Housing Urban and Rular Development Government Departments Closing in 2 days TDR #58556698

Tender For Construction Work Of Office Building (Electrification Work) For The Office Of Construction Block-1 Public Works Department In Bahraich District.

Issued by Government Departments · Bahraich, Uttar Pradesh
Tender Value
42.20 Lakhs
Estimated cost
Bid Submission
23 Nov 2026
2 days left
EMD
4.11 Lakhs
Bank guarantee accepted
Document Fee
2354
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Bahraich → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Construction Work Of Office Building (Electrification Work) For The Office Of Construction Block-1 Public Works Department In Bahraich District.

BOQ

Name of Work:- Janpad Bahraich me Nirman Khand-1 Lok Nirman Vibhag ke karyalaya hetu karyalaya bhawan ka nirman karya (Vidhyutkaran ka karya)
Sl. No. Item Description
1Point Wiring :Wiring for light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
2Group C
3Wiring for fan point/ exhaust fan point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
4Group C
5Wiring for call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
6Group C
7Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
8Supplying and fixing PVC batten/ angle holder including connections etc. as required.
9Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
105/6 A switch
113 pin 5/6 A socket outlet
12Telephone socket outlet
13TV antenna socket outlet
146 pin 15/16 A socket outlet
151 or 2 Module (75mmX75mm) 15/16 A Switch
164 Module (125mmX75mm)
17Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.(for 2 Module)
18Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
19Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
20Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. (for A.C. Point/MCB Point)
21Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
221 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
23Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required.
242 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
252 X 4 sq. mm + 1 X 4 sq. mm earth wire
262 X 6 sq. mm + 1 X 6 sq. mm earth wire
272 X 16 sq. mm + 1 X 6 sq. mm earth wire
28Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
29Single pole
30Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
31Supply and fixing of 32 Amp. DP MCB (10 KA) C Curve. CAT A
32Supply and fixing of 40 Amp. DP MCB (10 KA) C Curve. CAT A
33Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
34Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
3512 way Double door
36Supplying and fixing of following ways surface/ recessmounting, vertical type, 415 V, TPN MCB distribution board of sheet steel dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
374 way (4 + 24), Double door
38Supplying and fixing FP sheet steel enclosure on surface/ recess .
39Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
40Upto 450 mm sweep
41Supply and fixing of 32 Amp. FP MCB (10 KA) C Curve. CAT A
42Supply and fixing of 63 Amp. FP MCCB (16 KA) C Curve. CAT A
43Supply and fixing of 125 Amp. FP MCCB (25 KA) C Curve. CAT A
44Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
451200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
46LED Down lighter (SMD Type) (System lumen efficacy >135 lm/Watt)Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round /square/Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range - 5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/ 4000°K /5700°K / 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim .
478-10 Watt
4818 Watt
4930 Watt
50LED Panel light 2x2 ft., (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc.as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm)
5145 Watt
52LED Batten light (System lumen efficacy >135 lm/Watt)Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range - 15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K / 5700°K /6000°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm)
5318 -22 Watt
54Supplying, installation, Testing & Commissioning of LED Recessed / surface Down lighter (Round / square/ Rectangular) Double COB 36 Watt Type of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), life time of minimum 50000 Burning Hours with , 70% of initial Lumen maintainedtill life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. \\"complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc.as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C)
55Supply and fixing of 20 watt LED above protection austra Complete in all respect.
56Supply and Laying of 1800*900*12mm thick chequerd rubber matting of tested quality. complete in all respect. as per I.E. Rules.
57Supplying, installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4- 5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP- 66,IK-10, CRI >80 , under voltage and over voltage protection,EMI- EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
5872 Watt
59Supply & fixing of 12 Watt LED Bulb - B22 / E27 (Colour Temp.- 6500K / Lumens - 900 lm) cool day light, Input Volts (AC 90V-260V), 3-Star rating suitable for Batten/Angle holder including making connection.Complete in all respect.
60Supply & fixing of 225/300mm sweep ventilating (HeavyDuty) exhaust fan complete with Metallic Blade (Steel bird guard protector /Copper motor for high air suction performance /Capacitor etc.), Noise level : (45 - 50) dB, Power consumption : 45 W, Rated voltage : 230 V, Rated frequency : 50 Hz, Motor type : Normal Speed. Complete in all respect.
61Supplying and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade at the depth of 750 mm bellow ground level over a cushion of 75 mm thick sand all around and protected with burnt bricks on side and on top .On surface the cable run shall be fixed on MS clamps etc.of suitable size or as directed by the Engineer-Incharge ,complete in all respect.The armouring of the cable shall be properly connected with the earth conductor by clamps etc. Following size
62size 10 sq mm 4 core
63size 25 sq mm x 3-1/2core
64size 70 sq mm x 3-1/2core
65size 240 sq mm x 3-1/2core
66Supplying and making cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required.
674 X 10 Sqmm (25 mm)
684 X 16 Sqmm (28 mm)
693½ X 70 sq. mm (38 mm)
703½ X 240 sq. mm (62 mm)
71Supply & Erracetion of factory fabricated & wired metal clad dust and vermin proof floor mounting, M.S. Channel Base with bottom and top cable entreis Electrical control panel with TPN MCCB’s (Four Pole 36 KA with thermal magnatic release) Switches complete and instrument chamber etc. complete in all respects. The instrument chamber shall be separate and shall comprise of flush type digital metering system for phase to phase voltage and single phase voltage, current and other parameters (KVA, P.F, KW etc) in each phase with touch type selector switches for different readings, instrument fuses, current transformer etc. The panel board shall have suitable capacity electrolytic aluminium busbars as per IS8623 or above istulated with heat shrink sleeving and mounted on non hygroscopic supports such as CMC/BMC support with deteachable side covers and shall be suitable for extension on the sides. The MCCB’s shall be complete with suitable cable end boxes, compression glands and indicating lamp on incoming etc.
72Incoming -INCOMER:-1 Nos. 250 Amps. FP MCCB Microprocessor release 1 No. Multi Function Meter.1 Set of Surge Arrestor2 Set of phase indicating lamps with Single Pole MCB.5 Set of ON / OFF indicating lamps with Single Pole MCB.
73Outgoing - 125 Amp 4P MCCB - 1 Nos. (power d.b.)63 Amp 4P MCCB - 1 Nos. (for Light & fan d.b.)32 Amp 4P MCCB - 3 Nos.
74Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. (but without charcoal/ coke and salt) as required.
75Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
76Fire Detection :Supplying, installation, testing & commissioning of manual call box of MS Construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
77Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in MS box with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
78Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
79Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.
80Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required : Terrace Pump Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.
81450 lpm at 35 m Head
82Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
8380 mm dia
84100 mm dia
85Supplying and fixing single headed Internal Hydrant Valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :
86Single headed Stainless steel
87Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
8880 mm dia
89100 mm dia
90Supplying and fixing Orifice Plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
91Providing, installation, testing and commissioning of Non-Return Valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
9280 mm dia
93100 mm dia
94Providing, installation, testing and commissioning of stainless steel Y-Strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.
95100 mm dia
96Supplying and fixing 63 mm dia, 15 m long RRL Hose Pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :
97Stainless Steel (Grade 304)
98Supplying and fixing First-Aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
99Supplying & fixing 63 mm dia gun metal short Branch Pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :
100Stainless Steel (Grade 304)
101Supplying and fixing of Fire Brigade Connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
1022 way - 100 mm dia M.S. Pipe
103Supplying and fixing Air Vessel made of 250 mm dia, 8mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
104Providing & fixing of Pressure Switch in M.S. pipe line including connection etc. as required.
105Supplying and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade at the depth of 750 mm bellow ground level over a cushion of 75 mm thick sand all around and protected with burnt bricks on side and on top .On surface the cable run shall be fixed on MS clamps etc.of suitable size or as directed by the Engineer-Incharge ,complete in all respect.The armouring of the cable shall be properly connected with the earth conductor by clamps etc. Following size
106size 25 sq mm x 3-1/2core
107Supplying and making cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required.
1083½ X 25 sq. mm (28mm)
109Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
110Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
111Supply and Laying of 1800*900*12mm thick chequerd rubber matting of tested quality. complete in all respect. as per I.E. Rules
112Providing & fixing carbon steel Fire Man Axe with rubber insulated handle tested to 20000 volts.
113Providing and Fixing of Self illuminated /Auto Glow Exit Signs printed on photo-luminescent sheet containing self illuminated base chemical,of appropriate size not less than 400x150mm,suspended from ceilling or fixed to the walls with accessories as riquired and as directed at site.
114Providing & fixing dial type (150 mm dia) Pressure Gauge with isolation ball valve suitable for working pressure of 250 PSI cost shall be of inclusive of providing any short pieces, nipples, elbows etc as required. having calibration of 0-15 Kg/cm2.
115Providing, fixing, testing & commissioning of resilient rubber lined single Arch Vibration Eliminators suitable for raw water up to 45oC temperature, working pressure 8.8 Kg/cm2 and test pressure 20 Kg/cm2 for :-
116100 mm dia
117Providing & fixing cast iron air release valve of 25 mm dia including 25 mm dia Ball valve with fittings etc. as per the requirement.
118Providing & Fixing of 1.6 mm thick M.S/Door Frame, Door capable of accommodating fire Hose Reel, Landing Valve, Hose Pipes, fittings & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) Cost of fire extinguishers not included in item rate. (Liasioing with civil contractor for making Recessed type mansoary box (by civil contractor).
1191500x900 mm (Indoor Cabinet) Only Frame
120Control Panels (for Terrace Pump) :
121Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2 mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :63 Amp, 35kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. -2 Sets Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58556698
AUTHORITY Government Departments
TENDER VALUE 42.20 Lakhs
LAST DATE 23-11-2026
Authority
Authority Name Public Works Department
Work Description Tender for Construction Work Of Office Building (Electrification Work) For The Office Of Construction Block-1 Public Works Department In Bahraich District.
Basic Detail
Tender No 2642(VI)/02CBW(Gonda Zone)17EM/2026-27 Date 05-11-2026
Bidding Type Tender
Location
City Bahraich
State Uttar Pradesh
Key Dates
Publish Date 16 Nov 2026
Submission Date 23 Nov 2026
Open Date 23 Nov 2026
Finance
Tender Value 42.20 Lakhs
Tender Fee 2354
EMD 4.11 Lakhs
Exemption Not Available
Document List
6c753d4d-9d64-44d3-9fb2-06705fd08811.html
6T2BahraichOfficeBuilding2642.pdf
BOQ_2294594.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 16, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 23, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 2 days
Nov 23, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 2 days

Tender Documents

Download All (ZIP) ↓
html

6c753d4d-9d64-44d3-9fb2-06705fd08811.html

pdf

6T2BahraichOfficeBuilding2642.pdf

xls

BOQ_2294594.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender