Tender For Camc Of Air Cooling Plants, Air Conditioning System, Water Coolers ,Various Size Refrigerators, Desert Coolers Sterilization Machine At Sms Hospital Jaipur.
Tender Value
3.10 Crore
Estimated cost
Bid Submission
30 Nov 2026
1 days left
EMD
6.21 Lakhs
Bank guarantee accepted
Document Fee
2000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jaipur → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Camc Of Air Cooling Plants, Air Conditioning System, Water Coolers ,Various Size Refrigerators, Desert Coolers Sterilization Machine At Sms Hospital Jaipur.
BOQ
| Sl. No. | Item Description |
| 1 | All in all comprehensive maintenance of central air cooling plant including motor with blower, air washer section with nozzles, drift eliminators, starter panel, water pump, ducting, grills etc. complete in all respect as per OEM's guidelines and standard terms & conditions of PWD to meet efficient performance of the equipment. |
| 2 | All in all comprehensive maintenance of single/double Skin package type evaporative air cooling plant during defect liability period including air washer section, humidification section, fan section with motor, starter panel , water pump, ducting, grills etc. as per OEM's guidelines and standard terms & conditions of PWD to meet efficient performance of the equipment. |
| 3 | All in all comprehensive maintenance of Package type air conditioning system including indoor units , out door units ,ducting , grills , consumables , cabling , starting panel etc. complete in all respect as per OEM's guidelines and standard terms & conditions of PWD to meet out the maximum efficiency of the machine. |
| 4 | All in all comprehensive maintenance of various type air conditioners including repair / replacement of compressor, condensing/ cooling coil , refrigerant piping , fan motor , remote , charging of refrigerant whenever required and periodical servicing as per OEM's recommendations and standard terms & conditions of PWD to meet efficient performance of the equipment. |
| 5 | 1.0/1.5/2.0 Tr window type air conditioner |
| 6 | 1.5/1.8/2.0 Tr Split type air conditioner |
| 7 | 1.5/2.0/3.0/4.0 Tr Cassette type Split type air conditioner |
| 8 | All in all comprehensive maintenance of central air conditioning system including air cooled chiller and its control , AHU's , FCU's , Hot water generator , LT/APFC panels , Control Panel , Pipe line and pumps , valves , ducting , grills / diffusers , consumables etc. complete in all respect as per OEM's guidelines and standard terms & conditions of PWD to meet out the maximum efficiency of the machine. |
| 9 | All in all comprehensive maintenance of Water cooler including compressor, condensing/ cooling coil ,water tank with inner piping including repair / replacement of components like filters, membrane, charging of refrigerants whenever required , cleaning , servicing etc. as per OEM's recommendations and standard terms & conditions of PWD to meet efficient performance of the equipment. |
| 10 | Up to 60/120 Ltr capacity |
| 11 | 150/150 Ltr capacity |
| 12 | 150/400 Ltr to 225/400 Ltr capacity |
| 13 | All in all comprehensive maintenance of Reverse Osmosis water purification system including repair / replacement of components ,consumables , cleaning , servicing etc as per OEM's Guide lines to meet out the TDS level of Water as per client requirement / standard norms to meet efficient performance of the equipment. |
| 14 | 12-15 Ltr/hr capacity |
| 15 | 25 Ltr/hr capacity |
| 16 | 50 Ltr/hr capacity |
| 17 | 500 Ltr/hr capacity |
| 18 | All in all comprehensive maintenance of Domestic water purifier including replacement of components, consumables, cleaning, servicing etc. complete in all respect to meet efficient performance of the equipment. |
| 19 | All in all comprehensive maintenance of Variable refrigerant volume (VRV) air conditioning system including indoor units , out door units , cordless control , refrigerant piping , control cables , remote control , drain piping , consumables , LT panel etc. complete in all respect as per OEM's guidelines and standard terms & conditions of PWD to meet out the maximum efficiency of the machine. |
| 20 | All in all annual maintenance and repair charges of various make refrigerator (Fridge) including charging of refrigerant, replacement of compressor, relay, thermostate,Timer, indicating lamp,etc complete in all respect of following capacity |
| 21 | up to 210 litre capacity |
| 22 | above 210 & up to 400 litre capacity |
| 23 | Providing Manpower through Contracting agency for Supervision / Execution / Operation of various Electromechanical Installations. (one shift of 8 working Hrs per day ) on basis of minimum wages + VDA order Dt. 28.03.2025 Ministry of Labour and Employement Govt. of India |
| 24 | Engineer with B.Tech and1 Yrs, experience ,/Diploma Engineer with 3 Yrs. Experience in relevant field |
| 25 | Wireman, Electrician, Welder, Lineman, AC Mechanic, Fireman, , Supervisor, ELV technician or equivalent professional with ITI or Equivalent course and Experience of 2 years in relevant field ) ( 8 nos (4+4+4 ) for 12 month |
| 26 | Technical Helper Having basic Knowledge of E&M Services |
| 27 | P & F of Fire retardent flexible canvass connection made of fibreglass weave having silver grey silicon rubber coating, of height 200 mm with sufficient fold to avoid transmission of vibration with GI frame ,Gasket Nut Bolts for air cooling Plants/AHU/FCU etc as required. |
| 28 | Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive) & fabricated as per IS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. |
| 29 | 0.80mm |
| 30 | 1.00 mm |
| 31 | Supplying, installing, testing and balancing of double louvered of extruded Aluminium Powder coated supply/return air grills of various sizes, Each grill shall be with fixed aerofoil shaped horizontal front bar at 0 deflection and back adjustable vertical louvers, air distribution grid for straightening the air flow through the collar and register including fixing with steel screws etc. complete in all respect. |
| 32 | Supply air grill with key operated volume control damper |
| 33 | Return air grill without volume control damper |
| 34 | Supplying, installing, testing and balancing of extruded Aluminium powder coated Air Diffuser and complete with Flush, 20mm flanges with PVC/neoprene gasket, anti – smudge frame and removable inner core to facilitate the adjustable of air control damper, square/round/ rectangular as required.including fixing with steel screws etc. complete in all respect. |
| 35 | Supply Air Diffuser with Volume Control damper |
| 36 | Return Air Diffuser without Volume Control damper |
| 37 | Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapour diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required. |
| 38 | 19 mm thick for Outdoor Application with 26 SWG Aluminium Cladding |
| 39 | Gas charging of VRF/VRV system with R410A refrigerant gas. Before gas charging system shall be flushed with high purity Nitrogen Gas to remove carbon content, dirt particles to make sure that there is no chance of mixing any impurity with Refrigerant Gas. Thereafter System shall be tested with Nitrogen Gas at 1.5 Times of working pressure of R410 Refrigerant Gas to ensure leakproof system. Whole system shall be Vacuumed up to 500-micron level which ensures the zero-moisture content level in piping to ensure better cooling efficiency and long life of the system. |
| 40 | Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM must ensure that the cable is tested for complaince, either through their in house laboratory accrediated by NABL or by any Govt. laboratory accrediated by NABL and the laboratory's scope of accrediation should cover the requirements and testing procedure as per IS:10810. |
| 41 | Un Armoured |
| 42 | 4 core x 2.5 Sq.mm |
| 43 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. |
| 44 | 25 mm |
| 45 | 32 mm |
| 46 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 47 | 50 mm dia per running inch length |
| 48 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge. |
| 49 | Supply & fixing MS powder coated stand suitable for 2.5/3.0/4.0 Tr outdoor type of Split/Ductable/Tower AC. All as per pre approved by Engineer in charge. |
| 50 | SITC of Interconnecting refrigerant copper pipe for split/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizes as per OEM requirement & specifications including class 'O' Nitrile rubber sleeves (size as per item no. 22.43),7 mil Glass Cloth with 3 coats of anti UV paint (on area which is exposed to weather) chase cutting, supports, making good the same with sand cement plaster etc. as required. |
| 51 | Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C ' class (Heavy) pipes conforming to IS 3589 / 1239 part-I for chilled water / Condensor water applications including cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger, vibration isolators and nuts bolts including cutting hole and chase in brick walls and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of desired shade (for condensor water only) complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). |
| 52 | 25 mm dia |
| 53 | 32 mm dia |
| 54 | 40 mm dia |
| 55 | 50 mm dia |
| 56 | S & F of Auto air vent valve complete with socket, ball valve etc. as required. |
| 57 | SITC of AHU temperature controller including making connections etc. as required. |
| 58 | SITC of FCU Digital thermostate with manual or automatic fan speed , temperature setting including making connections as required. |
| 59 | Providing & fixing in position 15 mm 'V' shape mercury in glass industrial type thermometer including Making Drilling, socket in Existing MS Pipe Etc. as required. |
| 60 | Providing & fixing Stainless Steel pressure gauge with dial of 100 mm dia size and range 0 to 20 kg/sq.cm with 3 / 8 \\" BSP bottom entry , Ball valve , SS Syphon tube all fittings etc, duly calibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS Pipe Etc. as required. |
| 61 | SITC of Paddle type water flow switch with actuation & delay mechanism for sensitivity in the range of 4 to 10 GPM and suitable for installation in HVAC chilled water pipeincluding making connections, making hole in pipe etc. as required. |
| 62 | S & layiing 1.0 Sq.mm x 8 core copper control cable from FCU to Thermostate in existing conduit as required. |
| 63 | Supplying and charging of fresh refrigerant and testing of performance of air conditioner/ fridge/ water cooler of following capacity including capallary and strainer/ filter. |
| 64 | 1.5 TR Window/ Split A.C. |
| 65 | 2.0 TR Window/ Split A.C. |
| 66 | 60/120 Ltr. Water cooler |
| 67 | 150/150 Ltr. Water cooler |
| 68 | Replacement of defective compressor by company repaired compressor as per OEM recommendations of following gadgets including testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 69 | 1.5 TR A.C. |
| 70 | 2.0 TR A.C. |
| 71 | 60/120 Ltr. Water cooler |
| 72 | 150/150 Ltr. Water cooler |
| 73 | P & Replacement of condensing/ cooling coil of copper fins for following capacity A.C./ Water cooler/ Fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 74 | 1.5 TR A.C. |
| 75 | 2.0 TR A.C. |
| 76 | 60/120 Ltr. Water cooler |
| 77 | 150/150 Ltr. Water cooler |
| 78 | Servicing of 1.0/1.5/2.0 TR capacity Split/ Window type air conditioner |
| 79 | P & Replacement of overload protection of A.C./ Water cooler as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 80 | P & Replacement of thermostat of A.C./ Water cooler/fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 81 | P & Replacement of door gasket of 165/200 Ltr. Fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 82 | P & Replacement of door gasket of 286/310 Ltr. Fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 83 | P & Replacement of lamp of Fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 84 | P & Replacement of fan motor of evaporator/ condensor complete as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 85 | Dismentling of split air conditioner of any capacity/any type including existing indoor unit & outdoor unit , refrigerant piping , connecting cables , drain pipe etc. including shifting of dismentaled material to store complete as required |
| 86 | Supply & fixing of evaporative cooling Celdec pads of 200mm Thick made out from impregnated cellulose paper media of imported origin including fixing in Air washer complete in all respect. |
| 87 | Supply and installation of 50 mm thick MERV-8 synthetic media filter with efficiency 90% to 10 microns,made in Aluminium frame for air cooling machine /AHU etc as required. |
| 88 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. . |
| 89 | Providing and replacement of following ball bearing of air washer including removing the bearing and refixing the same at suitable location as required as per OEM recommendations. Replacement of material or components shall be use ae per guideline of OEM of original product. Allthe scrap material should be retained by the contractor. |
| 90 | UC 207 |
| 91 | UC 210 |
| 92 | UC 211 |
| 93 | UC 215 |
| 94 | All in all comprehensive maintenance of Diffrent size desert cooler including fan motor, blade, submersible pump, body frame including water tank, grill etc. complete in all respect as per OEM's guidelines and standard terms & conditions of PWD to meet efficient performance of the equipment. |
| 95 | All in all comprehensive maintenance of walking coolers of different capacity including replacement of all kind of spares i.e. compressor , fans , contoller wiring, stabilizers etc as reqd. |
| 96 | waliking cooler size ( 7.2mx5.4mx2.7m) |
| 97 | waliking cooler size ( 3mx3mx2.7m aprox) |
| 98 | waliking cooler size (1.8mx2.4mx2.13m aprox) |
| 99 | All in all comprehensive maintenance of different capacity central sterilization plant to ensure trouble free operation of sterilization machine including all spare component consumable and non consumable parts. |
| 100 | Sterilization machine Neuro Surgery 18 KW |
| 101 | Sterilization machine Charak Bhawan ENT OT 18 KW |
| 102 | Sterilization machine Charak bhawan Eye OT 18 KW |
| 103 | Sterilization machine Dhanwantri Ortho OT 3 Kw |
| 104 | Add: GST@18% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 20, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 30, 2026
17:00 IST