Defence Statutory Bodies & Commissions/Committees Closing in 17 days TDR #58561035

Tender For Repair/Replacement Of Internal And External Electrical Services And Allied Work In Wsa At 18 Wing Afs Pathankot.

Issued by Statutory Bodies & Commissions/Committees · Pathankot, Punjab
Tender Value
49.60 Lakhs
Estimated cost
Bid Submission
07 Dec 2026
17 days left
EMD
99200
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Pathankot → Punjab
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Replacement Of Internal And External Electrical Services And Allied Work In Wsa At 18 Wing Afs Pathankot.

BOQ

Name of Work:- REPAIR/REPLACEMENT OF INTERNAL AND EXTERNAL ELECTRICAL SERVICES AND ALLIED WORK IN WSA AT 18 WING AFS PATHANKOT.
Sl. No. Item Description
1Excavation in trenches n.exc 1.5m wide and n.exc 1.5m deep and getting out in any type of soil for laying of cable complete all as specified and directed by Engineer-in-charge.
2Returning filling in (soil) including spreading levelling, watering and well ramming in layers not exc 25cm thick all as specified and directed by Engineer -in-charge.
3Removal of excavated soil to a distance n.exc 50 m and depositing where directed at a level not exc 1.5 mtr above the ground level/starting point compalete all as specified and directed.
4Supply and fixing DWC Pipe of size 40x32 outer and inner dia for cable protection in trench complete all as specified and directed.
5Supply and fixing DWC Pipe of size 50x38 outer and inner dia for cable protection in trench complete all as specified and directed.
6Supply and fixing DWC Pipe of size 63x50 outer and inner dia for cable protection in trench complete all as specified and directed.
7Supply and fixing DWC Pipe of size 77x63 outer and inner dia for cable protection in trench complete all as specified and directed.
8Supply and fixing DWC Pipe of size 90x75 outer and inner dia for cable protection in trench complete all as specified and directed.
9M&L for cutting existing road/hard standing not exc 30x30 cm in wide & depth getting out excavated material for laying cable/GI tube, returning filling & well rammaing watering finish suraface 10 cm from top using PCC 1:3:6; including removal of surplase soil
10Supplying and fixing nominal bore, light grade, Galvanised mild steel pipe /tubing, complete with all fittings, laid under roads, drain, paths, fixed to poles/ walls with suitable mild steel clamps , bolts, nuts and washers as for cable proction complete all as specified and directed for followig sizes. (Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule):-(a) 80 mm bore
11(b) 50 mm bore
12(c ) 40 mm bore
13(d) 25 mm bore
14M&L for Straight through joint/End Joint kit for 25 Sqmm to 50 Sqmm regin cast complete heat shrink outdoor type suitable for 2/3.5/4 core LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 Note: Excvation & Earth work shall be mesured & paid sepreately in respective item of this sch.
15M&L for Straight through joint/End Joint kit for 70 Sqmm to 95 Sqmm regin cast complete heat shrink outdoor type suitable for 2/3.5/4 core LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 Note: Excvation & Earth work shall be mesured & paid sepreately in respective item of this sch.
16M&L for Straight through joint/End Joint kit for 120 Sqmm to 150 Sqmm regin cast complete heat shrink outdoor type suitable for 2/3.5/4 core LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 Note: Excvation & Earth work shall be mesured & paid sepreately in respective item of this sch.
17M&L for Straight through joint/End Joint kit for 185 Sqmm to 240 Sqmm regin cast complete heat shrink outdoor type suitable for 2/3.5/4 core LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 Note: Excvation & Earth work shall be mesured & paid sepreately in respective item of this sch.
18Taking down old u/s LT cable any size up to 185 sqmm 2/3.5/4 core retrieved.
19Supply and fixing LT XLPE insulated PVC shethed (heavy duty) galvanised steel strip or wire armoured electric power cable with aluminium conductor 1100 volts grade of size 3.5 core 185 sqmm all as per specified and directed
20Supply and fixing LT XLPE insulated PVC shethed (heavy duty) galvanised steel strip or wire armoured electric power cable with aluminium conductor 1100 volts grade of size 3.5 core 150 sqmm all as per specified and directed
21Supply and fixing LT XLPE insulated PVC shethed (heavy duty) galvanised steel strip or wire armoured electric power cable with aluminium conductor 1100 volts grade of size 3.5 core 120 sqmm all as per specified and directed
22Supply and fixing LT XLPE insulated PVC shethed (heavy duty) galvanised steel strip or wire armoured electric power cable with aluminium conductor 1100 volts grade of size 3.5 core 95 sqmm all as per specified and directed
23Supply and fixing LT XLPE insulated PVC shethed (heavy duty) galvanised steel strip or wire armoured electric power cable with aluminium conductor 1100 volts grade of size 3.5 core 70 sqmm all as per specified and directed
24Supply and fixing LT XLPE insulated PVC shethed (heavy duty) galvanised steel strip or wire armoured electric power cable with aluminium conductor 1100 volts grade of size 3.5 core 35 sqmm all as per specified and directed
25Supply and fixing LT XLPE insulated PVC shethed (heavy duty) galvanised steel strip or wire armoured electric power cable with aluminium conductor 1100 volts grade of size 4 core 25 sqmm all as per specified and directed
26Supply and fixing LT XLPE insulated PVC shethed (heavy duty) galvanised steel strip or wire armoured electric power cable with aluminium conductor 1100 volts grade of size 4 core 16 sqmm all as per specified and directed
27Supply installation commission and testing of Out door LT Panel board of size 1200 x1000 x 450 mm, (CPRI tested) LT415 Volts, 50 Hz , 3-phase, Bus Bar chamber comprising 4 Nos Aluminium strip bus bars air insulated and PVC sheathed capacity 600 Amps with colour coding with main indication IA with selector switch 03 Nos,digital ammeter with selector switch, digital volt meter 500V with selector switch and LED type/Neon type Indicating lamps panel mounting type RYB-3 Nos, factory assembled, outdoor type weather and vermin proof (Protection Class IP-54) made out of not less than 60 X 60 X 6 mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet with front hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint(First Quality) over a coat of red oxide primer complete comprising of following :-(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job. (b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job.INCOMING MCCB 350 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA)OUTGOING MCCB 250 Amp, 4 Pole , 415 Volts rating with Adjustable Over load setting (Breaking capacity 25KA)MCCB 100 Amp, 4 Pole , 415 Volts rating with Adjustable Over load setting (Breaking capacity 16 KA)-02 Nos MCCB 63 Amp, 4 Pole , 415 Volts rating with,Adjustable Over load setting (Breaking capacity 16 KA) Ics=100% of Icu- 2 Nos.Spreader Terminal of both side
28Supply installation commission and testing of Out door LT Panel board of size 1200 x 1000 x 450 mm, (CPRI tested) LT415 Volts, 50 Hz , 3-phase,Bus Bar chamber comprising 4 Nos aluminium strip bus bars air insulated and PVC sheathed capacity 600 Amps with colour coding with main indication IA with selector switch 03 Nos, digital ammeter with selector switch, digital volt meter 500V with selector switch and LED type/Neon type Indicating lamps panel mounting type RYB-3 Nos, factory assembled, outdoor type weather and vermin proof (Protection Class IP-54) made out of not less than 60 X 60 X 6 mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet with front hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint(First Quality) over a coat of red oxide primer complete comprising of following :-(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job. (b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job.INCOMINGMCCB 400 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA) -1 NoOUTGOINGMCCB 350 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA) -1 NoMCCB 100 Amps, 4 Pole , 415 Volts rating with,Adjustable overload setting (Breaking capacity 16 KA) Ics=100% of Icu- 4 NosSpreader Terminal of both side -06 Nos
29Supply installation commission and testing of Out door LT Panel board of size 1200 x 1000 x 450 mm, (CPRI tested) LT415 Volts, 50 Hz , 3-phase,Bus Bar chamber comprising 4 Nos aluminium strip bus bars air insulated and PVC sheathed capacity 750 Amps with colour coding and suitable for 200 amps with main indication IA with selector switch 03 Nos, digital ammeter 0 to 200 amps with selector switch, digital volt meter 500V with selector switch and LED type/Neon type Indicating lamps panel mounting type RYB-3 Nos, factory assembled, outdoor type weather and vermin proof (Protection Class IP-54) made out of not less than 60 X 60 X 6 mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet with front hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint(First Quality) over a coat of red oxide primer complete comprising of following (Feeder pillar for parking terminals) :-(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job. (b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job.INCOMINGMCCB 500 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA) -1 NoOUTGOING MCCB 400 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA) -1 No MCCB 100 Amps, 4 Pole , 415 Volts rating with,Adjustable overload setting (Breaking capacity 16 KA) Ics=100% of Icu- 3 Nos MCCB 63 Amps, 4 Pole , 415 Volts rating with,Adjustable overload setting(Breaking capacity 16 KA) Ics=100% of Icu- 2 Nos Spreader Terminal of both side -07 Nos
30Supply, installation, connecting electrically & commissioning LT feeder box , outdoor type of size 0.90x0.60x0.40 Mtr size factory fabricated made out of MS sheet of thickness 3.15 mm front and back door openable with locking arrangement mounted on angle iron legs made out of angle iron of size 40x40x6 mm , 1.0 mtr long , 0.7 mtr above ground level and 0.30 mtr embedded in PCC blocks of size 0.30x0.30x0.30 mtr -04 Nos duly painted with two coats of synthetic enamel paint over a coat of red oxide complete with 400 Amps rated aluminium bus bar suitable for 3 phase 4 wire supply dully drilled holes for cable connection mounted on epoxy based post insulators and MCCB 250 Amps , 36 KA , 3 Pole , 415 Volts make : Legrand complete all as specified and direc ted by Engr-in-Charge.(Note:-LT Panel/ LT feeder box must be approved by CPRI.)
31S&F Pole box with 6 Amps MCB provision and suitable connector for single phase connctions loop in and out 10 to 16 Sqmm 2/4 core aluminium armoured cable branch out 1.5 Sqmm single core copper PVC insulated cable enclosed in a thermoplastic polysterene/polycarbonate enclosure which should be shock proof safe IP 66/67 weather proof, rust proof, dust proof, water proof, flame retradant glow wire test at min 750 C internally embeded gasket with provision for cable entry through IP 66/67 themoplastic metric size glands and/or grommets enclosure size (205 x 255 x 112mm LBH), GI clamps made out of GI flat of size 25mm X 3 mm channel including making connections all as specified and directed. complete all as specified and directed.
32Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip 32 x 6 mm (up to 7.5 m in length from earth plate ) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no 3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia medium grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion.
33M&L for Multistandarded Copper Conductor cable of 3 Core 1.5 Sq mm size drawn through steel tubular poles for interconnection of cable looping box to Street Light Fitting all as Directed.
34Supply & fix in repair pressure die-cast aluminium IP 65 cool white flood Light luminaire with 150 Watt high power LED as light source with inbuilt surge protection upto 5 kv including with Bracket , double clamps complete with nut bolts with pole and connection wire complete.
35Supply & fix in repair pressure die-cast aluminium IP 65 cool white flood Light luminaire with 120 Watt high power LED as light source SMD LED with inbuilt surge protection upto 5 kv including with Bracket , double clamps complete with nut bolts with pole and connection wire complete.
36Supply & fix in repair pressure die-cast aluminium IP 65 cool white road way luminaire with high power LED as Light source with 90 Watt high power LED with inbuilt surge protection upto 5 kv including with suitable GI Pipe Bracket , double clamps complete with nut bolts with pole and 2.5 sqmm 3 core copper wire multistrand for connection from DB to Light complete.
37Taking down carefully copper/Aluminum point wiring (light, fan socket and power) complete including switches, ceiling rose lamp holder and regulator light fittings etc and removing from site and making good disturbed surfaces of walls floors etc. complete all as specified and directed by Engr-in-charge.
38Taking down DB's including MCB's etc all as directed.
39Taking down carefully unserviceable sub main wiring of any size/core/type including making good the disturbed surfaces.
40M&L for point wiring with 1.5 Sqmm (nominal area) two single core PVC insulated unsheathed multi stranded copper conductor cable 1100 volts grade, FRLS grade in and including medium grade concealed PVC conduit 20 dia or higher and conduit fittings and all accessories with suitable size of sunk type cast iron or pressed steel terminal box 1.2mm thick, duly painted for mounting of switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet as top cover, including contineous earth wire PVC insulated, unsheathed, multi stranded copper conductor cable 1.5 sqmm (nominal area) FRLS grade, green colour, up to common earth and connected to earth dolly compete all as specified and directed by Eng.-in-charge of the following. (Note: Colour code shall be maintained as per IE rule). (a) One light point/ /Fan/Exhaust /bell buzzer point controlled by one, one way switch
41(b) One three pin 5 Amp socket on same board with other switches.
42(c) One three pin 5 Amp socket on independent board
43All as per item No. above here in but with 2.5 Sqmm (nominal area) wire/cable for phase & neutral for one 3 Pin 15 amp socket on independent board including one 2.5 sqmm PVC insulated unsheathed multi stranded copper conductor cable FRLS,1100 volts grade as earth continuity conductor upto common earth & connected to earth dolly complete all as specified and directed by Eng.-in-charge.Make of the PVC FRLS Wire is Havells/Finolex/KEI .The make of conduit and its accessories should be polycab/AKG/Precision.
44M&L for point wiring with 1.5 Sqmm (nominal area) two single core PVC insulated unsheathed multi stranded copper conductor cable 1100 volts grade, FRLS grade in existing steel/PVC conduit with existing sunken box, for mounting of switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet as top cover, including contineous earth wire PVC insulated, unsheathed, multi stranded copper conductor cable 1.5 sqmm (nominal area) FRLS grade, green colour, up to common earth and connected to earth dolly compete all as specified and directed by Eng.-in-charge of the following. (Note: Colour code shall be maintained as per IE rule).(a) One light point/ bell buzzer point controlled by one, one way switch
45(b) One three pin 5 Amp socket on same board with other switches.
46(c) One three pin 5 Amp socket on independent board
47All as per item No. above here in but with 2.5 Sqmm (nominal area) wire/cable for phase & neutral for one 3 Pin 15 amp socket on independent board including one 1.5 sqmm PVC insulated unsheathed multi stranded copper conductor cable FRLS,1100 volts grade as earth continuity conductor upto common earth & connected to earth dolly complete all as specified and directed by Eng.-in-charge
48S&F switch piano flush type single pole one way 230 Volts 5/6 Amp complete all as specified and directed.
49S&F socket outlet 3 pin, 230 Volts 5/6 Amps flush type multipurpose 5 pin complete all as specified and directed
50S&F bell push flush type 5 Amps 230 Volts single pole complete all as specified and directed…
51Supply and fixing Socket outlet multipurpose having provision for 3 pin, 230 Volts 15/16 Amp and 3 pin, 5/6 Amp piano flush type ISI marked complete all as specified and directed…
52Supply and fixing Switch piano flush type single pole, one way, 230 volts 15/16 Amps ISI marked complete all as specified and directe..
53S&F Call bell ding dong type AC 230 Volts single pole complete all as specified and directed..
54S&F step type regular socket type double module 5 step for ceiling fan 1200/1400 mm size 230 volts 6 Ampds 120 watts..
55S&F ceiling rose surface bakelite 3 terminals of size 65x25mm. complete all as specified & directed. ..
56S&F lamp holder polycarbonate insulated body with back plate complete all as specified & directed..
57S & F in repair wall mounted LED Tube light fitting 20 Watts surface mounting general purpose LED Batterns including making connections with 2 core flexible copper wire 0.50 Sq mm from ceiling rose after fixing fitting in position at site on 02 Nos new round blocks including complete all as specified and directed.
58S & F in repair wall mounted LED Tube light fitting 10 Watts surface mounting general purpose LED Batterns including making connections with 2 core flexible copper wire 0.50 Sq mm from ceiling rose after fixing fitting in position at site on 02 Nos new round blocks including complete all as specified and directed.
59S & F in repair in repair LED panel Square (2'X2') 36 Watt Plano Taps recess mounted luminaires which suites various ceiling types with tapered housing makes in most flexible to install in low clerance ceiling .including making connections with 2 core flexible copper wire 0.50 Sq mm Complete all as specified and as directed by Engr-In-Charge.
60S & F in repair sleek LED Bulk head fitting 10 watt suitable for outdoor and indoor areas in perfect synchronization with functionality and aesthetics complete all as specified and directed.
61S & F in repair LED Building Security light fitting 30 watt energy saving environmental friendly long life LED Street light made up pressure die cast aluminium housing with high efficiency LEDs complete with GI Pipe bracket and clamps for fixing wall security light on wall or bldg all as specified and directed.
62M&L sub main wiring with 2 Single core FRLS PVC insulated unsheathed cable 1100 Volts grade heavy duty copper conductor multistranded of size 4.0 Sqmm (nominal area) drawing in and including 20mm dia medium duty PVC concealed conduit and conduit accessories and fittings. Including one single core green colour FRLS, PVC. Insulated unsheathed multi stranded copper conductor cable of size 4.0 Sqmm as earth continuity conductor upto common earth and connected to earth dolly complete all as specified & directed. (Note: Three run 4 Sqmm cable and one run conduit shall be measured as one run.)
63M&L sub main wiring with 2 Single core PVC insulated unsheathed FRLS cable 1100 Volts grade heavy duty copper conductor multistranded of size 4.0 Sq.mm. (nominal area)drawn in existing surface conduit/existing concealed conduit and fittings. Insulated unsheathed FRLS cable copper conductor multistranded of size 4.0 Sq. mm. as earth wire upto common earth and connected to earth dolly complete all as specified & directed. (Note: Three run 4 Sqmm cable and shall be measured as one run.)
64M&L sub main wiring with 2 Single core FRLS PVC insulated unsheathed cable 1100 Volts grade heavy duty copper conductor multistranded of size 6.0 Sqmm (nominal area) drawing in and including 20 mm dia medium duty PVC concealed conduit and conduit accessories and fittings. Including one single core green colour FRLS, PVC. Insulated unsheathed multi stranded copper conductor cable of size 6.0 Sqmm as earth continuity conductor upto common earth and connected to earth dolly complete all as specified & directed. (Note: Three run 6 Sqmm cable and one run conduit shall be measured as one run.)
65M&L sub main wiring with 2 Single core PVC insulated unsheathed FRLS cable 1100 Volts grade heavy duty copper conductor multistranded of size 6.0 Sq.mm. (nominal area)drawn in existing surface conduit/existing concealed conduit and fittings. Insulated unsheathed FRLS cable copper conductor multistranded of size 6.0 Sq. mm. as earth wire upto common earth and connected to earth dolly complete all as specified & directed. (Note: Three run 4 Sqmm cable and shall be measured as one run.)
66S & F in repair of Sheet Metal Enclouser Double door DB 415 volts, 4 way with 200 Amps rated bus bar Three pole & neutral (TPN) fixing on suitable rectanguler block, duly connected incoming and outgoing wires in DB and good finish to the old disturbed surface complete all as specified and direceted.
67S & F in repair of Sheet Metal Enclouser Double door DB 240 volts, 12 way with 200 Amps rated bus bar Single pole & neutral fixing on suitable rectanguler block, duly connected incoming and outgoing wires in DB and good finish to the old disturbed surface complete all as specified and direceted.
68S & F in repair of Sheet Metal Enclouser Double door DB 240 volts, 8 way with 200 Amps rated bus bar Single pole & neutral incl fixing on suitable rectanguler block, duly connected incoming and outgoing wires in DB and good finish to the old disturbed surface complete all as specified and direceted.
69S & F in repair of Sheet Metal Enclouser Double door DB 240 volts, 4 way with 200 Amps rated bus bar Single pole & neutral incl fixing on suitable rectanguler block, duly connected incoming and outgoing wires in DB and good finish to the old disturbed surface complete all as specified and direceted.
70S & F in repair MCB Single Pole Neutral C Curve 230 volts of capacity 32 Amp 10 KA complete all and specified and directed by Engr-in-Charge .
71S & F in repair MCB Single Pole of cap 6-32 Amp, C Curve 240 volts 10KA complete all as specified and directed.
72S & F in repair MCB, 63Amp, TPN breaking capacity 10KA, 415 Volt, 50 Hz complete all and specified and directed by Engr-in-Charge.
73Sheet metal enclosure MCB distribution board Vertical Tripal pole & neutral 415 Volt (VTPN) 4 way with Incomer MCCB 100 Amps 25 KA 4 Pole IP-43 IK-09 protection double door complete with appropriate size bus bar and neutral link, fixed flush in wall including chases cutting in wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed. Note - MCBs will be measured separately.
74M&L in replacement for point wiring for explosive sheds and other required bldgs with 1.5 sqmm 1100 volts grade Unilay-FRLS insulated copper conductor single core multi strand flexible cable in and including NEW ERW rigid steel conduit fittings and accessories including flame proof bends,couplers, junction boxes etc fixed on wall/ceiling with proper fixing arrangements incl copper conductor 1.5 sqmm PVC insulated unsheathed multistranded copper conductor single core cable (green color) as earth lead continuity conductor fixed to earth terminal and matellic body of light fittings complete all as suitable fir class II Zone IE IIA for one light point controlled by one way switch.
75All as per Srl item No-74 here in above but for Flame Proof 3 pin 16 Amps socket with 1.5 sqmm complete all as specified and directed.
76All as per Srl item No-74 here in above but for Flame Proof 3 pin 25 Amps socket with 2.5 sqmm complete all as specified and directed.
77M&L in replacement for point wiring for explosive sheds and other required bldgs with 1.5 sqmm 1100 volts grade Unilay-FRLSH insulated copper conductor single core multi strand flexible cable in and Existing ERW rigid steel conduit fittings and accessories including flame proof bends,couplers, junction boxes etc fixed on wall/ceiling with proper fixing arrangements incl copper conductor 1.5 sqmm PVC insulated unsheathed multistranded copper conductor single core cable (green color) as earth lead continuity conductor fixed to earth terminal and matellic body of light fittings complete all as suitable fir class II Zone IE IIA for one light point controlled by one way switch.
78All as per Srl item No-77 here in above but for Flame Proof 3 pin 16 Amps socket with 1.5 sqmm complete all as specified and directed.
79All as per Srl item No-77 here in above but for Flame Proof 3 pin 25 Amps socket with 2.5 sqmm complete all as specified and directed.
80Supply and fixing explosion proof rotary switch, single pole ON/OFF with cable termination box of 16 Amps rating 250 Volts class E Ex I C suitable for class 1, Zone 2.
81Supply and fixing inreplacement for flame proof switch socket and plug combind in LM6 cable termination box in LM6 , 16A, 250V,2P+Earth
82Supply and fixing in replacement for flame proof switch socket and plug combind in LM6 cable termination box in LM6 , 25A, 250V,2P+Earth
83S&F in replacement of flame proof LED light fitting 1x20 Watt including all accessories prewired with heat resistant glass cover, polyester resin enclosure and centrally locking system suitable for class I,Zone II E Ex II C including proper fixing arrangement on elevation on angle iron frame with clamps, nut, bolts & washers of suitable size as recommended by manufacturer and directed by Engr-in-Charge inluding electric connection
84S&F in replacement of flame proof LED light fitting 1x10 Watt including all accessories prewired with heat resistant glass cover, polyester resin enclosure and centrally locking system suitable for class I,Zone II E Ex II C including proper fixing arrangement on elevation on angle iron frame with clamps, nut, bolts & washers of suitable size as recommended by manufacturer and directed by Engr-in-Charge inluding electric connection
85Supply and fixing of Flame proof Bulk head LED light fitting of 30 watt , IP 66 Protection of cast aluminium alloy material and heat and impact resistance toughen A clear glass having anti corrisive epoxy powder coataed finish complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and directed.
86Supply and fixing of Flame proof Bulk head LED light fitting of 60 watt , IP 66 Protection of cast aluminium alloy material and heat and impact resistance toughen A clear glass having anti corrisive epoxy powder coataed finish complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and directed.
87M&L in repair Flame proof (FP) sub main wiring using approved colour coding as per IS with four single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 4 sqmm (nominal area) 1100 volts grade and one single core, PVC insulated, unsheathed FRLSH multistranded copper conductor of size 4 sqmm (nominal area) 1100 volts grade cable as earth wire including drawn through steel conduit , heavey duty and connected to main board and making good disturbed surface after taking out old unserviceable flame proof / non flame proof sub main wiring and disposing from site complete all as specified and as directedNote: four runs each of 4 sqmm cable and one RM of 4 sqmm cable as earth wire shall be considered as one running metre for payment purpose.
88Supply and Fixing in repair Flame proof Exhaust fans AC single phase Steel body 230/ 240 V of size 300 mm sweep with louver IP 65/IP 66 protection 1500 RPM suitable for Gas / Vapour Group of IIA & IIB and Zone 1 including cutting of existing wall/ surface and making good surface complete all as specified and directed by Engineer-in-Charge.
89M & L Flame proof distribution board SPN 8 Way (Totally enclosed dust and flame proof / jet proof) IP-66 Protection including flame proof MCB SPN 32 Amps -01 Nos(Incoming) , SP-5 to 30 Amps - 06 Nos (Outgoing) 240 Volts AC 10 KA Flame proof suitable for gas group I/IIA /IIB/IIC as per IS-2148 of 1981 with complete Internal Bus bar and wiring upto terminal complete all as specified and direcetd.
90M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron or steel earth lead wire 4mm dia size by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate no 3 of SSR part I including necessary excavation and earth work GI pipe 20mm dia light grade for watering and GI 15mm dia light grade pipe for protection of GI earth wire etc, PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to DB as indicated including testing complete. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58561035
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 49.60 Lakhs
LAST DATE 07-12-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Replacement Of Internal And External Electrical Services And Allied Work In Wsa At 18 Wing Afs Pathankot.
Basic Detail
Tender No GE/PAF-103/2026-27
Bidding Type Tender
Location
City Pathankot
State Punjab
Key Dates
Publish Date 17 Nov 2026
Submission Date 07 Dec 2026
Open Date 09 Dec 2026
Finance
Tender Value 49.60 Lakhs
Tender Fee 500
EMD 99200
Exemption Available
Document List
BOQ_896447.xls
fc19c509-a3af-4377-8604-267ea5091122.html
Tender103.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 17, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 07, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 17 days
Dec 09, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 19 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_896447.xls

html

fc19c509-a3af-4377-8604-267ea5091122.html

pdf

Tender103.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender