Design, Supply, Installation, Testing And Commissioning Of Dcs Based Terminal Automation System Comprising Of Tank Truck Loading System, Tank Wagon Loading System, Tank Farm Management System, Photo Pass Management System, Access Control System, Fire Alar, As per Tender-Maharashtra

Indian Oil Corporation Limited-IOCL has published Design, Supply, Installation, Testing And Commissioning Of Dcs Based Terminal Automation System Comprising Of Tank Truck Loading System, Tank Wagon Loading System, Tank Farm Management System, Photo Pass Management System, Access Control System, Fire Alar. Submission Date for this Tender is 07-10-2019. Access Control Systems Tenders in As per Tender Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

21768864
Design, Supply, Installation, Testing And Commissioning Of Dcs Based Terminal Automation System Comprising Of Tank Truck Loading System, Tank Wagon Loading System, Tank Farm Management System, Photo Pass Management System, Access Control System, Fire Alar
Open Tender
Indian
Maharashtra
As per Tender
07-10-2019

Tender Details

Design, supply, installation, testing and commissioning of DCS based Terminal Automation System comprising of Tank Truck Loading System, Tank Wagon Loading System, Tank Farm Management System, Photo Pass Management System, Access Control System, Fire Alarm System, Hydrocarbon Vapours Detection System, Fire Fighting Automation System etc along with associated works at Solapur TOP, Maharashtra

Key Value

Document Fees
Refer document
EMD
INR 2995618.0 /-
Tender Value
INR 84.82 Crore /-

BOQ Items

Name of Work: Design, supply, installation, testing and commissioning of DCS based Terminal Automation System comprising of Tank Truck Loading System, Tank Wagon Loading System, Tank Farm Management System, Photo Pass Management System, Access Control System, Fire Alarm System, Hydrocarbon Vapours Detection System, Fire Fighting Automation System etc along with associated works at Solapur TOP, Maharashtra.
Sl. No. Item Description Item Code / Make Quantity Units
1 10 SUPPLY COMPONENTS PHASE-I 10
2 20 TANK LORRY FILLING 20
3 30 Supply of Microprocessor based Coriolis mass flow meter for white oil application along with display unit and mounting accessories with adjustable screw support,bellow for vibrations etc complete as per specifications and tender document for loading of following main products \nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no additional cost to IOCL. 30
4 40 MS (for line size of 100 mm ) 40 10 EA
5 50 HSD (for line size of 100 mm ) 50 12 EA
6 60 SKO (for line size of 100 mm ) 60 2 EA
7 70 Water (Master MFM for TT calibration) for line size 50 mm along with structural support and required accessories for mounting 70 2 EA
8 80 Supply of Strainer cum Air eliminator with differential pressure transmitter with display unit & keyboard across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 80
9 90 For product line size 100 mm - TLF 90 24 EA
10 100 For Water Line size 50 mm - TT calibration (along with structural support and required accessories) 100 2 EA
11 110 Supply of Multistage Piston type Digital Control Valve (DCV) along with TRV with two nos. isolation valves at inlet and outlet of TRV with associated piping , secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 110
12 120 For product line size 100 mm - TLF 120 24 EA
13 130 For Water Line size 50 mm - TT calibration along with vacuum breaker & isolation ball valve mounted on a spool piece & mounting accessories so that the entire water after DCV is drained into the TT after completion of each batch during TT calibration. 130 2 EA
14 140 Supply of piston type, hydraulically operated ON-OFF Valve along with accessories, secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning ,tubing arrangement as per installation drawing etc for line size 100 mm complete as per specifications and tender document. 140 24 EA
15 150 Supply of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF metering skid complete as per specifications and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 150 42 EA
16 160 Supply of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermo well, mounting accessories etc complete as per specifications and tender document. \n(Mounting at each TLF loading point on main product for line size 100 mm) 160 24 EA
17 170 Supply of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 100 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 170 24 SET
18 180 Supply of top loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm) ,vacuum breaker with associated pipintg for loading arm with the metering skid , Stand post & mounting structure, bonding clip (for bonding of loading arm with TT) etc complete as per specifications and tender document. \nApplication: SKO 180 2 EA
19 190 Supply of bottom loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm), API Coupler, break away coupler, parking stand with compatible API adaptor, Ex-proof/intrinsic safe position sensor for parking stand, associated piping for connecting loading arm with the metering skid , mounting structure etc complete as per specifications and tender document. Application: MS, HSD 190 22 EA
20 200 Supply of vapour recovery arm of size 80 mm NB having 3” (80 NB) with poppeted vapour coupler, break away coupler, NRV, flame arrestor, reducers, mounting structures, parking stand with compatible API adaptor, associated accessories, mounting structure etc complete as per specifications and tender document.\nApplication : MS 200 10 EA
21 210 Supply of Ex-proof Rack Monitors for TT overfill protection system along with accessories like 10 pin gantry plug, ATC copper coiled cable of minimum 8m as per API RP1004 including required support for mounting of the Rack Monitor and gantry plug, etc complete as per specifications and tender document.\nNote: In addition to above, minimum 2 nos. portable Rack Monitor along with accessories and 2 nos. lockable bypass switch are to be provided against total supply of Rack Monitor. 210 12 EA
22 220 Supply of Resistance - Capacitance type Tank Truck grounding unit along with accessories like 3 nos. of heavy duty flexible coiled cables with high quality rugged, heavy duty SS/ brass grounding socket, FLP double compression glands, Ex-Plug, mounting structure etc, complete as per specification and tender documents.\n(2 nos. of coiled cable with socket for TT earthing relay interlocks and 1 no. for separate earthing of TT) 220 12 EA
23 230 Supply of heavy duty SS/brass earthing bolt compatible with offered earthing socket of the grounding unit for mounting on the Tank truck along with accessories like SS nut, lock washer etc complete as per specification and tender document. 230 1500 EA
24 240 Supply of Ex-proof field mounted Remote Interaction Terminal (RIT) along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents. 240 24 EA
25 250 Supply of Ex-proof field mounted Driver Ack Push Button station along with FLP double compression glands and Ex-Proof-plug, structural supports etc complete as per specifications and tender documents. 250 12 EA
26 260 Supply of Microprocessor based Field mounted dual arm Batch Controller with interface to minimum 2 nos. of main product + 2 nos. of blend product + 2 nos. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document.\n\nAlternatively vendor can supply 2 sets of Microprocessor based Field mounted single arm Batch Controller with interface to minimum 1 no. of main product + 1 no. of blend product + 1 no. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc in place of Dual Arm Batch Controller complete as per specification and tender document. 260
27 270 For TLF product loading 270 12 EA
28 280 For TT calibration with water 280 1 EA
29 290 Supply of intrinsically safe / flameproof type proximity card reader along with mounting accessories etc complete as per specifications and tender document for authorisation of TT at 290
30 300 TLF bays (1 no. Per bay) 300 12 EA
31 310 License area Entry barrier gates ( 2 nos. X 2) 310 4 EA
32 320 License area Exit barrier gates ( 1 no. X 3) 320 4 EA
33 330 Security Exit barrier gates ( 1 no.) 330 1 EA
34 340 Security Entry barrier gates ( 1 no.) 340 1 EA
35 350 Near Security Gate/TT parking ( for TT registration ) 350 2 EA
36 360 Supply, configuration and testing of Scratch proof, waterproof Smart cards along with messages printed compatible with proximity card reader complete as per specifications and tender document. 360 1500 EA
37 370 Supply of pre-fabricated Metering Skid (MS structure) for mounting of complete metering equipments as per BOQ and schematic drawing for one main product, one blend product and one additive dosing system. The metering assembly comprises of : \n\nMain product line: Strainer cum Air eliminator, Spool piece with tapping for additive dosing, Online Master Meter proving manifold, MFM,Spool piece with tapping for Temprature Transmitter installation, Pressure transmitter, spool piece with tapping for connecting outlet of TRV, ON-Off valve, DCV, Spool Piece with tapping for Ethanol blending & TRV installation. \n\nBlend Product line: Strainer cum air eliminator, Online Master Meter proving manifold, MFM, Spool piece with tapping for Temperature Transmitter installation, ON-Off valve, DCV, NRV, isolation valve and finally connected to Main stream line tap off point after DCV. \n\nAdditive Dosing System comprises of isolation valve, Additive injection mono block, connecting piping, NRV, isolation valve and finally connecting to Main stream tap off point before MFM. \n\nProvision to be made in the skid for mounting of Batch Controller, Rack Monitor, Grounding unit, RIT, Driver's Ack Push button stations, card reader, FLP sockets, FLP junctions boxes (Power, Signal and Control), FLP power isolator switch, interconnecting cables from respective equipment to JBs, cable trays with covers, glands, support, MS structure,Electroforged galvanized grating, nuts, bolts, gaskets, Tees, bends, elbows, WNRF flanges, nozzles, plugs, isolators, any other equipment if required as per design Engineering etc complete as per specification and tender document. 370 24 MT
38 380 Kindly note, irrespective of facility available or not, each metering skid shall have provision for installation of metering assembly of one main product, one blend product and one additive product as detailed in tender document. \n\nItems including the provision for skid for calibration meters as well.\nNote: \n1. All the equipments, JBs, cable trays, interconnecting cables etc as stated above to be installed and loop tested at factory. Complete assembly to be dispatched at site. The skid to be designed and fabricated by the party taking into consideration of all the equipment sizing, space available for mounting of the skid at the bottom of the gantry etc. The design Engineering along with weight calculation of individual skid excluding equipments to be submitted to IOCL prior to taking up fabrication job for review purpose. Payment shall be made based on theoretical weight calculation of the skid excluding weight of equipments, JBs, cable trays. The rate is also inclusive of surface preparation, painting, transportation of the skid to site etc complete in all respect. \n2. All unuse nozzle/ tapping/ opening to be blind flanged.\n3. For SKO metering SKID, tapping to be provided in the skid for both bottom and top loading as per design Engineering.\n 380
39 390 Supply of barrier gate of minimum boom length of 3 m along with accessories, controllers etc complete as per specification and tender document for installation at following location. 390
40 400 License area Entry gate 400 2 SET
41 410 License area Exit gate 410 2 SET
42 420 Security Exit gate 420 1 SET
43 430 Security Entry gate 430 1 SET
44 440 DISPLAY BOARDS 440
45 450 Supply of weather proof LED bay queuing display board (Minimum 15 lines x 100 mm Character height x 25 characters per line) for outdoor installation at TT parking area / Customer service building along with accessories like public address system, speakers, amplifier, mike, structural steel for mounting of the same, Aluminium canopy/sunshade etc complete as per specifications and tender document. 450 1 EA
46 460 Supply of LED monitor of minimum 55" along with required hardware and software for interfacing with TAS, lockable enclosure (wall / ceiling mounted) for mounting the monitor along with accessories at Driver's Rest Room for repeat display of 15 lines Bay Queue Display board complete as per specification and tender document. Kindly note, no additional payment shall be made for any additional hardware/ software/ cable etc required for integration of the monitor with TAS. 460 1 EA
47 470 Supply of LED monitor of minimum 55" along with required hardware and software for interfacing with TAS, lockable enclosure (wall / ceiling mounted) for mounting the monitor along with accessories, Aluminium canopy/ sunshade etc at invoice room for displaying the list of TTs whose invoice has been generated and TT is still inside license area complete in all respect as per tender requirement. Kindly note, no additional payment shall be made for any additional hardware/ software/ cable etc required for integration of the monitor with TAS. 470 1 EA
48 480 Supply of weather proof three line coloured LED display board with scroll and flash effects (Each line of min. 50 mm Character height x 11 characters per line) for outdoor application near Security Gate/ TT parking Area and license area Entry barrier Gate along with mounting structure, Aluminium canopy/ sunshade, accessories etc complete as per specifications and tender document for displaying the TT Registration no. in bilingual (English + local language) of reported TT whose proximity card has been shown on the PCR adjacent to the display board for TT reporting at security gate/TT parking area, TT status at TT parking area exit gate and the bay no. (Bilingual) etc of the authorised TT reported at license area Entry Gate as per FDR.\n2 nos. for TT reporting + 1 no. at Security Entry gate + 2 nos. per License Area Entry Barrier Gate (2X2) + 1 No. at Security Exit gate; Total - 2+1+4+1=8\nNote : 1 line for display in English & 2 lines for displaying in local language 480 8 EA
49 490 Supply of 3 KL Stainless Steel Mobile Prover tank along with accessories like flanges, ball valves, calibrated sight glass, plunger, hoses, blind flanges, etc mounted on Trailer chassis along with wheels with solid rubber tyres complete as per specifications and tender document.\nNote: Vendor to arrange for prime mover for calibration of MFM at site during entire commissioning and CAMC period at no additional cost to IOCL. 490 1 SET
50 500 Supply of Mobile Master meter (Master MFM) proving system for line size 100mm consisting of Master Mass flow meter with display unit, Master Temperature Transmitter with RTD with Thermo-well, Mounting accessories suitable for installation on 4" line size, 2 nos. isolation ball valve of 100mm, hose pipe, trolley mounted Master Meter Skid with suitable wheels, FLP JB, FLP double compression glands, power adapter along with accessories (if required) for powering of Master Meter, FRLS Copper Armoured Power & Signal Cable of minimum 15m each with compatible FLP power plugs for powering the MFM, integration of Mobile Master MFM with TAS and integration of temperature transmitter with Master MFM, supports for mounting the equipments, pipes, flanges, reducers, gaskets, nuts, bolts, studs etc complete as per specification and tender document. 500 1 SET
51 510 Ethanol Dosing System 510
52 520 Supply of Microprocessor based Coriolis mass flow meter for white oil (Ethanol) application alongwith display unit and mounting accessories with adjustable screw support, reducer (if required) etc for line size 2" suitable for maximum flowrate of 500 LPM complete as per specifications and tender document for ethanol blending.\nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no adddtional cost to IOCL . 520 10 EA
53 530 Supply of Strainer cum Air eliminator for line size 50 mm with differential pressure transmitter across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 530 10 EA
54 540 Supply of Multistage Piston type Digital Control Valve (DCV), NRV, isolation valve for line size 50 mm alongwith accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 540 10 EA
55 550 Supply of Piston type, hydraulically operated, solenoid operated ON-OFF Valve along with accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves , tubing arrangement as per installation drawing etc for line size 50 mm complete as per specifications and tender document. \n 550 10 EA
56 560 Supply of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermowell for line size 50mm, mounting accessories etc complete as per specifications and tender document. \nNote : One no. of additional thermo well along with accessories to be provided and installed on ethanol point for installation of Master Temperature transmitter with RTD. 560 10 EA
57 570 Supply of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 50 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 570 10 SET
58 580 Supply of 1 KL Stainless Steel Mobile Prover tank alongwith accesories like flanges, ball valves, calibrated sight glass, plunger, hoses, blinds flanges, etc mounted on Trailer chassis along with wheels with solid rubber tyres complete as per specifications and tender document.\nNote: Vendor to arrange for prime mover for calibration of MFM at site during entire commissioning and CAMC period at no additional cost to IOCL. 580 1 SET
59 590 Supply of Mobile Master meter (Master MFM) proving system for line size 50mm consisting of Master Mass flow meter with display unit, Master Temperature Transmitter with RTD with Thermo-well, Mounting accessories suitable for installation on 2" line size, 2 nos. isolation ball valve of 50 mm, hose pipe, trolley mounted Master Meter Skid with suitable wheels, FLP JB, FLP double compression glands, power adapter along with accessories (if required) for powering of Master MFM, FRLS Copper Armoured Power & Signal Cable of minimum 15 m each with compatible FLP power plugs for powering the MFM, integration of Mobile Master MFM with TAS and integration of temperature transmitter with Master MFM, supports for mounting the equipments, pipes, flanges, reducers, gaskets, nuts, bolts, studs etc complete as per specification and tender document. 590 1 SET
60 600 Additive dosing System 600
61 610 Supply of additive injection mono block along with accessories for XTRAPREMIUM and XTRAMILE complete as per specification and tender document.\nNote - All the wetted parts within Additive injection panel/ block shall be of SS 316 or better. 610 8 SET
62 620 Supply of Additive tanks (500 Litres each) and pump module for XTRAPREMIUM /XTRAMILE comprising of Additive Tank, Additive Pumps (Two per tank) , Mild Steel SKID, Flameproof Motor, NRV 25 mm, Flanged ball valve 25 mm, Pressure Relief Valve, Pressure Gauge with pulse dampener, Strainer 25 mm, interconnecting pipings (25 mm SS), flanges etc. auxiliary potential free contact/serial communication complete as per specification and tender document. 620
63 630 For Xtramile 630 1 SET
64 640 For XtraPremium 640 1 SET
65 650 Supply of ASTM A106 Gr B Schedule 80 pipe of 25 NB from additive header pipe to additive injection panel at TLF bay complete as per tender document.. 650 200 RM
66 660 Supply of Necessary hardware Like SS Tubing, reducer, Elbows, equal Tee ,unequal tee, Flanges, Coupling, Ball Valve for Isolation, NRV, 15 mm back pressure regulator on return line etc as required for piping and commissioning of the system complete in all respect. 660 1 LS
67 670 Note: Piping from Additive tank skid upto TLF header line up to meter skid along with isolation valve & return line shall be supplied and installed by IOCL. Integration of additive pumps for remote operation, level measurement shall be in the successful bidder's scope. 670
68 680 TLF Header line instruments 680
69 690 Supply of Bulk Air Eliminator as per product line size and flow requirement as per following sizes including mounting structure, foundation etc complete as per specification and tender document. 690
70 700 MS - 2 KL 700 1 EA
71 710 HSD-2.4 KL 710 1 EA
72 720 SKO- 0.4 KL 720 1 EA
73 730 ETHANOL-0.4 KL 730 1 EA
74 740 Supply of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF main header line complete as per specifications and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) (TLF HEADER-5,ITT-2) 740 4 EA
75 750 Tank Farm Management System 750
76 760 Supply of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 760
77 770 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 770
78 780 SKO :2X2 Nos. 780 4 EA
79 790 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges : MS-3X2 Nos.; ETHANOL-2X2 Nos.,HSD -3X2 Nos)- Antena size shall be 6 " or 8" depending upon tank nozzle size 790
80 800 MS-3X2 Nos.; ETHANOL-2X2 Nos.,HSD -3X2 Nos 800 16 EA
81 810 For U/G horizontal product tanks 810
82 820 ETHANOL MS - 1 NO, HSD - 2 Nos, SKO - 1 Nos.; ETHANOL - 2 Nos.; Bio Diesel - 2 Nos. 820 8 EA
83 830 Supply of Non-contact type Radar level gauges with instrument accuracy of +/-3 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 830
84 840 For water tanks : Water-4 Nos.;SLUDGE-1 Nos. 840 5 EA
85 850 Supply of Guided wave RADAR type level gauge with transmitter , instrument accuracy of +/- 3 mm or better, in built digital display, along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) as per specification. 850
86 860 For Additive tanks and For Blue Dye Dosing 860 3 EA
87 870 Supply of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. 870
88 880 With minimum 8 elements temperature sensor (for A/G vertical tanks) 880
89 890 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 890
90 900 SKO 900 2 EA
91 910 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 910
92 920 MS,HSD,Ethanol 920 8 EA
93 930 For U/G horizontal product tanks 930
94 940 MS - 1 NO, HSD - 2 Nos, SKO - 1 Nos.; ETHANOL - 2 Nos.; Bio Diesel - 2 Nos. 940 8 EA
95 950 Supply of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 950
96 960 For A/G vertical tanks - Three elements 960
97 970 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 970
98 980 SKO 980 2 EA
99 990 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 990
100 1000 MS,HSD,Ethanol 1000 8 EA
101 1010 For U/G horizontal product tanks-One element 1010
102 1020 MS - 1 NO, HSD - 2 Nos, SKO - 1 Nos.; ETHANOL - 2 Nos.; Bio Diesel - 2 Nos. 1020 8 EA
103 1030 Supply of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 1030
104 1040 For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) 1040 20 EA
105 1050 For U/G Product tanks 1050 8 EA
106 1060 For water tanks 1060 5 EA
107 1070 Supply of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document 1070
108 1080 For A/G Vertical Product tanks 1080 10 EA
109 1090 For U/G horizontal product tanks 1090 8 EA
110 1100 Supply of parallel redundant Communication Interface Units (CIU) including all accessories etc for tank farm management system complete as per specification and tender document. 1100
111 1110 For Primary Radar gauges installed on A/G vertical , under ground product tank, water tank ,slope ,additive & Sludge tank etc. 1110 1 SET
112 1120 For Secondary Radar Gauges installed on A/G product tanks 1120 1 SET
113 1130 Supply of 1 no. of Redundant TFMS Server (Form Factor:Rack ,Mountable in 19" rack ) along with 1 no. rack type (1U) ,one no. Min. 19" LED monitor with keyboard & mouse ,suitable for 19" mounting & 24x7 operation, Licensed OS (latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed software from Radar Gauge OEM etc complete as per specification and tender document. 1130 1 SET
114 1140 Supply of TFMS Workstation with minimum 27" LED colour monitor, keyboard, mouse, KVM Switch, Licensed OS(latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed client software from same Radar Gauge OEM etc complete as per specification and tender document. \nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 1140
115 1150 19" Rack type at Control Room, form factor - Rack, CPU height - 2U (Maximum) 1150 1 EA
116 1160 Blue Dye Dosing System 1160
117 1170 Supply of SKO Blue Dye Dosing Skid comprising of 1 no. SS Blue dye tank of Min. capacity of 500 Ltrs, Blue Dye dosing pumps of minimum capacity of 200 LPH along with Flameproof Motor (2 Nos.) , 1 no. agitator with FLP motor, Mild Steel Skid, NRVs, Flanged ball valves, Pressure Relief Valve, pulse dampener, Pressure transmitter with inbuilt display unit and keypad, solenoid valves (4 nos.), Turbine flow meters (2 nos. - for calculating the volume of SKO receipt into blue dye tank and volume of diluted Blue dye dosed into SKO receipt header line), Rotameter, Strainer with DPT, piping, flanges, auxiliary potential free contacts/serial communication for remote operation and feedback of the pumps, starter etc. complete as per specifications, drawing and tender document.\n\nNote: Blue dye to be injected in SKO receipt header line during product receipt. Provision to be made for diluting the blue dye with SKO tapped from the main receipt line before dosing as per drawing , Auto flushing of blue dye dosing system complete as per specification and tender document. 1170 1 LS
118 1180 Supply of A106 Gr B pipe Dia 25 mm from Blue Dye tank to SKO receipt header line (for dosing purpose) and from SKO receipt header line to Blue dye tank (for dilution & flushing purpose) complete as per specification and tender document. The job includes necessary installation of hardware like reducers, Elbows, equal Tees ,unequal Tees, Flanges, Coupling, Ball Valves for Isolation etc as required complete as per specification and tender document. 1180 300 RM
119 1190 Supply of Exd/FLP Emergency Stop push button stations, mushroom head type with protection cover to avoid accidental activation along with mounting structure, accessories etc complete as per specification and tender document. 1190 1 EA
120 1200 Push Buttons Outside Dyke Walls 1200
121 1210 Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. 1210
122 1220 For ROSOVs (A/G product tank's inlet, outlet and recirculation line) 1220 30 EA
123 1230 ESD PUSH BUTTON STATION 1230
124 1240 Supply of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. 1240
125 1250 Local ESD Push Button Station ( Each Battery of TLF -2 no., TLF pump house - 1 no.) 1250 3 EA
126 1260 Plant ESD Push Button Station ( Each battery of TLF - 2 No., Main entry/exit to Tank Wagon loading area from Terminal- 2 No.) 1260 4 EA
127 1270 Supply of ESD push button stations (for indoor application), mushroom head type with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. (control room - 1 no., security room - 1 no., TM's cabin - 1 no.) 1270 3 EA
128 1280 Control Room equipments 1280
129 1290 Supply of redundant fault tolerant Integrated Distributed Control System (DCS) along with DCS Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Input Output modules, Power supply units, Relays with base, barriers, TBs, Redundant host communication ports, Serial Interface Modules, HART modules, other communication modules, HMI , wirings, glands, plugs, other modules/ hardware required for interfacing with all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: Any other hardware, software, OPC server, Historian Server, storage, firewall, functional control key board etc required as per tender specification and design requirements, the same to be provided by the vendor at no additional cost to IOCL. 1290 1 SET
130 1300 Supply of Complete Terminal Automation Software along with required licences, dongle/keys, GUI, SCADA etc meeting the complete functional and technical requirements of the tender document. \nVendor to provide required software, licences, dongle/keys, GUI, SCADA etc for TAS Management Server, Distributed Control System, Operator work stations, fire fighting OIC, Alarm display and annunciation OIC, Engineering Work Stations(for safety PLC & DCS), Web Server, OPC Server, Historian Server / work station, any other devices connected to Control & Management LAN of the integrated Distributed Control System complete as per specification and tender document.\nTAS software shall be interfaced with following but not limited to major sub-systems / equipments alongwith GUI development for monitoring, logging, reporting, controls & interlocks etc as per specification and tender document.\n- Safety PLC\n- TAS-Management Server\n- TLF Automation System (TT reporting, registration & entry system, TT Queuing, FAN generation, TT registration number reading system, Photo pass management system,TT crew authorization system,Bay allocation, Additive Dosing system, Ethanol blending System, Interface with TLF equipments like BCU, MFM, Barrier Gates, Bay Queue Display, Bay allocation Display, Invoice generated display, rack monitors, Proximity card readers etc)\n-Tank Wagon loading Automation system (Rake inventory System,Rake registration system, FAN generation, Tank wagon allocation, Interface with TWG equipments like BCU, MFM etc,SAP-TWG integation)\n-Tank Wagon unloading Automation system\n-Tank Lorry Decantation System\n-TT calibration System\n-Bio Diesel Blending system - ANPR and Face recognisation 1300 1 LS
131 1310 -- Valve Automation System (ROSOVs, MOVs, DBBV, MCS Interface, SOVs, etc)\n-Tank Farm Management System ( TFMS Server, Primary & Secondary Radar Gauging, AOPS, Level transmitters, Level Switch, Density probes, MSTW, CIU etc)\n- Pipeline/ Refinery PLC Interface, OMC PLC interface\n - MCC, Pump, Borewell, DG Sets, Air compressors, VFDs\n- PA paging Interface \n- HC Detection System Interface\n-FAS Interface, Fire Fighting System, HVLR, Fire Alarm System Interface, Fire Engines, DG Set, Jockey pumps, Foam pumps, CFFS, Sprinkler & Fixed foam pourer system etc\n- VRU Package Units\n- Effluent Treatment plant\n- CCTV systems\n- Access Control System\n- SKO Blue Dye Dosing System\n- ESD System, Emergency panel, Power ESD, Local ESD, Wailing sirens\n- Pressure Transmitters\n- UPS & Power distribution boards etc\n- Interface with IOCL SAP through firewall\n- Visitor Management Software for setup, configuration, operation, events, history and archiving, recording, printing etc. complete as per specification and tender document - Any other Third Party Interface/ devices as per scope of the work order etc\nNote: The offered software shall also includes fault detection module and Web Server software for remote over IOCL Intranet across India as detatiled in the tender document.\n\n\n\n 1310
132 1320 Supply of Redundant SIL 3 TUV/ EXIDA certified Safety PLC along with PLC Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Dual redundant Input Output modules, Power supply units, Relays with base, barriers, TBs, Dual Ethernet ports per processor, Serial Interface Modules, HMI , wirings, glands, plugs, other modules/ hardware required for interfacing all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: The offered safety PLC shall be of the same make family of the integrated Distributed Control System. 1320 1 SET
133 1330 Supply of redundant TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LCD/LED monitor of minimum size of 19" suitable for 24x7 operation along with High availability redundancy software working on redundant (Primary and Secondary) hot standby mode , keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document.\n OR\nSupply of Dual Mode Redundant Grade with built in redundancy TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 19" suitable for 24x7 operation, keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document. \n\nTAS Management Servers (TAS-MS) shall have either of the above mentioned configuration meeting the complete specification and tender requirements. \n\nIn addition, the TAS-MS shall be configured to have Zero Downtime to repair, Full data redundancy shall be provided using proven technology , it shall also provide port level redundancy.The system solution shall be capable of self fault detection and isolation, all necessary hardware/software configuration etc to achieve the same shall be included. 1330 1 LOT
134 1340 Supply of 42 U Rack Enclosure cabinet/System cabinet with 19" rack size, along with accessories like Biometric fingerprint cum contactless smart card reader for front & back door seperately with accessories, limit switches, earthing arrangements, breaker, fuses, terminal blocks and wiring etc complete as per specification and tender document for mounting of below mentioned equipments. 1340
135 1350 For mounting of TAS Management Servers along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, Ethernet switch, GSM modems, MCBs etc as per specification and tender document. 1350 1 EA
136 1360 For mounting of CCTV Servers, Analytics Servers, NAS/SAN along with associated rack mounted monitors & keyboard, mouse, 4 port industrial grade KVM switches, power adapters, layer 3 Ethernet switch, MCBs etc as per specification and tender document. 1360 2 EA
137 1370 For mounting of Redundant ACS cum photopass management Server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking components, MCBs etc as per specification and tender document. 1370 1 EA
138 1380 For mounting of Redundant TFMS Server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, CIUs, MCBs etc as per specification and tender document. 1380 1 EA
139 1390 For mounting of Rack mounted Master Control Stations for MOVs & DBBVs along with power adaptors, MCBs, required accessories etc as per specification and tender document. 1390 2 EA
140 1400 For mounting of Rack mounted CPUs of Control room console workstation (Rack type) , one number 19" rack mounted monitor, rack mounted keyboard, mouse, KVM switches for connection of all CPUs along with power adaptors, MCBs, required accessories etc as per specification and tender document. 1400 2 EA
141 1410 Supply of Operator Interface Console Computer (OIC) with minimum 27" colour LED monitor,keyboard, mouse,KVM Switch, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. CPU shall be kept in Panel room in 42 U Rack. \nNote: CPU of control room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 1410
142 1420 19" Rack mounted at Control Room, form factor - Rack , Max. 2U height ( 3 OICs, 1 for alarm Display, 1 for fire fighting System) 1420 5 EA
143 1430 Supply of Operator Interface Console Computer (OIC) minimum 27" colour LED monitor,keyboard, mouse, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. 1430
144 1440 Tower type in TM's Cabin 1440 1 EA
145 1450 Supply of Engineering Workstation (EWS) with minimum 27" colour LED monitor, keyboard, mouse, KVM Switch, Safety PLC & DCS software, HMI software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. (Locations: 1 no. in CR for both DCS and Safety PLC) \nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 1450
146 1460 19" Rack mounted at Control Room, Form factor - Rack , Max. 2U height 1460 1 EA
147 1470 Supply of Tank Truck Entry System (TTES) Workstation with minimum 27" colour LED monitor, keyboard, mouse,KVM switch, software, SCADA, GUI, OS, Antivirus etc. complete as per specifications and tender document. (Locations: 2 nos. in Customer service Block +1 no. in Control room+1 no. in Lock shed room) \nNote: CPU of control room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 1470
148 1480 19" Rack mounted at Control Room, Form factor - Rack , Max. 2U height 1480 2 EA
149 1490 Tower type in Customer service block (2 nos.) and Lock shed room (1 no.) 1490 3 EA
150 1500 Supply of Web Server (Rack type mountable in 19" rack ) ,Rack type CPU -2U Max. , LED monitor of minimum size of 27" suitable for 24x7 operation, keyboard, mouse, KVM Switch, web application software, SCADA, GUI, OS, Antivirus etc located in panel Room complete as per specifications and Tender Document. \nNote: CPU of control room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 1500 1 EA
151 1510 Supply of minimum 19" colored LED monitor (19" Rack type at panel Room, form factor - Rack, CPU height - 1U) with , KVM switch, Rack type keyboard, mouse etc located in Control Room complete as per specifications and Tender Document. (For CPUs of Console kept in panel room) 1510 2 EA
152 1520 Supply of the NMS System covering Network Devices operational in Terminal Automation System. The Offered Network Management Solution (NMS) solution should support at least the following:\n• All the proposed NMS Components should be from single vendor. \n• NMS Software should support Graphical view up to port level for the all the devices.\nDiscovery of Network Elements.\n• Real time Traffic monitoring of Network Links and Devices with Historical reports for various periods.\n• Management of SNMPv1, SNMPv2, SNMPv3 & MIB etc.\n• Configuration of thresholds for Generating alarms.\n• Configuration of alarm actions (visual, audible, email, sms etc.) for each \nNetwork element.\n• Should be able to provide secured windows based consoles / secured web based consoles for accessibility to NMS.\n• Should have web browser interface with user name and Password Authentication.\n• Administrator/ Manager should have privilege to create/modify/delete user.\n• NMS should have support for SNMPv3 & IPv6, including dual-stack IPv4 & IPv6 to provide flexibility in protocol strategy and implementation.\n 1520 1 LS
153 1530 Supply of Terminal servers (rack mounted) with inbuilt/externally mounted lightening and Surge Protection Device Type (1+2) at all Serial ports, for interfacing and integration of field devices (Indoor & outdoor), LED Display unit for TT reporting,at Main Entry gate & Exit gate and TLF Entry gate for Bay allocation with TAS.In case the above listed equipments do not come with open communication protocol compatible to be directly interfaced with DCS Serial / MODBUS TCP IP module complete as per specification and tender document.\nNote: Terminal Servers to be configured in Dual Redundant mode. 1530
154 1540 16 ports at Customer service Block 1540 2 EA
155 1550 Supply of 24 ports Layer 3 Managed Ethernet Switches (10/100/1000 MBPS) with SFP, copper, fibre modules/ports along with accessories for connecting Plant management LAN equipments like CCTV System, TAS - MS Server/ Redundant OPC server, TFMS Server, TFMS work station, OICs, IOCL intranet for SAP connectivity through fire wall, Network printers, Access Control Server, Web Server Access over IOCL Intranet, connecting to OIC/ work stations etc which needs to be connected to both Plant Management LAN and Plant Control LAN for getting the entire GUIs of Complete Terminal Automation System and any other third party devices for interfacing with DCS etc.\nNote: \n1. Ethernet Switches to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs and any other equipment which are to be connected to above switch and the communication is through OFC cable. 1550 2 EA
156 1560 Supply of minimum 24 ports Layer 2 Managed Ethernet Switches (10/100/1000 MBPS) along with SFP, copper, fibre modules, accessories for connecting equipments installed in Plant Control LAN like TAS- MS Servers, OICs, TTES cum TWES , EWS, OPC Servers, Fire fighting OICs, Alarm Display OIC, DCS, Safety PLC, inter connecting building work stations etc as per system architecture and design requirement complete as per specification and tender document.\nNote:\n1. The switches are to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs, and any other equipment which are to be connected to above switch and the communication is through OFC cable. 1560 2 EA
157 1570 Supply of Layer 2 Managed Ethernet Switches along with accessories for connecting BCU with TAS, equipments installed in Customer service room, Lock room, Security room, Terminal Manager room and other TAS equipments as per system architecture and design requirement complete as per specification and tender document.\nNote: \n1. Ethernet switches for BCU communication shall have suitable mounting arrangement to mount inside FLP JBs. \n2. The switches are to be configured in Dual Redundant mode.\n3. All OICs, Workstations, Servers other than that of CCTV, ACS & TFMS are to be connected to both plant management and control LAN so that all the GUIs can be seen in all the PCs irrespective of its nomenclature like TTES, OIC, EWS, TM PC etc.\n4. Printers to be connected to Plant Management LAN and to be configured to all PCs, Workstation, TTES etc so that printout command can be issued from any of the Machine. 1570
158 1580 For BCU integration at TLF (copper ports of 10/100/1000 MBPS)-( Minimum 8 nos. copper ports and 2 nos. optical ports) 1580 30 EA
159 1590 For connecting all MODBUS TCP IP devices ( any other devices) to DCS Ethernet port directly for integration (copper ports of 10/100/1000 MBPS)- to be located in Control Room ( Minimum 8 nos. copper ports and 2 nos. optical ports) 1590 4 EA
160 1600 At Lock Shed - copper ports of 10/100/1000 MBPS [control LAN - 2 nos. & Management LAN - 2 nos.] ( Minimum 8 nos. copper ports and 2 nos. optical ports) 1600 4 EA
161 1610 At Admin Building for TM cabin - copper ports of 10/100/1000 MBPS [control LAN - 2 nos., Management LAN - 2 nos., CCTV - 2 no.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 1610 6 EA
162 1620 At customer service Room - copper ports of 10/100/1000 MBPS [control LAN - 2 nos. & Management LAN - 2 nos.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 1620 4 EA
163 1630 At Security Room - copper ports of 10/100/1000 MBPS [control LAN - 2 nos.,CCTV - 2 no.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 1630 4 EA
164 1640 At Driver rest room - copper ports of 10/100/1000 MBPS [Managent LAN - 2 nos.] (Minimum 4 nos. copper ports and 2 nos. optical ports) 1640 2 EA
165 1650 Supply of industrial grade redundant Serial to Ethernet converter of 8 port with mounting acessories etc complete in all respect as per specification and tender document. (Ports:- 6 Main + 2 Spare) 1650
166 1660 For MFM and other serial devices integration to DCS -TLF 1660 18 EA
167 1670 Supply of Wall mounted/wheel mounted Network Rack-minimum 19U 19" Rack for mounting of Terminal Server/Server/Client PC/Ethernet switches/LIU/ OFC components along with accessories like power sockets, MCBs, fan, mounting accessories etc complete in all respective at Security Room, TM room, Invoice Room, Customer service room for TAS equipments 1670 4 EA
168 1680 Supply of Wall mounted Network Rack-minimum 12U 19" Rack for mounting of Terminal Server/Ethernet switches/LIU/ OFC components along with accessories like power sockets, MCBs, fan, mounting accessories etc complete in all respective at Security Room, TM room, Invoice Room, Customer service room for TAS equipments 1680 4 EA
169 1690 Supply of Monochrome Laser Printer along with accessories for TAS and TFMS report printing in control room (2 nos.) and 2 nos. at security room complete as per specifications and tender document. 1690 4 EA
170 1700 Supply of heavy duty high speed laser printer along with Printer Stand and accessories for invoice printing in lock shed room, complete as per specifications and tender document. 1700 2 EA
171 1710 Supply of parallel redundant UPS of minimum capacity of 60 KVA or as per load calculation (whichever is higher) for entire TAS equipments and third party devices integrated with TAS and powered through TAS UPS with 30% spare capacity for future load connection. The scope also includes supply of parallel battery bank (2x50%) for minimum back up time of ½ hour at full load (rated capacity) along with stand, supports for mounting of the UPS and batteries etc complete as per specification and tender document. The batteries shall be Sealed Maintenance free type. 1710 1 SET
172 1720 Supply of UPS Power Distribution Panel along with Biometric fingerprint cum contactless smart card reader for front and rear gate sepearately with accessories for powering DCS Panel, Safety PLC Panel, TAS-MS, OIC, EWS, TFMS System, TTES, printers, Bay Instruments other control room equipments, Tank Farm Instruments, CCTV system, Fire Detection System, Access control system, Bay Queue Display boards, other display boards, ROSOV ESD port, header line instruments and any other TAS equipments where UPS power are required for smooth un-interrupted operation. Miscellaneous Instrumentation comprising of suitable MCCBs for Isolation, MCB etc are to be provided. The panel shall be complete in all respects with necessary indication lamps for powering, necessary control wiring with digital voltmeter & digital ammeter separately for UPS and Auxilliary supply for front and rear seperately etc as per specifications and tender document.\nNote: Minimum 20% spare power points to be made available for future use. 1720 1 LS
173 1730 Supply of Open desk operator consoles, chairs, printer tables etc complete as per specification and tender document. 1730
174 1740 Open desk operator consoles for mounting of monitor in two tiers , 2 nos. of key boards, 2 nos. of mouse, accesscories e.g. Telephone,VHF sets, Master control station for PA paging etc complete as per specification and tender document.\n(For mounting of 3 nos. OICs monitor, 1 no. Alarm Display OIC monitor, 1 no. Fire fighting OIC monitor, 1 no. TTES monitor , 1 TFMS workstation monitor, 1 no. CCTV client monitor,1 no. EWS monitor,1 Web server, storage etc.) 1740 10 EA
175 1750 Chairs (Godrej interio Ace Mid back high performance chair) 1750 10 EA
176 1760 Standard Printer Tables of Godrej or equivalent make (2 nos. at security gate, 1 no. in Lock shed room, 1 no. in security room for visitor management) 1760 4 EA
177 1770 Standard Computer Table of Godrej or equivalent make for installation of CCTV client , ACS client in security room (2 nos.),Photo pass management PC(1 No.), TTES in Customer service room (2 nos.) and TTES in lock shed room (1 no.) 1770 8 EA
178 1780 Supply of IP based Redundant GSM modem suitable for 24x7 operation along with accessories for auto SMS as per specification and tender document. 1780 1 Set
179 1790 Supply of video wall along with 1 no. Of hooter ,ack push button,accecories , cables etc for fire fighting cum critical Alarm display & annuniciation cum CCTV complete as per specifications and tender document. In control room:-Windows for all cameras should be available onsingle screen of 300-400 cm2 for min. 150 no. CCTV camera. \nAdditional Two Number (min. 55” each or meeting size of video wall) for Alarm LED display and Fire fighting display. 1790 1 EA
180 1800 Supply of video wall along with complete accecories , cables etc for CCTV complete as per specifications and tender document. In location in charge room:-viewing window size should be preferably be between 250-300 cm2 ( in two pages) for CCTV camera 1800 1 EA
181 1810 Supply of video wall along with complete accecories , cables etc for CCTV complete as per specifications and tender document. In security cabin:-viewing window size should be preferably be between min. 150-200 cm2 ( in two pages) for CCTV camera 1810 1 EA
182 1820 Supply of minimum 55" HD LED monitor along with 1 no. of hooter, ACK push button, mounting accessories, cables etc complete as per specifications and tender document. 1820 1 EA
183 1830 Supply of minimum 75" HD LED monitor along with mounting accessories, cables etc complete as per specifications and tender document. 1830 1 EA
184 1840 Hydrocarbon Detection system 1840
185 1850 Supply of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document. 1850
186 1860 Point type Infrared detector\n(Indicative location: Each class A tank dyke sump pit inside dyke wall - 5 nos., Near ROSOVs of MS tanks:-9 Nos., Ethanol tanks- 4 nos., TLF pump seal (MS+Ethanol) - 7 Nos and TW loading (MS)-3 Nos, Ethanol decantation-3 No. MS,Sludge pump seal-2 No., Pump house drain pit - 4 no.; Vapour recovery system drain pit - 1 no.) 1860 38 EA
187 1870 Open path type Infrared detector (0-90 m) along with alignment telescope, configuration & Testing kit etc (Tentative location: MS tanks covering ROSOVs -4 nos.) 1870 4 EA
188 1880 Open path type Infrared detector (0-90m) along with alignment telescope, configuration & testing kit etc (Tentative location: TLF- 1 Nos, Sick wagon- 1No., TT decantation -1No and TW Product pump house - 1 no., Product PH manifold TLF & TW- 4 nos.) 1880 8 EA
189 1890 Open path type Infrared detector (0-40 m) along with alignment telescope, configuration & Testing kit etc (Tentative location: MS tanks & Ethanol tanks covering ROSOVs -4 nos.) 1890 1 EA
190 1900 Supply of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessories and structural supports as per specification.( Tentative location : Each product tank dyke (MS+Ethanol)-2 nos., Pump House (TLF+TW+Decnatation) - 3 no.,Sludge Pump- 1 No. & Vapour recovery system-1no.) 1900 8 EA
191 1910 Supply of one no. of Portable Hydrocarbon vapour detector along with accessories complete as per specification and tender document. 1910 1 EA
192 1920 Automatic Fire Detection and Alarm System 1920
193 1930 Supply of microprocessor based automatic Fire Alarm Panel along with required Software, and hardware like Control module, monitor module, fault isolation module (in built/ External), mounting structure support etc complete as per standard design engineering, specification and tender document.\nLocation : Control Room 1930 1 EA
194 1940 Supply of Repeater Panel along with software, hardware, mounting accessories etc required as per standard design Engineer, specifications and tender document complete in all respect. \n(Tentative location : Security Gate - 1 no., Fire Pump House - 1 no.) 1940 2 EA
195 1950 Supply of addressable type detectors along with accessories, fault isolation module (Inbuilt/ External), structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 1950
196 1960 Combination/Multi-sensor Detector 1960 190 EA
197 1970 Rate of Rise Heat Detector 1970 3 EA
198 1980 IS detector 1980 3 EA
199 1990 Supply of Manual Call Point along with accessories, fault isolation module (Inbuilt/ External) and structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 1990
200 2000 Ex-proof and weather proof MCP 2000 14 EA
201 2010 Weather proof MCP 2010 21 EA
202 2020 Supply of Hooter along with accessories, fault isolation module (inbuilt/ External), structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 2020
203 2030 Weather proof Hooter 2030 17 EA
204 2040 Supply of Response Indicator along with accessories, mounting structure etc required as per standard design engineering, specification and tender document complete in all respect. 2040 71 EA
205 2050 Access Control System 2050
206 2060 Supply of half man height bi-directional turnstile (tripod) with controller along with accessories, mounting structure, pressure sensor etc required as per standard design engineering, specification and tender document complete in all respect. (Location : License area entry & exit gate - 2 nos. ; Entry/Exit to tank farm area - 2+1=3 nos.) 2060 9 EA
207 2070 Supply of Retractable Dual Lane Flap barrier with controller along with accessories, mounting structure, pressure sensor etc required as per standard design, engineering, specification and tender document complete in all respect. (Location: Admin building entry/exit ) 2070 1 set
208 2080 Supply of face detection cum fingerprint cum contactless type smart card reader with controller along with 2 nos. of electromagnetic door lock of 600 lb for single door/double door,EM locks for emergency door, 2 nos. of door position magnetic contact with buzzer etc as per specifications and tender document. (Location : control room entry/exit door - 4 nos., Panel room entry/exit door - 4 nos. ) 2080 4 EA
209 2090 Supply of Biometric fingerprint cum contactless type smart card reader with controller along with 2 nos. of electromagnetic door lock of 600 lb for single door/double door, 2 nos. of door position magnetic contact with buzzer etc as per specifications and tender document. (Location : Customer Service room- entry/exit door - 2 nos. ) 2090 2 EA
210 2100 Supply of Biometric fingerprint cum contactless type smart card reader with controller along with rolling electro magnetic heavy duty Lock/ latch, Sensor, agress switch/ Push Button, power supply unit, software , programming kit etc equired as per standard design engineering, specification and tender document complete in all respect for access control through Panel room Rolling Shutters entry/exit installed at Control Room 2100 1 EA
211 2110 Supply of Biometric fingerprint cum contactless type smart card reader along with accessories, software , programming kit etc required as per standard design engineering, specification and tender document complete in all respect. (Turnstile:- security entry/exit gate -Dual Lane-Uni directional : 2x2 nos. license area entry/exit gates (bi-directional) - 2x2 nos., entry/exit to tank farm area (bi-directional)-3x2 nos., Flap barrier - 2x2nos.) 2110 18 EA
212 2120 Supply of Door Frame Metal Detector, 4 nos. hand held metal detector along with accessories, mounting structure etc complete as per specification and tender document. 2120 1 EA
213 2130 Supply of 2"size SS 304 guiding rail along with mounting accessories complete as per specification and tender document near turnstile/ tripod/flap barrier etc to prevent un-authorised movement. 2130 100 RM
214 2140 Supply and configuration of Proximity smart access cards as per the specification and tender document. 2140 500 EA
215 2150 Supply of Redudnant ACS Server for photo pass management & visitor management (19" Rack type at panel Room, form factor - Rack, CPU height - 2U) with minimum 19" colored LED monitor, KVM switch, keyboard, mouse, OS, Antivirus etc located in Control Room complete as per specifications and Tender Document. 2150 1 SET
216 2160 Supply of Access Control cum photopass management System Software for setup, configuration, operation, events, history and archiving, alarm monitoring, recording, printing, time and attendance etc. complete as per specification and tender document including hardwired interface with TAS for ESD input. 2160 1 LS
217 2170 Supply of Client workstation of ACS cum Photopass management with minimum 27" coloured monitor,keyboard, mouse,KVM switch (extender/reciver) for Rack CPU, OS, Antivirus, HD coloured video camera (for taking visitors photograph) etc for ID badging & issuing of Visitor pass/Photo pass at security Room & other etc. complete as per specifications. 2170
218 2180 Rack Type - CPU in panel room with KVM sitch; Keyboard, mouse along with monitor etc. to be installed in security room for visitor pass 2180 1 EA
219 2190 Tower Type in Photopass room for TT crew/Contractor etc. 2190 1 EA
220 2200 Supply of Laser printer (Monochrome) for Visitor pass printing having flexibility to print on A4, A5, A6 paper complete as per specification and tender document. 2200 1 EA
221 2210 Supply of Colour photo pass printer along with integrated/seperate scanner for photo pass printing as per specification and tender document. 2210 1 EA
222 2220 Supply of PVC cards for printing of photo pass as per specification and tender document. 2220 1000 EA
223 2230 IP BASED CCTV SURVEILLANCE SYSTEM 2230
224 2240 Supply of HD IP Fixed Dome camera with IR and MFZ lens (2MP) along with power supply unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 2240 8 EA
225 2250 Supply of HD IP PTZ Camera (2MP) along with power supply unit (POE based) with POE injector (industrial grade),with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 2250 35 EA
226 2260 Supply of IP Fixed Bullet cameras with MFZ lens (8MP) – 4K resolution along with power supply unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 2260 8 EA
227 2270 Supply of IP Fixed Box cameras with varifocal lens (8MP) – 4K resolution along with power supply unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 2270 51 EA
228 2280 Supply of Integral Explosion Proof HD IP Fixed Cameras and MFZ lens (2MP) along with power supply unit , with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 2280 8 EA
229 2290 Supply of IP Fixed Bullet cameras with IR MFZ lens (8MP) – 4K resolution along with power supply unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document.(TT Reporting :-2+TTEntry/Exit:-2+Driver Entry/Exit-2,Helper Entry/Exit-2, Photo Pass issuance:- 2) 2290 10 EA
230 2300 Supply of 4 port Industrial grade layer 2 Managed POE based Ethernet Switch for connecting Cameras with 4 Nos. RJ copper port and 2 Nos. optical fibre ports with inbuilt/external surge protector (Type 1+2) at the input power supply as per specifications and Tender Document. 2300 65 EA
231 2310 Supply of outdoor Explosion proof cum weatherproof housing (IP 65 or better) suitable for installing Layer 2 switch, PSU, LIU and adaptor for Ethernet switch/media convertor, surge protectors and other accessories of CCTV cameras. Supply of required OFC components & accessories like LIU, splice trays, loaded adaptor, blank plates, UTP cables, Fibre patch cords, pigtails, tags, ties, Ethernet cable with RJ45 connector etc complete in all respect for functioning of CCTV camera.The scope also includes supply of Exd. blinding plugs, Exd. double compression cable glands etc as per specifications and Tender Document. 2310 60 EA
232 2320 Design, fabrication and supply of Heavy Duty self supported Hot Dip Galvanized Poles for mounting of CCTV cameras along with civil foundation along with GI foundation bolt, mounting brackets, ladder arrangement (taking into account of safety during climbing) on the pole for installation and maintenance of cameras, SS nut & bolts for fixing camera and other accessories required for complete installation and commissioning of the pole, submission of structural stability certificate based on existing soil bearing capacity and wind speed from Govt. Engineering colleges etc complete as per specifications and Tender Document of below mentioned height of the pole. (Foundation drawing and other details to be submitted prior to installation as per tender document)\nNote: In case pole do not have ladder arrangment for maintenance purpose, then vendor to arrange for ladder for installation & maintenance purpose throughout the contract period including CAMC period at no additional cost to IOCL. 2320
233 2330 10 M pole with cantilever arrangement for mounting of 1 fixed camera at 6m, 2 PTZ camera at 10 m and LED flood light at 8m of the pole across perimeter as per tender 2330 10 EA
234 2340 10 M pole with cantilever arrangement for mounting of 1 fixed camera at 6m and LED flood light at 8m of the pole across perimeter as per tender 2340 41 EA
235 2350 6 M pole 2350 15 EA
236 2360 12 M pole 2360 15 EA
237 2370 Supply of rack mounted CCTV Server (s) along with rack type monitor, optical mouse and combo 4 port KVM switch, OS, Antivirus, LIU etc complete as per specifications and Tender Document. \nNote: In case multiple servers are required to meet the tender requirement, vendor to provide the same at no additional cost to IOCL. In additional to above, Vendor to provide failover server to have redundancy in CCTV server such that failure of one server should not affect the CCTV operation and recording at its full resolution at no additional cost to IOCL. 2370 1 LS
238 2380 Supply of Network Attached Storage ( NAS ) / Storage Attached Network (SAN) for storing recorded video for a minimum period 90 days @ 15 FPS at full resolution & highest Video quality of all cameras (Continuous recording) complete as per specifications and Tender Document. 2380 600 TB
239 2390 Supply of CCTV client work station along with client software & licenses, key board, mouse, hardware & connector for repeat/ Dual display on wall mounted LED screen, OS, Antivirus, etc complete as per specifications and Tender Document. ( Location : Control Room - 1 no., Security room- 1 no. , TM room - 1 no.)\n\nNote: CCTV Work station shall have provision to connect to 2 nos. of UHD LED monitors . Required hardware & software is to be provided for the same. Incase the offered work station do not have such provision, then additional work station to be provided meeting the tender requirement at no additional cost to IOCL.Marketing CPU for control room & security room shall be kept in Panel room in 42 U Rack. KVM extender & reciever for these CPU is to be supplied at no additional cost. 2390
240 2400 ( Location : Control Room - 1 no., Security room- 1 no. , TM room - 1 no.) 2400 3 EA
241 2410 Supply of minimum 55" Ultra High Definition (4K) LED Display monitor along with mounting accessories etc complete as per specifications and Tender Document for repeat display of CCTV output. ( Location: Security Room-2 nos., TM Room- 2 nos.) 2410 4 EA
242 2420 Supply of minimum 75" Ultra High Definition (4K) LED Display monitor along with mounting accessories etc complete as per specifications and Tender Document for repeat display of CCTV output. (Location : Control room - 2 nos.) 2420 2 EA
243 2430 Supply of Layer 3 Managed Gigabit Ethernet Switch with minimum 24 ports or as per site requirement + 20 % spare whichever is higher along with SFP, copper, fibre modules, accessories complete as per specifications and Tender Document. \nNote- The switches are required to be configured in dual redundant mode \n 2430 2 EA
244 2440 Supply of Intelligent video operation, control, management, recording & processing software (VMS) complete , Advanced Analytics Software for ANPR and Face recognisation with OS, Antivirus etc including licenses as per specifications and Tender Document with minimum 125 cameras recording, 125 cameras viewing license, 5 LISC licence for remote viewing or as per actual nos. of cameras installed + 20% extra which ever is higher. 2440 1 LS
245 2450 Supply of Advanced Analytics Software for all fixed cameras (including varifocal, MFZ fixed cameras), Auto tracking video analytics for all PTZ camera along with compatible Redundant Analytics Server with OS, Antivirus etc including analytic license for actual number of camera installed + 20 % spare complete as per specifications and Tender Document. 2450 1 SET
246 2460 Miscellaneous 2460
247 2470 Supply of flameproof cum weather proof to IP 65 or better SIL 2 smart pressure transmitter with in built display, SS manifold, isolation valve, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender)\nNote:1. Pressure transmitter at suction shall have range from -1 Kg/cm2.\n2. Underground tank shall have PT in Pump discharge end only. 2470
248 2480 TLF pump Suction end 2480 21 EA
249 2490 TLF pumps Discharge end 2490 21 EA
250 2500 TW loading/unloading pump Suction end 2500 9 EA
251 2510 TW loading/unloading pump Discharge end 2510 9 EA
252 2520 Fire Hydrant lines 2520 4 EA
253 2530 Decantion Pump House 2530 8 EA
254 2540 Stripping Pumps -- Remote Seal Type 2540 10 EA
255 2550 Bio-Diesel Underground tank Discharge Line 2550 2 EA
256 2560 Supply of flameproof cum weather proof to IP 65 or better SIL 2 Smart Differential pressure transmitter with in built display, SS 3 way manifold, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender) 2560
257 2570 Across all TLF pump strainers (loading+unloading) 2570 21 EA
258 2580 Across all TW pump strainers (loading+unloading) 2580 9 EA
259 2590 Decantion Pump House 2590 4 EA
260 2600 Stripping Pumps---Remote Seal Type 2600 5 EA
261 2610 Supply of flameproof cum weather proof to IP 65 or better bi-colour magnetic flap type level gauge (side mounted) along with level transmitter with installed accuracy +/- 6 mm or better along with mounting accessories, complete as per specification and tender document. 2610
262 2620 Foam Tanks 2620 15 EA
263 2630 Foam Daughter Tanks for HVLR 2630 4 EA
264 2640 Fire Engine Service tanks 2640 7 EA
265 2650 DG Set Service Tanks 2650 3 EA
266 2660 Supply of Level switch ( Magnetic Float / displacer type ) for low and high level alarm along with mounting accessories etc as per specifications 2660
267 2670 Fire water Sump 2670 1 EA
268 2680 Static Water-TT calibration sump 2680 2 EA
269 2690 Supply of Wailing siren along with controller with a provision to operate locally as well as from control room, mounting accessories etc complete as per specification and tender document. 2690 1 EA
270 2700 Supply of Digital Rodent Repellent System along with mounting accessories for main controller(s) & transducers etc complete as per specification and tender document (Minimum nos of transducers: Control Room - 12 nos., Customer service room- 4 nos., Invoice room - 4 nos. & Security Room - 4 nos.) 2700 1 LS
271 2710 Supply of Ex-proof and weather proof Hooter cum Beacons along with accessories, mounting structure etc complete as per specification and tender document for audio visual alarm at field in case the MOVs installed at tank dyke drain and tank water draw off line is not fully closed. (HSD-1,MS-2,ETH-1,SKO-1,ATF-2)\nLocation : Near each tank dyke and to be installed outside dyke. 2710 6 EA
272 2720 Supply of solenoid valves (SOV) of 25/32/50/65 NB (as per line size) along with one no. of isolation by pass valve to bypass the SOV with associated piping, mounting accessories etc complete as per specification and tender document. \nNote: SOV need to be supplied factory fitted along with baypass valve and both side flanged option. 2720
273 2730 At the inlet of DG set Service tanks 2730 3 EA
274 2740 At the inlet of Fire Engine Service tanks 2740 7 EA
275 2750 Supply of Globe/ball valve of 25/32/40/50 NB (as per line size) along with electrical/electrohydraulic actuator , local indication, Local operation, one no. of isolation by pass valve for bypass with associated piping, mounting accessories etc complete as per specification and tender document. 2750 15 EA
276 2760 Supply of MCT block for entire Automation cable entry to Control Room, Admin Building, Invoice Room, Security Room, Customer service room, Driver's Rest Room with minimum 30% spare MCT blocks for future cable entry along with frame and mounting accessories complete as per specification and tender document. 2760 1 LS
277 2770 Supply of external surge & Lightening protection devices of suitable connector and type along with accessories complete as per specification and tender document at following places. 2770
278 2780 Type 1+2 SPD - Input power supply of UPS 2780 3 EA
279 2790 SPD (Type 2 / IC category C1,C2,C3,D1) - Serial port of MCS (RJ 45 type) 2790 32 EA
280 2800 Type 1 SPD - Earth pit 2800 10 EA
281 2810 Supply of wireless Repeater required for wireless communication as per tender document 2810 6 EA
282 2820 Supply of wireless Gateway required for wireless communication as per tender document 2820 2 EA
283 2830 Cabling, JB, Earthing: 2830
284 2840 Note: Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc 2840
285 2850 Supply of FRLS Armoured Copper Power cable as per tender specifications. 2850
286 2860 3C x 2.5 sqmm 2860 8000 RM
287 2870 4C x 2.5 sqmm 2870 6000 RM
288 2880 8C x 2.5 sqmm 2880 2300 RM
289 2890 10C x 2.5 sqmm 2890 2000 RM
290 2900 12C x 2.5 sqmm 2900 2000 RM
291 2910 24C x 2.5 sqmm 2910 1500 RM
292 2920 3C x 4 sqmm 2920 800 RM
293 2930 4C x 4 sqmm 2930 1000 RM
294 2940 4C x 6 sqmm 2940 300 RM
295 2950 4C x 10 sqmm 2950 300 RM
296 2960 Supply of FRLS Armoured Aluminium Power cable as per tender specifications. 2960
297 2970 3.5C x 120 sqmm 2970 300 RM
298 2980 Supply of FRLS Armoured Copper Control cable as per tender specifications. 2980
299 2990 2C x 1.5 sqmm 2990 8000 RM
300 3000 3C x 1.5 sqmm 3000 7500 RM
301 3010 4C x 1.5 sqmm 3010 6000 RM
302 3020 6C x 1.5 sqmm 3020 2000 RM
303 3030 8C x 1.5 sqmm 3030 1750 RM
304 3040 10C x 1.5 sqmm 3040 1200 RM
305 3050 12C x 1.5 sqmm 3050 1200 RM
306 3060 16C x 1.5 sqmm 3060 1500 RM
307 3070 18C x 1.5 sqmm 3070 2250 RM
308 3080 20C x 1.5 sqmm 3080 2000 RM
309 3090 24C x 1.5 sqmm 3090 1800 RM
310 3100 32C x 1.5 sqmm 3100 2750 RM
311 3110 36C x 1.5 sqmm 3110 1800 RM
312 3120 48C x 1.5 sqmm 3120 2750 RM
313 3130 Supply of FRLS Armoured Copper Signal cable as per tender specifications. 3130
314 3140 1P x 1.5 sqmm 3140 5000 RM
315 3150 2P x 1.5 sqmm 3150 1250 RM
316 3160 3P x 1.5 sqmm 3160 800 RM
317 3170 4P x 1.5 sqmm 3170 1000 RM
318 3180 6P x 1.5 sqmm 3180 900 RM
319 3190 8P x 1.5 sqmm 3190 800 RM
320 3200 10P x 1.5 sqmm 3200 500 RM
321 3210 12P x 1.5 sqmm 3210 500 RM
322 3220 16P x 1.5 sqmm 3220 500 RM
323 3230 18P x 1.5 sqmm 3230 500 RM
324 3240 1T x 1.5 sqmm 3240 250 RM
325 3250 8T x 1.5 sqmm 3250 1050 RM
326 3260 Supply of FS Armoured Copper Power cable as per tender specifications. 3260
327 3270 3C x 2.5 sqmm 3270 3000 RM
328 3280 3C x 4 sqmm 3280 800 RM
329 3290 4C x 2.5 sqmm 3290 1100 RM
330 3300 4C x 4 sqmm 3300 800 RM
331 3310 Supply of FS Armoured Copper Control cable as per tender specifications. 3310
332 3320 2C x 1.5 sqmm 3320 2000 RM
333 3330 3C x 1.5 sqmm 3330 500 RM
334 3340 4C x 1.5 sqmm 3340 1250 RM
335 3350 6C x 1.5 sqmm 3350 600 RM
336 3360 8C x 1.5 sqmm 3360 600 RM
337 3370 10C x 1.5 sqmm 3370 3000 RM
338 3380 12C x 1.5 sqmm 3380 1250 RM
339 3390 18C x 1.5 sqmm 3390 1250 RM
340 3400 24C x 1.5 sqmm 3400 1000 RM
341 3410 32C x 1.5 sqmm 3410 1500 RM
342 3420 36C x 1.5 sqmm 3420 1250 RM
343 3430 48C x 1.5 sqmm 3430 1250 RM
344 3440 Supply of FS Armoured Copper Signal cable as per tender specifications. 3440
345 3450 1P x 1.5 sqmm 3450 3250 RM
346 3460 2P x 1.5 sqmm 3460 3000 RM
347 3470 3P x 1.5 sqmm 3470 900 RM
348 3480 4P x 1.5 sqmm 3480 800 RM
349 3490 1T x 1.5 sqmm 3490 1250 RM
350 3500 Supply of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. 3500 1000 RM
351 3510 Supply of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. 3510 500 RM
352 3520 Supply of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. 3520
353 3530 10 m 3530 25 EA
354 3540 15 m 3540 25 EA
355 3550 20 m 3550 10 EA
356 3560 25 m 3560 12.5 EA
357 3570 30 m 3570 15 EA
358 3580 Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document 3580 12500 RM
359 3590 Supply of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 3590 750 RM
360 3600 Supply of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 3600 2000 RM
361 3610 Supply of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. 3610
362 3620 50 mm 3620 2000 RM
363 3630 100 mm 3630 4000 RM
364 3640 150 mm 3640 2500 RM
365 3650 300 mm 3650 1500 RM
366 3660 600 mm 3660 1000 RM
367 3670 Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. 3670
368 3680 24 ways JB 3680 15 EA
369 3690 18 ways JB 3690 20 EA
370 3700 12 ways JB 3700 25 EA
371 3710 8 ways JB 3710 25 EA
372 3720 6 ways JB 3720 25 EA
373 3730 4 ways JB 3730 25 EA
374 3740 Supply of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. 3740 500 RM
375 3750 Supply of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc 3750 10 MT
376 3760 Earth Pit 3760
377 3770 Supply of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) 3770
378 3780 TLF gantry 3780 2 EA
379 3790 TT earthing 3790 4 EA
380 3800 Control room 3800 4 EA
381 3810 Tank dyke 3810 12 EA
382 3820 SERVICE COMPONENTS PHASE-I 3820
383 3830 TANK LORRY FILLING 3830
384 3840 Installation, integration, testing and commissioning of Microprocessor based Coriolis mass flow meter for white oil application along with display unit and mounting accessories with adjustable screw support,bellow for vibrations etc complete as per specifications and tender document for loading of following main products \nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no additional cost to IOCL. 3840
385 3850 MS (for line size of 100 mm ) 3850 10 EA
386 3860 HSD (for line size of 100 mm ) 3860 12 EA
387 3870 SKO (for line size of 100 mm ) 3870 2 EA
388 3880 Water (Master MFM for TT calibration) for line size 50 mm along with structural support and required accessories for mounting 3880 2 EA
389 3890 Installation, integration, testing and commissioning of Strainer cum Air eliminator with differential pressure transmitter with display unit & keyboard across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 3890
390 3900 For product line size 100 mm - TLF 3900 24 EA
391 3910 For Water Line size 50 mm - TT calibration (along with structural support and required accessories) 3910 2 EA
392 3920 Installation, integration, testing and commissioning of Multistage Piston type Digital Control Valve (DCV) along with TRV with two nos. isolation valves at inlet and outlet of TRV with associated piping , secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 3920
393 3930 For product line size 100 mm - TLF 3930 24 EA
394 3940 For Water Line size 50 mm - TT calibration along with vacuum breaker & isolation ball valve mounted on a spool piece & mounting accessories so that the entire water after DCV is drained into the TT after completion of each batch during TT calibration. 3940 2 EA
395 3950 Installation, integration, testing and commissioning of piston type, hydraulically operated ON-OFF Valve along with accessories, secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning ,tubing arrangement as per installation drawing etc for line size 100 mm complete as per specifications and tender document. 3950 24 EA
396 3960 Installation, integration, testing and commissioning of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF metering skid complete as per specifications and tender document. \n(Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 3960 42 EA
397 3970 Installation, integration, testing and commissioning of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermo well, mounting accessories etc complete as per specifications and tender document. \n(Mounting at each TLF loading point on main product for line size 100 mm) 3970 24 EA
398 3980 Installation, integration, testing and commissioning of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 100 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 3980 24 SET
399 3990 Installation, testing and commissioning of top loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm) ,vacuum breaker with associated pipintg for loading arm with the metering skid , Stand post & mounting structure, bonding clip (for bonding of loading arm with TT) etc complete as per specifications and tender document. \nApplication: SKO 3990 2 EA
400 4000 Installation, testing and commissioning of bottom loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm), API Coupler, break away coupler, parking stand with compatible API adaptor, Ex-proof/intrinsic safe position sensor for parking stand, associated piping for connecting loading arm with the metering skid , mounting structure etc complete as per specifications and tender document. \nApplication: MS, HSD, SKO, ATF 4000 22 EA
401 4010 Installation, testing and commissioning of vapour recovery arm of size 80 mm NB having 3” (80 NB) with poppeted vapour coupler, break away coupler, NRV, flame arrestor, reducers, mounting structures, parking stand with compatible API adaptor, associated accessories, mounting structure etc complete as per specifications and tender document.\nApplication : MS 4010 10 EA
402 4020 Installation, testing and commissioning of Ex-proof Rack Monitors for TT overfill protection system along with accessories like 10 pin gantry plug, ATC copper coiled cable of minimum 8m as per API RP1004 including required support for mounting of the Rack Monitor and gantry plug, etc complete as per specifications and tender document.\nNote: In addition to above, minimum 2 nos. portable Rack Monitor along with accessories and 2 nos. lockable bypass switch are to be provided against total supply of Rack Monitor. 4020 12 EA
403 4030 Installation, integration, testing and commissioning of Resistance - Capacitance type Tank Truck grounding unit along with accessories like 3 nos. of heavy duty flexible coiled cables with high quality rugged, heavy duty SS/ brass grounding socket, FLP double compression glands, Ex-Plug, mounting structure etc, complete as per specification and tender documents.\n(2 nos. of coiled cable with socket for TT earthing relay interlocks and 1 no. for separate earthing of TT) 4030 12 EA
404 4040 Installation, integration, testing and commissioning of Ex-proof field mounted Remote Interaction Terminal (RIT) along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents.\n 4040 24 EA
405 4050 Installation, integration, testing and commissioning of Ex-proof field mounted Driver Ack Push Button station along with FLP double compression glands and Ex-Proof-plug, structural supports etc complete as per specifications and tender documents. 4050 12 EA
406 4060 Installation, integration, testing and commissioning of Microprocessor based Field mounted dual arm Batch Controller with interface to minimum 2 nos. of main product + 2 nos. of blend product + 2 nos. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document.\nOr\nInstallation, integration, testing and commissioning can supply 2 sets of Microprocessor based Field mounted single arm Batch Controller with interface to minimum 1 no. of main product + 1 no. of blend product + 1 no. of additive product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc in place of Dual Arm Batch Controller complete as per specification and tender document. 4060
407 4070 For TLF product loading 4070 12 EA
408 4080 For TT calibration with water 4080 1 EA
409 4090 Installation, testing and commissioning of intrinsically safe / flameproof type proximity card reader along with mounting accessories etc complete as per specifications and tender document for authorisation of TT at 4090
410 4100 TLF bays (1 no. Per bay) 4100 12 EA
411 4110 License area Entry barrier gates ( 2 nos. X 2) 4110 4 EA
412 4120 License area Exit barrier gates ( 1 no. X 3) 4120 4 EA
413 4130 Security Exit barrier gates ( 1 no.) 4130 1 EA
414 4140 Security Entry barrier gates ( 1 no.) 4140 1 EA
415 4150 Near Security Gate/TT parking ( for TT registration ) 4150 2 EA
416 4160 Installation of pre-fabricated Metering Skid (MS structure) for mounting of complete metering equipments as per BOQ and schematic drawing for one main product, one blend product and one additive dosing system. The metering assembly comprises of : \n\nMain product line: Strainer cum Air eliminator, Spool piece with tapping for additive dosing, Online Master Meter proving manifold, MFM,Spool piece with tapping for Temprature Transmitter installation, Pressure transmitter, spool piece with tapping for connecting outlet of TRV, ON-Off valve, DCV, Spool Piece with tapping for Ethanol blending & TRV installation. \n\nBlend Product line: Strainer cum air eliminator, Online Master Meter proving manifold, MFM, Spool piece with tapping for Temperature Transmitter installation, ON-Off valve, DCV, NRV, isolation valve and finally connected to Main stream line tap off point after DCV. \n\nAdditive Dosing System comprises of isolation valve, Additive injection mono block, connecting piping, NRV, isolation valve and finally connecting to Main stream tap off point before MFM. \n\nProvision to be made in the skid for mounting of Batch Controller, Rack Monitor, Grounding unit, RIT, Driver's Ack Push button stations, card reader, FLP sockets, FLP junctions boxes (Power, Signal and Control), FLP power isolator switch, interconnecting cables from respective equipment to JBs, cable trays with covers, glands, support, MS structure,Electroforged galvanized grating, nuts, bolts, gaskets, Tees, bends, elbows, WNRF flanges, nozzles, plugs, isolators, any other equipment if required as per design Engineering etc complete as per specification and tender document. \n\nKindly note, irrespective of facility available or not, each metering skid shall have provision for installation of metering assembly of one main product, one blend product and one additive product as detailed in tender document. 4160 24 MT
417 4170 Note: \n1. All the equipments, JBs, cable trays, interconnecting cables etc as stated above to be installed and loop tested at factory. Complete assembly to be dispatched at site. The skid to be designed and fabricated by the party taking into consideration of all the equipment sizing, space available for mounting of the skid at the bottom of the gantry etc. The design Engineering along with weight calculation of individual skid excluding equipments to be submitted to IOCL prior to taking up fabrication job for review purpose. Payment shall be made based on theoretical weight calculation of the skid excluding weight of equipments, JBs, cable trays. The rate is also inclusive of surface preparation, powder coating, painting, transportation of the skid to site etc complete in all respect. \n2. All unuse nozzle/ tapping/ opening to be blind flanged.\n3. For SKO metering SKID, tapping to be provided in the skid for both bottom and top loading as per design Engineering.\n 4170
418 4180 Installation, integration, testing and commissioning of barrier gate of minimum boom length of 3 m along with accessories, controllers etc complete as per specification and tender document for installation at following location. 4180
419 4190 License area Entry gate 4190 2 SET
420 4200 License area Exit gate 4200 2 SET
421 4210 Security Exit gate 4210 1 SET
422 4220 TT Parking Exit gate 4220 1 SET
423 4230 DISPLAY BOARDS 4230
424 4240 Installation, integration, testing and commissioning of weather proof LED bay queuing display board (Minimum 15 lines x 100 mm Character height x 25 characters per line) for outdoor installation at TT parking area / Customer service building along with accessories like public address system, speakers, amplifier, mike, structural steel for mounting of the same, Aluminium canopy/sunshade etc complete as per specifications and tender document. 4240 1 EA
425 4250 Installation, integration, testing and commissioning of LED monitor of minimum 55" along with required hardware and software for interfacing with TAS, lockable enclosure (wall / ceiling mounted) for mounting the monitor along with accessories at Driver's Rest Room for repeat display of 15 lines Bay Queue Display board complete as per specification and tender document. Kindly note, no additional payment shall be made for any additional hardware/ software/ cable etc required for integration of the monitor with TAS. 4250 1 EA
426 4260 Installation, integration, testing and commissioning of LED monitor of minimum 55" along with required hardware and software for interfacing with TAS, lockable enclosure (wall / ceiling mounted) for mounting the monitor along with accessories, Aluminium canopy/ sunshade etc at invoice room for displaying the list of TTs whose invoice has been generated and TT is still inside license area complete in all respect as per tender requirement. Kindly note, no additional payment shall be made for any additional hardware/ software/ cable etc required for integration of the monitor with TAS. 4260 1 EA
427 4270 Installation, integration, testing and commissioning of weather proof three line coloured LED display board with scroll and flash effects (Each line of min. 50 mm Character height x 11 characters per line) for outdoor application near Security Gate/ TT parking Area and license area Entry barrier Gate along with mounting structure, Aluminium canopy/ sunshade, accessories etc complete as per specifications and tender document for displaying the TT Registration no. in bilingual (English + local language) of reported TT whose proximity card has been shown on the PCR adjacent to the display board for TT reporting at security gate/TT parking area, TT status at TT parking area exit gate and the bay no. (Bilingual) etc of the authorised TT reported at license area Entry Gate as per FDR.\n2 nos. for TT reporting + 1 no. at Security Entry gate + 2 nos. per License Area Entry Barrier Gate (2X2) + 1 No. at Security Exit gate; Total - 2+1+4+1=8\nNote : 1 line for display in English & 2 lines for displaying in local language 4270 8 EA
428 4280 Ethanol Dosing System 4280
429 4290 Installation, integration, testing and commissioning of Microprocessor based Coriolis mass flow meter for white oil (Ethanol) application alongwith display unit and mounting accessories with adjustable screw support, reducer (if required) etc for line size 2" suitable for maximum flowrate of 500 LPM complete as per specifications and tender document for ethanol blending.\nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no adddtional cost to IOCL . 4290 10 EA
430 4300 Installation, integration, testing and commissioning of Strainer cum Air eliminator for line size 50 mm with differential pressure transmitter across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 4300 10 EA
431 4310 Installation, integration, testing and commissioning of Multistage Piston type Digital Control Valve (DCV), NRV, isolation valve for line size 50 mm alongwith accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 4310 10 EA
432 4320 Installation, integration, testing and commissioning of Piston type, hydraulically operated, solenoid operated ON-OFF Valve along with accessories, with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves , tubing arrangement as per installation drawing etc for line size 50 mm complete as per specifications and tender document. 4320 10 EA
433 4330 Installation, integration, testing and commissioning of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermowell for line size 50mm, mounting accessories etc complete as per specifications and tender document. \nNote : One no. of additional thermo well along with accessories to be provided and installed on ethanol point for installation of Master Temperature transmitter with RTD. 4330 10 EA
434 4340 Installation, testing and commissioning of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 50 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 4340 10 SET
435 4350 Additive dosing System 4350
436 4360 Installation, integration, testing and commissioning of additive injection mono block along with accessories for XTRAPREMIUM and XTRAMILE complete as per specification and tender document.\nNote - All the wetted parts within Additive injection panel/ block shall be of SS 316 or better. 4360 8 SET
437 4370 Installation, testing and commissioning of Additive tanks (500 Litres each) and pump module for XTRAPREMIUM /XTRAMILE comprising of Additive Tank, Additive Pumps (Two per tank) , Mild Steel SKID, Flameproof Motor, NRV 25 mm, Flanged ball valve 25 mm, Pressure Relief Valve, Pressure Gauge with pulse dampener, Strainer 25 mm, interconnecting pipings (25 mm SS), flanges etc. auxiliary potential free contact/serial communication complete as per specification and tender document. 4370
438 4380 For Xtramile 4380 1 SET
439 4390 For XtraPremium 4390 1 SET
440 4400 laying ,welding & commissioning of ASTM A106 Gr B Schedule 80 pipe of 25 NB from additive header pipe to additive injection panel at TLF bay complete as per tender document.. 4400 200 RM
441 4410 Laying ,welding and commissioning of Necessary hardware Like SS Tubing, reducer, Elbows, equal Tee ,unequal tee, Flanges, Coupling, Ball Valve for Isolation, NRV, 15 mm back pressure regulator on return line etc as required for piping and commissioning of the system complete in all respect. 4410 1 LS
442 4420 Note: Piping from Additive tank skid upto TLF header line along with isolation valve & return line shall be supplied and installed by IOCL. Integration of additive pumps for remote operation, level measurement shall be in the successful bidder's scope. 4420
443 4430 TLF Header line instruments 4430
444 4440 Installation,testing and commissioning of Bulk Air Eliminator as per product line size and flow requirement as per following sizes including mounting structure, foundation etc complete as per specification and tender document. 4440
445 4450 MS - 1.6 KL 4450 1 EA
446 4460 HSD-2.8 KL 4460 1 EA
447 4470 SKO- 0.4 KL 4470 1 EA
448 4480 ETHANOL-0.4 KL 4480 1 EA
449 4490 Installation,testing and commissioning of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF main header line complete as per specifications and tender document. \n(Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) (TLF HEADER-5,ITT-2) 4490 4 EA
450 4500 Tank Farm Management System 4500
451 4510 Installation, integration, testing and commissioning of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 4510
452 4520 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 4520
453 4530 SKO : 2X2 4530 4 EA
454 4540 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 4540
455 4550 MS :3X2, HSD :3X2, Ethanol :2X2 4550 16 EA
456 4560 For U/G horizontal product tanks 4560
457 4570 MS, HSD, SKO,ETHANOL, Bio-Diesel 4570 8 EA
458 4580 Installation,integration,testing and commissioning of Non-contact type Radar level gauges with instrument accuracy of +/-3 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 4580
459 4590 FIRE WATER, SLUDGE 4590 5 EA
460 4600 Installation,integration,testing and commissioning of Guided wave RADAR type level gauge with transmitter , instrument accuracy of +/- 3 mm or better,in built digital display, along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) as per specification. 4600
461 4610 For Additive tanks 4610 2 EA
462 4620 For Blue Dye Dosing 4620 1 EA
463 4630 Installation,integration,testing and commissioning of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. 4630
464 4640 With minimum 8 elements temperature sensor (for A/G vertical tanks) 4640
465 4650 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 4650
466 4660 SKO 4660 2 EA
467 4670 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 4670
468 4680 MS, HSD ,ETHANOL 4680 8 EA
469 4690 For U/G horizontal product tanks 4690
470 4700 MS, HSD, SKO,ETHANOL, Bio-Diesel 4700 8 EA
471 4710 Installation,integration,testing and commissioning of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 4710
472 4720 For A/G vertical tanks - Three elements 4720
473 4730 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 4730
474 4740 SKO 4740 2 EA
475 4750 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 4750
476 4760 MS, HSD ,ETHANOL 4760 8 EA
477 4770 For U/G horizontal product tanks-One element 4770
478 4780 MS, HSD, SKO,ETHANOL, Bio-Diesel 4780 8 EA
479 4790 Installation,integration,testing and commissioning of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 4790
480 4800 For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) 4800 20 EA
481 4810 For U/G Product tanks 4810 8 EA
482 4820 For water tanks 4820 4 EA
483 4830 For Sludge tank 4830 1 EA
484 4840 Installation,integration,testing and commissioning of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document 4840
485 4850 For A/G Vertical Product tanks 4850 10 EA
486 4860 For U/G horizontal product tanks 4860 8 EA
487 4870 Installation,integration,testing and commissioning of parallel redundant Communication Interface Units (CIU) including all accessories etc for tank farm management system complete as per specification and tender document. 4870
488 4880 For Primary Radar gauges installed on A/G vertical , under ground product tank, water tank ,slope ,additive & Sludge tank etc. 4880 1 SET
489 4890 For Secondary Radar Gauges installed on A/G product tanks 4890 1 SET
490 4900 Installation,integration, testing and commissioning of 1 no. of Redundant TFMS Server (Form Factor:Rack ,Mountable in 19" rack ) along with 1 no. rack type (1U) ,one no. Min. 19" LED monitor with keyboard & mouse ,suitable for 19" mounting & 24x7 operation, Licensed OS (latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed software from Radar Gauge OEM etc complete as per specification and tender document. 4900 1 SET
491 4910 Installation,integration,testing and commissioning of TFMS Workstation with minimum 27" LED colour monitor, keyboard, mouse, KVM Switch, Licensed OS(latest supported by TFMS software), Licensed Antivirus, Licensed latest MS Office professional, TFMS licensed client software from same Radar Gauge OEM etc complete as per specification and tender document. \nNote:CPU of control room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost 4910
492 4920 19" Rack type at Control Room, form factor - Rack, CPU height - 2U (Maximum) 4920 1 EA
493 4930 Blue Dye Dosing System 4930
494 4940 Installation, integration,testing and commissioning of SKO Blue Dye Dosing Skid comprising of 1 no. SS Blue dye tank of Min. capacity of 500 Ltrs, Blue Dye dosing pumps of minimum capacity of 200 LPH along with Flameproof Motor (2 Nos.) , 1 no. agitator with FLP motor, Mild Steel Skid, NRVs, Flanged ball valves, Pressure Relief Valve, pulse dampener, Pressure transmitter with inbuilt display unit and keypad, solenoid valves (4 nos.), Turbine flow meters (2 nos. - for calculating the volume of SKO receipt into blue dye tank and volume of diluted Blue dye dosed into SKO receipt header line), Rotameter, Strainer with DPT, piping, flanges, auxiliary potential free contacts/serial communication for remote operation and feedback of the pumps, starter etc. complete as per specifications, drawing and tender document.\n\nNote: Blue dye to be injected in SKO receipt header line during product receipt. Provision to be made for diluting the blue dye with SKO tapped from the main receipt line before dosing as per drawing , Auto flushing of blue dye dosing system complete as per specification and tender document. 4940 1 LS
495 4950 Installation of A106 Gr B pipe Dia 25 mm from Blue Dye tank to SKO receipt header line (for dosing purpose) and from SKO receipt header line to Blue dye tank (for dilution & flushing purpose) complete as per specification and tender document. The job includes necessary installation of hardware like reducers, Elbows, equal Tees ,unequal Tees, Flanges, Coupling, Ball Valves for Isolation etc as required complete as per specification and tender document. 4950 300 RM
496 4960 Installation, integration,testing and commissioning of Exd/FLP Emergency Stop push button stations, mushroom head type with protection cover to avoid accidental activation along with mounting structure, accessories etc complete as per specification and tender document. 4960 1 EA
497 4970 Push Buttons Outside Dyke Walls 4970
498 4980 Installation,integration,testing and commissioning of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS, along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. 4980
499 4990 For ROSOVs (A/G product tank's inlet, outlet and recirculation line) 4990 43 EA
500 5000 ESD PUSH BUTTON STATION 5000
501 5010 Installation,testing and commissioning of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. 5010
502 5020 Local ESD Push Button Station ( Each Battery of TLF -2 no., TLF pump house - 1 no., TW unloading P/H- 1 no., TW unloading area- 13 Nos. (1 no. after every 4 wagons,TW loading area- 13 Nos. (1 no. after every 4 wagons) 5020 30 EA
503 5030 Plant ESD Push Button Station ( Each battery of TLF - 2 No., Main entry/exit to Tank Wagon loading area from Terminal- 2 No., Cluster-13 No.) 5030 17 EA
504 5040 Installation, integration, testing and commissioning of ESD push button stations (for indoor application), mushroom head type with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. (control room - 1 no., security room - 1 no., TM's cabin - 1 no.) 5040 3 EA
505 5050 Control Room equipments 5050
506 5060 Design, engineering, installation, configuration, integration, testing and commissioning of redundant fault tolerant Integrated Distributed Control System (DCS) along with DCS Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Input Output modules, Power supply units, Relays with base, barriers, TBs, Redundant host communication ports, Serial Interface Modules, HART modules, other communication modules, HMI , wirings, glands, plugs, other modules/ hardware required for interfacing with all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: Any other hardware, software, OPC server, Historian Server, storage, firewall, functional control key board etc required as per tender specification and design requirements, the same to be provided by the vendor at no additional cost to IOCL. 5060 1 SET
507 5070 Design, installation, configuration, integration, testing and commissioning of Complete Terminal Automation Software along with required licences, dongle/keys, GUI, SCADA etc meeting the complete functional and technical requirements of the tender document. \nVendor to provide required software, licences, dongle/keys, GUI, SCADA etc for TAS Management Server, Distributed Control System, Operator work stations, fire fighting OIC, Alarm display and annunciation OIC, Engineering Work Stations(for safety PLC & DCS), Web Server, OPC Server, Historian Server / work station, any other devices connected to Control & Management LAN of the integrated Distributed Control System complete as per specification and tender document.\nTAS software shall be interfaced with following but not limited to major sub-systems / equipments alongwith GUI development for monitoring, logging, reporting, controls & interlocks etc as per specification and tender document.\n- Safety PLC\n- TAS-Management Server\n- TLF Automation System (TT reporting, registration & entry system, TT Queuing, FAN generation, TT registration number reading system, Photo pass management system,TT crew authorization system,Bay allocation, Additive Dosing system, Ethanol blending System, Interface with TLF equipments like BCU, MFM, Barrier Gates, Bay Queue Display, Bay allocation Display, Invoice generated display, rack monitors, Proximity card readers etc)\n-Tank Wagon loading Automation system (Rake inventory System,Rake registration system, FAN generation, Tank wagon allocation, Interface with TWG equipments like BCU, MFM etc,SAP-TWG integation)\n-Tank Wagon unloading Automation system\n-Tank Lorry Decantation System\n-TT calibration System\n-Bio Diesel Blending system - ANPR and Face recognisation 5070 1 LS
508 5080 -- Valve Automation System (ROSOVs, MOVs, DBBV, MCS Interface, SOVs, etc)\n-Tank Farm Management System ( TFMS Server, Primary & Secondary Radar Gauging, AOPS, Level transmitters, Level Switch, Density probes, MSTW, CIU etc)\n- Pipeline/ Refinery PLC Interface, OMC PLC interface\n - MCC, Pump, Borewell, DG Sets, Air compressors, VFDs\n- PA paging Interface \n- HC Detection System Interface\n-FAS Interface, Fire Fighting System, HVLR, Fire Alarm System Interface, Fire Engines, DG Set, Jockey pumps, Foam pumps, CFFS, Sprinkler & Fixed foam pourer system etc\n- VRU Package Units\n- Effluent Treatment plant\n- CCTV systems\n- Access Control System\n- SKO Blue Dye Dosing System\n- ESD System, Emergency panel, Power ESD, Local ESD, Wailing sirens\n- Pressure Transmitters\n- UPS & Power distribution boards etc\n- Interface with IOCL SAP through firewall\n- Visitor Management Software for setup, configuration, operation, events, history and archiving, recording, printing etc. complete as per specification and tender document - Any other Third Party Interface/ devices as per scope of the work order etc\nNote: The offered software shall also includes fault detection module and Web Server software for remote over IOCL Intranet across India as detatiled in the tender document.\n\n\n\n 5080
509 5090 Design, engineering, installation, configuration, integration, testing and commissioning of Redundant SIL 3 TUV/ EXIDA certified Safety PLC along with PLC Panels, Marshalling Panels, Biometric fingerprint cum contactless smart card reader with accessories, limit switches, Dual redundant Input Output modules, Power supply units, Relays with base, barriers, TBs, Dual Ethernet ports per processor, Serial Interface Modules, HMI , wirings, glands, plugs, other modules/ hardware required for interfacing all the required field and control room equipments including spare requirements, licenses, tags, GUI, licensed OPC compliant software etc complete as per specification and tender document.\nNote: The offered safety PLC shall be of the same make family of the integrated Distributed Control System. 5090 1 SET
510 5100 Design, engineering, installation, configuration, integration, testing and commissioning of redundant TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LCD/LED monitor of minimum size of 19" suitable for 24x7 operation along with High availability redundancy software working on redundant (Primary and Secondary) hot standby mode , keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document.\n OR\nDesign, engineering, installation, configuration, integration, testing and commissioning of Dual Mode Redundant Grade with built in redundancy TAS Management Server (Rack type mountable in 19" rack ) along with 1 no. rack type (1U) LED monitor of minimum size of 19" suitable for 24x7 operation, keyboard drawer, optical mouse and combo 4 port KVM switch, OS, Antivirus, SQL, oracle, RDBMS (license copy) etc complete as per specifications and Tender Document. \n\nTAS Management Servers (TAS-MS) shall have either of the above mentioned configuration meeting the complete specification and tender requirements. \n\nIn addition, the TAS-MS shall be configured to have Zero Downtime to repair, Full data redundancy shall be provided using proven technology , it shall also provide port level redundancy.The system solution shall be capable of self fault detection and isolation, all necessary hardware/software configuration etc to achieve the same shall be included. 5100 1 LOT
511 5110 Installation & commissioning of 42 U Rack Enclosure cabinet/System cabinet with 19" rack size, along with accessories like Biometric fingerprint cum contactless smart card reader for front & back door seperately with accessories, limit switches, earthing arrangements, breaker, fuses, terminal blocks and wiring etc complete as per specification and tender document for mounting of below mentioned equipments. 5110
512 5120 For mounting of TAS Management Servers along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, Ethernet switch, GSM modems, MCBs etc as per specification and tender document. 5120 1 EA
513 5130 For mounting of Redundant ACS cum photopass management Server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking components, MCBs etc as per specification and tender document. 5130 1 EA
514 5140 For mounting of Redundant TFMS Server along with associated rack mounted monitors, rack mounted keyboard, mouse, 4 port industrial grade KVM switches, power adapters, networking & OFC components, CIUs, MCBs etc as per specification and tender document. 5140 1 EA
515 5150 For mounting of Rack mounted Master Control Stations for MOVs & DBBVs along with power adaptors, MCBs, required accessories etc as per specification and tender document. 5150 3 EA
516 5160 For mounting of Rack mounted CPUs of Control room console workstation (Rack type) , one number 19" rack mounted monitor, rack mounted keyboard, mouse, KVM switches for connection of all CPUs along with power adaptors, MCBs, required accessories etc as per specification and tender document. 5160 2 EA
517 5170 Installation, configuration, integration, testing and commissioning of Operator Interface Console Computer (OIC) with minimum 27" colour LED monitor,keyboard, mouse,KVM Switch, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. \nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 5170
518 5180 19" Rack mounted at Control Room, form factor - Rack , Max. 2U height ( 3 OICs, 1 for alarm Display, 1 for fire fighting System) 5180 5 EA
519 5190 Installation, configuration, integration, testing and commissioning of Operator Interface Console Computer (OIC) minimum 27" colour LED monitor, keyboard, mouse, software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. 5190
520 5200 Tower type in TM's Cabin 5200 1 EA
521 5210 Installation, configuration, integration, testing and commissioning of Engineering Workstation (EWS) with minimum 27" colour LED monitor, keyboard, mouse, KVM Switch, Safety PLC & DCS software, HMI software, SCADA, GUI, OS, Antivirus, MS office professional etc. complete as per specifications and tender document. (Locations: 1 no. in CR for both DCS and Safety PLC) \nNote: In case of Tower type workstation is supplied in place of Rack type.Rack mount Kit to be provided for installation in the 19" Rack.\nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 5210
522 5220 19" Rack mounted at Control Room, Form factor - Rack , Max. 2U height 5220 1 EA
523 5230 Installation, configuration, integration, testing and commissioning of Tank Truck Entry System (TTES) Workstation with minimum 27" colour LED monitor, keyboard, mouse,KVM switch, software, SCADA, GUI, OS, Antivirus etc. complete as per specifications and tender document. (Locations: 2 nos. in Customer service Block +1 no. in Control room+1 no. in Lock shed room) \nNote: CPU of contol room shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 5230
524 5240 19" Rack mounted at Control Room, Form factor - Rack , Max. 2U height 5240 2 EA
525 5250 Tower type in Customer service block (2 nos.) and Lock shed room (1 no.) 5250 3 EA
526 5260 Installation, configuration, integration, testing and commissioning of minimum 19" colored LED monitor (19" Rack type at panel Room, form factor - Rack, height - 1U) with , KVM switch, Rack type keyboard, mouse etc located in Control Room complete as per specifications and Tender Document. (For CPUs of Console kept in panel room) 5260 2 EA
527 5270 Installation, configuration, integration, testing and commissioning of Web Server (Rack type mountable in 19" rack ) ,Rack type CPU -2U Max. , LED monitor of minimum size of 27" suitable for 24x7 operation, keyboard, mouse, KVM Switch, web application software, SCADA, GUI, OS, Antivirus etc located in panel Room complete as per specifications and Tender Document. \nNote: CPU shall be kept in Panel room in 42 U Rack. KVM extender & reciever is to be supplied at no additional cost. 5270 1 EA
528 5280 Installation, integration, maintenance and operation of the NMS System covering Network Devices operational in Terminal Automation System. The Offered Network Management Solution (NMS) solution should support at least the following:\n• All the proposed NMS Components should be from single vendor. \n• NMS Software should support Graphical view up to port level for the all the devices.\nDiscovery of Network Elements.\n• Real time Traffic monitoring of Network Links and Devices with Historical reports for various periods.\n• Management of SNMPv1, SNMPv2, SNMPv3 & MIB etc.\n• Configuration of thresholds for Generating alarms.\n• Configuration of alarm actions (visual, audible, email, sms etc.) for each \nNetwork element.\n• Should be able to provide secured windows based consoles / secured web based consoles for accessibility to NMS.\n• Should have web browser interface with user name and Password Authentication.\n• Administrator/ Manager should have privilege to create/modify/delete user.\n• NMS should have support for SNMPv3 & IPv6, including dual-stack IPv4 & IPv6 to provide flexibility in protocol strategy and implementation.\n 5280 1 LS
529 5290 Installation, configuration, integration, testing and commissioning of Terminal servers (rack mounted) with inbuilt/externally mounted lightening and Surge Protection Device Type (1+2) at all Serial ports, for interfacing and integration of card readers, Bay Queue display units (Indoor & outdoor), LED Display unit for TT reporting,at Main Entry gate & Exit gate and TLF Entry gate for Bay allocation with TAS.In case the above listed equipments do not come with open communication protocol compatible to be directly interfaced with DCS Serial / MODBUS TCP IP module complete as per specification and tender document.\n\nNote: Terminal Servers to be configured in Dual Redundant mode. 5290
530 5300 16 ports at Customer service Block 5300 2 EA
531 5310 Installation, configuration, integration, testing and commissioning of 24 ports Layer 3 Managed Ethernet Switches (10/100/1000 MBPS) with SFP, copper, fibre modules/ports along with accessories for connecting Plant management LAN equipments like CCTV System, TAS - MS Server/ Redundant OPC server, TFMS Server, TFMS work station, OICs, IOCL intranet for SAP connectivity through fire wall, Network printers, Access Control Server, Web Server Access over IOCL Intranet, connecting to OIC/ work stations etc which needs to be connected to both Plant Management LAN and Plant Control LAN for getting the entire GUIs of Complete Terminal Automation System and any other third party devices for interfacing with DCS etc.\nNote: \n1. Ethernet Switches to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs and any other equipment which are to be connected to above switch and the communication is through OFC cable. 5310 2 EA
532 5320 Installation, configuration, integration, testing and commissioning of minimum 24 ports Layer 2 Managed Ethernet Switches (10/100/1000 MBPS) along with SFP, copper, fibre modules, accessories for connecting equipments installed in Plant Control LAN like TAS- MS Servers, OICs, TTES cum TWES , EWS, OPC Servers, Fire fighting OICs, Alarm Display OIC, DCS, Safety PLC, inter connecting building work stations etc as per system architecture and design requirement complete as per specification and tender document.\nNote:\n1. The switches are to be configured in Dual Redundant mode.\n2. OFC ports to be provided for connecting interbuilding LANs, and any other equipment which are to be connected to above switch and the communication is through OFC cable. 5320 2 EA
533 5330 Installation, configuration, integration, testing and commissioning of Layer 2 Managed Ethernet Switches along with accessories for connecting BCU with TAS, equipments installed in Customer service room, Lock room, Security room, Terminal Manager room and other TAS equipments as per system architecture and design requirement complete as per specification and tender document.\nNote: \n1. Ethernet switches for BCU communication shall have suitable mounting arrangement to mount inside FLP JBs. \n2. The switches are to be configured in Dual Redundant mode.\n3. All OICs, Workstations, Servers other than that of CCTV, ACS & TFMS are to be connected to both plant management and control LAN so that all the GUIs can be seen in all the PCs irrespective of its nomenclature like TTES, OIC, EWS, TM PC etc.\n4. Printers to be connected to Plant Management LAN and to be configured to all PCs, Workstation, TTES etc so that printout command can be issued from any of the Machine. 5330
534 5340 For BCU integration at TWG-26 Nos & TT Calibration shed-4 Nos (copper ports of 10/100/1000 MBPS) 5340 30 EA
535 5350 For connecting all MODBUS TCP IP devices ( any other devices) to DCS Ethernet port directly for integration (copper ports of 10/100/1000 MBPS)- to be located in Control Room ( Minimum 8 nos. copper ports and 2 nos. optical ports) 5350 4 EA
536 5360 At Lock Shed - copper ports of 10/100/1000 MBPS [control LAN - 2 nos. & Management LAN - 2 nos.] ( Minimum 8 nos. copper ports and 2 nos. optical ports) 5360 4 EA
537 5370 At Admin Building for TM cabin - copper ports of 10/100/1000 MBPS [control LAN - 2 nos., Management LAN - 2 nos., CCTV - 2 no.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 5370 6 EA
538 5380 At customer service Room - copper ports of 10/100/1000 MBPS [control LAN - 2 nos. & Management LAN - 2 nos.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 5380 4 EA
539 5390 At Security Room - copper ports of 10/100/1000 MBPS [control LAN - 2 nos.,CCTV - 2 no.] (Minimum 8 nos. copper ports and 2 nos. optical ports) 5390 4 EA
540 5400 At Driver rest room - copper ports of 10/100/1000 MBPS [Managent LAN - 2 nos.] (Minimum 4 nos. copper ports and 2 nos. optical ports) 5400 2 EA
541 5410 Installation, testing and commissioning of industrial grade redundant Serial to Ethernet converter of 8 port with mounting acessories etc complete in all respect as per specification and tender document. (Ports:- 6 Main + 2 Spare) 5410
542 5420 For MFM and other serial devices integration to DCS -TLF 5420 4 EA
543 5430 For MFM and other devices integration to DCS -TWG 5430 13 EA
544 5440 Installation, testing and commissioning of Wall mounted/wheel mounted Network Rack-minimum 19U 19" Rack for mounting of Terminal Server/Server/Client PC/Ethernet switches/LIU/ OFC components along with accessories like power sockets, MCBs, fan, mounting accessories etc complete in all respective at Security Room, TM room, Invoice Room, Customer service room for TAS equipments 5440 3 EA
545 5450 Installation, testing and commissioning of Wall mounted Network Rack-minimum 12U 19" Rack for mounting of Terminal Server/Ethernet switches/LIU/ OFC components along with accessories like power sockets, MCBs, fan, mounting accessories etc complete in all respective at Security Room, TM room, Invoice Room, Customer service room for TAS equipments 5450 4 EA
546 5460 Installation, configuration, integration, testing and commissioning of Monochrome Laser Printer along with accessories for TAS and TFMS report printing in control room (2 nos.) and 2 nos. at security room complete as per specifications and tender document. 5460 4 EA
547 5470 Installation, configuration, integration, testing and commissioning of heavy duty high speed laser printer along with Printer Stand and accessories for invoice printing in lock shed room, complete as per specifications and tender document. 5470 2 EA
548 5480 Installation, integration, testing and commissioning of parallel redundant UPS of minimum capacity of 60 KVA or as per load calculation (whichever is higher) for entire TAS equipments and third party devices integrated with TAS and powered through TAS UPS with 30% spare capacity for future load connection. The scope also includes supply of parallel battery bank (2x50%) for minimum back up time of ½ hour at full load (rated capacity) along with stand, supports for mounting of the UPS and batteries etc complete as per specification and tender document. The batteries shall be Sealed Maintenance free type. 5480 1 SET
549 5490 Installation, integration, testing and commissioning of UPS Power Distribution Panel along with Biometric fingerprint cum contactless smart card reader for front and rear gate sepearately with accessories for powering DCS Panel, Safety PLC Panel, TAS-MS, OIC, EWS, TFMS System, TTES, printers, Bay Instruments other control room equipments, Tank Farm Instruments, CCTV system, Fire Detection System, Access control system, Bay Queue Display boards, other display boards, ROSOV ESD port, header line instruments and any other TAS equipments where UPS power are required for smooth un-interrupted operation. Miscellaneous Instrumentation comprising of suitable MCCBs for Isolation, MCB etc are to be provided. The panel shall be complete in all respects with necessary indication lamps for powering, necessary control wiring with digital voltmeter & digital ammeter separately for UPS and Auxilliary supply for front and rear seperately etc as per specifications and tender document.\nNote: Minimum 20% spare power points to be made available for future use. 5490 1 LS
550 5500 Installation & fixing of Open desk operator consoles, chairs, printer tables etc complete as per specification and tender document. 5500
551 5510 Open desk operator consoles for mounting of monitor in two tiers , 2 nos. of key boards, 2 nos. of mouse, accesscories e.g. Telephone,VHF sets, Master control station for PA paging etc complete as per specification and tender document.\n(For mounting of 3 nos. OICs monitor, 1 no. Alarm Display OIC monitor, 1 no. Fire fighting OIC monitor, 1 no. TTES monitor , 1 TFMS workstation monitor, 1 no. CCTV client monitor,1 no. EWS monitor,1 Web server, storage etc.) 5510 10 EA
552 5520 Installation, integration, configuration, testing and commissioning of IP based Redundant GSM modem suitable for 24x7 operation along with accessories for auto SMS as per specification and tender document. 5520 1 Set
553 5530 Installation, integration, configuration, testing and commissioning of video wall along with 1 no. Of hooter ,ack push button,accecories , cables etc for fire fighting cum critical Alarm display & annuniciation cum CCTV complete as per specifications and tender document. In control room:-Windows for all cameras should be available onsingle screen of 300-400 cm2 for min. 150 no. CCTV camera. \nAdditional Two Number (min. 55” each or meeting size of video wall) for Alarm LED display and Fire fighting display. 5530 1 EA
554 5540 Installation, integration, configuration, testing and commissioning of video wall along with complete accecories , cables etc for CCTV complete as per specifications and tender document. In location in charge room:-viewing window size should be preferably be between 250-300 cm2 ( in two pages) for CCTV camera 5540 1 EA
555 5550 Installation, integration, configuration, testing and commissioning of video wall along with complete accecories , cables etc for CCTV complete as per specifications and tender document. In security cabin:-viewing window size should be preferably be between min. 150-200 cm2 ( in two pages) for CCTV camera 5550 1 EA
556 5560 Installation, integration, configuration, testing and commissioning of of minimum 55" HD LED monitor along with 1 no. of hooter, ACK push button, mounting accessories, cables etc for critical alarms display & annunciation complete as per specifications and tender document. 5560 1 EA
557 5570 Installation, integration, configuration, testing and commissioning of of minimum 75" HD LED monitor along with mounting accessories, cables etc for Fire fighting system display complete as per specifications and tender document. 5570 1 EA
558 5580 Hydrocarbon Detection system 5580
559 5590 Conducting fire and hydrocarbon vapour mapping study through reputed agencies having proven track record of conducting similar studies for oil installation across globe,using standard licensed software along with submission of study reports as per specification and tender document. 5590 1 EA
560 5600 Installation, integration, calibration, testing and commissioning of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document. 5600
561 5610 Point type Infrared detector\n(Indicative location: Each tank dyke sump pit inside dyke wall - 5 nos., Near ROSOVs of MS tanks:-12 Nos., Ethanol tanks- 2 nos., TLF pump seal (MS+Ethanol) - 5 Nos and TW loading (MS)-3 Nos,TW decantation-1 No. MS,Sludge pump seal-2 No., Pump house drain pit - 4 no.; Vapour recovery system drain pit - 1 no.) 5610 35 EA
562 5620 Open path type Infrared detector (0-90 m) along with alignment telescope, configuration & Testing kit etc (Tentative location: MS tanks & Ethanol tanks covering ROSOVs -16 nos.) 5620 16 EA
563 5630 Open path type Infrared detector (0-90m) along with alignment telescope, configuration & testing kit etc (Tentative location: TLF- 1 Nos, Sick wagon- 1No., TT decantation -1No and TW Product pump house - 1 no., Product PH manifold TLF & TW- 4 nos.) 5630 8 EA
564 5640 Open path type Infrared detector (0-40 m) along with alignment telescope, configuration & Testing kit etc (Tentative location: MS tanks & Ethanol tanks covering ROSOVs -4 nos.) 5640 1 EA
565 5650 Installation, integration, configuration, testing and commissioning of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessories and structural supports as per specification.( Tentative location : Each product tank dyke (MS+Ethanol)-2 nos., Pump House (TLF+TW+Decnatation) - 1 no.,Sludge Pump- 1 No. & Vapour recovery system-1no.) 5650 5 EA
566 5660 Automatic Fire Detection and Alarm System 5660
567 5670 Installation, integration, testing and commissioning of microprocessor based automatic Fire Alarm Panel along with required Software, and hardware like Control module, monitor module, fault isolation module (in built/ External), mounting structure support etc complete as per standard design engineering, specification and tender document.\nLocation : Control Room 5670 1 EA
568 5680 Installation, integration, testing and commissioning of Repeater Panel along with software, hardware, mounting accessories etc required as per standard design Engineer, specifications and tender document complete in all respect. \n(Tentative location : Security Gate - 1 no., Fire Pump House - 1 no.) 5680 2 EA
569 5690 Installation, integration, testing and commissioning of addressable type detectors along with accessories, fault isolation module (Inbuilt/ External), structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 5690
570 5700 Combination/Multi-sensor Detector 5700 190 EA
571 5710 Rate of Rise Heat Detector 5710 3 EA
572 5720 IS detector 5720 2 EA
573 5730 Hydrogen Detector 5730 1 EA
574 5740 Installation, integration, testing and commissioning of Manual Call Point along with accessories, fault isolation module (Inbuilt/ External) and structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 5740
575 5750 Ex-proof and weather proof MCP 5750 14 EA
576 5760 Weather proof MCP 5760 21 EA
577 5770 Installation, integration, testing and commissioning of Hooter along with accessories, fault isolation module (inbuilt/ External), structural supports etc required as per standard design engineering, specification and tender document complete in all respect. 5770
578 5780 Weather proof Hooter 5780 17 EA
579 5790 Installation, integration, testing and commissioning of Response Indicator along with accessories, mounting structure etc required as per standard design engineering, specification and tender document complete in all respect. 5790 26 EA
580 5800 Access Control System 5800
581 5810 Installation, integration, testing and commissioning of half man height bi-directional turnstile (tripod) with controller along with accessories, mounting structure, pressure sensor etc required as per standard design engineering, specification and tender document complete in all respect. (Location : License area entry & exit gate - 2 nos. ; Entry/Exit to tank farm area - 2+1=3 nos.) 5810 6 EA
582 5820 Installation, integration, testing and commissioning of Retractable Dual Lane Flap barrier with controller along with accessories, mounting structure, pressure sensor etc required as per standard design, engineering, specification and tender document complete in all respect. (Location: Admin building entry/exit ) 5820 1 set
583 5830 Installation, integration, testing and commissioning of face detection cum fingerprint cum contactless type smart card reader with controller along with 2 nos. of electromagnetic door lock of 600 lb for single door/double door,EM locks for emergency door, 2 nos. of door position magnetic contact with buzzer etc as per specifications and tender document. (Location : control room entry/exit door - 4 nos., Panel room entry/exit door - 4 nos. ) 5830 4 EA
584 5840 Installation, integration, testing and commissioning of Biometric fingerprint cum contactless type smart card reader with controller along with 2 nos. of electromagnetic door lock of 600 lb for single door/double door, 2 nos. of door position magnetic contact with buzzer etc as per specifications and tender document. (Location : Customer Service room- entry/exit door - 2 nos. ) 5840 2 EA
585 5850 Installation, integration, testing and commissioning of Biometric fingerprint cum contactless type smart card reader with controller along with rolling electro magnetic heavy duty Lock/ latch, Sensor, agress switch/ Push Button, power supply unit, software , programming kit etc equired as per standard design engineering, specification and tender document complete in all respect for access control through Panel room Rolling Shutters entry/exit installed at Control Room 5850 1 EA
586 5860 Installation, integration, testing and commissioning of Biometric fingerprint cum contactless type smart card reader along with accessories, software , programming kit etc required as per standard design engineering, specification and tender document complete in all respect. (Turnstile:- security entry/exit gate (bi-directional) - : 2x2 nos. license area entry/exit gates (bi-directional) - 2x2 nos., entry/exit to tank farm area (bi-directional)- 2x2 nos.) ; Flap barrier - 2x2nos.) 5860 16 EA
587 5870 Installation, integration, testing and commissioning of Door Frame Metal Detector, 4 nos. hand held metal detector along with accessories, mounting structure etc complete as per specification and tender document. 5870 1 EA
588 5880 Installation of 2"size SS 304 guiding rail along with mounting accessories complete as per specification and tender document near turnstile/ tripod/flap barrier etc to prevent un-authorised movement. 5880 100 RM
589 5890 Installation, configuration, integration, testing and commissioning of Redudnant ACS Server for photo pass management & visitor management (19" Rack type at panel Room, form factor - Rack, CPU height - 2U) with minimum 19" colored LED monitor, KVM switch, keyboard, mouse, OS, Antivirus etc located in Control Room complete as per specifications and Tender Document. 5890 1 SET
590 5900 Installation, configuration, integration, testing and commissioning of Access Control cum photopass management System Software for setup, configuration, operation, events, history and archiving, alarm monitoring, recording, printing, time and attendance etc. complete as per specification and tender document including hardwired interface with TAS for ESD input. 5900 1 LS
591 5910 Installation, configuration,integration, testing and commissioning of Client workstation of ACS cum Photopass management with minimum 27" coloured monitor,keyboard, mouse,KVM switch for Rack CPU, OS, Antivirus, HD coloured video camera (for taking visitors photograph) etc for ID badging & issuing of Visitor pass/Photo pass at security Room & other etc. complete as per specifications. 5910
592 5920 Rack Type - CPU in panel room with KVM sitch; Keyboard, mouse along with monitor etc. to be installed in security room for visitor pass 5920 1 EA
593 5930 Tower Type in Photopass room for TT crew/Contractor etc. 5930 1 EA
594 5940 Installation, configuration, integration, testing and commissioning of Laser printer (Monochrome) for Visitor pass printing having flexibility to print on A4, A5, A6 paper complete as per specification and tender document. 5940 1 EA
595 5950 Installation, configuration, integration, testing and commissioning of Colour photo pass printer along with integrated/seperate scanner for photo pass printing as per specification and tender document. 5950 1 EA
596 5960 IP BASED CCTV SURVEILLANCE SYSTEM 5960
597 5970 Installation, configuration, integration, testing and commissioning of HD IP Fixed Dome camera with IR and MFZ lens (2MP) along with power supply unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 5970 8 EA
598 5980 Installation, configuration, integration, testing and commissioning of HD IP PTZ Camera (2MP) along with power supply unit (POE based) with POE injector (industrial grade),with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 5980 35 EA
599 5990 Installation, configuration, integration, testing and commissioning of IP Fixed Bullet cameras with MFZ lens (8MP) – 4K resolution along with power supply unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 5990 8 EA
600 6000 Installation, configuration, integration, testing and commissioning of IP Fixed Box cameras with varifocal lens (8MP) – 4K resolution along with power supply unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 6000 51 EA
601 6010 Installation, configuration, integration, testing and commissioning of Integral Explosion Proof HD IP Fixed Cameras and MFZ lens (2MP) along with power supply unit , with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document. 6010 8 EA
602 6020 Installation , testing & Commissioning of IP Fixed Bullet cameras with IR MFZ lens (8MP) – 4K resolution along with power Installation , testing & Commissioning unit (POE based), with inbuilt/external surge protection unit and mounting accessories etc complete as per specifications and Tender Document.(TT Reporting :-2+TTEntry/Exit:-2+Driver Entry/Exit-2,Helper Entry/Exit-2, Photo Pass issuance:- 2) 6020 10 EA
603 6030 Installation, configuration, integration, testing and commissioning of 4 port Industrial grade layer 2 Managed POE based Ethernet Switch for connecting Cameras with 4 Nos. RJ copper port and 2 Nos. optical fibre ports with inbuilt/external surge protector (Type 1+2) at the input power supply as per specifications and Tender Document. 6030 65 EA
604 6040 Installation, configuration, integration, testing and commissioning of outdoor Explosion proof cum weatherproof housing (IP 65 or better) suitable for installing Layer 2 switch, PSU, LIU and adaptor for Ethernet switch/media convertor, surge protectors and other accessories of CCTV cameras. Supply of required OFC components & accessories like LIU, splice trays, loaded adaptor, blank plates, UTP cables, Fibre patch cords, pigtails, tags, ties, Ethernet cable with RJ45 connector etc complete in all respect for functioning of CCTV camera.The scope also includes supply of Exd. blinding plugs, Exd. double compression cable glands etc as per specifications and Tender Document. 6040 60 EA
605 6050 Installation,errection & foundation of Heavy Duty self supported Hot Dip Galvanized Poles for mounting of CCTV cameras along with civil foundation along with GI foundation bolt, mounting brackets, ladder arrangement (taking into account of safety during climbing) on the pole for installation and maintenance of cameras, SS nut & bolts for fixing camera and other accessories required for complete installation and commissioning of the pole, submission of structural stability certificate based on existing soil bearing capacity and wind speed from Govt. Engineering colleges etc complete as per specifications and Tender Document of below mentioned height of the pole. (Foundation drawing and other details to be submitted prior to installation as per tender document)\nNote: In case pole do not have ladder arrangment for maintenance purpose, then vendor to arrange for ladder for installation & maintenance purpose throughout the contract period including CAMC period at no additional cost to IOCL. 6050
606 6060 10 M pole with cantilever arrangement for mounting of 1 fixed camera at 6m, 2 PTZ camera at 10 m and LED flood light at 8m of the pole across perimeter as per tender 6060 10 EA
607 6070 10 M pole with cantilever arrangement for mounting of 1 fixed camera at 6m and LED flood light at 8m of the pole across perimeter as per tender 6070 41 EA
608 6080 6 M pole 6080 15 EA
609 6090 12 M pole 6090 15 EA
610 6100 Installation, configuration, integration, testing and commissioning of rack mounted CCTV Server (s) along with rack type monitor, optical mouse and combo 4 port KVM switch, OS, Antivirus, LIU etc complete as per specifications and Tender Document. \nNote: In case multiple servers are required to meet the tender requirement, vendor to provide the same at no additional cost to IOCL. In additional to above, Vendor to provide failover server to have redundancy in CCTV server such that failure of one server should not affect the CCTV operation and recording at its full resolution at no additional cost to IOCL. 6100 1 LS
611 6110 Installation, configuration, integration, testing and commissioning of Network Attached Storage ( NAS ) / Storage Attached Network (SAN) for storing recorded video for a minimum period 90 days @ 15 FPS at full resolution & highest Video quality of all cameras (Continuous recording) complete as per specifications and Tender Document. 6110 600 TB
612 6120 Installation, configuration, integration, testing and commissioning of CCTV client work station along with client software & licenses, key board, mouse, hardware & connector for repeat/ Dual display on wall mounted LED screen, OS, Antivirus, etc complete as per specifications and Tender Document. ( Location : Control Room - 2 no., Security room- 1 no. ,Mkt. TM room - 1 no.,Pipeline TM Room - 1 no.)\n\nNote: CCTV Work station shall have provision to connect to 2 nos. of UHD LED monitors . Required hardware & software is to be provided for the same. Incase the offered work station do not have such provision, then additional work station to be provided meeting the tender requirement at no additional cost to IOCL.Marketing CPU for control room & security room shall be kept in Panel room in 42 U Rack. KVM extender & reciever for these CPU is to be supplied at no additional cost. 6120
613 6130 Rack type (2 U) with minimum 27" colored LED monitor :- Control Room - 1 no. ,Security Room - 1 no.(CPU to be kept in Mkt. panel room), Control Room - 1 no.(CPU to be kept in Pipeline Console room) 6130 3 EA
614 6140 Installation , testing & Commissioning of minimum 55" Ultra High Definition (4K) LED Display monitor along with mounting accessories etc complete as per specifications and Tender Document for repeat display of CCTV output. ( Location: Security Room-2 nos., TM Room- 2 nos.) 6140 2 EA
615 6150 Installation , testing & Commissioning of minimum 75" Ultra High Definition (4K) LED Display monitor along with mounting accessories etc complete as per specifications and Tender Document for repeat display of CCTV output. (Location : Control room - 2 nos.) 6150 2 EA
616 6160 Installation , testing & Commissioning of Layer 3 Managed Gigabit Ethernet Switch with minimum 24 ports or as per site requirement + 20 % spare whichever is higher along with SFP, copper, fibre modules, accessories complete as per specifications and Tender Document. \nNote- The switches are required to be configured in dual redundant mode \n 6160 1 EA
617 6170 Installation , testing & Commissioning of Intelligent video operation, control, management, recording & processing software (VMS) complete , Advanced Analytics Software for ANPR and Face recognisation with OS, Antivirus etc including licenses as per specifications and Tender Document with minimum 125 cameras recording, 125 cameras viewing license, 5 LISC licence for remote viewing or as per actual nos. of cameras installed + 20% extra which ever is higher. 6170 1 LS
618 6180 Installation , testing & Commissionin of Advanced Analytics Software for all fixed cameras (including varifocal, MFZ fixed cameras), Auto tracking video analytics for all PTZ camera along with compatible Redundant Analytics Server with OS, Antivirus etc including analytic license for actual number of camera installed + 20 % spare complete as per specifications and Tender Document. 6180 1 SET
619 6190 Miscellaneous 6190
620 6200 Installation, integration, configuration, testing and commissioning of flameproof cum weather proof to IP 65 or better SIL 2 smart pressure transmitter with in built display, SS manifold, isolation valve, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender).\nNote:1. Pressure transmitter at suction shall have range from -1 Kg/cm2.\n2. Underground tank shall have PT in Pump discharge end only. 6200
621 6210 TLF pump Suction end 6210 14 EA
622 6220 TLF pumps Discharge end 6220 14 EA
623 6230 TW loading/unloading pump Suction end 6230 14 EA
624 6240 TW loading/unloading pump Discharge end 6240 14 EA
625 6250 Fire Hydrant lines 6250 4 EA
626 6260 Decantion Pump House 6260 8 EA
627 6270 Stripping Pumps -- Remote Seal Type 6270 10 EA
628 6280 Bio-Diesel Underground tank Discharge Line 6280 2 EA
629 6290 Installation, integration, configuration, testing and commissioning of flameproof cum weather proof to IP 65 or better SIL 2 Smart Differential pressure transmitter with in built display, SS 3 way manifold, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender) 6290
630 6300 Across all TLF pump strainers (loading+unloading) 6300 14 EA
631 6310 Across all TW pump strainers (loading+unloading) 6310 14 EA
632 6320 Decantion Pump House 6320 4 EA
633 6330 Stripping Pumps---Remote Seal Type 6330 5 EA
634 6340 Installation, integration, configuration, testing and commissioning of flameproof cum weather proof to IP 65 or better bi-colour magnetic flap type level gauge (side mounted) along with level transmitter with installed accuracy +/- 6 mm or better along with mounting accessories, complete as per specification and tender document. 6340
635 6350 Foam Tanks 6350 15 EA
636 6360 Foam Daughter Tanks for HVLR 6360 4 EA
637 6370 Fire Engine Service tanks 6370 7 EA
638 6380 DG Set Service Tanks 6380 3 EA
639 6390 Installation, integration, configuration, testing and commissioning of Level switch ( Magnetic Float / displacer type ) for low and high level alarm along with mounting accessories etc as per specifications 6390
640 6400 Static water sump (For Fire water) and TT callibration water sump 6400 2 EA
641 6410 Service water sump 6410 1 EA
642 6420 Installation, integration, configuration, testing and commissioning of Wailing siren along with controller with a provision to operate locally as well as from control room, mounting accessories etc complete as per specification and tender document. 6420 1 EA
643 6430 Installation, integration, configuration, testing and commissioning of Digital Rodent Repellent System along with mounting accessories for main controller(s) & transducers etc complete as per specification and tender document (Minimum nos of transducers: Control Room - 12 nos., Customer service room- 4 nos., Invoice room - 4 nos. & Security Room - 4 nos.) 6430 1 LS
644 6440 Installation, integration, configuration, testing and commissioning of Ex-proof and weather proof Hooter cum Beacons along with accessories, mounting structure etc complete as per specification and tender document for audio visual alarm at field in case the MOVs installed at tank dyke drain and tank water draw off line is not fully closed. (HSD-1,MS-2,ETH-1,SKO-1,ATF-2)\nLocation : Near each tank dyke and to be installed outside dyke. 6440 6 EA
645 6450 Installation, integration, configuration, testing and commissioning of Solenoid valves (SOV) of 25 /32/50/65 NB (as per line size) along with one no. of isolation by pass valve to bypass the SOV with associated piping, mounting accessories etc complete as per specification and tender document. \nNote: SOV need to be supplied factory fitted along with baypass valve and both side flanged option. 6450
646 6460 At the inlet of DG set Service tanks 6460 3 EA
647 6470 At the inlet of Fire Engine Service tanks 6470 7 EA
648 6480 Installation, integration, testing and commissioning of Globe/ball valve of 25/32/40/50 NB (as per line size) along with electrical/electrohydraulic actuator , local indication, Local operation, one no. of isolation by pass valve for bypass with associated piping, mounting accessories etc complete as per specification and tender document. 6480 15 EA
649 6490 Installation, testing and commissioning of MCT block for entire Automation cable entry to Control Room, Admin Building, Invoice Room, Security Room, Customer service room, Driver's Rest Room with minimum 30% spare MCT blocks for future cable entry along with frame and mounting accessories complete as per specification and tender document. 6490 1 LS
650 6500 Installation,testing and commissioning of external surge & Lightening protection devices of suitable connector and type along with accessories complete as per specification and tender document at following places. 6500
651 6510 Type 1+2 SPD - Input power supply of UPS 6510 3 EA
652 6520 SPD (Type 2 / IC category C1,C2,C3,D1) - Serial port of MCS (RJ 45 type) 6520 32 EA
653 6530 Type 1 SPD - Earth pit 6530 10 EA
654 6540 Installation, configuration, integration, testing and commissioning of wireless Repeater required for wireless communication as per tender document 6540 6 EA
655 6550 Installation, configuration, integration, testing and commissioning of wireless Gateway required for wireless communication as per tender document 6550 2 EA
656 6560 Cabling, JB, Earthing: 6560
657 6570 Note: laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc 6570
658 6580 Laying, glanding, ferruling, termination of FRLS Armoured Copper Power cable as per tender specifications. 6580
659 6590 3C x 2.5 sqmm 6590 8000 RM
660 6600 4C x 2.5 sqmm 6600 6000 RM
661 6610 8C x 2.5 sqmm 6610 2300 RM
662 6620 10C x 2.5 sqmm 6620 2000 RM
663 6630 12C x 2.5 sqmm 6630 2000 RM
664 6640 24C x 2.5 sqmm 6640 1500 RM
665 6650 3C x 4 sqmm 6650 800 RM
666 6660 4C x 4 sqmm 6660 1000 RM
667 6670 4C x 6 sqmm 6670 300 RM
668 6680 4C x 10 sqmm 6680 300 RM
669 6690 Laying, glanding, ferruling, termination of FRLS Armoured Aluminium Power cable as per tender specifications. 6690
670 6700 3.5C x 120 sqmm 6700 300 RM
671 6710 Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. 6710
672 6720 2C x 1.5 sqmm 6720 8000 RM
673 6730 3C x 1.5 sqmm 6730 7500 RM
674 6740 4C x 1.5 sqmm 6740 6000 RM
675 6750 6C x 1.5 sqmm 6750 2000 RM
676 6760 8C x 1.5 sqmm 6760 1750 RM
677 6770 10C x 1.5 sqmm 6770 1200 RM
678 6780 12C x 1.5 sqmm 6780 1200 RM
679 6790 16C x 1.5 sqmm 6790 1500 RM
680 6800 18C x 1.5 sqmm 6800 2250 RM
681 6810 20C x 1.5 sqmm 6810 2000 RM
682 6820 24C x 1.5 sqmm 6820 1800 RM
683 6830 32C x 1.5 sqmm 6830 2750 RM
684 6840 36C x 1.5 sqmm 6840 1800 RM
685 6850 48C x 1.5 sqmm 6850 2750 RM
686 6860 Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. 6860
687 6870 1P x 1.5 sqmm 6870 5000 RM
688 6880 2P x 1.5 sqmm 6880 1250 RM
689 6890 3P x 1.5 sqmm 6890 800 RM
690 6900 4P x 1.5 sqmm 6900 1000 RM
691 6910 6P x 1.5 sqmm 6910 900 RM
692 6920 8P x 1.5 sqmm 6920 800 RM
693 6930 10P x 1.5 sqmm 6930 500 RM
694 6940 12P x 1.5 sqmm 6940 500 RM
695 6950 16P x 1.5 sqmm 6950 500 RM
696 6960 18P x 1.5 sqmm 6960 500 RM
697 6970 1T x 1.5 sqmm 6970 250 RM
698 6980 8T x 1.5 sqmm 6980 1050 RM
699 6990 Laying, glanding, ferruling, termination of FS Armoured Copper Power cable as per tender specifications. 6990
700 7000 3C x 2.5 sqmm 7000 3000 RM
701 7010 3C x 4 sqmm 7010 800 RM
702 7020 4C x 2.5 sqmm 7020 1100 RM
703 7030 4C x 4 sqmm 7030 800 RM
704 7040 Laying, glanding, ferruling, termination of FS Armoured Copper Control cable as per tender specifications. 7040
705 7050 2C x 1.5 sqmm 7050 2000 RM
706 7060 3C x 1.5 sqmm 7060 500 RM
707 7070 4C x 1.5 sqmm 7070 1250 RM
708 7080 6C x 1.5 sqmm 7080 600 RM
709 7090 8C x 1.5 sqmm 7090 600 RM
710 7100 10C x 1.5 sqmm 7100 3000 RM
711 7110 12C x 1.5 sqmm 7110 1250 RM
712 7120 18C x 1.5 sqmm 7120 1250 RM
713 7130 24C x 1.5 sqmm 7130 1000 RM
714 7140 32C x 1.5 sqmm 7140 1500 RM
715 7150 36C x 1.5 sqmm 7150 1250 RM
716 7160 48C x 1.5 sqmm 7160 1250 RM
717 7170 Laying, glanding, ferruling, termination of FS Armoured Copper Signal cable as per tender specifications. 7170
718 7180 1P x 1.5 sqmm 7180 3250 RM
719 7190 2P x 1.5 sqmm 7190 3000 RM
720 7200 3P x 1.5 sqmm 7200 900 RM
721 7210 4P x 1.5 sqmm 7210 800 RM
722 7220 1T x 1.5 sqmm 7220 1250 RM
723 7230 laying, glanding, ferruling, termination of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. 7230 1000 RM
724 7240 laying, glanding, ferruling, termination of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. 7240 500 RM
725 7250 laying, glanding, ferruling, termination of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. 7250
726 7260 10 m 7260 25 EA
727 7270 15 m 7270 25 EA
728 7280 20 m 7280 10 EA
729 7290 25 m 7290 12.5 EA
730 7300 30 m 7300 15 EA
731 7310 laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document 7310 12500 RM
732 7320 Fabrication , cutting , laying & connection of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 7320 750 RM
733 7330 Fabrication , cutting , laying & connection of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 7330 2000 RM
734 7340 Laying of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. 7340
735 7350 50 mm 7350 2000 RM
736 7360 100 mm 7360 4000 RM
737 7370 150 mm 7370 2500 RM
738 7380 300 mm 7380 1500 RM
739 7390 600 mm 7390 1000 RM
740 7400 Installation of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. 7400
741 7410 24 ways JB 7410 15 EA
742 7420 18 ways JB 7420 20 EA
743 7430 12 ways JB 7430 25 EA
744 7440 8 ways JB 7440 25 EA
745 7450 6 ways JB 7450 25 EA
746 7460 4 ways JB 7460 25 EA
747 7470 Laying of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. 7470 500 RM
748 7480 Design, fabrication, painting & errection of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc 7480 10 MT
749 7490 Earth Pit 7490
750 7500 Installation, testing and commisioning of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) 7500
751 7510 TLF gantry 7510 2 EA
752 7520 TT earthing 7520 4 EA
753 7530 Control room 7530 4 EA
754 7540 Tank dyke 7540 12 EA
755 7550 Comprehensive AMC - Phase I 7550
756 7560 First Year @4% of the basic CAPEX cost 7560 1 LS
757 7570 Second Year @4% of the basic CAPEX cost 7570 1 LS
758 7580 Third Year @7% of the basic CAPEX cost 7580 1 LS
759 7590 Fourth Year @7% of the basic CAPEX cost 7590 1 LS
760 7600 Fifth Year @10% of the basic CAPEX cost 7600 1 LS
761 7610 Sixth Year @6% of the basic CAPEX cost 7610 1 LS
762 7620 Seventh Year @12% of the basic CAPEX cost 7620 1 LS
763 7630 SUPPLY COMPONENTS PHASE-II 7630
764 7640 TANK WAGON LOADING 7640
765 7650 Supply of Microprocessor based Coriolis mass flow meter for white oil application along with display unit and mounting accessories with adjustable screw support,bellow for vibrations etc complete as per specifications and tender document for loading of following main products \nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no additional cost to IOCL. 7650
766 7660 MS (for line size of 100 mm ) 7660 14 EA
767 7670 HSD (for line size of 100 mm ) 7670 14 EA
768 7680 SKO (for line size of 100 mm ) 7680 14 EA
769 7690 Supply of Strainer cum Air eliminator with differential pressure transmitter with display unit & keyboard across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 7690
770 7700 For product line size 100 mm - TWG 7700 42 EA
771 7710 Supply of Multistage Piston type Digital Control Valve (DCV) along with TRV with two nos. isolation valves at inlet and outlet of TRV with associated piping , secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 7710
772 7720 For product line size 100 mm - TWG 7720 42 EA
773 7730 Supply of piston type, hydraulically operated, solenoid operated ON-OFF Valve with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning, secure key etc along with accessories complete as per specifications and tender document. 7730 336 EA
774 7740 Supply of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF metering skid complete as per specifications and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 7740 48 EA
775 7750 Supply of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermo well, mounting accessories etc complete as per specifications and tender document. \n(Mounting at each TLF loading point on main product for line size 100 mm) 7750 42 EA
776 7760 Supply of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 100 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 7760 42 SET
777 7770 Supply of top loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm) ,vacuum breaker with associated piping for loading arm with the metering skid , Stand post & mounting structure, bonding clip (for bonding of loading arm with TW) etc complete as per specifications and tender document. THe drop tube of loading arm should be 80 mm dia . \nApplication: MS/HSD/SKO/ATF 7770 336 EA
778 7780 Supply of Microprocessor based Field mounted Batch Controller with interface to minimum 4 no. of main product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document.For TWG product loading . out of this item or next item , only one shall be operated & accordingly quantity shall vary. The same shall be clarified while placing Phase 2 SAP work order. 7780 1 EA
779 7790 Supply of Microprocessor based Field mounted Batch Controller with interface to minimum 1 no. of main product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document.For TWG product loading . 7790 42 EA
780 7800 Supply of pre-fabricated Metering Skid (MS structure) for mounting of complete metering equipments as per BOQ and schematic drawing for one main product. The metering assembly comprises of : \n\nMain product line: Strainer cum Air eliminator, Online Master Meter proving manifold, MFM, Spool piece with tapping for Temprature Transmitter installation, Pressure Transmitter, spool piece with tapping for connecting outlet of TRV,DCV, Spool Piece with tapping for TRV installation. \n\nProvision to be made in the skid for mounting of Batch Controller,FLP sockets, FLP junctions boxes (Power, Signal and Control), FLP power isolator switch, interconnecting cables from respective equipment to JBs, cable trays with covers, glands, support, MS structure,Electroforged galvanized grating, nuts, bolts, gaskets, Tees, bends, elbows, WNRF flanges, nozzles, plugs, isolators, any other equipment if required as per design Engineering etc complete as per specification and tender document. \n 7800 42 MT
781 7810 Supply of Mobile Master meter (Master MFM) proving system for line size 100mm consisting of Master Mass flow meter with display unit, Master Temperature Transmitter with RTD with Thermo-well, Mounting accessories suitable for installation on 4" line size, 2 nos. isolation ball valve of 100mm, hose pipe, trolley mounted Master Meter Skid with suitable wheels, FLP JB, FLP double compression glands, power adapter along with accessories (if required) for powering of Master Meter, FRLS Copper Armoured Power & Signal Cable of minimum 15 m each with compatible FLP power plugs for powering the MFM, integration of Mobile Master MFM with TAS and integration of temperature transmitter with Master MFM, supports for mounting the equipments, pipes, flanges, reducers, gaskets, nuts, bolts, studs etc complete as per specification and tender document. 7810 1 SET
782 7820 Supply of Ex-proof field/IS mounted LED lamp along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents. 7820 14 EA
783 7830 Supply of Ex-proof/IS field mounted LCD/LED Display along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents. 7830 14 EA
784 7840 TWG Header line instruments 7840
785 7850 Supply of Bulk Air Eliminator as per product line size and flow requirement including mounting structure, foundation etc complete as per specification and tender document. 7850
786 7860 MS-2.8-KL 7860 1 EA
787 7870 HSD-2.8-KL 7870 1 EA
788 7880 SKO-2.8-KL 7880 1 EA
789 7890 Supply of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with keypad & display unit, SS manifold, 1 no. isolation ball valve, SS tubing, Aluminium canopy/sunshade with mounting accessories etc on the TLF main header line complete as per specifications and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 7890 3 EA
790 7900 Data Entry Terminal along with accessories 7900
791 7910 Supply of Ex/IS Wireless data entry terminal for wagon details along with accessories etc complete as per specification and tender document. 7910 2 EA
792 7920 Supply of Antenna, Pole/structural support ,submission of structural stablity certificate based on existing soil bearing capacity and wind speed from Govt. Engineering colleges, along with access points & required hardware for communication with DET & control room along with accessories etc complete as per specification and tender document. 7920 1 LS
793 7930 Rake inventory management System 7930
794 7940 Supply of Rake inventory management system for Wagon Number identification including with all the Hardware e.g. 2 No. RFID Tags Readers, 2 No. RFID Antenna to read RFID Tags installed on Tank Wagons for readings TW details from both side, Poles of approx 1 to 1.5 m Height,LIU, Network Switch & Port,U7 Monitoring Rack etc and integration with TAS system for inventory management for Rake as per specficiation and tender document. 7940 2 LS
795 7950 Tank Farm Management System 7950
796 7960 Supply of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 7960
797 7970 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 7970
798 7980 SKO : 1X2 7980 2 EA
799 7990 HSD B5 : 2X2 7990 4 EA
800 8000 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 8000
801 8010 BIODIESEL : 2X2 8010 4 EA
802 8020 Supply of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. 8020
803 8030 With minimum 8 elements temperature sensor (for A/G vertical tanks) 8030
804 8040 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 8040
805 8050 SKO : 1 8050 1 EA
806 8060 HSD B5 : 2 8060 2 EA
807 8070 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 8070
808 8080 BIODIESEL : 2 8080 2 EA
809 8090 Supply of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 8090
810 8100 For A/G vertical tanks - Three elements 8100
811 8110 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 8110
812 8120 SKO : 1 8120 1 EA
813 8130 HSD B5 : 2 8130 2 EA
814 8140 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 8140
815 8150 BIODIESEL : 2 8150 2 EA
816 8160 Supply of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 8160
817 8170 For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) 8170 10 EA
818 8180 Supply of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document 8180
819 8190 For A/G Vertical Product tanks 8190 5 EA
820 8200 Push Buttons Outside Dyke Walls 8200
821 8210 Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. 8210
822 8220 For ROSOVs (A/G product tank's inlet, outlet and recirculation line) 8220 13 EA
823 8230 ESD PUSH BUTTON STATION 8230
824 8240 Supply of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. 8240
825 8250 Local ESD Push Button Station ( TW loading & unloading P/H- 2 no., TW Gantry- 14 Nos. (1 no. after every 4 wagons,TW Unloading area- 14 Nos. (1 no. after every 4 wagons) 8250 30 EA
826 8260 Plant ESD Push Button Station ( One in each Cluster-14 No.) 8260 14 EA
827 8270 Cabling, JB, Earthing: 8270
828 8280 Note: Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc 8280
829 8290 Supply of FRLS Armoured Copper Power cable as per tender specifications. 8290
830 8300 3C x 2.5 sqmm 8300 8000 RM
831 8310 4C x 2.5 sqmm 8310 6000 RM
832 8320 8C x 2.5 sqmm 8320 2300 RM
833 8330 10C x 2.5 sqmm 8330 2000 RM
834 8340 12C x 2.5 sqmm 8340 2000 RM
835 8350 24C x 2.5 sqmm 8350 1500 RM
836 8360 3C x 4 sqmm 8360 800 RM
837 8370 4C x 4 sqmm 8370 1000 RM
838 8380 4C x 6 sqmm 8380 300 RM
839 8390 4C x 10 sqmm 8390 300 RM
840 8400 Supply of FRLS Armoured Aluminium Power cable as per tender specifications. 8400
841 8410 3.5C x 120 sqmm 8410 300 RM
842 8420 Supply of FRLS Armoured Copper Control cable as per tender specifications. 8420
843 8430 2C x 1.5 sqmm 8430 8000 RM
844 8440 3C x 1.5 sqmm 8440 7500 RM
845 8450 4C x 1.5 sqmm 8450 6000 RM
846 8460 6C x 1.5 sqmm 8460 2000 RM
847 8470 8C x 1.5 sqmm 8470 1750 RM
848 8480 10C x 1.5 sqmm 8480 1200 RM
849 8490 12C x 1.5 sqmm 8490 1200 RM
850 8500 16C x 1.5 sqmm 8500 1500 RM
851 8510 18C x 1.5 sqmm 8510 2250 RM
852 8520 20C x 1.5 sqmm 8520 2000 RM
853 8530 24C x 1.5 sqmm 8530 1800 RM
854 8540 32C x 1.5 sqmm 8540 2750 RM
855 8550 36C x 1.5 sqmm 8550 1800 RM
856 8560 48C x 1.5 sqmm 8560 2750 RM
857 8570 Supply of FRLS Armoured Copper Signal cable as per tender specifications. 8570
858 8580 1P x 1.5 sqmm 8580 5000 RM
859 8590 2P x 1.5 sqmm 8590 1250 RM
860 8600 3P x 1.5 sqmm 8600 800 RM
861 8610 4P x 1.5 sqmm 8610 1000 RM
862 8620 6P x 1.5 sqmm 8620 900 RM
863 8630 8P x 1.5 sqmm 8630 800 RM
864 8640 10P x 1.5 sqmm 8640 500 RM
865 8650 12P x 1.5 sqmm 8650 500 RM
866 8660 16P x 1.5 sqmm 8660 500 RM
867 8670 18P x 1.5 sqmm 8670 500 RM
868 8680 1T x 1.5 sqmm 8680 250 RM
869 8690 8T x 1.5 sqmm 8690 1050 RM
870 8700 Supply of FS Armoured Copper Power cable as per tender specifications. 8700
871 8710 3C x 2.5 sqmm 8710 3000 RM
872 8720 3C x 4 sqmm 8720 800 RM
873 8730 4C x 2.5 sqmm 8730 1100 RM
874 8740 4C x 4 sqmm 8740 800 RM
875 8750 Supply of FS Armoured Copper Control cable as per tender specifications. 8750
876 8760 2C x 1.5 sqmm 8760 2000 RM
877 8770 3C x 1.5 sqmm 8770 500 RM
878 8780 4C x 1.5 sqmm 8780 1250 RM
879 8790 6C x 1.5 sqmm 8790 600 RM
880 8800 8C x 1.5 sqmm 8800 600 RM
881 8810 10C x 1.5 sqmm 8810 3000 RM
882 8820 12C x 1.5 sqmm 8820 1250 RM
883 8830 18C x 1.5 sqmm 8830 1250 RM
884 8840 24C x 1.5 sqmm 8840 1000 RM
885 8850 32C x 1.5 sqmm 8850 1500 RM
886 8860 36C x 1.5 sqmm 8860 1250 RM
887 8870 48C x 1.5 sqmm 8870 1250 RM
888 8880 Supply of FS Armoured Copper Signal cable as per tender specifications. 8880
889 8890 1P x 1.5 sqmm 8890 3250 RM
890 8900 2P x 1.5 sqmm 8900 3000 RM
891 8910 3P x 1.5 sqmm 8910 900 RM
892 8920 4P x 1.5 sqmm 8920 800 RM
893 8930 1T x 1.5 sqmm 8930 1250 RM
894 8940 Supply of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. 8940 1000 RM
895 8950 Supply of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. 8950 500 RM
896 8960 Supply of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. 8960
897 8970 10 m 8970 25 EA
898 8980 15 m 8980 25 EA
899 8990 20 m 8990 10 EA
900 9000 25 m 9000 12.5 EA
901 9010 30 m 9010 15 EA
902 9020 Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document 9020 12500 RM
903 9030 Supply of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 9030 750 RM
904 9040 Supply of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 9040 2000 RM
905 9050 Supply of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. 9050
906 9060 50 mm 9060 2000 RM
907 9070 100 mm 9070 4000 RM
908 9080 150 mm 9080 2500 RM
909 9090 300 mm 9090 1500 RM
910 9100 600 mm 9100 1000 RM
911 9110 Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. 9110
912 9120 24 ways JB 9120 15 EA
913 9130 18 ways JB 9130 20 EA
914 9140 12 ways JB 9140 25 EA
915 9150 8 ways JB 9150 25 EA
916 9160 6 ways JB 9160 25 EA
917 9170 4 ways JB 9170 25 EA
918 9180 Supply of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. 9180 500 RM
919 9190 Supply of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc 9190 10 MT
920 9200 EARTH PIT 9200
921 9210 Supply of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) 9210
922 9220 TLF gantry 9220 2 EA
923 9230 TT earthing 9230 4 EA
924 9240 Control room 9240 4 EA
925 9250 Tank dyke 9250 12 EA
926 9260 SERVICE COMPONENTS PHASE-II 9260
927 9270 TANK WAGON LOADING 9270
928 9280 Installation, integration, testing and commissioning of Microprocessor based Coriolis mass flow meter for white oil application along with display unit and mounting accessories with adjustable screw support,bellow for vibrations etc complete as per specifications and tender document for loading of following main products \nNote: In case MFM is not having inbuilt ASTM table, vendor has to supply Flow Computers along with accessories as per tender document at no additional cost to IOCL. 9280
929 9290 MS (for line size of 100 mm ) 9290 14 EA
930 9300 HSD (for line size of 100 mm ) 9300 14 EA
931 9310 SKO (for line size of 100 mm ) 9310 14 EA
932 9320 Installation, integration, testing and commissioning of Strainer cum Air eliminator with differential pressure transmitter with display unit & keyboard across the Strainer along with accessories, SS tubing, needle valves etc complete as per specifications and tender document. 9320
933 9330 For product line size 100 mm - TLF 9330 42 EA
934 9340 Installation, integration, testing and commissioning of Multistage Piston type Digital Control Valve (DCV) along with TRV with two nos. isolation valves at inlet and outlet of TRV with associated piping , secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning of the DCV has been done, secure key etc along with accessories complete as per specifications and tender document. 9340
935 9350 For product line size 100 mm - TLF 9350 42 EA
936 9360 Installation, integration, testing and commissioning of piston type, hydraulically operated, solenoid operated ON-OFF Valve with secure locking arrangement of the needle valves to avoid manual throttling of the needle valves after final tuning, secure key etc along with accessories complete as per specifications and tender document. 9360 336 EA
937 9370 Installation, integration, testing and commissioning of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with display unit & keypad, SS manifold, 1 no. isolation ball valve, Aluminium canopy/sunshade with mounting accessories etc on the TLF metering skid complete as per specifications and tender document. \n(Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 9370 48 EA
938 9380 Installation, integration, testing and commissioning of flameproof cum weather proof, Temperature transmitter along with display unit and keypad, RTD, Thermo well, mounting accessories etc complete as per specifications and tender document. \n(Mounting at each TLF loading point on main product for line size 100 mm) 9380 42 EA
939 9390 Installation, integration, testing and commissioning of online proving valves manifold comprising of 1no. manual operated DBBV without actuator and 2 nos. of 100 NB, full bore, zero leakage, fire safe ball valves along with associated piping, Tee connection, gaskets, copper jumpers, fasteners, blind flanges at one end of each ball valves, pipe fittings, WNRF flanges etc for each loading point assembly for making arrangement to connect Mobile master meter for proving of TLF MFM complete as per specifications and tender documents. 9390 42 SET
940 9400 Installation, testing and commissioning of bottom loading arm of size 100 mm NB along with 1 no. full bore isolation ball valve (100 mm), API Coupler, break away coupler, parking stand with compatible API adaptor, Ex-proof/intrinsic safe position sensor for parking stand, associated piping for connecting loading arm with the metering skid , mounting structure etc complete as per specifications and tender document. \nApplication: MS, HSD, SKO, ATF 9400 336 EA
941 9410 Installation, integration, configuration, testing and commissioning of Microprocessor based Field mounted Batch Controller with interface to minimum 6 no. of main product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document. 9410
942 9420 For TWG product loading 9420 1 EA
943 9430 Installation, integration, configuration, testing and commissioning of Microprocessor based Field mounted Batch Controller with interface to minimum 1 no. of main product in Flameproof and weather proof enclosure along with accessories like double compression glands, Exd Plugs, hoods, structural supports etc complete as per specification and tender document. 9430
944 9440 For TWG product loading 9440 42 EA
945 9450 Installation of pre-fabricated Metering Skid (MS structure) for mounting of complete metering equipments as per BOQ and schematic drawing for one main product. The metering assembly comprises of : \n\nMain product line: Strainer cum Air eliminator, Online Master Meter proving manifold, MFM, Spool piece with tapping for Temprature Transmitter installation, Pressure Transmitter, spool piece with tapping for connecting outlet of TRV,DCV, Spool Piece with tapping for TRV installation. \n\nProvision to be made in the skid for mounting of Batch Controller,FLP sockets, FLP junctions boxes (Power, Signal and Control), FLP power isolator switch, interconnecting cables from respective equipment to JBs, cable trays with covers, glands, support, MS structure,Electroforged galvanized grating, nuts, bolts, gaskets, Tees, bends, elbows, WNRF flanges, nozzles, plugs, isolators, any other equipment if required as per design Engineering etc complete as per specification and tender document. \n 9450 42 MT
946 9460 Note: \n1. All the equipments, JBs, cable trays, interconnecting cables etc as stated above to be installed and loop tested at factory. Complete assembly to be dispatched at site. The skid to be designed and fabricated by the party taking into consideration of all the equipment sizing, space available for mounting of the skid at the Top of the tank wagon gantry etc. The design Engineering along with weight calculation of individual skid excluding equipments to be submitted to IOCL prior to taking up fabrication job for review purpose. Payment shall be made based on theoretical weight calculation of the skid excluding weight of equipments, JBs, cable trays. The rate is also inclusive of surface preparation, powder coating, painting, electroforged grating, transportation of the skid to site etc complete in all respect. \n2. All unuse nozzle/ tapping/ opening to be blind flanged.\n 9460
947 9470 Installation,integration, testing and commissioning of Ex-proof field/IS mounted LED lamp along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents. 9470 14 EA
948 9480 Installation,integration, testing and commissioning of Ex-proof/IS field mounted LED Display along with FLP double compression glands and Ex-Proof-plugs, structural supports etc complete as per specifications and tender documents. 9480 14 EA
949 9490 TWG Header line instruments 9490
950 9500 Installation,testing and commissioning of Bulk Air Eliminator as per product line size and flow requirement including mounting structure, foundation etc complete as per specification and tender document. 9500
951 9510 MS-2.8-KL 9510 1 EA
952 9520 HSD-2.8-KL 9520 1 EA
953 9530 SKO-2.8-KL 9530 1 EA
954 9540 Installation, integration, testing and commissioning of flameproof cum weather proof, min SIL 2 certified smart pressure transmitter with keypad & display unit, SS manifold, 1 no. isolation ball valve, SS tubing, Aluminium canopy/sunshade with mounting accessories etc on the TLF main header line complete as per specifications and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) (Range 0-15 kg/cm2) 9540 3 EA
955 9550 Data Entry Terminal along with accessories 9550
956 9560 Installation, integration, configuration, testing and commissioning of Ex/IS Wireless data entry terminal for wagon details along with accessories etc complete as per specification and tender document. 9560 2 EA
957 9570 Installation, integration, configuration, testing and commissioning of Antenna, Pole/structural support ,submission of structural stablity certificate based on existing soil bearing capacity and wind speed from Govt. Engineering colleges, along with access points & required hardware for coomunication with DET & control room along with accessories etc complete as per specification and tender document. 9570 1 LS
958 9580 Rake inventory management System 9580
959 9590 Installation, integration, configuration, testing and commissioning of Rake inventory management system for Wagon Number identification including with all the Hardware e.g. 2 No. RFID Tags Readers, 2 No. RFID Antenna to read RFID Tags installed on Tank Wagons for readings TW details from both side, Poles of approx 1 to 1.5 m Height,LIU, Network Switch & Port,U7 Monitoring Rack etc and integration with TAS system for inventory management for Rake as per specficiation and tender document. 9590 2 LS
960 9600 Tank Farm Management System 9600
961 9610 Installation, integration, testing and commissioning of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 9610
962 9620 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 9620
963 9630 SKO :1X2, 9630 2 EA
964 9640 HSD B5: 2X2 9640 4 EA
965 9650 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 9650
966 9660 BIO DIESEL : 2X2 9660 4 EA
967 9670 Installation,integration,testing and commissioning of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. 9670
968 9680 With minimum 8 elements temperature sensor (for A/G vertical tanks) 9680
969 9690 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 9690
970 9700 SKO :1X2, 9700 1 EA
971 9710 HSD B5: 2X2 9710 2 EA
972 9720 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 9720
973 9730 BIO DIESEL : 2X2 9730 2 EA
974 9740 Installation,integration,testing and commissioning of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 9740
975 9750 For A/G vertical tanks - Three elements 9750
976 9760 For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges) 9760
977 9770 SKO :1X2, 9770 1 EA
978 9780 HSD B5: 2X2 9780 2 EA
979 9790 For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges) 9790
980 9800 BIO DIESEL : 2X2 9800 2 EA
981 9810 Installation,integration,testing and commissioning of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) 9810
982 9820 For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges) 9820 10 EA
983 9830 Installation,integration,testing and commissioning of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document 9830
984 9840 For A/G Vertical Product tanks 9840 5 EA
985 9850 Installation, integration, testing and commissioning of all above Tank farm equipments with primary & secondary CIU , TFMS server , OIC , software , DCS, Safety PLC , SCADA , TAS software whereever required for complete functionality & logic as the case may be, 9850 1 EA
986 9860 Push Buttons Outside Dyke Walls 9860
987 9870 Installation,integration,testing and commissioning of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS, along with FLP double compression gland, Tag plates,TBs, mounting structure, accessories etc complete as per specifications and tender document. 9870
988 9880 For ROSOVs (A/G product tank's inlet, outlet and recirculation line) 9880 13 EA
989 9890 ESD PUSH BUTTON STATION 9890
990 9900 Installation,testing and commissioning of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation along with mounting structure complete as per specification and tender document. 9900
991 9910 Local ESD Push Button Station ( TW loading & unloading P/H- 2 no., TW Gantry- 14 Nos. (1 no. after every 4 wagons,TW Unloading area- 14 Nos. (1 no. after every 4 wagons) 9910 30 EA
992 9920 Plant ESD Push Button Station ( One in each Cluster-14 No.) 9920 14 EA
993 9930 Cabling, JB, Earthing: 9930
994 9940 Note: laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc 9940
995 9950 Laying, glanding, ferruling, termination of FRLS Armoured Copper Power cable as per tender specifications. 9950
996 9960 3C x 2.5 sqmm 9960 8000 RM
997 9970 4C x 2.5 sqmm 9970 6000 RM
998 9980 8C x 2.5 sqmm 9980 2300 RM
999 9990 10C x 2.5 sqmm 9990 2000 RM
1000 10000 12C x 2.5 sqmm 10000 2000 RM
1001 10010 24C x 2.5 sqmm 10010 1500 RM
1002 10020 3C x 4 sqmm 10020 800 RM
1003 10030 4C x 4 sqmm 10030 1000 RM
1004 10040 4C x 6 sqmm 10040 300 RM
1005 10050 4C x 10 sqmm 10050 300 RM
1006 10060 laying, glanding, ferruling, termination of FRLS Armoured Aluminium Power cable as per tender specifications. 10060
1007 10070 3.5C x 120 sqmm 10070 300 RM
1008 10080 Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. 10080
1009 10090 2C x 1.5 sqmm 10090 8000 RM
1010 10100 3C x 1.5 sqmm 10100 7500 RM
1011 10110 4C x 1.5 sqmm 10110 6000 RM
1012 10120 6C x 1.5 sqmm 10120 2000 RM
1013 10130 8C x 1.5 sqmm 10130 1750 RM
1014 10140 10C x 1.5 sqmm 10140 1200 RM
1015 10150 12C x 1.5 sqmm 10150 1200 RM
1016 10160 16C x 1.5 sqmm 10160 1500 RM
1017 10170 18C x 1.5 sqmm 10170 2250 RM
1018 10180 20C x 1.5 sqmm 10180 2000 RM
1019 10190 24C x 1.5 sqmm 10190 1800 RM
1020 10200 32C x 1.5 sqmm 10200 2750 RM
1021 10210 36C x 1.5 sqmm 10210 1800 RM
1022 10220 48C x 1.5 sqmm 10220 2750 RM
1023 10230 Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. 10230
1024 10240 1P x 1.5 sqmm 10240 5000 RM
1025 10250 2P x 1.5 sqmm 10250 1250 RM
1026 10260 3P x 1.5 sqmm 10260 800 RM
1027 10270 4P x 1.5 sqmm 10270 1000 RM
1028 10280 6P x 1.5 sqmm 10280 900 RM
1029 10290 8P x 1.5 sqmm 10290 800 RM
1030 10300 10P x 1.5 sqmm 10300 500 RM
1031 10310 12P x 1.5 sqmm 10310 500 RM
1032 10320 16P x 1.5 sqmm 10320 500 RM
1033 10330 18P x 1.5 sqmm 10330 500 RM
1034 10340 1T x 1.5 sqmm 10340 250 RM
1035 10350 8T x 1.5 sqmm 10350 1050 RM
1036 10360 Laying, glanding, ferruling, termination of FS Armoured Copper Power cable as per tender specifications. 10360
1037 10370 3C x 2.5 sqmm 10370 3000 RM
1038 10380 3C x 4 sqmm 10380 800 RM
1039 10390 4C x 2.5 sqmm 10390 1100 RM
1040 10400 4C x 4 sqmm 10400 800 RM
1041 10410 Laying, glanding, ferruling, termination of FS Armoured Copper Control cable as per tender specifications. 10410
1042 10420 2C x 1.5 sqmm 10420 2000 RM
1043 10430 3C x 1.5 sqmm 10430 500 RM
1044 10440 4C x 1.5 sqmm 10440 1250 RM
1045 10450 6C x 1.5 sqmm 10450 600 RM
1046 10460 8C x 1.5 sqmm 10460 600 RM
1047 10470 10C x 1.5 sqmm 10470 3000 RM
1048 10480 12C x 1.5 sqmm 10480 1250 RM
1049 10490 18C x 1.5 sqmm 10490 1250 RM
1050 10500 24C x 1.5 sqmm 10500 1000 RM
1051 10510 32C x 1.5 sqmm 10510 1500 RM
1052 10520 36C x 1.5 sqmm 10520 1250 RM
1053 10530 48C x 1.5 sqmm 10530 1250 RM
1054 10540 Laying, glanding, ferruling, termination of FS Armoured Copper Signal cable as per tender specifications. 10540
1055 10550 1P x 1.5 sqmm 10550 3250 RM
1056 10560 2P x 1.5 sqmm 10560 3000 RM
1057 10570 3P x 1.5 sqmm 10570 900 RM
1058 10580 4P x 1.5 sqmm 10580 800 RM
1059 10590 1T x 1.5 sqmm 10590 1250 RM
1060 10600 laying, glanding, ferruling, termination of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. 10600 1000 RM
1061 10610 laying, glanding, ferruling, termination of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. 10610 500 RM
1062 10620 laying, glanding, ferruling, termination of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. 10620
1063 10630 10 m 10630 25 EA
1064 10640 15 m 10640 25 EA
1065 10650 20 m 10650 10 EA
1066 10660 25 m 10660 12.5 EA
1067 10670 30 m 10670 15 EA
1068 10680 laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document 10680 12500 RM
1069 10690 Fabrication , cutting , laying & connection of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 10690 750 RM
1070 10700 Fabrication , cutting , laying & connection of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. 10700 2000 RM
1071 10710 Laying of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. 10710
1072 10720 50 mm 10720 2000 RM
1073 10730 100 mm 10730 4000 RM
1074 10740 150 mm 10740 2500 RM
1075 10750 300 mm 10750 1500 RM
1076 10760 600 mm 10760 1000 RM
1077 10770 Installation of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. 10770
1078 10780 24 ways JB 10780 15 EA
1079 10790 18 ways JB 10790 20 EA
1080 10800 12 ways JB 10800 25 EA
1081 10810 8 ways JB 10810 25 EA
1082 10820 6 ways JB 10820 25 EA
1083 10830 4 ways JB 10830 25 EA
1084 10840 Laying of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. 10840 500 RM
1085 10850 Design, fabrication, painting & errection of Structural steel (MS) for erection of cable bridge (if required) for laying of above ground cables at road crossing or any other place within the Terminal including painting, Civil foundations, nuts, bolts, washers, cleats, stiffners, gussets, base plate etc 10850 10 MT
1086 10860 EARTH PIT 10860
1087 10870 Installation, testing and commisioning of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation.\nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) 10870
1088 10880 TLF gantry 10880 2 EA
1089 10890 TT earthing 10890 4 EA
1090 10900 Control room 10900 4 EA
1091 10910 Tank dyke 10910 12 EA
1092 10920 SIL VERIFICATION / VALIDATION 10920
1093 10930 SIL verification from approved third party agencies. (For SIFs as per SIL Assessment study report/detail engg). All required documentation as per specs and other documentation mentioned elsewhere in tender scope has to be submitted. Complete as per specification / tender documents. 10930 1 LS
1094 10940 Validation of entire Safety System (SIS) for SIFs (for e.g. AOPS -SIF) shall be carried out from approved third party agency prior to trial period. Automation contractor shall bear the responsibility of its co-ordination and logistics. The third party has to submit a detailed report along with certification for SIS which is to be approved by IOCL along with all other required documentation as per specification and tender documents. 10940 1 LS
1095 10950 Services for Safety Instrumented System testing after installation in presence of safety, operation and engg. Team from user. Demonstration of safety system during pre OISD / OISD & statutory audits & there after periodic testing. Complete as per specifications / tender documents. 10950 1 EA
1096 10960 OTHER SERVICES 10960
1097 10970 Providing training to IOCL employee as per schedule/Module for 2 days as per tender document 10970 1 Module
1098 10980 Submission of detailed system design, Engineering, Documentations etc as per tender document 10980 1 LS
1099 10990 Submission of Final Detailed system design, Engineering, Documentations, as built drawings etc complete as per tender 10990 1 LS
1100 11000 Resident Engineer support on quarterly basis in case of shift addition during CAMC period 11000 1 EA
1101 11010 Design, development, modification, configuration, testing and commissioning of existing TAS software, DCS/PLC logic, GUI etc for implementation of following features after FAT (if required) or during CAMC period as stated in tender document. The job includes necessary tro-& fro travel, lodging, boarding, food etc required for implementation at site complete in all respect and as per direction of EIC. 11010
1102 11020 Loading point addition 11020 1 per LP
1103 11030 Product pump addition 11030 1 per pump
1104 11040 Product tank addition 11040 1 per tank
1105 11050 Product code change 11050 1 per product code
1106 11060 Deputation of an Engineer at IOCL HO, Mumbai for co-ordination, follow up, MIS preparation, filing, verifying the design Engineering etc throughout the project execution period excluding CAMC period. 11060 1 per Month
1107 11070 Comphrehensive AMC - PART -II 11070
1108 11080 Comprehensive Annual Maintenance Contract for a period of Seven years for entire Terminal Automation System after successful completion of SAT as described in Technical Bid. \nCost of all the required spares, hardwares, software modification, tools and tackles, ladders, labours, Preventive & Breakdown maintenance Service, calibration of instruments, proving & stampings of metering equipments, rectification/ replacement of faulty TAS equipment etc required for running and maintenance of the entire Terminal Automation System to the desired performance level throughout the contract period of CAMC is included in the item rates and the same has to be borne by the Vendor. \nThe scope also includes posting of Resident Engineer (s) to take care of running and maintenance of the entire Automation System complete as per the tender document. 11080
1109 11090 First Year @4% of the basic CAPEX cost 11090 1 LS
1110 11100 Second Year @4% of the basic CAPEX cost 11100 1 LS
1111 11110 Third Year @7% of the basic CAPEX cost 11110 1 LS
1112 11120 Fourth Year @7% of the basic CAPEX cost 11120 1 LS
1113 11130 Fifth Year @10% of the basic CAPEX cost 11130 1 LS
1114 11140 Sixth Year @6% of the basic CAPEX cost 11140 1 LS
1115 11150 Seventh Year @12% of the basic CAPEX cost 11150 1 LS
Disclaimer :