Defence Statutory Bodies & Commissions/Committees Closing in 17 days TDR #58694611

Tender For Repair & Maintenance Of Water Cooled Screw Chilled Air Conditioning Plant 3X450 Tonne Capacity At Ph-2 Bldg Mh Khadki Complete With Air Handling Unit , Replacement Of Filters , Unsv Control Valves , Ms Pipes , Insullation Of Chilled Water

Issued by Statutory Bodies & Commissions/Committees · Pune, Maharashtra
Tender Value
28.76 Lakhs
Estimated cost
Bid Submission
16 Dec 2026
17 days left
EMD
57536
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Pune → Maharashtra
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Repair & Maintenance Of Water Cooled Screw Chilled Air Conditioning Plant 3X450 Tonne Capacity At Ph-2 Bldg Mh Khadki Complete With Air Handling Unit , Replacement Of Filters , Unsv Control Valves , Ms Pipes , Insullation Of Chilled Water Pipes , Ducts, Control Panels , Starter, Rewinding Of Motors, Descaling Of Condenser, Cooling Tower, Including Periodical Maintenance As Per Manufacturer Maintenence Schedule Complete And Connected Certain Other Miscellaneous Items Of Air Conditioning Plant Under Ge (Mh&Rh) Khadki.

BOQ

Name of Work:- REPAIR & MAINTENANCE OF WATER COOLED SCREW CHILLED AIR CONDITIONING PLANT 3X450 TONNE CAPACITY AT PH-2 BLDG MH KHADKI COMPLETE WITH AIR HANDLING UNIT , REPLACEMENT OF FILTERS , UNSV CONTROL VALVES , MS PIPES , INSULLATION OF CHILLED WATER PIPES , DUCTS, CONTROL PANELS , STARTER, REWINDING OF MOTORS, DESCALING OF CONDENSER, COOLING TOWER, INCLUDING PERIODICAL MAINTENANCE AS PER MANUFACTURER MAINTENENCE SCHEDULE COMPLETE AND CONNECTED CERTAIN OTHER MISCELLANEOUS ITEMS OF AIR CONDITIONING PLANT UNDER GE (MH&RH) KHADKI.
Sl. No. Item Description
1Carrying out annual maintenance of 450 TR water chiller plant by approved OMC (original manufacturing company i.e DUNHAM-BUSH) including following routine work .
2i) Inspecting the machine 3 times a year in equal quarters. During this inspection the following work will be carried out:ii) Checking the refrigeration systemiii) Checking the operation of controlsiv) Checking of microprocessor logic operation
3v) Attending to service calls for trouble diagnosis apart from scheduled quarterly visits.vi) Reporting to you the condition of machine at the time of inspection and attending the same by overhauling compressor / replacing components, if found necessary (On extra chargeable basis)vii) Checking the system for any leaks and rectification of leaks. (if found Leakage, repair on chargeable basis)viii) Taking set of readings and evaluating to ensure satisfactory performance of the plantix) Spares will be replaced on extra chargeable basis in case required.x) Informing the operating personnel of changes or adjustments made and recommending to them improvements in trouble free operation of the plantxi) Imparting operational training to your operating staff at the beginning of contract complete all as specified and directed by Engineer-in-charge.
4Supply and replace the following defective / worn out spares / controls for the chiller Plant complete all as specified and directed by Engineer-in-charge.
5Pressure transducer - Low presure / High Pressure / Oil pressure up to 10 Kg / cm2
6Temperature sensor suitable for the chiller unit.Make : Dun-ham-bush/ Kirloskar/Blue Star or equivalent
7Pressure relief valve Make : Dun-ham-bush/ Kirloskar/Blue Star or equivalent
8Gaskit Partition Sr no M05 Make : Dun-ham-bush/ Kirloskar/Blue Star or equivalent
9Valve-Ball 7/8 Sr-17307 Make : Dun-ham-bush/ Kirloskar/Blue Star or equivalent
10Valve-Ball 1/8 Sr-17309 Make : Dun-ham-bush/ Kirloskar/Blue Star or equivalent
11Valve Saloined 5/8 ODF Make : Dun-ham-bush/ Kirloskar/Blue Star or equivalent
12M & L for descaling of complete condenser units for central type AC plant of capacity 450 TR by means of adding descaling chemical solution or equivalent in the cooling tower sump of required quantity and circulating the liquid to remove the scales inside the pipes and removing side covers of condenser, cleaning the water tubes by scrubbing with nylon brushes and flusing with fresh water, re fixing the covers, Inlet and out let pipes including replacement of neoprene rubber gasket etc. complete all as specified and directed by Engineer-in-charge
13Repairing /servicing and overhauling the centrifugal pump by dismantling the pump coupled with induction motor, opening the pump, inspecting for defects and replacing the worn out parts like gland bush, bearings, gland bolts and nuts,gland packing, gasket, water seal etc including repairs to pump shaft by remetalling, grinding, polishing and reassembling the same and replacing the rusted nuts, bolts, washers etc and coupling with motor testing complete for the following capacity of pump complete all as specified and directed by Engineer-in-charge.
14Primary chillar pump 20 HP of make Kirloskar, Crompton, Shakti
15Secondary chillar Pump 40 HP of make Bell & Gossett
16Condenser Pump 30 HP of make Kirloskar, Crompton, Shakti
17M & L for taking out the centrifugal pump motor and transporting to work shop , split opeing the motor removing the u/s burnt winding wire, cleaning the slots, re winding with super enameled copper conductor wire of suitable size including insulating materials, varnishing and drying and reassembling and transporting back to site , coupling with pump testing and commissioning complete all as specified and directed by Engineer-in-charge for the following capacities of motors : -
18Primary chillar Motor 20 HP of make Kirloskar Brothers
19Secondary chillar Motor 40 HP of make Bell & Gossett
20Condenser Motor 30 HP of make Kirloskar Brothers
21Blower Motor of Cap 5 HP to 7.5 HP of make Bharat Bijali
22Blower Motor of Cap 3 HP of make Bharat Bijali
23Dismantling the covers of cooling tower and the cooling fan blades from the position, electrical connections and taking down the cooling tower motor of capacity 10 HP, split opening the motor, removing the burnt out winding, cleaning the slots re winding with super enameled copper conductor wire of suitable size including insulating materials, varnishing and drying and reassembling and transporting back to site and testing on commissioning complete all as specified and directed by Engineer-in-charge.
24S&F cooling tower fins as per existing size and shape complete all as specified and directed by Engineer-in-charge.
25Descaling of cooling tower by dismantling the cooling tower fins removing the scales in the fins, sump by scrubbing with wire / nylon brush and refixing the fins in position including replacing the float valve for supply water line, painting the steel/wooden surfaces with two coats of enamel paint over a coat of zinc oxide primer and testing the cooling tower complete all as specified and directed by Engineer-in-charge..
26Supply and fill Gas R-134 a in cylinder for charging / topping up whenever required.
27M&L for leak testing of gas by evacaveting the gas by suitable means and filling with nitrogen gas for 24 hours rectifying the leakages with and incuding required material / brazing etc. and refilling gas testing chiller complete all as specified and directed by Engineer-in-charge.
28S&F in replacement of double fitted polymer fabric HDPE fresh air filter(Filter class-G3 as per EN 779) washable/cleanable type having efficiency 95% to 99% down to particle size of 10 micron, fabricated out of CRCA sheet metal duly painted with two coat of grey hammer tone spray painted over two coats of red oxide primer, with lifting handle, Box/flanged type, aluminium spacer etc, of make Thermadyne/ Pall supralon filter / Micron filter complete all as specified and directed by Engineer-in-charge of following sizes :-
29610X610X50 mm
30305x610x50 mm
31610x305x50 mm
32S&F in replacement of double fitted polymer fabric HDPE fresh air filter(GL-type) washable/cleanable type having efficiency 95% to 99% down to particle size of 5 micron, fabricated out of CRCA sheet metal duly painted with two coat of grey hammer tone spray painted over two coats of red oxide primer, with lifting handle, Box/flanged type, aluminium spacer etc, including taking down make Thermadyne/ Pall supralon filter / Micron filter complete all as specified and directed by Engineer-in-charge of following sizes :-
33610x610x305 mm
34305x610x305 mm
35610x305x305 mm
36Supply and replace in repairs butter fly valve of dia 100mm suitable for condensing /chiller water line with ISI marked including jointing with gasket ,nut,bolts washer complete all as specified and directed by Engineer-in-charge. Make CRI, Kirloskar, L & T
37S&F in replace in repairs butter fly valve of dia 125mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washer complete all as specified and directed by Engineer-in-charge. Make CRI, Kirloskar, L & T
38Supply and replace in repairs butter fly valve of dia 150 mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washerall complete all as specified and directed by Engineer-in-charge., Make CRI, Kirloskar, L & T
39S&F in replacement NRV of dia 250 mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washerall complete all as specified and directed by Engineer-in-charge.Make Kirloskar, BIR, Kartar
40Supply and fill compressor oil for centrifugal compressor for toping up / replacement as required complete all as specified and directed by Engineer-in-charge. Make : Kirloskar, Dunham-Bush, Castrol
41S&F in replacement of water pressure gauge as per existing .Make Emerald/ Wika / Rexroth
42S&F in replacement of Temp gauge as per existing. .Make Emerald/ Wika / Rexroth
43S&F in replacement of following ball bearing (NDE/DE) suitable for cooling tower motor ,chillar motor,Blower motor,condenser motor etc removing of existing unserviceable bearing of any type or make complete all as specified and directed by Engineer-in-charge. Make : SKF/TATA/FAG/ Nachi
446205/2Z
456206/2Z
466207/2Z
476208/2Z
48S&F in replacement of Power contactor AC-3 of Aux voltage 230V , 3NO+1NC of following capacities Make : L & T, Siemens, Legrand or equivalent
49MNX 50-TP of rating 32A,
50MNX 32-TP of rating 32A,
51MNX 25-TP of rating 25A,
52MNX 12-TP of rating 12A,
53S&F in replacement of over load relay with inbuilt single phase protection of following capacities Make : L & T, Siemens, Legrand or equivalent
54MN5 of rating 20-33A
55MN2 of rating 14-23A
56MN2 of rating 6-10A
57MN2 of rating 4-6A
58Supply and replace the strip heaters of capacity 3 KW / strip complete all as specified and directed by Engineer-in-charge.Make : Omega / Platinum / finned or equivalent
59Serviceing of existing installed VFD as per manufacturer's standard and testing complete all as specified and directed by Engineer-in-charge. Make : Danfoss
60S&F pully including taking down old unserviceable / damaged pully along with necessary fabrication to shaft for filling wear out portion and turning complete, including making allinment, quotated rate includes transportation, hardware & T&P as per site requirement complete all as specified and directed by Engineer-in-charge.
61Quarterly Greasing of AHU's all pedstal bearing as per IS Standard including cleaning of old unserviceable grease with help of grease gun up to topping up, rate should quotated including price of grease and T& P complete all as specified and directed by Engineer-in-charge.
62Supply and Replacement AHU blower DIDW fan blower having out velocity not exceeding S.P.(mm/wg) 50-60 m/s energy efficient fan with double inlet , double with forward or backward curved impeller for high static pressure mounted on aluminum extended side rail base frame, existing AHU of following capacity of Blowers motor :-
63Blower for Capacity 5 HP motor
64Blower for Capacity 3 HP motor
65Painting of 450 TR capacity existing cooling tower with existing color complete in all respect complete all as specified and directed by Engineer-in-charge.
66Descaling of cooling tower makeup tank by dismantling the strainer removing the scales in the tank, sump by scrubbing with wire / nylon brush and refixing the strainer position including replacing the float valve for supply water line, painting the steel/wooden surfaces with two coats of enamel paint over a coat of zinc oxide primer and testing the cooling tower complete all as specified and directed by Engineer-in-charge.
67Repairing /servicing and overhauling the Pan type humidifier are closed type & Connected to supply air duct Capacity upto 3 KW to 6 KW complete all as specified and directed by Engineer-in-charge. Make - Emerald or equivalend makes
68Supply and replacement and testing of GM gate/ globe valve heavy duty conferming to IS-778 with iron wheel head screwed both end for 40 mm or size as per existing complete all as specified and directed by Engineer-in-charge.
69Supply and replace three way mixing /modulating valve (Actuator) of diameter as per existing model No CN72220A2007 / CN7510A2001 proportional linear type, motorised mixing valve BS 4540 PN-10 -PN 40 having manual over ride facility with proportional thermostat/Humidity sensor and interconnecction wiring with 1.5 sq mm copper conductor multi core cable complete all as specified and directed by Engineer-in-charge. Make : Honeywell / Rapid / Energy
70Supply Erecrtion, Testing and commissioning in repair closed cell elastomeric nitrile rubber with aluminum foil laminated on oneside, having thermal Temperaturte, of 20 c as per EN 12667, moisture diffusion resistance factor or u Value of minium 7000 for base insulation material without the foil as per EN 12086, fire performance such that it passes Class 1 as per BS476 Part 7 for surface spread of flame and also fire performance of V0, HB as per UL 94, 1996, density without the foil between 40 to 55 KG/ Cum. the insulation material shall be FM ( factory Mutual) USA approved and dust & fiber free. the Aluminium foil shall be 60 microns thick and its weight shall be 193 gms as per EN ISO 2286-2, tensile strength 90 N/ 15 mm as per EN ISO 527-3 with elongation>10% as per EN ISO 527-3. All complete as specified in particular specification 19 mm thick thermal insulation complete all as specified and directed by Engineer-in-charge.
71Supply, assembly and erection of GI sheet with TDF flange rectangular/square duct made out of L shaped hollow profile, duly factory boxed including all accessories such as corner, cleat, carriage bolt, gasket and appropriate sealant on longitudinal joints etc complete with GI sheet of thickness 22 gauge complete all as specified and directed by Engineer-in-charge.
72Supply, assembly and erection of GI sheet with TDF flange rectangular/square duct made out of L shaped hollow profile, duly factory boxed including all accessories such as corner, cleat, carriage bolt, gasket and apropriate sealent on longitudinal joints etc complete with GI sheet of thickness 24 gauge complete all as specified and directed by Engineer-in-charge.
73S & F VFD for motor as per existing parameters and suitable for 40 HP motor along with programme setting recommanded by OEM (Dun Ham Bush) complete all as specified and directedMake : Danfoss / ABB / Seimense
74Repair to Microprocessor based control panel display unit for 450 TR AC chiller unit including spare parts complete all as specified and directed by Engineer-in-charge.Make : Kirloskar / Dun-Ham-Bush / Blue star
75S&F supply air diffuser for the 4-way square supply air ternimal should be in aluminium powder coated construction with easily removble central core & 4-way uniform air distribution. Volume control damper to be of opposed blade, nylon geared with aerofoil blades & blank matt powder coated (Out to out size shall be as per existing with full louvers with required duct connection size (as per opproved layouts) & as per approved sample (Color to match architects requirements) complete all as specified and directed by Engineer-in-charge.
76S& F air diffuser for the 4-way square return air ternimal should be in aluminium powder coated construction with easily removble central core & 4-way uniform air distribution.(Out to out size shall be as per existing with full louvers with required duct connection size (as per opproved layouts) & as per approved sample (Color to match architects requirements)complete all as specified and directed by Engineer-in-charge.
77M&L for descaling of Cooling coil of AHU's of any capacity by means of adding descaling chemical solution or equivalent of required quantity and circulating the liquid to remove the scales inside the pipes and cleaning the water tubes by scrubbing with nylon brushes and flusing with fresh water, re fixing the covers, Inlet and out let pipes including replacement of neoprene rubber gasket if required etc. complete all as specified and directed by Engineer-in-charge.
78Repair and replacement of old unserveacble AHU doors of any size door double skin pannel with pressure injected CFC & HCFC free PUF having 'K' value of 0.02 W/C/m & dinsity of 40 kg/ms pre coated, pre plasticized , galvanized outer and inner skin 0.06mm thick, air tight casing using gasket and self adhesiv,PVC Nylon hinges, passage handels view port and marine lamp ,limit switch etc of make : Kirloskar / Blue star / Voltas complete all as specified and directed by Engineer-in-charge.
79Supply and replace the worn out 'V' belts of blower motor. Make : Eco drive / fenner / reenolds rubber
80All as per Item No. 43 above but for A1738LP/A67
81All as per Item No. 43 above but for A1611LP/A62
82All as per Item No. 43 above but for B1973LP/B76
83All as per Item No. 43 above but for A1484LP/A57
84All as per Item No. 43 above but for A1509LP/A58
85All as per Item No. 43 above but for A1585LP/A61
86S&F in replacement MCCB of following capacities of Make : L & T/ Siemens/ Legrand
87630 A TP 50 KA Adjustable type 415V AC
88400A,TP.415V,50 Hz, 50 KA Fixed thermal magnetic type
89250A,TP.415V,50 Hz 36 KA Fixed thermal magnetic type
90125A,TP.415V,50 Hz 36 KA Fixed thermal magnetic type
91100A,TP.415V,50 Hz,25KA Fixed thermal magnetic type
92160A,TP.415V,50 Hz,36KA Fixed thermal magnetic type
9332A,TP,415V,50Hz,16KA Fixed thermal magnetic type
94S&F in replacement MCB of following capacities of Make : L & T/Siemens/Legrand
95TP 25 To 63 AMP.415V, 50 Hz,10 KA, C curve
966A to 32 Amp ,SP, 240V,50Hz,10 KA, C curve Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58694611
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 28.76 Lakhs
LAST DATE 16-12-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair & Maintenance Of Water Cooled Screw Chilled Air Conditioning Plant 3X450 Tonne Capacity At Ph-2 Bldg Mh Khadki Complete With Air Handling Unit , Replacement Of Filters , Unsv Control Valves , Ms Pipes , Insullation Of Chilled Water Pipes , Ducts, Control Panels , Starter, Rewinding Of Motors, Descaling Of Condenser, Cooling Tower, Including Periodical Maintenance As Per Manufacturer Maintenence Schedule Complete And Connected Certain Other Miscellaneous Items Of Air Conditioning Plant Under Ge (Mh&Rh) Khadki.
Basic Detail
Tender No CWE/KKE/TOKEN- 70 OF 2026-27
Bidding Type Tender
Location
City Pune
State Maharashtra
Key Dates
Publish Date 23 Nov 2026
Submission Date 16 Dec 2026
Open Date 19 Dec 2026
Finance
Tender Value 28.76 Lakhs
Tender Fee 500
EMD 57536
Exemption Not Available
Document List
BOQ_897662.xls
dcc3d5d0-1ebf-4e41-b004-26ed52346b34.html
Tender.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 23, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 16, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 17 days
Dec 19, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 20 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_897662.xls

html

dcc3d5d0-1ebf-4e41-b004-26ed52346b34.html

pdf

Tender.pdf

pdf

Tendernotice_1.pdf

Disclaimer