Tender For Rate Contract For Maintenance Of 132/33/11Kv Grid Station Chanderkote, 33/11Kv R-Station At Dharmund Including Oil Testing And Overhauling Of Transformers/Relays And Breakers Etc. Along With Their 33Kv D/C Chanderkote- Dharmond Tower Line
Tender Overview
Project Description
Tender for Rate Contract For Maintenance Of 132/33/11Kv Grid Station Chanderkote, 33/11Kv R-Station At Dharmund Including Oil Testing And Overhauling Of Transformers/Relays And Breakers Etc. Along With Their 33Kv D/C Chanderkote- Dharmond Tower Line And 33Kv Batote-Dharmond Tr. Line Falling Under The Jurisdiction Of Electric Project Division-Bhep Chanderkote.
BOQ
| Sl. No. | Item Description |
| 1 | Replacement of damaged 132KV isolators including carriage of the equipment from divisional store to working site damaged equipment to store. |
| 2 | Replacement of damaged 33KV isolators including carriage of the equipment from divisional store to working site damaged equipment to store. |
| 3 | Measuring of IR value, Leakage current and tightening of droppers of LA of 132 KV |
| 4 | Measuring of IR value, Leakage current and tightening of droppers of LA of 33 KV |
| 5 | Checking of oil level, measurement of IR value, filling of nitrogen gas etc. and tightening droppers of PT/CVT/CC of 132KV level. |
| 6 | Checking of oil level, measurement of IR value, filling of nitrogen gas etc. and tightening droppers of PT/CVT/CC of 33KV level. |
| 7 | Checking of oil level, measurement of IR value, filling of nitrogen gas etc. and tightening of all jumpers of current transformer at 132KV level. |
| 8 | Checking of oil level, measurement of IR value, filling of nitrogen gas etc. and tightening of all jumpers of current transformer at 33KV level. |
| 9 | Checking and tightening of N/B of bird barrier clamps, LA, Tunning device etc at 132 kv level and measuring of IR value |
| 10 | Checking of moving/ fixed contacts, cleaning, greasing of contacts, cleaning of post insulator and auxiliary switches, contacts, tightening of clamps etc of isolator at 132 KV level |
| 11 | Checking of moving/ fixed contacts, cleaning of post insulator and auxiliary switches, contacts, tightening of clamps etc of isolator at 33 KV level |
| 12 | Inspection and testing of breakers including inspection of operating mechanism, inspection of contacts and adjustments of various clearance of SF6/VCB at 132 KV |
| 13 | Inspection and testing of transformer including drying/ replacement of silica gel, checking of Bucholz relay, conservator oil level, indicator, temperature sensor, topping of oil, cooling system, measurement of IR value, dielectric strength of Oil, cleaning of 20 MVA transformer etc. |
| 14 | Inspection and testing of transformer including drying/ replacement of silica gel, checking of becholz relay, conservator oil level, indicator, temperature sensor, topping of oil, cooling system, measurement of IR value, dielectric strenght of Oil, cleaning of 10MVA&6.3 MVA tranformer etc. |
| 15 | Replacement of damaged bushings gaskets etc of power transformer including drainage of oil, opening of connectors, dismantling and replacement by new one, providing connections etc filling of filtered oil complete job( bushing rated for voltage upto 132 KV) |
| 16 | Replacement of damaged bushings gaskets etc of power transformer including drainage of oil, opening of connectors, dismantling and replacement by new one, providing connections etc filling of filtered oil complete job( bushing rated for voltage upto 33 KV) |
| 17 | Replacement of damaged/ burnt droppers or jumpers( emergency work) |
| 18 | Replacement of damaged Disc insulator along its fitting by lowering down the conductor and replace the damaged dis insulator and re erection the sting after replacement 132kv yard |
| 19 | Replacement of damaged Disc insulator along its fitting by lowering down the conductor and replace the damaged dis insulator and re erection the sting after replacement 33kv yard |
| 20 | Replacement of post insulators or providing additional post insulators of 132 KV stack upto 3 strings |
| 21 | Replacement of post insulators or providing additional post insulators of 33 KV stack upto 3 strings |
| 22 | Tightening of all nuts/ bolts and providing missing bolts and damaged members of Gantry columns and beams of 132 KV Way |
| 23 | Tightening of all nuts/ bolts and providing missing bolts and damaged members of Gantry columns and beams of 33 KV Way |
| 24 | Measuring of Earth resistivity, checking of electrical continuity of equipment earthing, lightning of earth connectors, removal of rust, re-tightening of 132/33 KV composite yard |
| 25 | Overhauling of Circuit Breaker132kv |
| 26 | Replacement of damaged Disc insulator 132kv. |
| 27 | Replacement of burnt /damaged jumpers and tightening of remaining jumpers on the same 33 kv tower. |
| 28 | Replacement of damaged Disc insulators 33kv tower line . |
| 29 | Restoration of snapped power conductor, complete job including mid span compression joint, laying of conductor, rough sagging, tension of conductor dead end assembly etc upto span to 500 meter tension to tension point. |
| 30 | Stringing and sagging of ACSR Conductor including sagging tensioning fitting of dead end assemblies etc (Complete Job). |
| 31 | Removal of tress if dropped on the transmission line in case the fault occurred |
| 32 | Repairing of damaged moose conductor by using helical sleeve or bolted or by shorting method without lowering the conductor. |
| 33 | Emergency tower top checking in case if the fault is not located from ground. |
| 34 | Providing of stay wire to the tower for its strengthening including complete job. |
| 35 | Checking and tightening of jumper including inserting/ removal of temporary local earthing.( complete job) |
| 36 | Checking and tightening of vibration dampers ( per circuit per tower) including insertion/ removal of temporary local earthing( Complete job) |
| 37 | Fixing of repair sleeves compression type for over ACSR Conductor. |
| 38 | Replacement of damaged Disc insulators tension string |
| 39 | Replacement of damaged disc insulators suspension string. |
| 40 | Tightening of nuts and bolts of tower superstructure. |
| 41 | Replacement of damaged/ burnt droppers or jumpers of isolators/breakers/transformer/ct/pt etc in 132kv or 33kv yard |
| 42 | Replacement of damaged CT/PT including carriage from store to working site 132kv or 33kv |
| 43 | Fixing of Anti climbing device/bird guard over tower |
| 44 | Checking and tightening of tower footing earthing bolt and measuring tower footing resistance |
| 45 | Fixing of new vibration dampers on earth wire/ACSR Dog conductor(including/inserting/removal of temporary local earthing) |
| 46 | Replacement of damaged or missing tower numbers |
| 47 | Branch cutting under the corridor of 33 KV Transmission line 16 meter wide and under tower structure. |
| 48 | Dismantling of Switchgear System of 33 KV C&R Panel |
| 49 | Dismantling of Switchgear System of 33 KV VCB Panel |
| 50 | Dismantling of Switchgear System of 11KV VCB Panel |
| 51 | Fixing, installing, testing and commissioning of Switchgear System complete job (including relay testing) of 33 KV C&R Panel |
| 52 | Fixing, installing, testing and commissioning of Switchgear System complete job (including relay testing) of 33KV VCB breaker |
| 53 | Fixing, installing, testing and commissioning of Switchgear System complete job (including relay testing) of 11KV VCB Panel |
| 54 | Fixing, installation, testing & commissioning, testing of fresh Numerical/Digital/electromagnetic Relays by way of Replacement of Damaged/Burnt already installed in panel.(including fabrication of slot in the pannel if required) |
| 55 | Fixing, installing, commissioning, testing of fresh Master tripping relay.(including fabrication of slot in the pannel if required) |
| 56 | Rectification ,setting right the electrical section (Panel wiring) of 11KV VCB Panel including replacement of damaged parts like Rotor selector switch, TNC switch etc excluding Relay & Motor |
| 57 | Rectification, Re-Alignment, setting right the mechnical section of 11KV Breakers which includes replacement of damaged parts excluding Vacuum interrupter |
| 58 | Rectification ,setting right the electrical section (Panel wiring) of 33KV C&R Panel including replacement of damaged parts like Rotor selector switch, TNC switch etc excluding Relay |
| 59 | Rectification, re-alignment, setting right the mechanical / electrical section of 33KV Breakers which includes replacement of damaged parts excluding Vacuum Interrupter & motor |
| 60 | Rewinding /repairing of Spring Charging motor of 11KV/33KV VCB breaker |
| 61 | Repairing of damaged parts including testing & commissioning of Electromagnetic relays/Trip Ckt supervision Relay/Buchloz Relay/Auxillary relays/Master Relay |
| 62 | Repairing of damaged parts including testing & commissioning of Numerical relays |
| 63 | Replacement and commissioning of damaged clamps of sizes |
| 64 | Installation, Testing & Commissioning of 33KV Post Insulators confirming to IEC 61109/92-93 with latest amendments including dismantling of damaged one, if any |
| 65 | Fixing, installation, testing and commissioning of 33KV Isolators(W E/B or W.O E/B) 1250 Amps including dismantling of damaged one, if any |
| 66 | Replacement of damaged isolator, testing and commissioning of 33KV Isolator Grovees including alignment of isolator and dismantling of damaged parts , if any |
| 67 | Erection of 10' Long Equipment structure Pipe in the 33KV ODY by using Grouting Bolts |
| 68 | Laying, Testing, commissioning of 33KV (E) grade ,400 Sqmm, armoured ,3-core,Xlpe Power Cable including dismantling of damaged one, if any |
| 69 | Laying, Testing, commissioning of 11KV (E) grade armoured ,400 Sq MM,3-core,Xlpe Power Cable including dismantling of damaged one, if any |
| 70 | Laying, Testing, commissioning of 11KV (E) grade armoured ,300 Sq mm,3-core,Xlpe Power Cable including dismantling of damaged one, if any |
| 71 | Laying, Testing, commissioning of 11KV (E) grade armoured ,240 Sq mm,3-core,Xlpe Power Cable including dismantling of damaged one, if any |
| 72 | Laying, Testing, commissioning of 11KV (E) grade armoured ,185/120 Sqmm,3-core,Xlpe Power Cable including dismantling of damaged one, if any |
| 73 | Laying, Testing, commissioning of 2.5 sqmm 2/4/6/8/12/16 Core Control cable armored , copper conductor sheathed PVC insulated multi colour voltage grade 1.1 KV |
| 74 | Laying, Testing, commissioning of L T Cable 3 1/2 corearmored , copper / Al conductor sheathed PVCinsulated . |
| 75 | Deweeding of 132KV /33 KV out door Yard of receiving station including cleaning of cable trenchs etc. |
| 76 | Making damaged 11KV XLPE cables of sizes and lengths ready for cable end termination by way of dragging of cable from cable trunch/cutting etc |
| 77 | Dressing of 11KV XLPE Power cables of Sizes in the cable trunch |
| 78 | Installation, Testing & Commissioning of 11KV 3 Core (400/300/240/185/120 Sq mm-I/D or O/D) Cable end termination Kit heat shrinkable including required size of lugs/thimbles including dismantling of damaged one |
| 79 | Installation, Testing & Commissioning of 33 KV 3 Core(630/400 Sqmm)-I/D or O/D Cable end termination Kit heat shrinkable outdoor including lugs/thimbles |
| 80 | Installation testing and commissioning of 11KV Vacuum Interrupter (BHEL, Crompton Greaves, Alsthom, ABB etc Make including dismantling of damaged one, if any |
| 81 | Installation, Testing & Commissioning of 33 KV Outdoor, Oil Cooled, Live Tank, single Phase , 3/2 Core CT set of different ratios including dismantling of damaged one, if any |
| 82 | Installation, Testing & Commissioning of 33 KV Outdoor, Oil Cooled, Copper Wound , single Phase , PT with rated primary voltage 33000/√3 & rated Secondary voltage 110/√3 per set of 3 pieces) including dismantling of damaged one, if any |
| 83 | Installation, Testing & Commissioning of 33 KV Lightening Arrestor Set, Outdoor, Metal Oxide Gapless (per set of 3 pieces) including dismantling of damaged one, if any |
| 84 | Installation, Testing & Commissioning of 11 KV Lightening Arrestor set, Outdoor, Metal Oxide Gapless (per set of 3 pieces) including dismantling of damaged one, if any |
| 85 | Installation, Testing & Commissioning of 11 KV Indoor ,Dry, Copper Wound ,Three Phase , PT Set in MS enclosure with rated primary voltage 11000/√3 & rated Secondary voltage 110/√3 (per set of 3 pieces) includingdismentling of damaged one, if any |
| 86 | Installation,Testing& Commissioning of 11 KV Indoor type,Dry,Resincast, Single Phase ,3/ 2 Core CT Set as per ISI specification preferably of BHEL/Crompton Greaves/Alsthom/Allind /ER Make) with required ratio (per set of 3 pieces) includingdismentling of damaged one, if any |
| 87 | Loading of Auxiliary transformer including dragging to loading site 25/63/100KVA upto 1000KVA |
| 88 | Unloading of Auxiliary transformer including dragging to requisite site 25/63/100KVA upto 1000KVA |
| 89 | Fixing and Commissiong of Panel Bush/Breaker Bush/Auxiliary switch/Interrupter Housing for 11KV VCB panels |
| 90 | Oil filling / topping of Power Transformer/33 KV CT/33KV PT etc |
| 91 | Improvement of Earthing / Extension of Earthing Mate including earthwork, Straightening, Welding etc using MS Flat |
| 92 | I/T/C of Aluminium Tubular Bus Bar |
| 93 | Loading of 10 MVA,33/11KV Power Transformer (from Transformer Bed to Plate Form) along with all allied accessories including its dismantling & dragging as per the requirements at site |
| 94 | Loading of 6.3 MVA,33/11KV Power Transformer (from Transformer Bed to Plate Form) along with all allied accessories including its dismantling & dragging as per the requirements at site |
| 95 | Loading of 5/4/3.15 MVA,33/11KV Power Transformer (from Transformer Bed to Plate Form) along with all allied accessories including its dismantling & dragging as per the requirements at site |
| 96 | Loading, Transportation &unloading of damaged transformer from site to central work shop PDD Jammu and Back after repair of transformer along with all allied accessories as per the requirements at site up to 1MVA. |
| 97 | Unloading of 6.3 MVA,33/11KV Power Transformer (from Plate Form to Transformer Bed ) along with all allied accessories including its dragging , rotation & stacking as per the requirements at site |
| 98 | Unloading of 5/4/3.15 MVA,33/11KV Power Transformer (from Plate Form to Transformer Bed ) along with all allied accessories including its dragging, rotation & stacking as per the requirements at site |
| 99 | Transportation of 10 MVA,33/11KV Power Transformer along with all allied accessories upto 50 Kms |
| 100 | Transportation of 6.3 MVA,33/11KV Power Transformer along with all allied accessories upto 50 Kms |
| 101 | Transportation of 5/4/3.15, 33/11KV Power Transformer along with all allied accessories upto 50 Kms |
| 102 | Additional transportation of 10 MVA,33/11KV Power Transformer along with all allied accessories per Km beyond 50 Kms |
| 103 | Additional transportation of 6.3 MVA,33/11KV Power Transformer along with all allied accessories per Km beyond 50 Kms |
| 104 | Additional transportation of 5/4/3.15 MVA,33/11KV Power Transformer along with all allied accessories per Km beyond 50 Kms |
| 105 | Installation, Testing and commissioning of 10 MVA,33/11KV Power Transformer (Complete Job) |
| 106 | Installation, Testing and commissioning of 6.3 MVA,33/11KV Power Transformer (Complete Job) |
| 107 | Installation, Testing and commissioning of 5/4/3.15 MVA 33/11KV Power Transformer (Complete Job) |
| 108 | Setting right of Power Transformer Protection ( Bucholz/Oil Temp./Winding Temp Ckt.) |
| 109 | De-commissioning of damaged 10/6.3/5/4/3.15 MVA Power Transformer |
| 110 | Testing & Commissioning of Parallel operation of Power Transformers |
| 111 | Loading of 11 KV Panel/33 KV C&R panel including dragging to loading site |
| 112 | Unoading of 11KV Panel/33 KV C&R panel including dragging to requisite site |
| 113 | Fixing , installation, testing and commissioning of 11 KV link set including dismantling of damaged one, if any |
| 114 | Fixing, installation, testing & commissioning of 11KV G.O Set 800 Amps including dismantling of damaged one, if any |
| 115 | Fixing ,installation testing &Commissioning of 11KV Isolators including dismantling of damaged one, if any |
| 116 | Fixing ,installation testing &Commissioning of (33KV DO / Fuse set) including dismantling of damaged one, if any |
| 117 | Installation/Testing/Commissioning of AC Distribution Board including dismantling of existing one if any |
| 118 | Installation/Testing/Commissioning of DC Distribution Board including dismantling of existing one if any |
| 119 | Repairing of A/C and D/C Distribution Board by way of replacing of damaged MCB(5A/10A) etc |
| 120 | Repairing of 33 KV ODY LED Lights |
| 121 | Fixing & Commissioning of Galvanised spiral Earthing of SWG No. 8, G.I wire of 115 turns confirming to REC-J1 construction standard |
| 122 | Fixing & Commissioning of 33KV Galvanised Guy Set including Guy wire, Guy Rods, Turn Buckle with plate ,Guy Insulators-Complete Job |
| 123 | Replacement of damaged/burnt of 100/150/200 Sqmm ACSR P.G Clamps in 132kv/33kv yard |
| 124 | Unloading of Steel of Sorts including carriage to requisite site |
| 125 | Loading of Steel of Sorts including carriage to loading site |
| 126 | Unloading of Conductor 50/100/150/200 Sqmm including carriage to requisite site |
| 127 | Loading of Conductor 50/100/150/200 Sqmm including carriage to loading site |
| 128 | Fixing , installation, testing & Commissioning of Disc (70 /45 KN) Disc Insulator including dismantling of damaged one, if any |
| 129 | Fixing , installation, testing & Commissioning of 33KV Insulators (10 KN) including dismantling of damaged one, if any |
| 130 | Fixing , installation, testing & Commissioning of 33KV G.I Pins with all accessories weighing 2700 gms including dismantling of damaged one, if any |
| 131 | Fixing , installation, testing & Commissioning of Tension fittings suitable for 50/100/150/200 SqmmACSR includingdismentalling of damaged one, if any |
| 132 | Fabrication of X-arms of different sizes of channel/Anglel/ Flat Iron and chequred plate. |
| 133 | Fixing of X-arms of different sizes of channel/Anglel/ Flat Iron with different sizes and sorts of nuts,bolts and washers |
| 134 | Restoration of Conductor snap 100/150/200 Sqmm |
| 135 | Restringing of loose conductor |
| 136 | Restoration of Burnt Jumper |
| 137 | Re-erection of tilted/fallen down poles |
| 138 | Fixing ,installation testing &Commissioning of 33 KV link set conforming to IS 9921/IEC-129 standards |
| 139 | Loading of various hardware/ porcelain /polymer materials in divisional stores for verification, carriage from stocking site to loading site including loading into the vehicle, like, 33KV isolators, 11KV link sets,33KV/11KV CTs & PTs, cable kits, 33/11 KV insulators along with GI pins, 33/11KV LAs etc. |
| 140 | UnLoading of various materials in divisional stores for verification, carriage upto stocking site and stocking at proper place like 33KV/11KV XLPE Cables of sizes , control cables of sizes etc. |
| 141 | Loading of various materials in divisional stores for verification, carriage from stocking site to loading site including loading into the vehicle, like, 33KV/11KV XLPE Cables of sizes , control cables of sizes etc. |
| 142 | Replacement of damaged burnt out of control cable of different size . |
| 143 | Fixing of Danger Plate |
| 144 | Fixing of Anti climbing devices |
| 145 | Installation / Fixing of Gurad netting of 33KV/11KV Lines as per REC |
| 146 | Repair/Refilling of fire extinguishers at 132/33/11 kvChanderkote Grid and 33/11 kv R/Stn Dharmund Grid ( including their transportation charges. |
| 147 | Servicing of water purifier at 132/33/11 kvChanderkote Grid and 33/11 kv R/Stn Dharmund Grid |
| 148 | Servicing of 2 tonvoltas AC at 132/33/11 kvChanderkote Grid and 33/11 kv R/Stn Dharmund Grid |
| 149 | Painting( aluminium Paint) of all accessiorieslikeTower Structures, CTs, PTs, Breakers, Power Transformers etc within the pheriphery of 132/33/11 kv Grid and 33/11 kv R/Stn. |
| 150 | Supply of Aluminium Paint Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender