Tender For Construction Of 04 Nos 400 Kl And 02 Nos 600 Kl Flood Pumping Stations Of Chamta From Iim Road To Shaheed Path And Annual Maintenance And Maintenance Work Of 05 Years At Gomti Nadi Banks Or 06 Different Places. (Part-A)
Tender Overview
Project Description
Tender for Construction Of 04 Nos 400 Kl And 02 Nos 600 Kl Flood Pumping Stations Of Chamta From Iim Road To Shaheed Path And Annual Maintenance And Maintenance Work Of 05 Years At Gomti Nadi Banks Or 06 Different Places. (Part-A)
BOQ
| Sl. No. | Item Description |
| 1 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :, 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources). |
| 2 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :, Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 3 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement, All works above plinth level upto floor V level, Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 4 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement, All works upto plinth level, Concrete of M30 grade with minimum cement content of 350 kg /cum |
| 5 | Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in anover all rates) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 6 | Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement., 20 mm cement plaster |
| 7 | Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer., Providing & Fixing of Door/ Windows Grill |
| 8 | 12 mm cement plaster of mix :, 1:6 (1 cement: 6 fine sand) |
| 9 | Mild steel or iron work of small sizes and sections such as holding down bolts, hold fast tierods, gratings etc. (when not included in an over all rates) wrought to required from including supply of steel and its wastage including cost of bolts, nuts if required for and welding, grinding and making holes as required complete. Z-Section steel windows. (DSR 10.25.2) |
| 10 | Providing and fixing angle iron frames for doors, windows and ventilators of mild steel Angle sections of size 35x35x5 mm, joints mitred and welded by angle iron 35x35x5 mm or 35x 5 mm flat pieces to the existing T-iron frame or to the wall with dash fastener, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer, all complete as per the direction of Engineer-In-charge |
| 11 | Finishing walls with water proofing cement paint of required shade :, Finishing walls with water-proofing on cement paint of approved make such as super snowcem. durrocem, robiacem, guttucem, supercem quality and of required shade on undecorated wall surfaces (two coat) overone and including one coat white cement primer to give an even shade after thoroughly brushing the surface to powdered materials including curing and cost of all materials |
| 12 | Painting on G.S. sheet with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :, Painting two coat over priming coat (but including cost of priming coat) on steel and other metal surfaces up to 10 cm. width or girth or small acies not exceeding 0.10sqm in area white superior synthetic enamel such as LUXOL3 Hi-gloss apcolite superla:, DULUX specified brushing to give an even shade and including cleaning the surface of all dirt dust and other foreign maiter sand papering and stoping including cost of all itaterials labour tools and plants etc required for proper 2 completion of the work |
| 13 | Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour., Distempering (Two coat) with oil bound distemper of approved brand and manufacture & of required shade on undecorated wall surface to give an even shade over & including a priming coat with cement primer of approved brand & manufacture such as Berger, J&N, Shalimar, Asian paints after thoroughly brushing the surface free from mortar droppings & other foreign matters & also including preparing the surface even with plaster of paris or approved synthetic material & sand papered smooth including cost ofall materials. (For Internal wall surface) |
| 14 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm(thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement :4 Coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including pointing the joints with white cement and matching pigment etc.,., complete. |
| 15 | Centering and shuttering including strutting, propping etc. and removal of form for :, Suspended floors, roofs, landings, balconies and access platform |
| 16 | Centering and shuttering including strutting, propping etc. and removal of form for :, Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 17 | Centering and shuttering including strutting, propping etc. and removal of form for :, Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts |
| 18 | Supply, Transportation by mechanical means and spreading , levelling and compaction of Earth inside Campus lead upto 15 km distance |
| 19 | Fencing with R.C.C. post placed at required distance, embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post one side only, provided with horizontal lines and two diagonals of barbed wire weighing 9.38 kg per 100 metres (minimum), between the two posts fitted and fixed with G.I. staples on wooden plugs or G.I. binding wire tied to 6 mm bar nibs fixed while casting the post (cost of R.C.C. posts, struts, earth work and concrete to be paid for separately) :- Payment to be made per metre cost of total length of barbed wire used., With G.I. barbed wire |
| 20 | Earth work in excavation by mechanical means (Hydraulic excavator) manual means over areas (exceeding 30cm in depth. 1 5m in width as well as 10 sqm on plan) including disposal of excavated carth, lead upto Som and lift upto 1.5m, disposed earth to be levelled and neatly dressed. (Analysis Rate) |
| 21 | Earth work in excavation by mechanical means (Hydraulic excavator) manual means over areas (exceeding 30cm in depth. 1 5m in width as well as 10 sqm on plan) including disposal of excavated carth, lead upto Som and lift upto 1.5m, disposed earth to be levelled and neatly dressed. (Analysis Rate) 1.50 to 3.0 Mtr |
| 22 | Earth work in excavation by mechanical means (Hydraulic excavator) manual means over areas (exceeding 30cm in depth. 1 5m in width as well as 10 sqm on plan) including disposal of excavated carth, lead upto Som and lift upto 1.5m, disposed earth to be levelled and neatly dressed. (Analysis Rate) 3.0 to 4.50 |
| 23 | Earth work in excavation by mechanical means (Hydraulic excavator) manual means over areas (exceeding 30cm in depth. 1 5m in width as well as 10 sqm on plan) including disposal of excavated carth, lead upto Som and lift upto 1.5m, disposed earth to be levelled and neatly dressed. (Analysis Rate) 4.50 to 6.0 Mtr |
| 24 | \\"Supply, Installation Testing & Commissioning of Electric sewage VT Propeller Axial Flow Pumping plant including level sensor for auto operation, column assembly ,Suction Stainer. Tee ,Reducer, coupling with all connected Equipment etc all Complete (Kirloskar, Flowmore or Equivalent Make, relevant to IS/B3 Standard )13000 LPM capacity ,12 M head , complete in all respect. Pumpset Data Sheets Liquid - Storm Water/Flood Water Sp. Gravity - 1.10 Pump Capacity - 13000 lpm Pump Size - 12'' Pump Speed - 1500 RPM Dischage - 780 m3 Bowl eff. - 82% Lubrication - water Motor Rating - 45 KW Speed - 1500 RPM Make - ABB Voltage - 415 frq - 50 Hz. T & P - vertical - Solid shaf-1 Load Detail Pump - 2000 KG (Approx) Motor - 400 KG (Approx) Details of discharge flange as per IS - 1538 (300 NB) MOC Casing :1.5-2% NiCI FG 260 Impeller :CF8M OR latest advance material, line-impeller Shaft/coupling-SS410, Col. pipe, dischare hood: MS\\" \\" No - Holes - 20 Dia of holes - 28 thickness - 32 mm Temp - deg C - Amb Viscosity - poise - Water Pump Type - Axial Flow Type No. of Stages - No's - 2 Sync. Speed - Rpm - 1500 Pump Efficiency Minimum - % - 86.5 Driver Type - RC Cooled Engine/VSS VI Mounting Motor Constructional Details Impeller Type - Open Type lmpeller Gland Packed/Mech Seal - Gland Packed Line Shaft bearing Lubrication - Self Water Lubrication Sump Depth - M - 6M Pump Setting Length (Stainer to sole plate) - 5.80 M - Approximate Location of Delivery Branch - Below Floor Discharge. Type of Column Type of Column Joint - Flanged Material of Construction Casing - 1.5-2% NICI CI FG 260 Impeller Line Shaft - SS410 Impeller Shaft - SS410 Shaft Coupling - SS410 Stainer - Steel Shaft Sleeve - SS410 Neck Rings - CF8 Sole Plate - MS Column Pipe - MS Discharge Head \\" \\"Flange Drilling - Mfg. Std. Painting - As per Mfg. Std. Scope of Supply Pump - as per above Stainer - as per above\\" |
| 25 | \\"Supply, Installation Testing & Commissioning of LT Starter Panel (mains and stater ) suitable for above Pump with required Civil work and Complete in all respect. Supply of LT panel with Three incoming ( 1 CSS +1 DG set) , AMP panel, APFC panel , Phase reversal and all safety measeres and 6 outgoing for pump, EOT crane, light & fan, for spare of PPT, Suitable capacity of Fully Automatic Star Delta Starter of MAKE ABB/ L&T/ Eqv. , comprising with following item as per given below. l. Contactor of suitable ratings. m. TOR of Suitable ratings. n. PB Switches o. Dual Amp & Voltmeter p. Amp meter Selector Switch q. Toggle Switches r. Indicating Lamps Phase Failure s. Phase reversal relay t. Single phase preventer u. Capacitor of suitable ratings. v. GSM\\" |
| 26 | \\"\\"\\"Supply, Installation Testing & Commissioning of 9 Nos. LT Starter & Motor Control Panel complete with two Incoming Sources (1 CSS + 1 DG), AMF/ATS arrangement, APFC Panel, nine pump outgoings, EOT crane outgoing, lighting/fan outgoing, spare outgoing, fully automatic Star-Delta starters and all associated protection, control and metering components as per technical specification. technical specification. Suitable capacity of Fully Automatic Star Delta Starter of MAKE ABB/ L&T/ Eqv. , comprising with following item as per given below. l. Contactor of suitable ratings. m. TOR of Suitable ratings. n. PB Switches o. Dual Amp & Voltmeter p. Amp meter Selector Switch q. Toggle Switches r. Indicating Lamps Phase Failure s. Phase reversal relay t. Single phase preventer u. Capacitor of suitable ratings. v. GSM\\"\\"\\" |
| 27 | Supply, Installation Testing & Commissioning of NR Valve special design for sewage purpose. Flanged end as per IS : 5312 Body, Cover-CI IS : 210, Gr. FG260 Door-CI IS : 210 Gr. FG260 Body Ring - bronze IS : 318 Gr. LTB2 Door Face - Natural Rubber Hinge Pin - SS ASTM A276 Type 410 Fasteners - CS IS : 1367, CL - 4.6/4.0 Gasket-Natural Rubber Flange Drilling - IS : 1538, Table 4 & 6 300 mm dia. |
| 28 | Supply, Installation Testing & Commissioning of NR Valve special design for sewage purpose. Flanged end as per IS : 5312 Body, Cover-CI IS : 210, Gr. FG260 Door-CI IS : 210 Gr. FG260 Body Ring - bronze IS : 318 Gr. LTB2 Door Face - Natural Rubber Hinge Pin - SS ASTM A276 Type 410 Fasteners - CS IS : 1367, CL - 4.6/4.0 Gasket-Natural Rubber Flange Drilling - IS : 1538, Table 4 & 6 600 mm dia. |
| 29 | Supply, Installation Testing & Commissioning of Cast Iron Rising Spindle Sluice Valve Flanged end as per IS : 14846 Body, Cover - CI IS : 210, Gr. FG260 Door-CI IS:210, Gr. FG260 Body Ring-Bronze IS : 318 Gr. LTB2 Door Face-Natural Rubber Hinge Pin - SS ASTM A276 type 410 Fasteners - CS IS : 1367, CL -4.6/4.0 Gasket-Natural Rubber Flange Drilling - IS : 1538, Table 4 & 6 300 mm dia. |
| 30 | Supply, Installation Testing & Commissioning of Cast Iron Rising Spindle Sluice Valve Flanged end as per IS : 14846 Body, Cover - CI IS : 210, Gr. FG260 Door-CI IS:210, Gr. FG260 Body Ring-Bronze IS : 318 Gr. LTB2 Door Face-Natural Rubber Hinge Pin - SS ASTM A276 type 410 Fasteners - CS IS : 1367, CL -4.6/4.0 Gasket-Natural Rubber Flange Drilling - IS : 1538, Table 4 & 6 600 mm dia. |
| 31 | \\"Supply, Installation Testing & Commissioning Traveling crane supply of 10 Ton Capacity 6 Mtr. Mt 12 Mtr. Span traveling crane standard make capacity block extra with required material (Indent/Mints or Equivalent make and should be relevant to IS/BS standard) complete in all respect with required civil work and complete in all respect. 1 . Type - Single Girder Crane for indoor application. 2. Type of Application - The Pump house. 3. Class of Duty - M5 as per IS 3177. 4. Standards - The crane to be Devid Manufactured and tested in accordance with the latest revisions & eshitions of IS IT IS 3177 and other relics ani pode and standards in medicured under Paragraph 5.0. 5. Location - Indoor. 6. Capacity SWL - 10 Tonnes. 7. Height of track rail - 5.9 Mtr above floor level (refer sketch) 8. Span - 9 Mtr. 10. Clearance height above the gantry rail - 1100 mm. 11. Cross trave of Crane - 9 Mtr. 12. Speeds, hoisting/lovering - 266 m/min (approximately), Cross travel - 17.0 m/min (approximately), Long Travel - 20.0 m/min (approximately), 13. Bridge Girder - Bridge girder shall be RSJ type with rubber bullet Indian Standard hot rolled structura sections as per 808-1957 IS 1173- 1957 IS 1864-1963 IS 800-1962 IS 816 1956 Garder should the strong and rugged to withstand the most severe condonatios of loads/swester diferent working conditions The Bridge Girder shall be designed to love maximum deflectim of span 900 at SWL in order to have better structural indegrity Sufficunt space shall be provided for ease of maininanis. 14. End Carriage - Fabricated out of MS Plate or C Channel of saitabile size to farm box except for essential openings which should be renforced. End camages se be fitted with substantial safitty stops to prevent the crane from falling and should not lnterfere with removal of wheel. 15. - - . 16. Cross travel and Long travel wheel - 0.75 KW 2 drive for LT motor and 0.55 KW 2 drive for CT motor LT Wheels shall be Double Flanged and CT Wheels Single Flanged of EN 9 nutinal. The item should be machined and hardened to required hardness. The wheals to be mounted on anninction bearings and shall\\" \\" facilitare easy removal & replacement. 17. Hook - Shall be shank C type forged steel conforming to IS 15560 with spring loaded safety laich and mounted on thrust bearing for freely swiveling. 18. Wire rope - Fibre or Steel core 6x36 or 6x37construction as per IS-2266 of Usha Martin Make Diameter so be specified by supplier. 19. Quality of steel for wire rope - 1960 KN as per IS-2266. 20 No of rope falls supporting the load - 6 21. Factor of safety for the wire rope - Min 5. 22. Rope drum - Machined out of seamless pipe of adequate thickness with machined grooves for the wire rope. The length/Dia should be sufficient to wind the wire rope in one layer only when the drum is in the fully wound position. Drum shall be mounted on antifriction ball roller bearings. Rope Drum Dia to Wire Rope Dia Ratio of Min 22:1 shall be maintained while designing the Rope Drum. Rope should be guided by Heady Duty spring Loaded Cast Iron Wire Rope Guide. 23 Sheaves - Sheaves machined out of Cast Iron with adequate no of grooves to suit the no. of falls. 24 Gear boxes - All gear boxes in the crane shall be rugged and totally enclosed im dustproof construction filled with oil Straight or helical spur gear should be used for all motions (worm, bevel gears should not be used) All gears shall be of EN9 and pinions of EN-24 with suitable hardness, hardened with machine cut or hobbed teeth, metric module only. The long travel mechanism shall be driven by two separate gearboxes at both ends of the span. All the extended shaft and end covers on gear box shall be provided with good quality oil seal to prevent leakage. Hoist should be provided with Heavy Duty Planetary Gearbox and CT/LT motion shall be provided with Helical Gearboxes All Gearboxes should be brought out from reputed manufacturers. No self-assembled fabricated gearboxes to be used by crane supplier. 25. Coupling - Gear couplings at all places, if required. 26 Bearings - Antifriction type Ball roller bearings of SKF/FAG URB/NTN/TIMKEN/RHP (NSK) make. \\" |
| 32 | Supply, Installation Testing & Commissioning. 300 mm Dia MS rising mains of 6.0 mm wall thickness including coupling and laying for discharge of the storm of the pumping plant including excavation laying of the pipe etc. 1.0 to 1.50 Mtr. deep into the underground trench excavated in the existing road etc all comp. as per direction of E/inch. as per the unit rate analysis. |
| 33 | Supply, Installation Testing & Commissioning. 600 mm Dia MS rising mains of 6.0 mm wall thickness including coupling and laying for discharge of the storm of the pumping plant including excavation laying of the pipe etc. 1.0 to 1.50 Mtr. Deep into the underground trench excavated in the existing road etc all comp.with required civil work and complete in all respect |
| 34 | Supply, Installation Testing & Commissioning of 400 KVA DG Set , Alternator Water Cooled with Standard Panel, Acoustic Enclosure and Base Frame with required civil work and complete in all respect complying latest Central pollution Control Board Guidlines (CPCB-IV) MAKE KIRLOSKER/STERLING/MAHINDRA/EQV. |
| 35 | Supply, Installation Testing & Commissioning of 500 KVA DG Set , Alternator Water Cooled with Standard Panel, Acoustic Enclosure and Base Frame with required civil work and complete in all respect complying latest Central pollution Control Board Guidlines (CPCB-IV) MAKE KIRLOSKER/STERLING/MAHINDRA/EQV. |
| 36 | \\"Supply, Installation Testing & Commissioning of 630 kva CSS transformer complete in all respect. Particulars (a) Designation (b) Transformer Location - Out Door (c) Degree of protection - IP -55 (as per IS : 2147) (d) Rated output - 01 No 630 KVA (e) No load transformation ration 11/0.433 KVA - 1 No (f) Number of Phase - Three (g) Rated frequency - 50 Hz. (h) Number of windings/ (i) Method of Connection (ii) HV winding - Delta (iii) LV winding - Star (i) Vector group - DYN - II (j) Impulse (peak) (k) Power frequency (Dry and wet) (l) Bushing (i) Voltage Classes HV Line LV Line (ii) Impulse (iii) Power Frequency with stand HV LV \\" |
| 37 | \\"Supply, Installation Testing & Commissioning of 750/800 kva CSS transformer complete in all respect. Particulars (a) Designation (b) Transformer Location - Out Door (c) Degree of protection - IP -55 (as per IS : 2147) (d) Rated output - 01 No 630 KVA (e) No load transformation ration 11/0.433 KVA - 1 No (f) Number of Phase - Three (g) Rated frequency - 50 Hz. (h) Number of windings/ (i) Method of Connection (ii) HV winding - Delta (iii) LV winding - Star (i) Vector group - DYN - II (j) Impulse (peak) (k) Power frequency (Dry and wet) (l) Bushing (i) Voltage Classes HV Line LV Line (ii) Impulse (iii) Power Frequency with stand HV LV \\" |
| 38 | \\"Supply, Installation Testing & Commissioning of HT VCB/Panel for 630 kva CSS transformer complete in all respect. Particulars (a)11kv 800A 26.3KA HT VCB (b) Overcurrent & earth fault relay (c) Master Trip Relay (d) TRIP CIRCUIT SUPERVISION RELAY (e) Three Phase ammeter, Acc. CI::1.0 (f) Three Phase voltmeter, Acc. CI::1.0 (g) Multifunction meter (h)Fixed type Voltage Transformer 100VA/v3/110V/3 (i) Current trasnformer resin cast dual core (j) 20A fuse base for bolted type fuse link, Size :F1 (k) 6A off set clip in type HRC fuse link, Size:F1 (l) 6A 1P 10KA, C-curve MCB (m) Auxilary Relay (n) Indicating light (o) Panel led lamp 150 mm (p) Door limit switch (q) Space heater 100W/230V (r) Thermostat (s) TNC 25A (t) Control terminal Block (u) Power Pack 230V AC-24VDC 7AH (v) Emergency push button with NC Element \\" |
| 39 | Supply, Installation, Testing & Commissioning of MS Work Specify as per site requirment. |
| 40 | \\"UNDER GROUND CABLES Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. \\" 240 Sqmm 3.5 Core |
| 41 | \\"UNDER GROUND CABLES Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. \\" 120 Sqmm 3.5 Core |
| 42 | Supply and burring of safe Earthing electrode pf T-39 Cu Copper coated, Length up to 3000mm, outer pipe 76.03 x 3.2 inner pipe 42.4 mm x 2.6 mm, terminal Dia 12mm, coating 80- 100 micro filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs active soil (BFC) capable of reducing the soil restively with good mixture of retaining capacity along with 30 CM square CI Frame with hinged cover & masonry housing. (from electrode terminal to switch board cost of 25x3 copper strip will be extra. |
| 43 | Supply/fabrication and Erection of 11 KV Double Pole Cable Exposure D/C complete with 410 SP-55 11 mtr long ST Pole-2 Nos, 11 kv pin insulator with pin and nut-9 nos, top channel 100x50 mm, MS angle 65x65x6mm, LT XLPE cable AL. 1x240sqmm-18mtr, danger board with clamp-2 nos, barbed wire, pole fencing-2 nos, aluminium lug- 12 nos, holding MS clamps-12 nos, nut bolts etc icluding painting of pole with aluminium paint over red oxide primer all complete as per UPPCL specification |
| 44 | S\E of 11 KV TPMO switches on poles including handle rod etc. complete in all respects as approved by E\I. (Previous Sanction Rate) (PS Rate) |
| 45 | S\E of 11 KV D.O. fuse set on poles complete in all respects as per approval of E\I. (Previous Sanction Rate) (PS Rate) |
| 46 | Supply and Laying of 80 mm dia G.I. pipe for the purpose of cable on the run pole through this G.I. pipe from level as cable carrier pipe should be tied with 2Nos. 50x6mm flat iron clamp with pole as per direction of E/I |
| 47 | Supply and laying of 185 sq. mm 3 core standered aluminium conductor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) II KV grade at a depth of 900 mm below ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks on sides and on top put across. The armouring of cable shall be properly connected with earth conductor by clamps etc. (Supply Rs 1045 + Laying Rs. 910 = Rs. 1955 ) |
| 48 | supplying and making 185 sqmm 3 Core outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required all complite as per direction of E/Ic. |
| 49 | Supply & fixing of 9 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 155 mm and base plate 12mm thik) having 3mm thikness with Double arm bracket (1 Mtr length each ) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect. |
| 50 | S/F of LED Street Light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 140 to 150 watt. Confirming to IP 66 protection having company LOGO engraved complete in all respect including labour as per direction of E/I. SI. No. 1425/2018 Cat-AAA. 15400-16500 system lumens High Power LED with Lenses, >1101m/W, PF70, Potted driver set (Not Circuitory) Phase to Phase Protection at 440V & > 300V auto cut and re-start feature, with 5 years warrantee. Proper completion of work as per direction of E/I - CAT-AAA |
| 51 | \\"Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C.. Sch. No. 1.10.3 |
| 52 | \\"Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. Sch. No. 1.12 |
| 53 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire. Sch. No. 1.14.1 |
| 54 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. Sch. No. 1.25 |
| 55 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. Sch. No. 1.32 |
| 56 | Supplying and fixing brass batten/ angle holder including connection etc. as required. Sch. No. 1.34 |
| 57 | Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. Sch. No. 1.35 |
| 58 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C. Sch.No. 1.55.3 |
| 59 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). Sch. No. 2.4 (A) 4 way (4 + 12), Double door, Sch. No. 2.4.1 |
| 60 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (A) Single Pole. Sch. No. 2.10.1 |
| 61 | Supply of 12W Extruded aluminium batten available in 2ft run length with multiple lumen packages and suitable for surface, wall & conduit ounting (with accessories). similar to Philips Type HSN Code MRP (INR) BN 021 LED12S 6500 PSU GR or equivalent. MR (RA-3) |
| 62 | Supply of 22W Extruded aluminium batten available in 4ft run length with multiple lumen packages and suitable for surface, wall & conduit ounting (with accessories). similar to Philips Type HSN Code MRP (INR) BN 021 LED22S 6500 PSU GR or equivalent. MR (RA-4) |
| 63 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. 19.1 |
| 64 | Supply of plastic body ventilation fan, 250mm sweep continously rated highly efficient similar to Crompton Cat. Efficio\\" or equivalent. MR (RA-6) |
| 65 | Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings andfixtures complete, including cutting and making good the walls and floors wherever required :, W.C. pan with ISI marked white solid plastic seat and lid |
| 66 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:, White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap |
| 67 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 68 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931:, 15 mm nominal bore. |
| 69 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes., 110 mm diameter |
| 70 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion., Coupler, 110mm |
| 71 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC rain water pipes conforming to IS 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion., Shoe (Plain), 110 mm Shoe |
| 72 | Control panel board with starter 32 amp. Main switch kit-kat Etc. |
| 73 | K.S.B. make Submersible pumpset 5.0 H.P. discharge 600 L.P.M. |
| 74 | 80 mm dia M.S. Column Pipe \\"C\\" Class (3.0m) |
| 75 | 80 mm dia M.S. Column Pipe \\"C\\" Class (1.5m) |
| 76 | 80 mm dia M.S. Column Pipe \\"C\\" Class (1.0m) |
| 77 | 80 mm dia C.I. D/F Sluice valve I.S.I |
| 78 | 80 mm dia C.I. D/F N.R.V. I.S.I |
| 79 | 80 mm dia C.I. D/F Band |
| 80 | 80 mm dia M.S. Clamp |
| 81 | 80 mm dia Rubber Packing |
| 82 | Flat copper Cable 1x3x6.00 mm2 |
| 83 | Nut, Bolt, Washer |
| 84 | Motor safety clamp |
| 85 | Cartage up down |
| 86 | Pump Guard |
| 87 | Installation of Pump-set |
| 88 | Supply and Installation of 1KW Mud pump in Sump well for cleaning of sunken part of sump after rainy season, including Piping, fitting and panel |
| 89 | Operation of 1st Year (0.5 % on Electrical Part) |
| 90 | Operation and Maintanance of 2nd Year (1 % on Electrical Part) |
| 91 | Operation and Maintanance of 3rd Year (1.25% on Electrical Part) |
| 92 | Operation and Maintanance of 4th Year (1.5 % on Electrical Part) |
| 93 | Operation and Maintanance of 5th Year (2 % on Electrical Part) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
TodayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 21 daysTender Documents