Housing Urban and Rular Development Local Bodies Closing in 12 days TDR #58603909

Tender For Re-Development Of Botanical Garden Bus Stand Sector 38 (Providing And Fixing Lighting Arrangements, Façade Light, Ev Charging Station, Led Screen And Other Electrical Works) Noida

Issued by Local Bodies · Ghaziabad, Uttar Pradesh
Tender Value
9.45 Crore
Estimated cost
Bid Submission
03 Dec 2026
12 days left
EMD
18.91 Lakhs
Bank guarantee accepted
Document Fee
8260
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Ghaziabad → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Re-Development Of Botanical Garden Bus Stand Sector 38 (Providing And Fixing Lighting Arrangements, Façade Light, Ev Charging Station, Led Screen And Other Electrical Works) Noida

BOQ

Name of Work:- Re-development of botanical garden bus stand sector 38 (Providing and fixing lighting arrangements, Façade Light, EV charging station, LED screen and other electrical works) Noida
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. (Group C) (DSR-25 Item No. 1.8.3)
2Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed pvc conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. (Group-C) (DSR-25 Item No. 1.55.3)
3Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed pvc conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. (DSR-25 Item No. 1.12)
4Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed pvc l conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required (DSR-25 Item No. 1.13)
5Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed pvc conduit as required.
62 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (DSR-25 Item No. 1.8.3)
72 X 6 sq mm + 1 X 6 sq mm earth wire (DSR-25 Item No. 1.14.4)
82 X 10 sq. mm + 1 X 6 sq. mm earth wire (DSR-25 Item No. 1.14.5)
94 X 6 sq. mm + 2 X 6 sq. mm earth wire (DSR-25 Item No. 1.14.9)
104 X 10 sq. mm + 2 X 6 sq. mm earth wire (DSR-25 Item No. 1.14.10)
114 X 16 sq. mm + 2 X 6 sq. mm earth wire (DSR-25 Item No. 1.14.11)
12Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. (DSR-25 Item No. 1.25)
13Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as reqd (DSR-25 Item No. 1.26)
14Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. (DSR-25 Item No. 1.31)
15Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. (DSR-25 Item No. 1.32)
16Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng andfixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (DSR-25 Item No. 1.56)
17Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, SP, MCB, in sheet pvc enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. (DSR-25 Item No. 2.18)
18Supplying and fixing of following sizes of medium class pvc conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (DSR-25 Item No. 1.21)
1920mm (DSR-25 Item No. 1.21.1)
2025mm (DSR-25 Item No. 1.21.2)
2132mm (DSR-25 Item No. 1.21.3)
22Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (DSR-25 Item No. 2.3)
238 way, Double door (DSR-25 Item No. 2.3.2)
24Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) (IP-43) (DSR-25 Item No. 2.4)
256 way (4 + 18), Double door (DSR-25 Item No. 2.4.2)
268 way (4 + 24), Double door (DSR-25 Item No. 2.4.3)
27Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Single pole ) (DSR-25 Item No. 2.10.1)
28Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. (DSR-25 Item No. 2.11)
29Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (40 Amp) (DSR-25 Item No. 2.12.1)
30Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.(63 Amp) (DSR-25 Item No. 2.13.2)
31Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. (DSR-25 Item No. 2.14)
3240 A (DSR-25 Item No. 2.14.2)
3363 A (DSR-25 Item No. 2.14.3)
34Supplying, Installation, Testing and commissioning of Passive Infrared (PIR) technology based occupancy sensor having high performance, non regulating programmable type, suitable for connected load upto 10Amp , for mounting height up to 3 meter and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required. (DSR-25 Item No. 7.1)
35Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
3636 watt panel light (DSR-25 Item No. 8.6.4)
37Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim (15 watt) (DSR-25 Item No. 8.13.3)
38Supply of Totally enclosed 300 mm dia exhaust fan, continously rated highly efficient heavy-dutymotor with ressure die cast aluminium rotor mounted on two ball bearings, Aerodynamically contoured blades handle maximum air with minimum power consumption. Rigid frame with rubber mountings for silent peratins. Expoxy powder coating with specially pretreated components for better resistance to corrosion. Degree of protection against dust & water entry is IP55 as per direction of E/I. (AOR)
39Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. (DSR-25 Item No. 9.1.3)
401200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
41Earthing with GI earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Mtr long etc. with charcoal/ coke and salt as required. (DSR-25 Item No. 5.4)
42Earthing with COPPER earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Mtr long etc. with charcoal/ coke and salt as required. (DSR-25 Item No. 5.6)
43Earthing with G.I. earth pipe 4.5 Mtr long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. (DSR-25 Item No. 5.2)
44Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. (DSR-25 Item No. 5.10)
45Providing and fixing 25 mm X 5 mm GI strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. (DSR-25 Item No. 5.11)
46Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. (DSR-25 Item No. 5.14)
47Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. (DSR-25 Item No. 5.15)
48Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing along with existing surface/recessed conduit/submain wiring/ cable as required. (DSR-25 Item No. 5.7)
49SITC of Outdoor LED System wattage not more than 80W, System efficacy>100LPW (±5%), CCT=3000Kfor uniform illumination ensuring every LED in Luminaire reproducing same color at all time. Fixture should have Integral Driver Fixture should be compatible for DMX512 .Housing should be extruded Aluminium alloy ensuring optimum thermal management , Fixture should be available in diffused optics wi (As per approved concept & Site requirement). Secondary Lens should be of PMMA material & covered with Heat Resistance Toughened Glass / PC cover, Ingress Protection should not be less than IP66, Impact Resistance should be IK08 or more. Total Inbuilt and Additional Surge protection of more than or equal to 6KV Internal + 20KV Additional SPD along with other necessary protections No Load protection, Over voltage protection, Short circuit protection. LED Life should be 50,000 B Hrs@L70 B10, , PF>0.95, Operating voltage range 140-270V AC, Operating ambient Temp 0 to +50°C, Operating Humidity 10-90% Powder coating should be corrosion resistant Nano technology powder coating in Silver grey colour. Standard Power cable should have IP67 connector. Technical Data Sheet, Type test Certificate from In-House NABL accredited Lab should be submitted on request. Manufacturer/OEM emblem/logo should be embossed into the Aluminium housing to allow identification of OEM & traceability till the life of the fixture. Manufacturer/OEM should have complete manufacturing set up in India with In-house capability of Housing, PCB & Driver Manufacturing and In-House NABL Accredited LAB for Electrical & photometry testing. Luminaire should comply with Performance & safety standards IEC 60598/ IEC60950 , IEC 60529, IS 10322-5, IS 161-03/05/06/07, Surge : IEC 61000-4-5, EMC : EN 55015
50SITC of Mono colour GREEN/BLUE/MAGENTA, 20W to 24W with Lumen Package of 50 lm Per Watt minimum In-ground with symmetrical luminaire made up of die-casting, front ring should be made up of stainless steel Minimum 304 grade front ring with silicone black gasket and toughened clear glass diffuser. BEAM shall be within range of 15 to 40 Deg. The ingress protection is IP66 and impact resistance of IK08. The luminaire shall be integrated with high power COB with CRI≥70, SDCM≤3, L70/ B10 @ 60000 Hrs Warranty Five Year
51SITC of 10 W/m encapsulated silcon flex, should be at least IP 67 3000K 24Vdc CRI >80 MacAdam step 3 Beam angle: 120°, Should be equipped with dot less homogenous lighting effect Electronic driver ON/OFF (External driver) MATERIAL CHARACTERISTICSCopper coated strip, Silicone moulded diffuser, End cap, Clip, This luminaire contains built-in LED modules. LED modules are engineered accordingly to the existing regulations of Lumen Maintenance (LM80) and Technical Memorandum (TM21), Lifespan of the luminaire > 50,000 hours at 40°C. Operating ambient temperature range is from -15°C to +50°C. Driver effici >70%, Power factor >0.80, Surge protection 3KV.IES, LM 79, LM 80, & TTC certificates will be provided from NABL accredited lab. Certification: CE Certified, Design Patented/Registered ROHS compliant BIS Certification for Luminaires & Drivers Warranty Five Year
52SITC of Highbay Light, NHB-5-50, 50W, LED, 3000k, IP66 Main Body with integrated heat sink, separate compartment for PCB with lens, should be made of high strength die cast aluminium in single piece using pressure die casting process. Integrated heat sink should ensure Premium thermal management. Extenal front frame to access the optical compartment , also should be made of high strength die cast aluminium. Separate Electronic compartment for control gear also should made made of die cast aluminium. Protection screen in clear tempered glass with high impact resistance. Finish-Pure Polyester powder coating(60microns mininum) in grey Colour. Precise structure and multi-protection silicon gasket ensures the ingress protection-IP 66. Dia - 185mm, Depth - 50mm Power LED Module with high efficacy LED's, on Printed Circuit Board with metal core plate. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection. Lens made of PC/PMMA should offer various type of symmetric optics -60°/90°/120°. Estimated LED Lifetime is > L70 @50,000 hours-Ts=85°C-Supporting LM80 report from LED Manufacturer should be submitted. BIS Certificate with manufacturer name same as brand proposed should be submitted. Sample Should be submitted for concerned engineer incharge for approval of light fixture.
53SITC of Linear Ground Buried Walkover Light, NGB-3-9, 16-20W, LED, 3000K, IP 67, 1M Length The housing in light weight, made of high strength die cast aluminium . Top cover in Stainless Steel. Protection screen in tempered glass with high impact resistance (=>IK08). Burying barrel in SS. Premium thermal management by heat sink integrated on the body. Precise structure and multi-protection silicon gasket ensures the ingress protection- IP67. Dimensions-L-1000mm, W-70mm, H-90mm , weight-4Kg. Power LED Module with high efficacy LED's, on Printed Circuit Board with metal core plate. External Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection. Lens made of PC/PMMA which should offer various type of symmetric optics -10°/15°/30°/45°/60°. Estimated LED Lifetime is > L70 @50,000 hours-Ts=85°C-Supporting LM80 report from LED Manufacturer should be submitted. BIS Certificate with manufacturer name same as brand proposed should be submitted. Sample Should be submitted for concerned engineer incharge for approval of light fixture.
54Supply, Installation, Testing and Commissioning of IP66 Outdoor Fixture of 40W-50W with asymmetric optics made of High efficient PMMA/PC Lens. the fixture comes with 3000K, CRI>70 & Load type 220-240V AC with pf >0.9 & operating temperature of the fixture must be -35°C to +50°C. The Luminaire shall be high quality integrated LED type with maximum system wattage of 40W - 50W with an efficacy not less than 100 lumen/watt (±5%). It's upper square frame made in die cast aluminum, auxiliary and optical compartment can be accessed by tilting the top frame, Bottom frame made in die cast aluminum with four-armed bracket with flange and a hole (Ø 28 mm) for attachment to the support. Frosted basket screen made in polymethylmethacrylate (PMMA) molded in a single piece. Impact resistance: IK06. Pure polyester powder coating in Standard NERI Grey Colour. IP Rating - IP 66.Height – 605mm (±5%), Length - 325mm (±5%), Width - 325mm (±5%),Weight - 6Kg (±5%), Area Exposed to Wind(S) - 0.15 m2Power LED Module with Company /brand name printed on PCB with the metal core plate. LED chips of CREE/NICHIA/OSRAM/LUMILED make shall be used. Colour Rendering Index: Ra > 70. Integral Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection (an additional surge protection device of 10kV also provided in-built the fixture). The luminaire should have refractive lens made of PMMA/PC to provide Type-II/Type-III/ Type-IV optics to for a high quality glare free lighting system. The CCT of 3000K with SDCM of < 5 and CRI >70. PF > 0.9 and THD < 10% & Surge Protection of upto 10KV. The Input voltage of 140-270V. The LED Lifetime shall be 100,000 hours @ Ts 85°C. LM80 report from LED Manufacturer should be submitted. Safety test report as per IEC 60598/IS 10322 from 3rd party NABL should be submitted. LM79 report also should be submitted from UL/UL Authorised/3rd party NABL Laboratory. BIS Certificate with manufacturer name same as brand proposed should be submitted. Sample should be submitted for approval from concerned engineer-in charge.
55SITC of 4M HEIGHT ARCHITECTURAL POST TOP GROOVED POLE 4M high post-top grooved pole made of steel pipe section of 76mm dia. Decorative Base in Steel - Its design starting with dia 260mm for 170mm height, then tapers to 180mm, followed by a cylindrical section of 165mm dia., 365mm Height. It ends with a Top section consist of a Ring of 205mm dia. and 40mm height followed by a taperinng section with Bottom dia. 175mm, Top dia 105mm and Height of 90mm. Total Height of the Base is 700mm. A Steel base plate of 300mm x 300mm is welded at the bottom of the base. additional brakcet This base plate along with foundation bolts of suitable size to be used for ensuring firm grouting into the specially designed RCC foundation. Decorative cast iron flower starting with a dia 102 mm increasing gradually to 160mm and then tapering to a dia 99mm.Total height of cast iron flower is 304 mm & weight is 6.3kgs. Decorative Ring are made of cast iron. All cast iron parts weight mentioned are with +/- 5% tolerance. Entire pole including the decorative elements shall be made to provide pleasing aesthetics as approved by Architect/ Engineer in-charge. After Fabrication, Entire Pole should be shot blasted for the effective adhesion of 3layer coating so as to avoid the corrosion. The pole should be provided with an inbuilt junction box with 1No. 32A Heavy Duty Stud type connector and 1No. 6A SP MCB, at the bottom - the inbuilt box should have a flush door of suitable size. Wind pressure calculation as per IS 875(part-3) & structural calculation report as per EN40 should be submitted to verify the pole strength. Pole & Cast iron parts are painted in 3 layer coating(coating thickness-100 microns minimum) in which 1st layer with etch primer, 2nd layer with epoxy primer & 3rd final layer with PU paint. Sample should be submitted for approval from Architect/ engineer-in-charge.
56Design, fabrication, assembling, wiring and supply, installation, testing and commissioning of Distribution Panels fabricated out of (load bearing member of 2mm and non load bearing member 1.6 mm thick) CRCA sheet steel in cubicle compartmentised modular 3b construction, free standing floor mounted with bottom cable entry, dust and vermin proof IP65 (Type Test report to be submitted) with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided at the bottom of the panels with appropriate stand etc. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.
57Incommer
584-pole 100 Amp,16KA MCCB - 1 Nos.
59100 A 4 Pole power contactor- 1 no
60Astronomical 24 hours time switch (L&T) - 1 no.
61By pass arrangement with toggle switch
62RYB LED indicating Lamp - 1 Set
63Bus Bar - 160 Amp TPN Aluminium - 1 Set
64outgoing
6532A DP MCB -10 nos.
6620A DP MCB -10 nos.
6710A DP MCB -5 nos.
68Soppy md fxing or 16 mm High mast shaft of approved make with rising system hot dip glavanized inside & out side dip,heaving pole sheet thickness 4 mm. Top dia minium 150 mm, Bottom dia 360 mm base plate 32 mm thick suitable for wind velocity as per IS 875 part 3 & having no circumferential weld, with accessories for high mast such as head frame suitable for 6 to 12 luminaries & its control gear boxes 1.5 HP power tool moter, 3 point suspension system with steel wire rope 6 mm dia, double drum winch, including making suitable foundation as per manufature drawing/ site reuiment along with foundation bolts nuts, washers, anchor plates etc completee in all respect. PS No. 21.3.1
69Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminium housing built with toughend glass UV Stablized CC Cover and lences build with manditory dirver set suitable for 170 to 200 Watt. Confirming to IP 66 protection IK-07 and above protection complete in all respect. (PS No. 23.26)CAT-AAA
7020400 to 24000 system lumen high power LED with lences greather then LM/W, power fector PG Greather then 0.95 TSD <10% full load , CRI>70 Potted driver Set in Metal housing (Not Circuitory). Phase to phase Protection at 440V & >300V auto cut and re-start feature, 4 KV internal Surge Protection, with 5 years warranty (CAT-AAA)
71Supply of Labour i.e Electrician/Lineman 8Hrs per day for 1 Months
72Supply and Laying of 90 mm dia (OD 90mm ID 76 mm nominal) size of (DWC) HDPE Pipe ISI Marked along with all accessories like socket, bend, couplers, etc. conforming to IS 14930, Part-II complete for drawing of power cable across the road by drilling 0f 120mm dia at 1 Mtr. below the road lable there by doing the work of providing DWC pipe by trenchless method with filling and cutting jointing rtc complete in all respects.
7311KV HT Panel (2 I/C + 2 O/G)
74Supplying, installation, testing & commissioning of indoor type floor mounted metal clad, 11 KV VCB panel totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS 13118 Internal ARC Tested, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, motorised/manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 phase, 50Hz AC supply with short circuit fault level of 350 MVA, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 630 Amps capacity, breaker featured with mechanical Phase indication Lamp & ON/OFF indicator with hand trip device, spring release coil, shunt trip coil, auxiliary relay (for tripping through RTT of Transformer) and auxiliary switch of 4 NO + 4 NC, suitable capacity power pack and equipped with following switchgears and accessories i/c connections suitable up to 3 x 185 sq.mm XLPE 11KV cable (cable entry from bottom), etc. as required. (Note-Cost of end termination not included in this item)
75a) Incoming- 2 No.Supply, Installation, Testing and Commissioning of indoor type Vacuum Circuit Breaker (VCB) suitable for 11 kV, 3 Phase, 50 Hz AC system, having rated current 630 Amps and minimum breaking capacity 18.4 kA, complete with metal-clad, compartmentalized construction, vacuum interrupter, spring charged motorized operating mechanism with manual and electrical operation, trip-free and anti-pumping features, mechanical ON/OFF and position indicators, including trip and closing coils, auxiliary contacts, interlocking (mechanical and electrical), control wiring, space heater, terminal blocks, earthing arrangement and all standard accessories, conforming to IS 13118 / IEC 62271-100 and IS 3427 standards, including all necessary factory and site testing and commissioning, complete in all respects as required.
76b) 2No. -11KV/110Volts PT Class 0.5 accuracy and 100 VA burden with 1 No. Voltmeter (0-15KV), digital type, slector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer.
77c) 2 No. (0-100A) dual scale Ammeter, digital type, selector switches for ammeters.
78d) 2 No. Microprocessor based numerical relay with O/L, E/F and S/C protection.
79e) 2 No. set of dual core dual ratio 3 CTs 100/50/5/5A of 15VA burden and accuracy Class-1.0 for metering and class 5P10 for protection.
80Busbar
81800 Amp TP high conductivity electrolytic Aluminium Bus Bar
82a) Outgoing - 2 No.Supply, Installation, Testing and Commissioning of indoor type Vacuum Circuit Breaker (VCB) suitable for 11 kV, 3 Phase, 50 Hz AC system, having rated current 630 Amps and minimum breaking capacity 18.4 kA, complete with metal-clad, compartmentalized construction, vacuum interrupter, spring charged motorized operating mechanism with manual and electrical operation, trip-free and anti-pumping features, mechanical ON/OFF and position indicators, including trip and closing coils, auxiliary contacts, interlocking (mechanical and electrical), control wiring, space heater, terminal blocks, earthing arrangement and all standard accessories, conforming to IS 13118 / IEC 62271-100 and IS 3427 standards, including all necessary factory and site testing and commissioning, complete in all respects as required.
83b) 2 Nos. - (0-75A) Ammeters, dual scale digital type & selector switches for Ammeters.
84c) 2 Nos.. - Mircroprocessor based numerical relays with O/L, E/F & S/C protections.
85d) 2 Nos. - set of dual core dual ratio 3 CTs 60/30/5/5A of 15VA burden and accuracy Class-1.0 for metering and class 5P10 for protection.
86e) 1set of 24 V DC power system for control including 2x65 AH SMF Batteries.
87HT PANEL descrive as above.
88TRANSFORMER
89Supply, Installation, Testing & Commissioning (SITC) of 1250 kVA, 11/0.433 kV, 3 Phase, 50 Hz, Outdoor Type Oil Immersed Distribution Transformer, ONAN/ONAF cooled, Copper wound with CRGO core, Dyn11 vector group, suitable for 11 kV Delta/433 V Star system, complete with On Load Tap Changer (OLTC) on HV side with tap range of +5% to -15% in 2.5% steps, AVR relay and RTCC panel for automatic/manual tap changing, conforming to latest IS 1180, IS 2026 and relevant IEC standards. The transformer shall be complete with Conservator, Buchholz Relay, Silica Gel Breather, Magnetic Oil Level Gauge (MOG), Oil Temperature Indicator (OTI), Winding Temperature Indicator (WTI), Pressure Relief Device (PRD), Marshalling Box, HV & LV cable termination arrangement, 3 Nos. 11 kV Polymer Lightning Arresters, separate neutral bushing for earthing, bi-directional rollers, lifting lugs, earthing terminals, rating plate, first filling of transformer oil, foundation channels, grouting, necessary control cables between transformer and HT Panel/RTCC panel, and all standard fittings, accessories, testing and commissioning required for complete and satisfactory operation at site. (DSR-25 Item No. 24.6.3)
90DG SET
91Supplying, Installation, Testing & Commissioning of Unit Rate ‘Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings:
92(A) Diesel Engine:
93Tourbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 0C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications.
94(B) Engine mounted Instrument Panel fitted with and having digital dis Plate for following:
95(i) Start-stop switch with key
96(ii) Water temperature indication
97(iii) Lubrication oil pressure indication
98(v) Battery charging indication and Voltage indication
99(vi) RPM indication
100(vii) Over speed indication
101(viii) Low lubricantion Oil trip indication
102(ix) Engine Running Hours indication
103(x) Fuel Level
104(C) Alternator:
105Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 0C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation.
106(D) Base Frame & Foundation:
107Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.
108(E) FUEL TANK:
109Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications.
110(F) Exhaust System:
111Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor.
112(G) Starting System:
11312V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set.
114(H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications.
115(I) AMF Panel:
116Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software, the panel shall be of DG Set OEM make etc. as per approved by Engineering in charge and including the following:
1171. Suitable numbers and appropriate capacity 4 pole motorised electrically operated draw out with cradle type 3 position ACB/ MCCB with electronic release for O/C & E/F and shunt trip.
1182. Auto/Manual/Test/Off selector switch
1193. Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay).
1204. 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering
1215. Energy analyser unit to indicate current, Voltage( LN & L_L), kW, kVA (Phase & Total), Frequency, KWH, PF.
1226. LED Indicating lamps for load on mains and load on set
1237. Fuse/ MCB for instruments
1248. Battery charger, complete with transformer/ rectifier,D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.
1259.Main supply failure monitor
12610.Supply failure timer
12711.Restoration timer
12812.Control unit with three impulse automatic engine start/stop and failure to start lockout.
12913. Impulse counter with locking and reset facility.
13014.ON/OFF/Control circuit switch with indicator
13115.Audio/Video annunciation fo
132(i)High water temperature
133(ii)Low lubricating oil pressure
134(iii)Engine over speed
135(iv)Engine fails to start
136(v)Full load/maximum load warning
13716.Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories
13817. Maintenance notification based on Engine Run Hour & due date.
13918. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel , interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring.
140As per above description 750 KVA DG set (DSR-25 Item No. 29.1.17)
141Supply and laying of 11KV grade cross linked polyethylene (XLPE) armoured, Unearthed (UE) aluminium conductor cables in the existing RCC/ HUME/ METAL pipe complete as required.(3 core 185 sq. mm)
142Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required : .(3 core 185 sq. mm)
143Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required : (3 core x 185 sq. mm)
144Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.
145150 mm dia (DSR-25 Item No. 5.14.2)
146250 mm dia (DSR-25 Item No. 5.14.3)
147Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade in existing RCC/hume pipe / metal pipe as directed by Engineer in charge compledte in all respects incl. excavation & refilling the armourting of cable shall be connected with earth conductor by clamp etc. (KEI/Polycab, Havell's make)
1483.5C x 300 sq.mm (PS No. 20b.1.19)
1493.5CX 240 sq mm (PS No. 20b.1.18)
1503.5CX25 sq mm (PS No. 20b.1.10)
1514C x 16 sq.mm (PS No. 20b.1.9)
1524C x 10 sq.mm (PS No. 20b.1.8)
153Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
1543.5 x 300 sq.mm (70 mm) (DSR-25 Item No. 11.1.30)
1553.5 x 240 sq.mm (62 mm) (DSR-25 Item No. 11.1.29)
1563.5 x 25 sq.mm (28 mm) (DSR-25 Item No. 11.1.20)
1574 x 16 sq.mm (28 mm) (DSR-25 Item No. 11.1.33)
1584 x 10 sq.mm (25 mm) (DSR-25 Item No. 11.1.32)
159Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
160120 mm dia (DSR-25 Item No. 15.16.3)
16190 mm dia (DSR-25 Item No. 15.16.2)
16263 mm dia (DSR-25 Item No. 15.16.1)
163EV Charging
164Supply, Installation, Testing & Commissioning (SITC) of 240 kW DC Fast Electric Vehicle Charger, outdoor/indoor type, floor mounted, having minimum 240 kW output capacity, suitable for charging Electric Vehicles with dual charging connectors (CCS2 / CHAdeMO / GB/T as applicable), input supply 415V ±10%, 3 Phase, 50 Hz AC, output voltage and current as per EV charging standards, charger efficiency minimum 95%, IP54/IP55 protection class, integrated energy meter, RFID authentication, HMI/LCD touch display, OCPP communication protocol compatibility, Ethernet/4G communication facility, emergency stop push button, overload protection, short circuit protection, earth fault protection, surge protection device (SPD), cooling arrangement, cable management system, charging cables and connectors complete.Item shall include foundation hardware, mounting arrangement, interconnection cabling from charger termination point to charger equipment, earthing, testing, commissioning, integration with CMS/BMS/SCADA (where applicable), complete in all respect as required and as per relevant IS/IEC/MoP/CEA guidelines. The charger shall be with smart charging system provision and shall have software and smart energy meter.Warranty - 3 Years Make:-P2Power
165Supply, Installation, Testing & Commissioning (SITC) of energy management software/system having smart charging system to manage load(charger), Power (MV/LV/Trafo) and energy (various sources energy now and in future like solar, BESS, DG etc.) AOR
166AC WORK
167Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for Dx split unit system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
16815.9 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) (DSR-25 Item No. 31.14.4)
1699.5 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) (DSR-25 Item No. 31.14.2)
170Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. DSR-2025 item No. 1.21
17120mm dia
17225mm dia
17332mm dia
174Hi-WALL UNITS (Dx SPLIT TYPE)
175Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).
1762.0 TR with 5 Star BEE Rating (DSR-25 Item No. 32.2.4)
177MAIN LT
178Design, manufacture supply, installation, testing and commissioning of the following extensible cubicle type indoor mounting, dead front, fully compartmentalised with hinged lockable detachable front & back openable, dust and vermin proof, floor mounting sheet steel clad switchboard fabricated out of 2 mm thick CRCA powder coated sheet steel suitable for use at 415 volts 3 phase 4 wire 50 cycle system and to withstand a symmetrical fault level as specified at 415 volts IEC 61439 Tested. Panels shall be fabricated in easily transportable sections, length, height, depth etc. to match with site condition. All incomer breaker and Bus Couplers shall be interlocked electrically as shown in SLD and specifications.
179The following provisions shall be required to be made in the switchboard as detailed below:
180The Switchboards shall have provision to accommodate all cables from the bottom /top as required.
181All live accessible parts shall be shrouded with 1mm thick polycarbonate/3 mm thick FRP sheet and all equipment shall be finger touch proof. The busbar insulation shall be with heat shrinkable sleeves according to the colour code. SMC shrouds and busbar supports shall be used.
182Galvanised hardware with zinc passivation shall be used in fabrication of Switchboards.
183All rear door of Main LT Panel shall be Almirah type with lockable arrangement.
184Space heater shall be provided with thermostat with 6A MCB as backup protection in each section of Main LT Panel & controlled with 20 A DP MCB, 10 KA.
185Provision of one 6/16 amp socket & compartment lighting for each vertical section of main LT Panel.
186The panel shall display Main Incomers Bus Couplers of Main LT Panel. This line diagram shall be made from luminous non fading materials to glow in dark and each breaker legend shall be provided with bi-colour LED lights to show the Phase indication Lamp & ON/OFF status of the respective feeder (Incomers / Bus couplers)
187All control & power wiring shall be broughtout upto the cable alley in the terminal blocks. 10% extra terminals shall be supplied along with Panel.
188An approval shall be taken for each panel before manufacturing.
189Suitable Aluminium earth bus to be provided throughout the length of Switchboards.
190All indication lamps / illuminated push buttons shall be LED type.
1912A SP MCBs shall be used as backup protections.
192Coil of all motor starters shall be fed from 440 V / 230 V Control Transformer.
193All incomer meters of Main LT Panel shall be multifunction & should have all the electrical parameters like, Voltage, Ampere, KW, KVAR, KWH, PF, Frequency etc. with communication port RS-485.
194All feeders with KWHr meter will be Electronic Dual Reading KWHr meter alongwith appropriate CT's and 1 sq. mm control wiring from each KWHr meter for RS-485 communication till DCU's compartment.
195Provision for providing 230V AC supply for Dual KWHr metering when any or all DG are in operation
196One separate compartment of minimum size 400 x 900 mm for power management system of D.C.U.'s with control wiring as per following specification and control wiring scheme. Control wiring shall be looped from each energy meter till DCU's compartment for sending DCU register change command from data connectivity.
197All CT & PT's shall be cast resin type. Class - 3 CT shall be provided up to 100 amp and above that the CT shall be Class - 1.
198Zone selective Interlocking to be hardwired between incoming & outgoing ACB of main LT Panel.
199All incomer ACBs of Main LT Panel shall be with microprocessor based releases (O/C, S/C & E/F), display of current/voltage and communication port RS-485, however ACB Incomers in other distribution panel and outgoing of Main LT Panel shall be with standard releases.( Ics=100%Icu=Icw )
200All Main LT Panel outgoing ACB shall be with inbuilt earth fault release with CT & MCCB shall be with earth fault module with associated neutral CT for feeder protection, for TP feeders & E/F release for FP feeders.
201All MCCB shall be provided with Rotary handle, door interlocked & lockable in off position of MCCB.
202All Main LT Panel outgoing MCCBs shall be with microprocessor based releases, line load reversibility, Ics = 100% Icu.
203Rating of Neutral bus-bar shall be 50% of phase-bus bar
204All MCB to be C Curve type
205Micro PLC for auto load management & interlocking as per logic specified.
206TRANSFORMER ACB INCOMING (2 NOS 1250 KVA)
2071 NOS 2500 Amps, 50 KA, 440 volt 4-P electrically operated draw out ACB complete with micro processor based tripping mechanism, shunt release (24V DC), earth fault release and inbuilt O/C & SC releases (Microprocessor based) having variable range with time lag facility to achieve discrimination. Required Automatic operation for AMF / Auto Synchronisation & Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / operation scheme indicated in Main Schematic Diagram. The ACB shall have suitable arrangement for termination of Bus duct on incoming side and busbar connection at outgoing side, complete with following for each ACB:-
208Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port for measurement of THD, KVARH KW, KWH, KVAR, PF, V, A, Hz , equivalent to EM6400,with 3 Nos. current transformers of required ratio, 15 VA Class 1.0
2096 nos NO/NC contacts for remote opening & closing.
210Red/Green/Amber Phase indication Lamp & ON/OFF/TRIP indicating lamps with 2A SP MCB backup protection.
2111 set of three phase indicating lamps along with 2A SP MCB backup protection.
212Spring charge& DC supply healthy indicating lamp with 2A SP MCB backup protection.
2131 no. current transformer of 2500/1250/5 dual ratio Class 1.0, 15 VA Burden for PF correction relay.
214Motor wound spring closing mechanism.
215Suitable arrangement to receive incoming Cable
216T-N-C Breaker control switch
217Control MCB, control terminals& wiring as required.
218One auto/manual selector switch
219Undervoltage, Overvoltage for persisted voltage of 105-180% & 20-95% of rated voltage.
220DG ACB INCOMING (2+1 NOS for future provission 750KVA DG SET )
2213 NOS 1250 Amps, 50 KA, 440 volt 4-P electrically operated draw out ACB complete with micro processor based tripping mechanism, shunt release (24V DC), earth fault release and inbuilt O/C & SC releases (Microprocessor based) having variable range with time lag facility to achieve discrimination. Required Automatic operation for AMF / Auto Synchronisation Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / operation scheme indicated in Drawing No.E-14 The ACB shall have suitable arrangement for termination of cable on incoming side and busbar connection at outgoing side, complete with following for each ACB:-
222Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port for measurement of THD, KVARH KW, KWH, KVAR, PF, V, A, Hz , equivalent to EM6400,with 3 Nos. current transformers of required ratio, 15 VA Class 1.0
2236 nos NO/NC contacts for remote opening & closing.
224Red/Green/Amber Phase indication Lamp & ON/OFF/TRIP indicating lamps with 2A SP MCB backup protection.
2251 set of three phase indicating lamps along with 2A SP MCB backup protection.
226Spring charge& DC supply healthy, DG set on, ACB ON indicating lamp with 2A SP MCB backup protection.
227Motor wound spring closing mechanism.
228Suitable arrangement to receive incoming cable of 3 runs of 3.5 x 300 sq. mm \\"Al.\\" XLPE conductor.
229T-N-C Breaker control switch
230Control MCB, control terminals& wiring as required.
231One auto/manual selector switch
232one set of push buttons for DG start, DG Stop Reset & Emergency Stop.
233One 16 amp automatic Battery charger with inbuilt facility of trickle / boost & consisting of :
234DC Ammeter (0-30)V.
235DC Voltmeter.(0-30)Amp
236Charger ON, OFF indications .
2371 Nos 8 Window annunciator for indications & Buzzer.
238Reverse Power relay
239BUSBAR FOR SECTION I, II & III
2403 NOS Electrolytic high conductivity aluminium three phase busbars rated at 4000 amps, & neutral bus-bar shall be with 50% of phase-bus bar of 50KA, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.
241BUS COUPLER
2422 No. 2500 Amps, 50 KA, 440 volt 4-P EDO ACB without release complete with following:
2433 Nos. NO/NC contacts for remote opening & closing
244Red/Green / Amber / Phase indication Lamp & ON/OFF / Trip indicating lamps with 2A SP MCB as backup protection.
245Backup MCB and terminal blocks as required.
246TNC Breaker Control switch
247Required Operation / Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / Operation scheme indicated in Drawing Operation / Interlocking shall be through micro PLC.
248Interlocking:
249Electrical through advance contacts in ACB’s (incomers & Bus couplers) and mechanical (castel key) interlocking should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possible of accidentally approaching two supplies at one bus section.
250OUTGOINGS
2516 No. 400 amps 36 kA 440 volt FP MCCB with overcurrent and short circuit releases and earth fault module complete with following for each feeder:
252Phase indication Lamp & ON/OFF indicating lamps with MCB as backup protection.
253Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port for measurement of KWHr, V, A, equivalent to EM6433 NG, with 3 Nos. current transformers of required ratio, 15 VA Class 1.0
2542 No. 250 amps 36 kA 440 volt FP MCCB with overcurrent and short circuit releases and earth fault module complete with following for each feeder:
255Phase indication Lamp & ON/OFF indicating lamps with MCB as backup protection.
256Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port for measurement of KWHr, V, A, equivalent to EM6433 NG, with 3 Nos. current transformers of required ratio, 15 VA Class 1.0
2572 No. 100 amps 36 kA 440 volt FP MCCB with overcurrent and short circuit releases and earth fault module complete with following for each feeder:
258Phase indication Lamp & ON/OFF indicating lamps with MCB as backup protection.
259Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port for measurement of KWHr, V, A, equivalent to EM6433 NG, with 3 Nos. current transformers of required ratio, 15 VA Class 1.0
260Micro PLC for Auto Load Management (Allen Bradley / Siemens/Mitsubishi) as per Logic mentioned in Drawing, comprising required Auxiliary relays (24V DC, indication lights, Push button, Emergency stop, A/M position switch 1 pole, Battery charger (230V A/C / 24V DC), Batteries, PLC - CPU - 226, 24V DC of Siemens make or equivalent, Digital I/O card, analogue card, 24V DC power supply as required.
261The Auto Synchronization and AMF operation of DG Sets shall be carried out by power command center installed on each DG Set by DG Manufacturer however required coordination and provisions to achieve the same in coordination with PLC based Auto Load Management is included in the scope of work of Panel Manufacturer.
26250 kA fault level continuous Earth Bus shall be part of Panel for full length of panel
2631 set of 32 amp 4P MCB with wiring upto compartment of D.C.U.'s along with 1 mm sq wire for all RS-485 communication port of KWH meter to D.C.U.'s compartment.
264The above Main LT Panel shall be along with following :-
265MDB panel for counter, toilet & other area DB's
266Incoming:
2671 No. of 100 Amp 4P MCCB of 35 KA Breaking capacity with heavy duty solid detachable neutral link & inbuilt overcurrent and short circuit releases.
268Metering for incoming:
2693 nos 100/5A Class 1, 5 VA Burden CT's for metering & 1 nos associated Neutral CT for earth fault module.
270Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port for measurement of PF, V, A, Hz, equivalent to EM6459 NG, with 3 Nos. current transformers of required ratio, 15 VA Class 1.0
271Phase indication Lamp & ON/OFF indicating lamps with MCB as backup protection.
272Bus Bars:
273Electrolytic high conductivity aluminium three phase and neutral busbars rated at 160 amps, 35KA, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.
274Outgoing
27515 Nos. 63 Amp FP MCB of 10 KA breaking capacity.
276MDB panel for counter, toilet & other area DB's as described above complete as required.
277Supply, Installation, testing and commissioning of HYBRID APFC Panel, 3 phase 4 wire, 415 V, 50 Hz AC System for Ambient temperature -5°C to +40°C of following capacity with passive solution of 60% capacity and active solution of 40% capacity,3Phase 4 wire Hybrid Power Factor Correction Solution (with arrangment for neutral current balance) to achieve >0.99 lag and TDDI/THDV values within IEEE recommended limits.APFC should be designed as per IS 16636 Or IEC 61921. The active section and passive section shall work in sync to give optimized output. The degree of protection of passive sectionshould be IP 42, and of active section should be minimum IP 21.The switching device for APFC passive section should be through capacitor duty contactor and for the active compensation system shall be IGBT based with 3 level topology having 12 IGBT in inverter circuit. The active compensationsystem should filter harmonics from 2nd to 50th individual harmonic order and shall be selectable for the entire range. The active compensation system should have feature to improve PF correction and harmonic filtration having response time < 100 Micro second. The hybrid panel shall be indoor type floor mounted free standing totally enclosed, extensible, fabricated in compartmentalised designed made of CRCA sheet steel of 2.0mm thick for framework &
278covers, 3 mm thick for gland plate i/c cleaning & finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section (capacitor and reactor), front and rear access, having suitable current carrying capacity, extensible TPN Aluminium alloy bus bar of high conductivity, DMC/SMC bus bar supports,bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 & 2) APFC Panel shall be in compliance with IS :16636 & CPWD Specifications etc. as per below details.
279(A) IncomersSuitable capacity MCCB/ACB (Upto 300 KVAR, MCCB and above 300 KVAR, ACB ) Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set alongwith required Instruments and accessories with extended rotary handel and door interlocking arrangment. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating.
280(B) Instruments & Indicationsa)For Passive Section :i) 3-Phase current sensing APFC microprocessor relay/controller , advance 12/16 stages (12 stages for over all capacity of panel (active + passive) below 500 KVAR and 16 stages 500 KVAR & above) and having display of Phase wise V, A, PF, Cos-Phi, KW, KVA, KVAR, THD-V , THD-I, harmonics up to 31 level. ii) Auto Manual Selector switch, auxiliary contactorswith timer for delay in manual mode. iii)Digital Multi function meter with LED Display for VA, PF, KW, KVA, KVAR, THD-V & I, Frequency.
281iv)Suitable rating control transformer shall be provided for control and indication circuit. v) All components like control transformer, meter, relay and indicating lamp shall be protected by using suitable rating individual MCB's. vi)Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS/HFFR 1100 V grade, PVC insulated multi stranded copper control wire. vii)Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge.
282b) For Active Section : Dedicated HMI (Human Machine Interface) (Minimum 7 inch display) for controlling and communication and having display of Phase wise V, A, PF, Cos-Phi, KW, KVA, KVAR, THD-V , THD-I, harmonics up to 50th level. Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge.
283400 KVAR (DSR -25 item no. 25.2.4)
284Digital Signage Board
285Design, supply, fabrication, transportation, installation, testing, commissioning of Active LED Videowall System with Pixel pitch 4mm or less, Videowall Size 5000mm (L) x 3000mm (H) ± 5% , should have maintenance from front or back, should have calibrated brightness of 6000nits or more, The brightness of active LED wall of 6000 nits has to be measured by the OEM in presence of Engineer-In-Charge at site using luminance meter which gives output in cd/sqm or nits and not in Lux. Purchase proof and calibration certificate of luminance meter to be submitted. , Should have Contrast ratio of 5000:1 or better, LED weight should be 30kg/m2 or less, Half Gain Horizontal / Vertical Viewing Angle should not be less than H 140 degree / V 140 degree, LED Refresh rate should be 3840Hz or higher, Should have Grey scale processing of 14 - 16bit or higher, LED Cabinet should be Fanless design and material should be Die-cast aluminum / carbon / magnesium alloy, LED Maximum Power consumption should not be more than 650w/m2, Operating Temperature should be -10 to 60 degree Celsius, LED Cabinets and modules should be IP65 front and IP65 back, LED Lamp lifetime should be 100000 hours or more, Compliance Certification on OEM Name CE, FCC, BIS Certifications are mandatory, Led Solution should have Remote health monitoring of LED screen temperature and voltage, Should supports Scheduling and remote management of LED Screen brightness, Over Temperature Protection- Adjust the screen brightness automatically to reduce the LED Screen Temperature, Auto dehumidification-Should be able to remove the Moisture from the Lamps if Screen is switched off for more than a week. LED System should include LED controller with at least 1 or HDMI input and LED outputs as per Resolution, LED controller shall be configure by LAN, LED System includes Smart Outdoor Power distribution as per requirement with Ingress Protection level of IP65, should have Front Door of 2 Hinges with Rack & Locking arrangement, PDU Mounting Should be possible to mount the rack either on a pole or on a wall with options of different mounting types, Power Load of PDU Should be able to support respective LED Wall Size, Should be possible to control the power distribution unit from the Central Control Center over IP, Protection from Short circuit & Over currents. PDU should provide Protection from Voltage surge & Leakage currents, Alarms for over currents & Voltage surge, should provide the Monthly reports for power consumptions, Provide Scheduling of Turn ON/OFF LED Screen Power from the CMS. The LED Solution includes CMS Software which Should have Central web enabled console to push content to monitors. The user interface must be browser-based for both administrator and typical user access. Should support Multi-lingual/ regional language contents as per the location/region of the Digital Signage Screen, Ability to manage display layout/design on individual screen from a centralized location based on clustering. Single screen or split screen with independently controlled frames. Facility of Scrolling ticker to separate multiple display on separate regions on the screen, Must have multiple customizable templates available, must have programmable content that will continue to run, even if the connection to the server is lost, Format Supported: Videos : WMV, MP4,MOV,AVI, MPEG , with all major codecs support Ticker: Live RSS & Static Text Ticker Images: JPEG, PNG, BMP, GIF Documents Files: PDF, Audio: MP3 Web Pages: http, https should be capable of running live streaming content from HTTP Live Streaming (HLS) , MPEG-DASH and RTSP, Ability to display Social Media Feeds i.e. Twitter, Facebook, RSS Feeds., The CMS software system must have the ability to customize delivery of content and scheduling to displays based on specific parameters such as: Grouping of Displays, Individual Display, Day of week, Time of day, CMS Security: Communication and data transfer between media player and server using HTTPS & FTPS/SFTP should be 256 bits encrypted or better. The LED System should include the Media Player to run the content with Operating system Android / Linux / Windows, should support upto 4K resolution, Memory 16GB or more., LED Pole Mounting Structure atleast 5m height RCC Foundation Material Should be mild steel (MS) with antirust paint / GI wall mounted using chemical anchor fasteners of Hilti or equivalent, anchor fasteners diameter should be minimum 12mm or more, Display should not rotate or vibrate with wind/storm in the region and should be fitted with suitable brackets for fixing/aligning Equipment’s, Structure design should withstand air pressure and screen load and should be approved by qualified structure engineers. Structure as per site requirement, 100% maintenance free, design flexibility, no affect by humidity & water durable to impact, no polishing required, including fastener/clamp etc. etc all complete as per detailed tender specification with 3 year warranty.
286Design, supply, fabrication, transportation, installation, testing, commissioning of Active LED Videowall System with Pixel pitch 4mm or less, Videowall Size 1000mm (L) x 2000mm (H) ± 5% , should have maintenance from front or back, should have calibrated brightness of 6000nits or more, The brightness of active LED wall of 6000 nits has to be measured by the OEM in presence of Engineer-In-Charge at site using luminance meter which gives output in cd/sqm or nits and not in Lux. Purchase proof and calibration certificate of luminance meter to be submitted. , Should have Contrast ratio of 5000:1 or better, LED weight should be 30kg/m2 or less, Half Gain Horizontal / Vertical Viewing Angle should not be less than H 140 degree / V 140 degree, LED Refresh rate should be 3840Hz or higher, Should have Grey scale processing of 14 - 16bit or higher, LED Cabinet should be Fanless design and material should be Die-cast aluminum / carbon / magnesium alloy, LED Maximum Power consumption should not be more than 650w/m2, Operating Temperature should be -10 to 60 degree Celsius, LED Cabinets and modules should be IP65 front and IP65 back, LED Lamp lifetime should be 100000 hours or more, Compliance Certification on OEM Name CE, FCC, BIS Certifications are mandatory, Led Solution should have Remote health monitoring of LED screen temperature and voltage, Should supports Scheduling and remote management of LED Screen brightness, Over Temperature Protection- Adjust the screen brightness automatically to reduce the LED Screen Temperature, Auto dehumidification-Should be able to remove the Moisture from the Lamps if Screen is switched off for more than a week. LED System should include LED controller with at least 1 or HDMI input and LED outputs as per Resolution, LED controller shall be configure by LAN, LED System includes Smart Outdoor Power distribution as per requirement with Ingress Protection level of IP65, should have Front Door of 2 Hinges with Rack & Locking arrangement, PDU Mounting Should be possible to mount the rack either on a pole or on a wall with options of different mounting types, Power Load of PDU Should be able to support respective LED Wall Size, Should be possible to control the power distribution unit from the Central Control Center over IP, Protection from Short circuit & Over currents. PDU should provide Protection from Voltage surge & Leakage currents, Alarms for over currents & Voltage surge, should provide the Monthly reports for power consumptions, Provide Scheduling of Turn ON/OFF LED Screen Power from the CMS. The LED System should include the Media Player to run the content with Operating system Android / Linux / Windows, should support upto 4K resolution, Memory 16GB or more., LED Pole Mounting Structure atleast 3m height RCC FoundationMaterial Should be Stainless steel (SS) with antirust paint / GI wall mounted using chemical anchor fasteners of Hilti or equivalent, anchor fasteners diameter should be minimum 12mm or more, Display should not rotate or vibrate with wind/storm in the region and should be fitted with suitable brackets for fixing/aligning Equipment’s, Structure design should withstand air pressure and screen load and should be approved by qualified structure engineers. Structure as per site requirement, 100% maintenance free, design flexibility, no affect by humidity & water durable to impact, no polishing required, including fastener/clamp etc. etc all complete as per detailed tender specification with 3 year warranty.
287Design, supply, fabrication, transportation, installation, testing, commissioning ofActive LED Videowall System with Pixel pitch 2.5mm or less, Videowall Size 610mm (L) x 2000mm (H) ± 5% , should have maintenance from front or back, should have calibrated brightness of 5000nits or more, The brightness of active LED wall of 5000 nits has to be measured by the OEM in presence of Engineer-In-Charge at site using luminance meter which gives output in cd/sqm or nits and not in Lux. Purchase proof and calibration certificate of luminance meter to be submitted. , Should have Contrast ratio of 5000:1 or better, LED weight should be 30kg/m2 or less, Half Gain Horizontal / Vertical Viewing Angle should not be less than H 140 degree / V 140 degree, LED Refresh rate should be 3840Hz or higher, Should have Grey scale processing of 14 - 16bit or higher, LED Cabinet should be Fanless design and material should be Die-cast aluminum / carbon / magnesium alloy, LED Maximum Power consumption should not be more than 780w/m2, Operating Temperature should be -10 to 60 degree Celsius, LED Cabinets and modules should be IP65 front and IP65 back, LED Lamp lifetime should be 100000 hours or more, Compliance Certification on OEM Name CE, FCC, BIS Certifications are mandatory, Led Solution should have Remote health monitoring of LED screen temperature and voltage, Should supports Scheduling and remote management of LED Screen brightness, Over Temperature Protection- Adjust the screen brightness automatically to reduce the LED Screen Temperature, Auto dehumidification-Should be able to remove the Moisture from the Lamps if Screen is switched off for more than a week. LED System should include LED controller with at least 1 or HDMI input and LED outputs as per Resolution, LED controller shall be configure by LAN, LED System includes Smart Outdoor Power distribution as per requirement with Ingress Protection level of IP65, should have Front Door of 2 Hinges with Rack & Locking arrangement, PDU Mounting Should be possible to mount the rack either on a pole or on a wall with options of different mounting types, Power Load of PDU Should be able to support respective LED Wall Size, Should be possible to control the power distribution unit from the Central Control Center over IP, Protection from Short circuit & Over currents. PDU should provide Protection from Voltage surge & Leakage currents, Alarms for over currents & Voltage surge, should provide the Monthly reports for power consumptions, Provide Scheduling of Turn ON/OFF LED Screen Power from the CMS. The LED System should include the Media Player to run the content with Operating system Android / Linux / Windows, should support upto 4K resolution, Memory 16GB or more., LED dual Pole Mounting Structure atleast 2m height RCC Foundation Material Should be Stainless steel (SS) with antirust paint / GI wall mounted using chemical anchor fasteners of Hilti or equivalent, anchor fasteners diameter should be minimum 12mm or more, Display should not rotate or vibrate with wind/storm in the region and should be fitted with suitable brackets for fixing/aligning Equipment’s, Structure design should withstand air pressure and screen load and should be approved by qualified structure engineers. Structure as per site requirement, 100% maintenance free, design flexibility, no affect by humidity & water durable to impact, no polishing required, including fastener/clamp etc. etc all complete as per detailed tender specification. with 3 year warranty.
288Supply, Installation, Testing & Commissioning of of The LED Solution includes CMS Software which Should have Central web enabled console to push content to monitors. The user interface must be browser-based for both administrator and typical user access. Should support Multi-lingual/ regional language contents as per the location/region of the Digital Signage Screen, Ability to manage display layout/design on individual screen from a centralized location based on clustering. Single screen or split screen with independently controlled frames. Facility of Scrolling ticker to separate multiple display on separate regions on the screen, Must have multiple customizable templates available, must have programmable content that will continue to run, even if the connection to the server is lost, Format Supported: Videos : WMV, MP4,MOV,AVI, MPEG , with all major codecs support Ticker: Live RSS & Static Text Ticker Images: JPEG, PNG, BMP, GIF Documents Files: PDF, Audio: MP3 Web Pages: http, https should be capable of running live streaming content from HTTP Live Streaming (HLS) , MPEG-DASH and RTSP, Ability to display Social Media Feeds i.e. Twitter, Facebook, RSS Feeds., The CMS software system must have the ability to customize delivery of content and scheduling to displays based on specific parameters such as: Grouping of Displays, Individual Display, Day of week, Time of day, CMS Security: Communication and data transfer between media player and server using HTTPS & FTPS/SFTP should be 256 bits encrypted or better, CMS also includes the PC with windows 10 Pro or higher, SDD 256GB, RAM 16GB or higher including the peripherals etc all complete specification with 3 year warranty.
289Digital Public address system
290Supply, Installation, Testing & Commissioning of 480W Digital Mixer Amplifier suitable for Public Address (PA), Voice Paging and Background Music (BGM) applications. The amplifier shall be a digital mixer amplifier with a minimum rated output power of 480 Watts RMS, operating on 100–240V AC, 50/60Hz, and supporting 100V line as well as 4 Ohm speaker outputs. It shall have a frequency response of 50 Hz–20 kHz, THD of ≤1%, and Signal-to-Noise Ratio of ≥60 dB. The amplifier shall provide a minimum of 5 mixing inputs, comprising 3 electronically balanced microphone inputs, 1 selectable Mic/Aux input, 2 auxiliary line inputs, and 1 recording output. It shall include phantom power on MIC-1, priority paging with adjustable muting, USB/SD card MP3 player, Bluetooth audio streaming, FM tuner, recording function, and 5-zone speaker selector with All Call facility. The unit shall have independent microphone, auxiliary, and master volume controls, along with Bass and Treble tone controls (±10 dB), LED indications for Power, Signal, Peak, and Protect, and forced-air fan cooling for continuous operation. System also include the 1 Nos Desktop Paging Microphone and 1 Nos 480W Digital Booster Amplifier from same OEM. The System shall be complete with all necessary accessories, mounting hardware, interconnections, testing, commissioning, and documentation as required for satisfactory operation etc as per technical specification.Make : TOA /AUDAC / Bosch
291Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. Make : TOA /AUDAC / Bosch
292Supply, Installation, Testing & Commissioning of 30W Weatherproof Horn Speaker suitable for outdoor Public Address (PA), Voice Paging, Emergency Announcement, and Background Music applications. The speaker shall be designed for 100V distributed speaker line systems, providing high speech intelligibility and reliable outdoor performance etc as per technical specification.Make : TOA /AUDAC / Bosch
293Supply, Installation, Testing & Commissioning of Window Intercom System suitable for communication through glass partitions, acrylic barriers, ticket counters, reception desks, banks, hospitals, airports, and customer service counters. The system shall provide simultaneous full-duplex two-way communication with high speech intelligibility etc as per technical specification.
294Supply, installation, testing & Commissioning of 16AWG 2 Care Speaker Cable (as per actual) etc. all complete. Approved Make: Kordz / Belden / Canare/SST
295Supply, installation, testing & Commissioning of 2 Core Sheilded Audio/Microphone Cable (as per actual) etc all complete. Approved Make: Kordz / Belden / Canare/Bronx
296CCTV Surveillance System
297Supplying Installation Testing and Commissioning of following Channel Network Video Recorder (NVR) with camera licenses to record for all channels having specifications and features etc as mentioned below :
2981) Network Video Recorder Embedded/ Installed OS (Linux) along with Camera Licenses to record per NVR and to provide a live view, storage and simultaneously Multi-channel playback of all IP camera or more and must be ONVIF with minimum support of 384 Mbps incoming Bandwidth.
2992) NVR should support video compressions : H.265 or better, H.264, MJPEG.
3003) Must support 1 channel RCA Input, 2 channel RCA Output for Two-way Talk with G.711U/A, G.711u, PCM, G726 audio compressions.
3014) Intelligent auto power on when power resumes after power outage.
3025) Storage: It should support minimum 8 SATA Slots with 20TB capacity/ Slot and RAID support of RAID 0/1/5/6/10
3036) Connectivity Interface : 2 Nos. x 10/100/1000 Mbps Ethernet Ports, 1x RS485, 1x RS232, 1x eSATA Port7) Backup Interface : Its should have 4 Nosx USB port (2x USB3.0, 2xUSB2.0)8) Video Output Ports: 2x HDMI and 2 VGA9) Alarm Ports: It should have 16/8 Ch In/ Out ports to connect various type of external sensors and output devices like hooter/ Siren etc.
30410) Email & SMS Altert options: Option for SMS/ Email Alerts to minimum 5 designated mobile number for power failure, HDD failure, vandalism, tempring, network disconnection and panic11) Web & Mobile Application: Web, Mobile app ( For iPhone, iPad, Android Phone) for alerts and viewing.12) Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6, UDP, DHCP, DNS, SMTP, UPnP, IP Filter, PPPoE, FTP, DDNS, Alarm Server, IP Search, Multicast, Auto Registration, ONVIF (Profile T, Profile S, Profile G), CGI, SDK and OEM Cloud for remote monitoring without any public IP need.
30513) Standards: CE, FCC, RoHS, BIS Certified 14) Power Supply : Should support AC100-240V, 50/60Hz Power supply.
30615) Operating Condition : -5°C to 50°C, humidity 90% (max) (non-condensing)16) The VMS application shall support all the features & functionalities of the offered cameras.17) VMS should consist Licenses for all channels to record Cameras with General, motion detection, intelligent, alarm and POS recording modes. VMS should be provided with Camera Licenses , with no dependency of VMS licenses by binding with the MAC address of the cameras to achieve the functionality.
30718) The NVR OEM shall be responsible for providing a mobile application compatible with both Android and iOS devices, enabling remote monitoring and playback of cameras/NVR footage.19) The OEM must provide its own DDNS server hosted in India, eliminating the need for a public IP address for remote monitoring over the Internet. 20) Must support Continuous, Alarm, Motion, Instant, Panic Recording Mode21) It should support Resolution: 32MP; 24MP; 16MP; 12MP; 8MP; 5MP; 4MP; 1080p; 720p; D1; CIF; QCIF22) When alarm recording is enabled and an event occurs, you can click the alarm icon on monitoring page to view the alert details. The snapshot function is supported on monitoring and playback page
30823) The Network Video Recorder (NVR) shall be configured to send email whenever a system message is created or an alarm event occurs. The email server shall be a valid SMTP server. Each recipient email address shall be configured to receive any combination of critical, warning, or informationalmessages or alarm notifications. When an alarm occurs, the email message includes the NVR name, time of alarm and a list of camera that is configured to record upon alarm24) It should have Web and GUI in terface.
30925) Built-In Artificial Intelligence: NVR should havebuilt-in AI :-- 2 Channel face detection and recognition, - Minimum 4 Channel perimeter protection, - Minimum 8 Channel Smart Motion Detection
31026) Face Recognition Database Capacity: It should support total Blacklist and Whitelist capacity of Minimum 20,000 Faces or more with Face Detection speed of 12 face images/sec and facility to add Name, gender, birthday, address, credential type, credential No., countries & regions and state to each face image. 27) Face & Human Attributes Search: Search Pictures/ Video by Gender, age group, glasses, expressions, face mask, beard, Top color, top type,hat, bag, age, gender and umbrella.
31128) ANPR Capability: It should support ANPR Camera with License plate, plate color, vehicle body, vehicle model, vehicle logo, calling, seatbelt, vehicle registration location etc vehicle attributes
31229) Alarm Notifications based on: Motion detection, video tampering, video loss, scene changing, PIR alarm, Camera external alarm, Face detection, face recognition, perimeter protection (intrusion and tripwire), ANPR, people counting, stereo analysis, crowd distribution, heat map, Disk Full, Storage Error, IP Conflict and abnormal behavior of fan,cybersecurity exception
31330) Alarm Notification should be linked with Recording, snapshots, Camera external alarm output, buzzer, logs, presets and email.
31431) General AI Based Search: Search Pictures by channel, time, event type, target classification (Fall Detection, People Approach Detection, People No. Exception Detection, People Staying Detection, Violence Detection.
31532) Smart playback function: Should support smart search for the selected area in the video and smart playback to improve the playback efficiency33) VCA (Video Content Analytic): Should support multiple video contented analytics based on camera analytics34) Analytics by NVR: Perimeter protection and face recognation
31664 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16/25/36/64, 2nd screen: 1/4/8/9/16 (DSR-25, item No. 40.11.2)
317Supplying Installation Testing and Commissioning of 5MP/6 MP IP IR Bullet Camera having following specifications, type of lens and features etc :- 1) Type of Camera: Bullet Camera2) Image Sensor: 1/2.8\\" or better progressive Scan CMOS get color image even at night condition3) Signal System: PAL/NTSC4) Minimum Illumination: 0.006Lux@ F1.4, AGC ON, 0 lux with IR or better
3185) Imaging: 1/3s to 1/30000s, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking.6) On Screen Display: Camera should display Camera title, Date & Time in live & recorded video both.7) Signal to Noise Ratio: > 50 dB 8) Lens Type & Focus: as given below.9) Day & Night: True Day & Night High Performance Mechanical IR cut filter with auto switch, IR Source Inbuilt IR LED's with effective distance upto 50 Mtrs integrated IR and 30 Mtrs for colour view in night.
31910) Video Compression (Minimum): H.265 or better, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.72311) Wide Dynamic Range: WDR (120dB or more)12) Digital Noise Reduction: DNR (2D/3D) On/Off13) Streaming: Triple streaming, configurable14) Video Streaming & Frame Rates: Triple streaming , configurable Main stream: 5MP/6MP @25/30 fps, Sub streams: D1@25/30 fps or better15) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser16) Profile Management: User configuration import, export17) Security: User Authentication, Digital Water Marking
32018) Onboard Storage: Camera should support built-in Micro SD/SDHC/SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card.19) Recording Management: Format SD, overwrite, storage management, video to NAS device,
32120) Edge Analytics: Tripwire, Intrusion, Motion Detection21) Alarm Trigger : Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection 22) Alarm Support: It should have 1/1 Alarm In/ Out Port23) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out Port for external Mic. and Speaker (As per site requirement) with G.711U/A / G.711Mu/ AAC/ G.726 audio compreesion
32224) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast,25) System Capability: ONVIF 26) VMS: Camera shall support open source VMS 27) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, account lockout, , video encryption, IP/MAC filtering, HTTPS, trusted upgrade
32328) Ethernet: 1 RJ 45 10/100 Ethernet port29) Power Input: The camera should supportsimultaneous dual power input—12 VDC (via poweradapter) and PoE—to ensure continuous operation inthe event of a failure in one power source.30) Power Requirement: 12VDC/24V DC/PoE(802.3af)/ePoE31) Enclosure: IP67 weather proof, IK10 40.6.1 40.6.2 40.7
32432) Operating Condition: Ambient Temperature:- ()05°C to 50°C, humidity 95% (max) (non-condensing) 33) IR life: 40000 hours or higher34) Video Bit rate: 32 KBPS - 8 MBPS or better35) Standards: BIS with ER, STQC Certified, CE, FCCand RoHS
3255MP/6MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized lens outdoor Bullet Camera. (DSR-25, item No. 40.6.2)
326Supplying Installation Testing and Commissioning of PTZ (Pan,Tilt and Zoom) IP IR Camera having following spcifications and features etc :-
327(1) IP IR PTZ Camera: Motorized PAN TILT ZOOMwith IR (2) Image Sensor: 1/2.8\\" or better progressive ScanCMOS (3)Signal System: PAL/NTSC (4) Minimum Illumination: 0.008 Lux@ F1.6, AGC ON,, 0 lux with IR, or better (5) Imaging: 1/1s to 1/30000s, Auto Gain Control ,White Balance- Auto, Back Light Compensation, Image Rotation, Multi zone Privacy Masking (Upto 24 Area), HLC, Defog, Region Of Interest and EIS features. (6) On Screen Display: Camera should display Camera title, Date & Time in live & recorded video both. (7) Signal to Noise Ratio: > 50 dB(8) Event Notification: Through Relays, E-Mails or FTP (9) Day & Night: True Day & Night High Performance echanical IR cut filter with auto switch, IR Source Inbuilt IR LED's with effective distance. The camera should have IR LED’s and cover distance up to 300 meter or above
32810) Auto Tracking: The camera should be equipped with Deep-learning-based auto tracking function using simultaneously all of the panning, tilting and zooming should be available. When a motion is detected in a registered monitoring area, the camera should track the motion (object) and capture it. (11) Pre/Post Event Buffering: The camera should support atleast of 5 seconds of pre & post eventbuffering. 12) Presets: 300 Presets (13) Video Compression (Minimum): H.265 or better, H.264, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 (14) Wide Dynamic Range: WDR (120dB or more), HLC & BLC (15) Digital Noise Reduction: DNR (2D+3D) On/Off (16) Image Setting: Rotate Mode, ROI ,EIS, Defog, saturation, brightness, contrast, sharpness adjustable through client software or web browser (17) Profile Management: User configuration import, export
32918) Cyber Security: Configuration encryption, AES 256-bit Encryption, Digest, account lockout, video encryption, IP/MAC filtering, trusted boot, trusted upgrade, trusted execution (19) Onboard Storage: Camera should support built in Micro SD/SDHC/SDXC Card slot upto 512 GB . It should be supplied with minimum 128GB Memory. (20) Recording Management: Format SD, overwrite, storage management, video to NAS device, remote archive access via FTP login(21) Edge based Video Analytics & Alarm Trigger: Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection, Tripwire, Intrusion, Object Abandon/ Missing, SMD, Face Detection
330(22) Network Protocol: SFTP, IPv6, IPv4, DNS,NTP,HTTP, HTTPS, SNMP, TCP/IP, PPPoE, NFS, ICMP,DHCP, SMTP, RTSPS. 23) System Capability: ONVIF Profile S, G & T. CCTV Camera OEM should be fulltime member of ONVIF and quoted models should be listed on ONVIF officialwebsite (All the certifications & Credentials should bevalid on the date of technical evaluation). 24) VMS: Camera shall support open source VMS 25) Connectivity: 1x LAN RJ-45 (10/100Base-T) 26) Audio Support: Audio Interface : The camera should have 1/1 Audio In/Out to connect External Mic and Speaker Audio Compression : PCM, G.711U/A, G.711MU, G.726, MPEG2-Layer2, G.722.1
331(27) Alarm In/Out : Alarm In/out- 7/2 Ch In/Out (28) Power Input: The camera should support simultaneous dual power input—DC/ AC (via power adapter) and PoE (802.3af)—to ensure continuous operation in the event of a failure in one power source. (29) Power Requirement: 24 VDC, 2.5 A (± 25%), PoE+ (802.3at) 30) Enclosure & Weather Proof Standard: IP67 weather proof and IK10, TVS 8000V lightning proof, surge protection, voltage transient protection 31) Operating Condition:- Ambient Temperature:- ()05°C to 50°C, humidity 95% (max) (non-condensing) (32) IR life: 40000 hours or higher
332(33) Video Bit rate: 32 KBPS - 8 MBPS or better (34) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS
3335MP IP IR motorized PTZ @25/30fps or better camera, Triple streaming , configurable on resolution:- Main stream: 5MP@25/30 fps Sub streams:1080p@25/30 fps, varifocal lens 3.95mm (±5mm) ~ 177.75mm (±5mm) or better with Automatic & manual Focus Adjustment provisions, 45x Optical zoom and 16x Digital zoom with angle of view H: 65.7°–1.9°V: 39.4°–1.1°D: 73.1°–2.1, PAN Travel:Pan: 0° ~ 360° endless,Manual Pan: 260° /s, Preset : 300° /s, Tilt Travel: Tilt: -20° ~ 90°, auto flip 180°, Manual Tilt: 120° /s, Preset : 200° /s (DSR-25 item No. 40.9.3)
334Supplying, Installation, Testing and Commissioning 4 TB capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications. (DSR-25 Item No. 40.12.1)
335Supply, installation, testing & Commissioning of 55\\" UHD Smart Professional Display with 440-500nits brightness, 1000000:1 Dynamic Contrast Ratio , 24/7 operation, HDMI, DP, DVI-D, RS232, LAN,USa WiFI, Screen share, 8GB inbuilt Memory,IP5X Dust Proof Certified 1 Design, Built-in Speakers, Narrow Bezel etc all complete with 3 year warranty. Approved Make: LG/Sony /Samsung
336Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 nshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required. MAKE : D-LINK / BELDEN / COMMSCOPE / LEGRAND (DSR-25 Item No. 39.17.1)
337Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit asrequired.
33820 mm (DSR-25 Item No. 1.21.1)
33925 mm (DSR-25 Item No. 1.21.2)
340Supplying Installation Testing and Commissioning of 24 port Cat6 Patch Panel loaded. Must be of 1U height with clear label holders and white label with the panel. ) MAKE : D-LINK / BELDEN /COMMSCOPE / LEGRAND (DSR-25 Item No. 39.11)
341SITC of Copper Patch Cords of length 3m (10ft) MAKE : D-LINK / BELDEN /COMMSCOPE / LEGRAND LEGRAND (DSR-25 Item No. 39.12.2)
342Supplying, laying and fixing of 6 Core Multi Mode Optical Fiber Cable MAKE : D-LINK / BELDEN /COMMSCOPE / LEGRAND LEGRAND (DSR-25 Item No. 39.20.1)
343Supply and fixing following port Rack Mount loaded LIU with pigtail, 6 Port MAKE : D-LINK / BELDEN /COMMSCOPE / LEGRAND LEGRAND (DSR-25 Item No. 39.21.1)
344Supply and fixing following port Rack Mount loaded LIU with pigtail, 12 Port MAKE : D-LINK / BELDEN /COMMSCOPE / LEGRAND LEGRAND (DSR-25 Item No. 39.21.1)
345Supplying and fixing Patch Cord of Optical Fiber Patch Cord 2meter. Mode MAKE : D-LINK / BELDEN /COMMSCOPE / LEGRAND LEGRAND (DSR-25 Item No. 39.22)
346Supplying and fixing 24U Rack with 4 inch Castor wheels and front brake Floor Standing Rack MAKE : FSS/Legrand/APC LEGRAND (DSR-25 Item No. 39.24)
347Supply, Installation, Testing & Commissioning of 8 port PoE Layer 2 Network Switch with PoE Support of 130W or higher with each copper port supporting 802.3at PoE+, At least 8 X RJ-45 Gigabit Ethernet Ports and additional 2 X 1G SFP Ports with non-blocking architecture by having Switching capacity of minimum 20Gbps and packet forwarding rate of 14Mpps or higher, 8K MAC table. MAKE : NETGEAR / D-LINK / ALCATEL LEGRAND (DSR-25 Item No. 39.1.1)
348Supply, Installation, Testing & Commissioning of 24 port PoE Layer 2 Network Switch with PoE Support of 370W or higher with each copper port supporting 802.3at PoE+ min. LEGRAND (DSR-25 Item No. 39.3.1)
349Supplying and fixing Outdoor Pole/ Wall mount 6U Rack, IP55, Front Door with Filter, Louver & Unique key Lock. 3 Socket PDU 5Amp - 1 No. Self adhesive thermal foam from inside. Hood For Air Inlet at front side.1U Cantilever Tray 250mmDepth, Gasket. etc complete as required. MAKE: FSS/Legrand/APC LEGRAND (DSR-25 Item No. 39.26)
350SITC of splicing of optical fiber, fiber optic connectors, SFP, junction boxes, patch cords, pigtails, and all other required accessories for complete CCTV system connectivity and commissioning, including testing and termination.
351Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS ontainer) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion(ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute. Operating temperature 0 to 40 0C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short
352circuit, battery deep discharge , 10 KV surge. Display for watt/VA,Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be with IGBT Based Inverter Technology, Communication RS232/ RS485/ SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accessories are inclusive in the cost. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc (10KVA)(DSR-25, item No. 26.1.4)
353Supplying and fixing 42U Rack with 6 inch Castor wheels and front brake Floor Standing Rack with Main Frame Pillar of 1.6mm CRCA Sheet with removable side panels, L- Shape adjustable ertical Mounting Rail of 2mm with 'U'Marking completely knocked-down condition (CKD) Shape, fitted with 4 number cooling fans, inimum 8nos two line cable entry/exit provision at top and bottom with rubber protection, Front door 5mm Toughened Glass with MS frame or MS perforated with lock, Rear MS vented or erforated door, Powder coated Color- RAL- 7035 or black, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required. (DSR-25, item No. 39.25) Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58603909
AUTHORITY Local Bodies
TENDER VALUE 9.45 Crore
LAST DATE 03-12-2026
Authority
Authority Name New Okhla Industrial Development Authority
Work Description Tender for Re-Development Of Botanical Garden Bus Stand Sector 38 (Providing And Fixing Lighting Arrangements, Façade Light, Ev Charging Station, Led Screen And Other Electrical Works) Noida
Basic Detail
Tender No 11/GM(Civil)/S M.(E/M)-III/2026-27
Bidding Type Tender
Location
City Ghaziabad
State Uttar Pradesh
Key Dates
Publish Date 19 Nov 2026
Submission Date 03 Dec 2026
Open Date 04 Dec 2026
Finance
Tender Value 9.45 Crore
Tender Fee 8260
EMD 18.91 Lakhs
Exemption Not Available
Document List
02c4d09c-90e4-43a6-900e-6bb41189c631.html
BOQ_2297682.xls
C.xls
TD.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 19, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 03, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 12 days
Dec 04, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 13 days

Tender Documents

Download All (ZIP) ↓
html

02c4d09c-90e4-43a6-900e-6bb41189c631.html

xls

BOQ_2297682.xls

xls

C.xls

pdf

TD.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender