Repair/ Maintenance Street Lights And Its Connected Items At Harni Camp And Harni Airfield At Af Stn Baroda, GE AF BARODA-Gujarat

Military Engineer Services-MES has published Repair/ Maintenance Street Lights And Its Connected Items At Harni Camp And Harni Airfield At Af Stn Baroda. Submission Date for this Tender is 25-09-2019. Brackets and Braces Tenders in GE AF BARODA Gujarat. Bidders can get complete Tender details and download the document.




Tender Notice

21669983
Repair/ Maintenance Street Lights And Its Connected Items At Harni Camp And Harni Airfield At Af Stn Baroda
Open Tender
Indian
Gujarat
GE AF BARODA
25-09-2019

Tender Details

Repair / Maintenance Street Lights And Its Connected Items At Harni Camp And Harni Airfield At Af Stn Baroda , Comprehensive Maintenance Of Street Light / High Mast Light / Tarmac Light Fitting Comprising Of 150W / 250W / 400W Hpsv / Hpmv / Lamp Fittings Of Any Make Any Model Fitted On The Pole At Any Height With Any Type Of Fixing Arrangement By Replacing The Ignitor , Ballasts Capacitor , Flexible Wire , Clamps , Nuts And Bolts And Lugs All As Directed By Engineer In Charge . ( Comprehensive Maintenanace Includes Only Repairing Of Street Lights Or Taking Down Street Light Fitting Of Any Capacity From Any Height From The Pole And Increase Or Decrease The Height Of The Fixing Arrangement By Removing The Bent Pipe And Clamps And Refixing It To The Proper Height And Removing All The Hanging Wires , Cables , Pvc Pipes , Old Rusted Clamps , Hanging Aluminium Wires , Hanging Grasses Etc And Tightening Of All Nuts , Bolts , Clamps And Fixing Of The Street Light Completed All As Specified And Directed , All As Above Item No 1 . 00 But For 400W Hpsv / Hpmv / Lamp Fittings Of Any Make Any Model Fitted On 11 Sqn Hanger At Height 18 Meter From Ground And High Mast Light At Runway Completed All As Specified And Directed , Note For Item No 1 & 2 Above . ( I ) T&P Including Ladder Or Any Other Arrengement For Repair Works Shall Be Arranged By The Cotractor At His Own Cost . The Quoted Rate Shall Be Deemed To Be Included For The Same . ( Ii ) Parts Required For Comprehensive Manintanance Shall Be Measured & Paid Seprately Under Respective Item Of Boq . . , S&F In Repair Of Mh / Hpsv / Hpmv Single End Tubular Type Lamp For Following Luminaires :- , Metal Hallide 400 Watt , Hpsv / Hpmv 250 Watt , S&F In Repair Of Open Construction Heavy Duty Copper Ballast For Following Luminaires :- , 400 Watt Mh Fitting , 250 Watt Mh Fittings , 2X24 Watt T-5 Fitting , S&F In Repair Of Electronic Ignitor Suitable For Suitable For Hpsv / Mh Fitting :- , Hpsv / Mh Fitting 400 Watt , Hpsv / Mh Fitting 250 Watt , Hpsv / Mh Fitting 150 Watt , Hpsv / Mh Fitting 70 Watt , S&F In Repair Of Lamp Holders Porcelain Threaded Type Suitable For Following Luminaires :- , Hpsv / Mh 400 Watt , Hpsv / Mh 250 Watt , 4X24 Watt T-5 Fitting , S&F In Repair Of Capacitor For Street Light Fitting Of Following Capacity :- , 70 Watt , 150 Watt , 250 Watt , 400 Watt , S&F In Repair Of Energy Conservation T 5 Fitting Road Way Luminaries Of Capacity 4X24 Watt Complete All As Specified And Directed . , S&F In Repair Of Tube Light Rod Suitable For Energy Conservation T 5 Lamp Road Way Luminaries Of Capacity 4X24 Watt Complete All As Specified And Directed . , S&F In Repairs Aesthetically Designed Led Security Light Luminiareis Of 70 Watts System Wattage For Energy Saving Having Ip 66 Degree Of Protection , With Minimum System Efficiency As>85% , Made Of Pressure Die Casting Aluminum Housing Power Coated In Graphite Grey And Heat Resistant Toughened Glass With Excellent Thermal Management Led Shold Have Lens Optics And Vandal Proof Prismatic Poly Carbonate Covers For Ensuring Efficient Optics And Uniform Distribution Of Light Fitting Should Have Operating Voltage Range Of 120-270 Vac , Thd<10% , P . F> . 95 The Fitting Should Have In Built Surge Protector Of 5 Kv And Cri>70 With Cct 5700 K Complete All As Specified And Directed . , S&F In Repairs Aesthetically Designed Led Security Light Luminaires Of 20 Watts System Wattage For Energy Saving Having Ip 66 Degree Of Protection , With Minimum System Efficiency As>85% , Made Of Pressure Die Casting Aluminum Housing Power Coated In Graphite Grey And Heat Resistant Toughened Glass With Excellent Thermal Management Led Shold Have Lens Optics And Vandal Proof Prismatic Poly Carbonate Covers For Ensuring Efficient Optics And Uniform Distribution Of Light Fitting Should Have Operating Voltage Range Of 120-270 Vac , Thd<10% , P . F> . 95 Complete All As Specified And Directed . , S&F In Repair Of Aviation / Obstruction Light Fitting With All Connection Accessories As Nuts , Bolts , Clamps As Per Site Complete All As Specified And Directed . , Supply , Install , Testing & Commissioning In Repairs High-Powered Electrically Driven Internally Mounted Power Motor For Raising And Lowering Of The Lantern Carriage Of High Mast Light Complete All As Specified And Directed . , Material And Labour For Stainless Steel Wire Ropes Overall Diameter Of The Rope Shall Not Be Less Than 6 Mm The Breaking Load Of Each Rope Shall Not Be Less Than 2000 Kg Suitable For High Mast Light Complete All As Specified And Directed . , M&L For Repairing The Raising And Lowering Mechanism Of High Mast Light With Opening The Gear Box And Replace The All Essential Spare Parts For Smooth Functioning Of Raising And Lowering Of The Lantern Carriage For Maintenance Purposes Complete All As Specified And Directed . , S&F In Repair Of Ground Test Terminal Point ( 750X450x300mm ) Out Door Type Fabricated From 3 . 15 Mm Thick Crca Sheet Duly Welded And Painted With One Coat Of Red Oxide Over Two Coats Synthetic Enamel Paint Front & Back Door Opening With Locking Arrangement Rybn With Aluminium Bus Bar ( Suitable Upto 100A ) , 25X3 . 15Mm With Insulator , Nut & Bolt One Incomming The Aluminium U / G Cable And One Out Going Aluminium Conductor U / G Cable With Angle Iron Stand 300Mm Height Including Pcc And Form Work Complete All As Specified And Directed . , Supply , Laying , Testing And Commissioning Xlpe Insulated Armoured Heavy Duty Electric Cable With Aluminium Conductor Cable 1100 Volts Grade In Trenches Ducts , Pipe On Walls , Poles Of Following Sizes Including Taking Down Old Unsv Cable Complete All As Specified And Directed . , 35 Sqmm 3 . 5 Core , 16 Sqmm 4 Core , 10 Sqmm 2 Core , Supply And Fix In Repair Of Street Light Frp Pvc Box Consisting Of 01 No Mcb 10 Amps , 10 Ka Capacity Including Aluminium Strip Bus Bar For Incoming And Outgoing Cable With Necessary Connection Duly Fixed On The Pole With Suitable Size Of Ms Clamp Complete All As Specified And Directed . , Dismantling / Taking Out Old Defective Cable Form Street Light Poles ( Junction Box To Fitting ) And Supply And Fix Aluminium Conductor Multistranded Including Pvc Conduit On Poles Or Passing Through Steel Or Pvc Conduit Pipe 1100 Volts Grade With Suitable Cable Lugs , Clamps , Nut Bolts Etc Complete As Per Specification As Required Of Following Sizes :- , 2 . 5 Sqmm Two Core Conductor . , 4 . 0 Sqmm Two Core Conductor , S&F In Repair Of Bracket With Clamp For Fixing Street Light Fitting Made Out Of Gi Pipe Light Grade Including Bending To Shape Of Length 1 . 5 M Complete :- , 25 Mm Dia , 40 Mm Dia , Supply , Install , Testing & Commissioning Of Cpri Approved Lt Panel Board , Outdoor Type , Floor Mounted , Factory Made Suitable For 415 Volt , 3 Ph , 4 Wire , 50 Hz , Ac Supply System Having Busbars Chamber With Copper Bus Bars Duly Insulated By Insulation Of Ryb Colour 300 Amps Rating Mounted On Porcelain Insulators . The Panels Shall Be Factory Made , Double Door , Made Out Of 3 . 15 Mm Thick Ms Sheet ( Crca ) Totally Enclosed Dust , Vermin & Rust Proof Front Operated , Front & Rear Opening With Locking Arrangement Fixed With Ms Angle Iron Frame Of Sie 50X50x6 Mm And Duly Painted With Two Coats Of Synthetic Enamel Paint Over A Coat Of Red Oxide Primer With Colour As Directed Including Internal Wiring With Multistranded Copper Conductor Cable Of Suitable Size Incl Lugs And Cable Gland To Incoming And Outgoing Cable Etc Including Taking Down Old Unserviceable Panel All As Directed At Site And Comprising Of The Following:- , ( I ) Alluminium Bus Bar 100 Ams Capacity - 04 Nos ( Ii ) Mccb 4 Pole 440 Volts 35 Ka 3 Phase , Cap 63 Amp - 01 No ( Iii ) Mcb Spn 32 Amp 10Ka -06 Nos ( V ) Digital Multi -Function Meter Messure Voltage , Current Frequency Power Factor ( Digital Type ) 0- 300 Amps-

Key Value

Document Fees
INR 500 /-
EMD
INR 28000.0 /-
Tender Value
INR 14 Lakhs /-

BOQ Items

Name of Work : REPAIR/ MAINT STREET LIGHTS AND ITS CONNECTED ITEMS AT HARNI CAMP AND HARNI AIRFIELD AT AF STN BARODA
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Comprehensive maintenance of street light/High Mast light/Tarmac light fitting comprising of 150W/ 250W/ 400W HPSV/ HPMV/ lamp fittings of any make any model fitted on the pole at any height with any type of fixing arrangement by replacing the ignitor, ballasts capacitor,flexible wire,clamps,nuts and bolts and lugs all as directed by Engineer in charge. (Comprehensive maintenanace includes only repairing of street lights or taking down street light fitting of any capacity from any height from the pole and increase or decrease the height of the fixing arrangement by removing the bent pipe and clamps and refixing it to the proper height and removing all the hanging wires,cables,PVC pipes,old rusted clamps,hanging aluminium wires,hanging grasses etc and tightening of all nuts,bolts,clamps and fixing of the street light completed all as specified and directed 400 Each Job
2 2 All as above item No 1.00 but for 400W HPSV/ HPMV/ lamp fittings of any make any model fitted on 11 SQN Hanger at height 18 meter from ground and high mast light at runway completed all as specified and directed \n 60 Each Job
3 2.01 Note for item no 1 & 2 above.\n(i) T&P including ladder or any other arrengement for repair works shall be arranged by the cotractor at his own cost. The quoted rate shall be deemed to be included for the same.\n(ii) Parts required for comprehensive manintanance shall be measured & paid seprately under respective item of BOQ..
4 3 S&F in repair of MH/HPSV/HPMV single end tubular type lamp for following luminaires :-
5 3.01 Metal Hallide 400 watt 100 Each
6 3.02 HPSV/HPMV 250 watt 50 Each
7 4 S&F in repair of open construction heavy duty copper ballast for following luminaires :-
8 4.01 400 Watt MH fitting\n 70 Each
9 4.02 250 Watt MH fittings 40 Each
10 4.03 2X24 Watt T-5 fitting 120 Each
11 5 S&F in repair of electronic ignitor suitable for suitable for HPSV/MH fitting :-
12 5.01 HPSV/MH fitting 400 watt 15 Each
13 5.02 HPSV/MH fitting 250 watt 15 Each
14 5.03 HPSV/MH fitting 150 watt 15 Each
15 5.04 HPSV/MH fitting 70 watt 15 Each
16 6 S&F in repair of lamp holders porcelain threaded type suitable for following luminaires :-
17 6.01 HPSV/MH 400 Watt 30 Each
18 6.02 HPSV/MH 250 Watt 15 Each
19 6.03 4X24 Watt T-5 fitting 400 Each
20 7 S&F in repair of capacitor for street light fitting of following capacity :-
21 7.01 70 watt 30 Each
22 7.02 150 watt 30 Each
23 7.03 250 watt 30 Each
24 7.04 400 watt 30 Each
25 8 S&F in repair of Energy conservation T 5 fitting road way luminaries of capacity 4x24 watt complete all as specified and directed. 20 Each
26 9 S&F in repair of tube light rod suitable for energy conservation T 5 Lamp road way luminaries of capacity 4x24 watt complete all as specified and directed. 400 Each
27 10 S&F in repairs aesthetically designed LED security light luminiareis of 70 Watts system wattage for energy saving having IP 66 degree of protection,with minimum system efficiency as>85%,made of pressure die casting aluminum housing power coated in graphite grey and heat resistant toughened glass with excellent thermal management LED shold have lens optics and vandal proof prismatic poly carbonate covers for ensuring efficient optics and uniform distribution of light Fitting should have operating voltage range of 120-270 VAC,THD<10%,P.F>.95 The fitting should have in built surge protector of 5 KV and CRI>70 with CCT 5700 K complete all as specified and directed. \n 20 Each
28 11 S&F in repairs aesthetically designed LED security light luminaires of 20 Watts system wattage for energy saving having IP 66 degree of protection,with minimum system efficiency as>85%,made of pressure die casting aluminum housing power coated in graphite grey and heat resistant toughened glass with excellent thermal management LED shold have lens optics and vandal proof prismatic poly carbonate covers for ensuring efficient optics and uniform distribution of light Fitting should have operating voltage range of 120-270 VAC,THD<10%,P.F>.95 complete all as specified and directed. \n\n 20 Each
29 12 S&F in repair of aviation/obstruction light fitting with all connection accessories as nuts, bolts, clamps as per site complete all as specified and directed. 6 Each
30 13 Supply, install, testing & commissioning in repairs high-powered electrically driven internally mounted power motor for raising and lowering of the lantern carriage of high mast light complete all as specified and directed. 4 Each
31 14 Material and labour for stainless steel wire ropes overall diameter of the rope shall not be less than 6 mm the breaking load of each rope shall not be less than 2000 Kg suitable for high mast light complete all as specified and directed. 40 RM
32 15 M&L for repairing the raising and lowering mechanism of high mast light with opening the gear box and replace the all essential spare parts for smooth functioning of raising and lowering of the lantern carriage for maintenance purposes complete all as specified and directed. 4 Each Job
33 16 S&F in repair of ground test terminal point (750x450x300mm) out door type fabricated from 3.15 mm thick CRCA sheet duly welded and painted with one coat of red oxide over two coats synthetic enamel paint front & back door opening with locking arrangement RYBN with aluminium bus bar (suitable upto 100A), 25x3.15mm with insulator, nut & bolt one incomming the aluminium U/G cable and one out going aluminium conductor U/G cable with angle iron stand 300mm height including PCC and form work complete all as specified and directed. 6 Each
34 17 Supply, laying, testing and commissioning XLPE insulated armoured heavy duty electric cable with aluminium conductor cable 1100 volts grade in trenches ducts, pipe on walls, poles of following sizes including taking down old UNSV Cable complete all as specified and directed.
35 17.01 35 sqmm 3.5 core 100 RM
36 17.02 16 sqmm 4 core 150 RM
37 17.03 10 sqmm 2 core 100 RM
38 18 Supply and fix in repair of street light FRP PVC box consisting of 01 No MCB 10 Amps, 10 KA capacity including aluminium strip bus bar for incoming and outgoing cable with necessary connection duly fixed on the pole with suitable size of MS clamp complete all as specified and directed. 60 Each
39 19 Dismantling/ taking out old defective cable form street light poles (Junction box to fitting) and supply and fix aluminium conductor multistranded including PVC conduit on poles or passing through steel or PVC conduit pipe 1100 volts grade with suitable cable lugs, clamps, nut bolts etc complete as per specification as required of following sizes :-
40 19.01 2.5 Sqmm two core conductor. 250 RM
41 19.02 4.0 Sqmm two core conductor 150 RM
42 20 S&F in repair of bracket with clamp for fixing street light fitting made out of GI pipe light grade including bending to shape of length 1.5 m complete :-
43 20.01 25 mm dia 50 Each
44 20.02 40 mm dia 50 Each
45 21 Supply, install, testing & commissioning of CPRI approved LT panel board, outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire , 50 HZ , AC supply system having busbars chamber with copper bus bars duly insulated by insulation of RYB colour 300 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS Sheet (CRCA) totally enclosed dust, vermin & rust proof front operated, front & rear opening with locking arrangement fixed with MS angle iron frame of sie 50X50X6 mm and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable etc including taking down old unserviceable panel all as directed at site and comprising of the following:- 2 Each Job
46 21.01 (i) Alluminium bus bar 100 Ams capacity - 04 Nos\n(ii) MCCB 4 pole 440 volts 35 KA 3 phase , cap 63 Amp - 01 No\n (iii) MCB SPN 32 Amp 10KA -06 Nos\n (v) Digital Multi -function meter messure voltage , Current frequency power factor (digital type ) 0- 300 Amps-01 No
47 22 S&F in replacement steel tubular swaged pole complete with cast iron base plate, final plug, bolts, nuts and screws as specified type 410 SP-31 of length 9 mtr complete all as specified 2 Each
48 23 M&L cement concrete 1:3:6 type C2 using 40 mm graded stone aggregate for foundation of poles/struts/stay etc completed all as specified and directed. 1 CUM
49 24 M&L cement concrete (1:3:6) type C1 using 20 mm graded stone aggregates for pedestal of poles, all including necessary form work, fair finishing to the exposed surfaces using extra cement completed all as specified and directed. 0.5 CUM
50 25 M&L for fixing MCCB 4 pole 100 Amps, 415 volts, 25 KA completed all as specified and directed 4 Each
51 26 M&L for fixing MCCB 4 pole 63 Amps, 415 volts, 25 KA completed all as specified and directed. 3 Each
52 27 M&L for fixing MCCB 4 pole 160 Amps, 415 volts, 10 KA completed all as specified and directed. 3 Each
53 28 S&F in repair of LED driver 75 watt suitable for LED street light 75 watt completed all as specified and directed. 20 Each
54 29 M&L for preparation of existng old painted surface of any description such as LT RCC electric pole of any height and applying one coats of synthetic enamel paint and in white/blue alternative strips of 30 cm width each all around the poles up to 1.5M height from ground level/top of PCC coping completed all as specified and directed. 20 Each Job
55 30 M&L for painting of existing LT Steel poles with two coats of synthetic enamel paint superior quality of silver colour of any hight and applying one coat of synthetic enamel paint upto 1.5 mtr hight from top of PCC pedstal (for bottom portion) at interval 30 cm in yellow/black colour including preparation of existing surfaces complete all as specified and directed. 50 Each Job
56 31 Trimming of tree branches around 3 meter from over head conductor with necessary tools and ladders completed all as specified and directed 50 Each span
57 32 Excavation in trenches not exceeding 1.5 m wide and not exeeding 1.5 m in depth and getting out in soft/loose soil for removing/laying of cable etc completed all as specified and directed. 75 CUM
58 33 M&L well burnt bricks sub class 'B' as in protection of cable laid dry, flat abutting each other width wise completed all as specified and directed 3 Per 1000 Nos
59 34 M&L for sand cushioning to PVC cable with using clean dry and natural river sand gently punning below/around cable completed all as specified and directed.\nNote :- Punned thickness shall be measured for payment. 25 CUM
60 35 Returning, filling excavated soil in trenches including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each completed all as specified and directed. 45 CUM
61 36 Removing surplus excavated soil to a distance not exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point completed all as specified and directed. 30 CUM
62 37 Supply only astronomical timer switch 110 to 240 VAC, LED indication complete all as per site completed all as specified and directed. 5 Each
63 38 Supply only contactor 40 Amps (MNX40) suitable for street light timer completed all as specified and directed. 5 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail