Tender For Provn Of 02 X 500 Kva Trolley Mounted 11 Kv Distr Transformer And 01X125 Kva Trolley Mounted Dg Set At Mamun Mil Stn
Tender Value
43.70 Lakhs
Estimated cost
Bid Submission
11 Dec 2026
20 days left
EMD
87400
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pathankot → Punjab
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of 02 X 500 Kva Trolley Mounted 11 Kv Distr Transformer And 01X125 Kva Trolley Mounted Dg Set At Mamun Mil Stn
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, Testing, Commissioning of Oil Cooled, Copper wound, Step down \\"BIS marked & BEE star labelled\\" transformer of capacity 500 KVA plinth mounted outdoor type with latest feature complete with standard fitted HT 11 KV 3 phase, LT 433 V 3, phase 4 wire, 50 C/S oil immerse, naturally cooled externally cooling tube delta connection on primary HT 11 KV side and star connection on secondary LT 433V with tapping at ±2.5% to ±5 % & ± 7.5 % on HV side and to be changed by means of hand operated off load tap changing gear including first filling of new transformer oil of dilectric strength not less than 55 KV with all fitting and accessories such as LT box with cable gland, HT box with cable gland, Silica gel, breather, Oil level indicator gauge, drain out valve (oil tank), exhaust vent, air release valve, temp gauge, cast iron wheel etc comply with EEL 2 IS 1180 2014 (Level III) with latest amendment 1,2,3 & 4 having total losses @50% load 1430W & total losses @100% load 4100W. Following items/ Accessories included in this rate, therefore No any extra cost will be paid for this items complete all as specified and directed by Engineer-in-charge.(i) Name, rating & diagram plate(ii) Off circuit tap changing switch(iii) Earthling terminals(iv) Lifting lugs(v) Oil drain valve with plug(vi) Oil filter valve with plug(vii) Conservator with oil filling hole(viii) Thermometer pocket(ix) Air release plug,(x) Silica gel breather, (xi) Removable inspection opening(xii) Explosion vent |
| 2 | Note:- 1.1.1 Contractor will produce BIS certification and compliance with energy efficiency levels (Star rating by BEE), test reports duly issued by NABL accredited BIS approval lab obtained from manufacturer (OEM) for each rating of transformer.1.1.2 The OEM of transformer should have in house NABL accredited lab for routine testing of transformer. |
| 3 | Supply and laying in trenches or fixed to wall/pole or passing through pipe or road crossing, testing and commissioning of HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty ) with aluminium conductor, 11KV (Earthed) grade, suitable for earthed system, with aluminium conductor of size 120 Sqmm 3 Core complete all specified and directed. |
| 4 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm including testing complete all as specified and all as directed. |
| 5 | M & L for LT UG cable 300 sqmm x 3.5 core, 1100 Volts grade XLPE insulated, armoured, heavy duty with aluminium conductor laid in trenches or fixed to walls/ poles or passing through pipes with and including, cable gland lugs/ thimbles/ ferrules including connecting, testing complete all as specified and as directed. |
| 6 | M & L for LT UG cable 185 sqmm x 3.5 core, 1100 Volts grade XLPE insulated, armoured, heavy duty with aluminium conductor laid in trenches or fixed to walls/ poles or passing through pipes with and including, cable gland lugs/ thimbles/ ferrules including connecting, testing complete all as specified and as directed. |
| 7 | M&L for cable end termination jointing kit , outdoor heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium cable of size 240 Sqmm to 300 Sqmm, 1100 volts complete all as specified and all as directed. |
| 8 | M&L for cable end termination jointing kit , outdoor heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium cable of size 150 Sqmm to 185 Sqmm, 1100 volts complete all as specified and all as directed. |
| 9 | M&L for trolley for 500 KVA transformer, factory fabricated manufactured of MS Sheet, angle irons, channels etc duly painted as per load class recommended by manufacturer's of transformer with four wheels and one spare wheel, hydraulic jack, toe rod/chain, air filling pump, four wheel drum brake system, spring loaded drawbar, leaf spring based suspension system provision for sliding screw jack 04 Nos for levelling of transformer etc complete all as specified and directed.Note: Drawing of trolley duly approved from manufacturer of transformer shall be submitted by the contractor. |
| 10 | Supply, Installation, Testing and Commissioning of capacity 125 KVA (100 KW) 415 Volt, 0.8 PF, 3 phase, 50 Hz factory assembled Silent Diesel Engine Driven Generating Set with flexible coupling 1500 RPM alongwith sound proof enclosure (accoustic enclosure) designed for reducing the sound level to 75 DB (A) average IS 8528 Part - 10 as per approved CPCB IV+ norms alongwith Retrofitted emission control device and as per GSR 371 (E) and independently supported from engine to outside of power house upto 1.00 mtr, AVM pads foundation as per manufacure's design, battery start with suitable cables for connecting from DG Set to panel board, DG set shall be capable of operating in including of the following accessories suitable for parallel operation/ independent operations:- (A) Prime Mover:- Diesel Engine of suitable capacity water cooled radiator type closed circuit as per BIS 649 or IS-1002 direct inject type turbo with turbo charger. The DG Set shall be capable of running 24 hrs continously with 10% overloading for one hour in every 12 hrs as per BIS-5514/BIS-649, Engine shall be equipped with all standard fitting as per manufacturers recommendations and mounted on common base frame through flexible coupling with following accessories :- (i) Battery charging ammeter(ii) Battery charging voltmeter(iii) Ignition key and starting with push button switch(iv) Lubricating oil pressure gauge(v) Electronic/Microprocessor based Governor controlling(vii) Toggle switch for idle running.(viii) Oil Temperature gauge(ix) Safety control (Trip):- (a) High water temperature (b) Low lubricant oil pressure (c) Over Speed |
| 11 | (x) Lubricant oil heater to avoid freezing(xi) 24 Hours starting equipment comprising of the following :- (a) 01 No, 12 Volts, 180 AH Battery. (b) Battery charging alternator with inbuilt regulator (c) Self starter motor of suitable capacity (d) Battery leads (Copper standard cable) of suitable size with brass thimbles and terminals(B) Alternator:- Alternator of capacity of 125 KVA/100 KW at NTP, 50 Hz, 415 Volt, 1500 RPM, 0.8 PF, running rate @ 1500 RPM, with insulation class 'H' self excited, self regulated, screen protected with self excited field brush rotating fixed designed to be coupled with above engine through flexible couping, the alternator shall be conforming to BIS-2613 or IS-4722.(C) Control Panel:- Alternator control inbuilt panel cubical type with internal wiring with copper conductor for 125 KVA, 415 volt, 03 Phase, 04 wire, 50 Hz alternator fabricated out 1.6mm thick MS sheet painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, microprocessor based generator set monitoring, metering and control system with LCD display designed to meet the demands of today's engine driven generator sets.Engine Metering: Oil pressure, Engine temperature, Starting battery voltage, Engine running hours, AC Alternator Metering: L-L Voltage and L-N Voltage, Current (phase and total), kVA (phase and total) and Frequency kwh, Total & per phase (kw & kVA), PF, Utility Voltage and FreqEngine Protection: Low lube oil pressure, High/Low coolant temperature, Battery High/Low/Weak Volts, Fail to Crank/Start, Sensor failure, Cranking lockout, Low fuel level |
| 12 | AC Alternator Protection: Over/Under Voltage, Over/Under Frequency, Loss of AC sensing. Overspeed, Over Current, kW Overload Data Logging: Engine hours, Control hours and upto5 recent fault codes Configurable glow plug control, 12/24 Volt DC operation, Sleep mode, In Power compatible (PC based service tool)Certifications - Meets the requirement of relevant ISO, EN, Mil Std. and CE standards Maintenance due alarm based on Engine Run Time and due date Fuel and DEF level visual display equipped with the following accessories :-(a) Suitable scaled flush mounted digital AC voltmeter with selector switch 0-500 Volt - 01 set.(b) Suitable scaled flush mounted digital ammeter with selector switch and CTs of suitable range - 01 set.(c) Frequency meter KWH and KW meter, moulded case circuit breaker 01 Nos for incoming as recommended by manufacturer, set of insulated copper bus bar of suitable capacity.(d) Frequency meter - 01 (e) Power factor meter - 01(f) MCCB for incoming as recommended by manufacturer - 01(g) Set of indicating Lamps for 03 phase RYB - 01(h) Oil pressure meter - 01(j) Set of copper bus bar of suitable size - 01 Nos(D) Other Fitting :- (i) Battery charger - Battery charger having electric circuit consisting of rectifiers, capacitors and resistance etc. The battery charger should be able to charge 12 volts, 180 AH battery 02 Nos at a time and with 01 Nos ammeter or suitable range provision of incoming electric connector single phase 220 volts and two terminal of connecting outgoing leads to connect battery including suitable size of wooden plank complete all as specified and directed. Please Enable Macros to View BoQ information |
| 13 | AC Alternator Protection: Over/Under Voltage, Over/Under Frequency, Loss of AC sensing. Overspeed, Over Current, kW Overload Data Logging: Engine hours, Control hours and upto5 recent fault codes Configurable glow plug control, 12/24 Volt DC operation, Sleep mode, In Power compatible (PC based service tool)Certifications - Meets the requirement of relevant ISO, EN, Mil Std. and CE standards Maintenance due alarm based on Engine Run Time and due date Fuel and DEF level visual display equipped with the following accessories :-(a) Suitable scaled flush mounted digital AC voltmeter with selector switch 0-500 Volt - 01 set.(b) Suitable scaled flush mounted digital ammeter with selector switch and CTs of suitable range - 01 set.(c) Frequency meter KWH and KW meter, moulded case circuit breaker 01 Nos for incoming as recommended by manufacturer, set of insulated copper bus bar of suitable capacity.(d) Frequency meter - 01 (e) Power factor meter - 01(f) MCCB for incoming as recommended by manufacturer - 01(g) Set of indicating Lamps for 03 phase RYB - 01(h) Oil pressure meter - 01(j) Set of copper bus bar of suitable size - 01 Nos(D) Other Fitting :- (i) Battery charger - Battery charger having electric circuit consisting of rectifiers, capacitors and resistance etc. The battery charger should be able to charge 12 volts, 180 AH battery 02 Nos at a time and with 01 Nos ammeter or suitable range provision of incoming electric connector single phase 220 volts and two terminal of connecting outgoing leads to connect battery including suitable size of wooden plank complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 20, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 11, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysDec 18, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 27 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender