Tender For Jal Jeevan Mission (Jjm)- Supplying ,Installation ,Comprehensive Testing And Commissioning Of 500 Kva Transformer At 9.5 Mld Wtp Kannadi, Including Civil Works .- Jal Jeevan Mission - Water Supply Scheme To Kannadi,Kuzhalmannam & Thenkuris
Tender Overview
Project Description
Tender for Jal Jeevan Mission (Jjm)- Supplying ,Installation ,Comprehensive Testing And Commissioning Of 500 Kva Transformer At 9.5 Mld Wtp Kannadi, Including Civil Works .- Jal Jeevan Mission - Water Supply Scheme To Kannadi,Kuzhalmannam & Thenkurissi-Supplying ,Installation ,Comprehensive Testing And Commissioning Of 500 Kva Transformer At 9.5 Mld Wtp Kannadi, Including Civil Works .-General Electrical Work
BOQ
| Sl. No. | Item Description |
| 1 | Name of work :- Supplying ,Installation ,Comprehensive Testing and Commissioning of 500 kVA Transformer at 9.5 MLD WTP Kannadi, including Civil Works . |
| 2 | OD145737/2026-2027:Supplying, laying, testing and commissioning of 300 sqmm, 11 kV grade, 3-core, XLPE insulated, aluminium conductor, armoured HT cable inside the premises of 9.5 MLD WTP Kannadi shall conform to IS 7098 (Part 2), IS 1255, IS 8130 and CEA (Measures relating to Safety and Electric Supply) Regulations, 2010. The work includes route survey, marking, trenching to required depth, sand bedding, protective tiles or brick covering, warning tape, backfilling, compaction, and restoration of surface. Cable laying and pulling shall be done using rollers, proper pulling eye, tension monitoring, and bending radius as per manufacturer and IS 1255, avoiding sheath damage and excessive sidewall pressure. Outdoor end terminations shall be made with heat-shrinkable jointing kits, suitable lugs, glands, phase identification, stress control, and earthing as per IS 7098 and IS 1255. Testing shall include insulation resistance, continuity, phase sequence, armour continuity, and HV DC test after laying and termination, with records submitted for approval. Temporary barricading, labour, tools, tackles, conveyance, safety measures, and commissioning coordination with KSEB/Electrical Inspectorate shall be included complete as required. |
| 3 | OD145772/2026-2027:Supply , Installation, Testing and Commissioning of Outdoor type 11kV, 630A, 26.3kA for 3 sec Horizontal Draw out VCB fitted with Manual/Motor operated spring charging mechanism with 230V AC motor and motor control switch, fail safe tripping with shunt trip coil of 24V DC, closing coil of 24V DC, Auxiliary Contact 2NO + 2NC, Mechanical ON/OFFindicator, Mechanical operation counter, protection CT, (--/5A 5P10,15VA,11kV/110V, Cl-0.2, 25VA PT Instantaneous IDMT relay with Microprocessor based 3O/C + and 1EF Protection relay, Strip Heater with thermostat, Digital Ammeter and Digital Voltmeter, Power pack 230V AC-24 V DC emergency OFF push button with HT Metering (3nos CT & 1 no PT Unit ) Provision for TOD Meter. |
| 4 | OD145795/2026-2027:Supplying and making following cable end jointing with heat shrinkable jointing kit, including, lugs and other jointingmaterials, for 3 core, XLPE aluminiumconductor cable of 11 KVgrade as required: 300 sq. mm |
| 5 | OD145810/2026-2027:Supply installation, Testing and Commissioning of a 500 kVA, 11KV/433V, ONAN, Copper wound power transformer. With On load tap changer (with microprocessor based AVR and local & remote control) +5% to -15% in steps of 1.25%. HV side & LVside Cable box with standard fittings and accessories.As per IS 1180(Part 1) 2021, Level -2 |
| 6 | OD145867/2026-2027:Re-conditioning of 6-pole structure, replacement of complaint spares, and enhancing capacity of switches and equipment at the 11 kV receiving structure of 9.5 MLD WTP Kannadi shall comply with IS 9921, IS 13118, IS 3427, IS 4237, IS 10118 and CEA Regulations 2010. The work shall begin with de-energization, isolation, LOTO, discharge, earthing, and permit-to-work procedures, followed by inspection of contacts, springs, coils, mechanical linkages, insulators, and metering equipment. Defective contacts, springs, coils, and mechanical parts shall be replaced with approved spares of correct rating, and the structure shall be cleaned, lubricated, aligned, and torqued to manufacturer recommendations. Calibrated meters and equipment shall be installed and tested for continuity, insulation resistance, contact resistance, and functional operation. The reconditioned switchgear shall be tested for HV, mechanical operation, interlocks, earth fault, overcurrent, and safety shutters, and made acceptable to the Electrical Inspectorate and KSEB. Labour, tools, calibrated meters, equipment hire, conveyance, documentation, and all associated works shall be included complete as required. |
| 7 | OD145870/2026-2027:Pre-survey of route, obtaining electrical isolation permits, road transport permits, working at height permits, site induction charges, and administrative coordination shall be carried out as per CEA Regulations 2010, Kerala Electricity Supply Code, Motor Vehicles Act, Factories Act, and applicable KSEB/Electrical Inspectorate procedures. The route survey shall identify physical constraints, overhead lines, road widths, turning radii, load limits, and required diversions or escort arrangements. Electrical isolation permits shall be obtained after lock-out/tag-out, test for dead, discharge, and earthing of the existing installation. Road transport permits, police clearances, working-at-height permits, hot-work permits if needed, and site induction shall be arranged before starting work. Risk assessment, job safety analysis, emergency response plan, and coordination with plant authorities shall be documented and approved. All administrative charges( excluding security deposit & arrear of Electrical charges to KSEB),liaison, documentation, and associated works shall be included complete as required.Including electrical scheme modification , submission to authorites , obtaining scheme approval, cordinating inspection after completion of work , preparing and submission of required documents, obtaining sanction for energisation etc complete for satisfactory commissioning of transformer and associated equipments |
| 8 | OD145881/2026-2027:Civil Works at Transformer Yard including Demolishing the existing plinth of 200 kVA transformer, Clearing the debris from the site,removal and trasporting existing tranformer from site to safe place as directed by departmental officer,Construction of RCC transformer plinth, oil sump pit, GI fencing with gate, and cable trench at 9.5 MLD WTP Kannadi shall conform to IS 456, IS 1786, IS 2502, IS 3370, IS 806, IS 277 and good engineering practice. Excavation shall be carried out to required depth and width, followed by PCC bed, reinforcement as per structural drawing, shuttering, concreting with approved grade, compaction, and curing. The transformer plinth shall be level, of adequate size and height, with embedded earth pads and provision for fixing transformer, while the oil sump pit shall be impervious and filled with gravel/pebbles for safe oil collection. GI fencing with gate shall be fixed on RCC/CI posts with proper alignment, bracing, anti-corrosive treatment, and locking arrangement. Cable trench shall be constructed with brick/RCC walls, sand bedding, protective covers, drainage slope, and earthing strip provision as required. Cement, sand, aggregate, steel, labour, shuttering, curing, finishing, and all associated civil works shall be included complete as required. |
| 9 | OD145883/2026-2027:Providing and fixing following size G.I. strip on surface or in recess for connections etc. as required. |
| 10 | OD145886/2026-2027:SITC of Plate Earthing (conforming to IS 3043) using CI Earth plates of size 1200mm x 1200mm x 12 mm, 50mm dia. GI pipe medium extending upto middle of the plate and clamping to the plate with GI clamps and bolts 800x50x12mm GI Strip, funnel, 20G GI wire mesh, 15mm GI water pipe, and supply of materials and constructing 1000x500x600mm brick masonry inspection chamber, plastering, fixing heavy duty CI cover plate having locking arrangement, CI frame painted with bituminous paint, earth pit with yellow paint below the chamber cover, filling with homogenious layer of charcoal, salt & sand, including excavation of earth pit up to permanent moisture level depth and back filling. |
| 11 | OD145892/2026-2027:Supply, Installation, Fixing,and Alignment of 600 mm × 50 mm GI Perforated Cable Tray, including all required GI supports, brackets,coupler,hardwares and accessories painting/touch-up where necessary. The work shall be as per standard engineering practices and site conditions, ensuring proper leveling,routing, and secure mounting. |
| 12 | OD145923/2026-2027:SITC of following panel boards. All panel boards/Enclosures shall be fabricated out of 14/16 gauge CRCA sheet powder coated in cubicle compartmentised, free standing, floor mounted, dust and vermin proff with reinforcement of suitable size angle iron, channel, 'T' sections wherever necessary fully meeting all the requirements specified in the technical specifications and drawings. Galvanized harwares with zinc passivation shall be used in fabrication. TPN switch gears shall be supplied with equally rated neutral link. All LEDs, controlling circuites, etc. shall be provided with fuses/MCBs at is incomer side to protect the controlling and indicating equipment in the lower sides.The charges include the removal of existing panel boards already installed the Clear Water pump house of 9.5 MLD WTP Kannadi and keeping the removed panel boards in a safe place as directed by departmental officers. the major components are as listed below:-A.\\"MSBIncoming800A 4P ACB EDO Type with Microprocessor 50KA- 1 No.RYB Indication lamps and Control Fuse - 1 SetMulti Function Digital Meter -1 NosCRCT 700/5A 10VA CL: 1 - 3 NosOutgoing 400A 4P 50 kA MCCB With Rotary Handle and Spreader Terminals - 1 No.250A 4P 50 kA MCCB With Rotary Handle and Spreader Terminals - 2 No.Spare Outlets For 2 Nos. 400A 4P MCCBsMisc Items800A Rated Aluminium Bus Bars 700/5A Cl:1 10 VA CT For APFCEarth Fault Relay - 1 No.\\"B)SITC Of 125/5A Cl 5P10 10 VA CT in Metal enclosure at Transformer Neutral For Earth Fault Relay - 1 noC)Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required including sand cushioning and protective covering (in ordinary soil).3.5 core 400 sq mm - 35 mtrD)Supply and laying of one number additional PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground in the same trench in one tier horizontal formation including widening the trench by 20 cm, refilling the trench etc. as required including sand cushioning and protective covering (in ordinary soil)3,5 core 400 sq mm -70 mE)Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 400 sq mm- 90 mF)Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 4 sq mm - 60 mG)Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm) - 12 Nos Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender