Tender For Repair, Maintenance Of Ac Plants At Mh Bhopal Under Ge Bhopal
Tender Value
14.50 Lakhs
Estimated cost
Bid Submission
08 Dec 2026
16 days left
EMD
29000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bhopal → Madhya Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Repair, Maintenance Of Ac Plants At Mh Bhopal Under Ge Bhopal
BOQ
| Sl. No. | Item Description |
| 1 | S&F in replacement 3 Pole Contactor 400 Amp AC1/265 Amp AC3, (1 NO & 1 NC ) AC 415 V, 50 Hz , 3 phase for contractor of Control panel complete all as specified and directed. [Make-Siemens/ABB Model AF265-30-11 /L&T or equivalent as approved by GE.] |
| 2 | S&F in replacement MCCB of control panel, 50 KA breaking capacity, 3 phase , 4 Pole AC , 320-400 range with Ics=Icu 100% and adjustable Thermal Magnetic Protection as per site requirement complete all as specified and directed. [Make-ABB/Siemens/Legrand] |
| 3 | S&F in replacement MCCB of control panel, 25 KA breaking capacity, 3 phase, 3 Pole AC , 100 A with Ics=Icu 100% and adjustable Thermal Magnetic Protection range as per site requirement complete all as specified and directed. [Make-ABB/Siemens/Legrand ] |
| 4 | M & L for servicing of Primary & secondary pump and remove all dirt, rust of shaft impeller by machining/grinding work etc. of capacity 7.5 HP including provision of gland packing, studs and nut bolts with bushes and painting MS items including angles, frames, mounting bracket etc of motor with two coats of paints after primer on angle on which motor fixed etc. as required at the site complete all as specified and directed. |
| 5 | Supply and fix rubber expansion below with flange 150mm dia 150mm long including Nut bolt washers etc and dismantling existing one complete all as specified and directed. |
| 6 | Supply and fix rubber expansion below with flange 200mm dia 150mm long including Nut bolt washers etc and dismantling existing one complete all as specified and directed. |
| 7 | Charging of refrigerant gas R-134a for Central AC Plant at site/contractor’s workshop including all necessary work such as cost of refrigerant, welding to refrigerant pipe line, copper pipe, etc and testing complete all as specified and directed. |
| 8 | Supply and installation in repair of 200 mm cast iron Y-type strainer flange ends with fittings (GI Nut Bolts, gasket etc) etc. complete all as specified and as directed. |
| 9 | Dismantling existing motor of capacity above 20 HP and upto 25 HP, 3 phase, 440V, 50Hz from foundation and carrying out servicing/repair and of motor and pump and replacement of DE & NDE bearing and mechanical seal as per existing one so as to match the manufacturers original specification and refitting the same, testing and commissioning including required lathework if required complete all as specified and directed. |
| 10 | All as per serial item no. 9 but for motor of capacity above 15 HP and upto 20HP complete all as specified and directed. |
| 11 | All as per serial item no. 9 but for motor of capacity above 10 HP and upto 15HP complete all as specified and directed. |
| 12 | Taking out old defective burnout motor of capacity above 20 HP and upto 25 HP, 3 phase, 440V, 50Hz from foundation and transfer it to workshop for rewinding with super enamelled copper wire of existing size & gauge and replacement of DE & NDE bearing as per existing one so as to match the manufacturers original specification and refitting the same, testing and commissioning including required lathework if required complete all as specified and directed. |
| 13 | All as per serial item no. 12 but for motor of capacity above 10 HP and upto 20HP complete all as specified and directed. |
| 14 | S & F in replacement fuses HRC cylindrical type model No. 3NA7260.OPC fuses of rating 400 Amps LT panel of AC plant complete all as specified and directed. [Make - L&T/Siemens/Minilec or equivalent as approved by GE.] |
| 15 | M&L for pumping down/locking the existing refrigerant gas in separate cylinder to carry out pressure leak test by nitrogen gas of the system of AC plant 3 X 250 TR for leak proof valve joint, seal other connected controls, flaries etc including identify & rectify of leak defects and maintaining constant pressure of 160lbs on low side and 200lbs at high side at least 24 hrs complete all as specified and directed.Note : Topping up of Refrigerant R134a shall be measured and paid separately |
| 16 | S&F in replacement thermostat programmable digital temperature control device for cut off in preset Cool/Hot conditions as per the sample complete all as specified and directed. [Make :Yudinyan/Gefran/Fuji or equivalent as approved by GE.] |
| 17 | M & L for complete descaling of condenser, evaporator unit of chiller, Make: Voltas, Model No. ACEGWFXR2501MLS1, 250 TR by disconnecting from the system, cleaning by descaling solution as recommended OEM, cleaning condenser tube by nylon brush & mild steel rod of suitable size, replacement of rubber joints and unserviceable nut bolts including repair of leakage tube if any complete all as specified and as directed. Note: - Whole process of De-scaling should be done by Voltas Refrigerator Mechanics (OEM). Arrangement of required T & P e.g., pump, tube, descaling solution, etc shall be provided by the contractor. |
| 18 | Supply only compressor oil grade CP 120 and of specifications as existing at the site, Make- Solest |
| 19 | Supply only Oil Return Filter 3/8 and of specifications as existing at the site, Make -Danfoss |
| 20 | Supply only Slide Valve O Ring and of specifications as existing at the site |
| 21 | Supply only Oil filter dryer core of both refrigerant circuit and of specifications as existing at the site |
| 22 | Supply only Water Differential Switch and of specifications as existing at the site |
| 23 | Supply only MCS EVX Controller and of specifications as existing at the site |
| 24 | Supply only Suction Pressure Transducer and of specifications as per existing one complete all as specified and directed. |
| 25 | Supply only Industrial type temperature sensor of evaporator entering, condenser entering and evaporation leaving discharge temp for chiller with complete pipe fittings of existing type and connected fittings and of specifications as existing at the site |
| 26 | Supply only Unloading Plunger and of specifications as existing at the site |
| 27 | Supply only Oil filter of both refrigerant circuit and of specifications as existing at the site |
| 28 | S&F in replacement 'C' Cash heater for 250 TR AC plant compressor of make as per existing one complete all as specified and directed. |
| 29 | S&F in replacement contactor of compressor control panel 3 phase, AC , 415 V not less than AC1 175A and AC3 140A all as per site requirement complete all as specified and directed. [Make-Siemens (Model: 3TS51) /L&T/Hager or equivalent as approved by GE.] |
| 30 | S&F in replacement contactor of compressor control panel 3 phase, AC , 415 V not less than AC1 250A and AC3 205A all as per site requirement complete all as specified and directed. [Make-Siemens suitable to existing Model: 3TS53 and equivalent to 3TS5322-0A..1-8K /L&T/Hager or equivalent as approved by GE.] |
| 31 | Supply and fix digital temperature sensor cooling tower as per existing one complete all as specified and directed |
| 32 | Material and labour for repairing and rewinding with super enamelled copper wire as per existing guage of capacity 10 HP motor of Cooling tower including removing existing winding , cleaning of slots replacement bush and bearing as per existing one etc including taking down existing motor from cooling tower, transportation from site to workshop complete all as specified and directed |
| 33 | S & F in replacement Transducer PT3-30 BAR with harness of compressor all as per site requirement complete all as specified and directed. [Make: - Voltas (PIN: M5186-10198P-030BG Model: M5 186-10198P-030BG) or equivalent as approved by GE.] |
| 34 | M & L for servicing of chiller / condensing pump & remove the all dirt, rust of shaft impeller by machining/grinding work etc of capacity 25 HP and mechanical seal, studs and nut bolts with bushes and painting with two coats of synthetic enamel paints over red oxide primer for all MS brackets, angle, channels etc tc as required at site all as directed by Engr-in-Charge. |
| 35 | S & F in replacement micro process computerised mother board incuding PLC controller suitable for Central AC Plant 250 TR Panel of Make: (MCS MAGNUM) FOR Voltas Chiller complete all as specified and as directed by Engr-in-Charge. |
| 36 | S & Fix in repalcement of Variable frequency drive (VFD) of 18.5 KW (25 HP) 50 Hz complete all as specified and directed. Make: ABB Model No -ACS310-03E-41A8-4 or equivalent in L&T SX2000, Crompton. |
| 37 | Cleaning the cooling tower by cleaning chemical 1039XL,1031XL and applying wire brush, solvent by removing the deposited impurities such as silt, dust particles mud, sand inside the dome and around the fills, on wire mesh, main shaft etc and other connected items complete all as specified and directed. |
| 38 | S & F in replacement sprinkler of cooling tower of central AC Plant of cap 250 TR of Make as per the site or as per approved complete all as specified and directed. |
| 39 | S & F in repairs PVC fins in cooling tower, size 600 mm X 300 mm X 150 mm, honeycomb type, made of virgin PVC, to be installed in cooling tower for central AC Plant of capacity 250 TR of make as per site requirement or as per approved complete all as specified and directed. |
| 40 | S& fixing industrial thermometer -20 to 50o C & 0 to 1200 F for chilled water and return water pipe line complete all as specified and directed |
| 41 | S& fixing dial type of 100mm dia pressure guage for chilled water and return water pipe line as per existing one complete all as specified and directed Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 19, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 08, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysDec 10, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓