Water Resources and Irrigation Government Departments Closing in 9 days TDR #58689280

Tender For Repairing & Maintenence Of Power Distribution System With Re-Orientation Of Main Incoming Line With Balance Load At All 3 Phases At Basirhat Irrigation Division Office, 24 Pgs North To Be Executed Through Metropolitan Mechanical And Electr

Issued by Government Departments · 24 Paraganas North, West Bengal
Tender Value
15.44 Lakhs
Estimated cost
Bid Submission
08 Dec 2026
9 days left
EMD
30883
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
24 Paraganas North → West Bengal
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repairing & Maintenence Of Power Distribution System With Re-Orientation Of Main Incoming Line With Balance Load At All 3 Phases At Basirhat Irrigation Division Office, 24 Pgs North To Be Executed Through Metropolitan Mechanical And Electrical Division.

BOQ

Name of Work:- Repairing & maintenence of power distribution system with re-orientation of main incoming line with balance load at all 3 phases at Basirhat Irrigation Division Office, 24 pgs North to be executed through Metropolitan Mechanical and Electrical Division.
Sl. No. Item Description
1Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.Up to 250A 4 way Enclosure (DEVTH004DD)(L&T)
2Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. 6 way Enclosure (DEHPI006DD)(L&T)
3SSupplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. 2+14 way Enclosure (DESPN016DDS)(L&T)
4Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 10kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection.250 A,4P mccbdy250 u1 250 10 kA FTFM with spreader links(CM9819600PO)(L&T)
5Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection
6(i) FP 63 A.(L&T)(BB40630C)
7(ii) TP 63 A.(L&T)(BB30630C)
8(iii) DP 40 A.(L&T)(BB20400C)
9(iv) SP 6-32 A.(L&T)
10Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Finolex) in 32 mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings and connection as required 4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC
11Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Finolex) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC
12Wiring in 1.1 KV grade single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) of following sizes in 25mm PVC casing-capping (Precision make) incl. necy. PVC clips, fittings etc.
13i)2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm)
14ii)2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm)
15iii)2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm)
16Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. to light/fan/call bell point with Modular type switch ((Legrand Mylinc) fixed on Modular GI / PVC switch board with top cover plate on wall incl. mending good damages to original finish. [PVC casingcapping and Switch board both on surface] . Average run 10 mtr
17Distribution Wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Finolex) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. with S & F 6A 5 pin Modular type plug socket and switch (Legrand Mylinc) fixed on 4 Module GI / PVC switch board with 3/4 Module top cover plate on wall incl. necy. connection making earthing attachment, painting and mending good damages to building works [PVC casing-capping and plug box both on surface] . Average run 1.5 mtr
18Supplying & Fixing GI Modular Switch Board (Legrand ) of the following sizes incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works.
19i)4 Module
20ii)6 Module
21iii)8 Module
22iv)12 Module
23Supply & Fixing 240 V 6 A Modular type switch (Legrand Mylinc) on existing GI Modular type switch board having top cover plate and making necessary connections as required
24Supply & Fixing 240 V 16 A modular key type switch (Legrand Mylinc) on GI Modular type switch board having top cover plate and making necessary connections as required
25Supply & Fixing 240 V, 6A, 3 pin Modular type plug socket (Legrand Mylinc) , without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
26Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Legrand Mylinc) , without plug top and switch, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
27Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Legrand Mylinc) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
28Supply & Fixing 240 V, 25A Modular switch type DP MCB (C-Curve) (Legrand Allzy ) on existing GI Modular type switch board with top cover plate and making necy. Conections with PVC Cu wire and earth continuity wire etc.
29Supply & Fixing 240 V, 25A Modular starter (L&T Encurve) on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
30Excavation of soil for installation of Earth Electrode and filling & ramming.For Soft Soil
31Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By Jindal-Medium GI pipe
32Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe
33Extra for treatment of soil by using salt & charcoal or coke for plate electrode
34Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
35Supply TMC501 Conventional industrial baflen Philips LEDtube, model no : TMC 501 P 1xT-LED 22W P3241 with 1no Mas LEDtube 1200mm 18W865 T8 I - 2100lm including necessary connection.
36Supply TMC501 Conventional industrial baflen Philips LEDtube, model no : TMC 501 P 2xT-LED 22W P3242 with 2nos Mas LEDtube 1200mm 18W865 T8 I - 2100lm including necessary connection.
37Supplying of approved make high speed ceiling fan (ISI marked) of following sizes having double ball bearing complete with standard down rod, canopy, hanging shackle, Aluminium blades, without regulator, A.C. 230-250 volts 900mm/ 1050mm/ 1200mm
38Supply and fixing of smart bright street light (36 Watt) complete with all accessories to be fixed /projected from the wall of the building or on pole incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc.
39SUPPLYING OF FOLLOWING XLPE INSULATED ALUMINUM CONDUCTOR ARMORED CABLES OF 1.1KV GRADE AS PER IS 7098 (PART 1) 1988 WITH UP TO DATE AMENDMENTS. (Rate in Rs. Per Mtr). 4 CORE 25 SQ MM(\\"GLOSTER\\")
40Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting
41Supply, fixing, testing & commissioning wall/floor mounted LT panel primer coated with powder coated paint &provided with required gasket for dust/vermin proof with degree of protection IP42 suitable for 415Volt 3phase, 50 Hz, 4 wire system fabricated out of CRCA sheet up to 2 mm thick (1.6mm for doors) duly compartmentalized for incomer, bus section, outgoings, cable alleys & CT, PT Ampere , Volt , selector switches, frequency , phase indicating lamp, Energy complete including cost of busbar supports, detachable cable gland plates,2 earthing terminals, internal wiring &fixing of separately supplied MCBs, MCCBs, ACB, panel mounted changeover witch/SFUs, etc. as required but excluding cost of busbar strips, Ampere , Volt , selector switch as per approved design & specification.(Main panel box of dimension : 3mm thk CRCA sheet of dimension : 1500mm (H) x 1200 mm (B) x 400 mm (D) double door with double coated powder paint, S & F of following materials as per direction of EIC.) (Main panel box of dimension : 3mm thk CRCA sheet of dimension : 1500mm (H) x 1200 mm (B) x 400 mm (D) double door with double coated powder paint, S & F of following materials as per direction of EIC.)CU Bus Bar Size 4 nos of Bus Bar 30 mm x 6 mm
42i)Supply of on load change over switch 250 A,CO3-250. cat. No-CO32500OOOO .Make : (L&T )-1 no
43ii)415 V Four Pole MCCB of Breaking capacity 10kA, 250 A,4P mccbdy250 u1 250A ,10 kA FTFM with spreader links(CM9819600PO)(L&T)-02 nos
44iii)415 V Four Pole MCCB of Breaking capacity 10kA, 160 A,4P mccbdy250u1 160A,10 kA FTFM with spreader links (CM9819500MO)(L&T)-02 nos
45iv)416 V Four Pole MCCB of Breaking capacity 10kA, 63A,4P mccbdy125u 63A,10 kA FTFM with spreader links(EM9098400H0)(L&T)-02 nos
46v)Supply of moving iron type analog AC ammeter (accuracy class 1.5), model-SMI-96 of following range 0 to 100A.-01 no
47vi)Supply of 0 to 600V range moving iron type analog AC voltmeter (accuracy class 1.5), model-SMI-96 -01 no
48vii)Supply of ammeter selector switch Current in Each phase with OFF, 4 Pos. 90° angle of throw (OFF-R-Y-B)-01 no
49viii)Supply of voltmeter selector switch Votage between phases with OFF, 4 Pos. 90° angle of throw (OFF-RY-YB-BR)-01 no
50ix)Supply of indoor tape insulated ring type low tension current transformer of following rating 100/5A 5VA, Cl 1.0 -03 nos
51x)Supply of 22.5 mm dia LED indicating lamps-06 nos
52xi)10sqmm 'FR' stranded Copper wire for staretr power wiring(Finolex)
53xii)1.5 sqmm'FR' stranded Copper Wire for starter control wiring (Finolex)
54xiii)Supply of different types of CU Lug(LS) Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58689280
AUTHORITY Government Departments
TENDER VALUE 15.44 Lakhs
LAST DATE 08-12-2026
Authority
Authority Name Irrigation And Waterways Department
Work Description Tender for Repairing & Maintenence Of Power Distribution System With Re-Orientation Of Main Incoming Line With Balance Load At All 3 Phases At Basirhat Irrigation Division Office, 24 Pgs North To Be Executed Through Metropolitan Mechanical And Electrical Division.
Basic Detail
Tender No WBIW/EE/MMED/e-NIT-16/2026-27
Bidding Type Tender
Location
City 24 Paraganas North
State West Bengal
Key Dates
Publish Date 23 Nov 2026
Submission Date 08 Dec 2026
Open Date 09 Dec 2026
Finance
Tender Value 15.44 Lakhs
Tender Fee Ref. Documents
EMD 30883
Exemption Available
Document List
81b1646f-06ef-4a99-ba96-8f11df1b9ec0.html
BOQ_5221166.xls
OID.pdf
Tendernotice_1.pdf
WB2911.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 23, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 08, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 9 days
Dec 09, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 10 days

Tender Documents

Download All (ZIP) ↓
html

81b1646f-06ef-4a99-ba96-8f11df1b9ec0.html

xls

BOQ_5221166.xls

pdf

OID.pdf

pdf

Tendernotice_1.pdf

pdf

WB2911.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender