BRR : 10838406
Click Here To View Tendering Authority. Price Bid City/State :  Hapur, Uttar Pradesh
Tender Brief : Tender for Providing, Installation And Commissning Of Digital Relay (Make C&S, Ashide And Abb) In Place Of Numerical/Mechanical/Damaged (Burnt) Relay Of 11 Kv Feeders At 33/11 Kv Sub-Stations Of Edd Hapur, In The Jurisdiction Of Etl-Hapur Of Etd-Hapur, Under Edc-Hapur. , Providing, Installation And Commissning Of Digital Relay (Make C&S, Ashide And Abb) In Place Of Numerical/Mechanical/Damaged (Burnt) Relay Of 11 Kv Feeders At 33/11 Kv Sub-Stations Of Edd Hapur, In The Jurisdiction Of Etl-Hapur Of Etd-Hapur, Numerical (3O/C+Ie/F) Should Have Following Technical Specification : (I) Current Rat... Read More
Tender Value
6,30,000
Submission Date
27-03-2026
Participated Bidder List
6 No of Bidder(s)
Sr No. Bidder Name Bid Analytics Technical Bid Financial Bid AOC Bid Value Rank
1 cnet-technologies Bid Analytics 6,87,500 L4
2 cnet-technologies Bid Analytics 6,50,000 L3
3 cnet-technologies Bid Analytics
4 cnet-technologies Bid Analytics 6,00,000 L2
5 cnet-technologies Bid Analytics 5,51,250 L1
6 cnet-technologies Bid Analytics
Work Detail
tender for providing, installation and commissning of digital relay (make c&s, ashide and abb) in place of numerical/mechanical/damaged (burnt) relay of 11 kv feeders at 33/11 kv sub-stations of edd hapur, in the jurisdiction of etl-hapur of etd-hapur, under edc-hapur. , providing, installation and commissning of digital relay (make c&s, ashide and abb) in place of numerical/mechanical/damaged (burnt) relay of 11 kv feeders at 33/11 kv sub-stations of edd hapur, in the jurisdiction of etl-hapur of etd-hapur, numerical (3o/c+ie/f) should have following technical specification : (i) current rating : 1a/5a site selectable. (ii) aux supply : 24-23 v ac/dc rated (as per iec). (iii) draw out with ct shorting. (iv) scada compatible with rs 485 port. (v) frant leds display for following : l1, l2, l3, e trip for faulty y phase/earth, low set trip, high set trip. (vi) relay should have minimum 4 di, 6 do. (vii) the relay should have cold load pick up, harmonic blocking and cbfp. it should have minimum 10 fault records and 10 events records. selting ranges (a) ip 5 to 400 % is step of 1 % (b) ip 5 to 3000% in step of 1% (c) ie 5 to 250 % is step of 1 % (d) ie 5 to 1500 % is step of 1 % (e) tp 0.01 to 1.50 % is step of 0.01 (f) te 0.01 to 1.50 % is step of 0.01 (g) tp 0.01 sec to 20 sec in step of 0.01 sec (h) te 0.01 sec to 20 sec in step of 0.01 sec all t&p, labour will be provided by contractor in all respects , retro-fitting / modification work in existing vcb/dcb panel for installation of protection relay of different make including modification of relay slot, mounting arrangement, wiring adjustment, drilling/cutting, supply of small hardware/material, transportation, labour and complete installation as required for proper commissioning of relay - complete in all respect will be done by contractor.
View Original Notice/Document
Result Documents
Tender Documents
Download File Name File Description
Download 212bca64-4dd2-4135-9541-3c3c8986f747 financialevaluation notice
Download boqcomparativechart boq document
Download finance_2102396 aoc document
Download finsummary_2102396 aoc document
Download File Name File Description
Download 1397e6a9-182b-4b79-b01a-7d653426ce15 Tender Documents
Download BOQ_2102396 Tender Documents
Download Standbidnew53 Tender Documents
Download Tendernotice_1 (8) Tender Documents
Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

Financial Evaluation In Progress

Financial bids are currently under review. Awarded bidder information will be published after final evaluation.

PriceBid
Similar Tenders Results
TenderDetail
Loading tenders