Tender For Running Maintenance, Operation & Comprehensive Maintenance Of Split Ac/ Window Ac/ Cassette Ac Units & Water Coolers In Vikas Bhawan, Ip Estate, New Delhi (Sh:- Repair/Replacement Of Electrical Installation In Various Blocks).
Tender Overview
Project Description
Tender for Running Maintenance, Operation & Comprehensive Maintenance Of Split Ac/ Window Ac/ Cassette Ac Units & Water Coolers In Vikas Bhawan, Ip Estate, New Delhi (Sh:- Repair/Replacement Of Electrical Installation In Various Blocks).
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.(a) Group C |
| 2 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 3 | (b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 4 | (c) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 5 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1. 5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable and 1. 5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required |
| 6 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (a) 3 x 1. 5 sq. mm |
| 7 | (b) 3 x 4 sq. mm |
| 8 | (c) 3 x 6 sq. mm |
| 9 | Supplying and drawing following pair 0. 5 mm dia FRLS/HFFR PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. 1 Pair |
| 10 | Supplying and drawing co-axial TV cable RG-6 grade, 0. 7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 11 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 25 mm |
| 12 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. 8.1) 5/6 amps switch |
| 13 | 8.2) 15/16 A switch |
| 14 | 8.3) 3 pin 5/6 A socket outlet |
| 15 | 8.4) 6 pin 15/16 A socket outlet |
| 16 | 8.5) Telephone socket outlet |
| 17 | 8.6) TV antenna socket outlet |
| 18 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 9.1) 5/6 A switch |
| 19 | 9.2) 15/16 A switch |
| 20 | 9.3) 3 pin 5/6 A socket outlet |
| 21 | 9.4) 6 pin 15/16 A socket outlet |
| 22 | 9.5) Telephone socket outlet |
| 23 | 9.6) TV antenna socket outlet |
| 24 | 9.7) Bell push |
| 25 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 26 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 27 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 12.1) 1 or 2 Module |
| 28 | 12.2) 3 Module |
| 29 | 12.3) 4 Module |
| 30 | 12.4) 6 Module |
| 31 | 12.5) 8 Module |
| 32 | 12.6) 12 Module |
| 33 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 &15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 34 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. 14.1) 100 A, 16 KA, TPMCCB |
| 35 | 14.2) 125 A, 16 KA, TPMCCB |
| 36 | 14.3) 150 A, 16 KA, TPMCCB |
| 37 | 14.4) 200 A, 16 KA, TPMCCB |
| 38 | 14.5) 250 A, 25 KA, TPMCCB |
| 39 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 15.1) 8 way, Double door |
| 40 | 15.2) 12 way, Double door |
| 41 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 16.1) 6 way (4 + 18), Double door |
| 42 | 16.2) 8 way (4 + 24), Double door |
| 43 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 17.1) Single pole |
| 44 | 17.2) Single pole and neutral |
| 45 | 17.3) Double pole |
| 46 | 17.4) Triple pole |
| 47 | 17.5) Triple pole and neutral |
| 48 | Supplying and fixing following rating, double pole, 240 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A |
| 49 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 25 mm |
| 50 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. 20.1) 1 or 2 Module (75mmX75mm) |
| 51 | 20.2) 3 Module (100mmX75mm) |
| 52 | 20.3) 4 Module (125mmX75mm) |
| 53 | 20.4) 6 Module (200mmX75mm) |
| 54 | 20.5) 8 Module (125mmX125mm) |
| 55 | 20.6) 12 Module (200mmX150mm) |
| 56 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 57 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS: 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI ≥80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness ≥ 1.20 mm)(a) 18 - 22 watt |
| 58 | (b) 36 watt |
| 59 | LED Panel light 2x2 ft. (System lumen efficacy =105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5°C to 40°C, internal surge protection of 2. 5 KV with Short & Open circuit protection, THD < 10%, P. F. =0. 95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1. 5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy =105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0. 50 mm) (a) 36 watt |
| 60 | Supplying, installation, testing & commissioning of LED surface mounted 10 watt IP66 (waterproof) glarefree, pressure die cast aluminium housing with unbreakable polycarbonate diffuser bulk head fitting. Total system Lumen of 10W LED should be 550 or above in cool day light (5700K to 6500K), power factor>0.95, CRI>75. complete with all accessories as required i/c connections with 1.5 sq. mm PVC copper wire etc. as required. |
| 61 | LED Panel light 1x4 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 1x4 ft., of following body material and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI ≥80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).(a) 36 watt |
| 62 | Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI ≥80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast/ Extruded aluminium Body including trim26.1) 8-10 watt |
| 63 | 26.2) 18 watt |
| 64 | Supplying & fixing of 25 mm Aluminium Conceal Profile with LED flexible strip light of warm white of 24 watt per 5 mtr. with driver complete with connetion, testing etc. complete as required. |
| 65 | Brush Less Direct Current (BLDC) MotorSupplying, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as required.(a) 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 66 | Supplying, Installation, Testing and Commissioning of 400 mm Sweep wall Fan suitable for 230 V 50 Hz Ac Supply complete with all accessories on existing wall etc. complete as required. |
| 67 | Supplying, installation, testing and commissioning of 250 mm sweep fresh air fan working on 230 +/- 10 V single phase 50 Hz Frequency complete with shutter in existing hole of suitable size making good the same i/c connections, interconnections etc. complete as required. |
| 68 | Supplying & drawing of following size of PVC insulated &pvc sheathed copper conductor round multicore flexible cable for indoor to outdoor and upto nearest power point i/c providing suitable copper lugs connection etc as required.(a) 3 x 1.5 sq.mm |
| 69 | (b) 3 x 4 sq.mm |
| 70 | Supply, Installation, Testing and Commissioning of Air Cooled HI Wall split type Air conditioners complete with Indoor unit (IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cut off and50 hz, 1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll /rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS694 or IS 9968 temperature sensing control IS/ International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS :1391 Part II 2023. The system shall be able to operate up to 50 Degree C (out door ambient temperature).Inverter Type - Hot & ColdInverter Type - Cooling only(a) 1.5 TR with 5 Star BEE Rating |
| 71 | Supplying and fixing of M.S. outdoor, floor/ wall mounting powder coated stand suitable for 1.5/2.0 Ton capacity split type A.C. outdoor unit complete as required. |
| 72 | Providing &Laying of refrigerant copper piping of size 1/4\\" or 3/8\\" & 5/8\\" diameter from indoor unit to outdoor unit of split type Air Conditioner unit along with 4 core 2.5 sq.mm PVC insulated and PVC sheathed flexible copper conductor cable including 20 mm size of cotton thread ribbed PVC flexible pipe from drip tray of Air Conditioner unit to drain pipe along with necessary support complete etc all as per Direction of Engineer-in-charge. |
| 73 | Supplying & drawing of 3x4 sqmm size of PVC insulated &pvc sheathed copper conductor round multicore flexible cable for indoor to outdoor and upto nearest power point i/c providing suitable copper lugs connection etc. as required. |
| 74 | Providing & fixing of 25 mm dia (SDR-13.5) UPVC heavy duty white colour drain pipe of with necessary fitting such as nipple, reducer, clamp on surface / recess i/c cutting the wall and making good the same complete as required. |
| 75 | Supplying, installation, testing & commissioning of Air Purifier having Air Multiplier Technology, covers uptoa area of 80 sqm, combine intelligent sensing with an advanced HEPA H13 filtration system captures gases2, pollutants and viruses, captures viruses and 99.95% of pollutants as small as 0.1 microns³, control using the link app and compatible voice services suitable to operate on single phase 240 Volts 50 HZ AC supply etc. complete as required. |
| 76 | Supplying, installation, testing & commissioning of 60 watt insect killer having 2 x 20 watt lamps made out of stainless steel, suitable for pest control for flies, insects, mosquitoes in covering area of 700-800 sq.ft. with protection grill etc. complete as reqd. |
| 77 | Supplying, installation, testing & commissioning of Air Purifier for an area coverage upto 670 sq. Ft., having a Pre-filter, Activated Carbon Filter, True HEPA H13 Filter, and Plasma filtration to remove up to 99.97% of dust and particulate matter as small as 0.1 μm. Air purifier should be capable to control with smart phone applications and suitable to operate on single phase 240 Volts 50 HZ AC supply etc. complete as required. |
| 78 | Supplying and fixing of 9 Fins Oil Filled Room Heater (ISI marked) with 3 possitions wattage Min-800W to Max-2000W, adustable thermostat, PTC heating element, over heat protection, castor wheels suitable for operation on 230V, 50Hz, single phase AC supply complete with testing etc. as required. |
| 79 | Supplying, installation, testing & commissioning of 800 watt Rod type quartz heater suitable for operation on 230V, 50Hz, single phase AC supply complete with testing etc. as required. |
| 80 | Supplying, installation, testing & commissioning of 2000 watt heat convector with two fan speed setting suitable for operation on 230V, 50Hz, single phase AC supply complete with testing etc. as required. |
| 81 | Less for credit of old dimantle material i.e. copper wire, conduit, MCB, LED light fittings, fans, copper cable/pipe, AC, air purifier, insect killer, oil heater etc. under buyback arrangement etc. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 1 dayTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender