Tender For Repair / Maintenance Of Starter Panels, Cables And Allied Works At Various Pump Houses Under Ge (West) Mathura
Tender Value
40 Lakhs
Estimated cost
Bid Submission
10 Dec 2026
19 days left
EMD
80000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Mathura → Uttar Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair / Maintenance Of Starter Panels, Cables And Allied Works At Various Pump Houses Under Ge (West) Mathura
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning of fully automatic oil immersed auto transformer motor starter / controller panel (Pedestal type) filled with transformer oil suitable for 125 HP rating of induction motor, rated voltage 415 Volt AC in sheet steel enclosure with IP-53 protection duly painted with weather resistant enamel paint, copper wire wound oil immersed auto transformer having E class insulation, impregnated in varnish with voltage tapping of 50%, 65% & 80% of rated voltage suitable for 03 Starts/Hr in duration of 15 Second each with 03 Nos oil immersed contactors, thermal overload relay of range 90 to 150 Amps, coil voltage 415 Volt AC, push button for ON-OFF operation, with provision of Ammeter, Voltmeter with selector switch and ON, OFF & Trip indication LED lamps including Voltmeter, single phase preventor, HRC fuse fitted inside the panel all as conforming to IS/IEC 60947-4-7 including dismantling of old worn out starter panel complete in all respect and as directed. |
| 2 | Supply & fixing in replacement of worn out starter with fully automatic star delta ( FASD) starter/controller suitable for 75 HP, 3 phase, 415 volt AC, AC-3 duty induction motor in sheet steel enclosure with IP 54 protection to changeover from star winding to delta winding with the help of electronc timer, having ON/OFF operation and overload protection with additional features like Auto ON (with 30 sec ON Delay), indications of supply ON/OFF and pump ON/OFF, reading of real time voltage & current of pump with unique dual analog meter, single phasing protection relay (SPPR), relay range 66 to 110 Amp, wide band coil operation from 65% to 110% of rated coil voltage - 380/415 Volt, phase-reversal protection, phase-unbalance protection, variable time-delay adjustment inside controller complete in all respect and conforming to IS/IEC 60947-4-1 standards complete all as specified and directed. |
| 3 | Supply & fixing in replacement of MCCB - 125 Amp, 415 Volt, 4 pole, 25 KA with adjustable thermal magnetic protection, Ics = 100% Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In in accordance with IS/IEC 60068-2-6 standard including making connection, testing and commissioning in DB complete all as specified and directed. |
| 4 | Supply & fixing in replacement of MCCB - 160 Amp, 415 Volt, 4 pole, 36 KA with adjustable thermal & magnetic protection/setting, Ics = 100 % Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In in accordance with IS/IEC 60068-2-6 standard including making connection, testing and commissioning in DB/LT Panel complete all as specified and directed. |
| 5 | Supply & fixing in replacement of MCCB - 200 Amp, 415 Volt, 4 pole, 36 KA with adjustable thermal & magnetic protection/setting, Ics = 100 % Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In in accordance with IS/IEC 60068-2-6 standard including making connection, testing and commissioning in DB complete all as specified and directed. |
| 6 | Supply & fixing in replacement of MCCB - 250 Amp, 415 Volt, 4 pole, 36 KA with adjustable thermal & magnetic protection/setting, Ics = 100 % Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In in accordance with IS/IEC 60068-2-6 standard including making connection, testing and commissioning in LT panel complete all as specified and directed. |
| 7 | Supply & fixing in replacement of MCCB - 315/320 Amp, 415 Volt, 4 pole, 36 KA with adjustable thermal & magnetic protection/setting, Ics = 100 % Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In in accordance with IS/IEC 60068-2-6 standard including making connection, testing and commissioning in LT panel complete all as specified and directed. |
| 8 | Supply & fixing in replacement of MCCB - 400 Amp, 415 Volt, 4 pole, 36 KA with adjustable thermal & magnetic protection/setting, Ics = 100 % Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In in accordance with IS/IEC 60068-2-6 standard including making connection, testing and commissioning in LT panel complete all as specified and directed. |
| 9 | Supply & fixing in replacement of MCCB - 630 Amp, 415 Volt, 4 pole, 36 KA with adjustable thermal & magnetic protection/setting, Ics = 100 % Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In in accordance with IS/IEC 60068-2-6 standard including making connection, testing and commissioning in LT panel complete all as specified and directed. |
| 10 | Supply & fixing in replacement of MCCB - 800 Amp, 415 Volt, 4 pole, 36 KA with adjustable thermal & magnetic protection/setting, Ics = 100 % Icu, thermal adjustable - 0.8 to 1 In, in accordance with IS/IEC 60068-2-6 standard including making connection, testing and commissioning in LT panel complete all as specified and directed. |
| 11 | M&L for rewinding and refixing after rewinding the same motor of Centrifugal pump of capacity 25 HP, three phase 415 volts, 50Hz AC with super enameled copper winding wire of suitbale size and gauge including insulating material, heating drying,re-assembling and testing complete all as specified and directed by Engineer in Charge. |
| 12 | Supply & fixing in replacement of worn out change over switch with Automatic Transfer Switch from one source to other with adjustable time delay of current rating 400 Amp, 4 pole, 415 Volt AC, utilization category AC 33 A, indicating status of the source to which load is connected, with provision of LCD display, phase separator for safety from phase to phase shorting & flashover having inbuilt protection for mains/DG against under/over voltage, under/over frequency and phase failure in SS Enlosure complete as conforming to IS / IEC 60947-6-1 including connecting all cable connections, testing and commissioning by providing alluminium lugs as required size complete in all respect and as directed.. |
| 13 | Supply & fixing in replacement of worn out change over switch with Automatic Transfer Switch from one source to other with adjustable time delay of current rating 125 Amp, 4 pole, 415 Volt AC, utilization category AC 31 A, indicating status of the source to which load is connected, with provision of LCD display, phase separator for safety from phase to phase shorting & flashover having inbuilt protection for mains/DG against under/over voltage, under/over frequency and phase failure in SS Enlosure complete as conforming to IS / IEC 60947-6-1 including connecting all cable connections, testing and commissioning by providing alluminium lugs as required size complete in all respect and as directed. |
| 14 | M&L for in replacement earthing with galvanised steel earth plate elctrode 600x600x6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr below GL) with the toop edge of the plate not less than 1.5 mtr below the normal group level connected to GI earth srtip of size 32x6mm thick soldered and riveted to earth plate,GI earth strip will be protected by using 50mm bore GI pipe (light grade) earth plate to equipment and watering pipe 20mm bore (light grade) and chamber/pit in PCC(1:3:6) type C1 using 20mm graded stone aggregate with precast RCC pit cover 50mm thick in (1:2:4) type B1using 20mm graded stone aggregate reinforced with 8mm dia MS TMT bar at 80mm c/c both way with lifting hook made out of 8mm dia TMT bar duly embedded in RCC cover in lieu of CI pit cover with angle iron frame including excavation and earth work and removal of surplus soil complete all as shown in electrical plase No.3 of SSR Part-I and as specified including earth plate surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers of charcoal dust, common salt complete and earth lead connected to earthing test point/main board all as specified and testing of earthing complete all as specified & directed.Note :- Earthing Strip and GI protection pipe upto 7.5 Mtr shall deemed to be included in the rate of above item. |
| 15 | Supply, installation, testing and commissioning of LT panel, outdoor type, floor mounted not less than of 1500 mm x 1650 mm x 600 mm IP -54 degree of protection suitable for 3 phase, 4 Wire system , 415 Volts, 50 Hz ,CPRI approved factory made having independent compartment for bus bar incoming feeder and each out going feeders, dust and vermin proof, outer shell fabricated of 2 mm thick CRCA sheet & made out angle iron frame of 40 mm x 40 mm x 5 mm (for external) with seven tank treatment process for powder coating with thickness not less than 60 micron provided with suitable gasket to make it dust/vermin proof & general construction confirming to IS 8063/93, pedestal flame grouted in PCC (1:2:4) type B-1 20 mm graded stone aggregate, thimble and cable entry boxes with cable glands including disconnecting and dismantling old LT panel of any size complete in all respect and comprising of the following: -Cont/- |
| 16 | Cont/-Inner Shell:- Inner shell made out of 1.6 mm thick CRCA sheet duly compartmentalised for each control gear, front lockable/openable by keys from both sides having chromium plated 19 mm dia fancy lock (02 Nos in each neutral flow of air 'U' type completely vermin proof & to accomodate incoming/outgoing MCCBs and TPN aluminium bus bar of rating not less than 1.5 times of rated capacity of incoming MCCB. The colour coded heat shrinkable sleave for bus bar and shall be mounted on non hydroscopic, non combustible, track resistant, high strength FRP/SMC/DMC material at an interval not more than 250 mm throughout complete all as specified and as directed.Cont/- |
| 17 | Cont/-Incoming:- (a) MCCB - 400 Amp, 415 Volt, 4 pole, 50 KA with adjustable thermal & magnetic protection/setting, Ics = 75 % Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In in accordance with IS/IEC 60068-2-6 standard - 01 EachOutgoing:-(a) Automatic Transfer switch from one source to other with adjustable time delay of current rating 400 Amp, 4 pole, 415 Volt AC, utilization category AC 31 A, indicating status of the source to which load is connected, with provision of LCD display, phase separator for safety from phase to phase shorting & flashover having inbuilt protection for mains/DG against under/over voltage, under/over frequency and phase failure - 01 EachCont/- |
| 18 | Cont/-(b) MCCB - 160 Amp, 415 Volt, 4 pole, 36 KA with adjustable thermal & magnetic protection/setting, Ics=100% Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In.- 05 Each(c) AC Analog Voltmeter( moving coil- rectifier type), 0 to 600 Volt, square flush size - 96mm x 96 mm, Accuracy class 1.5 including selector switch - 01 Each(d) AC Analog Ammeter CT operated( moving coil- rectifier type), square flush size - 96 mm x 96 mm, accuracy class 1.5 including selector switch - 01 Each(e) CT, resin casted of current ratio 400/5 Amp, burden -15 VA, accuracy class 1.0 - 01 Set ( 03 Nos of set)(f) LED Indicator lamp, 22.5 mm dia for RYB phase Indication -01 Set ( 03 Nos of set) |
| 19 | Supply, installation, testing and commissioning of LT panel, outdoor type, floor mounted not less than of 1500 mm x 1650 mm x 450 mm IP -54 degree of protection suitable for 3 phase, 4 Wire system , 415 Volts, 50 Hz ,CPRI approved factory made having independent compartment for bus bar incoming feeder and each out going feeders, dust and vermin proof, outer shell fabricated of 2 mm thick CRCA sheet & made out angle iron frame of 40 mm x 40 mm x 5 mm (for external) with seven tank treatment process for powder coating with thickness not less than 60 micron provided with suitable gasket to make it dust/vermin proof & general construction confirming to IS 8063/93, pedestal flame grouted in PCC (1:2:4) type B-1 20 mm graded stone aggregate, thimble and cable entry boxes with cable glands including disconnecting and dismantling old LT panel of any size complete in all respect and comprising of the following: Cont/- |
| 20 | Cont/-Inner Shell:- Inner shell made out of 1.6 mm thick CRCA sheet duly compartmentalised for each control gear, front lockable/openable by keys from both sides having chromium plated 19 mm dia fancy lock (02 Nos in each neutral flow of air 'U' type completely vermin proof & to accomodate incoming/outgoing MCCBs and TPN aluminium bus bar of rating not less than 1.5 times of rated capacity of incoming MCCB. The colour coded heat shrinkable sleave for bus bar and shall be mounted on non hydroscopic, non combustible,track resistant, high strength FRP/SMC/DMC material at an interval not more than 250 mm throughout complete all as specified and as directed. -Cont/- |
| 21 | Cont/-Incoming:-(a) MCCB - 200 Amp, 415 Volt, 4 pole, 36 KA with adjustable thermal & magnetic protection/setting, Ics = 100 % Icu, thermal adjustable - 0.8 to 1 In, magnetic adjustment - 5 to 10 In in accordance with IS/IEC 60068-2-6 standard. - 01 EachOutgoing:-(b) MCCB - 100 Amp, 415 Volt, 4 pole, 25 KA with adjustable thermal & fixed magnetic protection/setting, Ics = 100 % Icu, thermal adjustable - 0.8 to 1 In, in accordance with IS/IEC 60068-2-6 standard.- 02 Each (c) MCB four pole of current rating 40 Amp, C curve - 01 Each(d ) MCB FP of current rating 63 Amp, C curve - 01 Each(e) On load change over switch of current capacity 100 Amp four pole conforming to IS/IEC:60947-3 - 01 EachCont/- |
| 22 | Cont/-(f) AC Analog Voltmeter( moving coil- rectifier type), 0 to 600 Volt, square flush size - 96mm x 96 mm, Accuracy class 1.5 including selector switch - 01 Each(g) AC Analog Ammeter CT operated( moving coil- rectifier type), square flush size - 96 mm x 96 mm, accuracy class 1.5 including selector switch - 01 Each(h) CT, resin casted of current ratio 100/5 Amp, burden - 5 VA, accuracy class 1.0 - 01 Set ( 03 Nos of set)(j) LED Indicator lamp, 22.5 mm dia for RYB phase Indication -01 Set ( 03 Nos of set) |
| 23 | Supply & fixing in replacement starter with fully automatic star delta ( FASD) starter/controller with in built WLC suitable for 20 HP, 3 phase, 415 volt AC, AC-3 duty Submersible motor pump in sheet steel enclosure with IP 54 protection to changeover from star winding to delta winding with the help of electronic timer, having ON/OFF operation and overload protection with additional features like Auto ON (with 30 sec ON Delay), indications of supply ON/OFF and pump ON/OFF, reading of real time voltage & current of pump with unique dual analog meter, single phasing protection relay (SPPR), relay range 28 to 42 Amp, wide band coil operation from 65% to 110% of rated coil voltage - 380/415 Volt, phase-reversal protection, phase-unbalance protection, variable time-delay adjustment inside controller complete in all respect and conforming to IS/IEC 60947-4-1 standards complete all as specified and directed. |
| 24 | Supply and fix in replacement Single phase motor 2780 RPM of capacity 0.75KW/1.00HP, pressure booster pump rated discharge approx 1500 LPH at rated head 40 m suction discharge of pump 25x25 mm alongwith Pressure tank of capacity 24 litre all as complete all as specified and directed. |
| 25 | Supply, laying, testing and commissioning LT cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, elecric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 120 sqmm 3.5 core including taking down old unserviceable cable complete all as specified and directed. |
| 26 | S&F in repair contactor 95 Amp, 3 pole, 415 Volt with AC coil, cns-65 as per existing including electrical connection complete all as specified & directed. |
| 27 | S&F in repair contactor 70 Amp, 3 pole, 415 Volt with AC coil, cns-65 as per existing including electrical connection complete all as specified & directed. |
| 28 | M&L for in replacement contactor MNX 110 Amp, 3 pole, 415 volts including fixing of all necessary connections complete all as specified and directed. |
| 29 | M&L for in replacement starter 5HP with direct on line submersible pump starter three phase star delta fully automatic 5 HP, 3.7 KW, overload relay range 9-13 (Amp) complete all as specified and directed. |
| 30 | M&L for in replacement starter 10HP with direct on line submersible pump starter three phase star delta fully automatic 10 HP, 7.5 KW, overload relay range 17-25 (Amp) complete all as specified and directed. |
| 31 | M&L for in replacement starter 12.5HP with direct on line submersible pump starter three phase star delta fully automatic 12.5 HP, 9.3 KW, overload relay range 17-25 (Amp) complete all as specified and directed. |
| 32 | M&L for in replacement starter 15HP with direct on line submersible pump starter three phase star delta fully automatic 15 HP, 11 KW, overload relay range 23-32 (Amp) complete all as specified and directed. |
| 33 | Supply and laying in replacement PVC copper cable FRLS 10 Sqmm single core laid in open with the help of saddles of suitable size alongwith nut bolts all as specified and directed. |
| 34 | M&L for in replacement submersible copper cable flat three core PVC insulated & PVC sheathed industrial cable for submersible pump motors three core nominal area of conductor size 6 Sqmm complete all as specified and directed. |
| 35 | M&L for in replacement submersible copper cable flat three core PVC insulated & PVC sheathed industrial cable for submersible pump motors three core nominal area of conductor size 10 Sqmm complete all as specified and directed. |
| 36 | Supply and laying in replacement PVC copper cable 3 core 1.5 sqmm with PVC pipe laid in bridge with the help of saddles of suitable size alongwith nut bolts complete all as specified and directed. |
| 37 | S&F in replacement MCB Triple pole & neutral, 415 Volts, 63 Amp complete all as specified and directed. |
| 38 | S&F in replacement PVC cables copper conductor insulated and unsheathed multistranded single core of size 70 sqmm 1100 V including copper lugs complete all as specified and directed. |
| 39 | S&F in replacement PVC cables copper conductor insulated and unsheathed multistranded single core of size 50 sqmm 1100 V including copper lugs complete all as specified and directed. |
| 40 | S&F framed work such as grill gratings etc with ends of bars shouldered and/or riveted, or forged into spikes, framed guard bars, barred iron doors, ladders, framed balusters walk ways railing frame work of ceiling etc and similar work confirming to Fe-290 Gde E-165 complete all as specified and directed. |
| 41 | Dismantling of wrought iron or mild steel work of any description not otherwise provided for complete all as specified and directed by Engineer-in-charge. |
| 42 | Supply & laying in replacement cable, 1100 volts grade heavy duty with XLPE insulated aluminium conductor standard served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed of 95 Sqmm x 3.5 core size including fixing in Open with the help of saddles and nut bolt of suitable size all as specified and as directed. |
| 43 | Supply & laying in replacement cable, 1100 volts grade heavy duty with XLPE insulated aluminium conductor standard served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed of 70 Sqmm x 3.5 core size including fixing in Open with the help of saddles and nut bolt of suitable size all as specified and as directed. |
| 44 | Supply & laying in replacement cable, 1100 volts grade heavy duty with XLPE insulated aluminium conductor standard served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed of 50 Sqmm x 3.5 core size including fixing in Open with the help of saddles and nut bolt of suitable size all as specified and as directed. |
| 45 | Supply and fix in replacement soft starter Suitable for three phase motor pump 30 HP, With overload protection, underload protection, Locked load protection, soft start, soft stop, current limit, coated PCBA, Analog output ,built in bypass for energy saving. Operating voltage 208-600 volt AC all as directed by Engineer-in-charge |
| 46 | Supply and fix in replacement soft starter Suitable for three phase motor pump 25 HP, With overload protection, underload protection, Locked load protection, soft start, soft stop, current limit, coated PCBA, Analog output ,built in bypass for energy saving. Operating voltage 208-600 volt AC all as directed by Engineer-in-charge |
| 47 | Supply and fix fully cast aluminium body finished with polyurethane paint (with prior treatment) bollard of length 736 mm & circular base diameter of 177 mm and max diameter of leg of bollard 127 mm surmounted with fully cast aluminium body finished with PU paint with acrylic window cover B22 brass holder including OEM recommended PCC Foundation provided with aluminium cover with 20 Watt warm white Led bulb fixed/grouted in PCC base of size 45x45x60 cm with nut and bolts alongwith all as directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 19, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 10, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysDec 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 26 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender