Tender For Constructing 2 Nos Of Additional 110Kv Bays In 110Kv Substation Kizhakkambalam - Electrical Works
Tender Value
24.63 Lakhs
Estimated cost
Bid Submission
08 Dec 2026
15 days left
EMD
50000
Bank guarantee accepted
Document Fee
5900
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ernakulam → Kerala
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Constructing 2 Nos Of Additional 110Kv Bays In 110Kv Substation Kizhakkambalam - Electrical Works
BOQ
| Sl. No. | Item Description |
| 1 | Welding the ground electrode with the main electrode , after cleaning the surface neatly. Charges includes cost of low hydrogen content DC electrodes (No. E7018), hire charges of DC arc welding set, tools and plants, current charges, labour charges for holding MS rod in position and applying two coats of anti corrosive paints at the welded joints etc. complete as per the directions of departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 2 | Welding one end of the bended GI strip of size 50x6mm with the riser of the already laid earth mat, welding 150mm in length, 6mm thick on both sides & end of the strip & other end of the strip with yard structure at 2 points 50mm apart each welding points having 50mm length and 6mm thick on both sides & end of the strip including the charges for connecting the strip with structure using bolted joints as per the directions of the department officers. Charges includes hire charges of DC arc welding set, current charges, cost of low hydrogen content DC arc welding electrodes(No.E7018) cost of anti corrosive paint etc. complete. (cost index(e) : 1.3132 included in Rate) |
| 3 | Welding overlapping joints of 50x6mm GI strip with 50mm long, 6mm thick welding on all three sides after doing 2 Nos. bolted joints at the centre as specified after cleaning the surface. Charges includes hire charges of DC arc welding set, current charges, cost of low hydrogen content DC arc welding electrodes( No.E7018) cost of anti corrosive paint etc. complete. (cost index(e) :1.3132 included in Rate) |
| 4 | Preparing wiring schedule per transformer / feeder bay of 110 or 66 kV with details of type of cable core and colour ferrule No and terminal no of equipments/panels including giving full details in A4 sheet with computer print providing outer border line and sheet no etc. and supplying in the shape of book with special binding etc. and assisting the departmental officers at the time of relay testing and commissioning (cost index(e) : 1.3132 included in Rate) |
| 5 | Additional copy of the wiring schedule with spiral binding (cost index(e) : 1.3132 included in Rate) |
| 6 | Uncoiling 20/19 core 2.5sqmm, 12 core 4 sqmm control cable (Armoured or unarmoured) from cable drums cutting to required length and laying through trench/pipe/cable tray grouping the same neatly using cable tie and carefully including for providing loop wherever necessary and providing cable marker at both ends of cable as per direction of departmental staff at site. (cost index(e) : 1.3132 included in Rate) |
| 7 | Uncoiling 12/7/6 core 2.5 sq mm control cable (armoured and unarmoured) from cable drums and cutting to required length and laying through trench/pipe/cable tray grouping the same neatly using cable tie and carefully including for providing loops wherever necessary and cable marker, at both ends of cable as per direction of departmental staff at site.(cost index(e) : 1.3132 included in Rate) |
| 8 | Uncoiling 5/4/3/2 core 4sqmm control cable(armoured or unarmoured) from cable drums and laying through trench/pipe/cable tray neatly and carefully including for providing loops wherever necessary and cable marker at both ends of cable as per direction of departmental staff at site. (cost index(e) : 1.3132 included in Rate) |
| 9 | Uncoiling 4/2 core 2.5sqmm control cable (armored or unarmored) from cable drums and cutting to required length and laying through trench/pipe/cable tray neatly and carefully including for providing loops wherever necessary and cable marker at both ends of cable as per direction of departmentalstaff at site. (cost index(e) :1.3132 included in Rate) |
| 10 | Termination of cables in panel by using cable glands of fixing the cable rigidly by any means as per direction of departmental staff at site charges include for providing necessary suitable hole in the gland plate etc. for 20/19 core2.5sqmm cable/12 core 4 sqmm cable (using gland of size 28-32mm) (cost index(e) : 1.3132 included in Rate) |
| 11 | Termination of cables in panel by using cable glands of fixing the cable rigidly by any means as per direction of departmental staff at site charges include for providing necessary suitable hole in the gland plate etc. for 12/7/6 core 2.5 sqmm cable (using gland of size 25mm). (cost index(e) : 1.3132 included in Rate) |
| 12 | Termination of cables in panel by using cable glands of fixing the cable rigidly by any means as per direction of departmental staff at site charges include for providing necessary suitable hole in the gland plate etc. for 4/2 core 2.5 sq mm cable/4/2 core 4 sq mm cable (using gland of size 16-22mm). (cost index(e) 1.3132 included in Rate) |
| 13 | Doing termination of all sizes of PVC insulated copper control cable 2.5 mm², pealing, providing number and letter ferrules in the wire, stripping ends, crimping with suitable lugs and connecting to the terminals in the panel board and marshalling kiosk etc., neatly and carefully including cost of copper sockets and ferrules as per the direction of Departmental Officers at site. (cost index(e) : 1.3132 included in Rate) |
| 14 | Providing droppers and connecting to lines / equipments or jumper between two buses without suspension insulators using ACSR Moose/ Kundah/ wolf Single conductor at both ends with compressed/ bolted ends including uncoiling and cutting of conductor as per the direction of departmental officers. (For one phase) (cost index(e) : 1.3132 included in Rate) |
| 15 | Doing termination of all sizes of PVC insulated copper control cable 4.0 mm², pealing, providing number and letter ferrules in the wire, stripping ends, crimping with suitable lugs and connecting to the terminals in the panel board and marshalling kiosk etc., using cable tie and cable tie neatly and carefully including cost of copper sockets and ferrules as per the direction of Departmental Officers at site. (cost index(e) : 1.3132 included in Rate) |
| 16 | Providing droppers and connecting to lines / equipments or jumper between two buses with necessary suspension insulators for 33kV/66kV/110kV/220kV using ACSR Moose/ Kundah/ wolf Single conductor at both ends with compressed/ bolted ends including uncoiling and cutting of conductor as per the direction of departmental officers. (For one phase) (cost index(e) : 1.3132 included in Rate) |
| 17 | Welding of overlapping joints for mat,riser lap joints with 32/25mm MS rod placed in trenches, having 150mm in length 6mm in thick on both sides of the rod and both ends of overlapped MS rods with 6mm welding thickness after cleaning the surfaces neatly. Charges includes cost of low hydrogen DC electrode (No. E7018), hire charges of DC arc welding set and tools and plants required, current charges including labour charges for holding MS rod in position and applying two coats of anti corrosive paints at the welded joints etc. complete as per the directions of department officers. (cost index(e) : 1.3132 included in Rate) |
| 18 | Laying LT/DC cables in trench including drawing through pipes wherever necessary. (cost index(e) : 1.3132 included in Rate) |
| 19 | Supplying aluminium cable tags punching number and alphabets up to 7 digits and binding to cable using copper wire including cost of all materials as per the direction of Board Officials at site. (cost index(e) : 1.3132 included in Rate) |
| 20 | Making of cable clamps using 25x 3 mm GI strip (hot dipped)as per no of cables in cable tray cutting and holing to required length and for fixing as per the direction of departmental officers at site including supply of suitable nut and bolts (cost index(e) : 1.3132 included in Rate) |
| 21 | Fixing all type of terminal connecting strip with terminal connectors in the marshalling box or panel board wherever necessary (terminal connecting strip will be supplied departmentally ) charges includes for providing necessary suitable hole etc complete as per direction of departmental staff at site. (cost index(e) : 1.3132 included in Rate) |
| 22 | Providing interconnection between equipments using ACSR Moose/ Kundah/ wolf Single conductor at both ends with compressed/ bolted ends including uncoiling and cutting of conductor as per the direction of departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 23 | Transporting by head load, the materials issued departmentally to the site from the place of storage and distribution to erection site. (Distance to be specified ) (cost index(e) : 1.3132 included in Rate) |
| 24 | Cutting of steel angle in yard structure erection (cost index(e) : 1.3132 included in Rate) |
| 25 | Drilling holes in yard structure (cost index(e) : 1.3132 included in Rate) |
| 26 | Welding charge for welding on iron parts using arc welding as per standards (cost index(e) : 1.3132 included in Rate) |
| 27 | Laying of departmentally supplied GI strip/Copper strip of suitable size including cleaning and neatly bending of strips ,cutting, removing of metal/earth in the yard and burying earth strip to the required depth re-doing the yard metalling as per the direction of the departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 28 | Cutting 32mm MS rod in required length etc complete as per the direction of the departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 29 | Bending 32mm MS rod for crossing cable trench/foundations/risers etc. (cost index(e) : 1.3132 included in Rate) |
| 30 | Driving down the ground electrode upto a depth of 3m from the already taken earth pit as directed by the departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 31 | Laying of earth mat of required size as specified using 40/32/25mm MS rod including levelling lowering and placing in trenches, complete as per the direction of departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 32 | Welding the nodal points (cross joints ) in the trenches at two sides to a thickness of 6mm after cleaning the surface neatly. Charges includes cost of low hydrogen DC electrodes (No. E7018), hire charges of DC weldingset and tools and plants required, current charges, labour charges for holding MS rod in position and applying two coats of anti corrosive paints at the welded joints etc. complete as per the directions of departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 33 | Stub setting for equipments in correct alignment using template, water level etc. in concrete foundation excluding cost of excavation, concreting and back filling but including grouting, anchoring etc. and removing stub setting template after the predetermined setting period etc. complete asper specifications and direction of departmental officers at site. (cost index(e) : 1.3132 included in Rate) |
| 34 | Setting up Foundation bolt in correct alignment using template or water level etc in concrete foundation excluding Cost of excavation, concreting and back filling but including grouting anchoring etc. and removing template after the predetermined setting period etc. complete as per specifications and directions of departmental officers at site (cost index(e) : 1.3132 included in Rate) |
| 35 | Erection of yard structures and assembling of columns and beams using bolt and nut including punching of holes. (cost index(e) : 1.3132 included in Rate) |
| 36 | Lifting , conveying and stacking cover slabs carefully from the trench/drains etc.without any damage to the trench/drain and other existing structures and placing the slabs back after executing works if any including all labour and other expenses (based on item 55.25-MORTH) (cost index(c) : 1.4445 included in Rate) |
| 37 | Fixing departmentally supplied marshalling kiosk in the existing PT/CT structure by making suitable fixing arrangements including cutting , welding, drilling holes etc as required. (cost index(e) : 1.3132 included in Rate) |
| 38 | Dismantling of existing erected yard structures and assembling of columns and beams by unbolting nut & bolt as per the direction of departmental officer (cost index(e) : 1.3132 included in Rate) |
| 39 | 50.18.9.10.1 Providing and fixing PVC pipes includings jointing of pipes with one step pvc solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer in Charge. 150 mm dia 6 Kgf/cm2 (cost index(c) :1.4445 included in Rate) |
| 40 | Erection of 1 No. 110/66KV CT/PT/CVT/CC/220KV NCT on the already erected structure of above 1.5m height after opening of crates at the place of storage, leading to site carefully keeping at vertically not allowing tilting from vertical position more than the specified angles, keeping lines and levels as per the direction of the departmental officers, including all labour charges, hire charges of tools & tackles etc. (cost index(e) : 1.3132 included in Rate) |
| 41 | Loading one 110/66KV CT / CVT / PT / CC from the place of its storage to department lorry using required lifting device without causing any damage to equipment and its parts. (cost index(e) : 1.3132 included in Rate) |
| 42 | Unloading one 110/66KV CT/PT/CVT/CC from department lorry to substation site using suitable lifting device and dragging to safe place without causing any damage to CT as per the direction of the department officers. (cost index(e) : 1.3132 included in Rate) |
| 43 | Erection of 1 No. 110/66KV LA/Post insulator on the already erected structure after opening of crates at the place of storage leading to site carefully, keeping lines and levels as per the direction of the departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 44 | Loading one 110/66KV LA from the place of its storage to department lorry, if required, after dragging up to 50M using suitable lifting device carefully without causing any damage to equipments and fastening in the lorry make it ready for transportation as per the direction of the department officers. (cost index(e) : 1.3132 included in Rate) |
| 45 | Unloading one 110/66KV LA from department lorry to substation site using suitable lifting device and dragging to safe place without causing any damage to LA as per the direction of the department officers. (cost index(e) : 1.3132 included in Rate) |
| 46 | Unpacking carefully and leading with an initial lead of 50 m, one set of 3 pole EHT110/66KV Circuit Breaker from the place of storage, including support structure , mechanism box compressor, pipe lines etc. to site , cleaning and erecting on foundation using suitable lifting tools, after disassembling necessary parts if required, to lines and levels and assembling all the parts , connecting mechanism etc. in complete shape and making ready for commissioning as per the direction of departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 47 | Loading one set 110/66kV Circuit breaker with its interrupting poles, mechanism box, structures and all its accessories safely without causing any damage using necessary lifting devices to department lorry and fastening fortransportation. (cost index(e) : 1.3132 included in Rate) |
| 48 | Unloading one set 110/66kV Circuit breaker with its interrupting poles, mechanism box, structures and all its accessories safely without causing any damage using necessary lifting devices from department lorry and fastening for transportation. (cost index(e) : 1.3132 included in Rate) |
| 49 | Erection of one set 110/66KV Bus Isolator on the already erected structure including opening crates and conveyance of all accessories from the place of storage to the place of erection to lines and levels, erection of mechanism box , checking operation and aligning properly, including cutting, welding etc. complete as per the direction of departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 50 | Loading one set 110/66KV Bus Isolator with its insulator stacks, supporting channels, connecting pipes, isolating rods, mechanism box, structures and all its accessories safely without causing any damage using necessary lifting devices to department lorry and fastening for transportation. (cost index(e) : 1.3132 included in Rate) |
| 51 | Unloading one set 110/66KV bus isolator with its insulator stacks, supporting channels, connecting pipes, isolating rods, mechanism box, structures and all its accessories safely without causing any damage using necessary lifting devices from department lorry to substation compound and stacking properly for safe storage. (cost index(e) : 1.3132 included in Rate) |
| 52 | Erection of one set 110/66KV line Isolator on the already erected structure including opening crates and conveyance of all accessories from the place of storage to the place of erection to lines and levels including erection of mechanism box checking operation and aligning properly as per the direction of departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 53 | Loading one set 110/66KV Line Isolator with its insulator stacks, supporting channels, connecting pipes, isolating rods, earth switches, mechanism box, structures and all its accessories safely without causing any damage using necessary lifting devices to department lorry and fastening for transportation. (cost index(e) : 1.3132 included in Rate) |
| 54 | Unloading one set 110/66KV Line isolator with its insulator stacks, supporting channels, connecting pipes, isolating rods, earthing rods, mechanism box, structures and all its accessories safely without causing any damage using necessary lifting devices from department lorry to substation compound and stacking properly for safe storage. (cost index(e) : 1.3132 included in Rate) |
| 55 | Uncoiling, paving out, stringing and fixing of bus bar using ACSR Kundah / Moose single conductor for one phase of 66/110KV bus of span up to 30M by cutting the conductor to sufficient length, crimping using compressor / bolting the two ends, washing, cleaning and drying the insulator discs, fixing the conductors to the yard structure with sufficient tension using string of insulators and hardware complete. at both ends, fixing of arcing horns including transportation of materials from the stockyard to the site under the supervision and direction of department staff at site. (All materials will be supplied departmentally at free of cost). (cost index(e) : 1.3132 included in Rate) |
| 56 | Stringing and fixing earth wire of size 7/9, 7/10 or 7/3.15 between top of the columns and to terminal tower at 33/66/110/220KV substations with compressed / bolted ends at proper tension including uncoiling and cutting of conductor , jumpering, giving earth bond connections by drawing the end of the conductor through the columns, jointing wherever necessary providing back stays at the time of stringing etc. as per the direction of the departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 57 | Unpacking the transformer / feeder C&R panels, 110V battery charger, OLTC cubicle LT panel at the place of storage transporting to the place of erection and erecting after providing foundation bolt keeping to lines and levels as per the direction of departmental officers. (cost index(e) : 1.3132 included in Rate) |
| 58 | Levelling, Cutting and fixing in position departmentally supplied MS Chequered plate 6 mm, 10 mm or 12mm thick in suitable length and width including providing lifting legs and suitable holes for lifting including grinding sides and corners etc. complete. (cost index(e) :1.3132 included in Rate) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 21, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 08, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysDec 11, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender