Tender For Construction Of 33/11 Kv Indoor Type Sub Station At Sector-19 And Interlinking Of Praposed 33/11 Kv S/S At Sector-19 To 132/33 Kv S/S And Inter Linked To 33/11 Kv S/S (Mvvnl) Sector-10 Manjhola Yojna Moradabad.
Tender Overview
Project Description
Tender for Construction Of 33/11 Kv Indoor Type Sub Station At Sector-19 And Interlinking Of Praposed 33/11 Kv S/S At Sector-19 To 132/33 Kv S/S And Inter Linked To 33/11 Kv S/S (Mvvnl) Sector-10 Manjhola Yojna Moradabad.
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Installation, tesing and commissioning of INDOOR TYPE 33KV, HT VCB Panel Board having 2 Nos. Incomers, 1 No. Bus-coupler and 2 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 33KV, 1250Amp, 31.5kA rms-3s, pannel with SCADA compatibility Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 110V DC. The Board shall consist of following panels : |
| 2 | 33KV INCOMER VCB PANEL :33KV, 1250Amp, 31.5KA rms-3s panel with SCADA compatibility Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit Breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (110V DC)Current Transformers : 1 set of 3 Nos. Single Phase, 33KV, 600/300/5+5A, Core 1 : Class 5P10, 15VA and Core 2 : Class 0.5, 15VAPotential Transformers : 1 set of 3 Nos. Single Phase Fixed Type PTs having ratio 33KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protectionAccessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping DeviceIndications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC HealthyMetering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make |
| 3 | Protection & Auxiliary Relays :1 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing Over Current (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%), Earth Fault (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%). 1 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (45% - 90% in steps of 1%), No Voltage Protection (3% - 20% in steps of 1V). 1 No. Trip Circuit Supervision Relay1 No. High Speed Master Trip RelayAdditional Accessories and Features :Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of suppliesStandard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 110V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. (As Per Page No. Make:- ABB/Schneider/Siemens |
| 4 | 33KV OUTGOING VCB PANEL :Same description as INCOMER PANEL above except following changes :Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing PanelsCurrent Transformers : 1 set of 3 Nos. Single Phase, 33KV, 400/200/5+5A PS Class, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2)Additional Protection Relays : 1 No. Numerical Transformer Protection Relay shall have Transformer Differential Protection, Restricted Earth Fault Protection, Over Current + Earth Fault Protection. Relay shall have complete control features.2 No. Auxiliary Relays for Transformer OTI, WTI & Buchholz - Alram & Trip Protection1 No. Trip Circuit Supervision Relay1 No. High Speed Master Trip RelayAdditional Accessories and Features :8 Window Annunciator along with Hooter (As per page No. )Make:- ABB/Schneider/Siemens |
| 5 | 33KV BUS-COUPLER VCB PANEL :Same description as INCOMER PANEL above except following changes :Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays (As per page No. ) Make:- ABB/Schneider/Siemens |
| 6 | Supply, Installation, tesing and commissioning of INDOOR TYPE 11KV, HT VCB 1250Amp 25KA rms-3sec pannel with SCADA Campatibility Board having 2 Nos. Incomers, 1 No. Bus-coupler and 9 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 11KV, 800Amp, 18.4kA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 110V DC.. The Board shall consist of following panels : |
| 7 | 11KV INCOMER VCB PANEL :11KV, 800Amp, 18.4KA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit Breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (110V DC)Current Transformers : 1 set of 3 Nos. Single Phase, 11KV, 800/400/5+5+PS Class, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2)Potential Transformers : 1 set of 3 Nos. Draw-out Type Feeder Connected PTs having ratio 11KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protectionAccessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping DeviceIndications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC HealthyMetering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, AE & Elmeasure make |
| 8 | Protection & Auxiliary Relays :1 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing Over Current (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%), Earth Fault (Low Set : 5% - 200% / High Set : 50% - 1600% in steps of 1%). 1 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (45% - 90% in steps of 1%), No Voltage Protection (3% - 20% in steps of 1V).1 No. Trip Circuit Supervision Relay1 No. High Speed Master Trip RelayAdditional Accessories and Features :Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of suppliesStandard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 110V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. (As per page No. )Make:- ABB/Schneider/Siemens |
| 9 | 11KV OUTGOING VCB PANEL :Same description as INCOMER PANEL above except following changes :Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing PanelsCurrent Transformers : 1 set of 3 Nos. Single Phase, 11KV, 200/100/1+1, Core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA. (As per page No. )Make:- ABB/Schneider/Siemens |
| 10 | 11KV BUS-COUPLER VCB PANEL :Same description as INCOMER PANEL above except following changes :Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays (As per page No. ) Make:- ABB/Schneider/Siemens |
| 11 | Supply, Installation, testing commissioning with loading, unloading etc. 33/11 K.V. Power Transformer 10MVA outdoor distribution Transformer, Tapping range +5% to -15% in step of 2.5% each step with H.T./L.T. bushing, OTI, WTI, Buchholz, Marshalling box OLTC, AVR & RTCC Panel Having Losses-No load losses : 08KW & Load losses : 50 KW as per Latest Specification of UPPCL (Make: TRANSTRON/MODERN/ELECON or Whose Latest GTP Approved in MVVNL having valid CPRI/ERDA Type Test Report) page No. |
| 12 | Supply Installation, and Commissioning of 63 KVA, 11/0.433 KV Transformer including loading, unloading, local carriage with all material, labour, T&P required for proper completion of the work. (Make: TRANSTRON/MODERN/ELECON or Whose Latest GTP Approved in MVVNL having valid CPRI/ERDA Type Test Report) page No. |
| 13 | Construction of Power Transformer Plinth of Size 3.50 x 3.50 x 1 Mtr. and the top of Plinth 30 cm R.C.C. Work 1:2:4 with fixing of 02 Nos. Rail l.b. complete in all respect with required all material such as steel bar, brick, coarse sand, cement, labour and T&P etc for proper completion of the work as per specification of M.V.V.N.L. |
| 14 | Construction of Plinth for 63 KVA Transformer of size 2.00 x 1.25 x 1.0 Complete with all material, labour & T&P required for proper completion of work as per specifiaction drawing and direction of E/I. |
| 15 | Supply,Installation, testing & commissioning of 11 KV Indoor APFC pannel 12.65KV, 3960KVAr, 3- phase, 50 C/s housed in indoor type CRCA panel, capacitor bank having two variable steps of 1188 KVAR.and two variable steps 792 KVAR Aluminium busbars, Epoxy insulators, HT HRC fuse, Surge Suppressor etc. with details are follows-(10 11 KV, aluminium wound, Dry type series reactors a) 1188 KVAR, 11KV 0.2% for 1188 KVAR step-6 Nos., b) 0.792KVAr for 1188 KVAr 0.2% for 792 KVAR step-6 Nos., (2) 11 KV, 3- Phase dry type RVT-1 No. (3) 12 KV 3 Phase indoor type metal enclosed vaccum contactor-12 Nos. (4) Indoor type automatic PFcorrector unit-1 No. (5) IP 42, Indoor CRCA cubicle panel for accommodationg capacitors,series reator, Vaccum contactor, surge suppressor etc. -1set. |
| 16 | 9 KV,10 KA, Class lll surse arrestor |
| 17 | Control cables, lungs/thimble, Junction Box etc. |
| 18 | 11 KV 3 core al, XLPE Insulated 3x300 mm sq. Cable |
| 19 | 11 KV XLPE cable (3x300sq.mm) heat shrinkable jointing kit indoor. |
| 20 | 11 KV VCB Switchgear for capacitor bank with complete arangement Adddisnal pannel for connetion with existing 11 KV bus bar. |
| 21 | Casting of civil foundation. |
| 22 | Cable trench for laying of power/control cables. |
| 23 | Earthing for panel by Chemical pipe earthing.Make ABB/Schneider/Siemens/Crompton (As per page No. ) |
| 24 | Supply & Fixing of 200Amp./ 415volt Heavy Duty bouble break complete with HRC fuse and 200A 4way Al Bus Bar on angle iron frame complete in all respect As per page No |
| 25 | Supply & Fixing of 32Amp. 415V. Metal clad TPN requireable type switch fuse unit on angle iron frame complete in all respects. PWD SI No. 315-2018 Cat.B |
| 26 | Providing necessary T&P and furniture for maintenance staff as per Item Given below. Page No- |
| 27 | 12 mm thick Rubber mat of size 2x 1 m PWD S.O.R. 2018 Item No. 1136 No. 4Brass Earth chain(MR) Nos. 2Rubber hand gloves tested on 1100V. Pair 4Maximum load/ minimum load tripping board complete with all necessary equipments. No. 1Single line diagram with board complete. No. 1Notice board. No. 1Wall clock No. 1First aid boxNo. 1Sign. board of S/S with stand. No. 1Key board No. 1Table with drawer & sunmica Armed chair No. 1Armed chair No. 6Rack No. 2Bench No. 2 |
| 28 | Making fire fighting arrangements in the control room building as per Item Given below. Page No- i-Cost of Fire extinguisher 4.5 kg capacity complete with stand No. 4ii-Cost of Fire bucket complete No. 6iii-Cost of Fire bucket stand for 6 Nos. bucket made of M.S. Angle 45x45x6mm. No. 1 |
| 29 | Supply & Laying of Armoured control cable As per page No. Make Polycab/Gloster/Havells/Universal/KEI/Finolex |
| 30 | 4x2.5 Sqmm |
| 31 | 6x2.5 Sqmm |
| 32 | Supply, Installation, Testing & Commissioning of 24V, 20A Trickle cum Boost Battery Charger suitable for 24V 70AH Battery Bank and also to feed 5A Power to External Load such as Emergency Light etc.70AH, 30V Battery Bank SMF batteries with Mounting Rack & along with connecting Leads and other associated accessories. The Charger shall be suitable to operate Emergency Light Load along with 33kV HT VCB Closing / Opening and also 11kV VCB Closing & Opening. As per page No. |
| 33 | Construction of control cable trench of required size 0.30x0.45 Mtr. M-15 class brick work including plastering etc. and covered with R.C.C. slab (0.50x0.60M) size complete with all material, labour and T&P etc. required for proper completion of work. Detail analysis of Page No- |
| 34 | Supply & Filling of 20mm stone grit in yard 100mm thick complete in all respects. As per page No. |
| 35 | Supply & Laying of Al. conductor 33 KV (E) XLPE cross linked polyethylene) over all served cable with flat galvanised steel strip armouring at a depth of 1.0M below ground level over a cushion of 75mm thick sand bed alround and protect with bricks on sides and top surface 300x3x4 mm red stone the cable run shall be fixed on M.S clamp etc of suitable size and crossing the road cable shall run through 150mm dia hume pipe proper completion of work. Make Polycab/Gloster /Havells/Universal/KEI /Finolex As per page No. |
| 36 | (i) 300Sqmm 3 core |
| 37 | Supply & jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit 33KV 3Core Complete in all respects. Make:- Raychem/3M/Densons |
| 38 | Out door 240-300 Sqmm As per DSR 2018 SI No. 10.8.3 ( Base Rs 71644x0.789x109/110) |
| 39 | In door 240-300 Sqmm As per DSR 2018 SI No. 10.7.3 (Base Rs 34216x0.789x109/110=26751) |
| 40 | Supply & Laying of following type high conductivity aluminum strand compacted circular conductor XLP (E) armoured 11KV cable neutral earthed system confirming to IS 7098-Part-II(1985) with latest amendment at a depth of 1 Mtr. Below ground level over a cushion of 75mm thick sand around and protect with brick on sides and top of cable shall be properly connecting with the earth conductor by clamps etc. with the cost of all material, labour, T&P etc. required for proper completion of the work. Make Polycab/Gloster/Havells /Universal/KEI /Finolex |
| 41 | 70 Sqmm 3 core as per PWD SOR 2014 S.No. 20A.2.1 (Base Rs =1965x0.8475=1665.33) Say 1665.00 |
| 42 | 300 Sqmm 3 Core as per page No. |
| 43 | 400 Sqmm 3 core as per page No. |
| 44 | Supply & Jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit 11KV 3Core Complete in all respects.Make:- Raychem/3M/Densons |
| 45 | Indoor type 300-400 Sqmm As per DSR 2022 SI no. 10.4.4(Base Rs 16249x0.789x109/110) |
| 46 | Indoor type 70 Sqmm As per DSR 2018 SI no. 10.4.1(Base Rs 12181x0.789x109/110) |
| 47 | Outdoor type 300-400 Sqmm As per DSR 2018 SI no. 10.5.4(Base Rs 22795x0.789x109/110) |
| 48 | Outdoor type 70 Sqmm As per DSR 2018 SI no. 10.5.1(Base Rs 18248x0.789x109/110) |
| 49 | Supply and Erection of cable stand of size 3.00x0.50m above G.L. duly grouted with cement concrete upto 50 cm. depth for laying cables made of angle iron size (65x65x6mm) having welded M.S. flat of size 50x6mm on top middle, and 45mm above ground level for fixing cable by clamping with M.S. flat of 40x4mm size as per direction of E/I. As per page No. |
| 50 | Supply & Laying of Al. conductor PVC insulated armoured served. sheathed cable 1100V grade at a depth of 75cm below GL over a cushion of 75mm thick sand alround & protected with bricks on side and top. On surface the cable run shall be fixed on M.S clamps of suitable size and crossing the road cable should run through 150mm dia hume pipe and in case of air like catenary it shall be hanged with the help of G.I wire climpped at several places also armouring of cable shall be properly connected with earth conductor/terminal the job include the cost of all material, labour and T & P required for proper completion of the work. Make Polycab/Gloster/Havells /Universal /KEI /Finolex As per PWD SOR 2018 S.No.20a.1.8 & 20a.1.18 |
| 51 | 10sqmm 4 core (Base Rs 578x0.8475=489.85) |
| 52 | 50 Sqmm 3½core (Base Rs 861x0.8475=729.69) |
| 53 | Supply and fixing of palm or pin copper tin plated cable socket (lugs) to the cable leads insulating with tape and making connections etc. complete in all respects as per PWD SOR 2018, S.I. No. 504 |
| 54 | 10 Sqmm |
| 55 | 25 Sqmm |
| 56 | 50 Sqmm |
| 57 | Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc.. Complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of E/I. |
| 58 | 10 Sqmm 4 core As per PWD SOR 2018 SI no. 503 (h) |
| 59 | 50 Sqmm 3½ core As per PWD SOR 2018 SI no. 503 (L) |
| 60 | Supply & fixing of 7mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thick) having 3mm thickness with Single arm bracket (1Mtr length) on RCC foundation including the cost of 4 way connector with bakelite sheet fixed in G I Pole ,foundation, foundation bolts, excavation & back filling and Required T&P complete in all respect. UP PWD SOR 2024 SI No-21.2 Make:- Vallmont/Bajaj/RRISPAT CONSOUL (Base Rs 21657x0.8475=18354.30) |
| 61 | Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser/Reflector with 1.0 Sqmm 3 core multistand copper unarmored cable suitable lenght and 1 no 6 Amp SPMCB Complete driver set suitable for 60 to 72 watt. Confirming to IP 65 Protection Including Street light Bracket (60 cm long) with pole cap suitable for Street light Fittings complete in all respect as per direction of E/I.PWD SOR 2024 SI No-23.15 CAT-AAA Make Havells/Polycab/Philips/Jaquar (Base Rs 6318x0.8475=5354.50) |
| 62 | Supply and Burring of Safe Earthing Electrode T-39 Zn-Zinc Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 item no. 726 (D) |
| 63 | Supply and Burring of Safe Earthing Electrode T-39 Cu Copper Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 S.No. 727 (D) |
| 64 | Making suitable earth of GI pole with 2.5 Mts. long 20mm M.S rod connected with 7/16 SWG G.S. wire duly clamped & binded on pole including the cost of materials, labour and T & P required for proper completion of work as per direction of E/I. As Page No. |
| 65 | Supply and laying of 32mm x6 mm G.I strip from Earth Electrode directly in the ground as required complete in all respect as per PWD SOR-2018 item no. 717 |
| 66 | Supply and laying of 32mm x6 mm Copper strip Comlete As per PWD SOR 2018 SI. No. 720 |
| 67 | Supply & Fabrication of 8 SWG G.I. Wire mesh Security fencing by providing vertical supports of 50 x 50 x 6mm long including cutting bending at top at a distance of 0.60 Mtr. Including welding, cutting and Bending at bottom at a distance of 0.15 Mtr. Drilling of 04 Nos. Holes of 6mm Dia on Top for Holding the Barbed Wire at a distance of 125 mm hole to hole and 7 Hole in vertical position of 10mm Dia at a distance of 280mm hole to hole for riveting the chain link mesh of size 2\\" x 1\\" and MS Flat 50 x 6mm & 25x3mm and fixing the vertical support in plumb including brick work in repair wall with supply of all material, labour, T&P etc. required for proper completion of the work (Drawing Enclosed) as per MVVNL Specification |
| 68 | Supply & Fixing of Shock Treatment Chart (Prescribed Under I.E. Rules) duly framed with glass and supported from back with hard board or soft board with supply of all material, labour, T&P for proper completion of work. Complete in all respect. as per PWD SOR 2018 SI No. 1134 |
| 69 | Supply & Fixing of Recess/ Surface/ Pendent Mounting Round 10 to 15 Watt L.E.D. Down lighter having powder coated Die cast Aluminium Housing with Heat Sink, Diffuser/ Reflector and Driver set complete in all respect as per PWD SOR 2018 S. No. 1402 Cat AAA |
| 70 | Supply & Fixing of L.E.D. Tubelight with Batten suitable for up to 1x22 Watt L.E.D. Tubelight including Tube on surface complete in all respect as per PWD SOR 2018 S.No. 1413 Cat AAA |
| 71 | Supply & Fixing of L.E.D. Street Light Fittings having Die cast Aluminium Body and diffuser/ Reflector with 1.0sqmm 3 core Multistrand copper unarmoured cable suitable length ,1 no. 6 Amp. SPMCB complete Driver Set suitable for 45 to 50 Watt confirming to IP 65 Protection including street light Bracket (60 cm long) with Pole cap suitable for street light fittings complete in all respect as per Direction of E/I. PWD SOR 2018 S.No. 1421 |
| 72 | Making & Fixing of Retro Radium Board frame with 50sqmm Hollow M.S. Pipe & ACP Sheet 3mm & Retro Radium base 3mm thick including all materials, Labour, T&P etc. and Fixing at Site |
| 73 | S/Erection of 33 KV section Double Pole Structure (Riser) 13 Mtr. Long SP-55 Type S.T. Pole (Bottom Portion Galvanised) made of following types of supports duly grouted. Plinthed plastered and painted in the same manner as already specified for respective supports with 02 Nos. MS channels of size 125x65mm fixed with MS Clamp of size 75x 10mm and 65x65x6 mm angle iron bracing fixed with MS clamp of size 50 x6mm & 06 Nos. Pin Insulator etc. complete with all material and T&P etc. required for proper completion of work. (Only manufactures whose GTP will be Approved in MVVNL) |
| 74 | Supply of 33 KV XLPE cable standered compacted circular Al. conductor screen with extruded semi conducting compound, XLPE insulated in copper Tape, cores laid up to innersheath of PVC, Galvanised Steel Strip Armoured & overall sheathed cable confirming to IS 7098 (Part-2) 2011 with upto date Ammendments complete in all respect as per Direction of E/I. Make (Polycab/ Gloster/Sterlite/Torrent/L.S. Cable/ Havells) |
| 75 | 300 Sqmm 3 core |
| 76 | S/F and jointing of Indoor/outdoor 33 KV jointing kit (Heat Sink) per XLPE cable including cost of all material Labour and T & P as per proper completion of work as per direction of E/I. Make (Raychem/3M) |
| 77 | 300 Sqmm 3 core Indoor (300-240)Sqmm As par DSR 2022 SI no.10.7.3 (Base Rs 34216x0.789x109/110) |
| 78 | 300 Sqmm 3 core Outdoor (300-240)Sqmm As par DSR 2022 SI no.10.8.3( Base Rs 71644x0.789x109/110) |
| 79 | S/F of G.I. Pipe of following sizes for cable duly clamped with supports by 2 No. with clamps of 50 x 6 mm M.S. flats bolts, Nuts and washer required for proper completion of work. Make (TATA/SAIL/JINDAL) As per Page No. |
| 80 | 150 mm dia (18.20 Kg/M) |
| 81 | Supply of HDPE pipe upto PN-6 working pressure Rating material Grade PE-80 Nominal dia (OD) 160 mm 9.50 mm thickness complete in all respect as per relevants I.S. Technicals specification.As per Page No. |
| 82 | Drilling of Road Parallely & Road Crossing at a depth of 2 to 3 Mtr. as required & laying charges of cable & 160mm Dia HDPE Pipe complete with all material, labour, Drilling machine & required T&P etc. required for proper completion of work as per Direction of E/I. |
| 83 | Laying of 33 KV XLPE Cable in loop and On Pole with clamping etc. Complete in all respects with all required material & T&P etc as per direction of E/I as per PWD SOR 2024 S.I. No 20 C .1.19 |
| 84 | S/Making of suitable earth of O/H line pole with 2.5 Mtr. Long 20 mm dia M.S. rod complete with 7/16 SWG G.S. wire in 2.00 Mtr. Long 15 mm dia G.I. Pipe (0.96 Kg/Mtr.) duly clamped on pole with 3 No.s 20 x 3 mm M.S. Flate clamp with bolts nuts and washers complete with all material labour and T&P etc. required for proper completion of work.As per Page No. . |
| 85 | S/F of danger board of size 200 x 250 x 1.6 mm of M.S. sheet fixed with clamp of 20 x 3 mm M.S. flate including bolts, nuts and washerduly painted completed with all material, labour and T&P etc. for proper completion of work. As per Page No. |
| 86 | S/F of barbed wire (1.5kg) duly clamped with 2 No. clamps made of 20x3mm MM. at both ends on poles flate including bolts, required for nuts and T&P etc. required for proper completion of work. As per Page No. |
| 87 | S/F of cable route marker made of 1:2:4 R.C.C. Block size 1000x400x100 mm grouted with 1:3:6 cement stone grit coarse sand 30cm below G.L. with painting numbering & marking etc. complete with all required material T&P etc. complete in all respects as per direction of E/I. (As per drawing atteched) As per Page No. . |
| 88 | Supply, Installation, Testing & Commissioning of 33kv, 630A, 25kA/1Sec, 4-Way, non extensinle outdoor IP55, SF6 Gas insulated Ring Main Unit consist of four (3) motor operated Vacuum Circuit Breaker (VCB), and (1) one motor operated load break Switch, with Suitable site replaceable bushing and full front door cover, as per attached BOM (Ann II) (Configuration: CVVV) Make ABB/Schneider/Siemens (As per page No.) |
| 89 | Supply and Burring of Safe Earthing Electrode T-39 Zn-Zinc Coated, Length 3000 mm, outer pipe 76.30 mm x 3.2 mm inner pipe 42.40 mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square CI frame with hinged cover & masonary housing UPPWD SOR-2018 item no. 726 (D) |
| 90 | Supply and laying of 32 mm x 6 mm G.I. strip from earth electrode directly in the ground as required complete in all respect.UPPWD SOR-2018 item no. 717 |
| 91 | Construction of plinth for 33 KV CVVV RMU Size (3x1.25x0.5Mt) With All Meterial, labour and T & P Required for proper completion of work as per specification drawing and direction of E/l (as per specification attached) |
| 92 | Construction of fencing plinth for RMU of following sizes in Ist class brick work including plaster and providing flat bricks soling and pointing the same with 1:2 cement and fine sand mortar over 75mm thick cement concreting in the ratio 1:6:12 in open space of the cage as per direction of E/I and drawing |
| 93 | 4x 2.25 M For 33 KV CVVV RMU |
| 94 | Supply of fixing of 2.5 Mtr. High cage fabricated with 4.0mm thick chain link /wire mesh of equivalent weight fixed on 50x50x6mm angle iron frame having vertical members spaced at 1.0M to 1.25M. and horizontal members spaced at 1.20M the vetical members shall be grouted in ground and horizontal members in the wall to a depth of 300mm with ends folded. The cage shall have 1000x2000mm size single leaf door with locking arrangement having door frame fabricated with 40x40x5mm angle iron and 4 mm expanded G.I. wire mesh of equivalent weight duly fixed with the cage member. The cage shall have nut bolt arrangement for opening the sides by providing tees 45x20cm of angle iron size 50x50x6mm as per direction of E/I. It shall be painted with red oxide primer and synthetic enamelled paint as per direction of E/I. including all materials, labour and T & P for proper completion of work. As per PWD SOR 2018 S.I No 1142 Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 26 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 26 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender