item Code / Make Qty. Units
1 1 BUILDING AND STRUCTURE (Sch 'A' PART-I)
2 1.01 Lump sum price worked out by the Contractor for “BUILDING AND STRUCTURE” as listed in Schedule ‘A’ Part-I. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 33,52,00,000 inserted by the MES in Schedule ‘A’ Part-I. 1 LUMP SUM
3 2 EXCAVATION & EARTHWORK FOR SITE CLEARANCE AND AREA DEVELOPMENT, OTHER SCHEDULES (EXCEPT SCH 'A' PART-I) (Sch 'A' PART-II)
4 2.01 Lump sum price worked out by the Contractor for “EXCAVATION & EARTHWORK FOR SITE CLEARANCE AND AREA DEVELOPMENT, OTHER SCHEDULES (EXCEPT SCH 'A' PART-I)” as listed in Schedule ‘A’ Part-II. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 19,15,498.50 inserted by the MES in Schedule ‘A’ Part-II. 1 LUMP SUM
5 3 INTERNAL WATER SUPPLY (Sch 'A' PART-III)
6 3.01 Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY (Sch 'A' PART-III)” as listed in Schedule ‘A’ Part-III. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 2,74,237.80 inserted by the MES in Schedule ‘A’ Part-III. 1 LUMP SUM
7 4 INTERNAL WATER SUPPLY (Sch 'A' Part-III (A) (MISC))
8 4.01 S&F Chlorinated Polyvinyl Chloride (CPVC) pipes of size 20 mm outer dia having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including jointing of pipes and fittings with one step CPVC solvent cement fixed on wall / ceiling or laying in floors / concealed in walls etc complete all as specified and as directed. 1055 RM
9 4.02 S&F Chlorinated Polyvinyl Chloride (CPVC) pipes of size 25 mm outer dia having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including jointing of pipes and fittings with one step CPVC solvent cement fixed on wall / ceiling or laying in floors / concealed in walls etc complete all as specified and as directed. 525 RM
10 4.03 S&F Chlorinated Polyvinyl Chloride (CPVC) pipes of size 40 mm outer dia having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including jointing of pipes and fittings with one step CPVC solvent cement fixed on wall / ceiling or laying in floors / concealed in walls etc complete all as specified and as directed. 500 RM
11 4.04 S&F Chlorinated Polyvinyl Chloride (CPVC) pipes of size 50 mm outer dia having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including jointing of pipes and fittings with one step CPVC solvent cement fixed on wall / ceiling or laying in floors / concealed in walls etc complete all as specified and as directed. 730 RM
12 4.05 NOTE FOR SERIAL ITEM No. 4.01 TO 4.04 : CPVC pipes from service tanks to toilets at outside surface of building shall be fixed on surface of wall and inside the building shall be concealed.
13 4.06 S&F of shower rose cast copper alloy chromium plated 125 mm size with swivel joint for fixing to 15 mm bore GI pipe or union including GI pipe 15 mm, 300 mm long with each shower complete all as specified and as directed. 105 EACH
14 4.07 S&F of CP brass wall mixer hot and cold water screwed down for iron pipe of size 15 mm dia with 115 mm long bend pipe for connecting to overhead shower with bush and piston diverter fitting with aereter complete all as specified and as directed.\nMake : ESSCO model marvel type MQT-517B or equivalent. 105 EACH
15 4.08 S&F of brass non return valve screwed down for iron / CPVC pipe of size 15 mm dia medium weight complete all as specified and as directed.\nNote :-\n1. Pillar cocks for wash hand basins shall be part of Lumpsum of building.\n2. As per drawing No. ADG/2016/EM/012 Sheet No. 49/54 to 51/40 the GI pipe 80 mm as outlet to service tank has been shown as horizontal on terrace and vertical on wall and further branches of CPVC 50 mm has been shown for each floor. However, for effective distribution of water supply to each floor the GI pipe 80 mm shall be provided horizontal on terrace only and further CPVC pipe of 50 mm shall be provided vertically on wall from GI pipe 80 mm on terrace separate for each floor. Gate valves 40 mm to be provided on CPVC pipe 50 mm to be provided on terrace for controlling water supply of each floor.\n 105 EACH
16 4.09 S&F of Gun Metal Gate Valve of size 80 mm dia with iron wheel head, screwed both ends for iron pipes or for unions fixed complete all as specified and as directed. 10 EACH
17 4.1 Sub total
18 5 INTERNAL ELECTRIFICATION (Sch 'A' PART-IV)
19 5.01 Lump sum price worked out by the Contractor for “(INTERNAL ELECTRIFICATION)” as listed in Schedule ‘A’ Part-IV. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 26,47,904.20 inserted by the MES in Schedule ‘A’ Part-IV.\n 1 LUMP SUM
20 6 INTERNAL ELECTRIFICATION (Sch 'A' PART-IV(A) (MISC))
21 6.01 M&L for concealed point wiring with 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including stove enameled steel conduit of adequate size with all fittings and accessories including one run of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor to common earth and earth dolly complete all as specified and as directed for the following :-\n Item continued as 6.02 to 6.05\n\nNOTE : Modular metal flush box & cover plate will be measured and paid separately.
22 6.02 (a) One light / fan point controlled by one , one way switch. 2998 PER POINT
23 6.03 (b) One bell point controlled by one bell push. 17 PER POINT
24 6.04 (c) One socket outlet point 6 A on independent board. 1734 PER POINT
25 6.05 (d) One socket outlet point 6 A on same board. 200 PER POINT
26 6.06 M&L for concealed point wiring with 4.0 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including stove enameled steel conduit of adequate size with all fittings and accessories including one run of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor of size 4.0 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for one 16 Amp socket outlet on independent board complete all as specified and as directed.\n\nNOTE : Modular metal flush box and cover plate will be measured and paid separately. 710 PER POINT
27 6.07 S&F of Modular Metal Flush Box, 8 module complete all as specified and as directed. 300 EACH
28 6.08 M&L for concealed flame proof point wiring with 2.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories including PTFE (Teaflon) type sealing proof joint complete including FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 2.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for one light points controlled by one, one way flame proof switch complete all as specified and as directed. 8 PER POINT
29 6.09 S&F of switch flame proof rotary type with termination box in LM6, 16 Amp, Single Pole, 250 V complete all as specified and as directed. 8 EACH
30 6.1 M&L for concealed Sub main wiring with four run of 16.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 16 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB complete all as specified and as directed. 875 RM
31 6.11 M&L for concealed Sub main wiring with four run of 10.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 10 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB complete all as specified and as directed. 1050 RM
32 6.12 M&L for concealed Sub main wiring with four run of 6.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 6.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB and for AC complete all as specified and as directed. 140 RM
33 6.13 M&L for concealed Sub main wiring with four run of 4.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 4.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB complete all as specified and as directed. 455 RM
34 6.14 M&L for concealed Sub main wiring with two run of 6.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 6.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB and for AC complete all as specified and as directed. 100 RM
35 6.15 M&L for concealed Sub main wiring with two run of 4.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi stranded copper conductor single core cable drawn through and including rigid stove enameled steel ERW conduit of adequate size with all fittings and accessories concealed in walls, floors and ceilings complete including two runs of FRLSH PVC insulated and unsheathed single core multi stranded copper conductor cable of size 4.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for main DB to sub DB complete all as specified and as directed. 100 RM
36 6.16 S&F of MCB, DB, TPN, 4-ways (8 + 12 WAYS), DOUBLE DOOR, Horizontal type, IP-43, Ik-09 with metal door, rated bus bars, earth bar, neutral links complete including blanking plates as required and fixed flush to wall / other surface complete all as specified and as directed. 19 EACH
37 6.17 S&F of MCB, DB, TPN, 8-ways (8 + 24 WAYS), DOUBLE DOOR, Horizontal type, IP-43, Ik-09 with metal door, rated bus bars, earth bar, neutral links complete including blanking plates as required and fixed flush to wall / other surface complete all as specified and as directed. 54 EACH
38 6.18 S&F of MCB, DB, SPN, 8-ways, DOUBLE DOOR, IP-43, Ik-09 with metal door, rated bus bars, earth bar, neutral links complete including blanking plates as required and fixed flush to wall / other surface complete all as specified and as directed. 5 EACH
39 6.19 S&F of RCBO 4 pole, 300 mA 63 A, 10 KA, for Earth leakage, overload and short circuit protection complete all as specified and as directed. 24 EACH
40 6.2 S&F of RCBO 4 pole, 300 mA 32 A, 10 KA, for Earth leakage, overload and short circuit protection complete all as specified and as directed. 30 EACH
41 6.21 S&F of RCBO 4 pole, 300 mA 20 A, 10 KA, for Earth leakage, overload and short circuit protection complete all as specified and as directed. 7 EACH
42 6.22 S&F of RCBO 4 pole, 300 mA 16 A, 10 KA, for Earth leakage, overload and short circuit protection complete all as specified and as directed. 12 EACH
43 6.23 S&F MCB, SPN rupturing capacity 10 kA, ‘C’ curve, 06-32 Amp, ISI marked complete all as specified and as directed. 5 EACH
44 6.24 S&F of MCB, rupturing capacity 10 kA, ‘C’ curve, Single Pole, 6 to 32 Amp complete all as specified and as directed. 1060 EACH
45 6.25 Supply, installation, testing and commissioning of Heavy Duty exhaust fan 300 mm sweep, 1400 RPM, Air Delivery not less than 1900 CMH, single phase, 240 Volts, AC, 50 Hz and connecting up complete including louvers and provision of cable 3-core of size 0.75 Sqmm from ceiling rose to fan including writing of MES Number 2.0 cm height with synthetic enamel paint including making of suitable sized hole in the wall for fixing of the exhaust fan and making good the disturbed surfaces (if any) complete all as specified and as directed. 130 EACH
46 6.26 Supply, installation, testing and commissioning of Heavy Duty exhaust fan 380 mm sweep, 1400 RPM, Air Delivery not less than 4000 CMH, single phase, 240 Volts, AC, 50 Hz and connecting up complete including louvers and provision of cable 3-core of size 0.75 Sqmm from ceiling rose to fan including writing of MES Number 2.0 cm height with synthetic enamel paint including making of suitable sized hole in the wall for fixing of the exhaust fan and making good the disturbed surfaces (if any) complete all as specified and as directed. 20 EACH
47 6.27 Supply, installation, testing and commissioning of exhaust fan with automatic back shutter louvers 300/305 mm sweep, FLAME PROOF type and 1440 RPM or more, Air Delivery not less than 1120 CMH, single phase, 240 Volts, AC, 50 Hz and connecting up complete including louvers and provision of cable 3-core of size 0.75 Sqmm from ceiling rose to fan including writing of MES Number 2.0 cm height with synthetic enamel paint including making of suitable sized hole in the wall for fixing of the exhaust fan and making good the disturbed surfaces (if any) complete all as specified and as directed. 2 EACH
48 6.28 S&F, IP >=20, Class-I, LED light fitting 1 x 20 W (4 FT), CRI >=80, CT>=5700 K, wall / surface mounted, integrated type, constructed of fire retardant engineering grade extruded plastic and decorative end caps with integrated high efficiency electronic driver & surge suppressor of 2 KV or more, luminaire efficacy > 95 lumens/Watt, power factor >= 0.90, operating range - 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete including 01 No. 20 W (4 FT) LED lamp or strip LEDs as per OEM with all necessary internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed. 1666 EACH
49 6.29 S&F, IP >=20, Class-I, LED light fitting 1 x 40 W (4 FT), CRI >=80, CT>=5700 K, wall / surface mounted, integrated type, constructed of fire retardant engineering grade extruded plastic and decorative end caps with integrated high efficiency electronic driver & surge suppressor of 2 KV or more, luminaire efficacy > 95 lumens/Watt, power factor >= 0.90, operating range - 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete including 01 No. 40 W (4 FT) LED lamp or strip LEDs as per OEM with all necessary internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed. 25 EACH
50 6.3 S&F, IP >=20, Class-I, LED light fitting 1 x 10 W (2 FT), CRI >=80, CT>=5700 K, wall / surface mounted, integrated type, constructed of fire retardant engineering grade extruded plastic and decorative end caps with integrated high efficiency electronic driver & surge suppressor of 2 KV or more, luminaire efficacy > 95 lumens/Watt, power factor >= 0.90, operating range - 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete including 01 No. 100 W (2 FT) LED lamp or strip LEDs as per OEM with all necessary internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed. 38 EACH
51 6.31 S&F energy saving & environment friendly long life 25 W, CT >= 5700 K, LED building security light made up of pressure die-cast aluminium housing with acrylic cover as diffuser with IP 66 protection and impact resistance not less tha IK-07 complete with integrated type, with high efficiency electronic driver, surge suppressor of 5 KV or more and high brightness LEDs, luminaire efficacy > 110 lumens / Watt, power factor >= 0.90 operating range – 140 to 270 V, 50 Hz complete including bracket made out of 40 mm dia light grade GI pipe duly fixed with MS clamps, nuts, bolts etc. including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed. 42 EACH
52 6.32 S&F, IP 65, Class-I, energy saving, environment friendly, surface mounted, 10 W or next higher rating decorative Oval Bulk-Head edge-lit LED luminaire comprising of high brightness LEDs as light source with CRI >=80, CT>=6000 K integrated type with luminaire efficacy >95 lumens/Watt, Power Factor >= 0.90, operating range – 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete with all accessories internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed. 6 EACH
53 6.33 S&F, IP 65, Class-I, energy saving, environment friendly, surface mounted, 10 W or next higher rating decorative Oval, FLAME PROOF Bulk-Head edge-lit LED luminaire comprising of high brightness LEDs as light source with CRI >=80, CT>=6000 K integrated type with luminaire efficacy >95 lumens/Watt, Power Factor >= 0.90, operating range – 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete with all accessories internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed. 6 EACH
54 6.34 S&F of Bed side Lamp fitting with suitable metal shed and lamp holder and LED lamp 10 W complete all as specified and as directed. 461 EACH
55 6.35 S&F, IP >= 20, Class-I, ceiling mounted, LED square shape slim ceiling light fitting 36 W or next higher rating CRI >=80, CT>=5700 K, approx. dimensions 600 x 600 mm, integrated type with high efficiency electronic driver, surge suppressor of 2 KV or more and high brightness LEDs, luminaire efficacy >95 lumens/Watt, Power Factor >= 0.90, operating range – 140 to 270 V, 50 Hz fixed with suitable fixing arrangement complete with all accessories internally pre-wired and including connecting up with and including twin / three core twisted flexible copper conductor cable of suitable size complete all as specified and as directed. 4 EACH
56 6.36 S&F Single pole and neutral Sheet Metal Enclosure (industrial socket) with a two pin and earth plug socket for AC complete with one single pole MCB 16 to 20 Amp, 240 V complete all as specified and as directed. 4 EACH
57 6.37 Supply, installation, testing and commissioning indoor type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following for Ground Floor E WING complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 36 KA of rating 320 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-400 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 02 Nos. (First Floor, Second Floor)\n(b) MCCB 4 Pole, 415 V, 25 KA of rating 63 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 04 Nos. (Ground Floor, Third Floor, Lift 1 & 2).\n(c) Space for spare MCCB 4 Pole 63A A– 02 Nos. 1 EACH
58 6.38 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following Ground Floor D WING & C WING complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 36KA of rating 320 A with thermal magnetic release, adjustable short circuit and adjustable overload setting– 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-400 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 03 Nos. (First Floor, Second Floor & Third Floor)\n(b) MCCB 4 Pole, 415 V, 25 KA of rating 63 A with thermal magnetic release, adjustable short circuit and adjustable overload setting– 01 No. (Ground Floor).\n(c) Space for spare MCCB 4 Pole 100A A– 02 Nos.\n 2 EACH
59 6.39 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following Ground Floor A WING complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 35 KA of rating 250 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-300 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 03 Nos. (Ground Floor, First Floor & Second Floor)\n(b) MCCB 4 Pole, 415 V, 25 KA of rating 63 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 02 No. (Lift 1 and 2).\n(c) Space for spare MCCB 4 Pole 100A A– 02 Nos.\n 1 EACH
60 6.4 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following Ground Floor B WING complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 35 KA of rating 250 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-300 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting– 02 Nos. (Ground Floor)\n(b) MCCB 4 Pole, 415 V, 25 KA of rating 63 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 02 Nos. (First Floor, Second Floor).\n(c) Space for spare MCCB 4 Pole 100A A– 02 Nos.\n 1 EACH
61 6.41 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following for C WING, SECOND FLOOR, C WING THIRD FLOOR, D WING FIRST FLOOR, D WING SECOND FLOOR, D WING THIRD FLOOR, B WING FIRST FLOOR, B WING SECOND FLOOR complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-100 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCB TPN, 10 KA, 'C' Curve, 415 V, 63 A – 02 Nos. \n(b) MCB TPN, 10 KA, 'C' Curve, 415 V, 6- 32 A – 02 Nos. \n(c) Space for spare MCB TPN– 02 Nos.\n 7 EACH
62 6.42 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following for A WING, GROUND FLOOR, A WING FIRST FLOOR, E WING FIRST FLOOR complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-100 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCB TPN, 10 KA, 'C' Curve, 415 V, 63 A – 01 No. \n(b) MCB TPN, 10 KA, 'C' Curve, 415 V, 32 A – 03 Nos. \n(c) Space for spare MCB TPN– 02 Nos.\n 3 EACH
63 6.43 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following for C WING, GROUND FLOOR, D WING GROUND FLOOR complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-100 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCB TPN, 415 V, 6-32 A,10 KA – 04 Nos. \n(b) Space for spare MCB TPN– 02 Nos.\n 2 EACH
64 6.44 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following for A WING, SECOND FLOOR, C WING FIRST FLOOR complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-100 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCB TPN, 415 V, 63 A, 10 KA – 02 Nos. \n(b) MCB TPN, 415 V, 6-32 A, 10 KA – 02 Nos. \n(c) Space for spare MCB TPN– 01 No.\n 2 EACH
65 6.45 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following for B WING, GROUND FLOOR complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 63 A with thermal magnetic release, adjustable short circuit and adjustable overload setting– 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-100 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCB TPN, 10 KA, 'C' Curve, 6-32 A, 415 V – 04 Nos. \n(b) Space for spare MCB TPN– 02 Nos.\n 1 EACH
66 6.46 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following for E WING, SECOND FLOOR complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-100 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCB TPN, 10 KA, 'C' Curve, 6-32 A, 415 V – 01 No. \n(b) MCB TPN, 10 KA, 415 V, 32 A – 03 Nos. \n(c) Space for spare MCB TPN– 02 Nos\n 1 EACH
67 6.47 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following for E WING, GROUND FLOOR complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 100 A with thermal magnetic release, adjustable short circuit and adjustable overload setting – 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-100 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCB TPN, 10 KA, 'C' Curve, 415 V, 63 A – 01 No. \n(b) MCB TPN, 415 V, 6-32 A – 03 Nos. \n(c) Space for spare MCB TPN– 02 Nos.\n 1 EACH
68 6.48 Supply, installation, testing and commissioning indoor cubicle type LT panel, mounted on floor on suitable platform CPRI approved factory made, totally enclosed, dust and vermin proof with locking arrangement made of MS angle iron frame work and CRCA Sheet of 2 mm thick as per IS 5039 duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 V, 50 Hz, 3 phase 4 wire system and shall be complete with copper bus bar of capacity 125% of incoming switch gear fixed on porcelain base with suitable size of PVC copper strip, thimbles glands and shall be complete all as required and directed with the following accessories including PCC foundation and pillar. The panel will comprises of the following for E WING, THIRD FLOOR complete all as specified and as directed :-\nINCOMING :-\n(a) MCCB 4 Pole, 415 V, 25 KA of rating 63 A with thermal magnetic release, adjustable short circuit and adjustable overload setting– 01 No. (Incoming).\n(b) Digital Voltmeter 0-500 V with selector switch – 01 No.\n(c) Digital Ammeter 0-100 A with CTs and selector switch – 01 No.\n(d) LED type indicator lamp (RYB) – 01 Set.\nOUTGOING :-\n(a) MCB TPN, 10 KA, 6-32 A, 'C' Curve, ISI marked, 415 V, 32 A – 04 Nos. \n(b) Space for spare MCB TPN– 02 Nos.\n 1 EACH
69 6.49 NOTE FOR ITEM Nos. 6.37 to 6.48 here-in-before :-\n1. Design / Drawing / BOM of the panel board showing the dimensions including accessories is to be obtained from panel board manufacturer / supplier and is to be got approved from GE before placing final order to the manufacturer / supplier.\n2. Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates.\n
70 6.5 Supply, laying, testing and commissioning cable XLPE insulated screened PVC bedded, unarmoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 V grade of size 35 Sqmm 3.5 core (Main LT Panel to each Floor panel for four lifts). 400 RM
71 6.51 S&F of ceiling fan 1200 mm sweep BEE 5 star rated model ES-50 premium make : Havells or equivalent in Usha / Bajaj / Crompton Greaves and suspended from fan hook including electrically connecting with three core PVC insulated of 0.75 Sqmm copper conductor cable from ceiling rose to ceiling fan including writing of MES Number 2.0 cm height with synthetic enamel paint complete all as specified and as directed. 606 EACH
72 6.52 Sub total
73 7 EXTERNAL WATER SUPPLY (Sch 'A' Part-V)
74 7.01 Lump sum price worked out by the Contractor for “(EXTERNAL WATER SUPPLY)” as listed in Schedule ‘A’ Part-V. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 4,57,777.60 inserted by the MES in Schedule ‘A’ Part-V. 1 LUMP SUM
75 8 EXTERNAL WATER SUPPLY (Sch 'A' Part-V(A) (MISC))
76 8.01 Supply, jointing, testing and laying in trenches DI pipes with spigot and socket ends suitable for push on rubber joint centrifugally cast class K-7 for drinking water supply, inner side cement mortar and outer side black bitumen coating and any length of size 150 mm bore pipe and including push on rubber (EPDM) ring with ISI marked complete all as specified and as directed. 100 RM
77 8.02 Supply, jointing, testing and laying in trenches DI pipes with spigot and socket ends suitable for push on rubber joint centrifugally cast class K-7 for drinking water supply, inner side cement mortar and outer side black bitumen coating and any length of size 100 mm bore pipe and including push on rubber ((EPDM)) ring with ISI marked complete all as specified and as directed. 560 RM
78 8.03 M&L for DI specials / fittings confirming to IS:9523/2000 of size upto 150 mm bore suitable for DI pipes class K-12, PN-10, with inside cement mortar lining and black bitumen external coating such as bends (any type radius & angle) tapers, tee pieces, single branches, Y-junctions, double junctions, connecting pieces, nuts & bolts, gaskets, flanges including push on rubber joints etc complete all as specified and as directed. 600 KG
79 8.04 Construction of brick masonry chamber with sub class ‘B’ brick in CM (1:6) with PCC (1:4:8) type D-2 (using 40 mm graded stone aggregate) for foundation of internal dimension of 100cm x 100cm x 100cm including 15 mm thick plastering in CM (1:4) inside the chamber and on the external portion exposed above ground level, including 3 mm thick MS cover welded around with MS flat iron of size 40x6 mm including MS angle iron frame of size 40x40x6mm with locking arrangement including painting with two coats of synthetic enamel paint over a coat of red oxide primer including necessary earth work in soft / loose soil well ramming of soil around the constructed chamber complete all as specified and as directed. 3 EACH JOB
80 8.05 Construction of brick masonry chamber with sub class ‘B’ brick in CM (1:6) with PCC (1:4:8) type D-2 (using 40 mm graded stone aggregate) for foundation of internal dimension of 600mm x 600mm x 600mm including 15 mm thick plastering in CM (1:4) inside the chamber and on the external portion exposed above ground level, including 3 mm thick MS cover welded around with MS flat iron of size 40x6 mm including MS angle iron frame of size 40x40x6mm with locking arrangement including painting with two coats of synthetic enamel paint over a coat of red oxide primer including necessary earth work in soft / loose soil well ramming of soil around the constructed chamber complete all as specified and as directed. 1 EACH JOB
81 8.06 S&F foot valve 100 mm bore, conforming to IS-4038 with 3mm thick rubber gasket with necessary bolts, nuts, washers, etc of suitable size complete all as specified and as directed. 2 EACH
82 8.07 Supply, installation, testing and commissioning centrifugal pump set 1200 LPM discharge capacity working at 35 mtrs head (Head range 30 to 40 mtr and discharge range as per manufacturer design), 2900 RPM, suitable for drinking water and coupled with 3 phase, 50 c/s, 415 V electric motor of suitable capacity including suction pipe, suitable capacity star delta starter with over load, dry run and single phase protection etc (Starter to be mounted on proposed water supply panel board considered separately) and PCC foundation with MS base frame as per manufacturer design including connecting up with suction and delivery main and suitable size of copper conductor etc, cable from starter to motor complete all as specified and as per manufacturer’s specification. 2 EACH
83 8.08 Sub total
84 9 EXTERNAL ELECTRIFICATION (Sch 'A' PART-VI)
85 9.01 Lump sum price worked out by the Contractor for “(EXTERNAL ELECTRIFICATION)” as listed in Schedule ‘A’ Part-VI. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 19,78,971.60 inserted by the MES in Schedule ‘A’ Part-VI. 1 LUMP SUM
86 10 EXTERNAL ELECTRIFICATION (Sch 'A' PART-VI(A) (MISC))
87 10.01 Supply, installation, testing and commissioning of indoor type VCB panel board 11 KV 630 A, 3-Phase, 50 Hz AC supply system made of sheet metal duly painted (powder coated) totally enclosed free standing, floor mounted type with track mounted VCB horizontal / vertical isolation and horizontal draw out type, cubical should have not less than IP-43 Class degree of protection, copper bus bar, pre-wired for controller and accessories using copper conductor, suitable for side extension in both directions and provision for cable entry / outgoing system complete and comprising of the following :-\n\nINCOMING FEEDER PANEL = 01 No.\nOUTGOING TRANSFORMER FEEDER PANEL = 04 Nos.\n\n(A) Each Incoming Feeder should comprise of :-\nHT Vacuum Circuit Breaker Switchgear, Indoor type, dust and vermin proof, motorized as well as manually charged fully interlocked, horizontal draw out type, floor mounted, normal / highest working voltage – 11/12 KV, normal current – 630 A, 3-Phase, 50 HZ AC supply, Breaking capacity – 13.1 KA, Making capacity – 33 KA (p), insulation level KV(rms) / KV(p) -25/75, closing voltage – 110/24 V DC complete as per IS : 3427 & IS : 118 with all standards accessories and metering equipment and comprising the following :-\n(i) HT CT 100/50/5-5 (Dual Core), Class 5 P 10 for protection and Class 1.0 for metering, 15 VA burden, short time rating – 13.1 KA for 1 sec, having IS : 2705 marking, suitable for 12 KV – 03 Nos.\n\n Item Continued as 10.02\n 1 EACH JOB
88 10.02 (ii) HT PT (1x3 Phase), draw out type, resin cast, dry type, having rating 11 KV / 110 V Class-1, with VA burden 15 having IS : 3156 marking – 01 No. \n(iii) Microprocessor based combined Over Current and Earth fault relays.\n(iv) Over and under voltage relays.\n(v) Tripping relays\n(vi) Digital power factor meter.\n(vii) Digital Voltmeter with selector switch 0-15 V.\n(viii) Digital Ammeter with selector switch.\n(ix) Digital frequency meter.\n(x) LED indicator lamps for RYB, phase healthy, Breaker ON / OFF, trip circuit healthy, spring charged.\n(xi) Breaker Control switch.\n(xii) Push buttons for check Trip Circuit healthy and Emergency trip.\n(xiii) Switch for closing / tripping of VCB.\n(xiv) Alarm annunciator for DC supply fail / trip.\n(xv) Power pack of suitable capacity with I/P voltage 220 V AC & O/P voltage 110 V DC.\n(xvi) Other standard accessories as specified by OEM.\n\n(B) Each Outgoing Feeder Panel should comprise of :-\n\nHT Vacuum Circuit Breaker Switchgear, indoor type, dust and vermin proof, motorized as well as manually charged fully interlocked, horizontal draw out type floor mounted normal / highest working voltage – 11/12 KV, \n Item Continued as 10.03\n
89 10.03 normal current – 630 A, 3-Ph, 50 Hz AC supply, Breaking Capacity – 13.1 KA, making capacity – 33 KA (p), Insulation level KV(rms) / KV(p) – 28/75, Closing Voltage – 110/24 V DC complete as per IS : 3427 & IS : 118 with all standard accessories and metering equipment and comprising the following :-\n(i) HT CT (Dual Core), Class 5 P 10 for protection and Class 1.0 for metering, 15 VA burden, short time rating – 13.1 KA for 1 sec, having IS : 2705 marking, suitable for 12 KV – 03 Nos.\nNOTE : The HT CT Ratios shall be as follows :-\n\n(a) 50/25/5-5 for 630 KVA, 11/0.433 KV Distribution Transformer each.\n(b) 20/10/5-5 for 200 KVA & 100 KVA, 11/0.433 KV Distribution Transformer each.\n\n(ii) Microprocessor based combined Over Current and Earth fault relays.\n(iii) Over and Under Voltage relays.\n(iv) Tripping relays.\n(v) Digital maximum demand and KWH meter.\n(vi) Digital power factor meter.\n(vii) Digital Voltmeter with selector switch 0-15 KV.\n(viii) Digital Ammeter with selector switch.\n(ix) Digital frequency meter.\n(x) LED indicator lamps for RYB, phase healthy, Breaker ON / OFF, trip circuit healthy, spring charged.\n\n Item Continued as 10.04\n
90 10.04 (xi) Breaker Control switch.\n(xii) Push buttons for check Trip Circuit healthy and Emergency trip.\n(xiii) Switch for closing / tripping of VCB.\n(xiv) Alarm annunciator for DC supply fail / trip.\n(xv) Power pack of suitable capacity with I/P voltage 220 V AC & O/P voltage 110 V DC.\n(xvi) Other standard accessories as specified by OEM.\n\nNOTE :-\n1. Design / Drawing / BOM of the HT VCB Panel Board showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Necessary PCC foundation / plinth, cable ducts, sand cushioning etc. shall be as per the recommendations of OEM and cost of the same is deemed to be included in the quoted rates.\n3. The cost of Primary / Secondary Injection Tests, Calibration etc. during the complete defect liability period as and when required is deemed to be included in the quoted rates.\n4. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.\n5. The quoted rate shall be deemed to be inclusive of the factory inspection to be carried out by auth rep of Accepting Officer before dispatch and Pre-commissioning Inspection by SEI on ground.\n
91 10.05 Supply, installation, testing and commissioning of transformer platform / plinth mounted of capacity 630 KVA step down, BEE 5 Star rated (Energy Efficient Level 3), outdoor type 11.0/0.433 KV, 50 Hz, AC double wound core type, copper wound, oil immersed type, naturally air cooled with external cooling tubes, transformer delta connection on HT side & star connection on LV side in accordance with vector symbol DyN 11 (vector group-4) with off-load tap changer on HT side to vary secondary voltage +/- 7.5% in equal steps of 2.5% as per IS-1180 (Part-I) : 2014. The voltage regulation shall be as per IS including first fill of transformer oil upto appropriate level all as per IS-335 complete all as specified and as directed comprising with and including the following specifications :-\n\n(a) 01 No. Cable end box on HT side consisting of 03 Nos. porcelain bushing with busing brass rods, nuts, washers and cable glands suitable for reception of HT 11000 V grade XLPE insulated heavy duty cables including glands complete.\n(b) 01 No. cable end box on LT side consisting of 03 Nos. porcelain bushing with bushing brass rods, nuts, washers and cable glands suitable for reception of LT 1100 V grade XLPE insulated heavy duty cables including glands complete.\n(c) Oil conservator with filter type drain valve and oil level gauge.\n(d) Explosion vent with double diaphragm and sight glass.\n(e) Thermometer Pocket.\n(f) Two earthing terminal on tank body to facilitate fixing of 32 x 6 mm GI strip etc.\n Item Continued as 10.06 2 EACH JOB
92 10.06 (g) 01 No. thermometer dial type, vapor pressure type having range 0 to 120oC with maximum temperature indicator, re-setting device and marked maximum temperature point.\n(h) Rating plate with terminal marking plate.\n(j) Oil level gauge.\n(k) Oil drain filter valve.\n(l) Oil filling port on top cover with plug.\n(m) Air release valve / plug.\n(n) 04 Nos. plain solid cast steel detachable rollers.\n(o) First fill of transformer oil confirming to relevant IS and tested upto 60 KV dielectric strength.\n(p) Inspection cover.\n(q) Lifting lugs and jack lifting pad and support.\n(r) Silica gel breather without / with connecting pipes, first fill of dehydrating agent.\n(s) Cover lifting eyes.\n(t) Oil temperature indicator of approved range, including shut off valve between conservator and main tank.\n(u) Additional / Extra bushing for neutral outside of LV side.\n\nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.\n
93 10.07 Supply, installation, testing and commissioning of transformer platform / plinth mounted of capacity 200 KVA step down, BEE 5 Star rated (Energy Efficient Level 3), outdoor type 11.0/0.433 KV, 50 Hz, AC double wound core type, copper wound, oil immersed type, naturally air cooled with external cooling tubes, transformer delta connection on HT side & star connection on LV side in accordance with vector symbol DyN 11 (vector group-4) with off-load tap changer on HT side to vary secondary voltage +/- 7.5% in equal steps of 2.5% as per IS-1180 (Part-I) : 2014. The voltage regulation shall be as per IS including first fill of transformer oil upto appropriate level all as per IS-335 complete all as specified and as directed comprising with and including the following specifications :-\n(a) 01 No. Cable end box on HT side consisting of 03 Nos. porcelain bushing with busing brass rods, nuts, washers and cable glands suitable for reception of HT 11000 V grade XLPE insulated heavy duty cables including glands complete.\n(b) 01 No. cable end box on LT side consisting of 03 Nos. porcelain bushing with bushing brass rods, nuts, washers and cable glands suitable for reception of LT 1100 V grade XLPE insulated heavy duty cables including glands complete.\n(c) Oil conservator with filter type drain valve and oil level gauge.\n(d) Explosion vent with double diaphragm and sight glass.\n(e) Thermometer Pocket.\n Item Continued as 10.08 1 EACH
94 10.08 (f) Two earthing terminal on tank body to facilitate fixing of 32 x 6 mm GI strip etc.\n(g) 01 No. thermometer dial type, vapor pressure type having range 0 to 120oC with maximum temperature indicator, re-setting device and marked maximum temperature point.\n(h) Rating plate with terminal marking plate.\n(j) Oil level gauge.\n(k) Oil drain filter valve.\n(l) Oil filling port on top cover with plug.\n(m) Air release valve / plug.\n(n) 04 Nos. plain solid cast steel detachable rollers.\n(o) First fill of transformer oil confirming to relevant IS and tested upto 60 KV dielectric strength.\n(p) Inspection cover.\n(q) Lifting lugs and jack lifting pad and support.\n(r) Silica gel breather without / with connecting pipes, first fill of dehydrating agent.\n(s) Cover lifting eyes.\n(t) Oil temperature indicator of approved range, including shut off valve between conservator and main tank.\n(u) Additional / Extra bushing for neutral outside of LV side.\nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.
95 10.09 Supply, installation, testing and commissioning of transformer platform / plinth mounted of capacity 100 KVA step down, BEE 5 Star rated (Energy Efficient Level 3), outdoor type 11.0/0.433 KV, 50 Hz, AC double wound core type, copper wound, oil immersed type, naturally air cooled with external cooling tubes, transformer delta connection on HT side & star connection on LV side in accordance with vector symbol DyN 11 (vector group-4) with off-load tap changer on HT side to vary secondary voltage +/- 7.5% in equal steps of 2.5% as per IS-1180 (Part-I) : 2014. The voltage regulation shall be as per IS including first fill of transformer oil upto appropriate level all as per IS-335 complete all as specified and as directed comprising with and including the following specifications :-\n(a) 01 No. Cable end box on HT side consisting of 03 Nos. porcelain bushing with busing brass rods, nuts, washers and cable glands suitable for reception of HT 11000 V grade XLPE insulated heavy duty cables including glands complete.\n(b) 01 No. cable end box on LT side consisting of 03 Nos. porcelain bushing with bushing brass rods, nuts, washers and cable glands suitable for reception of LT 1100 V grade XLPE insulated heavy duty cables including glands complete.\n(c) Oil conservator with filter type drain valve and oil level gauge.\n(d) Explosion vent with double diaphragm and sight glass.\n(e) Thermometer Pocket.\n(f) Two earthing terminal on tank body to facilitate fixing of 32 x 6 mm GI strip etc.\n Item Continued as 10.10\n 1 EACH
96 10.1 (g) 01 No. thermometer dial type, vapor pressure type having range 0 to 120oC with maximum temperature indicator, re-setting device and marked maximum temperature reading point.\n(h) Rating plate with terminal marking plate.\n(j) Oil level gauge.\n(k) Oil drain filter valve.\n(l) Oil filling port on top cover with plug.\n(m) Air release valve / plug.\n(n) 04 Nos. plain solid cast steel detachable rollers.\n(o) First fill of transformer oil confirming to relevant IS and tested upto 60 KV dielectric strength.\n(p) Inspection cover.\n(q) Lifting lugs and jack lifting pad and support.\n(r) Silica gel breather without / with connecting pipes, first fill of dehydrating agent.\n(s) Cover lifting eyes.\n(t) Oil temperature indicator of approved range, including shut off valve between conservator and main tank.\n(u) Additional / Extra bushing for neutral outside of LV side.\nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.\n
97 10.11 Supply, installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel outdoor type, factory made of 250 KVAR capacity ready to use design confirming to IS 5039/IS 8623 and relevant IS / IEC codes rated for short circuit current rating of 50 KA, front open-able and lockable by keys having louvers and air vent, gasket & totally vermin proof and suitable for 415 / 440 V, 3 Phase, 50 Hz, AC and housed in elegant enclosure fabricated from minimum 3.15 mm thick CRCA sheet and minimum 2.0 mm thick for partitions anti-corrosive coating to improve power factor to 0.99 & finally powder coated in texture siemens grey RAL 7032 including suitable size and length of copper conductor cable PVC insulated for controls to each capacitor with and including the following accessories :-\n\n(a) 600 A capacity tinned copper bus-bar duly insulated with colour coded heat shrinkable sleeves and mounted on suitable sized DMC / epoxy insulators.\n(b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 36 KA of rating 400 A -01 No. as incoming.\n\n Item continued as 10.12 2 EACH
98 10.12 (c) A set of heavy duty, capacitor heavy duty, type MDXL or any suitable type, 440 V with output capacity 250 KVAR, capacitor bank in suitable steps and configuration to accommodate all possible set of automatic operation to maintain 0.99 power factor.\n(d) MCBs TP, “C” Series, 415 V of required sizes with required numbers and suitable ratings as per the capacity of the capacitors.\n(e) Microprocessor based control suitable for power factor correction with its unique features of four quadrant operation C/K ratio selection. The APFC controller should ON/OFF the capacitor banks of 250 KVAR capacity in suitable steps and configuration with indication whether it is lagging or leading.\n(f) Power Contactors heavy duty for suitable capacitors shall be provided for automatic operation of each capacitors with ON / OFF indications.\n(g) The APFC panel shall be provided with two external terminals, connected through GI strip 32 x 6 mm to existing transformer earthing / panel earthing all as specified and as directed.\n(h) Digital panel meters for current, voltage, frequency and power factor having programmable CT ratio and built in selector switches of size 96x96 mm, accuracy class-I, auxiliary support of 230 V, AC with SP MCB protection shall be provided.\n\n Item continued as 10.13
99 10.13 (j) All control wires shall be not less than 2.5 Sqmm, multistranded, copper conductor and properly bunched / tied, ferruled for proper identification and crimped with adequate size of lugs. The cubical will have a bottom support of channel of suitable size duly coated with zinc metal coating. A detachable pre-drilled gland plate of thickness 3.15 mm thick, cold zinc metal coated shall be provided with at the bottom for entry for armoured cable with adequate size of gland. Manufacturer name plate with feeder details & danger notice plate shall also be provided at suitable visible place.\n(k) Auxiliary contactor with required quantity of NO & NC contacts.\n(l) Auto / Manual Switch – 01 No.\n(m) Indicator lamp LED based with lamp holder all as specified and as directed.\n(n) CT of ratio 400/5 A, measuring class accuracy 0.5 to 1.0 for capacitor panel.\n(o) Spare CT 01 No. of ratio 400/5 A and necessary control cabling for sensing the pf in the main panel for APFC operation.\nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.\n
100 10.14 Supply, installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel outdoor type, factory made of 80 KVAR capacity ready to use design confirming to IS 5039/IS 8623 and relevant IS / IEC codes rated for short circuit current ranking of 50 KA, front open-able and lockable by keys having louvers and air vent, gasket & totally vermin proof and suitable for 415 / 440 V, 3 Phase, 50 Hz, AC and housed in elegant enclosure fabricated from minimum 3.15 mm thick CRCA sheet and minimum 2.0 mm thick for partitions anti-corrosive coating to improve power factor to 0.99 & finally powder coated in texture siemens grey RAL 7032 including suitable size and length of copper conductor cable PVC insulated for controls to each capacitor with and including the following accessories :-\n\n(a) 200 A capacity tinned copper bus-bar duly insulated with colour coded heat shrinkable sleeves and mounted on suitable sized DMC / epoxy insulators.\n(b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 160 A -01 No. as incoming.\n(c) A set of heavy duty, capacitor heavy duty, type MDXL or any suitable type, 440 V with output capacity 80 KVAR, capacitor bank in suitable steps and configuration to accommodate all possible set of automatic operation to maintain 0.99 power factor.\n\n Item continued as 10.15 1 EACH
101 10.15 (d) MCBs TP, “C” Series, 415 V of required sizes with required numbers and suitable ratings as per the capacity of the capacitors.\n(e) Microprocessor based control suitable for power factor correction with its unique features of four quadrant operation C/K ration selection. The APFC controller should ON/OFF the capacitor banks of 80 KVAR capacity in suitable steps and configuration with indication whether it is lagging or leading.\n(f) Power Contactors heavy duty for suitable capacitors shall be provided for automatic operation of each capacitors with ON / OFF indications.\n(g) The APFC panel shall be provided with two external terminals, connected through GI strip 32 x 6 mm to existing transformer earthing / panel earthing all as specified and as directed.\n(h) Digital panel meters for current, voltage, frequency and power factor having programmable CT ratio and built in selector switches of size 96x96 mm, accuracy class-I, auxiliary support of 230 V, AC with SP MCB protection shall be provided.\n\n Item continued as 10.16
102 10.16 (j) All control wires shall be not less than 2.5 Sqmm, multistranded, copper conductor and properly bunched / tied, ferruled for proper identification and crimped with adequate size of lugs. The cubicle will have a bottom support of channel of suitable size duly coated with zinc metal coating. A detachable pre-drilled gland plate of thickness 3.15 mm thick, cold zinc metal coated shall be provided with at the bottom for entry for armoured cable with adequate size of gland. Manufacturer name plate with feeder details & danger notice plate shall also be provided at suitable visible place.\n(k) Auxiliary contactor with required quantity of NO & NC contacts.\n(l) Auto / Manual Switch – 01 No.\n(m) Indicator lamp LED based with lamp holder all as specified and as directed.\n(n) CT of ratio 200/5 A, measuring class accuracy 0.5 to 1.0 for capacitor panel.\n(o) Spare CT 01 No. of ratio 200/5 A and necessary control cabling for sensing the pf in the main panel for APFC operation.\nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.\n
103 10.17 Supply, installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel outdoor type, factory made of 40 KVAR capacity ready to use design confirming to IS 5039/IS 8623 and relevant IS / IEC codes rated for short circuit current rating of 50 KA, front open-able and lockable by keys having louvers and air vent, gasket & totally vermin proof and suitable for 415 / 440 V, 3 Phase, 50 Hz, AC and housed in elegant enclosure fabricated from minimum 3.15 mm thick CRCA sheet and minimum 2.0 mm thick for partitions anti-corrosive coating to improve power factor to 0.99 & finally powder coated in texture siemens grey RAL 7032 including suitable size and length of copper conductor cable PVC insulated for controls to each capacitor with and including the following accessories :-\n\n(a) 200 A capacity tinned copper bus-bar duly insulated with colour coded heat shrinkable sleeves and mounted on suitable sized DMC / epoxy insulators.\n(b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 80 A -01 No. as incoming\n\n Item continued as 10.18 1 EACH
104 10.18 (c) A set of heavy duty, capacitor heavy duty, type MDXL or any suitable type, 440 V with output capacity 40 KVAR, capacitor bank in suitable steps and configuration to accommodate all possible set of automatic operation to maintain 0.99 power factor.\n(d) MCBs TP, “C” Series, 415 V of required sizes with required numbers and suitable ratings as per the capacity of the capacitors.\n(e) Microprocessor based control suitable for power factor correction with its unique features of four quadrant operation C/K ratio selection. The APFC controller should ON/OFF the capacitor banks of 40 KVAR capacity in suitable steps and configuration with indication whether it is lagging or leading.\n(f) Power Contactors heavy duty for suitable capacitors shall be provided for automatic operation of each capacitors with ON / OFF indications.\n(g) The APFC panel shall be provided with two external terminals, connected through GI strip 32 x 6 mm to existing transformer earthing / panel earthing all as specified and as directed.\n(h) Digital panel meters for current, voltage, frequency and power factor having programmable CT ratio and built in selector switches of size 96x96 mm, accuracy class-I, auxiliary support of 230 V, AC with SP MCB protection shall be provided.\n Item continued as 10.19
105 10.19 (j) All control wires shallnot be less than 2.5 Sqmm, multistranded, copper conductor and properly bunched / tied, ferruled for proper identification and crimped with adequate size of lugs. The cubical will have a bottom support of channel of suitable size duly coated with zinc metal coating. A detachable pre-drilled gland plate of thickness 3.15 mm thick, cold zinc metal coated shall be provided with at the bottom for entry for armoured cable with adequate size of gland. Manufacturer name plate with feeder details & danger notice plate shall also be provided at suitable visible place.\n(k) Auxiliary contactor with required quantity of NO & NC contacts.\n(l) Auto / Manual Switch – 01 No.\n(m) Indicator lamp LED based with lamp holder all as specified and as directed.\n(n) CT of ratio 100/5 A, measuring class accuracy 0.5 to 1.0 for capacitor panel.\n(o) Spare CT 01 No. of ratio 300/5 A and necessary control cabling for sensing the pf in the main panel for APFC operation.\nNOTE : -\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.\n
106 10.2 S&F of energy saving and environment friendly long life 45 W or next higher available rating, CT>=5700 K, LED street light made up of pressure die-cast aluminium housing with acrylic cover as diffuser with IP 66 protection and impact resistance not less than IK-07 complete with integrated type, with high efficiency electronic driver, built-in- surge suppressor / SPD of 10 KV or more and high brightness LEDs, luminaire efficacy > 110 lumens/Watt, power factor >=0.90, operating range – 140 to 270 V, 50 Hz complete including suitable fixing arrangement made out of 40 mm dia GI Bracket, necessary MS clamps, nuts, bolts etc. complete all as specified and as directed. 30 EACH
107 10.21 S&F of factory fabricated (CPRI type tested) weather proof, dust and vermin proof street light junction box of size 250(L) x 250(B) x 150(D) mm (minimum dimensions) made up of 3.15 mm thick CRCA sheet, powder coated after preparation of surfaces comprising of 04 Nos. aluminium bus-bar of size 20 x 4 mm mounted on suitable size spacer insulators with provn of 01 No. MCB SP 6 Amps, 10 KA breaking capacity, ‘C’ Curve and two openings at the bottom and one opening at the top with cable glands and fixing with the help of suitable sized MS clamps to steel poles including complete all as specified and as directed. 30 EACH
108 10.22 Supply, laying, jointing and testing of XLPE insulated screened PVC bedded galvanized steel strip armoured, heavy duty electric power cable with stranded aluminium conductor 11000 V grade (Earthed), IS:7098 Part-II ISI marked, latest version, of size 3 Core 95 Sqmm laid in trench, ducts etc or fixed to poles with GI pipe and Fl clamps 50 mm x 5 mm, including nuts, bolts and washers complete all as specified and as directed. \nNOTE :-\n(a) The cost of clamps, nuts bolts and washers etc shall be included in this item without any extra cost.\n(b) Necessary earthwork, PCC etc shall be measured and paid separately under relevant items of work. 2200 RM
109 10.23 Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade with stranded aluminium conductor of size 400 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed. 860 RM
110 10.24 Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade with stranded aluminium conductor of size 240 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed. 710 RM
111 10.25 Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade with stranded aluminium conductor of size 120 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed. 350 RM
112 10.26 Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade with stranded aluminium conductor of size 95 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed. 620 RM
113 10.27 Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade with stranded aluminium conductor of size 50 Sqmm 3.5 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed. 60 RM
114 10.28 Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade with stranded aluminium conductor of size 25 Sqmm 4 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed. 550 RM
115 10.29 Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade with stranded aluminium conductor of size 16 Sqmm 4 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed. 120 RM
116 10.3 Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade with stranded aluminium conductor of size 10 Sqmm 2 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed. 60 RM
117 10.31 Supply, laying, jointing and testing XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty), 1100 V grade with stranded aluminium conductor of size 6 Sqmm 2 Core in trenches / through GI pipe / fixed alongwith pole structure etc with all fixing and connecting accessories complete all as specified and as directed. 500 RM
118 10.32 Supply, erection, commissioning and testing of High Galvanized Mast Light 15 Meter High suitable for 06 Nos. 1 x 160 W LED Flood light and having three point suspension system with steel wire rope of 6 mm did and double drum winch with luminaire mounting arm, 01 No. LED type aviation obstruction light including lamp, lightning arrestor spike, power tools including lamp, lightning arrestor spike, power tools including cutting road / hard standing, excavation for RCC foundation complete with following and all as specified and as directed :-\n\n(a) High mast fabricated from steel plates conforming to BSEN-10025/IS:5986, cut and folded to from a polygonal section. Mast shall be in two sections for 16 mtr heights having only longitudinal weld conforming to BS-5135/AWS. The mast is to be provided with a fully penetrated flange which shall be free from any laminations or incursions. The welded connection of the base flange shall be fully developed to the strength of the entire section. The base flange shall be provided with supplementary gussets between bolt holes to ensure elimination of helical stress concentration. For environmental protection of the mast, the entire fabricated mast shall be Hot Dip Galvanized (As per IS:2629) internally and externally having uniform thickness of average 86 microns for bottom / top sections respectively and certificate from the OEM regarding the same to be submitted alongwith the PV and test certificates.\n\n(b) An adequate door opening shall be provided at the base of the mast. The opening shall be such that it permits clear access to equipment’s lich winch, cable, wire rope, plug and socket etc. and also facilitates easy removal of the winch for servicing. \n Item continued as 10.33 1 EACH JOB
119 10.33 The door opening shall be complete with a close fitting vandal resistant allen key locking with provision for external lock. The door opening shall be carefully designed and reinforced with adequate steel section so that the mast section at the base is unaffected, and undue buckling of the cut portion is prevented under heavy wind condition.\n\n(c) Mast structure shall sustain as assumed maximum reaction arising from wind speed as per IS-875 (Part-3) 1987 (three seconds) which is measured at a height of 10 mtrs above ground level.\n\n(d) The high mast shall be provided with accessories which include a raising and lowering system (R&L), trailing cable, power tool, lighting finial and aviation obstruction warning light.\n\n(e) The wire ropes shall be of stainless steel grade AISI 304 with minimum 6 mm diameter and 7/19 construction. Its central cores shall be also SS and have a minimum breaking strength of 2400 Kgs. The power tool shall be integral type suitable for handling the total head load. It shall have a mechanical torque limiter to ensure safety and also a manual handle shall be provided.\n\n(f) Earthing 04 Nos. (02 for FP Box and 02 for High mast) complete with Galvanized steel earth plate electrode 600 x 600 x 6.0 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below ground level with the top edge of the earth plate not less than 1.5 mtr below ground level and connected to galvanized iron earth lead strip 32 x 6 mm dia by means of bolts, nuts, check nuts and washer of \n Item continued as 10.34
120 10.34 galvanized iron including PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) precast RCC cover slab including one handle made out of 8 mm dia round bar embedded in precast slab and 20 mm bore medium grade galvanized steel tube for watering with one end fixed with cast iron funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection including charcoal and salt in alternate layers of 15 cm including necessary excavation and earth work in any type of soil complete all as shown in EP No. 3 of SSR Part-I and testing on completion complete all as specified and as directed.\n(g) Earthing 01 No. (for Surge protection device) complete with Galvanized steel earth plate electrode 600 x 600 x 6.0 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below ground level with the top edge of the earth plate not less than 1.5 mtr below ground level and connected to galvanized iron wire 4 mm dia by means of bolts, nuts, check nuts, and washer of galvanized iron including PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) precast RCC cover slab including one handle made out of 8 mm dia round bar embedded in precast slab and 20 mm bore medium grade galvanized steel tube for watering with one end fixed with cast iron funnel and wire mesh, 15 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection including charcoal and salt in alternate layers of 15 cm including necessary excavation and earth work in any type of soil complete all as shown in EP No. 3 of SSR Part-I and testing on completion complete all as specified and as directed.\n Item continued as 10.35
121 10.35 (h) The light luminaries shall be 160 W LED, CT>=5700 K made up of pressure die-cast aluminium housing with acrylic cover as diffuser with IP 66 protection and impact resistance not less than IK-07 complete with integrated type, with high efficiency electronic driver, surge suppressor 5 KV or more and high brightness LEDs, luminaire efficacy > 110 lumens/Watt, power factor >=0.90, operating range – 140 to 270 V, 50 Hz complete including suitable fixing arrangement made out of 40 mm dia GI Bracket, necessary MS clamps, nuts, bolts etc. complete all as specified and as directed.\n\n(j) The aviation obstruction light shall be LED type with IP 65/66 protection and all as per the recommendations of the OEM complete.\n\n(k) LT feeder pillar box both side openable with projected globe roof for rain water protection, manufactured by a CPRI approve manufacturer dust and vermin proof, suitable for 440 V, 3-Phase, 4 wire system made out of 3.15 mm thick CRCA sheet of size as per OEM and built upon rigid frame work having front and rear hinged double shutter doors with neoprene rubber gasket, epoxy powder coated including danger plate, earthing strip point and ventilation louvers at rear side, bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts and washers etc. and embedded with 50 x 50 x 6 mm mild steel angle iron frame complete with PCC foundation in Cement Concrete (1:2:4) (using 20 mm graded stone aggregate) and testing after insulation complete all as specified and as directed :- \n\n Item continued as 10.36
122 10.36 (i) Aluminium bus-bar 100 Amp, supported with suitable size of heavy duty porcelain stand lock with suitable size brass nut, bolts and washers with heat shrinkable PVC sleeving. The bus bar shall be colour coded (Red, Yellow and Blue) for 3-Phase and black for neutral.\n\n(ii) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 40 A – 01 No.\n\n(iii) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 32 A – 02 Nos.\n\n(iv) Digital Ammeter 0-100 Amps with 03 Nos. CT’s and 01 No. Selector switch and protection fuse – 01 Set.\n\n(v) Digital Voltmeter 0-500 Volt with 01 No. Selector switch and protection fuse.\n\n(vi) LED indication lamps (03 Nos.) with holder for main supply indicating RYB – 01 Set.\n\n(vii) Astro-Timer switch with 3-Pole 415 Volt with coil operating Voltage 230 Volt Contactor with and including fuse protection for automatic ON/OFF of security / street lighting – 01 Set. \n\n Item continued as 10.37
123 10.37 (viii) Contactor MNX 32, 3-Phase, 3-Pole, 415 Volt with coil operating Voltage 230 Volt – 02 Nos. push button switch 16 Amps and electrical interlocking between two contactors for forward and reverse operation of motor installed at high mast system.\n\n(ix) Connector / Terminal set 16-50 Sqmm 5-Pole fitted inside the mast for cable connection complete.\n\n(x) Surge Protection Device, type-2, 40 KA, 3P+N, 2 module with 01 No. 32 Amps MCB TPN including internal connection done by using suitable size of copper wire complete all as specified and as directed.\n\nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.
124 10.38 Supply, installation, testing and commissioning of LT panel board, “indoor pedestal type” of size 1500 mm (height) x 1800 mm (breadth) x 600 mm (depth) (minimum) dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-43 and general construction confirming to IS-13947, double door, front and back open-able. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation and tinned copper bus bar wrapped with coloured PVC tape/ sleeves of rating in conformity to the incoming ACB / MCCB rating. The Panel Board shall be fabricated out of 2.0 mm thick CRCA sheet duly pretreated and powder coated, supporting frame made out of 50 x 50 x 5 mm angle iron and MC 100 channel base suitable for 3-Phase, 4-wire system 415/440 Volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes including necessary arrangements for pedestal mounting viz. PCC platform etc. complete all as specified and directed with and including the following accessories :-\n\n(MAIN PANEL FOR 630 KVA TRANSFORMER)\nBUS BAR AND INTERNAL CONNECTIONS :-\n\nThe bus bars shall be made up of 04 Nos. tinned copper 1600 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves and rigidly mounted on suitable sized ‘F’ class insulators of non-hygroscopic, non-combustible, all internal connections from main bus bars to switch gears etc.\n Item continued as 10.39 1 EACH
125 10.39 PROVISION FOR CABLE ENTRY :-\nThe provision for cable entry / exit shall be provided in the bottom for both incoming and outgoing cables.\n\nINCOMING :-\nAir Circuit Breaker (ACB), 4-pole having breaking capacity 50 KA of rating 1250 A, manual draw-out (MDO) type with the following features :-\n\n(a) LSING Protection\n(b) LCD Display.\n(c) Communication through RS-485 Port.\n(d) True RMS sensing.\n(e) Current / Voltage / Power Measurement.\n(f) Thermal Memory.\n(g) Fault Indication.\n(h) Zone Selectivity.\n(j) Harmonics etc.\n\nOUTGOINGS :-\n(a) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 35 KA of rating 200 A – 04 Nos.\n(b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 40 A – 02 Nos.\n(c) S&F MCB, SPN, 10KA, 240 V, ‘C’ Curve, 06-32 A, ISI marked – 01 No.\n\n Item continued as 10.40
126 10.4 INSTRUMENTATION SYSTEM :-\n(a) Digital type AC Ammeter 0 to 1200 A with built-in selector switch and 03 Nos. CTs, (Accuracy Class – 1.0, CT Ratio – 1200/5, Burden – 15 VA), 3-Phase, Accuracy Class – 0.5, Size 96 x 96 mm.\n\n(b) Digital type AC Volt meter with built-in Selector switch, 3-Phase, 30-600 Volts range, Accuracy Class – 0.5, size 96 x 96 mm.\n\n(c) Indicator lamp with integral circuit (230/240 V) and cluster LED (Red, Orange, Blue) – 01 Set.\n\n(d) Danger notice plate of size 20 x 15 cm of 1.6 mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps, bolts and nuts of approved size, for LT conforming to IS:2551 – 02 Nos.\n \nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.
127 10.41 Supply, installation, testing and commissioning of LT panel board, “indoor pedestal type” of size 1500 mm (height) x 1800 mm (breadth) x 600 mm (depth) (minimum) dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-43 and general construction confirming to IS-13947, double door, front and back open-able. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation and tinned copper bus bar wrapped with coloured PVC tape/ sleeves of rating in conformity to the incoming ACB / MCCB rating. The Panel Board shall be fabricated out of 2.0 mm thick CRCA sheet duly pretreated and powder coated, supporting frame made out of 50 x 50 x 5 mm angle iron and MC 100 channel base suitable for 3-Phase, 4-wire system 415/440 Volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes including necessary arrangements for pedestal mounting viz. PCC platform etc. complete all as specified and directed with and including the following accessories :-\n\n(MAIN PANEL FOR 630 KVA TRANSFORMER)\nBUS BAR AND INTERNAL CONNECTIONS :-\n\nThe bus bars shall be made up of 04 Nos. tinned copper 1600 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves and rigidly mounted on suitable sized ‘F’ class insulators of non-hygroscopic, non-combustible, all internal connections from main bus bars to switch gears etc.\n Item continued as 10.42 1 EACH
128 10.42 PROVISION FOR CABLE ENTRY :-\nThe provision for cable entry / exit shall be provided in the bottom for both incoming and outgoing cables.\n\nINCOMING :-\nAir Circuit Breaker (ACB), 4-pole having breaking capacity 50 KA of rating 1250 A, manual draw-out (MDO) type with the following features :-\n\n(a) LSING Protection\n(b) LCD Display.\n(c) Communication through RS-485 Port.\n(d) True RMS sensing.\n(e) Current / Voltage / Power Measurement.\n(f) Thermal Memory.\n(g) Fault Indication.\n(h) Zone Selectivity.\n(j) Harmonics etc.\n\nOUTGOINGS :-\n(a) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 36 KA of rating 320 A – 02 Nos.\n(b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 40 A – 02 Nos.\n(c) S&F MCB, SPN, 10KA, 240 V, ‘C’ Curve, 06-32 A, ISI marked – 01 No.\n\n Item continued as 10.43
129 10.43 INSTRUMENTATION SYSTEM :-\n(a) Digital type AC Ammeter 0 to 1200 A with built-in selector switch and 03 Nos. CTs, (Accuracy Class – 1.0, CT Ratio – 1200/5, Burden – 15 VA), 3-Phase, Accuracy Class – 0.5, Size 96 x 96 mm.\n\n(b) Digital type AC Volt meter with built-in Selector switch, 3-Phase, 30-600 Volts range, Accuracy Class – 0.5, size 96 x 96 mm.\n\n(c) Indicator lamp with integral circuit (230/240 V) and cluster LED (Red, Orange, Blue) – 01 Set.\n\n(d) Danger notice plate of size 20 x 15 cm of 1.6 mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps, bolts and nuts of approved size, for LT conforming to IS:2551 – 02 Nos.\n \nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.
130 10.44 Supply, installation, testing and commissioning of LT panel board, “outdoor type” of size 1400 mm (height) x 1200 mm (breadth) x 600 mm (depth) (minimum) dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction confirming to IS-13947, double door, front and back open-able. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation and tinned copper bus bar wrapped with coloured PVC tape/ sleeves of rating in conformity to the incoming ACB / MCCB rating. The Panel Board shall be fabricated out of 3.15 mm thick CRCA sheet duly pretreated and powder coated, supporting frame made out of 50 x 50 x 5 mm angle iron and MC 100 channel base suitable for 3-Phase, 4-wire system 415/440 Volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes including necessary earthwork, PCC foundations, PCC plinth / platform etc. complete all as specified and directed with and including the following accessories :-\n\n(MAIN PANEL FOR 200 KVA TRANSFORMER)\nBUS BAR AND INTERNAL CONNECTIONS :-\n\nThe bus bars shall be made up of 04 Nos. tinned copper 500 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves and rigidly mounted on suitable sized ‘F’ class insulators of non-hygroscopic, non-combustible, all internal connections from main bus bars to switch gears etc.\n\n Item continued as 10.45 1 EACH
131 10.45 PROVISION FOR CABLE ENTRY :-\nThe provision for cable entry / exit shall be provided in the bottom for both incoming and outgoing cables.\n\nINCOMING :-\nMCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 36 KA of rating 350A..\n\nOUTGOINGS :-\n(a) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 63 A – 05 Nos.\n(b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 40 A – 02 Nos.\n(c) S&F MCB, SPN, 10KA, 240 V, ‘C’ Curve, 06-32 A, ISI marked – 01 No.\n\nINSTRUMENTATION SYSTEM :-\n(a) Digital type AC Ammeter 0 to 400 A with built-in selector switch and 03 Nos. CTs, (Accuracy Class – 1.0, CT Ratio – 400/5, Burden – 15 VA), 3-Phase, Accuracy Class – 0.5, Size 96 x 96 mm.\n\n Item continued as 10.46
132 10.46 (b) Digital type AC Volt meter with built-in Selector switch, 3-Phase, 30-600 Volts range, Accuracy Class – 0.5, size 96 x 96 mm.\n\n(c) Indicator lamp with integral circuit (230/240 V) and cluster LED (Red, Orange, Blue) – 01 Set.\n\n(d) Danger notice plate of size 20 x 15 cm of 1.6 mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps, bolts and nuts of approved size, for LT conforming to IS:2551 – 02 Nos.\n\nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates. \n
133 10.47 Supply, installation, testing and commissioning of LT panel board, “outdoor type” of size 1200 mm (height) x 1200 mm (breadth) x 600 mm (depth) (minimum) dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction confirming to IS-13947, double door, front and back open-able. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation and tinned copper bus bar wrapped with coloured PVC tape/ sleeves of rating in conformity to the incoming ACB / MCCB rating. The Panel Board shall be fabricated out of 3.15 mm thick CRCA sheet duly pretreated and powder coated, supporting frame made out of 50 x 50 x 5 mm angle iron and MC 100 channel base suitable for 3-Phase, 4-wire system 415/440 Volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands of suitable sizes including necessary earthwork, PCC foundations, PCC plinth / platform etc. complete all as specified and directed with and including the following accessories :-\n\n(MAIN PANEL FOR 100 KVA TRANSFORMER)\nBUS BAR AND INTERNAL CONNECTIONS :-\n\nThe bus bars shall be made up of 04 Nos. tinned copper 200 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves and rigidly mounted on suitable sized ‘F’ class insulators of non-hygroscopic, non-combustible, all internal connections from main bus bars to switch gears etc.\n\n Item continued as 10.48 1 EACH
134 10.48 PROVISION FOR CABLE ENTRY :-\nThe provision for cable entry / exit shall be provided in the bottom for both incoming and outgoing cables.\n\nINCOMING :-\nMCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 35 KA of rating 200A..\n\nOUTGOINGS :-\n(a) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 100 A – 01 No.\n(b) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit and adjustable overload setting having breaking capacity 25 KA of rating 63 A – 04 Nos.\n(c) S&F MCB, SPN, 10KA, 240 V, ‘C’ Curve, 06-32 A, ISI marked – 02 Nos.\n\nINSTRUMENTATION SYSTEM :-\n(a) Digital type AC Ammeter 0 to 200 A with built-in selector switch and 03 Nos. CTs, (Accuracy Class – 1.0, CT Ratio – 200/5, Burden – 15 VA), 3-Phase, Accuracy Class – 0.5, Size 96 x 96 mm.\n\n(b) Digital type AC Volt meter with built-in Selector switch, 3-Phase, 30-600 Volts range, Accuracy Class – 0.5, size 96 x 96 mm.\n\n Item continued as 10.49
135 10.49 (c) Indicator lamp with integral circuit (230/240 V) and cluster LED (Red, Orange, Blue) – 01 Set.\n\n(d) Danger notice plate of size 20 x 15 cm of 1.6 mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps, bolts and nuts of approved size, for LT conforming to IS:2551 – 02 Nos.\n\nNOTE :-\n1. Design / Drawing / BOM of the Transformer showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates. \n \n
136 10.5 M&L for cable route indicator using RCC post 1.20 mtr long, top 100 x 100 mm and bottom 200 x 200 mm with height not less than 50 cm above GL with engraved marking “HT CABLE” in bold letters during refilling of the trench complete all as specified and as directed.\nNOTE : The spacing between two consecutive cable route indicators shall not be more than 50.00 meters and also shall be provided at each and every bend or corner.\n 45 EACH
137 10.51 Sub total
138 11 SEWAGE DISPOSAL (Sch 'A' Part-VII)
139 11.01 Lump sum price worked out by the Contractor for “(SEWAGE DISPOSAL)” as listed in Schedule ‘A’ Part-VII. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 23,97,214.27 inserted by the MES in Schedule ‘A’ Part-VII. 1 LUMP SUM
140 12 SEWAGE DISPOSAL (Sch 'A' Part-VII (A) (MISC))
141 12.01 M&L for laying DWCPE (SN8) 180 (OD)/163(ID) mm dia meter pipes any length complete all as specified and as directed. 200 RM
142 12.02 Sub total
143 13 AREA DRAINAGE (Sch 'A' Part-VIII)
144 13.01 Lump sum price worked out by the Contractor for “(AREA DRAINAGE)” as listed in Schedule ‘A’ Part-VIII. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 37,67,621.80 inserted by the MES in Schedule ‘A’ Part-IX.\n 1 LUMP SUM
145 14 ROAD, PATH & CULVERT (Sch 'A' PART-IX)
146 14.01 Lump sum price worked out by the Contractor for “(ROAD, PATH & CULVERT)” as listed in Schedule ‘A’ Part-IX. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 29,23,004.00 inserted by the MES in Schedule ‘A’ Part-IX.\n 1 LUMP SUM
147 15 ROAD, PATH & CULVERT (Sch 'A' Part-IX(A) (MISC))
148 15.01 Cleaning and preparing the Road surface and making good for Road marking with material and labour by reflective Thermoplastic white road marking paint confirming to BIS 3262 laid down through Road marking machine in a layer of CRYSTALEX and use of 5 Kg Material per square meter by incorporating the white glass beads for reflectivity in 100 mm width complete all as specified as directed. 150 SQM
149 15.02 S&F delineator made of acrylic material fitted with high intensity reflex reflector in white/yellow colour fitted on CRCA pipe 60 cm long painted with powder coated or stove enamelled white/Black colour provided with wire gauge for safety of reflector (ART NO ARS-1006 of M/S Auto Materoad safty Pvt Ltd or other equivalent as approved by GE) embedded in PCC (1:2:4) type B1 with 20 mm graded stone aggregate (size of Block 30 Cmx30 Cmx 30 Cm) complete all as specified and as directed 20 EACH
150 15.03 S&F Cat eyes (3M USA brand) made of non breakable Polycarbonate with electonically welded prismatic retro reflective light on centre for maximum retroreflection in wet and dry conditions, with dust proof body (i.e. no dust accumulation on lens) and space built for finger grip. Bitumin adhesive B1-69 shall be used for fixing the Cat Eyes complete all as specified and as directed. 20 EACH
151 15.04 S&F SOLAR STUDS of approved make all as specified and as directed. 10 EACH
152 15.05 Sub total
153 16 SECURITY WALL, FENCING AND GATE (Sch 'A' Part-X)
154 16.01 Lump sum price worked out by the Contractor for “(SECURITY WALL, FENCING AND GATE)” as listed in Schedule ‘A’ Part-X. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 63,022.78 inserted by the MES in Schedule ‘A’ Part-X.\n 1 LUMP SUM
155 17 LIGHTNING PROTECTION (Sch 'A' PART-XI)
156 17.01 Lump sum price worked out by the Contractor for “(LIGHTNING PROTECTION)” as listed in Schedule ‘A’ Part-XI. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,99,055.20 inserted by the MES in Schedule ‘A’ Part-XI.\n 1 LUMP SUM
157 18 AIR CONDITIONING & REFRIGERATION (Sch 'A' Part-XII)
158 18.01 Supply, installation, testing and commissioning of wall mounted air cooled split type unit AC based on Inverter Technology, electric driven single phase outdoor and indoor units with cordless remote control unit and within built air ionizer and plasma filter for better indoor air quality, cutting, brazing and connecting copper pipe of suitable size for refrigerant and insulation to refrigerant pipe and making holes for passing of copper pipes and electric cables including initial charging of the non CFC refrigerant and testing the complete system for smooth functioning of split AC, BEF 5-Star rating confirming to IS:1391 Part-II 1992 hermetically sealed air compressor of capacitor 1.5 TR and factory made powder coated MS bracket or PCC platform for outer unit. PVC insulated and sheathed copper cable from stabilizer to outdoor and indoor units including PVC pipe 20 mm dia for sweating / drain water pipe upto mtr complete all as specified and as directed.\n\nNOTE :-\n(i) The Air Conditioner shall be initial filled / charged with refrigerant of specified quantity and the refrigerant to be used shall be non-CFC type and as per the latest technology.\n(ii) The cost of additional refrigerant pipes required (if any) is deemed to be included in the unit quoted rates.\n(iii) Suitable piping of adequate length and size 5/8” for drainage of condensate water from indoor unit shall be provided and the cost of the same is deemed to be included in the unit quoted rates.\n(iv) Anything missed out in the technical specifications but technically required for efficient working of the AC is deemed to be included in the unit quoted rates.\n 4 EACH
159 18.02 Supply, installation, testing and commissioning of refrigerator inverter type double door, toughened glass shelves, BEE 5-Star rating frost free defrosting, ISI marked, electric driven, single phase having capacity 170 Ltrs or nearest higher capacity, frost free working with non-CFC refrigerant including electric connection complete all as specified and as directed. 21 EACH
160 18.03 Supply, installation, testing and commissioning of refrigerator inverter type double door, toughened glass shelves, BEE 5-Star rating frost free defrosting, ISI marked, electric driven, single phase having capacity 285 Ltrs or nearest higher capacity, frost free working with non-CFC refrigerant including electric connection complete all as specified and as directed. 4 EACH
161 18.04 Supply, installation, testing and commissioning of Water Cooler storage type, ISI marked, electric driven 230 V, 50 Hz, single phase supply with all internal accessories, stainless steel body and tank, power saving PUF insulation, adjustable cold water thermostat, 10 degree to 25 degree centigrade, auto cut-off facility, over-load protection, stainless steel front panel, extended plastic legs, eco-friendly confirming to relevant IS and pf shall not be less than 0.85 compressor & approx storage capacity of 80 Ltrs and nominal cooling capacity of 40 Ltrs including electric connection complete all as specified and as directed. 18 EACH
162 18.05 S&F of wall mounted Voltage Stabilizer for automatic operation, single phase naturally air cooled indoor type copper wound as per BIS 8448:1989 reaffirmed 2003 and designed for input voltage variation between 170 V to 250 V with output voltage stabilized at 230 Volts with accuracy of + 2.5% with latest IC technology intelligent time delay relay of 2 to 3 minutes and high – low voltage cut-off, in-built thermal overload protection and digital display of input / output voltage of capacity 5.0 KVA with time relay suitable for A/C complete all as specified and as directed. 4 EACH
163 18.06 S&F of wall mounted Voltage Stabilizer for automatic operation, single phase naturally air cooled indoor type copper wound as per BIS 8448:1989 reaffirmed 2003 and designed for input voltage variation between 170 V to 250 V with output voltage stabilized at 230 Volts with accuracy of + 2.5% with latest IC technology intelligent time delay relay of 2 to 3 minutes and high – low voltage cut-off, in-built thermal overload protection and digital display of input / output voltage of capacity 1.0 KVA with time relay suitable for Water Cooler complete all as specified and as directed. 25 EACH
164 18.07 S&F of wall mounted Voltage Stabilizer for automatic operation, single phase naturally air cooled indoor type copper wound as per BIS 8448:1989 reaffirmed 2003 and designed for input voltage variation between 170 V to 250 V with output voltage stabilized at 230 Volts with accuracy of + 2.5% with latest IC technology intelligent time delay relay of 2 to 3 minutes and high – low voltage cut-off, in-built thermal overload protection and digital display of input / output voltage of capacity 0.5 KVA with time relay suitable for Refrigerator complete all as specified and as directed. 18 EACH
165 18.08 Sub total
166 19 FIRE ALARM SYSTEM (Sch 'A' Part-XIII)
167 19.01 Lump sum price worked out by the Contractor for “(FIRE ALARM SYSTEM)” as listed in Schedule ‘A’ Part-XIII. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 39,388.00 inserted by the MES in Schedule ‘A’ Part-XIII. 1 LUMP SUM
168 20 FIRE ALARM SYSTEM (Sch 'A' Part-XIII(A) (MISC))
169 20.01 Supply, installation, testing and commissioning detectors complying with and type certified to EN-45 addressable type microprocessor based programmable intelligent type multi-sensor heat and smoke combination detector Photoelectric / Optical with base with self built intelligence as per IS:11360 complete all as specified and as directed. 736 EACH
170 20.02 Supply, installation, testing and commissioning addressable response indicator having flashing green LED and red LED for indication of fire and continuous monitoring including necessary connection to pin point location of fire complete all as specified and as directed. 63 EACH
171 20.03 S&F addressable type manual call point resettable type compatible with main fire alarm control board microprocessor based as per IS:2189 and necessary blinking facility complete all as specified and as directed. 66 EACH
172 20.04 Supply, installation, testing and commissioning addressable electronic sounder cum strobe with range of 25-30 mtr with output not less than 04 Watts including necessary connection complete all as specified and as directed. 40 EACH
173 20.05 Supply, installation, testing and commissioning Fire Alarm Sounders / Sirens Electronic type horizontal single Stage continuous normal operation for at least 50 minutes with sound level 65 DB to 120 DB measured at 1.5 mtr with sound output variation of +5 DB range complete all as specified and as directed. 1 EACH
174 20.06 Supplying, installation, testing and commissioning Fire Alarm main control panel complying with BSEN 54 UPTP 200 detectors and modules (per each loop) microprocessor based addressable intelligent type and compatible with detectors for communication to detectors and response indicators together with mimic diagram made on Auto Cad and pasted on acrylic sheet with data logging facility and 2 x 16 character LCD, confirming to IS:2189 of capacity from 99 detectors and 99 modules upto 200 detector and modules per zone / loop complete with PA based evacuation system and suitable for 415 V 3 phase 50 Hz having its own standby power backup supply with batteries, battery charger etc. complete. The panel should also have an auto dialing facility and potential NO & NC contacts and 80 Watts PA amplifier The panel should have capacity of not less than 8 zones / loops complete all as specified and as directed. 1 EACH
175 20.07 Supplying, installation, testing and commissioning Fire Alarm main control panel complying with BSEN 54 UPTP 200 detectors and modules (per each loop) microprocessor based addressable intelligent type and compatible with detectors for communication to detectors and response indicators together with mimic diagram made on Auto Cad and pasted on acrylic sheet with data logging facility and 2 x 16 character LCD, confirming to IS:2189 of capacity from 99 detectors and 99 modules upto 200 detector and modules pre zone / loop complete with PA based evacuation system and suitable for 415 V 3 phase 50 Hz having its own standby power backup supply with batteries, battery charger etc. complete. The panel should also have an auto dialing facility and potential NO & NC contacts and 80 Watts PA amplifier. The panel should have capacity of not less than 4 zones / loops complete all as specified and as directed. 7 EACH
176 20.08 NOTE FOR SERIAL ITEM No. 20.06 & 20.07 :-\nAmplifier of this fire alarm control panel shall be linked with public addressable system with microphone and speakers etc. to be provided by user, auto dialing facility of this control panel shall be linked with pre decided telephone – 02 Nos. Telephone and wiring of telephone will be measured and paid separately.\n
177 20.09 Supply, installation, testing and commissioning Fire Alarm Fire repeater panel made of 1.2 mm thick MS Sheet with 2 x 16 character single phase 50 Hz having its own standby power backup supply with batteries, battery charger etc. complete. The panel should also have capacity of 8-16 zones complete all as specified and as directed. 1 EACH
178 20.1 Supply, laying, jointing and testing PVC insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 V grade with stranded copper conductor of size 1.5 Sqmm 4 Core in trenches / through GI pipe / fixed alongwith pole structure etc. with all fittings and connecting accessories complete all as specified and as directed. (From control room to security office). 500 RM
179 20.11 Supply and drawing of the 2 x 1.5 Sqmm size single core PVC insulated, unsheathed, FRLSH cable, 1100 V grade, ISI marked, with multi stranded copper conductor in the existing concealed steel conduit complete all as specified and as directed. 6250 RM
180 20.12 Supply and drawing of the 4 x 1.5 Sqmm size single core PVC insulated, unsheathed, FRLSH cable, 1100 V grade, ISI marked, with multi stranded copper conductor in the existing concealed steel conduit complete all as specified and as directed. 450 RM
181 20.13 M&L for stove enameled steel conduit and including conduit accessories of 25 mm dia medium grade concealed in wall / ceiling/ floor complete all as specified and as directed. 450 RM
182 20.14 M&L for stove enameled steel conduit and including conduit accessories of 20 mm dia medium grade concealed in wall / ceiling/ floor complete all as specified and as directed. 6250 RM
183 20.15 Sub total
184 21 FIRE FIGHTING AND SPIRAL STAIRCASE FOR FIRE EXIT (Sch 'A' Part-XIV)
185 21.01 Lump sum price worked out by the Contractor for “(FIRE FIGHTING AND SPIRAL STAIRCASE FOR FIRE EXIT)” as listed in Schedule ‘A’ Part-XIV. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,64,487.59 inserted by the MES in Schedule ‘A’ Part-XIV.\n 1 LUMP SUM
186 22 FIRE FIGHTING AND SPIRAL STAIRCASE FOR FIRE EXIT (Sch 'A' Part-XIV)(A) (MISC))
187 22.01 S&F of Valves, Sluice, flanged of Class PN 1.6, 150 mm (6”) dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.\n 10 EACH
188 22.02 S&F of Valves, Sluice, flanged of Class PN 1.6, 100 mm (4”) dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.\n 12 EACH
189 22.03 S&F of Valves, Sluice, flanged of Class PN 1.6, 80 mm (3”) dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.\n 2 EACH
190 22.04 S&F of 80 mm bore hand operated butterfly valve of pressure not less than 15 Kg/Sqcm all as conforming to relevant IS including jointing and testing complete all as specified and as directed.\n 52 EACH
191 22.05 S&F of Valve, reflux, with by-pass arrangement, 150 mm (6") dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.\n 6 EACH
192 22.06 S&F of Valve, reflux, with by-pass arrangement, 100 mm (4") dia all as conforming to IS-14846 including jointing and testing complete all as specified and as directed.\n 8 EACH
193 22.07 S&F of fire hydrant landing valve type-A (single head outlet) of 63 mm dia conforming to IS 5290 including jointing and testing complete all as specified and as directed.\n 52 EACH
194 22.08 S&F of 63 mm dia RRL Hose type 'A' 15 meter long hose conforming to IS-636 complete with male and female coupling conforming to IS-903 including jointing and testing complete all as specified and as directed.\n 92 EACH
195 22.09 S&F of hose box made of 18 gauge MS Sheet 800 mm x 600 mm x 250 mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red outside and brilliant white inside yard for keeping 2 Nos. hose pipe of length 15 meter each, branch pipe, nozzle, coupling etc. complete all as specified and as directed.\n 46 EACH
196 22.1 S&F of hose reel drum of 20 mm dia and 36 meter length conforming to IS-5132 including jointing and testing complete all as specified and as directed.\n 46 EACH
197 22.11 S&F of Gun metal fire brigade inlet connection (suction collecting head) consisting of four Nos. 63 mm dia instantaneous type male coupling with built-in check valves and 150 mm dia sluice valve (one No. 150 mm dia NRV) and 150 mm dia flanges outlet complete with all accessories all as conforming to relevant IS including testing complete all as specified and as directed.\n 4 EACH
198 22.12 S&F of 63 mm dia instantaneous inlet gun branch pipe with 15 mm bore nozzle short conforming to IS-903 including jointing and testing complete all as specified and as directed.\n 52 EACH
199 22.13 S&F of ICV / Alarm gong (Intermittent hudraulic alarm with alarm gong and water motor alarm) 100 mm all as confirming to relevant IS including testing complete all as specified and as directed.\n 10 EACH
200 22.14 S&F of fire hydrant stand post 80 mm dia GI / MS flanged type, 1.5 Mtr height with provn of single outlet conforming to IS-908 including jointing and testing complete all as specified and as directed.\n 12 EACH
201 22.15 S&F of Sprinkler glass bulb type (Standard response) as per IS : 15106 / TAC guidelines 68 degree temperature rating pendent type including testing complete all as specified and as directed.\n 530 EACH
202 22.16 S&F of Air cushioning tank (Air vessel) 250mm dia x 1000 mm high with dished top, made of minimum 6 mm thick MS pipe / plate complete with 20 mm dia brass air valve (ball type), 20 mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accessories all as confirming to relevant IS including testing complete all as specified and as directed.\n 10 EACH
203 22.17 S&F of Automatic Air Release Valve 50 mm dia suitable for domestic water with 50 mm gun metal stop valve all as confirming to relevant IS including testing complete all as specified and as directed.\n 10 EACH
204 22.18 Supply and laying of pipes ERW steel, 'Heavy Class' including specials, nominal dia 200 mm as per IS 3589 (1981) with minimum thickness 6.0 mm all as confirming to relevant IS including testing complete all as specified and as directed.\n 60 RM
205 22.19 Supply and laying of pipes ERW steel, 'Heavy Class' including specials, nominal dia 150 mm as per IS 3589 (1981) with minimum thickness 6.0 mm all as confirming to relevant IS including testing complete all as specified and as directed.\n 500 RM
206 22.2 S&F of MS ERW pipe 100 mm NB heavy duty including specials duly painted with 2 coats of synthetic enamel paint over coat of zinc chromate primer all as confirming to relevant IS including testing complete all as specified and as directed.\n 300 RM
207 22.21 S&F of MS ERW pipe 80 mm NB heavy duty including specials duly painted with 2 coats of synthetic enamel paint over coat of zinc chromate primer all as confirming to relevant IS including testing complete all as specified and as directed.\n 200 RM
208 22.22 M&L for construction of brick masonry valve pit of internal dimensions 1000 mm x 1000 mm x 1000 mm complete and fabrication of 3.15 mm thck MS sheet cover and angle iron frame made out of 50 mm x 50 mm x 6 mm MS angle iron and one side provided with hinge with locking arrangement and duly painted with two coats of black bituminous paint over a coat of red oxide primer including necessary earth work and PCC work complete all as specified and as directed.\n 6 EACH JOB
209 22.23 M&L for cutting of CI / MS / DI pipes in position for insertion of new tee, branches, valves etc. for bore of pipe upto and including 150 mm complete all as specified and as directed.\n 5 EACH JOB
210 22.24 M&L for Cement Concrete in foundation, filling mass concrete, type-C2, (1:3:6) (using 20 mm graded stone aggregate) for foundation of hose reel box, pipe line thrust block support etc. and finishing the surface even and smooth without using extra cement including necessary formwork complete all as specified and as directed.\n 10 CUM
211 22.25 S&F of Fire extinguisher, ISI marked, Dry Chemical Powder (ABC) type all as confirming to IS : 15683 of capacity 5 Kg with suitable hanging / fixing arrangement on wall etc. complete all as specified and as directed.\n 25 EACH
212 22.26 S&F of Fire extinguisher, ISI marked, Water CO2 / Stored Pressure type all as confirming to IS : 15683 of capacity 9 Ltrs with suitable hanging / fixing arrangement on wall etc. complete all as specified and as directed.\n 50 EACH
213 22.27 S&F of Fire extinguisher, ISI marked, CO2 type all as confirming to IS : 15683 of capacity 4.5 Kg with suitable hanging / fixing arrangement on wall etc. complete all as specified and as directed.\n 25 EACH
214 22.28 Supply and installation of 06 Nos. fire buckets made out of 24 gauge galvanized steel sheet and of capacity 13 Ltrs., painted white inside, red outside and black on bottom and inscribed with letters "FIRE" in black & bold with and including MS stand duly painted with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and provision of Shovel - 01 No., Fire hook - 01 No., Fire beater - 01 No. and manually operated MS bell etc. complete all as specified and as directed.\n 6 EACH JOB
215 22.29 Sub total
216 23 CENTRAL AC PLANT (Sch 'A' Part-XV)
217 23.01 Design, Supply, Installation, testing and commissioning of Microprocessor controlled water cooled centrifugal chiller type air conditioning plant of full load capacity not less than 360 TR (2 x 180TR) and with additional 1 x 180 TR as standby to meet 50% of full load capacity of head load suitable for complete operation with refrigerant R-407C or any non-CFC / non-HCFC based refrigerant with all equipment’s and accessories complete for Hospital Building of 155 BH (Ph-III) at Tezpur, to meet the inside design condition of temp 21 + 2oC and relative humidity 55 + 5% and as per OEM all as conforming to relevant IS complete all as specified and as directed.\n\nNOTE :-\n(i) The tenderer should visit the building / site condition and work out heat load based on the Building Plan, structural specifications, outside / inside parameters and design parameters as given in the tender and ascertain the plant capacity given in the schedule and technical parameters given under relevant schedules / items and PS.\n(ii) In case of any change considered necessary in the technical parameters given under relevant schedules / items and PS and plant capacity given in the schedule to provide the design parameters, the tenderer should furnish the same within 15 days prior to receipt of tender, duly justified with their heat load calculations.\n Item continued as 23.02 1 EACH JOB
218 23.02 (A) Three water cooled scroll chilling units complete and each comprising of following :-\n(i) One set of Multi Scroll Compressor, hermatically sealed type directly coupled with refrigerant cooled Screen Protected drip proof induction motor to run on 3 phase 50 Hz 415 V with necessary suitable starter, suction and discharge ports, automatic modulating capacity control with thermostat, suction strainer, crank case heater, oil separator, forced feed lubrication, internal overload trip, safety switch with gauge panels complete with HP / LP cutouts, anti freezeetc as specified.\n(ii) One set of shell and tube type water cooled condenser with shell and integrally finned copper tubing, complete with safety valves, drain valve, water inlet and outlet valves, hot gas inlet and liquid outlet isolating valves thermometer and pressure gauges at inlet and outlet and purge valves all as specified and as directed.\n(iii) One set of shell and tube water cooled scroll chiller units suitably insulated having shell and plain copper tubes all as specified and as per manufacturers design.\n(iv) One set of MS stand of suitable size and shape fabricated out of channel and angle iron of suitable size painted with two coats of black synthetic enamel paint over one coat of red oxide primer for mounting compressor, motor, condenser, chiller and control panels etc of above specification.\n\n Item continued as 23.03
219 23.03 (v) One set of anti-vibration mounting pads and suitable foundation as per manufacturer’s instruction including necessary foundation, bolts & nuts etc.\n(vi) Refrigerant piping complete with all require fittings and accessories such as thermo-setting expansion valve, refrigerant drier with isolating valves, pilot operated solenoid valves etc. with necessary bracket and support to inter connect compressor, chiller, condenser and expansion valves including insulation of suction lines and chiller lines with fire resisting insulating material of adequate thickness all as per manufacturer’s specifications.\n(vii) Microprocessor based controls comprising of following features :-\n(a) Automatic capacity control reducing energy system.\n(b) Microprocessor controlled pump down system.\n(c) Microprocessor based sequence of starting / stopping of equipment with fixed time delays.\n(d) Alarm history giving cause of tripping.\n(e) Data scanner system including operations instructions.\n(f) Oil pressure failure cut out LP / HP cut out.\n(g) Liquid line indicator.\n(viii) Fail safe features will be equipped with following :-\n(a) Under Voltage protection.\n Item continued as 23.04
220 23.04 (b) Single phasing protection.\n(c) Over load protection.\n(d) Phase imbalance protection.\n(e) Anti-freeze protection.\n(f) Power loss trip and shut down.\n(g) Phase reversal protection.\n(h) Over voltage / surge protection.\n(ix) One set of water flow switch in condenser and chiller water line at inlet and outlet.\n(x) First charge of refrigerant gas R-407 C or any non-CFC /non-HCFC based refrigerant and compressor oil as per manufacturer’s recommendation.\n\n(B) Chilled water cooling arrangement comprising of the following :-\n(i) Supply and fixing of MS Class ‘C’, heavy duty ERW chilled water piping of one lot of adequate size including fittings and fixtures duly welded, laid in ground or air, inside / outside the building alongwith necessary clamps, nuts, bolts etc adequately supported on rigid primary and secondary supports complete with balancing valves at chiller inlet and outlet for circulation of chilled water from chiller to AHU – 15 Nos. with necessary connection to chilled water expansion tank including with water pressure gauge / thermo meter in chiller inlet and outlet. \n\n Item continued as 23.05
221 23.05 AHU inlet and outlet complete with insulation of fire retardant quality expanded polystyrene moulded pipe section 50 mm thickness and density not less than 20 Kg/Cum covered with a layer of 120 gm/Sqm polythene sheet (as vapour barrier) duly reinforced with 26 gauge chicken wire mesh with buffing all joint and tied down with GI lacing wire and finally finished rigid with 26 gauge aluminium foil cladding, if laid inside the building, and with cement mortar of 1:3 of 12 mm thick, if laid in ground or air outside the building complete with all accessories comprising control valves like butterfly valves, balancing valves, Y-strainers, non-return valves, pressure gauges, thermometers, water flow switches, suitable EPDM bellows etc including excavation, refilling making good the excavated surface wherever the pipes are required to be laid in ground all as per technical requirement / design.\n\n(ii) Three Nos. primary centrifugal chilled water pump set with bronze impeller of suitable type-C (02 Nos. working + 01 No. standby) coupled with TEFC 3-Phase, 4-Pole squirrel cage induction motor suitable for operation on 50 Hz, 415 V AC supply alongwith suitable foundation including base frame as per manufacturer instruction and \n\n Item continued as 23.06
222 23.06 with anti-vibration rubber pads with suitable starter with overload protection, protection against phase reversal and single phase preventer and 03 Nos. dial type (150 mm) water pressure gauge and thermometer with suitable needle valves, butterfly valve on suction and delivery line, suction guide with strainer check valve on delivery line etc all as specified and as directed.\n(iii) Three Nos. secondary centrifugal chilled water pump set with bronze impeller of suitable type-C (02 Nos. working + 01 No. standby) coupled with TEFC 3-Phase, 4-Pole squirrel cage induction motor suitable for operation on 50 Hz, 415 V AC supply alongwith suitable foundation including base frame as per manufacturer instruction and with anti-vibration rubber pads with suitable starter with overload protection, protection against phase reversal and single phasing and 03 Nos. dial type (150 mm) water pressure gauge and thermometer with suitable needle valves, butterfly valve on suction and delivery line, suction guide with strainer check valve on delivery line etc all as specified and directed and including variable frequency drive.\n\n Item continued as 23.07
223 23.07 (iv) Chilled water expansion tank of adequate capacity made out of minimum 04 mm thick MS plate construction including insulation with 13 mm thick cross link polyethylene of self adhesive with aluminium foil protection. The tank shall be complete with necessary connection for piping vent and made up connection with necessary float valve, drain valve, incoming / outgoing line valves and drain connection with control valve and necessary inter-connection complete all as specified.\n(C) Condenser Water Cooling arrangement comprising of following :-\n(i) Three Nos. centrifugal type Condenser cooling water pump set of suitable type-C capacity with bronze impeller each of 50% capacity (02 Nos. working + 01 No. standby) coupled with TEFC 3-Phase, 4-Pole squirrel cage induction motor suitable for operation on 50 Hz, 415 V AC supply alongwith suitable foundation base frame as per manufacturer instruction and with anti-vibration rubber pads with suitable starter with overload protection, protection against phase reversal and single phasing and 03 Nos. dial type (150 mm) water pressure gauge, thermometer with suitable needle valves, butterfly valve on suction and delivery line, suction guide with strainer, check valve on delivery line etc all as specified and directed.\n\n Item continued as 23.08
224 23.08 (ii) Two Nos. induced draft FRP cooling tower of suitable type-C capacity of heat rejection capacity minimum 20% higher than total tonnage of AC plant (i.e. 360 TR x 1.2) for a water flow as recommended by OEM, made out with FRP type body and water basin, PVC filling with integral louvers and drift eliminator, filled with spray nozzles of having self-rotating type sprinklers, statically and dynamically balanced counter flow type fan direct driven with TEFC squirrel cage induction motor with suitable starter, suction screen, made up quick fill arrangement, overflow and drain connection switch necessary valves and suitable inspection ladder, access arrangement for cooling tower interior, cement concrete foundation, steel supporting structure, anti-vibration mountings etc complete all as specified and as directed and with necessary PCC hard standing around the area of width not less than 750 mm from the platform of the cooling tower.\n(iii) One lot of condenser water pipe line and fitting made out of MS ‘C’ grade from makeup water tank to cooling tower, from cooling tower to Condenser and return to cooling tower through condenser cooling water pumps with all controls and fittings complete with materials alongwith necessary clamps, vibration isolators and fittings such as tees, bends, necessary butterfly valves, check valves, Y-type strainer, non-return valves, suitable EPDM bellows and pressure gauges with needle valves, thermometeretc adequately supported on rigid supports etc all as specified and required.\n Item continued as 23.09
225 23.09 (iv) Two Nos. PVC makeup water tank of 10,000 Ltrs capacity, ISI marked, Triple layered, duly interconnected and erected on RCC staging of suitable height and size with suitable RCC slab with necessary foundation and PCC hard standing on surrounding area to a width of not less than 500 mm from the platform of makeup water tank including inlet and outlet, overflow connection and float valve assembly with necessary inter connection alongwith suitable control valves.\n\n(D) Required number of Air Handling Unit :-\n15 Nos. each having 8500 cfm capacity indoor type with necessary provision of air mixing chambers for fresh air draw through type having technical specification all as specified and as directed of sectionalized construction, factory made, floor mounted double skin type made of 25 mm thick modular AHU panels with GI casing of thickness 24 Gauge pre-coated outside layers and 24 Gauge inside layer injected with CFC free polyurethane foam (PUF) of 38 Kg/Cum density insulation complete with blower section, chilled water cooling coil section IP-55 Class F insulation motor and drive set, filter section with muffler and access door to attend the motor / fan and all accessories with lighting provision and all accessories with suitable starter and controls etc and each AHU comprising of following :-\n\n Item continued as 23.10
226 23.1 (i) 6/8 row Cooling coil of copper tube with aluminium fins with automatic controlled anti-freeze thermostat suitable for chilled water.\n(ii) Blower section complete with blower having forward curved centrifugal fan for weather maker suitable for static pressure all as specified and as directed, with minimum 2 bends GSS eliminators with suitable capacity TEFC squirrel cage induction motor (IP 55 and class F insulation) for operation on 3 phase 415 V 50 Hz AC supply with mounting frame work.\n(iii) Inbuilt pan humidifier – 01 Set.\n(iv) 50 mm thick washable type pre-filters with filter element made out of synthetic non-woven media supported by HDPE mesh on both side including stitching in diamond pattern complete including frame and suitable for efficiency 90% down to 10 micron EU-3 type-C complete with mounting frame work.\n(v) Secondary dry type cleanable and easily maintainable air filter supported by GI wire and folder to form accordion plate having an efficiency of 99% down to 5 micron EU-5 TYPE complete with mounting frame works.\n(vi) Drain connection, stainless steel (SS-304) drain pan and with necessary GI pipe for drain out the condensate to the open drain of the building.\n\n Item continued as 23.11
227 23.11 (vii) Acoustic insulation of AHU all as per manufacturer’s design and type to maintain 50 decibel and all as specified.\n(viii) Chilled water lines with suitable butterfly valve, Y strainer, pressure gauge, temperature gauge, on the supply line and with suitable butterfly valve, balancing valve, 3-way modulating control valve, pressure gauge, temperature gauge etc on the return chilled water line complete all as specified and as shown in the schematic diagram and as required.\n(E) Strip Heaters :-\nStrip Heaters for winter heating and monsoon reheating with strip heaters, controlled by humidistat, heating thermostat – 18 KW for each AHU x 15 AHUs.\n\n(F) Air Distribution System :-\nAir Distribution System including supply air duct made out of galvanized steel sheet, ducting from AHU to condition room, of commercial grade VIII as per IS-655 with suitable MS supporting arrangements including primary and secondary support from RCC roof / ceilings / walls / traverse for ducts inside the conditioned space and from wall / traverse / floor / ground for ducts outside non-conditioned space including \n\n Item continued as 23.12
228 23.12 necessary foundation for support etc complete with adjustable dampers, vanes etc complete as per specification and as per ducting layout marked tentatively on site plan to provide the required quantity of supply air in the condition room and to achieve the designed parameters with desirable velocity and noise level with uniform distribution of air and comprising of following accessories :-\n\n(i) New Mechanical Fire dampers of model CFD-FL approved 90 Minutes Fire Rating as per UL-555-1995 by CBRI in existing main supply air duct layout drawing including control wiring. The dampers shall be made of heavy gauge galvanized steel having multi blade construction. The blades shall be fitted with chrome plated shaft and self-lubricated phosphorous bronze bushes. The dampers shall also be provided with jam seal (compression type) on sides to prevent spread of smoke and fire. The blades of the dampers are held in the ‘open’ position by a high tensile spring and a fusible link. The fusible link should be UL stamped and operates at 74oC, causing the damper to close immediately on break fire to prevent the spread of fire through the ducts. Control wing from fire damper to AHU control panel to switch off AHU motors, heaters and humidifier when the fire damper is closed in the event of fire.\n\n Item continued as 23.13
229 23.13 (ii) Powder coated extruded aluminium section fresh air grill of suitable size in AHU room with GI volume control dampers, bird screen etc complete as required and as specified.\n(iii) Supply air diffuser duct mounted double louvered and double deflection type of powder coated aluminium with volume control dampers of required sizes and numbers.\n(iv) Return air grill duct mounted single louvered double deflection type of powder coated aluminiumof required sizes and numbers fitted on ducts all as shown in the drawing.\n(v) Acoustic lining to the main supply air duct from AHU upto a minimum length of 6 mtrs with 25 mm thick of Resin bonded glass wool of density 32 Kg/Cum overlapped with RO tissue, sealing all joints and finally covered with 0.5 mm perforated aluminium sheet.\n(vi) Humidistat cumdigital type thermometer – 01 No. with 99% efficiency and quick response time in each AHU room, Total AHU Room – 15 Nos.\nNOTE :Return air will come back from Air conditioned room to AHU room from above false ceiling provided in passage.\n\n Item continued as 23.14
230 23.14 (G) LT Panel :-\nCubical type vermin proof, dust proof, not less than IP-43 protection class, factory made by manufacturers having type test report of CPRI floor mounted main LT electric panel board totally enclosed with separate chambers for bus bars, cable entry / exit and meter for housing voltmeter / ammeters / KWH meters selector switch / indicator lamp etc suitable for 3 phase, 415 V, 50 Hz of 35 MVA rupturing capacity with copper bus bars (04 Nos.) of suitable rating fabricated from 2 mm thick CRCA sheet powder coated through seven tank process facility for pricking and degreasing duly inter connected with all allied accessories as required complete with following mountings :-\n\n(i) Necessary electric wiring for inter connection and inter locking as per specification with PVC multi core copper cable of suitable size but not less than 2.5 Sqmm.\n(ii) Status indication (ON, OFF) of each compressor, pumps, AHUs, cooling tower motor, heater banks at AHU, humidifier, dampers and other essential electrical components.\n\n Item continued as 23.15
231 23.15 (iii) Main incoming Air Circuit Breaker four pole 1250 Amps 50 KA 3 phase 415 V electrical draw out type microprocessor relay with over load protection, short circuit current protection, instantaneous current protection, ground fault protection, operation with AC/ DC charging motor and standard accessories as per OEM. Make :Legrand, L&T, Siemens, ABB, C&S Electri Ltd, Schneider, GE – 01 No. and busbar at incoming for 3 incoming of 31/2 x 400 Sqmm cable & free space below ACB for proper connection.\n(iv) Outgoing MCCB with rupturing capacity 50 KA – 03 Nos. suitable for scroll chilling unit and 01 No. spare, outgoing MCCB with rupturing capacity 25 KA – 15 Nos. suitable for AHU, heater & humidifier control panel + 2 Nos. spare, outgoing MCCB with rupturing capacity 25 KA – 03 Nos. suitable for condenser pump, outgoing MCCB with rupturing capacity 25 KA – 03 Nos. suitable for primary chiller pump, outgoing MCCB with rupturing capacity 25 KA – 03 Nos. suitable for secondary chiller pump, outgoing MCCB with rupturing capacity 25 KA – 02 Nos. for cooling tower, outgoing MCB TPN 32 A 10 KA – 03 Nos. (spare) outgoing MCB DP 32 A 10 KA – 03 Nos (Spare).\n\n Item continued as 23.16
232 23.16 (v) One digital tamper proof energy meter (KWH) and one set of LED type indicator lamp, digital voltmeter with inbuilt selector switch, at incoming, digital ammeter with suitable CTs with selector switch at incoming, individual digital ammeter with suitable CTs with selector switch for all motors.\n(vi) Starter for chiller units will be fixed in microprocessor control panel, space for starters eg. Primary chiller pumps – 03 Nos., secondary chiller pumps – 03 Nos. condenser pumps – 03 Nos. Cooling tower – 02 Nos. in above LT Panel (starters considered in respective item of equipment shall be fixed in this space). Starters and power contactors for AHU, strip heater, humidifier will be installed in control panel of AHU.\nNOTE : Starters with power contactors of suitable capacity for starting / stopping motors, over load relay, single phase preventer for all motors with trip button and toggle switch wherever required to be provided. Starters shall be fully automatic star delta starters for motors of capacity above 5HP & DOL starters for motors of capacity 5HP and below with necessary interlocking for safe operation of AC plant.\n\n Item continued as 23.17
233 23.17 (vii) Control Panel for AHU, strip heaters & humidifier – 15 Nos. :-\nCubical type vermin proof, dust proof, not less than IP-43 protection class, factory made by manufacturers having type test report of CPRI floor mounted main LT electric panel board totally enclosed with separate chambers for bus bars, cable entry / exit and metal for housing voltmeter / ammeters / KWH meters selector switch / indicator lamp etc suitable for 3 phase, 415 V, 50 Hz of 35 MVA rupturing capacity with copper bus bars (04 Nos.) of suitable rating fabricated from 2mm thick CRCA sheet powder coated through seven tank process facility for pricking and degreasing duly inter connected with all allied accessories as required complete with following mountings :-\n\n(i) Necessary electric wiring for inter connection and interlocking wiring as per specification with PVC multi core copper cable of suitable size but not less than 2.5 Sqmm.\n(ii) Status indication (ON, OFF) of each AHUmotor, strip heaters, humidifier, dampers and other essential electrical components.\n(iii) Main incoming MCCB of suitable capacity with rupturing capacity 25 KA. – 01 No.\n\n Item continued as 23.18
234 23.18 (iv) Outgoing MCCB of suitable capacity with rupturing capacity 25 KA – 01 No. suitable for AHU Motor.\n(v) Outgoing MCCB of suitable capacity with rupturing capacity 25 KA – 01 No. suitable for strip heaters.\n(vi) Outgoing MCCB of suitable capacity with rupturing capacity 10 KA – 01 No. suitable for humidifier.\n(vii) Automatic Star Delta starter with power contactors of suitable capacity for starting / stopping AHU motor with over load relay, single phase preventer with trip button and toggle switch. (This starter is considered in respective item of AHU and to be fixed in this LT panel.)\n(viii) Power contactors to make on/ off of strip heaters in steps controlled by heating humidistat and heating thermostat. Strip heaters shall have over load protection. \n(ix) DOL starter for humidifier controlled by humidistat.\n(x) One No. electronic digital thermometer with necessary sensors and switching arrangement for each AHU room (total 15 nos.) to display temperature of return air.\n\n Item continued as 23.19
235 23.19 (xi) Power cabling of adequate size and sufficient core from LT panel board to electric motors and other electrical equipment (03 Nos. Scroll Chilling Unit, 03 Nos. Condenser Pump, 06 Nos. Chilled water pumps, 02 No. Cooling Tower motor, AHU control panel to AHU Motor, strip heaters, humidifier – 15 Sets and other allied electrical equipment if any with multistranded copper conductor XLPE insulated, armoured cable laid neatly and in straight line in trenches / on wall / in cable trays with necessary saddles and clamps including copper lugs of suitable size and cable glands, etc complete all as specified and as per IE rules and electrical codes.\n(xii) Power cabling of adequate size and sufficient core from main LT panel to AHU control panel – 15 Nos. with multi stranded aluminium conductor XLPE insulated armoured cable laid neatly in trenches / on wall in cable tray including Aluminium lugs and cable gland etc complete all as specified and as per IE rules and electrical code.\n\n(xiii) Control wiring with PVC insulated copper conductor of suitable size with No. of cores as required cable on wall / cable tray etc and armoured PVC insulated, sheathed stranded copper conductor cable of suitable size with No. of cores as required when laid in trenches underground.\n\n Item continued as 23.20
236 23.2 (xiv) Earthing :-\n(a) M&L for earthing complete with Galvanized steel earth plate 600x600x6.0 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to GI strip of size 32x6 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel including excavation and earth work supplying and laying charcoal dust, common salt, PCC (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) as in chamber and MS angel iron frame 40x40x3 mm and RCC cover 40 mm thick (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) reinforced with 8 mm dia TMT bars @ 75 mm c/c both ways with MS handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI pipe light grade for watering all as shown in electrical plate No. 3 of SSR Part-I of 2009 and connected to earth test point including testing complete all as specified and as directed. (02 Nos. of main LT panel, 04 Nos. for AC plant equipment, 02 Nos. each for AHU control panel of one wing x 5 wing i.e. A, B, C, D, E)\n Item continued as 23.21
237 23.21 (b) Earthing busbar made out of 32 x 6 mm GI strip mounted on insulators suitable for 02 Nos. incoming and No. of outgoings as required for AC plant equipment -02 Sets.\n(c) Two earthing connection to LT panel with GI strip 32 x 6 mm.\n(d) Two earthing connection from earth bus bar with GI strip 32x6 mm to scroll chillers.\n(e) Two earthing connection from earth bus bar with GI strip 25 x 4 mm for motor of capacity 10 HP and above two earthing connection from earth bus bar with GI wire 4 mm dia for motor of capacity less than 10 HP.\n(f) Two earthing connection with GI strip 25x4 mm to each AHU control panel & AHU shall be connected\n\n(H) Miscellaneous Items :-\n(i) One Display board of size not less than 1 x 1 m showing schematic diagram and flow chart of the AC plant drawn on Acrylic white sheet with coloured paints duly marking the details duly fabricated with suitable aluminium frame.\n\n Item continued as 23.22
238 23.22 (ii) Supply and fixing glow sign board of Central AC plant size 3000x600x300 mm, weather proof made of MS angle 50 x 50 x 6 mm with white acrylic sheet 2 mm thick and writing “Central AC Plant 155 BH Ph-III, GE (S) Tezpur” with arial black font with suitable size not exceeding 150 mm and minimum size 100 mm and provision of 5 Nos. of LED tube light 1 x 20 Watt and other accessories and grouting on floor / roof with suitable primary and secondary supports.\n(iii) S&F of fire point comprising of water (Stored pressure) fire extinguisher (IS:6234) 9 Ltr capacity -02 Nos. dry chemical powder (ABC) extinguisher (IS:2171) 5 Kg capacity – 02 Nos, light weight squeeze grip type CO2 extinguisher (IS:2878) 3 Kg capacity – 02 Nos.\n(iv) Rubber matting of size 1x2m, 19 mm thick for LT panel – 02 Nos.\n(v) Painting with two coats of synthetic enameled paint over one coat of red oxide primer of all mild steel pipe / structure as per the standard colour of the central AC plant.\n\n(J) Minor Civil Work :-\nAny other minor masonry work required for erection and smooth functioning of AC plant such as :-\n\n Item continued as 23.23
239 23.23 (i) Foundation for pumping sets, motor, chiller unit, chilled water pipe, air handling unit, cooling tower make up water tank, expansion tank etc as per manufacturer design complete.\n(ii) Excavation for chilled water pipe line work, cable etc.\n(iii) Making good damaged civil work in fixing Ducts laying pipelines collars etc.\n(iv) All other civil work required for testing and commissioning of the plant.\n(v) All mild steel work fabricated in rolled steel sections, MS Plates, flats round bolts and nuts etc for supporting/ jointing / fastening condenser water pipes, chilled water pipes, make up and drains water pipes etc.\n(vi) Painting with two coats of synthetic enameled paint over one coat of red oxide primer of all mild steel pipe / structure as per the standard colour coding of the central AC Plant.\n(vii) Stenciling on pipe line showing arrow / indicator for flow of water / refrigerant / chilled water / hot water with distinguished colour and stenciling of name of major components for identification and full proof operation of switch gears / indicators.
240 23.24 Sub total
241 24 DG SET (Sch 'A' Part-XVI)
242 24.01 Lump sum price worked out by the Contractor for “(DG SET)” as listed in Schedule ‘A’ Part-XVI. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 30,183.00 inserted by the MES in Schedule ‘A’ Part-XVI.\n 1 LUMP SUM
243 25 DG SET (Sch 'A' Part-XVI(A) (MISC))
244 25.01 Supply, installation, testing and commissioning of silent built-in within an acoustic enclosure diesel engine driven generating set water cooled including AMF panel for standby power supply 415 Volts, 03-Phase, 4-Wire, 50 Cycles/Sec, 500 KVA (400.00 KW) or next higher standard size available at 0.8 power factor complete with alternator directly coupled to diesel engine, mounted on common base frame and complete with self-starter, fuel tank capacity not less than 8 hours fuel requirement and battery as recommended by OEM, battery leads, sound proof canopy etc. with features for automatic shutdown in the event of a circuit failure condition arising from low oil pressure, high coolant temperature, over speed etc. and microprocessor based gen-set controller with the following under-mentioned features and all as specified and as directed.\n\n(a) Alphanumeric LDC display with LED backlight.\n(b) Operator interface.\n(c) Suitable to provide a record of most recent fault conditions and fault history.\n(d) Complete alternator data, viz. voltage, Ph-Ph, Ph-neutral, KVA, Frequency etc.\n(e) Complete engine data viz. starting battery voltage, engine temperature, engine running hours, engine oil pressure etc.\n(f) Control including provision of service adjustment and calibration of DG control functions.\n Item Continued as 25.02 1 EACH
245 25.02 GENSET SPECIFICATIONS :-\nPrime Mover Rating : 500 KVA / 400.00 KW\nCurrent Rating : 695.65 A\nNo. of Phases : 03\nPower Factor : 0.8 (Lag)\n\nENGINE SPECIFICATIONS :-\nOutput Prime : 448 KWm\nAspiration : Turbocharged-aftercooled.\nNo. of Cylinders : 06, In line.\nRPM : 1500\nGovernor : Mechanical\n\nALTERNATOR SPECIFICATIONS :-\nVoltage : 415\nRPM / Frequency : 1500/50 Hz\nEnclosure : IP 23\nVoltage Regulation (Max) : +/- 1%.\nInsulation Class : H Class\n\nConformance Standards :-\nIS 4722, BS 5000, IS 1460, ISO 8528, BS 5514, ISO 3046.\n\nMake and Size of Battery : As recommended by OEM.\n\n Item Continued as 25.03
246 25.03 AMF PANEL SPECIFICATIONS :-\n\nASEB I/C : Air Circuit Breaker (ACB), 4-Pole having breaking capacity 50 KA of rating 1000 A, manual draw-out (MDO) type with LSING Protection, LCD Display, Communication through RS-485 Port, True RMS Sensing, Current/Voltage/Power Measurement, Thermal Memory, Fault Indication, Zone Selectivity, Harmonics etc. – 01 No.\n\nDG I/C : Air Circuit Breaker (ACB), 4-Pole having breaking capacity 50 KA of rating 1000 A, manual draw-out (MDO) type with LSING Protection, LCD Display, Communication through RS-485 Port, True RMS Sensing, Current/Voltage/Power Measurement, Thermal Memory, Fault Indication, Zone Selectivity, Harmonics etc. – 01 No.\n\nAMF O/G : Air Circuit Breaker (ACB), 4-Pole having breaking capacity 50 KA of rating 1000 A, manual draw-out (MDO) type with LSING Protection, LCD Display, Communication through RS-485 Port, True RMS Sensing, Current/Voltage/ Power Measurement, Thermal Memory, Fault Indication, Zone Selectivity, Harmonics etc. – 01 No.\n\nThe size / rating of all the connected accessories viz. Contactors, relays, timers, bus-bars, connecting cables etc. of the AMF Panel shall be in conformity with the I/C and O/G ACBs/MCCBs.\n\n Item Continued as 25.04
247 25.04 NOTE :- \n1. Design / Drawing / BOM of the AMF Panel and DG Set showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Necessary PCC foundation / plinth shall be as per the recommendations of OEM and cost of the same is deemed to be included in the quoted rates.\n3. The electrical connection of digital Multi-functional Meter in the AMF panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, Power Factor, Frequency etc. can be don of both SEB mains and DG mains.\n4. The cost of servicing including minor repairs / replacement such as topping up of coolant, engine / lube oil, diesel as well as lube-oil filters including periodical checking of the complete DG set and AMF Panel for the complete defect liability period as and when required is deemed to be included in the quoted rates.\n5. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.\n6. The quoted rate shall be deemed to be inclusive of first fill of engine oil and final successful acceptance test.\n7. The quoted rate shall be deemed to be inclusive of 8 Hrs test run at site as specified in the PS in presence of rep of Accepting Officer, all testing arrangements / equipments, resistive load including POL shall be made available by the contractor.
248 25.05 Supply, installation, testing and commissioning of silent built-in within an acoustic enclosure diesel engine driven generating set water cooled including AMF panel for standby power supply 415 Volts, 03-Phase, 4-Wire, 50 Cycles/Sec, 600 KVA (480.00 KW) or next higher standard size available at 0.8 power factor complete with alternator directly coupled to diesel engine, mounted on common base frame and complete with self-starter, fuel tank capacity not less than 8 hours fuel requirement and battery as recommended by OEM, battery leads, sound proof canopy etc. with features for automatic shutdown in the event of a circuit failure condition arising from low oil pressure, high coolant temperature, over speed etc. and microprocessor based gen-set controller with the following under-mentioned features and all as specified and as directed.\n(a) Alphanumeric LDC display with LED backlight.\n(b) Operator interface.\n(c) Suitable to provide a record of most recent fault conditions and fault history.\n(d) Complete alternator data, viz. voltage, Ph-Ph, Ph-neutral, KVA, Frequency etc.\n(e) Complete engine data viz. starting battery voltage, engine temperature, engine running hours, engine oil pressure etc.\n(f) Control including provision of service adjustment and calibration of DG control functions.\n\n Item Continued as 25.06 1 EACH
249 25.06 GENSET SPECIFICATIONS :-\nPrime Mover Rating : 600 KVA / 480.00 KW\nCurrent Rating : 834.78 A\nNo. of Phases : 03\nPower Factor : 0.8 (Lag)\n\nENGINE SPECIFICATIONS :-\nOutput Prime : 530 KWm\nAspiration : Turbocharged-aftercooled.\nNo. of Cylinders : 12, "Vee".\nRPM : 1500\nGovernor : Mechanical\n\nALTERNATOR SPECIFICATIONS :-\nVoltage : 415\nRPM / Frequency : 1500/50 Hz\nEnclosure : IP 23\nVoltage Regulation (Max) : +/- 1%.\nInsulation Class : H Class\n\nConformance Standards :-\nIS 4722, BS 5000, IS 1460, ISO 8528, BS 5514, ISO 3046.\n\nMake and Size of Battery : As recommended by OEM.\n\n Item Continued as 25.07
250 25.07 AMF PANEL SPECIFICATIONS :-\n\nASEB I/C : Air Circuit Breaker (ACB), 4-Pole having breaking capacity 50 KA of rating 1250 A, manual draw-out (MDO) type with LSING Protection, LCD Display, Communication through RS-485 Port, True RMS Sensing, Current/Voltage/Power Measurement, Thermal Memory, Fault Indication, Zone Selectivity, Harmonics etc. – 01 No.\n\nDG I/C : Air Circuit Breaker (ACB), 4-Pole having breaking capacity 50 KA of rating 1250 A, manual draw-out (MDO) type with LSING Protection, LCD Display, Communication through RS-485 Port, True RMS Sensing, Current/Voltage/Power Measurement, Thermal Memory, Fault Indication, Zone Selectivity, Harmonics etc. – 01 No.\n\nAMF O/G : Air Circuit Breaker (ACB), 4-Pole having breaking capacity 50 KA of rating 1250 A, manual draw-out (MDO) type with LSING Protection, LCD Display, Communication through RS-485 Port, True RMS Sensing, Current/Voltage/ Power Measurement, Thermal Memory, Fault Indication, Zone Selectivity, Harmonics etc. – 01 No.\n\nThe size / rating of all the connected accessories viz. Contactors, relays, timers, bus-bars, connecting cables etc. of the AMF Panel shall be in conformity with the I/C and O/G ACBs/MCCBs.\n\n Item Continued as 25.08
251 25.08 NOTE :- \n1. Design / Drawing / BOM of the AMF Panel and DG Set showing the dimensions is to be obtained from the OEM / Auth supplier and is to be got approved from GE before placing final order to the manufacturer.\n2. Necessary PCC foundation / plinth shall be as per the recommendations of OEM and cost of the same is deemed to be included in the quoted rates.\n3. The electrical connection of digital Multi-functional Meter in the AMF panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, Power Factor, Frequency etc. can be don of both SEB mains and DG mains.\n4. The cost of servicing including minor repairs / replacement such as topping up of coolant, engine / lube oil, diesel as well as lube-oil filters including periodical checking of the complete DG set and AMF Panel for the complete defect liability period as and when required is deemed to be included in the quoted rates.\n5. Anything missed out in the technical specifications but technically required for efficient working of the system is deemed to be included in the quoted rates.\n6. The quoted rate shall be deemed to be inclusive of first fill of engine oil and final successful acceptance test.\n7. The quoted rate shall be deemed to be inclusive of 8 Hrs test run at site as specified in the PS in presence of rep of Accepting Officer, all testing arrangements / equipments, resistive load including POL shall be made available by the contractor.\n
252 25.09 Sub total
253 26 HOSPITAL SIGNAGE (Sch 'A' Part-XVII)
254 26.01 Lump sum price worked out by the Contractor for “(HOSPITAL SIGNAGE)” as listed in Schedule ‘A’ Part-XVII. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 30,805.50 inserted by the MES in Schedule ‘A’ Part-XVII.\n 1 LUMP SUM
255 27 HOSPITAL SIGNAGE (Sch 'A' Part-XVII(A) (MISC))
256 27.01 S&F of single sided 3 Watts red LED signage (EXIT) with built-in battery backup for 2 hours complete all as specified and as directed. \nMAKE : Bajaj product code 220209 or equivalent in Philips / Wipro.\n 10 EACH
257 27.02 S&F of double sided 3 Watts green LED signage (EXIT) with built-in battery backup for 2 hours complete all as specified and as directed. \nMAKE : Bajaj product code 220210 or equivalent in Philips / Wipro.\n 3 EACH
258 27.03 S&F of double sided 3 Watts green LED signage (STAIR) with built-in battery backup for 2 hours complete all as specified and as directed. \nMAKE : Bajaj product code 111501 or equivalent in Philips / Wipro.\n 43 EACH
259 27.04 S&F of double sided 3 Watts green LED signage (TOILET) with built-in battery backup for 2 hours complete all as specified and as directed. \nMAKE : Bajaj product code 111505 or equivalent in Philips / Wipro.\n 44 EACH
260 27.05 S&F of double sided 3 Watts green LED signage (LIFT) with built-in battery backup for 2 hours complete all as specified and as directed. \nMAKE : Bajaj product code 111503 or equivalent in Philips / Wipro.\n 7 EACH
261 27.06 M&L for concealed point wiring with 1.5 Sqmm (nominal cross-sectional area) FRLSH PVC insulated and unsheathed 1100 V grade multi-stranded copper conductor single core cable drawn through and including stove enameled steel conduit of adequate size with all fittings and accessories including sunk mild steel terminal boxes for mounting modular switches, sockets, regulators etc complete including FRLSH PVC insulated & unsheathed single core multi-stranded copper conductor cable of size 1.5 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly for one socket outlet point 6 A on independent board complete all as specified and as directed. 107 PER POINT
262 27.07 S&F to wall single sided sign board made out of 3 mm thick acrylic sheet with vinyl film letters complete all as specified and as directed.\nNOTE : Sign Boards shall be of various sizes as per requirement. 25 SQM
263 27.08 S&F to wall single sided glow sign board made out of 3 mm thick acrylic sheet with vinyl film letters including necessary LED lighting, PGI Sheet housing etc complete all as specified and as directed.\nNOTE : Sign Boards shall be of various sizes as per requirement. 15 SQM
264 27.09 Sub total
265 28 LIFTS (Sch 'A' Part-XVIII)
266 28.01 Lump sum price worked out by the Contractor for “(LIFTS)” as listed in Schedule ‘A’ Part-XVIII. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 26,320.00 inserted by the MES in Schedule ‘A’ Part-XVIII.\n 1 LUMP SUM
267 29 LIFTS (Sch 'A' Part-XVIII(A) (MISC))
268 29.01 Supply, installation, testing and commissioning of stretches cum passenger lift suitable for 15 passengers (1020 kg) and lift suitable to serve G+3 upper floors with AC variable voltage and variable frequency (VVVF drive) drive complete with all standard accessories, simplex collective selective automatic operation with / without attendant, automatic centre opening doors with V3F door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue drive (ARD) system, full height standard Infra red door sensor with 154 Criss cross beams, built in announcing system without hand set (03 Nos. one each in car, machine room and near ground floor landing door) complete all as specified below :-\n\n(A) Make : OTIS / Johnson / Kone / ECE\n(NOTE : Contractor shall submit detailed construction drawings of lifts being provided with complete specifications as per IS:14665 latest revision, alongwith the tender)\n\n Item continued as 29.02 3 EACH
269 29.02 (a) Type of lift : Stretches cum Passenger (15 Passengers)\n(b) Load capacity : 1020 Kg\n(c) Speed : 0.50 mtr/sec with single speed mortar\n(d) Power supply : 415 V, 3 phase, 4 wire AC, 50 Hz.\n(e) Type of drive : AC variable voltage and variable frequency.\n(f) Type of machine : Gearless\n(g) Car size : 1000x2400 mm (maximum net inside car area - 2.47 Sqmm) as per IS:14665 (Part-3/Sec 1&2):2000\n(h) Car door : Automatic centre opening with V3F door drive sliding type, stainless steel, hairline finish (N-304) for car and landing doors at all floors.\n(j) Car enclosure : Standard manufacturing with MS frame & stainless steel hairline finish (N-304) in standard thickness with LED light fitting on ceiling of appropriate type / size / Wattage and concealed axial flow fan with stainless steel grill and also 02 Nos. vertical down light LED lamp and covered with stainless steel wire mesh all as per OEM.\n(k) Terminal buffers : Special spring buffers.\n(l) Door opening (Inside) : 800 x 2000 mm\n(m) Counter weight shall be of cast iron as recommended by OEM\n(n) Car and counter weight guide : Guide rails of ‘T’ Section Mild Steel as per OEM design.\n\n Item continued as 29.03
270 29.03 (o) Clear Hoist Size : As per OEM. (Bidder shall inspect the same at site before quoting).\n(p) Flooring : Aluminium chequerred plate 5 mm thick complete.\n(q) Signals :-\n(i) Combined luminous hall buttons with VFD hall position indicators at all floors.\n(ii) Vacuum filled Display (VFD) for car position indicator of stainless steel.\n(iii) One No. Car operating panel with Luminous buttons in car.\n(iv) Car direction indicator in car and landing. \n(v) Battery operated alarm bell and emergency light (rechargeable) alongwith suitable maintenance free battery.\n(vi) Overload warning feature in car cabin.\n(vii) Fireman’s switch 01 No. per lift to be installed at Ground floor near landing door.\n(viii) All signal fixture and car operating panel on stainless steel face plate.\n(ix) Full height standard infra red door sensor with 154 criss cross beams.\n\n Item continued as 29.04
271 29.04 (x) Built in announcing system without hand set, 03 Nos. one each for car, Ground Floor and machine room and with one hand set in machine room.\n(xi) The interior of the car should be provided with a device that audibly indicates the floor lift car has reached and indicates that car entrance / exit door is opened or closed. \n(r) Stops & Opening : 4-4 (all opening on the same side).\n(s) Safety Device : As per OEM Design Automatic Rescue Device (ARD) / automatic landing device to be operating with maintenance free batteries for landing all as specified. (Make : OTIS / Johnson / Kone / ECE).\n(t) Operation : Simplex collective selective Automatic operation with / without attendant.\n(u) Two separate earthing complete all as specified in SSR 2009 Part-I, Plate No. 3 and with Aluminium strip of size 25 x 4 mm from ground to lift machine room to be terminated in the control panel, machine and other equipment installed in the machine room.\n(v) Machine Room : Located above the hoist way and details as per OEM. (Bidder shall inspect the same at site before quoting).\n\n Item continued as 29.05
272 29.05 (w) Hoist-Way Construction : RCC wall construction as existing at site, total height from Ground level to slab of machine room – As per OEM. (Bidder shall inspect the same at site before quoting.\n(x) ACVVVF drive shall be of make OTIS / Johnson / Kone / ECE.\n(y) Control System shall be closed loop type.\n(z) Door shall have ACVVVF controlled door operator.\n(za) Faceplate shape shall be Rectangular and stainless steel in Hairline Finish.\n\n(B) (zb) Civil Work : Necessary civil work such as making good disturbed surfaces, modification to landing space to suit car size, necessary foundation to machine etc and one coat of white wash in the lift shaft after completion of lift installation.\n
273 29.06 Supply, installation, testing and commissioning of service cum passenger lift suitable for 10 Passengers (680 Kg) and suitable to serve G+3 upper floors with AC variable voltage and variable frequency (VVVF) drive complete with all standard accessories, simplex collective selective automatic operation with / without attendant, automatic centre opening doors with V3F door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue drive (ARD) system, full height standard Infra red door sensor with 154 Criss cross beams, built in announcing system without hand set (03 Nos. one each in car, machine room and near ground floor landing door) complete all as specified below :-\n\n(A) Make : OTIS / Johnson / Kone / ECE.\n(NOTE : Contractor shall submit detailed construction drawings of lifts being provided with complete specifications as per IS:14665 latest revision, alongwith the tender)\n\n Item continued as 29.07 1 EACH
274 29.07 (a) Type of lift : Service cum Passenger (10 Passengers)\n(b) Load capacity : 680 Kg\n(c) Speed : 1.00 mtr/sec with single speed mortar\n(d) Power supply : 415 V, 3 phase, 4 wire AC, 50 Hz.\n(e) Type of drive : AC variable voltage and variable frequency.\n(f) Type of machine : Gearless\n(g) Car size : Maximum net inside car area - 1.76 Sqmm as per IS:14665 (Part-3/Sec 1&2):2000\n(h) Car door : Automatic centre opening with V3F door drive sliding type, stainless steel, hairline finish (N-304) for car and landing doors at all floors.\n(j) Car enclosure : Standard manufacturing with MS frame & stainless steel hairline finish (N-304) in standard thickness with LED light fitting on ceiling of appropriate type / size / Wattage and concealed axial flow fan with stainless grill and also 02 Nos. vertical down light LED lamp and covered with stainless steel wire mesh all as per OEM.\n(k) Terminal buffers : Special spring buffers.\n(l) Door opening (Inside) : 800 x 2000 mm\n(m) Counter weight shall be of cast iron as recommended by OEM\n(n) Car and counter weight guide : Guide rails of ‘T’ Section Mild Steel as per OEM design.\n\n Item continued as 29.08
275 29.08 (o) Clear Hoist Size : As per OEM. (Bidder shall inspect the same at site before quoting).\n(p) Flooring : Aluminium chequerred plate 5 mm thick complete.\n(q) Signals :-\n(i) Combined luminous hall buttons with VFD hall position indicators at all floors.\n(ii) Vacuum filled Display (VFD) for car position indicator of stainless steel.\n(iii) One No. Car operating panel with Luminous buttons in car.\n(iv) Car direction indicator in car and landing. \n(v) Battery operated alarm bell and emergency light (rechargeable) alongwith suitable maintenance free battery.\n(vi) Overload warning feature in car cabin.\n(vii) Fireman’s switch 01 No. per lift to be installed at Ground floor near landing door.\n(viii) All signal fixture and car operating panel on stainless steel face plate.\n(ix) Full height standard infra red door sensor with 154 criss cross beams.\n\n Item continued as 29.09
276 29.09 (x) Built in announcing system without hand set, 03 Nos. one each for car, Ground Floor and machine room and with one hand set in machine room.\n(xi) The interior of the car should be provided with a device that audibly indicates the floor lift car has reached and indicates that car entrance / exit door is opened or closed. \n(r) Stops & Opening : 4-4 (all opening on the same side).\n(s) Safety Device : As per OEM Design Automatic Rescue Device (ARD) / automatic landing device to be operating with maintenance free batteries for landing all as specified. (Make : OTIS / Johnson / Kone / ECE).\n(t) Operation : Simplex collective selective Automatic operation with / without attendant.\n(u) Two separate earthing complete all as specified in SSR 2010 Part-I, Plate No. 3 and with Aluminium strip of size 25 x 4 mm from ground to lift machine room to be terminated in the control panel, machine and other equipment installed in the machine room.\n(v) Machine Room : Located above the hoist way and details as per OEM (Bidder shall inspect the same at site before quoting).\n\n Item continued as 29.10
277 29.1 (w) Hoist-Way Construction : RCC wall construction as existing at site, total height from Ground level to slab of machine room – As per OEM. Bidder shall inspect the same at site before quoting.\n(x) ACVVVF drive shall be of make OTIS / Johnson / Kone / ECE.\n(y) Control System shall be closed loop type.\n(z) Door shall have ACVVVF controlled door operator.\n(za) Faceplate shape shall be Rectangular and stainless steel in Hairline Finish.\n\n(B) (zb) Civil Work : Necessary civil work such as making good disturbed surfaces, modification to landing space to suit car size, necessary foundation to machine etc and one coat of white wash in the lift shaft after completion of lift installation.
278 29.11 Sub total
279 30 GEYSER (Sch 'A' Part-XIX)
280 30.01 Supply, installation, testing and commissioning of water heater storage type electric geyser (vertical type) 25 Ltr capacity with BEE 5-Star rating (minimum) and metallic body procelain enamel glass lined inner tank including fixing arrangement with providing including suitable capacity flexible cable 3-core with 3-pin plug of 16 A capacity maximum 2 mtr length, PVC connection pipe of suitable length for Hot and Cold water, fixing on wall with and including all necessary fitting material i.e. mild steel bolts (Bolts to be grouted), nuts, washers, etc complete all as specified and as directed. 40 EACH
281 30.02 Sub total
282 31 MORTUARY CABINET & WALK-IN COOLER (Sch 'A' Part-XX)
283 31.01 Lump sum price worked out by the Contractor for “(MORTUARY CABINET & WALK-IN COOLER)” as listed in Schedule ‘A’ Part-XX. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 36,271.60 inserted by the MES in Schedule ‘A’ Part-XX.\n 1 LUMP SUM
284 32 MORTUARY CABINET & WALK-IN COOLER (Sch 'A' Part-XX (A) (MISC)
285 32.01 Supply, installation, testing and commissioning Mortuary cabinet suitable for single phase, 230 V, 50 Hz, with 0.55 mm thick exterior and interior finish pre-painted GI Sheet, 0.5 mm thick front finish in stainless steel, including vapour proof incandescent lamp, electric temperature indicator cum controller, 3-phase carriage assembly, one piece stainless steel tray, inbuilt power panel, etc. suitable for unitary type refrigeration system and temperature range 4-6oC of capacity 02 body complete all as specified and as directed. 2 EACH
286 32.02 Supoly, installation, testing and commissioning of Walk-in Cold room of two chambers, freezer room of size 8'x8'x8' consisting of wall and ceiling panel made out of PGI sheet filled with 120 mm PUF insulation and Ante Room of size 5'x5'x8' consisting of wall and ceiling panel made out of PGI sheet filled with 60 mm PUF insulation, for Blood Bank and other low temperature application, anti skid GI flooring on 60 mm PUF, door of suitable dimension, hydraulic door closer, digital temperature indicator, Air cooled low temperature split unit of 2 HP rating with Reciprocating / Scroll Compressors working on R-22R -410a refrigerants to maintain temperature of 4 +2 degree Centigrade at an ambient temperature of 30 degree Centigrade complete all as specified and as directed. 1 EACH
287 32.03 Sub total
288 33 TELEPHONE / INTERCOM / MUSIC CABLE) (Sch 'A' Part-XXI)
289 33.01 Lump sum price worked out by the Contractor for “(TELEPHONE / INTERCOM / MUSIC CABLE))” as listed in Schedule ‘A’ Part-XXI. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,22,192.00 inserted by the MES in Schedule ‘A’ Part-XXI.\n 1 LUMP SUM
290 34 TELEPHONE / INTERCOM / MUSIC CABLE) (Sch 'A' Part-XXI(A) (MISC)
291 34.01 S&F of Telephone jack RJ-11 with shuttes complete all as specified and as directed. 120 EACH
292 34.02 M&L for PVC insulated telephone cable for indoor application confirming to TEC specification GIWIR 06/02 of following size of 0.5 Sqmm ATC unarmoured complete all as specified and as directed :-\n Item Continued as 34.03 to 34.06\n
293 34.03 (a) 1 Pair 800 RM
294 34.04 (b) 5 Pair 100 RM
295 34.05 (c ) 10 Pair 100 RM
296 34.06 (d) 20 Pair 100 RM
297 34.07 S&F of junction DB (upto 20 pair) of telephones complete all as specified and as directed. 20 EACH
298 34.08 M&L for two single core PVC insulated copper conductor of size 1.5 Sqmm multistranded 1100 V grade drawn through steel conduit or duct for musical audio system complete all as specified and as directed.\nNOTE : Conduit & conduit accessories shall be measured and paid separately. 2000 RM
299 34.09 M&L for two single core PVC insulated copper conductor of size 2.5 Sqmm multistranded 1100 V grade drawn through steel conduit or duct for musical audio system complete all as specified and as directed.\nNOTE : Conduit & conduit accessories shall be measured and paid separately.\n 1200 RM
300 34.1 M&L for CA TV co-axial cable 75 Ohms double old / foam type aluminium foil and tinned copper drawn through steel conduit or duct for musical audio system complete all as specified and as directed.\nNOTE : Conduit & conduit accessories wall shall be measured and paid separately.\n 1200 RM
301 34.11 S&F of Distribution booster set for video system for 5/6 TV complete all as specified and as directed. 10 EACH
302 34.12 S&F of Co-axial socket for TV cable connection complete all as specified and as directed. 32 EACH
303 34.13 Sub total
304 35 NURSE CALL SYSTEM (Sch 'A' Part-XXII)
305 35.01 Supply, installation and commissioning of wireless nurse call system for 20 users to facilitate patient assistance consisting of receiver cum digital unit with reset button etc operating on 230 V AC, Single phase, 50 Hz complete all as specified and as directed. 14 EACH
306 35.02 Supply, installation and commissioning of wireless nurse call system for 10 users to facilitate patient assistance consisting of receiver cum digital unit with reset button etc operating on 230 V AC, Single phase, 50 Hz complete all as specified and as directed. 11 EACH
307 35.03 Supply, installation and commissioning of wireless nurse call system for 5 users to facilitate patient assistance consisting of receiver cum digital unit with reset button etc operating on 230 V AC, Single phase, 50 Hz complete all as specified and as directed. 2 EACH
308 35.04 S&F of Wall Remote Call Switch for wireless nurse call system consisting of call and cancel button complete all as specified and as directed.\nNOTE : One nurse call system is for one ward / Dept.\n 375 EACH
309 35.05 Sub total
310 36 HAND DRYER (Sch 'A' Part-XXIII)
311 36.01 Supply and installation of Hand Dryer, automatic 230 V, Plastic body, 1800 Watt, maximum sensor range 20 cm, blowing rate 20 m/sec, hand dry time 10 second with selectric connection etc complete all as specified and as directed.\nMake : Toshi model HK-R6-1AC or equivalent in Askon / Innolife. 12 EACH
312 36.02 Supply and installation of automatic Soap Dispenser, ABS body with infrared sensor, operational with battery complete all as specified and as directed.\nMake : Ascon / Thoshi / Ultramind. 12 EACH
313 36.03 Sub total
314 37 PEDESTAL FAN (Sch 'A' Part-XXIV)
315 37.01 S&F of pedestal fan of 450 mm sweep AC, single phase, 230 V with all necessary fittings and accessories including provision of 3-core PVC insulated PVC sheated 3-Core multistranded copper conductor with 5 Amp plug top complete all as specified and as directed.\nMake : Havells Sprint - 18 HS or equivalent model in Usha / Bajaj. 25 EACH
316 37.02 Sub total
317 38 SHADOWLESS LIGHT / EMERGENCY LIGHT / NIGHT LIGHT (Sch 'A' Part-XXV)
318 38.01 Lump sum price worked out by the Contractor for “(SHADOWLESS LIGHT / EMERGENCY LIGHT / NIGHT LIGHT)” as listed in Schedule ‘A’ Part-XXV. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 9,195.00 inserted by the MES in Schedule ‘A’ Part-XXV.\n 1 LUMP SUM
319 39 SHADOWLESS LIGHT / EMERGENCY LIGHT / NIGHT LIGHT (Sch 'A' Part-XXV)
320 39.01 Supply only LED rechargeable portable emergency light with torch suitable for working on 230 V 50 Hz with battery, backup time 4-6 Hrs, auto on facility complete all as specified and as directed.\nMake : Philips model Ojas or equivalent in Havells / Bajaj. 25 EACH
321 39.02 S&F of shadowless light fitting complete with emergency power unit and battery back up for min 30 minutes (3 kVA), having dome of 810 mm dia, fully counter balanced and fixed on suspension rod, capable of having axial rotation of 360 degree. The unit to be suitable for minor OT and capable for operation on 230 V Single Phase, 50 cycles mains supply having lux level upto 40,000 complete all as specified and as directed. 2 EACH
322 39.03 S&F of mobile shadowless light fitting complete with emergency power unit and battery back up for min 30 minutes (3 kVA), having dome of 810 mm, fully counter balanced and fixed on suspension rod, capable of having axial rotation of 360 degree. The unit to be suitable for minor OT and capable for operation on 230 V Single Phase, 50 cycles mains supply having lux level upto 40,000 complete all as specified and as directed. 3 EACH
323 39.04 M&L for Skirting light white LED 3 x 1 Watt module including flush metal modular type box of 3 modules concealed in wall / roof / floor etc complete all as specified and as directed. 200 EACH
324 39.05 M&L for concealed sub-main wiring alongwith earth wire of size (2x1.50) Sqmm + (1x2.50) Sqmm earth wire, ISI marked, FRLS, PVC insulated, multi stranded, copper conductor, single core cable drawn through and including stove enameled steel conduit with all fittings and accessories ISI marked including cutting chases for conduits & sinking’s for modular boxes and making good to walls, floors etc complete all as specified and as directed.\nNOTE : Two runs of PVC wire, one run of earth wire and one run of steel conduit will be measured as one length.\n 2000 RM
325 39.06 M&L for concealed sub-main wiring alongwith earth wire of size (2x2.50) Sqmm + (1x2.50) Sqmm earth wire, ISI marked, FRLS, PVC insulated, multi stranded, copper conductor, single core cable drawn through and including stove enameled steel conduit with all fittings and accessories ISI marked including cutting chases for conduits & sinking’s for modular boxes and making good to walls, floors etc complete all as specified and as directed. \nNOTE : Two runs of PVC wire, one run of earth wire and one run of steel conduit will be measured as one length.\n 500 RM
326 39.07 S&F MCB DB single pole & neutral 8 way, IP-43, IK-09, double door with 200 Amps rated common bus bar and neutral link complete including blanking plate all as specified and as directed. 9 EACH
327 39.08 S&F MCB DB triple pole and neutral 4 ways (8+12 ways), IP-43, IK-09, double door with 200 Amps rated common bus bar and neutral link complete including blanking plate all as specified and as directed. 1 EACH
328 39.09 M&L for RCBO double pole 2 modules, 240 V, 300mA, 32 Amps, earth leakage overhead and short circuit protection complete all as specified and as directed. 9 EACH
329 39.1 S&F of MCB, SP, 10 KA, 230 V, “C” Curve, 06-25 A, ISI marked complete all as specified and as directed. 30 EACH
330 39.11 S&F of MCB, TPN, 10 KA, 230 V, “C” Curve, 06-25 A, ISI marked complete all as specified and as directed. 1 EACH
331 39.12 Sub total
332 40 CONDUIT PIPE (Sch 'A' Part-XXVI)
333 40.01 Lump sum price worked out by the Contractor for “(CONDUIT PIPE)” as listed in Schedule ‘A’ Part-XXVI. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,76,000.00 inserted by the MES in Schedule ‘A’ Part-XXVI.\n 1 LUMP SUM
334 41 UPS (Sch 'A' Part-XXVII)
335 41.01 Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 0.5 KVA with sealed lead acid battery 12 Volts 42 AH - 01 No. complete all as specified as directed.\nMake of UPS : Microtek / Luminous / Su kam.\nMake of Battery : Exide Power safe / Amaron / Luminous. 15 EACH
336 41.02 Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 1 KVA with sealed lead acid battery 12 Volts 9 AH - 06 Nos. complete all as specified as directed.\nMake of UPS : Microtek / Luminous / Su kam.\nMake of Battery : Exide Power safe / Amaron / Luminous. 10 EACH
337 41.03 Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 2 KVA with sealed lead acid battery 12 Volts 18 AH - 06 Nos. complete all as specified as directed.\nMake of UPS : Microtek / Luminous / Su kam.\nMake of Battery : Exide Power safe / Amaron / Luminous. 5 EACH
338 41.04 Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 3 KVA with sealed lead acid battery 12 Volts 26 AH - 06 Nos. complete all as specified as directed.\nMake of UPS : Microtek / Luminous / Su kam.\nMake of Battery : Exide Power safe / Amaron / Luminous. 5 EACH
339 41.05 Supply, installation and testing on line UPS for 30 min back up single phase AC input 160 to 260 V and output 230 + 1% of capacity 5 KVA with sealed lead acid battery 12 Volts 42 AH - 06 Nos. complete all as specified as directed.\nMake of UPS : Microtek / Luminous / Su kam.\nMake of Battery : Exide Power safe / Amaron / Luminous. 5 EACH
340 41.06 Supply, installation and testing on line UPS for 30 min back up three phase AC input 300 to 450 V and output 415 + 1% of capacity 3 KVA 3-phase 4-wire system with sealed lead acid battery 12 Volts with suitable AH capacity and No. of batteries as per OEM for 30 min backup complete all as specified as directed. 1 EACH
341 41.07 Supply, installation and testing on line UPS for 30 min back up three phase AC input 300 to 450 V and output 415 + 1% of capacity 5 KVA 3-phase 4-wire system with sealed lead acid battery 12 Volts with suitable AH capacity and No. of batteries as per OEM for 30 min backup complete all as specified as directed. 1 EACH
342 41.08 Sub total
343 42 DEMOLITION & DISMANTLING (Sch 'A' Part-XXVIII)
344 42.01 Lump sum price worked out by the Contractor for “(DEMOLITION & DISMANTLING)” as listed in Schedule ‘A’ Part-XXVIII. \nRepresenting ** ___ % ______ percent *Above / Below the lump sum price of Rs. 12,06,244.12 inserted by the MES in Schedule ‘A’ Part-XXVIII.\n 1 LUMP SUM
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.

Copyright © 2020 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail