Tender For Narnaul Town (2Nd And 3Rd W/W):- Construction Of Water Works Structures, R/W P/Stn. And B/Stns. At Various Location Including Wtp, Reinforced Cement Concrete S/S Tanks, Sump Well, Boundary Wall, Clear Water Tank, Pump Chamber, repair maint
Tender Overview
Project Description
Tender for Narnaul Town (2Nd And 3Rd W/W):- Construction Of Water Works Structures, R/W P/Stn. And B/Stns. At Various Location Including Wtp, Reinforced Cement Concrete S/S Tanks, Sump Well, Boundary Wall, Clear Water Tank, Pump Chamber, repair maintenace Lines, Truss Bridge, Pumping Machinery, D.G Set, Electric Transformers, House Connections And Laying The Distribution Pipe Lines Etc. O And M Of Complete Scope Of Work Mentioned In Dnit During Defect Liability Cum Maintenance Period Of 6 Year After Successful Completion Of 3 Months Trial Run Complete In All Respect.
BOQ
| Sl. No. | Item Description |
| 1 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd (50 Sqmm size) |
| 2 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make:Finolex / Havells / RR Cables. (35 Sqmm size) |
| 3 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make:Finolex / Havells / RR Cables. (70 Sqmm size) |
| 4 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make:Finolex / Havells / RR Cables. (240 Sqmm size) |
| 5 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set forClear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 4500 LPM x 25.00 M (For MBS-2 ITI) |
| 6 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 17.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For Mini Secretriat B/Stn.) |
| 7 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 20 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For ITI B/Stn. For supply) |
| 8 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 42.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At MBS-2 ITI for B/Stns.) |
| 9 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 25 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For Heera nagar B/stn. ) |
| 10 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 20 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For Old mandi B/Stn.) |
| 11 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 15 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For Devsthan B/Stn.) |
| 12 | `RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 4600 LPM x 15.00 M (At 3rd exist. W/W Naseebpur) |
| 13 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 27.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At 3rd exist. W/W Naseebpur) |
| 14 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set forClear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 2500 LPM x 40.00 M ( for Hafed B/stn.) |
| 15 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 37.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For Hafed B/Stn.) |
| 16 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 20 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For Fozdar colony B/Stn.) |
| 17 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For Bawripur B/Stn.) |
| 18 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set forClear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 2900 LPM x 45.00 M ( for Bawripur B/stn.) |
| 19 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 15 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For Kirarodh afgan B/Stn.) |
| 20 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set forClear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 4500 LPM x 45.00 M ( for old court B/stn.) |
| 21 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 75 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At Old cout B/stn.) |
| 22 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 42.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For B/Stn. No.23) |
| 23 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 42.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For B/Stn. No.24) |
| 24 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Clear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 3400 LPM x 45.00 M (For B/Stn. No.15) |
| 25 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 57.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For B/Stn. No.15) |
| 26 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 52.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At 2nd W/W for exist WTP-1) |
| 27 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 20 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At 2nd W/W for Prop. WTP-3) |
| 28 | `RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 9200 LPM x 15.00 M (At 2nd W/W for exist. WTP-1) |
| 29 | `RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 21700 LPM x 20.00 M (At R/W P/Stn. for 2nd and 3rd W/W) |
| 30 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 162.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At R/W P/Stn. for 2nd and 3rd W/W) |
| 31 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Clear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 9800 LPM x 45.00 M (At 2nd W/W for B/Stn.) |
| 32 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 165 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At 2nd W/W for B/Stn.) |
| 33 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 25 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At Ganesh Colony B/Stn.) |
| 34 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Clear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked`4600 LPM x 40.00 M (For Distt. Library B/stn.) |
| 35 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 70 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For B/Stn. No.13) |
| 36 | Less credit for old bricks bats @ 40% of item 5.7.4 plus 14.70 = 446.77 x 40 % = 178.71 cum |
| 37 | Less credit for old Good bricks @ 60% of item 5.7.4 plus 14.70 = 446.77 x 60 % = 268.10 cum (480 bricks per cum : 128670 bricks) |
| 38 | Less credit for old Good bricks @ 60% of item 5.7.4 = 172.50 x 60 % = 103.50 cum (480 bricks per cum : 49680 bricks) |
| 39 | Less credit for old bricks bats @ 40% of item 5.7.4 = 172.50 x 40 % = 69 cum |
| 40 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 45 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (At 3rd exist. W/W Naseebpur for w/w zone) |
| 41 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for motor rating of 47.50 HP. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2 mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200% while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485 Modbus RTU, Ambient Temperature -Heavy Duty: -10 ~ 50 deg C Normal Duty: -10 ~ 40 deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3 class 3C3, Application Humidity Below relative humidity 95% RH (no condensation) Altitude 0 to 1,000 m Without deration 1,001 to 4,000 m With deration of 1% per rise in 100 m, Vibration Up to 9.8 m/sec2 (1.0 G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200% at 0.5Hz in Sensorless Vector Control and 150% at 3Hz in V/F, Frequency Control Range 0 to 400Hz in V/F, 0 to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2 / Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required.(At 3rd exist. W/W Naseebpur for B/Stn.) |
| 42 | `CLEAR WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Clear water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked` 4200 LPM x 30.00 M (At 3rd exist. W/W Naseebpur for B/Stn.) |
| 43 | Less credit for old Good bricks @ 60% of item 5.7.4 = 154.59 x 60 % = 92.80 cum (480 bricks per cum : 44523 bricks) |
| 44 | Less credit for old bricks bats @ 40% of item 5.7.4 = 154.59 x 40 % = 61.84 cum |
| 45 | Credit of existing outlived pump sets. (At 2nd, 3RD W/W, MBS ITI and its B/Stn.) At 2nd water works for WTP-1 (R/W pump) :- 27.5 HP (2 no.)At 2nd water works for B/Stns. (C/W pump) :- 85 HP (2 no.)At MBS-2 for B/Stns. (C/W pump) :- 32.5 HP (2 no.)At MBS-2 for ITI B/Stns. (C/W pump) :- 17.5HP (2 no.)At 3rd water works (R/W pump) :- 15 HP (2 no.)At 3rd water works for W/W zone(C/W pump) :- 45 HP (2 no.)B/Stn. - 11 (Devsthan) :- 15 HP (2 no.)B/Stn. - 12 (Old court) :- 30 HP (2 no.)B/Stn. - 13 (Distt. Libraray) :- 40 HP (3 no.)B/Stn. - 16 (Hafed-II) :- 30 HP (2 no.)B/Stn. - 19 (Bawripur) :- 15 HP (2 no.) |
| 46 | Credit of existing outlived Panel Boards and cables etc. (At 2nd, 3RD W/W, MBS ITI and its B/Stn.) At 2nd water works for WTP-1 (R/W pump) :- 27.5 HP (2 no.)At 2nd water works for B/Stns. (C/W pump) :- 85 HP (2 no.)At MBS-2 for B/Stns. (C/W pump) :- 32.5 HP (2 no.)At MBS-2 for ITI B/Stns. (C/W pump) :- 17.5HP (2 no.)At 3rd water works (R/W pump) :- 15 HP (2 no.)At 3rd water works for W/W zone(C/W pump) :- 45 HP (2 no.)B/Stn. - 11 (Devsthan) :- 15 HP (2 no.)B/Stn. - 12 (Old court) :- 30 HP (2 no.)B/Stn. - 13 (Distt. Libraray) :- 40 HP (3 no.)B/Stn. - 16 (Hafed-II) :- 30 HP (2 no.)B/Stn. - 19 (Bawripur) :- 15 HP (2 no.) |
| 47 | Less credit for old Good bricks @ 60% of item 5.7.4 = 26.44 x 60 % = 15.86 cum (480 bricks per cum : 7615 bricks) |
| 48 | Less credit for old bricks bats @ 40% of item 5.7.4 = 26.44 x 40 % = 10.58 cum |
| 49 | Less credit for old Good bricks @ 60% of item 5.7.4 = 7.95 x 60 % = 4.77 cum (480 bricks per cum : 2289 bricks) |
| 50 | Less credit for old bricks bats @ 40% of item 5.7.4 = 7.95 x 40 % = 3.18 cum |
| 51 | Less credit for old Good bricks @ 60% of item 5.7.4 = 13.74 x 60 % = 8.25 cum (480 bricks per cum : 3959 bricks) |
| 52 | Less credit for old bricks bats @ 40% of item 5.7.4 = 13.74 x 40 % = 5.50 cum |
| 53 | Boring /excavation including pit making at entry and exit point to the precise dimensions for the Launch of the specialized Auger boring machine in normal soil condition but not in Rock/Bolders/ any underground utility like foundation, water supply line coming in alignment or other underground obstructions complete in all respect including caution sign boards, signals, watching fencing, site clearance etc.Including provision for probe radar survey to check any underground obstruction before finalizing the alignment.For 250 mm i/d MS casing pipe. (For Kiraroddh Afgan B/Stn.) |
| 54 | Providing and insertion of 250 mm i/d M.S. casing pipe 10 mm thick (Fe-330 grade) fabricated as per IS: 3589 of 1991 from steel plates conforming to IS 2062 including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182 and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88 to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work complete in all respect as per specification given in DNIT.250 mm i/d MS casing pipe (For Kiraroddh Afgan B/Stn.) |
| 55 | Providing and insertion of 150 mm i/d M.S. carrier pipe 10 mm thick (Fe-330 grade) fabricated as per IS: 3589 of 1991 from steel plates conforming to IS 2062 including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182 and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88 to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work complete in all respect as per specification given in DNIT.Providing concrete block 1:1-1/2:3 on both ends to plug the space between casing and carrier pipe including all material and labour complete in all respect to the entire satisfaction of Engineer in charge150 mm i/d MS carrier pipe (For Kiraroddh Afgan B/Stn.) |
| 56 | Boring /excavation including pit making at entry and exit point to the precise dimensions for the Launch of the specialized Auger boring machine in normal soil condition but not in Rock/Bolders/ any underground utility like foundation, water supply line coming in alignment or other underground obstructions complete in all respect including caution sign boards, signals, watching fencing, site clearance etc.Including provision for probe radar survey to check any underground obstruction before finalizing the alignment.For 250 mm i/d MS casing pipe. (For Heera Nagar B/Stn.) |
| 57 | Providing and insertion of 250 mm i/d M.S. casing pipe 10 mm thick (Fe-330 grade) fabricated as per IS: 3589 of 1991 from steel plates conforming to IS 2062 including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182 and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88 to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work complete in all respect as per srecification given in DNIT.250 mm i/d MS casing pipe (For Heera Nagar B/Stn.) |
| 58 | Providing and insertion of 150 mm i/d M.S. carrier pipe 10 mm thick (Fe-330 grade) fabricated as per IS: 3589 of 1991 from steel plates conforming to IS 2062 including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182 and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88 to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work complete in all respect as per srecification given in DNIT.Providing concrete block 1:1-1/2:3 on both ends to plug the space between casing and carrier pipe including all material and labour complete in all respect to the entire satisfaction of Engineer in charge150 mm i/d MS carrier pipe (For Heera Nagar B/Stn.) |
| 59 | Boring /excavation including pit making at entry and exit point to the precise dimensions for the Launch of the specialized Auger boring machine in normal soil condition but not in Rock/Bolders/ any underground utility like foundation, water supply line coming in alignment or other underground obstructions complete in all respect including caution sign boards, signals, watching fencing, site clearance etc.Including provision for probe radar survey to check any underground obstruction before finalizing the alignment.For 400 mm i/d MS casing pipe. (For Old Mandi B/Stn.) |
| 60 | Providing and insertion of 400 mm i/d M.S. casing pipe 10 mm thick (Fe-330 grade) fabricated as per IS: 3589 of 1991 from steel plates conforming to IS 2062 including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182 and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88 to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work complete in all respect as per srecification given in DNIT.400 mm i/d MS casing pipe (For Old Mandi B/Stn.) |
| 61 | Providing and insertion of 250 mm i/d M.S. carrier pipe 10 mm thick (Fe-330 grade) fabricated as per IS: 3589 of 1991 from steel plates conforming to IS 2062 including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182 and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88 to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work complete in all respect as per specification given in DNIT.Providing concrete block 1:1-1/2:3 on both ends to plug the space between casing and carrier pipe including all material and labour complete in all respect to the entire satisfaction of Engineer in charge250 mm i/d MS carrier pipe (For Old Mandi B/Stn.) |
| 62 | Less credit for old steel bars from dismantled OHSR @ 70 kg (Cum) = 147.64 x 70 = 10334.94 kg |
| 63 | Less credit for old steel bars from dismantled OHSR @ 70 kg (Cum) = 210.82 x 70 = 14757.42 kg |
| 64 | Less credit for old Good bricks @ 60% of item 5.7.4 = 21.99 x 60 % = 13.19 cum (480 bricks per cum : 6333 bricks) |
| 65 | Less credit for old bricks bats @ 40% of item 5.7.4 = 21.99 x 40 % = 8.80 cum |
| 66 | Less credit for old steel bars from dismantled structures @ 70 kg (Cum) = 6.00 x 70 = 420 kg |
| 67 | Less credit for old steel bars from dismantled structures @ 70 kg (Cum) = 11.75 x 70 = 822.50 kg. |
| 68 | Less credit for old steel bars from dismantled structures @ 70 kg (Cum) = 1.16 x 70 = 81.20 kg. |
| 69 | Less credit for old steel bars from dismantled structures @ 70 kg (Cum) = 3.55 x 70 = 248.50 kg. |
| 70 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, SolidCopper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make:Finolex / Havells / RRCables. (120 Sqmm size) |
| 71 | Operation and maintenance of Complete Scope of work mentioned in DNIT during 6 Year of Defect Liability cum maintenance Period after successful completion of 3months trial run period (will be charged to the A/mtc.estimate) complete in all respects as per approved NIT. |
| 72 | HSR Itmes(As per uploaded DNIT) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 22 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 25 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender