| Name of Work: CONSTRUCTION OF MEDICAL COLLEGE AT VILLAGE KORIYAWAS IN DISTT. MOHINDERGARH. (PDG. ELECTRICAL SERVICES ONLY) | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | SUB-HEAD - I : INTERNAL WIRING Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required.Group -C (1.3.3) | 9241 | Point | |
| 2 | 2 | Group -C | 10302 | Point | |
| 3 | 3 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required Group - B (1.10.02) | 5162 | Point | |
| 4 | 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (1.7.1) | 8450 | Metre | |
| 5 | 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire | 190764 | Metre | |
| 6 | 6 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire | 2440 | Metre | |
| 7 | 7 | 4 x 6 sq.mm + 2 x 6 sq.mm. earth wire | 3450 | Metre | |
| 8 | 8 | 4 x 10 sq.mm + 2 x 6 sq.mm. earth wire | 3685 | Metre | |
| 9 | 9 | 4 x 16 sq.mm + 2 x 6 sq.mm. earth wire | 14138 | Metre | |
| 10 | 10 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (1.14.1) | 3450 | Metre | |
| 11 | 11 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire | 20956 | Metre | |
| 12 | 12 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire | 2010 | Metre | |
| 13 | 13 | 4 x 6 sq.mm + 2 x 6 sq.mm. earth wire | 275 | Metre | |
| 14 | 14 | 4 x 10 sq.mm + 2 x 6 sq.mm. earth wire | 705 | Metre | |
| 15 | 15 | 4 x 16 sq.mm + 2 x 6 sq.mm. earth wire | 720 | Metre | |
| 16 | 16 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. | 6441 | Each | |
| 17 | 17 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. | 3739 | Each | |
| 18 | 18 | Supplying and fixing 25 amps, 240 volts, SPN modular socket outlet, with 2 pole and earth,along with 25 amps \"C\" curve, SP modular MCB with modular cover sheet and concealed GI Box complete in all respect as required. | 438 | Each | |
| 19 | 19 | Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 amps \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. | 50 | Each | |
| 20 | 20 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required | 220585 | Meter | |
| 21 | 21 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required | 51915 | Meter | |
| 22 | 22 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required | 3068 | Each | |
| 23 | 23 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required | 2292.75 | Each | |
| 24 | 24 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required | 233 | Each | |
| 25 | 25 | Supply and fixing movement sensorwith 120 degree detection range, 230 V, 50 Hz., 1000 Watt resistive Load, minimum 7 mtr. Detection distance, -10 to 40 degree celcious working temprature, < 93% RH working humidity, Time delay 8 - 10 sec. min. 3 min. max., ambient light 10 Lux. complete as required. | 26 | Each | |
| 26 | 26 | SUB-HEAD II - FANS & LIGHT FIXTURES: Supply of 2'x2' 31Watt, Indoor Recess mounting LED Square Fitting for Armstrong Ceiling Powder quoted CRCA housing body diffuser of Special Polycarbonate material and driver set complete in all respect, 3600 system lumens, 70mm height with fully covered PMMA diffuser type, 110lm/W, CCT 6500, PF>0.95, THD <10% at full load, CRI>80, Flicker free (Ripple<5% rated output current), 4Kv Surge, Avg Life Class 50000Hrs @L70, complete in all respect. Equivalent to Philips RC380B LED36S -6500 G4 L60 W60 PSU OD | 3663 | Each | |
| 27 | 27 | Supply of 2'x2' 32Watt, Indoor Recess mounting LED Square Fitting for Armstrong Ceiling Powder quoted CRCA housing body diffuser of Special Polycarbonate material and driver set complete in all respect, 4000 system lumens, 125 Lm/W, UGR < 16, CCT 6500, PF>0.95, THD <10% at full load, CRI>80, Flicker free (Ripple<5% rated output current), 4Kv Surge, Avg Life Class 50000Hrs @L70, complete in all respect. Equivalent to Philips RC600B LED40S/865 PSU W60L60 IN | 1617 | Each | |
| 28 | 28 | Supply of 2'x2' 36Watt, Clean Room recess mounting LED Square Fitting, Powder quoted CRCA housing body with clear acrylic cover of Special Polycarbonate material and driver set complete in all respect, with min 3300 system lumens, suitable for front opening. CCT 6500, PF>0.90, THD <10% at full load, CRI>80, & Avg Life Class 50000Hrs @L70, complete in all respect. Equivalent to Philips CR652B LED33S CR CW CA | 300 | Each | |
| 29 | 29 | Supply of 2'x2' 30Watt, Indoor Recess mounting LED Square Fitting for Armstrong Ceiling Powder quoted CRCA housing body diffuser of Special Polycarbonate material and driver set complete in all respect, 3000 system lumens, with fully covered PMMA diffuser type, 100lm/W, CCT 6500, PF>0.90, THD <10% at full load, CRI>80, Avg Life Class 40000Hrs @L70, complete in all respect. | 1051 | Each | |
| 30 | 30 | Supply and fixing of 23 watt 4ft Rail fitting suitable for Ceiling & Suspended mounting only with 2600 system lumens, having Powder coated CRCA housing integrated LEDs, diffuser and searviceable driver set complete in all respect with Avg Life 50k Hrs @L70, 120lumen/W, IP20 complete in all respect. Euivalent to Philips RC780B LED26S-6500 PSU W6L120 OD SI | 2593 | Each | |
| 31 | 31 | Supply, installation, connecting, testing and commissioning of LED 4ft Batten with a nominal system lumen output of 2000 lumens and a minimum system efficacy of 100 lm/W. The luminaire shall have a rated system lifetime of 25,000 burning hours at L70. The luminaire should have a color temperature of 6500K/4000K and CRI>80. The luminaire shall meet IP20 rating with THD < 10% and PF > 0.9. The luminaire housing should made of extrusion Al with a PC diffuser. The total power consumption should not exceed 21W (including driver).Including connection with 1.5 sqmm FRLS PVC insulated copper conductor, Similar to Philips MakeBN021 LED20S | 2872 | Each | |
| 32 | 32 | Supply of high quality sleek & decorative integrated LED luminaire with a minimum system lumen of 15000 Lm and system wattage not exceeding 105W with an efficiency =140 lumen/watt, CCT of 6500K with SDCM of < 3 and CRI > 80. The housing should be of high quality die cast aluminum with PF > 0.95 and THD < 15%. Input voltage of 140-270V. Lifetime of 50K hours @L70. Product should be suitable for continuous operation (16-18 Hrs./day). It should have universal mounting arrangements i.e. Suspension (eyebolt) with a lockable pin. The Ingress protection should be minimum IP65 with an IK rating of 08. High Efficiency polycarbonate lens with beam angle of 54 degree. | 27 | Each | |
| 33 | 33 | Supply of surface/wall mounted occupancy sensor enabled LED Batten with a system lumen output of 4000 lumens and a min system efficacy of 120 lumen/watt, have a CRI > 80. The luminaire is made of CRCA housing and shall have diffused optics. wattage 34W, P.F>0.95, CRI>80, 4kV inbuilt surge protection, & high-low cut-off circuit beyond input voltage 140-270V with auto & restart facility. The encapsulated driver should be replaceable & maintain on site. | 500 | Each | |
| 34 | 34 | Supplying, fixing, connecting, testing and commissioning of LED mirror light luminaire with 10W watt complete with electronic ballast, lamp including connection etc. complete as required,Including connection with 1.5 sqmm FRLS PVC insulated copper conductor similar to Philips Cat. No. ULTRON, STYLISH LIVING | 870 | Each | |
| 35 | 35 | Supplying, fixing, connecting, testing and commissioning of Bulkhead type light fitting complete with , wire guard, holder, electronic ballast 1 x 10 W lamp including connections etc.Including connection with 1.5 sqmm FRLS PVC insulated copper conductor as required similar to Philips Cat. No. Endura LED or equivalent | 250 | Each | |
| 36 | 36 | Supply, installation, connecting, testing and commissioning of LED Patint bed light with a nominal system lumen output of 1553 lumens and a minimum system efficacy of 153 lm/W. The luminaire shall have a rated system lifetime of 50000 burning hours at L70. The luminaire should have a color temperature of 4000K and CRI>80, beam angl of LED 120 degree. The luminaire shall meet IP20 rating with THD < 10% and PF > 0.95. The luminaire housing should made of extrusion Al with a PC diffuser. The total power consumption should not exceed 28 W (including driver).Including connection with 1.5 sqmm FRLS PVC insulated copper conductor, Similar to Wipro LW06-401-XXX-40-WS | 837 | Each | |
| 37 | 37 | Supply, installation, connecting, testing and commissioning of illuminated exit sign with 1 x 6 watt LED lamp including providing maintenance free batteries & charger capable of working for 2 hr duration mounted on ceiling/wall complete with the approved EXIT self adhesive labels as per site requirement as required including connection with 1.5 sqmm FRLS PVC insulated copper conductor similar to Prolite or equivalent | 401 | Each | |
| 38 | 38 | Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 70W Watt. Confirming to IP 66 protection having Company LOGO Engraved complete in all respect with 7700 system lumens, High Power LED with lenses, >110lm/W, PF>0.95, THD <10% at full load, CRI>70, Avg Life Class 50000Hrs@L70, Potted driver Set (NotCircuitory) with BIS No. written on it, Phase to phase Protection at 440V & >300V auto cut and re-start feature | 43 | Each | |
| 39 | 39 | Supply and fixing of Recess mounting round 6 Watt 8 Watt , Cut out Min 125mm, Height Min 40mm,, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr Continuous Operation, 660-880 system lumens, 110lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect, | 2661 | Each | |
| 40 | 40 | Supply and fixing of Surface mounting round 13 Watt 15 Watt , Cut out Min 150mm, Height Min 40mm,, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr Continuous Operation, 1980-2200 system lumens, 110lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect | 2642 | Each | |
| 41 | 41 | Supplying of surface/ recessed type LED down-lighter with high efficiency white reflector and high transmissive diffuser ,fitting complete with, holder, electronic driver, heat sink and LED (less than 10% THD), low depth with die cast aluminium housing 1 x 18 W LED with CRI >70, including with driver connections..Including connection with 1.5 sqmm FRLS PVC insulated copper conductor as required. | 98 | Each | |
| 42 | 42 | Supply and fixing of Surface mounting round 36 to 40 Watt , Cut out Min 150mm, Height Min 40mm,, LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set, suitable for 24Hr Continuous Operation, min. 4000 system lumens, 110lm/W, PF>0.95, THD <10% at full load, CRI>80, Avg Life Class 50000Hrs @L70, complete in all respect | 88 | Each | |
| 43 | 43 | Supply & fixing of 6.5 watt LED wall light fitting. | 963 | Each | |
| 44 | 44 | Supplying, erection, connecting, testing and commissioning of 1200mm sweep ceiling fan complete with blades, down rod, shackle insulator, canopy etc. including providing of electronic step regulator with faceplate matching the existing modular switches as required,Including connection with 1.5 sqmm FRLS PVC insulated copper conductor. | 3946 | Each | |
| 45 | 45 | Supplying, erection, connecting, testing and commissioning of 1400mm sweep ceiling fan complete with blades, down rod, shackle insulator, canopy etc. including providing of electronic step regulator with faceplate matching the existing modular switches as required,Including connection with 1.5 sqmm FRLS PVC insulated copper conductor. | 61 | Each | |
| 46 | 46 | Supply, installation, connecting, testing and commissioning of occupancy cum photo sensor including all wiring to control the light fixtures in the circuit in the existing conduits required similar to Philips cat no. occuswitch | 100 | Each | |
| 47 | 47 | Supplying, erection, connecting, testing and commissioning of following size exhaust fan complete with gravity louver and connection with 3 core flexible wire as required. a) 380mm 900 RPM | 824 | Each | |
| 48 | 48 | b) 450mm 900 RPM | 83 | Each | |
| 49 | 49 | SUBHEAD- III: M.V. PANELS/ DISTRIBUTION BOARD Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required 400 A, 35 KA,TPMCCB (2.2.12) | 2 | Each | |
| 50 | 50 | Supplying and fixing following way ,single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 Way Double Door (MR) | 10 | Nos. | |
| 51 | 51 | 8 way, Double door | 19 | Nos. | |
| 52 | 52 | 12 way, Double Door | 78 | Nos. | |
| 53 | 53 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 Way Double door | 247 | Nos. | |
| 54 | 54 | 6 way Double door | 42 | Nos. | |
| 55 | 55 | 8 way Double door | 23 | Nos. | |
| 56 | 56 | Supplying and fixing following way surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required.(Note : Vertical type MCB TP DB is normally used where 3 phase outlet are required.) 4 way (4 + 12), Double door (2.5.1) | 31 | Nos. | |
| 57 | 57 | 8 way (4 + 24), Double door | 85 | Nos. | |
| 58 | 58 | 12 way (4 + 36), Double door | 172 | Nos. | |
| 59 | 59 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps (2.12.1) | 107 | Nos | |
| 60 | 60 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps (2.15.2) | 142 | Nos | |
| 61 | 61 | 63 amps | 327 | Nos | |
| 62 | 62 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required 40 amps (2.13.1) | 79 | Nos | |
| 63 | 63 | 63 amps | 279 | Each | |
| 64 | 64 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required 100 A, 30 KA,FPMCCB (2.2.13) | 6 | Each | |
| 65 | 65 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole (2.10.1) | 12246 | Nos. | |
| 66 | 66 | Supplying, installation, testing and commissioning of cubical type MV Panel made out of 14 SWG CRCA sheet steel, totally enclosed IP-54 protection, free standing, floor mounted dust and vermin proof, indoor type compartmentalized powder coated of approved shade after antirust treatment (with min seven tanks ) suitable with busbar interconnection with suitable size of copper lead/solid Aluminium strips, control circuits & bottom base channel of MS section not less than 100mmx50mmx5mm (thick), Fabrication shall be done in transportable section ,entire panel shall have a common earth busbar at rear with 2 nos earth stud cable alleys, cable gland plates in two half as required as per single line diagram & specification enclosed with the following switch gears (Floor Panel Light and Power). NOTE: All MCCBs shall have Ics=Icu=100% MCB Should be connected throught terminal Strip of suitable rating MCCB should be Extended rotary operating mechanism with door interlocking with defeat feature and padlock facility. MCCB should have spreader links & phase barriers. The incoming MCCB shall be microprocessor based with inbuilt O/L & S/C release with E/F protection and all Outgoings MCCB's shall be thermal-magnetic based with inbuilt O/L & S/C release. All outgoing MCCB feeders shall have ON/OFF Trip indication lights (LED Type) Make : MCB / RCCB / RCBO : ABB / L&T / Legrand (Lexic) / Schneider (M9-Acti 9) / Siemens AIR CIRCUIT BREAKER (ACB) : ABB (E max) / L & T (U power Omega) / Schnieder (Masterpact NW) / Siemens (3WL) MCCB (Microprocessor) : ABB (Tmax) / L & T (D sine) / Schnieder (Compact NXS / NS) / Siemens (3VL) / Legrand (DPX) MCCB (Thermo-Magnetic) : ABB (Tmax) / L & T (D sine / Schnieder (Easypact CVS / Compact) / Siemens (3VT / 3VL) MPCB (Microprocessor) : ABB / L & T / Schnieder / Siemens (I)(a) For Hospital Same as above item no.-32 but following mountings. Sub LT Panel INCOMER:- 1 Nos. 200 Amps. 4P MCCB (36 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-250 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 250 Amps. TP&N aluminium bus bars (36 KA) OUT GOINGS:- 4 Nos.63 Amps. TPN MCCB (25 KA) with electronic releases. 8 Nos. 40A TPN, MCB (10KA). | 21 | Set | |
| 67 | 67 | Same as above item no. -31 but following mountings. (AHU floor Panel) INCOMER:- 1 Nos. 250 Amps. 4P MCCB (36 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses.1 No. 0-250 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 300 Amps. TP&N aluminium bus bars (36 KA) OUT GOINGS:- 1 Nos.100 Amps. TPN MCCB (25 KA) with electronic releases. 4 Nos.63 Amps. TPN MCCB (25 KA) with electronic releases. 8 Nos. 32A TPN, MCB (10KA). | 21 | Set | |
| 68 | 68 | Same as above item no. -31 but following mountings. (Ventilation and smoke extration Panel) INCOMER:- 1 Nos. 400 Amps. 4P MCCB (36 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-400 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 400 Amps. TP&N aluminium bus bars (36 KA) OUT GOINGS:- 3 Nos.100 Amps. TPN MCCB (25 KA) with electronic releases. 6 Nos.63 Amps. TPN MCCB (25 KA) with electronic releases. 4 Nos. 32A TPN, MCB (10KA). | 2 | Set | |
| 69 | 69 | Same as above item no. -31 but following mountings. (X-ray Panel) INCOMER:- 1 Nos. 400 Amps. 4P MCCB(35 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-400 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 500 Amps. TP&N aluminium bus bars (35 KA) OUT GOINGS:-4 Nos. 125 Amps. TPN MCCB (25 KA) with electronic releases.D80:D99 | 1 | Set | |
| 70 | 70 | Same as above item no. -31 but following mountings. (CT MRI Panel) INCOMER:- 1 Nos. 250 Amps. 4P MCCB(35 KA) with electronic releases.1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-250 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 400 Amps. TP&N aluminium bus bars (35 KA) OUT GOINGS:- 3 Nos. 125 Amps. TPN MCCB (25 KA) with electronic releases. | 1 | Set | |
| 71 | 71 | Same as above item no. -31 but following mountings. (Main UPS Panel- OT/ICU) INCOMER:- 2 Nos. 200 Amps. 4P MCCB(35 KA) with electronic releases. 2 Set phase indication lights (R, Y, B) 2 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 2 No. 0-200 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 400 Amps. 4P CU bus bars (35 KA) OUT GOINGS:- 12 Nos. 40 Amps. 4P MCB(25 KA) | 2 | Set | |
| 72 | 72 | Same as above item no. -31 but following mountings. (Main UPS Panel- Misc) INCOMER:- 2 Nos. 160 Amps. 4P MCCB(35 KA) with electronic releases. 2 Set phase indication lights (R, Y, B) 2 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 2 No. 0-160 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 400 Amps. 4P CU bus bars (35 KA) OUT GOINGS:- 8 Nos. 125 Amps. 4P MCB(35 KA) | 2 | Set | |
| 73 | 73 | Same as above item no. -31 but following mountings. (Main UPS Floor Panel- Misc) INCOMER:- 1 Nos. 125 Amps. 4P MCCB(35 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-160 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 200 Amps. 4P CU bus bars (35 KA) OUT GOINGS:- 6 Nos. 63 Amps. 4P MCB(25 KA) 6 Nos. 40 Amps. 4P MCB(25 KA) | 20 | Set | |
| 74 | 74 | Same as above item no. - 4 but following mountings. (Lift Panel ) INCOMER:- 1 Nos. 250 Amps. 4P MCCB(25 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-250 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 250 Amps. TP&N Aluminium bus bars OUT GOINGS:- 10 Nos. 100/63 Amps. TPN MCCB(25 KA) with electronic releases. 10 Nos. 40 A TPN, MCB (25KA). | 4 | Set | |
| 75 | 75 | FOR ACADEMIC BLOCK Same as above item no. -34 but following mountings. Floor pANEL) INCOMER:- 1 Nos. 200 Amps. 4P MCCB (36 KA) with electronic releases.1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-250 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 250 Amps. TP&N aluminium bus bars (36 KA) OUT GOINGS:- 4 Nos.63 Amps. TPN MCCB (25 KA) with Thermal releases. 4 Nos. 40A TPN, MCB (10KA). With Thermal releases | 8 | Set | |
| 76 | 76 | Same as above item no. -5 but following mountings. (AHU floor Panel) INCOMER:- 1 Nos. 250 Amps. 4P MCCB (36 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses.1 No. 0-250 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 300 Amps. TP&N aluminium bus bars (36 KA) OUT GOINGS:- 1 Nos.100 Amps. TPN MCCB (25 KA) with electronic releases. 4 Nos.63 Amps. TPN MCCB (25 KA) with electronic releases. 8 Nos. 32A TPN, MCB (10KA). | 8 | Set | |
| 77 | 77 | FOR EXAMINATION HALL Same as above item no.-32 but following mountings. Sub LT Panel INCOMER:- 1 Nos. 160 Amps. FP MCCB (36 KA) with Thermal releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-630 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 200 Amps. TP&N aluminium bus bars (36 KA) OUT GOINGS:- 2 No. 40A DP, MCB (16KA) 3 Nos. 40A FP, MCCB (25KA). 5 Nos. 63 Amp. FP, MCCB (25KA) | 1 | Set | |
| 78 | 78 | FOR CENTRAL WORK SHOP Same as above item no.-32 but following mountings. Sub LT Panel INCOMER:- 1 Nos. 250 Amps. FP MCCB (50 KA) with Thermal releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-250 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 300 Amps. TP&N aluminium bus bars (50 KA) OUT GOINGS:- 2 No. 40A DP, MCB (16KA) 2 No. 63A FP, MCCB (25KA) 1 Nos. 200A FP, MCCB (50KA). | 1 | Set | |
| 79 | 79 | Metering Panel for Type II Same as above item no.-32 but following mountings. Sub LT Panel INCOMER:- 1 Nos. 100 Amps. 4P MCCB (25 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-200 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 160 Amps. TP&N aluminium bus bars (25 KA) OUT GOINGS:- 6 No. 40 amp. DP MCB (10KA) 6 Nos. Space for Meter | 4 | Set | |
| 80 | 80 | Metering Panel for Type III Same as above item no.-32 but following mountings. Sub LT Panel INCOMER:- 1 Nos. 160 Amps. 4P MCCB (25 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-200 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 200 Amps. TP&N aluminium bus bars (25 KA) OUT GOINGS:- 6 No. 40 amp. FP MCB (10KA) 6 Nos. Space for Meter OUT GOINGS:- 6 No. 40 amp. FP MCB (10KA) 6 Nos. Space for Meter | 3 | Set | |
| 81 | 81 | Metering Panel for Type IV Same as above item no.-32 but following mountings. Sub LT Panel INCOMER:- 1 Nos. 200 Amps. 4P MCCB (25 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-200 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 250 Amps. TP&N aluminium bus bars (25 KA) OUT GOINGS:- 6 No. 63 amp. FP MCB (10KA) 6 Nos. Space for Meter | 3 | Set | |
| 82 | 82 | Metering Panel for Type - V Same as above item no.-32 but following mountings. Sub LT Panel 1 Nos. 250 Amps. 4P MCCB (25 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-200 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 320 Amps. TP&N aluminium bus bars (25 KA) OUT GOINGS:- 4 No. 100 amp. FP Isolator (10KA) 4 Nos. Space for Meter | 3 | Set | |
| 83 | 83 | Metering Panel for SR. RESIDENT Same as above item no.-32 but following mountings. Sub LT Panel INCOMER:- 1 Nos. 125 Amps. 4P MCCB (25 KA) with electronic releases. 1 Set phase indication lights (R, Y, B) 1 No. Volt Meter (digital type) with inbuilt VSS & control fuses. 1 No. 0-200 Amp. Ammeter (digital type) with inbuilt ASS BUS BARS:- 160 Amps. TP&N aluminium bus bars (25 KA) OUT GOINGS:- 6 No. 40 amp. DP MCB (10KA) 6 Nos. Space for Meter | 9 | NOS. | |
| 84 | 84 | SUBHEAD- I: L.V. PANEL BOARDMain L.T. Panel (for sub station 1) Design, manufacture, supply ,installation, inspection, handling, assembling, affecting proper connections, testing and commissioning of 14 SWG CRCA sheet steel fabricated cubical type Main L.T. Panel with PLC based load manager, floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 54. The bubsbar shall be of aluminium. The main LT panel shall be as per IEC439 (TTA). Make : System Integrator of ABB(ArTu), Schneider(Prisma), Siemens(Sivakon) / L&T (Terra) Authorized certificate and agreement copy with OEM to be submit while drawing approvals through contractor. Tender based authorization or any other certifications shall not be valid.No changes in the IEC shall be allowed at the time or after tendering.Further,Only OEM's system integrator for TTA panels as per IEC439 shall be allowed to manufacturer & supply Non TTA panels also. all Specification as per PDF of DNIT | 1 | Set | |
| 85 | 85 | Main L.T. Panel (for sub station 2) Design, manufacture, supply ,installation, inspection, handling, assembling, affecting proper connections, testing and commissioning of 14 SWG CRCA sheet steel fabricated cubical type Main L.T. Panel with PLC based load manager, floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 54. The bubsbar shall be of aluminium. The main LT panel shall be as per IEC439 (TTA). Make : System Integrator of ABB(ArTu), Schneider(Prisma), Siemens(Sivakon) / L&T (Terra) Authorized certificate and agreement copy with OEM to be submit while drawing approvals through contractor. Tender based authorization or any other certifications shall not be valid.No changes in the IEC shall be allowed at the time or after tendering.Further,Only OEM's system integrator for TTA panels as per IEC439 shall be allowed to manufacturer & supply Non TTA panels also. All specification as per DNIT in PDF format 2 No. 100 A 35 ka FP MCCB | 1 | Set | |
| 86 | 86 | AUTOMATIC FIRE DETECTION & SUPPRESSION SYSTEM in PANEL Supply, Installation, Testing & Commissioning of Automatic Direct pressure Release LPCB (LPS 1666) approved System for Electrical Panel application utilising 2.5 LB/ 5 LB/ 10 LB Novec 1230/ FK5-1-12/ FK5-1-12 clean agent for Electrical Panels panels. The tested system must be approved for Enclosed and Ventilated (Natural and Forced Airlflow) Electrical Panels. The cylinder made of mild steel TPED approved along with sturdy metal bracket having direct low pressure dual discharge valve having safety brust disc for over pressurization and ball valve with open and closed option. The DLP valve having push in connector for tube to be connected with double push mechanism. The pressure guage having integrated pressure switch for visual and automatic monitoring of system pressure . The clean agent Novec 1230/ FK5-1-12/ FK5-1-12 to be filled in approved filling plant. The heart of the system linear heat sensing tube made of special polymer red colour 4mm I.D. 6mm O.D. pressurized with Nitrogen to be installed as per the OEM Manual. All the tube fittings to be OEM supplied .The system to be designed,installed and commisioned as per system manual approved by LPCB. The system installer to be trained and certiifed by OEM of the system activation during gas discharge. 2.5 LB Novec 1230/ FK5-1-12, LPCB/UL/FM approved for Enclosed and Ventilated (Natural and Forced Airflow) Electrical Panels, Direct Discharge complete system consisting of DLP Assembly with automatic valve, push in connector for tube, 2.5 LB Novec 1230/ FK5-1-12 gas, mounting bracket, End of Line adopter and low pressure switch for monitoring system activation. (Make: Firetrex/ SafeFire/ Tracefire) | 80 | Nos. | |
| 87 | 87 | 5.0 LB Novec 1230/ FK5-1-12, LPCB/UL/FMapproved for Enclosed and Ventilated (Natural and Forced Airflow) Electrical Panels, Direct Discharge complete system consisting of DLP Assembly with automatic valve, push in connector for tube, 5.0 LB Novec 1230/ FK5-1-12 gas, mounting bracket, End of Line adopter and low pressure switch for monitoring system activation. (Make: Firetrex/ SafeFire/ Tracefire) | 35 | Nos. | |
| 88 | 88 | Linear pneumatic heat Detection Tube with all necessary fittings & supports. (Make: Firetrex/ SafeFire/ Tracefire) | 3500 | Mtrs. | |
| 89 | 89 | Master Control Unit with Audio Visual Alarm with wiring to make complete system operational . The control Panel should have provision for integration with fire Alarm /SCAD/BMS System. | 115 | Nos. | |
| 90 | 90 | AUTOMATIC POWER FACTOR CORRECTION PANEL (CAPACITOR PANEL) Design, manufacture, supply, installation, inspection, handling, assembling, affecting proper connections, testing and commissioning of 16 SWG CRCA sheet steel fabricated cubical type 640 KVAR A P F C Panel-01/02/03 consisting of1/ 2/ 5 / 10 / 15 / 20 / 25 / 50 / 60 KVAR capacitor units in tier formation, housed in an integrated cubicle type automatic switching ON and OFF control panel, floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 52, powder coated after proper treatment with 9 tank process with top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2.5 sq. mm. copper wires, ckt labels etc. The Aluminium Bus Bar shall be of suitable length, 500 volts, 3 phase 50 Hz TPN, electrolytic aluminium as per IS 8623 . All MCCB's shall be thermal-magnetic based with inbuilt O/L & S/C release. All MCCB's shall be Ics = 100% Icu, with rotary handle & pad locking arrangement, with adjustable O/L & S/C trip setting as per load requirement. All TP MCCB shall be with heavy duty solid isolable neutral link. The breaking capacity specified is Ics value. The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmeter, selector switches, CT's, PT's, etc. AC3 duty contactors should be used for switching individual capacitor banks. The fault withstanding capacity of panel & its control gear shall be min. 35 KA rms for 1 sec. Each section of capacitor panel shall have Verticle hood & exhaust fans for ventilation purpose. The maximum height of the panel should not exceed 2100 mm unless specifically approved. INCOMING Incomer circuit breaker has been included in the main panel. 1 set- 3 CTs , ratio 1000/5A Class 1.0 accuracy 15 VA burden for metering. 1Nos- (0-1000A) digital Ammeter with selector switch Micro processor based automatic power factor control relay (3 phase) (including power factor meter) in 16 steps for automatic cut off or add on capacitor units to keep the power factor at 0.95 with variation of loads. All associated auxiliary contactors / relays shall be provided with in the scope of work. Phase indicating lamps with HRC fuses, and indicating in each capacitor chamber unit to indicate On/Off status of capacitor unit. BUS BARS 1000 AMP, 500 Volts, 3 phase 50 HZ TPN high conductivity electrolytic Aluminium bus bar of suitable length, SMC / DMC supports, with colour coding and insulated by heat shrinkable sleeves and clips on shrouds for joints. The current density of bus bar shall be minimum 1.3 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 85 deg C. The temperature rise should be restricted to 35 deg C above ambient temperature. OUTGOINGS - 7 nos. of 160 AMPS TPN 35 KA MCCB and 120 amps AC3 duty contactor with 60 KVAR, MPP resin filled, super heavy duty ,480 V capacitor bank, with copper coil 7% detuned filters, auto-manual selector switch, start stop push button for manual operation including on/off indicating lamps and delay timer complete.2 nos. of 100 AMPS TPN 35 KA MCCB and 60 amps AC3 duty contactor with 30 KVAR, MPP resin filled, super heavy duty ,480 V capacitor bank, with copper coil 7% detuned filters, auto-manual selector switch, start stop push button for manual operation including on/off indicating lamps and delay timer complete. | 3 | Set | |
| 91 | 91 | SUB HEAD-IV : T.V. , TELEPHONE SYSTEM Supplying, drawing, connecting and testing of 0.5 mm dia annealed copper conductor PVC insulated PVC sheathed telephone wire in existing conduit/wire way duct etc. as required of following sizes: 2 Pair (4 core) DSR 2018 1.18.2 | 2625 | Metre | |
| 92 | 92 | Providing, laying, connecting and testing of multi-core telephone armoured cable of conductor size 0.63mm dia annealed copper conductor PVC insulated PVC sheathed jelly filled (as per DOT specification) cable along wall or ceiling or through existing pipe. 20 Pair telephone cable | 200 | Metre | |
| 93 | 93 | 10 Pair telephone cable | 400 | Metre | |
| 94 | 94 | 5 Pair telephone cable | 800 | Metre | |
| 95 | 95 | Providing, fixing connecting and testing of under noted size of solderless telephone tag block Krone make in surface/recess in wall required size of M.S. box with hinged lockable cover duly stove enamel painted. 5 Pair tag block | 36 | Each | |
| 96 | 96 | 10 pair tag block | 21 | Each | |
| 97 | 97 | 100 pair tag block | 1 | Each | |
| 98 | 98 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20mm dia PVC conduit | 600 | Metre | |
| 99 | 99 | 25mm dia PVC conduit | 1200 | Metre | |
| 100 | 100 | 32mm dia PVC conduit | 300 | Metre | |
| 101 | 101 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required 1 or 2 Module (75mmX75mm) | 350 | Each | |
| 102 | 102 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required Supplying and fixing M.S. box with modular type telephone (RJ-11) outlet complete as required. | 175 | Each | |
| 103 | 103 | Supplying and fixing M.S. box with modular type coaxial outlet for TV antenna complete as required. | 175 | Each | |
| 104 | 104 | Providing, laying, connecting and testing of unarmoured TV cable RG-6 PVC insulated cable along wall or ceiling or through existing pipe. | 3500 | Metre | |
| 105 | 105 | SUBHEAD: - V - EARTHING Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. Details of cost for one each | 52 | Each | |
| 106 | 106 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal or coke and salt) as required. | 114 | Set | |
| 107 | 107 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required | 85 | Set | |
| 108 | 108 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) | 540 | Meter | |
| 109 | 109 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) | 1310 | Meter | |
| 110 | 110 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required | 1789 | Meter | |
| 111 | 111 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required | 1406.5 | Meter | |
| 112 | 112 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. | 2000 | Metre | |
| 113 | 113 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. | 1190 | Meter | |
| 114 | 114 | Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for connections etc. as required. | 1468 | Meter | |
| 115 | 115 | SUBHEAD-VI- LIGHTNING PROTECTION SYSTEM Supply, Erection, Installation & Commissioning of External Lightning Wide Area Protection System based on pro-active Early Streamer Emission (ESE) Technology. No external power source required. Break down time not more than 245.5 Micro second. Wind Resistance up to 120miles/hours. Produces a leader of not less than 2x10E8 V/m/s in the lightning generated electromagnetic field with Level-I protection radius of 79 meters at 5 mtr. Mast including mast for supporting the device. Device confirming to NFC17-102 & UNE 21186 standards & CPRI Tested. | 5 | Set | |
| 116 | 116 | Supply, Erection, Installation & Commissioning of the Down Conductor which is a 70 Sq. mm flexibile, single core pvc insulated copper cable . | 200 | RM | |
| 117 | 117 | Supply, Erection, Installation & Commissioning of Lightning Event Counter (Model: LEC-IV) for counting the number of lightning strikes without any power supply. The Counter should be mounted on the Down Conductor and the triggering impulse should be > = 1.5 KA for 8/20µs. The Lightning Event Counter should be robust, non-resettable mechanical counter with IP65 rated enclosure suitable for external application. | 5 | Set | |
| 118 | 118 | Supply, Erection, Installation & Commissioning of the Earthing system which should cater for the Lightning Protection System earthing and should be maintenance free. Earth Enhancing Compounds should be used to treat the soil for lowering the effective ground impedance. Maintenance free earth pits made of ground enhancing material (GEM) - 3 or 4 bags of 11.3 Kg each and 250 microns copper bonded ground rods - 4 nos of size 5' length and 5/8\" diameter connected with each other with 25 x 3 mm Copper Strip and high performance earth clamps. | 10 | Set | |
| 119 | 119 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal or coke and salt) as required. | 18 | Set | |
| 120 | 120 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. | 36 | Each | |
| 121 | 121 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. | 225 | each | |
| 122 | 122 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) | 2200 | Metre | |
| 123 | 123 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) | 2000 | Metre | |
| 124 | 124 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. | 36 | each | |
| 125 | 125 | Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. | 450 | Mtr. | |
| 126 | 126 | SUB HEAD-V : RISING MAIN Supplying, installing on wall, testing and commissioning of following capacity rising mains made of 1.6mm thick IP 42 sheet steel enclosure duly painted with powder coating, wall straps, fully PVC insulated 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating in convenient sections and suitable for 415 V, 3 phase, 4 wire, 50 Hz, A.C. supply with extension joints, fire proof barriers, expansion joints, thrust pads including jointing and earthing with 2 runs of galvanised iron strips etc. as required. (Rising mains confirming to IS 8623, TEC 439) 200 A (S.C. rating for 1 sec - 15 kA) 3.1.1 300 A (S.C. rating for 1 sec - 20 kA) | 46 | Meter | |
| 127 | 127 | Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required 400 A 25kA SC for 1 sec 1.13.1 | 57 | Meter | |
| 128 | 128 | 800 A 50kA SC for 1 sec | 350 | Meter | |
| 129 | 129 | 1250 A 50kA SC for 1 sec | 100 | Meter | |
| 130 | 130 | 1600 A 50kA SC for 1 sec | 50 | Meter | |
| 131 | 131 | Supplying, installing, testing and commissioning of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains complete with TPN disconnector FSU and HRC fuses, connections, earthing etc. as required 100 A TPN | 15 | Each | |
| 132 | 132 | 200 A TPN | 54 | Each | |
| 133 | 133 | Supplying, installation, testing & commisioning of following capacity End Feed Unit for the existing Air Insulated Compact Type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure (IP54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required 200 A 15kA SC for 1 sec 315 A 25kA SC for 1 sec | 1 | Each | |
| 134 | 134 | 630 A 50kA SC for 1 sec | 2 | Each | |
| 135 | 135 | 800 A 50kA SC for 1 sec | 2 | Each | |
| 136 | 136 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required 400 A, 35 KA,TPMCCB | 1 | Each | |
| 137 | 137 | 800 A, 50 KA,TPMCCB | 2 | Each | |
| 138 | 138 | SUB-HEAD - IV : LT CABLES Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm | 5950 | Meter | |
| 139 | 139 | Above 35 sq.mm. and up to 95 sq.mm. | 1550 | Meter | |
| 140 | 140 | Above 95 sq.mm. and upto 185 sq.mm. | 2450 | Meter | |
| 141 | 141 | Above 185 sq.mm. and up to 400 sq.mm. | 3800 | Meter | |
| 142 | 142 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, rotective covering and refilling the trench etc as required Up to 35 sq.mm. | 3600 | Meter | |
| 143 | 143 | Above 35 sq.mm. and up to 95 sq.mm. | 1050 | Meter | |
| 144 | 144 | Above 95 sq.mm. and upto 185 sq.mm. | 1500 | Meter | |
| 145 | 145 | Above 185 sq.mm. and up to 400 sq.mm. | 2400 | Meter | |
| 146 | 146 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required Up to 35 sq.mm. | 760 | Meter | |
| 147 | 147 | Above 35 sq.mm. and up to 95 sq.mm. | 195 | Meter | |
| 148 | 148 | Above 95 sq.mm. and upto 185 sq.mm. | 305 | Meter | |
| 149 | 149 | Above 185 sq.mm. and up to 400 sq.mm. | 480 | Meter | |
| 150 | 150 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Up to 35 sq.mm. | 1380 | Meter | |
| 151 | 151 | Above 35 sq.mm. and up to 95 sq.mm. | 380 | Meter | |
| 152 | 152 | Above 95 sq.mm. and upto 185 sq.mm. | 595 | Meter | |
| 153 | 153 | Above 185 sq.mm. and up to 400 sq.mm. | 920 | Meter | |
| 154 | 154 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required Upto 35 sq. mm (clamped with 1mm thick saddle | 600 | Meter | |
| 155 | 155 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp | 175 | Meter | |
| 156 | 156 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp | 250 | Meter | |
| 157 | 157 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) | 400 | Meter | |
| 158 | 158 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle) | 3200 | Meter | |
| 159 | 159 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) | 1950 | Meter | |
| 160 | 160 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) | 593 | Meter | |
| 161 | 161 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) | 800 | Meter | |
| 162 | 162 | Supply of following siz of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC shethed armoured cable as per IS 7098:1988 with up to date amendment 3.5 x 400 sq.mm. | 2000 | Metre | |
| 163 | 163 | 3.5 x 300 sq.mm. | 4800 | Metre | |
| 164 | 164 | 3.5 x 240 sq.mm. | 2000 | Metre | |
| 165 | 165 | 3.5 x 225 sq.mm. | 3000 | Metre | |
| 166 | 166 | 3.5 x 185 sq.mm | 2250 | Metre | |
| 167 | 167 | 3.5 x 150 sq.mm | 2300 | Metre | |
| 168 | 168 | 3.5 x 120 sq.mm | 1750 | Metre | |
| 169 | 169 | 3.5 x 95 sq.mm | 1450 | Metre | |
| 170 | 170 | 3.5 x 70 sq.mm | 2100 | Metre | |
| 171 | 171 | 3.5 x 50 sq.mm | 1750 | Metre | |
| 172 | 172 | 3.5 x 35 sq.mm | 1950 | Metre | |
| 173 | 173 | 3.5 x 25 sq.mm. | 1700 | Meter | |
| 174 | 174 | 4 x 25 sq.mm | 250 | Metre | |
| 175 | 175 | 4 x 16 sq.mm | 4450 | Metre | |
| 176 | 176 | 4 x 10 sq.mm | 3500 | Metre | |
| 177 | 177 | 2 x 16 sq.mm, | 2200 | meter | |
| 178 | 178 | Supplying and making cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required. 2 X 6 sq. mm (19mm) 9.1.1 | 500 | Each | |
| 179 | 179 | 2 X 10 sq. mm (19mm) | 200 | Each | |
| 180 | 180 | 2 X 16 sq. mm (22mm) | 202 | Each | |
| 181 | 181 | 3½ X 25 sq. mm (28mm) | 22 | Each | |
| 182 | 182 | 3½ X 35 sq. mm (32mm) | 42 | Each | |
| 183 | 183 | 3½ X 50 sq. mm (35mm) | 40 | Each | |
| 184 | 184 | 3½ X 70 sq. mm (38mm) | 40 | Each | |
| 185 | 185 | 3½ X 95 sq. mm (45mm) | 24 | Each | |
| 186 | 186 | 3½ X 120 sq. mm (45mm) | 40 | Each | |
| 187 | 187 | 3½ X 150 sq. mm (50mm) | 44 | Each | |
| 188 | 188 | 3½ X 185 sq. mm (57mm) | 40 | Each | |
| 189 | 189 | 3½ X 225 sq. mm (62mm) | 20 | Each | |
| 190 | 190 | 3½ X 240 sq. mm (62mm) | 20 | Each | |
| 191 | 191 | 3½ X 300 sq. mm (70mm) | 28 | Each | |
| 192 | 192 | 3½ X 400 sq. mm (82mm) | 20 | Each | |
| 193 | 193 | 4 X 10 sq. mm (25mm) | 330 | Each | |
| 194 | 194 | 4 X 16 sq. mm (28mm) | 228 | Each | |
| 195 | 195 | Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5 x 400 sq.mm | 5 | Each | |
| 196 | 196 | 3.5 x 300 sq.mm | 5 | Each | |
| 197 | 197 | 3.5 x 240 sq.mm | 5 | Each | |
| 198 | 198 | 3.5 x 185 sq.mm | 5 | Each | |
| 199 | 199 | 3.5 x 150 sq.mm | 5 | Each | |
| 200 | 200 | 3.5 x 120 sq.mm | 5 | Each | |
| 201 | 201 | 3.5 x 95 sq.mm | 5 | Each | |
| 202 | 202 | 3.5 x 70 sq.mm | 5 | Each | |
| 203 | 203 | 3.5 x 50 sq.mm | 5 | Each | |
| 204 | 204 | 3.5 x 35 sq.mm | 5 | Each | |
| 205 | 205 | 3.5 x 25 sq.mm | 5 | Each | |
| 206 | 206 | 4 x 16 sq.mm | 5 | Each | |
| 207 | 207 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5 x 400 sq.mm | 8 | Each | |
| 208 | 208 | 3.5 x 300 sq.mm | 10 | Each | |
| 209 | 209 | 3.5 x 240 sq.mm | 6 | Each | |
| 210 | 210 | 3.5 x 185 sq.mm | 4 | Each | |
| 211 | 211 | 3.5 x 150 sq.mm | 4 | Each | |
| 212 | 212 | 3.5 x 120 sq.mm | 4 | Each | |
| 213 | 213 | 3.5 x 95 sq.mm | 4 | Each | |
| 214 | 214 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 100mm dia 14.14.1 | 420 | Metre | |
| 215 | 215 | 150 mm dia | 100 | Meter | |
| 216 | 216 | 250 mm dia | 100 | Meter | |
| 217 | 217 | 300 mm dia | 50 | Meter | |
| 218 | 218 | SUBHEAD - VIII - CABLE TRAY Supply and fixing of cable tray/steel work in position including clamps, frame work of flats, angle iron, channel with fabrication work including cutting, bending, welding, drilling bolting etc. as per design as required. One coat of primer and 2 coats of enamel paint of approved shade shall be provided. | 5000 | Kg. | |
| 219 | 219 | Supply and fixing of perforated 2mm thick CRCA sheet steel power coated cable tray of following sizes complete with bend/tee joints, coupling plate & nuts bolts etc. including providing and fixing of M.S. painted hanger etc. as required. 150mm wide 50 mm depth 4.1.2 | 1100 | Metre | |
| 220 | 220 | 300mm wide 62.5mm depth | 1050 | Metre | |
| 221 | 221 | 450mm wide 62.5mm depth | 775 | Metre | |
| 222 | 222 | 600mm wide 75mm depth | 800 | Metre | |
| 223 | 223 | 900mm wide 75mm depth | 500 | Metre | |
| 224 | 224 | SUB-HEAD -IX : A. Street Lighting Supplying, installation & testing of 7.0 m high octagonal GI pole with single arm as per approved sample made from 3 mm sheet steel (Grade S 355 J0) with top diameter as 75mm and bottom dia as 150mm and base plate of 240x240x16 mm with suitable slot shaped holes for mounting the same on a shallow foundation, GI weather proof junction box with 16A SP MCB, loop-in-loop out terminals for 2nos. 4Cx16 sq.mm YWY cables and 3x2.5 sq.mm copper conductor from junction box to fitting and connected accessories as required etc. Contractor to include the cost of RCC foundation for pole as per structural detail. | 250 | Nos. | |
| 225 | 225 | Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 110Watt. to 120 Watt and Confirming to IP66 protection having Company LOGO Engraved complete in all respect with 12100-13200 system lumens High Power LED with lenses, >110lm/W, PF>0.95, THD <10% at full load, CRI>70, Avg Life Class 50000Hrs@L70, Potted driver Set (NotCircuitory) with BIS No. written on it, Phase to phase Protection at 440V & >300V auto cut and re-start feature, fitting itself suitable for 60-65mm OD pipe | 187 | Set | |
| 226 | 226 | Supply of Single piece Integral LED Solar Street Light Pressure Die Cast Aluminium Housing (LM6 Alloy) reliable & robust construction, Minimum 4600lumens with system efficacy of >175 lumens per watt, SMD LEDs With PMMA Lens plat, External built proper heat sinks and Toughen Glass/PC ensuring IP65 & Life of LED luminaire engine should be 50000hrs along with built in high efficiency MPPT charge controller along with LiFePO4 battery & high efficiency reliable PV Module suitable for even harsh conditions, CCT >5000, CRI 70,The fixture should have designed for Street light application & should have flexible angle of mounting from 0- 15 Degree for diverse geographical condition. PIR sensor, Dimming for optimum of autonomy uses up to 24hrs. System should have Smart self-diagnostic feature for indicating battery charging, cut off & fault if any. Company Logo shall be engraved to avoid any distrusts, Complete system should have minimum warrantee of 36 months. Luminaire Shall be suitable for mounting height 6mtr, Max Weight 20kgs. | 63 | Nos. | |
| 227 | 227 | supply and fixing of 40 amp TPN automatic street light cubicle control pannel with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 seeries with contactors ,HRC fuse,isolating switch,metering instrument,and instrument box with CTs etc.complete in all respect. | 10 | Set | |
| 228 | 228 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required | 6000 | Meter | |
| 229 | 229 | above 35 sq,mm, upto 95 sq,mm. | 1000 | Meter | |
| 230 | 230 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required upto 35 sq.mm. | 2750 | Meter | |
| 231 | 231 | Supply of following siz of 1.1KV grade multicore aluminium conductor XLPE insulated and PVC shethed armoured cable as per IS 7098:1988 with up to date amendment Size 6 sq.mm x 2 core | 2750 | rmt | |
| 232 | 232 | size 16 sq mm x 4 core | 6000 | rmt | |
| 233 | 233 | size 50 sq.mm x 3.5 core | 1000 | rmt | |
| 234 | 234 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required Size 6 sq.mm x 2 core | 500 | each | |
| 235 | 235 | size 16 sq mm x 4 core | 120 | each | |
| 236 | 236 | size 50 sq mm X 3.5 C | 4 | each | |
| 237 | 237 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required | 84 | Nos. | |
| 238 | 238 | Supplying and laying 25 mm X 3 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) | 2500 | Mtr. | |
| 239 | 239 | SUB-HEAD -IX : B Post Top Light S & F GI conical 4 mtr. Pole base dia 118 mm top dia 75 mm sheet thickness 3 mm Eq. to Bajaj BCP-4030 with foundation bolt | 100 | Nos. | |
| 240 | 240 | Supply and fixing of decorative 40 to 45 Watt LED Post top indirect light luminaire having Pressure die cast aluminium body and Clear glass with driver set confirming to IP 65 and above protection complete in all respect. | 100 | Nos. | |
| 241 | 241 | supply and fixing of 40 amp TPN automatic street light cubicle control pannel with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 seeries with contactors ,HRC fuse,isolating switch,metering instrument,and instrument box with CTs etc.complete in all respect. | 2 | Set | |
| 242 | 242 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required upto 35 sq.mm. | 1600 | Meter | |
| 243 | 243 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required up to 35 sq.mm. | 1600 | Meter | |
| 244 | 244 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required Size 6 sq.mm x 2 core | 450 | rmt | |
| 245 | 245 | size 16 sq mm x 4 core | 1400 | rmt | |
| 246 | 246 | size 35 sq.mm x 3.5 core | 200 | rmt | |
| 247 | 247 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required Size 6 sq.mm x 2 core | 200 | each | |
| 248 | 248 | size 16 sq mm x 4 core | 120 | each | |
| 249 | 249 | size 35 sq mm X 3.5 C | 4 | each | |
| 250 | 250 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required | 10 | Nos. | |
| 251 | 251 | Supplying and laying 25 mm X 3 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) | 500 | Mtr. | |
| 252 | 252 | Supplying and laying 6 SWG G.I. wire at 0.50 meter below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. | 1200 | Mtr. | |
| 253 | 253 | SUB-HEAD -IX : B BOLLARD Light Supply and fixing of decorative 8 to 16 Watt LED bollard luminaire with driver set confirming to IP 65 protection complete in all respect | 100 | Nos. | |
| 254 | 254 | supply and fixing of 40 amp TPN automatic street light cubicle control pannel with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 seeries with contactors ,HRC fuse,isolating switch,metering instrument,and instrument box with CTs etc.complete in all respect. | 2 | Set | |
| 255 | 255 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required upto 35 sq.mm. | 900 | Meter | |
| 256 | 256 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required up to 35 sq.mm. | 100 | Meter | |
| 257 | 257 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required Size 6 sq.mm x 2 core | 150 | rmt | |
| 258 | 258 | size 16 sq mm x 4 core | 1000 | rmt | |
| 259 | 259 | size 35 sq.mm x 3.5 core | 100 | rmt | |
| 260 | 260 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required Size 6 sq.mm x 2 core | 200 | each | |
| 261 | 261 | size 16 sq mm x 4 core | 120 | each | |
| 262 | 262 | size 35 sq mm X 3.5 C | 4 | each | |
| 263 | 263 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required | 10 | Nos. | |
| 264 | 264 | Supplying and laying 25 mm X 3 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) | 100 | Mtr. | |
| 265 | 265 | Supplying and laying 6 SWG G.I. wire at 0.50 meter below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. | 500 | Mtr. | |
| 266 | 266 | SUB-HEAD IX - : C High Mast Supply & fixing of 16 mtr High mast shaft of approved make with rising system hot dip glavanized inside & out side dip,heaving pole sheet thickness 3 mm. Top dia minium 150 mm, Bottom dia 310 mm base plate 25 mm thick suitable for wind velocity as per IS 875 part 3 & having no circumferential weld, with accessories for high mast such as head frame suitable for 6 luminaries & its control gear boxes 0.75 HP power tool moter, 3 point suspension system with steel wire rope 6 mm dia, double drum winch, including making suitable foundation as per manufature drawing/ site reuiment along with foundation bolts nuts, washers, anchor plates etc completee in all respect. | 4 | Each | |
| 267 | 267 | Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminium housing built with dirver set suitable for 170 to 200 housing built with dirver set suitable for 140 to 150 Watt. Confirming to IP 66 protection complete in all respect. | 24 | Each | |
| 268 | 268 | supply and fixing of 40 amp TPN automatic street light cubicle control pannel with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 seeries with contactors ,HRC fuse,isolating switch,metering instrument,and instrument box with CTs etc.complete in all respect. | 4 | Set | |
| 269 | 269 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required | 8 | Nos. | |
| 270 | 270 | Supplying and laying 25 mm X 3 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) | 80 | Mtr. | |
| 271 | 271 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required upto 35 sq.mm. | 150 | Meter | |
| 272 | 272 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required up to 35 sq.mm. | 50 | Meter | |
| 273 | 273 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required size 16 sq mm x 4 core | 200 | rmt | |
| 274 | 274 | size 35 sq.mm x 3.5 core | 200 | rmt | |
| 275 | 275 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required size 16 sq mm x 4 core | 8 | each | |
| 276 | 276 | size 35 sq mm X 3.5 C | 4 | each | |
| 277 | 277 | SUB HEAD-V: SUB-STATION EQUIPMENTS TRANSFORMER (33 KV / 0.4 KV) Supply, testing & commissioning of Outdoor mounted type 33 KV / 433 Volt Transfomer (as per IS : 2026, P1 to P5), 3 phase, 6.25% impedance, Dyn 11 vector group, 50 cycles, (ONAN) oil immersed naturally cooled, step down, copper wound, continuous duty, temperature rise above 50oC in oil by thermometer 40oC, in winding by resistance 45oC and other standard accessories as required including followings : The Transformer losses should confirm to IS : 1180 (Part 1)-2014. a) Cable Termination box with disconnecting facility for 33 KV 3C-300 sq mm XLPE cable at 33 KV side b) LV side box suitable for suitable Amp bus duct termination c) Automatic On Load Tap Changer +10% to -10% @ 1.25% in 16 equal steps with RTCC Panel (Remote tap changer control panel) consisting of followings - As per DNIT specification of PDF DNIT | 4 | set | |
| 278 | 278 | HT PANEL EQUIPMENTS HT PANEL- (33 KV - 6 VCB PANEL) Supply,installation, testing & commissioning of indoor type floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 4X, The switchgear boards shall have a single front, single tier, fully compartmentalized, metal enclosed construction complying with clause No. 3.102 of IEC 62271-200, comprising of a row of free standing floor mounted panels. Each circuit shall have a separate vertical panel with distinct compartments for circuit breaker truck, cable termination, main bus-bars and auxiliary control devices. The adjacent panels shall be completely separated by steel sheets except in bus-bar compartments. The Service Class Continuity of Switchgears shall be LSC 2B-PM (as per IS/IEC 62271-200) • The Switchgear shall have an Internal Arc Classification of IAC AFLR. Switchgear shall have an internal arc of 31.5kA for 1 second.In case of any Inspection window provided on breaker compartment door, same should also be in line with IAC classifications. comprising of 1250Amp, continuous rated Copper busbars and droppers, 01nos. Rack-In-Rack-Out Handle, structure made from AluZinc/GI sheets to prevent corrosion and rusting.The complete panel incl. HT and LT chamber shall be manufactured by approved OEM at its own facility, and same will be verified via stage/final inspection. License parter, system integrator, panel builder, half-panel concept is not allowed. 33 KV 4 VCB HT Panel fully encapsulated pole VCB breakers (1 incomer and 3 out goings), totally enclosed & fully interlocked, horizontal drawout, horizontal isolation type breaker, having capacities as mentioned below, single break, trip free mechanism, motorised charged and auto closing breaker suitable for use on 33 KV, 3 Phase, 50 Hz A. C. supply with short circuit fault level of 31.5 kA, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but continuous rated Copper busbars and droppers , Cu. earth bar, earth bar, breaker featured with mechanical ON / OFF indicator with hand trip device, spring release coil, shunt trip coil, control voltage of 24 Volt DC, TNC, LED type indicating lamps for phases and trip conditions and auxiliary switch of 6 NO + 6 NC and equipped with following switchgears and accessories.HT Panel - 03 as described above All specification as per PDF format of DNIT | 1 | Set | |
| 279 | 279 | As per item no. 126 with following mountings- Incoming - 1 Nos. 630 Amp. VCB breakers with followings in each breaker - 33kV, 1250Amp, 31.5kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03 Nos. encapsulated vacuum bottles of same make as of circuit breaker, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC) (a) 1 set (3 nos) 33 KV / v3 / 110 / v3 Volts drawout type PT Class 0.5 accuracy and 50 VA burden with 1 No. Voltmeter (0-36 KV), digital type, selector switch for voltmeter and protection fuses/MCB for HT metering. (b) 3 nos. dual core dual ratio CTs of ratio 200/100/1/1A of 7.5 VA burden and accuracy class-0.5 for metering and class 5P10 for protection. (c) 1 No. - (0-200A) Ammeter, digital type with selector switches.HT Panel - 03 as described above all other specification as per PDF format of DNIT | 1 | Set | |
| 280 | 280 | SUB HEAD-VII : Miscellaneous Supply, erection, testing & commissioning of 230 V, single phase, 2 wire, A.C. to 24V D.C. 180 AH sealed maintenance free batteries with semiconductor/ IGBT (half wave rectifier) with auto-manual trickle boost facility battery charging units complete including 1 No. Distribution board having 63 Amps DP MCB incomer and 12 No. 16/ 20 Amps DP MCBs (D.C. duty) as outgoing complete as required as per technical specifications. | 1 | Set | |
| 281 | 281 | Supplying and laying of 1000 mm wide x 3 mm thick insulated mat made from highly electrical resistant elastomer of tested quality to withstand 65 KV dielectric strength as per IS 15652 complete in all respects. (For 33KV) | 15 | Metre | |
| 282 | 282 | Supplying and laying of 1000 mm wide x 2 mm thick insulated mat made from highly electrical resistant elastomer of tested quality to withstand 30 KV dielectric strength as per IS 15652 complete in all respects. (For LT Panels) | 30 | Metre | |
| 283 | 283 | Supplying and fixing of fire bucket, round bottom made of GI sheet 9 to 11 liters capacity duly painted as per fire brigade design, supported on hanging bracket chained and locaked, initially filled with fine river sand, water as per direction of Engineer Incharge. | 12 | Each | |
| 284 | 284 | Supplying and fixing of shock treatment chart (prescribed under I.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T & P for proper completion of work. | 4 | Each | |
| 285 | 285 | Supplying and fixing of carbon dioxide fire extinguisher type 4.5 kgs. Capacity (ISI marked IS:2878 and TAC approved) complete with initial charge and wall bracket, alongwith supply of all amterials and labor for proper completion of work.. | 4 | Each | |
| 286 | 286 | Supplying and fixing of first aid box as approved complete with standard kit as prescribed by Indian Red Cross. | 4 | Each | |
| 287 | 287 | Supplying & laying of following size DWC HDPE pipe ISI marked alongwith all accessories like socket, bend, couplers etc. confirming to IS : 14930 Part-II complete with fitting, cutting & jointing etc. direct in ground (75cm below ground level) including excavation & refilling the trench but excluding sand cushioning & protective covering etc. as required. 200 MM dia (OD - 200 MM & ID - 175 MM nominal) | 100 | Metre | |
| 288 | 288 | Providing and fixing UPVC pipes as per IS:4985 suitable for 6 Kg/ sq cm pressure, including all fittings with accessories i.e bends, junctions, cowls, offsets, PVC pipe clips/holders etc. and jointing with rubber rings and cement solvent complete as per manufacturer's specifications with excavation, refilling and disposal of surplus earth, including cutting holes in walls and floors ,wherever required and making good the same, complete as directed by the Engineer-in-Charge. 110 mm outer dia | 10 | Metre | |
| 289 | 289 | 200 mm outer dia | 10 | Metre | |
| 290 | 290 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. | 60 | Each | |
| 291 | 291 | SUB HEAD-VIII : MV CABLES Supply of 3 core stranded aluminium conductor 33KV grade XLPE (E) (Cross linked Polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cable confirming to IS : 7098 (part II with latest amendments). 300 sq. mm 3 core | 1000 | Metre | |
| 292 | 292 | Laying of one number XLPE power cable of 33 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. 120 sq. mm 3 core | 500 | Metre | |
| 293 | 293 | Supply and making Indoor end termination Kit of 33 KV XLPE cable. (Make : Raychem / 3M) 120 sq. mm 3 core | 8 | set | |
| 294 | 294 | 300 sq.mm 3 core | 2 | Set | |
| 295 | 295 | Supply and making Outdoor end termination Kit of 33 KV XLPE cable. (Make : Raychem / 3M) 120 sq. mm 3 core | 2 | set | |
| 296 | 296 | 300 sq.mm 3 core | 2 | set | |
| 297 | 297 | Supply and making Straight Through type jointing Kit of 33 KV XLPE cable. (Make : Raychem / 3M) 33 KV 3 x 120 | 4 | set | |
| 298 | 298 | 33 KV 3 x 300 | 2 | set | |
| 299 | 299 | SUB HEAD-X : Sandwiched Bus ducts Supplying, installation, testing and commissioning of TPN Aluminium conductor of current rating 0.8 Amps/Sqmm. LT Bus duct outdoor sandwiched type of following ratings , 50 KA rms for 1 sec suitable for connecting between transformer and main LT panel ACB including tinned copper flexible end connection at both ends and earthing with continuous 2 runs of Aluminium strips 50 x 6 mm as per specifications and as per latest IS code complete as required. 800 Amps. 50 KA SC for 1 sec. | 75 | Metre | |
| 300 | 300 | 1600 A 50kA SC for 1 sec | 150 | Metre | |
| 301 | 301 | 3200 Amps. 50 KA SC for 1 sec. | 225 | Metre | |
| 302 | 302 | Meters and Customer Interface UnitsLT 3P-4W direct connected pre-payment keypad based BIS marked Digital Energy meter, 10-60 Amp,415V (P-P), accuracy class 1.0 along with Parallel bluetooth freedom unit for remote monitoring at houses, with inbuilt load control switch,Make:Secure | 140 | NOS | |
| 303 | 303 | LT 3P-4W direct connected pre-payment keypad based BIS marked Digital Energy meter, 20-80 Amp,415V (P-P), | 1 | NOS | |
| 304 | 304 | accuracy class 1.0 along with Parallel bluetooth freedom unit for remote monitoring at houses, with inbuilt load control switch, Make:Secure Accessories: Telephonic cable 4Pair or 4 core (four different colors ) form each meter to Each CIU/Flats, | 1000 | METER (Length) | |
| 305 | 305 | Power line signal Injector (PLSI) suitable for transformer (above 1 MVA to 2MVA rating) for DG Sensing for each transformer; item is required for dual source application (Means If DG back up given to customers) | 1 | NOS | |
| 306 | 306 | 4-Core 50sq mm wires from each Distribution Transformer to MCCB of each DC Injector (PLSI) -If required-This item required only dual source application only | 1000 | METER (Length) | |
| 307 | 307 | Common meter reading instrument for down the data form meters | 1 | NOS | |
| 308 | 308 | Vending Infrastructure: Vending Computer PC with Processor P-4 dual core, 2 GB Ram. Hard disk 500GB, 1-CD/DVD combo driver R/W type, 4 | 1 | Nos. | |
| 309 | 309 | USB Port, 1- Serial Port 9 PIN D Type, TFT monitor- Make HP/ Dell/ Equivalent with Licensed Operating System (Window 7/ XP) Impact Token or Report Printer with Serial Port, Make: Any reputed make | 1 | nos | |
| 310 | 310 | Internet connection (broad band), for vending station | 1 | Nos. | |
| 311 | 311 | Vasco key for digital password geneartion (Mnager +cashier Role) | 2 | Nos. | |
| 312 | 312 | Installation/Commissioning of System/Person for Vending System Operation: Implementation of vending system, data base defining/mapping of consumer, Training to system operators along with user manual. | 1 | Per Consumer | |
| 313 | 313 | Installation of Prepayment Meters in existing Panel Note:-Meter Incoming & outgoing control cables from source to load in Customer scope | 1 | Nos. | |
| 314 | 314 | Commissioning Of PLSI (LT side Control cable form transformer incomer to PLSI input customer scope ) | 1 | Nos. | |
| 315 | 315 | Laying of telephonic cable from each meter to each CIU/Flats for remote access of data/operation from homes along with both side RJ-11 Connector punching | 3000 | METER (Length) | |
| 316 | 316 | SUB HEAD-IV: D.G. SETS Supply, testing and Commissioning of Silent type Diesel Generating Set at 0.8 PF, 415 Volts, 50 cycles per second, 1500 rpm, 3 phase, suitable for parallel operation, 0.85 load factor including circuit breaker for isolation, sound proof acoustic and weather proof enclosure, residential type silencer (as per CPCB norms-2) fabricated out of CRCA sheet of 14 / 16 SWG thickness with 9 tank pretreated before powder coating with ventillation system complete in all respects comprising of the following. Diesel Engine - Diesel Engine suitable for driving alternator of above rating, compression ignition, 4 stroke cycle, Radiator cooled, turbo charged, battery starting, 1500 RPM, suitable for above output of alternator at 40oC, 50% RH & at 210 M MSL and confirming to BS 5514, BS 649, IS 10000, capable of taking 10% overloading for one hour after 12 hrs of prime continuous loading, complete with all the accessories i.e. tachometer with hour meter, flexible coupling with guard, crank case of steel, crank shaft, conncting rods, electronic governing system, dynamically balanced flywheel, air intake manifold, Air cleaner, anti vibration pads, starter motor, including all other accessories required to complete the system. Instrument Panel - Engine mounted Instrument Panel fitted with and having digital display for followings : Start stop switch with key Water temperature indication Lubrication oil pressure indication.Lubrication oil temperature indication. Battery charging indication RPM indication Over speed indication Low Lube oil trip indication Engine hours indication Alternator - Synchronous Alternator of above capacity at 0.8 PF, 3 phase, 415 volts, 50 cycles, 4 wire, 1500 RPM, suitable for operation at 40 deg C, 50% RH & at 210 meter above MSL, capable of taking 10% overlioading for one hour after 12 hrs of prime continuous loading, brushless, self excited, self regulated through AVR, continuous duty confirming to IS 4722, BS 2613 suitable for tropical conditions, class H insulation, including terminal box suitable for bus duct termination as required. Note : - Alternator should have with all other accessories as per specified in Technical specfications. Base Frame - Both the engine and alternator shall be mounted on suitable base frame made of MS channel which shall be installed on cement concrete foundation and vibration isolating arrangement as per recommendations of manufacturer. Power Controller For DG synchronization Microprocessor based Power command controller (P.C.- 3.3 Jakson or equivalent) suitable for auto / manual synchronization & auto load sharing. Daily service Fuel tank of 990 liters capacity fabricated out of 2 mm thick MS sheet complete with inlet and outlet connections, oil indication gauge, drain plug, air breather, provision for fuel transfer system, level indicators and all standard accessories etc. as required. Exhaust Silencer - Exhaust manifold with residential silencer. The D G set should be supplied with required hardware for external PLC based auto synchronization, auto load sharing, auto load management system. Starting system - 24 Volt DC starting system comprising of starter motors : voltage regulator and arrangement for initial excitation complete with 12/24 Volts suitable nos. lead acid type batteries of suitable AH. Ventillation System - Arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air into the atmosphere as per standard specifications. 1010 KVA | 3 | SET | |
| 317 | 317 | 500 KVA | 2 | SET | |
| 318 | 318 | Supply, Fixing, testing and Commissioning of Exhaust gas piping system of Class `B' MS pipe as per IS:1239 for upto 150 mm dia and for 200 mm dia & above MS pipe as per IS:3589 with welded joints, cut to required lengths with necessary bends, fittings, flanges, painting over primer coat, with mineral wool / rock wool insulation of minimum 75 mm thick of 150 Kg per cu M density on all sides of exhaust pipe, with chicken mesh wrapping and 26 SWG aluminium sheet cladding complete as required. The aluminum foil should be tightly cladded to insulation surface of pipe. The aluminum cladding shall be locked with sheet metal screws with other sections of aluminium foil. The measurement shall be done on the basis of centre line. (Stack height should be in accordance with emission regulations of CPCB, which will go well above the top most terrace) The exhaust piping system should be suitable for upto 550oC temperature, the surface temperature of exhaust pipe shall not exceed more than 60oC. (The rates are exclusive of support structure) 250 mm dia (wall thickness - 4.85 mm) | 100 | M | |
| 319 | 319 | Supply & fixing of SS Bellow of following diameter 250 mm dia | 6 | set | |
| 320 | 320 | Supply & fabrication of D G exhaust pipe supports by M.S angle iron of size not less than 100 x 50 mm x 6/8 mm duly grouted in the wall through minimum 8 mm thick plate and with suitable MS angle / channel iron structure. The entire MS support structure should be painted by 2 coats of anti corrosive paint over primer coat of approved shade and make. The design of support to be duly approved by the Structural Consultant / Architect before fabrication and installation. | 3500 | Kg | |
| 321 | 321 | Supplying, Laying, terminating, testing, commissioning of folowing sizes of Copper Conductor XLPE insulated, PVC sheathed armoured cable 1100 V grade. On surface the cable run shall be fixed on G.I. clamps etc of suitable size or as directed by the E-I-C complete in all respects. Supply and providing cable identification markers. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. as per specifications complete as required. 3 C x 6 sq.mm | 200 | Metre | |
| 322 | 322 | 3 C x 4 sq.mm | 150 | Metre | |
| 323 | 323 | 3 C x 2.5 sq.mm | 150 | Metre | |
| 324 | 324 | Making end termination with brass double compression gland including crimping of copper solderless lugs/ferrules for armoured power copper conductor cables of 1.1 KV grade of following sizes. 3 C x 6 sq.mm (Copper) | 10 | Set | |
| 325 | 325 | 3 C x 4 sq.mm (Copper) | 10 | Set | |
| 326 | 326 | 3 C x 2.5 sq.mm (Copper) | 10 | Set | |
| 327 | 327 | SUB-HEAD -VI- FIRE DETECTION SYSTEM Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 6839 | nos | |
| 328 | 328 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. | 46 | Nos. | |
| 329 | 329 | Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required | 13 | Nos. | |
| 330 | 330 | Supplying, installation, testing & commissioning of addressable beam detector with short circuit isolator (inbuilt or seperate) complete with emitter and receiver including connections with remote test features etc complete as required. | 4 | Nos. | |
| 331 | 331 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required | 3074 | Nos. | |
| 332 | 332 | MANUAL CALL POINT Supplying, installation, testing & commissioning of addressable manual call point complete as required Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 217 | Nos. | |
| 333 | 333 | FAULT ISOLATOR Supplying, installation, testing & commissioning of fault isolator complete with base as required | 358 | Nos. | |
| 334 | 334 | MONITOR MODULES Supply , Installation , Testing and Commissioning of Addressable Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall provide DPDTcontact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 18 | Nos. | |
| 335 | 335 | CONTROL MODULES Supplying, installation, testing & commissioning of addressable fire control module complete as required Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 139 | Nos. | |
| 336 | 336 | Supplying, installation, testing & commissioning of addressable phone control module complete as required | 186 | Nos. | |
| 337 | 337 | Hooter cum strobe Supplying, installation, testing & commissioning of addressable strobe complete as required | 217 | Nos. | |
| 338 | 338 | FIRE ALARM CONTROL PANEL Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications Ten Loop Panel 17.2.1.1 | 4 | Nos. | |
| 339 | 339 | Two Loop Panel | 11 | Nos. | |
| 340 | 340 | Supply , Installation , Testing and Commissioning of Addressable Fire Fighter's Telephone Jack with suitable module for two way communication between Remote Fire Fighter & Fire Command Center Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 186 | Nos. | |
| 341 | 341 | Supply , Installation , Testing and Commissioning of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center. Approved Makes : Ansul / Edwards / Notifier / Wissenschaftler / Rux | 24 | Nos. | |
| 342 | 342 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required Approved makes : Polycab/ RR Kabel/ Paramount/ Parasheild | 60250 | RM | |
| 343 | 343 | SUB-HEAD -VII- PA SYSTEM Speakers Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required Approved Makes : Bosch / Honeywell /System Sensor/ Ateis Ceiling Mounted Speakers | 1963 | Nos. | |
| 344 | 344 | Wall Mounted Speakers | 5 | Nos. | |
| 345 | 345 | PA CONTROLLER Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required | 10 | Nos. | |
| 346 | 346 | DIGITAL AMPLIFIERS Supply, installing, testing and commissioning of 1X500W Class-D Amplifier with 2 independent channels and can provide automatic re-settable overcurrent, overload, overheating, overvoltage, under-voltage and DC protection Approved Makes : Bosch Praesedio / Honeywell - X618/ Ateis 500 Watts | 27 | Nos. | |
| 347 | 347 | PAGING STATION Supply, installing, testing and commissioning of IP based Networkable touch screen paging station for selection of zones, supervision of system status, setting of scheduled broadcasts with the following functions: . Built-in monitoring loudspeaker . Detachable goose-neck microphone . LCD touchscreen display . Audio input Approved Makes : Bosch Praesedio / Honeywell - X618/ Ateis | 4 | Nos. | |
| 348 | 348 | Supplying and Laying of 2 core twin twisted 48/0.2 ATC, Multi strand, over all armoured speaker cable as specified in the Tender Specifications Approved makes : Polycab / Incoll /Skyton / Falcon / RR Kabel | 20850 | RM | |
| 349 | 349 | MODULAR OT Supply, Installation, Testing and commissioning of Wall & Ceiling Panels System for Modular Operation Theatre designed and constructed for exact size, easy field installation with a height of 3 mtrs. The pre fabricated OT should be free standing structure constructed from puff insulated Stainless Steel Panels. These panels are produced in double band laminator in which Stainless steel sheets of thickness of 0.80-1.0 mm is used on bothe sides. The core should consists of rigid polyurethane foam, which has been injected under high pressure, with a minimum density of 40kg/m3 .The construction shall be of single wall type. The Total thickness of Panels is 60mm. Sprayed with Antibacterial & Antifungal Paint to thickness of 300 microns Preferred make of Steel -Tata/Jindal/SAIL. All cablings within the Walls has to be supported by PVC conduits..Wall and Ceiling Panel System should be CE certified and in compliance under Class 1 Medical device | 14 | Lot | |
| 350 | 350 | Ceiling Panel System using SS Puff Panels with Antibacterial Paint Supply, Installation, Testing and commissioning of Ceiling Panels System for Modular Operation Theatre designed and constructed for exact size, easy field installation with a height of 3 mtrs. The pre fabricated OT should be free standing structure constructed from puff insulated Stainless Steel Panels. These panels are produced in double band laminator in which Stainless steel sheets of thickness of 0.80-1.0 mm is used on bothe sides. The core should consists of rigid polyurethane foam, which has been injected under high pressure, with a minimum density of 40kg/m3 .The construction shall be of single wall type. The Total thickness of Panels is 60mm. Sprayed with Antibacterial & Antifungal Paint to thickness of 300 microns Preferred make of Steel -Tata/Jindal/SAIL. All cablings within the Walls has to be supported by PVC conduits.Ceiling Panel System should be CE certified and in compliance under Class 1 Medical device | 14 | Lot | |
| 351 | 351 | LAMINAR AIR FLOW SYSTEM WITH MINI PLEAT FILTERS Supply, Installation, Testing and commissioning of LAMINAR AIR FLOW SYSTEM of size ( 2400 x 2400 mm) . The laminar should be constructed with Aluminium sheet Laminar system will introduce the highest air quality into the operation theatre. Air should be diffused into the room uniformly over the total area through perforated alumnium grills. .The air diffusers should be installed in a manner which allows them to be removed for easy maintenance of air filter. HEPA filters of H14 Grade 99.97% efficiency are used to ensure high quality clean air is supplied and under tight control of bacteria infection system. Laminar System should be CE certified and in compliance under Class 1 Medical devices/Equivalent . (2400mmx2400mm) | 14 | Nr | |
| 352 | 352 | DIMMABLE PERIPHERAL LED LIGHTS Supply, Installation, Testing and commissioning of PERIPHERAL LIGHTS * Recess mounted luminaire with screwless design for easy maintenance * Digital ballast with dimmer control * Non-yellowing clear acrylic diffuser is sealed with bottom frame and specially design sealant to ensure dust proof * Pre-anodized high purity specular finish aluminium reflector for precise light distribution | 112 | Nr | |
| 353 | 353 | AUTOMATIC HERMETICALLY SEALED SLIDING DOOR AUTOMATIC SLIDING DOOR IN HPL LAMINATE . Door Size - 1800 (W.) x 2100 (H.) mm WITH TOUCHLESS SENSOR , FOOT SWITCH. | 14 | Nr. | |
| 354 | 354 | AUTOMATIC SLIDING DOOR IN HPL LAMINATE . Door Size - 1000 (W.) x 2100 (H.) mm WITH TOUCHLESS SENSOR , FOOT SWITCH. *The Door leaf made of extruded aluminium profiles . The door leaf panel should be finished in HPL .The Door Panel should not have any vertical joints on both sides. **For smooth sliding the door moves on nylon wheels within an single piece aluminium extruded track. The Door leaf will have one view window of size 500 x 700mm . Door controller should be microprocessor based electronic automation unit (CE Marked) for controlling door movement, the acceleration and speed of the door. Features such as full opening, half opening,permanent opening .It includes photocell for user's safety .Door opening and closing should be through Touchless Hand Sensor & Foot Switch .In case of power failure door shoould be manually openable. Automatic Door should be CE certified and in compliance under Class 1 Medical device /Equivalent . | 14 | Nr. | |
| 355 | 355 | SURGEON CONTROL PANEL Supply, Installation, Testing and commissioning of TOUCHSCREEN OPERATING ROOM CONTROL PANEL (CE MARKED ) * Time Elapsed Clock * Time Day Clock ** Medical Gas Alarm - 5 service with audio visual alarm with sensors * Temp & Humidity display with controlling and sensors Hands free telephone | 14 | Nr | |
| 356 | 356 | TWO PLATE LED XRAY - DIMMABLE Supply, Installation, Testing and Commissioning of Two Plate dimmable X-Ray viewing screen designed to provide a high level of control luminance without flicker. The dimming range should be from 3-100% . The Xray should have inbuilt sensor for Xray film . On/Off and dimming operation should be through integrated PCB. TWO PLATE XRAY should be CE certified and in compliance under Class 1 Medical devices /Equivalent . | 14 | Nr | |
| 357 | 357 | PRESSURE RELIEF DAMPER Supply and Installation and Commissioning of proper Pressure Relief Dampers having multi 304 graded stainless steel blades for maintaining the positive pressure inside the operation theatre PRESSURE RELIEF DAMPER should be CE certified /Equivalent . | 14 | Nr | |
| 358 | 358 | CONDUCTIVE FLOORING WITH SELF LEVELLING Supply and Installation and Commissioning of 2.00 mm thick CONDUCTIVE ESD tiles /roll as per EN 427.(Imported) The tiles/roll are manufactured from PVC chips coated with a conductive substance. The tiles/roll will offer guarantee a longlife conductivity independently from humidity and temperature. Tiles/roll should be highly compressed with a compact surface. These conductive tiles /roll should be completly free from volatile antistatic chemicals, and ensures a permanent and stable conductive performance of the floor over its entire life time. The welding / seaming shall be done using hot air welding machine. The Electrical Resistance offered by the tiles is as per IEC 61340-4-1, EN 1081(100v) ANSI/ESD 7.1. The laying of Copper tape and conductive addhesive has to be laid before the tiles are laid. | 14 | Lot | |
| 359 | 359 | LIST BOARD Supply and Installation ,Testing and commissioning of OPERATING WRITING LIST BOARD made out of Toughened Glass in 10mm thickness of size (948mm x 648mm) | 14 | Nr | |
| 360 | 360 | HATCH BOX FOR DIRTY LINEN Supply and Installation and Commissioning of HATCH BOX made out of Stainless Steel SS 304 grade for dispoasl of dirty linen /waste.Each Hatch will be equipped with two doors and the door will be operated electronically .The Hatch will be designed in such a way that only one door will be opened at one time.The UV light wiil be so installed that it is kept on while both the doors are closed ,this UV light has to be automatically turned off in case of opening of either of the doors. There shall be indicators on both sides of the OT so that door open/close status can be monitored from both ends.HATCH BOX should be CE certified and in compliance under Class 1 Medical devices /Equivalent . | 14 | Nr | |
| 361 | 361 | PENDANTS - ANESTHESIA (Imported ) Supply and Installation and Commissioning of 'SINGLE ARM PENDANTS for Anesthesia (CE Marked) : Single Arm Pendant will have 1000mm arms with motorized Horizontal movement having load carrying capacity of 200kgs. The arm will be rotated upto 330degree to 340 degree . The Pendant will have electro magnetic brakes system which will be adaptable to variuos safety requirements and construction faciliteis. Brake indicators \"Brake Guide\" should be available with visual feedback (LED illumination). Anesthesia Pendant will have 1 arm with shelves as per points :- 1) 5/15 Amp Electrical sockets without switches - 8 to 10 nos., 2) shelfs with side rails - 4 nos. with 1 drawer 3) Gas interface set for interface plate - 1 no., 4) Interface plate with electrical fittings- 1no. 5) Provision to fix 6 Nos Gas Outlets. | 14 | Nr. | |
| 362 | 362 | PENDANTS - SURGEON (Imported ) Supply and Installation and Commissioning of DOUBLE ARM PENDANTS for Surgeons ( CE Marked) : Double Arm Pendant will have (1000mm + 800mm) arms with Horizontal movement having load carrying capacity of 200kgs. The arm will be rotated upto340 degree . The Pendant will have electro magnetic brakes system which will be adaptable to variuos safety requirements and construction faciliteis. Brake indicators \"Brake Guide\" should be available with visual feedback (LED illumination). Surgeon Pendant will have 2 arms with shelves as per points :- 1) 5/15 Amp Electrical sockets without switches - 8 to 10 nos., 2) shelfs with side rails - 4 nos. with 1 drawer 3) Gas interface set for interface plate - 1 no., 4) Interface plate with electrical fittings- 1no. 5) Provision to fix 6 Nos Gas Outlets. | 14 | Nr. | |
| 363 | 363 | OT LIGHT (Imported ) Supply and installation of OT light .160000x160000 LUX | 14 | Nr | |
| 364 | 364 | VIEW WINDOW Supply, Installation, Testing and commissioning of VIEW WINDOW with 6mm toughened glass on both sides. Motorized Blinds of reputed make sandwiched in both glasses . The window will be recessed into wall. View Window size : 1800 x 1500 mm. View Window should be CE certified and in compliance under Class 1 Medical device | 28 | Nr. | |
| 365 | 365 | ELECTRICAL CONDUITING & WIRRING INSIDE OT Supply, Installation, Testing and commissioning of ELECTRICAL CONDUITING AND WIRRING INSIDE OT . All wires should run within PVC conduits of 25mm size . Electrical distribution board complete with all accessories. Internal wiring with FRLS wires of reputed brands such as Bonton /finolex etc ,Wires will be of size 2.5Sqmm,4sq.and 6sqmm..Electrical Switchsockets of 6/16amp of approved make min 4 nos on each walls. | 14 | Lot | |
| 366 | 366 | Storage Unit Supply and Installation of Storage unit as per specifications | 14 | Nr. | |
| 367 | 367 | SCRUB SINK \"The Scrub Sink should be made of 1.5mm thick Stainless Steel SS 304 grade . The scrub sink should be\"\"provided with a front access panel which should be easily removed for access to the water controlled valve, waste connections, stoppers and strainers. Hands free operation should include infra-red sensors with built-in range of adjustment.\"\"Thermostatic mixing, valve control should be located behind the access panel and maintain constant\" \"water temperature.\" \"User defined time 1, 3,5,10 min. are available. This timing should be adjustable to meet individual\"application requirements, provided with infrared sensors, thermostatic control taps with fail-safe temperature controls.\"\"All units should have reduced anti splash front. It should have manual foot and operation mode. The station should also have inbuilt soap dispensers. | 14 | Nr. | |
| 368 | 368 | UPS UPS load per OT should be provided minimum 10 KVA with one 10 KVA backup for all OTs and reduntancy( n+1) should switch automatically. The battery bank may be common for UPS. For eg. there are 8 MOT, the USP should be 10KVAx8 and one 10 KVA as standby for all OTs. As per the specification | 14 | Nr. | |
| 369 | 369 | Aluminimum grill for return air approx Size- 300 x 450mm complete set | 56 | Nr. | |
| 370 | 370 | HOSPITAL MANAGEMENT SYSTEM Electronic Registration System with HIS Module for patient management/OPD which can expend from registration to other required module, including required Servers/Registration Workstation,Printer and other H/w equipments etc all complete.Apporved Make:- Wipro Limited, Napier Healthcare, Tenwave Infotech Pvt Ltd, IICONS | 1 | JOB | |
| 371 | 371 | OXYGEN GAS SYSTEM Fully automatic Oxygen Controls control panel(flow 1200 lpm) SITC of fully Automatic pneumatically operated oxygen control panel. Visual indication of the manifold is provided by 3 guages within control panel, Indicating Pressure of the right & Left hand bank and the supply pressure from control panel to distribution system with sensing faciliteies to provide visual signals na other anciliary services such as heaters. Pannel should be fitted with audio alarm indication for changeover of empty cylinder. The entire manifold will be hydraulically tested at 130 Kg/Cm2 pressure, duly degreased foroxygen Service, and supplied in sealed cover, ready for assembly at site etc. complete as required. (Note : Excluding Supply of cylinder.) | 1 | Set | |
| 372 | 372 | Oxygen Manifold - 2 banks x 15 cylinders. SITC of oxygen manifold of Size (15 working + 15 Standby) for Indian type bulk cylinders, high pressure copper annealed tail pipes complete with middle frame, chains for individual bulk oxygen cylinder, NRV's and 40 nos. pig tail pipes. it should be suitable to withstand a working pressure of 145 kg/cm2 and should be tested at 300 kg/cm2. etc. complete as required. | 1 | Set | |
| 373 | 373 | Oxygen Manifold (Emergency) - 2 banksx 6 cylinder SITC of oxygen manifold of Size (6 working + 6 Standby) for Indian type bulk cylinders, high pressure copper annealed tail pipes complete with middle frame, chains for individual bulk oxygen cylinder, NRV's and 12 nos. pig tail pipes. it should be suitable to withstand a working pressure of 130 kg/cm2 and should be tested at 300 kg/cm2. etc. complete as required. | 1 | Set | |
| 374 | 374 | Gas Outlets with probes - Oxygen SITC for Oxygen Outlets as Per standards, Terminal units shall be capable of single-handed insertion and removal of the medical gas probe. The wall mounted first fix assembly shall consist of brass pipeline termination block with copper stub pipe secured between a back plate and a gas specific plate to allow limited radial movement of the copper stub to align with the pipeline. The gas specific plate shall be permanently fixed to the backplate etc. complete as required. | 710 | No | |
| 375 | 375 | Oxygen Flow meters SITC for Oxygen flowmeter complete with humidifier bottle, The flow meter must be constructed with chromium plated brass body, extremely robust, to take care of the day to day usage demand. Flow meter cartridge type knob : easy to maintain, offers optimum adjustment quality and superior designing and engineering to provide high level of accuracy, with no significant affect from restrictions caused by down-stream equipments. The flow meters should be 0-15 LPM range for oxygen. etc complete as required. | 710 | No | |
| 376 | 376 | NITROUS OXIDE SYSTEM Fully automatic Nitrous Oxide Controls(500lpm) SITC for Fully Automatic pneumatically operated N2O control panel. With heater, The entire manifold will be hydraulically tested at 250 Kg/Cm2 pressure, duly degreased , etc complete as required. | 1 | Set | |
| 377 | 377 | N2O Manifold - 2 banks X 4 Cylinder SITC for (4 working + 4 Standby) size of N2O manifold complete with middle frame, chains, NRV's 8 nos. pig tail pipes, Manifold should have high pressure copper annealed tail pipes with one end having brass bull nose suitable for Nitrous Oxide cylinders and other end suitable for Manifold non- return Valves. Each manifold will have one terminal header and a NPT connection for the Automatic Control Panel. etc. complete as required. | 1 | Set | |
| 378 | 378 | Nitrous oxide manifold - Emergency 2 Banks X 2 Cylinders SITC for (2 working + 2 Standby) size of N2O manifold complete with middle frame, chains, NRV's 4 nos. pig tail pipes, Manifold should have high pressure copper annealed tail pipes with one end having brass bull nose suitable for Nitrous Oxide cylinders and other end suitable for Manifold non- return Valves. Each manifold will have one terminal header and a NPT connection for the Automatic Control Panel. etc. complete as required. | 1 | Set | |
| 379 | 379 | Gas Outlets with probes - Nitrous Oxide SITC for Nitrous Oxide outlets as Per standards, Terminal units shall be capable of single- handed insertion and removal of the medical gas probe. The wall mounted first fix assembly shall consist of brass pipeline termination block with copper stub pipe secured between a back plate and a gas specific plate to allow limited radial movement of the copper stub to align with the pipeline. The gas specific plate shall be permanently fixed to the backplate, etc. complete as required. | 10 | Set | |
| 380 | 380 | CARBON DIOXIDE SYSTEM Fully auto CO2 Controls (50lpm) SITC for Fully Automatic pneumatically operated CO2 control panel. With heater, The entire manifold will be hydraulically tested at 250 Kg/Cm2 pressure, duly degreased , etc complete as required. | 1 | Set | |
| 381 | 381 | CO2 Manifold - 2 banks X 2Cylinders SITC for (2 working + 2 Standby) size of CO2 manifold complete with middle frame, chains, NRV's 4 nos. pig tail pipes, Manifold should have high pressure copper annealed tail pipes with one end having brass bull nose suitable for Carbon dioxide cylinders and other end suitable for Manifold non- return Valves. Each manifold will have one terminal header and a NPT connection for the Automatic Control Panel. etc. complete as required. | 1 | Set | |
| 382 | 382 | CO2 Manifold (Emergency) - 2 banks x 1 cyl SITC for (1 working + 1 Standby) size of CO2 manifold complete with middle frame, chains, NRV's 2 nos. pig tail pipes, Manifold should have high pressure copper annealed tail pipes with one end having brass bull nose suitable for Carbon dioxide cylinders and other end suitable for Manifold non- return Valves. Each manifold will have one terminal header and a NPT connection for the Automatic Control Panel. etc. complete as required. | 1 | Set | |
| 383 | 383 | Gas Outlets with probes - CO2 SITC for Carbon diaoxide outlets as Per HTM 2022,Terminal units shall be capable of single- handed insertion and removal of the medical gas probe. The wall mounted first fix assembly shall consist of brass pipeline termination block with copper stub pipe secured between a back plate and a gas specific plate to allow limited radial movement of the copper stub to align with the pipeline. The gas specific plate shall be permanently fixed to the backplate, etc. complete as required. | 10 | No | |
| 384 | 384 | Triplex Compressed Air System: 5000 LPM SITC for TRIPLEX Compressed air system complete with oil free air compressor (3 nos. x 80 cfm) equipped with air receiver capacity of 3000 ltrs. And complete with Air Dryer of 75 cfm. It should be consist of oil-less, stationery air cooled silenced (Reciprocating) air compressor. It should be equipped with three electrical motors, one Air reservoir Tank, Air filters, Pressure Regulator-cum-filter, Air Dryer with moisture separator. Interconnecting pipes with necessary valves and fittings thereof. etc. complete as required. | 1 | Set | |
| 385 | 385 | Gas Outlets with probes - Medical Air ( 4 Bar) SITC for Compressed M.Air- 4 Bar outlets as Per standards , Terminal units shall be capable of single-handed insertion and removal of the medical gas probe. The wall mounted first fix assembly shall consist of brass pipeline termination block with copper stub pipe secured between a back plate and a gas specific plate to allow limited radial movement of the copper stub to align with the pipeline. The gas specific plate shall be permanently fixed to the backplate, etc. complete as required. | 175 | No | |
| 386 | 386 | Gas Outlets with probes - Surgical Air (7 Bar) SITC for Compressed M.Air- 7 Bar outlets as Per HTM 2022/ NFPA, Terminal units shall be capable of single-handed insertion and removal of the medical gas probe. The wall mounted first fix assembly shall consist of brass pipeline termination block with copper stub pipe secured between a back plate and a gas specific plate to allow limited radial movement of the copper stub to align with the pipeline. The gas specific plate shall be permanently fixed to the backplate, etc. complete as required. | 10 | set | |
| 387 | 387 | Quadruplex Vacuum System: 7000 LPM , -450 Hg, SITC for QUADRUPLEX Vacuum Central system complete with Vaccum pumps (4 Nos X 10 HP) Model - 15V each pump should be reciproting base frame mounted with motor and 1 No 4000 ltrs. Capacity vacuum reservoir, The Vaccum System should include three medical Vaccum pumps each with electrical motors, silencers, bacteria filters They should be capable of removing more than 99.9% of oil and smoke particles from the exhaust. etc. complete as required. | 1 | Set | |
| 388 | 388 | Outlets with probes - Vacuum SITC for Vacuum outlets as per standards, Terminal units shall be capable of single-handed insertion and removal of the medical gas probe. The wall mounted first fix assembly shall consist of brass pipeline termination block with copper stub pipe secured between a back plate and a gas specific plate to allow limited radial movement of the copper stub to align with the pipeline. The gas specific plate shall be permanently fixed to the backplate, etc. complete as required. | 710 | N0 | |
| 389 | 389 | Ward Vacuum with regulator and jar (600 Ml) | 700 | N0 | |
| 390 | 390 | Theater Suction jars with regulator (theatres,2*2000 ml) | 10 | No | |
| 391 | 391 | Copper pipe: SITC for Medical Grade copper pipe with required copper fittings, All pipes shall be drawn half hard temp., solid drawn, seamless, phosphorous deoxidised, non-arsenic and degreased copper pipe conforming to EN 1057:1996 (originally BS 2871-1971 Part 1 (Table X) and chemical composition as per BS-6017 of 1981 table 2, The supplies of copper pipe would be accompanied with manufacturers test certificate for the physical properties of copper pipes and their Chemical composition. The supply of pipes be further substantiated with inspection certificate from the third party like SGS/Lloyds Register. etc. complete as required. 12mm | 2000 | Mtr | |
| 392 | 392 | 15mm | 6000 | Mtr | |
| 393 | 393 | 22mm | 5000 | Mtr | |
| 394 | 394 | 28mm | 3300 | Mtr | |
| 395 | 395 | 42mm | 1700 | Mtr | |
| 396 | 396 | 54mm | 860 | Mtr | |
| 397 | 397 | 76mm | 375 | Mtr | |
| 398 | 398 | 108 mm | 300 | Mtr | |
| 399 | 399 | Zonal Valve Service ( Valves with Box) 1gas+1Vac | 35 | No | |
| 400 | 400 | 2gas+1Vac | 25 | No | |
| 401 | 401 | 3gas+1Vac | 5 | NO | |
| 402 | 402 | 4gas+1Vac | 4 | No | |
| 403 | 403 | 5gas+1Vac | 10 | NO | |
| 404 | 404 | Isolation Valve service12 mm dia | 15 | No | |
| 405 | 405 | 15 mm dia | 20 | No | |
| 406 | 406 | 22 mm dia | 20 | No | |
| 407 | 407 | 28 mm dia | 30 | No | |
| 408 | 408 | 42 mm dia | 15 | No | |
| 409 | 409 | 54 mm dia | 10 | No | |
| 410 | 410 | 76 mm dia | 5 | No | |
| 411 | 411 | Master Alarm service ( Digital ), post source | 1 | No | |
| 412 | 412 | Area Alarm service ( Digital) 2 Gas ( 1 O2 + 1 Vac) | 35 | No | |
| 413 | 413 | 3 Gas ( 1 O2 + 1 Vac + 1 MA4) | 25 | No | |
| 414 | 414 | 4 Gas ( 1 O2 + 1 Vac + 1 MA4 + 1 n2o) | 5 | No | |
| 415 | 415 | 5 Gas ( 1 O2 + 1 Vac + 1 N2O + 1 CO2 + 1 SA7) | 4 | No | |
| 416 | 416 | 6 Gas ( 1 O2 + 1 Vac + 1 N2O + 1 CO2 + 1 SA7 + 1 ma4) | 10 | No | |
| 417 | 417 | Antistatic Hose High Pressure Antistatic Hose | 1400 | Mtr | |
| 418 | 418 | Low pressure Antistatic Hose | 1250 | Mtr | |
| 419 | 419 | Bed Head Panels (Size - 1500 X 300 X 110 mm) SITC for pure extruded aluminium made with powder coat finish, having 5 Nos gas outlets, 2 Nos electric panels having 4 nos of 6/16 Amp switches and 4 Nos of electrical sockets ( 6/16 Amp) Make - Legrand or similer type, Provision for Nurse call display, SS IV pole with holder and utility basket etc. | 250 | No | |
| 420 | 420 | Single arm OT pendant SITC for Single arm swiveling pendant having 2 Nos of O2, 2 Nos of VAC, 1 No of Nitrous oxide, I No of medical air (4 Bar), 1 No Surgical Air (7 Bar)and 1 No of CO2 gas outlet points, 6 Nos of electrical switch and sockets( Legrand, 6/16 Amp). The pendant should have 2 Nos of IV poles ( SS 304) and 2 Nos of Monitor selves. | 20 | No | |
| 421 | 421 | Kit conversion for Nitrous Oxide | 10 | Set | |
| 422 | 422 | Kit conversion for Oxygen | 20 | Set | |
| 423 | 423 | Combined electric control panel for Air compressor and Vacuum pumps Electrical control panel is made of MS Sheet having thickness 16 SWG and should be epoxy powder coated. The electrical control panel would be equipped with auto manual selector, 4 nos. Star-Delta starters each compatible to 10 HP motors for compressors and 4 nos. DOL starters compatible to 20 HP each electric motor for Vacuum pumpsThe electrical control panel would be further equipped for triplex/cascade system for vacuum pumps & Air Compressors and also be equipped with safety equipment for the air compressors. | 1 | Set | |
| 424 | 424 | PNEUMATIC TUBE SYSTEM Central controller with all hardware as per specs, zone controller and software, including statistic functions and user license as per specs Stations | 1 | Set | |
| 425 | 425 | DST Trough Station | 30 | EACH | |
| 426 | 426 | Multi Receive Station | 2 | EACH | |
| 427 | 427 | Multi Send Station | 2 | EACH | |
| 428 | 428 | Carrier receive Basket | 25 | EACH | |
| 429 | 429 | Empty Carrier rack | 25 | EACH | |
| 430 | 430 | Carriers – | 60 | EACH | |
| 431 | 431 | 3- way - DIVERTER 160 | 10 | EACH | |
| 432 | 432 | Blower with all accessories - BLOWER SU8 noch anpasse | 3 | EACH | |
| 433 | 433 | Tubes with clamps, support structure and all accessories | 700 | METER | |
| 434 | 434 | Communication and Low Voltage wiring with adapters, boosters and all accessories | 1 | LOT | |
| 435 | 435 | SUPPLY & INSTALLATION OF Nos 120 KVA UPS WITH 10-15 MIN BACK UP. - Supply, unloading, installation , testing & commissiong of micro processor / DSP controlled 120 KVA, IGBT based rectifier to achieve THDI <3% and input power factor 0.99 at 50%-100% loading, Built-in Delta Star Isolation Transformer at inverter output before static switch, True Online Double Conversion (VFI as per IEC 62040-3) UPS using PWM IGBT technology , 3 Phase input and 3 phase 415 V output UPS system; and each comprising of the following: 100% rated Inbuilt static switch at the invertor output . 100% rated Inbuilt static switches at the static bypass line. 100% rated Inbuilt Maintenance Bypass. Soft Start 0-100% in 120 Second(Selectable) Built-in Phase sequence protector & corrector ( UPS should not go on bypass/battery bank if the phase are reveresd) & Back feed Protection Voltage Distotion - <1% on linear & <3% on Non linear load Input Voltage Range- +/- 20% Web-enabled Monitoring and Management through SNMP protocols for multi-OS environments. Supplying, unloading, installing , testing and commissioning of Lead Acid sealed maintenance free 12V, batteries for 120 KVA ystem, for providing 10-15 minutes backup to 120 KVA UPS The bank of batteries shall comprise required Nos of batteries. 12V/120AH/40 Nos Supply, unloading, installation,testing & commissioning of matching cabinet/open racks to house SMF batteries for 120 KVA UPS system along with interconnecting links, MCCB etc. complete as required & as per specifications. | 1 | SET | |
| 436 | 436 | SUB-HEAD -V- IP CCTV SYSTEM Supply , Installation , Testing and Commissioning of LC-LC singlemode fiber patch cord for LIU to switch connectivity. Approved Make List :- Belden/Siemon/Panduit/Leviton | 50 | Nos. | |
| 437 | 437 | Supply , Installation , Testing and Commissioning of CAT 6 UTP cable 23 AWG solid copper conductors for Connectivity of Hub room to End Point. Approved Makes: Belden/Siemon/Panduit/Leviton | 27720 | Mtr. | |
| 438 | 438 | Supply , Installation , Testing and Commissioning of CAT6 information outlet (I/O) for Data, Voice, Camera & Wi-Fi at user end. Approved Makes: Belden/Siemon/Panduit/Leviton | 462 | Nos. | |
| 439 | 439 | Supply , Installation , Testing and Commissioning of loaded 24 port CAT6 jack panel for CAT6 cable termination at rack end. Approved Makes: Belden/Siemon/Panduit/Leviton | 20 | Nos. | |
| 440 | 440 | Supply , Installation , Testing and Commissioning of CAT6 patch cord 3 feet for rack side switch to jack panel connectivity. Approved Makes: Belden/Siemon/Panduit/Leviton | 462 | Nos. | |
| 441 | 441 | Supply , Installation , Testing and Commissioning of CAT6 patch cord 7 feet for information outlet (I/O) to end user device connectivity. Approved Makes: Belden/Siemon/Panduit/Leviton | 462 | Nos. | |
| 442 | 442 | Supply , Installation , Testing and Commissioning of 1, 2 and 4 port face plate white for I/O fixing at user side. Approved Makes: Belden/Siemon/Panduit/Leviton | 462 | Nos. | |
| 443 | 443 | Supply , Installation , Testing and Commissioning of 3 MP Dome Camera , ONVIF profile S & G ,UL , CE , FCC Certified , 1/2.8\" CMOS sensor ,3.6 mm fixed focal , triple stream ,Min Illumination :0.01 Lux @ (F1.2, AGC ON), 0.028 Lux @(F2.0, AGC ON), 0 Lux with IR , Shutter Speed : 1/5 ? 1/100,000 s , Edge analytics : line crossing , perimeter intrusion , stationary object ,Video Compression : H.265 ,H.264 , frame rate 30 fps @ 3MP , Edge analytics : line crossing , perimeter intrusion ,Face detection , cross counting , stationary object ,Inbuilt IR LED , IR distance upto 30 mtrs ,IP 66 , POE . Approved Makes :Allgovision/ Impulse / Avigilon / Pelco/ Axis | 260 | Nos. | |
| 444 | 444 | Supply , Installation , Testing and Commissioning of 3 MP Bullet Camera , ONVIF profile S & G ,UL , CE ,FCC Certified , 1/2.8\" CMOS sensor ,3.6 mm fixed focal , triple stream , Min Illumination :0.05 Lux @ (F1.2, AGC ON), 0 Lux with IR , Shutter Speed : 1/5 ? 1/100,000 s , Video Compression : H.265 , H.264 , frame rate 30 fps @ 3MP , Edge analytics : line crossing , perimeter intrusion ,Face detection , cross counting , stationary object ,Inbuilt IR LED , IR distance upto 30 mtrs ,IP 66 , POE . Approved Makes :Allgovision/ Impulse / Avigilon / Pelco/ Axis | 202 | Nos. | |
| 445 | 445 | Supply, installation, testing and commissioning of 64 Channel NVR upgradable to 128 Channel, H.264 Recording and Playback , Embedded Linux OS, Pre-Installed VMS with licenses,ONVIF profile S & G , Intel Based i7 Processor , 2x4GB, DDR3 RAM , Intel HD Graphics , Throughput Input: 640Mbps / Output: 640Mbps,Decoding Rate Up to 3840 PPS @ D1, 2.5” SATA x 1 (for OS) + 3.5” SATA x 8 ports , e-SATA Port for External Storage Device , RAID 0/1/5/6/10 Support , COM Port RS-232 x1 and RS-485 x 1, USB 3.0 x 2 + USB 2.0 x 3 , Digital Input : TTL-level x 4 , Digital Output : Relay NC/NO x2 (DC24V/1A) , 1 x WAN (10/100/1000 BaseT) , 1 x LAN (10/100/1000 BaseT), 1 x SFP Port (1 Gbps). Approved Makes :Allgovision/ Impulse / Avigilon / Pelco/ Axis | 8 | Nos. | |
| 446 | 446 | Supply , Installation , Testing and Commissioning of 6TB Surviellance Hard Disk. Approved Makes: WD /segate /Toshiba/HP | 46 | Nos. | |
| 447 | 447 | Supply , Installation , Testing and Commissioning of Full HD 55\" LED Professional Display Panel. Approved Makes: Panasonic / LG/ Sony/ Samsung | 9 | Nos. | |
| 448 | 448 | Supply , Installation , Testing and Commissioning of 24 port Fabric (SFP) switch with 20 Nos. of 20 100M/1G SFP Port , 4 Nos. of GbE RJ45/SFP Combo Port , 4 Nos. of 1G/10G SFP+ Port ,1 X Console , Switching bandwidth 128 Gbps , 32K MAC address support , Support L2 feature STP, RSTP ,MSTP . Support 802.1Q VLAN , port based VLAN , 4K VLAN entries , MAC based VLAN , IP subnet based VLAN . Support IEEE 802.3ad LACP . L3 features - static routing , DHCP server. Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista | 2 | Nos. | |
| 449 | 449 | Supply , Installation , Testing and Commissioning of 24 port L2 Managed switch having port density 24 Nos of 10M/100M/1G RJ45 Port POE /POE+ ports , 2 Nos of GbE RJ45/SFP Combo Port , 1X console port , Available POE power 370 W , 52 Gbps switching bandwidth , 8K MAC address support , Support L2 feature STP, RSTP ,MSTP . Support 802.1Q VLAN , port based VLAN , 4K VLAN entries , MAC based VLAN , IP subnet based VLAN . Support IEEE 802.3ad LACP . L3 features - static routing , DHCP feature , Device Management system - topology view , floor view , map view , dashboard , traffic monitoring , cable diagnostics.CE,FCC certified. Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista | 26 | Nos. | |
| 450 | 450 | Supply , Installation , Testing and Commissioning of Workstation PC: Intel(R) Core(TM) i7-3770 Processor (8M Cache, up to 3.90 GHz); RAM: 8GB (1x8GB) Non-ECC DDR3 1600MHz ; Keyboard: 12 function keys; Chassis: Tower/Workstation; DVD: 8X Slimline DVD+/-RW, Data Only; Dual Graphics Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000; Hard disk: 250GB, 7200 RPM 3.5\" SATA 6Gb/s Hard Drive; Operating system: Windows 7 Professional 64 Bit or latest. Approved Makes: HP / DELL / IBM / LENOVO | 5 | Nos. | |
| 451 | 451 | Supply , Installation , Testing and Commissioning of fiber Modules 1G BASE Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista | 52 | Nos. | |
| 452 | 452 | COLD ROOM WORKS FOR MORTUARY AND AUTOPSY Supply ,Installation,Testing & Commissioning of cold storage facility with refrigeration units along with 60mm thick Poly Urethene Foam (PUF) panels inside the pre constructed stone masonary with RCC roof finished room ,to operate in temperature range +2 degre celcius to +8 degree celcius ,with design at ambient temperature of 43 degree celcius, with external dimensions of cold room as (2 NO IN AUTOPSY AND 1 NO IN MORTURY) , as per tender specifications:PUF PANEL STRUCTURE The walls and ceiling panel should be fabricated from 0.40 mm thick sheet with inner and outer finish of Pre Painted GI sheet having PUF thickness of 60mm. Supply and installation of 60 mm thick Aluminium Cheq sheet with Marine Ply Floor for flooring inside Walk-in-Cold Room. Supply & installation of 1 No. flush door with clear opening of 34\" x 78\" ,made of 60 mm PUF panel, inner & outer with Pre Painted GI. There should be high quality cam lock with metal plunger, hinges & handle on the door for automatic closure of the door with out any manual push. 1 number of Vapour proof LED light fittings with suitable switching and wiring in casing caping is inclusive . All accessories required for installation of cold room facility is inclusive . | 450 | SQMTR | |
| 453 | 453 | REFRIGERATION UNITS Supply ,Installation,Testing & Commissioning refrigeration unit with hermetic Scroll Compressor is to be installed with 20,000 BTU/Hr capacity @ +4 deg C room temperature and +35 deg C ambient temperature to be operated on 440V, 3 ph, 50 HZ power supply with one no of machine as Standby with copper piping of manufacture recommended size and insulation . APPROVED MAKES: BLUE STAR, VOLTAS, DAIKIN, PUF PANEL : BLUE STAR/KOLPACK/VOLTAS/LLYODS. EVAPORATING UNIT: BLUE STAR/ KOLPACK/BOHN/LLYODS/VOLTAS CONDENSING UNIT: BLUE STAR/ KOLPACK/BOCK/VOLTAS/LLYODS The Manufacturer should have inhouse facility of both PUF Panel and Refrigeration Units. | 8 | Nos | |
| 454 | 454 | ACCESS CONTROL SYSTEM: Supply ,Installation ,Testing & Commissioning of 4 Door 4 reader access control panel with onboard 32 Bit RISC ARM CPU, 8MB flash memory, shall support up to 100000 card user, 400000 event transactions, TCP/IP, the panel should have inbuilt 4 GB SD memory card to take mirror image of device configuration. data shall support standard Wiegand readers, Access Control panel should have MODBUS connectivity to integrate the panel with BMS (Building Management System), with metal enclosure & inbuilt power supply, facility of din-rail mounting should available. capable to integrate with IP/CCTV & NVR for access event alerts, Inbuilt door interlocking facility, SNMP alerts facility, Low battery and AC fail alert facility & reader Tamper detection alert facility should available. Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart i | 25 | Nos. | |
| 455 | 455 | Supply ,Installation ,Testing & Commissioning of 2 Door 2 reader access control panel with onboard 32 Bit RISC ARM CPU, 8MB flash memory, shall support up to 100000 card user, 400000 event transactions, TCP/IP, the panel should have inbuilt 4 GB SD memory card to take mirror image of device configuration. data shall support standard Wiegand readers, Access Control panel should have MODBUS connectivity to integrate the panel with BMS (Building Management System), with metal enclosure & inbuilt power supply, facility of din-rail mounting should available. capable to integrate with IP/CCTV & NVR for access event alerts, Inbuilt door interlocking facility, SNMP alerts facility, Low battery and AC fail alert facility & reader Tamper detection alert facility should available. Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart i | 2 | Nos. | |
| 456 | 456 | Power Supply- Supply, Installation , testing and commissioning of 12 V SMPS DC Power Supply Unit, highly regulated and spikes free terminal voltage and heavy sourcing current for regulated terminal voltage. Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart i | 125 | Nos. | |
| 457 | 457 | Supply & Installation of Cloud Compatible enterprise level Web based Modular Access Management and Time Attendance software with SQL Database and support up to desired number of users. Single GUI Plateform with complete modular software with provision to integrate with different application ie; Access Control, VMS, Alarm Management, etc. Employee Self Service - login module for Employee/HOD/MANAGER where they can view their attendance; they can apply for leave/manual punch/tour entry/outdoor entry though internet with their login ID & password. Same way manager can online approve all application sent by employee. Comprehensive Email and SMS module for to send various SMS & Email on the base of different events in Access Control & Time Attendance system. It should support Multi company, multi location, multi department, multi login with different rights, muti hierarchy of employee, Should support maker & checker facility - the local administrator should able to add the users but he should not able to authenticate/approve the User, Approval right of the added user should be with main Administrator. Dedicated output reports for Payroll integration, Duress Authentications, Email & SMS can be sent on every configured event ie; Leave Application/approval, Manaual Punch Application/Approval,Outdoor Application/Approval, Tour Application/Approval, Condone Application/Approval . Holiday restriction (Reader Wise), Device Configuration – Push/Pull, Dual Authentications, Easy Employee tracking as outdoor Employee Attendance should marked with their GPS Location, Employee can mark Offline attendance (If No Network) through Android Mobile App. Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart i | 1 | Job | |
| 458 | 458 | Supply ,Installation ,Testing & Commissioning of Mifare smart Card Reader Technical Specs. Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart I Read Range -4-9 cms Data Read CSN/Sector Type Smart Card (Mifare Classic) Transmit Frequency 13.56 MHz Card (Transponder ) Mifare® Series (ISO14443-A) Card Read Time 0.1 Sec Output Interface Wiegand Format (32 Bits) LED Indicator Bi Color LED Power supply 12V DC @ 100mA Material Abs Plastic Card should be read in1 sec A Wiegand output that easily interfaces with most existing Wiegand protocol access control panels. Compact and Elegant. Easily installed on walls and doors. | 125 | Nos. | |
| 459 | 459 | Supply ,Installation ,Testing & Commissioning of Mifare Smart Card Contactless transmission of data and supply energy (No battery needed), Operating Distance: Upto 100mm (Depending on Antenna Geometry), Operating Frequency: 13.56 MHZ. Fast Data Transfer: 106 Kbit/s High Data Integrity: 16 Bit CRC, parity, bit coding, bit counting. 1 Kbyte, organized in 16 sectors with 4 blocks of 16bytes each (one block consists of 16 byte), User definable access conditions for each memory block. Data retention of 10 years. Mutual three pass authentication (ISO/IEC DIS9798-2), Data encryption on RF-Channel with replay attack protection. Individual set of two keys per sector (per application) to support multi-application with key hierarchy. Unique serial number for each device. Transport key protects access to EEPROM on chip delivery. Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart i | 400 | Nos. | |
| 460 | 460 | Supply ,Installation ,Testing & Commissioning of Electromagnetic Lock 600 lbs, Single leaf, LED Status Display, Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart i | 125 | Nos. | |
| 461 | 461 | Supply ,Installation ,Testing & Commissioning of Electromagnetic Lock 1200 lbs, double leaf, LED Status Display, Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart i | 1 | Nos. | |
| 462 | 462 | Supply , Installation , Testing and commissioning of CAT 6 UTP cable 23 AWG solid copper conductors. Approved Makes: Belden / Siemon / Panduit / Leviton / Molex | 3000 | Nos. | |
| 463 | 463 | Supply and Laying of 8 Core x 1.0 sq mm multi strand, copper, unarmoured shielded Cable as per specification (between the every card readers & the access controllers) Approved Makes : Polycab / RRKable / CMI / Paramount | 5600 | RM | |
| 464 | 464 | Supply ,Installation ,Testing & Commissioning of U/L Clamp made of aluminium anodised for EM Lock. Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart i | 125 | Nos. | |
| 465 | 465 | Supply , Installation , Testing and commissioning of Exit push button as required. Approved Makes :Cardex / Lenel / Impulse / Bosch / Smart i | 125 | Nos. | |
| 466 | 466 | Supply & laying of Supply and drawing of 2 C X 1.5 Sq mm multi stranded twisted unshielded FRLS Copper cable for Access control system. Approved Makes : Polycab / RR Kabel / Paramount / Parasheild | 1500 | RM | |
| 467 | 467 | SOLAR POWER GENERATION SYSTEM Poly Crystalline 330Wp Modules,With inbilt bypass diode, Frame should be Al anodize,power tolerance of +/-3%,Vmp and Imp shall not vary more than 2%, With junction box arrangement having inbuild bypass diode,weather proof,IP-65,with RFID tag. Material warranty upto 5 year and performance warranty 25 year. MAKE- SOVA, SAATVIK, ADANI | 1516 | 500 KW | |
| 468 | 468 | STRING INVERTER SUITABLE FOR 80 KWp-2 Nos., 50 KWp-2 Nos., 30 KWp-8 Nos., (Total 12 Nos.) SOLAR SYSTEM GRID CONNECTED String INVERTER, House MPPT, Grid interactive, output should compatible with grid frequency. IGBT/MOSFET, Microprodessor, DSP, 415 V, 3-Phase,50Hz +/-3%, Ambient tem -20 dec to +50 Deg, Humidity 95%, Protection IP-20 for indoor and IP-65 outdoor, grid voltage tolerance -20% to +15%, No load losses lees then 1% of rated power, efficiency 93% or above, THD less then 3%, P.F more then 0.9, fully automatic, having internal protections against any fault in feeder, inverter desing as per IEC/BIS standard for efficiency and enviornmental tests as per IEC 61683/IS 61683 and IEC 60068-2 (1,2,14,30). MPPT as per IEC 60068-2(1,2,14,30) / BIS.Junction box should be IP-65 for outdoor and IP 55 for indoor as per IEC 529. Inverter should be grid integrated. MAKE- Delta, Growatt,Solex STRING INVERTER 30 KWp | 8 | Each | |
| 469 | 469 | STRING INVERTER 50 KWp | 2 | Each | |
| 470 | 470 | STRING INVERTER 80 KWp | 2 | Each | |
| 471 | 471 | Data Logger PV array energy production: Digital Meters to log the actual value of AC/DC Voltage,Current &Energy generated by the PV systems shall have to be provided. Two way LT 415V energy meters (import – export) class 0.5 compliant shall be incorporated in the system on main AC Grid supply. | 12 | Each | |
| 472 | 472 | Weather Station Solar Irradiance: An integrating Pyranometer (Class-II or better) should be provided, with the sensor mounted in the plane of the array. Readout should be integrated with data logging system.Wind Speed : An integrated wind speed measurement unit be provided.Temperature Sensor: Integrated temperature Sensor for measuring the module surface temperature, Inverter inside enclosure temperature and ambient temperature to be complete with readout integrated with the data logging system. | 1 | Each | |
| 473 | 473 | Monitoring System logging systems (Hardware and software): for Solar PV Plant, for plant control and monitoring shall be provided with the following features (M/S. HP/WIPRO/DELL/LENOVO/SS MAKE): One no. of suitable Desktop Computer with minimum configuration of 3 GHz Pentium i3 latest (3MB Cache) with minimum 500GB HDD, 4 GB RAM, 2 Parallel & 2 Serial Port, Wi-Fi LAN Card, DVD RW Drive, 20” LED Display, USB Scroll Mouse, Windows 10 along with All in one 1200 dpi/12 ppm Desktop LaserJet printer along with a 1 KVA on-line ups with battery backup. | 1 | Each | |
| 474 | 474 | CCAT-6 Cable for Networking | 100 | Running Mtr | |
| 475 | 475 | Array Struchure Hot dip galvanized MS mounting structures may be used for mounting the modules / panels / arrays. Minimum thickness of galvanization should be at least 120 microns. • Each structure should have angle of inclination as per the site conditions to take maximum insolation. However to accommodate more capacity the angle inclination may be reduced until the plant meets the The Mounting structure shall be so designed to withstand the speed for the wind zone of the location where a PV system is proposed to be installed (wind speed of 150 kM/ hour). The mounting structure steel shall be as per latest IS 2062: 1992 and galvanization of the mounting structure shall be in compliance of latest IS 4759. • Structural material shall be corrosion resistant and electrolytically compatible with the materials used in the module frame, The fasteners used should be made up of stainless steel. The structures shall be designed to allow easy replacement of any module. The array structure shall be so designed that it will occupy minimum space without sacrificing the output from the SPV panels. • The total load of the structure (when installed with PV modules) on the terrace should be less than 60 kg/m2 . The minimum clearance of the structure from the roof level should be 300 mm. | 500 | 500 KW | |
| 476 | 476 | Electrical/ DC Side DC Cable from String to DCDB 4 sq mm (Module to DCDB) | 4000 | Running Mtr | |
| 477 | 477 | DC Cable from String to DCDB 10 sq mm (DCDB to Inverter) | 1000 | Running Mtr | |
| 478 | 478 | DC cable termination with MC4 connector size 1cx4 sq mm | 200 | Nos. | |
| 479 | 479 | DCDB Array Junction Box (DCDB) suitable for outdoor (IP-65), Structure mounted type construction with following items: Ten numbers 16 Amp, 1000Volt DC, positive side Pull out fuse as incomers suitable for 4 Sq. mm. Cu. Flexible solar cable connection (Make :- Little Fuse / Bussman/ Reputed) Enclosure with structure/wall mounting arrangement Suitable for outdoor Application along with suitable heat dissipation facility. (Make :- JMV) | 12 | Nos. | |
| 480 | 480 | Electrical/ AC Side 30 KW SPP Nos.8 Supply & Laying of 4C x 6 sqmm Copper insulated PVC Insulated Flexible cable 1.1 KV Rated on existing cable tray (Inverter to Solar LT Panel ) | 400 | Running Mtr | |
| 481 | 481 | 50 KW SPP Nos.2 Supply & Laying of 4Cx 25 sqmm Copper insulated PVC Insulated Flexible cable 1.1 KV Rated on existing cable tray (Inverter to Solar LT Panel ) | 100 | Running Mtr | |
| 482 | 482 | 80 KW SPP Nos.2 Supply & Laying of 4Cx 35 sqmm Copper insulated PVC Insulated Flexible cable 1.1 KV Rated on existing cable tray (Inverter to Solar LT Panel ) | 100 | Running Mtr | |
| 483 | 483 | (For 30 KW SPP) 3.5C x 50 Sq mm Al. Arm. Cable on existing cable tray from Solar LT Panel to Main Solar LT Panel. | 600 | Running Mtr | |
| 484 | 484 | (For 50 KW SPP) 3.5C x 70 Sq mm Al. Arm. Cable on existing cable tray from Solar LT Panel to Main Solar LT Panel. | 150 | Running Mtr | |
| 485 | 485 | (For 80 KW SPP) 3.5C x 120 Sq mm Al. Arm. Cable on existing cable tray from Solar LT Panel to Main Solar LT Panel. | 200 | Running Mtr | |
| 486 | 486 | (For 30 KW SPP) Solar LT Panel Distribution panel with 1 Nos 4P MCB of 63 Amp, with SPD in enclosure,metalic. | 8 | Nos. | |
| 487 | 487 | (For 50 KW SPP) Solar LT Panel Distribution panel with 1 Nos 4P MCCB of 100 Amp, with SPD in enclosure,metalic. | 2 | Nos. | |
| 488 | 488 | (For 80 KW SPP) Solar LT Panel Distribution panel with 1 Nos 4P MCCB of 200 Amp, with SPD in enclosure,metalic. | 2 | Nos. | |
| 489 | 489 | Main Solar LT Panel Distribution panel with 1 Nos TPN MCCB of 260 Amp rating 16 KA 1 nos 100 A MCCB, SPD With SOLAR NET-METER in enclosure,metalic with mounting arrangement. | 1 | Nos. | |
| 490 | 490 | Earthing Chemo-m.f Earthing Electrode 3 Meter, Earthing conductors shall have a minimum size of 6.0 mm1 nos. copper, 10 mm 2 nos. Aluminium or 70 mm 2 nos.hot dip galvinezed GI STRIP 25*3 | 1000 | Running Mtr | |
| 491 | 491 | Earthing for Equipments. 10 Sqmm Single Core Copper | 200 | Running Mtr | |
| 492 | 492 | Lighting Arrestor 1 meter | 12 | Nos. | |
| 493 | 493 | Accessories ( MC4, Lugs, Cable Tie,Cable Tray, Fastners) | 1 | Job | |
| 494 | 494 | Civil Material | 500 | 500 KW | |
| 495 | 495 | System installation, Transportaion & Material Shifting | 500 | 500 KW | |
| 496 | 496 | Integrated Building Management System (IBMS) : Supply,Installation,testing and commissioning of IBMS & allied works as detailed below and as per specifications: (approved vendors:Siemens/Honeywell/Schneider) Central Works Station : Intel Pentium IV machine with 2.4 GHz speed, 1 GB RAM 160 GB HDD, Multimedia extenal modem as per specifications this should be server base suitable for data points as required | 1 | No | |
| 497 | 497 | Colour Monitor SVGA - 22 inch | 1 | No | |
| 498 | 498 | 132 column 240 CPS printer (Alarm and report) | 1 | No | |
| 499 | 499 | Mouse | 1 | No | |
| 500 | 500 | UPS with 20 minutes battery backup | 1 | No | |
| 501 | 501 | Software and System Interface Units : Supply,Installation,testing and commissioning of the following Web Based software for BAS as per specifications. Developing,testing and commissioning of the software for the building automation system along with unlimited user license. | 1 | No | |
| 502 | 502 | Providing all necessary software and hardware for the interface of the following system/equipment including providing necessary integrators/modules (RS-232/modbus Bacnet/Lonworks output to be provided by other vendors) Chilling Machines | 1 | lot | |
| 503 | 503 | DG sets | 1 | lot | |
| 504 | 504 | Fire Alarm System | 1 | lot | |
| 505 | 505 | UPS system | 1 | lot | |
| 506 | 506 | LT -ACV Breakers | 1 | lot | |
| 507 | 507 | Lifts | 1 | lot | |
| 508 | 508 | VAV Boxes | 1 | lot | |
| 509 | 509 | AHU VFDs | 1 | lot | |
| 510 | 510 | Venturi Valves | 1 | lot | |
| 511 | 511 | Supply,Installation,testing and commissioning of Web based energy auditing softwarware for data management and analysis should have pre-designed reports ,accessible from anywhere via an internet browser and able to seamlessly integrate into the building automation system | 1 | No | |
| 512 | 512 | Supply,Installation,testing and commissioning of following controllers as per the specifications: Standalone intelligent lonworks based controllers with 32 bit microprocessor, real time clock and EEPROM as per the specifications. The controller shall be housed in a vandal proof, lockable and secure MS cabinets to be supplied along with controllers. | 1 | lot | |
| 513 | 513 | Web Based system interface modules consisting of gateways, other interface units as required as per specifications. The units shall be housed in vandal proof lockable and secure wall mounted MS cabinets to be supplied along with the controllers. | 1 | lot | |
| 514 | 514 | Hand Held Portable Operator Terminals | 1 | lot | |
| 515 | 515 | Sensors and Field Devices Supply,Installation,testing and commissioning of the following sensors/transmitters/transducers/ field devices as per the specifications Immersion type temperaure sensors for measuring chilled water supply and return temperature in the Range 32F-160F | 10 | Nos | |
| 516 | 516 | Duct type temperauture sensor for measuring supply air temperature at the AHUs of the (Range 45F-150F) | 10 | Nos | |
| 517 | 517 | Out side air temperature and RH sensor for measuring the outside air temperature (35F-130F) and humidity | 1 | Nos | |
| 518 | 518 | Pressure transmitter for measuring pressure in water supply and return headers (0-10Kg/m2) | 1 | Nos | |
| 519 | 519 | Electromagnetic type flow meters for following chilled/hot water supply and return main header 600 mm dia pipe | 1 | Nos | |
| 520 | 520 | 450mm dia pipe | 1 | Nos | |
| 521 | 521 | 150mm dia pipe | 1 | Nos | |
| 522 | 522 | Differential Pressure switch across the Air Handling Units indicating the filter status (pressure differential 2mm-15mm) | 4 | Nos | |
| 523 | 523 | Differential Pressure switch across the AHU/Fan sections for indicating the fan status of pessure differential range 10mm-50mm. | 5 | Nos | |
| 524 | 524 | Level switches for indicating water levels in sumps and tanks. | 4 | Nos | |
| 525 | 525 | Differential Pressure switch for pumps status | 7 | Nos | |
| 526 | 526 | Room Temperature + RH Sensor | 1 | Nos | |
| 527 | 527 | Flame Proof Level Switches for DG Tanks | 2 | Nos | |
| 528 | 528 | Modulating typer Damper Actuators - 5 Nm | 6 | Nos | |
| 529 | 529 | CO2 Sensors | 6 | Nos | |
| 530 | 530 | Occupancy Sensor for controlling of VAV Boxes | 30 | Nos | |
| 531 | 531 | VFDs Supply,Installation,testing and commissioning of the following Variable Frequency Drives for the Air Handling Units and Cooling Towers as per specifications 15.0-20 HP motor | 3 | Nos | |
| 532 | 532 | 12.5 HP motor | 2 | Nos | |
| 533 | 533 | 10 HP motors | 5 | Nos | |
| 534 | 534 | 7.5 HP motors | 4 | Nos | |
| 535 | 535 | 5 HP motor | 1 | Nos | |
| 536 | 536 | 3 HP motor (Approved Vendors : Danfoss/ABB/Siemens) | 1 | Nos | |
| 537 | 537 | VAV Boxes SUPPLY, Installation,TESTING & COMMISSIONING OF Variable Air Volume Boxes VAVs shall be pressure independent type & low velocity type, cooling only VAV Boxes shall be slow reacting type capable of delivering variable air volume type by the action of opposed bade dampers.These shall be supplied with end flanges for attachment to flanged duct ends and shall have internal accoustic treatment shall be in double skin GSS construction and completely sealed, easily removable. The access shall be provided in the bottom side only. VAV shall be electronically controlled networkable controller type complete with low leakage damper actuator,microprocessor unit,wall/ceiling mounted temperature sensor with on/off switch control transformer unit handler bracket VAV Boxes shall also be able to reset any air flow between zero and the max. air quantity that the boxes can handle without changing orifices or other parts Each VAV Shall be supplied with one operating switch in the related rooms, which shall chnge the temperature setpoint of VAV including cost of wall switch. The quoted price shall be inclusive of the temperature sensor for each VAV unit & associated internal cable required for proper functioning of the VAV Boxes. The temperature sensor and the entire control mechanism shall be fully campatible with IBMS.Data like temperature,setpoint and damper position shall be monitored thru IBMS system. The capacities of the units as per specification are as follows 0 - 800 CFM | 30 | Nos | |
| 538 | 538 | 801 - 1350 CFM | 15 | Nos | |
| 539 | 539 | 1351 - 2100 CFM | 6 | Nos | |
| 540 | 540 | 2101 - 3200 CFM | 3 | Nos | |
| 541 | 541 | 3201 - 4000 CFM | 5 | Nos | |
| 542 | 542 | 4001 - 8000 CFM | 3 | Nos | |
| 543 | 543 | Differential Pressure Sensor (Approved Vendors: Trox/Balcolair/Titus/Belimo) | 15 | Nos. | |
| 544 | 544 | Ventury Valves Supply,Installation,testing and commissioning of venturi valves based airflow as per air flows as mentioned below.The system shall comprise of one supply and one exhaust valve operating as tracking pair.The valves shall have provision to communicate to IBMS over bacnet/lon protocol.The valve shall control the airflow within 5% of desired air flow The valve shall also monitor and control the temperature as set from the room unit.To maintain a comfortable temp in the room without compromising the air flow requirement of the room The capacities of the units shall be as follows . The room display shall provide to display the supply and exhaust air in the room and also allow the change to offset in the supply and exhaust air flow.The display shall also display the temperature in the room. 1000-1200 cfm (for isolation ward) | 5 | Pair | |
| 545 | 545 | 3000 cfm (for Opration Theatre) (Approved Vendors:Phoenix Control/Siemens/Honeywell) | 3 | Pair | |
| 546 | 546 | Cable & Conduits Supply,Installation,testing and commissioning of the following cables as per specifications : Signal cable ( 2 x 1.5 Sq. MM., stranded tinned Cu conductor, flexible, PVC sheathed type | 3500 | RM | |
| 547 | 547 | Communication cable ( 2 x 1.5 Sq. MM., stranded tinned Cu conductor, flexible, PVC sheathed, Shielded type | 3000 | RM | |
| 548 | 548 | Conduits : Supply,Installation,testing and commissioning of the following conduits for running cables as per specifications : M.S. Conduit for signal cable (25 mm) | 3500 | RM | |
| 549 | 549 | M.S. Conduit for communication cable ( 20 mm) | 2000 | RM | |
| 550 | 550 | GS Trunking Supply,Installation,testing and commissioning of 2 mm thick galvanised steel trunking of the following complete with angle iron support/hangers etc. as per the specifications. 40x300x40 mm | 200 | RM | |
| 551 | 551 | 40x300x40 mm | 100 | RM | |
| 552 | 552 | 40x150x40 mm | 100 | RM | |
| 553 | 553 | Sub-Head- I (HVAC Work) VRV/VRF System. Supply, installation, testing and commissioning of Modular type VRV/VRF outdoor unit equipped with highly efficient scroll with 100% inverter technology in each outdoor unit suitable for 415 ± 10% , 50 cycles,special heat exchanger, outdoor db (A) level less than 68 at a distance of 1 mt. The outdoor unit shall be suitable to operate in an ambient temperature range of 5 deg C to 48 Deg C and Refrigerant shall be R-410a . The Unit shall have free phase technology to avoid phase reversal and shall have capability to charge refrigerant automatically with refrigerant cooled PCB. The unit shall consist of indoor units & external condensing units,complete in all respects, exclusive of insulated copper refrigerant piping, drain piping of required size, electrical & microprocessor panel, wiring, control cabling and earthing, isolating valves, stands and supports with all other necessary accessories for proper functioning of the units. Make- Daikin, Mitsubishi Electric, O' General. Outdoor Units 10 HP 12 HP | 10 | Nos. | |
| 554 | 554 | 14 HP | 10 | Nos. | |
| 555 | 555 | 16 HP | 11 | Nos. | |
| 556 | 556 | 18HP | 34 | Nos. | |
| 557 | 557 | 20 HP | 27 | Nos. | |
| 558 | 558 | 54 HP | 20 | Nos. | |
| 559 | 559 | Unloading, Lifting, Shifting, Positioning of outdoor unit of different capacity complete in all respect. | 112 | Nos. | |
| 560 | 560 | Indoor Units (Nominal Capacity) Supply, installation, testing and commissioning of Indoor units equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section with DX coil, outer cabinet, drain pan, insulation, pipe connections etc. of various capacities. Make- Daikin, Mitshubishi Electric, O' General. Ceiling Mounted Cassette(Round Flow) Type Units 1.056TR3 | 14 | Nos. | |
| 561 | 561 | 1.32 TR | 24 | Nos. | |
| 562 | 562 | 1.65TR | 48 | Nos. | |
| 563 | 563 | 2.0TR | 38 | Nos. | |
| 564 | 564 | 2.64TR | 62 | Nos. | |
| 565 | 565 | 3.3TR | 122 | Nos. | |
| 566 | 566 | 4.125TR | 46 | Nos. | |
| 567 | 567 | SITC of split A.C.1.5 Ton capacity 3 Star inverter type Mitsubishi (Electric/heavy)Daikin/ O' General make complete with outdoor stand, approx. 10 mtr refrigerant piping, suitable voltage Stabilizer included in above cost complete in all respect. | 60 | Nos. | |
| 568 | 568 | Supply, installation, testing and commissioning of Corded / Cordless Remotes. Make- Daikin, Mitshubishi Electric, O' General. | 394 | Nos. | |
| 569 | 569 | Supply and fixing of Y-Joint. Make- Daikin, Mitshubishi Electric, O' General. | 392 | Nos. | |
| 570 | 570 | Refrigerant Piping Supplying & Installation of interconnecting following sizes of one end expanded refrigerant copper pipe work with Y-joints and Headers of following outer diameter, insulated with closed cell electrometric nitrile rubber tubular insulation between each set of indoor & outdoor units, all piping inside the room shall be propelrly fixed/supported with suitable size of clamp/ M.S. hanger and all external piping shall run in M.S. painted cable tray (mentioned as separate item) etc. as reqd. (The final refrigerant pipe sizes shall be as per manufacturer). Make Copper Pipe- Rajco, Maxflow, Totaline, Mandev, Insulation Make- A-Flex, K-Flex, Superlon. 41.3 mm dia with 25mm thick insulation | 2120 | Rmt. | |
| 571 | 571 | 38.6 mm dia with 25mm thick insulation | 1260 | Rmt. | |
| 572 | 572 | 34.9 mm dia with 19mm thick insulation | 840 | Rmt. | |
| 573 | 573 | 28.6 mm dia with 19mm thick insulation | 3280 | Rmt. | |
| 574 | 574 | 22.2 mm dia with 19mm thick insulation | 2870 | Rmt. | |
| 575 | 575 | 19.1 mm dia with 13mm thick insulation | 4510 | Rmt. | |
| 576 | 576 | 15.9 mm dia with 13mm thick insulation | 30300 | Rmt. | |
| 577 | 577 | 12.7 mm dia with 13mm thick insulation | 3090 | Rmt. | |
| 578 | 578 | 9.5 mm dia with 13mm thick insulation | 10550 | Rmt. | |
| 579 | 579 | 6.4 mm dia with 13mm thick insulation | 3090 | Rmt. | |
| 580 | 580 | SITC of inline cabinet/circular fan with 15 mm static for LABS and toilets complete with inlet outlet duct connections , starter panel , all accessories and supports as per drawings and specification . Make - kruger, nicotra, wolter , greenheck 2500 cfm | 54 | Nos | |
| 581 | 581 | 1700 cfm | 52 | Nos | |
| 582 | 582 | 1000 cfm | 78 | Nos | |
| 583 | 583 | 800 cfm | 106 | Nos | |
| 584 | 584 | 100 cfm | 328 | Nos | |
| 585 | 585 | 200 cfm | 284 | Nos | |
| 586 | 586 | SITC of site fabricated GI duct as per IS standard complete with specification and accessories . | 10350 | Sqm | |
| 587 | 587 | Cable Tray Providing, fabricating and installation following size of perforated M.S. Painted cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders including painting, etc., as required. Make- Super Steel, Indeana, Fittwell Insustry, MEM. 150mm x 50mm x 1.6mm thickness | 10560 | Rmt. | |
| 588 | 588 | Drain Piping Providing and fixing of PVC Piping complete with fittings, supports as per specifications and duly insulated with 6mm thick closed cell nitrile rubber insulation. Make- Kisan, Prakash, Supreme, Prince. 25 mm dia | 24240 | Rmt. | |
| 589 | 589 | 40mm dia | 12120 | Rmt. | |
| 590 | 590 | Sub Head - II (ELECTRICAL WORK) Supply, Installation, testing & commissioning of 12 way TPN distribution board with double metal door including 1no. 40Amp. FP MCB as incomer and 12 Nos. 6Amp. 10KV C curve SP MCB as outgoing for Cassette type indoor units complete in all respect and as per requirement. Make- Schneider, Legrand, L&T, Anchor. | 88 | Nos. | |
| 591 | 591 | Supply, laying, testing and commissioning of Power cabling XLPE insulated, armoured, Copper conductor of 1.1 KV grade complete in all respect. Make: KEI / Havells / Rallison / Polycab / Gloster 4C x 10 sq.mm | 17710 | Rmt. | |
| 592 | 592 | 4C x 6 sq.mm | 3410 | Rmt. | |
| 593 | 593 | 3C x 2.5 sq.mm | 23760 | Rmt. | |
| 594 | 594 | Supply, laying, testing and commissioning of Communication cabling , unarmoured, Copper conductor with PVC conduit complete in all respect. Make: KEI / Havells / Rallison / Polycab / Gloster 2C x 1.5 sq.mm | 35200 | Rmt. | |
| 595 | 595 | Providing and fixing 8 SWG GI for earthing complete in all respect. | 2200 | Rmt. | |
| 596 | 596 | RCC/PCC work for Foundation or MS Stand for Outdoor units. All complite as per. | 242 | Rmt. | |
| 597 | 597 | OUTDOOR TYPE HVAC PANEL FOR VRV OUTDOOR SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be outdoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Main LT Panel shall use all draw out type breakers at incommer suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. short circuit, instantaneous & earthfault protection with Current & Voltage metering. INCOMING 1 Nos. 1000 Amp FP EDO ACB 50KA BUSBARS 1 Nos. 1250 Amp FP busbars of aluminium alloy as per SLD. OUTGOING 25 Nos. 50 Amp FP MCB + ELCB INSTRUMENTS 1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).1 Sets breaker 'ON' & 'OFF' & TRIP indicating lamp (one set for each incoming breaker). 2 Sets auto trip indicating lamp . Note: All outgoings should have RYB indications with backup MCB as indicated in single line diagrams. Short Circuit Breaking capacity should not less than 36KA. RELAYS AS PER SLD | 26 | Set | |
| 598 | 598 | Supply installation testing and commissioning of 50Amp FP isolator in weather proof 4Module enclosure alangwith all accessories for mounting isolator box near outdoor unit etc as required. | 242 | Set | |
| 599 | 599 | SECTION - I- LOCAL AREA NETWORK ( LAN ) STRUCTURED CABLING SYSTEM PASSIVESupply , Installtion , Testing and Comissioning of armoured 6 core Singlemode OFC cable for interfloor switches connectivity. Approved Make List :- Belden/Siemon/Panduit/Der Wiser | 3200 | Mtr | |
| 600 | 600 | Supply , Installtion , Testing and Comissioning of 6 port loaded LIU with LC adaptor plates , pigtel cables etc complete as required. Approved Make List :- Belden/Siemon/Panduit/Der Wiser | 32 | Nos. | |
| 601 | 601 | Supply , Installtion , Testing and Comissioning of 24 port loaded LIU for with LC adaptor plates , pigtel cables for core switch to access switch connectivity over fiber. Approved Make List :- Belden/Siemon/Panduit/Der Wiser | 8 | Nos. | |
| 602 | 602 | Supply , Installtion , Testing and Comissioning of LC-LC singlemode fiber patch cord for LIU to switch connectivity. Approved Make List :- Belden/Siemon/Panduit/Der Wiser | 98 | Nos. | |
| 603 | 603 | Supply , Installation , Testing and Commissioning of CAT 6 UTP cable 23 AWG solid copper conductors for Connectivity of Hub room to End Point. Approved Makes: Belden/Siemon/Panduit/Der Wiser | 124980 | Mtr | |
| 604 | 604 | Supply , Installation , Testing and Commissioning of CAT6 information outlet (I/O) for Data, Voice, Camera & Wi-Fi at user end. Approved Makes: Belden/Siemon/Panduit/Der Wiser | 2083 | Nos. | |
| 605 | 605 | Supply , Installation , Testing and Commissioning of loaded 24 port CAT6 jack panel for CAT6 cable termination at rack end. Approved Makes: Belden/Siemon/Panduit/Der Wiser | 94 | Nos. | |
| 606 | 606 | Supply , Installation , Testing and Commissioning of CAT6 patch cord 3 feet for rack side switch to jack panel connectivity. Approved Makes: Belden/Siemon/Panduit/Der Wiser | 2083 | Nos. | |
| 607 | 607 | Supply , Installation , Testing and Commissioning of CAT6 patch cord 7 feet for information outlet (I/O) to end user device connectivity. Approved Makes: Belden/Siemon/Panduit/Der Wiser | 2083 | Nos. | |
| 608 | 608 | Supply , Installation , Testing and Commissioning of 1, 2 and 4 port face plate white for I/O fixing at user side. Approved Makes: Belden/Siemon/Panduit/Der Wiser | 2083 | Nos. | |
| 609 | 609 | Supply , Installation , Testing and Commissioning of 42 U (600W/1000D) floor mount rack with fans , 2 cable managers , satationary shelf , 2 Nos. of hardware pkts. Approved Makes: Poweride/MTS/Rittal/APC/APW | 4 | Nos. | |
| 610 | 610 | Supply , Installtion , Testing and Comissioning of 15U wall mount rack with fans , 2 cable managers , satationary shelf , 2 Nos. of hardware pkts. Approved Makes: Poweride/MTS/Rittal/APC/APW | 30 | Nos. | |
| 611 | 611 | LAN Supply , Installation , Testing and Commissioning of Core Switch should have Min 24 x 10 G Based SFP+ port , Min 1 x QSFP+ port , 2x Stacking port comprising 400 Gbps of stacking bandwidth from day 1 ,Min 2xQSFP28 Port from day1, Support less than 50 Millisecond convergence based of RFC 3619/REP/G.8032 , Min Operating temp 0-50 Degree C ,Must have Common criteriacertification EAL3/NDcPP/NDPP,CE.2 and CB certified.RPS Support . Min 850Gbps switching backplane ,Min 4GB RAM, 32GB Memory, Min 270K Mac address.Auto adustable fan based on temperture variation. Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista | 1 | Nos. | |
| 612 | 612 | Supply , Installation , Testing and Commissioning of Access switch should have 48 x10/100/1000T port , Min 8 x1 G SFP port , should be upgradable to Min 4x 10 G based SFP+ port , 2x Stacking port comprising 40 Gbps of stacking bandwidth from day 1 , Min 2 x 10G Copper port support ,Support less than 50 Millisecond convergence based of RFC 3619/REP/G.8032 , Min Operating temp 0-50 Degree C ,Must have Common criteriacertification EAL3/NDcPP/NDPP, should support AVB,CE.2 and CB certified.Min 740 PoE/PoE+ buwer budget based on IEEE 802.3af/IEEE 802.3at, Min 1GB RAM & 4GB Flash.Auto adustable fan based on temperture variation. Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista | 44 | Nos. | |
| 613 | 613 | Supply , Installation , Testing and Commissioning of Access switch should have 24 x10/100/1000T port , Min 8 x1 G SFP port , should be upgradable to Min 4x 10 G based SFP+ port , 2x Stacking port comprising 40 Gbps of stacking bandwidth from day 1 ,Support less than 50 Millisecond convergence based of RFC 3619/REP/G.8032 , Min Operating temp 0-50 Degree C ,Must have Common criteriacertification EAL3/NDcPP/NDPP, should support AVB,CE.2 and CB certified.Min 370 Watt PoE/PoE+ power budget based on IEEE 802.3af/IEEE 802.3at,RPS Support, Min 1GB RAM & 4GB Flash.Auto adustable fan based on temperture variation. Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista | 5 | Nos. | |
| 614 | 614 | Supply , Installation , Testing and Commissioning of fiber Modules 1G BASE Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista | 92 | Nos. | |
| 615 | 615 | Supply , Installation , Testing and Commissioning of Stacking Cable Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista | 46 | Nos. | |
| 616 | 616 | Supply, Installation, Testing & Commissioning of Appliance based customised ITAM for asset inventory management with ability to map physical locations and exact rack elevations for audit and support control. Appliance shall be Intel x86 based device with secure intranet server with Linux Based operating system and relational databases for long term storage. Appliance includes license for 500 units under control. Aprroved Makes: Nexxus/ Siemens/Torque | 1 | Nos. | |
| 617 | 617 | SUB HEAD :- SMOKE EXTRACTION WORKS Item Description SUB-HEAD 'A' - MECHANICAL VENTILATION Supply Axial Flow Fan unit Supply, installation, testing and commissioning of AMCA Certified Ceiling hang axial flow type supply air fan for basement ventilation of following capacity with ms powder coated GSS/M.S. casing and aluminium alloy impellers with sections, blades, the impeller directly driven by TEFC induction motor (efficiency 2) and ’F’ class insulation suitable for 3 Phase, 50 Hz, 415±10% Volt, ac supply, Suitable capacity of TP isolator with M.S enclosure box complete as required and as per specifications. Fans should be statically & dynamically balanced.The fan static pressure shall be 25mm WC . Make- Kruger/ Green Heck/Flaktwood 15000 CFM (MR) | 4 | Nos. | |
| 618 | 618 | 25000 CFM (MR) | 6 | Nos. | |
| 619 | 619 | Exhaust Axial Flow Fan unit Supply, installation, testing and commissioning of AMCA certified Ceiling hang axial flow type exhaust air fan for basement ventilation of following capacity with powder coated GSS/M.S. casing and aluminium alloy impellers with high efficiency sections, blades, the impeller directly driven by TEFC induction motor (efficiency 1) and ’H’ class insulation suitable for 3 Phase, 50 Hz, 415±10% Volt, ac supply, suitable capacity of TP isolator with M.S enclosure box complete as required and as per specifications. Fans should be statically & dynamically balanced .The fan static pressure shall be 25 mm WC. Fan and Motor for Fire exhaust fans shall be suitable for operation at minimum 250 deg C for 2 hrs. (MR) 20000 CFM (MR) | 12 | Nos. | |
| 620 | 620 | 30000 CFM (MR) | 6 | Nos. | |
| 621 | 621 | SUB-HEAD 'B' - AIR DISTRIBUTION WORK Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. i)Thickness 0.63 mm sheet | 2000 | SQM. | |
| 622 | 622 | Thickness 0.80 mm sheet | 4500 | SQM. | |
| 623 | 623 | Thickness 1.00 mm sheet | 2500 | SQM. | |
| 624 | 624 | Thickness 1.25 mm sheet | 1000 | SQM. | |
| 625 | 625 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. i)Thickness 0.63 mm sheet | 600 | SQM. | |
| 626 | 626 | Thickness 0.80 mm sheet | 200 | SQM. | |
| 627 | 627 | Thickness 1.00 mm sheet | 650 | SQM. | |
| 628 | 628 | Thickness 1.25 mm sheet | 200 | SQM. | |
| 629 | 629 | Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets,nuts, bolts, screws linkages, flanges etc, as per specifications | 40 | SQM. | |
| 630 | 630 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. | 210 | SQM. | |
| 631 | 631 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. | 150 | SQM. | |
| 632 | 632 | Supply, installation, testing and commissioning of fresh air/ exhaust air Louver comprising of powder coated GI louvers with bird screen as required. | 95 | SQM | |
| 633 | 633 | Supply, installation & testing of GI back draft dampers (16 G Blade & Frame) similar constrction to gravity louvers (for Basement fans- fire case as specified in the drawing.) , provided with suitable links to prevent the back pressure of air. | 80 | SQM | |
| 634 | 634 | SITC of Fully automatic STAR DELTA starter suitable for operating 15 kw motors/fan capacity, complete with contactors,Timer, overload protection relay, current sensing type single phase preventer, ON indications, push buttons, auto / manual / off selector switch,other accessories. complete as required. | 6 | Set | |
| 635 | 635 | SITC of Fully automatic STAR DELTA starter suitable for operating 11 kw motors/fan capacity, complete with contactors,Timer, overload protection relay, current sensing type single phase preventer, ON indications, push buttons, auto / manual / off selector switch,other accessories. complete as required. | 6 | Set | |
| 636 | 636 | SITC of Fully automatic DOL starter suitable for operating 7.5 kw motors/fan capacity, complete with contactors,Timer, overload protection relay, current sensing type single phase preventer, ON indications, push buttons, auto / manual / off selector switch,other accessories. complete as required. | 16 | Set | |
| 637 | 637 | Supply, laying testing and commissioning of following sizes of XLPE insulated PVC sheathed armoured aluminium conductor cable of 1.1 KV grade on existing cable tray / surface include ing clamps, ties etc. as required. 3 core x 16 sqmm. | 350 | Metre | |
| 638 | 638 | 3 core x 10 sqmm. | 400 | Metre | |
| 639 | 639 | 3 core x 6 sqmm. | 950 | Metre | |
| 640 | 640 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. (DSR 5.16) 6 SWG G.I. wire | 1500 | Metre | |
| 641 | 641 | CABLE TRAYS Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 100 mm. Width x 50mm. Depth x 1.6mm. Thickness. | 850 | Metre | |
| 642 | 642 | 150 mm. Width x 50mm. Depth x 1.6mm. Thickness. | 200 | Metre | |
| 643 | 643 | 300 mm. Width x 50mm. Depth x 1.6mm. Thickness. | 200 | Metre | |
| 644 | 644 | NURSE CALLING SYSTEM Supply, Installation, Testing and Commissioning of Nurse Calling Station as per following decription- PUSH kit 540 No. Wall mounting frame, 13mm (wall mounting) - 540 No. PUSH+PULL kit, 866 Standard - 88 No. Wall mounting frame, 13mm (wall mounting) - 88 No. REPO+ kit, 866 Standard - 94 No. TREX 2G kit, 866 Standard - 60 No. Charging unit - 60 No.SITC Front end wireless based and back end CAT 6 wire based with OTA real time software system with all above physical units nurses call bell system | 250 | Per Bed | |
| 645 | 645 | 12 HP | 10 | Nos. | |
| 646 | 646 | 14 HP | 10 | Nos. | |
| 647 | 647 | 16 HP | 11 | Nos. | |
| 648 | 648 | 18HP | 34 | Nos. | |
| 649 | 649 | 20 HP | 27 | Nos. | |
| 650 | 650 | 54 HP | 20 | Nos. | |
| 651 | 651 | Unloading, Lifting, Shifting, Positioning of outdoor unit of different capacity complete in all respect. | 112 | Nos. | |
| 652 | 652 | Indoor Units (Nominal Capacity) Supply, installation, testing and commissioning of Indoor units equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section with DX coil, outer cabinet, drain pan, insulation, pipe connections etc. of various capacities. Make- Daikin, Mitshubishi Electric, O' General. Ceiling Mounted Cassette(Round Flow) Type Units 1.056TR | 14 | Nos. | |
| 653 | 653 | 1.32 TR | 24 | Nos. | |
| 654 | 654 | 1.65TR | 48 | Nos. | |
| 655 | 655 | 2.0TR | 38 | Nos. | |
| 656 | 656 | 2.64TR | 62 | Nos. | |
| 657 | 657 | 3.3TR | 122 | Nos. | |
| 658 | 658 | 4.125TR | 46 | Nos. | |
| 659 | 659 | SITC of split A.C.1.5 Ton capacity 3 Star inverter type Mitsubishi (Electric/heavy)Daikin/ O' General make complete with outdoor stand, approx. 10 mtr refrigerant piping, suitable voltage Stabilizer included in above cost complete in all respect. | 60 | Nos. | |
| 660 | 660 | Supply, installation, testing and commissioning of Corded / Cordless Remotes. Make- Daikin, Mitshubishi Electric, O' General. | 394 | Nos. | |
| 661 | 661 | Supply and fixing of Y-Joint. Make- Daikin, Mitshubishi Electric, O' General. | 392 | Nos. | |
| 662 | 662 | Refrigerant Piping Supplying & Installation of interconnecting following sizes of one end expanded refrigerant copper pipe work with Y-joints and Headers of following outer diameter, insulated with closed cell electrometric nitrile rubber tubular insulation between each set of indoor & outdoor units, all piping inside the room shall be propelrly fixed/supported with suitable size of clamp/ M.S. hanger and all external piping shall run in M.S. painted cable tray (mentioned as separate item) etc. as reqd. (The final refrigerant pipe sizes shall be as per manufacturer). Make Copper Pipe- Rajco, Maxflow, Totaline, Mandev, Insulation Make- A-Flex, K-Flex, Superlon.41.3 mm dia with 25mm thick insulation | 2120 | Rmt. | |
| 663 | 663 | 38.6 mm dia with 25mm thick insulation | 1260 | Rmt. | |
| 664 | 664 | 34.9 mm dia with 19mm thick insulation | 840 | Rmt. | |
| 665 | 665 | 28.6 mm dia with 19mm thick insulation | 3280 | Rmt. | |
| 666 | 666 | 22.2 mm dia with 19mm thick insulation | 2870 | Rmt. | |
| 667 | 667 | 19.1 mm dia with 13mm thick insulation | 4510 | Rmt. | |
| 668 | 668 | 15.9 mm dia with 13mm thick insulation | 30300 | Rmt. | |
| 669 | 669 | 12.7 mm dia with 13mm thick insulation | 3090 | Rmt. | |
| 670 | 670 | 9.5 mm dia with 13mm thick insulation | 10550 | Rmt. | |
| 671 | 671 | 6.4 mm dia with 13mm thick insulation | 3090 | Rmt. | |
| 672 | 672 | SITC of inline cabinet/circular fan with 15 mm static for LABS and toilets complete with inlet outlet duct connections , starter panel , all accessories and supports as per drawings and specification . Make - kruger, nicotra, wolter , greenheck 2500 cfm | 54 | Nos | |
| 673 | 673 | 1700 cfm | 52 | Nos | |
| 674 | 674 | 1000 cfm | 78 | Nos | |
| 675 | 675 | 800 cfm | 106 | Nos | |
| 676 | 676 | 100 cfm | 328 | Nos | |
| 677 | 677 | 200 cfm | 284 | Nos | |
| 678 | 678 | SITC of site fabricated GI duct as per IS standard complete with specification and accessories . | 10350 | Sqmtr | |
| 679 | 679 | Cable Tray Providing, fabricating and installation following size of perforated M.S. Painted cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders including painting, etc., as required. Make- Super Steel, Indeana, Fittwell Insustry, MEM. 150mm x 50mm x 1.6mm thickness | 10560 | Rmt. | |
| 680 | 680 | Drain Piping Providing and fixing of PVC Piping complete with fittings, supports as per specifications and duly insulated with 6mm thick closed cell nitrile rubber insulation. Make- Kisan, Prakash, Supreme, Prince. 25 mm dia | 24240 | Rmt. | |
| 681 | 681 | 40mm dia | 12120 | Rmt. | |
| 682 | 682 | Sub Head - II (ELECTRICAL WORK) Supply, Installation, testing & commissioning of 12 way TPN distribution board with double metal door including 1no. 40Amp. FP MCB as incomer and 12 Nos. 6Amp. 10KV C curve SP MCB as outgoing for Cassette type indoor units complete in all respect and as per requirement. Make- Schneider, Legrand, L&T, Anchor. | 88 | Nos | |
| 683 | 683 | Supply, laying, testing and commissioning of Power cabling XLPE insulated, armoured, Copper conductor of 1.1 KV grade complete in all respect. Make: KEI / Havells / Rallison / Polycab / Gloster 4C x 10 sq.mm | 17710 | Rmt. | |
| 684 | 684 | 4C x 6 sq.mm | 3410 | Rmt. | |
| 685 | 685 | 3C x 2.5 sq.mm | 23760 | Rmt. | |
| 686 | 686 | Supply, laying, testing and commissioning of Communication cabling , unarmoured, Copper conductor with PVC conduit complete in all respect. Make: KEI / Havells / Rallison / Polycab / Gloster 2C x 1.5 sq.mm | 35200 | Rmt. | |
| 687 | 687 | Providing and fixing 8 SWG GI for earthing complete in all respect. | 2200 | Rmt. | |
| 688 | 688 | RCC/PCC work for Foundation or MS Stand for Outdoor units. All complite as per. | 242 | Nos | |
| 689 | 689 | OUTDOOR TYPE HVAC PANEL FOR VRV OUTDOOR SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be outdoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Main LT Panel shall use all draw out type breakers at incommer suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. short circuit, instantaneous & earthfault protection with Current & Voltage metering. INCOMING 1 Nos. 1000 Amp FP EDO ACB 50KA BUSBARS 1 Nos. 1250 Amp FP busbars of aluminium alloy as per SLD. OUTGOING 25 Nos. 50 Amp FP MCB + ELCB INSTRUMENTS 1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port. 1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker). 1 Sets breaker 'ON' & 'OFF' & TRIP indicating lamp (one set for each incoming breaker). 2 Sets auto trip indicating lamp . Note: All outgoings should have RYB indications with backup MCB as indicated in single line diagrams. Short Circuit Breaking capacity should not less than 36KA. RELAYS AS PER SLD | 26 | Set | |
| 690 | 690 | Supply installation testing and commissioning of 50Amp FP isolator in weather proof 4Module enclosure alangwith all accessories for mounting isolator box near outdoor unit etc as required. SUB-HEAD -VI- FIRE DETECTION SYSTEM | 242 | Set | |
| 691 | 691 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 6839 | Nos | |
| 692 | 692 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. | 46 | Nos. | |
| 693 | 693 | Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required | 13 | Nos. | |
| 694 | 694 | Supplying, installation, testing & commissioning of addressable beam detector with short circuit isolator (inbuilt or seperate) complete with emitter and receiver including connections with remote test features etc complete as required. | 4 | Nos. | |
| 695 | 695 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required | 3074 | Nos. | |
| 696 | 696 | MANUAL CALL POINT Supplying, installation, testing & commissioning of addressable manual call point complete as required Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 217 | Nos. | |
| 697 | 697 | FAULT ISOLATOR Supplying, installation, testing & commissioning of fault isolator complete with base as required | 358 | Nos. | |
| 698 | 698 | MONITOR MODULES Supply , Installation , Testing and Commissioning of Addressable Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall provide DPDTcontact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 18 | Nos. | |
| 699 | 699 | CONTROL MODULES Supplying, installation, testing & commissioning of addressable fire control module complete as required Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 139 | Nos. | |
| 700 | 700 | Supplying, installation, testing & commissioning of addressable phone control module complete as required | 186 | Nos. | |
| 701 | 701 | Hooter cum strobe Supplying, installation, testing & commissioning of addressable strobe complete as required | 217 | Nos. | |
| 702 | 702 | FIRE ALARM CONTROL PANEL Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications Ten Loop Panel | 4 | Nos. | |
| 703 | 703 | Two Loop Panel | 11 | Nos. | |
| 704 | 704 | Supply , Installation , Testing and Commissioning of Addressable Fire Fighter's Telephone Jack with suitable module for two way communication between Remote Fire Fighter & Fire Command Center Approved Makes :Ansul / Edwards / Notifier / Wissenschaftler / Rux | 186 | Nos. | |
| 705 | 705 | Supply , Installation , Testing and Commissioning of Fire Fighter's Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center. Approved Makes : Ansul / Edwards / Notifier / Wissenschaftler / Rux | 24 | Nos. | |
| 706 | 706 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required Approved makes : Polycab/ RR Kabel/ Paramount/ Parasheild | 60250 | RM | |
| 707 | 707 | SUB-HEAD -VII- PA SYSTEM SPEAKERS Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required Approved Makes : Bosch / Honeywell /System Sensor/ Ateis Ceiling Mounted Speakers | 1963 | Nos. | |
| 708 | 708 | Wall Mounted Speakers | 5 | Nos. | |
| 709 | 709 | PA CONTROLLER Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required | 10 | Nos. | |
| 710 | 710 | DIGITAL AMPLIFIERS Supply, installing, testing and commissioning of 1X500W Class-D Amplifier with 2 independent channels and can provide automatic re-settable overcurrent, overload, overheating, overvoltage, under-voltage and DC protection Approved Makes : Bosch Praesedio / Honeywell - X618/ Ateis 500 Watts | 27 | Nos. | |
| 711 | 711 | PAGING STATION Supply, installing, testing and commissioning of IP based Networkable touch screen paging station for selection of zones, supervision of system status, setting of scheduled broadcasts with the following functions: . Built-in monitoring loudspeaker . Detachable goose-neck microphone . LCD touchscreen display . Audio input Approved Makes : Bosch Praesedio / Honeywell - X618/ Ateis | 4 | Nos. | |
| 712 | 712 | Supplying and Laying of 2 core twin twisted 48/0.2 ATC, Multi strand, over all armoured speaker cable as specified in the Tender Specifications Approved makes : Polycab / Incoll /Skyton / Falcon / RR Kabel | 20850 | RM | |
| 713 | 713 | HOSPITAL BUILDING Design, manufacture, supply, installation, testing and commissioning of 20 passenger/ 1360 kgs hospital Elevators with machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 25 Mtrs with following stops As per PDF DNIT Specification | 12 | EACH | |
| 714 | 714 | Design, manufacture, supply, installation, testing and commissioning of 20 passenger/ 1360 kgs hospital Elevators with machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 20 Mtrs with following stops as per PDF format of DNIT | 6 | EACH | |
| 715 | 715 | ACADEMIC BLOCK Design, manufacture, supply, installation, testing and commissioning of 15 passenger/ 1020 kgs Elevators without machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 28 Mtrs with following stops as PER PDF DNIT format of Specification | 4 | EACH | |
| 716 | 716 | Boys Hostel Design, manufacture, supply, installation, testing and commissioning of 08 passenger/ 884 kgs Elevators without machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 32 Mtrs with following stops Ground, 1 to 9 floors All specification as per PDF format of DNIT | 3 | EACH | |
| 717 | 717 | Girls Hostel Design, manufacture, supply, installation, testing and commissioning of 08 passenger/ 884 kgs Elevators without machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 28 Mtrs with following stops Ground, 1 to 8 floors All specification as per PDF format of DNIT | 3 | EACH | |
| 718 | 718 | Junior Resident Design, manufacture, supply, installation, testing and commissioning of 06 passenger/ 408 kgs Elevators without machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 16 Mtrs with following stops All specification as per PDF format of DNIT | 2 | EACH | |
| 719 | 719 | Sr. Resident Design, manufacture, supply, installation, testing and commissioning of 06 passenger/ 408 kgs Elevators without machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 32 Mtrs with following stops All specification as per PDF format of DNIT | 2 | Each | |
| 720 | 720 | Nurse Hostel Design, manufacture, supply, installation, testing and commissioning of 06 passenger/ 408 kgs Elevators without machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 12 Mtrs with following stops All specification as per PDF format of DNIT | 2 | EACH | |
| 721 | 721 | Type 2 Design, manufacture, supply, installation, testing and commissioning of 08 passenger/ 544 kgs Elevators without machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 16 Mtrs with following stops All specification as per PDF format of DNIT | 2 | EACH | |
| 722 | 722 | Type 3 & 4 Design, manufacture, supply, installation, testing and commissioning of 08 passenger/ 544 kgs Elevators without machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 12 Mtrs with following stops All specification as per PDF format of DNIT | 4 | EACH | |
| 723 | 723 | Type 5 Design, manufacture, supply, installation, testing and commissioning of 06 passenger/ 408 kgs Elevators without machine room and handing over the same to the owner in satisfactory working condition with A.C. variable voltage and variable frequency control, directional control of cars, scratch free stainless steel enclosure, automatic central opening car doors, landing doors and flooring with smooth anti skid surface, strong enough to take the rated load without any deformation or damage, The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition. The offer shall also include Automatic rescue device with dry maintenance free batteries, for automatic anchoring of the lift at nearest floor in case of power failure, intercom facility and full height sensor, potential free contacts in controller as per specifications. Passenger lift as above with one side travel of 12 Mtrs with following stops All specification as per PDF format of DNIT | 2 | EACH | |
| 724 | 724 | Escalator Design, manufacture, supply, installation, testing and commissioning of indoor type escalator EN-115 with 4.2 mtrs rise, 35 degrees, 02 flat step, 1000mm step width , speed 0.5mps, outercladding in manufactures scope. The cost shall include 12 months free comprehensive maintenance for defect liability period after completion of work and handing over of the lift to owner in satisfactory working condition All specification as per PDF format of DNIT | 6 | EACH | |
| 725 | 725 | FIRE FIGHTING Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainlesssteel shaft, mechanical seal conforming to IS 1520. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S.fabricated Common base plate, coupling, coupling guard,foundation bolts etc.as required. Suitable cement concrete foundation duly plastered with anti vibration pads. 2850 lpm at 88 m Head | 2 | set | |
| 726 | 726 | 1620 lpm at 88 m Head | 1 | set | |
| 727 | 727 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following,complete in all respects, as required : (Diesel Driven Pump). Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 2850 lpm at 88 m Head | 1 | set | |
| 728 | 728 | 1620 lpm at 88 m Head | 1 | set | |
| 729 | 729 | Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 180 lpm at 88 m Head | 3 | set | |
| 730 | 730 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required : INCOMING All other specification mention in PDF file of DNIT 5.1 and 5.2 | 1 | Set | |
| 731 | 731 | Incomings 400A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500Amps Outgoings ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pumps 125 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets Jockey Pump 63 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets Diesel Engine Control Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification | 1 | set | |
| 732 | 732 | Incomings 630A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-630 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 800Amps Outgoings (Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pump 200 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets Jockey Pump 100 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets Diesel Engine Control Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification Incomings 800A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-800 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 1000Amps Outgoings ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pump 250 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 100 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets | 1 | Set | |
| 733 | 733 | PIPES & ACCESSORIES Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 150 mm. Dia | 6050 | m | |
| 734 | 734 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 450 lpm at 35 m Head | 4 | set | |
| 735 | 735 | 900 lpm at 35 m Head | 7 | set | |
| 736 | 736 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Gunmetal | 118 | set | |
| 737 | 737 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. | 118 | each | |
| 738 | 738 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 100mm dia | 2 | set | |
| 739 | 739 | 150mm dia | 2 | set | |
| 740 | 740 | 250mm dia | 2 | set | |
| 741 | 741 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 250mm dia | 2 | Each | |
| 742 | 742 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. | 8 | Each | |
| 743 | 743 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 150 mm dia | 2 | Each | |
| 744 | 744 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : 150mm dia | 2 | set | |
| 745 | 745 | Providing and fixining gun matel ball valve | 10 | each | |
| 746 | 746 | Providing and fixining pressure gauge | 10 | each | |
| 747 | 747 | Providing and fixing in position the industrial type pressure switch | 10 | each | |
| 748 | 748 | Fire Extinguisher Providing and fixing 6 Kg clean agent or ABC extinguisher with IS: 2171. (ISI marked) | 600 | Each | |
| 749 | 749 | Providing and fixing 4.5 Kg clean agent or CO2 extinguisher with IS: 2171. (ISI marked) | 600 | Each |