Tender For Civil And Utility Work For Construction Of New Buildings And Upgradation Of Existing Building At Icat Manesar. Sub-Head: Civil Work Including Electrical Work, Sanitary & Plumbing, Water Supply, Sewage, Hvac, Fire-Fighting Including Fire Pr
Tender Overview
Project Description
Tender for Civil And Utility Work For Construction Of New Buildings And Upgradation Of Existing Building At Icat Manesar. Sub-Head: Civil Work Including Electrical Work, Sanitary & Plumbing, Water Supply, Sewage, Hvac, Fire-Fighting Including Fire Protection, Lift, Cctv And Other Allied Works Etc
BOQ
| Sl. No. | Item Description |
| 1 | TTL BUILDING |
| 2 | Civil works |
| 3 | Electrical Internal Works |
| 4 | LV and Gas Suppersion System |
| 5 | External Electrical Work TTL & VEL |
| 6 | Internal Plumbing Works |
| 7 | Internal Fire Fighting Works |
| 8 | HVAC Works |
| 9 | EEL BUILDING |
| 10 | Civil works |
| 11 | Electrical Internal Works |
| 12 | LV and Gas Suppersion System |
| 13 | External Electrical Work EEL |
| 14 | Internal Plumbing Works |
| 15 | Internal Fire Fighting Works |
| 16 | HVAC Works |
| 17 | VEL BUILDING |
| 18 | Civil works |
| 19 | Electrical Internal Works |
| 20 | LV and Gas Suppersion System |
| 21 | Internal Plumbing Works |
| 22 | Internal Fire Fighting Works |
| 23 | HVAC Works |
| 24 | EXTERNAL PLUMBING |
| 25 | EXTERNAL FIRE FIGHTING |
| 26 | Rain water harvesting |
| 27 | \\"NOTE:-THE ABOVE RATE SHALL BE INCLUSIVE OF ALL TAXES & DUTIES, ROYALTIES, CESS, FEE, ENVIORMENTAL & POLLUTION, FITNESS & SAFETY CLEARANCE CHARGES (IF ANY), OR ANY OTHER INCIDENTAL CHARGES ETC INCLUDING GST.\\" Please Enable Macros to View BoQ information Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 BILL OF QUANTITY CIVIL-INTERIOR-FACADE ICAT MANESAR S.No Ref. Code Description Qty. Unit Rate Amount CPWD DSR 2023 & NSR TTL (In Rs.) |
| 28 | 2.6 0.0875115740740741 All kinds of soil 1501.94 Cum 186.27 279764.11 |
| 29 | 2.26 0.101400462962963 All kinds of soil 1092.32 Cum 133.06 145348.38 |
| 30 | 2.26 0.101400462962963 All kinds of soil 682.7 Cum 266.13 181685.48 |
| 31 | 2.26 0.101400462962963 All kinds of soil 273.08 Cum 399.19 109011.29 |
| 32 | 2.34 0.106956018518519 Chlorpyriphos/ Lindane emulsifiable concentrate of 20% 358.08 Litre 246.35 88211.81 |
| 33 | 2.35 0.107673611111111 Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: 2.35.3.1 With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration 644.55 Sqm 325.37 209714.96 Close timbering in trenches including strutting, shoring and packing cavities (wherever required) complete. (Measurements to be taken of the face area timbered). 0.0944560185185185 Depth not exceeding 1.5 m 218.42 Sqm 146.86 32077.2 0.0944675925925926 Depth exceeding 1.5 m but not exceeding 3 m 218.42 Sqm 162.97 35595.49 0.0944791666666667 Depth exceeding 3 m but not exceeding 4.5 m 218.42 Sqm 199.02 43468.67 MR Depth exceeding 3 m but not exceeding 4.5 m 145.61 Sqm 264.69 38542.22 1.9a 0.0425694444444444 Disposal of moorum/building rubbish/ malba/ similar unserviceable, dismantled or waste material by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 10 km for all lifts, complete as per directions of Engineer-in-charge. 279.5 Cum 229.2 64062.73 1.9b 0.0423842592592593 Carriage of earth upto 5 KM 150.19 Cum 342.82 51489.21 |
| 34 | 4.1 a) 0.167453703703704 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) 40.18 Cum 7148.51 287204.37 |
| 35 | 4.2 Note : (1) Excess/less cement used than specified in this item is payable/recoverable separately. (2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS: 456 -2000 in the items of BMC and RMC. 0.18056712962963 All works upto plinth level : 4.20.1.1 M-10 grade plain cement concrete (cement content considered @ 220 kg/cum) R.O Cum 9271.61 |
| 36 | FORM WORK |
| 37 | 5.9 a ) 0.214594907407407 Foundations, footings, bases of columns, etc. for mass concrete 134.68 Sqm 411.52 55423.81 b ) 0.214606481481482 Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. R.O Sqm 884.12 c ) 0.214618055555556 Suspended floors, roofs, landings, balconies and access platform R.O Sqm 973.06 d ) 0.214641203703704 Lintels, beams, plinth beams, girders, bressumers and cantilevers 612.29 Sqm 772.78 473167.43 e ) 0.214652777777778 Columns,Pillars, Piers, Abutments, Posts and Struts 853.15 Sqm 1008.79 860642.63 f) 0.214664351851852 Stairs, (excluding landings) except spiral-staircases R.O Sqm 802.74 g ) 0.214768518518519 Edges of slabs and breaks in floors and walls. 5.9.16.1 Under 20cms wide R.O Metre 218.85 STEEL REINFORCEMENT |
| 38 | 5.22 a 0.223680555555556 Thermo-Mechanically Treated bars of grade Fe-500D or more. 41248.41 KG 113.18 4668404.31 b 5.22A Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete above plinth level. 5.22A .6 Thermo-Mechanically Treated bars of grade Fe-500D or more. 31953.44 KG 113.18 3616420.25 |
| 39 | 5.37 Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. 0.231261574074074 All works upto plinth level a ) 5.33.1.2 Concrete of M30 grade with minimum cement content of 350 kg /cum 212.52 Cum 10132.69 2153357.06 0.231273148148148 All works above plinth level upto floor V level b ) 5.33.2.2 Concrete of M30 grade with minimum cement content of 350 kg /cum 142.0 Cum 10505.91 1491821.46 |
| 40 | 5.44 The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge. (Material shall conform to ASTM 6063). 0.238900462962963 Floor Joint of 100 mm gap R.O Metre 6708.34 |
| 41 | 5.45 0.239594907407407 Wall Joint of 100 mm gap R.O Metre 5567.75 |
| 42 | 0.240289351851852 The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063.) 0.240289351851852 Roof Joint of 100 mm gap R.O Metre 6281.39 |
| 43 | 16.75 (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately). |
| 44 | 4.2 shuttering and finishing: 0.168090277777778 1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) R.O cum 10384.02 |
| 45 | 6.1 0.250717592592593 Cement mortar 1:6 (1 cement : 6 coarse sand) 128.28 Cum 7484.58 960122.74 |
| 46 | 0.252800925925926 Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 47 | 0.259050925925926 |
| 48 | 8.2 0.33474537037037 Granite of any colour and shade a ) 8.2.2.1 Area of slab upto 0.50 sqm R.O Sqm 5680.93 b ) 8.2.2.2 Area of Slab over 0.50sqm R.O Sqm 5390.03 |
| 49 | 8.3 0.335439814814815 Granite work. R.O Metre 536.19 |
| 50 | 8.31 5.3A NSR Providing and fixing of 1st quality vitrified wall tiles (thiuckness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy,bottle green, black of size 1200x600 mm or as approved by Engineer-in-Charge, over 12 mm thick plaster of cement mortar 1:6 (1 cement : 6 coarse sand) and jointing with3 mm space and filling with epoxy grout complete. 45.6 Sqm 2000.0 91200.0 |
| 51 | 9.21 0.389594907407407 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws 3.78 Sqm 2510.85 9491.0 |
| 52 | 9.24 0.391678240740741 Rectangular or square. R.O Sqm 208.99 |
| 53 | 9.46 0.406967592592593 20 mm dia R.O Metre 412.68 |
| 54 | 9.127 1.0 mm thick. 7.56 Sqm 941.63 7118.7 |
| 55 | 21.18 |
| 56 | NSR - 1 - |
| 57 | 9.161 - |
| 58 | 9.162 - |
| 59 | 9.164 minutes of fire resistance both integrity & radiation control (EW120) and minimum 15 min of insulation (EI15) and having a sound reduction of 37dB and LT of 86%. Glass shall be compliant to class 2(B)2 category of Impact Resistance as per EN 12600. The glass should be manufactured in UL & TUV audited Facility and including UL-EU Certification.The maximum glazing size cannot be more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The test report for the complete system (Glazed Door or Partition) will be considered valid only if it contains the stamp and signature of the authorized signatory from the glass manufacturer. (Actual glass size is to be measured at site for payments). R.O Sqm 45835.33 - - |
| 60 | 9.139 - 2HRS. WOODEN FIRE DOORS - |
| 61 | 9.162E The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal, having mitred cut joint (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS 4351. The smoke seal material shall be of EPDM tested in accordane with ASTM E-84 of minimum size 10 x 4mm. fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed to the three sides to masonary wall opening with CSK/Hex headed fastner of minimum 8 mm dia size and minimum 80mm long hot dip galvanized with 8mm dia Polyamide sleeves @ 5 number at each on vertical sides and 3 number on top side. Door shutter: The double skinned double leaf partially insulated door shutters shall be consisting of minimum 50 mm thickness and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffners as per IS: 16074 including resin bonded mineral wool/ ceremic wool infill material of minimum density 96 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaves. Integral astragals to be provided for double leaf door on the meeting style each on active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935 2002 or butt hinges as per IS 12817, of minimum size 100x75x3 mm @ 5 numbers hiiges upto 2400mm height or as per test evidence, whichever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Accessories Hardware - Fire doorset assembly shall be provided with one number of single point panic push bar (cross bar) for active leaf and one number double point panic push bar (cross bar) with bottom strike of desired finish with verticle shoot bolts on top and bottom for inacitvie leaf of double leaf door as per EN 1125, one number external trim with half cylinder 42 mm long with one side key as per EN 1125, two number heavy duty door closers of size EN 3-5 with standard arm with of desired finish (suitable for 1250 mm wide door leaf) conforming to IS 3564/EN 1154, and one number surface mounted door coordinator for sequencing of closing. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer. 9.162E.1 Single leaf partially Insulated metal fire rated doorset of FD 120 PI classification with 120 minutes integrity and 30 minutes insulation as per IS 3614 2021 for Staircase/Exit pathway/ Refuge area etc R.O Sqm 19820.25 - - |
| 62 | 9.162F Door shutter: The double skinned double leaf partially insulated door shutters shall be consisting of minimum 50 mm thickness and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffners as per IS: 16074 including resin bonded mineral wool/ ceremic wool infill material of minimum density 96 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaves. Integral astragals to be provided for double leaf door on the meeting style each on active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935 2002 or butt hinges as per IS 12817, of minimum size 100x75x3 mm @ 5 numbers hiiges upto 2400mm height or as per test evidence, whichever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Accessories Hardware - Fire doorset assembly shall be provided with one number of single point panic push bar (cross bar) for active leaf and one number double point panic push bar (cross bar) with bottom strike of desired finish with verticle shoot bolts on top and bottom for inacitvie leaf of double leaf door as per EN 1125, one number external trim with half cylinder 42 mm long with one side key as per EN 1125, two number heavy duty door closers of size EN 3-5 with standard arm with of desired finish (suitable for 1250 mm wide door leaf) conforming to IS 3564/EN 1154, and one number surface mounted door coordinator for sequencing of closing. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer. 9.162F.1 Double leaf partially Insulated metal fire rated doorset of FD 120 PI classification with 120 minutes integrity and 30 minutes insulation as per IS 3614 2021 for Staircase/Exit pathway/ Refuge area etc R.O Sqm 20285.6 - - |
| 63 | NSR - 3 ACOUSTIC INSULATION : The Panels filled with Acoustic material Rock wool confirming to IS-8183 of 96 kg/m3 density, very good noise absorber for high, mid & low frequencies along with, 6 MM thick anti donning layer having Thermal Conductivity 0.037 @ 20 C as per EN ISO 8497 (DIN 52613) and 2 mm thick Sound Damping layer MTS 05-303 to achieve higher Sound STC as per site condition. - |
| 64 | MR - MR Insulated Hollow metal fire doors with panic bar - |
| 65 | Door frame shall be step rebate grooved profile of size 125 x 75mm made out of 1.20mm (18gauge) minimum thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. Frames to have inbuild grooved sealing system for taking fire rated seals. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with fire rated puff. - Door leaf shall be 60mm thick fully flush double skin step design door, insulated with or without vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be 120kg high density mineral wool insulation material. Intumescent seals 15 x 1.5mm to be provided. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable shall be maximum 200 x 300mm (or max 0.06sq.mt) with clear borosilicate fire rated glass of 6mm. Glass shall be fixed with suitable gasket and with clip-on arrangement. - Door and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. - Rate shall include supply and installation of frame,shutter as a complete assembly including all hardware, smoke seals & glass with tape. 47.88 Sqm 19567.0 936867.96 - |
| 66 | 9.147 9.147.F1 Casement door single panel with zinc alloy (zamak) 3D - hinges, multi-point locking system with cylinder, zinc alloy (zamak) powder coated handles on both sides. 9.147.F1.1 Using R3 series with frame (55 mm & above) 1.58 Sqm 13113.35 20653.53 x (50 mm & above) & sash (55 mm & above) x (85 mm & above) (Height upto 2.5 metre). - |
| 67 | 26.86 26.86.3 Frame size 50 x 100 mm 22.8 Mtr 947.7 21607.56 - |
| 68 | 26.88 melt adhesive on both faces of shutter and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge. (Note: stainless steel butt hinges and necessary S.S screws shall be paid separately) 26.88.2 35 mm thick 6.3 Sqm 5701.23 35917.77 - |
| 69 | Wire mesh / Glazing of plain/ toughened/ laminated/ douue glass unit with I without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately. - 9.147.A1.1 TWO track two panels sliding Window With Aluminium channel for rdler track, wool pile, nylon rolers with SS 304 body. 9.147.A1.1 using R2series with frame (40 mm & above) x (40 mm & above) & sash (25 mm & above) x (50 mm & above) With Zinc aloy (zamak) powder coated touch locks with hook (Height upto 1.2 metre) 25.92 Sqm 8708.81 225732.44 - - |
| 70 | WOODEN DOOR & WINDOW - a ) NSR Providing and fixing approved brand and manufacture SS 304 Lever Handle D-type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 2.0 Pair 3101.0 6202.0 - b ) NSR Providing and fixing approved brand and manufacture SS 304 grade SS 304 grade Mortice lock with key cylinder fixed fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 2.0 Each 2992.0 5984.0 - c ) NSR Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 250mm long with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 4.0 Each 326.0 1304.0 - d ) NSR Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 150mm long with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 2.0 Each 226.0 452.0 - e ) NSR Providing and fixing approved brand and manufacture SS 304 grade wall mounted door buffer fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 387.0 - - f ) NSR Providing and fixing approved brand and manufacture SS 304 grade Door Stopper - door mounted hanging type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 2.0 Each 448.0 896.0 - g ) 9.84 Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.. 2.0 Each 1031.72 2063.44 - Providing and fixing approved brand and manufacturer SS 304 grade hardware's for Glass Doors etc. - h) NSR Providing and fixing approved brand and manufacture SS 304 grade Top & Bottom Patch fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 4156.0 - i ) NSR Providing and fixing approved brand and manufacture SS 304 grade D type 1200mm Pull Handle with 32mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Pair 8592.0 - - j ) NSR Providing and fixing approved brand and manufacture SS 304 grade D type 300mm Pull Handle with 22mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Pair 2206.0 - k ) NSR Providing and fixing approved brand and manufacture SS 304 grade Centre Patch Lock with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 3713.0 - l ) NSR Providing and fixing approved-quality frosted decorative film on existing glass partitions, doors and windows, comprising precision-cut/plotter-cut patterns, stripes, logos or other approved designs, as per approved drawings and sample. The work shall include cleaning and degreasing the glass surface, measurement, preparation of artwork, cutting and weeding of the film, application using suitable installation solution and tools, accurate alignment, removal of air bubbles, edge finishing and cleaning, complete as per the instructions of the Engineer-in-Charge.. 36.54 Sqm 1650.0 60291.0 - m NSR Providing, supplying, and installing an ultra-slim, floor-to-ceiling sleek glass partition system. The framework shall be fabricated using high-strength, precision-engineered Galvanized Iron (GI) sections with a visible profile width not exceeding 35mm to 45mm. The GI frames must be treated with an anti-corrosive primer and finished with premium architectural-grade polyester powder coating (matte black/charcoal grey) to a minimum thickness of 60 microns. The infill panels shall consist of 12mm (or 10mm) thick clear/frosted fully toughened safety glass conforming to IS 2553 / BS EN 12150 standards, with all edges highly polished and jointed seamlessly using clear architectural-grade structural silicone sealant. The system must include heavy-duty EPDM rubber gaskets within the GI channels to ensure rigid gripping, vibration dampening, and acoustic insulation. R.O Sqm 8050.0 - The rate shall include all necessary floor anchoring, ceiling channeling, wall fastening hardware, scaffolding, lifting to all floor levels, wastage, safety protections, clean-up, and commissioning complete as per architectural drawings and instructions of the Engineer-in-Charge. - Full height glass partition of 12mm thick glass fixed to the floor with aluminium \\"U \\" channel so as to hold the glass below the tile / wooden flooring level and in the ceiling with gypsum board so as to give finish of the frame less glass. The glass shall be edge polished and all joints shall be filled with silicon sealent of appropriate grade and extra sealent cleaned to give a finished look. R.O Sqm 5693.0 - 75 MM THICK FULL HEIGHT BOTH SIDE GYPBOARD PARTITION - Ht - From FFL to 50mm above false ceiling lvl or as mentioned in drawing - Fabricating & fixing in place partitions of overall thickness as specified, formed out of the following components. - a Framework: - Partition to have 48mm GI C-Studs framework at spacing not exceeding 600mm both ways as per details. Framework to be secured to wall surface/column surface closely structural support using wood screw with wooden/pvc rawel plug as per details. horizontal frame members at floor level, skirting level and false ceiling & at intermediate level, shall be as per Indian gypsum details specifications. - Provide an additional hollock wood/Sal wood member of 50mm x 50mm x 100mm treated with anti-termite and fire retardant paints as spacer at the true ceiling level and sub frames for doors and glazed openings while fixing the frame work as per details - b Cladding - The framework to be cladded on both sides with 2 layers of 12.5 mm thk tapered edge gypsum board (IS-2095/1982) in line and level fixed with dry wall screw of 25 mm for first layer and 35 mm for second layer @ 300mm c/c with staggered joints to avoid through joints and finished with proprietary jointing tape and compound as per manufacturer's specification. Joints to be sand papered to achieve a smooth and seamless finish. - c Infill - As an acoustic requirement, contractor to affix 50mm thick glass wool of density 24kg/m3 blanket wrapped in RP tissue suitably affixed to partition framework using where necessary GI binding wire, duct tape as indicated in the drawing. - d Finishes - Two coats of gypboard primer to be applied to finished surfaces and then smoothened using chalk putty as directed. - e Special Provisions - Contractor to make provision for all electrical/networking boxes and to provide 30mm dia cut-outs as required. Electrical/Network boxes /other services to be provided at desired height and location as indicated in the drawing. - At all locations where services are penetrating the partition above false ceiling to have additional GI frame work around the duct/cable tray/pipe and the gaps between the frame work and service to be filled with appropriate fire stop material as directed - f Skirting - Necessary provision to be made to fix the skirting as per details. - g Above ceiling - Partition framework to go upto true ceiling and cladded with single layer of 12.5 mm thick gypsum board on both sides as per details - (measurement of area below ceiling will be considered for payment) - (i) Full height with laminat on the both sides- 75 mm thick R.O Sqm 4000.0 - (ii) Full height partition with gypsum on the both sides- 100 mm thick R.O Sqm 2000.0 - (iii) Full height partition with gypsum on one side and laminate on the other side 100mm R.O Sqm 2500.0 - (iv) 100 mm thk. Half Height laminated partition of 1.2 m height including MDF lining on top edges of gypsum complete . R.O Sqm 1600.0 - Providing and fixing of aluminium skirting of 75 mm with rubber beading at top, to be fixed on Wooden/Gypsum partitions with screws complete as per direction of engineer incharge. - NSR Providing and fixing of toilet cubicles as per following specifications as per size in High pressure laminated waterproof board (HPL board) mentioned in drawings and colour and texture as approved by Engineer In Charge 4.0 Nos 53000.0 212000.0 Door Size : 600mm * 1755mm Divider : (1770mm) Height Thickness of Compact Laminate : 12mm Overall, Height of Cubicles :1950 to 2000mm (Including bottom gap 130mm) a) S S Adjustable Leg- 316 b) S S Coat Hook -304 c) S S Door Knob -304 d) S S Lockset with indicator- 304 e) S S Hinge- 304 f) SS U channel - 304 g) SS Toprail - 304 h) SS Door stopper Channel- 304 i) S.S. F Channel Grade 304 j)Noise Deafening tapes for grooves in doors & Pilasters. - Modular Seek modern Aluminium Partition – 3.0 m High R.O Sqm 6000.0 - Providing and fixing 3000 mm high (Approx) modular aluminium partition, comprising powder-coated extruded aluminium framework conforming to IS 733 & IS 1285, with minimum 50-micron powder coating, and 8 mm thick clear toughened safety glass, fixed with aluminium glazing beads and EPDM/neoprene gaskets, including necessary vertical/horizontal members, stiffeners, cleats, brackets, anchors, fasteners, sealant and all accessories. Framework shall be securely fixed to floor, walls/columns and soffit and shall be sufficiently rigid for the 3.0 m height, complete as per approved shop drawings and direction of Engineer-in-Charge. - Providing and fixing 8 mm thick clear toughened safety glass door of approved size, including necessary patch fittings/hinges, SS 304 handles 450 mm, lock, floor spring/door closer, glass connectors, gaskets, stoppers and all required SS 304 fittings and accessories, complete with cutting, edge polishing, holes/notches and fixing in the modular aluminium partition, as per approved shop drawings and direction of Engineer-in-Charge. R.O Sqm 6500.0 - n NSR Providing and fixing approved-quality digitally printed self-adhesive decorative film on existing glass partitions, doors and windows, with approved design, colour, graphics, logo or pattern as per the approved artwork and sample. The work shall include measurement of glass surfaces, artwork preparation, colour printing using suitable printing technology and compatible ink, application of protective laminate wherever specified, cleaning and degreasing of the glass, cutting, alignment, application of film, removal of air bubbles, edge trimming and finishing, complete as per the manufacturer's recommendations and instructions of the Engineer-in-Charge. R.O Sqm 1250.0 - - |
| 71 | 10.25 0.434050925925926 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works R.O Kg 181.13 - - |
| 72 | 10.28 - |
| 73 | 10.28 Profile C - Fixing with adjustable lugs with split end tail to each jamb 10.2 Mtr 641.97 6548.1 - |
| 74 | 12.51 0.535486111111111 Gutter (600 mm over all girth) R.O Mtr 1378.6 - - |
| 75 | 11.3 0.460428240740741 40 mm thick with 20 mm nominal size stone aggregate R.O Sqm 644.54 - - |
| 76 | 11.6 0.462511574074074 18 mm thick. R.O Sqm 694.76 - - |
| 77 | 11.26 0.476400462962963 25 mm thick R.O Sqm 2044.49 - - |
| 78 | 11.27 - |
| 79 | 11.41 - |
| 80 | 11.41A 11.41A.1 Double charge vitrified tile polished finish of size - 11.41A.1.1 Size of Tile 600 x 600 mm R.O Sqm 1525.46 0.486851851851852 Size of Tile 1000x1000 mm R.O Sqm 1890.7 - - |
| 81 | 11.46 0.490324074074074 Size of Tile 1000x1000 mm R.O Sqm 2269.43 - - |
| 82 | 11.41 0.486828703703704 Size of Tile 600x600 mm R.O Sqm 1630.19 - - |
| 83 | 11.46 0.490300925925926 Size of Tile 600x600 mm R.O Sqm 1703.23 - - |
| 84 | 11.46 0.490300925925926 Size of Tile 600x600 mm R.O Sqm 1703.23 - - |
| 85 | 11.48 - |
| 86 | NSR - |
| 87 | NSR - |
| 88 | 11.51 0.493761574074074 18 mm thick Italian Marble stone slab, Perlato, Rosso verona, R.O Sqm 6929.56 - Fire Red or Dark Emperadore etc. - MR Cement plaster skirting up to 100 mm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 50.0 Rmt 250.0 12500.0 - - |
| 89 | 11.56 0.497233796296296 Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. R.O Sqm 4702.68 - - |
| 90 | 11.55 0.496539351851852 Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. R.O Sqm 3344.12 - - |
| 91 | NSR - |
| 92 | NSR - |
| 93 | NSR - |
| 94 | NSR - |
| 95 | NSR a) Flooring R.O Sqm 2549.0 - b) Skirting R.O Sqm 2549.0 - c) Floor strip on edges R.O Metre 509.8 - - |
| 96 | 16.9 - |
| 97 | NSR NSR Supplying, conveying, laying, and commissioning of high-performance, chemical-resistant Electrostatic Discharge (ESD) Conductive Homogeneous PVC Flooring Sheet of 2.0 mm thickness of required size specifically certified for advanced research and chemistry laboratories including earthing arrangements as per OME's specifications. The complete scope of work must satisfy the given technical compliance ESD flooring with 100 ohm Class D with PVC R.O Sqm 2750.0 - |
| 98 | NSR - |
| 99 | NSR - |
| 100 | NSR - |
| 101 | 11.19 0.471539351851852 Light shade pigment using white cement R.O Sqm 1609.57 - |
| 102 | NSR - |
| 103 | NSR Approved make of Unitex loop pile carpet with 4 mm thick pu underlay & glued as per international fixing standard. Specification Pile material - 100% olefin polypropylene Pile yarn weight - 650 gsm Backing type - pvc reinforced by glass fiber. Flame resistant - pass Underlay - 6mm polyurethane base Make: Unitex or equivalent - |
| 104 | 13.1 0.542384259259259 1:6 (1 cement : 6 fine sand) 1429.18 Sqm 349.82 499952.51 |
| 105 | 13.2 0.543078703703704 1:6 (1 cement : 6 fine sand) 1117.07 Sqm 401.92 448973.4 |
| 106 | 13.16 0.552789351851852 1:3(1 cement: 3 fine sand) R.O Sqm 315.29 |
| 107 | 13.11 |
| 108 | 13.22 10 to 13 m R.O Sqm 91.4 13 to 16 m R.O Sqm 182.81 16 to 19 m R.O Sqm 274.21 19 to 22 m R.O Sqm 365.61 22 to 25 m R.O Sqm 457.01 |
| 109 | 13.26 |
| 110 | 13.87 Old work (one or more coats) R.O Sqm 14.59 |
| 111 | 13.45 0.572928240740741 New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm R.O Sqm 234.65 |
| 112 | 13.47 0.57431712962963 New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) 1117.07 Sqm 179.55 200572.71 |
| 113 | 13.82 Two coats 1429.18 Sqm 144.24 206145.11 |
| 114 | 13.61 Two or more coats on new work 218.05 Sqm 163.6 35673.3 |
| 115 | 13.52 0.577789351851852 On steel work R.O Sqm 253.69 |
| 116 | 21.1 0.875706018518518 For fixed portion 21.1.1.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) R.O Kg 557.13 |
| 117 | 0.875717592592593 21.1.2.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) R.O Kg 665.79 |
| 118 | 21.2 0.876412037037037 Pre-laminated particle board with decorative lamination on both sides R.O Sqm 1170.5 |
| 119 | 21.3 a) 0.877094907407407 With float glass panes of 4.0 mm thickness (weight not less than 10 kg/ sqm) R.O Sqm 1234.93 |
| 120 | 21.8 0.88056712962963 Upto 5mm depth and 5 mm width R.O Metre 101.53 |
| 121 | NSR ALUMINIUM WORK SUB HEAD TOTAL |
| 122 | 22.7 Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge. (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : 0.921539351851852 With average thickness of 120 mm and minimum thickness at khurra as 65mm. R.O Sqm 1767.82 |
| 123 | 22.4 0.919456018518519 Serrated with central bulb (225mm wide,8-11mm thick) R.O Meter 343.84 |
| 124 | 22.14 0.926423611111111 Cement mortar 1:4 (1cement : 4 coarse sand) R.O Cum 15904.29 |
| 125 | 12.21 0.514594907407407 In 75 x75 mm deep chase R.O Meter 320.22 |
| 126 | 12.22 |
| 127 | 22.1 0.917372685185185 Using rough kota stone. R.O Sqm 1590.47 |
| 128 | 22.2 0.91806712962963 Using rough kota stone. R.O Sqm 2124.72 |
| 129 | 0.932650462962963 For vertical surface two coats @ 0.70 kg per sqm per coat |
| 130 | 25.2 a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. - Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub- head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places.. Note:- 2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NBL Certified laboratories 6) Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml R.O Sqm 3683.92 |
| 131 | 25.3 Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. R.O Sqm 3902.4 |
| 132 | 8.32 a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design. b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium item.s The Contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places.\\" R.O Sqm 5262.79 |
| 133 | 12.45 (ii) 0.531273148148148 12.5 mm thick tapered edge Glass Reinforced Gypsum (GRG) board conforming to IS: 2095- (Part 3) : 1996 (Board with BIS certification marks) R.O Sqm 1595.19 |
| 134 | 12.58 0.540289351851852 8 mm thick fully perforated calcium silicate board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process to give stable crystalline structure with minimum compressive strength 225 kg/ sq. cm, bending strength 100 kg/sq. cm , of size 595x595 mm, having perforation of dia. 10 mm with minimum perforated area 18 % with non woven tissue on the back side, having an NRC ( Noise Reduction Coefficient) of 0.85, with 50 mm thick rockwool of 48 kg /cum backing. Sqm 1877.85 |
| 135 | 12.52 0.536134259259259 GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece. 98.72 Sqm 2170.95 214311.47 WOODEN CEILING |
| 136 | 26.27 at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be prepainted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge. 1.10211805555556 With 16 mm thick beveled tegular mineral fibre Antimicrobial false ceiling tile confirming to ISO 5 (class 100 ) specifications R.O Sqm 2568.04 |
| 137 | 26.65 |
| 138 | NSR NSR Providing and fixing decorative wooden false ceiling comprising approved-quality plywood/MDF/HDHMR substrate with natural wood veneer or approved wood-grain laminate finish, fixed over a properly levelled and securely anchored GI/MS supporting framework, including necessary battens, channels, brackets, screws, fasteners, joint treatment, edge trims and finishing/polishing complete as per approved drawings and specifications. The ceiling shall be accurately aligned, securely fixed and finished with uniform colour and texture. All exposed edges shall be neatly finished, and necessary cut-outs shall be provided for lighting fixtures, AC diffusers and other ceiling services. R.O Sqm 4250.0 |
| 139 | 0.64099537037037 |
| 140 | 0.629907407407407 |
| 141 | 15.57 |
| 142 | 0.0425694444444444 |
| 143 | 8.28 0.352789351851852 Decorative veneer facings of approved manufacture R.O Sqm 2042.39 |
| 144 | NSR FACADE WORK |
| 145 | 2.6 0.0875115740740741 All kinds of soil R.O Cum 186.27 |
| 146 | 2.26 0.101400462962963 All kinds of soil R.O Cum 133.06 |
| 147 | 4.1 a) 0.167453703703704 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) R.O Cum 7148.51 |
| 148 | FORM WORK |
| 149 | 5.9 a ) 0.214594907407407 Foundations, footings, bases of columns, etc. for mass concrete R.O Sqm 411.52 b ) 0.214606481481482 Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. R.O Sqm 884.12 c ) 0.214618055555556 Suspended floors, roofs, landings, balconies and access platform R.O Sqm 973.06 d ) 0.214641203703704 Lintels, beams, plinth beams, girders, bressumers and cantilevers R.O Sqm 772.78 e ) 0.214652777777778 Columns,Pillars, Piers, Abutments, Posts and Struts R.O Sqm 1008.79 f) 0.214664351851852 Stairs, (excluding landings) except spiral-staircases R.O Sqm 802.74 g ) 0.214768518518519 Edges of slabs and breaks in floors and walls. 5.9.16.1 Under 20cms wide R.O Metre 218.85 STEEL REINFORCEMENT |
| 150 | 5.22 a 0.223680555555556 Thermo-Mechanically Treated bars of grade Fe-500D or more. R.O Kg 113.18 |
| 151 | 5.37 Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. 0.231261574074074 All works upto plinth level a ) 5.33.1.2 Concrete of M30 grade with minimum cement content of 350 kg /cum R.O Cum 10132.69 0.231273148148148 All works above plinth level upto floor V level |
| 152 | 10.25 0.434050925925926 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works R.O Kg 181.13 |
| 153 | 25.3 Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. R.O Sqm 3902.4 |
| 154 | 12.51 0.535439814814815 Flashings/ Aprons.( Upto 600 mm) 61.01 Rmt 509.59 31090.0 MR Providing and fixing of laser cut jali in MDF with PU paint finish 42.31 Sqm 12560.0 531413.6 TOTAL OF FAÇADE WORK SHEET PILING |
| 155 | MR SHEET PILING SUB HEAD TOTAL in Figures 45984320.86 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 BILL OF QUANTITY CIVIL-INTERIOR-FACADE ICAT MANESAR S.No Ref. Code Description Qty. Unit Rate Amount CPWD DSR 2023 & NSR EEL (In Rs.) |
| 156 | 2.6 0.0875115740740741 All kinds of soil 432.07 Cum 186.27 80481.03 |
| 157 | 2.26 0.101400462962963 All kinds of soil 106.29 Cum 133.06 14143.36 |
| 158 | 2.26 0.101400462962963 All kinds of soil R.O Cum 266.13 |
| 159 | 2.26 0.101400462962963 All kinds of soil R.O Cum 399.19 |
| 160 | 2.34 0.106956018518519 Chlorpyriphos/ Lindane emulsifiable concentrate of 20% 357.55 Litre 246.35 88081.24 |
| 161 | 2.35 0.107673611111111 Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: 2.35.3.1 With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration 643.58 Sqm 325.37 209400.36 Close timbering in trenches including strutting, shoring and packing cavities (wherever required) complete. (Measurements to be taken of the face area timbered). 0.0944560185185185 Depth not exceeding 1.5 m R.O Sqm 146.86 0.0944675925925926 Depth exceeding 1.5 m but not exceeding 3 m R.O Sqm 162.97 0.0944791666666667 Depth exceeding 3 m but not exceeding 4.5 m R.O Sqm 199.02 MR Depth exceeding 3 m but not exceeding 4.5 m R.O Sqm 264.69 1.9a 0.0425694444444444 Disposal of moorum/building rubbish/ malba/ similar unserviceable, dismantled or waste material by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 10 km for all lifts, complete as per directions of Engineer-in-charge. 261.45 Cum 229.2 59926.37 1.9b 0.0423842592592593 Carriage of earth upto 5 KM 43.21 Cum 342.82 14812.14 |
| 162 | 4.1 a) 0.167453703703704 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) 80.36 Cum 7148.51 574454.49 |
| 163 | 4.2 Note : (1) Excess/less cement used than specified in this item is payable/recoverable separately. (2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS: 456 -2000 in the items of BMC and RMC. 0.18056712962963 All works upto plinth level : 4.20.1.1 M-10 grade plain cement concrete (cement content considered @ 220 kg/cum) R.O Cum 9271.61 |
| 164 | FORM WORK |
| 165 | 5.9 a ) 0.214594907407407 Foundations, footings, bases of columns, etc. for mass concrete 102.57 Sqm 411.52 42209.83 b ) 0.214606481481482 Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. R.O Sqm 884.12 c ) 0.214618055555556 Suspended floors, roofs, landings, balconies and access platform R.O Sqm 973.06 d ) 0.214641203703704 Lintels, beams, plinth beams, girders, bressumers and cantilevers 104.52 Sqm 772.78 80768.45 e ) 0.214652777777778 Columns,Pillars, Piers, Abutments, Posts and Struts 73.08 Sqm 1008.79 73722.24 f) 0.214664351851852 Stairs, (excluding landings) except spiral-staircases R.O Sqm 802.74 g ) 0.214768518518519 Edges of slabs and breaks in floors and walls. 5.9.16.1 Under 20cms wide R.O Metre 218.85 STEEL REINFORCEMENT |
| 166 | 5.22 a 0.223680555555556 Thermo-Mechanically Treated bars of grade Fe-500D or more. 17367.18 KG 113.18 1965578.52 b 5.22A Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete above plinth level. 5.22A .6 Thermo-Mechanically Treated bars of grade Fe-500D or more. 12702.61 KG 113.18 1437652.77 |
| 167 | 5.37 Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. 0.231261574074074 All works upto plinth level a ) 5.33.1.2 Concrete of M30 grade with minimum cement content of 350 kg /cum 84.55 Cum 10132.69 856754.54 0.231273148148148 All works above plinth level upto floor V level b ) 5.33.2.2 Concrete of M30 grade with minimum cement content of 350 kg /cum 107.88 Cum 10505.91 1133354.01 |
| 168 | 5.35 specified cement content therein. |
| 169 | 5.44 The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge. (Material shall conform to ASTM 6063). 0.238900462962963 Floor Joint of 100 mm gap R.O Metre 6708.34 |
| 170 | 5.45 0.239594907407407 Wall Joint of 100 mm gap R.O Metre 5567.75 - - |
| 171 | 0.240289351851852 The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063.) - 0.240289351851852 Roof Joint of 100 mm gap R.O Metre 6281.39 - - |
| 172 | 16.75 (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately). |
| 173 | 4.2 shuttering and finishing: 0.168090277777778 1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) R.O cum 10384.02 - - - |
| 174 | 6.1 0.250717592592593 Cement mortar 1:6 (1 cement : 6 coarse sand) R.O Cum 7484.58 - - |
| 175 | 0.252800925925926 Cement mortar 1:6 (1 cement : 6 coarse sand) - |
| 176 | 0.259050925925926 - |
| 177 | 6.15 - |
| 178 | 6.5 - - |
| 179 | 8.2 0.33474537037037 Granite of any colour and shade - a ) 8.2.2.1 Area of slab upto 0.50 sqm R.O Sqm 5680.93 - b ) 8.2.2.2 Area of Slab over 0.50sqm 57.29 Sqm 5390.03 308784.22 - |
| 180 | 8.3 0.335439814814815 Granite work. 66.0 Metre 536.19 35388.6 |
| 181 | 8.31 5.3A NSR Providing and fixing of 1st quality vitrified wall tiles (thiuckness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy,bottle green, black of size 1200x600 mm or as approved by Engineer-in-Charge, over 12 mm thick plaster of cement mortar 1:6 (1 cement : 6 coarse sand) and jointing with3 mm space and filling with epoxy grout complete. 185.78 Sqm 2000.0 371558.4 |
| 182 | 9.21 0.389594907407407 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws R.O Sqm 2510.85 |
| 183 | 9.24 0.391678240740741 Rectangular or square. R.O Sqm 208.99 |
| 184 | 9.46 0.406967592592593 20 mm dia R.O Metre 412.68 |
| 185 | 9.127 0.463217592592593 1.0 mm thick. R.O Sqm 941.63 |
| 186 | 21.18 |
| 187 | NSR - 1 |
| 188 | 9.161 |
| 189 | 9.162 |
| 190 | 9.164 minutes of fire resistance both integrity & radiation control (EW120) and minimum 15 min of insulation (EI15) and having a sound reduction of 37dB and LT of 86%. Glass shall be compliant to class 2(B)2 category of Impact Resistance as per EN 12600. The glass should be manufactured in UL & TUV audited Facility and including UL-EU Certification.The maximum glazing size cannot be more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The test report for the complete system (Glazed Door or Partition) will be considered valid only if it contains the stamp and signature of the authorized signatory from the glass manufacturer. (Actual glass size is to be measured at site for payments). R.O Sqm 45835.33 |
| 191 | 9.139 2HRS. WOODEN FIRE DOORS |
| 192 | 9.162E The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal, having mitred cut joint (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS 4351. The smoke seal material shall be of EPDM tested in accordane with ASTM E-84 of minimum size 10 x 4mm. fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed to the three sides to masonary wall opening with CSK/Hex headed fastner of minimum 8 mm dia size and minimum 80mm long hot dip galvanized with 8mm dia Polyamide sleeves @ 5 number at each on vertical sides and 3 number on top side. Door shutter: The double skinned double leaf partially insulated door shutters shall be consisting of minimum 50 mm thickness and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffners as per IS: 16074 including resin bonded mineral wool/ ceremic wool infill material of minimum density 96 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaves. Integral astragals to be provided for double leaf door on the meeting style each on active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935 2002 or butt hinges as per IS 12817, of minimum size 100x75x3 mm @ 5 numbers hiiges upto 2400mm height or as per test evidence, whichever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Accessories Hardware Fire doorset assembly shall be provided with one number of single point panic push bar (cross bar) for active leaf and one number double point panic push bar (cross bar) with bottom strike of desired finish with verticle shoot bolts on top and bottom for inacitvie leaf of double leaf door as per EN 1125, one number external trim with half cylinder 42 mm long with one side key as per EN 1125, two number heavy duty door closers of size EN 3-5 with standard arm with of desired finish (suitable for 1250 mm wide door leaf) conforming to IS 3564/EN 1154, and one number surface mounted door coordinator for sequencing of closing. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer. 9.162E.1 Single leaf partially Insulated metal fire rated doorset of FD 120 PI classification with 120 minutes integrity and 30 minutes insulation as per IS 3614 2021 for Staircase/Exit pathway/ Refuge area etc R.O Sqm 19820.25 |
| 193 | 9.162F Door shutter: The double skinned double leaf partially insulated door shutters shall be consisting of minimum 50 mm thickness and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffners as per IS: 16074 including resin bonded mineral wool/ ceremic wool infill material of minimum density 96 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaves. Integral astragals to be provided for double leaf door on the meeting style each on active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935 2002 or butt hinges as per IS 12817, of minimum size 100x75x3 mm @ 5 numbers hiiges upto 2400mm height or as per test evidence, whichever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Accessories Hardware Fire doorset assembly shall be provided with one number of single point panic push bar (cross bar) for active leaf and one number double point panic push bar (cross bar) with bottom strike of desired finish with verticle shoot bolts on top and bottom for inacitvie leaf of double leaf door as per EN 1125, one number external trim with half cylinder 42 mm long with one side key as per EN 1125, two number heavy duty door closers of size EN 3-5 with standard arm with of desired finish (suitable for 1250 mm wide door leaf) conforming to IS 3564/EN 1154, and one number surface mounted door coordinator for sequencing of closing. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer. 9.162F.1 Double leaf partially Insulated metal fire rated doorset of FD 120 PI classification with 120 minutes integrity and 30 minutes insulation as per IS 3614 2021 for Staircase/Exit pathway/ Refuge area etc R.O Sqm 20285.6 |
| 194 | NSR - 3 ACOUSTIC INSULATION : The Panels filled with Acoustic material Rock wool confirming to IS-8183 of 96 kg/m3 density, very good noise absorber for high, mid & low frequencies along with, 6 MM thick anti donning layer having Thermal Conductivity 0.037 @ 20 C as per EN ISO 8497 (DIN 52613) and 2 mm thick Sound Damping layer MTS 05-303 to achieve higher Sound STC as per site condition. R.O |
| 195 | MR MR Insulated Hollow metal fire doors with panic bar |
| 196 | Door frame shall be step rebate grooved profile of size 125 x 75mm made out of 1.20mm (18gauge) minimum thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. Frames to have inbuild grooved sealing system for taking fire rated seals. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with fire rated puff. Door leaf shall be 60mm thick fully flush double skin step design door, insulated with or without vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be 120kg high density mineral wool insulation material. Intumescent seals 15 x 1.5mm to be provided. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable shall be maximum 200 x 300mm (or max 0.06sq.mt) with clear borosilicate fire rated glass of 6mm. Glass shall be fixed with suitable gasket and with clip-on arrangement. Door and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate shall include supply and installation of frame,shutter as a complete assembly including all hardware, smoke seals & glass with tape. R.O Sqm 19567.0 |
| 197 | 9.147 9.147.F1 Casement door single panel with zinc alloy (zamak) 3D hinges, multi-point locking system with cylinder, zinc alloy (zamak) powder coated handles on both sides. 9.147.F1.1 Using R3 series with frame (55 mm & above) 46.62 Sqm 13113.35 611344.6 x (50 mm & above) & sash (55 mm & above) x (85 mm & above) (Height upto 2.5 metre). |
| 198 | 26.86 26.86.3 Frame size 50 x 100 mm R.O Mtr 947.7 |
| 199 | 26.88 melt adhesive on both faces of shutter and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge. (Note: stainless steel butt hinges and necessary S.S screws shall be paid separately) 26.88.2 35 mm thick R.O Sqm 5701.23 |
| 200 | Wire mesh / Glazing of plain/ toughened/ laminated/ douue glass unit with I without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately. 9.147.A1.1 TWO track two panels sliding Window With Aluminium channel for rdler track, wool pile, nylon rolers with SS 304 body. 9.147.A1.1 using R2series with frame (40 mm & above) x (40 mm & above) & sash (25 mm & above) x (50 mm & above) With Zinc aloy (zamak) powder coated touch locks with hook (Height upto 1.2 metre) R.O Sqm 8708.81 |
| 201 | WOODEN DOOR & WINDOW a ) NSR Providing and fixing approved brand and manufacture SS 304 Lever Handle D-type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Pair 3101.0 b ) NSR Providing and fixing approved brand and manufacture SS 304 grade SS 304 grade Mortice lock with key cylinder fixed fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 2992.0 c ) NSR Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 250mm long with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 326.0 d ) NSR Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 150mm long with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 226.0 e ) NSR Providing and fixing approved brand and manufacture SS 304 grade wall mounted door buffer fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 387.0 f ) NSR Providing and fixing approved brand and manufacture SS 304 grade Door Stopper - door mounted hanging type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 448.0 g ) 9.84 Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.. R.O Each 1031.72 Providing and fixing approved brand and manufacturer SS 304 grade hardware's for Glass Doors etc. h) NSR Providing and fixing approved brand and manufacture SS 304 grade Top & Bottom Patch fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 4156.0 i ) NSR Providing and fixing approved brand and manufacture SS 304 grade D type 1200mm Pull Handle with 32mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Pair 8592.0 j ) NSR Providing and fixing approved brand and manufacture SS 304 grade D type 300mm Pull Handle with 22mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 40.0 Pair 2206.0 88240.0 k ) NSR Providing and fixing approved brand and manufacture SS 304 grade Centre Patch Lock with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 40.0 Each 3713.0 148520.0 l ) NSR Providing and fixing approved-quality frosted decorative film on existing glass partitions, doors and windows, comprising precision-cut/plotter-cut patterns, stripes, logos or other approved designs, as per approved drawings and sample. The work shall include cleaning and degreasing the glass surface, measurement, preparation of artwork, cutting and weeding of the film, application using suitable installation solution and tools, accurate alignment, removal of air bubbles, edge finishing and cleaning, complete as per the instructions of the Engineer-in-Charge.. 1200.0 Sqm 1650.0 1980000.0 - m NSR Providing, supplying, and installing an ultra-slim, floor-to-ceiling sleek glass partition system. The framework shall be fabricated using high-strength, precision-engineered Galvanized Iron (GI) sections with a visible profile width not exceeding 35mm to 45mm. The GI frames must be treated with an anti-corrosive primer and finished with premium architectural-grade polyester powder coating (matte black/charcoal grey) to a minimum thickness of 60 microns. The infill panels shall consist of 12mm (or 10mm) thick clear/frosted fully toughened safety glass conforming to IS 2553 / BS EN 12150 standards, with all edges highly polished and jointed seamlessly using clear architectural-grade structural silicone sealant. The system must include heavy-duty EPDM rubber gaskets within the GI channels to ensure rigid gripping, vibration dampening, and acoustic insulation. R.O Sqm 8050.0 - The rate shall include all necessary floor anchoring, ceiling channeling, wall fastening hardware, scaffolding, lifting to all floor levels, wastage, safety protections, clean-up, and commissioning complete as per architectural drawings and instructions of the Engineer-in-Charge. Full height glass partition of 12mm thick glass fixed to the floor with aluminium \\"U \\" channel so as to hold the glass below the tile / wooden flooring level and in the ceiling with gypsum board so as to give finish of the frame less glass. The glass shall be edge polished and all joints shall be filled with silicon sealent of appropriate grade and extra sealent cleaned to give a finished look. 900.0 Sqm 5693.0 5123700.0 75 MM THICK FULL HEIGHT BOTH SIDE GYPBOARD PARTITION Ht - From FFL to 50mm above false ceiling lvl or as mentioned in drawing Fabricating & fixing in place partitions of overall thickness as specified, formed out of the following components. a Framework: Partition to have 48mm GI C-Studs framework at spacing not exceeding 600mm both ways as per details. Framework to be secured to wall surface/column surface closely structural support using wood screw with wooden/pvc rawel plug as per details. horizontal frame members at floor level, skirting level and false ceiling & at intermediate level, shall be as per Indian gypsum details specifications. Provide an additional hollock wood/Sal wood member of 50mm x 50mm x 100mm treated with anti-termite and fire retardant paints as spacer at the true ceiling level and sub frames for doors and glazed openings while fixing the frame work as per details b Cladding The framework to be cladded on both sides with 2 layers of 12.5 mm thk tapered edge gypsum board (IS-2095/1982) in line and level fixed with dry wall screw of 25 mm for first layer and 35 mm for second layer @ 300mm c/c with staggered joints to avoid through joints and finished with proprietary jointing tape and compound as per manufacturer's specification. Joints to be sand papered to achieve a smooth and seamless finish. c Infill As an acoustic requirement, contractor to affix 50mm thick glass wool of density 24kg/m3 blanket wrapped in RP tissue suitably affixed to partition framework using where necessary GI binding wire, duct tape as indicated in the drawing. d Finishes Two coats of gypboard primer to be applied to finished surfaces and then smoothened using chalk putty as directed. e Special Provisions Contractor to make provision for all electrical/networking boxes and to provide 30mm dia cut-outs as required. Electrical/Network boxes /other services to be provided at desired height and location as indicated in the drawing. At all locations where services are penetrating the partition above false ceiling to have additional GI frame work around the duct/cable tray/pipe and the gaps between the frame work and service to be filled with appropriate fire stop material as directed f Skirting Necessary provision to be made to fix the skirting as per details. g Above ceiling Partition framework to go upto true ceiling and cladded with single layer of 12.5 mm thick gypsum board on both sides as per details (measurement of area below ceiling will be considered for payment) (i) Full height with laminat on the both sides- 75 mm thick 60.0 Sqm 4000.0 240000.0 - (ii) Full height partition with gypsum on the both sides- 100 mm thick 60.0 Sqm 2000.0 120000.0 - (iii) Full height partition with gypsum on one side and laminate on the other side 100mm 60.0 Sqm 2500.0 150000.0 - (iv) 100 mm thk. Half Height laminated partition of 1.2 m height including MDF lining on top edges of gypsum complete . 30.0 Sqm 1600.0 48000.0 - Providing and fixing of aluminium skirting of 75 mm with rubber beading at top, to be fixed on Wooden/Gypsum partitions with screws complete as per direction of engineer incharge. 320.0 Rmt 425.0 136000.0 - NSR Providing and fixing of toilet cubicles as per following specifications as per size in High pressure laminated waterproof board (HPL board) mentioned in drawings and colour and texture as approved by Engineer In Charge 20.0 Nos 53000.0 1060000.0 Door Size : 600mm * 1755mm Divider : (1770mm) Height Thickness of Compact Laminate : 12mm Overall, Height of Cubicles :1950 to 2000mm (Including bottom gap 130mm) a) S S Adjustable Leg- 316 b) S S Coat Hook -304 c) S S Door Knob -304 d) S S Lockset with indicator- 304 e) S S Hinge- 304 f) SS U channel - 304 g) SS Toprail - 304 h) SS Door stopper Channel- 304 i) S.S. F Channel Grade 304 j)Noise Deafening tapes for grooves in doors & Pilasters. Modular Seek modern Aluminium Partition – 3.0 m High 90.0 Sqm 6000.0 540000.0 Providing and fixing 3000 mm high (Approx) modular aluminium partition, comprising powder-coated extruded aluminium framework conforming to IS 733 & IS 1285, with minimum 50-micron powder coating, and 8 mm thick clear toughened safety glass, fixed with aluminium glazing beads and EPDM/neoprene gaskets, including necessary vertical/horizontal members, stiffeners, cleats, brackets, anchors, fasteners, sealant and all accessories. Framework shall be securely fixed to floor, walls/columns and soffit and shall be sufficiently rigid for the 3.0 m height, complete as per approved shop drawings and direction of Engineer-in-Charge. - Toughened Glass Door 8.0 Sqm 6500.0 52000.0 Providing and fixing 8 mm thick clear toughened safety glass door of approved size, including necessary patch fittings/hinges, SS 304 handles 450 mm, lock, floor spring/door closer, glass connectors, gaskets, stoppers and all required SS 304 fittings and accessories, complete with cutting, edge polishing, holes/notches and fixing in the modular aluminium partition, as per approved shop drawings and direction of Engineer-in-Charge. - n NSR Providing and fixing approved-quality digitally printed self-adhesive decorative film on existing glass partitions, doors and windows, with approved design, colour, graphics, logo or pattern as per the approved artwork and sample. The work shall include measurement of glass surfaces, artwork preparation, colour printing using suitable printing technology and compatible ink, application of protective laminate wherever specified, cleaning and degreasing of the glass, cutting, alignment, application of film, removal of air bubbles, edge trimming and finishing, complete as per the manufacturer's recommendations and instructions of the Engineer-in-Charge. 257.0 Sqm 1250.0 321250.0 |
| 202 | 10.25 0.434050925925926 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works R.O Kg 181.13 |
| 203 | 10.28 |
| 204 | 10.28 Profile C Fixing with adjustable lugs with split end tail to each jamb R.O Mtr 641.97 |
| 205 | 12.51 0.535486111111111 Gutter (600 mm over all girth) 214.3 Mtr 1378.6 295433.29 |
| 206 | 11.3 0.460428240740741 40 mm thick with 20 mm nominal size stone aggregate R.O Sqm 644.54 |
| 207 | 11.6 0.462511574074074 18 mm thick. R.O Sqm 694.76 |
| 208 | 11.26 0.476400462962963 25 mm thick R.O Sqm 2044.49 |
| 209 | 11.27 |
| 210 | 11.41 |
| 211 | 11.41A 11.41A.1 Double charge vitrified tile polished finish of size 11.41A.1.1 Size of Tile 600 x 600 mm 50.0 Sqm 1525.46 76273.02 0.486851851851852 Size of Tile 1000x1000 mm 1115.85 Sqm 1890.7 2109737.84 |
| 212 | 11.46 0.490324074074074 Size of Tile 1000x1000 mm 44.31 Sqm 2269.43 100557.19 |
| 213 | 11.41 0.486828703703704 Size of Tile 600x600 mm R.O Sqm 1630.19 |
| 214 | 11.46 0.490300925925926 Size of Tile 600x600 mm R.O Sqm 1703.23 |
| 215 | 11.46 0.490300925925926 Size of Tile 600x600 mm R.O Sqm 1703.23 |
| 216 | 11.48 |
| 217 | 11.51 0.493761574074074 18 mm thick Italian Marble stone slab, Perlato, Rosso verona, 891.38 Sqm 6929.56 6176875.58 Fire Red or Dark Emperadore etc. - MR Cement plaster skirting up to 100 mm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 50.0 Rmt 250.0 12500.0 |
| 218 | 11.56 0.497233796296296 Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. R.O Sqm 4702.68 |
| 219 | 11.55 0.496539351851852 Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. 50.0 Sqm 3344.12 167206.15 |
| 220 | NSR a) Flooring R.O Sqm 2549.0 b) Skirting R.O Sqm 2549.0 c) Floor strip on edges R.O Metre 509.8 |
| 221 | NSR NSR Supplying, conveying, laying, and commissioning of high-performance, chemical-resistant Electrostatic Discharge (ESD) Conductive Homogeneous PVC Flooring Sheet of 2.0 mm thickness of required size specifically certified for advanced research and chemistry laboratories including earthing arrangements as per OME's specifications. The complete scope of work must satisfy the given technical compliance ESD flooring with 100 ohm Class D with PVC 550.0 Sqm 2750.0 1512500.0 |
| 222 | 11.19 0.471539351851852 Light shade pigment using white cement R.O Sqm 1609.57 |
| 223 | NSR Approved make of Unitex loop pile carpet with 4 mm thick pu underlay & glued as per international fixing standard. Specification Pile material - 100% olefin polypropylene Pile yarn weight - 650 gsm Backing type - pvc reinforced by glass fiber. Flame resistant - pass Underlay - 6mm polyurethane base Make: Unitex or equivalent |
| 224 | 13.1 0.542384259259259 1:6 (1 cement : 6 fine sand) 3324.88 Sqm 349.82 1163102.28 |
| 225 | 13.2 0.543078703703704 1:6 (1 cement : 6 fine sand) R.O Sqm 401.92 |
| 226 | 13.16 0.552789351851852 1:3(1 cement: 3 fine sand) R.O Sqm 315.29 |
| 227 | 13.11 |
| 228 | 13.22 10 to 13 m R.O Sqm 91.4 13 to 16 m R.O Sqm 182.81 16 to 19 m R.O Sqm 274.21 19 to 22 m R.O Sqm 365.61 22 to 25 m R.O Sqm 457.01 |
| 229 | 13.26 |
| 230 | 13.87 0.602106481481481 Old work (one or more coats) R.O Sqm 14.59 |
| 231 | 13.45 0.572928240740741 New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm R.O Sqm 234.65 |
| 232 | 13.47 0.57431712962963 New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) 935.32 Sqm 179.55 167939.47 |
| 233 | 13.82 0.598634259259259 Two coats 3324.88 Sqm 144.24 479581.25 |
| 234 | 13.61 0.584039351851852 Two or more coats on new work 1057.9 Sqm 163.6 173073.33 |
| 235 | 13.52 0.577789351851852 On steel work R.O Sqm 253.69 |
| 236 | 21.1 0.875706018518518 For fixed portion 21.1.1.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) R.O Kg 557.13 |
| 237 | 0.875717592592593 21.1.2.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) R.O Kg 665.79 |
| 238 | 21.2 0.876412037037037 Pre-laminated particle board with decorative lamination on both sides R.O Sqm 1170.5 |
| 239 | 21.3 a) 0.877094907407407 With float glass panes of 4.0 mm thickness (weight not less than 10 kg/ sqm) R.O Sqm 1234.93 |
| 240 | 21.8 0.88056712962963 Upto 5mm depth and 5 mm width R.O Metre 101.53 |
| 241 | NSR ALUMINIUM WORK SUB HEAD TOTAL |
| 242 | 22.7 Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge. (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : 0.921539351851852 With average thickness of 120 mm and minimum thickness at khurra as 65mm. R.O Sqm 1767.82 |
| 243 | 22.4 0.919456018518519 Serrated with central bulb (225mm wide,8-11mm thick) R.O Meter 343.84 |
| 244 | 22.14 0.926423611111111 Cement mortar 1:4 (1cement : 4 coarse sand) R.O Cum 15904.29 |
| 245 | 12.21 0.514594907407407 In 75 x75 mm deep chase R.O Meter 320.22 |
| 246 | 12.22 |
| 247 | 22.1 0.917372685185185 Using rough kota stone. R.O Sqm 1590.47 |
| 248 | 22.2 0.91806712962963 Using rough kota stone. R.O Sqm 2124.72 |
| 249 | 0.932650462962963 For vertical surface two coats @ 0.70 kg per sqm per coat |
| 250 | 25.2 a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub- head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places.. Note:- 2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NBL Certified laboratories 6) Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml 889.07 Sqm 3683.92 3275261.6 |
| 251 | 25.3 Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. 889.07 Sqm 3902.4 3469510.13 |
| 252 | 8.32 a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design. b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium item.s The Contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places.\\" R.O Sqm 5262.79 |
| 253 | 12.45 (ii) 0.531273148148148 12.5 mm thick tapered edge Glass Reinforced Gypsum (GRG) board conforming to IS: 2095- (Part 3) : 1996 (Board with BIS certification marks) R.O Sqm 1595.19 |
| 254 | 12.58 0.540289351851852 8 mm thick fully perforated calcium silicate board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process to give stable crystalline structure with minimum compressive strength 225 kg/ sq. cm, bending strength 100 kg/sq. cm , of size 595x595 mm, having perforation of dia. 10 mm with minimum perforated area 18 % with non woven tissue on the back side, having an NRC ( Noise Reduction Coefficient) of 0.85, with 50 mm thick rockwool of 48 kg /cum backing. Sqm 1877.85 |
| 255 | 12.52 0.536134259259259 GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece. 3338.67 Sqm 2170.95 7248083.68 WOODEN CEILING |
| 256 | 26.27 at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be prepainted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge. 1.10211805555556 With 16 mm thick beveled tegular mineral fibre Antimicrobial false ceiling tile confirming to ISO 5 (class 100 ) specifications R.O Sqm 2568.04 |
| 257 | 26.65 |
| 258 | NSR NSR Providing and fixing decorative wooden false ceiling comprising approved-quality plywood/MDF/HDHMR substrate with natural wood veneer or approved wood-grain laminate finish, fixed over a properly levelled and securely anchored GI/MS supporting framework, including necessary battens, channels, brackets, screws, fasteners, joint treatment, edge trims and finishing/polishing complete as per approved drawings and specifications. The ceiling shall be accurately aligned, securely fixed and finished with uniform colour and texture. All exposed edges shall be neatly finished, and necessary cut-outs shall be provided for lighting fixtures, AC diffusers and other ceiling services. 50.0 Sqm 4250.0 212500.0 |
| 259 | NSR R.O R.O |
| 260 | NSR R.O R.O R.O |
| 261 | 0.64099537037037 R.O |
| 262 | 15.3 R.O |
| 263 | 0.629907407407407 R.O |
| 264 | 15.57 R.O |
| 265 | 0.0425694444444444 R.O |
| 266 | Nsr R.O |
| 267 | Nsr R.O |
| 268 | 8.28 0.352789351851852 Decorative veneer facings of approved manufacture 50.0 Sqm 2042.39 102119.74 |
| 269 | Nsr - |
| 270 | Nsr FACADE WORK |
| 271 | 2.6 0.0875115740740741 All kinds of soil 270.4 Cum 186.27 50367.0 |
| 272 | 2.26 0.101400462962963 All kinds of soil 67.6 Cum 133.06 8995.12 |
| 273 | 4.1 a) 0.167453703703704 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) 9.68 Cum 7148.51 69197.6 |
| 274 | FORM WORK |
| 275 | 5.9 a ) 0.214594907407407 Foundations, footings, bases of columns, etc. for mass concrete 72.0 Sqm 411.52 29629.6 b ) 0.214606481481482 Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. R.O Sqm 884.12 c ) 0.214618055555556 Suspended floors, roofs, landings, balconies and access platform R.O Sqm 973.06 d ) 0.214641203703704 Lintels, beams, plinth beams, girders, bressumers and cantilevers 123.1 Sqm 772.78 95130.54 e ) 0.214652777777778 Columns,Pillars, Piers, Abutments, Posts and Struts 52.2 Sqm 1008.79 52658.75 f) 0.214664351851852 Stairs, (excluding landings) except spiral-staircases R.O Sqm 802.74 g ) 0.214768518518519 Edges of slabs and breaks in floors and walls. 5.9.16.1 Under 20cms wide R.O Metre 218.85 STEEL REINFORCEMENT |
| 276 | 5.22 a 0.223680555555556 Thermo-Mechanically Treated bars of grade Fe-500D or more. 9102.03 Kilogram 113.18 1030147.18 |
| 277 | 5.37 Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. 0.231261574074074 All works upto plinth level a ) 5.33.1.2 Concrete of M30 grade with minimum cement content of 350 kg /cum 57.26 Cum 10132.69 580175.12 0.231273148148148 All works above plinth level upto floor V level |
| 278 | 10.25 0.434050925925926 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works 50658.85 Kg 181.13 9175657.15 |
| 279 | 25.3 Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. R.O Sqm 3902.4 |
| 280 | 12.51 0.535439814814815 Flashings/ Aprons.( Upto 600 mm) R.O Rmt 509.59 MR Providing and fixing of laser cut jali in MDF with PU paint finish R.O Sqm 12560.0 TOTAL OF FAÇADE WORK SHEET PILING |
| 281 | MR SHEET PILING SUB HEAD TOTAL in Figures 99973889.08 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 BILL OF QUANTITY CIVIL-INTERIOR-FACADE ICAT MANESAR S.No Ref. Code Description Qty. Unit Rate Amount CPWD DSR 2023 & NSR VEL (In Rs.) |
| 282 | 2.6 0.0875115740740741 All kinds of soil 9183.9 Cum 186.27 1710671.28 - |
| 283 | 2.26 0.101400462962963 All kinds of soil 6887.93 Cum 133.06 916534.3 - |
| 284 | 2.26 0.101400462962963 All kinds of soil 4591.95 Cum 266.13 1222045.73 - |
| 285 | 2.26 0.101400462962963 All kinds of soil 2295.98 Cum 399.19 916534.3 - |
| 286 | 2.25 - |
| 287 | 2.27 - |
| 288 | 2.34 0.106956018518519 Chlorpyriphos/ Lindane emulsifiable concentrate of 20% 743.73 Litre 246.35 183215.39 - |
| 289 | 2.35 0.107673611111111 Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: - 2.35.3.1 With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration 1338.72 Sqm 325.37 435574.6 - Close timbering in trenches including strutting, shoring and packing cavities (wherever required) complete. (Measurements to be taken of the - face area timbered). 0.0944560185185185 Depth not exceeding 1.5 m 242.25 Sqm 146.86 35577.69 0.0944675925925926 Depth exceeding 1.5 m but not exceeding 3 m 242.25 Sqm 162.97 39479.92 0.0944791666666667 Depth exceeding 3 m but not exceeding 4.5 m 242.25 Sqm 199.02 48212.28 MR Depth exceeding 3 m but not exceeding 4.5 m 161.5 Sqm 264.69 42748.22 - - 1.9a 0.0425694444444444 Disposal of moorum/building rubbish/ malba/ similar unserviceable, dismantled or waste material by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 10 km for all lifts, complete as per directions of Engineer-in-charge. R.O Cum 229.2 - - 1.9b 0.0423842592592593 Carriage of earth upto 5 KM 918.39 Cum 342.82 314840.62 - |
| 290 | 4.1 a) 0.167453703703704 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) 133.87 Cum 7148.51 956985.71 - |
| 291 | 4.17 - |
| 292 | 4.2 Note : (1) Excess/less cement used than specified in this item is payable/recoverable separately. (2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS: 456 -2000 in the items of BMC and RMC. - 0.18056712962963 All works upto plinth level : - 4.20.1.1 M-10 grade plain cement concrete (cement content considered @ 220 kg/cum) R.O Cum 9271.61 - - - |
| 293 | FORM WORK - |
| 294 | 5.9 a ) 0.214594907407407 Foundations, footings, bases of columns, etc. for mass concrete 72.68 Sqm 411.52 29907.38 - b ) 0.214606481481482 Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. 1443.35 Sqm 884.12 1276093.88 - c ) 0.214618055555556 Suspended floors, roofs, landings, balconies and access platform 2743.32 Sqm 973.06 2669404.4 - d ) 0.214641203703704 Lintels, beams, plinth beams, girders, bressumers and cantilevers 1784.39 Sqm 772.78 1378939.55 - e ) 0.214652777777778 Columns,Pillars, Piers, Abutments, Posts and Struts 1886.54 Sqm 1008.79 1903115.29 - f) 0.214664351851852 Stairs, (excluding landings) except spiral-staircases R.O Sqm 802.74 - - g ) 0.214768518518519 Edges of slabs and breaks in floors and walls. - 5.9.16.1 Under 20cms wide R.O Metre 218.85 - - STEEL REINFORCEMENT - |
| 295 | 5.22 a 0.223680555555556 Thermo-Mechanically Treated bars of grade Fe-500D or more. 188469.29 KG 113.18 21330537.45 - b 5.22A Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete above plinth level. - 5.22A .6 Thermo-Mechanically Treated bars of grade Fe-500D or more. 135901.27 KG 113.18 15381005.89 - - |
| 296 | 5.37 Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. - 0.231261574074074 All works upto plinth level - a ) 5.33.1.2 Concrete of M30 grade with minimum cement content of 350 kg /cum 1341.07 Cum 10132.69 13588695.18 - 0.231273148148148 All works above plinth level upto floor V level - b ) 5.33.2.2 Concrete of M30 grade with minimum cement content of 350 kg /cum 366.97 Cum 10505.91 3855348.27 - |
| 297 | 5.38 - |
| 298 | 5.35 - |
| 299 | 5.44 The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge. (Material shall conform to ASTM 6063). - 0.238900462962963 Floor Joint of 100 mm gap R.O Metre 6708.34 - - |
| 300 | 5.45 0.239594907407407 Wall Joint of 100 mm gap R.O Metre 5567.75 - - |
| 301 | 0.240289351851852 The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063.) - 0.240289351851852 Roof Joint of 100 mm gap R.O Metre 6281.39 - - |
| 302 | 16.75 (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately). |
| 303 | 4.2 shuttering and finishing: 0.168090277777778 1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) 2.77 cum 10384.02 28749.62 - - |
| 304 | 6.1 0.250717592592593 Cement mortar 1:6 (1 cement : 6 coarse sand) R.O Cum 7484.58 - - |
| 305 | 0.252800925925926 Cement mortar 1:6 (1 cement : 6 coarse sand) - |
| 306 | 0.259050925925926 - |
| 307 | 6.15 - |
| 308 | 6.5 - - |
| 309 | 8.2 0.33474537037037 Granite of any colour and shade - a ) 8.2.2.1 Area of slab upto 0.50 sqm R.O Sqm 5680.93 - b ) 8.2.2.2 Area of Slab over 0.50sqm 122.93 Sqm 5390.03 662602.17 - |
| 310 | 8.3 0.335439814814815 Granite work. 210.0 Metre 536.19 112600.1 - |
| 311 | 8.31 5.3A NSR Providing and fixing of 1st quality vitrified wall tiles (thiuckness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy,bottle green, black of size 1200x600 mm or as approved by Engineer-in-Charge, over 12 mm thick plaster of cement mortar 1:6 (1 cement : 6 coarse sand) and jointing with3 mm space and filling with epoxy grout complete. 96.74 Sqm 2000.0 193488.0 |
| 312 | 9.21 0.389594907407407 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws 26.46 Sqm 2510.85 66437.01 - |
| 313 | 9.23 - |
| 314 | 9.24 0.391678240740741 Rectangular or square. R.O Sqm 208.99 - - |
| 315 | 9.46 0.406967592592593 20 mm dia R.O Metre 412.68 - - |
| 316 | 9.127 1.0 mm thick. 52.92 Sqm 941.63 49830.88 - |
| 317 | 9.12 - |
| 318 | 21.18 - |
| 319 | NSR - 1 - |
| 320 | 9.161 - |
| 321 | 9.162 - |
| 322 | 9.164 minutes of fire resistance both integrity & radiation control (EW120) and minimum 15 min of insulation (EI15) and having a sound reduction of 37dB and LT of 86%. Glass shall be compliant to class 2(B)2 category of Impact Resistance as per EN 12600. The glass should be manufactured in UL & TUV audited Facility and including UL-EU Certification.The maximum glazing size cannot be more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The test report for the complete system (Glazed Door or Partition) will be considered valid only if it contains the stamp and signature of the authorized signatory from the glass manufacturer. (Actual glass size is to be measured at site for payments). R.O Sqm 45835.33 - - |
| 323 | 9.139 - 2HRS. WOODEN FIRE DOORS - |
| 324 | 9.162E The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal, having mitred cut joint (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS 4351. The smoke seal material shall be of EPDM tested in accordane with ASTM E-84 of minimum size 10 x 4mm. fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed to the three sides to masonary wall opening with CSK/Hex headed fastner of minimum 8 mm dia size and minimum 80mm long hot dip galvanized with 8mm dia Polyamide sleeves @ 5 number at each on vertical sides and 3 number on top side. Door shutter: The double skinned double leaf partially insulated door shutters shall be consisting of minimum 50 mm thickness and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffners as per IS: 16074 including resin bonded mineral wool/ ceremic wool infill material of minimum density 96 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaves. Integral astragals to be provided for double leaf door on the meeting style each on active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935 2002 or butt hinges as per IS 12817, of minimum size 100x75x3 mm @ 5 numbers hiiges upto 2400mm height or as per test evidence, whichever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Accessories Hardware - Fire doorset assembly shall be provided with one number of single point panic push bar (cross bar) for active leaf and one number double point panic push bar (cross bar) with bottom strike of desired finish with verticle shoot bolts on top and bottom for inacitvie leaf of double leaf door as per EN 1125, one number external trim with half cylinder 42 mm long with one side key as per EN 1125, two number heavy duty door closers of size EN 3-5 with standard arm with of desired finish (suitable for 1250 mm wide door leaf) conforming to IS 3564/EN 1154, and one number surface mounted door coordinator for sequencing of closing. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer. 9.162E.1 Single leaf partially Insulated metal fire rated doorset of FD 120 PI classification with 120 minutes integrity and 30 minutes insulation as per IS 3614 2021 for Staircase/Exit pathway/ Refuge area etc R.O Sqm 19820.25 - - |
| 325 | 9.162F Door shutter: The double skinned double leaf partially insulated door shutters shall be consisting of minimum 50 mm thickness and having box like structure, slots cut and holes punched, for fixing of hardwares with stiffners as per IS: 16074 including resin bonded mineral wool/ ceremic wool infill material of minimum density 96 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaves. Integral astragals to be provided for double leaf door on the meeting style each on active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing butt hinges as per EN 1935 2002 or butt hinges as per IS 12817, of minimum size 100x75x3 mm @ 5 numbers hiiges upto 2400mm height or as per test evidence, whichever is more, fixed with M6 25 screws. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Accessories Hardware - Fire doorset assembly shall be provided with one number of single point panic push bar (cross bar) for active leaf and one number double point panic push bar (cross bar) with bottom strike of desired finish with verticle shoot bolts on top and bottom for inacitvie leaf of double leaf door as per EN 1125, one number external trim with half cylinder 42 mm long with one side key as per EN 1125, two number heavy duty door closers of size EN 3-5 with standard arm with of desired finish (suitable for 1250 mm wide door leaf) conforming to IS 3564/EN 1154, and one number surface mounted door coordinator for sequencing of closing. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer. 9.162F.1 Double leaf partially Insulated metal fire rated doorset of FD 120 PI classification with 120 minutes integrity and 30 minutes insulation as per IS 3614 2021 for Staircase/Exit pathway/ Refuge area etc R.O Sqm 20285.6 - - |
| 326 | NSR - 3 ACOUSTIC INSULATION : The Panels filled with Acoustic material Rock wool confirming to IS-8183 of 96 kg/m3 density, very good noise absorber for high, mid & low frequencies along with, 6 MM thick anti donning layer having Thermal Conductivity 0.037 @ 20 C as per EN ISO 8497 (DIN 52613) and 2 mm thick Sound Damping layer MTS 05-303 to achieve higher Sound STC as per site condition. - |
| 327 | MR - MR Insulated Hollow metal fire doors with panic bar - |
| 328 | Door frame shall be step rebate grooved profile of size 125 x 75mm made out of 1.20mm (18gauge) minimum thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. Frames to have inbuild grooved sealing system for taking fire rated seals. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with fire rated puff. - Door leaf shall be 60mm thick fully flush double skin step design door, insulated with or without vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be 120kg high density mineral wool insulation material. Intumescent seals 15 x 1.5mm to be provided. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable shall be maximum 200 x 300mm (or max 0.06sq.mt) with clear borosilicate fire rated glass of 6mm. Glass shall be fixed with suitable gasket and with clip-on arrangement. - Door and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. - Rate shall include supply and installation of frame,shutter as a complete assembly including all hardware, smoke seals & glass with tape. 22.05 Sqm 19567.0 431452.35 - |
| 329 | 9.147 9.147.F1 Casement door single panel with zinc alloy (zamak) 3D - hinges, multi-point locking system with cylinder, zinc alloy (zamak) powder coated handles on both sides. 9.147.F1.1 Using R3 series with frame (55 mm & above) 32.4 Sqm 13113.35 424872.7 x (50 mm & above) & sash (55 mm & above) x (85 mm & above) (Height upto 2.5 metre). - |
| 330 | 26.86 26.86.3 Frame size 50 x 100 mm R.O Mtr 947.7 - - |
| 331 | 26.88 melt adhesive on both faces of shutter and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge. (Note: stainless steel butt hinges and necessary S.S screws shall be paid separately) 26.88.2 35 mm thick R.O Sqm 5701.23 - - |
| 332 | Wire mesh / Glazing of plain/ toughened/ laminated/ douue glass unit with I without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately. - 9.147.A1.1 TWO track two panels sliding Window With Aluminium channel for rdler track, wool pile, nylon rolers with SS 304 body. 9.147.A1.1 using R2series with frame (40 mm & above) x (40 mm & above) & sash (25 mm & above) x (50 mm & above) With Zinc aloy (zamak) powder coated touch locks with hook (Height upto 1.2 metre) 32.4 Sqm 8708.81 282165.55 - - |
| 333 | WOODEN DOOR & WINDOW - a ) NSR Providing and fixing approved brand and manufacture SS 304 Lever Handle D-type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 10.0 Each 3101.0 31010.0 - b ) NSR Providing and fixing approved brand and manufacture SS 304 grade SS 304 grade Mortice lock with key cylinder fixed fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 10.0 Each 2992.0 29920.0 - c ) NSR Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 250mm long with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 12.0 Each 326.0 3912.0 - d ) NSR Providing and fixing approved brand and manufacture SS 304 grade Tower bolt 150mm long with 10mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 226.0 - - e ) NSR Providing and fixing approved brand and manufacture SS 304 grade wall mounted door buffer fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 387.0 - - f ) NSR Providing and fixing approved brand and manufacture SS 304 grade Door Stopper - door mounted hanging type fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 12.0 Each 448.0 5376.0 - g ) 9.84 Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.. R.O Each 1031.72 - - Providing and fixing approved brand and manufacturer SS 304 grade hardware's for Glass Doors etc. - h) NSR Providing and fixing approved brand and manufacture SS 304 grade Top & Bottom Patch fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Each 4156.0 - - i ) NSR Providing and fixing approved brand and manufacture SS 304 grade D type 1200mm Pull Handle with 32mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. R.O Pair 8592.0 - - j ) NSR Providing and fixing approved brand and manufacture SS 304 grade D type 300mm Pull Handle with 22mm dia fixed with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 15.0 Pair 2206.0 33090.0 - k ) NSR Providing and fixing approved brand and manufacture SS 304 grade Centre Patch Lock with SS screws etc. complete in all respects as per manufacturers' specifications & as directed by Engineer-in-charge. 1.0 Each 3713.0 3713.0 - l ) NSR Providing and fixing approved-quality frosted decorative film on existing glass partitions, doors and windows, comprising precision-cut/plotter-cut patterns, stripes, logos or other approved designs, as per approved drawings and sample. The work shall include cleaning and degreasing the glass surface, measurement, preparation of artwork, cutting and weeding of the film, application using suitable installation solution and tools, accurate alignment, removal of air bubbles, edge finishing and cleaning, complete as per the instructions of the Engineer-in-Charge.. 274.66 Sqm 1650.0 453182.4 - m NSR Providing, supplying, and installing an ultra-slim, floor-to-ceiling sleek glass partition system. The framework shall be fabricated using high-strength, precision-engineered Galvanized Iron (GI) sections with a visible profile width not exceeding 35mm to 45mm. The GI frames must be treated with an anti-corrosive primer and finished with premium architectural-grade polyester powder coating (matte black/charcoal grey) to a minimum thickness of 60 microns. The infill panels shall consist of 12mm (or 10mm) thick clear/frosted fully toughened safety glass conforming to IS 2553 / BS EN 12150 standards, with all edges highly polished and jointed seamlessly using clear architectural-grade structural silicone sealant. The system must include heavy-duty EPDM rubber gaskets within the GI channels to ensure rigid gripping, vibration dampening, and acoustic insulation. R.O Sqm 8050.0 - The rate shall include all necessary floor anchoring, ceiling channeling, wall fastening hardware, scaffolding, lifting to all floor levels, wastage, safety protections, clean-up, and commissioning complete as per architectural drawings and instructions of the Engineer-in-Charge. - Full height glass partition of 12mm thick glass fixed to the floor with aluminium \\"U \\" channel so as to hold the glass below the tile / wooden flooring level and in the ceiling with gypsum board so as to give finish of the frame less glass. The glass shall be edge polished and all joints shall be filled with silicon sealent of appropriate grade and extra sealent cleaned to give a finished look. 36.0 Sqm 5693.0 204948.0 - 75 MM THICK FULL HEIGHT BOTH SIDE GYPBOARD PARTITION - Ht - From FFL to 50mm above false ceiling lvl or as mentioned in drawing - Fabricating & fixing in place partitions of overall thickness as specified, formed out of the following components. - a Framework: - Partition to have 48mm GI C-Studs framework at spacing not exceeding 600mm both ways as per details. Framework to be secured to wall surface/column surface closely structural support using wood screw with wooden/pvc rawel plug as per details. horizontal frame members at floor level, skirting level and false ceiling & at intermediate level, shall be as per Indian gypsum details specifications. - Provide an additional hollock wood/Sal wood member of 50mm x 50mm x 100mm treated with anti-termite and fire retardant paints as spacer at the true ceiling level and sub frames for doors and glazed openings while fixing the frame work as per details - b Cladding - The framework to be cladded on both sides with 2 layers of 12.5 mm thk tapered edge gypsum board (IS-2095/1982) in line and level fixed with dry wall screw of 25 mm for first layer and 35 mm for second layer @ 300mm c/c with staggered joints to avoid through joints and finished with proprietary jointing tape and compound as per manufacturer's specification. Joints to be sand papered to achieve a smooth and seamless finish. - c Infill - As an acoustic requirement, contractor to affix 50mm thick glass wool of density 24kg/m3 blanket wrapped in RP tissue suitably affixed to partition framework using where necessary GI binding wire, duct tape as indicated in the drawing. - d Finishes - Two coats of gypboard primer to be applied to finished surfaces and then smoothened using chalk putty as directed. - e Special Provisions - Contractor to make provision for all electrical/networking boxes and to provide 30mm dia cut-outs as required. Electrical/Network boxes /other services to be provided at desired height and location as indicated in the drawing. - At all locations where services are penetrating the partition above false ceiling to have additional GI frame work around the duct/cable tray/pipe and the gaps between the frame work and service to be filled with appropriate fire stop material as directed - f Skirting - Necessary provision to be made to fix the skirting as per details. - g Above ceiling - Partition framework to go upto true ceiling and cladded with single layer of 12.5 mm thick gypsum board on both sides as per details - (measurement of area below ceiling will be considered for payment) - (i) Full height with laminat on the both sides- 75 mm thick 9.0 Sqm 4000.0 36000.0 - (ii) Full height partition with gypsum on the both sides- 100 mm thick 9.0 Sqm 2000.0 18000.0 - (iii) Full height partition with gypsum on one side and laminate on the other side 100mm 9.0 Sqm 2500.0 22500.0 - (iv) 100 mm thk. Half Height laminated partition of 1.2 m height including MDF lining on top edges of gypsum complete . 9.0 Sqm 1600.0 14400.0 - Providing and fixing of aluminium skirting of 75 mm with rubber beading at top, to be fixed on Wooden/Gypsum partitions with screws complete as per direction of engineer incharge. R.O Rmt 30.0 - - NSR Providing and fixing of toilet cubicles as per following specifications as per size in High pressure laminated waterproof board (HPL board) mentioned in drawings and colour and texture as approved by Engineer In Charge 6.0 Nos 53000.0 318000.0 Door Size : 600mm * 1755mm Divider : (1770mm) Height Thickness of Compact Laminate : 12mm Overall, Height of Cubicles :1950 to 2000mm (Including bottom gap 130mm) a) S S Adjustable Leg- 316 b) S S Coat Hook -304 c) S S Door Knob -304 d) S S Lockset with indicator- 304 e) S S Hinge- 304 f) SS U channel - 304 g) SS Toprail - 304 h) SS Door stopper Channel- 304 i) S.S. F Channel Grade 304 j)Noise Deafening tapes for grooves in doors & Pilasters. - Modular Seek modern Aluminium Partition – 3.0 m High 135.0 Sqm 6000.0 810000.0 Providing and fixing 3000 mm high (Approx) modular aluminium partition, comprising powder-coated extruded aluminium framework conforming to IS 733 & IS 1285, with minimum 50-micron powder coating, and 8 mm thick clear toughened safety glass, fixed with aluminium glazing beads and EPDM/neoprene gaskets, including necessary vertical/horizontal members, stiffeners, cleats, brackets, anchors, fasteners, sealant and all accessories. Framework shall be securely fixed to floor, walls/columns and soffit and shall be sufficiently rigid for the 3.0 m height, complete as per approved shop drawings and direction of Engineer-in-Charge. - Toughened Glass Door 3.0 Sqm 6500.0 19500.0 Providing and fixing 8 mm thick clear toughened safety glass door of approved size, including necessary patch fittings/hinges, SS 304 handles 450 mm, lock, floor spring/door closer, glass connectors, gaskets, stoppers and all required SS 304 fittings and accessories, complete with cutting, edge polishing, holes/notches and fixing in the modular aluminium partition, as per approved shop drawings and direction of Engineer-in-Charge. - n NSR Providing and fixing approved-quality digitally printed self-adhesive decorative film on existing glass partitions, doors and windows, with approved design, colour, graphics, logo or pattern as per the approved artwork and sample. The work shall include measurement of glass surfaces, artwork preparation, colour printing using suitable printing technology and compatible ink, application of protective laminate wherever specified, cleaning and degreasing of the glass, cutting, alignment, application of film, removal of air bubbles, edge trimming and finishing, complete as per the manufacturer's recommendations and instructions of the Engineer-in-Charge. R.O Sqm 1250.0 - - |
| 334 | 10.25 0.434050925925926 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works R.O Kg 181.13 - - |
| 335 | 10.28 - |
| 336 | 10.28 Profile C - Fixing with adjustable lugs with split end tail to each jamb R.O Mtr 641.97 - - |
| 337 | 12.51 0.535486111111111 Gutter (600 mm over all girth) R.O Mtr 1378.6 - - |
| 338 | 11.3 0.460428240740741 40 mm thick with 20 mm nominal size stone aggregate R.O Sqm 644.54 - - |
| 339 | 11.6 0.462511574074074 18 mm thick. R.O Sqm 694.76 - - |
| 340 | 11.26 0.476400462962963 25 mm thick R.O Sqm 2044.49 - - |
| 341 | 11.27 - |
| 342 | 11.41 - |
| 343 | 11.41A 11.41A.1 Double charge vitrified tile polished finish of size - 11.41A.1.1 Size of Tile 600 x 600 mm R.O Sqm 1525.46 - 0.486851851851852 Size of Tile 1000x1000 mm 518.83 Sqm 1890.7 980961.04 - |
| 344 | 11.46 0.490324074074074 Size of Tile 1000x1000 mm 11.02 Sqm 2269.43 25011.41 - |
| 345 | 11.41 0.486828703703704 Size of Tile 600x600 mm 48.0 Sqm 1630.19 78249.14 - |
| 346 | 11.46 0.490300925925926 Size of Tile 600x600 mm 3.2 Sqm 1703.23 5450.33 - |
| 347 | 11.46 0.490300925925926 Size of Tile 600x600 mm R.O Sqm 1703.23 - - |
| 348 | 11.48 - |
| 349 | NSR - |
| 350 | NSR - |
| 351 | 11.51 0.493761574074074 18 mm thick Italian Marble stone slab, Perlato, Rosso verona, R.O Sqm 6929.56 - Fire Red or Dark Emperadore etc. - MR Cement plaster skirting up to 100 mm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 50.0 Rmt 250.0 12500.0 - - |
| 352 | 11.56 0.497233796296296 Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. R.O Sqm 4702.68 - - |
| 353 | 11.55 0.496539351851852 Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. R.O Sqm 3344.12 - - |
| 354 | NSR - |
| 355 | NSR - |
| 356 | NSR - |
| 357 | NSR - |
| 358 | NSR a) Flooring R.O Sqm 2549.0 - b) Skirting R.O Sqm 2549.0 - c) Floor strip on edges R.O Metre 509.8 - - |
| 359 | 16.9 - |
| 360 | NSR NSR Supplying, conveying, laying, and commissioning of high-performance, chemical-resistant Electrostatic Discharge (ESD) Conductive Homogeneous PVC Flooring Sheet of 2.0 mm thickness of required size specifically certified for advanced research and chemistry laboratories including earthing arrangements as per OME's specifications. The complete scope of work must satisfy the given technical compliance ESD flooring with 100 ohm Class D with PVC R.O Sqm 2750.0 - - |
| 361 | NSR - |
| 362 | NSR - |
| 363 | NSR - |
| 364 | 11.19 0.471539351851852 Light shade pigment using white cement R.O Sqm 1609.57 - - |
| 365 | NSR - |
| 366 | NSR Approved make of Unitex loop pile carpet with 4 mm thick pu underlay & glued as per international fixing standard. R.O Specification R.O Pile material - 100% olefin polypropylene R.O Pile yarn weight - 650 gsm R.O Backing type - pvc reinforced by glass fiber. R.O Flame resistant - pass R.O Underlay - 6mm polyurethane base R.O Make: Unitex or equivalent R.O - |
| 367 | NSR - |
| 368 | 13.1 0.542384259259259 1:6 (1 cement : 6 fine sand) 3269.97 Sqm 349.82 1143892.7 - |
| 369 | 13.2 0.543078703703704 1:6 (1 cement : 6 fine sand) 1672.35 Sqm 401.92 672150.64 - |
| 370 | 13.16 0.552789351851852 1:3(1 cement: 3 fine sand) R.O Sqm 315.29 - - |
| 371 | 13.11 - |
| 372 | 13.22 10 to 13 m R.O Sqm 91.4 - 13 to 16 m R.O Sqm 182.81 - 16 to 19 m R.O Sqm 274.21 - 19 to 22 m R.O Sqm 365.61 - 22 to 25 m R.O Sqm 457.01 - - |
| 373 | 13.26 - |
| 374 | 13.87 0.602106481481481 Old work (one or more coats) R.O Sqm 14.59 - - |
| 375 | 13.45 0.572928240740741 New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm R.O Sqm 234.65 - - |
| 376 | 13.47 0.57431712962963 New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) 1672.35 Sqm 179.55 300274.09 - |
| 377 | 13.82 0.598634259259259 Two coats 3269.97 Sqm 144.24 471660.57 - |
| 378 | 13.61 0.584039351851852 Two or more coats on new work 583.74 Sqm 163.6 95500.92 - |
| 379 | 13.52 0.577789351851852 On steel work R.O Sqm 253.69 - - |
| 380 | NSR - |
| 381 | NSR - |
| 382 | NSR - |
| 383 | 21.1 0.875706018518518 For fixed portion - 21.1.1.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) R.O Kg 557.13 - - |
| 384 | 0.875717592592593 21.1.2.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) R.O Kg 665.79 - - |
| 385 | 21.2 0.876412037037037 Pre-laminated particle board with decorative lamination on both sides R.O Sqm 1170.5 - - |
| 386 | 21.3 a) 0.877094907407407 With float glass panes of 4.0 mm thickness (weight not less than 10 kg/ sqm) R.O Sqm 1234.93 - - |
| 387 | NSR - |
| 388 | 21.8 0.88056712962963 Upto 5mm depth and 5 mm width R.O Metre 101.53 - - |
| 389 | NSR - ALUMINIUM WORK SUB HEAD TOTAL - - |
| 390 | 22.7 Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: - (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. - (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. - (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge. - (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. - (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : - 0.921539351851852 With average thickness of 120 mm and minimum thickness at khurra as 65mm. R.O Sqm 1767.82 - - |
| 391 | 22.4 0.919456018518519 Serrated with central bulb (225mm wide,8-11mm thick) R.O Meter 343.84 - - |
| 392 | 22.14 0.926423611111111 Cement mortar 1:4 (1cement : 4 coarse sand) R.O Cum 15904.29 - - |
| 393 | 12.21 0.514594907407407 In 75 x75 mm deep chase R.O Meter 320.22 - - |
| 394 | 12.22 - |
| 395 | 22.1 0.917372685185185 Using rough kota stone. R.O Sqm 1590.47 - - |
| 396 | 22.2 0.91806712962963 Using rough kota stone. R.O Sqm 2124.72 - - |
| 397 | 22.3 - |
| 398 | 0.932650462962963 For vertical surface two coats @ 0.70 kg per sqm per coat - |
| 399 | 25.1 - |
| 400 | 25.2 a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: - b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. - c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. - d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. - e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. - Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub- head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places.. - Note:- 2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NBL Certified laboratories - 6) Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml 360.17 Sqm 3683.92 1326822.26 - |
| 401 | 25.3 Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. 360.17 Sqm 3902.4 1405513.16 - |
| 402 | 25.4 - |
| 403 | 8.32 a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design. - b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. - The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium item.s The Contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places.\\" R.O Sqm 5262.79 - - |
| 404 | NSR - |
| 405 | NSR - - |
| 406 | 12.45 (ii) 0.531273148148148 12.5 mm thick tapered edge Glass Reinforced Gypsum (GRG) board conforming to IS: 2095- (Part 3) : 1996 (Board with BIS certification marks) R.O Sqm 1595.19 - - |
| 407 | 12.58 0.540289351851852 8 mm thick fully perforated calcium silicate board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process to give stable crystalline structure with minimum compressive strength 225 kg/ sq. cm, bending strength 100 kg/sq. cm , of size 595x595 mm, having perforation of dia. 10 mm with minimum perforated area 18 % with non woven tissue on the back side, having an NRC ( Noise Reduction Coefficient) of 0.85, with 50 mm thick rockwool of 48 kg /cum backing. R.O Sqm 1877.85 - - |
| 408 | 12.52 0.536134259259259 GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece. 795.48 Sqm 2170.95 1726940.63 - WOODEN CEILING - |
| 409 | NSR - |
| 410 | NSR - |
| 411 | 26.27 at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be prepainted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge. - 1.10211805555556 With 16 mm thick beveled tegular mineral fibre Antimicrobial false ceiling tile confirming to ISO 5 (class 100 ) specifications R.O Sqm 2568.04 - - |
| 412 | 26.65 - |
| 413 | NSR - NSR Providing and fixing decorative wooden false ceiling comprising approved-quality plywood/MDF/HDHMR substrate with natural wood veneer or approved wood-grain laminate finish, fixed over a properly levelled and securely anchored GI/MS supporting framework, including necessary battens, channels, brackets, screws, fasteners, joint treatment, edge trims and finishing/polishing complete as per approved drawings and specifications. The ceiling shall be accurately aligned, securely fixed and finished with uniform colour and texture. All exposed edges shall be neatly finished, and necessary cut-outs shall be provided for lighting fixtures, AC diffusers and other ceiling services. R.O Sqm 4250.0 - - |
| 414 | NSR - - |
| 415 | NSR - R.O Nos 0.0 - - |
| 416 | 0.64099537037037 - |
| 417 | 15.3 - |
| 418 | 0.629907407407407 - |
| 419 | 15.57 - |
| 420 | 0.0425694444444444 - |
| 421 | Nsr - |
| 422 | Nsr - |
| 423 | 8.28 0.352789351851852 Decorative veneer facings of approved manufacture R.O Sqm 2042.39 - - |
| 424 | Nsr - |
| 425 | Nsr - |
| 426 | Nsr - |
| 427 | Nsr - |
| 428 | Nsr - |
| 429 | Nsr - |
| 430 | Nsr - |
| 431 | Nsr - FACADE WORK - - |
| 432 | 2.6 0.0875115740740741 All kinds of soil R.O Cum 186.27 - - |
| 433 | 2.26 0.101400462962963 All kinds of soil R.O Cum 133.06 - - |
| 434 | 2.25 - |
| 435 | 4.1 a) 0.167453703703704 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) R.O Cum 7148.51 - - - |
| 436 | FORM WORK - |
| 437 | 5.9 a ) 0.214594907407407 Foundations, footings, bases of columns, etc. for mass concrete R.O Sqm 411.52 - - b ) 0.214606481481482 Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. R.O Sqm 884.12 - - c ) 0.214618055555556 Suspended floors, roofs, landings, balconies and access platform R.O Sqm 973.06 - - d ) 0.214641203703704 Lintels, beams, plinth beams, girders, bressumers and cantilevers R.O Sqm 772.78 - - e ) 0.214652777777778 Columns,Pillars, Piers, Abutments, Posts and Struts R.O Sqm 1008.79 - - f) 0.214664351851852 Stairs, (excluding landings) except spiral-staircases R.O Sqm 802.74 - - g ) 0.214768518518519 Edges of slabs and breaks in floors and walls. - 5.9.16.1 Under 20cms wide R.O Metre 218.85 - - STEEL REINFORCEMENT - |
| 438 | 5.22 a 0.223680555555556 Thermo-Mechanically Treated bars of grade Fe-500D or more. R.O Kilogram 113.18 - - |
| 439 | 5.37 Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. - 0.231261574074074 All works upto plinth level - a ) 5.33.1.2 Concrete of M30 grade with minimum cement content of 350 kg /cum R.O Cum 10132.69 - - 0.231273148148148 All works above plinth level upto floor V level - |
| 440 | 10.25 0.434050925925926 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works R.O Kg 181.13 - - |
| 441 | 25.3 Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. R.O Sqm 3902.4 - - |
| 442 | 25.4 - |
| 443 | NSR - |
| 444 | NSR - |
| 445 | 12.51 0.535439814814815 Flashings/ Aprons.( Upto 600 mm) 93.54 Rmt 509.59 47666.92 MR Providing and fixing of laser cut jali in MDF with PU paint finish 52.0 Sqm 12560.0 653120.0 - - TOTAL OF FAÇADE WORK - SHEET PILING - |
| 446 | MR SHEET PILING SUB HEAD TOTAL in Figures 117505170.7 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 NAME OF WORK : PROPOSED TTL LAB ICAT MANESAR Internal Electrical Work S.No DSR 2025/MR DESCRIPTON UNIT QTY RATE AMOUNT I SUB HEAD I :- INTERNAL WIRING Point wiring in Steel conduit, with modular type switch :- |
| 447 | 1.3 0.0437847222222222 Group C Point 41.0 2205.0 90396.0 |
| 448 | 1.54 0.0792013888888889 Group C Point 61.0 1308.0 79761.0 Power plug wiring in Steel conduit (2 x 4 Sq.Mm.) :- |
| 449 | 1.5 Circuit / Sub main wiring in Steel conduit :- |
| 450 | 0.0465509259259259 |
| 451 | 0.0465740740740741 |
| 452 | 0.0465856481481481 |
| 453 | 0.0466319444444444 |
| 454 | 0.0466435185185185 S/F light plug point Modular Type Accessories :- |
| 455 | 1.31 S/F power plug point modular Type Accessories :- |
| 456 | 0.0584259259259259 II SUB HEAD II :- DISTRIBUTION BOARDS & MCB's |
| 457 | 2.1 0.0902893518518518 Single pole Each 120.0 299.08 35889.48 |
| 458 | 0.0861342592592593 |
| 459 | 0.0861458333333333 |
| 460 | 0.0854398148148148 |
| 461 | 0.0854513888888889 |
| 462 | 0.085462962962963 S/F DP MCB Isolator |
| 463 | 2.12 0.0916782407407408 40 Amps Each 1.0 495.32 495.32 S/F 4P MCB Isolator |
| 464 | 2.13 0.0923842592592593 63 Amps Each 5.0 1170.08 5850.41 S/F DP (RCCB) |
| 465 | 2.14 0.0930787037037037 40 Amps Each 15.0 2636.09 39541.39 III SUB HEAD III :- INTERNAL LIGHTING FIXTURES & FANS NOTE : SELECTION OF LIGHT FIXTURE IS TENTATIVE FINAL SELECTION IS DONE BY ARCHITECT ONLY |
| 466 | 8.2 Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim . |
| 467 | 0.334756944444444 |
| 468 | 0.334768518518519 |
| 469 | 0.334780092592593 |
| 470 | 8.7 Supplying, Installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output.LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 471 | 0.338240740740741 |
| 472 | 0.338263888888889 |
| 473 | 8.1 Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 474 | 0.340289351851852 |
| 475 | 0.340324074074074 |
| 476 | 8.16 Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year, OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 477 | 0.344467592592593 |
| 478 | 0.376423611111111 |
| 479 | 1.5 0.076400462962963 Upto 450 mm sweep Each R.O 583.47 |
| 480 | 1.51 1.51 Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes. Each R.O 272.84 |
| 481 | DSR CIVIL 10.18 |
| 482 | MR 300 mm sweep 900 rpm Each R.O 3043.0 |
| 483 | MR Total in Figures 1850876.11 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 NAME OF WORK : PROPOSED ELECTRICAL AND ELECTRONICS LAB (EEL) ICAT MANESAR Internal Electrical Work S.No DSR 2025/MR DESCRIPTON UNIT QTY RATE AMOUNT I SUB HEAD I :- INTERNAL WIRING Point wiring in Steel conduit, with modular type switch :- |
| 484 | 1.3 0.0437847222222222 Group C Point 376.0 2205.0 829001.0 |
| 485 | 1.54 0.0792013888888889 Group C Point 563.0 1308.0 736152.0 Power plug wiring in Steel conduit (2 x 4 Sq.Mm.) :- |
| 486 | 1.5 Circuit / Sub main wiring in Steel conduit :- |
| 487 | 0.0465509259259259 |
| 488 | 0.0465740740740741 |
| 489 | 0.0465856481481481 |
| 490 | 0.0466319444444444 |
| 491 | 0.0466435185185185 S/F light plug point Modular Type Accessories :- |
| 492 | 1.31 S/F power plug point modular Type Accessories :- |
| 493 | 0.0584259259259259 II SUB HEAD II :- DISTRIBUTION BOARDS & MCB's |
| 494 | 2.1 0.0902893518518518 Single pole Each 516.0 299.08 154324.76 |
| 495 | 0.0861342592592593 |
| 496 | 0.0861458333333333 |
| 497 | 0.0854398148148148 |
| 498 | 0.0854513888888889 |
| 499 | 0.085462962962963 S/F DP MCB Isolator |
| 500 | 2.12 0.0916782407407408 40 Amps Each 5.0 495.32 2476.58 S/F 4P MCB Isolator |
| 501 | 2.13 0.0923842592592593 63 Amps Each 19.0 1170.08 22231.54 S/F DP (RCCB) |
| 502 | 2.14 0.0930787037037037 40 Amps Each 57.0 2636.09 150257.29 III SUB HEAD III :- INTERNAL LIGHTING FIXTURES & FANS NOTE : SELECTION OF LIGHT FIXTURE IS TENTATIVE FINAL SELECTION IS DONE BY ARCHITECT ONLY |
| 503 | 8.2 Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim . |
| 504 | 0.334756944444444 |
| 505 | 0.334768518518519 |
| 506 | 0.334780092592593 |
| 507 | 0.334791666666667 |
| 508 | 8.7 Supplying, Installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output.LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 509 | 0.338240740740741 |
| 510 | 0.338263888888889 |
| 511 | 8.1 Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 512 | 0.340289351851852 |
| 513 | 0.340324074074074 |
| 514 | 8.16 Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year, OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 515 | 0.344467592592593 |
| 516 | 0.376423611111111 |
| 517 | 1.5 0.076400462962963 Upto 450 mm sweep Each 5.0 583.47 2917.33 |
| 518 | 1.51 1.51 Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes. Each 5.0 272.84 1364.22 |
| 519 | DSR CIVIL 10.18 |
| 520 | MR 300 mm sweep 900 rpm Each 5.0 3043.0 15215.0 |
| 521 | MR RACEWAYS AND CABLE TRAYS 4.1 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement) |
| 522 | 0.167384259259259 |
| 523 | 0.167407407407407 |
| 524 | 0.167430555555556 |
| 525 | 0.16744212962963 RACE WAYS :- Providing and laying 1.6 mm thick pregalvanized GI factory fabricated raceways of the following sizes including 2 mm thick GI covers, providing knock out holes and all required fixing accessories including 6 SWG GI earth wire complete as required including floor /wall supports, bends, access boxes and tap off boxes as per specification and cross over as per site requirement. Note:- Blue & Orange colour shall be considered for Power & Data raceway respectively. The item shall include the cost of chipping, cutting the floor for laying the raceway and making good the finish including chicken mesh complete as required as per site requirement. |
| 526 | MR Total in Figures 13031166.71 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 NAME OF WORK : PROPOSED VEL LAB ICAT MANESAR Internal Electrical Work S.No DSR 2025/MR DESCRIPTON UNIT QTY RATE AMOUNT I SUB HEAD I :- INTERNAL WIRING Point wiring in Steel conduit, with modular type switch :- |
| 527 | 1.3 0.0437847222222222 Group C Point 148.0 2205.0 326309.0 |
| 528 | 1.54 0.0792013888888889 Group C Point 221.0 1308.0 288969.0 Power plug wiring in Steel conduit (2 x 4 Sq.Mm.) :- |
| 529 | 1.5 Circuit / Sub main wiring in Steel conduit :- |
| 530 | 0.0465509259259259 |
| 531 | 0.0465740740740741 |
| 532 | 0.0465856481481481 |
| 533 | 0.0466319444444444 |
| 534 | 0.0466435185185185 S/F light plug point Modular Type Accessories :- |
| 535 | 1.31 S/F power plug point modular Type Accessories :- |
| 536 | 0.0584259259259259 II SUB HEAD II :- DISTRIBUTION BOARDS & MCB's |
| 537 | 2.1 0.0902893518518518 Single pole Each 168.0 299.08 50245.27 |
| 538 | 0.0861342592592593 |
| 539 | 0.0861458333333333 |
| 540 | 0.0854398148148148 |
| 541 | 0.0854513888888889 |
| 542 | 0.085462962962963 S/F DP MCB Isolator |
| 543 | 2.12 0.0916782407407408 40 Amps Each 4.0 495.32 1981.27 S/F 4P MCB Isolator |
| 544 | 2.13 0.0923842592592593 63 Amps Each 5.0 1170.08 5850.41 S/F DP (RCCB) |
| 545 | 2.14 0.0930787037037037 40 Amps Each 15.0 2636.09 39541.39 III SUB HEAD III :- INTERNAL LIGHTING FIXTURES & FANS NOTE : SELECTION OF LIGHT FIXTURE IS TENTATIVE FINAL SELECTION IS DONE BY ARCHITECT ONLY |
| 546 | 8.2 Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round/square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim . |
| 547 | 0.334756944444444 |
| 548 | 0.334768518518519 |
| 549 | 0.334780092592593 |
| 550 | 8.7 Supplying, Installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output.LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 551 | 0.338240740740741 |
| 552 | 0.338263888888889 |
| 553 | 8.1 Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 554 | 0.340289351851852 |
| 555 | 0.340324074074074 |
| 556 | 8.16 Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year, OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 557 | 0.344467592592593 |
| 558 | 0.376423611111111 |
| 559 | 1.5 0.076400462962963 Upto 450 mm sweep Each R.O 583.47 |
| 560 | 1.51 1.51 Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes. Each R.O 272.84 |
| 561 | DSR CIVIL 10.18 |
| 562 | MR 300 mm sweep 900 rpm Each R.O 3043.0 |
| 563 | MR CABLE TRAYS 4.1 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement) |
| 564 | 0.167384259259259 |
| 565 | 0.167407407407407 |
| 566 | 0.167430555555556 |
| 567 | 0.16744212962963 Total in Figures 4097793.8 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 INTERNAL PLUMBING WORKS PROJECT - TTL,EEL,VEL BUILDING OF INTERNATIONAL CENTRE FOR AUTOMOTIVE TECHNOLOGY- ICAT , MANESAR SNo D.S.R. No. DESCRIPTION QTY EEL UNIT Rate Amount A. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - SANITARY FIXTURES & ACCESSORIES |
| 568 | 17.31 |
| 569 | 0.709039351851852 0.709039351851852 White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests R.O Nos 7101.71 |
| 570 | 17.78 |
| 571 | 0.710428240740741 |
| 572 | 0.713240740740741 0.713240740740741 Flat back Wash Basin size 550X400 mm with single 15mm C. P. brass pillar tap 7.0 Nos 1972.03 13804.23 |
| 573 | 17.10.2.1 17.10.2.1 610 x 510 bowl depth 200 mm 1.0 Nos 5184.88 5184.88 |
| 574 | 0.71599537037037 0.71599537037037 Size 600x450x200 mm R.O Nos 6911.14 |
| 575 | 17.16A |
| 576 | 17.22A 17.22A 32 mm dia (for Wash Basin) R.O Nos 1085.92 |
| 577 | 17.22B 17.22B (a) 15mm nominal dia R.O Nos 7283.62 |
| 578 | Flexible pipe 17.28.2.1 32 mm dia 14.0 Nos 125.46 1756.38 |
| 579 | 17.71 |
| 580 | 0.759039351851852 0.759039351851852 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms R.O Nos 706.67 B. - SANITARY FIXTURES & ACCESSORIES |
| 581 | MR-PL-1 |
| 582 | MR-PL-2 |
| 583 | MR-PL-3 |
| 584 | MR-PL-4 |
| 585 | MR-PL-5 |
| 586 | MR-PL-5 |
| 587 | 15 mm nominal bore R.O Nos 1651.0 |
| 588 | MR-PL-6 MR-PL-6 15 litre capacity water heater For Toilets / Kitchens R.O Nos 9378.0 |
| 589 | MR-PL-7 |
| 590 | MR-PL-8 RO WATER PURIFIER AND WATER COOLER SYSTEM |
| 591 | Feed flow rate - 150 lph Feed water TDS in ppm, subject to thehardness of water being less than 500ppm - Bore well / Municipality feed water having TDS1000 ppm (Max) Iron / Maganese - Nil Oil / Grease - Nil Hydrogen Sulphide - Nil Rejectio of TDS : 90-95% Dimension in mm (W x D x H) in mm - (470 x 490 x 610) mm Recovery - 30% ELECTRICAL RATING Input Power Rating - 48 V DC Operating Voltage - 230 V AC, 50 Hz Power consumption - 96 W Pump*2 - 48 V DC Solenoids - 24 V DC PRESSURE REQUIREMNTS Minimum Inlet Pressure - 0.5 Kg/cm2 Maximum Inlet Pressure - 2 KG/cm2 System Pressure - 5 kg/cm2 Operating Temperature - 5 to 45' C RO Membrane Flushing - Fresh Water Particulate Filter: Membrane Life Enhancer - 10 microns Filter.. Sediment Filter - 10 microns Pre carbon RO Membrane Filter Post Carbon Filter RO Membrane Permanently kills Bacteria and Viruses that cause water - borne diseases like polio, Hepatitis, Diarrhea, Typhoid & gives pure drinking water. RO element - 250 Gms of Membrane Antiscalent 80 GPD x 2 in concealed housing 90% or more, which effectively removes TDS R.O. WATER PURIFIER SUITABLE FOR 50 LPH MR-PL-9 Supply, Installation, Testing & Commissioning of Reverse Osmosis based Water Purifier having output capacity of 50 LPH. 1.0 Set 68700.0 68700.0 |
| 592 | MR-PL-10 RO WATER PURIFIER AND WATER COOLER SYSTEM |
| 593 | MR-PL-9 |
| 594 | MR-PL-10 BASEMENT DEWATERING SUMP PUMP Supply, installing, testing and commissioning of non clog submersible type drainage / dewatering pump suitable for automatic operation, float valve operated, automatic / manual operation, including NRV & all accessories, inlet & outlet arrangements, required cable etc. complete in all respects. |
| 595 | MR C. - SOIL, WASTE & VENT PIPES AND FITTINGS (Centrifugally Cast Spun Iron) The following items include providing, fixing and testing in position of ISI marked (IS : 3989) centrifugally cast spun iron soil, waste, and vent pipes and fittings cut to required lengths, fixing at wall, ceiling or on floor including connections to all required fittings complete in all respects. |
| 596 | 17.35.1.2 17.35.1.2 100mm dia Centrifugally cast (spun) iron S & S Pipe 166.0 R.M. 1239.08 205687.12 17.35.2.2 75mm dia Centrifugally cast (spun) iron S & S Pipe 15.0 R.M. 1244.59 18668.83 |
| 597 | 0.748622685185185 0.748622685185185 100 mm 48.0 Nos. 653.25 31356.07 0.748634259259259 75 mm 8.0 Nos. 552.25 4417.97 0.748645833333333 50 mm R.O Nos. 444.05 |
| 598 | 0.734039351851852 0.734039351851852 For 100 mm dia pipe 96.0 Nos. 380.77 36554.38 0.734050925925926 For 75 mm dia pipe 8.0 Nos. 377.78 3022.27 |
| 599 | 17.60.1.1 17.60.1.1 100 mm inlet & 100 mm outlet 17.0 Nos 2095.13 35617.16 |
| 600 | 17.57.1.2 17.57.1.2 100 mm dia 30.0 Nos 538.5 16154.99 17.57.2.2 75 mm dia 10.0 Nos 379.94 3799.35 |
| 601 | 17.38.1.2 17.38.1.2 100 mm dia 10.0 Nos 740.04 7400.37 17.38.2.2 75 mm dia 10.0 Nos 548.63 5486.26 |
| 602 | 17.39.1.2 17.39.1.2 100 mm dia 10.0 Nos 598.21 5982.1 17.39.2.2 75 mm dia 10.0 Nos 409.79 4097.91 |
| 603 | 17.44.1.2 17.44.1.2 100*100*100 mm 17.0 Nos 852.01 14484.13 17.44.2.2 75*75*75 mm 10.0 Nos 588.92 5889.23 |
| 604 | 0.753483796296296 0.753483796296296 100 mm dia 166.0 M 86.89 14423.79 0.75349537037037 75 mm dia 15.0 M 66.06 990.9 D. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - RAIN WATER PIPES AND FITTINGS - (Rigid PVC) |
| 605 | 0.52849537037037 0.52849537037037 110 mm dia R.O M 396.04 |
| 606 | Bend 87.5o 12.42.5.2 110 mm bend R.O Nos 157.78 |
| 607 | 0.529884259259259 0.529884259259259 110 mm R.O Nos 389.64 |
| 608 | 12.44 |
| 609 | 12.22 E. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - INTERNAL WATER SUPPLY PIPES AND FITTINGS |
| 610 | Internal work exposed on wall 0.754872685185185 15mm nominal outer dia pipes R.O R.M. 300.97 0.754884259259259 20mm nominal outer dia pipes 9.0 R.M. 351.55 3093.63 0.754895833333333 25mm nominal outer dia pipes R.O R.M. 421.39 0.754907407407407 32mm nominal outer dia pipes R.O R.M. 544.38 0.754918981481482 40mm nominal outer dia pipes 7.0 R.M. 737.68 4868.66 0.754930555555556 50mm nominal outer dia pipes 13.0 R.M. 980.3 12939.92 |
| 611 | Concealed work including cutting chase and making good the wall etc. 0.75556712962963 15mm nominal outer dia pipes 186.0 R.M. 522.39 96968.89 0.755578703703704 20mm nominal outer dia pipes 73.0 R.M. 564.16 40957.83 0.755590277777778 25mm nominal outer dia pipes 7.0 R.M. 658.24 4344.36 0.755601851851852 32mm nominal outer dia pipes 9.0 R.M. 775.82 6827.23 50 mm nominal outer dia pipes R.O R.M. 776.87 |
| 612 | 0.757002314814815 0.757002314814815 40mm dia nominal bore R.O R.M. 852.01 0.757013888888889 50mm dia nominal bore R.O R.M. 1100.14 MR-PL-18 65mm dia nominal bore R.O R.M. 1325.0 MR-PL-19 80mm dia nominal bore R.O R.M. 1765.0 MR-PL-20 100mm dia nominal bore R.O R.M. 2340.0 |
| 613 | 0.776446759259259 0.776446759259259 40mm dia nominal bore R.O R.M. 44.76 0.776458333333333 50mm dia nominal bore R.O R.M. 53.52 MR-PL-21 65mm dia nominal bore R.O R.M. 60.0 MR-PL-22 80mm dia nominal bore R.O R.M. 75.0 MR-PL-23 100mm dia nominal bore R.O R.M. 90.0 |
| 614 | 0.762511574074074 0.762511574074074 15 mm nominal bore R.O nos 426.95 0.762523148148148 20 mm nominal bore 3.0 nos 485.35 1456.04 0.762534722222222 25 mm nominal bore R.O nos 486.97 |
| 615 | 0.761828703703704 0.761828703703704 32 mm nominal bore R.O Nos. 723.67 0.761840277777778 40 mm nominal bore R.O Nos. 866.91 0.761851851851852 50 mm nominal bore 2.0 Nos. 1077.37 2154.73 0.761863425925926 65 mm nominal bore R.O Nos. 1828.21 |
| 616 | DSR (E&M) 2025 1.13268518518519 80 mm dia R.O NOS 5673.06 1.13269675925926 100 mm dia R.O NOS 7630.19 |
| 617 | DSR (E&M) 2025 MR-PL-25 65 mm dia R.O NOS 3800.0 1.13542824074074 80 mm dia R.O NOS 5369.78 |
| 618 | 0.761122685185185 |
| 619 | 18.21.2.1 |
| 620 | 0.784733796296296 |
| 621 | 0.78681712962963 |
| 622 | MR-PL-26 MR-PL-26 15 mm dia pipe (9 mm thick insulation) R.O M 115.0 |
| 623 | MR-PL-27 MR-PL-27 for 15 mm dia pipe over 9 mm thick insulation R.O M 80.0 |
| 624 | MR-PL-28 MR-PL-28 32 mm dia R.O Set 18500.0 MR-PL-29 40 mm dia R.O Set 22900.0 |
| 625 | 300 mm R.O rm 2098.8 18.48 Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fitting and base support for tank. 2000 litres capacity R.O LTR 11.54 Total in Figures 1164306.31 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 INTERNAL PLUMBING WORKS PROJECT - TTL,EEL,VEL BUILDING OF INTERNATIONAL CENTRE FOR AUTOMOTIVE TECHNOLOGY- ICAT , MANESAR SNo D.S.R. No. DESCRIPTION QTY TTL UNIT Rate Amount A. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - SANITARY FIXTURES & ACCESSORIES |
| 626 | 17.31 |
| 627 | 0.709039351851852 0.709039351851852 White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests R.O Nos 7101.71 |
| 628 | 17.78 |
| 629 | 0.710428240740741 |
| 630 | 0.713240740740741 0.713240740740741 Flat back Wash Basin size 550X400 mm with single 15mm C. P. brass pillar tap 2.0 Nos 1972.03 3944.06 |
| 631 | 17.10.2.1 17.10.2.1 610 x 510 bowl depth 200 mm R.O Nos 5184.88 |
| 632 | 0.71599537037037 0.71599537037037 Size 600x450x200 mm R.O Nos 6911.14 |
| 633 | 17.16A |
| 634 | 17.22A 17.22A 32 mm dia (for Wash Basin) 2.0 Nos 1085.92 2171.84 |
| 635 | 17.22B 17.22B (a) 15mm nominal dia R.O Nos 7283.62 |
| 636 | Flexible pipe 17.28.2.1 32 mm dia 2.0 Nos 125.46 250.91 |
| 637 | 17.71 |
| 638 | 0.759039351851852 0.759039351851852 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms R.O Nos 706.67 B. - SANITARY FIXTURES & ACCESSORIES |
| 639 | MR-PL-1 |
| 640 | MR-PL-2 |
| 641 | MR-PL-3 |
| 642 | MR-PL-4 |
| 643 | MR-PL-5 |
| 644 | MR-PL-5 |
| 645 | 15 mm nominal bore R.O Nos 1651.0 |
| 646 | MR-PL-6 MR-PL-6 15 litre capacity water heater For Toilets / Kitchens R.O Nos 9378.0 |
| 647 | MR-PL-7 |
| 648 | MR-PL-8 RO WATER PURIFIER AND WATER COOLER SYSTEM |
| 649 | Feed flow rate - 150 lph Feed water TDS in ppm, subject to thehardness of water being less than 500ppm - Bore well / Municipality feed water having TDS1000 ppm (Max) Iron / Maganese - Nil Oil / Grease - Nil Hydrogen Sulphide - Nil Rejectio of TDS : 90-95% Dimension in mm (W x D x H) in mm - (470 x 490 x 610) mm Recovery - 30% ELECTRICAL RATING Input Power Rating - 48 V DC Operating Voltage - 230 V AC, 50 Hz Power consumption - 96 W Pump*2 - 48 V DC Solenoids - 24 V DC PRESSURE REQUIREMNTS Minimum Inlet Pressure - 0.5 Kg/cm2 Maximum Inlet Pressure - 2 KG/cm2 System Pressure - 5 kg/cm2 Operating Temperature - 5 to 45' C RO Membrane Flushing - Fresh Water Particulate Filter: Membrane Life Enhancer - 10 microns Filter.. Sediment Filter - 10 microns Pre carbon RO Membrane Filter Post Carbon Filter RO Membrane Permanently kills Bacteria and Viruses that cause water - borne diseases like polio, Hepatitis, Diarrhea, Typhoid & gives pure drinking water. RO element - 250 Gms of Membrane Antiscalent 80 GPD x 2 in concealed housing 90% or more, which effectively removes TDS R.O. WATER PURIFIER SUITABLE FOR 50 LPH MR-PL-9 Supply, Installation, Testing & Commissioning of Reverse Osmosis based Water Purifier having output capacity of 50 LPH. R.O Set 68700.0 |
| 650 | MR-PL-10 RO WATER PURIFIER AND WATER COOLER SYSTEM |
| 651 | MR-PL-9 |
| 652 | MR-PL-10 BASEMENT DEWATERING SUMP PUMP Supply, installing, testing and commissioning of non clog submersible type drainage / dewatering pump suitable for automatic operation, float valve operated, automatic / manual operation, including NRV & all accessories, inlet & outlet arrangements, required cable etc. complete in all respects. |
| 653 | MR C. - SOIL, WASTE & VENT PIPES AND FITTINGS (Centrifugally Cast Spun Iron) The following items include providing, fixing and testing in position of ISI marked (IS : 3989) centrifugally cast spun iron soil, waste, and vent pipes and fittings cut to required lengths, fixing at wall, ceiling or on floor including connections to all required fittings complete in all respects. |
| 654 | 17.35.1.2 17.35.1.2 100mm dia Centrifugally cast (spun) iron S & S Pipe R.O R.M. 1239.08 17.35.2.2 75mm dia Centrifugally cast (spun) iron S & S Pipe R.O R.M. 1244.59 |
| 655 | 0.748622685185185 0.748622685185185 100 mm R.O Nos. 653.25 0.748634259259259 75 mm R.O Nos. 552.25 0.748645833333333 50 mm R.O Nos. 444.05 |
| 656 | 0.734039351851852 0.734039351851852 For 100 mm dia pipe R.O Nos. 380.77 0.734050925925926 For 75 mm dia pipe R.O Nos. 377.78 |
| 657 | 17.60.1.1 17.60.1.1 100 mm inlet & 100 mm outlet 6.0 Nos 2095.13 12570.76 |
| 658 | 17.57.1.2 17.57.1.2 100 mm dia R.O Nos 538.5 17.57.2.2 75 mm dia R.O Nos 379.94 |
| 659 | 17.38.1.2 17.38.1.2 100 mm dia R.O Nos 740.04 17.38.2.2 75 mm dia R.O Nos 548.63 |
| 660 | 17.39.1.2 17.39.1.2 100 mm dia R.O Nos 598.21 17.39.2.2 75 mm dia R.O Nos 409.79 |
| 661 | 17.44.1.2 17.44.1.2 100*100*100 mm 6.0 Nos 852.01 5112.05 17.44.2.2 75*75*75 mm R.O Nos 588.92 |
| 662 | 0.753483796296296 0.753483796296296 100 mm dia R.O M 86.89 0.75349537037037 75 mm dia R.O M 66.06 D. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - RAIN WATER PIPES AND FITTINGS - (Rigid PVC) |
| 663 | 0.52849537037037 0.52849537037037 110 mm dia 53.0 M 396.04 20911.1 |
| 664 | Bend 87.5o 12.42.5.2 110 mm bend 12.0 Nos 157.78 1893.33 |
| 665 | 0.529884259259259 0.529884259259259 110 mm 35.0 Nos 389.64 13637.48 |
| 666 | 12.44 |
| 667 | 12.22 E. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - INTERNAL WATER SUPPLY PIPES AND FITTINGS |
| 668 | Internal work exposed on wall 0.754872685185185 15mm nominal outer dia pipes R.O R.M. 300.97 0.754884259259259 20mm nominal outer dia pipes R.O R.M. 351.55 0.754895833333333 25mm nominal outer dia pipes R.O R.M. 421.39 0.754907407407407 32mm nominal outer dia pipes R.O R.M. 544.38 0.754918981481482 40mm nominal outer dia pipes R.O R.M. 737.68 0.754930555555556 50mm nominal outer dia pipes R.O R.M. 980.3 |
| 669 | Concealed work including cutting chase and making good the wall etc. 0.75556712962963 15mm nominal outer dia pipes 46.0 R.M. 522.39 24134.48 0.755578703703704 20mm nominal outer dia pipes 32.0 R.M. 564.16 17996.62 0.755590277777778 25mm nominal outer dia pipes 4.0 R.M. 658.24 2896.24 0.755601851851852 32mm nominal outer dia pipes R.O R.M. 775.82 50 mm nominal outer dia pipes R.O R.M. 776.87 |
| 670 | 0.757002314814815 0.757002314814815 40mm dia nominal bore R.O R.M. 852.01 0.757013888888889 50mm dia nominal bore R.O R.M. 1100.14 MR-PL-18 65mm dia nominal bore R.O R.M. 1325.0 MR-PL-19 80mm dia nominal bore R.O R.M. 1765.0 MR-PL-20 100mm dia nominal bore R.O R.M. 2340.0 |
| 671 | 0.776446759259259 0.776446759259259 40mm dia nominal bore R.O R.M. 44.76 0.776458333333333 50mm dia nominal bore R.O R.M. 53.52 MR-PL-21 65mm dia nominal bore R.O R.M. 60.0 MR-PL-22 80mm dia nominal bore R.O R.M. 75.0 MR-PL-23 100mm dia nominal bore R.O R.M. 90.0 |
| 672 | 0.762511574074074 0.762511574074074 15 mm nominal bore R.O nos 426.95 0.762523148148148 20 mm nominal bore R.O nos 485.35 0.762534722222222 25 mm nominal bore 1.0 nos 486.97 486.97 |
| 673 | 0.761828703703704 0.761828703703704 32 mm nominal bore 1.0 Nos. 723.67 723.67 0.761840277777778 40 mm nominal bore R.O Nos. 866.91 0.761851851851852 50 mm nominal bore R.O Nos. 1077.37 0.761863425925926 65 mm nominal bore R.O Nos. 1828.21 |
| 674 | DSR (E&M) 2025 1.13268518518519 80 mm dia R.O NOS 5673.06 1.13269675925926 100 mm dia R.O NOS 7630.19 |
| 675 | DSR (E&M) 2025 MR-PL-25 65 mm dia R.O NOS 3800.0 1.13542824074074 80 mm dia R.O NOS 5369.78 |
| 676 | 0.761122685185185 |
| 677 | 18.21.2.1 |
| 678 | 0.784733796296296 |
| 679 | 0.78681712962963 |
| 680 | MR-PL-26 MR-PL-26 15 mm dia pipe (9 mm thick insulation) R.O M 115.0 |
| 681 | MR-PL-27 MR-PL-27 for 15 mm dia pipe over 9 mm thick insulation R.O M 80.0 |
| 682 | MR-PL-28 MR-PL-28 32 mm dia 1.0 Set 18500.0 18500.0 MR-PL-29 40 mm dia 1.0 Set 22900.0 22900.0 |
| 683 | 300 mm 200.0 rm 2098.8 419760.0 18.48 Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fitting and base support for tank. 2000 litres capacity R.O LTR 11.54 Total in Figures 701886.48 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 INTERNAL PLUMBING WORKS PROJECT - TTL,EEL,VEL BUILDING OF INTERNATIONAL CENTRE FOR AUTOMOTIVE TECHNOLOGY- ICAT , MANESAR SNo D.S.R. No. DESCRIPTION QTY VEL UNIT Rate Amount A. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - SANITARY FIXTURES & ACCESSORIES |
| 684 | 17.31 |
| 685 | 0.709039351851852 0.709039351851852 White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests R.O Nos 7101.71 |
| 686 | 17.78 |
| 687 | 0.710428240740741 |
| 688 | 0.713240740740741 0.713240740740741 Flat back Wash Basin size 550X400 mm with single 15mm C. P. brass pillar tap R.O Nos 1972.03 |
| 689 | 17.10.2.1 17.10.2.1 610 x 510 bowl depth 200 mm 1.0 Nos 5184.88 5184.88 |
| 690 | 0.71599537037037 0.71599537037037 Size 600x450x200 mm 3.0 Nos 6911.14 20733.42 |
| 691 | 17.16A |
| 692 | 17.22A 17.22A 32 mm dia (for Wash Basin) Nos 1085.92 |
| 693 | 17.22B 17.22B (a) 15mm nominal dia R.O Nos 7283.62 |
| 694 | Flexible pipe 17.28.2.1 32 mm dia 10.0 Nos 125.46 1254.56 |
| 695 | 17.71 |
| 696 | 0.759039351851852 0.759039351851852 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms R.O Nos 706.67 B. - SANITARY FIXTURES & ACCESSORIES |
| 697 | MR-PL-1 |
| 698 | MR-PL-2 |
| 699 | MR-PL-3 |
| 700 | MR-PL-4 |
| 701 | MR-PL-5 |
| 702 | MR-PL-5 |
| 703 | 15 mm nominal bore 8.0 Nos 1651.0 13208.0 |
| 704 | MR-PL-6 MR-PL-6 15 litre capacity water heater For Toilets / Kitchens R.O Nos 9378.0 |
| 705 | MR-PL-7 |
| 706 | MR-PL-8 RO WATER PURIFIER AND WATER COOLER SYSTEM |
| 707 | Feed flow rate - 150 lph Feed water TDS in ppm, subject to thehardness of water being less than 500ppm - Bore well / Municipality feed water having TDS1000 ppm (Max) Iron / Maganese - Nil Oil / Grease - Nil Hydrogen Sulphide - Nil Rejectio of TDS : 90-95% Dimension in mm (W x D x H) in mm - (470 x 490 x 610) mm Recovery - 30% ELECTRICAL RATING Input Power Rating - 48 V DC Operating Voltage - 230 V AC, 50 Hz Power consumption - 96 W Pump*2 - 48 V DC Solenoids - 24 V DC PRESSURE REQUIREMNTS Minimum Inlet Pressure - 0.5 Kg/cm2 Maximum Inlet Pressure - 2 KG/cm2 System Pressure - 5 kg/cm2 Operating Temperature - 5 to 45' C RO Membrane Flushing - Fresh Water Particulate Filter: Membrane Life Enhancer - 10 microns Filter.. Sediment Filter - 10 microns Pre carbon RO Membrane Filter Post Carbon Filter RO Membrane Permanently kills Bacteria and Viruses that cause water - borne diseases like polio, Hepatitis, Diarrhea, Typhoid & gives pure drinking water. RO element - 250 Gms of Membrane Antiscalent 80 GPD x 2 in concealed housing 90% or more, which effectively removes TDS R.O. WATER PURIFIER SUITABLE FOR 50 LPH MR-PL-9 Supply, Installation, Testing & Commissioning of Reverse Osmosis based Water Purifier having output capacity of 50 LPH. R.O Set 68700.0 |
| 708 | MR-PL-10 RO WATER PURIFIER AND WATER COOLER SYSTEM |
| 709 | MR-PL-9 |
| 710 | MR-PL-10 BASEMENT DEWATERING SUMP PUMP Supply, installing, testing and commissioning of non clog submersible type drainage / dewatering pump suitable for automatic operation, float valve operated, automatic / manual operation, including NRV & all accessories, inlet & outlet arrangements, required cable etc. complete in all respects. |
| 711 | MR C. - SOIL, WASTE & VENT PIPES AND FITTINGS (Centrifugally Cast Spun Iron) The following items include providing, fixing and testing in position of ISI marked (IS : 3989) centrifugally cast spun iron soil, waste, and vent pipes and fittings cut to required lengths, fixing at wall, ceiling or on floor including connections to all required fittings complete in all respects. |
| 712 | 17.35.1.2 17.35.1.2 100mm dia Centrifugally cast (spun) iron S & S Pipe 142.0 R.M. 1239.08 175825.32 17.35.2.2 75mm dia Centrifugally cast (spun) iron S & S Pipe 50.0 R.M. 1244.59 61607.13 |
| 713 | 0.748622685185185 0.748622685185185 100 mm 50.0 Nos. 653.25 32662.58 0.748634259259259 75 mm 20.0 Nos. 552.25 11044.94 0.748645833333333 50 mm Nos. 444.05 |
| 714 | 0.734039351851852 0.734039351851852 For 100 mm dia pipe 100.0 Nos. 380.77 38077.48 0.734050925925926 For 75 mm dia pipe 40.0 Nos. 377.78 15111.36 |
| 715 | 17.60.1.1 17.60.1.1 100 mm inlet & 100 mm outlet 19.0 Nos 2095.13 39807.41 |
| 716 | 17.57.1.2 17.57.1.2 100 mm dia 30.0 Nos 538.5 16154.99 17.57.2.2 75 mm dia 10.0 Nos 379.94 3799.35 |
| 717 | 17.38.1.2 17.38.1.2 100 mm dia 10.0 Nos 740.04 7400.37 17.38.2.2 75 mm dia 10.0 Nos 548.63 5486.26 |
| 718 | 17.39.1.2 17.39.1.2 100 mm dia 10.0 Nos 598.21 5982.1 17.39.2.2 75 mm dia 10.0 Nos 409.79 4097.91 |
| 719 | 17.44.1.2 17.44.1.2 100*100*100 mm 19.0 Nos 852.01 16188.15 17.44.2.2 75*75*75 mm 10.0 Nos 588.92 5889.23 |
| 720 | 0.753483796296296 0.753483796296296 100 mm dia 142.0 M 86.89 12338.43 0.75349537037037 75 mm dia 50.0 M 66.06 3302.99 D. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - RAIN WATER PIPES AND FITTINGS - (Rigid PVC) |
| 721 | 0.52849537037037 0.52849537037037 110 mm dia 79.0 M 396.04 31366.65 |
| 722 | Bend 87.5o 12.42.5.2 110 mm bend 16.0 Nos 157.78 2524.44 |
| 723 | 0.529884259259259 0.529884259259259 110 mm 59.0 Nos 389.64 22988.89 |
| 724 | 12.44 |
| 725 | 12.22 E. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - INTERNAL WATER SUPPLY PIPES AND FITTINGS |
| 726 | Internal work exposed on wall 0.754872685185185 15mm nominal outer dia pipes R.O R.M. 300.97 0.754884259259259 20mm nominal outer dia pipes 15.0 R.M. 351.55 5413.85 0.754895833333333 25mm nominal outer dia pipes 41.0 R.M. 421.39 17150.43 0.754907407407407 32mm nominal outer dia pipes 25.0 R.M. 544.38 13772.72 0.754918981481482 40mm nominal outer dia pipes 19.0 R.M. 737.68 13794.54 0.754930555555556 50mm nominal outer dia pipes 48.0 R.M. 980.3 47446.38 |
| 727 | Concealed work including cutting chase and making good the wall etc. 0.75556712962963 15mm nominal outer dia pipes 141.0 R.M. 522.39 73840.01 0.755578703703704 20mm nominal outer dia pipes 87.0 R.M. 564.16 49025.28 0.755590277777778 25mm nominal outer dia pipes 31.0 R.M. 658.24 20273.67 0.755601851851852 32mm nominal outer dia pipes 7.0 R.M. 775.82 5120.42 50 mm nominal outer dia pipes 40.0 R.M. 776.87 31074.83 |
| 728 | 0.757002314814815 0.757002314814815 40mm dia nominal bore R.O R.M. 852.01 0.757013888888889 50mm dia nominal bore R.O R.M. 1100.14 MR-PL-18 65mm dia nominal bore 15.0 R.M. 1325.0 19875.0 MR-PL-19 80mm dia nominal bore 25.0 R.M. 1765.0 44125.0 MR-PL-20 100mm dia nominal bore R.O R.M. 2340.0 |
| 729 | 0.776446759259259 0.776446759259259 40mm dia nominal bore R.O R.M. 44.76 0.776458333333333 50mm dia nominal bore R.O R.M. 53.52 MR-PL-21 65mm dia nominal bore 15.0 R.M. 60.0 900.0 MR-PL-22 80mm dia nominal bore 25.0 R.M. 75.0 1875.0 MR-PL-23 100mm dia nominal bore R.O R.M. 90.0 |
| 730 | 0.762511574074074 0.762511574074074 15 mm nominal bore R.O nos 426.95 0.762523148148148 20 mm nominal bore 9.0 nos 485.35 4368.13 0.762534722222222 25 mm nominal bore 4.0 nos 486.97 1947.9 |
| 731 | 0.761828703703704 0.761828703703704 32 mm nominal bore 4.0 Nos. 723.67 2894.66 0.761840277777778 40 mm nominal bore 5.0 Nos. 866.91 4334.55 0.761851851851852 50 mm nominal bore 2.0 Nos. 1077.37 2154.73 0.761863425925926 65 mm nominal bore 2.0 Nos. 1828.21 3656.42 |
| 732 | DSR (E&M) 2025 1.13268518518519 80 mm dia R.O NOS 5673.06 1.13269675925926 100 mm dia R.O NOS 7630.19 |
| 733 | DSR (E&M) 2025 MR-PL-25 65 mm dia R.O NOS 3800.0 1.13542824074074 80 mm dia 2.0 NOS 5369.78 10739.56 |
| 734 | 0.761122685185185 |
| 735 | 18.21.2.1 |
| 736 | 0.784733796296296 |
| 737 | 0.78681712962963 |
| 738 | MR-PL-26 MR-PL-26 15 mm dia pipe (9 mm thick insulation) R.O M 115.0 |
| 739 | MR-PL-27 MR-PL-27 for 15 mm dia pipe over 9 mm thick insulation R.O M 80.0 |
| 740 | MR-PL-28 MR-PL-28 32 mm dia 1.0 Set 18500.0 18500.0 MR-PL-29 40 mm dia 1.0 Set 22900.0 22900.0 |
| 741 | 300 mm R.O rm 2098.8 18.48 Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fitting and base support for tank. 2000 litres capacity 4000.0 LTR 11.54 46173.6 Total in Figures 2968075.01 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 NAME OF WORK : PROPOSED ELECTRICAL AND ELECTRONICS LAB (TTL) ICAT MANESAR S. No DSR/MR Description of Item UNIT QTY RATE AMOUNT SUB HEAD I : STRUCTURED CABLING SYSTEM PASSIVE |
| 742 | 1.63820601851852 |
| 743 | 1.63959490740741 |
| 744 | 39.22 |
| 745 | 1.63751157407407 |
| 746 | 39.15 |
| 747 | 1.63403935185185 |
| 748 | 1.63405092592593 |
| 749 | 1.64099537037037 SUB HEAD II : IP CCTV SYSTEM |
| 750 | 1.63681712962963 |
| 751 | 39.14 |
| 752 | 39.11 |
| 753 | 1.63334490740741 |
| 754 | 1.63335648148148 SUB HEAD III : FAS with Integrated PA System A Fire Panel & Annunciators B Repeater Panel 28.2.1.4 Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. Nos 1.0 119352.46 119352.46 C Detectors |
| 755 | 1.16810185185185 D Modules |
| 756 | 1.16821759259259 |
| 757 | 1.1681712962963 |
| 758 | 1.16813657407407 |
| 759 | MR E Notification Devices |
| 760 | 1.168125 F Fire Fighter Telephone Talk Back |
| 761 | 1.16827546296296 G IP Based Public Address System 1.16884259259259 Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. Nos 1.0 159894.98 159894.98 |
| 762 | 1.1687962962963 H Cables & Conduits |
| 763 | 1.17015046296296 |
| 764 | 0.0562731481481481 surface/recess including cutting the wall and making good the same in case of recessed conduit as required . 25 mm SUB HEAD IV : GAS SUPPRESSION SYSTEM |
| 765 | MR Total in Figures 5436894.98 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 NAME OF WORK : PROPOSED ELECTRICAL AND ELECTRONICS LAB (EEL) ICAT MANESAR LV SERVICES WORK S. No DSR/MR Description of Item UNIT QTY RATE AMOUNT SUB HEAD I : STRUCTURED CABLING SYSTEM PASSIVE |
| 766 | 1.63820601851852 |
| 767 | 1.63961805555556 |
| 768 | 39.22 |
| 769 | 1.63751157407407 |
| 770 | 39.15 |
| 771 | 1.63403935185185 |
| 772 | 1.63405092592593 |
| 773 | 39.25 SUB HEAD II : LOCAL AREA NETWORK (LAN) |
| 774 | 1.63681712962963 |
| 775 | 39.14 |
| 776 | 39.11 |
| 777 | 1.63334490740741 |
| 778 | 1.63335648148148 SUB HEAD III : FAS with Integrated PA System A Fire Panel & Annunciators |
| 779 | 1.16806712962963 28.2.1.1 10-loop Panel Nos 1.0 500451.51 500451.51 C Detectors |
| 780 | 1.16810185185185 |
| 781 | 1.16811342592593 D Modules |
| 782 | 1.16821759259259 |
| 783 | 1.1681712962963 |
| 784 | 1.16813657407407 |
| 785 | MR E Notification Devices |
| 786 | 1.168125 |
| 787 | MR F Fire Fighter Telephone Talk Back |
| 788 | 1.16827546296296 |
| 789 | 1.16825231481481 G IP Based Public Address System |
| 790 | 1.16876157407407 |
| 791 | 1.16884259259259 |
| 792 | 1.16877314814815 H Cables & Conduits |
| 793 | 1.17015046296296 |
| 794 | 0.0562731481481481 SUB HEAD : IV GAS SUPPRESSION SYSTEM |
| 795 | MR Total in Figures 6860818.55 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 NAME OF WORK : PROPOSED ELECTRICAL AND ELECTRONICS LAB (EEL) ICAT MANESAR LV SERVICES WORK S. No DSR/MR Description of Item UNIT QTY RATE(RS) AMOUNT(RS) SUB HEAD I : STRUCTURED CABLING SYSTEM PASSIVE |
| 796 | 1.63820601851852 |
| 797 | 1.63959490740741 |
| 798 | 39.22 |
| 799 | 1.63751157407407 |
| 800 | 39.15 |
| 801 | 1.63403935185185 |
| 802 | 1.63405092592593 |
| 803 | 1.64100694444444 SUB HEAD II : IP CCTV SYSTEM |
| 804 | 1.63681712962963 |
| 805 | 39.14 |
| 806 | 39.11 |
| 807 | 1.63334490740741 |
| 808 | 1.63335648148148 A SUB HEAD III : FAS with Integrated PA System B Fire Panel & Annunciators |
| 809 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS 28.2.1.2 2 loop Panel Each 1.0 262790.75 262790.75 |
| 810 | 1.16810185185185 1.16810185185185 Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. Nos 60.0 3152.4 189143.86 D 1.16811342592593 Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. Nos R.O 321.12 |
| 811 | 1.16821759259259 |
| 812 | 1.1681712962963 |
| 813 | 1.16813657407407 E MR Supplying, installing, testing and commissioning approved make Addressable Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance Nos 6.0 5506.0 33036.0 |
| 814 | 1.168125 1.168125 Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. Nos 6.0 2924.68 17548.07 F |
| 815 | 1.16827546296296 1.16825231481481 Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required. Nos 3.0 6313.19 18939.57 G |
| 816 | 1.16884259259259 |
| 817 | 1.16877314814815 H 1.1687962962963 Supplying, installation, testing & commissioning ofceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required. Nos 3.0 2681.217 8043.65 |
| 818 | 1.17015046296296 1.17015046296296 Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. Mtrs. 1000.0 405.07 405068.4 0.0562731481481481 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in Mtrs. 1500.0 176.3 264448.8 surface/recess including cutting the wall and making good the same in case of recessed conduit as required . 25 mm Total in Figures DSR 1920266.82 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 NAME OF WORK : PROPOSED VEL & TTL LAB ICAT MANESAR External Electrical Work S.No DSR 2025/MR Description Unit Qty Rate Amount |
| 819 | MR 11KV SINGLE PANEL HT VCB (INDOOR)- ONE INCOMER CUM OUTGOING IN IP-4X ENCLOSURE Design, Manufacture and Supply of 1 Panel, 11 kV HT VCB Switch Board with Following Accessories : Incoming 630A, 11kV, 350MVA for 3 Sec., TP, Horizontally isolated, horizontally drawout type, motorised spring charged, closing mechanism, motor voltage 230V AC, shunt tripping & Closing coil Voltage 24V DC, Electrically Operated, Trip Free, Dust & Vermin Proof, Vacuum Circuit Breaker(VCB) With Mechanical & Electrical OFF/ON Indicators & Provided with Following - 1 No. CT chamber with double wound single phase, cast resin CT, 15VA burden with core-1 for metering (CL-1) and core-2 for protection (CL-5P10) and of 200-100/5A ratio - 3 Nos. IDMT relay with 3 elements for over current (50-200%) and 1 element for earth fault protection(10-40%). - 1 Set Anti Pumping Relay - 1 Set Master Trip Relay - 1 Set Trip circuit supervision relay - 1 Set Potential Transformers, 3 Phase, 3 Limb, Drawout Type, Resin Cast 11000/(Root 3)/110/(Root 3) Ratio Class 1 Accuracy, 100 VA Burden, with HV fuse on primary side and MCB / MPCB on secondary side. - 1 Set 6 Windows Annunciator with Hooter - 1 Set 1 Window for over current trip - 1 Set 1 Window for earth fault trip - 1 Set 1 Window for master trip relay - 1 Set 1 Window for Emergency Stop Push Button - 1 Set 2 Windows Spare - 1 Set Digital Ammeter with inbuilt selector switch - 1 Set Digital Voltmeter with inbuilt selector switch - 1 Set A set of breaker ON/OFF/Trip/DC control supply healthy/Trip circuit healthy/ Spring Charged VCB in test / VCB in service & R,Y,B phase indication lamps. - 1 Set Emergency stop push button - 1 Set Limit switches with 4 NO/ 4 NC breaker auxiliary contacts - 1 Set Control:- T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement. - 1 Set All control wiring with protection & test terminal block as required. - 1 Set Strip heater with thermostat for moisture absorption. - 1 Set Suitable for connection to 3C x 240 sq.mm. Cross linked polythelene(XLPE) 11kV cables or as called for. - 1 Set Cable box for 3C x 240 sq.mm 11kV XLPE Al. conductor cable. - 1 Set HT Danger Plate - 1 Set Incoming as described above. 1 Sets Powerpack as Required to Be Included (220V/24V DC), 7AH Battery for Each Breaker Module. SINGLE PANEL 11KV HT VCB PANEL AS DESCRIBED ABOVE Set 2.0 553246.0 1106492.0 11KV DRY TYPE INDOOR TRANSFORMER (11 KV /0.433 KV) (2000 KVA) |
| 820 | 24.27 The transformer shall be provided with standard fittings/accessories as per relevant IS and mentioned below, protection alarm/trip protection, 3 nos. of Polymeric Zinc Oxide surge Arrestors on HV Side. Winding Temperature scanner (Digital) with alarm/Trip contacts with RTD Sensors per LV winding and space for mounting differential protection CT's in LV chamber with neutral brought out separately including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/HT Panel for safety tripping, complete as confirming to IS-2026 Part-11, i/c supplying and grouting of suitable M.S. Channel with all accessories ,complete in all respects as required at site as per CPWD specifications . Design ambient condition : a) air temperature 50 0C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. The transformer should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. All testing shall as per relevant IS Code. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551/ NEMA Standard. Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Rating and terminal marking plates; c) Thermometer pocket with cap; d) Lifting lugs for the complete transformer as well as for core and winding assembly; e) Bi-directional flat rollers (for transformers above 200 kVA); f) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); g) Bird guard; h) Jacking pads (for transformer above 1 600 kVA); i) Name Rating & Diagram Plate. j) Monogram Plate.k) Additional neutral separately brought out on bushing for earthing. Each R.O 6343703.8 |
| 821 | 1.01922453703704 OR 11KV OIL COOLED TRANSFORMER (11 KV /0.433 KV) (2000 KVA) |
| 822 | 24.18 The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with +12.5 percent combined voltage and frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise shall not exceed 40 0C for oil and 45 0C for winding up to 200 KVA and 45 0C for oil and 50 0C for winding for above 200 KVA. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180 (Part 3) shall be referred for paint thickness for normal to medium corrosive atmosphere. For highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in Charge. Design ambient condition : a) air temperature 50 0C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551 / NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible, as per IS: 1180 Part-3. The entries on the rating plate shall be indelibly marked. Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase transformers; g) Thermometer pocket with cap; h) Oil filling holes having (1¼″ nominal size thread) with cover (for sealed type transformers without conservator); i) Lifting lugs for the complete transformer as well as for core and winding assembly; j) Pressure relief device or explosion vent above 200 kVA; k) One filter valve on the upper side of the tank (for transformers above 200 kVA); l) Unidirectional flat rollers (for transformers above 200 kVA); m) Inspection hole (for transformers above 200 kVA); n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); o) Buchholz relay for transformers above 800 kVA. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oil temperature indicator and winding temperature indicators for transformers above 200 kVA with suitable tripping mechanism above permissible limit s) Jacking pads (for transformer above 1 600 kVA); t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge (for transformer above 1600 kVA) with low oil level alarm contact; v) Non return valve (for conducting pressure test); w) Pressure relief device or explosion vent x). Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug for all transformers of capacity 50 KVA and above. bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. |
| 823 | 1.0125462962963 UNINTERRUPTED POWER SUPPLY (UPS) |
| 824 | 26.2 Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) at operating temperature 0 to 40 0C, Relative humidity 0 to 95%, Online double conversion true sine wave Uninterrupted hot swapable (allow for the replacement or addition of battery modules without shutting down the entire system) modular Power Supply (UPS) system with N+1 modules (N denotes total number of modules required for rated capacity). The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. UPS shall have inbuilt phase sequence correction. The UPS systems offered are to be of the latest technology with Digital Control Microprocessor based for reliable operation using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with PWM (Pulse Width Modulation). The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >96% while operating on battery mode and delivering quality power to the 100% non-linear loads. Current total harmonic effect(ITHD) on the input grid shall be < 5% at 50 %load. (The required LC ( inductor (L) and a capacitor (C)) filters shall be included in UPS cost), extreme power factor kit to be included to limit the input power factor (PF) to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%, 50 Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins, Sine wave output. Non condensing, noise level less than 60db at 1 meter distance, protections: Input Under voltage over voltage, abnormal out voltage, battery over charging, output over current, short circuit protection, battery deep discharge protection, 10KV surge. UPS must comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-type UPS. . Communication RS232/RS485/SNMP port open protocol for BMS integration, all hardware & software for iOT Communication as per approved by Engineering in charge. Required battery racks and interconnecting copper conductor cables of suitable size and connectors and all required accessories are inclusive of the cost). This system must provide a means for logging and alarming of all monitored points plus email notification. Forced air-cooling with integral inbuilt fans with redundancy (if one fan fail UPS should be able to handle at least 80% of the load, Noise Level 65 DB at 1 meter distance. The system shall be in compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification. Display Panel (minimum) (In-build 5 inch or more LC Display / LED) to display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage, Frequency. c) Output: Voltage, frequency, Current. d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage. f) Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data (On LCD/LED): UPS should capture and display up to 3000 events like: Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h) Statistical Data: No. of power failures / Transfers to Bypass / Total Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation / Bypass feeding the load / UPS Fault /Battery charging and discharging, overload, battery voltage and battery capacity. j) Audible Alarms : Mains Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over, Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage, Over Load and short circuit, Over Temperature. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc |
| 825 | 1.08480324074074 |
| 826 | 1.08475694444444 |
| 827 | MR NOTE:- MCCB's Wherever Specified shall have Rotary Handle. Suppy, installation, testing, Design, manufacture, supply inspection, handling, assembling, affecting proper connections, testing and commissioning of 2mm CRCA sheet steel fabricated cubical type Main L.T. Panel floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 52, As per IEC 61439 after proper treatment with 9 tank process with top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2.5 sq. mm. FRLS copper wires, ckt labels etc. The panel feeders shall be suitable for terminating suitable nos. 3.5 / 4 core armoured aluminium cable as required. Panel Should Be Internal Arc tested at 50ka for .3 sec as per IEC61641. (TTA Type Panel) (Under no case temperature of main LT panel shall be more at any point of the panel. To avoid heating necessary exhaust fans shall have to be provided along with top louvers). Degree of protection IP-42 The internal control wiring shall fuse less. All control wiring and metering protection shall be by MCB's. Colour: Siemens Gray Powder Coated or as per approved shade. INCOMER FROM 2000KVA OUTDOOR TRANSFORMER - 1 Nos having 1 Nos. 3200 amps Four Pole EDO 50kA (Ics=Icu) ACB fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated Position Indicator and Frame Earthing Contact ,Confiming to IS 13947-2 1993 as Amended upto Date Complete with Following Accessories. 1 set of 3 CT's of ratio 3200/5A, Class 1.0 accuracy 15 VA burden for APFCR. Independent manual spring closing mechanism - 1 No. Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set. Multifunction meter with selector switch with suitable CT's and back up MCBs. The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmeter, selector switches, cast resin type CT's & PT's, etc. Separate CT's shall be provided for protective and measuring system and for APFCR of capacitor bank with suitable VA. 3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required. Shunt trip coil 220 Volt AC. BUS BAR 3500A TPN Aluminium bus bar with heat Shrink Sleeve OUTGOING ALL THE MCCB'S SHALL BE EQUIPPED/ PROVIDED WITH ALL ACCESSORIES & IN BUILT PROTECTION RELEASES 1 Nos. 2000 AMPS TP+N ACB 1 No. 1600A 50KA 4P ACB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. 2 No. 630A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. 2 No. 400A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. 3 No. 250A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. 1 No. 160A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. 1 No. 125A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. 1 No. 400A 50KA 4P MCCB (SPARE) 1 No. 160A 50KA 4P MCCB (SPARE) 1 No. 125A 50KA 4P MCCB (SPARE) Other items such as 1 set of control wiring 1 Set of designation plates NOTE :- Adequate Quantity of Fire Suppression system with Pneumatic gas cylinder and Heat Sensitive Pneumatic tubing to be used in panel as per the current fire norms & SURGE PROTECTION DEVICES Type 1 ( Class B), 4 Mode, spar type suitable for 10/350µs surge, 3Nos. phase to earth and 1Nos. neutral to earth with impulse Current Iimp. ≥ 50KA Per mode & In ≥ 25kA per Mode. Complete Panel as Above and complete SET 1.0 1996000.0 1996000.0 |
| 828 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 400 AMP FP MCCB BUS BAR : 500 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 7 No 40 AMP FP MCB with indication lights 1 No 25 AMP FP MCB with indication lights 7 No 63 AMP 4P MCB with indication lights 5 No 125 AMP 4P MCCB with indication lights 2 No 160 AMP 4P MCCB with indication lights complete panel as above and complete SET 1.0 473596.0 473596.0 |
| 829 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 125 AMP FP MCCB BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 6 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 75000.0 75000.0 |
| 830 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 125 AMP FP MCCB BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 6 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 75000.0 75000.0 |
| 831 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 160 AMP FP MCCB BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 3 No 100 AMP FP MCCB with indication lights 3 No 32 AMP FP MCB with indication lights 3 No 16 AMP 4P MCB with indication lights 8 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 155000.0 155000.0 |
| 832 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 160 AMP FP MCCB THRU 30KVA UPS BYPAS SWITCH BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 8 No 40 AMP DP MCB with indication lights 4 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 87500.0 87500.0 |
| 833 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 630 AMP FP MCCB BUS BAR : 800 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 3 No 40 AMP FP MCB with indication lights 2 No 25 AMP FP MCB with indication lights 3 No 63 AMP 4P MCB with indication lights 5 No 125 AMP 4P MCCB with indication lights 2 No 160 AMP 4P MCCB with indication lights 1 No 250 AMP 4P MCCB with indication lights complete panel as above and complete SET 1.0 438036.0 438036.0 |
| 834 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 125 AMP FP MCCB BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 1 No 40 AMP DP MCB with indication lights 8 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 65000.0 65000.0 |
| 835 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 250 AMP FP MCCB THRU 100 KVA UPS BYPAS SWITCH BUS BAR : 300 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 4 No 125 AMP 4P MCCB with indication lights 8 No 40 AMP DP MCB with indication lights 8 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 269000.0 269000.0 LT CABLE AND ACCESSORIES SUPPLY OF L.T. CABLE: Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required. |
| 836 | MR DSR 10 LT CABLE LAYING DSR 10.1 Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required. |
| 837 | DSR 10.1.1 |
| 838 | DSR 10.1.2 |
| 839 | DSR 10.1.3 |
| 840 | DSR 10.1.4 DSR 11 LT CABLE JOINTING & END TERMINATION DSR 11.1 Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed/ XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required. |
| 841 | DSR 11.1.20 |
| 842 | DSR 11.1.21 |
| 843 | DSR 11.1.22 |
| 844 | DSR 11.1.23 |
| 845 | DSR 11.1.24 |
| 846 | DSR 11.1.25 |
| 847 | DSR 11.1.26 |
| 848 | DSR 11.1.27 |
| 849 | DSR 11.1.29 |
| 850 | DSR 11.1.30 CABLE TRAYS WITH SUPPORTS |
| 851 | 4.6 0.170856481481481 150 mm width X 50 mm depth X 1.6 mm thickness Meter 150.0 842.67 126400.5 0.17087962962963 300 mm width X 50 mm depth X 1.6 mm thickness meter 200.0 1114.46 222892.0 0.170902777777778 450 mm width X 50 mm depth X 2.0 mm thickness Meter 150.0 1510.09 226513.5 0.170914351851852 600 mm width X 50 mm depth X 2.0 mm thickness Meter 50.0 2020.1 101005.0 HT CABLE AND ACCESSORIES |
| 852 | MR 16 Supply & Testing of following 11 KV (E) grade multicore Aluminium conductor XLPE insulated cable, insulation screening with extruded semi conducting compound in combination with copper tape armoured cores laid up, inner sheath of PVC tape, galvanised steel flat strip armoured and overall PVC sheathed cable conforming to IS: 7098 (Part - II) and complete with all latest amendments etc. complete as required. 3 C x 240 Sq. mm 11 KV (E) Metre 450.0 3381.0 1521450.0 |
| 853 | DSR 22 DSR 22.1 H V CABLE LAYING DSR 22.1.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 854 | DSR 22.1.2 DSR 23.1 H.T Termination: DSR ITEM |
| 855 | DSR 23.1 |
| 856 | 0.9590625 |
| 857 | DSR 23.2 |
| 858 | 0.959756944444444 |
| 859 | DSR 23.3 |
| 860 | 0.960451388888889 DSR 2 MISCELLANEOUS ITEMS - DSR |
| 861 | 2.22 MISCELLANEOUS ITEMS - MR Items |
| 862 | MR DSR 5 EARTHING |
| 863 | 5.9 RCC Hume pipes Providing and laying non pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixtures of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete. |
| 864 | 0.795868055555556 |
| 865 | 0.79587962962963 |
| 866 | 0.795844907407407 Manholes Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design. |
| 867 | 0.772928240740741 Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : |
| 868 | 0.773622685185185 Total 25406198.9 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 NAME OF WORK : PROPOSED EEL LAB ICAT MANESAR External Electrical Work S.No DSR 2025/MR Description Unit Qty Rate Amount 11KV TRANSFORMER (11 KV /0.433 KV) (3000 KVA) |
| 869 | 24.6 Rating & diagram plate - 1 Set Earthing terminals - 1 Set Lifting lugs and cover lifting lugs - 1 Set Plain oil level gauge - 1 No Bottom filter-cum-drain valve with plug - 1 No Top filter valve with plug - 1 No Pulling lugs - 1 Set Thermometer pocket and dial type OTI - 1 Set Silica gel breather - 1 No Conservator - 1 No Inspection window and air release plug - 1 Set HV termination - cable box - 1 Set LV termination - Extedable bus terminals for LT XLPE cable connectivity Detachable type radiators - 1 Set Bidirectional rollers - 1 Set On-load tap changer (OLTC) - 1 Set Marshalling box - 1 No Magnetic Oil Gauge (MOG) - 1 No Buchholz relay - 1 No Routine testing as per IS:2026 and routine test certificate - 1 Job MR 3000KVA Each 1.0 7148452.0 7148452.0 |
| 870 | MR Suppy, installation, testing, Design, manufacture, supply inspection, handling, assembling, affecting proper connections, testing and commissioning of 2mm CRCA sheet steel fabricated cubical type Main L.T. Panel floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 52, As per IEC 61439 after proper treatment with 9 tank process with top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2.5 sq. mm. FRLS copper wires, ckt labels etc. The panel feeders shall be suitable for terminating suitable nos. 3.5 / 4 core armoured aluminium cable as required. Panel Should Be Internal Arc tested at 50ka for .3 sec as per IEC61641. (TTA Type Panel) (Under no case temperature of main LT panel shall be more at any point of the panel. To avoid heating necessary exhaust fans shall have to be provided along with top louvers). Degree of protection IP-42 The internal control wiring shall fuse less. All control wiring and metering protection shall be by MCB's. Colour: Siemens Gray Powder Coated or as per approved shade. INCOMER FROM EXISTING LT PANEL - 1 Nos having 1 Nos. 2000 amps Four Pole EDO 50kA (Ics=Icu) ACB fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated Position Indicator and Frame Earthing Contact ,Confiming to IS 13947-2 1993 as Amended upto Date Complete with Following Accessories. 1 set of 3 CT's of ratio 2000/5A, Class 1.0 accuracy 15 VA burden for APFCR. Independent manual spring closing mechanism - 1 No. Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set. Multifunction meter with selector switch with suitable CT's and back up MCBs. The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmeter, selector switches, cast resin type CT's & PT's, etc. Separate CT's shall be provided for protective and measuring system and for APFCR of capacitor bank with suitable VA. 3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required. Shunt trip coil 220 Volt AC. BUS BAR 2500A TPN Aluminium bus bar with heat Shrink Sleeve OUTGOING ALL THE MCCB'S SHALL BE EQUIPPED/ PROVIDED WITH ALL ACCESSORIES & IN BUILT PROTECTION RELEASES 1 No. 800A 50KA 4P ACB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. Make ABB 4 No. 400A 50KA 4P ACB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. Make ABB 2 No. 630A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. Make ABB 1 No. 200A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. Make ABB 4 No. 125A 50KA 4P MCCB with Microprocessor Based Releases, ON Indication, with selector switch, matching cast resin CT's. Make ABB 1 No. 630A 50KA 4P MCCB (Spare) Make ABB 1 No. 400A 50KA 4P MCCB (Spare) Make ABB 1 No. 160A 50KA 4P MCCB (Spare) Make ABB 1 No. 125A 50KA 4P MCCB (Spare) Make ABB Other items such as Make ABB 1 set of control wiring 1 Set of designation plates Complete Panel as Above and complete SET 1.0 2250000.0 2250000.0 |
| 871 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 400 AMP FP MCCB BUS BAR : 500 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 29 No 40 AMP DP MCB with indication lights 1 No 20 AMP DP MCB with indication lights 7 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 457741.0 457741.0 |
| 872 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 630 AMP FP MCCB BUS BAR : 800 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 2 No 250 AMP FP MCCB with indication lights 4 No 125 AMP FP MCCB with indication lights 10 No 40 AMP FP MCB with indication lights 1 No 63 AMP DP MCB with indication lights 1 No 40 AMP DP MCB with indication lights 1 No 20 AMP FP MCB with indication lights 6 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 573253.0 573253.0 |
| 873 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 400 AMP FP MCCB BUS BAR : 500 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 1 No 125 AMP FP MCCB with indication lights 2 No 32 AMP FP MCB with indication lights 3 No 32 AMP DP MCB with indication lights 6 No 63 AMP DP MCB with indication lights 16 No 40 AMP DP MCB with indication lights 7 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 485600.0 485600.0 |
| 874 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 800 AMP FP ACB BUS BAR : 1000 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 9 No 125 AMP FP MCCB with indication lights 2 No 100 AMP FP MCCB with indication lights 7 No 32 AMP FP MCB with indication lights 2 No 32 AMP DP MCB with indication lights 2 No 63 AMP DP MCB with indication lights 2 No 40 AMP FP MCB with indication lights 1 No 40 AMP DP MCB with indication lights 9 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 549471.0 549471.0 |
| 875 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 125 AMP FP MCCB BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 8 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 142464.0 142464.0 |
| 876 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 125 AMP FP MCCB BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 8 No 63 AMP 4P MCB with indication lights complete panel as above and complete SET 1.0 142464.0 142464.0 |
| 877 | MR Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 250 AMP FP MCCB ( CABLE FROM THE EXISTING CENTRALISED UPS DISTRIBUTIONSYSTEM ) BUS BAR : 300 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 2 Nos 125 AMP 4P mccb with indication lamps 6 No 40 AMP DP MCB with indication lights 6 No 63 AMP 4P MCB with indication lights 1 No 63 AMP DP MCB with indication lights complete panel as above and complete SET 1.0 182553.0 182553.0 |
| 878 | MR Design, Manufacture, Supply, Installation, Testing and Commissioning of Panel Fabricated out of 16 SWG CRCA sheet steel, IP 54, wall / floor mounting type with rain canopy The sheet steel shall undergo minimum 7 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes 415 /240 V electrolitic Aluminium Bus Bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect, Panel Should Have Double Earthing Provision Which Connected to the Nearest Earth Grid. INCOMER: 1 no. 100A, 25KA 4P MCCB with microprocessor based releases, ON indication, 1 no. multifunction meter (showing all power parameters), with Selector Switch, Matching Cast Resin CT's. + 3 Nos 63A DP MCB For each Phase.with 3 Nos Astronomical Weekly programmable time switch (SST- 1min) ON Phase for automaitc switching of landscape light fixtures at sun set and sun rise or twilight (auto on/ auto off and auto mode) with manual override faiclity with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site. BUS BAR TPN Aluminium bus bar with heat Shrink Sleeve rated for 125A. OUTGOING 18 nos 16A DP MCB 4 nos 40A DP MCB 2 nos 63A 4P MCB Other items such as 1 Set of control wiring 1 Set of designation plates All Items complete as above SET 1.0 193274.0 193274.0 LT CABLE AND ACCESSORIES SUPPLY OF L.T. CABLE: Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required. |
| 879 | MR DSR 10 LT CABLE LAYING DSR 10.1 Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required. |
| 880 | DSR 10.1.1 |
| 881 | DSR 10.1.2 |
| 882 | DSR 10.1.3 |
| 883 | DSR 10.1.4 DSR 11 LT CABLE JOINTING & END TERMINATION DSR 11.1 Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed/ XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required. |
| 884 | DSR 11.1.20 |
| 885 | DSR 11.1.21 |
| 886 | DSR 11.1.22 |
| 887 | DSR 11.1.23 |
| 888 | DSR 11.1.24 |
| 889 | DSR 11.1.25 |
| 890 | DSR 11.1.26 |
| 891 | DSR 11.1.27 |
| 892 | DSR 11.1.29 |
| 893 | DSR 11.1.30 CABLE TRAYS WITH SUPPORTS |
| 894 | 4.6 0.170856481481481 150 mm width X 50 mm depth X 1.6 mm thickness Meter 150.0 842.67 126400.23 0.17087962962963 300 mm width X 50 mm depth X 1.6 mm thickness meter 200.0 1114.46 222892.56 0.170902777777778 450 mm width X 50 mm depth X 2.0 mm thickness Meter 500.0 1510.09 755043.3 0.170914351851852 600 mm width X 50 mm depth X 2.0 mm thickness Meter 50.0 2020.1 101004.75 DSR 2 MISCELLANEOUS ITEMS - DSR |
| 895 | 2.22 MISCELLANEOUS ITEMS - MR Items |
| 896 | MR DSR 5 EARTHING |
| 897 | 5.9 RCC Hume pipes Providing and laying non pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixtures of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete. |
| 898 | 0.795868055555556 |
| 899 | 0.79587962962963 |
| 900 | 0.795844907407407 Manholes Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design. |
| 901 | 0.772928240740741 Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : |
| 902 | 0.773622685185185 EXTERNAL LIGHTING SYSTEM DSR 12 POLE ERECTION 12.3 Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
| 903 | 0.502094907407407 12.6 Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape , Hole Seeling to be done complete as required. |
| 904 | 0.504178240740741 EXTERNAL LIGHTING SYSTEM SUPPLY OF EXTERNAL LIGHTING SYSTEM |
| 905 | 8.1 0.34181712962963 72 watt Nos. 5.0 2015.0 10074.24 |
| 906 | MR 2x6 sqmm Metre 50.0 211.0 10550.0 |
| 907 | 0.293761574074074 Upto 35 sq. mm Metre 50.0 265.5 13274.91 |
| 908 | 0.0536111111111111 3 core 2.5 sq.mm Metre 50.0 155.31 7765.56 TOTAL 26171918.7744 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 INTERNAL FIRE FIGHTING SYSTEM PROJECT - TTL BUILDING OF INTERNATIONAL CENTRE FOR AUTOMOTIVE TECHNOLOGY- ICAT , MANESAR S.No DESCRIPTION REF: DSR (E&M) QTY UNIT RATE (Rs.) AMOUNT (Rs.) A. (SCHEDULED ITEMS - AS PER DSR (E&M) 2025 |
| 909 | Supply, erection and testing of ISI marked ERW M.S. pipes (Class C - heavy duty) and specials etc. (as per IS:1239 for upto 150 mm dia and IS:3589 for 200 mm and above) for above ground laying for hydrants and sprinkler system including transportation of materials upto the worksite, cutting the pipes to required length, edge preperation, welding, fixing / erection of pipes including specials i.e. bends, tees, reducers, flanges, expansion joints and bellows wherever required, washers, nuts, bolts etc. in proper position including all supports. jointing by welding, aligning the pipe line, painting with two primer coat by zinc chromate primer and two coats of synthetic enamel fire red colour, providing tapping for pressure gauges and for other instruments etc. Hydrostatic testing of system at 1.5 times of operating pressure or 15 kg / sq cm whichever is higher and as specified, flushing & cleaning by water etc. complete as per drawings & direction of the Engineer-in-charge. The pipes and accessories will be provided with all type of supports (Maximum Support spacing = up to 25 mm dia @ 2 m, 32 mm to 100 mm dia @ 2.5 m, 150 mm & above dia @ 3 m) by minimum 3 mm thick G.I. clevis / sprinkler hangers / clamps / Tie rod supports with G.I. nuts, bolts, anchor / dash fastner and washer for hydrant / sprinkler piping, for 150 mm dia pipe the support will be through 50x50x6 mm painted / pre galvanized MS angle iron along with G.I. U clamp, nuts, washers, anchor fasteners etc as the case may be. upto 40 mm dia. pipe threaded fittings and threaded joints shall be provided (by white lead and spun yarn) and for 50 mm dia & above pipes welded joints shall be used. The Ductile iron fittings or Malleable Iron (IS : 1879) fittings shalll be heavy duty suitable to withstand at least a pressure of 150% of maximum working pressure with minimum of 15kg/cm2. 25 mm dia 1.12987268518519 75.0 M 965.45 72408.6 32 mm dia 1.12988425925926 5.0 M 1090.33 5451.63 40 mm dia 1.12989583333333 55.0 M 1321.19 72665.7 50 mm dia 1.12990740740741 35.0 M 1633.92 57187.05 65 mm dia 1.12991898148148 55.0 M 2051.58 112836.74 80 mm dia 1.12993055555556 20.0 M 2389.48 47789.68 100 mm dia 1.12994212962963 30.0 M 3229.0 96870.11 150 mm dia 1.1299537037037 5.0 M 4511.37 22556.85 |
| 910 | Providing, fixing, jointing and testing in position ISI marked (IS : 1239) G.I pipes (Medium class-B) (with screwed jointing by teflon tape) for dry piping of water curtain system complete with all necessary G.I fittings i.e. sockets, elbows, tees, bends, reducers, unions, plugs, supports, clamps, Hangers etc. The Galvanization shall conform to IS : 4736. The work shall include the painting with two primer coat by zinc chromate primer and two coats of synthetic enamel fire red colour, providing tapping for pressure gauges and for other instruments etc. Hydrostatic testing of system at 1.5 times of operating pressure or 15 kg / sq cm whichever is higher and as specified, flushing & cleaning by water etc. complete as per drawings & direction of the Engineer-in-charge. The pipes and accessories will be provided with all type of supports (Maximum Support spacing = up to 25 mm dia @ 2 m, 32 mm to 100 mm dia @ 2.5 m, 150 mm & above dia @ 3 m) by minimum 3 mm thick G.I. clevis / sprinkler hangers / clamps / Tie rod supports with G.I. nuts, bolts, anchor / dash fastner and washer. 80mm dia 1.130625 12.0 M 1588.79 19065.5 |
| 911 | Supply & installation of ISI marked single headed 63 mm dia. Stainless steel Hydrant Valve (Type A) suitable for hydrostatic test pressure of 21 kg/sqcm, 80 mm dia flanged inlet with 63 mm female instantaneous outlet confirming to IS : 5290 on the fire wet riser/down comer, including making 80 NB pipe flange connection with riser, fixing the landing valves in proper positions, including supply of nuts, bolts, gaskets, caps, chains etc. testing the hydrant and completing the work in all respect as per directions of the Engineer-in-charge. |
| 912 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required. 80 MM NB 1.13268518518519 R.O NOS 5673.06 - 100 MM NB 1.13269675925926 3.0 NOS 7630.19 22890.56 150 MM NB 1.13270833333333 R.O NOS 10218.01 - |
| 913 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 914 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required 80 NB 1.13476851851852 R.O NOS 8662.8 - 100 NB 1.13478009259259 R.O NOS 12438.54 - 150 NB 1.13480324074074 R.O NOS 19816.87 - |
| 915 | Providing and fixing C I body flanged S S strainer fabricated out of 1.6 mm thick Stainless Steel 304 sheet having 3 to 5 mm dia perforation. 80 mm dia. 1.13542824074074 R.O NOS 5369.78 - 100 mm dia. 1.13543981481481 R.O NOS 7629.14 - 150 mm dia. 1.13545138888889 R.O NOS 12259.09 - |
| 916 | Providing ISI marked RRL (IS : 636, type-A) fire hose pipe 15 meter long and 63 mm dia with ISI marked (IS : 903) suitable for hydrostatic test pressure 21 kg/sqcm, Stainless steel male and female coupling bound and rivetted to hose pipes with copper rivets and copper wire complete as required. |
| 917 | Supply, fixing, testing & commissioning of 20 mm bore and 40 meter long hose (high pressure rubber braided hose pipe as per IS:444 or Thermo plastic (Textile reinforced) fire hose pipe as per IS 12585) and hose reel, (The complete assembly shall be capable of withstanding the hydrostatic test pressure 21 kg/sqcm), for first aid fire fighting conforming to IS : 884, with 180o full swing drum, fixing brackets, 5 mm dia shut off Stainless steel nozzle, connecting directly from the riser through 40 mm dia. MS (Class C) pipe with sockets, elbows, nipples, 40x20 mm reducer, 20 dia pipe, 20 mm dia. hand lever operated isolating ball valve, etc. including providing operating instructions on a metal plate and fixing it near hose reel. The system shall be complete in all respects as per drawings and directions of Engineer-in-charge. |
| 918 | Providing Stainless steel ISI marked 63 mm. dia. male Instantaneous pattern short branch pipes with 20 mm dia. Nozzle as per IS : 903, suitable for hydrostatic test pressure 21 kg/sqcm and suitable for interconnections to hose pipe coupling as required. |
| 919 | Supply, installation and testing of cylindrical type flanged air cushion tank, 250 mm dia, 1200 mm long and of thickness 8 mm M.S., suitable supporting legs with MS plate of size 75x75x5 mm at the bottom and grouted in CC foundation. The air cushion tank shall be provided with air release valve, stop cock, safety valve, pressure gauge, 25 mm dia drain valve, tested to min 25 Kg/cm2 complete including painting with synthetic enamel paint of approved shade with all accessories as per direction of the Engineer-in-charge. (For Risers) |
| 920 | Supply, fixing, testing & commisioning of C.P. bronze / gun metal standard response Standard coverage type Sprinklers as per IS : 9972, comprises of 15mm dia conventional pattern, (K=80), 68oC, glass bulb type sprinklers, UL / FM listed / approved. The jointing shall be done by teflon tape and the installation shall be complete as per the drawings with positioning of sprinklers as per final coordinated plan and requirement of IS : 15105, local fire service & Engineer-in-charge. Pendant sprinkler 1.13959490740741 52.0 Nos 628.59 32686.71 Upright sprinkler 1.13960648148148 52.0 Nos 628.59 32686.71 Horizontal Sidewall Sprinkler 1.13961805555556 2.0 Nos 733.53 1467.06 |
| 921 | Providing & fixing UL listed water flow detectors / switches (Vane type) for sprinkler system, shall have sensitivity in the range of 4 to 10 US gallon per minute and static pressure rating of 450 PSI including accessories, junction box, suitable for indoor / outdoor mounting. The detector shall respond to water flow in the specified direction after a preset time delay that is field adjustable, complete as required suitable for fixing on fire pipe including connection for wiring. for 100 mm diameter pipe 1.1409837962963 3.0 Set 8467.61 25402.83 |
| 922 | Supply, fixing, testing & commisioning of UL / FM listed / approved SS 304 braided sprinkler flexible hose having branch line inlet of 25 mm dia and sprinkler head outlet of 15 mm dia, suitable for hydrostatic test pressure 21 kg/sqcm. The installation shall be complete as per the drawings with positioning of sprinklers as per final coordinated plan and requirement of IS : 15105, local fire service & Engineer-in-charge. 1000 mm length 1.14238425925926 50.0 Nos 1787.13 89356.41 |
| 923 | Supply, installation, testing & commisioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
| 924 | Providing and fixing of pressure switch in M.S. pipe line including connection etc. as required. B. (NON SCHEDULED ITEMS - AS PER MARKET RATES) |
| 925 | Supply & erection of ISI marked portable fire extinguishers, confirming to IS:15683, wall mounted type, wall brackets complete in all respect as per standard item with all accessories, delivery hose & nozzle whereever required, including fixing on walls as per the directions of Engineer-in-charge. Water CO2 type. 9 Lt. capacity MR-FF-1 6.0 NOS 7740.0 46440.0 ABC dry powder Type 6 kg. capacity MR-FF-3 6.0 NOS 6080.0 36480.0 |
| 926 | Providing & fixing neoprene rubber double flanged rubber expansion joint (anti vibration bellow) of standard length as per manufacturers specifications. suitable for hydrostatic test pressure of 21 kg/sqcm including all necessary fittings i.e. rubber gasket, nuts, bolts, washers etc complete as required. 80 mm dia. MR-FF-5 R.O NOS 6020.0 150 mm dia. MR-FF-6 R.O NOS 7350.0 |
| 927 | Providing & fixing standard carbon steel fireman axe with rubber insulated handle tested to 20000 Volts. |
| 928 | Supply, fixing, testing & commissioning of 25 mm dia inspecting and testing assembly with gun metal valve, sight glass, by pass valve and connection to the drain line as required to complete the system. |
| 929 | Providing and fixing weather proof standard fire hose cabinet (750 mm x 600 mm x 250 mm) outdoor type made of not less than 16 SWG MS sheet having glassed hinged door (5 mm thick glass) including necessary locking arrangement with handle for housing two nos.15 meter long fire hose pipes, branch pipe as required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coat of fire red colour). The cabinet shall be mounted on self standing mounted type MS Angle iron frame as required. The words \\"FIRE HOSE\\" to be painted on the box. |
| 930 | Providing and fixing standard fire hose cabinet door with frame (900 mm x 2000 mm ) or (suitable to fit in the duct made of not less than 16 SWG MS sheet having glass hinged door (5 mm thick glass) including necessary locking arrangement with handle as required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coats of fire red colour). The door shall be fixed in the masonry wall or as required. The words \\"FIRE HOSE\\" to be painted on the box. |
| 931 | Providing & fixing 100 mm dia dial pressure gauge including making connections with MS pipe complete in all respects. TOTAL - 1072481.53 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 INTERNAL FIRE FIGHTING SYSTEM PROJECT - EXISTING EEL BUILDING OF INTERNATIONAL CENTRE FOR AUTOMOTIVE TECHNOLOGY- ICAT , MANESAR S.No DESCRIPTION REF: DSR (E&M) QTY UNIT RATE (Rs.) AMOUNT (Rs.) A. (SCHEDULED ITEMS - AS PER DSR (E&M) 2025 |
| 932 | Supply, erection and testing of ISI marked ERW M.S. pipes (Class C - heavy duty) and specials etc. (as per IS:1239 for upto 150 mm dia and IS:3589 for 200 mm and above) for above ground laying for hydrants and sprinkler system including transportation of materials upto the worksite, cutting the pipes to required length, edge preperation, welding, fixing / erection of pipes including specials i.e. bends, tees, reducers, flanges, expansion joints and bellows wherever required, washers, nuts, bolts etc. in proper position including all supports. jointing by welding, aligning the pipe line, painting with two primer coat by zinc chromate primer and two coats of synthetic enamel fire red colour, providing tapping for pressure gauges and for other instruments etc. Hydrostatic testing of system at 1.5 times of operating pressure or 15 kg / sq cm whichever is higher and as specified, flushing & cleaning by water etc. complete as per drawings & direction of the Engineer-in-charge. The pipes and accessories will be provided with all type of supports (Maximum Support spacing = up to 25 mm dia @ 2 m, 32 mm to 100 mm dia @ 2.5 m, 150 mm & above dia @ 3 m) by minimum 3 mm thick G.I. clevis / sprinkler hangers / clamps / Tie rod supports with G.I. nuts, bolts, anchor / dash fastner and washer for hydrant / sprinkler piping, for 150 mm dia pipe the support will be through 50x50x6 mm painted / pre galvanized MS angle iron along with G.I. U clamp, nuts, washers, anchor fasteners etc as the case may be. upto 40 mm dia. pipe threaded fittings and threaded joints shall be provided (by white lead and spun yarn) and for 50 mm dia & above pipes welded joints shall be used. The Ductile iron fittings or Malleable Iron (IS : 1879) fittings shalll be heavy duty suitable to withstand at least a pressure of 150% of maximum working pressure with minimum of 15kg/cm2. 25 mm dia 1.12987268518519 1000.0 M 965.45 965448.0 32 mm dia 1.12988425925926 92.0 M 1090.33 100310.05 40 mm dia 1.12989583333333 150.0 M 1321.19 198179.19 50 mm dia 1.12990740740741 202.0 M 1633.92 330050.99 65 mm dia 1.12991898148148 84.0 M 2051.58 172332.47 80 mm dia 1.12993055555556 165.0 M 2389.48 394264.83 100 mm dia 1.12994212962963 100.0 M 3229.0 322900.38 150 mm dia 1.1299537037037 150.0 M 4511.37 676705.59 |
| 933 | Providing, fixing, jointing and testing in position ISI marked (IS : 1239) G.I pipes (Medium class-B) (with screwed jointing by teflon tape) for dry piping of water curtain system complete with all necessary G.I fittings i.e. sockets, elbows, tees, bends, reducers, unions, plugs, supports, clamps, Hangers etc. The Galvanization shall conform to IS : 4736. The work shall include the painting with two primer coat by zinc chromate primer and two coats of synthetic enamel fire red colour, providing tapping for pressure gauges and for other instruments etc. Hydrostatic testing of system at 1.5 times of operating pressure or 15 kg / sq cm whichever is higher and as specified, flushing & cleaning by water etc. complete as per drawings & direction of the Engineer-in-charge. The pipes and accessories will be provided with all type of supports (Maximum Support spacing = up to 25 mm dia @ 2 m, 32 mm to 100 mm dia @ 2.5 m, 150 mm & above dia @ 3 m) by minimum 3 mm thick G.I. clevis / sprinkler hangers / clamps / Tie rod supports with G.I. nuts, bolts, anchor / dash fastner and washer. 80mm dia 1.130625 12.0 M 1588.79 19065.5 |
| 934 | Supply & installation of ISI marked single headed 63 mm dia. Stainless steel Hydrant Valve (Type A) suitable for hydrostatic test pressure of 21 kg/sqcm, 80 mm dia flanged inlet with 63 mm female instantaneous outlet confirming to IS : 5290 on the fire wet riser/down comer, including making 80 NB pipe flange connection with riser, fixing the landing valves in proper positions, including supply of nuts, bolts, gaskets, caps, chains etc. testing the hydrant and completing the work in all respect as per directions of the Engineer-in-charge. |
| 935 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required. 80 MM NB 1.13268518518519 R.O NOS 5673.06 - 100 MM NB 1.13269675925926 R.O NOS 7630.19 - 150 MM NB 1.13270833333333 2.0 NOS 10218.01 20436.02 |
| 936 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 937 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required 80 NB 1.13476851851852 R.O NOS 8662.8 - 100 NB 1.13478009259259 R.O NOS 12438.54 - 150 NB 1.13480324074074 R.O NOS 19816.87 - |
| 938 | Providing and fixing C I body flanged S S strainer fabricated out of 1.6 mm thick Stainless Steel 304 sheet having 3 to 5 mm dia perforation. 80 mm dia. 1.13542824074074 R.O NOS 5369.78 - 100 mm dia. 1.13543981481481 R.O NOS 7629.14 - 150 mm dia. 1.13545138888889 R.O NOS 12259.09 - |
| 939 | Providing ISI marked RRL (IS : 636, type-A) fire hose pipe 15 meter long and 63 mm dia with ISI marked (IS : 903) suitable for hydrostatic test pressure 21 kg/sqcm, Stainless steel male and female coupling bound and rivetted to hose pipes with copper rivets and copper wire complete as required. |
| 940 | Supply, fixing, testing & commissioning of 20 mm bore and 40 meter long hose (high pressure rubber braided hose pipe as per IS:444 or Thermo plastic (Textile reinforced) fire hose pipe as per IS 12585) and hose reel, (The complete assembly shall be capable of withstanding the hydrostatic test pressure 21 kg/sqcm), for first aid fire fighting conforming to IS : 884, with 180o full swing drum, fixing brackets, 5 mm dia shut off Stainless steel nozzle, connecting directly from the riser through 40 mm dia. MS (Class C) pipe with sockets, elbows, nipples, 40x20 mm reducer, 20 dia pipe, 20 mm dia. hand lever operated isolating ball valve, etc. including providing operating instructions on a metal plate and fixing it near hose reel. The system shall be complete in all respects as per drawings and directions of Engineer-in-charge. |
| 941 | Providing Stainless steel ISI marked 63 mm. dia. male Instantaneous pattern short branch pipes with 20 mm dia. Nozzle as per IS : 903, suitable for hydrostatic test pressure 21 kg/sqcm and suitable for interconnections to hose pipe coupling as required. |
| 942 | Supply, installation and testing of cylindrical type flanged air cushion tank, 250 mm dia, 1200 mm long and of thickness 8 mm M.S., suitable supporting legs with MS plate of size 75x75x5 mm at the bottom and grouted in CC foundation. The air cushion tank shall be provided with air release valve, stop cock, safety valve, pressure gauge, 25 mm dia drain valve, tested to min 25 Kg/cm2 complete including painting with synthetic enamel paint of approved shade with all accessories as per direction of the Engineer-in-charge. (For Risers) |
| 943 | Supply, fixing, testing & commisioning of C.P. bronze / gun metal standard response Standard coverage type Sprinklers as per IS : 9972, comprises of 15mm dia conventional pattern, (K=80), 68oC, glass bulb type sprinklers, UL / FM listed / approved. The jointing shall be done by teflon tape and the installation shall be complete as per the drawings with positioning of sprinklers as per final coordinated plan and requirement of IS : 15105, local fire service & Engineer-in-charge. Pendant sprinkler 1.13959490740741 535.0 Nos 628.59 336295.97 Upright sprinkler 1.13960648148148 50.0 Nos 628.59 31429.53 Horizontal Sidewall Sprinkler 1.13961805555556 2.0 Nos 733.53 1467.06 |
| 944 | Providing & fixing UL listed water flow detectors / switches (Vane type) for sprinkler system, shall have sensitivity in the range of 4 to 10 US gallon per minute and static pressure rating of 450 PSI including accessories, junction box, suitable for indoor / outdoor mounting. The detector shall respond to water flow in the specified direction after a preset time delay that is field adjustable, complete as required suitable for fixing on fire pipe including connection for wiring. for 150 mm diameter pipe 1.14099537037037 2.0 Set 10120.41 20240.83 |
| 945 | Supply, fixing, testing & commisioning of UL / FM listed / approved SS 304 braided sprinkler flexible hose having branch line inlet of 25 mm dia and sprinkler head outlet of 15 mm dia, suitable for hydrostatic test pressure 21 kg/sqcm. The installation shall be complete as per the drawings with positioning of sprinklers as per final coordinated plan and requirement of IS : 15105, local fire service & Engineer-in-charge. 1000 mm length 1.14238425925926 250.0 Nos 1787.13 446782.05 |
| 946 | Supply, installation, testing & commisioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
| 947 | Providing and fixing of pressure switch in M.S. pipe line including connection etc. as required. B. (NON SCHEDULED ITEMS - AS PER MARKET RATES) |
| 948 | Supply & erection of ISI marked portable fire extinguishers, confirming to IS:15683, wall mounted type, wall brackets complete in all respect as per standard item with all accessories, delivery hose & nozzle whereever required, including fixing on walls as per the directions of Engineer-in-charge. Water CO2 type. 9 Lt. capacity MR-FF-1 12.0 NOS 7740.0 92880.0 ABC dry powder Type 6 kg. capacity MR-FF-3 12.0 NOS 6080.0 72960.0 |
| 949 | Providing & fixing neoprene rubber double flanged rubber expansion joint (anti vibration bellow) of standard length as per manufacturers specifications. suitable for hydrostatic test pressure of 21 kg/sqcm including all necessary fittings i.e. rubber gasket, nuts, bolts, washers etc complete as required. 80 mm dia. MR-FF-5 R.O NOS 6020.0 - 150 mm dia. MR-FF-6 R.O NOS 7350.0 - |
| 950 | Providing & fixing standard carbon steel fireman axe with rubber insulated handle tested to 20000 Volts. |
| 951 | Supply, fixing, testing & commissioning of 25 mm dia inspecting and testing assembly with gun metal valve, sight glass, by pass valve and connection to the drain line as required to complete the system. |
| 952 | Providing and fixing weather proof standard fire hose cabinet (750 mm x 600 mm x 250 mm) outdoor type made of not less than 16 SWG MS sheet having glassed hinged door (5 mm thick glass) including necessary locking arrangement with handle for housing two nos.15 meter long fire hose pipes, branch pipe as required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coat of fire red colour). The cabinet shall be mounted on self standing mounted type MS Angle iron frame as required. The words \\"FIRE HOSE\\" to be painted on the box. |
| 953 | Providing and fixing standard fire hose cabinet door with frame (900 mm x 2000 mm ) or (suitable to fit in the duct made of not less than 16 SWG MS sheet having glass hinged door (5 mm thick glass) including necessary locking arrangement with handle as required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coats of fire red colour). The door shall be fixed in the masonry wall or as required. The words \\"FIRE HOSE\\" to be painted on the box. |
| 954 | Providing & fixing 100 mm dia dial pressure gauge including making connections with MS pipe complete in all respects. TOTAL 4680287.76 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 INTERNAL FIRE FIGHTING SYSTEM PROJECT - VEL BUILDING OF INTERNATIONAL CENTRE FOR AUTOMOTIVE TECHNOLOGY- ICAT , MANESAR S.No DESCRIPTION REF: DSR (E&M) QTY UNIT RATE (Rs.) AMOUNT (Rs.) A. (SCHEDULED ITEMS - AS PER DSR (E&M) 2025 |
| 955 | Supply, erection and testing of ISI marked ERW M.S. pipes (Class C - heavy duty) and specials etc. (as per IS:1239 for upto 150 mm dia and IS:3589 for 200 mm and above) for above ground laying for hydrants and sprinkler system including transportation of materials upto the worksite, cutting the pipes to required length, edge preperation, welding, fixing / erection of pipes including specials i.e. bends, tees, reducers, flanges, expansion joints and bellows wherever required, washers, nuts, bolts etc. in proper position including all supports. jointing by welding, aligning the pipe line, painting with two primer coat by zinc chromate primer and two coats of synthetic enamel fire red colour, providing tapping for pressure gauges and for other instruments etc. Hydrostatic testing of system at 1.5 times of operating pressure or 15 kg / sq cm whichever is higher and as specified, flushing & cleaning by water etc. complete as per drawings & direction of the Engineer-in-charge. The pipes and accessories will be provided with all type of supports (Maximum Support spacing = up to 25 mm dia @ 2 m, 32 mm to 100 mm dia @ 2.5 m, 150 mm & above dia @ 3 m) by minimum 3 mm thick G.I. clevis / sprinkler hangers / clamps / Tie rod supports with G.I. nuts, bolts, anchor / dash fastner and washer for hydrant / sprinkler piping, for 150 mm dia pipe the support will be through 50x50x6 mm painted / pre galvanized MS angle iron along with G.I. U clamp, nuts, washers, anchor fasteners etc as the case may be. upto 40 mm dia. pipe threaded fittings and threaded joints shall be provided (by white lead and spun yarn) and for 50 mm dia & above pipes welded joints shall be used. The Ductile iron fittings or Malleable Iron (IS : 1879) fittings shalll be heavy duty suitable to withstand at least a pressure of 150% of maximum working pressure with minimum of 15kg/cm2. 25 mm dia 1.12987268518519 255.0 M 965.45 246189.24 32 mm dia 1.12988425925926 5.0 M 1090.33 5451.63 40 mm dia 1.12989583333333 42.0 M 1321.19 55490.17 50 mm dia 1.12990740740741 75.0 M 1633.92 122543.69 65 mm dia 1.12991898148148 165.0 M 2051.58 338510.21 80 mm dia 1.12993055555556 150.0 M 2389.48 358422.57 100 mm dia 1.12994212962963 120.0 M 3229.0 387480.46 150 mm dia 1.1299537037037 150.0 M 4511.37 676705.59 |
| 956 | Providing, fixing, jointing and testing in position ISI marked (IS : 1239) G.I pipes (Medium class-B) (with screwed jointing by teflon tape) for dry piping of water curtain system complete with all necessary G.I fittings i.e. sockets, elbows, tees, bends, reducers, unions, plugs, supports, clamps, Hangers etc. The Galvanization shall conform to IS : 4736. The work shall include the painting with two primer coat by zinc chromate primer and two coats of synthetic enamel fire red colour, providing tapping for pressure gauges and for other instruments etc. Hydrostatic testing of system at 1.5 times of operating pressure or 15 kg / sq cm whichever is higher and as specified, flushing & cleaning by water etc. complete as per drawings & direction of the Engineer-in-charge. The pipes and accessories will be provided with all type of supports (Maximum Support spacing = up to 25 mm dia @ 2 m, 32 mm to 100 mm dia @ 2.5 m, 150 mm & above dia @ 3 m) by minimum 3 mm thick G.I. clevis / sprinkler hangers / clamps / Tie rod supports with G.I. nuts, bolts, anchor / dash fastner and washer. 80mm dia 1.130625 18.0 M 1588.79 28598.25 |
| 957 | Supply & installation of ISI marked single headed 63 mm dia. Stainless steel Hydrant Valve (Type A) suitable for hydrostatic test pressure of 21 kg/sqcm, 80 mm dia flanged inlet with 63 mm female instantaneous outlet confirming to IS : 5290 on the fire wet riser/down comer, including making 80 NB pipe flange connection with riser, fixing the landing valves in proper positions, including supply of nuts, bolts, gaskets, caps, chains etc. testing the hydrant and completing the work in all respect as per directions of the Engineer-in-charge. |
| 958 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required. 80 MM NB 1.13268518518519 R.O NOS 5673.06 - 100 MM NB 1.13269675925926 6.0 NOS 7630.19 45781.12 150 MM NB 1.13270833333333 8.0 NOS 10218.01 81744.06 |
| 959 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 960 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required 80 NB 1.13476851851852 R.O NOS 8662.8 - 100 NB 1.13478009259259 R.O NOS 12438.54 - 150 NB 1.13480324074074 R.O NOS 19816.87 - |
| 961 | Providing and fixing C I body flanged S S strainer fabricated out of 1.6 mm thick Stainless Steel 304 sheet having 3 to 5 mm dia perforation. 80 mm dia. 1.13542824074074 R.O NOS 5369.78 - 100 mm dia. 1.13543981481481 R.O NOS 7629.14 - 150 mm dia. 1.13545138888889 R.O NOS 12259.09 - |
| 962 | Providing ISI marked RRL (IS : 636, type-A) fire hose pipe 15 meter long and 63 mm dia with ISI marked (IS : 903) suitable for hydrostatic test pressure 21 kg/sqcm, Stainless steel male and female coupling bound and rivetted to hose pipes with copper rivets and copper wire complete as required. |
| 963 | Supply, fixing, testing & commissioning of 20 mm bore and 40 meter long hose (high pressure rubber braided hose pipe as per IS:444 or Thermo plastic (Textile reinforced) fire hose pipe as per IS 12585) and hose reel, (The complete assembly shall be capable of withstanding the hydrostatic test pressure 21 kg/sqcm), for first aid fire fighting conforming to IS : 884, with 180o full swing drum, fixing brackets, 5 mm dia shut off Stainless steel nozzle, connecting directly from the riser through 40 mm dia. MS (Class C) pipe with sockets, elbows, nipples, 40x20 mm reducer, 20 dia pipe, 20 mm dia. hand lever operated isolating ball valve, etc. including providing operating instructions on a metal plate and fixing it near hose reel. The system shall be complete in all respects as per drawings and directions of Engineer-in-charge. |
| 964 | Providing Stainless steel ISI marked 63 mm. dia. male Instantaneous pattern short branch pipes with 20 mm dia. Nozzle as per IS : 903, suitable for hydrostatic test pressure 21 kg/sqcm and suitable for interconnections to hose pipe coupling as required. |
| 965 | Supply, installation and testing of cylindrical type flanged air cushion tank, 250 mm dia, 1200 mm long and of thickness 8 mm M.S., suitable supporting legs with MS plate of size 75x75x5 mm at the bottom and grouted in CC foundation. The air cushion tank shall be provided with air release valve, stop cock, safety valve, pressure gauge, 25 mm dia drain valve, tested to min 25 Kg/cm2 complete including painting with synthetic enamel paint of approved shade with all accessories as per direction of the Engineer-in-charge. (For Risers) |
| 966 | Supply, fixing, testing & commisioning of C.P. bronze / gun metal standard response Standard coverage type Sprinklers as per IS : 9972, comprises of 15mm dia conventional pattern, (K=80), 68oC, glass bulb type sprinklers, UL / FM listed / approved. The jointing shall be done by teflon tape and the installation shall be complete as per the drawings with positioning of sprinklers as per final coordinated plan and requirement of IS : 15105, local fire service & Engineer-in-charge. Pendant sprinkler 1.13959490740741 148.0 Nos 628.59 93031.41 Upright sprinkler 1.13960648148148 148.0 Nos 628.59 93031.41 Horizontal Sidewall Sprinkler 1.13961805555556 15.0 Nos 733.53 11002.96 |
| 967 | Providing & fixing UL listed water flow detectors / switches (Vane type) for sprinkler system, shall have sensitivity in the range of 4 to 10 US gallon per minute and static pressure rating of 450 PSI including accessories, junction box, suitable for indoor / outdoor mounting. The detector shall respond to water flow in the specified direction after a preset time delay that is field adjustable, complete as required suitable for fixing on fire pipe including connection for wiring. for 100 mm diameter pipe 1.1409837962963 1.0 Set 8467.61 8467.61 for 150 mm diameter pipe 1.14099537037037 2.0 Set 10120.41 20240.83 |
| 968 | Supply, fixing, testing & commisioning of UL / FM listed / approved SS 304 braided sprinkler flexible hose having branch line inlet of 25 mm dia and sprinkler head outlet of 15 mm dia, suitable for hydrostatic test pressure 21 kg/sqcm. The installation shall be complete as per the drawings with positioning of sprinklers as per final coordinated plan and requirement of IS : 15105, local fire service & Engineer-in-charge. 1000 mm length 1.14238425925926 148.0 Nos 1787.13 264494.97 |
| 969 | Supply, installation, testing & commisioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
| 970 | Providing and fixing of pressure switch in M.S. pipe line including connection etc. as required. B. (NON SCHEDULED ITEMS - AS PER MARKET RATES) |
| 971 | Supply & erection of ISI marked portable fire extinguishers, confirming to IS:15683, wall mounted type, wall brackets complete in all respect as per standard item with all accessories, delivery hose & nozzle whereever required, including fixing on walls as per the directions of Engineer-in-charge. Water CO2 type. 9 Lt. capacity MR-FF-1 11.0 NOS 7740.0 85140.0 ABC dry powder Type 6 kg. capacity MR-FF-3 11.0 NOS 6080.0 66880.0 |
| 972 | Providing & fixing neoprene rubber double flanged rubber expansion joint (anti vibration bellow) of standard length as per manufacturers specifications. suitable for hydrostatic test pressure of 21 kg/sqcm including all necessary fittings i.e. rubber gasket, nuts, bolts, washers etc complete as required. 80 mm dia. MR-FF-5 R.O NOS 6020.0 - 150 mm dia. MR-FF-6 R.O NOS 7350.0 - |
| 973 | Providing & fixing standard carbon steel fireman axe with rubber insulated handle tested to 20000 Volts. |
| 974 | Supply, fixing, testing & commissioning of 25 mm dia inspecting and testing assembly with gun metal valve, sight glass, by pass valve and connection to the drain line as required to complete the system. |
| 975 | Providing and fixing weather proof standard fire hose cabinet (750 mm x 600 mm x 250 mm) outdoor type made of not less than 16 SWG MS sheet having glassed hinged door (5 mm thick glass) including necessary locking arrangement with handle for housing two nos.15 meter long fire hose pipes, branch pipe as required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coat of fire red colour). The cabinet shall be mounted on self standing mounted type MS Angle iron frame as required. The words \\"FIRE HOSE\\" to be painted on the box. |
| 976 | Providing and fixing standard fire hose cabinet door with frame (900 mm x 2000 mm ) or (suitable to fit in the duct made of not less than 16 SWG MS sheet having glass hinged door (5 mm thick glass) including necessary locking arrangement with handle as required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coats of fire red colour). The door shall be fixed in the masonry wall or as required. The words \\"FIRE HOSE\\" to be painted on the box. |
| 977 | Providing & fixing 100 mm dia dial pressure gauge including making connections with MS pipe complete in all respects. Total in Figures 3490463.0 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 EXTERNAL PLUMBING WORKS PROJECT - INTERNATIONAL CENTRE FOR AUTOMOTIVE TECHNOLOGY- ICAT , MANESAR SNo DESCRIPTION D.S.R. No. QTY. UNIT RATE (Rs.) AMOUNT (Rs.) A. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - EXTERNAL WATER SUPPLY SYSTEM |
| 978 | Providing, fixing G. I. pipes complete with all required G. I. fittings including trenching and refilling etc. (external work) Domestic line to fill VEL building oht (tapping from existing supply line) 40 mm. dia nominal bore 0.758391203703704 190.0 M. 647.53 123031.13 |
| 979 | Providing and filling sand of grading zone V or coarser grade alround the G.I. pipes in external work. 40 mm. dia nominal bore 0.778530092592593 190.0 M. 175.25 33297.46 |
| 980 | Painting G. I. Pipes & fittings with two coats of anti-corrosive bitumastic paint of approved quality 40 mm. dia nominal bore 0.777835648148148 190.0 M. 26.5 5034.5 |
| 981 | Providing & fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) 40 mm nominal bore 0.761840277777778 1.0 Nos 866.91 866.91 |
| 982 | Making connection of G.I.distribution branch with G.I.mains of following size by providing and fixing Tee, including cutting and threading the pipe etc. complete. 25 to 40 mm. Nominal bore 0.759039351851852 1.0 Nos 956.95 956.95 |
| 983 | Fixing water meter and stop cock in G.I.pipe line including cutting and threading the pipe and making longscrews etc.complete ( cost of water meter and stop cock to be paid seperately ) |
| 984 | Excavating trenches upto 1.5 meter depth in all kind of soil of required width for pipes. including excavation for sockets and dressing of sides ramming of bottoms including getting out the excavated soil & then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc & disposing of surplus excavated soil as directed within a lead of 50m. (i) Pipes, cables etc, not exceeding 80 mm dia. 2.10.1.1 190.0 RM 226.25 42987.62 |
| 985 | Constructing brick masonry chamber 600 x 600 x 750 mm inside with F.P.S. brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for Sluice Valve, with C. I. surface box 100 mm top diameter, 160 mm bottom diameter and 180mm deep (inside) with chained lid and RCC top slab with 1 : 2 : 4 mix (1 cement : 2 coarse sand : 4 grade stone aggregate 20 mm nominal size); necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1 : 3 (1 cement : 3 coarse sand ) 12 mm thick finished with a floating coat of neat cement complete as per standard design |
| 986 | Constructing brick masonry chamber 600 x 450 x 500 mm, inside with F.P.S. brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for Water Meter complete with C. I. double flap surface box 400x200x200 mm (inside) with locking arrangment and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 grade stone aggregate 20mm nominal size) necessary excavation,foundation concrete 1:5:10 (1 cement :5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand ) 12 mm thick finished with a floating coat of neat cement complete as per standard design B. (NON SCHEDULED ITEMS - AS PER MARKET RATES) - EXTERNAL WATER SUPPLY SYSTEM |
| 987 | Providing, fixing, joints and testing in position the following uPVC Pipe conferming to IS:4985 of 6kg sqcm for garden irrigation system cut to required length pipe to be laid below level in trenches up to required depth, including excavation in all kind of soil. 32 mm OD MR-PL-32 8.0 M. 277.0 2216.0 40 mm OD MR-PL-33 200.0 M. 316.0 63200.0 50 mm OD MR-PL-34 R.O M. 363.0 - 75 mm OD MR-PL-35 R.O M. 495.0 - 90 mm OD MR-PL-36 R.O M. 545.0 - |
| 988 | Providing & fixing in position 25 mm dia lawn hydrants consisting of 25 mm dia Ball valve, GI nipple and threaded hose receiver complete as required. |
| 989 | Providing & fixing 16mm dia and 4mm pvc drip irrigation hose for irrigation of black color with emitter, straight connector and all accessories complete in all respects. C. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - STORM WATER DRAINAGE SYSTEM UNDERGROUND DRAINS |
| 990 | Excavating trenches in all kind of soil of required width for pipes. including excavation for sockets and dressing of sides, ramming of bottoms, including getting out the excavated soil & then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc & disposing of surplus excavated soil as directed within a lead of 50m. up to 1.50 m depth Pipes 80 mm to 300 mm diameter 2.10.1.2 140.0 RM 369.55 51736.47 Pipes 300 mm diameter but not exceeding 600mm 2.10.1.3 260.0 RM 576.91 149995.99 1.50 m to 3.00 m depth Pipes 80 mm to 300 mm diameter 2.11 49.0 RM 880.31 43135.19 Pipes 300 mm diameter but not exceeding 600mm 2.11 91.0 RM 1374.27 125058.9 3.0 m to 4.50 m depth Pipes 80 mm to 300 mm diameter 2.12 R.O RM 2097.02 - Pipes 300 mm diameter but not exceeding 600mm 2.12 R.O RM 3119.6 - |
| 991 | Open timbering in trenches including strutting and shoring complete. (Measurement to be taken of the face area timbered) Depth not exceeding 1.5 meter 0.0972337962962963 1620.0 SQM 75.61 122487.02 Depth 1.5 to 3.00 meter 0.0972453703703704 810.0 SQM 85.63 69361.14 Depth 3.0 to 4.50 meter 0.0972569444444444 R.O SQM 102.05 - |
| 992 | Providing and laying Non pressure NP 2 class (light duty) RCC pipe with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1cement : 2 fine sand ) including testing of joints etc. complete. 150 mm. dia. RCC Pipes 0.795856481481481 R.O M. 583.94 - 250 mm. dia. RCC Pipes 0.795868055555556 140.0 M. 944.25 132195.02 300 mm. dia. RCC Pipes 0.79587962962963 175.0 M. 1043.42 182598.22 450 mm. dia. RCC Pipes 0.795891203703704 85.0 M. 1701.02 144587.12 500 mm. dia. RCC Pipes 0.795902777777778 R.O M. 2013.69 - 600 mm. dia. RCC Pipes 0.795914351851852 R.O M. 2354.22 - |
| 993 | Providing and laying in position cement concrete excluding the cost of centering and shuttering. (in all type of work upto plinth level) by 1:4:8 (1 cement : 4 coarse sand : 8 graded stone agg. 40 mm nominal size) |
| 994 | Constructing brick masonary road gully chamber 50 x 45 x 60cm with F.P.S. brick in cement mortar 1 : 4 (1 cement : 4 coarse sand) including 500 x 450 mm pre cast RCC horizontal grating with frame complete as per standard design. |
| 995 | Constructing brick masonary road gully chamber 110x50x77.5 cm with F.P.S. brick in cement mortar 1 : 4 (1 cement : 4 coarse sand) including 500 x 450 mm pre cast RCC horizontal grating with frame and vertical grating complete as per standard design. |
| 996 | Providing extra depth of Catch pits including excavation, all civil work complete. For 500 x 450 mm inner size M.R 8.0 M 3200.0 25600.0 For 1100 x 500 mm inner size M.R 25.0 M 5200.0 130000.0 D. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - EXTERNAL SEWERAGE SYSTEM |
| 997 | Excavating trenches in all kind of soil of required width for pipes. including excavation for sockets and dressing of sides, ramming of bottoms, including getting out the excavated soil & then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc & disposing of surplus excavated soil as directed within a lead of 50m. up to 1.50 m depth Pipes 80 mm to 300 mm diameter 2.10.1.2 100.0 RM 369.55 36954.62 Pipes 300 mm diameter but not exceeding 600mm 2.10.1.3 100.0 RM 576.91 57690.77 1.50 m to 3.00 m depth Pipes 80 mm to 300 mm diameter 2.11 35.0 RM 880.31 30810.85 Pipes 300 mm diameter but not exceeding 600mm 2.11 35.0 RM 1374.27 48099.58 3.0 m to 4.50 m depth Pipes 80 mm to 300 mm diameter 2.12 R.O RM 1998.3 - Pipes 300 mm diameter but not exceeding 600mm 2.12 R.O RM 3119.6 - |
| 998 | Open timbering in trenches including strutting and shoring complete. (Measurement to be taken of the face area timbered) Depth not exceeding 1.5 meter 0.0972337962962963 810.0 SQM 75.61 61243.51 Depth 1.5 to 3.00 meter 0.0972453703703704 405.0 SQM 85.63 34680.57 Depth 3.0 to 4.50 meter 0.0972569444444444 R.O SQM 102.05 - |
| 999 | Providing and laying Non pressure NP 2 class (light duty) RCC pipe with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1cement : 2 fine sand ) including testing of joints etc. complete. 150 mm. dia. RCC Pipes 0.795856481481481 25.0 M. 583.94 14598.47 250 mm. dia. RCC Pipes 0.795868055555556 140.0 M. 944.25 132195.02 300 mm. dia. RCC Pipes 0.79587962962963 165.0 M. 1043.42 172164.04 450 mm. dia. RCC Pipes 0.795891203703704 R.O M. 1701.02 - |
| 1000 | Providing and laying in position cement concrete excluding the cost of centering and shuttering. (in all type of work upto plinth level) by 1:4:8 (1 cement : 4 coarse sand : 8 graded stone agg. 40 mm nominal size) |
| 1001 | Constructing brick masonry manhole with F.P.S. bricks in cement mortar 1 : 4 (1 cement : 4 coarse sand) RCC top slab with 1 : 2 : 4 mix (1 cement : 2 coarse sand : 4 grade stone aggregate 20mm nominal size); foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) inside plastering 12 mm thick with cement mortar 1:3 (1cement 3 coarse sand ) finished with a floating coat of neat cement and making channels in cement concrete 1:2:4 (1cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) finishd with a floating coat of neat cement complete as per standard design Inside size 90 x 80 cm & 45 cm deep including CI cover with frame (light duty) 455 x 610mm internal dimension total wt. of cover & frame to be not less than 38 kg (wt. of cover 23 kg and wt. of frame 15 kg) 19.7.1.1 15.0 Nos 13401.42 201021.23 Inside size 120 x 90 cm & 90 cm deep including CI cover with frame (medium duty) 500mm internal dimension total wt. of cover & frame to be not less than 116 kg (wt. of cover 58 kg and wt. of frame 58 kg) 19.7.2.1 2.0 Nos 27709.93 55419.86 |
| 1002 | Extra for depth for manhole with F.P.S. bricks size 90 X 80 cm 19.8.1.1 12.0 M 9261.37 111136.5 size 120 X 90 cm 19.8.2.1 1.0 M 11108.42 11108.42 |
| 1003 | Making connection of sewer/drain line with existing manhole including breaking into & making good the wall, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1 : 3 (1cement : 3 coarse sand) finished with a floating coat of neat cement and making necessary channels for the drain etc. complete For pipes 350 to 450 mm diameter 0.806284722222222 2.0 nos 1394.08 2788.15 |
| 1004 | Providing M.S. foot rests including fixing in manholes with 20*20*10 cm cement concrete blocks 1:3:6 (1 cement : 3 coarse sand :6 graded stone aggregate 20 mm nominal size) as per standard design : with 20 x 20 mm square bar |
| 1005 | Providing and fixing square mouth S. W. Gully trap grade `A' complete with C.I. grating brick masonry chamber with F.P.S bricks and water tight CI cover with frame of 300 x 300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design 180 x 150 mm. size P type 19.4.3.1 5.0 nos 2940.58 14702.88 |
| 1006 | Constructing Grease trap 80 x 40 x 46 cm (inside) with one brick thick brick masonry wall with inlet and outlet drain with bricks in cement mortar 1 : 4 (1 cement : 4 fine sand) plastered 12 mm thick with 1 : 4 (1 cement : 4 coarse sand) finished with a floating coat of neat cement on inside and exposed surfaces having two stone baffled walls 34.5 cm deep and third one 19 cm deep, each 40 mm thick and 45 cm long embedded 2.5 cm on either side in brick masonry, 40 mm thick 100 x 60 cm stone cover and 7.5 cm thick bed concrete 1 : 5 : 10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) with 40 mm flooring in cement concrete 1 : 2 : 4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5 mm nominal size) with a floating coat of neat cement including all earth excavation, refilling and disposal of surplus earth complete as per standard design. 80 x 40 x 46 cm. size MR 1.0 nos 80000.0 80000.0 E. (SCHEDULED ITEMS AS PER D.S.R. - 2023) - RAIN WATER PIPES AND FITTINGS - (Rigid PVC) |
| 1007 | Providing and fixing on wall face unplasticised - Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion - Single socketed pipes 110 mm dia 0.52849537037037 R.O M 396.04 160 mm dia MR 10.0 M 509.49 5094.9 |
| 1008 | Providing and fixing on wall face unplasticised - PVC moulded fittings / accessories for unplasticised - Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion - Bend 87.5o 110 mm bend 12.42.5.2 R.O Nos 157.78 160 mm bend MR 30.0 Nos 202.97 6089.18 |
| 1009 | Providing and fixing unplasticised - PVC pipe clips of approved design to unplasticised - Rigid PVC rain water pipes by means of 50x50x50 mm hard wood plug screwed with MS screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm 0.529884259259259 R.O Nos 389.64 160 mm MR 80.0 Nos 501.26 40100.4 |
| 1010 | Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. |
| 1011 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. |
| 1012 | Providing and fixing 15 cm wide, 45 cm overall semi-circular plain G.S. sheet gutter with iron brackets 40x3 mm size, bolts, nuts and washers, e.t.c., including making necessary connections with rain water pipes complete. 0.80 mm thick with zink coating not less than 275 gm/sqmt. Total in Figures 2924652.79 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 EXTERNAL FIRE FIGHTING AND FIRE PLANT ROOM SYSTEM PROJECT - INTERNATIONAL CENTRE FOR AUTOMOTIVE TECHNOLOGY- ICAT , MANESAR S.No DESCRIPTION REF: DSR 2023 Total QTY UNIT RATE (Rs.) AMOUNT (Rs.) A. (SCHEDULED ITEMS - AS PER DSR (DSR VOL-2 2023) RATES) |
| 1013 | Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 0.772928240740741 3.0 NOS 11399.0 34197.01 B. (SCHEDULED ITEMS - AS PER DSR (E&M) 2025 |
| 1014 | Supply, laying & jointing of ISI marked ERW Mild Steel pipes (class C - heavy duty) (as per IS:1239 for upto 150 mm dia and IS:3589 for 200 mm and above) including all fittings i.e. reducer, elbows, tees, flanges, washers, nuts, boltsetc. below ground including transportation of all materials to work site, earth work in excavation in all kinds of soil upto 1.50 meter depth, edge preparation, jointing by welding, laying the pipes in trenches in proper alignment, back filling the trenches in layers of 20 cms, consolidation of each deposited layer, watering, ramming, disposal of surplus earth within a lead of 200 m and as directed, Hydrostatic testing of system at 1.5 times of operating pressure or 15 kg / sq cm whichever is higher and as specified, providing 1:2:4 concrete thrust blocks of suitable size at all bends, tees and junctions with form works, completing the work in all respect as per drawings & direction of the Engineer-in-charge. The rates will include providing and laying 4 mm thick \\"Pypkote\\" tar based polymeric corrosion protection tape over coat of zinc chromate primer as per manufacturers specs, as directed and as per IS:10221. 150 mm dia 1.12918981481481 365.0 M 5356.14 1954990.22 |
| 1015 | Supply, erection and testing of ISI marked ERW M.S. pipes (Class C - heavy duty) and specials etc. (as per IS:1239 for upto 150 mm dia and IS:3589 for 200 mm and above) for above ground laying for hydrants and sprinkler system including transportation of materials upto the worksite, cutting the pipes to required length, edge preperation, welding, fixing / erection of pipes including specials i.e. bends, tees, reducers, flanges, expansion joints and bellows wherever required, washers, nuts, bolts etc. in proper position including all supports. jointing by welding, aligning the pipe line, painting with two primer coat by zinc chromate primer and two coats of synthetic enamel fire red colour, providing tapping for pressure gauges and for other instruments etc. Hydrostatic testing of system at 1.5 times of operating pressure or 15 kg / sq cm whichever is higher and as specified, flushing & cleaning by water etc. complete as per drawings & direction of the Engineer-in-charge. The pipes and accessories will be provided with all type of supports (Maximum Support spacing = up to 25 mm dia @ 2 m, 32 mm to 100 mm dia @ 2.5 m, 150 mm & above dia @ 3 m) by minimum 3 mm thick G.I. clevis / sprinkler hangers / clamps / Tie rod supports with G.I. nuts, bolts, anchor / dash fastner and washer for hydrant / sprinkler piping, for 150 mm dia pipe the support will be through 50x50x6 mm painted / pre galvanized MS angle iron along with G.I. U clamp, nuts, washers, anchor fasteners etc as the case may be. upto 40 mm dia. pipe threaded fittings and threaded joints shall be provided (by white lead and spun yarn) and for 50 mm dia & above pipes welded joints shall be used. The Ductile iron fittings or Malleable Iron (IS : 1879) fittings shalll be heavy duty suitable to withstand at least a pressure of 150% of maximum working pressure with minimum of 15kg/cm2. 80 mm dia 1.12993055555556 4.0 M 2389.48 9557.94 150 mm dia 1.1299537037037 150.0 M 4511.37 676705.59 |
| 1016 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Stainless Steel cap and chain as required : |
| 1017 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required. 80 MM NB 1.13268518518519 3.0 NOS 5673.06 17019.17 100 MM NB 1.13269675925926 3.0 NOS 7630.19 22890.56 150 MM NB 1.13270833333333 3.0 NOS 10218.01 30654.02 |
| 1018 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required 150 MM NB 1.13340277777778 3.0 NOS 25152.02 75456.06 |
| 1019 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 1020 | Providing ISI marked RRL (IS : 636, type-A) fire hose pipe 15 meter long and 63 mm dia with ISI marked (IS : 903) suitable for hydrostatic test pressure 21 kg/sqcm, Stainless steel male and female coupling bound and rivetted to hose pipes with copper rivets and copper wire complete as required. |
| 1021 | Providing Stainless steel ISI marked 63 mm. dia. male Instantaneous pattern short branch pipes with 20 mm dia. Nozzle as per IS : 903, suitable for hydrostatic test pressure 21 kg/sqcm and suitable for interconnections to hose pipe coupling as required. |
| 1022 | Supply, fixing, testing & commissioning of cast iron body and brass/bronze working parts, UL listed installation control valve assembly, suitable for hydrostatic test pressure 21 kg/sqcm, complete with Hydraulic Alarm motor & hydraulically driven mechanical gong bell to sound continuous alarm when sprinkler system activates, butterfly valve, alarm valve, test valve, pressure gauge, emergency releases, pressure switch, 50 mm dia drain valve, flanges, gasket etc. to complete the system as required, as per manufacturers specifications. 150 mm diameter 1.14170138888889 3.0 Set 53314.77 159944.3 S.No DESCRIPTION Total QTY UNIT RATE (Rs.) AMOUNT (Rs.) C. (NON SCHEDULED ITEMS - AS PER MARKET RATES) |
| 1023 | Supply & erection of ISI marked portable fire extinguishers, confirming to IS:15683, wall mounted type, wall brackets complete in all respect as per standard item with all accessories, delivery hose & nozzle whereever required, including fixing on walls as per the directions of Engineer-in-charge. Water CO2 type. 9 Lt. capacity MR-FF-1 2.0 NOS 7740.0 15480.0 D.C.P. Type 6 kg. capacity MR-FF-2 5.0 NOS 12390.0 61950.0 ABC dry powder Type 6 kg. capacity MR-FF-3 2.0 NOS 6080.0 12160.0 CO2 gas type. 6.5 kg. cap. -Trolley mounted MR-FF-4 4.0 NOS 23490.0 93960.0 |
| 1024 | Providing and fixing weather proof standard fire hose cabinet (750 mm x 600 mm x 250 mm) outdoor type made of not less than 16 SWG MS sheet having glassed hinged door (5 mm thick glass) including necessary locking arrangement with handle for housing two nos.15 meter long fire hose pipes, branch pipe as required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coat of fire red colour). The cabinet shall be mounted on self standing mounted type MS Angle iron frame as required. The words \\"FIRE HOSE\\" to be painted on the box. |
| 1025 | Providing & fixing 100 mm dia dial pressure gauge including making connections with MS pipe complete in all respects. Total in Figures 3240847.0 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 S.No. SSR-2020/DSR -2025/ NS Description QTY Unit Rate Amount |
| 1026 | Supplying, installing, testing and commissioning of aircooled variable refrigerant volume / Flow modular type airconditioning system with R410a refrigerant. The PCB Chamber of outdoor unit should be refrigerant cooled suitable for 415±10% 3 Phase, 50 cycles. The unit shall consist of indoor and out door units with individual controller as per detail given in specifications and having following items : (These items are to be given in Indian rupees with custom duites, inland frt,clearance etc on Site basis) Modular type outdoor units equipped with highly efficient 100% inverter type hermitically sealed scroll compressors, minimum two comprossors for and above 14 HP modules, with special precoated heat exchanger, low noise condenser fan housed in compact housing duly powder coated and manufacturer of compressor and outdoor unit should be same. The Unit should have automatic refrigerant charge function. The static pressure of the outdoor unit shall be more then 78 Pa to avoid hot air recirculation. The unit shall be able to operate upto to 45°C in cooling mode.The unit shall also have feature to automatically modulate the evaporative temperature between 6 deg C to 11 deg C with respect to load for better comfort and energy efficiency etc complete as reqd. The units should have free phase technology for countinued operation. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping .The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 of following capacitites: Cost of R 410 A Gas should be inclusive The outdoor unit should include all loading, unloading, transportation, power cabling/wiring from near the indoor and outdoor units respectively. The outdoor unit should include all loading, unloading, transportation, power cabling/wiring,( Y/T joints which is required for ODU Zone requirement Modules) from near the indoor and outdoor units respectively. Outdoor Units-Heat Pump , Fully Gas Charged and Aluminum fins within the ODU (condensing) unit shall be coated with polysiloxane based coating. The Vendor should considere the deration on ODU election as per Manesar Ambient conditions a 1.29378472222222 30 HP Outdoor unit VRV/VRF Zone-01 1.0 No. 597270.8904 597270.8904 b 1.29378472222222 16 HP Outdoor unit VRV/VRF Zone-02 1.0 No. 318544.4749 318544.4749 |
| 1027 | Supply, installation, testing and commissioning of following Wall Mounted /Cassette type units with panel and inbuilt drain pump/slim Ceiling Mounted duct type/Ceiling Mounted Built in type/Ceiling Mounted Ductable type units VRF Air Conditioners with cordless/corded remote controller.Fully Factory assembled,wired and tested Indoor Units as per specifications ans as required to make the system complete. Aluminum fins within the IDU (evaporator unit) shall be oxycoat (Epoxy coating followed by oxycoat (PU /Polysiloxine) coating, The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. |
| 1028 | a 1.29795138888889 300-320 CFM / 0.8 TR R.O No. 28682.82756 1.29796296296296 320-335 CFM / 1.0-102 TR R.O No. 29079.9235 b 1.29862268518519 525-560 CFM / 1.25-1.30 TR 1.0 No. 31561.77308 31561.77308 c 1.29863425925926 565-635 CFM / 1.5-1.60 TR 1.0 No. 32156.49778 32156.49778 d 1.29864583333333 650-740 CFM / 1.7-2.0 TR R.O No. 33149.23761 e 1.29865740740741 875-883 CFM / 2.4-2.50 TR 5.0 No. 34638.34736 173191.7368 f 1.29866898148148 1130 -1150 CFM / 3.0-3.20 TR R.O No. 36920.72977 g 1.29939814814815 1200-1377 CFM / 3.95-4.0 TR R.O No. 42280.60567 h 1.29940972222222 1600-2050 CFM / 4.5-4.6 TR R.O No. 59351.13479 i 1.30001157407407 1600-2050 CFM / 5.5 TR R.O No. 68383.22887 j 1.30002314814815 2047-2295 CFM / 6.36 TR R.O No. 71757.6251 k 1.30003472222222 2542-2825 CFM / 8.0-8.02 TR R.O No. 78307.8696 |
| 1029 | a 1.29515046296296 300-310 CFM / 0.6-0.63 TR R.O No. 20783.19226 b 1.29516203703704 310-320 CFM / 0.8 TR R.O No. 23092.23157 c 1.29517361111111 335-350 CFM / 1.0 TR R.O No. 36225.81189 d 1.29518518518519 400-410 CFM / 1.2-1.30 TR R.O No. 36722.18181 Ceiling Mounted Cassette Unit 1.29445601851852 450-460CFM / 0.8 TR R.O No. 20501.91597 1.29446759259259 450-460CFM /1.0 TR 4.0 No. 25627.39496 102509.5799 c 1.29447916666667 600-670 CFM / 1.2-1.3 TR 6.0 No. 35482.17622 212893.0573 d 1.29449074074074 812-830 CFM / 1.6 TR 6.0 No. 36275.44888 217652.6933 e 1.29450231481481 812-830 CFM / 2.0 TR R.O No. 36523.63384 f 1.29451388888889 850-865 CFM / 2.4 TR R.O No. 37516.37367 g 1.29452546296296 850-865 CFM / 2.6 TR R.O No. 37516.37367 h 1.29453703703704 1130-1165 CFM / 3.2-3.6 TR R.O No. 40692.22194 i 1.29454861111111 1200-1220 CFM / 4.0-4.1 TR R.O No. 42082.05771 |
| 1030 | a 1.2972337962963 250-270 CFM / 0.6-0.63 TR R.O No. 15433.4276 b 1.29724537037037 250-270 CFM / 0.8-0.8 TR R.O No. 15880.16052 |
| 1031 | NS Supply, installation, tesing and commissioning of Imported Remote controllers (Corded) for operation of Cassette/Ductable indoor units and AHU's. 23.0 Nos 4840.0 111320.0 |
| 1032 | NS Supply, installation, testing and commissioning of touch screen controller (Which is controlled 30 nos. indoor units in terms of ON/Off Status, temp. Status, Fan Speed, ODU On/Off Status etc.) with all accessories and controls. 1.0 Nos 90750.0 90750.0 |
| 1033 | NS Supply, installation, tesing and commissioning of Imported fittings Y-joints insulated, distributer and headers for all Indoor units at both the ends floors layout as per layout drawings.All interconnecting joints, Y Joints with polysiloxane based coating 25.0 Nos 5082.0 127050.0 |
| 1034 | Supply, installation, testing and commissioning of Interconnecting refrigerant pipe work with (13/ 19mm thick) cross linked closed cell Oxide Acetate Foam tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with hangers and All interconnecting Copper piping, joints, U bends with oxycoat dual barrier coating shall run in cable tray. (Note: Ref. Piping Length may be review as per site routing) a 1.30140046296296 06.35 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 90.0 RM 235.3161087 21178.44978 b 1.30141203703704 09.5 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 50.0 RM 318.0444282 15902.22141 c 1.30142361111111 12.70 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 170.0 RM 447.6521287 76100.86187 d 1.30143518518519 15.86 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 80.0 RM 565.310183 45224.8146399999 e 1.30144675925926 19 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 65.0 RM 679.2914232 44153.94251 f 1.30145833333333 22.2 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 40.0 RM 830.9600089 33238.40035 g 1.30146990740741 25.4 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 20.0 RM 981.709391 19634.18782 h 1.30148148148148 28.58 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 40.0 RM 1063.518507 42540.74028 i 1.30149305555556 31.8 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 5.0 RM 1123.266738 5616.333688 j 1.30150462962963 34.9 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 15.0 RM 1182.095765 17731.43647 k 1.3015162037037 38.1 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation R.O RM 1215.187093 l 1.30152777777778 41.27 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation R.O RM 1257.470456 |
| 1035 | NS Supply, installation, testing, termination and commissioning of control cum transimission wiring (should be shielded cable in PVC Pipe) of 2C x 1.5 Sqmm Cu between indoor unit and out door unit and indoor units and its remote controller. a 2C x 1.5 Sqmm Cu Cable or as per Manufacturer OEM 400.0 RM 273.0 109200.0 b Perforated GI Tray with hangers & supports for copper piping (300 mm wide) 80.0 RM 1029.0 82320.0 c Perforated GI Tray with hangers & supports for copper piping (450 mm wide) 40.0 RM 1271.0 50840.0 |
| 1036 | NS Supply , charging & Leackage testing of refrigerant -410a in additional copper piping circuit. 18.0 Kgs. 1210.0 21780.0 |
| 1037 | Providing and fixing of Air Cooled Split airconditioners each comprising an outdoor unit consisting of hermetic Invertor scroll compressor, air cooled condensing unit, Condenser fan etc. with outer casing and indoor fan coil unit(s) consisting of centrifugal fans, fan motor, DX cooling coil, outer casing, filter, control and power panel with corded/cordless remote control, stablizer etc. both inter connected with copper refrigerant pipe (Compressor capable Approx. 30-40 mtr. copper piping) and drain pipe of required length as given, cabling and wiring, insulation with cross linked polyethelene foam, full charge of refrigerant gas and oil, M.S. base frame, supports etc. complete as per specifications and drawings. The cost shall also include angle iron stands for outdoor units . If A common Servo oil type stablizer than not required stablizer. a 1.33476851851852 2.0 TR Hi-wall Unit with ref.circuit and approx 30-40 meter of ref.and drain piping & Cabling with sequencing controller (15 Working + 15 Standby) as per specifications & Drawing, For Server Room R.O Nos. 52758.60693 |
| 1038 | a NS - 5KVA R.O Nos. 4538.0 |
| 1039 | a NS 3Cx2.5 Sqmm. R.O Rmt 296.0 |
| 1040 | Supplying, fixing,testing and commissioning of following PVC pipes for condensate drain duly insulated with Fire rated Class O kinny foam /Nitrile Rubber & vapour barrier duly secured with adhesive tape as per specification ,cut to required length and installed with all joints , including the necessary fittings. (For all the AHU/FCU units upto the main header in the shaft dor vertical risers) a 65mm dia 10.0 RM 700.0 7000.0 b 50mm dia 10.0 RM 538.0 5380.0 c 40mm dia 30.0 RM 406.0 12180.0 d 30mm dia 50.0 RM 325.0 16250.0 e 25 mm dia 60.0 RM 263.0 15780.0 |
| 1041 | Supply,installation,testing and commissioning of Propeller fan of the following capacity of approved make and specification. Fan shall be supplied with aluminum gravity louver & bird screen and Speed Regulator. a NS 200 mm dia propeller fan, with single phase motor R.O No. 4533.0 b NS 300 mm dia propeller fan, with single phase motor R.O No. 5633.0 c NS 450 mm dia propeller fan , with single phase motor 10.0 No. 6281.0 62810.0 |
| 1042 | Supply, installation, testing and commissioning of Circular/Rectangular swing type Inline fan with fiire retardent Canvas connection Speed Regulator of the following capacity of approved make and specification. a NS 50-300 CFM, 5-7 mm SP WG with Single phase motor 1.0 No. 8418.0 8418.0 b NS 350-500 CFM, 7-10 mm SP WG with Single phase motor 1.0 No. 14893.0 14893.0 c NS 550-800 CFM, 10-12 mm SP WG with Single phase motor R.O No. 21368.0 NS 850-1000 CFM, 10-12 mm SP WG with Single phase motor R.O No. 25253.0 |
| 1043 | SITC of Long case Tube axial flow fans, as per specifications and approved makes suitable for three phase operation respectively Normal/Smoke case. |
| 1044 | a 7000 CFM (For Liftwell/Liftlobby Pressurization) R.O No. 80938.0 b 12500 CFM (For Liftwell/Liftlobby Pressurization) R.O No. 110075.0 |
| 1045 | a 3000 CFM For Smoke extract R.O No. 45973.0 b 5000-5500 CFM For Normal & Smoke extract R.O No. 62808.0 c 12000 CFM For Normal & Smoke extract R.O No. 114608.0 |
| 1046 | Supply of following HVAC dedicated VFDs with IP 55 enclosures with Mains disconnect, complying with the tender specifications and having: 1. built-in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the VFD. 2. built-in EMC Filters (electromagnetic compatibility filters) for for VFDs for restriction of conducted emissions to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 2, 3. Three-feedback PID controller having capability to simultaneously accept 3 feedback signals from temperature sensors or pressure sensors or CO2 sensors for process optimization and accordingly regulate the speed of the AHUs or pumps. 4. Provision for additional 3 PID controllers to control external devices such as chilled water modulating valve, fresh air damper, etc. thus reducing the number of I/Os in DDC Controllers & improving system reliability. 5. Automatic Energy Optimization / Load dependent flux optimization functionality for maximum energy savings. 6. MODBUS RTU as the communication protocol between BMS & VFDs. 7. VFDs not meeting above requirements shall provide external disconnect, external harmonic filters, additional external EMC Filters to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 1 (50 m), external PLCs / DDCs to achieve 3 Feedback PID Controller functionality and external devices controlling capabilities. a NS Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for for 4-5.5 kW motor rating as per the specifications(3 Phase variable frequency output for Exh. Fan, . These variable speed drives shall get the input from the remote air differential pressure adjuster , as described above in item. R.O No. 55038.0 b NS Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for for 11.0 kW motor rating as per the specifications(3 Phase variable frequency output for TFA Fan/ AHU . These variable speed drives shall get the input from the remote air differential pressure adjuster , as described above in item. R.O No. 148925.0 c NS Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for for1.1-2.2 kW motor rating as per the specifications(3 Phase variable frequency output for Scrubber Exh.Fan/AHU , . These variable speed drives shall get the input from the remote air differential pressure adjuster , as described above in item. R.O No. 80938.0 |
| 1047 | Supply,installation testing and commissioning of AIR CURTAIN of following size as per approved make With Speed regulator and Door limit switch/sensor .(At entrance) a SSR-22007 1100 mm long (High flow type) R.O No. 61237.23 b SSR-22007 1800 mm long (High flow type) R.O No. 66680.53 c SSR-22007 1600 mm long (High flow type) R.O No. 74845.5 |
| 1048 | a Up to 4500 CFM, 21 Watt R.O No. 99225.0 b 6500 to 8000 CFM, 36 Watt R.O No. 132300.0 c 9000 to 16000 CFM, 54 Watt R.O No. 182700.0 d 300 to 1200 CFM, For IDU Duct Mount R.O No. 40950.0 UVGI units for AHU OR |
| 1049 | a Up to 4000 CFM, 21 Watt b 4500 to 7000 CFM, 36 Watt c 300 to 1200 CFM, For IDU Duct Mount |
| 1050 | Supply,Installation,balancing and commissioning of fabricated at site GSS sheet metal ducts (rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter,vanes, hangers, supports etc.) in accordance with the approved shop drawings and specifications , and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to suit pieces. (May Be existing Duct Reuse partially) a 30.12.2.1 0.63mm (24 gauge) GSS 30.0 SqM 1114.993906 33449.81717 b 30.12.2.2 0.8 mm (22 gauge) GSS 5.0 SqM 1300.673023 6503.365114 c 30.12.2.3 1.0mm (20 gauge) GSS R.O SqM 1701.44577 d 30.12.2.4 1.25mm (18 gauge) GSS R.O SqM 1896.316923 |
| 1051 | Supply,Installation,balancing and commissioning of factory fabricated GSS sheet metal ducts (rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter,vanes, hangers, supportsetc.) in accordance with the approved shop drawings and specifications , and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to suit pieces. (May Be existing Duct Reuse partially) a 30.12.1.1 0.63mm (24 gauge) GSS 100.0 SqM 1094.771428 109477.1428 b 30.12.1.2 0.8 mm (22 gauge) GSS R.O SqM 1270.339306 c 30.12.1.3 1.0mm (20 gauge) GSS R.O SqM 1367.774882 d 30.12.1.4 1.25mm (18 gauge) GSS R.O SqM 1850.356745 |
| 1052 | a NS 250 mm Dia. 2.0 RM 1053.0 2106.0 |
| 1053 | Supplying and fixing of Extruded aluminium supply and return air grilles/diffusers/louvres with dampers, supply air plenum etc. duly powder coated as per specifications and drawings. a 30.15 Aluminium supply air grilles with damper. 1.5 Sqm. 8845.495758 13268.24364 b 13.16 Aluminium return/Exh. air grilles without damper. 1.5 Sqm. 5777.194309 8665.791464 c 30.17 Aluminium supply air square diffuser with damper R.O Sqm. 11803.49278 d 30.18 Aluminium return/exhaust air square diffuser without damper. R.O Sqm. 7900.554509 e NS Aluminium return/exhaust air Valve circular/squirell diffuser without damper. 1.0 Sqm. 8100.0 8100.0 f NS Linear air grilles (150 MM wide) R.O RM 1098.0 g NS Aluminium supply air collar damper R.O Sqm. 4500.0 h NS Jet Diffusers (315mm Dia.) R.O Nos. 7440.0 i NS AI Volume control dampers for ducts R.O Sqm. 4500.0 j NS 2-Slot linear air diffusers R.O RM 2538.0 k NS 3-Slot linear air diffusers R.O RM 2940.0 |
| 1054 | Supplying and fixing of extruded aluminium louvres with frame bird screeen , mounting arrangement etc. as per specifications and drawings. a Fresh Air/Exhaust Louvers 1.0 Sqm. 8700.0 8700.0 |
| 1055 | NS Spcl. Note: In Air Distribution Works Smoke extract Duct should be fire rated for 2 hrs. So Vendor give their quoate accordingly. |
| 1056 | Supply and installation of cross linked open cell Oxide Acetate ( Acco Isolate) Foam/Open Cell Nitrile Rubber Acoustic insulation on ducts having density of 30 to 60 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 15mm thick Oxice Acetate Acco Isolate/Nitrile rubber accosound Acoustic open cell insulation on one side for Duct acoustic insulation 25.0 Sqm 1320.0 33000.0 |
| 1057 | Supply and installation of cross linked closed cell Oxide Acetate ( Thermo Isolate) Foam/Nitrile Rubber Thermal insulation on ducts having density 0f 30 ±3 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 25 mm thick insulation oxide acetate foam/Nitrile Rubber laminated with two layer canvas with starbond adhesive supply air duct R.O SqM 750.0 b NS 13 mm thick insulation oxide acetate foam/Nitrile Rubber laminated with aluminium foil supply air duct 80.0 SqM 630.0 50400.0 c NS 9mm thick insulation oxide acetate foam/ Nitrile Rubber laminated with aluminium foil supply air duct 20.0 SqM 468.0 9360.0 |
| 1058 | Supply and installation of cross linked open cell Oxide Acetate ( Acco Isolate) Foam/Open Cell Nitrile Rubber Acoustic insulation on ducts having density of 30 to 60 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 25mm thick Oxice Acetate Acco Isolate//Nitrile rubber accosound Acoustic open cell insulation on one side for AHU Room acoustic insulation R.O SqM 1620.0 |
| 1059 | Supply and installation of cross linked closed cell Oxide Acetate ( Thermo Isolate) Foam/Nitrile Rubber Thermal insulation on ducts having density 0f 30 ±3 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 19mm thick oxide acetate insulation for underceck plain R.O SqM 1152.0 |
| 1060 | The rates for the distribution boards from the Breakers and instruments shall also include the following : A Wiring for light / Fan points with 1.5 sq. mm PVC insulated copper conductor 1100 Volt grade stranded flexible FRLS wires of approved make in 1.6 mm thick 25 mm dia MS conduit including cost of providing & fixing saddles, hangers, supports, cutting chases and filling chases for recessed conduiting, and including the cost of providing and fixing a 6 amp 240 Volt Modular Plate type switches of approved quality, colour, make and design with moulded cover plate in zinc chromate passivated MS box and including the cost of running 1.5 sq. mm PVC insulated copper earth wire for loop earthing etc. complete B TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate size of neutral link. C All MCB’s shall be of minimum 10 KA breaking capacity and MCCB 's shall be not lessthan 25KA D The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermal magnetic microprocessor releases as per BOQ and following : i. MCCB rating upto 250 Amps with thermal magnetic releases. ii. MCCB above 250 Amps with microprocessor releases. E All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic. F Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993. i. IP 42 for indoor panels. ii. IP 55 for ODU panel. G All MCCB’s shall be provided with operating mechanism for door interlock. H All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire. I Providing cable clamps / supports within distribution boards cable alley. J Current density of aluminium shall be 1sq mm for 1.0 Amps for rated current of bus bars. K Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirment. L All meter shall be digital type and all starter shall be as per Type-2 Coordination chart M Current Transfomer shall be resin cast. N All Panel Shall be BMS Compitable |
| 1061 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of following LT panels fabricated out of 14 guage CRCA sheet steel in cubical formationwith reinforecment of suitable size angle iron and channel T iron flats. All steel material used in the construction of panels shall be powder coated. A solid busbar shall be provided at the bottom of the panel with two connecting eyes for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase , 4 wire supply system. All the hardware used in the fabrication of the panel shall be galvanized with zinc passivation. The panel shall be compartmentalized to accommodate one feeder in each compartment. A vertcal cable alley of suitable width shall be provided to serve on or two vertical feeder sections. Also the opening between the busbar chamber and the feeder section shall be shrouded with bakelite / hylam sheet with min.3 mm thickness. The panel drawing shall be approved before taking up the fabrication and compitable BMS if in future required. In All panel Each starter should have remote control and interlocking facilities including auto manual switch, NO/NC contacts for control and must have auto manual operation suitable to take signal from fire alarm panel for automatic operation of fan in case of fire. All smoke /vent. fan panel the starters shall have suitable facility to operate with fire sensing control modules. |
| 1062 | Supplying, Installation, Testing and Commissioning of dust, damp and vermin proof free floor standing / wall mounted factory built sheet steel enclosed modular construction extendable panel, suitable for operation on 415 + 10% volts, 50 Hz AC 3 phase 4 wire system fabricated out of suitable sized square tubular section and covered with 2.0mm thick CRCA sheet, hinged doors of 2mm thick CRCA sheet, duly painted complete with aluminium bus bars, interconnection with solid copper conductor wires / aluminium strips, neutral links, earth bus etc. necessary metering protections & indications and mounted with the following as per drawing and technical specifications attached etc. complete as required. a ODU's Panel-01-TERRHVAC Same as above item but outdoor Panel with following accessories. INCOMING: 1 No. 100 amps, 415V TPN MCCB with overcurrent and short circuit releases, all indication, push button etc. Coloured (Red, Yellow, Blue) phase indicating lamp - 1 set (0 - 100 A) CT operated Ammeter with selector switch & 3 nos. CTs ratio 100/5A , 15VA burden & accuracy class of 1.0 - 1 set 0-500 V Voltmeter with selector switch - 1 set BUSBAR: 125 Amp. TPN, 35 kA Al. Bus Bar OUTGOINGS: 80A, TPN ELCB with 300mA -3 Nos. (Incl. 1No. Spare) 40A, TPN ELCB with 300mA - 2 Nos. (Incl. 1No. Spare) ODU Panel Described as above/As per Manufacturer ODU Configuration. 1.0 Set 114950.0 114950.0 Spcl. Note : All Above mentioned panel SITC as per actual GA dwgs. equipments and final config,. Of ODU's. |
| 1063 | Power Cabling and Earthing: Spcl. All Cables Should be FRLS Cables Sch. Chapter 20.1 Supply, installation, testing & commisioning of Aluminum conductor cables Fire survival cables of 1.1 KV grade with termination glands and identification tags, clamps and saddles etc. FRLS Type 20a.1.20 3.5Cx400 Sqmm R.O Rmt 3103.231184 a NS 3.5Cx300 Sqmm R.O Rmt 2181.0 b 20a.1.18 3.5Cx240 Sqmm R.O Rmt 2136.229049 c 20a.1.17 3.5Cx185 Sqmm R.O Rmt 1710.637806 d 20a.1.10 3.5Cx25 Sqmm R.O Rmt 602.9975286 e 20a.1.14 3.5Cx95 Sqmm R.O Rmt 1091.094613 f 20a.1.12 3.5Cx50 Sqmm R.O Rmt 791.4342562 g NS 3Cx50 Sqmm R.O Rmt 551.0 h NS 3Cx35 Sqmm R.O Rmt 456.0 i NS 3Cx25 Sqmm R.O Rmt 393.0 j NS 3Cx16 Sqmm R.O Rmt 329.0 k NS 3Cx10 Sqmm R.O Rmt 313.0 l NS 3Cx 06 Sqmm R.O Rmt 278.0 m NS 3Cx04 Sqmm R.O Rmt 218.0 n NS 2Cx04 Sqmm (Cu Conductor) R.O Rmt 206.0 o 20a.1.2 2Cx10 Sqmm R.O Rmt 494.5315097 p NS 4Cx 10 Sqmm Cu 40.0 Rmt 920.0 36800.0 q NS 4Cx 06 Sqmm Cu 20.0 Rmt 603.0 12060.0 r 20a.1.9 4Cx 16 Sqmm R.O Rmt 568.0677937 |
| 1064 | Supply, installation, testing & commisioning of Copper conductor , PVC insulated, Fire survival cable of 1.1 KV grade (Which is Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers and AHU to Panel). a NS 5C x 1.5 Sqmm 30.0 RM 234.0 7020.0 |
| 1065 | a 0.376053240740741 3.5Cx400 Sqmm R.O Set 1430.280723 b 0.376041666666667 3.5Cx300 Sqmm R.O Set 1098.448242 c 0.376030092592593 3.5Cx240 Sqmm R.O Set 944.0220455 d 0.376006944444444 3.5Cx185 Sqmm R.O Set 804.3031059 e 0.375925925925926 3.5Cx25 Sqmm R.O Set 287.710711 f 0.375972222222222 3.5Cx95 Sqmm R.O Set 540.4916872 g 0.375949074074074 3.5Cx50 Sqmm R.O Set 379.631066 h 0.375821759259259 3Cx50 Sqmm R.O Set 342.862924 i 0.375810185185185 3Cx35 Sqmm R.O Set 322.6404459 j 0.375798611111111 3Cx25 Sqmm R.O Set 252.7809761 k 0.375787037037037 3Cx16 Sqmm R.O Set 248.1849584 l 0.375775462962963 3Cx10 Sqmm R.O Set 236.2353123 m 0.375775462962963 3Cx 06 Sqmm R.O Set 236.2353123 n 0.375775462962963 3Cx04 Sqmm R.O Set 236.2353123 o 0.375706018518519 2Cx04 Sqmm (Cu Conductor) R.O Set 220.6088519 p 0.375775462962963 2Cx10 Sqmm R.O Set 236.2353123 q 0.376064814814815 4Cx 10 Sqmm Cu 4.0 Set 247.2657549 989.0630194 r 0.376064814814815 4Cx 06 Sqmm Cu 2.0 Set 246.3465513 492.6931026 s 0.376076388888889 4Cx 16 Sqmm R.O Set 284.0338968 |
| 1066 | a 0.170844907407407 100 mm. Width x 50mm. Depth x 1.6mm. Thickness. 15.0 Rmt 614.9471747 9224.207621 b 0.170856481481481 150 mm. Width x 50mm. Depth x 1.6mm. Thickness. 15.0 Rmt 658.1497415 9872.246123 c 0.170868055555556 225 mm. Width x 50mm. Depth x 1.6mm. Thickness. R.O Rmt 822.6871769 d 0.17087962962963 300 mm. Width x 50mm. Depth x 1.6mm. Thickness. R.O Rmt 885.1930183 e 0.170902777777778 450 mm. Width x 50mm. Depth x 1.6mm. Thickness. R.O Rmt 1114.993906 |
| 1067 | a 5.12 6 SWG G.I. wire 30.0 Rmt 263.8114187 7914.342562 Total in Figures (HVAC Electrical Works) 3225426.004894 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 S.No. SSR-2020/DSR -2025/ NS Description Actual Qty. Unit Rate Amount |
| 1068 | Supplying, installing, testing and commissioning of aircooled variable refrigerant volume / Flow modular type airconditioning system with R410a refrigerant. The PCB Chamber of outdoor unit should be refrigerant cooled suitable for 415±10% 3 Phase, 50 cycles. The unit shall consist of indoor and out door units with individual controller as per detail given in specifications and having following items : (These items are to be given in Indian rupees with custom duites, inland frt,clearance etc on Site basis) Modular type outdoor units equipped with highly efficient 100% inverter type hermitically sealed scroll compressors, minimum two comprossors for and above 14 HP modules, with special precoated heat exchanger, low noise condenser fan housed in compact housing duly powder coated and manufacturer of compressor and outdoor unit should be same. The Unit should have automatic refrigerant charge function. The static pressure of the outdoor unit shall be more then 78 Pa to avoid hot air recirculation. The unit shall be able to operate upto to 45°C in cooling mode.The unit shall also have feature to automatically modulate the evaporative temperature between 6 deg C to 11 deg C with respect to load for better comfort and energy efficiency etc complete as reqd. The units should have free phase technology for countinued operation. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping .The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 of following capacitites: Cost of R 410 A Gas should be inclusive The outdoor unit should include all loading, unloading, transportation, power cabling/wiring from near the indoor and outdoor units respectively. The outdoor unit should include all loading, unloading, transportation, power cabling/wiring,( Y/T joints which is required for ODU Zone requirement Modules) from near the indoor and outdoor units respectively. Outdoor Units-Heat Pump , Fully Gas Charged and Aluminum fins within the ODU (condensing) unit shall be coated with polysiloxane based coating. The Vendor should considere the deration on ODU election as per Manesar Ambient conditions a 1.29378472222222 40 HP Outdoor unit VRV/VRF Zone-01 1.0 No. 517634.77 517634.77 b 1.29378472222222 54 HP Outdoor unit VRV/VRF Zone-02 1.0 No. 318544.47 318544.47 c 1.29378472222222 58 HP Outdoor unit VRV/VRF Zone-03,04 2.0 No. 557452.83 1114905.66 |
| 1069 | Supply, installation, testing and commissioning of following Wall Mounted /Cassette type units with panel and inbuilt drain pump/slim Ceiling Mounted duct type/Ceiling Mounted Built in type/Ceiling Mounted Ductable type units VRF Air Conditioners with cordless/corded remote controller.Fully Factory assembled,wired and tested Indoor Units as per specifications ans as required to make the system complete. Aluminum fins within the IDU (evaporator unit) shall be oxycoat (Epoxy coating followed by oxycoat (PU /Polysiloxine) coating, The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. |
| 1070 | a 1.29795138888889 300-320 CFM / 0.8 TR R.O No. 28682.83 1.29796296296296 320-335 CFM / 1.0-102 TR R.O No. 29079.92 b 1.29862268518519 525-560 CFM / 1.25-1.30 TR R.O No. 31561.77 c 1.29863425925926 565-635 CFM / 1.5-1.60 TR R.O No. 32156.5 d 1.29864583333333 650-740 CFM / 1.7-2.0 TR R.O No. 33149.24 e 1.29865740740741 875-883 CFM / 2.4-2.50 TR R.O No. 34638.35 f 1.29866898148148 1130 -1150 CFM / 3.0-3.20 TR R.O No. 36920.73 g 1.29939814814815 1200-1377 CFM / 3.95-4.0 TR R.O No. 42280.61 h 1.29940972222222 1600-2050 CFM / 4.5-4.6 TR R.O No. 59351.13 i 1.30001157407407 1600-2050 CFM / 5.5 TR R.O No. 68383.23 j 1.30002314814815 2047-2295 CFM / 6.36 TR R.O No. 71757.63 k 1.30003472222222 2542-2825 CFM / 8.0-8.02 TR 2.0 No. 78307.87 156615.74 |
| 1071 | a 1.29515046296296 300-310 CFM / 0.6-0.63 TR 7.0 No. 20783.19 145482.35 b 1.29516203703704 310-320 CFM / 0.8 TR R.O No. 23092.23 c 1.29517361111111 335-350 CFM / 1.0 TR R.O No. 36225.81 d 1.29518518518519 400-410 CFM / 1.2-1.30 TR R.O No. 36722.18 Ceiling Mounted Cassette Unit 1.29445601851852 450-460CFM / 0.8 TR R.O No. 20501.92 1.29446759259259 450-460CFM /1.0 TR 17.0 No. 25627.39 435665.71 c 1.29447916666667 600-670 CFM / 1.2-1.3 TR 37.0 No. 35482.18 1312840.52 d 1.29449074074074 812-830 CFM / 1.6 TR 9.0 No. 36275.45 326479.04 e 1.29450231481481 812-830 CFM / 2.0 TR 34.0 No. 36523.63 1241803.55 f 1.29451388888889 850-865 CFM / 2.4 TR R.O No. 37516.37 g 1.29452546296296 850-865 CFM / 2.6 TR 1.0 No. 37516.37 37516.37 h 1.29453703703704 1130-1165 CFM / 3.2-3.6 TR 2.0 No. 40692.22 81384.44 i 1.29454861111111 1200-1220 CFM / 4.0-4.1 TR R.O No. 42082.06 |
| 1072 | a 1.2972337962963 250-270 CFM / 0.6-0.63 TR R.O No. 15433.43 b 1.29724537037037 250-270 CFM / 0.8-0.8 TR R.O No. 15880.16 |
| 1073 | NS Supply, installation, tesing and commissioning of Imported Remote controllers (Corded) for operation of Cassette/Ductable indoor units and AHU's. 109.0 Nos 4840.0 527560.0 |
| 1074 | NS Supply, installation, testing and commissioning of touch screen controller (Which is controlled 110 nos. indoor units in terms of ON/Off Status, temp. Status, Fan Speed, ODU On/Off Status etc.) with all accessories and controls. 1.0 Nos 114950.0 114950.0 |
| 1075 | NS Supply, installation, tesing and commissioning of Imported fittings Y-joints insulated, distributer and headers for all Indoor units at both the ends floors layout as per layout drawings.All interconnecting joints, Y Joints with polysiloxane based coating 105.0 Nos 5082.0 533610.0 |
| 1076 | Supply, installation, testing and commissioning of Interconnecting refrigerant pipe work with (13/ 19mm thick) cross linked closed cell Oxide Acetate Foam tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with hangers and All interconnecting Copper piping, joints, U bends with oxycoat dual barrier coating shall run in cable tray. (Note: Ref. Piping Length may be review as per site routing) a 1.30140046296296 06.35 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 300.0 RM 25.44 7630.83 b 1.30141203703704 09.5 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 250.0 RM 318.04 79511.11 c 1.30142361111111 12.70 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 400.0 RM 447.65 179060.85 d 1.30143518518519 15.86 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 325.0 RM 565.31 183725.81 e 1.30144675925926 19 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 330.0 RM 679.29 224166.17 f 1.30145833333333 22.2 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 100.0 RM 830.96 83096.0 g 1.30146990740741 25.4 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 60.0 RM 981.71 58902.56 h 1.30148148148148 28.58 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 60.0 RM 1063.52 63811.11 i 1.30149305555556 31.8 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 30.0 RM 1123.27 33698.0 j 1.30150462962963 34.9 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 20.0 RM 1182.1 23641.92 k 1.3015162037037 38.1 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 20.0 RM 1215.19 24303.74 l 1.30152777777778 41.27 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 120.0 RM 1257.47 150896.45 |
| 1077 | NS Supply, installation, testing, termination and commissioning of control cum transimission wiring (should be shielded cable in PVC Pipe) of 2C x 1.5 Sqmm Cu between indoor unit and out door unit and indoor units and its remote controller. a 2C x 1.5 Sqmm Cu Cable or as per Manufacturer OEM 1450.0 RM 273.0 395850.0 b Perforated GI Tray with hangers & supports for copper piping (300 mm wide) 250.0 RM 1029.0 257250.0 c Perforated GI Tray with hangers & supports for copper piping (450 mm wide) 120.0 RM 1271.0 152520.0 |
| 1078 | NS Supply , charging & Leackage testing of refrigerant -410a in additional copper piping circuit. 80.0 Kgs. 1210.0 96800.0 |
| 1079 | Providing and fixing of Air Cooled Split airconditioners each comprising an outdoor unit consisting of hermetic Invertor scroll compressor, air cooled condensing unit, Condenser fan etc. with outer casing and indoor fan coil unit(s) consisting of centrifugal fans, fan motor, DX cooling coil, outer casing, filter, control and power panel with corded/cordless remote control, stablizer etc. both inter connected with copper refrigerant pipe (Compressor capable Approx. 30-40 mtr. copper piping) and drain pipe of required length as given, cabling and wiring, insulation with cross linked polyethelene foam, full charge of refrigerant gas and oil, M.S. base frame, supports etc. complete as per specifications and drawings. The cost shall also include angle iron stands for outdoor units . If A common Servo oil type stablizer than not required stablizer. a 1.33476851851852 2.0 TR Hi-wall Unit with ref.circuit and approx 30-40 meter of ref.and drain piping & Cabling with sequencing controller (15 Working + 15 Standby) as per specifications & Drawing, For Server Room R.O Nos. 52758.61 |
| 1080 | a NS - 5KVA R.O Nos. 4538.0 |
| 1081 | a NS 3Cx2.5 Sqmm. R.O Rmt 296.0 |
| 1082 | Supplying, fixing,testing and commissioning of following PVC pipes for condensate drain duly insulated with Fire rated Class O kinny foam /Nitrile Rubber & vapour barrier duly secured with adhesive tape as per specification ,cut to required length and installed with all joints , including the necessary fittings. (For all the AHU/FCU units upto the main header in the shaft dor vertical risers) a 65mm dia 50.0 RM 700.0 35000.0 b 50mm dia 60.0 RM 538.0 32280.0 c 40mm dia 100.0 RM 406.0 40600.0 d 30mm dia 150.0 RM 325.0 48750.0 e 25 mm dia 500.0 RM 263.0 131500.0 |
| 1083 | Supply,installation,testing and commissioning of Propeller fan of the following capacity of approved make and specification. Fan shall be supplied with aluminum gravity louver & bird screen and Speed Regulator. a NS 200 mm dia propeller fan, with single phase motor R.O No. 4533.0 b NS 300 mm dia propeller fan, with single phase motor R.O No. 5633.0 c NS 450 mm dia propeller fan , with single phase motor 3.0 No. 6281.0 18843.0 |
| 1084 | Supply, installation, testing and commissioning of Circular/Rectangular swing type Inline fan with fiire retardent Canvas connection Speed Regulator of the following capacity of approved make and specification. a NS 50-300 CFM, 5-7 mm SP WG with Single phase motor 1.0 No. 8418.0 8418.0 b NS 350-500 CFM, 7-10 mm SP WG with Single phase motor 4.0 No. 14893.0 59572.0 c NS 550-800 CFM, 10-12 mm SP WG with Single phase motor 2.0 No. 21368.0 42736.0 NS 850-1000 CFM, 10-12 mm SP WG with Single phase motor 1.0 No. 25253.0 25253.0 |
| 1085 | SITC of Long case Tube axial flow fans, as per specifications and approved makes suitable for three phase operation respectively Normal/Smoke case. |
| 1086 | a 7000 CFM (For Liftwell/Liftlobby Pressurization) R.O No. 80938.0 b 12500 CFM (For Liftwell/Liftlobby Pressurization) R.O No. 110075.0 |
| 1087 | a 2000-3500 CFM For Normal & Smoke extract 7.0 No. 45973.0 321811.0 b 5000-5500 CFM For Normal & Smoke extract 2.0 No. 62808.0 125616.0 c 7000-7500 CFM For Normal & Smoke extract 4.0 No. 67988.0 271952.0 d 11500-12000 CFM For Normal & Smoke extract 4.0 No. 114608.0 458432.0 |
| 1088 | Supply of following HVAC dedicated VFDs with IP 55 enclosures with Mains disconnect, complying with the tender specifications and having: 1. built-in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the VFD. 2. built-in EMC Filters (electromagnetic compatibility filters) for for VFDs for restriction of conducted emissions to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 2, 3. Three-feedback PID controller having capability to simultaneously accept 3 feedback signals from temperature sensors or pressure sensors or CO2 sensors for process optimization and accordingly regulate the speed of the AHUs or pumps. 4. Provision for additional 3 PID controllers to control external devices such as chilled water modulating valve, fresh air damper, etc. thus reducing the number of I/Os in DDC Controllers & improving system reliability. 5. Automatic Energy Optimization / Load dependent flux optimization functionality for maximum energy savings. 6. MODBUS RTU as the communication protocol between BMS & VFDs. 7. VFDs not meeting above requirements shall provide external disconnect, external harmonic filters, additional external EMC Filters to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 1 (50 m), external PLCs / DDCs to achieve 3 Feedback PID Controller functionality and external devices controlling capabilities. a NS Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for for 4-5.5 kW motor rating as per the specifications(3 Phase variable frequency output for Exh. Fan, . These variable speed drives shall get the input from the remote air differential pressure adjuster , as described above in item. 5.0 No. 55038.0 275190.0 b NS Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for for 11.0 kW motor rating as per the specifications(3 Phase variable frequency output for TFA Fan/ AHU . These variable speed drives shall get the input from the remote air differential pressure adjuster , as described above in item. R.O No. 148925.0 c NS Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for for1.1-2.2 kW motor rating as per the specifications(3 Phase variable frequency output for Scrubber Exh.Fan/AHU , . These variable speed drives shall get the input from the remote air differential pressure adjuster , as described above in item. 4.0 No. 80938.0 323752.0 |
| 1089 | Supply,installation testing and commissioning of AIR CURTAIN of following size as per approved make With Speed regulator and Door limit switch/sensor .(At entrance) a SSR-22007 1100 mm long (High flow type) R.O No. 61237.23 b SSR-22007 1800 mm long (High flow type) R.O No. 66680.53 c SSR-22007 1600 mm long (High flow type) R.O No. 74845.5 |
| 1090 | a Up to 4500 CFM, 21 Watt No. 99225.0 b 6500 to 8000 CFM, 36 Watt No. 132300.0 c 9000 to 16000 CFM, 54 Watt No. 182700.0 d 300 to 2800 CFM, For IDU Duct Mount No. 40950.0 UVGI units for AHU OR |
| 1091 | a Up to 4000 CFM, 21 Watt b 4500 to 7000 CFM, 36 Watt c 300 to 1200 CFM, For IDU Duct Mount |
| 1092 | Supply,Installation,balancing and commissioning of fabricated at site GSS sheet metal ducts (rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter,vanes, hangers, supports etc.) in accordance with the approved shop drawings and specifications , and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to suit pieces. (May Be existing Duct Reuse partially) a 30.12.2.1 0.63mm (24 gauge) GSS 300.0 SqM 1114.99 334498.17 b 30.12.2.2 0.8 mm (22 gauge) GSS 400.0 SqM 1300.67 520269.21 c 30.12.2.3 1.0mm (20 gauge) GSS 60.0 SqM 1701.45 102086.75 d 30.12.2.4 1.25mm (18 gauge) GSS 80.0 SqM 1896.32 151705.35 |
| 1093 | Supply,Installation,balancing and commissioning of factory fabricated GSS sheet metal ducts (rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter,vanes, hangers, supportsetc.) in accordance with the approved shop drawings and specifications , and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to suit pieces. (May Be existing Duct Reuse partially) a 30.12.1.1 0.63mm (24 gauge) GSS 700.0 SqM 1094.77 766340.0 b 30.12.1.2 0.8 mm (22 gauge) GSS 600.0 SqM 1270.34 762203.58 c 30.12.1.3 1.0mm (20 gauge) GSS R.O SqM 1367.77 d 30.12.1.4 1.25mm (18 gauge) GSS R.O SqM 1850.36 |
| 1094 | a NS 250 mm Dia. 30.0 RM 1053.0 31590.0 |
| 1095 | Supplying and fixing of Extruded aluminium supply and return air grilles/diffusers/louvres with dampers, supply air plenum etc. duly powder coated as per specifications and drawings. a 30.15 Aluminium supply air grilles with damper. R.O Sqm. 8845.5 b 13.16 Aluminium return/Exh. air grilles without damper. 24.0 Sqm. 5777.19 138652.66 c 30.17 Aluminium supply air square diffuser with damper R.O Sqm. 11803.49 d 30.18 Aluminium return/exhaust air square diffuser without damper. R.O Sqm. 7900.55 e NS Aluminium return/exhaust air Valve circular/squirell diffuser without damper. 3.0 Sqm. 8100.0 24300.0 f NS Linear air grilles (150 MM wide) R.O RM 1098.0 g NS Aluminium supply air collar damper R.O Sqm. 4500.0 h NS Jet Diffusers (315mm Dia.) 12.0 Nos. 7440.0 89280.0 i NS AI Volume control dampers for ducts 2.0 Sqm. 4500.0 9000.0 j NS 2-Slot linear air diffusers R.O RM 2538.0 k NS 3-Slot linear air diffusers R.O RM 2940.0 |
| 1096 | Supplying and fixing of extruded aluminium louvres with frame bird screeen , mounting arrangement etc. as per specifications and drawings. a Fresh Air/Exhaust Louvers 20.0 Sqm. 8700.0 174000.0 |
| 1097 | NS Spcl. Note: In Air Distribution Works Smoke extract Duct should be fire rated for 2 hrs. So Vendor give their quoate accordingly. |
| 1098 | Supply and installation of cross linked open cell Oxide Acetate ( Acco Isolate) Foam/Open Cell Nitrile Rubber Acoustic insulation on ducts having density of 30 to 60 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 15mm thick Oxice Acetate Acco Isolate/Nitrile rubber accosound Acoustic open cell insulation on one side for Duct acoustic insulation 10.0 Sqm 1320.0 13200.0 |
| 1099 | Supply and installation of cross linked closed cell Oxide Acetate ( Thermo Isolate) Foam/Nitrile Rubber Thermal insulation on ducts having density 0f 30 ±3 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 25 mm thick insulation oxide acetate foam/Nitrile Rubber laminated with two layer canvas with starbond adhesive supply air duct R.O SqM 750.0 b NS 13 mm thick insulation oxide acetate foam/Nitrile Rubber laminated with aluminium foil supply air duct 40.0 SqM 630.0 25200.0 c NS 9mm thick insulation oxide acetate foam/ Nitrile Rubber laminated with aluminium foil supply air duct R.O SqM 468.0 |
| 1100 | Supply and installation of cross linked open cell Oxide Acetate ( Acco Isolate) Foam/Open Cell Nitrile Rubber Acoustic insulation on ducts having density of 30 to 60 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 25mm thick Oxice Acetate Acco Isolate//Nitrile rubber accosound Acoustic open cell insulation on one side for AHU Room acoustic insulation R.O SqM 1620.0 |
| 1101 | Supply and installation of cross linked closed cell Oxide Acetate ( Thermo Isolate) Foam/Nitrile Rubber Thermal insulation on ducts having density 0f 30 ±3 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 19mm thick oxide acetate insulation for underceck plain R.O SqM 1152.0 |
| 1102 | The rates for the distribution boards from the Breakers and instruments shall also include the following : A Wiring for light / Fan points with 1.5 sq. mm PVC insulated copper conductor 1100 Volt grade stranded flexible FRLS wires of approved make in 1.6 mm thick 25 mm dia MS conduit including cost of providing & fixing saddles, hangers, supports, cutting chases and filling chases for recessed conduiting, and including the cost of providing and fixing a 6 amp 240 Volt Modular Plate type switches of approved quality, colour, make and design with moulded cover plate in zinc chromate passivated MS box and including the cost of running 1.5 sq. mm PVC insulated copper earth wire for loop earthing etc. complete B TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate size of neutral link. C All MCB’s shall be of minimum 10 KA breaking capacity and MCCB 's shall be not lessthan 25KA D The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermal magnetic microprocessor releases as per BOQ and following : i. MCCB rating upto 250 Amps with thermal magnetic releases. ii. MCCB above 250 Amps with microprocessor releases. E All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic. F Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993. i. IP 42 for indoor panels. ii. IP 55 for ODU panel. G All MCCB’s shall be provided with operating mechanism for door interlock. H All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire. I Providing cable clamps / supports within distribution boards cable alley. J Current density of aluminium shall be 1sq mm for 1.0 Amps for rated current of bus bars. K Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirment. L All meter shall be digital type and all starter shall be as per Type-2 Coordination chart M Current Transfomer shall be resin cast. N All Panel Shall be BMS Compitable |
| 1103 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of following LT panels fabricated out of 14 guage CRCA sheet steel in cubical formationwith reinforecment of suitable size angle iron and channel T iron flats. All steel material used in the construction of panels shall be powder coated. A solid busbar shall be provided at the bottom of the panel with two connecting eyes for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase , 4 wire supply system. All the hardware used in the fabrication of the panel shall be galvanized with zinc passivation. The panel shall be compartmentalized to accommodate one feeder in each compartment. A vertcal cable alley of suitable width shall be provided to serve on or two vertical feeder sections. Also the opening between the busbar chamber and the feeder section shall be shrouded with bakelite / hylam sheet with min.3 mm thickness. The panel drawing shall be approved before taking up the fabrication and compitable BMS if in future required. In All panel Each starter should have remote control and interlocking facilities including auto manual switch, NO/NC contacts for control and must have auto manual operation suitable to take signal from fire alarm panel for automatic operation of fan in case of fire. All smoke /vent. fan panel the starters shall have suitable facility to operate with fire sensing control modules. Vent.Fan Panel a Vent Panel- MCC -1 (GF) Incoming 1 no. 100 amp MCCB Phase indicating lights with control fuses. Breaker ON/OFF/TRIP indicating lights. Bus Bars 125 amp TPN Aluminum Bus Bar with heat shrinkable insulation colored sleeves. Outgoings 4 nos. 2.5-4 A,TP MPCB (with VFD (1.1 KW)Space Provision only , VFD Separte Item In BOQ) 2 nos. 9-14 A,TP MPCB (with VFD (5.5 KW)Space Provision only , VFD Separte Item In BOQ) 3 nos. 2.5-4 A,TP MPCB (with Dol Starter ,1.1 KW) 2 nos. 4-6.3 A,TP MPCB (with Dol Starter ,2.2 KW) 1 nos. 6-10 A,TP MPCB (with Dol Starter ,3.7 KW) NS Panel as described above and in drawings. 1.0 No. 152500.0 152500.0 b Vent Panel- MCC -2 (1st) Incoming 1 no. 100 amp MCCB Phase indicating lights with control fuses. Breaker ON/OFF/TRIP indicating lights. Bus Bars 125 amp TPN Aluminum Bus Bar with heat shrinkable insulation colored sleeves. Outgoings 1 nos. 6-10 A,TP MPCB (with VFD (3.7 KW)Space Provision only , VFD Separte Item In BOQ) 2 nos. 9-14 A,TP MPCB (with VFD (5.5 KW)Space Provision only , VFD Separte Item In BOQ) 2 nos. 6-10 A,TP MPCB (with Dol Starter ,3.7 KW) NS Panel as described above and in drawings. 1.0 No. 95770.0 95770.0 |
| 1104 | Supplying, Installation, Testing and Commissioning of dust, damp and vermin proof free floor standing / wall mounted factory built sheet steel enclosed modular construction extendable panel, suitable for operation on 415 + 10% volts, 50 Hz AC 3 phase 4 wire system fabricated out of suitable sized square tubular section and covered with 2.0mm thick CRCA sheet, hinged doors of 2mm thick CRCA sheet, duly painted complete with aluminium bus bars, interconnection with solid copper conductor wires / aluminium strips, neutral links, earth bus etc. necessary metering protections & indications and mounted with the following as per drawing and technical specifications attached etc. complete as required. a ODU's Panel-01-TERRHVAC Same as above item but outdoor Panel with following accessories. INCOMING: 1 No. 200 amps, 415V TPN MCCB with overcurrent and short circuit releases, all indication, push button etc. Coloured (Red, Yellow, Blue) phase indicating lamp - 1 set (0 - 200 A) CT operated Ammeter with selector switch & 3 nos. CTs ratio 200/5A , 15VA burden & accuracy class of 1.0 - 1 set 0-500 V Voltmeter with selector switch - 1 set BUSBAR: 250 Amp. TPN, 35 kA Al. Bus Bar OUTGOINGS: 80A, TPN ELCB with 300mA -7 Nos. (Incl. 1No. Spare) 40A, TPN ELCB with 300mA - 0 Nos. (Incl. 1No. Spare) ODU Panel Described as above/As per Manufacturer ODU Configuration. 2.0 Set 151250.0 302500.0 Spcl. Note : All Above mentioned panel SITC as per actual GA dwgs. equipments and final config,. Of ODU's. |
| 1105 | Power Cabling and Earthing: Spcl. All Cables Should be FRLS Cables Sch. Chapter 20.1 Supply, installation, testing & commisioning of Aluminum conductor cables Fire survival cables of 1.1 KV grade with termination glands and identification tags, clamps and saddles etc. FRLS Type 20a.1.20 3.5Cx400 Sqmm R.O Rmt 3103.23 a NS 3.5Cx300 Sqmm R.O Rmt 2181.0 b 20a.1.18 3.5Cx240 Sqmm R.O Rmt 2136.23 c 20a.1.17 3.5Cx185 Sqmm R.O Rmt 1710.64 d 20a.1.10 3.5Cx25 Sqmm R.O Rmt 603.0 e 20a.1.14 3.5Cx95 Sqmm R.O Rmt 1091.09 f 20a.1.12 3.5Cx50 Sqmm R.O Rmt 791.43 g NS 3Cx50 Sqmm R.O Rmt 551.0 h NS 3Cx35 Sqmm R.O Rmt 456.0 i NS 3Cx25 Sqmm R.O Rmt 393.0 j NS 3Cx16 Sqmm R.O Rmt 329.0 k NS 3Cx10 Sqmm R.O Rmt 313.0 l NS 3Cx 06 Sqmm 260.0 Rmt 278.0 72280.0 m NS 3Cx04 Sqmm 280.0 Rmt 218.0 61040.0 n NS 2Cx04 Sqmm (Cu Conductor) R.O Rmt 206.0 o 20a.1.2 2Cx10 Sqmm R.O Rmt 494.53 p NS 4Cx 10 Sqmm Cu 220.0 Rmt 920.0 202400.0 q NS 4Cx 06 Sqmm Cu R.O Rmt 603.0 r 20a.1.9 4Cx 16 Sqmm R.O Rmt 568.07 |
| 1106 | Supply, installation, testing & commisioning of Copper conductor , PVC insulated, Fire survival cable of 1.1 KV grade (Which is Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers and AHU to Panel). a NS 5C x 1.5 Sqmm 160.0 RM 234.0 37440.0 |
| 1107 | a 0.376053240740741 3.5Cx400 Sqmm R.O Set 1430.28 b 0.376041666666667 3.5Cx300 Sqmm R.O Set 1098.45 c 0.376030092592593 3.5Cx240 Sqmm R.O Set 944.02 d 0.376006944444444 3.5Cx185 Sqmm R.O Set 804.3 e 0.375925925925926 3.5Cx25 Sqmm R.O Set 287.71 f 0.375972222222222 3.5Cx95 Sqmm R.O Set 540.49 g 0.375949074074074 3.5Cx50 Sqmm R.O Set 379.63 h 0.375821759259259 3Cx50 Sqmm R.O Set 342.86 i 0.375810185185185 3Cx35 Sqmm R.O Set 322.64 j 0.375798611111111 3Cx25 Sqmm R.O Set 252.78 k 0.375787037037037 3Cx16 Sqmm R.O Set 248.18 l 0.375775462962963 3Cx10 Sqmm R.O Set 236.24 m 0.375775462962963 3Cx 06 Sqmm 16.0 Set 236.24 3779.76 n 0.375775462962963 3Cx04 Sqmm 18.0 Set 236.24 4252.24 o 0.375706018518519 2Cx04 Sqmm (Cu Conductor) R.O Set 220.61 p 0.375775462962963 2Cx10 Sqmm R.O Set 236.24 q 0.376064814814815 4Cx 10 Sqmm Cu 22.0 Set 247.27 5439.85 r 0.376064814814815 4Cx 06 Sqmm Cu R.O Set 246.35 s 0.376076388888889 4Cx 16 Sqmm R.O Set 284.03 |
| 1108 | a 0.170844907407407 100 mm. Width x 50mm. Depth x 1.6mm. Thickness. 40.0 Rmt 614.95 24597.89 b 0.170856481481481 150 mm. Width x 50mm. Depth x 1.6mm. Thickness. 30.0 Rmt 658.15 19744.49 c 0.170868055555556 225 mm. Width x 50mm. Depth x 1.6mm. Thickness. R.O Rmt 822.69 d 0.17087962962963 300 mm. Width x 50mm. Depth x 1.6mm. Thickness. R.O Rmt 885.19 e 0.170902777777778 450 mm. Width x 50mm. Depth x 1.6mm. Thickness. R.O Rmt 1114.99 |
| 1109 | a 5.12 6 SWG G.I. wire 160.0 Rmt 263.81 42209.83 Total in Figures (HVAC Electrical Works) 15507041.95 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 S.No. SSR-2020/DSR -2025/ NS Description Actual Qty. Unit Rate Amount |
| 1110 | Supplying, installing, testing and commissioning of aircooled variable refrigerant volume / Flow modular type airconditioning system with R410a refrigerant. The PCB Chamber of outdoor unit should be refrigerant cooled suitable for 415±10% 3 Phase, 50 cycles. The unit shall consist of indoor and out door units with individual controller as per detail given in specifications and having following items : (These items are to be given in Indian rupees with custom duites, inland frt,clearance etc on Site basis) Modular type outdoor units equipped with highly efficient 100% inverter type hermitically sealed scroll compressors, minimum two comprossors for and above 14 HP modules, with special precoated heat exchanger, low noise condenser fan housed in compact housing duly powder coated and manufacturer of compressor and outdoor unit should be same. The Unit should have automatic refrigerant charge function. The static pressure of the outdoor unit shall be more then 78 Pa to avoid hot air recirculation. The unit shall be able to operate upto to 45°C in cooling mode.The unit shall also have feature to automatically modulate the evaporative temperature between 6 deg C to 11 deg C with respect to load for better comfort and energy efficiency etc complete as reqd. The units should have free phase technology for countinued operation. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping .The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 of following capacitites: Cost of R 410 A Gas should be inclusive The outdoor unit should include all loading, unloading, transportation, power cabling/wiring from near the indoor and outdoor units respectively. The outdoor unit should include all loading, unloading, transportation, power cabling/wiring,( Y/T joints which is required for ODU Zone requirement Modules) from near the indoor and outdoor units respectively. Outdoor Units-Heat Pump , Fully Gas Charged and Aluminum fins within the ODU (condensing) unit shall be coated with polysiloxane based coating. The Vendor should considere the deration on ODU election as per Manesar Ambient conditions a 1.29378472222222 26 HP Outdoor unit VRV/VRF Zone-01 1.0 No. 517634.77 517634.77 b 1.29378472222222 16 HP Outdoor unit VRV/VRF Zone-02 1.0 No. 318544.47 318544.47 c 1.29378472222222 28 HP Outdoor unit VRV/VRF Zone-03 1.0 No. 557452.83 557452.83 |
| 1111 | Supply, installation, testing and commissioning of following Wall Mounted /Cassette type units with panel and inbuilt drain pump/slim Ceiling Mounted duct type/Ceiling Mounted Built in type/Ceiling Mounted Ductable type units VRF Air Conditioners with cordless/corded remote controller.Fully Factory assembled,wired and tested Indoor Units as per specifications ans as required to make the system complete. Aluminum fins within the IDU (evaporator unit) shall be oxycoat (Epoxy coating followed by oxycoat (PU /Polysiloxine) coating, The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. |
| 1112 | a 1.29795138888889 300-320 CFM / 0.8 TR RO No. 28682.83 1.29796296296296 320-335 CFM / 1.0-102 TR RO No. 29079.92 b 1.29862268518519 525-560 CFM / 1.25-1.30 TR RO No. 31561.77 c 1.29863425925926 565-635 CFM / 1.5-1.60 TR RO No. 32156.5 d 1.29864583333333 650-740 CFM / 1.7-2.0 TR RO No. 33149.24 e 1.29865740740741 875-883 CFM / 2.4-2.50 TR RO No. 34638.35 f 1.29866898148148 1130 -1150 CFM / 3.0-3.20 TR RO No. 36920.73 g 1.29939814814815 1200-1377 CFM / 3.95-4.0 TR RO No. 42280.61 h 1.29940972222222 1600-2050 CFM / 4.5-4.6 TR RO No. 59351.13 i 1.30001157407407 1600-2050 CFM / 5.5 TR RO No. 68383.23 j 1.30002314814815 2047-2295 CFM / 6.36 TR RO No. 71757.63 k 1.30003472222222 2542-2825 CFM / 8.0-8.02 TR RO No. 78307.87 |
| 1113 | a 1.29515046296296 300-310 CFM / 0.6-0.63 TR 2.0 No. 20783.19 41566.38 b 1.29516203703704 310-320 CFM / 0.8 TR RO No. 23092.23 c 1.29517361111111 335-350 CFM / 1.0 TR RO No. 36225.81 d 1.29518518518519 400-410 CFM / 1.2-1.30 TR RO No. 36722.18 Ceiling Mounted Cassette Unit 1.29445601851852 450-460CFM / 0.8 TR RO No. 20501.92 1.29446759259259 450-460CFM /1.0 TR RO No. 24419.95 c 1.29447916666667 600-670 CFM / 1.2-1.3 TR 10.0 No. 35482.18 354821.76 d 1.29449074074074 812-830 CFM / 1.6 TR 3.0 No. 36275.45 108826.35 e 1.29450231481481 812-830 CFM / 2.0 TR 9.0 No. 36523.63 328712.7 f 1.29451388888889 850-865 CFM / 2.4 TR RO No. 37516.37 g 1.29452546296296 850-865 CFM / 2.6 TR RO No. 37516.37 h 1.29453703703704 1130-1165 CFM / 3.2-3.6 TR 6.0 No. 40692.22 244153.33 i 1.29454861111111 1200-1220 CFM / 4.0-4.1 TR RO No. 42082.06 |
| 1114 | a 1.2972337962963 250-270 CFM / 0.6-0.63 TR RO No. 15433.43 b 1.29724537037037 250-270 CFM / 0.8-0.8 TR RO No. 15880.16 |
| 1115 | NS Supply, installation, tesing and commissioning of Imported Remote controllers (Corded) for operation of Cassette/Ductable indoor units and AHU's. 30.0 Nos 4840.0 145200.0 |
| 1116 | NS Supply, installation, testing and commissioning of touch screen controller (Which is controlled 30 nos. indoor units in terms of ON/Off Status, temp. Status, Fan Speed, ODU On/Off Status etc.) with all accessories and controls. 1.0 Nos 90750.0 90750.0 |
| 1117 | NS Supply, installation, tesing and commissioning of Imported fittings Y-joints insulated, distributer and headers for all Indoor units at both the ends floors layout as per layout drawings.All interconnecting joints, Y Joints with polysiloxane based coating 27.0 Nos 5082.0 137214.0 |
| 1118 | Supply, installation, testing and commissioning of Interconnecting refrigerant pipe work with (13/ 19mm thick) cross linked closed cell Oxide Acetate Foam tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with hangers and All interconnecting Copper piping, joints, U bends with oxycoat dual barrier coating shall run in cable tray. (Note: Ref. Piping Length may be review as per site routing) a 1.30140046296296 06.35 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 95.0 RM 235.32 22355.03 b 1.30141203703704 09.5 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 130.0 RM 318.04 41345.78 c 1.30142361111111 12.70 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 170.0 RM 447.65 76100.86 d 1.30143518518519 15.86 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 230.0 RM 565.31 130021.34 e 1.30144675925926 19 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation 185.0 RM 679.29 125668.91 f 1.30145833333333 22.2 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 50.0 RM 830.96 41548.0 g 1.30146990740741 25.4 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 20.0 RM 981.71 19634.19 h 1.30148148148148 28.58 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 50.0 RM 1063.52 53175.93 i 1.30149305555556 31.8 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 10.0 RM 1123.27 11232.67 j 1.30150462962963 34.9 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation 35.0 RM 1182.1 41373.35 k 1.3015162037037 38.1 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation RO RM 1215.19 l 1.30152777777778 41.27 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation RO RM 1257.47 |
| 1119 | NS Supply, installation, testing, termination and commissioning of control cum transimission wiring (should be shielded cable in PVC Pipe) of 2C x 1.5 Sqmm Cu between indoor unit and out door unit and indoor units and its remote controller. a 2C x 1.5 Sqmm Cu Cable or as per Manufacturer OEM 700.0 RM 273.0 191100.0 b Perforated GI Tray with hangers & supports for copper piping (300 mm wide) 150.0 RM 1029.0 154350.0 c Perforated GI Tray with hangers & supports for copper piping (450 mm wide) 80.0 RM 1271.0 101680.0 |
| 1120 | NS Supply , charging & Leackage testing of refrigerant -410a in additional copper piping circuit. 25.0 Kgs. 1210.0 30250.0 |
| 1121 | Providing and fixing of Air Cooled Split airconditioners each comprising an outdoor unit consisting of hermetic Invertor scroll compressor, air cooled condensing unit, Condenser fan etc. with outer casing and indoor fan coil unit(s) consisting of centrifugal fans, fan motor, DX cooling coil, outer casing, filter, control and power panel with corded/cordless remote control, stablizer etc. both inter connected with copper refrigerant pipe (Compressor capable Approx. 30-40 mtr. copper piping) and drain pipe of required length as given, cabling and wiring, insulation with cross linked polyethelene foam, full charge of refrigerant gas and oil, M.S. base frame, supports etc. complete as per specifications and drawings. The cost shall also include angle iron stands for outdoor units . If A common Servo oil type stablizer than not required stablizer. a 1.33476851851852 2.0 TR Hi-wall Unit with ref.circuit and approx 30-40 meter of ref.and drain piping & Cabling with sequencing controller (15 Working + 15 Standby) as per specifications & Drawing, For Server Room RO Nos. 52758.61 |
| 1122 | a NS - 5KVA RO Nos. 4538.0 |
| 1123 | a NS 3Cx2.5 Sqmm. RO Rmt 296.0 |
| 1124 | Supplying, fixing,testing and commissioning of following PVC pipes for condensate drain duly insulated with Fire rated Class O kinny foam /Nitrile Rubber & vapour barrier duly secured with adhesive tape as per specification ,cut to required length and installed with all joints , including the necessary fittings. (For all the AHU/FCU units upto the main header in the shaft dor vertical risers) a 65mm dia 20.0 RM 700.0 14000.0 b 50mm dia 20.0 RM 538.0 10760.0 c 40mm dia 40.0 RM 406.0 16240.0 d 30mm dia 60.0 RM 325.0 19500.0 e 25 mm dia 80.0 RM 263.0 21040.0 |
| 1125 | Supply,installation,testing and commissioning of Propeller fan of the following capacity of approved make and specification. Fan shall be supplied with aluminum gravity louver & bird screen and Speed Regulator. a NS 200 mm dia propeller fan, with single phase motor 4.0 No. 4533.0 18132.0 b NS 300 mm dia propeller fan, with single phase motor 1.0 No. 5633.0 5633.0 c NS 450 mm dia propeller fan , with single phase motor 5.0 No. 6281.0 31405.0 |
| 1126 | Supply, installation, testing and commissioning of Circular/Rectangular swing type Inline fan with fiire retardent Canvas connection Speed Regulator of the following capacity of approved make and specification. a NS 50-300 CFM, 5-7 mm SP WG with Single phase motor 1.0 No. 8418.0 8418.0 b NS 350-500 CFM, 7-10 mm SP WG with Single phase motor 2.0 No. 14893.0 29786.0 c NS 550-800 CFM, 10-12 mm SP WG with Single phase motor RO No. 21368.0 NS 850-1000 CFM, 10-12 mm SP WG with Single phase motor RO No. 25253.0 |
| 1127 | SITC of Long case Tube axial flow fans, as per specifications and approved makes suitable for three phase operation respectively Normal/Smoke case. |
| 1128 | a 7000 CFM (For Liftwell/Liftlobby Pressurization) RO No. 80938.0 b 12500 CFM (For Liftwell/Liftlobby Pressurization) RO No. 110075.0 |
| 1129 | a 3000 CFM For Smoke extract 1.0 No. 45973.0 45973.0 b 5000-5500 CFM For Normal & Smoke extract 5.0 No. 62808.0 314040.0 c 12000 CFM For Normal & Smoke extract 2.0 No. 114608.0 229216.0 |
| 1130 | Supply of following HVAC dedicated VFDs with IP 55 enclosures with Mains disconnect, complying with the tender specifications and having: 1. built-in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the VFD. 2. built-in EMC Filters (electromagnetic compatibility filters) for for VFDs for restriction of conducted emissions to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 2, 3. Three-feedback PID controller having capability to simultaneously accept 3 feedback signals from temperature sensors or pressure sensors or CO2 sensors for process optimization and accordingly regulate the speed of the AHUs or pumps. 4. Provision for additional 3 PID controllers to control external devices such as chilled water modulating valve, fresh air damper, etc. thus reducing the number of I/Os in DDC Controllers & improving system reliability. 5. Automatic Energy Optimization / Load dependent flux optimization functionality for maximum energy savings. 6. MODBUS RTU as the communication protocol between BMS & VFDs. 7. VFDs not meeting above requirements shall provide external disconnect, external harmonic filters, additional external EMC Filters to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 1 (50 m), external PLCs / DDCs to achieve 3 Feedback PID Controller functionality and external devices controlling capabilities. a NS Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for for 4-5.5 kW motor rating as per the specifications(3 Phase variable frequency output for Exh. Fan, . These variable speed drives shall get the input from the remote air differential pressure adjuster , as described above in item. 2.0 No. 55038.0 110076.0 b NS Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for for 11.0 kW motor rating as per the specifications(3 Phase variable frequency output for TFA Fan/ AHU . These variable speed drives shall get the input from the remote air differential pressure adjuster , as described above in item. RO No. 148925.0 c NS Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for for1.1-2.2 kW motor rating as per the specifications(3 Phase variable frequency output for Scrubber Exh.Fan/AHU , . These variable speed drives shall get the input from the remote air differential pressure adjuster , as described above in item. 5.0 No. 80938.0 404690.0 |
| 1131 | Supply,installation testing and commissioning of AIR CURTAIN of following size as per approved make With Speed regulator and Door limit switch/sensor .(At entrance) a SSR-22007 1100 mm long (High flow type) RO No. 61237.23 b SSR-22007 1800 mm long (High flow type) RO No. 66680.53 c SSR-22007 1600 mm long (High flow type) RO No. 74845.5 |
| 1132 | a Up to 4500 CFM, 21 Watt R.O No. 99225.0 b 6500 to 8000 CFM, 36 Watt R.O No. 132300.0 c 9000 to 16000 CFM, 54 Watt R.O No. 182700.0 d 300 to 1200 CFM, For IDU Duct Mount R.O No. 40950.0 UVGI units for AHU OR |
| 1133 | a Up to 4000 CFM, 21 Watt b 4500 to 7000 CFM, 36 Watt c 300 to 1200 CFM, For IDU Duct Mount |
| 1134 | Supply,Installation,balancing and commissioning of fabricated at site GSS sheet metal ducts (rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter,vanes, hangers, supports etc.) in accordance with the approved shop drawings and specifications , and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to suit pieces. (May Be existing Duct Reuse partially) a 30.12.2.1 0.63mm (24 gauge) GSS 300.0 SqM 1114.99 334498.17 b 30.12.2.2 0.8 mm (22 gauge) GSS 250.0 SqM 1300.67 325168.26 c 30.12.2.3 1.0mm (20 gauge) GSS 50.0 SqM 1701.45 85072.29 d 30.12.2.4 1.25mm (18 gauge) GSS 80.0 SqM 1896.32 151705.35 |
| 1135 | Supply,Installation,balancing and commissioning of factory fabricated GSS sheet metal ducts (rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter,vanes, hangers, supportsetc.) in accordance with the approved shop drawings and specifications , and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to suit pieces. (May Be existing Duct Reuse partially) a 30.12.1.1 0.63mm (24 gauge) GSS 250.0 SqM 1094.77 273692.86 b 30.12.1.2 0.8 mm (22 gauge) GSS 200.0 SqM 1270.34 254067.86 c 30.12.1.3 1.0mm (20 gauge) GSS R.O SqM 1367.77 d 30.12.1.4 1.25mm (18 gauge) GSS R.O SqM 1850.36 |
| 1136 | a NS 250 mm Dia. 10.0 RM 1053.0 10530.0 |
| 1137 | Supplying and fixing of Extruded aluminium supply and return air grilles/diffusers/louvres with dampers, supply air plenum etc. duly powder coated as per specifications and drawings. a 30.15 Aluminium supply air grilles with damper. R.O Sqm. 8845.5 b 13.16 Aluminium return/Exh. air grilles without damper. 15.0 Sqm. 5777.19 86657.91 c 30.17 Aluminium supply air square diffuser with damper R.O Sqm. 11803.49 d 30.18 Aluminium return/exhaust air square diffuser without damper. R.O Sqm. 7900.55 e NS Aluminium return/exhaust air Valve circular/squirell diffuser without damper. 1.5 Sqm. 8100.0 12150.0 f NS Linear air grilles (150 MM wide) R.O RM 1098.0 g NS Aluminium supply air collar damper R.O Sqm. 4500.0 h NS Jet Diffusers (315mm Dia.) R.O Nos. 7440.0 i NS AI Volume control dampers for ducts R.O Sqm. 4500.0 j NS 2-Slot linear air diffusers R.O RM 2538.0 k NS 3-Slot linear air diffusers R.O RM 2940.0 |
| 1138 | Supplying and fixing of extruded aluminium louvres with frame bird screeen , mounting arrangement etc. as per specifications and drawings. a Fresh Air/Exhaust Louvers 20.0 Sqm. 8700.0 174000.0 |
| 1139 | NS Spcl. Note: In Air Distribution Works Smoke extract Duct should be fire rated for 2 hrs. So Vendor give their quoate accordingly. |
| 1140 | Supply and installation of cross linked open cell Oxide Acetate ( Acco Isolate) Foam/Open Cell Nitrile Rubber Acoustic insulation on ducts having density of 30 to 60 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 15mm thick Oxice Acetate Acco Isolate/Nitrile rubber accosound Acoustic open cell insulation on one side for Duct acoustic insulation R.O Sqm 1320.0 |
| 1141 | Supply and installation of cross linked closed cell Oxide Acetate ( Thermo Isolate) Foam/Nitrile Rubber Thermal insulation on ducts having density 0f 30 ±3 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 25 mm thick insulation oxide acetate foam/Nitrile Rubber laminated with two layer canvas with starbond adhesive supply air duct R.O SqM 750.0 b NS 13 mm thick insulation oxide acetate foam/Nitrile Rubber laminated with aluminium foil supply air duct R.O SqM 630.0 c NS 9mm thick insulation oxide acetate foam/ Nitrile Rubber laminated with aluminium foil supply air duct R.O SqM 468.0 |
| 1142 | Supply and installation of cross linked open cell Oxide Acetate ( Acco Isolate) Foam/Open Cell Nitrile Rubber Acoustic insulation on ducts having density of 30 to 60 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 25mm thick Oxice Acetate Acco Isolate//Nitrile rubber accosound Acoustic open cell insulation on one side for AHU Room acoustic insulation R.O SqM 1620.0 |
| 1143 | Supply and installation of cross linked closed cell Oxide Acetate ( Thermo Isolate) Foam/Nitrile Rubber Thermal insulation on ducts having density 0f 30 ±3 Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of -70°C to +100°C and fire rating Class O as per BS 476 Part 6 from CBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 and as per the approved specifications. a NS 19mm thick oxide acetate insulation for underceck plain R.O SqM 1152.0 |
| 1144 | The rates for the distribution boards from the Breakers and instruments shall also include the following : A Wiring for light / Fan points with 1.5 sq. mm PVC insulated copper conductor 1100 Volt grade stranded flexible FRLS wires of approved make in 1.6 mm thick 25 mm dia MS conduit including cost of providing & fixing saddles, hangers, supports, cutting chases and filling chases for recessed conduiting, and including the cost of providing and fixing a 6 amp 240 Volt Modular Plate type switches of approved quality, colour, make and design with moulded cover plate in zinc chromate passivated MS box and including the cost of running 1.5 sq. mm PVC insulated copper earth wire for loop earthing etc. complete B TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate size of neutral link. C All MCB’s shall be of minimum 10 KA breaking capacity and MCCB 's shall be not lessthan 25KA D The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermal magnetic microprocessor releases as per BOQ and following : i. MCCB rating upto 250 Amps with thermal magnetic releases. ii. MCCB above 250 Amps with microprocessor releases. E All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic. F Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993. i. IP 42 for indoor panels. ii. IP 55 for ODU panel. G All MCCB’s shall be provided with operating mechanism for door interlock. H All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire. I Providing cable clamps / supports within distribution boards cable alley. J Current density of aluminium shall be 1sq mm for 1.0 Amps for rated current of bus bars. K Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirment. L All meter shall be digital type and all starter shall be as per Type-2 Coordination chart M Current Transfomer shall be resin cast. N All Panel Shall be BMS Compitable |
| 1145 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of following LT panels fabricated out of 14 guage CRCA sheet steel in cubical formationwith reinforecment of suitable size angle iron and channel T iron flats. All steel material used in the construction of panels shall be powder coated. A solid busbar shall be provided at the bottom of the panel with two connecting eyes for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase , 4 wire supply system. All the hardware used in the fabrication of the panel shall be galvanized with zinc passivation. The panel shall be compartmentalized to accommodate one feeder in each compartment. A vertcal cable alley of suitable width shall be provided to serve on or two vertical feeder sections. Also the opening between the busbar chamber and the feeder section shall be shrouded with bakelite / hylam sheet with min.3 mm thickness. The panel drawing shall be approved before taking up the fabrication and compitable BMS if in future required. In All panel Each starter should have remote control and interlocking facilities including auto manual switch, NO/NC contacts for control and must have auto manual operation suitable to take signal from fire alarm panel for automatic operation of fan in case of fire. All smoke /vent. fan panel the starters shall have suitable facility to operate with fire sensing control modules. Vent.Fan Panel a Vent Panel- MCC -1 (Base) Incoming/Outgoing 1 nos. 4-6.3 A,TP MPCB (with VFD (2.2 KW)Space Provision only , VFD Separte Item In BOQ) Phase indicating lights with control fuses. Breaker ON/OFF/TRIP indicating lights. NS Panel as described above and in drawings. 1.0 No. 29890.0 29890.0 b Vent Panel- MCC -2 (Base) Incoming 1 no. 32 amp MCB Phase indicating lights with control fuses. Breaker ON/OFF/TRIP indicating lights. Bus Bars 50 amp TPN Aluminum Bus Bar with heat shrinkable insulation colored sleeves. Outgoings 1 nos. 2.5-4 A,TP MPCB (with VFD (1.1 KW)Space Provision only , VFD Separte Item In BOQ) 2 nos. 4-6.3 A,TP MPCB (with Dol Starter ,2.2 KW) NS Panel as described above and in drawings. 1.0 No. 64050.0 64050.0 c Vent Panel- MCC -3 (Base) Incoming 1 no. 32 amp MCB Phase indicating lights with control fuses. Breaker ON/OFF/TRIP indicating lights. Bus Bars 50 amp TPN Aluminum Bus Bar with heat shrinkable insulation colored sleeves. Outgoings 1 nos. 4-6.3 A,TP MPCB (with VFD (2.2 KW)Space Provision only , VFD Separte Item In BOQ) 1 nos. 4-6.3 A,TP MPCB (with Dol Starter ,2.2 KW) NS Panel as described above and in drawings. 1.0 No. 54290.0 54290.0 d Vent Panel- MCC -4 (GF) Incoming 1 no. 63 amp MCCB Phase indicating lights with control fuses. Breaker ON/OFF/TRIP indicating lights. Bus Bars 80 amp TPN Aluminum Bus Bar with heat shrinkable insulation colored sleeves. Outgoings 2 nos. 9-14 A,TP MPCB (with VFD (5.5 KW)Space Provision only , VFD Separte Item In BOQ) NS Panel as described above and in drawings. 1.0 No. 33550.0 33550.0 |
| 1146 | Supplying, Installation, Testing and Commissioning of dust, damp and vermin proof free floor standing / wall mounted factory built sheet steel enclosed modular construction extendable panel, suitable for operation on 415 + 10% volts, 50 Hz AC 3 phase 4 wire system fabricated out of suitable sized square tubular section and covered with 2.0mm thick CRCA sheet, hinged doors of 2mm thick CRCA sheet, duly painted complete with aluminium bus bars, interconnection with solid copper conductor wires / aluminium strips, neutral links, earth bus etc. necessary metering protections & indications and mounted with the following as per drawing and technical specifications attached etc. complete as required. a ODU's Panel-01-TERRHVAC Same as above item but outdoor Panel with following accessories. INCOMING: 1 No. 160 amps, 415V TPN MCCB with overcurrent and short circuit releases, all indication, push button etc. Coloured (Red, Yellow, Blue) phase indicating lamp - 1 set (0 - 160 A) CT operated Ammeter with selector switch & 3 nos. CTs ratio 160/5A , 15VA burden & accuracy class of 1.0 - 1 set 0-500 V Voltmeter with selector switch - 1 set BUSBAR: 200 Amp. TPN, 35 kA Al. Bus Bar OUTGOINGS: 80A, TPN ELCB with 300mA -5 Nos. (Incl. 1No. Spare) 40A, TPN ELCB with 300mA - 2 Nos. (Incl. 1No. Spare) ODU Panel Described as above/As per Manufacturer ODU Configuration. 1.0 Set 133100.0 133100.0 Spcl. Note : All Above mentioned panel SITC as per actual GA dwgs. equipments and final config,. Of ODU's. |
| 1147 | Power Cabling and Earthing: Spcl. All Cables Should be FRLS Cables Sch. Chapter 20.1 Supply, installation, testing & commisioning of Aluminum conductor cables Fire survival cables of 1.1 KV grade with termination glands and identification tags, clamps and saddles etc. FRLS Type 20a.1.20 3.5Cx400 Sqmm R.O Rmt 3103.23 a NS 3.5Cx300 Sqmm R.O Rmt 2181.0 b 20a.1.18 3.5Cx240 Sqmm R.O Rmt 2136.23 c 20a.1.17 3.5Cx185 Sqmm R.O Rmt 1710.64 d 20a.1.10 3.5Cx25 Sqmm R.O Rmt 603.0 e 20a.1.14 3.5Cx95 Sqmm R.O Rmt 1091.09 f 20a.1.12 3.5Cx50 Sqmm R.O Rmt 791.43 g NS 3Cx50 Sqmm R.O Rmt 551.0 h NS 3Cx35 Sqmm R.O Rmt 456.0 i NS 3Cx25 Sqmm R.O Rmt 393.0 j NS 3Cx16 Sqmm R.O Rmt 329.0 k NS 3Cx10 Sqmm R.O Rmt 313.0 l NS 3Cx 06 Sqmm 40.0 Rmt 278.0 11120.0 m NS 3Cx04 Sqmm 120.0 Rmt 218.0 26160.0 n NS 2Cx04 Sqmm (Cu Conductor) R.O Rmt 206.0 o 20a.1.2 2Cx10 Sqmm R.O Rmt 494.53 p NS 4Cx 10 Sqmm Cu 80.0 Rmt 920.0 73600.0 q NS 4Cx 06 Sqmm Cu 20.0 Rmt 603.0 12060.0 r 20a.1.9 4Cx 16 Sqmm R.O Rmt 568.07 |
| 1148 | Supply, installation, testing & commisioning of Copper conductor , PVC insulated, Fire survival cable of 1.1 KV grade (Which is Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers and AHU to Panel). a NS 5C x 1.5 Sqmm 150.0 RM 234.0 35100.0 |
| 1149 | a 0.376053240740741 3.5Cx400 Sqmm R.O Set 1430.28 b 0.376041666666667 3.5Cx300 Sqmm R.O Set 1098.45 c 0.376030092592593 3.5Cx240 Sqmm R.O Set 944.02 d 0.376006944444444 3.5Cx185 Sqmm R.O Set 804.3 e 0.375925925925926 3.5Cx25 Sqmm R.O Set 287.71 f 0.375972222222222 3.5Cx95 Sqmm R.O Set 540.49 g 0.375949074074074 3.5Cx50 Sqmm R.O Set 379.63 h 0.375821759259259 3Cx50 Sqmm R.O Set 342.86 i 0.375810185185185 3Cx35 Sqmm R.O Set 322.64 j 0.375798611111111 3Cx25 Sqmm R.O Set 252.78 k 0.375787037037037 3Cx16 Sqmm R.O Set 248.18 l 0.375775462962963 3Cx10 Sqmm R.O Set 236.24 m 0.375775462962963 3Cx 06 Sqmm 4.0 Set 236.24 944.94 n 0.375775462962963 3Cx04 Sqmm 12.0 Set 236.24 2834.82 o 0.375706018518519 2Cx04 Sqmm (Cu Conductor) R.O Set 220.61 p 0.375775462962963 2Cx10 Sqmm R.O Set 236.24 q 0.376064814814815 4Cx 10 Sqmm Cu 8.0 Set 247.27 1978.13 r 0.376064814814815 4Cx 06 Sqmm Cu 2.0 Set 246.35 492.69 s 0.376076388888889 4Cx 16 Sqmm R.O Set 284.03 |
| 1150 | a 0.170844907407407 100 mm. Width x 50mm. Depth x 1.6mm. Thickness. 20.0 Rmt 614.95 12298.94 b 0.170856481481481 150 mm. Width x 50mm. Depth x 1.6mm. Thickness. 20.0 Rmt 658.15 13162.99 c 0.170868055555556 225 mm. Width x 50mm. Depth x 1.6mm. Thickness. R.O Rmt 822.69 d 0.17087962962963 300 mm. Width x 50mm. Depth x 1.6mm. Thickness. R.O Rmt 885.19 e 0.170902777777778 450 mm. Width x 50mm. Depth x 1.6mm. Thickness. R.O Rmt 1114.99 |
| 1151 | a 5.12 6 SWG G.I. wire 150.0 Rmt 263.81 39571.71 TOTAL CARRIED (HVAC Electrical Works) 7652968.57 Tender Inviting Authority : BRIDGE AND ROOF CO. (INDIA) LIMITED., KANKARIA CENTRE, 4TH & 5TH FLOOR, 2/1, RUSSEL STREET, KOLKATA - 700071 Name of Work : CIVIL AND UTILITY WORK FOR CONSTRUCTION OF NEW BUILDINGS AND UPGRADATION OF EXISTING BUILDING AT ICAT MANESAR.” SUB-HEAD: Civil Work including Electrical work, Sanitary & Plumbing, Water Supply, Sewage, HVAC, Fire-Fighting including Fire Protection, Lift, CCTV and other Allied Works etc Notice Inviting e-Tender (eNIT) No : B AND R / HO / 51314 / ICAT / MANESAR / NIT / CW / 01, DATED 20.11.2026 S.NO DSR 2023 DESCRIPTION Total QTY. UNIT DSR Rate Amount (In Rs.) |
| 1152 | NSR (i) From 0-50 meter 50.0 RM 729.0 36450.0 (ii) From 50 - 200 meter onwards |
| 1153 | 2.6 All kind of soil |
| 1154 | 2.26 0.101400462962963 All kinds of soil. 30.0 Cum 126.8 3804.0 |
| 1155 | 0.231956018518519 |
| 1156 | JSR 5.2.2 |
| 1157 | 5.9 (a) 0.214618055555556 Suspended floors, roofs, landings, balconies and acees platform 24.0 Sqm 937.25 22494.0 |
| 1158 | 19.16 0.0 |
| 1159 | Providing and constructing masonry de-silting chamber 3.0 m x 2.0 m x 1.5 m depth inside with 75 class designated brick work in cement mortar 1:6 (1cement : 6 fine sand) with DI double seal Heavy duty 560mm dia manhole cover (2Nos.). top slab 1:2:4 mix (1cement : 2coarse sand : 4 graded stone aggregate 20mm nominal size) with minimum 1.5% reinforcement, foundation concrete 1:5:10 (1cement : 5 fine sand:10 grade stone aggregate 20mm nominal size including baffle wall, necessary excavation, back filling and disposal of surface earth. Complete with inlet, outlet and overflow arrangement. Foot rest @400mm c/c, grating of required size with 16mm sq.bars and frame @20mm clear spacing fixed at month of pipe as per site conditions and direction of Engineer in charge. Drilling: Drilling percolation borehole ---mm dia with reverse rotary method in all types of soil up to 60 m (approx.) depth including cost for mobilization of rig and making good the area upon completion of work. Contractor shall arrange for all necessary tools, water and consumable and laying for drilling. Providing and laying pea gravel all around the casing pipe. 160 mm dia UPVC blind pipe of 6 Kg/cm2 - 100 m or as per site with bail plug and well cap, complete as per approved drawing. Rate shall include excavation, back filling and all other operations necessary for completing the job. TOTAL Amount 816616.0 |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 13 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 14 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender