Tender For Supply Installation Testing and Commissioning of Ring Main Unit (Rmu) And Standby 100Kva, 33/0.433Kv, 3-Phase Auxilary Transformer With Allied Material For 2X10mva, 33/11Kv Receiving Station At Aiims Awantipora Under Capex Budget
Tender Overview
Project Description
Tender for Supply Installation Testing and Commissioning of Ring Main Unit (Rmu) And Standby 100Kva, 33/0.433Kv, 3-Phase Auxilary Transformer With Allied Material For 2X10mva, 33/11Kv Receiving Station At Aiims Awantipora Under Capex Budget
BOQ
| Sl. No. | Item Description |
| 1 | Item Description |
| 2 | 33kV RING MAIN UNIT (4-way type,two isolators and two Circuit breaker scheme): Out-door type RMU, SF6 Insulated, Extensible type, at 33kV system voltage and breaking capacity 25kA for three second, with SF6 insulated VCB with O/C + E/F Relay system comprising of a)33kV, 630 Amp. motorized Isolators including earthing switches with making capacity 62.5kA, having mechanical ON/OFF.b)33kV,630Amp motorized, spring operated, Circuit Breakers (CB) with earthing switches. VCB must meet 10000 ON-OFF mechanical operation, and the operating sequence must be O-0.3sec-CO-3Min-CO. Suitable CT shall be placed in Cable chamber for protection.( c). Cu Bus - Bar of 630 Amp. rating.d)One (1) No. Numerical Aux powered relay having Non-directional 0/C and E/F protection (for No. Circuit Breaker feeder). Relay should have minimum 4-DI & 6-DO. The relay shall also interface via an RS 232/485 port in order to send, as a minimum, real-time readings using the MODBUS protocol. e)Incoming Isolators shall have FPI with electrical reset contact / facility.f)All necessary potential-free contacts for indications relevant to RMU monitoring and control.g)Capacitor Voltage Dividers serving live-line cable indicators in No. Breaker & Isolator.h)The RMU must be offered with a single- phase Auxiliary VT 33KV/230V AC, 500VA and 26AH, 24V battery with 7amps Battery Charger.i)The RMU (Gas tank +Cable chamber) must be Internal tested for 25KA for 1 sec duration with AFLR classification. RMU shall have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. |
| 3 | 33 kV, Single core 400 mm² Aluminium, Flat strip Armoured XLPE Cable FRLS (from four pole to RMU and RMU to 33 kV Bus with 12 runs of 90 mtr each). |
| 4 | 33 kV, 1 core 185sq.mm, Al conductor, XLPE, insulated, armoured cable (for 33kV/440V Auxilarry Transformer,with six runs of 30 mtr each) |
| 5 | 33 kV Heat Shrinkable Cable Termination Kits (Indoor/Outdoor) to be used with cables - 400 sq.mm. |
| 6 | Straight Through Jointing kit for 400 sqmm |
| 7 | 33 kV Heat Shrinkable Cable Termination Kits (Indoor/Outdoor) to be used with cables - 185 sq.mm |
| 8 | 6 core 2.5 sq.mm.Control Cable Copper Armoured, 1.1 kV Grade, ISI, FRLS. |
| 9 | Warning Tap |
| 10 | Cable Route Markers. |
| 11 | Excavation in any type of soil including hard laterite soil. |
| 12 | Backfilling of excavated soil |
| 13 | Sand for cushioning of the cables in the trench. |
| 14 | Mechanical transport 30kms of sand |
| 15 | Head load 100 mtrs of sand |
| 16 | P/laying of HDPE Pipe outer dia 160 mm Inner dia 148 mm for laying of 33 kV cable including excavation and back filling |
| 17 | GI Pipe 150 mm dia with required no of collars for road crossing including termination points |
| 18 | RCC protective cover of size 600 mm (width) x 250mm (Length) x 60 mm (Thickness) for underground cables |
| 19 | Brick Masonary Chamber 900mm x900mm x1050mm with RCC top slab, Cast Iron cover in CI Frame (38Kg) |
| 20 | Earthing of RMU --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mmx10 mm & 50 mmx6 mm for connection of RMU body as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 21 | Cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size for foundations) |
| 22 | Centering and shuttering including struttings, propping etc and removal of formwork. |
| 23 | 15 mm cement plaster 1:4 (1 - cement: 4 -fine sand) for foundations. |
| 24 | Constructing masonry chamber (600x600x900)mm .inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover & frame to be not less than 38 kg (weight of cover 23kg & weight of frame 15 kg) & RCC top slab 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) & inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design with common burnt clay F.P.S. (non modular ) bricks of class designation 7.5 |
| 25 | Reinstatement of roads (length x .7 m x 0.2 m thick) |
| 26 | Wire mesh boundary fencing around the RMU i/c fixing in cement concrete base, complete job as per site engineer. |
| 27 | 11 Mtr. Long Pole ( ST-410 SP56) |
| 28 | GI V cross-arm with top Bracket including clamps/GI Channel X-arm with Belting/Brace iron including clamps |
| 29 | 200 mm² ACSR Conductor |
| 30 | PG Clamps for 200 mm² ACSR Conductor |
| 31 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 32 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting |
| 33 | Galvinized Nuts and Bolts. |
| 34 | Danger Plates with Clamps |
| 35 | Anti-Climbing Device with Clamps |
| 36 | Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3mm |
| 37 | Red Oxide |
| 38 | Aluminium Paint |
| 39 | Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8) mm, nut-bolts, 2 Nos turn-buckles, 1.8m long,20 mm diameter solid GS stay rod & 7/4 mm dia GI stranded wire complete |
| 40 | Dismantling of existing ACSR 200 sqmm Panther conductor (Rate to be quoted in erection only) |
| 41 | Laying, stringing and binding of dismantled ACSR 200 sqmm Panther conductor (Rate to be quoted in erection only) |
| 42 | Dismantling of existing 11 mtr ST Poles alongwith the allied material i/c safe handling, stacking,carriage and handover to the stores (Rate to be quoted in erection only) |
| 43 | 100 kVA,33/0.433 kV, 3-phase Distribution Transformers with normal OCTC on HV side Transformer with Bimetallic Terminal Connectors Energy Level-I (corresponding to previous Energy efficiency level II) as per IS 1180 (Part I of 2014), Copper wound, and with LV Cable Box having Detachabale Aluminium Gland plate. Transformer should have arrangement for vertical take off of cable |
| 44 | 9 Mtr. Long Pole (ST-410 SP33) |
| 45 | 33 kV, Lightening Arrestor,(33 kV ,10 kA ,Station class,ZnO, Polymer) gapless |
| 46 | 33 kV Isolator, with Earthing Blade (36kV,800 A, Outdoor ,3 poles,25 kA). |
| 47 | 33 kV Horn Gap Fuse set |
| 48 | Galvanised iron of sorts |
| 49 | 120 mm² XLPE LT Cable 1 Core, armoured, FRLS. |
| 50 | Earthing of 100 kVA SubStation--Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mm x10 mm & 50 mm x 6 mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 51 | MCCB- 160 Amps, 36 kA, 4P Ics=100% Icu at 415(kA rms) alongwith cubicle. |
| 52 | Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, High impact polyprophelene copolymer container, flame retardant. |
| 53 | Cement bottoming 1:2:4 mix as per Standards, 0.66 cum /pole |
| 54 | Cement bottoming 1:2:4 mix as per Standards, 0.48 cum /pole Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 14 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender