Power Government Departments Closing in 35 days TDR #58645598

Tender For Internal Electrical Installation And Wiring Of The First Floor Of Inspection Bungalow (I.B.) At Level (+) 4.000 Including Supply Of All Materials At Bankura Area Office, Wbsetcl As Per Schedule

Issued by Government Departments · Bankura, West Bengal
Tender Value
6.88 Lakhs
Estimated cost
Bid Submission
26 Dec 2026
35 days left
EMD
5000
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Bankura → West Bengal
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Internal Electrical Installation And Wiring Of The First Floor Of Inspection Bungalow (I.B.) At Level (+) 4.000 Including Supply Of All Materials At Bankura Area Office, Wbsetcl As Per Schedule , A1 [Dsr Ns-8] Sub-Main, New I.B. Main Db (A6) To The Distribution Block A13 In Ffdb-1, 4 X 25 Sq.Mm + 2 X 10 Sq.Mm Earth Wire, Frls/Hffr Pvc Cu In 32 Mm Medium Class Pvc Conduit (Est. 30 M + 20% Provision = 36 M). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3) - Any Isi-Marked Make. , A2 [Dsr Ns-1] 63 A Tpn Mcb, C-Curve, 10 Ka, On The First-Floor Outgoing Way Of The New I.B. Main Db (A6), In Series With The 300 Ma Rccb A7 - Overcurrent Protection Of Sub-Main A1 And Link Feeder A5 - Complete With Connections, Testing And Commissioning. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , A2a [Dsr Ns-7] 80 A Four Pole (Tpn) Mcb, C-Curve, 10 Ka, Is/Iec 60947-2, Din-Rail Mounted, Main Incomer Of The New I.B. Main Db (A6) - The ConsumerS Circuit Breaker, Cea Regulations 2023, Reg. 37 - Complete With Connections, Testing And Commissioning. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , A3 [Dsr 2.5.3] 12 Way (4+36) Tpn Vertical Mcb Db, Double Door, Without Mcbs And Incomer - Ffdb-1 And Ffdb-2. Sheet Steel, Powder Coated, Ip-42/43, Is/Iec 61439-3. Make: Factory-Assembled, Of The Make Of The Mcbs (Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric). , A4 [Dsr Ns-11] 63 A, 4 Pole, 415 V Rccb, 30 Ma Sensitivity, Type A (Is 12640-1 / Iec 61008-1), In Mcb Db - Incomer And Isolating Switch Of Ffdb-1 And Ffdb-2, Each Fed From The Distribution Block A13 - Complete With Connections, Testing And Commissioning. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , A5 [Dsr Ns-8] Link Feeder, Distribution Block A13 In Ffdb-1 (Line Side Of The Ffdb-1 Rccb) To Ffdb-2, 4 X 25 Sq.Mm + 2 X 10 Sq.Mm Earth Wire, Frls/Hffr Pvc Cu In 32 Mm Medium Class Pvc Conduit (Est. 8 M). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3) - Any Isi-Marked Make. , A6 [Dsr 2.5.2] 8 Way (4+24) Tpn Vertical Mcb Db, Double Door, Without Mcbs And Incomer, With An Incomer Section For The 80 A Four Pole Mcb A2a - New I.B. Main Db Beside The Wbsedcl 3-Phase Meter. Sheet Steel, Powder Coated, Ip-42/43, Is/Iec 61439-3. Make: Factory-Assembled, Of The Make Of The Mcbs (Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric). , A7 [Dsr Ns-6] 63 A, 4 Pole, 415 V Rccb, 300 Ma Sensitivity, Type Ac, In Mcb Db - First-Floor Outgoing Of The New I.B. Main Db, Also Isolating The First Floor - Complete With Connections, Testing And Commissioning. Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , A8 [Dsr 2.10.2] 5-32 A Spn Mcb (32 A), C-Curve, 10 Ka - Ground-Floor Outgoing Of The New I.B. Main Db. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , A9 [Dsr 2.14.2] 40 A 2 Pole Rccb 30 Ma - Ground-Floor Outgoing Of The New I.B. Main Db (Cea Regulations 2023, Reg. 44). Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , A10 [Dsr Ns-9] Link, Wbsedcl Meter Outgoing Terminals To The Main Incomer A2a, 4 X 35 Sq.Mm + 2 X 16 Sq.Mm Earth Wire, Frls/Hffr Pvc Cu In 40 Mm Medium Class Pvc Conduit (Est. 3 M + 20% Provision = 4 M). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3) - Any Isi-Marked Make. , A11 [Dsr 1.14.4] Link, Ground-Floor Outgoing (A8 + A9) To The Existing Ground Floor Main Switch, 2 X 6 Sq.Mm + 1 X 6 Sq.Mm Earth Wire (Est. 3 M). Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , A12 [Dsr 2.21] M.V. Danger Notice Plate 200 X 150 Mm, Mild Steel 2 Mm, Vitreous Enamelled - On The New I.B. Main Db, Ffdb-1 And Ffdb-2 (Cea Regulations 2023, Reg. 20). Make: Any, Approved By The E.I.C. , A13 [Dsr Ns-3] 4 Pole Distribution Block Set, 125-160 A, 415 V, Ip20 With Cover, In Ffdb-1 Ahead Of Its Rccb (A4) - A Single 4 Pole Block Or 4 Single Pole Blocks, Per Pole One Supply Terminal 25-35 Sq.Mm And At Least Two Outgoing Terminals For 25 Sq.Mm Flexible Conductor With Ferrule - With 25 Sq.Mm Jumpers To The Ffdb-1 Rccb; Feeds The Ffdb-1 Rccb And The Link A5 To Ffdb-2 - Supply, Fixing, Connection, Testing And Commissioning. Standard Iec 60947-7-1. Make: Elmex / Connect Well / Yogya Equipments, Or Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , B1 [Dsr 1.10.2] Light / Fan / Exhaust Fan Point Wiring, 1.5 Sq.Mm Frls/Hffr Cu, Modular Switch, Gi Box, Earthing - Group B, Points Of 3 To 6 M Route Length From The Switchboard (6 Battens, 4 Toilet Down Lighters, 8 Down Lighters Dl-9 To Dl-11 And Dl-16 To Dl-20, Fl-1, 4 Cove-Light Points, 4 Fan Points Cf-1, Cf-4 To Cf-6, Exhaust Fans Ex-2, Ex-3). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3), Modular Switch Is 3854 And Plate - Any Isi-Marked Make. , B1a [Dsr 1.10.3] Light / Fan / Exhaust Fan Point Wiring As B1 - Group C, Points Of Over 6 M Route Length From The Switchboard (Conference Down Lighters Dl-1 To Dl-8 And Dl-12 To Dl-14, Fans Cf-2, Cf-3; Dining Dl-15; Battens L12, L15; Exhaust Fans Ex-1, Ex-4 - Route Lengths Scaled From Drg. Bnk/Ib/El/01, Clause 5(E)); Quantities Of B1 And B1a Fixed At Measurement. Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3), Modular Switch Is 3854 And Plate - Any Isi-Marked Make. , B2 [Dsr 2.10.1] 5-32 A Sp Mcb (10 A), C-Curve, 10 Ka - 6 Lighting + 1 Stair + 2 Fan Circuits (Ff-Ltg-2A: Not More Than 10 Points Per Lighting Circuit, Clause 5(E)). Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , B3 [Dsr 1.14.1] Circuit Wiring 2 X 1.5 + 1 X 1.5 Sq.Mm Earth Wire From Ffdb-1 To The Switchboards Of The 9 Lighting / Fan Circuits - 17 Runs (Db To First Switchboard And Between The Switchboards Of A Circuit) X 9 M Average, And 8 M From Sb-11 To The Roof-Door Switchboard Sb-13 - + Provision (161 M + 31 M) - Payable On Actual Measurement. Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , B4 [Dsr 8.9.3] Led Batten Luminaire 36 W, 4000 K, Surface / Ceiling Mounted, Supply, Installation, Testing And Commissioning - Bed Room 2, V.I.P. 3, V.V.I.P. 3 (L1, L2, L11, L12, L23, L14, L15, L24 Of Drg. Bnk/Ib/El/01); No Batten On The Stair (B14a). Bis (Crs) Registered. Make: Any, Approved By The E.I.C. , B5 [Dsr 8.2.3] Led Down Lighter 12-15 W, 4000 K, Recessed Or Surface, One In Each Toilet (L3, L10, L13, L16 Of Drg. Bnk/Ib/El/01), Supply, Installation, Testing And Commissioning. Bis (Crs) Registered. Make: Any, Approved By The E.I.C. , B6 [Dsr 9.2.4] Bldc Ceiling Fan Without Remote, For Speed Control By Wall Regulator, 1400 Mm Sweep, Is 374, Supply, Installation, Testing And Commissioning - Cf-1 To Cf-6 Of Drg. Bnk/Ib/El/01. Make: Any, With The Bis Mark Where Compulsory, Approved By The E.I.C. , B7 [Dsr Ns-4] Exhaust Fan, 300 Mm Sweep, Metal Body With Shutters, Is 2312 - Supply Only - Ex-1 To Ex-4 Of Drg. Bnk/Ib/El/01. Make: Any, With The Bis Mark Where Compulsory, Approved By The E.I.C. , B8 [Dsr 1.50.1] Installation, Testing And Commissioning Of Exhaust Fan Up To 450 Mm Sweep In The Existing Opening, Including Making Good The Damage And Connections , B9 [Dsr 1.11] Twin Control (Two-Way) Light Point Wiring, 1.5 Sq.Mm Frls/Hffr Cu In Medium Class Pvc Conduit, 2 Way Modular Switches, Modular Plate, Gi Box, Earthing - Stair Strip Lines Cv-5 And Cv-6 (Sb-11 / Sb-12); Roof-Stair Strip Lines Cv-7 And Cv-8 (Sb-11 / Sb-13), Each Point Feeding The First Driver Of Its Line (B14a). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3), Modular Switch Is 3854 And Plate - Any Isi-Marked Make. , B10 [Dsr 8.2.5] Led Recessed Down Lighter 22 W, Round, 4000 K, In The False Ceilings - Conference Room 14 (Dl-1 To Dl-14), Dining Room 6 (Dl-15 To Dl-20) Of Drg. Bnk/Ib/El/01 - Supply, Installation, Testing And Commissioning. Bis (Crs) Registered. Make: Any, Approved By The E.I.C. , B11 [Dsr 8.15.3] Led Flood Light 100 W, Ip-65 Minimum - Fl-1 On The Roof, Switched At The Roof-Door Switchboard Sb-13 - Supply, Installation, Testing And Commissioning. Bis (Crs) Registered. Make: Any, Approved By The E.I.C. , B12 [Dsr 1.25] Two Module Stepped Type Electronic Fan Regulator On The Modular Plate Of The Fan Point - Cf-1 To Cf-6. Standard Is 11037. Make: Of The Make And Range Of The Modular Switches (Any Isi-Marked). , B13 [Dsr 1.47] Extra Down Rod Of 10 Cm Length, 15 Mm Dia G.I. Pipe, Heavy Gauge, Painted - Fans Under The False Ceilings Cf-2, Cf-3, Cf-6, 30 Cm Each (Est.). Make: Any, Approved By The E.I.C. , B14 [Dsr Ns-5] Led Cove Light Set Of 5 M - Flexible Led Strip 12 V Dc, About 25 W Per 5 M, Warm White (Outer Cove) Or Magenta (Inner Cove), With One 12 V Dc Constant-Voltage Selv Driver Of Not Less Than 30 W (Bis Registered), 230 V Loop In 20 Mm Pvc Conduit, 12 V Leads - Supply, Installation, Testing And Commissioning - Conference Room 8 Sets, Dining Room 5 Sets. Make: Any, Approved By The E.I.C. , B14a [Dsr Ns-10] Led Strip Light Set Of 5 M For The Stair - Flexible Led Strip As B14, 4000 K, In 5 M Of Surface-Mounted Aluminium Led Profile With Frosted / Opal Diffuser And End Caps, Screw-Fixed On The Wall Just Below The Slab, Light Directed Down, With One 12 V Dc Constant-Voltage Selv Driver Of Not Less Than 30 W (Bis Registered), 230 V Loop In 20 Mm Pvc Conduit, 12 V Leads - Supply, Installation, Testing And Commissioning - Stair Cv-5, Cv-6 And Roof Stair Cv-7, Cv-8 Of Drg. Bnk/Ib/El/01, 2 Sets Each. Make: Any, Approved By The E.I.C. , B15 [Dsr 1.10.3] Call Bell Point Wiring, 1.5 Sq.Mm Frls/Hffr Cu, Modular Bell Push, Gi Box, Earthing - Group C - Bed Room, V.I.P. Room And V.V.I.P. Room, Push At The Bedside, Buzzer (B16) Above The Outside Of The Room Door (Clause 5(F)). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3) And Modular Bell Push - Any Isi-Marked Make. , B16 [Dsr 1.38] Call Bell / Buzzer, Single Phase 230 V, Complete - One For Each Call Bell Point Of B15. Make: Any, Approved By The E.I.C. , C1 [Dsr 1.32] Gi Box With Modular Plate, 6 Pin 5/6 & 15/16 A Socket And 15/16 A Switch - S1, S8, S11 (One In Each Guest Room), S4 To S7 (Conference Room), S14 (Lobby). Switch Is 3854, Socket Is 1293. Make: Any Isi-Marked; Plate Of The Same Make And Range. , C1a [Dsr 1.31] Gi Box With Modular Plate, 3 Pin 5/6 A Socket And 5/6 A Switch - Bedside Outlets S2, S3, S9, S10, S12, S13. Switch Is 3854, Socket Is 1293. Make: Any Isi-Marked; Plate Of The Same Make And Range. , C2 [Dsr 1.32] Gi Box With Modular Plate, 6 Pin 5/6 & 15/16 A Socket And 15/16 A Switch. Switch Is 3854, Socket Is 1293. Make: Any Isi-Marked; Plate Of The Same Make And Range. , C3 [Dsr 1.14.2] Circuit Wiring 2 X 2.5 + 1 X 2.5 Sq.Mm Earth Wire (15 Socket Points X 9 M = 135 M). Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , C4 [Dsr 2.10.1] 5-32 A Sp Mcb (16 A), C-Curve, 10 Ka - Socket Circuits Ff-Sp-1 To Ff-Sp-6 And Ff-Sp16. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , C5 [Dsr 2.14.1] 25 A 2 Pole Rccb 30 Ma - Fridge Circuit Ff-Sp16. Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , C5a [Dsr 2.14.2] 40 A 2 Pole Rccb 30 Ma - Ahead Of Each Pair Of Socket Circuits (Ff-Sp-1 + Ff-Sp-2, Ff-Sp-3 + Ff-Sp-4, Ff-Sp-5 + Ff-Sp-6). Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , C6 [Dsr 2.10.1] 5-32 A Sp Mcb (10 A), C-Curve, 10 Ka - Conference Audio-Visual Power Circuits Ff-Av-1 And Ff-Av-2. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , C7 [Dsr 2.14.1] 25 A 2 Pole Rccb 30 Ma - Ahead Of The Circuits Ff-Av-1 And Ff-Av-2. Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , C8 [Dsr 1.31] Gi Box With Modular Plate, 3 Pin 5/6 A Socket And 5/6 A Switch - Conference Audio-Visual Power Points Av1 To Av6 (Projector At Ceiling, Screen, Av Rack 2, ChairmanS End 2; Av1 To Av3 On Ff-Av-1, Av4 To Av6 On Ff-Av-2). Switch Is 3854, Socket Is 1293. Make: Any Isi-Marked; Plate Of The Same Make And Range. , C9 [Dsr 1.14.2] Circuit Wiring 2 X 2.5 + 1 X 2.5 Sq.Mm Earth Wire, Circuits Ff-Av-1 And Ff-Av-2 (6 Points X 9 M = 54 M, + Provision 5 M). Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , C10 [Dsr 1.21.2] 25 Mm Medium Class Pvc Conduit, Laid Empty With Gi Pull Wire, For Audio-Visual Signal / Speaker Cables By Others (Est. 60 M). Standard Is 9537 (Part 3). Make: Any Isi-Marked. , C11 [Dsr 1.22.2] Metal Pull Box 100 X 100 X 60 Mm With Phenolic Laminated Cover On The Empty Av Conduit. Make: Any, Approved By The E.I.C. , D1 [Dsr 1.14.3] Circuit Wiring 2 X 4 + 1 X 4 Sq.Mm Earth Wire To Geyser Points (3 X 9 M = 27 M). Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , D2 [Dsr 2.10.3] 5-32 A Dp Mcb (20 A), C-Curve, 10 Ka - Geyser Circuits. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , D3 [Dsr 2.14.1] 25 A 2 Pole Rccb 30 Ma - Geyser Circuits (Wet Location, Mandatory). Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , D4 [Dsr 2.16] Dp Sheet Steel Enclosure On Surface / Recess With 25 A Dp Mcb, C-Curve - The Switch At Each Geyser Point, Outside The W.C. & Bath Beside Its Door (Clause 5(G)). Mcb Is/Iec 60898-1, 10 Ka. Make: Mcb - Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric; Enclosure Of The Same Make. , E1 [Dsr 2.10.3] 5-32 A Dp Mcb (20 A), C-Curve, 10 Ka, In Ffdb-2 - One For Each Of The 6 Air-Conditioner Circuits; Circuit Wiring, Switch At Each Unit And Ac Units Under The Separate Air-Conditioning Tender (Clause 5(H)). Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , F1 [Dsr 2.10.1] 5-32 A Sp Mcb (16 A), C-Curve, 10 Ka - 2 Spare Ways In Ffdb-1 (Mcbs Fitted; No Circuit Wiring In This Contract). Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , F2 [Dsr 2.10.3] Provision - 20/25 A Dp Mcb, C-Curve, 10 Ka, In A Spare Way Of Ffdb-2, Fixed And Connected To The Busbar, For A Socket Or Ac Circuit Called For During Execution; Executed Only On The Written Order Of The E.I.C. (Clause 5(N)). Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , F3 [Dsr 1.14.3] Provision - Circuit Wiring 2 X 4 + 1 X 4 Sq.Mm Earth Wire From Ffdb-2, For The Circuits Of The Provision Mcbs F2 Or Any Other Circuit Of This Size Called For During Execution; Executed Only On The Written Order Of The E.I.C. (Clause 5(N)) - Payable On Actual Measurement. Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , G1 [Dsr 5.15] 25 X 5 Mm Gi Strip On Surface/Recess - Earth Riser And Bonding (Est. 42 M + 20% Provision = 50 M). Hot-Dip Galvanised (Is 2629 / Is 4736). Make: Any. , G2 [Dsr 5.18] 6 Swg Dia Gi Wire Loop Earthing Along Conduit (100 M + Provision 14 M = 114 M). Hot-Dip Galvanised (Is 2629 / Is 4736). Make: Any. , G3 [Dsr 5.2] Earthing With G.I. Earth Pipe 4.5 M Long, 40 Mm Dia, With Accessories, Masonry Enclosure With Cover Plate And Locking Arrangement, Watering Pipe, Charcoal / Coke And Salt - 1 No. New Electrode, Added To The Existing Earth Bus And Earth Pit Of The I.B. And Bonded To The Earth Bar Of The New I.B. Main Db (Clause 5(I)). Hot-Dip Galvanised (Is 2629 / Is 4736). Make: Any. , G4 [Dsr 5.15] 25 X 5 Mm Gi Strip Earth Lead From The New Electrode To The Earth Bar Of The New I.B. Main Db (Est. 10 M). Hot-Dip Galvanised (Is 2629 / Is 4736). Make: Any. , H1 [Dsr Ns-2] Testing, Commissioning And Handing Over - Ir, Earth Continuity/Resistance, Polarity, Rccb Tests With An Rcd Tester; Test Report, Marked-Up As-Built Drawings, Warranty Cards; Inspectorate Liaison

BOQ

Name of Work:- Internal Electrical Installation and wiring of the First Floor of Inspection Bungalow (I.B.) at Level (+) 4.000 including supply of all materials at Bankura Area Office, WBSETCL as per schedule
Sl. No. Item Description
1A1 [DSR NS-8] Sub-main, new I.B. main DB (A6) to the distribution block A13 in FFDB-1, 4 x 25 sq.mm + 2 x 10 sq.mm earth wire, FRLS/HFFR PVC Cu in 32 mm medium class PVC conduit (est. 30 m + 20% provision = 36 m). Wire 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; conduit IS 9537 (Part 3) — any ISI-marked make.
2A2 [DSR NS-1] 63 A TPN MCB, C-curve, 10 kA, on the FIRST-FLOOR OUTGOING WAY of the new I.B. main DB (A6), in series with the 300 mA RCCB A7 — overcurrent protection of sub-main A1 and link feeder A5 — complete with connections, testing and commissioning. Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
3A2A [DSR NS-7] 80 A four pole (TPN) MCB, C-curve, 10 kA, IS/IEC 60947-2, DIN-rail mounted, MAIN INCOMER of the new I.B. main DB (A6) — the consumer’s circuit breaker, CEA Regulations 2023, Reg. 37 — complete with connections, testing and commissioning. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
4A3 [DSR 2.5.3] 12 way (4+36) TPN vertical MCB DB, double door, without MCBs and incomer — FFDB-1 and FFDB-2. Sheet steel, powder coated, IP-42/43, IS/IEC 61439-3. Make: factory-assembled, of the make of the MCBs (ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric).
5A4 [DSR NS-11] 63 A, 4 pole, 415 V RCCB, 30 mA sensitivity, type A (IS 12640-1 / IEC 61008-1), in MCB DB — incomer and isolating switch of FFDB-1 and FFDB-2, each fed from the distribution block A13 — complete with connections, testing and commissioning. Make: any ISI-marked, preferably the make of the MCBs.
6A5 [DSR NS-8] Link feeder, distribution block A13 in FFDB-1 (line side of the FFDB-1 RCCB) to FFDB-2, 4 x 25 sq.mm + 2 x 10 sq.mm earth wire, FRLS/HFFR PVC Cu in 32 mm medium class PVC conduit (est. 8 m). Wire 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; conduit IS 9537 (Part 3) — any ISI-marked make.
7A6 [DSR 2.5.2] 8 way (4+24) TPN vertical MCB DB, double door, without MCBs and incomer, with an incomer section for the 80 A four pole MCB A2A — NEW I.B. MAIN DB beside the WBSEDCL 3-phase meter. Sheet steel, powder coated, IP-42/43, IS/IEC 61439-3. Make: factory-assembled, of the make of the MCBs (ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric).
8A7 [DSR NS-6] 63 A, 4 pole, 415 V RCCB, 300 mA sensitivity, type AC, in MCB DB — first-floor outgoing of the new I.B. main DB, also isolating the first floor — complete with connections, testing and commissioning. Standard IS 12640-1. Make: any ISI-marked, preferably the make of the MCBs.
9A8 [DSR 2.10.2] 5-32 A SPN MCB (32 A), C-curve, 10 kA — ground-floor outgoing of the new I.B. main DB. Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
10A9 [DSR 2.14.2] 40 A 2 pole RCCB 30 mA — ground-floor outgoing of the new I.B. main DB (CEA Regulations 2023, Reg. 44). Standard IS 12640-1. Make: any ISI-marked, preferably the make of the MCBs.
11A10 [DSR NS-9] Link, WBSEDCL meter outgoing terminals to the main incomer A2A, 4 x 35 sq.mm + 2 x 16 sq.mm earth wire, FRLS/HFFR PVC Cu in 40 mm medium class PVC conduit (est. 3 m + 20% provision = 4 m). Wire 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; conduit IS 9537 (Part 3) — any ISI-marked make.
12A11 [DSR 1.14.4] Link, ground-floor outgoing (A8 + A9) to the existing ground floor main switch, 2 x 6 sq.mm + 1 x 6 sq.mm earth wire (est. 3 m). Wire FRLS/HFFR PVC insulated Cu, 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; in medium class PVC conduit, IS 9537 (Part 3) — any ISI-marked make.
13A12 [DSR 2.21] M.V. danger notice plate 200 x 150 mm, mild steel 2 mm, vitreous enamelled — on the new I.B. main DB, FFDB-1 and FFDB-2 (CEA Regulations 2023, Reg. 20). Make: any, approved by the E.I.C.
14A13 [DSR NS-3] 4 pole distribution block set, 125–160 A, 415 V, IP20 with cover, in FFDB-1 ahead of its RCCB (A4) — a single 4 pole block or 4 single pole blocks, per pole one supply terminal 25–35 sq.mm and at least two outgoing terminals for 25 sq.mm flexible conductor with ferrule — with 25 sq.mm jumpers to the FFDB-1 RCCB; feeds the FFDB-1 RCCB and the link A5 to FFDB-2 — supply, fixing, connection, testing and commissioning. Standard IEC 60947-7-1. Make: Elmex / Connect well / Yogya Equipments, or ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
15B1 [DSR 1.10.2] Light / fan / exhaust fan point wiring, 1.5 sq.mm FRLS/HFFR Cu, modular switch, GI box, earthing — Group B, points of 3 to 6 m route length from the switchboard (6 battens, 4 toilet down lighters, 8 down lighters DL-9 to DL-11 and DL-16 to DL-20, FL-1, 4 cove-light points, 4 fan points CF-1, CF-4 to CF-6, exhaust fans EX-2, EX-3). Wire 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; conduit IS 9537 (Part 3), modular switch IS 3854 and plate — any ISI-marked make.
16B1A [DSR 1.10.3] Light / fan / exhaust fan point wiring as B1 — Group C, points of over 6 m route length from the switchboard (conference down lighters DL-1 to DL-8 and DL-12 to DL-14, fans CF-2, CF-3; dining DL-15; battens L12, L15; exhaust fans EX-1, EX-4 — route lengths scaled from Drg. BNK/IB/EL/01, clause 5(e)); quantities of B1 and B1A fixed at measurement. Wire 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; conduit IS 9537 (Part 3), modular switch IS 3854 and plate — any ISI-marked make.
17B2 [DSR 2.10.1] 5-32 A SP MCB (10 A), C-curve, 10 kA — 6 lighting + 1 stair + 2 fan circuits (FF-LTG-2A: not more than 10 points per lighting circuit, clause 5(e)). Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
18B3 [DSR 1.14.1] Circuit wiring 2 x 1.5 + 1 x 1.5 sq.mm earth wire from FFDB-1 to the switchboards of the 9 lighting / fan circuits — 17 runs (DB to first switchboard and between the switchboards of a circuit) x 9 m average, and 8 m from SB-11 to the roof-door switchboard SB-13 — + provision (161 m + 31 m) — payable on actual measurement. Wire FRLS/HFFR PVC insulated Cu, 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; in medium class PVC conduit, IS 9537 (Part 3) — any ISI-marked make.
19B4 [DSR 8.9.3] LED batten luminaire 36 W, 4000 K, surface / ceiling mounted, supply, installation, testing and commissioning — bed room 2, V.I.P. 3, V.V.I.P. 3 (L1, L2, L11, L12, L23, L14, L15, L24 of Drg. BNK/IB/EL/01); no batten on the stair (B14A). BIS (CRS) registered. Make: any, approved by the E.I.C.
20B5 [DSR 8.2.3] LED down lighter 12-15 W, 4000 K, recessed or surface, one in each toilet (L3, L10, L13, L16 of Drg. BNK/IB/EL/01), supply, installation, testing and commissioning. BIS (CRS) registered. Make: any, approved by the E.I.C.
21B6 [DSR 9.2.4] BLDC ceiling fan without remote, for speed control by wall regulator, 1400 mm sweep, IS 374, supply, installation, testing and commissioning — CF-1 to CF-6 of Drg. BNK/IB/EL/01. Make: any, with the BIS mark where compulsory, approved by the E.I.C.
22B7 [DSR NS-4] Exhaust fan, 300 mm sweep, metal body with shutters, IS 2312 — supply only — EX-1 to EX-4 of Drg. BNK/IB/EL/01. Make: any, with the BIS mark where compulsory, approved by the E.I.C.
23B8 [DSR 1.50.1] Installation, testing and commissioning of exhaust fan up to 450 mm sweep in the existing opening, including making good the damage and connections
24B9 [DSR 1.11] Twin control (two-way) light point wiring, 1.5 sq.mm FRLS/HFFR Cu in medium class PVC conduit, 2 way modular switches, modular plate, GI box, earthing — stair strip lines CV-5 and CV-6 (SB-11 / SB-12); roof-stair strip lines CV-7 and CV-8 (SB-11 / SB-13), each point feeding the first driver of its line (B14A). Wire 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; conduit IS 9537 (Part 3), modular switch IS 3854 and plate — any ISI-marked make.
25B10 [DSR 8.2.5] LED recessed down lighter 22 W, round, 4000 K, in the false ceilings — conference room 14 (DL-1 to DL-14), dining room 6 (DL-15 to DL-20) of Drg. BNK/IB/EL/01 — supply, installation, testing and commissioning. BIS (CRS) registered. Make: any, approved by the E.I.C.
26B11 [DSR 8.15.3] LED flood light 100 W, IP-65 minimum — FL-1 on the roof, switched at the roof-door switchboard SB-13 — supply, installation, testing and commissioning. BIS (CRS) registered. Make: any, approved by the E.I.C.
27B12 [DSR 1.25] Two module stepped type electronic fan regulator on the modular plate of the fan point — CF-1 to CF-6. Standard IS 11037. Make: of the make and range of the modular switches (any ISI-marked).
28B13 [DSR 1.47] Extra down rod of 10 cm length, 15 mm dia G.I. pipe, heavy gauge, painted — fans under the false ceilings CF-2, CF-3, CF-6, 30 cm each (est.). Make: any, approved by the E.I.C.
29B14 [DSR NS-5] LED cove light set of 5 m — flexible LED strip 12 V DC, about 25 W per 5 m, warm white (outer cove) or magenta (inner cove), with one 12 V DC constant-voltage SELV driver of not less than 30 W (BIS registered), 230 V loop in 20 mm PVC conduit, 12 V leads — supply, installation, testing and commissioning — conference room 8 sets, dining room 5 sets. Make: any, approved by the E.I.C.
30B14A [DSR NS-10] LED strip light set of 5 m for the stair — flexible LED strip as B14, 4000 K, in 5 m of surface-mounted aluminium LED profile with frosted / opal diffuser and end caps, screw-fixed on the wall just below the slab, light directed down, with one 12 V DC constant-voltage SELV driver of not less than 30 W (BIS registered), 230 V loop in 20 mm PVC conduit, 12 V leads — supply, installation, testing and commissioning — stair CV-5, CV-6 and roof stair CV-7, CV-8 of Drg. BNK/IB/EL/01, 2 sets each. Make: any, approved by the E.I.C.
31B15 [DSR 1.10.3] Call bell point wiring, 1.5 sq.mm FRLS/HFFR Cu, modular bell push, GI box, earthing — Group C — bed room, V.I.P. room and V.V.I.P. room, push at the bedside, buzzer (B16) above the outside of the room door (clause 5(f)). Wire 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; conduit IS 9537 (Part 3) and modular bell push — any ISI-marked make.
32B16 [DSR 1.38] Call bell / buzzer, single phase 230 V, complete — one for each call bell point of B15. Make: any, approved by the E.I.C.
33C1 [DSR 1.32] GI box with modular plate, 6 pin 5/6 & 15/16 A socket and 15/16 A switch — S1, S8, S11 (one in each guest room), S4 to S7 (conference room), S14 (lobby). Switch IS 3854, socket IS 1293. Make: any ISI-marked; plate of the same make and range.
34C1A [DSR 1.31] GI box with modular plate, 3 pin 5/6 A socket and 5/6 A switch — bedside outlets S2, S3, S9, S10, S12, S13. Switch IS 3854, socket IS 1293. Make: any ISI-marked; plate of the same make and range.
35C2 [DSR 1.32] GI box with modular plate, 6 pin 5/6 & 15/16 A socket and 15/16 A switch. Switch IS 3854, socket IS 1293. Make: any ISI-marked; plate of the same make and range.
36C3 [DSR 1.14.2] Circuit wiring 2 x 2.5 + 1 x 2.5 sq.mm earth wire (15 socket points x 9 m = 135 m). Wire FRLS/HFFR PVC insulated Cu, 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; in medium class PVC conduit, IS 9537 (Part 3) — any ISI-marked make.
37C4 [DSR 2.10.1] 5-32 A SP MCB (16 A), C-curve, 10 kA — socket circuits FF-SP-1 to FF-SP-6 and FF-SP16. Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
38C5 [DSR 2.14.1] 25 A 2 pole RCCB 30 mA — fridge circuit FF-SP16. Standard IS 12640-1. Make: any ISI-marked, preferably the make of the MCBs.
39C5A [DSR 2.14.2] 40 A 2 pole RCCB 30 mA — ahead of each pair of socket circuits (FF-SP-1 + FF-SP-2, FF-SP-3 + FF-SP-4, FF-SP-5 + FF-SP-6). Standard IS 12640-1. Make: any ISI-marked, preferably the make of the MCBs.
40C6 [DSR 2.10.1] 5-32 A SP MCB (10 A), C-curve, 10 kA — conference audio-visual power circuits FF-AV-1 and FF-AV-2. Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
41C7 [DSR 2.14.1] 25 A 2 pole RCCB 30 mA — ahead of the circuits FF-AV-1 and FF-AV-2. Standard IS 12640-1. Make: any ISI-marked, preferably the make of the MCBs.
42C8 [DSR 1.31] GI box with modular plate, 3 pin 5/6 A socket and 5/6 A switch — conference audio-visual power points AV1 to AV6 (projector at ceiling, screen, AV rack 2, chairman’s end 2; AV1 to AV3 on FF-AV-1, AV4 to AV6 on FF-AV-2). Switch IS 3854, socket IS 1293. Make: any ISI-marked; plate of the same make and range.
43C9 [DSR 1.14.2] Circuit wiring 2 x 2.5 + 1 x 2.5 sq.mm earth wire, circuits FF-AV-1 and FF-AV-2 (6 points x 9 m = 54 m, + provision 5 m). Wire FRLS/HFFR PVC insulated Cu, 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; in medium class PVC conduit, IS 9537 (Part 3) — any ISI-marked make.
44C10 [DSR 1.21.2] 25 mm medium class PVC conduit, laid EMPTY with GI pull wire, for audio-visual signal / speaker cables by others (est. 60 m). Standard IS 9537 (Part 3). Make: any ISI-marked.
45C11 [DSR 1.22.2] Metal pull box 100 x 100 x 60 mm with phenolic laminated cover on the empty AV conduit. Make: any, approved by the E.I.C.
46D1 [DSR 1.14.3] Circuit wiring 2 x 4 + 1 x 4 sq.mm earth wire to geyser points (3 x 9 m = 27 m). Wire FRLS/HFFR PVC insulated Cu, 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; in medium class PVC conduit, IS 9537 (Part 3) — any ISI-marked make.
47D2 [DSR 2.10.3] 5-32 A DP MCB (20 A), C-curve, 10 kA — geyser circuits. Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
48D3 [DSR 2.14.1] 25 A 2 pole RCCB 30 mA — geyser circuits (wet location, mandatory). Standard IS 12640-1. Make: any ISI-marked, preferably the make of the MCBs.
49D4 [DSR 2.16] DP sheet steel enclosure on surface / recess with 25 A DP MCB, C-curve — the switch at each geyser point, outside the W.C. & Bath beside its door (clause 5(g)). MCB IS/IEC 60898-1, 10 kA. Make: MCB — ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric; enclosure of the same make.
50E1 [DSR 2.10.3] 5-32 A DP MCB (20 A), C-curve, 10 kA, in FFDB-2 — one for each of the 6 air-conditioner circuits; circuit wiring, switch at each unit and AC units under the separate Air-Conditioning tender (clause 5(h)). Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
51F1 [DSR 2.10.1] 5-32 A SP MCB (16 A), C-curve, 10 kA — 2 spare ways in FFDB-1 (MCBs fitted; no circuit wiring in this Contract). Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
52F2 [DSR 2.10.3] PROVISION — 20/25 A DP MCB, C-curve, 10 kA, in a spare way of FFDB-2, fixed and connected to the busbar, for a socket or AC circuit called for during execution; executed only on the written order of the E.I.C. (clause 5(n)). Standard IS/IEC 60898-1. Make: ABB / BCH Electric / GE / Havells / L&T / Schneider / Siemens / C&S Electric.
53F3 [DSR 1.14.3] PROVISION — circuit wiring 2 x 4 + 1 x 4 sq.mm earth wire from FFDB-2, for the circuits of the provision MCBs F2 or any other circuit of this size called for during execution; executed only on the written order of the E.I.C. (clause 5(n)) — payable on actual measurement. Wire FRLS/HFFR PVC insulated Cu, 1.1 kV, IS 694 — make: Finolex / Polycab / Havells / KEI; in medium class PVC conduit, IS 9537 (Part 3) — any ISI-marked make.
54G1 [DSR 5.15] 25 x 5 mm GI strip on surface/recess — earth riser and bonding (est. 42 m + 20% provision = 50 m). Hot-dip galvanised (IS 2629 / IS 4736). Make: any.
55G2 [DSR 5.18] 6 SWG dia GI wire loop earthing along conduit (100 m + provision 14 m = 114 m). Hot-dip galvanised (IS 2629 / IS 4736). Make: any.
56G3 [DSR 5.2] Earthing with G.I. earth pipe 4.5 m long, 40 mm dia, with accessories, masonry enclosure with cover plate and locking arrangement, watering pipe, charcoal / coke and salt — 1 No. new electrode, added to the existing earth bus and earth pit of the I.B. and bonded to the earth bar of the new I.B. main DB (clause 5(i)). Hot-dip galvanised (IS 2629 / IS 4736). Make: any.
57G4 [DSR 5.15] 25 x 5 mm GI strip earth lead from the new electrode to the earth bar of the new I.B. main DB (est. 10 m). Hot-dip galvanised (IS 2629 / IS 4736). Make: any.
58H1 [DSR NS-2] Testing, commissioning and handing over — IR, earth continuity/resistance, polarity, RCCB tests with an RCD tester; test report, marked-up as-built drawings, warranty cards; Inspectorate liaison Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58645598
AUTHORITY Government Departments
TENDER VALUE 6.88 Lakhs
LAST DATE 26-12-2026
Authority
Authority Name West Bengal State Electricity Trasnmission Company Limited
Work Description Tender for Internal Electrical Installation And Wiring Of The First Floor Of Inspection Bungalow (I.B.) At Level (+) 4.000 Including Supply Of All Materials At Bankura Area Office, Wbsetcl As Per Schedule , A1 [Dsr Ns-8] Sub-Main, New I.B. Main Db (A6) To The Distribution Block A13 In Ffdb-1, 4 X 25 Sq.Mm + 2 X 10 Sq.Mm Earth Wire, Frls/Hffr Pvc Cu In 32 Mm Medium Class Pvc Conduit (Est. 30 M + 20% Provision = 36 M). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3) - Any Isi-Marked Make. , A2 [Dsr Ns-1] 63 A Tpn Mcb, C-Curve, 10 Ka, On The First-Floor Outgoing Way Of The New I.B. Main Db (A6), In Series With The 300 Ma Rccb A7 - Overcurrent Protection Of Sub-Main A1 And Link Feeder A5 - Complete With Connections, Testing And Commissioning. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , A2a [Dsr Ns-7] 80 A Four Pole (Tpn) Mcb, C-Curve, 10 Ka, Is/Iec 60947-2, Din-Rail Mounted, Main Incomer Of The New I.B. Main Db (A6) - The ConsumerS Circuit Breaker, Cea Regulations 2023, Reg. 37 - Complete With Connections, Testing And Commissioning. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , A3 [Dsr 2.5.3] 12 Way (4+36) Tpn Vertical Mcb Db, Double Door, Without Mcbs And Incomer - Ffdb-1 And Ffdb-2. Sheet Steel, Powder Coated, Ip-42/43, Is/Iec 61439-3. Make: Factory-Assembled, Of The Make Of The Mcbs (Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric). , A4 [Dsr Ns-11] 63 A, 4 Pole, 415 V Rccb, 30 Ma Sensitivity, Type A (Is 12640-1 / Iec 61008-1), In Mcb Db - Incomer And Isolating Switch Of Ffdb-1 And Ffdb-2, Each Fed From The Distribution Block A13 - Complete With Connections, Testing And Commissioning. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , A5 [Dsr Ns-8] Link Feeder, Distribution Block A13 In Ffdb-1 (Line Side Of The Ffdb-1 Rccb) To Ffdb-2, 4 X 25 Sq.Mm + 2 X 10 Sq.Mm Earth Wire, Frls/Hffr Pvc Cu In 32 Mm Medium Class Pvc Conduit (Est. 8 M). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3) - Any Isi-Marked Make. , A6 [Dsr 2.5.2] 8 Way (4+24) Tpn Vertical Mcb Db, Double Door, Without Mcbs And Incomer, With An Incomer Section For The 80 A Four Pole Mcb A2a - New I.B. Main Db Beside The Wbsedcl 3-Phase Meter. Sheet Steel, Powder Coated, Ip-42/43, Is/Iec 61439-3. Make: Factory-Assembled, Of The Make Of The Mcbs (Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric). , A7 [Dsr Ns-6] 63 A, 4 Pole, 415 V Rccb, 300 Ma Sensitivity, Type Ac, In Mcb Db - First-Floor Outgoing Of The New I.B. Main Db, Also Isolating The First Floor - Complete With Connections, Testing And Commissioning. Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , A8 [Dsr 2.10.2] 5-32 A Spn Mcb (32 A), C-Curve, 10 Ka - Ground-Floor Outgoing Of The New I.B. Main Db. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , A9 [Dsr 2.14.2] 40 A 2 Pole Rccb 30 Ma - Ground-Floor Outgoing Of The New I.B. Main Db (Cea Regulations 2023, Reg. 44). Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , A10 [Dsr Ns-9] Link, Wbsedcl Meter Outgoing Terminals To The Main Incomer A2a, 4 X 35 Sq.Mm + 2 X 16 Sq.Mm Earth Wire, Frls/Hffr Pvc Cu In 40 Mm Medium Class Pvc Conduit (Est. 3 M + 20% Provision = 4 M). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3) - Any Isi-Marked Make. , A11 [Dsr 1.14.4] Link, Ground-Floor Outgoing (A8 + A9) To The Existing Ground Floor Main Switch, 2 X 6 Sq.Mm + 1 X 6 Sq.Mm Earth Wire (Est. 3 M). Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , A12 [Dsr 2.21] M.V. Danger Notice Plate 200 X 150 Mm, Mild Steel 2 Mm, Vitreous Enamelled - On The New I.B. Main Db, Ffdb-1 And Ffdb-2 (Cea Regulations 2023, Reg. 20). Make: Any, Approved By The E.I.C. , A13 [Dsr Ns-3] 4 Pole Distribution Block Set, 125-160 A, 415 V, Ip20 With Cover, In Ffdb-1 Ahead Of Its Rccb (A4) - A Single 4 Pole Block Or 4 Single Pole Blocks, Per Pole One Supply Terminal 25-35 Sq.Mm And At Least Two Outgoing Terminals For 25 Sq.Mm Flexible Conductor With Ferrule - With 25 Sq.Mm Jumpers To The Ffdb-1 Rccb; Feeds The Ffdb-1 Rccb And The Link A5 To Ffdb-2 - Supply, Fixing, Connection, Testing And Commissioning. Standard Iec 60947-7-1. Make: Elmex / Connect Well / Yogya Equipments, Or Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , B1 [Dsr 1.10.2] Light / Fan / Exhaust Fan Point Wiring, 1.5 Sq.Mm Frls/Hffr Cu, Modular Switch, Gi Box, Earthing - Group B, Points Of 3 To 6 M Route Length From The Switchboard (6 Battens, 4 Toilet Down Lighters, 8 Down Lighters Dl-9 To Dl-11 And Dl-16 To Dl-20, Fl-1, 4 Cove-Light Points, 4 Fan Points Cf-1, Cf-4 To Cf-6, Exhaust Fans Ex-2, Ex-3). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3), Modular Switch Is 3854 And Plate - Any Isi-Marked Make. , B1a [Dsr 1.10.3] Light / Fan / Exhaust Fan Point Wiring As B1 - Group C, Points Of Over 6 M Route Length From The Switchboard (Conference Down Lighters Dl-1 To Dl-8 And Dl-12 To Dl-14, Fans Cf-2, Cf-3; Dining Dl-15; Battens L12, L15; Exhaust Fans Ex-1, Ex-4 - Route Lengths Scaled From Drg. Bnk/Ib/El/01, Clause 5(E)); Quantities Of B1 And B1a Fixed At Measurement. Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3), Modular Switch Is 3854 And Plate - Any Isi-Marked Make. , B2 [Dsr 2.10.1] 5-32 A Sp Mcb (10 A), C-Curve, 10 Ka - 6 Lighting + 1 Stair + 2 Fan Circuits (Ff-Ltg-2A: Not More Than 10 Points Per Lighting Circuit, Clause 5(E)). Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , B3 [Dsr 1.14.1] Circuit Wiring 2 X 1.5 + 1 X 1.5 Sq.Mm Earth Wire From Ffdb-1 To The Switchboards Of The 9 Lighting / Fan Circuits - 17 Runs (Db To First Switchboard And Between The Switchboards Of A Circuit) X 9 M Average, And 8 M From Sb-11 To The Roof-Door Switchboard Sb-13 - + Provision (161 M + 31 M) - Payable On Actual Measurement. Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , B4 [Dsr 8.9.3] Led Batten Luminaire 36 W, 4000 K, Surface / Ceiling Mounted, Supply, Installation, Testing And Commissioning - Bed Room 2, V.I.P. 3, V.V.I.P. 3 (L1, L2, L11, L12, L23, L14, L15, L24 Of Drg. Bnk/Ib/El/01); No Batten On The Stair (B14a). Bis (Crs) Registered. Make: Any, Approved By The E.I.C. , B5 [Dsr 8.2.3] Led Down Lighter 12-15 W, 4000 K, Recessed Or Surface, One In Each Toilet (L3, L10, L13, L16 Of Drg. Bnk/Ib/El/01), Supply, Installation, Testing And Commissioning. Bis (Crs) Registered. Make: Any, Approved By The E.I.C. , B6 [Dsr 9.2.4] Bldc Ceiling Fan Without Remote, For Speed Control By Wall Regulator, 1400 Mm Sweep, Is 374, Supply, Installation, Testing And Commissioning - Cf-1 To Cf-6 Of Drg. Bnk/Ib/El/01. Make: Any, With The Bis Mark Where Compulsory, Approved By The E.I.C. , B7 [Dsr Ns-4] Exhaust Fan, 300 Mm Sweep, Metal Body With Shutters, Is 2312 - Supply Only - Ex-1 To Ex-4 Of Drg. Bnk/Ib/El/01. Make: Any, With The Bis Mark Where Compulsory, Approved By The E.I.C. , B8 [Dsr 1.50.1] Installation, Testing And Commissioning Of Exhaust Fan Up To 450 Mm Sweep In The Existing Opening, Including Making Good The Damage And Connections , B9 [Dsr 1.11] Twin Control (Two-Way) Light Point Wiring, 1.5 Sq.Mm Frls/Hffr Cu In Medium Class Pvc Conduit, 2 Way Modular Switches, Modular Plate, Gi Box, Earthing - Stair Strip Lines Cv-5 And Cv-6 (Sb-11 / Sb-12); Roof-Stair Strip Lines Cv-7 And Cv-8 (Sb-11 / Sb-13), Each Point Feeding The First Driver Of Its Line (B14a). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3), Modular Switch Is 3854 And Plate - Any Isi-Marked Make. , B10 [Dsr 8.2.5] Led Recessed Down Lighter 22 W, Round, 4000 K, In The False Ceilings - Conference Room 14 (Dl-1 To Dl-14), Dining Room 6 (Dl-15 To Dl-20) Of Drg. Bnk/Ib/El/01 - Supply, Installation, Testing And Commissioning. Bis (Crs) Registered. Make: Any, Approved By The E.I.C. , B11 [Dsr 8.15.3] Led Flood Light 100 W, Ip-65 Minimum - Fl-1 On The Roof, Switched At The Roof-Door Switchboard Sb-13 - Supply, Installation, Testing And Commissioning. Bis (Crs) Registered. Make: Any, Approved By The E.I.C. , B12 [Dsr 1.25] Two Module Stepped Type Electronic Fan Regulator On The Modular Plate Of The Fan Point - Cf-1 To Cf-6. Standard Is 11037. Make: Of The Make And Range Of The Modular Switches (Any Isi-Marked). , B13 [Dsr 1.47] Extra Down Rod Of 10 Cm Length, 15 Mm Dia G.I. Pipe, Heavy Gauge, Painted - Fans Under The False Ceilings Cf-2, Cf-3, Cf-6, 30 Cm Each (Est.). Make: Any, Approved By The E.I.C. , B14 [Dsr Ns-5] Led Cove Light Set Of 5 M - Flexible Led Strip 12 V Dc, About 25 W Per 5 M, Warm White (Outer Cove) Or Magenta (Inner Cove), With One 12 V Dc Constant-Voltage Selv Driver Of Not Less Than 30 W (Bis Registered), 230 V Loop In 20 Mm Pvc Conduit, 12 V Leads - Supply, Installation, Testing And Commissioning - Conference Room 8 Sets, Dining Room 5 Sets. Make: Any, Approved By The E.I.C. , B14a [Dsr Ns-10] Led Strip Light Set Of 5 M For The Stair - Flexible Led Strip As B14, 4000 K, In 5 M Of Surface-Mounted Aluminium Led Profile With Frosted / Opal Diffuser And End Caps, Screw-Fixed On The Wall Just Below The Slab, Light Directed Down, With One 12 V Dc Constant-Voltage Selv Driver Of Not Less Than 30 W (Bis Registered), 230 V Loop In 20 Mm Pvc Conduit, 12 V Leads - Supply, Installation, Testing And Commissioning - Stair Cv-5, Cv-6 And Roof Stair Cv-7, Cv-8 Of Drg. Bnk/Ib/El/01, 2 Sets Each. Make: Any, Approved By The E.I.C. , B15 [Dsr 1.10.3] Call Bell Point Wiring, 1.5 Sq.Mm Frls/Hffr Cu, Modular Bell Push, Gi Box, Earthing - Group C - Bed Room, V.I.P. Room And V.V.I.P. Room, Push At The Bedside, Buzzer (B16) Above The Outside Of The Room Door (Clause 5(F)). Wire 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; Conduit Is 9537 (Part 3) And Modular Bell Push - Any Isi-Marked Make. , B16 [Dsr 1.38] Call Bell / Buzzer, Single Phase 230 V, Complete - One For Each Call Bell Point Of B15. Make: Any, Approved By The E.I.C. , C1 [Dsr 1.32] Gi Box With Modular Plate, 6 Pin 5/6 & 15/16 A Socket And 15/16 A Switch - S1, S8, S11 (One In Each Guest Room), S4 To S7 (Conference Room), S14 (Lobby). Switch Is 3854, Socket Is 1293. Make: Any Isi-Marked; Plate Of The Same Make And Range. , C1a [Dsr 1.31] Gi Box With Modular Plate, 3 Pin 5/6 A Socket And 5/6 A Switch - Bedside Outlets S2, S3, S9, S10, S12, S13. Switch Is 3854, Socket Is 1293. Make: Any Isi-Marked; Plate Of The Same Make And Range. , C2 [Dsr 1.32] Gi Box With Modular Plate, 6 Pin 5/6 & 15/16 A Socket And 15/16 A Switch. Switch Is 3854, Socket Is 1293. Make: Any Isi-Marked; Plate Of The Same Make And Range. , C3 [Dsr 1.14.2] Circuit Wiring 2 X 2.5 + 1 X 2.5 Sq.Mm Earth Wire (15 Socket Points X 9 M = 135 M). Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , C4 [Dsr 2.10.1] 5-32 A Sp Mcb (16 A), C-Curve, 10 Ka - Socket Circuits Ff-Sp-1 To Ff-Sp-6 And Ff-Sp16. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , C5 [Dsr 2.14.1] 25 A 2 Pole Rccb 30 Ma - Fridge Circuit Ff-Sp16. Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , C5a [Dsr 2.14.2] 40 A 2 Pole Rccb 30 Ma - Ahead Of Each Pair Of Socket Circuits (Ff-Sp-1 + Ff-Sp-2, Ff-Sp-3 + Ff-Sp-4, Ff-Sp-5 + Ff-Sp-6). Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , C6 [Dsr 2.10.1] 5-32 A Sp Mcb (10 A), C-Curve, 10 Ka - Conference Audio-Visual Power Circuits Ff-Av-1 And Ff-Av-2. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , C7 [Dsr 2.14.1] 25 A 2 Pole Rccb 30 Ma - Ahead Of The Circuits Ff-Av-1 And Ff-Av-2. Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , C8 [Dsr 1.31] Gi Box With Modular Plate, 3 Pin 5/6 A Socket And 5/6 A Switch - Conference Audio-Visual Power Points Av1 To Av6 (Projector At Ceiling, Screen, Av Rack 2, ChairmanS End 2; Av1 To Av3 On Ff-Av-1, Av4 To Av6 On Ff-Av-2). Switch Is 3854, Socket Is 1293. Make: Any Isi-Marked; Plate Of The Same Make And Range. , C9 [Dsr 1.14.2] Circuit Wiring 2 X 2.5 + 1 X 2.5 Sq.Mm Earth Wire, Circuits Ff-Av-1 And Ff-Av-2 (6 Points X 9 M = 54 M, + Provision 5 M). Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , C10 [Dsr 1.21.2] 25 Mm Medium Class Pvc Conduit, Laid Empty With Gi Pull Wire, For Audio-Visual Signal / Speaker Cables By Others (Est. 60 M). Standard Is 9537 (Part 3). Make: Any Isi-Marked. , C11 [Dsr 1.22.2] Metal Pull Box 100 X 100 X 60 Mm With Phenolic Laminated Cover On The Empty Av Conduit. Make: Any, Approved By The E.I.C. , D1 [Dsr 1.14.3] Circuit Wiring 2 X 4 + 1 X 4 Sq.Mm Earth Wire To Geyser Points (3 X 9 M = 27 M). Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , D2 [Dsr 2.10.3] 5-32 A Dp Mcb (20 A), C-Curve, 10 Ka - Geyser Circuits. Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , D3 [Dsr 2.14.1] 25 A 2 Pole Rccb 30 Ma - Geyser Circuits (Wet Location, Mandatory). Standard Is 12640-1. Make: Any Isi-Marked, Preferably The Make Of The Mcbs. , D4 [Dsr 2.16] Dp Sheet Steel Enclosure On Surface / Recess With 25 A Dp Mcb, C-Curve - The Switch At Each Geyser Point, Outside The W.C. & Bath Beside Its Door (Clause 5(G)). Mcb Is/Iec 60898-1, 10 Ka. Make: Mcb - Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric; Enclosure Of The Same Make. , E1 [Dsr 2.10.3] 5-32 A Dp Mcb (20 A), C-Curve, 10 Ka, In Ffdb-2 - One For Each Of The 6 Air-Conditioner Circuits; Circuit Wiring, Switch At Each Unit And Ac Units Under The Separate Air-Conditioning Tender (Clause 5(H)). Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , F1 [Dsr 2.10.1] 5-32 A Sp Mcb (16 A), C-Curve, 10 Ka - 2 Spare Ways In Ffdb-1 (Mcbs Fitted; No Circuit Wiring In This Contract). Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , F2 [Dsr 2.10.3] Provision - 20/25 A Dp Mcb, C-Curve, 10 Ka, In A Spare Way Of Ffdb-2, Fixed And Connected To The Busbar, For A Socket Or Ac Circuit Called For During Execution; Executed Only On The Written Order Of The E.I.C. (Clause 5(N)). Standard Is/Iec 60898-1. Make: Abb / Bch Electric / Ge / Havells / L&T / Schneider / Siemens / C&S Electric. , F3 [Dsr 1.14.3] Provision - Circuit Wiring 2 X 4 + 1 X 4 Sq.Mm Earth Wire From Ffdb-2, For The Circuits Of The Provision Mcbs F2 Or Any Other Circuit Of This Size Called For During Execution; Executed Only On The Written Order Of The E.I.C. (Clause 5(N)) - Payable On Actual Measurement. Wire Frls/Hffr Pvc Insulated Cu, 1.1 Kv, Is 694 - Make: Finolex / Polycab / Havells / Kei; In Medium Class Pvc Conduit, Is 9537 (Part 3) - Any Isi-Marked Make. , G1 [Dsr 5.15] 25 X 5 Mm Gi Strip On Surface/Recess - Earth Riser And Bonding (Est. 42 M + 20% Provision = 50 M). Hot-Dip Galvanised (Is 2629 / Is 4736). Make: Any. , G2 [Dsr 5.18] 6 Swg Dia Gi Wire Loop Earthing Along Conduit (100 M + Provision 14 M = 114 M). Hot-Dip Galvanised (Is 2629 / Is 4736). Make: Any. , G3 [Dsr 5.2] Earthing With G.I. Earth Pipe 4.5 M Long, 40 Mm Dia, With Accessories, Masonry Enclosure With Cover Plate And Locking Arrangement, Watering Pipe, Charcoal / Coke And Salt - 1 No. New Electrode, Added To The Existing Earth Bus And Earth Pit Of The I.B. And Bonded To The Earth Bar Of The New I.B. Main Db (Clause 5(I)). Hot-Dip Galvanised (Is 2629 / Is 4736). Make: Any. , G4 [Dsr 5.15] 25 X 5 Mm Gi Strip Earth Lead From The New Electrode To The Earth Bar Of The New I.B. Main Db (Est. 10 M). Hot-Dip Galvanised (Is 2629 / Is 4736). Make: Any. , H1 [Dsr Ns-2] Testing, Commissioning And Handing Over - Ir, Earth Continuity/Resistance, Polarity, Rccb Tests With An Rcd Tester; Test Report, Marked-Up As-Built Drawings, Warranty Cards; Inspectorate Liaison
Basic Detail
Tender No SE/AO/BNK/e-NIT/ELEC/26-27/04
Bidding Type Tender
Location
City Bankura
State West Bengal
Key Dates
Publish Date 20 Nov 2026
Submission Date 26 Dec 2026
Open Date 31 Dec 2026
Finance
Tender Value 6.88 Lakhs
Tender Fee Ref. Documents
EMD 5000
Exemption Not Available
Document List
7285ebb9-991c-4ab2-8ad4-bef5cd23f7be.html
BOQ_2569274.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 20, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 26, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 35 days
Dec 31, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 40 days

Tender Documents

Download All (ZIP) ↓
html

7285ebb9-991c-4ab2-8ad4-bef5cd23f7be.html

xls

BOQ_2569274.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender