Tender For Repair / Maintenance Of Lt Panels And Allied Works In Dilbagh Area At Af Stn Halwara Under Ge (Af) Halwara
Tender Value
30 Lakhs
Estimated cost
Bid Submission
08 Dec 2026
22 days left
EMD
60000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ludhiana → Punjab
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair / Maintenance Of Lt Panels And Allied Works In Dilbagh Area At Af Stn Halwara Under Ge (Af) Halwara
BOQ
| Sl. No. | Item Description |
| 1 | M&L in replacement for feeder pillers box factory made -out door type made out of MS sheet (CRCA) of thickness not less that 3 mm. of size 75 x 75 x 45 cm with aluminium bus bar strip 4 Nos of 600 Amps rated suitable for 1100 volt (LT) mounted on LT porcelain insulator front opening door two leaf braced with hinged, mounted on 4 Nos of angle iron 50x50 mm duly welded with box and grouted in PCC block of size 30cmx30cmx15cm in concrete 1:3:6. Top of box MS sheet duly bent in/slope, tapper with projection of 30 mm on all side, weather/vermin proof with high quality of rubber beeding on panel door, cable entry arrangements at bottom includes earthing terminals 2 Nos at both side and painted with two coats of smoke grey stove enameled paint over a primer coat including providing MCCB, 4 pole,fixed type 400 Amps, 36 KA rating-01 No, complete all as specified and directed. |
| 2 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement mortar and comprising of the following switchgear, accessories and including taking down existing LT panel any type(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase 415 Volts 4 pole 36 KA 315 Amp - 01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 100 Amp -06 Nos (outgoing) |
| 3 | Supply, installation, testing and commissioning of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glands, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed:-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 1000 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase, 415 volts, 4 pole 36 KA, 630 Amp -01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 315 Amp -02 Nos (outgoing)(j) MCCB 3 phase, 415 volts, 4 pole 25 KA, 100 Amp - 06 Nos (outgoing) |
| 4 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet, outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed :-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase 415 Volts 4 pole 36 KA 400 Amp - 01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 125 Amp -03 Nos (outgoing)(g) MCCB 3 phase, 415 volts, 4 pole 25 KA, 100 Amp -03 Nos (outgoing) |
| 5 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessorie, complete all as specified and directed :-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase 415 Volts 4 pole 36 KA 400 Amp - 01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 125 Amp -02 Nos (outgoing)(g) MCCB 3 phase 415 volts 4 pole 25 KA 100 Amp - 04 Nos (outgoing) |
| 6 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15 mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed:-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase 415 Volts 4 pole 36 KA 400 Amp - 01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 100 Amp -06 Nos (outgoing) |
| 7 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glands, thimbles etc. The panel should have 4 No of angle iron base frame made of 50x50x6mm (60 cm long legs) fixed in ground in and including PCC block of size 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15 mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed:-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 2000 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) ACB Control microprocess, draw out type TPN 1000 Amps 50 KA - 01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 36 KA, 400Amp -03 No (outgoing)(g) MCCB 3 phase, 415 volts, 4 pole 25 KA, 160 Amp -03 No (outgoing) |
| 8 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glands, thimbles etc. The panel should have 4 No of angle iron base frame made of 50x50x6mm (60 cm long legs) fixed in ground in and including PCC block of size 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15 mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed:-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 2000 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) ACB Control microprocess, draw out type TPN 1000 Amps 50 KA - 01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 36 KA, 400Amp -02 No (outgoing)(g) MCCB 3 phase, 415 volts, 4 pole 25 KA, 250 Amp -02 No (outgoing)(h) MCCB 3 phase, 415 volts, 4 pole 25 KA, 100 Amp -03 No (outgoing) |
| 9 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed:-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase 415 Volts 4 pole 36 KA 400 Amp - 01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 200 Amp -01 Nos (outgoing)(g) MCCB 3 phase 415 volts 4 pole 25 KA 160 Amp - 03 Nos (outgoing) |
| 10 | Supply, installation, testing and commissioning in replacemnt of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed:-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase 415 Volts 4 pole 36 KA 400 Amp - 01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 160 Amp -04 Nos (outgoing)(g) MCCB 3 phase 415 volts 4 pole 25 KA 100 Amp - 02 Nos (outgoing) |
| 11 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glants, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed:-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 600 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase 415 Volts 4 pole 36 KA 315 Amp - 01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 25 KA, 125 Amp -02 Nos (outgoing)(g) MCCB 3 phase 415 volts 4 pole 25 KA 100 Amp - 04 Nos (outgoing) |
| 12 | Supply, installation, testing and commissioning in replacemnt of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glands, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed:-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 1000 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase, 415 volts, 4 pole 36 KA, 630 Amp -01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 36 KA, 400 Amp -01 Nos (outgoing)(g) MCCB 3 phase, 415 volts, 4 pole 25 KA, 200 Amp - 02 Nos (outgoing)(h) MCCB 3 phase, 415 volts, 4 pole 25 KA, 125 Amp - 02 Nos (outgoing) |
| 13 | Supply, installation, testing and commissioning in replacement of LT panel board as pere IS 8632, made out of 3.15mm thick CRCA sheet , outdoor cubical type (double door) totally enclosed weather, dust and vermin proof with front and rear opening of 415 volots, 3 phase, 4 wire 50 Hz including internal wiring with copper conductor and two coats of synthetic enamel paint over a coat of red oxide primer including connecting all incoming and outgoing cable feeders with necessary cable glands, thimbles etc. The panel should have 4 No of angle iron base frame made of 40x40x6mm (60 cm long legs) fixed in ground including 30x30x30cm PCC 1:2:4 type B-1 using 20mm graded stone aggregates, finishing with cement plaster 15mm thick in cement mortar 1:4 and comprising of the following switchgear, accessories, complete all as specified and directed:-(a) 04 strips of Aluminium bus bars with insulation colour sleeves of capacity 1000 Amp fixed on PVC heat shrinkable insulator heavy duty.(b) Volt meter 0-500 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch - 01 No(c) Amp meter 0-300 volts, digital type, panel mounted, flush type, three phase of size 96x96mm complete with built in selector switch with suitable size CTs - 01 No(d) Indicator lamp LED type on all phases (R. Y. B.) -03 Nos(e) MCCB 3 phase, 415 volts, 4 pole 36 KA, 630 Amp -01 No (incoming)(f) MCCB 3 phase, 415 volts, 4 pole 36 KA, 200 Amp -02 Nos (outgoing)(j) MCCB 3 phase, 415 volts, 4 pole 25 KA, 160 Amp - 03 Nos (outgoing)(j) MCCB 3 phase, 415 volts, 4 pole 25 KA, 125 Amp - 02 Nos (outgoing) |
| 14 | Note for Sl Item No : 2 to 13 :(a) Panel should have providing locking arrangements on both side of doors. (b) Panel should have providing 03 nos door hinges in each door of both sides. (c) Panel should have fixed min 02 to 03 feet height from ground surface level.(d) Layout diagram of panel shall be produced by contractor for approval of Accepting Officer before placing order to manufacturer and panel shall be brought at site as per approved drawing.(e) Contractor is required to submit purchase vouchers, e-way bill and test certificates while claiming payment of LT panels. |
| 15 | M&L in replacement for earthing complete with GI earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at depth not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcol dust and common salt filling in alternate layers and electrode connected by galvanised iron strip 32 mm x 6 mm by means of bolts, nuts, check nuts and washers connected to test termination point protected by 40mm bore GI pipe medium grade and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1:2:4 type B1 including excavation and earth work, disposal of surplus soil to a distance not exceeding 50 m complete all as specified and shown in electrical plate No 3 of SSR Part I, complete all as specified and directed. Note- (i) The unit rate shall deemed to be include for GI water pipe, protection pipe, wire mesh, funnel, excavation, RCC pit cover, PCC, test point, GI strip 32 X 6 mm from top of earth plate upto 7.5 m.(ii) PCC pit shall be provided at least 1.5m away from the earth pit and extra cost of additional length of water pipes and fixing junction, Elbows etc. shall be deemed to be included in the unit rate. (iii) RCC pit cover shall be percast of RCC 1:2:4, type B-1, 80 mm thick reinforced with XPM weighing not less than 4kg/Sqm in liue of cast iron cover. Please Enable Macros to View BoQ information |
| 16 | M&L in replacement for earthing complete with GI earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at depth not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcol dust and common salt filling in alternate layers and electrode connected by galvanised iron strip 32 mm x 6 mm by means of bolts, nuts, check nuts and washers connected to test termination point protected by 40mm bore GI pipe medium grade and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1:2:4 type B1 including excavation and earth work, disposal of surplus soil to a distance not exceeding 50 m complete all as specified and shown in electrical plate No 3 of SSR Part I, complete all as specified and directed. Note- (i) The unit rate shall deemed to be include for GI water pipe, protection pipe, wire mesh, funnel, excavation, RCC pit cover, PCC, test point, GI strip 32 X 6 mm from top of earth plate upto 7.5 m.(ii) PCC pit shall be provided at least 1.5m away from the earth pit and extra cost of additional length of water pipes and fixing junction, Elbows etc. shall be deemed to be included in the unit rate. (iii) RCC pit cover shall be percast of RCC 1:2:4, type B-1, 80 mm thick reinforced with XPM weighing not less than 4kg/Sqm in liue of cast iron cover. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 16, 2026
11:30 IST
Tender Published
Tender notice published.
TodayDec 08, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 22 daysDec 10, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 24 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender