Tender For Repair To 22 Kv Electric Panel, Cable, Gods In Sub Station Under Ge (I) (Navy) Lonavla (8517/E8)
Tender Value
43.58 Lakhs
Estimated cost
Bid Submission
12 Dec 2026
20 days left
EMD
87200
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pune → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair To 22 Kv Electric Panel, Cable, Gods In Sub Station Under Ge (I) (Navy) Lonavla (8517/E8)
BOQ
| Sl. No. | Item Description |
| 1 | Excavatioin in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and taking out soft/loose soil for laying of cable /erection of pole/stay pit excavation. |
| 2 | All as per Sl item No 1 herein before but in hard/dence soil |
| 3 | M&L for crushed stone sand for cable cushoining laid in trenches for protection of cable |
| 4 | M&L for Returning and filling including spreading levelling watering and well ramming in layers not exceeding 25 cm |
| 5 | M&L for Removing excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point |
| 6 | Supply and laying factory cast, unreinforced precast concrete cable cover factory made embossed the mark “HT CABLE” class HV type1 flat size 300x180x40 mm laid in trenches as specified and as directed. |
| 7 | Taking out under ground 22 KV (E) Grade HT cable of size 120 to 300 Sqmm from two or four pole/trenches/walls / ducts etc., for carrying out repairs , relaying, rerouting, laying back through same / different route after carrying out repair / issue unde schedule of credit complete all as specified and directed by Engineer-in-Charge at site. |
| 8 | Supply laying and testing cable XLPE insulated screened PVC bedded galvanized steel strip or wire armored, electric power cable heave duty with aluminum conductor 22000 volts earthed grade 3 core cable cross sectional area 120 sqmm complete all as specified and as directed. |
| 9 | Supply and fix in repairs out door type cable end termination joint heat shrinkable type for 22 KV (E) Grade HT cable of size 120 sqmm x 3 Core to 185 Sqmm x 3 Core and connecting the cable with the load and testing complete all as specified and as directed by Engineer-in-Charge at site. |
| 10 | Supply and fix in repairs out door type cable end termination joint heat shrinkable type for 22 KV (E) Grade HT cable of size 240 sqmm x 3 Core to 300 Sqmm x 3 Core and connecting the cable with the load and testing complete all as specified and as directed by Engineer-in-Charge at site. |
| 11 | Supply and fix in repairs indoor type cable end termination joint heat shrinkable type for 22 KV (E) Grade HT cable of size 120 sqmm x 3 Core to 185 Sqmm x 3 Core and connecting the cable with the load and testing complete all as specified and as directed by Engineer-in-Charge at site. |
| 12 | Supply and fix in repairs indoor type cable end termination joint heat shrinkable type for 22 KV (E) Grade HT cable of size 240 sqmm x 3 Core to 300 Sqmm x 3 Core and connecting the cable with the load and testing complete all as specified and as directed by Engineer-in-Charge at site. |
| 13 | M&L for removing / dismantling existing burnt / defective 22 KV (E) Grade HT straight through joint and providing new straight through joint heat shrinkable type for 22 KV (E) Grade HT XLPE cables of size120 sqmm x 3 Core to 185 Sqmm x 3 Core Sqmm complete all as specified and as directed by Engineer-in-Charge at site. |
| 14 | M&L for removing / dismantling existing burnt / defective 22 KV (E) Grade HT straight through joint and providing new straight through joint heat shrinkable type for 22 KV (E) Grade HT XLPE cables of size240 sqmm x 3 Core to 300 Sqmm x 3 Core Sqmm complete all as specified and as directed by Engineer-in-Charge at site. |
| 15 | M&L for removing / dismantling existing burnt / defective 22 KV (E) Grade HT Touch Proof Kit and providing new HT Touch Proof Kit for RMU i.e joint for three terminals will be considered as each joint. |
| 16 | M & L in repairs for GI pipe/ tubes light grade of size 100 mm dia for UG cable protection with all fittings laid in trenches, on poles to crossing the roads/Nalah etc . |
| 17 | Cutting and filling bituminus road/Hard surface as per direction of Engr in Charge for laying of HT UG cable and match the existing road to the existing system. |
| 18 | Repair/maintance of switch air break & DO switch , gang operated triple pole mechanically operated mounted on insulator and steel frame with 9 insulators of 22 KV rating upto 400 amps with operating mechanism worked from ground level for current rating upto 400 amps 22 KV working pressure complete,below maition all work rate are deemed including this rate Note: 1) All rusted /non opreaded nut bolt replace 2) GOD opreaded handle to be welded as per requirment. 3) opreted rod as per requrment replace or to be welded. 4) conected acessories with AB & DO switch as per requiment repair/repalce. 5) all GOD acessories greaseing and alliment done as per requirment.6) Jumper/cable lux replace and refixing with copper lux and brass nut bolts as per site requirment. |
| 19 | M & L for earthing complete with GI earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the earth plate not less than 1.5m below normal ground level connected with GI strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel including necessary excavation and earth work in any type of soil, removing surplus soil to a distance not exc 50m, with and including PCC chamber in PCC(1:2:4) type B1, using (20 mm graded stone aggregate),\\"mild steel angle iron frame\\" made out of MS angle iron of size 40x40x6 mm thick duly painted with two coats of synthetic enamel paint over one coat of red oxide zinc chrome primer hinged with and including 10 mm thick CI cover with handle, watering arrangement with funnel internally secured with wire mesh with 20mm dia medium grade GI pipe for watering, 40 mm dia light grade, GI pipe for lead protection in & including alternate layers of charcoal dust and common salt complete all as shown in electrical \\"Plate No-3 of SSR Part-I-2009\\" and connected to earthing test point all as specified and as directed including testing on completion.Note: GI earth strip 32 x 6 mm upto 7.5 RM is included in the unit rate quoted |
| 20 | M&L for Loose filling with aggregates of gauge 40 to 80 mm in substation premises including cleaning of substation complete all as specified and as directed at site by Engineer in Charge . |
| 21 | Supply and fix PT Potential transformer of Ratio 22000/RT3/110/RT3V ,IS 3156-1992 with Frequency 50 Hz class B type of make as per sample complete all as specified and as directed. |
| 22 | Supply and fix Current transformer of Ratio 50-100-200/5-5A,IS 2705-1992 with Frequency 50 Hz class B type Phase to earth secondry- 1 winding 110/root 3 V, 50VA complete all as specified and as directed. Model No-ECS22F. |
| 23 | M & L for dismantling 22 KV VCB Panel (01no) (01 I/C panel) to carry out repairs and replacement of worn out spare parts including servicing/ testing/calibration of relays and taking out defective Part of 22 kv VCB 800/1250 Amp of any make type and servicing of VCB by cleaning isolating contacts, moving parts removing dust particles from busbar chamber spout, gear mechanism and moving parts, check and repairing spring charging motor with gear assembly, tighting of nut bolts of entire trolley components all as directed inserting in trolley also checking all mechanical and electrical parts with wiring if any problem rectify it ,after work test High voltage test of VCB pole by Vidar with standard as per specified a) Checking of Mechanically and electrically full operation b) Check and repair/replacement faulty part of VCB c) Full Breakproperly overhauling ,servicing with smooth opertation as Engineer direction d) Mechanism servicing and lubrication e) Control wiring repairing and tightness f) Power connection tightness g) Check vaccume interrupter by HVtest kit or Vidar test kit h) Check contact resistance measurement i) Check insulation resistance test j) High voltage testing of VCB k) Submission of test report in standard format of vacuum circuit breaker. L) Check coil resistance M) Remove moisture of front side of vcb and bus duct back side of vcb with heating all panel by hot air gun n) Busbar rapping by HV tape or HT Sleave Note : 1) All test certificate and defect list provide by contractor 2) If After repair/replace or maintance, any defecte creat in VCB panel than contrector resove defect without any cost till completion date done this work. (3) VCB panel service and any type fault done/resolved by only MSEDL or ABB Company authorised compny/Dealers and its authorised certificate provide by contractors. |
| 24 | M & L for dismantling 22 KV VCB Panel (06 nos) (01 I/C +05 OG) to carry out repairs and replacement of worn out spare parts including servicing/ testing/calibration of relays and taking out defective Part of 22 kv VCB 800/1250 Amp of any make type and servicing of VCB by cleaning isolating contacts, moving parts removing dust particles from busbar chamber spout, gear mechanism and moving parts, check and repairing spring charging motor with gear assembly, tighting of nut bolts of entire trolley components all as directed inserting in trolley also checking all mechanical and electrical parts with wiring if any problem rectify it ,after work test High voltage test of VCB pole by Vidar with standard as per specified a) Checking of Mechanically and electrically full operation b) Check and repair/replacement faulty part of VCB c) Full Breakproperly overhauling ,servicing with smooth opertation as Engineer direction d) Mechanism servicing and lubrication e) Control wiring repairing and tightness f) Power connection tightness g) Check vaccume interrupter by HVtest kit or Vidar test kit h) Check contact resistance measurement i) Check insulation resistance test j) High voltage testing of VCB k) Submission of test report in standard format of vacuum circuit breaker. L) Check coil resistance M) Remove moisture of front side of vcb and bus duct back side of vcb with heating all panel by hot air gun n) Busbar rapping by HV tape or HT Sleave Note : 1) All test certificate and defect list provide by contractor 2) If After repair/replace or maintance, any defecte creat in VCB panel than contrector resove defect without any cost till completion date done this work. (3) VCB panel service and any type fault done/resolved by only MSEDL or ABB Company authorised compny/Dealers and its authorised certificate provide by contractors. |
| 25 | M & L for dismantling 22 KV VCB Panel (03 nos) (01 I/C +02 OG) to carry out repairs and replacement of worn out spare parts including servicing/ testing/calibration of relays and taking out defective Part of 22 kv VCB 800/1250 Amp of any make type and servicing of VCB by cleaning isolating contacts, moving parts removing dust particles from busbar chamber spout, gear mechanism and moving parts, check and repairing spring charging motor with gear assembly, tighting of nut bolts of entire trolley components all as directed inserting in trolley also checking all mechanical and electrical parts with wiring if any problem rectify it ,after work test High voltage test of VCB pole by Vidar with standard as per specified a) Checking of Mechanically and electrically full operation b) Check and repair/replacement faulty part of VCB c) Full Breakproperly overhauling ,servicing with smooth opertation as Engineer direction d) Mechanism servicing and lubrication e) Control wiring repairing and tightness f) Power connection tightness g) Check vaccume interrupter by HVtest kit or Vidar test kit h) Check contact resistance measurement i) Check insulation resistance test j) High voltage testing of VCB k) Submission of test report in standard format of vacuum circuit breaker. L) Check coil resistance M) Remove moisture of front side of vcb and bus duct back side of vcb with heating all panel by hot air gun n) Busbar rapping by HV tape or HT Sleave Note : 1) All test certificate and defect list provide by contractor 2) If After repair/replace or maintance, any defecte creat in VCB panel than contrector resove defect without any cost till completion date done this work. (3) VCB panel service and any type fault done/resolved by only MSEDL or ABB Company authorised compny/Dealers and its authorised certificate provide by contractors. |
| 26 | M & L for dismantling 22 KV VCB Panel (05 nos) (01 I/C +04 OG ) to carry out repairs and replacement of worn out spare parts including servicing/ testing/calibration of relays and taking out defective Part of 22 kv VCB 800/1250 Amp of any make type and servicing of VCB by cleaning isolating contacts, moving parts removing dust particles from busbar chamber spout, gear mechanism and moving parts, check and repairing spring charging motor with gear assembly, tighting of nut bolts of entire trolley components all as directed inserting in trolley also checking all mechanical and electrical parts with wiring if any problem rectify it ,after work test High voltage test of VCB pole by Vidar with standard as per specified a) Checking of Mechanically and electrically full operation b) Check and repair/replacement faulty part of VCB c) Full Breakproperly overhauling ,servicing with smooth opertation as Engineer direction d) Mechanism servicing and lubrication e) Control wiring repairing and tightness f) Power connection tightness g) Check vaccume interrupter by HVtest kit or Vidar test kit h) Check contact resistance measurement i) Check insulation resistance test j) High voltage testing of VCB k) Submission of test report in standard format of vacuum circuit breaker. L) Check coil resistance M) Remove moisture of front side of vcb and bus duct back side of vcb with heating all panel by hot air gun n) Busbar rapping by HV tape or HT Sleave Note : 1) All test certificate and defect list provide by contractor 2) If After repair/replace or maintance, any defecte creat in VCB panel than contrector resove defect without any cost till completion date done this work. (3) VCB panel service and any type fault done/resolved by only MSEDL or ABB Company authorised compny/Dealers and its authorised certificate provide by contractors. |
| 27 | M & L for dismantling 22 KV VCB Panel (03 nos) (01 I/C +02 OG ) to carry out repairs and replacement of worn out spare parts including servicing/ testing/calibration of relays and taking out defective Part of 22 kv VCB 800/1250 Amp of any make type and servicing of VCB by cleaning isolating contacts, moving parts removing dust particles from busbar chamber spout, gear mechanism and moving parts, check and repairing spring charging motor with gear assembly, tighting of nut bolts of entire trolley components all as directed inserting in trolley also checking all mechanical and electrical parts with wiring if any problem rectify it ,after work test High voltage test of VCB pole by Vidar with standard as per specified a) Checking of Mechanically and electrically full operation b) Check and repair/replacement faulty part of VCB c) Full Breakproperly overhauling ,servicing with smooth opertation as Engineer direction d) Mechanism servicing and lubrication e) Control wiring repairing and tightness f) Power connection tightness g) Check vaccume interrupter by HVtest kit or Vidar test kit h) Check contact resistance measurement i) Check insulation resistance test j) High voltage testing of VCB k) Submission of test report in standard format of vacuum circuit breaker. L) Check coil resistance M) Remove moisture of front side of vcb and bus duct back side of vcb with heating all panel by hot air gun n) Busbar rapping by HV tape or HT Sleave Note : 1) All test certificate and defect list provide by contractor 2) If After repair/replace or maintance, any defecte creat in VCB panel than contrector resove defect without any cost till completion date done this work. (3) VCB panel service and any type fault done/resolved by only MSEDL or ABB Company authorised compny/Dealers and its authorised certificate provide by contractors. |
| 28 | M & L for Calibration presses and injector test carried out of 06 VCB panel's all current transformer & potential transformer including of primary/secondary injection by using testing transformer monitored withstanding capacity of CT& PT all as specification as directed a) Cleaning and checking CT primary terminals and remove moisture and connection tightness Primary and secondary b) Checking primary ratio ,polarity,CT knee point Volt.burden check,% error ,winding restance. c) Insulation resistance test with all core D) Relay tripping throw CT primary injection test e)Check control wiring of on relay and meter with tightness f) Power and control connection tightness g) repairing faulty wiring h) Submission of test report in standard format of vacuum circuit breaker. i) Rectify CT proper connection Protection and metering core Note : 1) All test certificate and defect list provide by contractor 2) If After repair/replace or maintance, any defecte creat in VCB panel than contrector resove defect without any cost till completion date done this work. |
| 29 | Supply and fixing in Replacement Indicating lamps R,Y,B of 22 KV VCB Panel complete all as specified and as directed. |
| 30 | Supply and fixing in Replacement Ammeter for HT of 22 KV VCB Panel complete all as specified and as directed. |
| 31 | Supply and fixing in Replacement spring charge motor of 22 KV VCB Panel complete all as specified and as directed. |
| 32 | Supply and fixing in Replacement closing coil of 22 KV VCB Panel complete all as specified and as directed. |
| 33 | Supply and fixing in Replacement Triping coil of 22 KV VCB Panel complete all as specified and as directed. |
| 34 | Supply and fixing in Replacement Tulip contacts (14 Fingers) of 22 KV VCB Panel ) complete all as specified and as directed. |
| 35 | Supply only Bus Bar tape of 22 KV VCB Panel complete all as specified and as directed. |
| 36 | S&F Digital. Ammeter (1 phase) make-elmeasure 1/5A complete all as specified and as directed. |
| 37 | S&F Digital Ammeter ( 3 phase) make-elmeasure 1/5A complete all as specified and as directed. |
| 38 | S&F Digital Multifunction meter with Current/voltage complete all as specified and as directed. |
| 39 | S&F Power Pack- SMPS base with battery backup Input V-230 V AC, Output- 30 V DC. |
| 40 | S &F Space Heater-230vAc,200w as per direction of Engg-in -charge |
| 41 | S &F PT Fuse 22 KV small as per dite and as per direction of Engg-in -charge |
| 42 | S &F Breaker control switch 4 passion all as per direction of Engg-in -charge |
| 43 | S &F coils mounting bracket all as per direction of Engg-in -charge |
| 44 | Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 33 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m. |
| 45 | M&L for Dehumidification of Current Transformers (CTs) in HT switchgear by opening associated VCB, switching OFF, isolating and earthing HT supply, removal of accumulated moisture by controlled heating using hot-air gun/hot-air blower, portable heater/heating lamp, etc., including temperature monitoring, drying of CT insulation, IR testing by suitable Megger, recording of readings, removal of moisture/condensation, restoration of covers and re-energisation of HT supply through VCB, complete as directed by Engineer-in-Charge. Rate to include all labour, tools, equipment, testing instruments, PPE, consumables and safety precautions, ensuring no damage or moisture ingress/condensation to VCB, CTs and associated equipment complete all as specified and as directed by the Engg-in-charge. |
| 46 | S&F MOSIL Spray 320 ,500 ml (Class H Anti-Track Coating) on cleaned and completely dried electrical insulation surfaces of HT switchgear/VCB/CT assemblies, including removal of dust, dirt and moisture, preparation of the surface, application of the coating uniformly by aerosol spray to provide insulation and anti-tracking/moisture-resistant protection, complete all as specified and as directed by the Engg-in-charge. |
| 47 | M& L for shiffting and trasporting of Transformer for existing place to required site by crain incldin disconecion from 22KV HT side cable/jumpers also LT side cable as per direction of E-in-charge Note:- 1)Transfermer Electric conection disconect and after shifting reconection rate demeed including this rate. 2) contractor should be respond within one hours from contacted phonically.3) contractor should complete work with in 8 hrs from intimation by JE/Engr-in-charge failing which contractor will penelty of Rs 5000/- per Hrs is applicable. |
| 48 | M&L for Filteration and dehydration of transformer oil through filteration and dehydration machine by means of continuous circulation of transformer oil through filteration and dehydration machine till dielectric strength of the oil is achieved up to 50 KV for one minute at 2.5 mm gap and oil is completely filtered. Note: 1) Due to Filteration and dehydration of transformer oil required elecric supply(Such as DG set) arrangement by contractor & its rate deemed to including this rate. 2)Oil samples are to collected from top and bottom of oil tank and test results to be submitted for each sample before and after filteration. |
| 49 | Supply and topping up /replacement of new transformer oil of dielectric strength 50 KV at 2.5 mm gap in transformers conforming to IS - 335 / 1983 of various cap installed in various locations .Make of Transformer oil: Power Oil / Indian Oil / AparNote : New Transformer oil in the transformer will be filled in the transformer only after filteration and dehydration of existing transformer oil of the transformer. (b) Transformer oil shall be supplied in sealed barrel with test result and test cert. |
| 50 | M&L for disconnection of electric supply, dismantling the top cover, carefully, taking out old gasket and replacement of the same with and including new cork sheet, cleaning of the conservator tank, breather assembly, replacement of silica gel, oil level looking glass, bushings, gasket, nuts, bolts, washers etc. including connecting up complete for Tranformers 22 / 0.433 kV of different capacities all as directed by Engineer-in-Charge.Note: Spares required for replacement will be measured and paid separately under respective item except 6 mm thick tope cover cork sheet gasket. |
| 51 | M&L for Scrubing of old rusted paint from transformer and preparation of surfaces for fresh painting. Painting of transformer by means of spray painting with two coats of synthetic enamel paint of approved colour of transformer up cap 25 KVA to 315 KVA and writing SM NO/MES NO of the transformer. |
| 52 | All as per item No 52 above but of cap 350 KVA to 1MVA |
| 53 | M&L testing of transformer at site, checking for oil leakages, sealing of the leakages in the main tank / conservator / radiator fins by means of application of sealent or welding / brazing as applicable and directed by engineer-in-Charge at siteNote: Spares required to be replaced will be measured and paid separately under respective item. |
| 54 | Supply only HT Bushings(As per sample). |
| 55 | Supply only LT Bushings ( as per sample) |
| 56 | Supply and fixing Silica gel breather assembly including nipple of suitable size |
| 57 | Supply and fixing Silica gel complete all as specified and as directed. Note: 1) silica gel replaced various location timely to timely where its colour will be change by moisture effects. |
| 58 | Supply and fixing Cork Sheet gasket for HT /LT Bushings 6 mm thick |
| 59 | Supply,& fixing change over switch with enclosure of capacity 100 Amps 415 Volt , 50 Hz four pole type complete all as specified and as directed. |
| 60 | Supply,& fixing change over switch with enclosure of capacity 200Amps 415 Volt , 50 Hz four pole type complete all as specified and as directed. |
| 61 | M&L for Scrubing of existing rusted surface of poles 11 mtr long and prepration and painting of surfaces with one coat of red oxide and two coat aliminium paint fine finishing includign cross arms bracing , clamps and supports complete all as specified and as directed. |
| 62 | M& L for disconnection of electric supply and earthing connections, sealing the ends, transporting the transformer to civil workshop, dis-assembling into various components, lifting the core and winding, dismantling the core, checking the winding if any defect, reassembling / laminating the core, varnishing with insulating varnish of approved / specified thickness, baking / drying out in oven for appropriate time, reassembling the transformer complete with and including replacement of HT/LT Bushings, 6 mm thick cork sheet for bushings, top cover gasket, carrying out HV/LV/ Insulation/ Impedance etc.any test all as specified by Eng-in-charge for satisfactory functioning of transformer, transporting back to MES installation, carrying out precommissioning test, and connecting up complete all for satisfactory functioning of the transformer all as specified and directed by E-in-Charge at site for 22/0.433 KV transformers of capacity upto 315 KVA Note:1) Transformer shifting charges from one place to another place where there is a defective transformer transport rate including this rate.2) Transformer carried out for repair transport rate including this rate.3) Due to transport/shifting any defecte creat ,it will done by contract 4) After repair & refixning ,if any fault again creat this repair transfer due to running this contract ,again repair done by contract no any more additional cost. 5) During the inspection if winding found defective the same rewinding will be measured separately. |
| 63 | All as per Sl Item No 63 herein before but of capacity 400KVA-1000 KVA. |
| 64 | M&L for rewinding of the transformer with suitable gauge of super enamelled copper winding all as specified and directed . |
| 65 | S&F HT 22 KV Barrel fuses of capacity 60 Amps complete all as specified and as directed. |
| 66 | All as per item no 66 but for 30 Amp |
| 67 | All as per item no 66 but for 25 Amp |
| 68 | All as per item no 66 but for 20 Amp |
| 69 | All as per item no 66 but for 15 Amp |
| 70 | All as per item no 66 but for 10 Amp |
| 71 | All as per item no 66 but for 5 Amp |
| 72 | M&L for defect rectification HT/LT cable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, Echo fault locator with high frequency distance calculator etc.including and additional excavation in normal alluvial strata required for exposing the cable fault ; removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of size up to 240 Sq mm 3 core & LT cable of size upto 240 Sqmm. The fault locating equipments will be brought to site within the hours of instruction from Engr-in-Charge as specified Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 19, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 12, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysDec 14, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓