Tender For repair maintenance E&M Services Installed At Da Staff Qtrs, Karkardooma, Delhi. (Sh:- Renovation Work At Type Ii Qtr No. 251 To 258 And miscellaneous electrical installation Work Under Pwd Sub-Division 3/M2533, Da Staff Qtr., Shahdara, Del
Tender Overview
Project Description
Tender for repair maintenance E&M Services Installed At Da Staff Qtrs, Karkardooma, Delhi. (Sh:- Renovation Work At Type Ii Qtr No. 251 To 258 And miscellaneous electrical installation Work Under Pwd Sub-Division 3/M2533, Da Staff Qtr., Shahdara, Delhi.)
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. \\"Group A\\" |
| 2 | Rewiring for light point/ fan point/ exhaust fan point/call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. \\" Group A\\" |
| 3 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 4 | 20 mm |
| 5 | 25 mm |
| 6 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 7 | 2 X 1.5 sq mm + 1 X 1.5 sq mm earth wire |
| 8 | 2 X 4 sq mm + 1 X 4 sq mm earth wire |
| 9 | 2 X 6 sq mm + 1 X 6 sq mm earth wire |
| 10 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 11 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 12 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 13 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 14 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 15 | 5/6 amps switch |
| 16 | 3 pin 5/6 amp socket outlet |
| 17 | 15/16 amp switch |
| 18 | 6 pin 15/16 amp socket outlet |
| 19 | Bell push |
| 20 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. |
| 21 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc. as required. |
| 22 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required. |
| 23 | Supply of the following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 24 | 8 way, Double door |
| 25 | 12 way, Double door |
| 26 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 27 | 6 way (4 + 18), Double door |
| 28 | Supplying and fixing 5 amps to 32 amps rating, 240 volts, C series, miniature circuit breaker suitable for lighting and other loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole |
| 29 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.A) 63 amps |
| 30 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.A) 63 amps |
| 31 | Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 32 | 125 Amp, 36KA, FPMCCB |
| 33 | 250 Amp, 36KA, FPMCCB |
| 34 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperaturerise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.Brush Less Direct Current (BLDC) Fan withoutRemote |
| 35 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 36 | Supplying, Installation, testing and commissioning of Fresh Air fan of 250mm sweep complete with louvers & blades in plastic body with self-opening louvers in the existing opening including making the hole to suit the size of the above fan, making good the damaged, connections, earthing etc., as required. |
| 37 | Supplying, installation, testing and commissioning of heavy-duty exhaust fan of 300 mm sweep, 900 RPM confirming to IS 2312/67 complete with louvers and frames in the existing opening including making the hole to suit the size of the above fan, making good the damage, connections, earthing etc, as required. |
| 38 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 39 | 18-22 Watt |
| 40 | Supplying, Installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body(Thickness > 1.20 mm) |
| 41 | 36 Watt |
| 42 | Supplying and fixing of 10-12 watt LED Bulkhead fitting, pressure die-casting aluminium housing having colour rendering (CRI) of ≥85, THD<20% and co-related colour temperature (CCT) of (5700/6500K) having system efficiency not less than 110 lumen per watt complete. etc. i/c making connections, testing, commissioning etc. as required. The manufacturer should provide LM-79 & LM-80 reports along with guarantee of 5 year. as required. |
| 43 | Supplying and fixing of existing damaged fitting into 10 to 12 watt 600 mm long high efficiency efficacy more than 120 LED linear batten Luminaries having pressure die-casting aluminium housing and polycarbonate diffuser within built APFC driver having efficiency of driver 85% power factor > 0.90, THD <20% with minimum 2.5 KV surge protection, LED life with not less than 50000 burning hours etc. suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency 110 luman per watt. and colour temperature of 6500 K, CRI >85 including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable with the help of two nos. fastener Hook, etc. The manufacturer should provide LM-79 & LM-80 reports along with guarantee of 5 year. as required. |
| 44 | Supplying, installation, testing and commissioning of Plug Tops Range, Convenient gripping, High heat resistant body, Nickel plated pins, Easy wire routing with additional space, Sturdy body with elegant design including connection etc. as required. |
| 45 | 3 Pin Plug 6A |
| 46 | 3 Pin Plug 16A |
| 47 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 48 | 120 Watt |
| 49 | Supplying and Laying of one number PVC insulated Aluminium conductor and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe/Open Duct etc. as required. |
| 50 | 3 x 10 sq.mm armourd Aluminium conductor cable |
| 51 | SITC of DWC/HDPE pipe for covering the street light pole of dia upto 200 mm and height minimum 2 Mtr. including cutting jointing etc. with the help of hydra/Tower wagon, pipe must be fixed to the pole from above side to the bottom by removing the arm bracket and fixed the bracket as previous for the protection due to electrocution. (colour of pipe is decide by engineer-in-charge or his representative. |
| 52 | Supplying, installation, testing and commissioning of fancy PVC Round Batten Brass bulb Holder for Wall including connection etc. as required. |
| 53 | Supply and fixing 3 mm. thick phenolic, laminated Hylum sheet cover on existing M.S. Box with brass screw i/c cutting the sheet for existing switch, socket etc. as required. |
| 54 | SITC of All in One computer system with following configurations:a) CPU : Intel Core i7 150U (12 MB cache, 10 cores, 12 threads, Up to 5.4 Ghzb) Operating System :- Window 11 Home , Single Language c) Video Card:- NVIDIA @ GeForce@MX570A with 2GB GDDR6 graphics Momory d) Monitor:- 27\\" FHD, WVA e) Memory :- 16 GB 2x8 GB DDR5, 5200 MT/sf) Storage 1TB, M2, PCle NVMe, SSD g) Stand :- Triangle stand h) Microsoft office :- Microsoft office Home 2024 + Microsoft 365 Basic 1 Year subscription (Make:- DELL Model No. Dell 27 150U (EC27250) or better model or equivalent in HP) |
| 55 | Supplying, installation, testing and commissioning of Monochrone Laser Jet Multifunctional A4 Printer i.e., Print, Scan, Copier, Autoduplex printing, Wireless Printing, Network printing, ADF etc. complete as required. |
| 56 | Supplying, installation, testing and commissioning of 650VA UPS along with 12V 7Ah battery etc. complete as required |
| 57 | Less on Account of buy back of old dismantled material received from the work |
| 58 | Assorted Copper Wire 1.5,4,6 |
| 59 | Assorted Ceiling Fan, Wall Fan, Exhaust fan & PVC Exhaust fan |
| 60 | Assorted LED fittings |
| 61 | Assorted LED Panel 2 x 2 |
| 62 | Assorted LED Street light |
| 63 | Assorted switch/socket & fan Regulator |
| 64 | Assorted MCB/DB |
| 65 | Assorted MCCB |
| 66 | Assorted PVC Conduit |
| 67 | Note:- During the preparation of any running or final bill by the contractor it is essential that the contractor shall submit GST paid invoice, E-way bill and delivery challan for all items without these documents the bill will not be considered submitted in proper form & shall be returned back to the contractor by Junior Engineer (E). Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender