Tender For Replacement Of Damage Main Switch, Mccb, Cables And Pedestal Including Other Allied Works In Various Sectors, Parks And Shopping Centre At U/E Ambala. (Including Three Year Free maintenance And Defect Liability Period Free Of Cost).
Tender Overview
Project Description
Tender for Replacement Of Damage Main Switch, Mccb, Cables And Pedestal Including Other Allied Works In Various Sectors, Parks And Shopping Centre At U/E Ambala. (Including Three Year Free maintenance And Defect Liability Period Free Of Cost).
BOQ
| Sl. No. | Item Description |
| 1 | [13.32]Providing and fixing bolts including nuts and washers complete. |
| 2 | [23.22.1.10]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.10. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 125 to 160 amp, 25 KA |
| 3 | [23.22.2.2]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 2.2. MCCB Enclosure made of Sheet Steel suitable for mounting MCCB of following ratings MCCB up to 250 A FP |
| 4 | [23.22.5.4]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.4. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 40 amp to 63 amp. Double pole |
| 5 | [23.22.8.2]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 8.2. SITC Four pole ON LOAD Manual change over switch in SS enclosure of following Ratings 100 amp 415 volts |
| 6 | [23.27.3]Supply and erection of Godrej Almirah typeM.S. pedestal made of 50 mm x 50 mm x 6 mm angle iron frame with 3.00 mm thick M.S. sheet covering including shutters with suitable hinges and locking arrangement with Godrej type handle including round bars . The top covering should have downward overhang of 75 mm on all sides of pedestal , having two sets of water proof ventilation holes of suitable size on the sides , at top and bottom , each set containing four Nos. holes to discharge the heat produced by the current . The shutters fixed with rubber gasket of superior quality and of suitable size to make it water proof . The pedestal duly painted both inside and outside with two coats of approved paint and primary coat and its legs are embeded upto the entire depth in 1:2:4 cement concrete block , projected 75 mm all around the pedestal and and 200 mm above the ground level including the cost of all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of the work:- 3. M.S. pedestal of size 750 mm wide , 1200 mm high ,300 mm deep and bottom totally open , duly embeded in cement concrete block of size 900 mm x 450 mm x 200 mm above ground level , having a base of size 1050 mm x 600 mm x 250 mm below ground level . 0 0 |
| 7 | [23.8.6]FITTING AND ACCESSORIES 6. Supply and erection 10-60 A single phase A.C. energy metre , LCD display and optical port , with RFID or similar remote reading features with rag bolts on wall/existing pedestal including the cost of rag bolts required to complete the job in all respect with necessary connections and bonding to earth. |
| 8 | [24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. |
| 9 | [24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required. |
| 10 | [24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. |
| 11 | [24.13.18]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 18. 10 Sq mm 4 core (Arm.) |
| 12 | [24.13.32]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 32. 25 Sq mm 4 core (Arm.) |
| 13 | [24.13.48]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 48. 50 Sq mm 4 core (Arm.) |
| 14 | [24.4.3]STREET LIGHT 3. Supply and erection of 32mm dia metre 1.5 m long bracket (B-class) making an angle of 10° to 15° with horizontal plane for mounting street light fitting fixing of GI. bracket on wall with 2 nos. 32 mm x 3 mm thick M.S. clamps including cost of cutting, welding of G.I. pipe complete with cement sand mixture, bolts and nuts etc. including necessary connections. |
| 15 | [24.5.1.1]MISCELLANEOUS ITEMS 1.1. Supply and jointing three core submersible flat cables of approved make with bare bunched copper conductor insulated and sheathed with PVC for submersible pump motors /fountain lights etc with voltage grade 1100 volts marked with IS:694, 1990 including cost of jointing, materials as well as carriage, loading, unloading etc. complete in all respect up to the entire satisfaction of Engineer- in-Charge. Submersible Copper Cable 3 Core 1.5 sqmm |
| 16 | [24.5.2.3]MISCELLANEOUS ITEMS 2.3. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 63/50 mm outer dia/inner dia |
| 17 | NS Item -Supply and Erection of Galvanized steel item (Flat, Angle, Channel) and Nut and Bolts etc. including cutting, bending to the required shape, drilling hole, carriage, loadingunloading complete in all respect up to the entire satisfaction of Engineer-in-charge.(Ex-GST 18%). |
| 18 | S/E and Erection of ACSR PVC Insulated Conductor 30 Sqmm (confirming to IS 398(PART-II)-1976 -1996,4826-1976 , IS: 1521-1972 and IS:1778-1980 with latest amendments and the erection of the same with accessories including stringing and sagging of conductor as well as jointing and binding with insulator at spots complete in all respect up to the entire satisfaction of the engineer –in - charge. |
| 19 | Supply, Installation Testing and Commissioning of LED Street Light Fixture with Wattage range of (45 Watt) with body made of High Pressure Single Piece Die Cast Aluminum Alloy and cover made of PMMA (polymethymethacrylate) having system Lumen)120Ipw with inbuilt Protection against Short Circuit, Miswiring, Over Voltage and Surage Protection of 6 KV. The IP of fixture and Driver Compartment should be IP66 and same for the LED Compartment. The driving current should be ( 700mA with THD ( 5% and PF ). 90 and Operating Voltage between 120-270V and CRI ) 70 and Impact Resistance of IK)05. The specifications as mentioned above should be duly tested and Mentioned in LM79 Report from Govt. Approved NABL Accredited Labrotary and LM80 Report of LED Chip from the Manufacturer required to complete the job in all respect including erection on existing pole for fixing including connection of the same upto the entire satisfaction of Engineer-in-Charges of the work. (Warranty- 3 Years Including Driver against any manufacturing defect) (Including Three Years replacement warranty and three years Free Mtc./Defect Liability Period Free Of Cost). The logo of company should be embossed on the fixture. (Make: Bajaj / Philips / LT/Panasonic/Wipro or equivalent make approved in HSVP). Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender