Power Government Departments Closing in 11 days TDR #58736246

Tender For Supply Installation Testing and Commissioning of Ring Main Unit (Rmu) And Standby 100Kva, 33/0.433Kv, 3-Phase Auxilary Transformer With Allied Material For 2X10mva, 33/11Kv Receiving Station At Aiims Awantipora Under Capex Budget

Issued by Government Departments · Pulwama, Jammu and Kashmir
Tender Value
1.79 Crore
Estimated cost
Bid Submission
09 Dec 2026
11 days left
EMD
3.60 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Pulwama → Jammu and Kashmir
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Supply Installation Testing and Commissioning of Ring Main Unit (Rmu) And Standby 100Kva, 33/0.433Kv, 3-Phase Auxilary Transformer With Allied Material For 2X10mva, 33/11Kv Receiving Station At Aiims Awantipora Under Capex Budget

BOQ

Name of Work:- SITC OF RING MAIN UNIT (RMU) AND STANDBY 100KVA, 33/0.433KV, 3-PHASE AUXILARY TRANSFORMER WITH ALLIED MATERIAL FOR 2X10MVA, 33/11KV RECEIVING STATION AT AIIMS AWANTIPORA under CAPEX budget
Sl. No. Item Description
1Item Description
233kV RING MAIN UNIT (4-way type,two isolators and two Circuit breaker scheme): Out-door type RMU, SF6 Insulated, Extensible type, at 33kV system voltage and breaking capacity 25kA for three second, with SF6 insulated VCB with O/C + E/F Relay system comprising of a)33kV, 630 Amp. motorized Isolators including earthing switches with making capacity 62.5kA, having mechanical ON/OFF.b)33kV,630Amp motorized, spring operated, Circuit Breakers (CB) with earthing switches. VCB must meet 10000 ON-OFF mechanical operation, and the operating sequence must be O-0.3sec-CO-3Min-CO. Suitable CT shall be placed in Cable chamber for protection.( c). Cu Bus - Bar of 630 Amp. rating.d)One (1) No. Numerical Aux powered relay having Non-directional 0/C and E/F protection (for No. Circuit Breaker feeder). Relay should have minimum 4-DI & 6-DO. The relay shall also interface via an RS 232/485 port in order to send, as a minimum, real-time readings using the MODBUS protocol. e)Incoming Isolators shall have FPI with electrical reset contact / facility.f)All necessary potential-free contacts for indications relevant to RMU monitoring and control.g)Capacitor Voltage Dividers serving live-line cable indicators in No. Breaker & Isolator.h)The RMU must be offered with a single- phase Auxiliary VT 33KV/230V AC, 500VA and 26AH, 24V battery with 7amps Battery Charger.i)The RMU (Gas tank +Cable chamber) must be Internal tested for 25KA for 1 sec duration with AFLR classification. RMU shall have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works.
333 kV, Single core 400 mm² Aluminium, Flat strip Armoured XLPE Cable FRLS (from four pole to RMU and RMU to 33 kV Bus with 12 runs of 90 mtr each).
433 kV, 1 core 185sq.mm, Al conductor, XLPE, insulated, armoured cable (for 33kV/440V Auxilarry Transformer,with six runs of 30 mtr each)
533 kV Heat Shrinkable Cable Termination Kits (Indoor/Outdoor) to be used with cables - 400 sq.mm.
6Straight Through Jointing kit for 400 sqmm
733 kV Heat Shrinkable Cable Termination Kits (Indoor/Outdoor) to be used with cables - 185 sq.mm
86 core 2.5 sq.mm.Control Cable Copper Armoured, 1.1 kV Grade, ISI, FRLS.
9Warning Tap
10Cable Route Markers.
11Excavation in any type of soil including hard laterite soil.
12Backfilling of excavated soil
13Sand for cushioning of the cables in the trench.
14Mechanical transport 30kms of sand
15Head load 100 mtrs of sand
16P/laying of HDPE Pipe outer dia 160 mm Inner dia 148 mm for laying of 33 kV cable including excavation and back filling
17GI Pipe 150 mm dia with required no of collars for road crossing including termination points
18RCC protective cover of size 600 mm (width) x 250mm (Length) x 60 mm (Thickness) for underground cables
19Brick Masonary Chamber 900mm x900mm x1050mm with RCC top slab, Cast Iron cover in CI Frame (38Kg)
20Earthing of RMU --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mmx10 mm & 50 mmx6 mm for connection of RMU body as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
21Cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size for foundations)
22Centering and shuttering including struttings, propping etc and removal of formwork.
2315 mm cement plaster 1:4 (1 - cement: 4 -fine sand) for foundations.
24Constructing masonry chamber (600x600x900)mm .inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover & frame to be not less than 38 kg (weight of cover 23kg & weight of frame 15 kg) & RCC top slab 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) & inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design with common burnt clay F.P.S. (non modular ) bricks of class designation 7.5
25Reinstatement of roads (length x .7 m x 0.2 m thick)
26Wire mesh boundary fencing around the RMU i/c fixing in cement concrete base, complete job as per site engineer.
2711 Mtr. Long Pole ( ST-410 SP56)
28GI V cross-arm with top Bracket including clamps/GI Channel X-arm with Belting/Brace iron including clamps
29200 mm² ACSR Conductor
30PG Clamps for 200 mm² ACSR Conductor
3133kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
3233kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting
33Galvinized Nuts and Bolts.
34Danger Plates with Clamps
35Anti-Climbing Device with Clamps
36Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3mm
37Red Oxide
38Aluminium Paint
39Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8) mm, nut-bolts, 2 Nos turn-buckles, 1.8m long,20 mm diameter solid GS stay rod & 7/4 mm dia GI stranded wire complete
40Dismantling of existing ACSR 200 sqmm Panther conductor (Rate to be quoted in erection only)
41Laying, stringing and binding of dismantled ACSR 200 sqmm Panther conductor (Rate to be quoted in erection only)
42Dismantling of existing 11 mtr ST Poles alongwith the allied material i/c safe handling, stacking,carriage and handover to the stores (Rate to be quoted in erection only)
43100 kVA,33/0.433 kV, 3-phase Distribution Transformers with normal OCTC on HV side Transformer with Bimetallic Terminal Connectors Energy Level-I (corresponding to previous Energy efficiency level II) as per IS 1180 (Part I of 2014), Copper wound, and with LV Cable Box having Detachabale Aluminium Gland plate. Transformer should have arrangement for vertical take off of cable
449 Mtr. Long Pole (ST-410 SP33)
4533 kV, Lightening Arrestor,(33 kV ,10 kA ,Station class,ZnO, Polymer) gapless
4633 kV Isolator, with Earthing Blade (36kV,800 A, Outdoor ,3 poles,25 kA).
4733 kV Horn Gap Fuse set
48Galvanised iron of sorts
49120 mm² XLPE LT Cable 1 Core, armoured, FRLS.
50Earthing of 100 kVA SubStation--Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mm x10 mm & 50 mm x 6 mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
51MCCB- 160 Amps, 36 kA, 4P Ics=100% Icu at 415(kA rms) alongwith cubicle.
52Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, High impact polyprophelene copolymer container, flame retardant.
53Cement bottoming 1:2:4 mix as per Standards, 0.66 cum /pole
54Cement bottoming 1:2:4 mix as per Standards, 0.48 cum /pole Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58736246
AUTHORITY Government Departments
TENDER VALUE 1.79 Crore
LAST DATE 09-12-2026
Authority
Authority Name Power Development Department
Work Description Tender for Supply Installation Testing and Commissioning of Ring Main Unit (Rmu) And Standby 100Kva, 33/0.433Kv, 3-Phase Auxilary Transformer With Allied Material For 2X10mva, 33/11Kv Receiving Station At Aiims Awantipora Under Capex Budget
Basic Detail
Tender No PDP 02 of 2026 27
Bidding Type Tender
Location
City Pulwama
State Jammu and Kashmir
Key Dates
Publish Date 26 Nov 2026
Submission Date 09 Dec 2026
Open Date 12 Dec 2026
Finance
Tender Value 1.79 Crore
Tender Fee 3000
EMD 3.60 Lakhs
Exemption Available
Document List
BOQ_1128134.xls
cbb6b2d4-2b1e-4423-93c1-7bfad940d2a4.html
SBDAIIMS.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 26, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 09, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 11 days
Dec 12, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 14 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_1128134.xls

html

cbb6b2d4-2b1e-4423-93c1-7bfad940d2a4.html

pdf

SBDAIIMS.pdf

pdf

Tendernotice_1.pdf

Disclaimer