Housing Urban and Rular Development Government Departments Closing in 12 days TDR #58570607

Tender For Electrical & Allied Work For Additional Classrooms & Upgradation Of Existing Building At Lal Bahadur Shastri Government Post Graduate College, Halduchaur (Nainital).

Issued by Government Departments · Nainital, Uttarakhand
Tender Value
1.76 Crore
Estimated cost
Bid Submission
01 Dec 2026
12 days left
EMD
3.54 Lakhs
Bank guarantee accepted
Document Fee
5900
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Nainital → Uttarakhand
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Electrical & Allied Work For Additional Classrooms & Upgradation Of Existing Building At Lal Bahadur Shastri Government Post Graduate College, Halduchaur (Nainital).

BOQ

Name of Work:- Electrical & Allied work for additional classrooms & Upgradation of Existing building at Lal Bahadur Shastri Government Post Graduate College, Halduchaur (Nainital).
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
2Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
3Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loopearthing as required.
4Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
5Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
6Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire (For Circuit Wiring & Light Plug Wiring)
7Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 6 sq. mm + 1 X 6 sq. mm (For Single Phase DB. From Sub Panel to DB)
8Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 6 sq. mm + 2 X 6 sq. mm (For Three Phase DB. From Sub Panel to DB)
9Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 10 sq. mm + 2 X 6 sq. mm (For Three Phase DB. From Sub Panel to DB)
10Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 16 sq. mm + 2 X 16 sq. mm (For Three Phase DB. From Sub Panel to DB)
11Supplying and fixing following Modular base & cover plate one existing modular metal boxes etc. as required 6 Module
12Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required 5/6 A switch
13Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required 3 pin 5/6 A socket outlet
14Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required 15/16 A Switch
15Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required 6 pin 15/16 A Socket outlet
16Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
17Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
18Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
19Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
20Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
21Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
22Supplying and fixing brass batten/ angle holder including connection etc. as required.
23Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.1 or 2 Module (75mmX75mm)
24Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet
25Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.TV antenna socket outlet
26Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Bell push
27Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm
28Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm
29Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, Unarmored Telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
30Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 2 Pair
31Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
32Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.1 run of cable
33Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm
34Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
35Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep
36Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes.
37Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing.
38Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
39Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
40Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
41Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)8 way , Double door
42Supplying and Fixing Following way, Horizontal Type Three Pole and Neutral, Sheet Steel, MCB Distribution Board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).6 Way (4 + 18), Double Door
43Supplying and Fixing Following way, Horizontal Type Three Pole and Neutral, Sheet Steel, MCB Distribution Board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).8 Way (4 + 24), Double Door
44Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 A
45Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 A
46Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 A
47Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as Required. 25 A
48Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as Required. 40 A
49Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as Required.63 A
50Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required Above 35 sq. mm and upto 95 sq. mm
51Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 95 sq. mm (38mm)
52Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm width X 50 mm depth X 1.6 mm thickness
53Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness
54Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.225 mm width X 50 mm depth X 1.6 mm thickness
55Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.450 mm width X 50 mm depth X 2.0 mm thickness
56Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100 mm width X 50 mm depth X 1.6 mm thickness
57Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness
58Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.225 mm width X 50 mm depth X 1.6 mm thickness
59Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.450 mm width X 50 mm depth X 2.0 mm thickness
60Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm width X 50 mm depth X 1.6 mm thickness
61Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150 mm width X 50 mm depth X 1.6 mm thickness
62Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.225 mm width X 50 mm depth X 1.6 mm thickness
63Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.450 mm width X 50 mm depth X 2.0 mm thickness
64Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness
65Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
66Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
67Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Cross member\\"(galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 mm width X 50 mm depth X 2.0 mm thickness
68Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Reducer\\" (galvanisation not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
69Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Reducer\\" (galvanisation not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
70Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Reducer\\" (galvanisation not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
71Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Reducer\\" (galvanisation not less than 50 microns) with perforation not more than17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 mm width X 50 mm depth X 2.0 mm thickness
72Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 150 AMP BUS BAR : 150 AMP, 440 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature. OUT GOINGS : 1 No 40 AMP 4P MCB (Light DB 1) ,1 No 40 AMP 4P MCB (Light DB 2) 1 No 63 AMP 4P MCB (Power DB 1)1 No 63 AMP 4P MCB (Power DB 2)4 No 63 AMP 4P MCB (Spare) Complete panel as above and complete
73Providing and Supplying of LED Batten 20 Watts 1150 mm
74Providing and Supplying of 9W Led Bulb With Battery-Is:16102, Warranty for free replacement 1 year
75Providing and Supplying of 12W Warm White Ceramic Circular LED Surface Ceiling Light
76Providing and Supplying of Aluminium Wall Fan 2 year Warranty
77Providing and Supplying of Exhaust Fan 300 mm
78Providing and Supplying of 2 Ton 5 Star, Inverter AC Wall Mount Split AC
79Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :25 mm dia
80Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :50 mm dia
81Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :100 mm dia
82Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :150 mm dia
83Excavating trenches of required width for pipes, cables, etc, including excavation for sockets, depth upto 1.5 m, including getting out the excavated materials, returning the soil as required in layers not exceeding 20 cm in depth, including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, within a lead of 50 m : 2.13.1 Ordinary rock 2.13.1.2 Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia
84Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
85100 mm dia
86Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
87100 mm dia
88Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
89Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : 150mm dia
90Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 40 m
91Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Stainless Steel (Grade 304)
92Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Stainless Steel (Grade 304)
93Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 4 way - 150 mm dia M.S. Pipe 2 way-100 mm dia M.S. Pipe
94Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 100mm dia
95Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel
96Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
97Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 1000mm
98Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : 150mm dia
99Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : Pendent Sprinkler
100Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 100mm dia
101Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. (d) Suitable cement concrete foundation duly plastered and with anti vibration pads.900 lpm at 35 m Head
102Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
103Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 150mm dia
104Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
105Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
106Providing & fixing 25mm x 5mm G.I. strip on surface or in recess for connections etc. as required.
107Providing and Fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing alongwith existing surface/ recessed conduit/ submain wiring/ cable as required.
108Supplying, fabricating and installing following size of perforated painted with powder coating M.S. cable trays,with perforation not more than 17.5%, in covenient section, joined with connectors, suspended from the ceiling with MS suspenders including bolts & nuts, painting suspenders etc. as required. 100 mm width X 50 mm depth X 1.6 mm thickness
109Supplying, fabricating and installing following size of perforated painted with powder coating M.S. cable trays,with perforation not more than 17.5%, in covenient section, joined with connectors, suspended from the ceiling with MS suspenders including bolts & nuts, painting suspenders etc. as required. 300 mm width X 50 mm depth X 1.6 mm thickness
110Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
111Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
112Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4x16 sqm mm (28mm)
113Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 4 x 1.5 Sq. mm
114Providing & Supplying Extinguisher Fire Carbondioxide 4.5 kg,duly charged, Portable and complete as per defence specification
115Providing & Supplying ceasefire Wall Mounted Automatic Fire Extinguisher Powder Based (as per IS 4308 ) Automatic
116Providing & Supplying FIREMAN'S AXE 3 kg (Fire suppression hand tools)
117Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required.
118Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required.
119Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
120Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
121Supplying and fixing of following sizes of PVC conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 25mm
122Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/recessed Steel/PVC conduit as required 1 run of cable.
123Supplying and fixing of GI box of following size modules, along with modular base & cover plate for modular switches in recess etc as required. 1 or 2 Module (75mmx75mm)
124Supply, installation, testing and commissioning of following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. RJ 45 Socket
125Supply, installation, testing and commissioning of 9U rack complete with all accessories etc complete as per specifications and as required.
126Supply, installation, testing and commissioning of 42U rack complete with all accessories etc complete as per specifications and as required.
127Supply, installation, testing and commissioning of 12 port unmanaged ethernet switch.
128Supply, installation, testing and commissioning of 24 port managed ethernet switch with 2 nos fiber ports.
129Supply, installation, testing and commissioning of Cat-6 shuttered 12 port fully loaded patch panel.
130Supply, installation, testing and commissioning of 24 port Patch panel fully loaded patch panel. Cat-6 UTP
131Supply, installation, testing and commissioning of Cat-6 UTP 24AWG patch cord, 1 meter, Plug 30U, snaglless etc as required.
132Supplying and Fixing of following sizes of PVC conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
133Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/recessed Steel/PVC conduit as required 1 run of cable.
134Supply, installation, testing and commissioning of IP Camera Indoor 4MP with RJ 45 connector/jack.
135Supply, installation, testing and commissioning of IP Camera Outdoor 4MP with RJ 45 connector/jack.
136Supply, installation, testing and commissioning of NVR 32 channel complete with all respect accessories and suitable for minimum 8 slot harddisk.
137Supply, installation, testing and commissioning of hard disk 4TB per NVR.
138Supply, installation, testing and commissioning of Switch 16 port POE.
139Supply, installation, testing and commissioning of Switch 24 port POE.
140Supply, installation, testing and commissioning of Back Box.
141Supply, installation, testing and commissioning of 48\\" LED Screen for Observation and reviewing.
142Supply and fixing of 2 meter patch cord with complete connectors.
143Supply, installation, testing and commissioning of 42U RACK with PDU and respected accessories.
144Supply, installation, testing and commissioning of 9U RACK with PDU and respected accessories.
145Supply, installation, testing & commissioning of Numeric 20KVA Online Ups with inbuilt isolation transformer.
146Supply, installation, testing & commissioning of SMF 12V*26 AH X 16 NOS. BATTERY, RACK & LINKS .
147Supply, installation, testing & commissioning of on grid intrective roof top Solar photo voltaic powre generation System Including Space Frame Complete in all respect
148Main LT Panel Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.INCOMER : 400 AMP FP MCCB with Change Over Switch of 250 Amp ,BUS BAR : 400 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp.The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature.with Multi Function Meter OUT GOINGS : 01 nos 100 Amp MCCB 4Pole 10 ka for Librery Panel , 01 nos 125 Amp MCCB 4 Pole 10 ka for Fire Panel ,3 No 63 AMP 4P MCCB Including Indication Lights (Ground Floor Power DB's), 3 No 63 AMP 4P MCB Including Indication Lights (Ground Floor Light DB's) 3 No 40 AMP FP MCB Including Indication Lights (UPS DB) 2 No 63 AMP 4P MCB (Spare) ,2 No 40 AMP DP MCB (for Ext. light Circuit),3 No 40 AMP 4P MCB (for Water Lifting Pump) complete panel as above and complete
149Supply, installation, testing and commissioning of Power Generator- DG set of 58.5 KVA CPCB-IV+ Mahindra Silent D/G Set Comprising of Mahindra Engine Model V4355G2/ 75.5BHP/ Water Cooled, 1500RPM coupled with 58.5 KVA 3 phase Crompton or LS alternator, Turbo charged, A1 class governing, 4 cylinders make complete with all accessories including Base Frame, Fuel Tank, battery with leads, Sound Proof Canopy & AMF Control Panel.
150Supply, installation, testing & commissioning of Aquaguard Storage Type Water Cooler 60 LPH Cooling Capacity AquaguardR AQUAGUARD PRO PURECHILL 80 PSS UV+CuZn)Specifications Type of Water CoolerStorage Type Cooling Capacity Rating of Water Cooler (In LPH) 60 Type of Pressure Water CoolerFaucet Type Type of Storage Water Cooler Cooler which store or cool water in the same container Storage Capacity for Storage Type Water Coolers (In Liters) 80 Outer Body Material Mild Steel Number of Faucets 2 complete in all Respect
151Supply, installation, testing & commissioning of Reverse Osmosis based Water Treatment System above 50 LPH Capacity Above 50 LPH and upto100 LPH Storage Tank (Inclusive in the scope of Supply) (for without storage tank)Complete in all Respect Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58570607
AUTHORITY Government Departments
TENDER VALUE 1.76 Crore
LAST DATE 01-12-2026
Authority
Authority Name Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited
Work Description Tender for Electrical & Allied Work For Additional Classrooms & Upgradation Of Existing Building At Lal Bahadur Shastri Government Post Graduate College, Halduchaur (Nainital).
Basic Detail
Tender No 1675/BRIDCUL/1093/26 Dated 28.10.2026
Bidding Type Tender
Location
City Nainital
State Uttarakhand
Key Dates
Publish Date 17 Nov 2026
Submission Date 01 Dec 2026
Open Date 01 Dec 2026
Finance
Tender Value 1.76 Crore
Tender Fee 5900
EMD 3.54 Lakhs
Exemption Not Available
Document List
06badaa3-18ad-4115-a942-6493bac3ab0b.html
BOQ_120727.xls
sbdupgradationexistingbui_1.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 17, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 01, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 12 days
Dec 01, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 12 days

Tender Documents

Download All (ZIP) ↓
html

06badaa3-18ad-4115-a942-6493bac3ab0b.html

xls

BOQ_120727.xls

pdf

sbdupgradationexistingbui_1.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender